Deep Sea Electronics PLC: DSE8660 Operator Manual
Deep Sea Electronics PLC: DSE8660 Operator Manual
Deep Sea Electronics PLC: DSE8660 Operator Manual
E-mail: [email protected]
Website: www.deepseaplc.com
Any reference to trademarked product names used within this publication is owned by their respective companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice.
Indicates a procedure or practice, which, if not strictly observed, could result in damage or
CAUTION! destruction of equipment.
Indicates a procedure or practice, which could result in injury to personnel or loss of life if not
WARNING! followed correctly.
TABLE OF CONTENTS
Section Page
1 BIBLIOGRAPHY .............................................................................................. 6
1.1 INSTALLATION INSTRUCTIONS ....................................................................................... 6
1.2 TRAINING GUIDES ............................................................................................................. 6
1.3 MANUALS............................................................................................................................ 6
2 INTRODUCTION .............................................................................................. 7
3 SPECIFICATIONS ............................................................................................ 8
3.1 TERMINAL SPECIFICATION .............................................................................................. 8
3.2 POWER SUPPLY REQUIREMENTS .................................................................................. 8
3.3 GENERATOR BUS AND MAINS VOLTAGE / FREQUENCY SENSING ........................... 8
3.4 MAINS AND LOAD CURRENT SENSING .......................................................................... 9
3.5 INPUTS ................................................................................................................................ 9
3.5.1 DIGITAL INPUTS .......................................................................................................... 9
3.6 OUTPUTS .......................................................................................................................... 10
3.6.1 OUTPUTS A & B ......................................................................................................... 10
3.6.2 OUTPUTS C & D ........................................................................................................ 10
3.6.3 OUTPUTS E,F,G,H,I & J ............................................................................................. 10
3.7 COMMUNICATION PORTS .............................................................................................. 11
3.7.1 USB CONNECTION ................................................................................................... 12
3.7.2 USB HOST-MASTER (USB DRIVE CONNECTION) ................................................. 12
3.7.3 RS232 ......................................................................................................................... 13
3.7.4 RS485 ......................................................................................................................... 15
3.7.5 ETHERNET ................................................................................................................. 16
3.7.5.1 DIRECT PC CONNECTION ................................................................................................................. 16
3.7.5.2 CONNECTION TO BASIC ETHERNET ................................................................................................ 17
3.7.5.3 CONNECTION TO COMPANY INFRASTRUCTURE ETHERNET ....................................................... 18
3.7.5.4 CONNECTION TO THE INTERNET ..................................................................................................... 19
3.8 DSENET® FOR EXPANSION MODULES ....................................................................... 22
3.9 SOUNDER ......................................................................................................................... 23
3.9.1 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION .................................. 23
3.10 DIMENSIONS AND MOUNTING ................................................................................... 24
3.10.1 DIMENSIONS ............................................................................................................. 24
3.10.2 CABLE TIE FIXING POINTS ...................................................................................... 26
3.10.3 SILICON SEALING GASKET...................................................................................... 26
3.11 APPLICABLE STANDARDS.......................................................................................... 27
3.11.1 ENCLOSURE CLASSIFICATIONS ............................................................................. 28
4 INSTALLATION .............................................................................................. 30
4.1 TERMINAL DESCRIPTION ............................................................................................... 30
4.1.1 DC SUPPLY, FUEL AND START OUTPUTS ............................................................. 30
4.1.2 MAGNETIC PICKUP, CAN AND EXPANSION .......................................................... 31
4.1.3 LOAD SWITCHING AND MAINS VOLTAGE SENSING (V1) .................................... 32
4.1.4 GENERATOR BUS VOLTAGE SENSING (V2) .......................................................... 32
4.1.5 MAINS CURRENT TRANSFORMERS ....................................................................... 33
4.1.1 LOAD CURRENT TRANSFORMER ........................................................................... 34
4.1.1.1 ADVANTAGES OF LOAD CT ............................................................................................................... 34
4.1.2 CONFIGURABLE DIGITAL INPUTS .......................................................................... 35
4.1.3 PC CONFIGURATION INTERFACE CONNECTOR .................................................. 35
4.1.4 RS485 CONNECTOR ................................................................................................. 36
4.1.5 RS232 CONNECTOR ................................................................................................. 36
4.2 TYPICAL WIRING DIAGRAMS ......................................................................................... 37
4.2.1 3 PHASE, 4 WIRE ...................................................................................................... 38
4.2.2 SINGLE MAINS, MULTIPLE GENERATORS ............................................................. 39
4.2.3 DUAL MAINS, MULTIPLE GENERATORS ................................................................ 40
4.2.4 MULTIPLE MAINS, MULTIPLE GENERATORS ........................................................ 41
4.2.5 DSENET® ................................................................................................................... 42
4.2.6 EARTH SYSTEMS ...................................................................................................... 43
1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained from the DSE
website www.deepseaplc.com
1.3 MANUALS
2 INTRODUCTION
This document details the installation and operation requirements of the DSE8660 modules, part of the DSEPower®
range of products.
The manual forms part of the product and should be kept for the entire life of the product. If the product is passed or
supplied to another party, ensure that this document is passed to them for reference purposes.
This is not a controlled document. You will not be automatically informed of updates. Any future updates of this
document will be included on the DSE website at www.deepseaplc.com
The DSE8600 series is designed to provide differing levels of functionality across a common platform. This allows
the generator OEM greater flexibility in the choice of controller to use for a specific application.
The DSE8660 module has been designed to monitor the mains (utility) supply and automatically start/stop one ore
more generator sets equipped with DSE8610 controllers depending upon the status of the mains (utility) supply.
Synchronising and Load Sharing features are included within the controller, along with the necessary protections for
such a system. This provides forward sync, back sync (no break changeover) and start/stop upon changing load
levels.
The user also has the facility to view the system operating parameters via the LCD display.
The powerful ARM microprocessor contained within the module allows for incorporation of a range of complex
features:
Using a PC and the Configuration Suite software allows alteration of selected operational sequences, timers and
alarms.
Additionally, the module’s integral fascia configuration editor allows adjustment of a subset of this information.
A robust plastic case designed for front panel mounting houses the module. Connections are via locking plug and
sockets.
3 SPECIFICATIONS
3.1 TERMINAL SPECIFICATION
Connection type Two part connector.
• Male part fitted to module
• Female part supplied in module
packing case - Screw terminal,
rising clamp, no internal spring. Example showing cable entry and screw
Minimum cable size 0.5mm² (AWG 24) terminals of a 10 way connector
Maximum cable size 2.5mm² (AWG 10)
NOTE: For purchasing additional connector plugs from DSE, please see the section entitled
Maintenance, Spares, Repair and Servicing elsewhere in this document.
