B9512G B8512G Installation Manual enUS 18617908491 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 46

Control panels

B9512G/B8512G

en UL Installation manual
Control panels Table of contents | en 3

Table of contents
1 Introduction 5
1.1 About documentation 5
1.1.1 Related documentation 5
1.2 Bosch Security Systems, Inc. product manufacturing dates 7
2 System overview 8
2.1 Parts list 8
2.2 Control panel capacities 8
3 Control panel installation 10
3.1 Installing the enclosure 10
3.2 Installing the control panel 10
3.2.1 Earth ground 11
3.2.2 Ground Fault Detect enable 11
3.2.3 Ground fault detection troubleshooting 11
3.3 Control panel to module wiring overview 12
4 Power supply 15
4.1 Secondary (DC) power 15
4.1.1 Install the battery 15
4.1.2 BATTERY STATUS LED 16
4.1.3 Battery maintenance 17
4.1.4 Battery supervision 17
4.1.5 Battery charging circuit float charge 18
4.1.6 Battery discharge and recharge schedule 18
4.2 B520 aux power supply 18
4.2.1 SDI2 address settings 19
4.2.2 Supervision 19
4.2.3 Auxiliary power supply trouble conditions 19
4.2.4 Installation and control panel wiring (B520) 19
4.2.5 Powered device and battery wiring 20
5 On-board outputs 23
5.1 Circuit protection 23
5.2 Total available power 23
5.3 Continuous power outputs 24
5.4 Programmable power outputs 24
5.4.1 Terminals 6 and 7 24
5.4.2 Terminal 8 25
5.5 USB power 25
6 Control panel board overview 26
7 System wiring diagrams 27
7.1 Power supply side wiring 27
7.2 Input points wiring with D125B, D130, or D129 28
7.3 Input points wiring with or without EOL resistors 29
7.4 SDI and ZONEX wiring 30
7.5 SDI2 devices general system wiring 31
7.5.1 SDI2 bus wiring recommendations 31
7.6 2-wire smoke wiring (D125B) 33
7.7 Earth ground wiring 34
7.7.1 Ground Fault Detect enable 34
7.7.2 Ground fault detection troubleshooting 34

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


4 en | Table of contents Control panels

8 B925F Fire Keypad operating instructions 36


9 B926F Fire Keypad operating instructions 37
10 D1255RB operating instructions 38
11 D1256RB operating instructions 39
12 Specifications 40
12.1 Wire requirements 41

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Introduction | en 5

1 Introduction
This section includes an introduction to documents for this product and other document-
related instructions.

1.1 About documentation


This document has instructions for a trained installer to install, configure, and operate this
control panel, and optional peripheral devices.
(Bosch Security Systems, Inc. recommends that installers follow good wiring practices such as
those described in NFPA 731, Standard for the Installation of Electronics Premises Security
Systems.)
Throughout this document, the words “control panel” refer to all control panels covered by
this document (B9512G/B8512G).
Notifications
This document uses Notices, Cautions, and Warnings to draw your attention to important
information.

Notice!
These include important notes for successful operation and programming of equipment, or
indicate a risk of damage to the equipment or environment.

Caution!
These indicate a hazardous situation which, if not avoided, could result in minor or moderate
! injury.

Warning!
These indicate a hazardous situation which, if not avoided, could result in death or serious
! injury.

Copyright
This document is the intellectual property of Bosch Security Systems B.V. and is protected by
copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered
trademarks and must be treated accordingly.

1.1.1 Related documentation


Control panel documents

Control Panels (B9512G/B8512G) Release Notes*

Control Panels (B9512G/B8512G) Installation Manual+


+
Control Panels (B9512G/B8512G/B6512/B5512/B4512/B3512) Operation Manual*

Control Panels (B9512G/B8512G) Program Entry Guide+


+
Control Panels (B9512G/B8512G) UL Installation Manual*
+
Control Panels (B9512G/B8512G) SIA Quick Reference Guide*

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


6 en | Introduction Control panels

Control Panels (B9512G/B8512G/B6512/B5512/B4512/B3512) ULC Installation Manual

*Shipped with the control panel.


+
Located on the documentation CD shipped with the control panel.

Keypad documents

Basic Keypad (B915) Installation Guide*

Two-line Alphanumeric Keypad (B920) Installation Guide*

Fire Keypads (B925F/B926F) Installation Guide*

Two-line Capacitive Keypad with Inputs (B921C) Installation Guide*

ATM Style Alphanumeric Keypad (B930) Installation Guide*

B940W Touch screen KP, White Quick installation guide*

Touch Screen Keypad (B942/B942W) Installation Guide*

*Shipped with the keypad.

Optional module documents

Octo-input Module (B208) Installation and Operation Guide*

POPEX Module (B299) Installation Guide*

Octo-output Module (B308) Installation and Operation Guide*


+
Conettix Ethernet Communication Module (B426) Installation and Operation Guide*

Plug-in Telephone Communicator (B430) Installation Guide Installation Guide*

Conettix Plug-in GPRS Cellular Communicator (B442) Installation and Operation Guide*

Conettix Plug-in HSPA+ Cellular Communicator (B443) Installation and Operation Guide*

Conettix Cellular Communicators B44x Installation Manual

B444‑A | B444‑V Quick installation guide*


+
Conettix Plug-in Communicator Interface (B450) Installation and Operation Guide*

Auxiliary Power Supply (B520) Installation and Operation Guide*

Retrofit ZONEX Module (B600) Installation Guide

RADION receiver SD (B810) Installation Guide*

SDI2 Inovonics Interface Module (B820) Installation Guide*

Access Control Module (B901) Installation Guide

Dual Class B Initiating Module (D125B) Installation Instructions

Multiplex Bus Interface (D8125MUX) Operation and Installation Guide

OctoPOPIT Module (D8128D) Installation Guide

Access Control Interface Module (D9210C) Installation and Operation Guide

*Shipped with the module.


+
Located on the documentation CD shipped with the module.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Introduction | en 7

1.2 Bosch Security Systems, Inc. product manufacturing dates


Manufacturing dates
For product manufacturing dates, go to http://www.boschsecurity.com/datecodes/ and refer
to the serial number located on the product label.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


8 en | System overview Control panels

2 System overview
This section has the following information:
– Parts list, page 8
– Control panel capacities, page 8
– Accessories
– Features

2.1 Parts list


Control panels ship assembled from the factory with the following parts:
Literature
– Control Panels (B9512G/B8512G) UL Installation Manual
– Control Panels (B9512G/B8512G/B5512/B4512/B3512) Operation Manual
– Control Panels (B9512G/B8512G) SIA Quick Reference Guide
– Control Panels (B9512G/B8512G) Documentation CD
– Product Label in French
– 7000/9000 Series Point Chart Label
HW pack
– 1 kΩ EOL resistors
– Battery wires
Assembly
– PC board with protective cover
– Mounting skirt
– One #6 x 3/4-inch screw

2.2 Control panel capacities


Features B9512G B8512G

Number of users 2000 500

Total number of doors 321 81

Number of cards/tokens 2000 500

Number of custom functions 32 8

Number of areas 32 8

Number of points 599 99

Number of outputs 599 99

Total number of keypads 322 162

Number of octo-intput modules (B208) 59 9

Number of POPEX modules (B299) 6 1

Number of octo-output modules (B308) 59 9

Number of on-board Ethernet ports 1 1

Number of B426 or B450 modules 2 2

Number of plug-in telephone communication modules (B430) 2 2

Number of plug-in cellular modules (B442/B443/B444-A/B444-V) 1 1

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels System overview | en 9

Features B9512G B8512G

Number of auxiliary power supply modules (B520) 8 4

Number of wireless receivers (B810/B820) 1 1

Number of cameras3 16 8
1
The control panel supports 32 doors using the optional B901 Access Control Module. The control panel
supports up to 8 doors using the optional D9210C Access Control Interface Module.
2
The control panel supports up to 16 of the keypads as SDI keypads.
3
Bosch IP cameras use is supplementary in UL Listed systems.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


10 en | Control panel installation Control panels

3 Control panel installation


Refer to Enclosures to determine if the application requires a specific enclosure.
Enclosure and control panel (back view) overview

Callout ᅳ Description Callout ᅳ Description

1 ᅳ Hooks to attach the mounting skirt (2) 5 ᅳ Enclosure mounting holes (5)

2 ᅳ Three-hole pattern for mounting modules (4) 6 ᅳ Holes to attach the mounting skirt to hooks (2)

3 ᅳ Mounting location for the tamper switch 7 ᅳ Tab to secure the mounting skirt

4 ᅳ Mounting skirt screw location

3.1 Installing the enclosure


Notice!
Electromagnetic interference (EMI)
EMI can cause problems on long wire runs.

1. Remove the knockouts.


2. Mount the enclosure. Use all enclosure mounting holes. Refer to the mounting
instructions supplied with the selected enclosure.
3. Pull the wires into the enclosure through the knockouts.
4. Position the supplied point label chart on the inside of the enclosure door (optional).

