Trane Rooftop Package Unit Service Manaual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

Packaged Cooling with

Electric Heat Rooftop Units

Precedent™
TSC060-120
50 Hz

February 2004 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Introduction

Precedent™ . . . The same Trane quality... With its sleek compact cabinet, rounded
with added flexibility. Precedent is a corners and beveled top, it may just be
flexible line of packaged units that covers the most aesthetically pleasing packaged
a wide variety of applications. unit on the planet. And, of course,
ReliaTel™ microprocessor controls Precedent carries the Trane reputation
provide superior flexibility for the for excellence, quality and reliability. It’s
simplest to the most sophisticated hard to stop a Trane.
applications. In addition to controls, From simple applications, to the most
Precedent offers many other outstanding complex, Precedent has the solution.
features and option choices.

© 2004 American Standard Inc. All rights reserved RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Contents

Introduction 2
Features and Benefits 4
Application Considerations 9
Selection Procedure 10
Model Number Description 12
General Data 13
Performance Data 14
Zone Controls 33
Electrical Data 34
Jobsite Connections 35
Dimensional Data 36
Weights 44
Mechanical Specifications 45

RT-PRC016-EN 3
Downloaded from www.Manualslib.com manuals search engine
Features and
Benefits

Easy Access Panels


Remove two screws for access to the
standardized internal components and
wiring.
Easy-Adjust Idler Arm
With the Easy-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money. Patented Condenser Coil
Precedent boasts a patented 1+1+1
Hybrid coil, permanently gapped for
easy of cleaning.
Unit Cabinet
The compact cabinet with rounded
corners takes up less room and is less
costly to ship. The beveled and ribbed
top is not only aesthetically pleasing, it is
designed to prevent water from pooling.
Single Point Power
A single electrical connection powers the
Colored And Numbered Wiring
unit.
You save time and money tracing wires
and diagnosing the unit.

Convertible Units
• The units ship in a downflow Sloped Drain Pans
configuration. They can be easily Every Precedent unit has a non-
converted to horizontal by simply corrosive, removable, double-sloped
moving two panels. drain pan that’s easy to clean and
reversible to allow installation of drain
• Units come complete with horizontal trap on either side of the unit.
Compressors duct flanges so the contractor doesn’t
Precedent™ contains the best have to field fabricate them. These Through the Base Condensate
compressor technology available to duct flanges are a time and cost saver. Every unit includes provisions for
achieve the highest possible through the base condensate drain
performance. Our compressor line connections. This allows the drain to be
includes Trane built reciprocating and connected through the roof curb instead
scrolls. of a roof penetration.

Easy Access Panels Foil-Faced Insulation


Easy access panels reduce the number of All panels in the Evaporator section of
possible water entry points. the unit have cleanable foil-faced
insulation. All edges are either captured
Low Ambient Cooling or sealed to ensure no fibers get into the
All Precedent units have cooling airstream.
capabilities down to 0°F as standard.

Unit Base
For added water integrity, Precedent has
a raised 29 mm (1 1/8") lip around the
unit’s downflow supply and return to
prevent water from blowing into the
ductwork.

4 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Features and
Benefits

Standardized Components Flexible Applications


• Only two roof curbs for the 5-10 ton
• Components are placed in the same Precedent line. . .simplifies curb
location on all Precedent™ units.
selection.
Familiarize yourself with one Precedent
and you are familiar with every • ReliaTel microprocessor controls to
Precedent. meet either the simple or the more
complex application.
• Airflow is outstanding. The Precedent
can replace an older machine with old
ductwork and, in many cases, improve
comfort through better air distribution.
• Belt drive — standard or oversized
supply fan motors meet a wide airflow
range.
• Precedent offers ultimate flexibility.
Options and components are not pre-
packaged at the factory. Units are built
to order in our standard “shortest in
the industry” ship cycle time.
Easy Access Low Voltage Terminal
Board
Precedent’s Low Voltage Terminal Board
is external to the electrical control
cabinet. It is extremely easy to locate and
attach the thermostat wire. This is
another cost and time saving installation
feature.

Low Voltage Connections


The wiring of the low voltage
connections to the unit and the zone
sensors is as simple as 1-1, 2-2, and 3-3.
This simplified system makes it easy for
the installer to wire
Single-Side Service
Single-side service is standard on all
Precedent units.

RT-PRC016-EN 5
Downloaded from www.Manualslib.com manuals search engine
Features and
Benefits

• Eliminates the need for field-installed


components with its built-in anti-
short-cycle timer, time delay relay
and minimum ‘’on’’ time controls.
These controls are factory tested to
assure proper operation.
• Requires no special tools to run the
Precedent unit through its paces
during testing. Simply place a
jumper between Test 1 and Test 2
terminals on the Low Voltage
Terminal Board and the unit will walk
through its operational steps. The
unit automatically returns control to
the zone sensor after stepping
through the test mode a single time,
Micro Controls even if the jumper is left on the unit.
Several years ago, Trane was the first to • As long as the unit has power and
introduce microprocessor controls into the LED is lit, the Micro is
the Light Commercial Market. That operational. The light indicates that
design, along with immeasurable the Micro is functioning properly.
experience, has provided the
technology for Trane’s second- • Features expanded diagnostic
generation ReliaTel™ microprocessor capabilities when used with Trane’s
controls. Integrated Comfort ™ Systems.
ReliaTel™ Micro: • As an energy benefit, softens
electrical ‘’spikes’’ by staging on fans,
• Provides unit control for heating, compressors and heaters.
cooling, and ventilating by utilizing
input from sensors that measure • The Intelligent Fallback or Adaptive
outdoor and indoor temperature. Control is a benefit to the building
occupant. If a component goes
• Improves quality and reliability astray, the unit will continue to
through the use of time-tested operate at predetermined
microprocessor controls and logic. temperature set points.
• Prevents the unit from short cycling, • Intelligent Anticipation is a standard
considerably improving compressor feature of the Micro. Functioning
life. constantly, the Micro and zone
sensors work together in harmony,
• Ensures that the compressor will run
to provide tight comfort control.
for a specific amount of time, which
allows oil to return for better
lubrication, enhancing the reliability of
the compressor.
• Reduces the number of components
required to operate the unit, thereby
reducing possibilities for component
failure.

6 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Features and
Benefits

Factory-installed Options The following options round-out the


Hinged Access Doors complete line of Precedent™ options:
These doors permit easy access to the — 0 - 50% Manual or Motorized
filter, fan/heat, and compressor/control Outside Air
sections. They reduce the potential roof
damage from screws or sharp access — Hail Protection Quality Coil Guards
door corners. — Electric Heaters (available as field
Economizer installed accessories)
Equipped with either dry bulb, reference — Discharge Air Sensor
or comparative enthalpy sensing, this — Wide array of Zone Sensors and
feature provides free cooling as the Thermostats
outdoor temperature and/or humidity
decreases. Economizers, correctly — Factory built Roof Curb
installed, offer a valuable energy One of Our Finest Assets:
savings. Factory-installed economizers Trane Sales Representatives are a
save time and ensure proper installation. Support group that can assist you with:
Phase Monitor — Product
Phase monitor shall provide 100% — Application
protection for motors and compressors — Service
against problems caused by phase loss, — Training
phase imbalance, and phase reversal. — Special Applications
Phase monitor is equipped with an LED — Specifications
that provides an ON or FAULT indicator. — Computer Programs and much more
Clogged Filter/Fan Fail Switches Precedent has the features and benefits
These sensors allow a zone sensor that make it first class in the light
service light or Integrated Comfort commercial rooftop market. Designed
System to indicate a dirty filter or a fan with input from field contractors and
that’s not working. The field installation engineers, its airflow performance is
charges for these valuable feedback outstanding.
devices often eliminate them from Precedent…The same Trane
consideration. Factory installation can quality…with added flexibility.
make such features a good investment.
Comm-3/4 Trane Communication
Interface
Available factory or field-installed. This
module when applied with ReliaTel™
easily interfaces with Trane’s Integrated
Comfort™ System.

RT-PRC016-EN 7
Downloaded from www.Manualslib.com manuals search engine
Features and
Benefits

Quality And Reliability Testing • We perform a 100% coil leak test at the
• All Precedent™ designs were rigorously factory. The evaporator and condenser
rain tested at the factory to ensure coils are leak tested at 1375 kPa (200
water integrity. psig) and pressure tested to 3100 kPa
(450 psig).
• Actual shipping tests were performed
to determine packaging requirements. • All parts are inspected at the point of
Units were test shipped around the final assembly. Sub-standard parts are
country to determine the best identified and rejected immediately.
packaging. • Every unit receives a 100% unit run test
• Factory shake and drop tests were before leaving the production line to
used as part of the package design make sure it lives up to rigorous Trane
process to help assure that the unit requirements.
arrives at the job site in top condition. We test designs at our factory not on
• Rigging tests include lifting a unit into our customers!
the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.

VariTrac™

VariTrac
When Trane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.

8 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Application
Considerations

Application of this product should be Condensate Trap


within the cataloged airflow and cooling The evaporator is a draw-thru
considerations. configuration. A trap must be field
Low Ambient Cooling provided prior to start-up on the cooling
The Precedent™ line features, with cycle.
ReliaTel™ microprocessor controls, low Clearance Requirements
ambient cooling down to 18°C (0°F). The recommended clearances identified
Contact your local Trane Representative with unit dimensions should be
for more assistance with low ambient maintained to assure adequate service
cooling applications. maximum capacity and peak operating
Barometric Relief efficiency. Actual clearances which
This product line offers an optional appear inadequate should be reviewed
barometric relief damper. for use in with the local Trane sales personnel.
conjunction with economizer option. Unit Pitch
This accessory consists of gravity These units have reversible sloped
dampers which open with increased condensate drain pans. Units must be
pressure. As the building air pressure installed level, any unit slope must be
increases, the pressure in the unit return toward the side of unit where
air section also increases, opening the condensate drain is connected.
dampers and relieving the conditioned
space.
NOTE: THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER
DURING ECONOMIZING OPERATION
IS SYSTEM RELATED.
PRESSURE DROP OF THE RETURN AIR
SYSTEM SHOULD BE CONSIDERED TO
CONTROL BUILDING PRESSURIZA-
TION.

RT-PRC016-EN 9
Downloaded from www.Manualslib.com manuals search engine
Selection
Procedure - SI Units

Cooling Capacity Step 3 Heating Capacity


Step 1 In order to select the correct unit which Step 1
Calculate the building’s total and sensible meets the building’s requirements, the Calculate the building heating load using
cooling loads at design conditions. Use fan motor heat must be deducted from the Trane calculation form or other
the Trane calculation methods or any the gross cooling capacity. The amount standard accepted method.
other standard accepted method. of heat that the fan motor generates is
dependent on the effort by the motor - Step 2
Factors used in unit selection: cfm and static pressure. To determine Size the system heating capacity to
A the total unit static pressure: match the calculated building heating
Total Cooling Load: 16.7 kW load. The following are building heating
External Static (duct system) requirements:
B 110 Pa
Sensible Cooling Load: 11.7 kW A
Standard Filter 1 in. 37 Pa Total heating load of 5 kW
C from Table PD-21
Airflow: 3400 m3/h B
Economizer 5 Pa 2000 cfm
D (100% Return Air) from
Electrical Characteristics: 380-415/50/3 C
Table PD-21 380 volt/3 phase Power Supply
E Electric Heater Size 7.5 kW 17 Pa
Summer Design Conditions: Entering The electric heat accessory capacities are
from Table PD-21 listed in Table PD-23. From the table, the
Evaporator Coil: 27 DB, 19 WB Outdoor
Ambient: 35 Total Static Pressure 169 Pa smallest heater will deliver 7.5 kW at
Note: The Evaporator Fan Performance 380 V. Referring to Table ED-2, the
F electric heater selection is
External Static Pressure: 110 Pa Table PD-6 has deducted the pressure
drop for a 25 mm filter already in the BAYHTRR412A.
unit (see note below Table PD-6). Air Delivery Selection
Step 2 Therefore, the actual total static pressure External static pressure drop through the
Table PD-1 shows that a TSC060AD has a is 169-17 (from Table PD-21) = 152 Pa. air distribution system has been
gross cooling capacity of 17.8 kW and calculated to be 110 Pa. From Table PD-
14.4 kW sensible capacity at 3400 m3/h With 3400 m3/h and 152 Pa
Table PD-6 shows .67 kW for this unit. 21 static pressure drop through the
and 35 DB outdoor ambient with 27 DB, economizer is 5 Pa and the 7.5 kW heater
19 WB air entering the evaporator. Note below the table gives a formula to
calculate Fan Motor Heat, is 17 Pa (110 + 5 + 17). Enter Table PD-6
To Find Capacity at Intermediate Fan Motor Heat (kw) = for a TSC060AD at 3400 m3/h and 132 Pa
Conditions Not in the Table 1.144 x (Fan kW) + 0.132 static pressure. The standard motor will
When the design conditions are between = 1.144 x 0.67 + 0.132 = 0.90 kW give the desired airflow at a rated kW of
two numbers that are in the capacity 0.64.
table, interpolation is required to Now subtract the fan motor heat from
the gross cooling capacity of the unit: Accessory Selection
approximate the capacity. Note: Select accessories needed to
Extrapolation outside of the table Net Total Cooling Capacity
= 17.8 kW - 0.9 = 16.9 kW. accommodate the application.
conditions is not recommended.
Net Sensible Cooling Capacity
= 14.4 kW - 0.9 = 13.5 kW.
Step 4
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.

10 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Selection
Procedure - IP Units

Cooling Capacity Step 3 Heating Capacity


In order to select the correct unit which Step 1
Step 1
meets the building’s requirements, the Calculate the building heating load using
Calculate the building’s total and sensible
fan motor heat must be deducted from the Trane calculation form or other
cooling loads at design conditions. Use
the gross cooling capacity. The amount standard accepted method.
the Trane calculation methods or any
of heat that the fan motor generates is
other standard accepted method. Step 2
dependent on the effort by the motor -
Factors used in unit selection: cfm and static pressure. To determine Size the system heating capacity to
the total unit static pressure: match the calculated building heating
A
load. The following are building heating
Total Cooling Load: 59 MBh External Static (duct system) requirements:
B 0.45 wg
A
Sensible Cooling Load: 40 MBh Standard Filter 1 in. 0.15 wg Total heating load of 15 MBH
C from Table PD-21a
B
Airflow: 2000 cfm Economizer 0.02 wg 2000 cfm
D (100% Return Air) from C
Electrical Characteristics: 380-415/50/3 Table PD-21a 380 volt/3 phase Power Supply
E Electric Heater Size 26 MBh 0.07 wg The electric heat accessory capacities are
Summer Design Conditions: Entering from Table PD-21a listed in Table PD-23a. From the table,
Evaporator Coil: 80 DB, 67 WB Outdoor
Total Static Pressure 0.69 wg the smallest heater will deliver 26 MBh at
Ambient: 95
Note: The Evaporator Fan Performance 380 volts. Referring to Table ED-2, the
F electric heater accessory selection is
Table PD-6a has deducted the pressure
External Static Pressure: 0.45 in. wg BAYHTRR412A.
drop for a 1 in. filter already in the unit
Step 2 (see note below Table PD-6a). Therefore, Air Delivery Selection
Table PD-1a shows that a TSC060AD has the actual total static pressure is 0.69 - External static pressure drop through the
a gross cooling capacity of 62.0 MBh and 0.15 (from Table PD-21a) = 0.50 wg. air distribution system has been
46.4 MBh sensible capacity at 2000 cfm calculated to be 0.45 inches of water.
With 2000 cfm and 0.50 wg.
and 95 DB outdoor ambient with 80 DB, From Table PD-21a static pressure drop
Table PD-6a shows .83 bhp for this unit.
67 WB air entering the evaporator. through the economizer is 0.02 and the
Note below the table gives a formula to
To Find Capacity at Intermediate calculate Fan Motor Heat, 26 kW heater is 0.07 inches of water (0.45
Conditions Not in the Table Fan Motor Heat (MBh) = + 0.02 + 0.07). Enter Table PD-6a for a
When the design conditions are between 2.915 x (Fan BHP) + 0.451 TSC060AD at 2000 cfm and 0.54 static
two numbers that are in the capacity = 2.915 x 0.83 + 0.451 = 2.87 MBh pressure. The standard motor will give
table, interpolation is required to the desired airflow at a rated bhp of
Now subtract the fan motor heat from about 1.01.
approximate the capacity. Note:
the gross cooling capacity of the unit:
Extrapolation outside of the table Accessory Selection
Net Total Cooling Capacity
conditions is not recommended. Select accessories needed to
= 62 MBh - 2.87 = 59.1 MBh.
accommodate the application.
Net Sensible Cooling Capacity
= 46.4 MBh - 2.87 = 43.5 MBh.
Step 5
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.