This is achieved without the need for internal batteries or other external
requirements.
Maximum supply voltage 35V continuous (60V protection for surges)
Reverse polarity protection -35V continuous
Maximum operating current 400mA at 24V
(all inputs and outputs on) 200mA at 12V
Maximum standby current 110mA at 24V
(all inputs and outputs off) 210mA at 12V
3.5 INPUTS
Number 11
Arrangement Contact between terminal and ground
Low level threshold 2.1V minimum
High level threshold 6.6V maximum
Maximum input voltage +50V DC with respect to plant supply negative
Minimum input voltage -24V DC with respect to plant supply negative
Contact wetting current 7mA typical
Open circuit voltage 12V typical
3.6 OUTPUTS
Type Voltage free relays, fully configurable, normally used for generator bus / mains load switch control.
Rating 8A resistive @ 250 V AC
10
11
The USB port is provided to give a simple means of connection between a PC and the DSE8660 series controller.
Using the DSE Configuration Suite Software, the operator is then able to control the module, starting or stopping the
generator(s), selecting operating modes, etc.
Additionally, the various operating parameters (such as output volts, oil pressure, etc.) of the remote generator(s)
are available to be viewed or changed.
To connect a DSE8600 series module to a PC by USB, the following items are required:
NOTE: - The DC supply must be connected to the module for configuration by PC.
NOTE: - Refer to DSE8600 series Configuration Suite Manual (DSE part 057-119) for further details on
configuring, monitoring and control.
Capability to add USB Host facility for USB ‘Pendrive’ type interface for data recording
Connector Type A.
For data logging max maximum size 16Gb.(see viewing the instrument pages)
NOTE:- Refer to DSE8600 series Configuration Suite Manual (DSE part 057-119) for further details on
configuring, monitoring and control.
12
3.7.3 RS232
The RS232 port on the DSE8600 series controller supports the Modbus RTU protocol.
The Gencomm register table for the controller is available upon request from the DSE Technical Support
Department.
RS232 is for short distance communication (max 15m) and is typically used to connect the DSE86xx series
controller to a telephone or GSM modem for more remote communications.
Many PCs are not fitted with an internal RS232 serial port. DSE DOES NOT recommends the use of USB to RS232
convertors but can recommend PC add-ons to provide the computer with an RS232 port.
Recommended PC Serial Port add-ons (for computers without internal RS232 port):
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
• Brainboxes VX-001 Express Card RS232 (for laptops and nettops PCs)
• Brainboxes PX-246 PCI Express 1 Port RS232 1 x 9 Pin (for desktop PCs)
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales:[email protected]
NB DSE Have no business tie to Brainboxes. Over many years, our own engineers have used these products and
are happy to recommend them.
13
• Wavecom Fastrak Supreme GSM modem kit (PSU, Antenna and modem)*
DSE Part number 0830-001-01
NOTE: *For GSM modems, a SIM card is required, supplied by your GSM network provider:
• For SMS only, a ‘normal’ voice SIM card is required. This enables the controller to send SMS messages to
designated mobile phones upon status and alarm conditions.
• For a data connection to a PC running DSE Configuration Suite Software, a ‘special’ CSD (Circuit Switched
Data) SIM card is required that will enable the modem to answer an incoming data call. Many ‘pay as you
go’ services will not provide a CSD (Circuit Switched Data) SIM card.
14
3.7.4 RS485
The RS485 port on the DSE8600 series controller supports the Modbus RTU protocol.
The DSE Gencomm register table for the controller is available upon request from the DSE Technical Support
Department.
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices) and allows for
connection to PCs, PLCs and Building Management Systems (to name just a few devices).
One advantage of the RS485 interface is the large distance specification (1.2km when using Belden 9841 (or
equivalent) cable). This allows for a large distance between the DSE8600 series module and a PC running the DSE
Configuration Suite software. The operator is then able to control the module, starting or stopping the generator(s),
selecting operating modes, etc.
The various operating parameters (such as output volts, oil pressure, etc.) of the remote generator(s) can be
viewed or changed.
NOTE: - For a single module to PC connection and distances up to 6m (8yds), the USB connection
method is more suitable and provides for a lower cost alternative to RS485 (which is more suited to longer
distance connections).
Recommended PC Serial Port add-ons (for computers without internal RS485 port).
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
• Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and nettop PCs)
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales:[email protected]
NB DSE Have no business tie to Brainboxes. Over many years, our own engineers have used these products and
are happy to recommend them.
15
3.7.5 ETHERNET
The DSE8660 is fitted with ETHERNET socket for connection to LAN (local area networks)
Description
1 TX+
2 TX-
3 RX+
4 Do not connect
5 Do not connect
6 RX-
7 Do not connect
8 Do not connect
Requirements
• DSE8660
• Crossover Ethernet cable (see Below)
• PC with Ethernet port
Crossover
network cable
16
Requirements
• DSE8660
• Ethernet cable (see below)
• Working Ethernet (company or home network)
• PC with Ethernet port
Ethernet cable
Ethernet router
or ADSL router
17
NOTE:- DSE Stock a 2m (2.2yds) Ethernet Cable – Part number 016-137. Alternatively they can be
purchased from any good PC or IT store.
Requirements
• DSE8660
• Ethernet cable (see below)
• Working Ethernet (company or home network)
• PC with Ethernet port and Windows Internet Explorer 6 or above, Firefox
18
NOTE:- DSE Stock a 2m (2.2yds) Ethernet Cable – Part number 016-137. Alternatively they can be
purchased from any good PC or IT store.
DSL or ADSL
router
INTERNET Ethernet cable
The DSL/ADSL
router will route
external
DSL or ADSL
router Optional ‘Local’
site PC
PC remote
from generator
site
19
10baseT/100baseT
Pin Connection 1 (T568A) Connection 2 (T568A)
white/green stripe white/green stripe For the advanced
1
Engineer, this cable
2 green solid green solid has both ends
terminated as
3 white/orange stripe white/orange stripe T568A (as shown
below) or T568B.
4 blue solid blue solid
NOTE:- DSE Stock a 2m (2.2yds) Ethernet Cable – Part number 016-137. Alternatively they can be
purchased from any good PC or IT store.
20
As modem/routers differ enormously in their configuration, it is not possible for DSE to give a complete guide to
their use with the DSE8660. However it is possible to give a description of the requirements in generic terms. For
details of how to achieve the connection to your modem/router you are referred to the supplier of your
modem/router equipment.
The DSE8660 makes its data available over Modbus TCP and as such communicates over the Ethernet using a
Port configured via the DSE config suite software..
