Technical Specification for
Feeder Pillar Panel
(Distribution panel without ACB)
Specification no – GN101-03-SP-18-01
Prepared / Reviewed by Approved by: Rev Date
Hemanshi Kaul Devender Sharma R1 January 12,2010
___________________________________________________________________________________________
Page 1 of 25
GN101-03-SP-17-01
Index
1. Scope of supply ............................................................................................... 3
2. Codes & Standards .......................................................................................... 3
3. Service Conditions ........................................................................................... 3
4. Feeder Pillar Configuration ............................................................................. 4
5. Panel Construction .......................................................................................... 4
6. Fuse Base ......................................................................................................... 7
7. Operational requirements................................................................................ 7
8. Name Pate and Finish ...................................................................................... 7
9. Compacted feeder pillars. ............................................................................... 8
10. Testing and Inspection .................................................................................... 8
11. Packing and Delivery ....................................................................................... 9
12. Deviation ……………………………………………………………………………..9
List of Annexure……………………………………………………………………..……..10
___________________________________________________________________________________________
Page 2 of 25
GN101-03-SP-17-01
1. Scope of supply
This shall include Design, manufacture, testing at manufacturers works before
dispatch, packing, delivery of material to BSES Stores and submission of documents
to purchaser.
2. Codes & Standards
The equipment shall confirm to this specification and latest revision of following codes
with all amendments:-
Title Indian Standard
2.1 IS 5039 Specification for distribution pillars below 1000v AC
2.2 IS 13947 part 2 Low Voltage switchgear
2.3 IS 8623 Specification for low voltage switchgear
2.4 IS 12063 Classification of degrees of protection provided by
enclosures of electrical equipment
2.5 IS 13703 Low voltage HRC fuses
2.6 IS 5 Color of ready mixed paints
2.7 IS 191 Specification for copper
2.8 IS 5082 Wrought Aluminum & Al alloy plates & sheets for electrical
applications
3. Service Conditions
The feeder pillar panel shall be designed to work satisfactorily under following service
conditions:-
Title Indian Standard
3.1 Supply Voltage 3 phase neutral, AC 433Volt +/-10%
3.2 Supply Frequency 50 Hz +/- 5%
3.3 Location of panel Outdoor, on foot path or roadside
3.4 Pollution Heavily Polluted and Dry
3.5 Humidity 90% maximum
3.6 Ambient Temperature Average 40 Deg C, Maximum 50 Deg C
3.7 Incoming supply to feeder From distribution transformer or Main feeder
pillar panel pillar panel
3.8 Seismic Zone 4
___________________________________________________________________________________________
Page 3 of 25
GN101-03-SP-17-01
4. Feeder Pillar Configuration
The feeder pillar panel shall have following configuration:-
4.0 Feeder Pillar Type Incoming feeder ( Circuit Outgoing feeder ( Circuit
ways ) & Cable size ways ) & Cable size
4.1 A-1 , 8-Way 2 X 400A TP fuse / cable 6 X 250A TP fuse / cable
size 4CX300Sqmm size 4CX150Sqmm
4.2 B-1, 5-Way 1 X 400A TP fuse / cable 4 X 250A TP fuse / cable
size 4CX300Sqmm size 4CX150Sqmm
4.3 C-1, 7-Way 1 X 250A TP fuse / cable 5 X 100A TP fuse
size 4CX150Sqmm 1 X 250A TP fuse /
cable size 4CX95Sqmm
5. Panel Construction
The feeder pillar panel construction shall confirm to following features:-
5.0 Panel Construction Free Standing floor mounted with steel frame,
Welded Construction Continuous welding from inside, Spot welding not
acceptable.
5.1 Ingress Protection IP 55 as per IS 12063
class for enclosure
5.2 Material Galvanized sheet Steel CRCA
5.3 Sheet Steel Thickness 3mm - Support frames
2mm Galv. - Covers, Doors & Canopy
5.4 Base frame for 8 Way 3mm MS Channel 50mm height painted in Black
& 7 way panel Color
5.5 Bottom holes on four Oval Shape, for grouting bolts
Sides
5.6 Pedestal for 5 way Of height 400mm with side covers of FRP or
Galvanized MS painted in black
5.7 Cable entry From Bottom only
5.8 Lifting Lug 2 nos lug welded on top
5.9 Canopy on top With minimum 10 Deg C slope extended 50mm
outside panel front and rear
___________________________________________________________________________________________
Page 4 of 25
GN101-03-SP-17-01
5.10 Door type for front & Centre Opening double leaf with insulating rubber grip
rear access handle
5.11 Double leaf doors Right hand side leaf can be opened only after left
hand side leaf
5.12 Door Hinges Minimum three anti theft type hinges
MS screw -3mm dia & 8mm length
Tight fit brass tube – 100mm ID, 12.7mm OD & 20mm
length
5.13 Door Opening angle Min 120 Deg
5.14 Padlocking facility For Front and Rear door by total 4 nos L- drop
arrangement. 2 nos front door and 2 nos rear door.
