j1939 Modbus TCP MN67215 ENG 2 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

Industrial Electronic Devices

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 3 of 21
Industrial Electronic Devices Page 3 of 21

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for
each individual application, legal and safety regulation. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit
switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who
have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated
by personnel untrained. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the
possibility of damage.

CE CONFORMITY
The declaration is made by us. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 4 of 21
Industrial Electronic Devices Page 4 of 21

CONNECTION SCHEME:

Figure 2: Connection scheme for HD67215


ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 5 of 21
Industrial Electronic Devices Page 5 of 21

Figure 2: Connection scheme for HD67215-A1


ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 6 of 21
Industrial Electronic Devices Page 6 of 21

CHARACTERISTICS:

The HD67215 is Gateway Modbus TCP from/to J1939 line.


It allows the following characteristics:

Electrical isolation between Modbus TCP and J1939;


Mountable on Rail DIN;
Temperature range -40°C to 85°C.

POWER SUPPLY:

Recommended Power Supply


VDC VAC
24v 12v

Caution: Not reverse the polarity power .


VDC VAC

Vmin Vmax Vmin Vmax

8v 35v 8v 19v

HD67215 HD67215-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 7 of 21
Industrial Electronic Devices Page 7 of 21

CONFIGURATION:

The “Gateway J1939 to Modbus TCP Slave”, allows a J1939 network to communicate with a Modbus TCP network.

You need Compositor SW67215 software on your PC in order to perform the following:
Define that the J1939 frame of the J1939 are reading from Modbus.

USE OF COMPOSITOR SW67215:

To configure the Gateway, use the available software that runs with
Windows, called SW67215. It is downloadable on the site
www.adfweb.com and its operation is described in this document.

When launching the SW67215 the right window appears


(Fig. 2):

Figure 2: Main window for SW67215

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 8 of 21
Industrial Electronic Devices Page 8 of 21

NEW PROJECT / OPEN PROJECT:

The “New Project” button creates the folder which contains the entire device configuration.
A device configuration can also be imported and exported:

To clone the configurations of a Programmable “J1939 to Modbus TCP Slave” Gateway in order to configure another device in the
same manner, it is necessary to maintain the folder and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to duplicate the project folder with another name
and open the new folder with the button “Open Project”;
When a new project is created or an existent project is open, it will be possible to access the various configuration section of the
software:

o Set Communication;
o Receive J1939;
o Define J1939;
o Transmit J1939;
o Define J1939.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 9 of 21
Industrial Electronic Devices Page 9 of 21

SET COMMUNICATION:

This section defines the fundamental communication parameters of two


buses, J1939 and Modbus TCP.

By pressing the “Set communication” button from the main window for
SW67215 (Fig. 2) the window “Set Communication” appears (Fig. 3). It is
divided in two sub-section, one for the J1939 (CAN Bus) and the other for
the Modbus TCP (Ethernet):

In the fields “Baud Rate”, the velocity of J1939 bus id defined;


In the field “Time out Data” insert a time, when this time is
elapsed the data isn’t reliable and in the Modbus register you can
read “FFFF”;
The field “Modbus register” insert a number of register, in this
register you can visualize if the data is reliable, if 1 the data is ok,
if 0 the data is oldest of the time inserted in the time out data;
If the field “Peer to Peer” is cheked the gateway accept any ID
that have the PGN inserted in the section “Receive J1939”;
If the field “Filter FECA” is checked when the FECA PGN arrives the
gateway puts the values in Standby. If the time, expressed in
milliseconds and written at the right side of “Filter FECA”, is
elapsed and there aren’t arrived the frames of Transport Protocol
the gateway put the data of FECA into Modbus Registers.
Otherwise if the Transport Protocol arrives before the time is
elapsed the gateway put his data into Modbus Registers discarding
the data of FECA. When this field is checked the values aren’t
updated when the FECA frame arrive but there is an offset of xx
ms. You can use this function if there is only one J1939 device in
the network; Figure 3: “Set Communication” window
If “Send frame every xx ms” is checked the gateway sends the
J1939 frames defined in “Transmit J1939” section every xx ms.
Otherwise a frame is sent in J1939 when a modbus register is
written into the gateway;
If the field “Enable Remote Request” is checked it is possible to use the “Remote Request”. To use this, is necessary to insert in the
four fields under the four Modbus Registers.
In the field “IP” insert the IP address that you want to give at slave Modbus;

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 10 of 21
Industrial Electronic Devices Page 10 of 21
In the field “SubNet Mask”, insert the SubNet Mask of your Network;
If the field “Use Gateway” is checked in the fields under it is possible to insert the IP address used for going out to the net;
In the field “Port”, insert the number of port that Modbus TCP use;
If the field “Enable write J1939 on request” is checked, the field “Write J1939 frame” in “Transmit J1939 frame info” is enabled. If this
field is not checked, the device send a J1939 frame for every written register. Otherwise it is possible to select when to send the J1939
frame.
If the field “Enable Fun 1, 2, 5 and 15” is checked, the Modbus function for the status are enabled. It is possible to use the status (bit)
to read or write the data of J1939. The definition of the register are fixed and start from 1 (or 2 if the Master Modbus has the offset)
for the number of byte that you use per 8.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 11 of 21
Industrial Electronic Devices Page 11 of 21

RECEIVE J1939:

Figure 4: “Receive CAN frame” window

By pressing the “Receive J1939” button from the main window for SW67215 (Fig. 2) the window “Receive CAN frame” appears (Fig. 4).