RT-PRC016-EN 11
Downloaded from www.Manualslib.com manuals search engine
Model
Number
Description

T S C 060 A D R O A ** C 0 0 0 0 0 0 0 0 0 0 1
1 2 3 4,5,6 7 8 9 10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25

Digit 1 - Unit Function Digits 12, 13 - Service Sequence Digit 18 - Through the Base Provisions
T = DX Cooling ** = Factory Assigned 0 = No Through the Base Provisions

Digit 2 - Efficiency Digit 14 - Fresh Air Selection Digit 19 - Disconnect/Circuit Breaker/Phase


S = Standard Efficiency 0 = No Fresh Air Monitor (3 phase only)
A = Manual Outside Air Damper 0-50% 0 = No Disconnect or Circuit Breaker
Digit 3 - Airflow B = Motorized Outside Air Damper 0-50% 3 = Phase Monitor Only (No Disconnect,
C = Economizer, Dry Bulb 0-100% No Circuit Breaker)
C = Convertible
without Barometric Relief
D = Economizer, Dry Bulb 0-100% Digit 20 - Convenience Outlet
Digits 4,5,6 - Nominal Gross Cooling with Barometric Relief
Capacity (MBh) E = Economizer, Reference Enthalpy 0 = No Convenience Outlet
kW Tons 0-100% without Barometric Relief
060 = 17.6 5 F = Economizer, Reference Enthalpy Digit 21 - Communications Options
072 = 21.1 6 0-100% with Barometric Relief 0 = No Communications Interface
090 = 26.4 7.5 G = Economizer, Comparative Enthalpy 1 = Comm-3/4 Communications Interface
102 = 29.9 8.5 0-100% without Barometric Relief 2 = Comm-5 Communications Interface
120 = 35.1 10 H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
Digit 22 - Refrigeration System Option
Digit 7 - Major Design Sequence 0 = Standard Refrigeration System
Digit 15 - Supply Fan/Drive Type/Motor
A = First
0 = Standard Drive
1 = Oversized Motor Digit 23 - Refrigeration Controls
Digit 8 - Unit Voltage 0 = No Refrigeration Control
D = 380-415/50/3 Digit 16 - Hinged Service Access/Filters
0 = Standard Panels/Standard Filters Digit 24 - Smoke Detector
Digit 9 - Unit Controls A = Hinged Access Panels/Standard Filters 0 = No Smoke Detector
R = ReliaTel™ Microprocessor B = Standard Panels/
50 mm (2”) Pleated Filters Digit 25 - Monitoring Controls
Digit 10 - Heating Capacity C = Hinged Access Panels/ 0 = No Monitoring Control
0 = No Electric Heat 50 mm (2”) Pleated Filters 1 = Clogged Filter Switch
2 = Fan Failure Switch
Digit 11 - Minor Design Sequence Digit 17 - Condenser Coil Protection 3 = Discharge Air Sensing Tube
0 = Standard Coil 4 = Clogged Filter Switch and Fan Fail
A = First Sequence Switch
1 = Standard Coil with Hail Guard
2 = Epoxy Coated Condenser Coil 5 = Clogged Filter Switch and Discharge
3 = Epoxy Coated Condenser Coil with Air Sensing Tube
Hail Guard 6 = Fan Fail Switch and Discharge Air
Sensing Tube
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube

12 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


General
Data

Table GD - 1 — General Data


Convertible Units Convertible Units Convertible Units Convertible Units Convertible Units
TSC060AD TSC072AD TSC090AD TSC102AD TSC120AD
Cooling Performance 1
Gross Capacity - kW (MBh) 18.2 (62.0) 23.2 (79.0) 26.7 (91.0) 31.1 (106.0) 34.9 (119.0)
COP (EER)2 2.99 (10.2) 3.08 (10.5) 3.02 (10.3) 3.02 (10.3) 2.99 (10.2)
Nominal Airflow - m3/h (cfm) 3400 (2000) 4080 (2400) 5100 (3000) 5780 (3400) 6800 (4000)
Rated Airflow - m3/h (cfm) 3400 (2000) 3570 (2100) 4460 (2625) 5100 (3000) 5950 (3500)
Net Capacity - kW (MBh) 17.3 (59.0) 22.0 (75.0) 25.2 (86.0) 29.9 (102.0) 33.1 (113.0)
System Power - kW 5.78 7.14 8.35 9.90 11.08
Compressor
Number -Type 1-Climatuff Scroll 1-Trane 3-D Scroll 1-Trane 3-D Scroll 2-Climatuff Scroll 2-Climatuff Scroll
Outdoor Sound Rating - dB 3 80 85 85 83 79
Outdoor Coil - Type Lanced Lanced Lanced Lanced Lanced
Tube Size - in. OD 0.3125 0.3125 0.3125 0.3125 0.3125
Face Area - m2 (sq ft) 1.02 (10.96) 1.29 (13.88) 1.29 (13.88) 1.75 (18.89) 2.41 (25.92)
Rows / FPI 3 / 17 2 / 17 2 / 17 2 / 17 2 / 17
Indoor Coil - Type Lanced Lanced Lanced Lanced Lanced
Tube Size OD - in. 0.3125 0.3125 0.3125 0.3125 0.3125
Face Area - m2 (sq ft) 0.62 (6.68) 0.92 (9.89) 0.92 (9.89) 1.15 (12.36) 1.15 (12.36)
Rows / FPI 3 / 16 2 / 16 3 / 16 3 / 16 4 / 16
Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice Short Orifice
Drain Connection No. / Size - in. 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT
Outdoor Fan - Type Propeller Propeller Propeller Propeller Propeller
No. Used / Diameter - in. 1 / 22 1 / 26 1 / 26 1 / 26 1 / 26
DriveType / No. Speeds Direct / 1 Direct / 1 Direct / 1 Direct / 1 Direct / 1
CFM 2900 5100 5200 5500 5800
No. Motors / kW (HP) 1 / 0.30 (0.40) 1 / .56 (0.75) 1 / .56 (0.75) 1 / .56 (0.75) 1 / .56 (0.75)
Motor RPM 950 950 950 950 950
Belt Drive Indoor Fan -Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1 1 1
Fan Diameter x Width - mm (in.) 280 X 280 (11 x 11) 305 X 305 (12 x 12) 305 X 305 (12 x 12) 381 X 381 (15 x 15) 381 X 381 (15 x 15)
DrvieType / No. Speeds Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed
No. Motors 1 1 1 1 1
Standard Motor Power - kW (HP) 1.1 (1.5) 1.1 (1.5) 1.5 (2.0) 1.5 (2.0) 2.2 (3.0)
Oversized Motor Power - kW (HP) - 1.5 (2.0) 2.2 (3.0) 2.2 (3.0) -
Motor RPM - Standard / Oversized 1450 / - 1450 / 1450 1450 / 2850 1450 / 2850 2850 / -
Motor Frame Size 56 56 56 56 56
Filters - Type Furnished Throwaway Throwaway Throwaway Throwaway Throwaway
(No.) Size Reccommended - mm (2) 508 X 762 X 25 (4) 406 X 635 X 50 (4) 406 X 635 X 50 (4) 508 X 635 X 50 (4) 508 X 635 X 50
(No.) Size Reccommended - in. (2) 20 X 30 X 1 (4) 16 X 25 X 2 (4) 16 X 25 X 2 (4) 20 X 25 X 2 (4) 20 X 25 X 2
Refrigerant Charge - kg (lbs) of R-22 4 3.7 (8.2) 3.7 (8.2) 4.5 (10.0) Circuit 1 - 3.8 (8.3) Circuit 1 - 3.4 (7.5)
Circuit 2 - 2.0 (4.4) Circuit 2 - 3.3 (7.3)
Notes:
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor
heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to ± 20 % of nominal airflow.
2. EER are rated at ARI conditions.
3. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table "Sound Power Level".
4. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature.

RT-PRC016-EN 13
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-1 — Gross Cooling Capacities (kW) - TSC060AD - (SI)


Ambient Temperature (C)
Enter. 30 35 40 45
Dry
Bulb Entering Wet Bulb Temperature (C)
m3/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 16.2 13.9 18.5 11.3 19.9 8.3 15.0 13.3 17.4 11.3 19.3 8.0 13.9 12.7 16.1 10.7 18.4 7.5 12.7 12.1 14.7 9.5 17.3 7.0
27 16.7 16.7 18.6 14.1 20.0 11.1 15.8 15.8 17.4 13.6 19.4 10.8 14.8 14.8 16.1 13.0 18.5 10.3 13.8 13.8 14.7 12.3 17.3 9.8
3060 30 18.1 18.1 18.7 16.9 20.2 13.6 17.2 17.2 17.7 16.5 19.5 13.5 16.2 16.2 16.5 15.9 18.5 13.1 15.1 15.1 15.1 15.1 17.3 12.6
33 19.3 19.3 19.2 19.2 20.3 16.2 18.5 18.5 18.5 18.5 19.6 16.1 17.6 17.6 17.6 17.6 18.7 15.9 16.6 16.6 16.6 16.6 17.5 15.4
24 16.7 14.8 18.8 11.8 20.1 8.6 15.5 14.2 17.8 11.3 19.5 8.3 14.2 13.5 16.5 11.4 18.7 7.7 13.1 12.9 15.0 10.8 17.6 7.2
27 17.5 17.5 18.9 14.9 20.2 11.4 16.5 16.5 17.8 14.4 19.6 11.2 15.4 15.4 16.5 13.8 18.8 10.8 14.4 14.4 15.1 13.1 17.6 10.3
3400 30 18.8 18.8 19.1 17.9 20.4 14.1 17.9 17.9 18.2 17.6 19.7 14.1 16.9 16.9 17.0 17.0 18.8 13.8 15.8 15.8 15.8 15.8 17.7 13.4
33 19.8 19.8 19.8 19.8 20.6 16.8 19.2 19.2 19.2 19.2 19.9 16.9 18.3 18.3 18.3 18.3 19.0 16.8 17.4 17.4 17.4 17.4 17.9 16.4
24 17.1 15.6 19.1 12.3 20.2 8.8 15.9 15.0 18.1 11.8 19.7 8.5 14.6 14.3 16.8 11.2 18.9 7.9 13.4 13.4 15.3 11.4 17.8 7.5
27 18.1 18.1 19.2 15.5 20.4 11.6 17.1 17.1 18.2 15.1 19.8 11.5 16.0 16.0 16.9 14.6 19.0 11.3 14.9 14.9 15.4 13.9 17.9 10.8
3740 30 19.3 19.3 19.5 18.7 20.6 14.5 18.5 18.5 18.6 18.6 20.0 14.6 17.6 17.6 17.6 17.6 19.1 14.4 16.5 16.5 16.5 16.5 17.9 14.1
33 20.2 20.2 20.2 20.2 20.8 17.4 19.6 19.6 19.6 19.6 20.2 17.6 18.9 18.9 18.9 18.9 19.3 17.6 18.0 18.0 18.0 18.0 18.3 17.4
24 17.4 16.4 19.3 12.6 20.3 9.1 16.2 15.8 18.4 12.2 19.8 8.8 14.9 14.9 17.1 11.7 19.0 8.1 13.9 13.9 15.5 12.1 18.0 7.7
27 18.6 18.6 19.4 16.1 20.5 12.3 17.7 17.7 18.4 15.8 19.9 11.8 16.6 16.6 17.2 15.3 19.1 11.6 15.4 15.4 15.8 14.6 18.1 11.2
4080 30 19.7 19.7 19.7 19.4 20.7 14.9 19.0 19.0 19.0 19.0 20.1 15.0 18.1 18.1 18.1 18.1 19.3 15.0 17.1 17.1 17.1 17.1 18.2 14.7
33 20.5 20.5 20.5 20.5 20.9 17.9 20.0 20.0 20.0 20.0 20.4 18.2 19.3 19.3 19.3 19.3 19.5 18.3 18.4 18.4 18.4 18.4 18.6 18.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-1a — Gross Cooling Capacities (MBH) _ TSC060AD _ (IP)


Ambient Temperature (F)
Enter. 85 95 105 115
Dry
Bulb Entering Wet Bulb Temperature (F)
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 56.1 47.1 64.4 37.0 68.8 25.1 51.6 44.7 60.6 36.7 66.9 23.9 47.0 42.4 55.6 34.5 64.0 22.6 42.4 40.1 50.2 30.3 60.0 20.8
80 57.3 56.5 64.6 45.8 69.3 34.2 53.3 53.3 60.7 43.9 67.3 32.9 49.5 49.5 55.7 41.6 64.2 31.4 45.7 45.7 50.4 39.2 60.1 29.6
1800 85 61.3 61.3 64.9 54.5 69.7 42.0 57.7 57.7 61.0 52.9 67.6 41.4 53.9 53.9 56.3 50.7 64.4 40.3 50.0 50.0 51.2 48.3 60.2 38.4
90 65.0 65.0 65.8 63.3 70.4 49.7 62.1 62.1 62.4 62.2 68.0 49.7 58.5 58.5 58.5 58.5 64.6 48.8 54.4 54.4 54.4 54.4 60.3 47.2
75 57.5 49.8 65.4 38.5 69.3 25.5 53.0 47.5 61.8 38.7 67.5 24.4 48.3 45.1 56.9 36.6 64.7 23.0 43.7 42.8 51.3 34.2 60.9 21.4
80 59.3 59.3 65.6 47.9 69.8 35.4 55.7 55.7 62.0 46.4 68.0 34.2 51.6 51.6 57.1 44.1 65.0 32.7 47.7 47.7 51.5 41.6 61.0 30.9
2000 85 63.6 63.6 66.0 57.3 70.5 43.1 60.3 60.3 62.5 56.2 68.3 43.0 56.4 56.4 58.0 54.1 65.2 42.1 52.2 52.2 52.8 51.7 61.2 40.6
90 66.9 66.9 67.2 66.5 71.1 51.4 64.4 64.4 64.4 64.4 68.9 51.8 61.0 61.0 61.0 61.0 65.6 51.3 57.1 57.1 57.1 57.1 61.5 50.1
75 58.8 52.5 66.1 39.8 69.6 25.9 54.3 50.2 62.8 38.1 67.9 24.9 49.4 47.8 58.0 38.6 65.3 23.4 44.8 44.8 52.2 36.2 61.6 21.7
80 61.5 61.5 66.4 49.8 70.3 36.8 57.8 57.8 63.0 48.6 68.3 35.0 53.6 53.6 58.2 46.5 65.6 33.9 49.4 49.4 52.6 44.0 61.8 32.2
2200 85 65.4 65.4 67.0 59.8 71.0 44.6 62.4 62.4 63.7 59.2 69.0 44.3 58.7 58.7 59.4 57.4 66.0 43.8 54.3 54.3 54.3 54.3 62.0 42.5
90 68.4 68.4 68.4 68.4 71.7 52.8 66.1 66.1 66.1 66.1 69.6 53.6 63.1 63.1 63.0 63.0 66.4 53.6 59.3 59.3 59.3 59.3 62.4 52.7
75 60.0 55.1 66.6 40.8 70.0 26.4 55.5 52.8 63.6 39.6 68.3 25.3 50.6 50.4 59.0 37.4 65.7 24.0 46.2 46.2 53.1 38.2 62.2 22.1
80 63.2 63.2 67.1 51.4 70.7 37.7 59.6 59.6 63.8 50.7 68.8 35.8 55.4 55.4 59.2 48.8 66.2 35.0 51.1 51.1 53.5 46.3 62.4 33.4
2400 85 66.7 66.7 67.8 62.0 71.5 45.3 64.1 64.1 64.8 61.9 69.5 45.5 60.5 60.5 60.8 60.6 66.6 45.2 56.3 56.3 56.2 56.2 62.7 44.3
90 69.5 69.5 69.5 69.5 72.1 54.1 67.4 67.4 67.4 67.4 70.2 55.3 64.6 64.6 64.5 64.5 67.1 55.7 61.1 61.1 61.0 61.0 63.2 55.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

14 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-2 — Gross Cooling Capacities (kW) - TSC072AD - (SI)