3.2 Installing the control panel


1. Position the control panel over the inside back of the enclosure.
2. Align the Holes to attach the mounting skirt to hooks with the hooks.
3. Slide the control panel down so that it hangs on the hooks.
4. Secure the mounting skirt screw.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Control panel installation | en 11

3.2.1 Earth ground


To help prevent damage from electrostatic discharges or other transient electrical surges,
connect the system to earth ground before making other connections. The earth ground icon
identifies the earth ground terminal. Recommended earth ground references are a grounding
rod or a cold water pipe. Make the connection using 14 AWG (1.8 mm) to 16 AWG (1.5 mm)
wire.
To help prevent damage from electrostatic discharges or other transient electrical surges,
connect the system to earth ground before making other connections. The icon shows the
earth ground terminal. Use a recommended earth ground reference, such as a grounding rod
or a cold water pipe. Make the connection using 14 AWG (1.8 mm) to 16 AWG (1.5 mm) wire.

Notice!
Do not use telephone or electrical ground
Do not use telephone or electrical ground for the earth ground connection. Do not connect
other control panel terminals to earth ground.

Caution!
Avoid electrostatic discharge
! Always touch the earth ground connection with the icon first, before beginning work on the
control panel.

3.2.2 Ground Fault Detect enable


To meet UL 864 requirements, enable Ground Fault Detect.
A ground fault is a circuit impedance to ground sufficient to result in the annunciation of a
trouble condition.
The control panel has a ground fault detection circuit that when enabled, detects ground
faults on Terminals 1 to 9 and 11 to 30.
If a ground fault condition occurs, the keypads annunciate a ground fault and control panel
transmits a trouble message.
When the control panel recognizes that the ground fault condition is corrected, and remains
corrected for between 5 to 45 consecutive seconds, the control panel clears the fault from the
keypad display and sends a restoral report.
The control panel detects ground fault at ≤ 300 Ω.
Enabling Ground Fault Detect and reports
4 In RPS or in the Installer Services Portal programming tool (available in Europe, Middle
East, Africa, and China), set the following parameters:
– PANEL WIDE PARAMETERS > Miscellaneous > Ground Fault Detection. Set to Enable.
– PANEL WIDE PARAMETERS > Report Routing > Burglar Reports > Trouble Report. Set to
Yes.
– PANEL WIDE PARAMETERS > Report Routing > Burglar Reports > Burg Restore (After
Trouble). Set to Yes.

3.2.3 Ground fault detection troubleshooting


The control panel requires -2.1 V decay to 0.
Measuring and comparing voltage for ground fault detection
1. Set your digital voltmeter (DVM) to measure VDC.
2. Connect the red DVM lead to control panel Terminal 10, and the black DVM lead to
Terminal 9.
3. Compare this voltage to the following table.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


12 en | Control panel installation Control panels

Control panel voltage at Terminals 9 and 10) Terminal potentially causing ground fault

~ 0 VDC 4, 9, 12, 15, 18, 21

~ 13.65 VDC 5, 6, 7, 8, 26, 30

~ 2.51 VDC 11, 13, 14, 16, 17, 19, 20, 22

~ 2.44 to 3.2 VDC 24

~ 10.9 to 11.2 VDC 25

~ 7.2 VDC 28

~ 5.8VDC 29

~ 7.35 VDC 1, 2

3.3 Control panel to module wiring overview


You can use interconnect or terminal wiring to connect devices to the control panel.
If SDIx is configured for SDI2, use either SDI2 bus.
Using terminal wiring in parallel

Notice!
Wire size
For terminal wiring, use 18 AWG to 22 AWG (1.0 mm to 0.6 mm) wire.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Control panel installation | en 13

MOD-2

MODULE RELEASE

MOD-1

PWR+/R 30
29

A/Y 29
28
SDI2

olice
ting B/G 28
27

COM/B 27
26

ire

SDI2
SDIx

PWR+/R 26

A/Y 25
SDIx

B/G 24

COM/B 23

ZONEX TAMPER RESET


ZONEX TMPR

Using interconnect wiring

Notice!
More information
For more information on interconnect wiring, refer to SDI2 interconnect wiring.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


14 en | Control panel installation Control panels

SDI2 devices daisy chained with interconnect wiring

MOD-2

MODULE RELEASE

MOD-1

PWR+/R 30
29

A/Y 29
28
SDI2

olice
ting B/G 28
27

COM/B 27
26

ire
SDI2
SDIx

PWR+/R 26

A/Y 25
SDIx

B/G 24

COM/B 23

ZONEX TAMPER RESET


ZONEX TMPR

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Power supply | en 15

4 Power supply
This section provides information on installing and maintaining primary power, batteries, and
auxiliary power.

4.1 Secondary (DC) power

4 5
A 12 V sealed lead-acid rechargeable battery (such as the D126/D1218) supplies secondary
power to maintain system operation during interruptions of primary (AC) power.

Notice!
Use sealed lead acid batteries only
The charging circuit is calibrated for lead-acid batteries. Do not use gel-cell or NiCad
batteries.

Extra batteries
To increase battery back-up time, connect a second 12 V battery in parallel to the first battery.
Use a D122/D122L Dual Battery Harness to ensure proper and safe connection.
Refer to Standby battery requirements and calculations.
D1218 Battery
The D1218 is a 12 V, 18 Ah battery for use in applications requiring extended battery standby
time. The control panel does not support more than 38 Ah of battery.

4.1.1 Install the battery


1. Put the battery upright in the base of the enclosure.
2. Locate the red and black leads supplied in the hardware pack.
3. Connect the black battery lead to 4 .
4. Connect the other end to the negative (-) side of the battery.
5. Connect the red battery lead to 5.
6. Connect the other end to the positive (+) side of the battery.

Warning!
High current arcs are possible
The positive (red) battery lead and the terminal labeled 5 can create high current arcs if
! shorted to other terminals or the enclosure. Use caution when you touch the positive lead
and the terminal labeled 5. Always disconnect the positive (red) lead from the battery before
you remove it from the terminal labeled 5.

Caution!
Battery terminals and wire are not power limited

! Maintain a 0.250 in (6.4 mm) space between the battery terminals, battery wiring, and all
other wiring. Battery wiring cannot share the same conduit, conduit fittings, or conduit
knockouts with other wiring.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


16 en | Power supply Control panels

Non-power-limited wiring
BATTERY STATUS
Off: Normal
On: Missing
Quick Flash: Low
Slow Flash:

1 2 Charging

Low 12.1 VDC


Load Shed 10.2 VDC
Do not connect
to a receptacle
controlled by
a switch.

1 CLASS 2
16.5 VAC 40 VA 60 Hz

2 TRANSFORMER

All exte
3 + AUX POWER Require
POWER SUPPL
4 BATTERY ( - ) The Power S
refer to the B
Battery: Replace every 3 to
5 BATTERY ( + ) 5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
OUTPUT
6
A (1) The system is intended
panel has been approv
RevPol.
3 7
OUTPUT
B (2)
WARNING!
To prevent risk of shock,
OUTPUT disconnect AC power and
8
C (3) communication lines before

4 9 COMMON
servicing.

ON-BOARD POINTS
Owner I
be removed by
10 EARTH GROUND
Voltage Ranges: Open 3.7 - 5.0 VDC,
WARNING! WARNING!
Multi-Battery Incorrect wiring will 1k End-of-line-Resistors Required (P/N 15093130-004),
installation requires damage this
Model D122 or D122L equipment. Point 1 Point 2 Point 3 Point 4 Point 5 Point 6 Point 7 Point 8
Dual Battery Harness. Devices powered by
Improper installation any output must be
can be a fire hazard. supervised. 11 12 13 14 15 16 17 18 19 20 21 22

USB POWER B
STATUS L A
I S
N E
K T
USB ETHERNET POINT 1 COM POINT 2 POINT 3 COM POINT 4 POINT 5 COM POINT 6 POINT 7 COM POINT 8

Callout ᅳ Description

1 ᅳ Conduit required for use with external batteries

2 ᅳ Battery wires

3 ᅳ 0.25 in (6.4 mm) minimum. To ensure proper spacing, use tie-wraps or similar devices to
secure wires.

4 ᅳ Output wires

5 ᅳ Sensor loop wires

6 ᅳ 12 V sealed lead-acid rechargeable battery (D126/D1218)

Charging the battery


1. Connect the battery
2. Connect the transformer.
3. Allow the control panel to charge the battery while you complete the installation.

4.1.2 BATTERY STATUS LED


The control panel includes one BATTERY STATUS LED with 4 LED patterns to indicate the
battery status.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Power supply | en 17

LED pattern Function Refer to

Battery is fully charged. N/A

Off

Battery charge is below 13.4 Low battery, page 17 and


VDC and the battery is Battery restoral, page 17
Flashing slowly recharging.

Battery voltage dropped to Low battery, page 17 and


between 12.1 VDC and 10.2 Battery restoral, page 17
Flashing quickly VDC.
LED turns off when voltage
reaches at least 13.4 and > 200
mA.

Battery is missing, shorted, or Missing battery, page 17


reversed.
On Steady

4.1.3 Battery maintenance


Use 12 VDC sealed lead-acid rechargeable battery (7 Ah, 18 Ah, or 38 Ah). The control panel
supports up to 38 Ah of battery. If you use two batteries, they must have the same capacity,
and you use a D22/D122L to connect them.
Replace the batteries every 3 to 5 years. If you install two batteries, replace them both at the
same time.
Record the date of installation directly on the battery.

Caution!
Heavy discharges possible

! The system can have heavy discharges if you exceed the maximum output ratings or install
the transformer in an outlet that is routinely switched off. Routine heavy discharges can lead
to premature battery failure.