You must configure your modem/router to allow inbound traffic on this port. For more information you are referred to
your WAN interface device (modem/router) manufacturer.
It is also important to note that if the port assigned (setting from software “Modbus Port Number”) is already in use
on the LAN, the DSE8660 cannot be used and another port must be used .
As the DSE8660 makes its user interface available to standard web browsers, all communication uses the chosen
port. It is usual for a firewall to make the same port outgoing open for communication.
Network Address and Port Translation (NAPT) allows a single device, such as the modem/router gateway, to act as
an agent between the Internet (or "public external network") and a local (or "internal private") network. This means
that only a single, unique IP address is required to represent an entire group of computers.
For our DSE8660 application, this means that the WAN IP address of the modem/router is the IP address we need
to access the site from an external (internet) location.
When requests reaches the modem/router, we want this passed to a ‘virtual server’ for handling, in our case this is
the DSE8660 module.
Result : Traffic arriving from the WAN (internet) on port xxx is automatically sent to IP address set within the
configuration software on the LAN (DSE8660) for handling.
NOTE:- Refer to DSE8600 series Configuration Suite Manual (DSE part 057-119) for further details on
configuring, monitoring and control.
21
NOTE: As a termination resistor is internally fitted to the host controller, the host controller must be
the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to the ‘last’ unit on the DSENet®. For
connection details, you are referred to the section entitled ‘typical wiring diagram’ elsewhere in this
document.
22
3.9 SOUNDER
DSE8600 Series features an internal sounder to draw attention to warning, shutdown and electrical trip alarms.
Should an external alarm or indicator be required, this can be achieved by using the DSE Configuration Suite PC
software to configure an auxiliary output for Audible Alarm, and by configuring an auxiliary input for Alarm Mute (if
required).
The audible alarm output activates and de-activates at the same time as the module’s internal sounder. The Alarm
mute input and internal alarm mute button activate ‘in parallel’ with each other. Either signal will mute both the
internal sounder and audible alarm output.
Example of configuration to achieve external sounder with external alarm mute button:
23
3.10.1 DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
PANEL CUTOUT
220mm x 160mm (8.7” x 6.3”)
WEIGHT
0.7kg (1.4lb)
24
FIXING CLIPS
Supplied fixing clips hold the module into the panel fascia.
Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip.
• Insert the three ‘prongs’ of the fixing clip into the slots in the side of the 8600 series module case.
• Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip are
inside their allotted slots.
• Turn the fixing clip screws clockwise until they make contact with the panel fascia.
• Turn the screws a little more to secure the module into the panel fascia. Take care not to over tighten the
fixing clip screws.
Fixing clip
NOTE: In conditions of excessive vibration, mount the module on suitable anti-vibration mountings.
25
Integral cable tie fixing points are included on the rear of the module’s case to aid wiring. This additionally provides
strain relief to the cable loom by removing the weight of the loom from the screw connectors, thus reducing the
chance of future connection failures.
Care should be taken not to overtighten the cable tie (for instance with cable tie tools) to prevent the risk of damage
to the module case.
The supplied silicon gasket provides improved sealing between the 8600 series module and the panel fascia.
The gasket is fitted to the module before installation into the panel fascia.
Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal.
Sealing gasket
Gasket fitted to
module
26
BS 4884-1 This document conforms to BS4884-1 1992 Specification for presentation of essential
information.
BS 4884-2 This document conforms to BS4884-2 1993 Guide to content
BS 4884-3 This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068-2-1
-30°C (-22°F)
(Minimum temperature)
BS EN 60068-2-2
+70°C (158°F)
(Maximum temperature)
BS EN 60950 Safety of information technology equipment, including electrical business equipment
BS EN 61000-6-2 EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4 EMC Generic Emission Standard (Industrial)
BS EN 60529 IP65 (front of module when installed into the control panel with the supplied sealing
(Degrees of protection gasket)
provided by enclosures) IP42 (front of module when installed into the control panel WITHOUT being sealed to
(see overleaf) the panel)
UL508 12 (Front of module when installed into the control panel with the supplied sealing
NEMA rating gasket).
(Approximate) 2 (Front of module when installed into the control panel WITHOUT being sealed to
(see overleaf) the panel)
IEEE C37.2 Under the scope of IEEE 37.2, function numbers can also be used to represent
(Standard Electrical Power functions in microprocessor devices and software programs.
System Device Function The 8600 series controller is device number 11L-8600 (Multifunction device
Numbers and Contact protecting Line (mains) – 8600 series module).
Designations)
As the module is configurable by the generator OEM, the functions covered by the
module will vary. Under the module’s factory configuration, the device numbers
included within the module are :
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
27
IP CLASSIFICATIONS
IP65 (Front of module when module is installed into the control panel with the optional sealing gasket).
IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
0 No protection 0 No protection
1 Protected against ingress solid objects with a 1 Protection against dripping water falling vertically. No
diameter of more than 50 mm. No protection against harmful effect must be produced (vertically falling
deliberate access, e.g. with a hand, but large drops).
surfaces of the body are prevented from approach.
2 Protected against penetration by solid objects with a 2 Protection against dripping water falling vertically.
diameter of more than 12 mm. Fingers or similar There must be no harmful effect when the equipment
objects prevented from approach. (enclosure) is tilted at an angle up to 15° from its
normal position (drops falling at an angle).
3 Protected against ingress of solid objects with a 3 Protection against water falling at any angle up to 60°
diameter of more than 2.5 mm. Tools, wires etc. from the vertical. There must be no harmful effect
with a thickness of more than 2.5 mm are prevented (spray water).
from approach.
4 Protected against ingress of solid objects with a 4 Protection against water splashed against the
diameter of more than 1 mm. Tools, wires etc. with equipment (enclosure) from any direction. There must
a thickness of more than 1 mm are prevented from be no harmful effect (splashing water).
approach.
5 Protected against harmful dust deposits. Ingress of 5 Protection against water projected from a nozzle
dust is not totally prevented but the dust must not against the equipment (enclosure) from any direction.
enter in sufficient quantity to interface with There must be no harmful effect (water jet).
satisfactory operation of the equipment. Complete
protection against contact.
6 Protection against ingress of dust (dust tight). 6 Protection against heavy seas or powerful water jets.
Complete protection against contact. Water must not enter the equipment (enclosure) in
harmful quantities (splashing over).
28
NEMA CLASSIFICATIONS
12 (Front of module when module is installed into the control panel with the optional sealing gasket).
2 (front of module when module is installed into the control panel WITHOUT being sealed to the panel)
NOTE: - There is no direct equivalence between IP / NEMA ratings. IP figures shown are approximate
only.