Ambient Temperature (C)
Enter. 30 35 40 45
Dry
Bulb Entering Wet Bulb Temperature (C)
m3/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 20.9 17.5 23.3 14.6 24.6 10.3 19.7 16.8 22.4 13.6 24.0 9.9 18.4 16.1 21.2 12.9 23.2 9.4 17.1 15.4 19.7 12.9 22.0 9.0
27 21.6 21.2 23.4 17.4 24.8 13.5 20.4 20.4 22.5 17.0 24.1 13.3 19.4 19.4 21.2 16.4 23.3 12.8 18.2 18.2 19.8 15.7 22.1 12.3
3670 30 22.9 22.9 23.6 20.6 25.0 16.5 22.1 22.1 22.7 20.4 24.3 16.3 21.0 21.0 21.5 19.9 23.5 16.1 19.9 19.9 20.2 19.2 22.2 15.6
33 24.0 24.0 24.1 23.8 25.2 19.4 23.4 23.4 23.3 23.3 24.5 19.3 22.5 22.5 22.4 22.4 23.6 19.3 21.4 21.4 21.4 21.4 22.3 18.8
24 21.5 18.5 23.6 15.2 24.8 10.6 20.3 17.9 22.8 14.2 24.2 10.1 19.0 17.2 21.6 13.6 23.4 9.8 17.6 16.4 20.1 12.9 22.3 9.3
27 22.3 22.3 23.8 18.1 25.1 14.5 21.3 21.3 22.9 17.9 24.3 13.6 20.2 20.2 21.6 17.3 23.6 13.4 19.0 19.0 20.2 16.6 22.4 12.8
4080 30 23.6 23.6 24.0 21.6 25.3 17.6 22.9 22.9 23.2 21.5 24.6 16.8 21.8 21.8 22.0 21.1 23.7 16.7 20.7 20.7 20.8 20.5 22.5 16.3
33 24.6 24.6 24.6 24.6 25.5 20.0 23.9 23.9 23.9 23.9 24.8 20.1 23.1 23.1 23.1 23.1 23.9 20.1 22.1 22.1 22.1 22.1 22.7 19.8
24 22.0 19.5 23.9 15.8 25.0 10.7 20.8 18.9 23.1 14.7 24.4 10.4 19.5 18.2 21.9 14.2 23.5 10.1 18.1 17.4 20.5 13.5 22.5 9.6
27 22.9 22.9 24.0 18.7 25.3 13.9 22.1 22.1 23.2 18.6 24.5 13.9 20.9 20.9 22.0 18.2 23.7 13.6 19.7 19.7 20.6 17.6 22.6 13.3
4490 30 24.1 24.1 24.3 22.4 25.5 17.4 23.4 23.4 23.5 22.4 24.8 17.3 22.5 22.5 22.5 22.2 23.9 17.2 21.3 21.3 21.3 21.3 22.8 17.0
33 25.0 25.0 25.0 25.0 25.7 20.7 24.4 24.4 24.4 24.4 25.1 20.8 23.7 23.7 23.7 23.7 24.2 20.8 22.6 22.6 22.6 22.6 23.1 20.7
24 22.4 20.3 24.1 16.3 25.2 10.9 21.2 19.8 23.2 15.1 24.5 10.7 19.9 19.1 22.2 14.7 23.6 10.3 18.5 18.4 20.8 14.0 22.7 9.9
27 23.4 23.4 24.3 19.3 25.5 14.5 22.6 22.6 23.4 19.2 24.7 14.7 21.5 21.5 22.3 19.0 23.8 14.0 20.3 20.3 20.9 18.4 22.8 13.7
4900 30 24.5 24.5 24.6 23.2 25.6 17.8 23.8 23.8 23.9 23.2 25.0 17.8 23.0 23.0 23.0 23.0 24.1 17.7 21.8 21.8 21.8 21.8 23.0 17.7
33 25.4 25.4 25.4 25.4 25.9 21.2 24.8 24.8 24.8 24.8 25.3 21.4 24.1 24.1 24.1 24.1 24.4 21.4 23.1 23.1 23.1 23.1 23.4 21.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-2a — Gross Cooling Capacities (MBH) - TSC072AD - (IP)


Ambient Temperature (F)
Enter. 85 95 105 115
Dry
Bulb Entering Wet Bulb Temperature (F)
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 72.2 59.1 80.6 47.1 85.1 31.0 67.5 56.5 77.7 44.1 82.7 29.6 62.6 53.9 73.0 41.8 79.9 28.0 57.4 51.2 67.5 39.2 75.5 26.0
80 73.8 70.7 81.0 56.1 85.8 42.2 69.4 68.2 77.9 55.0 83.4 40.7 65.0 65.0 73.1 52.6 80.4 39.0 60.6 60.6 67.6 50.0 75.8 36.8
2160 85 77.7 77.7 81.4 66.3 86.3 51.7 74.3 74.3 78.2 65.6 83.8 50.1 70.3 70.3 73.6 63.5 80.7 49.2 66.0 66.0 68.3 61.0 76.1 47.4
90 81.3 81.3 82.4 76.3 87.1 59.8 78.8 78.8 79.4 76.0 84.6 59.4 75.1 75.1 75.3 74.6 81.3 59.0 70.8 70.8 70.7 70.7 76.6 57.4
75 74.2 62.5 81.6 49.2 85.7 31.5 69.3 59.9 78.7 46.0 83.4 30.1 64.4 57.3 74.2 43.7 80.2 28.5 59.1 54.6 68.9 41.1 76.3 26.6
80 76.1 75.0 82.1 58.2 86.5 43.7 72.1 72.1 79.0 57.4 84.2 42.1 67.9 67.9 74.4 55.4 80.9 40.4 63.3 63.3 69.0 53.0 76.8 38.4
2400 85 80.0 80.0 82.6 69.1 86.8 52.8 77.1 77.1 79.5 68.7 84.7 51.6 73.1 73.1 75.3 67.3 81.4 50.7 68.7 68.7 70.1 65.0 77.2 49.4
90 83.3 83.3 83.8 79.7 87.1 61.5 80.7 80.7 80.9 79.4 85.5 61.5 77.5 77.5 77.5 77.5 82.1 61.1 73.3 73.3 73.3 73.3 77.8 60.2
75 75.8 65.6 82.3 50.7 86.2 32.0 71.0 63.2 79.4 49.8 84.0 30.7 66.0 60.6 75.4 45.6 80.7 29.0 60.6 57.8 70.0 42.9 77.0 27.2
80 78.1 78.1 82.9 60.1 87.2 44.1 74.6 74.6 79.8 59.4 84.7 44.3 70.3 70.3 75.6 58.1 81.2 41.3 65.7 65.7 70.1 55.7 77.6 39.8
2640 85 81.7 81.7 83.6 71.6 88.2 54.0 79.1 79.1 80.5 71.3 85.4 53.6 75.4 75.4 76.6 70.7 82.0 52.1 70.9 70.9 71.6 68.7 78.1 51.3
90 84.8 84.8 85.0 82.5 89.1 62.3 82.3 82.3 82.3 82.3 86.1 61.2 79.4 79.4 79.4 79.4 82.8 63.0 75.2 75.2 75.2 75.2 78.7 62.8
75 77.0 68.3 82.9 52.2 86.6 32.5 72.5 66.4 80.0 51.4 84.5 31.2 67.5 63.7 76.2 47.1 81.2 29.5 62.1 61.0 70.8 44.7 77.6 27.8
80 79.6 79.6 83.7 61.8 87.6 44.7 76.6 76.6 80.6 61.3 85.4 44.0 72.4 72.4 76.5 60.5 81.8 42.1 67.7 67.7 71.1 58.2 78.1 40.9
2880 85 83.0 83.0 84.4 73.9 88.7 54.9 80.4 80.4 81.5 73.9 86.2 54.1 77.1 77.1 77.8 73.8 82.7 53.5 72.7 72.7 72.9 71.9 78.8 53.0
90 85.9 85.9 86.0 85.0 89.6 65.2 83.6 83.6 83.6 83.6 87.0 63.2 81.0 81.0 81.0 81.0 83.5 65.0 76.8 76.8 76.8 76.8 79.5 65.3
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC016-EN 15
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-3 — Gross Cooling Capacities (kW) - TSC090AD - (SI)


Ambient Temperature (C)
Enter. 30 35 40 45
Dry
Bulb Entering Wet Bulb Temperature (C)
m3/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 24.5 21.6 26.9 17.1 28.1 12.0 22.7 20.6 25.8 16.3 27.7 11.5 20.8 19.6 24.1 15.4 26.8 11.0 19.0 18.7 22.0 14.8 25.6 10.3
27 25.4 25.4 27.1 21.1 28.5 15.9 24.1 24.1 25.9 20.8 27.8 15.9 22.5 22.5 24.3 20.0 27.0 15.5 20.9 20.9 22.2 19.0 25.7 14.8
4590 30 27.0 27.0 27.4 25.3 28.7 19.5 26.0 26.0 26.4 25.3 28.1 19.7 24.8 24.8 25.0 24.8 27.1 19.6 23.2 23.2 23.1 23.1 25.8 19.2
33 28.1 28.1 28.1 28.1 29.0 23.3 27.5 27.5 27.5 27.5 28.4 23.6 26.5 26.5 26.5 26.5 27.4 23.9 25.3 25.3 25.3 25.3 26.1 23.6
24 25.1 23.0 27.2 18.1 28.4 12.4 23.4 22.1 26.2 17.1 27.8 11.9 21.4 21.1 24.6 16.8 27.1 11.3 19.7 19.7 22.5 15.3 25.9 10.7
27 26.3 26.3 27.4 22.0 28.6 16.3 25.1 25.1 26.4 22.0 28.0 16.2 23.6 23.6 24.9 21.4 27.2 16.0 21.9 21.9 22.8 20.4 26.0 15.6
5100 30 27.6 27.6 27.8 26.4 29.0 20.2 26.8 26.8 27.0 26.8 28.3 20.4 25.7 25.7 25.7 25.7 27.4 20.6 24.3 24.3 24.3 24.3 26.2 20.4
33 28.6 28.6 28.6 28.6 29.3 24.1 28.1 28.1 28.1 28.1 28.7 24.6 27.3 27.3 27.3 27.3 27.8 25.0 26.2 26.2 26.2 26.2 26.6 25.1
24 25.6 24.2 27.4 18.4 28.4 12.5 24.0 23.5 26.5 18.3 28.0 12.2 22.0 22.0 25.1 17.1 27.3 11.7 20.4 20.4 22.9 16.2 26.2 11.1
27 26.9 26.9 27.7 22.8 28.8 16.5 25.9 25.9 26.8 23.0 28.3 16.7 24.5 24.5 25.4 22.7 27.4 16.5 22.8 22.8 23.5 21.8 26.3 16.3
5610 30 28.0 28.0 28.1 27.3 29.1 20.6 27.4 27.4 27.4 27.4 28.7 21.2 26.5 26.5 26.4 26.4 27.7 21.4 25.2 25.2 25.2 25.2 26.5 21.4
33 28.9 28.9 28.9 28.9 29.5 24.7 28.5 28.5 28.5 28.5 29.1 25.6 27.8 27.8 27.8 27.8 28.1 26.0 26.8 26.8 26.8 26.8 27.0 26.3
24 26.1 25.4 27.6 18.5 28.5 12.7 24.5 24.5 26.7 19.1 28.1 12.5 22.8 22.8 25.4 18.0 27.4 12.0 21.1 21.1 23.4 17.0 26.3 11.4
27 27.3 27.3 27.9 23.4 28.9 16.8 26.5 26.5 27.1 23.9 28.5 17.1 25.3 25.3 25.8 23.8 27.7 17.0 23.6 23.6 24.1 23.1 26.5 16.9
6120 30 28.3 28.3 28.4 28.1 29.2 21.0 27.8 27.8 27.8 27.8 28.8 21.8 27.0 27.0 27.0 27.0 27.9 22.1 25.8 25.8 25.8 25.8 26.8 22.3
33 29.1 29.1 29.1 29.1 29.6 25.2 28.8 28.8 28.8 28.8 29.3 26.4 28.2 28.2 28.2 28.2 28.4 26.9 27.3 27.3 27.3 27.3 27.4 27.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-3a — Gross Cooling Capacities (MBH) - TSC090AD - (IP)


Ambient Temperature (F)
Enter. 85 95 105 115
Dry
Bulb Entering Wet Bulb Temperature (F)
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 84.4 72.7 92.7 55.2 96.6 35.6 77.7 69.1 89.4 52.6 95.2 34.0 70.4 65.4 83.4 50.6 92.5 32.0 63.7 61.9 75.3 46.9 88.2 29.8
80 86.5 86.5 93.3 67.5 97.8 48.9 81.2 81.2 89.6 66.8 96.2 48.4 75.1 75.1 83.8 64.0 93.1 46.6 69.4 69.4 75.8 60.3 88.5 44.1
2700
85 91.5 91.5 94.2 80.6 98.9 59.9 87.7 87.7 90.6 80.8 97.2 60.5 82.5 82.5 85.1 78.8 93.5 59.5 76.4 76.4 77.7 75.2 88.8 58.1
90 95.1 95.1 95.7 93.2 100.0 71.0 92.6 92.6 92.5 92.5 97.5 71.8 88.7 88.7 88.7 88.7 94.3 72.6 83.7 83.7 83.6 83.6 89.5 71.8
75 86.5 77.3 93.5 56.9 97.1 36.1 80.0 73.9 90.6 56.4 95.8 34.6 72.6 70.1 85.2 52.3 93.2 32.7 65.6 65.6 76.9 49.9 89.1 30.5
80 89.4 89.4 94.3 70.0 98.3 52.8 84.9 84.9 91.0 70.2 96.9 49.4 78.8 78.8 85.6 68.2 93.9 48.9 72.7 72.7 77.8 64.5 89.6 46.3
3000
85 93.6 93.6 95.4 83.8 99.4 61.1 90.6 90.6 92.2 85.2 98.0 62.3 86.1 86.1 87.3 84.2 94.5 61.9 80.1 80.1 80.1 80.1 90.0 61.2
90 96.8 96.8 97.0 96.7 100.5 72.8 94.8 94.8 94.8 94.8 99.0 75.4 91.5 91.5 91.4 91.4 95.4 75.8 87.0 87.0 87.0 87.0 90.9 75.9
75 88.1 81.3 94.3 59.1 97.5 36.7 82.1 78.5 91.4 58.6 96.2 35.2 74.1 74.1 86.4 54.8 93.7 33.4 68.1 68.1 78.5 51.2 89.8 31.2
80 91.4 91.4 95.1 72.1 98.7 50.2 87.6 87.6 92.1 73.3 97.4 50.3 82.2 82.2 87.1 72.0 94.5 49.7 75.6 75.6 79.7 68.7 90.4 48.3
3300
85 95.1 95.1 96.2 86.6 99.8 62.1 92.7 92.7 93.6 89.0 98.5 63.8 88.8 88.8 89.2 89.1 95.2 64.0 83.5 83.5 83.5 83.5 90.9 63.9
90 97.9 97.9 97.9 97.9 101.0 74.3 96.4 96.4 96.3 96.3 99.7 77.5 93.5 93.5 93.5 93.5 96.3 78.6 89.4 89.4 89.4 89.4 92.1 79.5
75 89.5 85.0 95.1 60.6 97.8 37.2 84.0 83.1 92.2 60.7 96.6 35.7 76.7 76.7 87.5 57.3 94.1 34.0 70.4 70.4 80.0 53.8 90.4 31.9
80 92.9 92.9 95.6 74.0 99.0 50.8 89.7 89.7 93.0 76.0 97.8 51.0 84.8 84.8 88.3 75.6 95.2 50.9 78.1 78.1 81.6 72.8 90.9 49.5
3600
85 96.2 96.2 96.9 88.9 100.2 63.1 94.2 94.2 94.7 92.3 99.0 65.1 90.7 90.7 90.7 90.7 95.8 65.8 86.0 86.0 86.0 86.0 91.7 66.3
90 98.7 98.7 98.7 98.7 101.3 75.7 97.5 97.5 97.5 97.5 100.1 79.4 94.9 94.9 94.9 94.9 97.0 81.1 91.2 91.2 91.2 91.2 93.0 82.7
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

16 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-4 — Gross Cooling Capacities (kW) - TSC102AD - (SI)