4.1.4 Battery supervision


Low battery
If the control panel is programmed for power supervision, it sends a Battery Low report in the
Conettix Modem4 format or a Low System Battery (302) report in the Conettix ANSI-SIA
Contact ID format.
Missing battery
If the control panel is programmed for power supervision, it sends a Battery Missing/Dead
report in the Conettix Modem4 format, or a Control Panel Battery Missing (311) report in the
Conettix ANSI-SIA Contact ID format.
Battery restoral
When AC returns and the battery is charged, If the control panel is programmed for power
supervision, it sends a Low System Battery Restore report in the Conettix Modem4 format or a
Control Panel Battery Restored to Normal (302) report in the Conettix ANSI-SIA Contact ID
format.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


18 en | Power supply Control panels

4.1.5 Battery charging circuit float charge


The float voltage for the battery charging circuit is 13.65 VDC when operating within load
range.
Load shed
Load shed relay protects battery: During an AC power loss, the battery supplies all power to
the security system. If the battery voltage falls below 10.0 V during an AC power loss, a load
shed relay disconnects the battery from the control panel and disables control panel. Load
shed protects the battery from being damaged by deep discharge.
When AC power restores, the load shed relay reconnects the charging circuit on control panel
to the battery and the battery begins to recharge.
Over load with AC present
If devices draw more than 1.6 A of auxiliary current from the control panel with AC applied,
the control panel indicates a Panel Over-current system trouble. Unless corrected, this
condition prevents the control panel from properly maintaining the battery charge level, and
leaves the system vulnerable to failing during power outages.
To correct the issue, remove all loads to the control panel and disconnect the battery and AC
power. Fix the condition creating the over current and reconnect AC power.
A shorted battery condition (created either by a shorted cell inside the battery or by a short
on Terminals 4 and 5), might prevent the control panel from operating, or might cause the
control panel to detect a missing battery condition.

Caution!
Shorting the battery terminals is dangerous.
!
4.1.6 Battery discharge and recharge schedule
Battery Discharge 13.30 VDC BATTERY STATUS LED slow flash.
discharge/ Cycle 12.1 VDC Low Battery Report, if programmed.
recharge BATTERY STATUS LED quick flash.
schedule 10.2 VDC Minimum operational voltage.
10.2 VDC Battery load shed.

Recharge AC ON Load shed relay resets, battery charging begins.


Cycle 12.50 VDC (under Battery Restoral Report sent, BATTERY STATUS LED
load) off.
13.4 VDC and charging Battery float charged. BATTERY STATUS LED off.
current < 200 mA

4.2 B520 aux power supply


The optional B520 provides up to 2 A of 12 VDC standby power for Fire and Burglar
applications. For Burglar applications, an additional 2 A of alarm power is available, allowing 2
A of standby current and up to 4 A of alarm current.
The control panels support the following number of B520 modules:
– B9512G. 8
– B8512G. 4
The power supply draws approximately 15 mA (+/- 1 mA) from the control panel.
For additional information on supported peripherals, refer to the technical documentation of
these peripherals.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Power supply | en 19

When using multiple NACs, the power for each D192G to support notification appliances must
have its own power limited and isolated power from a UL864 listed supply, such that one NAC
does not prevent another NAC from providing its alarm notification operation.

4.2.1 SDI2 address settings


Notice!
The module reads the address switch setting only during module power up. If you change the
setting after you apply power to the module, you must cycle the power to the module in order
for the new setting to take effect.

If multiple B520 modules reside on the same system, each B520 module must have a unique
address.

4.2.2 Supervision
The control panel supervises any B520 on the SDI2 bus.
With any failure to receive an expected response from a B520, all keypads show a system
fault. The control panel sends a module trouble report to the central station (if configured for
module trouble reports).

4.2.3 Auxiliary power supply trouble conditions


Each auxiliary power supply module on the SDI2 bus monitors several conditions including AC
status, battery status, over current status, and a tamper input. Each of these conditions
produces a unique system trouble condition at all keypads. The control panel sends a module
trouble report to the central station (if configured for module trouble reports).

4.2.4 Installation and control panel wiring (B520)


Calculate power consumption
Make sure that there is enough power for the module and the other powered devices that you
want to connect to the system.
Refer to On-board outputs, page 23.

Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
! result in personal injury and/or equipment damage.

Installing the module


1. Set the module address.
2. Insert the plastic mounting clips onto the standoff locations inside the enclosure or on a
mounting skirt, when required.
3. Mount the module onto the plastic mounting clips.
4. Tighten the supplied mounting screws.
Wiring to earth ground
4 To help prevent damage from electrostatic charges or other transient electrical surges,
connect the system to earth ground before making other connections.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


20 en | Power supply Control panels

Notice!
Earth ground reference
Do not use telephone or electrical ground for the earth ground connection. Use 14 AWG (1.8
mm) to 16 AWG (1.5 mm) wire when making the connection
Use a grounding rod or a cold water pipe.
Run wire as close as possible to grounding device.

Callout ᅳ Description

1 ᅳ B520 Auxiliary Power Supply Module

2 ᅳ 14 AWG - 16 AWG (1.8 mm - 1.5 mm) wire

3 ᅳ Ground device (grounding rod or cold water pipe)

Wiring to the control panel

Notice!
Terminal wiring
Use the terminal strip labeled with PWR, A, B, and COM for SDI2 IN to wire to corresponding
control panel SDI2 terminals. Do not use interconnect wiring.
Use 12 AWG to 22 AWG (2.0 mm to 0.6 mm) wire.

2 SDI2 OUT SDI2 IN

1 MOD-2

MODULE RELEASE
PWR A B COM PWR A B COM

MOD-1

3
PWR+/R 30
29
R
A/Y 29
28
Y
SDI2

olice
ting B/G 28
27
G
COM/B 27
26
B
ire
SDI2
SDIx

PWR+/R 26

A/Y 25
SDIx

B/G 24

COM/B 23

Callout ᅳ Description

1 ᅳ Control panel

2 ᅳ B520 Auxiliary Power Supply Module

3 ᅳ Terminal strip wiring

4.2.5 Powered device and battery wiring


When you wire the output of a B520 to a SDI2 module, the B520 provides power to the
module while passing through data between the control panel and the module.
2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.
Control panels Power supply | en 21

Wiring SDI2 modules

1 SDI2 OUT SDI2 IN 1 SDI2 OUT SDI2 IN

PWR A B COM PWR A B COM PWR A B COM PWR A B COM

R YGB

3
4
2
2

PWR A B COM
PWR A B COM

Callout ᅳ Description

1 ᅳ B520 Auxiliary Power Supply Module

2 ᅳ Powered device (SDI2 module)

3 ᅳ Terminal strip wiring

4 ᅳ Interconnect wiring (P/N: F01U079745)

1. Do one of the following:


Use terminal wiring to connect the SDI2 OUT terminal strip labeled with PWR, A, B, and
COM on the B520 to the terminals labeled PWR, A, B, and COM on the first module.
Connect an interconnect wiring cable (included) to the SDI2 OUT interconnect connector
on the B520 to the interconnect connector on the first module.
2. Connect additional modules in series with the first module.
Wiring to batteries

Notice!
Battery wiring requirements
You must wire BATT 1. You must wire BATT 2 if you configure the B520 for two batteries.
When you use BATT 2, both batteries must have the same rating.
Maximum standby power cannot exceed 36 Ah.

1
BATT 1 + - BATT 2 + -

R B R B

3 2

Callout ᅳ Description

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


22 en | Power supply Control panels

1 ᅳ B520 Auxiliary Power Supply Module

2 ᅳ Battery 2 (BATT 2) - (12 V nominal lead acid)

3 ᅳ Battery 1 (BATT 1) - (12 V nominal lead acid)

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels On-board outputs | en 23

5 On-board outputs
The control panel provides three powered relay outputs.

5.1 Circuit protection


The powered outputs come with circuit protection.
Four self-resetting circuit breakers protect the control panel from short circuits on the
continuous and programmable power outputs. Each breaker protects a separate terminal or
group of terminals:
– Terminal 3, auxiliary power
– Power terminals
– Terminal 6. Alarm power output
– Terminal 7. Alternate alarm power output
– Terminal 8. Switched auxiliary power
– Terminals 26 and 30, power +
– ZONEX connection

Notice!
A short circuit on one terminal disrupts power to the other two terminals.

Notice!
UL requirement
Supervise devices powered from a power output.

5.2 Total available power


The system produces up to 1.4 A of combined power at 12.0 VDC nominal. The outputs in this
section share the available power. These outputs appear as shown on the faceplate.

3 Auxiliary power
Power devices requiring continuous power.

6 Output A (1), Alarm power output


Programmable output normally open, power on alarm.

7 Output B (2), Alternate alarm power output


Programmable output normally open, power on alarm.

8 Output C (3), Switched auxiliary power


Programmable output normally closed, switches power off when the Sensor Reset command
is executed.

26 SDIx Power+ / R
Powers serial device interface (SDI) keypads, or use to power serial device interface 2 (SDI2)
devices, such as keypads and expansion modules.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


24 en | On-board outputs Control panels

30 SDI2 Power+ / R
Powers serial device interface 2 (SDI2) devices, such as keypads and expansion modules.

ZONEX Power
Powers ZONEX modules such as the D8125, D8128D, and D8129 connected through the B600.