5.15 Locking facility on By L- drop type arrangement
door
5.16 Tower bolts at top and On left hand side door
bottom of door
5.17 External hardware Galvanized steel nut and bolts
5.18 Phase & Neutral bus Aluminum grade 19501 ( H2 )
as per IS 5082
5.19 Bus bar color coding Heat shrinkable tape of color Red , Yellow , Blue &
for R, Y , B and Black respectively.
Neutral
5.20 Bus Bar size in mm Phase Neutral
5.20.1 8 - Way 50X10 mm 50X10 mm
5.20.2 5 - Way 50X6 mm 50X6 mm
5.20.3 7 - Way 50X6mm 50X6 mm
5.21 Bus for 8 – Way Bolted type removable link to be provided at middle of
all the phases and neutral bus bar to adapt two
incomers from separate source.
5.22 Earth Bus at panel 25X6mm Aluminum
bottom
5.23 Bus bar arrangement Horizontal, with R phase bus at top
5.24 Neutral bus bar With holes for connection incoming and outgoing
cables up to 300Sqmm
5.25 Bus Bar support SMC / DMC, 1100v Grade
insulators
5.26 Bus Bar phase FRP / Acrylic insulating sheet
barriers
___________________________________________________________________________________________
Page 5 of 25
GN101-03-SP-17-01
5.27 Cable size
4CX300Sqmm cable
Incoming for 8 way
panel
5.28 Incoming for 5 & 7- 4CX300Sqmm cable for 5 Way & 4CX150Sqmm
Way panel cable for 7 Way panel
5.29 Outgoing for 8 way 4CX150Sqmm cable
panel
5.30 Outgoing for 5 & 7- 4CX150Sqmm cable for 5 Way & 4CX95Sqmm cable
Way panel for 7 Way panel
5.31 Terminals for cables Al grade 19501 ( H2) as per IS 5082, with galvanized
steel nut bolts size M10 & two plane washers + spring
washers & spacers
M16 size nut bolt for incomer of 8 way panel
5.32 Terminal shape ‘ z ‘ Strips , 2nos per terminal
5.33 Z Strip dimensions 8 way panel incomer 50 X 10 mm
supported on
insulators 5 & 7 way panel incomer 50X6 mm
All outgoing feeders 40X6mm
5.34 Ease of taking current Possible with Z Strip terminal
reading with open
clamp type ammeter
5.35 Gland plate at panel Galvanized MS, 3mm thick for multi core cable
bottom
5.36 Cable supports Non ferrous clamps at bottom
5.37 Cable termination 300mm minimum
clearance from gland
plate
5.38 Earth studs on both With M10 galvanized steel nut bolts
side of panel bottom
5.39 Flexible earth Flexible PVC Cu wire 2.5Sqmm green color
connection to doors
5.40 Panel maximum Width Depth Height
dimensions in mm
8 - Way 1225 650 1650
5 - Way 900 550 1850
7- Way 1050 650 1650
5.41 Holder for lamp for 8 230v Incandescent lamp controlled through 2amp
way panel SPMCB
5.42 Small power socket 5/15 amp 3pin socket controlled through 16amp
for 8 way panel SPMCB
___________________________________________________________________________________________
Page 6 of 25
GN101-03-SP-17-01
6. Fuse Base
The equipment shall have all the following features –
6.1 Fuse base connection to main bus By bus bar and not by flexible jumpers
bar
6.2 Size 2as per IS 13703 for 400A
6.3 Current rating of fuse base at 8 way & 5 way 400A,
maximum ambient temperature 7 way – 250A
50Deg C
6.4 Fuse base current carrying part Plated copper as per IS191
6.5 Fuse base insulating material DMC / Porcelain
6.6 Make For DMC - GE, Siemens, L& T, ABB
For porcelain – Sample to be
approved by BSES.