1 Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.
IP30
2 Provides a degree of protection against limited amounts of falling water and dirt.
IP31
3 Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure.
IP64
3R Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure.
IP32
4 (X) Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the
formation of ice on the enclosure. (Resist corrosion).
IP66
12/12K Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.
IP65
13 Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants.
IP65
29
4 INSTALLATION
The DSE8600 Series module is designed to be mounted on the panel fascia. For dimension and mounting details,
see the section entitled Specification, Dimension and mounting elsewhere in this document.
4 Not Connected
5 Not Connected
6 Not Connected
2.5mm²
7 Functional Earth Connect to a good clean earth point.
AWG 13
1.0mm²
8 Output relay E Plant Supply Positive from terminal 2. 3 Amp rated.
AWG 18
1.0mm²
9 Output relay F Plant Supply Positive from terminal 2. 3 Amp rated.
AWG 18
1.0mm²
10 Output relay G Plant Supply Positive. from terminal 2. 3 Amp rated.
AWG 18
1.0mm²
11 Output relay H Plant Supply Positive from terminal 2. 3 Amp rated.
AWG 18
1.0mm²
12 Output relay I Plant Supply Positive from terminal 2. 3 Amp rated.
AWG 18
1.0mm²
13 Output relay J Plant Supply Positive from terminal 2. 3 Amp rated.
AWG 18
30
23 Not Connected
24 Not Connected
25 Not Connected
26 Not Connected
27 Not Connected
0.5mm²
28 DSENet expansion + Use only 120Ω RS485 approved cable
AWG 20
0.5mm²
29 DSENet expansion - Use only 120Ω RS485 approved cable
AWG 20
0.5mm²
30 DSENet expansion SCR Use only 120Ω RS485 approved cable
AWG 20
0.5mm²
31 MultiSet Comms (MSC) Link H Use only 120Ω RS485 approved cable
AWG 20
0.5mm²
MSC 32 MultiSet Comms (MSC) Link L Use only 120Ω RS485 approved cable
AWG 20
0.5mm²
33 MultiSet Comms (MSC) Link SCR Use only 120Ω RS485 approved cable
AWG 20
34 Not Connected
GOV
35 Not Connected
37 Not Connected
AVR
38 Not Connected
NOTE: Screened 120ΩΩ impedance cable specified for use with CAN must be used for the DSENet link
and the Multiset comms (MSC) link.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω
Ω impedance cable suitable for CAN
use (DSE part number 016-030)
31
NOTE: - The above table describes connections to a three phase, four-wire system. For alternative
wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.
NOTE: The above table describes connections to a three phase, four wire system. For alternative
wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.
32
WARNING! - Do not disconnect this plug when the CTs are carrying current. Disconnection will open
circuit the secondary of the C.T.’s and dangerous voltages may then develop. Always ensure the CTs are
not carrying current and the CTs are short circuit connected before making or breaking connections to the
module.
NOTE: - The 8600 series module has a burden of 0.5VA on the CT. Ensure the CT is rated for the
burden of the 8600 series controller, the cable length being used and any other equipment sharing the CT.
If in doubt, consult your CT supplier.
NOTE: - Take care to ensure correct polarity of the CT primary as shown below. If in doubt, check with
the CT supplier.
CT LABELLING
s1 is the secondary of the CT that connects to the DSE Module’s input for the CT measuring (I1,I2,I3)
s2 is the secondary of the CT that should be commoned with the s2 connections of all the other CTs and connected
to the CT common terminal of the DSE8600 series modules.
CT labelled as
p1, k or K To Load
To Supply CT labelled as
p2, l or L
NOTE: Take care to ensure correct polarity of the CT primary as shown overleaf. If in doubt, check
with the CT supplier.
33
WARNING! - Do not disconnect this plug when the CT is carrying current. Disconnection will open
circuit the secondary of the C.T. and dangerous voltages may then develop. Always ensure the CT is not
carrying current and the CT is short circuit connected before making or breaking connections to the
module.
NOTE: - Load CT is NOT REQUIRED in a system including only one mains supply (with one 8660
controller). See section below detailing advantages of the load CT in a multiple mains (multiple 8660)
system.
NOTE: - The 8600 series module has a burden of 0.5VA on the CT. Ensure the CT is rated for the
burden of the 8600 series controller, the cable length used and any other equipment sharing the CT. If in
doubt, consult your CT supplier.
NOTE: - Take care to ensure correct polarity of the CT primary as shown below. If in doubt, check with
the CT supplier.
NOTE: - Take care to ensure correct polarity of the CT primary as shown in the previous section. If in
doubt, check with the CT supplier.
The load CT is only required when there is more than one DSE8660 on the same system.
When the load CT is fitted the 8660 transfers the right amount of load to the mains before disconnecting the
generator(s), preventing them from being shock loaded.
Without the load CT, the 8660 does not know how much load to transfer to the mains when other 8660’s are still in
island mode. The 8660 would transfer a pre-determined amount of load before disconnecting the generator(s) from
the mains. This would lead to there being too much load or not enough load transferred, and the generator(s) would
be shock loaded as the generator(s) disconnect from the mains.
34
NOTE: The USB connection cable between the PC and the DSE8600 series module must not extend
beyond 5m (5yds). For distances over 5m, it is possible to use a third party USB extender. Typically, they
extend USB up to 50m (yds). The supply and support of this type of equipment is outside the scope of
Deep Sea Electronics PLC.
CAUTION! Care must be taken not to overload the PCs USB system by connecting more than the
recommended number of USB devices to the PC. For further information, consult your PC supplier.
CAUTION! This socket must not be used for any other purpose.
35
PIN No NOTES
A Two core screened twisted pair cable.
120Ω impedance suitable for RS485 use.
B Recommended cable type - Belden 9841
Max distance 1200m (1.2km) when using Belden 9841 or direct equivalent.
SCR
Location of RS232
connector
4.1.5 RS232 CONNECTOR
PIN No NOTES
1 Received Line Signal Detector (Data Carrier Detect)
2 Received Data
3 Transmit Data
4 Data Terminal Ready
5 Signal Ground
6 Data Set Ready
7 Request To Send
8 Clear To Send
9 Ring Indicator
View looking into the male connector on the 8600 series module
36
Genset manufacturers and panel builders may use these diagrams as a starting point; however, you are referred to
the completed system diagram provided by your system manufacturer for complete wiring detail.
Further wiring suggestions are available in the following DSE publications, available at www.deepseaplc.com to
website members.
37
38
39
40
41
4.2.5 DSENET®
DSENet® is the communication port between the host controller (DSE86xx series) and the expansion device as
shown below. Further details are contained within the Specification section of this document and within the operator
manual for the specific expansion module you are connecting to.
