Technical Specifications For Power Distribution Board (PDB)
Technical Specifications For Power Distribution Board (PDB)
Technical Specifications For Power Distribution Board (PDB)
1. SCOPE
The Power cable for incoming & outgoing feeders shall be taken care
by the Department .
a) The contactors shall be air break type, equipped with three main
contacts and required numbers of NO & NC auxiliary contacts, the
main contacts of particular contactor shall have AC-3 or AC-4 ratings
as specified in data sheet.
b) Unless otherwise specified, the coils of the contactor shall be suitable
for operation on 240volts, single phase AC supply and shall work
satisfactorily between 65 to 110% of the rated value.
• LED indication lamps for indication of ‘Supply ON’ (for R/Y/B phases),
‘ CB Off/CB On/Trip-OC/Trip-SC/Trip-EF As required.
d. Bus Bars
i. The main Bus bars shall be of high conductivity copper of uniform
cross–section throughout their length. The standard busbars and
supporting arrangement shall be designed and tested to withstand
a short circuit fault level of 50 kA for 1 second.
ii. The Busbars should consist of 1 set of hard drawn, high
conductivity, TPN (neutral equally rated to phase bars),
iii. The maximum operating temperature of busbars including joints,
at design ambient temperature shall not exceed 75ºC for normal
operating condition & 100ºC for short circuit condition.
iv. The bus bars shall be rigidly supported at equal intervals to
withstand the stresses due to full short circuit and also to take
care of thermal expansion.
v. Only high tensile electro galvanized cadmium plated bolts, nuts
and washers shall be used. The washers shall be spring and plain
type. Both vertical and horizontal busbars shall be capable of
withstanding dynamic & thermal stresses of specified short circuit
currents for 1 sec.
vi. Bus chamber should be steel clad having front and rear bolted
covers.
vii. The Bus bar supported at sufficient intervals on non-hygroscopic,
non-inflammable SMC supports.
viii. All busbars shall be encased throughout with colour coded
insulated sleeving of 1100V grade and joints shall be fitted with
insulated shrouds. Red, yellow & blue colour shall be used for
phase busbars and black colour shall be used for neutral busbars.
Main busbars should be of full length as that of the panel.
ix. Vertical bus bars for feeding individual feeder should be full height
of the panel. Sufficient clearance should be maintained in the bus
chamber for proper cooling of the busbar. Busbar should be
extensible type to facilitate future extensions.
x. Removable links shall be provided on feeders to permit isolation of
the neutral bus bar.
xi. A separate GI horizontal earth bar of adequate cross section shall
be provided all along the length of the switchboard with necessary
terminating arrangement for connecting external earth conductor.
The earth bus shall be rated for faults withstand capacity of 50KA
for 1 sec having dimension 40mm × 6mm.
e. Panel wiring:
i. The entire control wiring is done with high grade bright copper
annealed multi strand PVC, FRLS flexible heat resistant
switchboard wires of minimum size 1.5 mm² Grey wire for control
circuits and 2.5 mm² for CT circuits, all doors are earthed with the
help of 1.5 sq.mm yellow green wire. Electronic Card signal wiring
is done with 1 sq.mm Shielded wire preferably be enclosed in
plastic channels or neatly bunched together. The wiring shall with
proper lugs. All wires and cable should have proper ferrule
numbers for easy identification.
ii. All wire termination except for Elmex type terminal blocks shall be
made with ring/fork tongue compression type connectors. Wires
shall not be tapped in between terminal points. Type of lug shall
suit relevant application.
iii. The terminal block shall be grouped and segregated according to
circuit functions and different voltage levels, and shall have 20%
spare terminals. Individual terminals in each block in each group
shall be serially numbered in accordance with the drawings. Such
numbering shall be legible, permanent and indelible. Terminal
block for CTs shall be provided with drop out facility for testing
purposes for shorting and shall be segregated from other
terminals. Sufficient clear space shall be provided between gland
plate and terminal blocks.
iv. Inside the cubicles, the wiring for control, signalling, protection
and instrument circuits shall be done with BIS approved , PVC
insulated, flame retardant type, copper conductor multistrand wire
to be used.
v. The insulation grade shall be 650volts. The wiring shall be
enclosed in plastic channels or neatly bunched together.
f. Instrument Transformer:
a) Current Transformer shall generally confirm to IS-2705,
b) Current transformer for instrument shall have an accuracy class
1.0 and accuracy limit factor less than 5.0.
c) For all outgoing and incomer feeder, suitable rating of CT as
indicated in BOM with resin cast wound to be provided for
measuring the feeder current through analogue meter and for
connection to current transducer for all outgoing feeders.
g. Control Transformer:
For feeding control supply to the auxiliary systems and contactors
coils, control transformers with resin cast wound type to be
provided as indicated in the BOM. Control transformer shall be
provided with HRC fuses on primary side and miniature circuit
breakers with auxiliary contact on the secondary side.
h. Earthing:
1. All cubicles shall be connected to an earth bus bar running
throughout the length of the switchboard. The earth bus bar size
shall be minimum 50x6 mm² GI. Provision shall be made to
connect the same to the plant earthing grid at two ends.
2. Vertical earth bus shall be provided for earthing of all feeders.
3. All doors and movable parts shall be connected to the earth bus
with flexible copper connections.
4. All non-current carrying metallic parts of the equipment and
components shall be earthed.
5. The main Earth bar available in cable duct in OPF sub-station to
be connected in the PDB panel by running earth bus along the
cable tray with suitable welding. Further running earth bus along
the cable tray up to the Electrical Plate Drier.
i. Painting:
LT switchboards shall be painted and the finishing shade shall be
light grey having shade No. 631 as per IS: 5.
All unpainted steel parts shall be cadmium plated or suitably
treated to prevent rust formation. If these parts are moving
elements, then they shall be greased.
1. The vendor shall have to supply detailed design and dimension drawing for
foundation/Erection of the PDB. Necessary site data as required will be
provided by the purchaser if required.
2. Construction of minor foundation and other civil engineering work as per
design drawing shall be carried out by the vendor
3. The vendor shall indicate in the erection drawing the requirement of power
and various services facilities like water any special requirement, the same
will be provided by the purchaser.
4. The scope of vendor includes unloading, alignment and positioning of the
PDB in the place provided by the purchaser
5. Erection work will be carried out by the vendor, necessary manpower and all
the tools etc are to be brought by the vendor on returnable basis duly
making entry in the main gate.
6. Engineers of the vendor engaged in erection, commissioning work may
make their own lodging arrangement.
7. Vendor shall follow IE rule/other safety guidelines by department, apprise
themselves of it and shall not jeopardize theirs and other`s safety while
working.
DATA SHEET
Bidder’s
Sl. No. Particulars of equipment Units Purchaser’s requirement Response /
compliance
GENERAL DATA
3. System Frequency Hz 50
7. Location Indoor
RATING
13. One minute Power frequency KV 2.5 KV / min for Power Circuit and
withstand voltage 1.5 KV / min for control circuit.
CONSTRUCTION
BUS BAR
37. SFU
A Make L&T/SIEMENS
38. CT