AEML - Aarey B9 B10 - VB
AEML - Aarey B9 B10 - VB
AEML - Aarey B9 B10 - VB
New New Ph. IDMT Ph. Inst E/F. IDMT E/F. Inst New TCC
Sr.No SW No FEEDER NAME IED Name New Relay
Location Panel No CT Ratio reference
Ip>(In) tIp> (Curve) I>(In) tl> I>>(In) tl>> IEp>(In) tIEp> (Curve) IE>>(In) tlE>> IE>>>(In) tlE>>>
ARH1B9TR1O, 7SJ85-P1J495420
33 KV GIS TRAFO Appendix 3.1 and
1 SW NO 91 1 1.1 0.1 (VI) 6 0.1 - - - - 0.4 0.1 - - and 800/5
FEEDER ARH1B9TR1D 7UT85-P1F494041
3.2
33 KV GIS LINE FEEDER-
2 SW NO 92
1
ARH1B9OG1 2 2 0.1 (VI) 6 0.12 - - 0.4 0.05 (NI) 0.6 0.1 - - 7SJ85-P1J495420 800/5 Appendix 3.3
ARH1B9CP1A, 7SJ85-P1J495420
3 SW NO 93 33 KV GIS CAPACITOR-1 3 0.75 0.2 (VI) 7 0.1 - - 0.2 0.05 (NI) 0.3 0.1 - - and 800/5 Appendix 3.4
ARH1B9CP1B 7SJ81-P1J678412
AAREY - Board 9
4 SW NO 94 33 KV GIS INCOMER-1 ARH1B9IC1 4&5 1 0.15 (NI) 2.4 0.5 2.4 0.3 - - 0.3 0.5 1 0.15 7SJ85-P1J714839 2500/5 Appendix 3.5
Appendix 3.2, 3,3
5 SW NO 95 BUS COUPLER ARH1B9BC 6 0.8 0.12 (NI) 2.4 0.2 2.4 0.1 - - 0.22 0.35 0.6 0.15 7SJ85-P1J714839 2500/5
and 3.4
33 KV GIS LINE FEEDER-
6 SW NO 97
2
ARH1B9OG2 8 2 0.1 (VI) 6 0.12 - - 0.4 0.05 (NI) 0.6 0.1 - - 7SJ85-P1J495420 800/5 Appendix 3.3
33 KV GIS LINE FEEDER-
7 SW NO 98
3
ARH1B9OG3 9 2 0.1 (VI) 6 0.12 - - 0.4 0.05 (NI) 0.6 0.1 - - 7SJ85-P1J495420 800/5 Appendix 3.3
8 SW NO 99 33 KV GIS INCOMER-2 ARH1B9IC2 10 & 11 1 0.15 (NI) 2.4 0.5 2.4 0.3 - - 0.3 0.5 1 0.15 7SJ85-P1J714839 2500/5 Appendix 3.5
ARH1B9CP2A, 7SJ85-P1J495420
9 SW NO 100 33 KV GIS CAPACITOR-2 12 0.75 0.2 (VI) 7 0.1 - - 0.2 0.05 (NI) 0.3 0.1 - - and 800/5 Appendix 3.4
ARH1B9CP2B 7SJ81-P1J678412
10 SW NO 101 33KV GIS LINE FEEDER-4 ARH1B9OG4 13 2 0.1 (VI) 6 0.12 - - 0.4 0.05 (NI) 0.6 0.1 - - 7SJ85-P1J495420 800/5 Appendix 3.3
33 KV GIS LINE FEEDER-
11 SW NO 102
133 KV GIS LINE FEEDER-
ARH1B10OG1 1 2 0.1 (VI) 6 0.12 - - 0.4 0.05 (NI) 0.6 0.1 - - 7SJ85-P1J495420 800/5 Appendix 3.3
12 SW NO 103
2
ARH1B10OG2 2 2 0.1 (VI) 6 0.12 - - 0.4 0.05 (NI) 0.6 0.1 - - 7SJ85-P1J495420 800/5 Appendix 3.3
ARH1B10CP1A, 7SJ85-P1J495420
13 SW NO 104 33 KV GIS CAPACITOR-1 3 0.75 0.2 (VI) 7 0.1 - - 0.2 0.05 (NI) 0.3 0.1 - - and 800/5 Appendix 3.4
ARH1B10CP1B 7SJ81-P1J678412
14 SW NO 105 33 KV GIS INCOMER-1 ARH1B10IC1 4&5 1 0.15 (NI) 2.4 0.5 2.4 0.3 - - 0.3 0.5 1 0.15 7SJ85-P1J714839 2500/5 Appendix 3.5
AAREY - Board 10
18 SW NO 110 33 KV GIS INCOMER-2 ARH1B10IC2 10 & 11 1 0.15 (NI) 2.4 0.5 2.4 0.3 - - 0.3 0.5 1 0.15 7SJ85-P1J714839 2500/5 Appendix 3.5
ARH1B10CP2A, 7SJ85-P1J495420
19 SW NO 111 33 KV GIS CAPACITOR-2 12 0.75 0.2 (VI) 7 0.1 - - 0.2 0.05 (NI) 0.3 0.1 - - and 800/5 Appendix 3.4
ARH1B10CP2B 7SJ81-P1J678412
20 SW NO 112 33KV GIS LINE FEEDER-5 ARH1B10OG5 13 2 0.1 (VI) 6 0.12 - - 0.4 0.05 (NI) 0.6 0.1 - - 7SJ85-P1J495420 800/5 Appendix 3.3
Page 1 of 14
Adani Electricity Mumbai Limited (AEML)
Substation Aarey 33kV
Board 9 and 10
Device type: 7SJ85
Product code: 7SJ85-DAAA-AA0-0AAAA0-AC0111-12113B-BAA000-000AC0-CB1BA1-EB0
Short product code (TNS): P1J495420
Location 20MVA Transformer Feeder