Ambient Temperature (C)
Enter. 30 35 40 45
Dry
Bulb Entering Wet Bulb Temperature (C)
m3/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 28.0 24.3 31.5 19.5 33.4 14.1 26.0 23.3 30.0 18.7 32.5 13.5 23.9 22.2 27.8 17.7 31.3 12.9 21.6 21.6 25.4 17.3 29.7 12.2
27 29.0 28.4 31.6 24.3 33.6 18.7 27.4 27.1 30.1 23.6 32.7 18.5 25.6 25.6 28.0 22.7 31.4 17.8 23.9 23.9 25.6 21.6 29.8 17.1
5200 30 31.0 31.0 31.9 29.0 33.9 23.0 29.7 29.7 30.5 28.6 32.9 22.8 28.1 28.1 28.1 28.1 31.5 22.5 26.3 26.3 26.5 25.7 29.9 22.0
33 32.6 32.6 32.7 32.1 34.1 27.3 31.6 31.6 31.6 31.4 33.2 27.3 30.4 30.4 30.3 30.3 31.8 27.2 28.9 28.9 28.8 28.8 30.2 26.8
24 28.8 25.8 31.9 20.4 33.6 14.4 26.8 24.8 30.5 19.6 32.8 13.9 24.2 24.2 28.5 18.7 31.6 13.4 22.5 22.5 26.0 17.6 30.1 12.6
27 30.1 29.8 32.1 25.4 34.0 19.2 28.6 28.6 30.7 25.0 32.9 19.1 26.8 26.8 28.8 24.2 31.7 18.6 25.0 25.0 26.3 23.1 30.2 17.9
5780 30 32.0 32.0 32.5 30.5 34.2 23.7 30.9 30.9 30.9 30.9 33.2 23.7 29.4 29.4 29.4 29.4 31.9 23.6 27.6 27.6 27.7 27.2 30.3 23.2
33 33.4 33.4 33.4 33.2 34.5 28.1 32.6 32.6 32.5 32.5 33.6 28.5 31.4 31.4 31.4 31.4 32.3 28.5 30.0 30.0 30.0 30.0 30.8 28.3
24 29.5 27.3 32.2 21.1 33.8 14.7 27.6 26.3 31.0 20.5 33.0 14.4 25.1 25.1 29.1 19.6 31.8 13.8 23.5 22.9 26.5 18.5 30.4 12.9
27 31.0 31.0 32.5 26.5 34.2 19.7 29.7 29.7 31.2 26.3 33.3 19.5 27.9 27.9 29.4 25.6 32.0 19.2 26.0 26.0 27.0 24.5 30.5 18.7
6360 30 32.7 32.7 33.0 31.7 34.6 24.5 31.7 31.7 31.7 31.7 33.6 24.6 30.4 30.4 30.5 29.9 32.3 24.5 28.8 28.8 28.8 28.6 30.7 24.3
33 34.0 34.0 34.0 34.0 34.8 28.9 33.2 33.2 33.2 33.2 33.9 29.5 32.1 32.1 32.1 32.1 32.7 29.7 30.9 30.9 30.9 30.9 31.3 29.7
24 30.1 28.7 32.5 21.7 33.9 15.1 27.9 27.9 31.3 21.4 33.1 14.7 26.0 26.0 29.3 20.4 32.2 14.2 24.2 23.9 27.0 19.4 30.6 13.3
27 31.7 31.7 32.8 27.4 34.4 20.0 30.5 30.5 31.6 27.4 33.4 20.0 28.8 28.8 29.8 26.9 32.3 19.7 26.9 26.9 27.6 25.9 30.7 19.4
6940 30 33.2 33.2 33.2 33.2 34.8 25.0 32.3 32.3 32.4 31.7 33.7 25.2 31.2 31.2 31.2 30.9 32.6 25.4 29.7 29.7 29.7 29.7 31.0 25.3
33 34.4 34.4 34.4 34.4 35.2 30.0 33.7 33.7 33.7 33.7 34.2 30.4 32.9 32.9 32.9 32.9 33.1 30.8 31.5 31.5 31.5 31.5 31.4 31.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-4a — Gross Cooling Capacities (MBH) - TSC102AD - (IP)


Ambient Temperature (F)
Enter. 85 95 105 115
Dry
Bulb Entering Wet Bulb Temperature (F)
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 96.7 81.9 109.1 63.4 115.0 42.2 89.1 78.1 104.0 60.7 112.1 40.4 81.2 74.1 96.3 59.2 107.9 38.3 73.7 70.3 87.0 55.2 102.4 35.8
80 98.2 98.2 109.4 78.3 116.1 58.1 92.7 90.8 104.2 76.3 113.0 56.2 85.7 85.2 96.6 72.9 108.5 53.9 79.3 79.3 87.4 68.8 102.7 51.3
3060 85 105.0 105.0 110.2 93.1 117.3 70.8 100.0 100.0 105.0 91.8 113.6 70.4 93.6 93.6 98.0 88.8 108.9 68.7 86.8 86.8 89.2 84.7 103.1 66.7
90 110.4 110.4 111.6 107.4 118.0 84.0 106.5 106.5 106.4 106.4 114.4 83.5 101.4 101.4 101.7 99.6 109.6 83.1 94.8 94.8 94.9 94.6 103.5 81.6
75 99.3 87.0 110.2 65.9 115.6 42.9 91.8 83.2 105.8 63.7 112.9 41.1 83.6 79.1 98.7 60.6 108.8 39.0 75.2 75.2 89.0 58.6 103.4 36.5
80 102.5 100.4 110.9 81.6 116.9 59.2 96.7 95.9 106.0 80.4 113.8 58.8 89.7 89.7 99.0 77.4 109.6 56.1 82.9 82.9 89.7 73.3 103.9 53.5
3400 85 108.4 108.4 111.9 97.4 118.2 72.7 104.1 104.1 107.2 97.0 114.6 72.7 98.2 98.2 100.8 94.9 110.1 71.5 91.0 91.0 91.0 91.0 104.2 70.0
90 113.2 113.2 113.1 113.1 119.5 86.5 109.7 109.7 109.9 107.6 115.6 86.6 105.1 105.1 105.1 104.4 111.0 86.9 99.4 99.4 99.2 99.2 105.1 86.0
75 101.6 91.8 111.3 67.8 116.2 43.6 94.3 88.2 107.1 66.5 113.5 41.8 84.7 84.7 100.4 63.0 109.5 39.6 78.4 76.4 90.9 59.0 104.2 37.1
80 105.4 104.4 112.1 84.5 117.6 60.0 100.3 100.3 107.4 84.0 114.7 59.4 93.4 93.4 100.9 81.6 110.0 57.9 86.1 86.1 91.7 77.7 104.8 55.6
3740 85 111.0 111.0 113.3 101.2 118.9 74.2 107.0 107.0 108.9 101.7 116.0 74.8 101.8 101.8 101.8 101.8 111.2 73.8 94.9 94.9 94.9 94.9 105.3 72.9
90 115.2 115.2 115.2 115.2 120.3 88.6 112.1 112.1 112.1 111.1 116.5 89.3 107.8 107.8 107.7 107.7 112.1 90.2 102.6 102.6 102.6 102.6 106.4 90.0
75 103.5 96.3 112.1 69.5 116.6 43.8 94.9 94.9 107.9 68.7 114.0 42.5 87.5 87.5 101.8 65.6 110.0 40.3 80.7 79.5 92.4 61.7 104.8 37.8
80 107.9 107.9 113.0 87.1 118.1 60.8 103.1 103.1 108.6 87.3 115.3 60.3 96.8 96.8 102.5 85.6 110.7 59.5 89.1 89.1 93.7 82.0 105.4 57.5
4080 85 112.9 112.9 114.4 104.5 119.5 75.5 109.3 109.3 110.4 105.7 116.7 76.5 104.5 104.5 104.5 104.5 111.9 76.7 98.2 98.2 98.6 96.7 106.2 75.5
90 116.7 116.7 116.7 116.7 120.9 90.6 113.9 113.9 113.8 113.8 117.9 92.9 109.9 109.9 109.8 109.8 113.0 93.2 104.9 104.9 104.9 104.9 107.5 93.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RT-PRC016-EN 17
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-5 — Gross Cooling Capacities (kW) - TSC120AD - (SI)


Ambient Temperature (C)
Enter. 30 35 40 45
Dry
Bulb Entering Wet Bulb Temperature (C)
m3/h Temp 16 19 22 16 19 22 16 19 22 16 19 22
Airflow (C) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24 31.9 28.6 35.3 22.8 37.2 15.9 29.6 27.4 33.6 21.7 36.5 15.4 27.1 26.2 31.0 20.5 35.2 14.8 24.6 24.6 28.4 19.9 33.2 14.0
27 33.4 33.4 35.5 28.2 37.7 21.4 31.6 31.6 33.9 27.8 36.7 21.4 29.5 29.5 31.3 26.6 35.3 20.7 27.5 27.5 28.9 25.5 33.3 19.9
6120
30 35.5 35.5 36.0 33.8 38.1 26.5 34.2 34.2 34.5 33.8 37.0 26.7 32.3 32.3 32.2 32.2 35.5 26.6 30.4 30.4 30.4 30.4 33.4 25.9
33 37.1 37.1 37.1 37.1 38.5 31.6 36.2 36.2 36.2 36.2 37.3 31.9 34.8 34.8 34.8 34.8 35.9 32.3 33.2 33.2 33.2 33.2 34.0 31.8
24 32.7 30.4 35.7 23.8 37.5 16.3 30.5 29.3 34.2 22.8 36.8 15.9 27.8 27.8 31.9 21.8 35.5 15.3 25.7 25.7 29.0 21.2 33.7 14.5
27 34.5 34.5 36.0 29.5 38.0 21.9 32.9 32.9 34.5 29.4 37.0 22.0 30.9 30.9 32.3 28.5 35.7 21.7 28.7 28.7 29.7 27.4 33.8 21.0
6800
30 36.3 36.3 36.6 35.4 38.4 27.4 35.3 35.3 35.3 35.3 37.3 27.6 33.7 33.7 33.7 33.7 35.9 27.8 31.8 31.8 31.7 31.7 34.0 27.5
33 37.9 37.9 37.8 37.8 38.9 32.8 37.0 37.0 37.0 37.0 37.8 33.3 35.9 35.9 35.9 35.9 36.5 33.9 34.4 34.4 34.4 34.4 34.7 33.8
24 33.5 32.2 36.0 24.7 37.8 16.9 31.1 31.1 34.7 23.9 37.0 16.3 28.9 28.9 32.4 22.9 35.8 15.7 26.6 26.6 29.6 22.5 34.1 14.9
27 35.3 35.3 36.4 30.6 38.2 22.4 34.0 34.0 35.0 30.8 37.4 22.7 32.0 32.0 33.0 30.2 36.0 22.5 29.9 29.9 30.5 29.1 34.2 22.0
7480
30 37.0 37.0 37.0 37.0 38.7 28.1 36.1 36.1 36.1 36.1 37.9 28.9 34.7 34.7 34.7 34.7 36.4 29.1 32.9 32.9 32.9 32.9 34.5 29.0
33 38.4 38.4 38.3 38.3 39.2 33.7 37.7 37.7 37.7 37.7 38.4 34.9 36.7 36.7 36.7 36.7 37.0 35.4 35.3 35.3 35.3 35.3 35.3 35.3
24 33.9 33.9 36.3 24.9 37.9 17.3 32.0 32.0 35.0 25.6 37.5 16.1 29.8 29.8 32.8 23.9 36.1 16.2 27.5 27.5 29.8 23.6 34.4 15.3
27 35.9 35.9 36.7 31.7 38.5 22.8 34.8 34.8 35.5 32.2 37.7 23.2 32.9 32.9 33.6 31.9 36.3 23.2 30.6 30.6 30.6 30.6 34.5 23.0
8160
30 37.5 37.5 37.5 37.5 38.9 28.8 36.7 36.7 36.7 36.7 38.1 29.8 35.5 35.5 35.5 35.5 36.7 30.2 33.7 33.7 33.7 33.7 34.9 30.5
33 38.8 38.8 38.7 38.7 39.5 34.6 38.4 38.4 38.2 38.2 38.7 36.1 37.3 37.3 37.3 37.3 37.4 36.7 36.0 36.0 36.0 36.0 36.0 36.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-5a — Gross Cooling Capacities (MBH) - TSC120AD - (IP)


Ambient Temperature (F)
Enter. 85 95 105 115
Dry
Bulb Entering Wet Bulb Temperature (F)
CFM Temp 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
75 109.9 96.4 122.1 73.8 128.5 47.6 101.2 92.1 116.7 70.3 125.9 45.7 91.8 87.5 107.7 67.7 121.6 43.4 82.1 82.1 97.2 63.2 115.0 40.9
80 113.5 113.5 122.6 90.4 129.9 65.7 106.6 106.6 117.1 89.2 127.2 65.0 99.0 99.0 108.4 85.4 122.2 62.4 91.0 91.0 98.2 81.0 115.2 59.7
3600 85 120.2 120.2 123.8 108.0 131.3 80.9 115.2 115.2 118.5 107.9 127.8 81.5 108.1 108.1 110.5 104.9 122.6 80.6 100.3 100.3 100.3 100.3 115.4 78.4
90 125.4 125.4 125.4 125.4 132.7 96.3 121.8 121.8 121.8 121.8 128.7 97.3 116.4 116.4 116.4 116.4 123.6 98.2 109.2 109.2 109.2 109.2 116.4 97.0
75 112.7 102.4 123.1 75.6 129.3 48.4 104.2 98.3 118.5 73.6 126.9 46.6 93.7 93.7 109.9 70.9 122.7 44.3 85.6 85.6 99.3 67.2 116.5 41.9
80 117.3 117.3 124.1 94.1 130.8 66.9 111.1 111.1 119.0 94.0 128.2 66.8 103.5 103.5 110.8 90.8 123.5 65.3 95.2 95.2 100.8 86.6 116.8 62.5
4000 85 123.2 123.2 125.6 112.8 132.3 82.9 119.0 119.0 120.8 114.1 129.5 84.5 112.5 112.5 112.5 112.5 124.1 84.2 104.9 104.9 104.8 104.8 117.1 83.0
90 127.9 127.9 127.9 127.9 133.8 99.2 124.9 124.9 124.9 124.9 130.8 102.4 120.2 120.2 120.2 120.2 125.3 103.1 113.9 113.9 113.8 113.8 118.4 102.9
75 115.1 108.2 124.5 77.5 130.0 49.2 107.0 104.4 119.8 77.6 127.6 47.4 97.3 97.3 111.7 73.2 123.6 45.2 88.7 88.7 101.1 71.1 117.6 42.7
80 120.1 120.1 125.3 97.3 131.6 67.9 114.9 114.9 120.6 98.4 129.0 68.2 107.3 107.3 112.9 96.1 124.5 68.1 98.9 98.9 103.1 92.0 118.0 65.1
4400 85 125.5 125.5 127.0 116.9 133.1 84.7 121.9 121.9 122.8 119.6 130.5 87.0 116.4 116.4 116.3 116.3 125.3 88.0 108.7 108.7 108.7 108.7 118.4 87.0
90 130.0 130.0 129.7 129.7 134.7 101.8 127.3 127.3 127.2 127.2 131.9 105.9 123.0 123.0 123.0 123.0 126.7 107.5 117.2 117.2 117.2 117.2 120.2 108.4
75 117.1 113.2 125.5 81.7 130.6 50.0 108.8 108.8 120.8 80.6 128.3 48.2 100.5 100.5 113.2 76.3 124.3 46.1 91.6 91.6 102.7 72.1 118.5 43.6
80 122.3 122.3 126.5 100.7 132.2 68.9 117.8 117.8 122.0 102.4 129.8 69.5 110.5 110.5 114.9 101.3 125.7 69.3 102.2 102.2 105.2 97.3 119.0 67.7
4800 85 127.2 127.2 128.4 121.1 133.8 86.3 124.1 124.1 124.1 124.1 131.2 89.2 119.0 119.0 119.0 119.0 126.5 90.9 112.0 112.0 112.0 112.0 119.7 90.9
90 131.3 131.3 131.5 131.5 135.4 104.2 129.3 129.3 129.0 129.0 132.8 108.9 125.2 125.2 125.2 125.2 127.8 111.4 119.8 119.8 119.8 119.8 121.7 113.3
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling, subtract indoor fan heat.
2. TGC = Total Gross Capacity
3. SHC = Sensible Heat Capacity