5.3 Continuous power outputs

3 26 30
The continuous current draw for powered devices connected to Terminals 3, 26, and 30, and
the ZONEX connector must not exceed 1.4 A. Devices powered from these outputs operate at
12.0 VDC Nominal.

Notice!
Power Restricted for Fire and Combined Fire and Burglary Systems
Use the Fire system power formula, page 25 to calculate the current available for fire and
combined fire and burglary systems

5.4 Programmable power outputs

6 7 8
The power outputs at Terminals 6, 7, and 8 are programmed as Outputs A (1), B (2), and C
(3).
Assign each output an output type (Steady Alarm Bell, for example), when assigning it to an
area. You can assign an output to one or more areas.
The defaults are:
– Output A (1) - Terminal 6 - as a Steady Alarm Bell output
– Output B (2) - Terminal 7 - as a Pulsed Fire Bell output
– Output C (3) - Terminal 8 - as a Verification or Reset output for smoke detectors
The Program Entry Guide contains complete instructions for programming outputs. Refer to
the Bell Parameters section of the program to set the Fire Bell, Alarm Bell output responses
for outputs. Four annunciation patterns are available: Steady, Pulsed, California Standard, and
Temporal Code 3.
If Terminals 6, 7, and 8 do not provide the expected output, check:
– The Outputs section of the program for Outputs A (1), B (2), and C (3).
– The Bell Parameters section of the program to confirm that the Alarm and Fire Bell
responses are programmed for the expected duration and pattern.
– The Point Assignments section to confirm that each point is programmed for the
expected local response.

5.4.1 Terminals 6 and 7

6 7
When activated, Terminals 6 (Output A) and 7 (Output B), provide a positive (+) 12.0 VDC
Nominal power output. Use the power at Terminals 6 and 7 to power bells, siren drivers,
piezoelectric sounders, electronic horns, or other devices.
Programming determines the format of the output and the conditions that activate it.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels On-board outputs | en 25

When using Output A or Output B to activate notification appliance circuits in UL Listed fire
alarm applications, install a D192G.
Power restricted for Fire and Combined Fire and Burglary Systems
Fire systems are prohibited from using the battery for supplying alarm power. Use the fire
system power formula that follows to calculate the current available for fire and combined fire
and burglary systems.
Fire system power formula
Calculating the current available at Terminals 6 and 7 for fire and combined fire and burglary
systems:
1. Add together the current draws for all devices connected to Terminals 3, 26, and 30, and
the ZONEX connector. This is the total current required for the normal standby condition
(NSC).
2. The current available for NSC is 1.4 A. Subtract the NSC current required calculated in
Step 1 from the NSC current available, 1.4 A. The difference is the alarm current available
for Terminals 6 and 7.
In formula format: 1.4 A – NSC current required (Step 1) = Alarm current available
Refer to Approved applications for module or accessory current requirements

5.4.2 Terminal 8

8
Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts the
power at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or other
devices that reset by interrupting power.
Verify and reset Output C
The default program sets Output C (Terminal 8) as a verification and reset output. Refer to
Output Parameters and Point Assignments in the control panel Program Entry Guide for
instructions on programming verification and resetting outputs and points.
Performing a sensor reset at a keypad produces a five-second activation of verification and
reset outputs. The control panel ignores verification and resettable points during the five
seconds.

5.5 USB power

3
USB
In addition to connecting RPS or the Installer Services Portal programming tool (available in
Europe, Middle East, Africa, and China) to the control panel for programming, you can use the
USB port on the control panel to power USB-powered devices.
When enabled, the USB port provides 500 mA of 5 V power. The port draws the power from
the control panel. Make sure that there is enough power for all the powered devices you want
to connect to the system.
Enabling USB power:
4 Do one of the following:
Press the control panel RESET button 3 times.
Use the keypad Installer menu (refer to [7] USB Power).
The USB POWER STATUS LED lights when power to the USB is turned on.
You can disable USB at any time. Use the Installer menu or press the control panel RESET
button 3 times.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


26 en | Control panel board overview Control panels

6 Control panel board overview

BATTERY STATUS MOD-2


Off: Normal
On: Missing
Quick Flash: Low
Slow Flash:
Charging

MODULE RELEASE
Low 12.1 VDC Minimum system requirements for Classification in accordance with ANSI/SIA
CP-01-2010. UL Listed and Classified control unit Model B9512G and B8512G.
Load Shed 10.2 VDC Do not connect UL Listed and Classified keypad Model B942, B930, B925F, B926F, B921C,
to a receptacle B920, B915, D1255RB, D1256RB and D1257RB. UL Listed Local Bell.
controlled by
a switch. The equipment should be installed in accordance with the NFPA 70 (National Electrical
Code) and NFPA 72 (National Fire Alarm Code). MOD-1
1 CLASS 2 Depending on the application, the installation may need to be in accordance with one or
16.5 VAC 40 VA 60 Hz
more of the following UL standards: UL681, UL1076, UL1641 and C22.1, CEC, Part 1.

2 TRANSFORMER Use of a D185 is not suitable for remote station protected premises service where separate
transmissions circuits are required for fire, supervisory (when applicable) and trouble
signals.
All external connections except Terminal 5 (BATTERY(+) are inherently power limited. PWR+/R 30
3 + AUX POWER
Requirements for battery standby time might reduce allowable output.
POWER SUPPLY REQUIREMENTS A/Y 29
4 BATTERY ( - ) The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all Accessory Devices. For System Loading,
refer to the B9512G/B8512G UL Listing Document, ULLD. Auxiliary powered devices: 11.8 to 12.5 VDC

SDI2
Battery: Replace every 3 to B/G 28
5 BATTERY ( + ) The B9512G/B8512G Control Panel is UL Listed For CS, RS, L, AUX, Prop and Res Fire and Res, Prop,
5 years with one or two Cent. Stat, Local, and PS Con. Merc. Burg, MSV, BSV, Holdup, suitable as a dual line trans. sys.
Model D126 or D1218 12V Signaling means: DAC, Cell or IP
OUTPUT Lead Acid Batteries. COM/B 27
6
A (1) The system is intended to be checked by a Qualified Technician at least every 3 years. The types of initiating circuits the control
panel has been approved for are A, M, WF, SS. The types of signaling the control panel has been approved for are DAC, OT, NC,

SDI2
OUTPUT RevPol.
7 B (2)
WARNING! Refer to the system wiring diagrams in the B9512G/B8512G
ULLD and to the D125B Installation Instructions for compatible

SDIx
OUTPUT To prevent risk of shock,
8 disconnect AC power and smoke detectors. 2-wire Compatible Identifier “A”. Printed
C (3) communication lines before information describing proper installation, operation, testing,
servicing. maintenance, repair service and response to an alarm is to be
9 COMMON provided with this equipment. PWR+/R 26
ON-BOARD POINTS
WARNING!
Owner Instructions (P/N F.01U.307.371): Not to

SDIx
10 EARTH GROUND be removed by anyone except occupant. A/Y 25
Voltage Ranges: Open 3.7 - 5.0 VDC, Short 0.0 - 1.3 VDC, Normal 2.0 - 3.0 VDC
WARNING! WARNING!
Multi-Battery Incorrect wiring will 1k End-of-line-Resistors Required (P/N 15093130-004), Max Loop Current: 5 mA B/G 24
installation requires damage this
Model D122 or D122L equipment. Point 1 Point 2 Point 3 Point 4 Point 5 Point 6 Point 7 Point 8
Dual Battery Harness. Devices powered by
Improper installation any output must be COM/B 23
can be a fire hazard. supervised. 11 12 13 14 15 16 17 18 19 20 21 22

USB POWER B
STATUS A
L S
I E
N
K T POINT 1 COM POINT 2 POINT 3 COM POINT 4 POINT 5 COM POINT 6 POINT 7 COM POINT 8
USB ETHERNET ZONEX TMPR RESET
ZONEX TMPR

Callout ᅳ Description Callout ᅳ Description

1 ᅳ BATTERY STATUS LED 9 ᅳ Tamper switch connector location

2 ᅳ Holes to stabilize plug-in modules 10 ᅳ Zonex module connector location

3 ᅳ Plug-in module connectors 11 ᅳ Sensor loop terminals for points 1 to 8

4 ᅳ Plug-in module connector 12 ᅳ BASE-T LED (green)

5 ᅳ SDI2 wiring 13 ᅳ On-board Ethernet connector

6 ᅳ SDIx wiring (use as SDI or SDI2) 14 ᅳ LINK LED (yellow)

7 ᅳ Heartbeat LED (blue) 15 ᅳ USB connector

8 ᅳ RESET button 16 ᅳ USB POWER STATUS LED

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels System wiring diagrams | en 27

7 System wiring diagrams


Notice!
UL notifications
Add additional power using only a UL Listed 12.0 VDC regulated, power-limited power supply
such as the B520.
All terminals except Outputs A (1), B (2), and C (3) (Terminals 6, 7, and 8) are supervised.
For proper supervision, do not loop wire under terminals. Break the wire run to provide
supervision of connections.

Notice!
The installation document of the fire product shall specify that all wiring, including that to the
non-fire alarm equipment, shall be installed in accordance with the requirements of the
National Fire Alarm and Signaling Code, NFPA 72.

