Generador Perkins A65pe3
Generador Perkins A65pe3
Standby Prime
Volt Code Voltage Winding Connection Phase Power Factor Hz Amps Standby
Model kW / kVA kW / kVA
A65PE3 61 480 / 277 HI WYE 3 0.8 60 98 65 (81) 58 (73)
A65PE3 62 460 /266 HI WYE 3 0.8 60 102 65 (81) 58 (73)
A65PE3 63 440 / 254 HI WYE 3 0.8 60 107 65 (81) 58 (73)
A65PE3 64 240 / 139 LOW WYE 3 0.8 60 196 65 (81) 58 (73)
A65PE3 65 220 / 127 LOW WYE 3 0.8 60 213 65 (81) 58 (73)
A65PE3 66 208 / 120 LOW WYE 3 0.8 60 226 65 (81) 58 (73)
A65PE3 67 240 / 120 2 DELTA 1 1.0 60 271 65 (81) 58 (73)
A65PE3 51 415 / 240 HI WYE 3 0.8 50 - - -
A65PE3 53 380 / 220 HI WYE 3 0.8 50 - - -
A65PE3 55 220 / 127 LOW WYE 3 0.8 50 - - -
A65PE3 57 220 / 110 2 DELTA 1 1.0 50 - - -
Stand-By ratings are continuous electrical service during the interruption of normal power. No overload capacity is
specified at these ratings.
Prime ratings available with variable loads are continuous, 10% overload capacity for one hour in twelve hours periods.
Both ratings per BS 5514, DIN 6271, ISO-3046
Many industrial, commercial and residential voltages are available
ALTERNATOR ESPECIFICATIONS A65PE3
Type Four pole, revolving field Four pole, revolving field, direct coupled to
Rotor Insulation Class H engine flywheel, provides excellent
7Temperature Rise 150°C Standby alignment.
Material Epoxy resin Insulation is of class H, ready to be used
Line-To-Line Harmonic Factor (Max) 5% on harsh environments where sea spray,
Telephone Interference Factor (Tif) 1% sand and chemical corrosion are existing
Voltage Regulator Solid State factors.
Cooling Self-ventilated and drip proof Voltage regulator provides Volts/Hertz
Bearing 1 each, pre-lubed compensation to improve the motor starting
Coupling Direct, Flexible Disc capabilities, therefore support the engine
Load Capacity (Standby) 100% handling transient loads.
Overload Capacity (Prime) 110% Dynamically balanced rotor, with damper
Voltage Regulation winding, help dissipate transient voltage
No Load To Full Load ±1 % interference during load variations.
One Step Load Acceptance The windings have a 2/3 pitch in order to
Per NFPA 110 100% reduce the harmonic content of voltage.
Robust mechanical structure permits easy
access to connections.
ENGINE ESPECIFICATIONS
Manufacturer PERKINS Robust industrial grade PERKINS diesel
Model 1104D-E44TG1 engine, for reliable endurance.
Bore 4.1 in (105 mm)
Direct fuel injection system and swirl intake
Stroke 5.0 in (127 mm)
ports combine for a low fuel consumption and
Number Of Cylinders 4
excellent transient response.
Piston Displacement 268.5 in3 (4.4L)
Compression Ratio 16.2:1 Cylinder Head provides superior airflow
Cooling System Type Liquid through specially designed intake manifold
Engine Type In-Line – 4 Cycle
ports, large valves and seats resulting in
superior engine performance in torque
Aspiration Turbocharged after cooled Tu
reserve, fuel consumption and emissions. .
Engine Crankcase Vent System Closed
Cylinder Replaceable Liner Dynamically Balanced Crankshaft, with
EPA Tier 3 induction-hardened journal surfaces
Governor Type Electronic significantly increases wear life.
Frequency Regulation Belt Fan Drive provides superior noise and
No Load To Full Load 0.5% vibration reduction.
Air Cleaner Dry Element
Powered by : Perkins
STANDARD EQUIPMENT
ENGINE - Housing & Flywheel metering facilities via the * Running Time Meter
- Air Cleaner - Charging Alternator 12VDC LCD display, accessed via * LED and LCD alarm
- Fuel Pump - Battery Kit & Battery Rack the SCROLL push button indication
- Fuel Filter GENERATOR - Ac Voltmeter
- Oil Pump - Synchronous, Brush-less - Ac Ammeter GENERAL
- Full Flow Oil Filter - Four Pole - Frequency Meter - Steel Skid Base Frame
- Jacket Water Pump - Single Bearing - Vibration Shock Mounts - Industrial Muffler
- Thermostat and Housing - Direct Coupled With Flex - Engine Shutdowns - Rain Cap
- Exhaust Manifold Dry - Class H Insulation * High Water Temperature - Lifting Points
- Oil Cooler - Drip-Proof Construction * Low Oil Pressure - Acrylic Enamel Paint
- Blower Fan & Fan Drive CONTROL PANEL - Engine Gauges
- Radiator - Unit Mounted - Digital type * Battery Voltmeter
- Electric Starting Motor 12VDC - Automatic Mains Failure module * Water Temperature
- Turbocharged provides engine and electrical * Oil Pressure
INSTALLATION AND APPLICATION DATA A65PE3
W L
General configuration for reference only, do not use these dimensions for installation purposes. Contact your
local dealer for certified drawings.
All Specifications and Materials are subject to change without prior notice.