Copper Network Card: Installation Instructions
Copper Network Card: Installation Instructions
Technical data
2 - Stand offs 1 - Wire link Using the Copper Network card a maximum of up to 31 Control
1 - Spade tag panels can be connected in a secure network loop, with up to
This copper network card is used to allow data to pass 1.2Km cable distance between panels dependent on cable
between control panels in a Vigilon Compact networked fire type.
system. The card must be plugged into the Master Control
board MCB of the panel in a dedicated slot 'CARD 2'. The card
has terminals to accept external network wiring.
A bank of dual-in-line switches on the card allow setting of
& The Network card must be plugged into
CARD 2 slot.
address number and baud rate.
Wire link to Network card
new
Card installation Master Control Board (MCB)
0V L2- L2+ 0V L1- L1+
If a second loop card is to be
installed, then first fit the network
card into slot marked 'CARD 2'
PB1A PB2 PB1B
on the MCB using the standoffs
supplied and then fit the second Terminals for network
loop card into the network card. connections
N/C N/C
Cable screen
N/C
N/C
Where a multicore cable is being
used ensure the unused cores
(cores without signal) are 0V L2- L2+ 0V L1- L1+ 0V L2- L2+ 0V L1- L1+
connected to 0V.
PB1A PB1B PB1A PB1B
The cable screen must Connections for Network card in Connections for Network card in
Card 2 Card 2
be connected to an earth
terminal in the backbox, MASTER CONTROL BOARD MASTER CONTROL BOARD
Dual in line (DIL) switches DIL switches location on the Network card
"
Component side
12345
63 on on on on on on 678
On Off
Address Baud
- factory settings
WEEE Directive:
At the end of their useful life, the packaging,
At the end of their useful life, the packaging, product and batteries should be
product and batteries should be disposed of disposed of via a suitable recycling centre.
via a suitable recycling centre and in Do not dispose of with your normal household waste.
accordance with national or local legislation. Do not burn.
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
oblication to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk
by Honeywell Telephone +44 (0) 116 246 2000 Fax (UK): +44 (0)116 246 2300