18 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-6 — Belt Drive Evaporator Fan Performance - TSC060AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
3
m /h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive
2720 - - 703 0.27 757 0.31 806 0.35 854 0.39 899 0.43 944 0.49 985 0.54 1023 0.59 1060 0.64
3060 706 0.32 760 0.35 815 0.40 861 0.45 904 0.49 947 0.54 988 0.58 1028 0.64 1067 0.70 1104 0.76
3400 773 0.43 821 0.46 873 0.51 918 0.57 958 0.62 998 0.67 1036 0.71 1073 0.76 1111 0.82 1147 0.89
3740 840 0.56 885 0.60 930 0.65 977 0.71 1016 0.77 1053 0.82 1089 0.88 1124 0.93 1158 0.98 1191 1.03
4080 909 0.71 950 0.76 990 0.80 1034 0.87 1074 0.93 1110 1.00 1143 1.06 1177 1.12 1209 1.17 1241 1.23

External Static Pressure (Pascals)


275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Drive
2720 1093 0.69 1126 0.74 1160 0.79 1190 0.84 1222 0.90
3060
3400
1138 0.82
1182 0.96
1171 0.87
1215 1.02
1203 0.93
1246 1.09
1232 0.98
1276 1.15
1262
1306
1.04
1.21
← 1.12 Nom kW Standard Motor &
Hi Static Drive
3740 1226 1.10 1258 1.17 1290 1.25 - - - -
4080 1272 1.29 - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-6a — Belt Drive Evaporator Fan Performance -TSC060AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor & Drive
1600 - - 703 0.36 757 0.41 806 0.47 854 0.52 899 0.58 944 0.65 985 0.73 1023 0.79 1060 0.86
1800 706 0.42 760 0.47 815 0.54 861 0.60 904 0.66 947 0.72 988 0.78 1028 0.86 1067 0.94 1104 1.02
2000 773 0.57 821 0.62 873 0.69 918 0.76 958 0.83 998 0.90 1036 0.96 1073 1.02 1111 1.10 1147 1.19
2200 840 0.75 885 0.80 930 0.87 977 0.95 1016 1.03 1053 1.10 1089 1.17 1124 1.24 1158 1.31 1191 1.39
2400 909 0.96 950 1.02 990 1.08 1034 1.16 1074 1.25 1110 1.34 1143 1.419 1177 1.50 1209 1.57 1241 1.65

External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Drive
1600 1093 0.92 1126 0.99 1160 1.06 1190 1.13 1222 1.20
1800
2000
1138
1182
1.10
1.28
1171 1.17
1215 1.37
1203 1.25
1246 1.46
1232 1.32
1276 1.54
1262
1306
1.39
1.62
← 1-1/2 HP Standard Motor &
Hi Static Drive
2200 1226 1.48 1258 1.57 1290 1.67 - - - -
2400 1272 1.73 - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

RT-PRC016-EN 19
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-7 - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Std Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive
2720 707 0.26 774 0.31 837 0.37 898 0.43 953 0.48 1001 0.54 1045 0.59 1087 0.65 1129 0.71 1168 0.77
3060 778 0.36 840 0.41 897 0.48 953 0.54 1008 0.60 1058 0.67 1102 0.73 1143 0.79 1181 0.85 1219 0.92
3400 850 0.48 908 0.54 961 0.60 1012 0.67 1062 0.74 1111 0.81 1157 0.88 1198 0.95 1237 1.02 1274 1.09
3740 923 0.63 978 0.69 1028 0.76 1075 0.83 1120 0.91 1166 0.99 1211 1.06 1254 1.14 1294 1.22 1330 1.29
4080 997 0.80 1049 0.87 1096 0.94 1140 1.02 1183 1.10 1223 1.18 1266 1.27 - - - - - -


1.12 Nom kW Standard Motor & Hi Static Drive

External Static Pressure (Pascals)


275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Drive
2720
3060
1206 0.83
1256 0.99
1241 0.89
1291 1.05
1275 0.96
1326 1.12
1306 1.02
1359 1.19
1338
1390
1.09
1.26
← 1.12 Nom kW Standard Motor &
Hi Static Drive
3400 1309 1.16 1343 1.24 1376 1.31 - - - -
3740 - - - - - - - - - -
4080 - - - - - - - - - -
Notes: Factory Supplied Motors, In Commercial Equipment, Are
Data Includes Pressure Drop Due To Wet Coils And Filters. Definite Purpose Motors, Specifically Designed And
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-7a - Belt Drive Evaporator Fan Performance- TSC060AD - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor &
Low Static Drive 1-1/2 HP Standard Motor & Drive
1600 707 0.35 774 0.42 837 0.50 898 0.57 953 0.65 1001 0.72 1045 0.80 1087 0.87 1129 0.95 1168 1.03
1800 778 0.48 840 0.56 897 0.64 953 0.72 1008 0.81 1058 0.89 1102 0.98 1143 1.06 1181 1.15 1219 1.23
2000 850 0.65 908 0.73 961 0.81 1012 0.90 1062 1.00 1111 1.09 1157 1.19 1198 1.28 1237 1.37 1274 1.47
2200 923 0.84 978 0.93 1028 1.02 1075 1.12 1120 1.22 1166 1.32 1211 1.43 1254 1.53 1294 1.63 1330 1.74
2400 997 1.07 1049 1.17 1096 1.27 1140 1.37 1183 1.48 1223 1.59 1266 1.70 - - - - - -

1-1/2 HP Standard Motor & Hi Static Drive

External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1/2 HP Standard Motor & Drive 1-1/2 HP Standard Motor & Hi Static Drive
1600 1206 1.12 1241 1.20 1275 1.28 1306 1.37 1338 1.46
1800 1256 1.32 1291 1.41 1326 1.50 1359 1.60 1390 1.69
2000 1309 1.56 1343 1.66 1376 1.76 - - - -
2200 - - - - - - - - - -
2400 - - - - - - - - - -
Notes: Factory Supplied Motors, In Commercial Equipment, Are
Data Includes Pressure Drop Due To Wet Coils And Filters. Definite Purpose Motors, Specifically Designed And
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

20 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-8 — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive
3260 - - - - 573 0.25 630 0.30 680 0.36 726 0.41 769 0.47 811 0.52 851 0.58 889 0.65
3670 - - 548 0.26 602 0.31 656 0.37 706 0.43 751 0.49 792 0.55 832 0.61 871 0.67 908 0.74
4080 - - 584 0.33 635 0.38 682 0.45 732 0.51 777 0.58 818 0.64 856 0.71 893 0.77 930 0.84
4490 569 0.35 621 0.42 670 0.47 715 0.54 758 0.60 802 0.68 845 0.75 883 0.82 919 0.89 953 0.96
4890 612 0.45 660 0.51 706 0.58 749 0.64 789 0.71 830 0.79 870 0.87 909 0.95 945 1.02 979 1.10


1.12 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Std Motor 1.12 Nom kW Standard Motor
& Drive & Hi Static Drive
3260 925 0.71 960 0.77 994 0.83 1026 0.89 1057 0.95
3670 944 0.81 978 0.87 1010 0.94 1043 1.01 1073 1.08
4080 964 0.91 998 0.99 1030 1.06 1063 1.14 1092 1.21
4490 986 1.04 1019 1.11 1051 1.19 1082 1.27 1112 1.35
4890 1011 1.18 1043 1.26 1073 1.34 1103 1.42 1133 1.51
1.50 Nom kW Over-Sized Motor
& Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Definite Purpose Motors, Specifically Designed And
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-8a — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor & Drive
1920 - - - - 573 0.34 630 0.41 680 0.48 726 0.55 769 0.62 811 0.70 851 0.78 889 0.87
2160 - - 548 0.35 602 0.42 656 0.50 706 0.58 751 0.65 792 0.73 832 0.81 871 0.90 908 0.99
2400 - - 584 0.45 635 0.52 682 0.60 732 0.69 777 0.77 818 0.86 856 0.95 893 1.04 930 1.13
2640 569 0.47 621 0.56 670 0.64 715 0.72 758 0.81 802 0.91 845 1.01 883 1.10 919 1.20 953 1.29
2880 612 0.60 660 0.69 706 0.78 749 0.86 789 0.96 830 1.06 870 1.16 909 1.27 945 1.37 979
← 1.48
1-1/2 HP Standard Motor
External Static Pressure (Inches of Water) & Hi Static Drive
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Mtr
& Drive
1920 925 0.95 960 1.03 994 1.11 1026 1.19 1057 1.27
2160 944 1.08 978 1.17 1010 1.26 1043 1.36 1073 1.44 ← 1-1/2 HP Standard Motor &
2400 964 1.22 998 1.32 1030 1.42 1063 1.53 1092 1.63 Hi Static Drive
2640 986 1.39 1019 1.49 1051 1.60 1082 1.71 1112 1.81
2880 1011 1.58 1043 1.69 1073 1.79 1103 1.90 1133 2.02
2 HP Over-Sized Mtr & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 Definite Purpose Motors, Specifically Designed And
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

RT-PRC016-EN 21
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-9 — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive
3260 - - 565 0.23 627 0.29 679 0.34 726 0.39 771 0.45 814 0.51 857 0.57 899 0.63 939 0.70
3670 566 0.26 609 0.31 663 0.36 716 0.42 762 0.48 804 0.54 843 0.60 883 0.67 922 0.74 960 0.81
4080 619 0.35 660 0.40 701 0.45 751 0.51 798 0.59 839 0.65 877 0.71 914 0.78 950 0.85 984 0.93
4490 672 0.45 710 0.51 745 0.56 788 0.62 833 0.69 875 0.77 914 0.85 949 0.91 984 0.98 1016 1.06
4890 726 0.58 762 0.64 795 0.70 828 0.76 869 0.82 911 0.91 950 0.99 986 1.07 1019 1.14 1051 1.22
1.12 Nom kW Standard Motor & Drive 1.12 Nom kW Standard Motor
& Hi Static Drive

External Static Pressure (Pascals)


275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Hi Static Drive
3260 978 0.76 1015 0.83 1051 0.90 1086 0.97 1118 1.04
3670 996 0.87 1034 0.95 1069 1.02 1103 1.09 1136 1.17
4080 1020 1.00 1055 1.08 1089 1.16 1122 1.23 1154 1.31
4490 1049 1.14 1081 1.23 1113 1.31 1144 1.40 1176 1.48
4890 1081 1.30 1112 1.38 1141 1.47 1170 1.57 1199 1.66
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes: Factory Supplied Motors, In Commercial Equipment, Are
Data Includes Pressure Drop Due To Wet Coils And Filters. Definite Purpose Motors, Specifically Designed And
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 Tested To Operate Reliably And Continuously At All
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-9a — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor & Drive

1920 - - 565 0.31 627 0.39 679 0.45 726 0.52 771 0.60 814 0.69 857 0.77 899 0.85 939 0.93
2160 566 0.35 609 0.41 663 0.48 716 0.57 762 0.64 804 0.72 843 0.80 883 0.90 922 0.99 960 1.08
2400 619 0.47 660 0.54 701 0.60 751 0.69 798 0.78 839 0.87 877 0.95 914 1.04 950 1.14 984 1.24
2640 672 0.61 710 0.68 745 0.76 788 0.83 833 0.93 875 1.04 914 1.13 949 1.22 984 1.31 1016 1.42
2880 726 0.77 762 0.86 795 0.94 828 1.02 869 1.11 911 1.21 950 1.33 986 1.44 1019 1.53 1051 1.63
1-1/2 HP Standard Motor & Drive 1-1/2 HP Std Motor & Hi Static Drive

External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Hi Static Drive
1920 978 1.02 1015 1.11 1051 1.20 1086 1.30 1118 1.39
2160 996 1.17 1034 1.27 1069 1.36 1103 1.46 1136 1.56
2400 1020 1.35 1055 1.45 1089 1.55 1122 1.66 1154 1.76
2640 1049 1.53 1081 1.65 1113 1.76 1144 1.87 1176 1.98
2880 1081 1.74 1112 1.86 1141 1.97 1170 2.10 1199 2.22
2 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 Definite Purpose Motors, Specifically Designed And
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

22 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-10 — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4080 - - - - - - 701 0.47 750 0.54 794 0.60 834 0.67 873 0.73 909 0.80 945 0.87
4590 - - - - 699 0.53 743 0.59 787 0.66 830 0.74 871 0.82 908 0.89 943 0.96 977 1.04
5100 - - 703 0.61 747 0.68 789 0.74 827 0.82 867 0.90 906 0.98 944 1.06 980 1.15 1013 1.23
5610 713 0.69 755 0.77 797 0.85 836 0.92 873 1.00 908 1.08 944 1.17 980 1.26 1016 1.35 1050 1.45
6120 771 0.88 809 0.96 848 1.06 885 1.14 921 1.22 954 1.30 986 1.39 1019 1.49 1052 1.58 1085 1.69


1.50 Nom kW Standard Motor
External Static Pressure (Pascals) & Hi Static Drive
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Motor 1.50 Nom kW Standard Motor
& Drive & Hi Static Drive
4080 980 0.95 1013 1.02 1046 1.10 1076 1.17 1106 1.25
4590 1010 1.11 1043 1.19 1074 1.27 1105 1.36 1134 1.44
5100 1045 1.31 1076 1.39 1105 1.47 1134 1.56 1163 1.65
5610 1081 1.54 1111 1.63 1141 1.72 1168 1.80 1197 1.90
6120 1116 1.79 1148 1.89 1177 1.99 1204 2.08 1232 2.18
2.24 Nom kW Over-Sized Motor
& Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Definite Purpose Motors, Specifically Designed And
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-10a — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Low Static Drive 2 HP Standard Motor & Drive
2400 - - - - - - 701 0.63 750 0.72 794 0.81 834 0.90 873 0.98 909 1.08 945 1.17
2700 - - - - 699 0.70 743 0.79 787 0.89 830 0.99 871 1.09 908 1.19 943 1.29 977 1.39
3000 - - 703 0.81 747 0.91 789 0.99 827 1.10 867 1.20 906 1.31 944 1.43 980 1.54 1013 1.65
3300 713 0.93 755 1.03 797 1.15 836 1.24 873 1.34 908 1.45 944 1.57 980 1.69 1016 1.82 1050 1.94
3600 771 1.19 809 1.29 848 1.42 885 1.53 921 1.63 954 1.74 986 1.87 1019 1.99 1052 2.13 1085 2.26

2 HP Standard Motor
External Static Pressure (Inches of Water) & Hi Static Drive
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Mtr 2 HP Standard Motor &
& Drive Hi Static Drive
2400 980 1.27 1013 1.37 1046 1.47 1076 1.57 1106 1.68
2700 1010 1.49 1043 1.60 1074 1.71 1105 1.82 1134 1.93
3000 1045 1.76 1076 1.87 1105 1.98 1134 2.09 1163 2.21
3300 1081 2.06 1111 2.18 1141 2.30 1168 2.42 1197 2.55
3600 1116 2.39 1148 2.53 1177 2.66 1204 2.79 1232 2.93
3 HP Over-Sized Mtr & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
Factory Supplied Motors, In Commercial Equipment, Are
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
Definite Purpose Motors, Specifically Designed And
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

RT-PRC016-EN 23
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Motor & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4080 - - 673 0.42 718 0.47 769 0.54 814 0.61 855 0.67 893 0.73 929 0.81 965 0.88 999 0.96
4590 702 0.51 738 0.56 773 0.62 817 0.68 862 0.76 904 0.85 941 0.92 975 0.98 1009 1.06 1041 1.14
5100 771 0.68 805 0.74 837 0.81 870 0.87 912 0.94 951 1.03 989 1.12 1025 1.21 1056 1.28 1088 1.36
5610 842 0.89 873 0.96 903 1.03 930 1.10 963 1.17 1000 1.25 1037 1.34 1073 1.45 1106 1.55 1136 1.63
6120 913 1.14 942 1.22 970 1.30 996 1.37 1021 1.45 1052 1.52 1086 1.61 1121 1.71 1153 1.82 1184 1.93
1.50 Nom kW Standard Motor & Drive 1.50 Nom kW Standard Motor & 2.24 Nom kW OS
Hi Static Drive Motor & Hi Static Drive

External Static Pressure (Pascals)


