Iskra mt174 Manual
Iskra mt174 Manual
Iskra mt174 Manual
MT174
Three-Phase Static Electricity
Multi Tariff Meter
with Maximum Demand Indicator
and Load-profile
The 85 A terminal blocks has only one screw per current terminal, while 120 A terminal blocks has
two screws per current terminal. Due to indirect pressure to the conductors the terminal screws do not
damage it. The current terminals make a reliable and durable contact regardless if the conductor is made of
copper or aluminium.
Voltage metering elements are power supplied via potential links. Sliding potential links are self- braking and
enable easy disconnection of current and voltage metering circuitry. In the metering mode they should be
in their lowest position (closed contact), and in the meter testing mode they should be in their highest
position (opened contact). On request, the potential links can be located under the meter cover.
1
3
1
2
Potential links in the terminal block of direct connect meters for Imax = 120A
Terminal block for CT operated meters
The CT operated meters have separate voltage terminals (Fig. 5, item 2) in the terminal block. They are
used for supplying the voltage metering circuitry. The voltage terminals are equal to the current
terminals (Fig. 5, item 1). The current and
voltage terminals are made of solid brass with a 5 mm bore diameter; the conductors are fixed in the
terminals with two screws.
1 3
2
Auxiliary Terminals
Up to six auxiliary terminals can be built in a terminal block. They are used for tariff inputs, impulse
outputs or tariff outputs or RS485 interface. Due to a limited number of auxiliary terminals, all stated inputs
and outputs as well as the interface can not be built in the meter at the same time. The bore diameter of the
auxiliary terminals is 3.5 mm. Wires are fixed with a screw. Three auxiliary voltage terminals for power
supply of an external device can be also built-in. The auxiliary terminals are nickel-plated at a tropical
meter version.
The meter connection diagram is stuck on the inner side of the terminal block cover or is printed on the
meter nameplate. The meters can be connected in three-phase four- or three-wire networks, as well as in a
single-phase two-wire network.
1. Check if voltage and maximum current printed on the meter name plate correspond to the voltage on the
network and to the current which will flow through the meter.
3. Connect the meter in compliance with the connection diagram which is stuck in the inner side of the terminal
cover (or printed on the meter name plate).
4. Tighten the terminal screws with appropriate torque. The recommended torque for tightening current terminal
screws is 2.5 Nm.
• kWh/imp (kvarh/imp) LED is lit (load current is smaller than the meter starting current)
• kWh/imp (kvarh/imp) LED is blinking with frequency that is proportional to the measured demand
(the meter measures and registers energy)
• kWh/imp (kvarh/imp) LED is not lit (the meter is in no-power state). In this case the following should be
checked:
a) At directly connected meters: voltage links in lower position (if not, the voltage
links slides should be moved to their lower position)
b) Connected current conductors to the meter (if not, they should be connected)
c) If both above conditions are fulfilled, it means that there is no voltage in the
network. If there is a voltage in the network, something is wrong with the
meter. In such a case the meter should be replaced.
6. Check the L1, L2 and L3 indicators on the LCD if current conductors are connected correctly:
• Some of the L1 L2 L3 indicators are not displayed (voltage in these phases is not
present). Check if current conductors of these phases are connected and/or their voltage links are in
the bottom position (at direct connected meters) or find the reason for the phase voltage absence and
eliminate it.
• Some of the L1 L2 L3 indicators are blinking and at the same time import energy indicator is displayed
indicating that current through that metering element is reversed. In such a case change the input and
the output of the corresponding current terminals.
• L1 L2 L3 indicators are blinking – reversed phase sequence that causes rotation of magnetic field in
reversed direction. In this case check current conductors sequence in the meter or find the place of
reversed voltage phase sequence and connect them correctly.
Note: Reversed phase sequence does not influence in energy measurement accuracy
7. Check if alarm flags are displayed on the LCD and delete them. If necessary, remove a cause that they are
displayed.
8. Check RTC date and time and correct them, if necessary.
9. Perform a meter billing reset (press the orange pushbutton)
10. Seal the meter (the terminal cover and the orange pushbutton cover).
LCD
The 7-segment LCD, with additional characters and symbols, complies with the VDEW specifications. Large
characters and a wide angle view enable easy data reading. The LCD back-light illumination is available
on request. The LCD is illuminated by short (Tp < 2 s) pressing the blue pushbutton. On request the back-light is
turned-on all the time.
LCD
Data are displayed in the right-side by means of eight alphanumeric characters. The size of data characters is 8
mm high and 4 mm width. The OBIS code (by IEC 62056-61), without the first two characters from the left side,
is employed for data identification. It is displayed in the left side corner by means of five 6 mm high
alphanumeric characters.
A physical unit of displayed physical quantity is shown in the right top corner. The indicator of L1, L2, L3
phase voltages presence is displayed in the middle of the top row. If certain phase voltage is not present, the
indicator of that phase is not displayed.
When the indicators L1L2L3 blink, this indicates wrong phase sequence.
When the indicator L1, L2 or L3 blinks and at the same time the arrow ← indicating export energy flow direction
is displayed, it indicates reverse energy flow through the metering element in that phase. In the LCD bottom
row there are eleven signal flags that indicate current valid tariff, meter status and alarms. The meaning of
signal flags (see item 2.5.3) is engraved on the meter name plate below them.
DATA DISPLAY
Data defined in Auto scroll sequence and in Manual scroll sequence are displayed on the LCD.