DSE stock and supply Belden cable 9841 which is a high quality 120Ω
Ω impedance cable suitable for
DSENet® use (DSE part number 016-030)
42
The typical wiring diagrams located within this document show connections for a negative earth system (the battery
negative connects to Earth)
When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the following
points must be followed:
• Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
• All points shown as Earth on the typical wiring diagram should connect to BATTERY NEGATIVE (not earth).
Where neither the battery positive nor battery negative terminals are connected to earth, the following points must to
be followed
• Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
• All points shown as Earth on the typical wiring diagram should connect to BATTERY NEGATIVE (not earth).
43
NOTE : DSE8600 series does not support the 2510/2520 display modules.
44
5 DESCRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.
Bus on load
LED
Transfer to
Bus(Manual
Mains available Mode only)
LED
Bus available
Mains on load LED
LED
Start engine(s)
(when in
Manual or Test
Mode)
Select Stop
Mode
Select Auto
Select Manual Mode
Mode Select Test
Mode
45
Mains Available
LED.
On when the
mains is within
limits and able to
take load.
Bus Available
LED.
On when the
generator is
within limits
and able to
Close Mains LED. Close Bus LED. take load.
On When The Mains Is On When The Bus Is On
On Load. Load.
46
NOTE: For further details, see the section entitled ‘OPERATION’ elsewhere in this manual.
47
NOTE: For further details, see the section entitled ‘OPERATION’ elsewhere in this manual.
48
The complete order and contents of each information page are given in the following sections
Once selected the page will remain on the LCD display until the user selects a different page, or after an extended
period of inactivity (LCD Page Timer), the module will revert to the status display.
If no buttons are pressed upon entering an instrumentation page, the instruments are displayed automatically
subject to the setting of the LCD Scroll Timer.
The LCD Page and LCD Scroll timers are configurable using the DSE Configuration Suite Software or by using the
Front Panel Editor.
Alternatively, to scroll manually through all instruments on the currently selected page, press the scroll
buttons. The ‘autoscroll’ is disabled.
To re-enable ‘autoscroll’ press the scroll buttons to scroll to the ‘title’ of the instrumentation page (i.e.
Engine). A short time later (the duration of the LCD Scroll Timer), the instrumentation display will begin to
autoscroll.
When scrolling manually, the display will automatically return to the Status page if no buttons are pressed for the
duration of the configurable LCD Page Timer.
If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw the operator’s
attention to the alarm condition.
49
5.3.1 STATUS
This is the ‘home’ page, the page that is displayed when no other page has been selected, and the page that is
automatically displayed after a period of inactivity (LCD Page Timer) of the module control buttons.
Factory setting of Status screen showing engine stopped... ...and engine running
The contents of this display may vary depending upon configuration by the generator manufacturer / supplier.
The display above was achieved with the factory settings, shown below in the DSE Configuration suite software:
NOTE:- The following sections detail instrumentation pages, accessible using the scroll left and right
buttons, regardless of what pages are configured to be displayed on the ‘status’ screen.
50
5.3.2 MAINS
5.3.3 BUS
51
NOTE: Factory Default settings are for the RS232 port to be enabled (no modem connected), operating
at 19200 baud, modbus slave address 10.
When the DSE86xx series module is power up, it will send ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the DSE86xx series
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the modem does not
‘hang up’.
If the DSE86xx series module does not correctly communicate with the modem, “Modem initialising’ will appear on
the Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, then if the modem is dialled, it will
answer after two rings (using the factory setting ‘initialisation strings’. Once the call is established, all data is passed
from the dialling PC and the DSE86xx series module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module will dial out whenever
an alarm is generated. Note that not all alarms will generate a dial out; this is dependant upon module configuration
of the event log. Any item configured to appear in the event log will cause a dial out.
52
NOTE:- Modem diagnostic screens are available on 73xx module versions 5 and above only. The
modem screens appear only when the module has been configured for use with a modem.
Modem diagnostic screens are included; press when viewing the Serial Port instrument to cycle the available
screens. If you are experiencing modem communication problems, this information will aid troubleshooting.
Example:
Line Description
RTS Request To Send Flow control
CTS Clear To Send Flow control
DSR Data Set Ready Ready to communicate
DTR Data Terminal Ready Ready to communicate
DCD Data Carrier Detect Modem is connected
Shows the last command sent to the modem and the result
of the command.
53
1)
2)
In case of communication failure between the modem and DSE8600 series module, the modem is automatically
reset and initialisation is attempted once more:
3)
In the case of a module that is unable to communicate with the modem, the display will continuously cycle
between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and attempts to
communicate with it again, this will continue until correct communication is established with the modem.
In this instance, you should check connections and verify the modem operation.
Many GSM modems are fitted with a status LED to show operator cell status and ringing indicator. These can be a
useful troubleshooting tool.
In the case of GSM connection problems, try calling the DATA number of the SIMCARD with an ordinary telephone.
There should be two rings, followed by the modem answering the call and then ‘squealing’. If this does not happen,
you should check all modem connections and double check with the SIM provider that it is a DATA SIM and can
operate as a data modem. DATA is NOT the same as FAX or GPRS and is often called Circuit Switched Data
(CSD) by the SIM provider.
NOTE: In the case of GSM modems, it is important that a DATA ENABLED SIM is used. This is often a
different number than the ‘voice number’ and is often called Circuit Switched Data (CSD) by the SIM
provider.
If the GSM modem is not purchased from DSE, ensure that it has been correctly set to operate at 9600 baud. You
may need to install a terminal program on your PC and consult your modem supplier to do this. GSM modems
purchased from DSE are already configured to work with the DSE86xx series module.
54
‘Master inactivity timeout’ should be set to at least twice the value of the system scan time. For example if a modbus
master PLC requests data from the DSE86xx modbus slave once per second, the timeout should be set to at least
2 seconds.
The DSE Modbus Gencomm document containing register mappings inside the DSE module is available upon
request from [email protected]. Email your request along with the serial number of your DSE module to
ensure the correct information is sent to you.
BatteryVoltage=ReadRegister(10,0405,1) : reads register (hex) 0405 as a single register (battery volts) from slave
address 10.
WriteRegister(10,1008,2,35701, 65535-35701): Puts the module into AUTO mode by writing to (hex) register 1008, the
values 35701 (auto mode) and register 1009 the value 65535-35701 (the bitwise opposite of auto mode)
Warning=(ReadRegister(10,0306,1) >> 11) & 1) : reads (hex) 0306 and looks at bit 12 (Warning alarm present)
ElectricalTrip=(ReadRegister(10,0306,1) >> 10) & 1) : reads (hex) 0306 and looks at bit 11 (Electrical Trip alarm
present)
55
5.3.5 ABOUT
Contains important information about the module and the firmware versions. This information may be asked for
when contacting DSE Technical Support Department for advice.