6.7 Fuse base mounting screws With insulating caps
6.8 FRP Barriers for open live parts 1.6mm thick white colored sheet
6.9 HRC fuse pullers – 1 no / Type of Suitable for 400A, 250A & 100A HRC
fuse fuse
7. Operational requirements
7.1 Clearance between phase to Minimum 25mm
phase and phase to earth
7.2 Continuous rated operating 433 volt +/- 10 %
voltage
7.3 Power frequency high voltage 2000Volt
withstand capacity for one minute
7.4 Insulation resistance value for Minimum 100MOhm with 500V
phase and neutral bus bar Megger
7.5 Temperature rise above ambient As per IS 13947_1
45 Deg C
8. Name Pate and Finish
8.1 Name plate On front door top left side showing
1) Purchase name and PO number
2) Manufacturer name
3) Month & year of manufacturing
4) No of ways
5) Property of BSES
8.2 Labels for incoming and outgoing Sticker type labels inside panel door
feeders
8.3 SLD SLD to be screen printed inside the
front door.
___________________________________________________________________________________________
Page 7 of 25
GN101-03-SP-17-01
8.4 Marking for panel earth stud Green letter ‘E’, on riveted AL label
8.5 Danger board in English and local Red color background with black
language, riveted on doors lettering on 1.6mm thick Al plate
8.6 Surface preparation for painting Sand blasting or 7 tank process
8.7 Painting Powder coated grade A polyester paint
with min thickness 60 microns
8.8 Paint shade Shade – 538 as per IS:5 – Post office
red
8.9 Fluorescent strip painting on 50mm wide horizontal strip of
panel fluorescent paint around panel in the
middle of panel
9. Compacted feeder pillars.
9.1 Door type for front access Centre Opening double leaf with
insulating rubber grip handle only front
side.
9.2 Rear side No door at read side. Panel to be
access only from front.
9.3 All other constructions shall be as per above mentioned construction
9.4 Use of compacted feeder pillars Where sufficient space at rear side is
not available due to space constraints
at site.
10. Testing and Inspection
The equipment shall have all the following features –
10.1 Type test Only type tested components – fuse
base, insulators and aluminum bus
bar shall be accepted
Test reports as per relevant IS to be
submitted by vendor
10.2 Test report validity Valid for last 5 years
10.3 Acceptance and routine test 1) Visual inspection, dimension
(Inspection test witness by checks and paint thickness check.
purchaser) 2) Bill of material check
3) Wiring checks.
4) Insulation resistance test for main
and auxiliary circuit
5) High voltage test on main and
auxiliary circuit
6) Operational check
10.4 Tolerances on panel dimensions Maximum +/- 5mm
___________________________________________________________________________________________
Page 8 of 25
GN101-03-SP-17-01
10.2.9 No negative tolerance on bus bar dimensions and bus bar clearances
10.2.10 Prototype panel to be approved by BSES
11. Packing and Delivery
11.1 Packing protection Against Shocks, vibration and
corrosion
11.2 Packing identification labels To show purchaser name, PO
number, Manufacturer serial
number
11. 3 Handling instruction To be marked on packing boxes
12. Deviation
Deviation to specification to be submitted in writing by vendor. Bidder to submit copy
of specification and GTP along with company seal and signature on each page.
___________________________________________________________________________________________
Page 9 of 25
GN101-03-SP-17-01
List of Annexure
Annexure A – Guaranteed Technical Particular
Annexure B – General arrangement drawing for 8 Way Panel
Annexure C – General arrangement drawing for 5 Way Panel
Annexure D – General arrangement drawing for 7 Way Panel
Annexure E – General arrangement drawing for compacted type 8 Way Panel
___________________________________________________________________________________________
Page 10 of 25
GN101-03-SP-17-01
ANNEXURE A Guaranteed Technical Particulars
Bidder to submit hard copy duly filled and signed along with techno commercial offer.
Bidder to submit separate GTP for each type of feeder pillar panel
S. BRPL / BYPL
Particulars Vendor Data
No Requirement
Name
1 Manufacturer Address
Contact no.