7.1 Power supply side wiring

BAT 2- CHGR-
BAT 2+ VAUX+
BAT 1- SUPV
BAT 1+ CHGR+

5 BATTERY STATUS
Off: Normal
On: Missing
Quick Flash: Low
Slow Flash:
Charging

Low 12.1 VDC


Load Shed 10.2 VDC
Do not connect
to a receptacle
controlled by
a switch.

1 CLASS 2
16.5 VAC 40 VA 60 Hz

2 TRANSFORMER

7 6 3 + AUX POWER
All exte
Require
POWER SUPPL
4 BATTERY ( - ) The Power S
refer to the B

8 9 5 BATTERY ( + )
Battery: Replace every 3 to
5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
OUTPUT
6
A (1) The system is intended
AUX PWR 10 OUTPUT
panel has been approv
RevPol.
7
ALARM TRIG B (2)
WARNING!
To prevent risk of shock,
COM 8
OUTPUT disconnect AC power and
C (3) communication lines before
SUPV IN servicing.
9 COMMON ON-BOARD POINTS
ALARM CKT Owner I
be removed by
10 EARTH GROUND

+ - WARNING!
Multi-Battery
WARNING!
Incorrect wiring will
Voltage Ranges: Open 3.7 - 5.0 VDC,
1k End-of-line-Resistors Required (P/N 15093130-004),
installation requires damage this
Model D122 or D122L equipment. Point 1 Point 2 Point 3 Point 4 Point 5 Point 6 Point 7 Point 8
Dual Battery Harness. Devices powered by
Improper installation any output must be
can be a fire hazard. supervised. 11 12 13 14 15 16 17 18 19 20 21 22
13
12
USB POWER B
STATUS L A
I S
N E
K T
USB ETHERNET POINT 1 COM POINT 2 POINT 3 COM POINT 4 POINT 5 COM POINT 6 POINT 7 COM POINT 8

11

Callout ᅳ Description Callout ᅳ Description

1 ᅳ D113 Supervision module, battery lead (if required 8 ᅳ To control panel SDI2 wiring
by local AHJ)

2 ᅳ Batteries 9 ᅳ D192G Notification appliance module

3 ᅳ D122/D122L Dual Battery Harness, as required 10 ᅳ To OUTPUT A (1) or OUTPUT B (2)

4 ᅳ To supervision point 11 ᅳ 560 Ω, 2 W EOL resistor (P/N: 15-03130-005)

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


28 en | System wiring diagrams Control panels

5 ᅳTransformer 12 ᅳ Listed audible signaling devices rated at 12.0 VDC


nominal (do not use vibrating type horns)

6 ᅳ B520 Auxiliary Power Supply Module 13 ᅳ To earth ground

7 ᅳ To powered devices

7.2 Input points wiring with D125B, D130, or D129


BATTERY STATUS
Off: Normal
On: Missing
Quick Flash: Low
Slow Flash:
Charging

Low 12.1 VDC


Load Shed 10.2 VDC
Do not connect
to a receptacle
controlled by
a switch.

1 CLASS 2
16.5 VAC 40 VA 60 Hz

2 TRANSFORMER

All exte
3 + AUX POWER Require
POWER SUPPL
4 BATTERY ( - ) The Power S
refer to the B
Battery: Replace every 3 to
5 BATTERY ( + ) 5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
OUTPUT
6
A (1) The system is intended
panel has been approv
OUTPUT RevPol.
7 B (2)
WARNING!

8
OUTPUT
To prevent risk of shock,
disconnect AC power and
1 Loop B+
C (3) communication lines before
servicing. 2 Loop B-
9 COMMON ON-BOARD POINTS
Owner I 3 Loop B-
be removed by
10 EARTH GROUND

WARNING! WARNING!
Voltage Ranges: Open 3.7 - 5.0 VDC, 4 Loop B+
Multi-Battery Incorrect wiring will 1k End-of-line-Resistors Required (P/N 15093130-004),
installation requires
Model D122 or D122L
damage this
equipment. Point 1 Point 2 Point 3 Point 4 Point 5 Point 6 Point 7 Point 8
5 Zone B
Dual Battery Harness. Devices powered by
Improper installation any output must be
can be a fire hazard. supervised. 11 12 13 14 15 16 17 18 19 20 21 22 6 Aux Power
7 Earth Ground
USB POWER B
A
8 Common
STATUS L
I S
N
K
E 9 Zone A
T
USB ETHERNET POINT 1 COM POINT 2 POINT 3 COM POINT 4 POINT 5 COM POINT 6 POINT 7 COM POINT 8
10 Loop A+
11 Loop A-
12 Loop A-
13 Loop A+

Sw. Aux Pwr 1


Zone B 2
Zone A 3
Pnl Common 4
Pnl Common 5
Loop B- 6
Loop A- 7
Loop B+ 8
Loop A+ 9
Earth Ground 10

Figure 7.1: Input wiring with a D125B and a D129

Callout ᅳ Description

1 ᅳ D125B Dual Class B Initiating Module

2 ᅳ To compatible UL listed two-wire smoke detectors. Refer to the D125B Installation Instructions for a listing
of compatible two-wire smoke detectors.

3 ᅳ D129 Dual Class A Initiation Circuit Module

4 ᅳ For wiring instructions, refer to the D129 Dual Class A Initiation Circuit Module Installation Instructions.

Notice!
The D129 must be mounted inside the enclosure with the control panel. The power for the
D129 module must be mounted within the same room no more than 20 ft (6 m) apart. The
interconnecting wires between the control panel and external power supply must be in
conduit.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels System wiring diagrams | en 29

Notice!
Use zero retard except for waterflow devices.
All external connections except Terminal 5 (battery positive) are power limited.
Optionally, for 24 V applications, use a UL 864 listed, regulated, power-limited 24 VDC power
supply with a D130 Relay Module. Refer to the D130 Installation Instructions for correct
wiring requirements.

7.3 Input points wiring with or without EOL resistors


Notice!
EOL resistors
For the dual EOL resistor circuit style order ICP-1K22AWG-10, package of 10 1.0 kΩ EOL
resistors.

2
1 NC
4
Point
COM

Callout - Description

1 - Point sensor loop terminals

2 - Normally closed device (contact)

3 - 1.0 kΩ resistor at device

4 - 1.0 kΩ resistor at EOL (end-of-line)

2
1
3
Point
COM

Figure 7.2: Single EOL (NC or NO)

Callout - Description

1 - Point sensor loop terminals

2 - Normally closed device (contact)

3 - Normally open device (contact)

4 - EOL Resistor – 1.0 kΩ (2.0 kΩ and No EOL optional)

Notice!
The No EOL option does not support the use of NO and NC contacts simultaneously.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


30 en | System wiring diagrams Control panels

7.4 SDI and ZONEX wiring


Notice!
Install Fire and Intrusion devices only on separate circuits. Refer to the ICP-SDI-9114
Installation Instructions.
All external connections except Terminal 5 (battery positive) are power limited.

MOD-2

MODULE RELEASE

MOD-1

PWR+/R 30
29

A/Y 29
28
SDI2

olice
ting B/G 28
27
2 2 3 3
SDI2

COM/B 27
26
1
ire
SDI2
SDIx

PWR+/R 26

A/Y 25
7
SDIx

B/G 24

COM/B 23

6
ZONEX 1

ZONEX TAMPER RESET


ZONEX TMPR

ZONEX 2

POPIT POPIT
4 In
+

Out
-

Aux
5
Gn

POPIT POPIT
4 In
+

Out
-

Aux
5 Gnd

Callout ᅳ Description Callout ᅳ Description

1 ᅳ B600 5 ᅳUp to 119 D9127U/T POPITs

2 ᅳ SDI keypads when configuring SDIx for SDI (refer 6 ᅳ ZONEX connection cable (P/N: F01U295103)
to System power/size) (included)

3 ᅳ Up to 8 D9210C Access Control Interface Modules 7 ᅳ Interconnect cable (P/N: F01U079745) (included)

4 ᅳ D8125 POPEX Modules

*The number of D8129 Octo-relay modules allowed for each ZONEX terminal on the B600 is limited by the number
of D8128D OctoPOPITs connected to the same terminal. Refer to the D8128D Installation Guide or the D8129
Operation and Installation Guide for detailed instructions.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels System wiring diagrams | en 31

7.5 SDI2 devices general system wiring

MOD-2

MODULE RELEASE

1 2 3 4
MOD-1

PWR+/R 30
29

A/Y 29
28
SDI2

olice
ting B/G 28
27

COM/B 27
26

ire 5 6 7
SDI2
SDIx

PWR+/R 26

A/Y 25
SDIx

B/G 24 9
COM/B 23

8 8 8

ZONEX TAMPER RESET


ZONEX TMPR

Callout ᅳ Description B9512G Capacity B8512G Capacity

1 ᅳ B208 59 9

2 ᅳ B299 6 1

3 ᅳ B308 59 9

4 ᅳ B426 or B450 2 2

5 ᅳ B520 8 4

6 ᅳ B810 or B820 1 1

7 ᅳ B901 32 8

8 ᅳ SDI2 keypads 32 16

9 ᅳ Configurable for SDI keypads and access control interface modules, or SDI2 devices

Notice!
Each SDI2 bus supports up to 99 devices.
The SDI2 power terminal (PWR+/R) is power limited. The SDI2 terminals are supervised.