• Update Network settings using DSE Configuration Suite Software+ 1 Power cycle off/on before the editor
pages are updated..
Network
IP address
192.xxx.xx.xx
DHCP Disabled
Network
Network
Subnet mask
255.255.255.0
Network
Gateway address
192.xxx.xx.xxx
Network
DNS address
192.xxx.xx.xx
Network
MAC address Unique setting for each module
E8.A4.C1.0.A.C2
DHCP
HOST
DOMAIN
Vendor
MODBUS over IP
TCP Port
Port 502
Pref IP 0.0.0.0
56
The DSE data logging pages show information depending on the configuration in the module.
Inserting a USB drive to the host USB will display the following change to the page.
Data Logging
Log to USB drive
Logging active
Do not remove USB drive
NOTE:- Removal of the USB drive should only be carried out using the following method.
Press and hold the tick button until “Ok to remove USB drive” is displayed.
Data Logging
Log to USB drive
Logging active
Ok to remove USB drive
Data Logging
Time remaining Remaining time available for logging
xxxx h xx m information.
xxxx hours xx minutes
Data Logging
Memory remaining Memory space remaining, this depends
xxxx what size memory drive is fitted (Max
16Gb) or allocated internal (2Mb)
memory left available.
.
57
Under default factory settings, the event log only includes shutdown and electrical trip alarms logged (The event
log does not contain Warning alarms), however this is configurable by the system designer using the DSE
Configuration Suite software.
Once the log is full, any subsequent shutdown alarms will overwrite the oldest entry in the log.
Hence, the log will always contain the most recent shutdown alarms.
The module logs the alarm, along with the date and time of the event
If the module is configured and connected to send SMS text, a text of the event is sent also.
To view the event log, repeatedly press the next page button until the LCD screen displays the Event log :
Event log 1
This is event 1.
Oil Pressure Low
Shutdown
12 Sep 2007, 08:25:46
Continuing to press down cycles through the past alarms after which the display shows the most recent
alarm and the cycle begins again.
To exit the event log and return to viewing the instruments, press the next page button to select the next
instrumentation page.
58
59
5.6 CONTROLS
Stop / Reset
This button places the module into its Stop/Reset mode. This will clear any alarm conditions for
which the triggering criteria have been removed. If the engine(s) is(are) running and the module is in
Stop mode, the module will automatically instruct the changeover device to unload the generator bus
(‘Close Bus becomes inactive (if used)). The start request is taken away. Should a remote start
signal be present while operating in this mode, a remote start will not occur.
Manual
This mode allows manual control of the functions. Once in Manual mode the module will respond to
the start button, sending a start request to the engine(s) over the MSC link. If the engine is
running off-load in the Manual mode and a remote start signal becomes present, the module will
automatically instruct the changeover device to place the generator bus on load (‘Close Bus
becomes active (if used)). Upon removal of the remote start signal, the generator bus remains on
load until either selection of the ‘STOP/RESET’ or ‘AUTO’ modes.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere in this
manual.
Auto
This button places the module into its ‘Automatic’ mode. This mode allows the module to control the
function of the system automatically. The module will monitor the remote start input and mains supply
status and once a start request is made, the set(s) will be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the load from the generator
bus and shut the set(s) down observing the stop delay timer and cooling timer as necessary. The
module will then await the next start event. For further details, please see the more detailed
description of ‘Auto operation’ elsewhere in this manual.
Test
This button places the module into its ‘Test’ mode. This allows an on load test of the generator(s).
Once in Test mode the module will respond to the start button, sending a start request to the
engine(s) over the MSC link, and run on load, in parallel with the mains supply.
For further details, please see the more detailed description of ‘Test operation’ elsewhere in this
manual.
Start
This button is only active in TEST or MANUAL mode.
Pressing this button in manual or test mode will request the engines to start and run off load (manual)
or on load (test).
60
CLOSE MAINS
This push button is used to control the closure of the mains load switching device and has two modes
of operation :
1. Synchronising is NOT enabled. Pressing this button when the mains is available off load and in
MANUAL mode, the bus load switch is opened and the mains load switch is closed. Further
presses of this button will have no effect.
2. Synchronising is enabled. Pressing this button when the mains is available and in MANUAL
mode, the 8660 controller, will volts match and synchronise with the Bus. The mains load switch
is then closed in parallel with the Bus.
NOTE: If the bus is live when the manual button is pressed, synchronising will take place
before the load switch is closed.
CLOSE BUS
This push button is used to control the closure of the bus load switching device and has two modes of
operation :
3. Synchronising is NOT enabled. Pressing this button when the bus is off load and in MANUAL
mode, the mains load switch is opened and the bus load switch is closed. Further presses of this
button will have no effect.
4. Synchronising is enabled. Pressing this button when the bus is live and in MANUAL mode, the
8660 controller, will volts match and synchronise with the Mains. The bus load switch is then
closed in parallel with the mains.
NOTE: If the bus is live when the manual button is pressed, synchronising will take place
before the load switch is closed.
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in this manual.
61
6 OPERATION
The following description details the sequences followed by a module containing the standard ‘factory configuration’.
Remember that if you have purchased a completed generator set or control panel from your supplier, the module’s
configuration will probably have been changed by them to suit their particular requirements.
Always refer to your configuration source for the exact sequences and timers observed by any particular module in
the field.
62
In STOP mode, the module will remove the generator bus from load (if necessary) before remove the start request
from the engines.
Any latched alarms (electrical trip) that have been cleared are reset when STOP mode is entered.
The engine will not be started by the DSE8660 when in STOP mode. If remote start signals are given or the mains
supply fails, the start request is not sent to the engines until AUTO mode is entered.
If Immediate mains dropout is enabled, the mains load switch is opened and closed as appropriate, when the mains
fails or becomes available to take load.
NOTE: If a digital input configured to panel lock is active, changing module modes will not be possible.
Viewing the instruments and event logs is NOT affected by panel lock.
Activate auto mode by pressing the pushbutton. An LED indicator beside the button confirms this action.
Auto mode will allow the generator to operate fully automatically, starting and stopping as required with no user
intervention.
To allow for ‘false’ start requests such as mains brownouts, the start delay timer begins. There are individual start
delay timers for each of the different start request types.
Should all start requests be removed during the start delay timer, the unit will return to a stand-by state.
If a start request is still present at the end of the start delay timer, the starting request is sent to the engine(s) over
the MSC data link.