275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Hi Static Drive
4080 1035 1.04 1070 1.12 1104 1.19 1137 1.27 1168 1.35
4590 1073 1.22 1104 1.31 1136 1.40 1167 1.48 1198 1.57
5100 1117 1.44 1146 1.53 1176 1.62 1205 1.72 1233 1.82
5610 1165 1.72 1194 1.80 1220 1.88 1248 1.98 1275 2.08
6120 1215 2.04 1242 2.13 1269 2.22 1295 2.31 1319 2.40
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes: Factory Supplied Motors, In Commercial Equipment, Are
Data Includes Pressure Drop Due To Wet Coils And Filters. Definite Purpose Motors, Specifically Designed And
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Tested To Operate Reliably And Continuously At All
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Low Static Drive 2 HP Standard Motor & Drive
2400 - - 673 0.56 718 0.63 769 0.72 814 0.82 855 0.90 893 0.98 929 1.08 965 1.18 999 1.29
2700 702 0.68 738 0.76 773 0.83 817 0.92 862 1.02 904 1.13 941 1.23 975 1.32 1009 1.42 1041 1.52
3000 771 0.91 805 1.00 837 1.08 870 1.17 912 1.26 951 1.38 989 1.51 1025 1.62 1056 1.72 1088 1.82
3300 842 1.19 873 1.29 903 1.38 930 1.47 963 1.57 1000 1.68 1037 1.80 1073 1.94 1106 2.08 1136 2.19
3600 913 1.53 942 1.63 970 1.74 996 1.84 1021 1.94 1052 2.04 1086 2.16 1121 2.29 1153 2.44 1184 2.59

2 HP Standard Motor & Drive 2 HP Std Motor & Hi Static Drive


3 HP Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Hi Static Drive
2400 1035 1.39 1070 1.50 1104 1.60 1137 1.70 1168 1.81
2700 1073 1.64 1104 1.76 1136 1.87 1167 1.99 1198 2.11
3000 1117 1.93 1146 2.05 1176 2.17 1205 2.31 1233 2.44
3300 1165 2.30 1194 2.41 1220 2.52 1248 2.66 1275 2.79
3600 1215 2.73 1242 2.86 1269 2.98 1295 3.10 1319 3.22
3 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 Definite Purpose Motors, Specifically Designed And
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

24 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-12 — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4620 - - - - - - 613 0.45 655 0.54 695 0.62 733 0.71 769 0.81 802 0.90 833 1.00
5200 - - - - 611 0.48 650 0.55 688 0.64 725 0.73 761 0.83 796 0.93 828 1.03 861 1.13
5780 - - 612 0.51 651 0.59 689 0.68 724 0.76 759 0.86 792 0.96 825 1.07 856 1.18 887 1.28
6350 622 0.56 659 0.64 693 0.72 729 0.82 764 0.92 795 1.01 826 1.11 857 1.22 887 1.34 916 1.46
6930 671 0.71 706 0.80 738 0.89 770 0.98 804 1.09 834 1.19 864 1.30 892 1.40 920 1.52 948 1.64


1.50 Nom kW Standard
Motor & Hi Static Drive
External Static Pressure (Pascals)
275 300 325 350 375 400 425 450 475 500
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Drive 1.50 Nom kW Std Mtr & Hi Static Dr
4620 863 1.11 892 1.21 920 1.33 946 1.44 973 1.55 999 1.67 1025 1.79 1050 1.90 1073 2.02 1098 2.14
5200 891 1.24 919 1.35 946 1.46 973 1.58 999 1.71 1024 1.83 1048 1.96 1072 2.09 1096 2.22 1119 2.34
5780 917 1.40 946 1.51 974 1.63 1001 1.75 1026 1.88 1051 2.01 1074 2.14 1099 2.27 1121 2.41 1143 2.55
6350 945 1.58 974 1.70 1001 1.82 1028 1.95 1054 2.08 1079 2.20 1103 2.34 1126 2.48 1148 2.62 1170 2.76
6930 976 1.78 1002 1.91 1029 2.04 1055 2.17 1081 2.30 1105 2.43 1130 2.58 1154 2.72 1176 2.85 1199 3.01
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Table PD-12a — Belt Drive Evaporator Fan Performance -TSC102AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Low Static Drive 2 HP Standard Motor & Drive
2720 - - - - - - 613 0.60 655 0.72 695 0.84 733 0.95 769 1.08 802 1.21 833 1.34
3060 - - - - 611 0.64 650 0.74 688 0.85 725 0.98 761 1.11 796 1.25 828 1.38 861 1.52
3400 - - 612 0.68 651 0.79 689 0.91 724 1.02 759 1.15 792 1.29 825 1.43 856 1.58 887 1.72
3740 622 0.76 659 0.86 693 0.97 729 1.10 764 1.23 795 1.35 826 1.49 857 1.64 887 1.79 916 1.96
4080 671 0.96 706 1.08 738 1.19 770 1.32 804 1.46 834 1.60 864 1.74 892 1.88 920 2.04 948 2.20


2 HP Standard Motor &
Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Mtr & Drive 2 HP Std Motor & Hi Static Drive
2720 863 1.48 892 1.63 920 1.78 946 1.93 973 2.08 999 2.24 1025 2.39 1050 2.55 1073 2.71 1098 2.88
3060 891 1.66 919 1.81 946 1.96 973 2.12 999 2.29 1024 2.46 1048 2.63 1072 2.80 1096 2.98 1119 3.14
3400 917 1.87 946 2.03 974 2.18 1001 2.34 1026 2.52 1051 2.69 1074 2.86 1099 3.05 1121 3.23 1143 3.41
3740 945 2.11 974 2.28 1001 2.44 1028 2.61 1054 2.78 1079 2.96 1103 3.14 1126 3.32 1148 3.51 1170 3.71
4080 976 2.38 1002 2.56 1029 2.73 1055 2.91 1081 3.09 1105 3.26 1130 3.45 1154 3.65 1176 3.83 1199 4.03
3 HP Over-Sized Motor & Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

RT-PRC016-EN 25
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-13 — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4620 - - - - 646 0.50 689 0.58 734 0.67 781 0.77 826 0.88 865 0.98 898 1.07 928 1.16
5200 616 0.51 654 0.57 693 0.64 735 0.73 773 0.82 812 0.92 855 1.03 897 1.15 934 1.27 969 1.38
5780 675 0.68 711 0.75 743 0.82 781 0.91 819 1.01 853 1.11 886 1.21 925 1.34 964 1.47 1000 1.60
6350 735 0.89 770 0.97 799 1.04 830 1.12 865 1.23 899 1.34 930 1.45 960
← 1.56 994 1.68 1028 1.82
6930 796 1.14 828 1.23 857 1.31 883 1.39 913 1.48 945 1.60 977 1.72 1006 1.84 1034 1.96 1061 2.08
1.50 Nom kW Std Mtr 2.24 Nom kW Over-Sized
& High Static Drive Motor & High Static Drive

External Static Pressure (Pascals)


275 300 325 350 375 400 425 450 475 500
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & High Static Drive
4620 956 1.25 982 1.33 1008 1.42 1033 1.51 1056 1.60 1079 1.69 1102 1.78 1125 1.87 1146 1.95 1168 2.04
5200 999 1.49 1026 1.58 1052 1.68 1078 1.78 1101 1.88 1124 1.98 1146 2.08 1168 2.18 1188 2.27 1209 2.37
5780 1034 1.73 1067 1.86 1094 1.97 1120 2.08 1145 2.20 1168 2.31 1191 2.42 1213 2.53 1234 2.63 1254 2.74
6350 1063 1.96 1098 2.11 1129 2.26 1158 2.40 1185 2.53 1210 2.66 1234 2.78 1256 2.90 1278 3.03 1299 3.15
6930 1093 2.23 1125 2.38 1157 2.53 1188 2.70 1218 2.86 1245 3.01 1273 3.16 1297 3.31 - - - -
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes: Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Data Includes Pressure Drop Due To Wet Coils And Filters. Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 Will Not Be Affected.

Table PD-13a — Belt Drive Evaporator Fan Performance -TSC102AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Mtr & Low Static Drive 2 HP Standard Motor & Drive
2720 - - - - 646 0.67 689 0.78 734 0.90 781 1.04 826 1.18 865 1.31 898 1.44 928 1.56
3060 616 0.69 654 0.77 693 0.86 735 0.98 773 1.10 812 1.23 855 1.39 897 1.55 934 1.70 969 1.85
3400 675 0.92 711 1.01 743 1.10 781 1.22 819 1.36 853 1.49 886 1.62 925 1.79 964 1.97 1000 2.14
3740 735 1.20 770 1.30 799 1.40 830 1.51 865 1.65 899 1.79 930 1.94 960 2.09 994 2.26 1028 2.44

4080 796 1.53 828 1.65 857 1.76 883 1.86 913 1.99 945 2.15 977 2.30 1006 2.47 1034 2.63 1061 2.79
3 HP Over-Sized Mtr & Drive

2 HP Std Motor &


Hi Static Drive

External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & High Static Drive 3 HP Over-Sized Motor & Drive
2720 956 1.67 982 1.79 1008 1.91 1033 2.03 1056 2.14 1079 2.26 1102 2.38 1125 2.5 1146 2.62 1168 2.74
3060 999 1.99 1026 2.12 1052 2.26 1078 2.39 1101 2.52 1124 2.66 1146 2.79 1168 2.92 1188 3.05 1209 3.18
3400 1034 2.32 1067 2.49 1094 2.64 1120 2.79 1145 2.94 1168 3.09 1191 3.24 1213 3.39 1234 3.53 1254 3.68
3740 1063 2.63 1098 2.84 1129 3.03 1158 3.21 1185 3.39 1210 3.56 1234 3.73 1256 3.89 1278 4.06 1299 4.23
4080 1093 2.99 1125 3.19 1157 3.40 1188 3.62 1218 3.83 1245 4.03 1273 4.24 1297 4.44 - - - -
3 HP Over-Sized Motor & Drive
Notes: Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Data Includes Pressure Drop Due To Wet Coils And Filters. Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 Will Not Be Affected.

26 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-14 — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Standard Motor & Low Static Drive 2.24 Nom kW Standard Motor & Drive
5440 - - - - - - - - 718 0.72 754 0.82 789 0.93 822 1.03 856 1.14 887 1.25
6120 - - - - - - 731 0.81 764 0.90 797 0.99 829 1.10 860 1.22 892 1.34 922 1.46
6800 - - 715 0.81 747 0.90 782 1.01 814 1.11 844 1.21 874 1.32 903 1.44 932 1.56 960 1.69
7480 741 0.95 773 1.04 803 1.14 834 1.24 864 1.36 894 1.48 922 1.59 948 1.70 975 1.82 1001 1.95
8160 803 1.21 833 1.31 861 1.42 887 1.52 916 1.64 945 1.77 972 1.90 997 2.02 1022 2.14 1046 2.27

External Static Pressure (Pascals)


275 300 325 350 375 400 425 450 475 500
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Standard Motor & Drive
5440 917 1.36 945 1.47 973 1.60 999 1.72 1024 1.84 1048 1.97 1072 2.10 1095 2.23 1117 2.37 1140 3.36
6120 951 1.57 979 1.69 1007 1.82 1033 1.94 1059 2.07 1082 2.20 1107 2.34 1130 2.49 1152 2.63 1173 3.71
6800 988 1.82 1015 1.95 1042 2.08 1068 2.21 1093 2.35 1117 2.48 1142 2.63 1164 2.76 1187 2.91 1209 4.11
7480 1028 2.09 1053 2.23 1078 2.38 1103 2.52 1128 2.66 1152 2.81 1176 2.95 1198 3.10 1221 3.25 - -
8160 1071 2.41 1095 2.55 1119 2.70 1142 2.86 1166 3.02 1189 3.17 1212 3.33 - - - - - -
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Table PD-14a — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Low Static Drive 3 HP Standard Motor & Drive
3200 - - - - - - - - 718 0.97 754 1.10 789 1.25 822 1.38 856 1.53 887 1.67
3600 - - - - - - 731 1.08 764 1.20 797 1.33 829 1.48 860 1.63 892 1.79 922 1.95
4000 - - 715 1.09 747 1.21 782 1.35 814 1.49 844 1.63 874 1.77 903 1.93 932 2.09 960 2.27
4400 741 1.27 773 1.40 803 1.53 834 1.67 864 1.82 894 1.98 922 2.13 948 2.28 975 2.44 1001 2.62
4800 803 1.62 833 1.76 861 1.90 887 2.04 916 2.20 945 2.38 972 2.55 997 2.71 1022 2.87 1046 3.04

External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive
3200 917 1.82 945 1.97 973 2.14 999 2.30 1024 2.47 1048 2.65 1072 2.82 1095 3.00 1117 3.17 1140 3.36
3600 951 2.11 979 2.27 1007 2.43 1033 2.60 1059 2.78 1082 2.95 1107 3.14 1130 3.33 1152 3.52 1173 3.71
4000 988 2.44 1015 2.62 1042 2.79 1068 2.97 1093 3.15 1117 3.33 1142 3.52 1164 3.70 1187 3.91 1209 4.11
4400 1028 2.81 1053 3.00 1078 3.19 1103 3.38 1128 3.57 1152 3.77 1176 3.96 1198 4.15 1221 4.36 - -
4800 1071 3.23 1095 3.42 1119 3.62 1142 3.83 1166 4.04 1189 4.25 1212 4.46 - - - - - -
3 HP Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

RT-PRC016-EN 27
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-15 — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Standard Motor & Low Static Drive 2.24 Nom kW Standard Motor & Drive
5440 - - 691 0.67 730 0.75 771 0.84 807 0.94 844 1.04 886 1.16 926 1.28 965 1.41 1000 1.53
6120 729 0.84 761 0.91 792 0.99 829 1.08 865 1.19 898 1.30 930 1.41 965 1.53 1002 1.67 1038 1.81
6800 802 1.13 833 1.22 860 1.29 890 1.38 923 1.50 956 1.62 986 1.73 1015 1.85 1044 1.98 1077 2.12
7480 876 1.49 905 1.58 931 1.67 955 1.75 983 1.86 1014 1.99 1045 2.12 1072 2.25 1098 2.37 1125 2.51
8160 950 1.91 977 2.02 1002 2.11 1025 2.20 1048 2.30 1074 2.42 1102 2.56 1131 2.71 1156 2.84 1181 2.98
2.24 Nom kW Standard Motor & High Static Drive

External Static Pressure (Pascals)


275 300 325 350 375 400 425 450 475 500
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Std Mtr & Drive
5440 1029 1.64 1057 1.75 1084 1.86 1108 1.96 1132 2.06 1155 2.17 1177 2.27 1198 2.37 1219 2.48 1239 3.46
6120 1072 1.95 1106 2.10 1134 2.22 1160 2.35 1185 2.47 1209 2.59 1231 2.70 1252 2.82 1274 2.94 1295 4.10
6800 1111 2.28 1143 2.43 1174 2.58 1204 2.74 1232 2.90 1260 3.05 1283 3.18 1306 3.32 - - - -
7480 1152 2.65 1182 2.81 1211 2.97 1241 3.14 1270 3.31 - - - - - - - - - -
8160 1205 3.12 1229 3.27 - - - - - - - - - - - - - - - -
2.24 Nom kW Standard Motor & High Static Drive
Notes: Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Data Includes Pressure Drop Due To Wet Coils And Filters. Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Table PD-15a — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Low Static Drive 3 HP Standard Motor & Drive
3200 - - 691 0.89 730 1.00 771 1.13 807 1.26 844 1.39 886 1.55 926 1.72 965 1.89 1000 2.06
3600 729 1.13 761 1.22 792 1.32 829 1.45 865 1.60 898 1.74 930 1.89 965 2.06 1002 2.24 1038 2.43
4000 802 1.52 833 1.63 860 1.73 890 1.86 923 2.01 956 2.17 986 2.32 1015 2.48 1044 2.65 1077 2.85
4400 876 1.99 905 2.12 931 2.24 955 2.35 983 2.49 1014 2.66 1045 2.84 1072 3.01 1098 3.18 1125 3.36
4800 950 2.56 977 2.70 1002 2.84 1025 2.96 1048 3.08 1074 3.24 1102 3.43 1131 3.63 1156 3.81 1181 4.00
3 HP Standard Motor & High Static Drive

External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Std Mtr & Drive
3200 1029 2.20 1057 2.35 1084 2.49 1108 2.63 1132 2.77 1155 2.91 1177 3.05 1198 3.18 1219 3.32 1239 3.46
3600 1072 2.62 1106 2.81 1134 2.98 1160 3.15 1185 3.31 1209 3.47 1231 3.63 1252 3.78 1274 3.94 1295 4.10
4000 1111 3.05 1143 3.26 1174 3.47 1204 3.68 1232 3.88 1260 4.09 1283 4.27 1306 4.46 - - - -
4400 1152 3.55 1182 3.76 1211 3.99 1241 4.21 1270 4.44 - - - - - - - - - -
4800 1205 4.19 1229 4.39 - - - - - - - - - - - - - - - -
3 HP Standard Motor & High Static Drive
Notes: Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Data Includes Pressure Drop Due To Wet Coils And Filters. Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

