0% found this document useful (0 votes)
104 views

Display Control Module

This document provides information on the 2003A-1 fire and gas detection control and indicating system display control module. It has 8 independent inputs that can be monitored individually or in two groups of 4. Each input has a bi-color LED that will flash red for an alarm and yellow for an open circuit. The module regulates input voltage and monitors onboard fuses. It is used to interface alarm and fault contacts from other equipment.

Uploaded by

Paul
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views

Display Control Module

This document provides information on the 2003A-1 fire and gas detection control and indicating system display control module. It has 8 independent inputs that can be monitored individually or in two groups of 4. Each input has a bi-color LED that will flash red for an alarm and yellow for an open circuit. The module regulates input voltage and monitors onboard fuses. It is used to interface alarm and fault contacts from other equipment.

Uploaded by

Paul
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

DATA SHEET

WORMALD 01-23-05

SYSTEM 2003A-1

2003A-1 FIRE AND GAS DETECTION, CONTROL AND INDICATING SYSTEM

, --USERwINF.ORMATION

-DISPLAY" CONTROL:1IODULE

Contents

Section 1. Introduction

Section 2. Specification

Section 3. Controls & Indications

Section 4. Functional Description

Section , . 5. Input / Output Definitions

Section 6. Installation & Setting Up Instructions

Section 7, Application Instructions

Pa All information is subJca to changc without ualcc .


Newton Heath
Manchester
M1068A

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex . 668618
DATA SHEET
TIT WORMALD 01-23-05

I~M ZOO3A-1 ~G~ DISPLAY CONTR DULE~

Features

" Eight independent inputs

:~:: Individual . ;.and common alarm indications


,\ ~.

''"A L A~ a1
Front panel indication of open-circuit input
field cables

" On-board fuse failure monitoring & indication


2-

0 On-board input voltage regulator


3` .

" Bi-colour channel LEDs


`.a a -
,,--
(r '~

,~+u~ .T

1 . Introduction
The 2003A-1 DISPLAY CONTROL module provides the An alarm condition will cause the relevant channel and
facility to interface the system with volt-free alarm and group LED to illuminate flashing red. When the alarm i.5
fault contacts from other manufacturers equipment. accepted both LEDs illuminate steady . Additional alarms
in the group will cause the group alarm to re-flash in
The module will accept up to eight (two groups of four)
addition to flashing the associated input channel LED .
independent inputs from non-pulsing sources (e .g .
keyswitches) . The LED for each of the eight channels is a The module has input voltage regulation, an on-board fuse,
bi-colour device, illuminating red for "alarm" or yellow for fuse failure monitor and indication facilities .
"open circuit" input wiring .

Ordering Code Description

01-23-OS Display Control Module


This module is usually supported by a Facilities module which must be ordered separately - see data sheet 01-23-03
Part1Wcrkr--..-,"-F-.. " - A orme on Is subJect to chmge wlthout uotlee . "~».~,~,~"~.~,.~,~-~~~-~~-~~~~~1m~
Newton Heath
Manchester
A 10 6B A

Tel . (061) 205 2321


Fax. (061) 205 8028
Telex, 6686 t E
DATA SHEET
01-23-05

SYSTEM ZOO3A-1 DISPLAY CONTROL MODULE

2. Specification

2.1 Mechanical
2,2 Electrical
Dimensions : 160 x 25 x 222mm
Supply Voltage: 23V to 33V do
Connector: DIN 41612 Type D male max 1V 1~ to P~ riPP
ripple
(Polarised°,1r12ar1~13a;~.203b)± ~::M: :~~: .. t . . ;:- :..
Power Consumption: Quiescent monitoring 43mA
Weight : 345 grams Quiescent . .... 33mA
Temperature Range: Operating 0 to 55C Alarm ........... 3OOmA
Storage -10 to 60C Input: 4.5mA sinking
Humidity Range: 0 to 90% RH Output: 200uiA sourcing (maac)
(non-condensing)
Inputs : Resistance measuring
Front Panel: 160mm x 25mm Q < Alarm < 1K6
finished in semi-gloss black 1K6 < Quiescent < 9K0
to BS4800 9K < Open Circuit
PCB: Glass Fibre Reinforced End of Line Resistor : SK6 0.25 watt
Epoxy Resin to BS4584
Pt. 3 and BS9762 Fuse: SOOmA 20 mm x 5 mm
Quick blow (F)
Protective Coating: Clear protective lacquer
CPL 200H
2,.3 Input Monitoring Diagram
.
immimuq
100R 1K8 5K8 9K 100K

DIN CONNECTORS
EACH WITH
?x78 ROWS OF PINS

Park Works Ail Informadar Is subJea to chmge wllhwt notice . 3A-1-5 Z 4-3-A-AU G' 91
Newton Heath
Manchester
M106BA

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex . 668618
DATA SHEET
' WORMALD 01-23-OS

-------
DISPLAY CONTROL MODULE
SYSTEM ZOO3A-1

3 . Controls and Indications

1. GROUP A ALARM (Red): The LED illuminates


flashing when one of the four inputs in Group 'A'
are active. This LED flashes in antiphase to the
input LED and will illuminate steady when the
module is accepted via the. facilities module., . It . , .
may also be illuminatedafrom :~the reflash (11/17) , . , . . ... , , ~.- .
carry input for Group 'A'.