63
Once the generator bus becomes available, the load is transferred. If required, the generator bus is first
synchronised with the mains supply. This operation is automatic, using the MSC data link.
Load ramping takes place when appropriate, the DSE8660 controls the generator(s) bus to provide the configured
power to the load and/or mains supply.
Pf – The generator(s) will product power at the power factor configured into the Load power factor parameter.
The kVAr is variable in order to achieve this.
In this mode, the generator(s) are used to provide a variable amount of active power (kW), to maintain the mains
import/export levels at the configured values. This is configured into the Load parallel power parameter.
How much reactive power is taken from or exported to the mains depends upon the kVAr/pf selection:
KVAr – The generator(s) will be used to provide enough kVAr to keep the mains import/export VAr at the level
configured into the Load Parallel VAr parameter. The mains power factor is variable in order to achieve this.
Pf – The generator(s) will be used to provide enough kVAr to keep the mains import/export at the power factor
configured into the Load power factor parameter. The mains kVAr is variable in order to achieve this.
As the load increases and decreases, sets may automatically start and stop, depending upon their configuration.
If all start requests are removed, the stopping sequence will begin.
The return delay timer operates to ensure that the starting request has been permanently removed and is not just a
short-term removal.
If there are no starting requests at the end of the return delay timer, the load is transferred back from the generator
bus to the mains supply and the start request is removed from the engine(s).
64
NOTE: If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate Manual mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
Manual mode allows the operator to start and stop the set(s) manually, and if required change the state of the load
switching devices.
In manual mode, the load is not transferred to the generator bus unless a ‘loading request’ is made.
A loading request can come from a number of sources.
Parallel operation is governed by configuration. See the previous section Auto Mode: Engine Running for further
details.
• Press the transfer to bus button. The load is ramped to the bus, the mains breaker is opened.
• Press the transfer to mains button. The load is transferred to the mains. The generator bus breaker is
opened.
• Press the auto mode button to return to automatic mode.
65
NOTE: If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate test mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
Test mode will start the set(s) and parallel the mains to the generator bus to provide a Test on load function.
Depending upon configuration this can be continuous parallel or island mode operation.
Parallel operation is governed by configuration. See the previous section entitled Auto Mode: Engine Running for
further details.
In test mode, the set will continue to run on load until either:
• The stop button is pressed – The generator bus breaker is opened and the set(s) are called to stop.
• The auto button is pressed. The set(s) will observe all auto mode start requests and stopping timers
before beginning the Auto mode stopping sequence.
66
NOTE: At no time are the generators paralleled with more than one mains supply at a time. Paralleling
with mains supplies is always taken in turn.
Priority Condition
HIGHEST
Auto mode, mains failed, bus not on load
Auto mode, mains has returned
Auto mode, mains failed, bus on load
Auto mode, mains available, requesting control over generators
Test on load mode
Manual mode, sets running or about to run (start button has been pressed)
Auto mode, mains available
Manual mode, sets not running (waiting for start button to be pressed)
Stop mode
LOWEST
Where two or more 8660 controllers have the same conditions in the table above, the ‘Set Priority’ configuration
setting comes into effect. If two or more 8660 controllers have the same priority number, an electrical trip alarm is
generated - Priority Selection Error - and the priority numbers must be changed before the system will operate.
NOTE: If a 8660 requests to control the generators (either automatically or manually) it will not be
allowed to do so until higher priority 8660 controllers have relinquished control over them.
For typical one line diagram of a multi-mains system, see the section entitled “Typical system schematics”
elsewhere in this manual.
67
The 8660 controller incorporates an optional (but recommended) extra CT measuring the size of the load. Used in
conjunction with the CTs measuring the amount of load on the mains supply, this CT allows the 8660 to determine
what portion of the load is being supplied by the generators.
This allows the 8660 to remove the sets from this load when there is little or no current passing through the bus
breaker. For example: When the generators are ramping off load.
68
7 PROTECTIONS
When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configured will illuminate.
The audible alarm can be silenced by pressing the Mute button
The LCD display will jump from the ‘Information page’ to display the Alarm Page
The LCD will display multiple alarms. These will automatically scroll in the order that they occurred.
7.1 INDICATIONS
Indications are non-critical and often status conditions. They do not appear on the LCD of the module as a text
message. However, an output or LED indicator can be configured to draw the operator’s attention to the event.
Example
69
7.2 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to
draw the operators attention to an undesirable condition.
In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and
shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However enabling ‘all warnings
are latched’ will cause warning alarms to latch until reset manually. This is enabled using the 8600 series
configuration suite in conjunction with a compatible PC.
Display Reason
BATTERY UNDER The DC supply has fallen below the low volts setting level for the duration of the
VOLTAGE low battery volts timer
BATTERY OVER VOLTAGE The DC supply has risen above the high volts setting level for the duration of the
high battery volts timer
AUXILIARY INPUTS Auxiliary inputs can be user configured and will display the message as written by
the user.
kW OVERLOAD The measured Total kW is above the setting of the kW overload warning alarm
70
Electrical trips are latching alarms and stop the Generator(s). Remove the fault then press Stop/Reset to reset
the module.
Display Reason
AUXILIARY INPUTS If an auxiliary input configured as an electrical trip is active, the appropriate
message will be displayed as configured by the user.
kW OVERLOAD The measured Total kW is above the setting of the kW overload Electrical
Trip alarm
MSC OLD UNITS ON BUS If the module detects a module on the MSC link which is incompatible with
the current module, then the MSC Compatibility alarm will be triggered.
Check all the modules’ version numbers (under About | Application Number
on the modules’ displays), modules pre V3 cannot communicate with
modules V4 and onwards. Use the DSE Configuration Suite Software to
upgrade the firmware (Tools | Update Firmware) of the older modules to V4
and onwards.
NOTE: This protection operates only when in parallel with the mains supply and is disabled at all other
times.
Should either of these alarms operate, the module will perform a controlled shutdown (electrical trip) of the
generator. This operation must be manually reset :
1) Press button. The engine will stop if it is still running and the alarm is cleared.
2) Activate digital input configured to “Clear ROCOF/Vector shift” if this has been provided.
3) Press and button together and hold for 5 seconds. The ROCOF/Vector shift instrument is displayed
and all ‘peak hold’ values are reset, clearing the ROCOF/Vector shift alarm.
For details on activating and configuring the ROCOF/Vector shift protection, you are referred to the 8600
configuration software manual.
71
8 SCHEDULER
DSE8600 Series contains an inbuilt exercise run scheduler, capable of automatically starting and stopping the set.