28 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-16 — Standard Motor & Sheave/Fan Speed (RPM)


Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns
Model No. Open Open Open Open Open Open Closed
TSC060AD N/A 898 967 1036 1105 1174 1243
TSC072AD N/A 698 751 806 859 913 967
TSC090AD N/A 752 806 860 914 968 1020
TSC102AD N/A 688 737 786 835 885 934
TSC120AD N/A 782 838 894 950 1006 1062
Factory set at 3 turns open

Table PD-17 — Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (RPM)
Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns
Model No. Open Open Open Open Open Open Closed
TSC060AD N/A 691 760 829 898 967 1036
TSC072AD N/A 537 590 644 698 752 806
TSC090AD N/A 671 714 757 800 843 886
TSC102AD N/A 629 664 701 737 773 811
TSC120AD N/A 717 754 799 844 885 922
Factory set at 3 turns open

Table PD-18 — Standard Motor & High Static Drive Accessory Sheave/Fan Speed (RPM)
Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns
Model No. Open Open Open Open Open Open Closed
TSC060AD N/A 1243 1311 1379 1450 1515 1588
TSC072AD N/A 967 1021 1075 1128 1183 1235
TSC090AD 1020 1073 1127 1181 1235 1289 N/A
TSC102AD 936 981 1032 1083 1134 1182 N/A
TSC120AD 1062 1118 1174 1229 1285 1341 N/A
Factory set at 3 turns open

Table PD-19 — Oversized Motor & Drive Sheave/Fan Speed (RPM)


Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns
Model No. Open Open Open Open Open Open Closed
TSC072AD N/A 967 1021 1075 1128 1183 1235
TSC090AD 1112 1182 1252 1322 1392 1460 N/A
TSC102AD N/A 971 1041 1111 1181 1251 1321
TSC120AD N/A N/A N/A N/A N/A N/A N/A
Factory set at 3 turns open

Table PD-20 — Sound Power Level - dB (ref. 10 -12 Watts)


Unit Octave Center Frequency Overall
Model No. 63 125 250 500 1000 2000 4000 8000 dBA
TSC060AD 84 91 79 77 74 71 68 63 80
TSC072AD 83 90 86 82 79 75 70 63 85
TSC090AD 83 90 86 83 80 75 71 64 85
TSC102AD 83 89 84 81 77 72 69 62 83
TSC120AD 83 86 80 77 73 69 66 60 79
Note:
Tests follow ARI 270-95

RT-PRC016-EN 29
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-21 — Static Pressure Drops Through Accessories - (Pascals)


Economizer Electric Heater
OA/RA Dampers2 Accessory (kW)3
Unit Airflow Standard Pleated Filters 100% OA 100% RA 100% OA 100% RA
Model No. (m3/h) Filters1 (50 mm) Downflow Horizontal 9 13-27 40
TSC060AD 2720 25 37 30 11 30 4 11 13 -
3400 37 55 46 17 46 6 17 21 -
4080 55 72 64 26 64 9 25 30 -
TSC072AD 3260 10 17 25 2 15 5 - 5 -
4080 15 22 27 5 20 5 - 8 -
4890 22 30 33 10 25 10 - 13 -
TSC090AD 4080 15 22 27 5 20 5 - 8 -
5100 25 32 35 12 30 12 - 16 -
6120 35 45 52 17 62 20 - 25 -
TSC102AD 4620 12 20 31 7 22 10 - 6 -
5780 20 27 47 15 45 15 - 10 -
6930 30 40 75 17 77 22 - 15 -
TSC120AD 5440 17 25 42 12 35 12 - 9 10
6800 27 37 65 17 75 20 - 14 17
8160 40 50 85 22 87 25 - 20 26
Notes:
1. Tested with standard filters. The TSC060AD has 25 mm (1 inch) standard fiters. The TSC072AD - 120AD has 50 mm (2 inch) standard filters.
The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nominal kW ratings at 415 V

Table PD-21a — Static Pressure Drops Through Accessories - (Inches of Water Column)
Economizer Electric Heater
OA/RA Dampers2 Accessory (kW)3
Unit Airflow Standard Pleated Filters 100% OA 100% RA 100% OA 100% RA
Model No. (CFM) Filters1 (2 inch) Downflow Horizontal 9 13-27 40
TSC060AD 1600 0.10 0.15 0.12 0.04 0.12 0.01 0.045 0.053 -
2000 0.15 0.22 0.18 0.07 0.18 0.02 0.070 0.083 -
2400 0.22 0.29 0.26 0.10 0.26 0.04 0.100 0.120 -
TSC072AD 1920 0.04 0.07 0.10 0.01 0.06 0.02 - 0.021 -
2400 0.06 0.09 0.11 0.02 0.08 0.02 - 0.034 -
2880 0.09 0.12 0.13 0.04 0.10 0.04 - 0.052 -
TSC090AD 2400 0.06 0.09 0.11 0.02 0.08 0.02 - 0.034 -
3000 0.10 0.13 0.14 0.05 0.12 0.05 - 0.063 -
3600 0.14 0.18 0.21 0.07 0.25 0.08 - 0.102 -
TSC102AD 2720 0.05 0.08 0.12 0.03 0.09 0.04 - 0.026 -
3400 0.08 0.11 0.19 0.06 0.18 0.06 - 0.041 -
4080 0.12 0.16 0.30 0.07 0.31 0.09 - 0.059 -
TSC120AD 3200 0.07 0.10 0.17 0.05 0.14 0.05 - 0.036 0.042
4000 0.11 0.15 0.26 0.07 0.30 0.08 - 0.056 0.070
4800 0.16 0.20 0.34 0.09 0.35 0.10 - 0.081 0.106
Notes:
1. Tested with standard filters. The TSC060AD has 25 mm (1 inch) standard fiters. The TSC072AD - 120AD has 50 mm (2 inch) standard filters.
The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2. OA = Outside Air and RA = Return Air
3. Nominal kW ratings at 415 V

Table PD-22 - Electric Heater Voltage Correction Factors (Apply to Auxiliary Electric Heat
Capacity)
Nominal Distribution Capacity
Voltage Voltage Multipiler
380 0.84
415 400 0.93
415 1.00

30 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Performance
Data

Table PD-23 — Auxiliary Electric Heat Capacity (SI)


Total2 Stage 1 Stage 2
Unit Unit
Model No. Voltage KW No. Stages KW KW
7.5 / 9.0 2 3.75 / 4.5 3.75 / 4.5
TSC060AD 380-415/50/3 10.9 / 13.0 2 5.45 / 6.5 5.45 / 6.5
14.4 / 17.2 2 8.95 / 10.7 5.45 / 6.5
11.3 / 13.5 1 11.3 / 13.5 —-
TSC072AD 380-415/50/3 16.9 / 20.2 2 11.3 / 13.5 5.6 / 6.7
22.6 / 26.9 2 11.3 / 13.5 11.3 / 13.5
11.3 / 13.5 1 11.3 / 13.5 —-
TSC090AD 380-415/50/3 16.9 / 20.2 2 11.3 / 13.5 5.6 / 6.7
22.6 / 26.9 2 11.3 / 13.5 11.3 / 13.5
TSC102AD 380-415/50/3 16.9 / 20.2 2 11.3 / 13.6 5.6 / 6.7
22.6 / 26.9 2 11.3 / 13.7 11.3 / 13.5
16.9 / 20.2 2 11.3 / 13.8 5.6 / 6.7
TSC120AD 380-415/50/3 22.6 / 26.9 2 11.3 / 13.9 11.3 / 13.5
33.9 / 40.4 2 11.3 / 13.10 22.5 / 26.9
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 380V / 415V. For other than rated voltage, CAP=(Voltage/Rated Voltage)2 x Rated Cap.

Table PD-23A — Auxiliary Electric Heat Capacity (IP)


Total2 Stage 1 Stage 2
Unit Unit
Model No. Voltage MBH No. Stages MBH MBH
26 / 31 2 13 / 16 13 / 16
TSC060AD 380-415/50/3 38 / 45 2 19 / 23 19 / 23
50 / 59 2 31 / 37 19 / 23
39 / 47 1 39 / 47 —-
TSC072AD 380-415/50/3 58 / 69 2 39 / 47 20 / 23
78 / 92 2 39 / 47 39 / 47
39 / 47 1 39 / 47 —-
TSC090AD 380-415/50/3 58 / 69 2 39 / 47 20 / 23
78 / 92 2 39 / 47 39 / 47
TSC102AD 380-415/50/3 58 / 69 2 39 / 47 20 / 23
78 / 92 2 39 / 47 39 / 47
58 / 69 2 39 / 47 20 / 23
TSC120AD 380-415/50/3 78 / 92 2 39 / 47 39 / 47
116 / 138 2 39 / 47 77 / 92
Notes:
1. Does not include indoor fan power or heat
2. Heaters are rated at 380 / 415V. For other than rated voltage, CAP=(Voltage/Rated Voltage)2 x Rated Cap.

RT-PRC016-EN 31
Downloaded from www.Manualslib.com manuals search engine
Performance
Data

Table PD-24 — Air Temperature Rise Across Electric Heaters (Degrees C)

kW 3400 m3/h 4100 m3/h 5100 m3/h 5800 m3/h 6800 m3/h
380V / 415V Voltage Stages TSC060AD TSC072AD TSC090AD TSC102AD TSC120AD
07.5 / 09.0 380-415/50/3 2 6.6 / 7.9 —- —- —- —-
10.9 / 13.0 380-415/50/3 2 9.6 / 11.4 —- —- —- —-
11.3 / 13.5 380-415/50/3 1 —- 8.3 / 9.9 6.6 / 7.9 —- —-
14.4 / 17.2 380-415/50/3 2 12.6 / 15.1 —- —- —- —-
16.9 / 20.2 380-415/50/3 2 —- 12.4 / 14.8 9.9 / 11.8 8.7 / 10.4 7.4 / 8.9
22.6 / 26.9 380-415/50/3 2 —- 16.5 / 19.7 13.2 / 15.7 11.7 / 13.9 9.9 / 11.8
33.8 / 40.4 380-415/50/3 2 —- —- —- —- 14.8 / 17.7
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (C0) across Elect Htr = (kW x 2985)/( m3/h)

Table PD-24A — Air Temperature Rise Across Electric Heaters (Degrees F)

kW 2000 CFM 2400 CFM 3000 CFM 3400 CFM 4000 CFM
380V / 415V Voltage Stages TSC060AD TSC072AD TSC090AD TSC102AD TSC120AD
07.5 / 09.0 380-415/50/3 2 11.9 / 14.2 —- —- —- —-
10.9 / 13.0 380-415/50/3 2 17.2 / 20.5 —- —- —- —-
11.3 / 13.5 380-415/50/3 1 —- 14.9 / 17.8 11.9 / 14.2 —- —-
14.4 / 17.2 380-415/50/3 2 22.8 / 27.2 —- —- —- —-
16.9 / 20.2 380-415/50/3 2 —- 22.3 / 26.6 17.8 / 21.3 15.7 / 18.8 13.4 / 16.0
22.6 / 26.9 380-415/50/3 2 —- 29.8 / 35.4 23.8 / 28.3 21.0 / 25.0 17.9 / 21.3
33.8 / 40.4 380-415/50/3 2 —- —- —- —- 26.7 / 31.9
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (F0) across Elect Htr = (kW x 3414)/(1.08 x CFM)

32 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Zone Controls

Zone Sensors Non-programmable manual auto Conventional Thermostats


Zone Sensors are the building changeover with digital LCD Display — Conventional Thermostats are the
occupant’s comfort control devices for Auto, heat, cool or off mode selection building occupant’s comfort control
Precedent™ units with the ReliaTel button. Auto or off fan bottom. Status devises when a generic thermostat is
indication LCD indicators — System on,
control. The zone sensor offering desired.
heat, cool, or service.
operates with the Reliatel Manual
microprocessor Changeover —
Manual Changeover — Heat, Cool or Off One Heat, One
System Switch. Fan Auto or Off Switch. Cool Thermostat.
One Heat, Cool or Off
temperature System Switch.
setpoint lever. Fan Auto or On
Switch. Set Point
Dial. Adjustable
Heat Anticipator.
Automatic Changeover — One Heat,
Two Cool Thermostat. Off, Auto System
Switch. Auto/On Fan Switch.

Programmable Night Setback — Auto


or manual changeover with seven-day
programming. Keyboard selection of
Manual/Automatic Changeover —Auto, Heat, Cool, Fan, Auto, or On.
Heat, Cool or Off System Switch. Fan All programmable sensors have
Auto or Off
Switch. Two
temperature
setpoint
levers. Optional Programmable Electronic Night Setback
Status Indication Thermostat — Heating setback and
LED lights, cooling setup with 7-day, programming
System On, capability. Available in two-stage
Heat, Cool, or heating/cooling or one-stage heating/
Service. cooling versions with automatic
changeover.
System On, Heat, Cool, Service LED/
indicators as standard. Night Setback
Sensors have one (1) Occupied, one (1)
Unoccuped, and two (2) Override
programs per day.
Remote Sensor — Sensor(s) available
for all zone sensors to provide Integrated Comfort™ System —
remote sensing Sensor(s) available with optional
capabilities. temperature
adjustment and
override buttons
to provide
central control
through a Trane
Integrated
Comfort™
system.

RT-PRC016-EN 33
Downloaded from www.Manualslib.com manuals search engine
Electrical
Data

Table ED-1 — Unit Wiring


Standard Indoor Fan Motor Oversized Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum
Model No. Voltage Range Ampacitiy Circuit Breaker1 Ampacitiy Circuit Breaker1
TSC060AD 342-456 17.7 25 17.7 25
TSC072AD 342-456 23.2 35 24.2 35
TSC090AD 342-456 24.8 35 26.5 35
TSC102AD 342-456 26.8 35 28.5 35
TSC120AD 342-456 31.2 40 31.2 40
Notes:
1. All units to be installed under local codes

Table ED-2 — Unit Wiring With Electric Heat Single Point Connection — 380-415 Volts
Standard Indoor Fan Motor Oversized Indoor Fan Motor
Minimum Maximum Fuse Minimum Maximum Fuse
Unit Heater Heater2 Control Circuit Size Or Maximum Circuit Size Or Maximum
Model No. Model No. kW Rating MBH Stages Ampacitiy Circuit Breaker1 Ampacitiy Circuit Breaker1
TSC060AD BAYHTRR412A 7.5 / 9.0 26 / 31 2 19.8 / 21.0 25 / 25 19.8 / 21.0 25 / 25
BAYHTRR418A 10.9 / 13.0 38 / 45 2 26.1 / 28.0 30 / 30 26.1 / 28.0 30 / 30
BAYHTRR423A 14.4 / 17.2 50 / 59 2 32.8 / 35.3 35 / 40 32.8 / 35.3 35 / 40
TSC072AD BAYHTRS418A 11.3 / 13.5 39 / 47 1 26.9 / 28.9 35 / 35 28.1 / 30.1 35 / 35
BAYHTRS427A 16.9 / 20.2 58 / 69 2 37.5 / 40.5 40 / 45 38.8 / 41.8 40 / 45
BAYHTRS436A 22.6 / 26.9 78 / 92 2 48.3 / 52.1 50 / 60 49.5 / 53.4 50 / 60
TSC090AD BAYHTRS418A 11.3 / 13.5 39 / 47 1 28.1 / 30.1 35 / 35 30.3 / 32.3 35 / 35
BAYHTRS427A 16.9 / 20.2 58 / 69 2 38.8 / 41.8 40 / 45 40.9 / 43.9 45 / 45
BAYHTRS436A 22.6 / 26.9 78 / 92 2 49.5 / 53.4 50 / 60 51.6 / 55.5 60 / 60
TSC102AD BAYHTRT427A 16.9 / 20.2 58 / 69 2 38.8 / 41.8 40 / 45 40.9 / 43.9 45 / 45
BAYHTRT436A 22.6 / 26.9 78 / 92 2 49.5 / 53.4 50 / 60 51.6 / 55.5 60 / 60
TSC120AD BAYHTRT427A 16.9 / 20.2 58 / 69 2 40.9 / 43.9 45 / 45 40.9 / 43.9 45 / 45
BAYHTRT436A 22.6 / 26.9 78 / 92 2 51.6 / 55.5 60 / 60 51.6 / 55.5 60 / 60
BAYHTRT454A 33.8 / 40.4 116 / 138 2 73.1 / 79.0 80 / 80 73.1 / 79.0 80 / 80
Notes:
1. All units to be installed under local codes
2. kW and MBH shown for 380V / 415V