2 to 4. INPUT A (Red/Yellow): These four LEDS are


bi-coloured and will illuminate flashing if the *- fi
associated input is active and will steady on
Accept. A yellow indcation is given when the
relevant channel input is open circuit if the
monitoring utility is selected. 4- 7

5. GROUP B ALARM (Red): The LED


illuminates flashing when one of the four inputs in
Group 'B' are active. This LED flashes in 4- 8
antiphase to the input LED and will illuminate
steady when the module is accepted via the
facilities module. It may also be illuminated from
the reflash (R/F) carry input for Group 'B'. 4- 9
4 -"
6 to 10 INPUT B (Red/Yellow) : These four LEDS are
bi-coloured and will illuminate flashing if the
associated input is active and will steady on
accept. A yellow indication is given is when the 4- 10
relevant chancel input is open circuit if the !-
monitoring utility is selected .

11 . FAULT (Yellow) : This LED is illuminated if


module fuse failure occurs . 4- 11
FAULT;' ;,,

--

1 . Group A Alarm LED 6. Group B Alarm LED


Front Panel Layout - Actual Size
2. Input IA Alarm/Fault LED 7. Input 1B Alarm/Fault LED

3. Input 2A Alarm/Fault LED 8. Input 2B Alarm/Fault LED

4. Input 3A Alarm/Fault LED 9. Input 3B Alarm/Fault LED

5. Input 4A Alarm/Fault LED 10. Input 4BAlann/Fault LED

11 . Module Fault LED

Park or AllMlnformailmsubJecl
is to change without notice. 3A - I- 514-4-A-AU G'91
Newton Heath
Manchester
M1068A

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex. 668618
DATA SHEET
01-23-05

DISPLAY CONTROL MODULE


SYSTEM 2003A-1
4. Functional Description
In the following description only Groin 'A' Inputs 1 to 4 FUSE FAILURE
are discussed. Reference to Section 5 Input/Output
Definitions will enable the reader to apply the description The module fuse failure will be indicated by the
to Group 'B' and the other four inputs. module fault LED being illuminated steady .

ALARM

When a 24V do steady signal ::.is,~:applied=~kca, :InpuL :1A-A


(Terminal 1) a flashing 24V dc/high~impedance..(Hi/HiZ):is:s- .~~ ~...:.,; .~ ~,..,,...
output on 1A (Terminal 6) and also on the 'F' reflash
output (Terminal 10). The front panel LED IA will flash
and the 'A' LED will flash in antiphase.

Whew the module is accepted, via the facilities module, all


active LEDs will illuminate steady and the flashing outputs
will give a steady 24V do output .

Should a second alarm become active on Group 'A', e.g


Input 2 (Terminal 2), the output 2A (Terminal 'n will flash
24V dc/HiZ and the Group 'A' output Terminal 1p
(previously steady from accepted alarm IA) will reflash.

The front panel LED 2A will flash (the alarm LED IA


remaining steady) and the Group 'A' LED will flash in
antipUase to the LED 2A .
This sequence continues for all four inputs in the group.

The group reflash outputs can be cascaded by linking the -.


reflash output of one group to the R/F carry input of
another group. This enables one output to flash for more
than four steady inputs . This will be indicated by the input
alarm LED and all affected group front panel LEDs .

All inputs are non latching and .an ,alarm .will,- .via_~ the , . . .,
facilities module, generate a common. alarm .and -alarm _ _
sounder outputs.

FAULT MONITORING

Should a monitored input line become open circuit the


relevant LED will illuminate yellow immediately, and a
signal will, via the facilities module, give a common fault
and fault sounder output. Acceptance of the fault will
cause the fault sounder to cancel .

All fault monitoring indications and outputs are non


latching .

Park Works 3A-1-5145-A-AUG'91


All Information Is subject to -;henge without notice.
Newton Heath
Manchester
M106BA

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex. 668618
LINE M NITORS 0 V

. ;:. ¢ "IVL 8
INPUT AA 1J~, ~~. . . . _ a. . .N OUTPUT 1A
H

INPUT ' 2A O-
2 r-~ N ' ~ ~lll 7 OUTPUT 2A

INPUT 3A 3~ ~ .. d ~ ~ Jln 8 OUTPUT 3A

(L 4 ~ g
p INPUT 4A O-J[_.- & F-N V -- UTPUT A

II I i I ~. a 6 W-' O RE-FLASH'A'

RJF CARRY U---I _ ~-f- COMMON ALARM


/~.i L COMMON ALARM SOUNDER
z z -
FLASH O O ACCEPT
DETECTION FUSE FAIL
U
CIRCUITRY O z FLASH SYNC
COMMON FAULT
RJF CARRY ~ 5 ~--~- COMMON FAULT SOUNDER

W20
& ---0 RE-FLASH'B'
11 r
-- NL
16
._ju cc
INPUT 18 ,~~~l- _ ~ OUTPUT 18

1 2f y' N ~ X1 7
INPUT 2B0-{- - U OUTPUT 2B
1 3-F L~ N X1 8
INPUT 3Bp-{ _ ~ W -0 OUTPUT 3B

INPUT 4810-~ ~ 1--N ¢ jltL-p OUTPUT 4B

OV

'"me on s su oct to mge wi out no ce .