Up to 16 scheduled start/stop sequences can be configured to repeat on a 7-day or 28-day cycle.
Scheduled runs may be on load or off load depending upon module configuration.
Example
• Scheduled runs will not occur when the module is in STOP/RESET mode.
• Scheduled runs will not occur when the module is in MANUAL mode.
• Activation of a Scheduled Run ‘On Load’ when the module is operating OFF LOAD in Manual mode will
have no effect, the set continues to run OFF LOAD
• Scheduled runs will operate ONLY if the module is in AUTO mode with no Shutdown or Electrical Trip alarm
present.
• If the module is in STOP or MANUAL mode when a scheduled run begins, the engine will not be started.
However, if the module is moved into AUTO mode during a scheduled run, the engine will be called to start.
• Depending upon configuration by the system designer, an external input can be used to inhibit a scheduled
run.
• If the engine is running OFF LOAD in AUTO mode and a scheduled run configured to ‘On Load’ begins, the
set is placed ON LOAD for the duration of the Schedule.
72
Use the module’s navigation buttons to traverse the menu and make value changes to the parameters:
Previous page
73
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset button.
Press , the first ‘#’ changes to ‘0’. Press (up or down) to adjust it to the correct value.
Press (right) when the first digit is correctly entered. The digit you have just entered will now show
‘#’ for security.
Repeat this process for the other digits of the PIN number. You can press (left) if you need to move
back to adjust one of the previous digits.
When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not
correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
NOTE: The PIN number is not set by DSE when the module leaves the factory. If the module has a PIN
code set, this has been affected by your generator supplier who should be contacted if you require the
code. If the code has been ‘lost’ or ‘forgotten’, the module must be returned to the DSE factory to have the
module’s code removed. A charge will be made for this procedure.
NB - This procedure cannot be performed away from the DSE factory.
74
Press the (left) or (right) buttons to cycle to the section you wish to view/change.
Press the (up or down) buttons to select the parameter you wish to view/change within the
currently selected section.
To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are
editing the value.
Press the (up or down) buttons to change the parameter to the required value.
Press to save the value. The parameter ceases flashing to indicate that it has been saved.
To exit the editor at any time, press and hold the button.
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to
ensure security.
NOTE: More comprehensive module configuration is possible using the 86xx series PC configuration
software. Please contact us for further details.
75
76
Press the (left) or (right) buttons to cycle to the section you wish to
view/change.
Press the (up or down) buttons to select the parameter you wish to
view/change within the currently selected section.
To edit the parameter, press to enter edit mode. The parameter begins to flash to
indicate that you are editing the value.
Press the (up or down) buttons to change the parameter to the required
value.
Press to save the value. The parameter ceases flashing to indicate that it has
been saved.
To exit the editor at any time, press and hold the button.
Running Editor (Factory default settings are shown in bold italicised text)
77
10 COMMISSIONING
10.1.1 PRE-COMMISSIONING
Before the system is started, it is recommended that the following checks are made:-
1. The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible with the
system.
2. Check all mechanical parts are fitted correctly and that all electrical connections (including earths) are
sound.The unit DC supply is fused and connected to the battery and that it is of the correct polarity.
3. Check the operation of the MSC datalink. Use the DSE Config Suite to check this on the SCADA | BUS |
MSC LINK page. Verify the number of sets on the bus.
4. Ensure all 8610 controllers in the system have been fully commissioned using the DSE “Four Steps to
Successful Synchronising”.
5. Place the 8660 module into STOP mode. Place the 8610(s) into AUTO mode. Initiate a start by pressing the
START button of the 8660. All 8610’s start upon receipt of the MSC start command.
6. The bus will remain off load so long as the mains supply is healthy and on load.
7. Press the 8610 STOP button to remove the start request and stop the set(s).
8. Set the modules internal clock/calendar to ensure correct operation of the scheduler and event logging
functions. For details of this procedure see section entitled Front Panel Configuration – Editing the date and
time.
9. If, despite repeated checking of the connections between the 8600 series controller and the customer’s
system, satisfactory operation cannot be achieved, then the customer is requested to contact the factory for
further advice on:-
78
11 FAULT FINDING
Check 8660 ATS and 8610 engine controllers are in AUTO mode.
Module appears to ‘revert’ to an When editing a configuration using the PC software it is vital that the
earlier configuration configuration is first ‘read’ from the controller before editing it. This edited
configuration must then be “written” back to the controller for the changes to
take effect.
When editing a configuration using the fascia editor, be sure to press the
Accept button to save the change before moving to another item or exiting
the fascia editor
Bus will not take load Ensure the generator available LED is lit
Check that the output configuration is correct to drive the load switch device
and that all connections are correct.
Remember that the set will not take load in manual mode unless the mains
supply fails, a remote start on load input is present or the close generator
button is pressed.
Inaccurate measurements on Check that the CT primary, CT secondary and VT ratio settings are correct for
controller display the application.
Check that the CTs are wired correctly with regards to the direction of current
flow (p1,p2 and s1,s2) and additionally ensure that CTs are connected to the
correct phase (errors will occur if CT1 is connected to phase 2).
The 8600 series controller is true RMS measuring so gives more accurate
display when compared with an ‘averaging’ meter such as an analogue panel
meter or some lower specified digital multimeters.
Accuracy of the controller is better than 1% of full scale. Ie Gen volts full scale
is 333V ph-n so accuracy is ±3.33V (1% of 333V).
NOTE: The above fault finding is provided as a guide check-list only. As the module can be configured
to provide a wide range of different features, always refer to the source of your module configuration if in
doubt.
79
If you require additional plugs from DSE, please contact our Sales department using the part numbers below.
80
NOTE: A maximum of twenty (20) expansion modules can be connected to the DSENet®.
NOTE: DSENet® utilises an RS485 connection. Using Belden 9841 (or equivalent) cable allows for the
expansion cable to be extended to a maximum of 1.2km.
DSE Stock and supply Belden 9841 cable. DSE Part Number 016-030.
81
13 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any applicable
warranty, you are referred to your original equipment supplier (OEM).
14 DISPOSAL
14.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
Directive 2002/96/EC
If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of
WEEE separately from your other waste.
Exemption Note: Category 9. (Monitoring & Control Instruments) as defined in Annex 1B of the WEEE directive will
be exempt from the RoHS legislation. This was confirmed in the August 2005 UK´s Department of Trade and
Industry RoHS REGULATIONS Guide (Para 11).
Despite this exemption, DSE has been carefully removing all non RoHS compliant components from our supply
chain and products.
When this is completed a Lead Free & RoHS compatible manufacturing process will be phased into DSE
production.
This is a process that is almost complete and is being phased through different product groups.
82
83
84