Table ED-3 — Electrical Characteristics - Evaporator Fan Motor - 50 Hz


Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Amps Amps
Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
TSC060AD 1 380-415 3 1.5 4.3 25.3 - - - - - -
TSC072AD 1 380-415 3 1.5 4.3 25.3 1 380-415 3 2.0 5.3 36.4
TSC090AD 1 380-415 3 2.0 5.3 36.4 1 380-415 3 3.0 7.0 57.0
TSC102AD 1 380-415 3 2.0 5.3 36.4 1 380-415 3 3.0 7.0 57.0
TSC120AD 1 380-415 3 3.0 7.0 57.0 - - - - - -

Table ED-4 — Electrical Characteristics - Compressor Motor and Condenser Motor - 50 Hz


Compressor Motor Condenser Fan Motor
Unit Amps Amps
Model No. No. Volts Phase HP1 RPM RLA1 LRA1 No. Phase HP FLA LRA
TSC060AD 1 380-415 3 5.7 2875 9.5 74.00 1 1 0.40 1.9 2.8
TSC072AD 1 380-415 3 7.5 2875 12.7 95.00 1 1 0.75 2.8 7.1
TSC090AD 1 380-415 3 8.3 2875 13.20 100.00 1 1 0.75 2.8 7.1
TSC102AD 2 380-415 3 6.0/3.8 2875 9.3/6.9 74.0/48.0 1 1 0.75 2.8 7.1
TSC120AD 2 380-415 3 6.0/4.8 2875 9.9/8.5 74.0/61.8 1 1 0.75 2.8 7.1
Note:
1. Comp1/Comp2

34 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Jobsite
Connections

Zone Sensors — Typical Number Of Wires


DISCONNECT
SWITCH
(BY OTHERS) A — Manual Changeover . . . . . . . . . . . . . . . . . 4
Manual/Auto Changeover . . . . . . . . . . . . . 5
Manual/Auto Changeover with
ZONE SENSOR Status Indication LED’s . . . . . . . . . . . . . 10
OR THERMOSTAT Programmable Night Setback with
Status Indication LED’s . . . . . . . . . . . . . . 7
ROOFTOP
UNIT Thermostats — Typical Number of Wires
A — 3 wires, 24-volts, Cooling Only
4 wires, 24-volts, with Electric Heat
B — 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.

RT-PRC016-EN 35
Downloaded from www.Manualslib.com manuals search engine
Dimensional
Data TSC060

All dimensions are in inches/millimeters.

TSC060

36 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Dimensional
Data TSC060

All dimensions are in inches/millimeters.

TSC060 — Downflow Airflow Supply/Return

TSC060 — Horizontal Airflow Supply/Return

TSC060 — Unit Clearance and Roof Opening

RT-PRC016-EN 37
Downloaded from www.Manualslib.com manuals search engine
Dimensional
Data TSC060

All dimensions are in inches/millimeters.

TSC060 — Roof Curb

TSC060 — Downflow Duct Connections — Field Fabricated

38 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Dimensional
Data TSC072-120

All dimensions are in inches/millimeters.

TSC072-090

TSC102-120

RT-PRC016-EN 39
Downloaded from www.Manualslib.com manuals search engine
Dimensional
Data TSC072-120

All dimensions are in inches/millimeters.

TSC072-120 — Downflow Airflow Supply


and Return

TSC072-120 — Horizontal Airflow Supply


and Return

TSC072-120 — Unit Clearance and Roof


Opening

40 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Dimensional
Data TSC072-120

All dimensions are in inches/millimeters.

TSC072-120 — Roof Curb

TSC072-120 — Downflow Duct Connections —


Field Fabricated
ALL FLANGES 1 1/4” (31 MM)

RT-PRC016-EN 41
Downloaded from www.Manualslib.com manuals search engine
Dimensional TSC060
Data Options/Accessories

All dimensions are in inches/millimeters.

TSC060 — Economizer , Manual or Motorized Fresh Air Damper TSC060 — Barometric Relief Damper Hood

TSC060 — Swing Diameter for Hinged Doors Option

42 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Dimensional TSC072-120
Data Options/Accessories

All dimensions are in inches/millimeters.

TSC072-120 — Economizer and Barometric


Relief Damper Hoods

TSC072-120 — Swing Diameter for


Hinged Door(s) Option

RT-PRC016-EN 43
Downloaded from www.Manualslib.com manuals search engine
Weights

Table W-1 - Maximum Unit and Corner Weights and Center of Gravity Dimensions (SI)
Maximum Weights(2) (kg) Corner Weights(1) (kg) Center of Gravity (mm)
Unit
Model No. Shipping(2) Net(2) A B C D Length Width
TSC060AD 270 235 75 56 48 56 790 480
TSC072AD 373 326 107 83 58 78 970 560
TSC090AD 436 389 131 101 67 89 970 530
TSC102AD 453 405 133 106 72 94 990 560
TSC120AD 493 445 147 115 81 104 990 560
Notes:
(1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
(2) Weights are approximate.

Table W-1a - Maximum Unit and Corner Weights and Center of Gravity Dimensions (IP)
Maximum Weights (lbs) Corner Weights(1) (lbs) Center of Gravity (in)
Unit
Model No. Shipping(2) Net A B C D Length Width
TSC060AD 595 518 165 124 105 124 31 19
TSC072AD 823 718 235 182 128 173 38 22
TSC090AD 962 857 289 222 148 197 38 21
TSC102AD 998 893 294 233 159 207 39 22
TSC120AD 1087 982 323 253 178 229 39 22
Notes:
(1) Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
(2) Weights are approximate.

Table W-2 - Accessory Net Weights(1) (2) (kg) Table W-2a - Accessory Net Weights(1) (2) (lbs)
Net Weights(2) Net Weights(2)
Accessory (3)
TSC060 TSC072-120 Accessory(3) TSC060 TSC072-120
Economizer 12 16 Economizer 26 36
Barometric Relief 3 5 Barometric Relief 7 10
Motorized Outside Air Damper 9 14 Motorized Outside Air Damper 20 30
Manual Outside Air Damper 7 12 Manual Outside Air Damper 16 26
Roof Curb 32 52 Roof Curb 70 115
Oversized Motor 2 4 Oversized Motor 5 8
Coil Guards 5 9 Coil Guards 12 20
Hinged Doors 5 5 Hinged Doors 10 12
Electric Heaters 7 14 Electric Heaters 15 30
Notes: Notes:
(1) Weights for options not listed are < 3 kg. (1) Weights for options not listed are < 5 lbs.
(2) Net weight should be added to unit weight when ordering factory-installed 2) Net weight should be added to unit weight when ordering factory-installed
accessories. accessories.
(3) Some accessories not available on all units. (3) Some accessories not available on all units.

44 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Mechanical
Specifications

General UnitTop Outdoor Fans


The units shall be convertible airflow.The The top cover shall be one piece The outdoor fan shall be direct-drive,
operating range shall be between 46°C construction or where seams exist, it statically and dynamically balanced,
and -18°C (115°F and 0°F) in cooling as shall be double-hemmed and gasket- draw-through in the vertical discharge
standard from the factory for all units. All sealed. The ribbed top adds extra position. The fan motor shall be
units shall be factory assembled, strength and prevents water from permanently lubricated and shall have
internally wired, fully charged with R-22, pooling on unit top. built-in thermal overload protection.
and 100 percent run tested to check Filters Indoor Fan
cooling operation, fan and blower One inch, throwaway filters shall be All units shall have belt drive motors.
rotation, and control sequence before standard on all 5 ton units.The filter rack Units with belt drive motors shall have
leaving the factory. Wiring internal to the can be converted to two inch capability. an adjustable idler-arm assembly for
unit shall be colored and numbered for 50 mm (2 inch) filters shall be factory quick-adjustment to fan belts and motor
simplified identification. supplied on all 6-10 ton units. Optional 50 sheaves. All motors shall be thermally
Casing mm (2 inch) pleated filters shall be protected. Oversized motors shall be
Unit casing shall be constructed of zinc available. available for high static operations.
coated, heavy gauge, galvanized steel. Compressors Controls
Exterior surfaces shall be cleaned, All units shall have direct-drive, hermetic, Unit shall be completely factory-wired
phosphatized, and finished with a scroll type compressors with centrifugal with necessary controls and contactor
weather-resistant baked enamel finish. type oil pumps. Motor shall be suction pressure lugs or terminal block for
Cabinet construction shall allow for all gas-cooled and shall have a voltage power wiring. Units shall have single
maintenance on one side of the unit. utilization range of plus or minus 10 point power connection as standard.
Service panels shall have lifting handles percent of unit nameplate voltage. Unit shall provide an external location
and be removed and reinstalled by Internal overloads shall be provided with for mounting a fused disconnect device.
removing only a single fastener while the scroll compressors. Low and high
providing a water and air tight seal. All Microprocessor controls provide for all
pressure switches shall be standard. 24 volt control functions. The resident
exposed vertical panels and top covers in
the indoor air section shall be insulated Refrigerant Circuits control algorithms shall make all
with a cleanable foil-faced, fire-retardent Service pressure ports, and refrigerant heating, cooling, and/or ventilating
permanent, odorless glass fiber material. line filter driers are factory-installed as decisions in response to electronic
The base of the unit shall be insulated standard. An area shall be provided for signals from sensors measuring indoor
with 13 mm, 16 kg (1/2 inch, 1 pound) replacement suction line driers. and outdoor temperatures. The control
density foil-faced, closed-cell material. All Evaporator and Condenser Coils algorithm maintains accurate
insulation edges shall be either captured Internally finned, 8 mm (5/16”) copper temperature control, minimizes drift
or sealed.The unit’s base pan shall have tubes mechanically bonded to a from set point, and provides better
no penetrations within the perimeter of configured aluminum plate fin shall be building comfort. A centralized
the curb other than the raised 29 mm (11/8 standard. Coils shall be leak tested at the Microprocessor shall provide anti-short
inch high downflow supply/return factory to ensure the pressure integrity. cycle timing and time delay between
openings to provide an added water The evaporator coil and condenser coil compressors to provide a higher level of
integrity precaution, if the condensate shall be leak tested to 1375 kPa (200 psig) machine protection.
drain backs up.The base of the unit shall and pressure tested to 3100 kPa (450
have provisions for forklift and crane psig).The condenser coil shall have a
lifting, with forklift capabilities on three patent pending 1 + 1 + 1 hybrid coil
sides of the unit. designed with slight gaps for ease of
cleaning. A removeable, reversible,
double-sloped condensate drain pan with
provision for through the base
condensate drain is standard.

RT-PRC016-EN 45
Downloaded from www.Manualslib.com manuals search engine
Mechanical
Specifications

Accessories/Options Economizer Discharge Air Sensing


This accessory shall be either field or This factory of field-installed option
Electric Heaters factory-installed and shall be available provides true discharge air sensing in
Field-installed electric heat modules shall with or without barometric relief.The heating models.This sensor is a status
be available for installation within basic assembly includes fully modulating 0-100 indicator readable through Tracer™ or
unit. Electric heater elements shall be percent motor and dampers, minimum Tracker™.
constructed of heavy-duty nickel position setting, preset linkage, wiring Oversized Motors
chromium elements internally delta harness with plug, spring return actuator Factory or field-installed oversized
connected for 200 volt, wye connected and fixed dry bulb control.The barometric motors shall be available for high static
for 380-415 volt. Staging shall be relief shall provide a pressure operated applications.
achieved through the unitary control damper that shall be gravity closing and
processor (UCP). Each heater package shall prohibit entrance of outside air Clogged Filter/Fan Failure Switch
shall have automatically reset high limit during the equipment “off” cycle. A dedicated differential pressure switch is
control operating through heating Optional solid state or differential available, factory-installed, to achieve
element contactors. All heaters shall be enthalpy control shall be available for active fan failure indication and/or
individually fused from the factory, where either factory or field installation.The clogged filter indication.These indications
required. Power assemblies shall provide factory-installed economizer arrives in will be registered with either a zone
single-point connection. the shipping position and shall be moved sensor with status indication lights or an
to the operating position by the installing Integrated Comfort™ System.
Roof Curb
contractor. High Pressure Cutout
The roof curb shall be designed to mate
with the unit’s downflow supply and Phase Monitor Standard on all units.
return and provide support and a water Phase monitor shall provide 100% Hinged Access Doors
tight installation when installed properly. protection for motors and compressors Sheet metal hinges are available factory-
The roof curb design shall allow field- against problems caused by phase loss, installed on the Filter/Evaporator, Supply
fabricated rectangular supply/return phase imbalance, and phase reversal. Fan/Heat, and the Compressor/Control
ductwork to be connected directly to the Phase monitor is equipped with an LED Access Doors.
curb. Curb shall be shipped knocked down that provides an ON or FAULT indicator.
Black Epoxy Coated Condenser Coil
for field assembly and shall include wood Remote Potentiometer The coil provides corrosion protection to
nailer strips. The minimum position setting of the condenser coils for seacoast application.
economizer shall be adjusted with this The protection is a factory-applied
accessory. thermoset vinyl coating, bonded to
Manual Outside Air Damper normal aluminum fin stock.The uniform
Factory or field-installed rain hood and thickness of the bonded vinyl layer
screen shall provide up to 50 percent exhibits excellent corrosion protection.
outside air.
Motorized Outside Air Dampers
Factory or field-installed manually set
outdoor air dampers shall provide up to
50 percent outside air. Once set, outdoor
air dampers shall open to set position
when indoor fan starts.The damper shall
close to the full closed position when
indoor fan shuts down.

46 RT-PRC016-EN

Downloaded from www.Manualslib.com manuals search engine


Mechanical
Specifications

Control Options Differential Pressure Switches


These factory or field-installed sensors
Comm-3/4 Trane Communication allow individual fan failure and dirty filter
Interface indication for microprocessor controlled
This factory or field-installed option shall units.The fan failure switch will disable all
be provided to interface microprocessor unit functions and “flash” the Service
controlled units with theTrane Integrated LED on the zone sensor.The dirty filter
Comfort™ systems. switch will light the Service LED on the
Comm-5 LonTalk Communication zone sensor and will allow continued unit
Interface operation.
This factory or field-installed option shall Reference Enthalpy Control
be provided to allow the unit to Replaces the dry bulb control with a wet
communicate as aTrane Comm-5 device bulb changeover controller which has a
or directly with generic LonTalk Network fully adjustable set point. Enthalpy control
Building Automation System Controls. offers a higher level of comfort control,
Zone Sensor along with energy savings potential, than
This field-installed control shall be the standard dry bulb control.This is due
provided to interface with the Micro to the additional wet bulb sensing
equipped units and shall be available in capability.This option shall be available
either manual, automatic programmable for microprocessor controlled units. It can
with night setback, with system be field-installed, or factory-installed with
malfunction lights, or remote sensor the factory-installed economizer.
options. Differential Enthalpy Control
Thermostats Replaces the standard dry bulb control
Two stage heating and cooling operation with two enthalpy sensors that compare
or one stage heating and cooling shall be total heat content of the indoor air and
available, for field installation, in either outdoor air to determine the most
manual or automatic changeover. efficient air source.This control option
Automatic programmable electronic with offers the highest level of comfort control,
night set back shall also be available. plus energy efficiency, available.This
option shall be available for
microprocessor controlled units. It can be
field-installed, or factory-installed with the
factory-installed economizer.
Low Ambient Cooling
All microprocessor units shall have
cooling capabilities down to 18°C (0°F) as
standard.

RT-PRC016-EN 47
Downloaded from www.Manualslib.com manuals search engine
Literature Order Number RT-PRC016-EN
File Number PL-UN-000-RT-PRC016-EN-02-04
Trane Supersedes PL-UN-000-RT-PRC016-EN-12-03
A business of American Standard Companies Stocking Location 03-03 Webb/Mason 02-04 Electronic Only
www.trane.com

For more information, contact your local district Trane has a policy of continuous product and product data improvement and reserves the right to change
office or e-mail us at [email protected] design and specifications without notice

Downloaded from www.Manualslib.com manuals search engine