Function group Function Function block Settings category Setting internal name Setting name Settings group1 Unit
Power system
General
PhsSeq Phase sequence ABC
Meas.point I-3ph 1
CT 3-phase
General CTConnect CT connection 3-phase + IN
Tracking Tracking active
MuIndex Measuring-point ID 1
CT phases ARtg Rated primary current 800.0 A
ARtgSec Rated secondary current 5A
VI 3ph 1
General
Rated values ARtgObj Rated current 800.00 A
VRtgObj Rated voltage 33.00 kV
VARtgObj Rated apparent power 20.00 MVA
Power-system data SysNeutPt Power-sys. neutral point grounded
Measurements PQSign P, Q sign not reversed
Inrush detect.
Mode Mode on
StrValAMax Operat.-range limit Imax 31.25 A
BlkIrshCWA Blocking with CWA yes
BlkIrsh2Ha Blocking with 2. harmonic yes
StrVal2Ha 2nd harmonic content 15.00%
CrossBlk Cross-blocking no
CrossBlkTm Cross-blocking time 0.06 s
TrFltRec Start flt.rec yes
50/51 OC-3ph-B1
Definite-T 1
Mode Mode off
Definite-T 2
Mode Mode on
BlkOp Operate & flt.rec. blocked no
InrushDet Blk. w. inrush curr. detect. no
StrVal Threshold 2 A
OpDlTmms Operate delay 0.10 s
Definite-T 2
Mode Mode off
Inverse-T 1
Mode Mode off
Adani Electricity Mumbai Limited (AEML)
Substation Aarey 33kV
Board 9 and 10
Device name: 7UT85
Product code: 7UT85-DAAA-AA0-0AAAA0-AC0111-12113B-BAA000-000AC0-CC5BA1-CF0
Short product code (TNS): P1F494041
Location 20MVA Transformer Feeder
Function group Function Function block Settings category Setting internal name Setting name Settings group1 Unit
General
Device HzRtg Rated frequency 50 Hz
ActSG Activat. of settings group settings group 1
Power system
General
PhsSeq Phase sequence ABC
Meas.point I-3ph 1
CT 3-phase
General CTConnect CT connection 3-phase + IN-
separate
MuIndex Measuring-point ID 1
CT phases ARtg Rated primary current 800.0 A
ARtgSec Rated secondary current 5A
CT IN ARtgIN Rated primary current 800.0 A
ARtgSecIN Rated secondary current 5A
Meas.point I-3ph 2
CT 3-phase
General CTConnect CT connection 3-phase + IN-
separate
MuIndex Measuring-point ID 2
CT phases ARtg Rated primary current 1600.0 A
ARtgSec Rated secondary current 5A
CT IN ARtgIN Rated primary current 1600.0 A
ARtgSecIN Rated secondary current 5A
Transformer side 1
General
Rated values VARtgObj Rated apparent power 20.00 MVA
VRtgObj Rated voltage 33.00 kV
ARtgObj Rated current 800 A
SideNumber Side number Side 1
49 Th.overl. 1
Mode Mode off
Transformer side 2
General
Rated values VARtgObj Rated apparent power 20.00 MVA
VRtgObj Rated voltage 0.42 kV
ARtgObj Rated current 1600 A
Inrush detect.
Mode Mode off
50/51 OC-3ph-A1
87N REF - To be configured to REF protection
Mode Mode on
BlkOp Operate & flt.rec. blocked no
StrVal Threshold 0.50 A
Slope 0.01
OpDlTmms Operate delay 0 s
50N/51N OC-1ph-B1 - To be used to configure Standby Earth Fault protection.
Definite-T 1
Mode Mode on
BlkOp Operate & flt.rec. blocked no
MeasMethod Method of measurement fundamental comp.
StrVal Threshold 35 A
OpDlTmms Operate delay 0.10 s
Inverse-T 1
Mode Mode on
BlkOp Operate & flt.rec. blocked no
InrushDet Blk. w. inrush curr. detect. no
StrVal Threshold 1 A