2 Type of Panel Offered 8-way , 5-Way & 7-Way
3 Main bus bar rating As per clause 4.1 to 4.3
Quantity
Rating in amp
4 No. of Incoming feeders
HRC fuse type / make
Quantity
Rating in amp
5 No. of Outgoing feeders
HRC fuse type / make
Galvanized CRCA sheet
6 Panel construction
steel
MinIP55- ingress protection
7 Panel enclosure class
Galvanized sheet steel 2MM min. for cover, doors
8
thickness & canopy
3mm MS channel 50mm
Base frame for 8 way &
9 height painted in black
7 way only
color
___________________________________________________________________________________________
Page 11 of 25
GN101-03-SP-17-01
Of height 400mm with side
10 Pedestal for 5 Way covers of FRP or Galv. MS
painted in black.
Centre opening double leaf
Door type for front &
11 with insulating rubber grip
rear access
handle
Minimum three anti theft
12 Door Hinges
type hinges
13 Padlocking facility Provided
L- drop type locking 2 nos of each front and
14
arrangement at door rear door
15 External steel hardware Galvanized nut & bolts
Aluminum grade 19501 (
16 Phase & neutral bus bar
H2 ) as per IS5082
Heat shrinkable tape of
Bus bar color coding for
17 Red, Yellow, Blue & Black
R, Y , B & neural.
color
18 Bus bar size in mm
Phase= 50X10MM
8 Way
Neutral= 50X10MM
Phase= 50X6MM
7 Way
Neutral= 50X6MM
Phase= 50X6MM
5 Way
Neutral= 50X6MM
18 Earth bus size 25x6mm Aluminum
Main bus bar short
19 circuit withstand ……………In KA for 1sec
capacity
Main bus bar maximum
20 above ambient of 45 deg C
temperature rise
Bus bar support
21 SMC / DMC, 1100V grade
insulators
Al grade 19501 ( H2) as
per IS 5082, with
Terminals suitable for galvanized steel nut bolts
22
cables size size M16 & two plane
washers + spring washers
& spacers
___________________________________________________________________________________________
Page 12 of 25
GN101-03-SP-17-01
Incoming cable for 8 & 5
23 4CX300Sqmm
way panel
Incoming cable for 7
24 4CX150Sqmm
way panel
Outgoing cable for 8 & 5
25 4CX150Sqmm
way panel
Outgoing cable for for 7
24 4CX95Sqmm
way panel
Z' strips supported on
25 Terminal shape
insulator, 2per terminal
8 way panel 50x10mm
Z Strips dimensions
26
7 & 5 way panel 40x6mm
Gland plate at panel Galv. MS 3mm thick for
27
bottom multi core cable
Cable termination
28 300mm minimum from
clearance
gland plate
Earth studs on both side With M10 galvanized steel
29
of panel bottom nut bolts
Panel maximum
30
dimensions in mm
Width - 1225, Depth - 650,
8 - Way
Height - 1650
Width - 1050, Depth - 650,
7- Way
Height - 1650
Width - 900, Depth - 550,
5- Way
Height - 1850
Holder for 230V Controlled through 2amp
31
Incandescent Lamp SPMCB
5/15 amp 3pin socket Controlled through 16amp
32
power socket SPMCB
Fuse base size as per Size 1 for 250A
33 IS13703
Size 2 for 400A
Current rating of fuse
base at max. ambient
8 & 5 -WAY - 400A
34 temperature 48deg C
7- way - 250A
Fuse base current
carrying part
Fuse base current Plated copper as per IS
35
carrying part 191
___________________________________________________________________________________________
Page 13 of 25
GN101-03-SP-17-01
36 Fuse base material DMC/ Porcelain
For DMC - GE, Siemens,
37 Make L&T or ABB
For Porcelain - -----------
HRC fuse pullers - 1no/ Suitable for 400A, 250A
38
Type of HRC Fuse and 100A HRC fuse & link
Phase- phase &
Clearance between live
39 parts minimum 25mm
Phase -earth
Continuous rated
40 433volt +/- 10%
operating voltage
High voltage withstand
41 2000V at 50Hz for 1 min.
capacity
Insulation resistance Minimum 100Mohm with
42
Ph- Ph & Ph-earth 500v Meggar
43 Labels & name plates As per specification
Surface preparation for Sand blasting or 7 tank
44
painting process
Power coated grade A
45 Painting polyester paint min.
thickness 50 microns
46 Shade - Post office red Shade - 538 as per IS:5
Fluorescent paint strip 50mm wide painted in the
47 on panel middle of panel
Foundation Bolts Required
48
___________________________________________________________________________________________
Page 14 of 25