Data from Auto scroll sequence are displayed in a circle, and each data is displayed for 8 seconds as a
standard (default) display time.
At Manual scroll sequence the blue push-button should be pressed for displaying the next piece of data. Data in
Manual scroll sequence remains displayed until the push-button is pressed again or until time for automatic
return into the Auto scroll sequence is elapsed.
The signal flags in the LCD bottom row indicate certain meter status and alarms. They are grouped into three
groups:
• actual tariff (first four flags on the left side)
• alarms (four flags in the middle)
• meter status (last three flags on the right side)
The MT174 meters enable indication of many different alarms but only four of them can be displayed on the
LCD. If more than four alarms are to be indicated on the LCD, one signal flag can be used for two different
alarms (e.g. one signal flag for both the meter cover and the terminal cover opening)
The signal flags from left to right have the following functions:
LEDs
The meters for active energy only are provided with a LED (imp/kWh). The meters for active and reactive
energy are provided with two LEDs (imp/kWh and imp/kvarh). The meters for active, reactive and
apparent energy are provided with three LEDs (imp/kWh, imp/kVAh and imp/kvarh). The LED(s) are
used for testing the meter accuracy and indicating meter operation. If current throughthe meter is smaller
than the meter starting current, the LEDs (or a LED) are (is) permanently lit.
In the meter test mode pulse rate is increased to 40.000 imp/kWh (kVAh/imp and kvarh/imp) in order to
shorten time needed for testing the meters at low loads.
3 2 1 3 1
RESET - an orange pushbutton under the hinged door that is fixed to the meter cover
Its primary function is to perform manual billing reset of the meter.
DATA SCROLL - a blue pushbutton that is always accessible. Its primary function is to display data from the
Manual sequence on request
At the orange pushbutton the time duration of pressing does not influence to its function, while at the blue
pushbutton there are three different time durations of pressing - each of them causing different effect:
a. Short - pressing shorter than 2 sec. - the next data in the menu is displayed.
b. Long - pressing longer than 2 sec. and shorter than 5 sec. - a submenu or a function whose name
is displayed on the LCD is selected.
c. Prolonged - pressing longer than 5 sec.
- the meter is returned up for one level of operation (e.g. on the third level it is necessary to press
the blue pushbutton
three times and always keep it pressed for
more than 5 sec. in order to return to the automatic data display mode).
DISPLAY TESTING
A display is tested to check if all its segments function properly. In the automatic data display the blue
pushbutton should be pressed for a short time (Tp < 2 s). The display is tested for 10 seconds and all its
segments are displayed. After 10 seconds the meter returns to automatic data display mode automatically.
MANUAL DATA DISPLAY
Data are displayed on request as follows. The meter is set to the display testing mode. During the LCD test,
the blue pushbutton is pressed for a short time (Tp <2 s). The Std dAtA title is displayed. In this way a menu
for selecting data display on request is entered.
In order to enter into the data display on request menu, the blue pushbutton should be pressed for a long time
(2 s < Tp < 5 s). The first data from the Manual scroll list is displayed on the LCD. For displaying the following
data from the Manual scroll list (see below), the blue pushbutton should be pressed for a short time again.
If the blue pushbutton has not been pressed for some time, the meter automatically returns back into the Auto
scroll mode.
The exit from the Manual data display mode is performed by prolonged pressing the blue push- button
(Tp > 5 s).
One pulse output (active energy meters for one energy flow direction or absolute meters) or two pulse
outputs (active and reactive energy meter for one energy flow direction or active energy meters for two
energy flow directions) can be built into the MT174 meters.
Note: Pulse output(s) are not available, if the meter is equipped with tariff output(s).
Note: Besides the 41 terminal either the 42 or the 43 auxiliary terminal can be used.
The pulse output is passive and complies with the IEC 62053-32 standard, class A (S0 in compliance with DIN
43864). The pulse constant is equal to the half value of the meter constant and the standard pulse width is 40
ms. However, a smaller pulse constant or a larger pulse length can be set on request. The class A
pulses can be transferred to
0.5 m distance.
The pulse output(s) can be performed as an opto- mos relay with a make contact that can changeover
25 W (100 mA, 250 V) on request. In this case pulse transmission at a distance of 1 km is made
possible. The pulse constant is equal to one tenth
of the meter constant and the standard pulse width is 100 ms. However, a smaller pulse constant or other
pulse lengths can be set on request.
Optional pulse widths are: 10 ms, 20 ms, 30 ms, 40 ms, 50 ms, 60 ms, 80 ms and 100 ms. The default pulse
width is 40 ms at class A pulse output and
100 ms at optomos relay pulse outputs.
Optional pulse constants at direct connected meters are: 1.000 pls/kWh, 500 pls/kWh, 250 pls/kWh, 200
pls/kWh, 100 pls/kWh, 50 pls/kWh, 25 pls/kWh, 20 pls/kWh and 10 pls/kWh
The default pulse constants depending on the pulse output type and the meter Imax current is given in the table
below
Default output
pulse constant Warning:
Pulse (pls/kWh) Imax = When other than default pulse width and pulse
output Imax constant are required, attention should be paid that
up to 100 A the selected values do not cause overlapping of the
Class A 85
50 or25 pulses at maximum load.
(S0) A0 120 0
Optomo 10 A50
s relay 0
The pulse outputs can be dedicated to any energy which is measured.
MT174 METER IN PHOTOVOLTAIC (PV) INSTALLATIONS