7.5.1 SDI2 bus wiring recommendations


Use the following SDI2 bus wiring recommendations for SDI2 installation. The control panel
and SDI2 modules use the SDI2 bus to communicate with one another.
You can wire modules via home run, daisy chain, or single level T-tap anywhere on the SDI2
bus.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


32 en | System wiring diagrams Control panels

MOD-2

MODULE RELEASE

MOD-1
3

PWR+/R 30
29

A/Y 29
28
2 2 2
SDI2

olice
ting B/G 28
27

COM/B 27
26

ire
SDI2
SDIx

PWR+/R 26

A/Y 25
2 2
SDIx

B/G 24

COM/B 23
4
2 2

ZONEX TAMPER RESET 2 2


ZONEX TMPR

2
2

Callout ᅳ Description

1 ᅳ Control panel

2 ᅳ SDI2 device (module or keypad)

3 ᅳ Daisy chain wiring

4 ᅳ Single-level T-tapped wiring

5 ᅳ Home run wiring

Notice!
There can only be a difference of 2 volts (maximum) between the AUX power terminals of the
control panel or power supply and the device for the modules and keypads to work properly
under all conditions.

Maximum cable lengths


Follow these rules when wiring the SDI2 bus:
– The SDI2 bus requires the use of unshielded cable from 12 AWG to 22 AWG (0.65 mm to
2 mm).
– Refer to the SDI2 device or keypad documentation for the allowable maximum distance
from the control panel.
– Maximum overall cable lengths are listed in the following table:

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels System wiring diagrams | en 33

Cable capacitance Overall cable length Cable capacitance Overall cable length

pF/ft ft m pF/ft ft m

< 17 7500 2286 27 5185 1580

18 7500 2286 28 5000 1524

19 7350 2240 29 4828 1472

20 7000 2134 30 4700 1433

21 6666 2032 31 4516 1376

22 6363 1939 32 4400 1341

23 6086 1855 33 4242 1293

24 5800 1768 34 4100 1250

25 5600 1707 35 4000 1219

26 5385 1641 36 3800 1158


Table 7.1: Maximum cable length

Notice!
Use unshielded cable only.
Maximum capacitance of 140nF (140,000 pF) per system. Contact the wire manufacturer for
the capacitance ratings of the wire being used.

7.6 2-wire smoke wiring (D125B)

BATTERY STATUS
CCD 0x - 0xxxx - 000 © RADIONICS INC.

Off: Normal

PTC2 PTC1 On: Missing


Quick Flash: Low
Slow Flash:
Charging

Low 12.1 VDC


R2 R1 Load Shed 10.2 VDC
R13

Do not connect
R3
C1
R7
C3

C2

R4
R5
R6

to a receptacle

R21 R14 R11 controlled by


U1 a switch.

1 CLASS 2
R12
R9 16.5 VAC 40 VA 60 Hz

2 TRANSFORMER
R10 R22
All exte
3 + AUX POWER Require
RV1 RV4
RV3 POWER SUPPL
R8 4 BATTERY ( - ) The Power S
refer to the B
D125B

RV2 Battery: Replace every 3 to


1992

5 BATTERY ( + )
TB1/J1 5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
OUTPUT
6
A (1) The system is intended
panel has been approv
D125B 7
OUTPUT
B (2)
RevPol.

WARNING!
To prevent risk of shock,
1 2 3 4 5 6 7 8 9 10 OUTPUT disconnect AC power and
8
C (3) communication lines before
SWITCH ZONE ZONE PANEL B- A- B+ A+ EARTH servicing.
POWER B A COMMON LOOP LOOP LOOP LOOP GND 9 COMMON ON-BOARD POINTS
Owner I
be removed by

1 4 7, 9 10 10 EARTH GROUND
Voltage Ranges: Open 3.7 - 5.0 VDC,
WARNING! WARNING!
Multi-Battery Incorrect wiring will
5 6, 8
installation requires
Model D122 or D122L
Dual Battery Harness.
damage this
equipment.
Devices powered by
Point 1 Point 2
1k End-of-line-Resistors Required (P/N 15093130-004),
Point 3 Point 4 Point 5 Point 6 Point 7 Point 8
Improper installation any output must be
can be a fire hazard. supervised. 11 12 13 14 15 16 17 18 19 20 21 22

2
USB POWER B

3 STATUS L
I
N
A
S
E
K T
USB ETHERNET POINT 1 COM POINT 2 POINT 3 COM POINT 4 POINT 5 COM POINT 6 POINT 7 COM POINT 8

Callout ᅳ Description Callout ᅳ Description

1 ᅳ Switched auxiliary power from relay C of the control 6 ᅳ Supervised smoke detector to B LOOP negative
panel

2 ᅳ Supervised connection to Zone B power from an on- 7 ᅳ Supervised smoke detector to A LOOP negative
board point of the control panel

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


34 en | System wiring diagrams Control panels

Callout ᅳ Description Callout ᅳ Description

3 ᅳ Supervised connection to Zone A power from an on- 8 ᅳ Supervised smoke detector to B LOOP positive
board point of the panel

4/5 ᅳ Connection to common the control panel (one 9 ᅳ Supervised smoke detector to A LOOP positive
connection only)

7.7 Earth ground wiring


To help prevent damage from electrostatic discharges or other transient electrical surges,
connect the system to earth ground before making other connections. The icon shows the
earth ground terminal. Use a recommended earth ground reference, such as a grounding rod
or a cold water pipe. Make the connection using 14 AWG (1.8 mm) to 16 AWG (1.5 mm) wire.

Notice!
Do not use telephone or electrical ground
Do not use telephone or electrical ground for the earth ground connection. Do not connect
other control panel terminals to earth ground.

Caution!
Avoid electrostatic discharge
! Always touch the earth ground connection with the icon first, before beginning work on the
control panel.

7.7.1 Ground Fault Detect enable


To meet UL 864 requirements, enable Ground Fault Detect.
A ground fault is a circuit impedance to ground sufficient to result in the annunciation of a
trouble condition.
The control panel has a ground fault detection circuit that when enabled, detects ground
faults on Terminals 1 to 9 and 11 to 30.
If a ground fault condition occurs, the keypads annunciate a ground fault and control panel
transmits a trouble message.
When the control panel recognizes that the ground fault condition is corrected, and remains
corrected for between 5 to 45 consecutive seconds, the control panel clears the fault from the
keypad display and sends a restoral report.
The control panel detects ground fault at ≤ 300 Ω.
Enabling Ground Fault Detect and reports
4 In RPS or in the Installer Services Portal programming tool (available in Europe, Middle
East, Africa, and China), set the following parameters:
– PANEL WIDE PARAMETERS > Miscellaneous > Ground Fault Detection. Set to Enable.
– PANEL WIDE PARAMETERS > Report Routing > Burglar Reports > Trouble Report. Set to
Yes.
– PANEL WIDE PARAMETERS > Report Routing > Burglar Reports > Burg Restore (After
Trouble). Set to Yes.

7.7.2 Ground fault detection troubleshooting


The control panel requires -2.1 V decay to 0.
Measuring and comparing voltage for ground fault detection
1. Set your digital voltmeter (DVM) to measure VDC.
2. Connect the red DVM lead to control panel Terminal 10, and the black DVM lead to
Terminal 9.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels System wiring diagrams | en 35

3. Compare this voltage to the following table.

Control panel voltage at Terminals 9 and 10) Terminal potentially causing ground fault

~ 0 VDC 4, 9, 12, 15, 18, 21

~ 13.65 VDC 5, 6, 7, 8, 26, 30

~ 2.51 VDC 11, 13, 14, 16, 17, 19, 20, 22

~ 2.44 to 3.2 VDC 24

~ 10.9 to 11.2 VDC 25

~ 7.2 VDC 28

~ 5.8VDC 29

~ 7.35 VDC 1, 2

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


36 en | B925F Fire Keypad operating instructions Control panels

8 B925F Fire Keypad operating instructions

This keypad is a full-function system controller and Local Service Representative


annunciator. The illuminated keypad has a display and a
sounder that emits distinct condition tones to alert you Name
to fire alarm, fire trouble, or fire supervisory events as
they occur. In conjunction with the display and sounder, Address
seven status indicators provide the following system status
information as described below.
Required: Mount this document in view of the fire Phone
keypad.
Overview
Status indicators Fire Status indicators
The Status indicators provide a quick Alphanumeric display The Fire Status indicators provide
visual reference of the system status. a quick visual reference of the fire
Ready to arm system status.
Lights when the system is ready Fire
to turn on (arm). Lights when a fire alarm
On (armed) A1 Lobby condition exists; turns off when
Lights when the system is on GAS
System Ready all fire alarm points return to
(armed). normal.
Silenced
ACK
Lights when a fire alarm condition
is silenced; turns off when a
Gas SILENCE user presses the RESET button
Lights when a gas alarm exists. RESET or if another fire alarm condition
Power DRILL
appears.
Lights to indicate the control Supervisory
panel has AC power. Lights when any point
programmed as supervisory is
Fire function keys not normal; turns off when all
ACK. Press to acknowledge the system alarm or trouble condition. supervisory points return to
SILENCE. Press to silence fire alarm or trouble. normal.
RESET. Press to reset devices such as smoke detectors. Trouble
DRILL. Press and hold to initiate fire drill. Lights when a trouble condition
Navigation and number keys exists.
The keypad includes keys for navigating and entering passcodes: Intrusion function keys
PREV and NEXT. Use to scroll through menus or menu selections. ALL. Press to turn the system All On.
ENTER. Use to complete the entry of your passcode or other PART. Press to turn the system Part On.
numbers, or to answer Yes to a keypad request. BYPASS. Press to open the menu to bypass points.
backspace when you enter names and numbers. MENU. Press to open the keypad’s Main menu.
ESC. Use to exit from menus and functions, or use as a
backspace when you enter names and numbers.
Number keys. Use to enter passcodes or other numbers and
letters.