Newton Heath
Manchester
11 10 6E3A

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex. 66861 8
DATA SHEET
01-23-05

SYSTE M 2003A-1 DISPLAY CONTROL MODULE

5 . Input/Output Definitions

Screw Signal States Sy s tem Put or


Signal Name Test
Terminal Active Output
Quiesc ent Activated Accepted

1 Input 1 A HiZ Hi To Alarm


2 Input 2q HiZ Hi To Alarm IlP
Input 3 A H i Z Hi To Alarm

4 Input 4 A Hi Z Hi To Alarm
Re f 1 as h 'A' Hi Z Flashing To Alarm
6 Output 1 A HiZ Flashing Hi pip
7 Output 2A HiZ Flashing Hi U/P
8 Output 3A H iZ Flashing Hi O/P
9 Output 4q HiZ Flashing Hi pip
i o Output Group ' A' HiZ Flashing Hi O/P
Input 1 B H iZ Hi To Alarm Il
1 2 Input 2 B HiZ Hi To Alarm I/ P
1 3 Input 3B HiZ Hi To Alarm I/P
1 4 Input 4B Hi Z Hi To Alarm I/ P
1 5 Re f 1ash '13' H iZ Flashing To Alarm I/ P
16 Output 1 g HiZ Flashing Hi o/P
1 7 output 2 B Hi Z Flashing Hi ()/
1g Output 3B HiZ Flashing Hi o(P
19 Output 4B H iZ Flashing Hi 0/P
20 Output Group 'B' H iZ Flashing Hi ()/P

KEY

HIZ a High Impedance


Hi - 2a v DC
Fl a sh i n g g High Impedance +24 V do

Park Works All Information is sabJect to dimge wlthou[ notice . 3A-1-514-7-A-AU G' 91
Newton Heath
Manchester
M 10 bBA

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex . 668618
DATA SHEET

IF# WORMALD 01-23-05

6. Installation and Setting Up Instructions

Link 1 (LK 1)

FAULT MONITORING ENABLE


If the link is fitted all eight inpuLlinesaremonitored,for-opeu -circuit andhwill individually indicate yellow on
the front panel . Without the linlaall line-monitoring..is disabled and.the:front panel will only indicate alarms .

FUSE (FS 1)

FS 1 Fuse 5(?OmA 20nini x Smm Quick Blow (F).

Parle~iYelb_ . . . , . . .. ,. .. o a on s a e o mgc w at ¢ot cc .


Newton Heath
Manchester
Ml06BA

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex . 66861 8
DATA SHEET
01-23-05'

DISPLAY CONTROL MODULE


SYSTE M 2003A-1

7. APPLICATION INSTRUCTIONS

7 .1 Schematic Cell

D1SPiAY "~~~° -,CONTRO L .


GROUP A

0 1 J INPUT 1A OUT'PUT to ~r 08

0 2 1 INPUT 2A OUTPUT 2A 07

0 3 f INPUT 3A OUTPUT 3A N 0 8

04 f INPUT 4A OUTPUT 4A X 09

00 5 in HEFLASH UP GRAUP'A' CV PN 1 0

GROUP B

1 1 f INPUT 1B OUTPUT 1B N 1 8

1 2 f INPUT 2B OUTPUT 2B N 1 7

1 3 f INPUT 3B OUTPUT 38 N 1 8

1 4 f INPUT 40 OUTPUT 48 N 1 9

1 5 M REFLASH VP GROUP-B' QPK 20

7 .2 Output Circuit

All outputs are open collector active high .

Current sourcing 200 mA .

Total maximum module source current 200 mA .

MODULE FUSED + 24V do

ofP

Park Works All intormetlm Is subject to chsnge wlthaut notice. 3A-1-5149-A-AU G' 91
Newton Heath
Manchester
M106BA

Tel . (061) 205 2321


Fax . (061) 205 8028
Telex . 66861 8
DATA SHEET
WORMALD 01-23-OS

-D SPLAY COb OD ULE


SYSTEM 2003A-1

7 . APPLICATION INSTRUCTIONS

7.3 Driving Single Output from Multiple Inputs

LED will flash on any input alarm, steady when accepted and reflash if another input becomes active.

7 .4 Volt-Free Contact Device


2av ac

A
5k8

Q INPUT TO DISPLAY
CONTROL MODULE

.~_ . _ _ .
All Inforwetlw Is subject to change without notice . -1-51410-A-AUG'91
Newton Heath
Manchester
N 10 6BA

Tel.. (061) 205 2321


Fax. (061) 205 8028
Telex. 668618