Operation
Normal operation
When in normal operation and off (disarmed), the keypad shows programmed idle text, such as *Fire System*, or System
Ready.
Fire Alarm operation
When a firm alarm occurs, the Fire indicator lights, and the keypad emits a pulsing high-pitched fire tone (____ ____ ____). The
tone sounds for the duration set by your security company. The keypad shows the first point that entered alarm and its area.
Press ACK to acknowledge the alarm. The keypad shows the next point in alarm, if applicable. Press SILENCE to silence the
alarm.
Fire Trouble operation
When a trouble condition occurs (such as wiring for a point is cut or AC power fails), the keypad sounder activates briefly
approximately every six seconds. The Trouble indicator lights and the keypad shows the highest priority trouble. Press ACK
to acknowledge the trouble. To view and acknowledge additional system or point troubles, press NEXT repeatedly.
Fire Supervisory operation
When a supervisory condition occurs, the sounder activates briefly approximately every six seconds. The Supervisory
indicator lights and the keypad shows a fire supervisory message. Press ACK to acknowledge the supervisory condition. To
view and acknowledge point supervisory conditions, press NEXT repeatedly.
Silence and reset
Alarm or Trouble silence. Press SILENCE and enter your passcode.
Detector reset. Press RESET and enter your passcode (if required). You can also use [CMD][4][7], or the Menu to
reset detectors.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels B926F Fire Keypad operating instructions | en 37

9 B926F Fire Keypad operating instructions

This keypad is a full-function system controller and Local Service Representative


annunciator. The illuminated keypad has a display and a
sounder that emits distinct condition tones to alert you Name
to fire alarm, fire trouble, or fire supervisory events as
they occur. In conjunction with the display and sounder, Address
seven status indicators provide the following system status
information as described below.
Required: Mount this document in view of the fire Phone
keypad.
Overview
Status indicators Fire Status indicators
The Status indicators provide a quick Alphanumeric display The Fire Status indicators provide
visual reference of the system status. a quick visual reference of the fire
Ready to arm system status.
Lights when the system is ready Fire
to turn on (arm). Lights when a fire alarm
On (armed) A1 Lobby condition exists; turns off when
Lights when the system is on GAS
System Ready all fire alarm points return to
(armed). normal.
Silenced
ACK
Lights when a fire alarm condition
is silenced; turns off when a
Gas SILENCE user presses the RESET button
Lights when a gas alarm exists. RESET or if another fire alarm condition
Power DRILL
appears.
Lights to indicate the control Supervisory
panel has AC power. Lights when any point
programmed as supervisory is
Fire function keys not normal; turns off when all
ACK. Press to acknowledge the system alarm or trouble condition. supervisory points return to
SILENCE. Press to silence fire alarm or trouble. normal.
RESET. Press to reset devices such as smoke detectors. Trouble
DRILL. Press and hold to initiate fire drill. Lights when a trouble condition
Navigation and number keys exists.
The keypad includes keys for navigating and entering passcodes:
PREV and NEXT. Use to scroll through menus or menu selections.
ENTER. Use to complete the entry of your passcode or other
numbers, or to answer Yes to a keypad request.
backspace when you enter names and numbers.
ESC. Use to exit from menus and functions, or use as a
backspace when you enter names and numbers.
Number keys. Use to enter passcodes or other numbers and
letters.

Operation
Normal operation
When in normal operation and off (disarmed), the keypad shows programmed idle text, such as *Fire System*, or System
Ready.
Fire Alarm operation
When a firm alarm occurs, the Fire indicator lights, and the keypad emits a pulsing high-pitched fire tone (____ ____ ____). The
tone sounds for the duration set by your security company. The keypad shows the first point that entered alarm and its area.
Press ACK to acknowledge the alarm. The keypad shows the next point in alarm, if applicable. Press SILENCE to silence the
alarm.
Fire Trouble operation
When a trouble condition occurs (such as wiring for a point is cut or AC power fails), the keypad sounder activates briefly
approximately every six seconds. The Trouble indicator lights and the keypad shows the highest priority trouble. Press ACK
to acknowledge the trouble. To view and acknowledge additional system or point troubles, press NEXT repeatedly.
Fire Supervisory operation
When a supervisory condition occurs, the sounder activates briefly approximately every six seconds. The Supervisory
indicator lights and the keypad shows a fire supervisory message. Press ACK to acknowledge the supervisory condition. To
view and acknowledge point supervisory conditions, press NEXT repeatedly.
Silence and reset
Alarm or Trouble silence. Press SILENCE and enter your passcode.
Detector reset. Press RESET and enter your passcode (if required). You can also use [CMD][4][7], or the Menu to
reset detectors.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


38 en | D1255RB operating instructions Control panels

10 D1255RB operating instructions

This keypad is a system controller and annunciator. The Local Service Representative
illuminated keypad has a 16-character vacuum fluorescent
display (VFD) and a sounder that emits distinct condition Name
tones to alert you to fire alarm, fire trouble, or fire supervisory
events as they occur. In conjunction with the VFD and the Address
sounder, four status LEDs provide the following system status
indications: Fire, Silenced, Supervisory, and Trouble.
Required: Mount this document in view of the fire Phone
keypad.
Overview
Status indicators
The Status indicators provide a quick visual reference of the system status.
Fire: Lights when a fire alarm condition exists; turns off when all fire alarm points return to normal.
Silenced: Lights after a fire alarm is silenced; turns off when a PIN and ESC is entered. This clears the alarm
or trouble memory from the keypad display, when all points are in a normal state.
Supervisory: Lights when any point programmed as supervisory is not normal; turns off when all supervisory
points return to normal.
Trouble: Lights when any system trouble or point trouble exists; turns off when the system and all points
return to normal.

Alphanumeric display Number keys


Use one or two in combination
with the COMMAND bar to
Built-in sounder 1 2 3 perform a function, or use to enter
The built-in sounder emits the a PIN before pressing the ENT key.
following warning tones: 4 5 6

Fire signal: pulsed, high-pitched 7 8 9 COMMAND bar


bell tone during fire alarm. Use in combination with one or
0 COMMAND
Trouble signal: two-tone warble two numeric keys to perform a
during a trouble event. function.
Invalid key buzz: buzz tone when
invalid key is pressed.
Keypad encoding tone: muted
beep tone as each key is
pressed.

Navigation keys
Use ESC/Menu to enter the command menu, to complete a command entry, or to return to idle text.
Use PREV to return to the previously viewed menu item.
Use NEXT/Acknowledge to acknowledge an alarm or off-normal condition, or to move to the next menu item.
Use ENT/Yes to complete a PIN entry, or to select a menu item.

Operation
Normal operation
When the system is operating normally and is disarmed, the display shows the programmed idle text. The default system
normal message is * FIRE SYSTEM *.
Fire Alarm operation
When an alarm occurs, the Fire LED activates, and the keypad emits a pulsing high-pitched fire tone. The tone sounds for a
pre-programmed length of time. A display message appears that describes the first point that entered an alarm. Press the
NEXT key to acknowledge the alarm. To view and acknowledge additional points that are in alarm, press NEXT repeatedly.
The display shows Ax ## FIRE ALARM (x = the area number; ## = the number of fire alarms in Area x).
Fire Trouble operation
When a trouble condition occurs (such as wiring for a point is cut, AC power fails, and so on), the keypad sounder activates
briefly approximately every six seconds. The Trouble LED illuminates and Ax ## FIRE TRBL or the highest priority system
trouble appears in the display. Press the NEXT key to acknowledge the trouble. To view and acknowledge additional system
or point troubles, press NEXT repeatedly.
Fire Supervisory operation
Fire Supervisory Operation. When a supervisory condition occurs, the sounder activates briefly approximately every six
seconds. The Supervisory LED illuminates and Ax ## FIRE SUPV appears in the display. Press the NEXT key to acknowledge
the supervisory condition. To view and acknowledge point supervisory conditions, press NEXT repeatedly.
Silence and reset
Alarm silence. Enter PIN (if required) and press ENT.
Trouble silence. Press the COMMAND bar and select 4.
Detector reset. Press the COMMAND bar and select 4 + 7.
Annunciating reset. Enter PIN (if required) and press ESC. This clears alarm or trouble memory from the keypad display,
when all points are in a normal state.

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels D1256RB operating instructions | en 39

11 D1256RB operating instructions

This keypad is a system controller and annunciator. The Local Service Representative
illuminated keypad has a 16-character vacuum fluorescent
display (VFD) and a sounder that emits distinct condition Name
tones to alert you to fire alarm, fire trouble, or fire supervisory
events as they occur. In conjunction with the VFD and the Address
sounder, four status LEDs provide the following system status
indications: Fire, Silenced, Supervisory, and Trouble.
Required: Mount this document in view of the fire Phone
keypad.
Overview
Status indicators
The Status indicators provide a quick visual reference of the system status.
Fire: Lights when a fire alarm condition exists; turns off when all fire alarm points return to normal.
Silenced: Lights after a fire alarm is silenced; turns off when a PIN and ESC is entered. This clears the alarm
or trouble memory from the keypad display, when all points are in a normal state.
Supervisory: Lights when any point programmed as supervisory is not normal; turns off when all supervisory
points return to normal.
Trouble: Lights when any system trouble or point trouble exists; turns off when the system and all points
return to normal.

Alphanumeric display Function keys


Use one or two in combination
with the COMMAND bar to
Built-in sounder perform a function, or use to enter
The built-in sounder emits the a PIN before pressing the ENT key.
following warning tones:
Fire signal. Pulsed, high-pitched
bell tone during fire alarm.
Trouble signal. Two-tone warble
during a trouble event.
Invalid key buzz. Buzz tone when
invalid key is pressed.
Keypad encoding tone. Muted
beep tone as each key is
pressed.

Navigation keys
Use ESC/Menu to enter the command menu, to complete a command entry, or to return to idle text.
Use PREV to return to the previously viewed menu item.
Use NEXT/Acknowledge to acknowledge an alarm or off-normal condition, or to move to the next menu item.
Use ENT to complete a PIN entry, or to select a menu item.

Operation
Normal operation
When the system is operating normally and is disarmed, the display shows the programmed idle text. The default system
normal message is * FIRE SYSTEM *.
Fire Alarm operation
When an alarm occurs, the Fire LED activates, and the keypad emits a pulsing high-pitched fire tone. The tone sounds for a
pre-programmed length of time. A display message appears that describes the first point that entered an alarm. Press the
NEXT key to acknowledge the alarm. To view and acknowledge additional points that are in alarm, press NEXT repeatedly.
The display shows Ax ## FIRE ALARM (x = the area number; ## = the number of fire alarms in Area x).
Fire Trouble operation
When a trouble condition occurs (such as wiring for a point is cut, AC power fails, and so on), the keypad sounder activates
briefly approximately every six seconds. The Trouble LED illuminates and Ax ## FIRE TRBL or the highest priority system
trouble appears in the display. Press the NEXT key to acknowledge the trouble. To view and acknowledge additional system
or point troubles, press NEXT repeatedly.
Fire Supervisory operation
Fire Supervisory Operation. When a supervisory condition occurs, the sounder activates briefly approximately every six
seconds. The Supervisory LED illuminates and Ax ## FIRE SUPV appears in the display. Press the NEXT key to acknowledge
the supervisory condition. To view and acknowledge point supervisory conditions, press NEXT repeatedly.
Silence and reset
Alarm silence. Press the Alarm Silence key to silence a fire alarm.
Trouble silence. Press the Trouble Silence key to silence a fire trouble.
Detector reset. Press the Detector Reset key to reset detection devices.
Annunciating reset. Press the Annunciator Reset key to clear all alarm, trouble, and supervisory messages when all points
are in a normal state.

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


40 en | Specifications Control panels

12 Specifications
Control panel power supply specifications

Voltage input Primary Terminals 16.5 VAC 40 VA class 2 plug-in transformer (D1640)
(power supply) 1
and 2

Secondary Terminals Use 12 VDC sealed lead-acid rechargeable battery (7 Ah, 18 Ah, or
4 38 Ah). The control panel supports up to 38 Ah of battery. If you
and 5 use two batteries, they must have the same capacity and you must
connect them using the D122/D122L.

Current Control Panel: Idle 190 mA; Alarm 265 mA


requirements Refer to the Current Rating Chart for Standby Battery Calculations section in the Control
Panels (B9512G/B8512G) Installation and System Reference Guide for the current draw
requirements of other system components.

Power outputs All external connections are power-limited except battery terminals.

Continuous 1.4 A maximum at 12.0 VDC nominal (continuous supply) total for all devices
Power and outputs including the ZONEX connection, the plug-in module connector,
Outputs and Terminals 3, 26, and 30.

Alarm Power 2.0 A maximum (1.4 A max for commercial fire) at 12.0 VDC nominal output for
Output all devices and outputs including the ZONEX connection, the plug-in module
connector, and Terminals 3, 6, 7, 26, and 30. Output can be steady or one of
three pulsed patterns depending on programming. Refer to Relays in the RPS
Help or in the Installer Services Portal programming tool (available in Europe,
Middle East, Africa, and China) Help.

Switched Terminal 1.4 A maximum at 12.0 VDC nominal output. Continuous output is
Aux Power 8 interrupted by Sensor Reset or alarm verification depending on
programming. Refer to Relays in the RPS Help, in the Installer
Services Portal programming tool (available in Europe, Middle East,
Africa, and China) Help, or in the Control Panels (B9512G/B8512G)
Program Entry Guide.

Fire and To comply with UL 985 and 864 listing standards for fire alarm systems
Fire/ (effective March 1, 1989), the total combined continuous and alarm current
Burglary draw for the system during alarm conditions must be limited to 1.4 A provided
Systems by the primary power supply (rectified AC). If current draw for the system
exceeds 1.4 A, remove connected devices until the current draw falls below
1.4 A. Then, connect the removed devices to an external power supply1 (such
as B520).
1
Requires a UL Listed power supply.

Minimum 10.2 VDC


operating
voltage

SDI bus SDI bus A: 9 VDC 4572 m (15000 ft) maximum


SDI bus B: 9 VDC 4572 m (15000 ft) maximum

SDI2 bus SDI2 bus A: 12 VDC nominal (7500 ft) maximum2

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Specifications | en 41

SDI2 bus B: 12 VDC nominal (7500 ft) maximum2

Network Built-in 10/100 Ethernet LAN (RJ-45 connector)

USB USB 2.0 full speed

Environmental Temperature: 0°C to +49°C (+32°F to +120°F)

Relative Maximum 93% non-condensing


Humidity:

Arming B940W, B942/B942W, B930, B921C, B920, B915/B915I, D1260, D1257RB, D1256RB, D1255/
stations D1255RB, Keyswitch

Point With 1.0 kΩ resistors Open - 3.7 to 5.0 VDC


thresholds Normal - 2.0 to 3.0 VDC
(Single EOL Short - 0.0 to 1.3 VDC
resistor circuit Short circuit current - 5 mA
style)
With 2.0 kΩ resistors Open - 4.1 to 5.0 VDC
On-board
Normal - 3.0 to 4.1 VDC
points 1 to 8
Short - 0.0 to 3.0 VDC
Short circuit current - 5 mA

No EOL Open - 2.6 to 5.0 VDC


Short - 0.0 to 2.4 VDC
Short circuit current - 5 mA

Point Dual EOL (1.0 kΩ + 1.0 kΩ) Short - 0 to 1.67 VDC


thresholds Open - 4.12 to 4.95 VDC
(Dual EOL on- Normal - 1.69 to 2.94 VDC
board points) Fault - 2.95 to 4.10 VDC
Short circuit current - 5 mA

Compatible B8103 Universal Enclosure, D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack
enclosures Resistant Enclosure, BATB-40 and BATB-80 Battery Boxes.

12.1 Wire requirements


Terminal label Terminal description Requirements

1 AC 18 AWG to 14 AWG (1.02 mm to 1.8 mm)

2 AC 18 AWG to 14 AWG (1.02 mm to 1.8 mm)

3 + AUX POWER Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on current

4 BATTERY - Bosch supplied wire lead, included with control panel.

5 BATTERY +

6 Output A (1) Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on current
7 Output B (2)

8 Output C (3)

9 COMMON

10 EARTH GROUND 16 AWG to 14 AWG (1.5 mm to 1.8 mm)


Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001
42 en | Specifications Control panels

11 POINT 1 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

12 POINT 1/2 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

13 POINT 2 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

14 POINT 3 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

15 POINT 3/4 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

16 POINT 4 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

17 POINT 5 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

18 POINT 5/6 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

19 POINT 6 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

20 POINT 7 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

21 POINT 7/8 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

22 POINT 8 Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on loop
resistance less than 100 Ω

ZONEX ZONEX Bosch supplied wire, included with the optional B600

23 SDIx COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on peripheral
device current

24 SDIx DATA BUS B 22 AWG to 14 AWG (0.65 mm to 1.8 mm)

25 SDIx DATA BUS A

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Control panels Specifications | en 43

26 SDIx POWER Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on peripheral
device current

27 SDI2 COMMON Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on peripheral
device current

28 SDI2 DATA BUS B 22 AWG to 14 AWG (0.65 mm to 1.8 mm)

29 SDI2 DATA BUS A

30 SDI2 POWER Terminal accommodates 22 AWG to 14 AWG (0.65 mm to


1.8 mm), use appropriate wire size based on peripheral
device current

Bosch Security Systems B.V. UL Installation manual 2020-06 | 07 | F.01U.304.001


44 | Specifications Control panels

2020-06 | 07 | F.01U.304.001 UL Installation manual Bosch Security Systems B.V.


Bosch Security Systems B.V.
Torenallee 49
5617 BA Eindhoven
Netherlands
www.boschsecurity.com
© Bosch Security Systems B.V., 2020

You might also like