The means of the fields of the table are:


In the field “Data Page” insert the data page, the value is 0 or 1 (usually is 0)
In the field “PGN” insert the PGN of the data you would to read from modbus to J1939. (in the J1939 protocol the PGN is an
identifier);
In the field “Source Address” insert the address of the device that send the frame.
If the field “Multi Frame” is checked the frame use transposrt protocol functions;
In the field “StartByte” insert the byte wich you would start read, this field is enable only when the field multi frame is checked;
In the field “N° Byte” insert the number of byte you would read, for example your start byte is 20 an N°byte is 10, you can read the
byte from 20 to 30.
If the field “Cancel Data” is checked and the Modbus Register in the section “set communication” is 0 the gateway when the data is
oldest of the time inserted in the “time out data” you visualize “FFFF” in the Modbus registers of this PGN.
In the field “Mnemonic” the description for the frame is defined.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 12 of 21
Industrial Electronic Devices Page 12 of 21

DEFINE RECEIVE J1939

By pressing the “Define J1939” button, near “Receive J1939” from the main
window for SW67215 (Fig. 2) the window “Receive CAN Frame Info” appears
(Fig. 5):

In the field Correlated there are the list of frames J1939 who you
inserted in Receive J1939 Section
In the field MODBUS there are the modbus words.
In the field Index MODBUS there is the address who contain the
Modbus word.
In the field Selecet Frame Byte you select the position of the byte.

For example:

Click on the frame, insert the valid address in the field Index MODBUS, select
the byte position(Byte 1 in high MODBUS byte and Byte 2 in low MODBUS
byte), click the “New” button, in the field MODBUS appears the names of
modbus words (The first word is name IND MB 0, second IND MB 1, third Ind
MB 2 and so on).

Figure 5: “Receive CAN frame info” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 13 of 21
Industrial Electronic Devices Page 13 of 21

TRANSMIT J1939

Figure 6: “Transmit J1939 frame” window

By pressing the “Receive J1939” button from the main window of SW67215 the window “Receive J1939 frame” appears (Fig. 6):

In the right scenario:

In the field “Priority” insert the priority of the frame, in J1939 protocol is a number among 0,1,2,3,4,5,6,7. The number 0 is the
highest priority and 7 is the lowest;
In the field “Data Page” insert the data page, in the J1939 protocol is 0 or 1;
In the field “PGN” insert the PGN of the data you would to write from modbus to J1939. (in the J1939 protocol the PGN is an
identifier);
In the field “ID device” you insert the ID of device that send the frame.
In the field “Mnemonic” the description for the frame is defined.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 14 of 21
Industrial Electronic Devices Page 14 of 21

DEFINE TRANSMIT J1939

By pressing the “Define J1939” button from the main window for SW67215
(Fig. 2) the window “Transmit J1939 Frame Info” appears (Fig. 7):

In the field Correlated there are the list of frames J1939 who you
inserted in Transmit J1939 Section;
In the field MODBUS there are the modbus words;
In the field Index MODBUS there is the address who contain the
Modbus word;
In the field Selecet Frame Byte you select the position of the byte;
With the field “Write J1939 Frame” it is possible to decide when to
send the J1939 frame. If a modbus word has written “False ”in
this field, the J1939 frame is not sent immediately but it is sent
when another word have this field “True”. It is possible to have
this function only if the field “Enable write J1939 on request” in
the “Set Communication” window is checked.

For example:

Click on the PGN, insert the valid address in the field Index MODBUS, select
the byte position (B1 in high MODBUS byte and B2 in low MODBUS byte),
click the “New” button, in the field MODBUS appears the names of modbus
words (The fist word is name IND MB 0, second IND MB 1, third Ind MB 2
and so on).

Figure 7: “Transmit J1939 frame info” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 15 of 21
Industrial Electronic Devices Page 15 of 21

REMOTE REQUEST
In the “Priority and Destination” Register you have to indicate the Priority of the request in the high byte of the register (usually this value is
equal to 6) and the Address of the Destination Device in the low byte of register.
In the “PGN Part 1” you have to indicate the first two byte of the PGN while in the “PGN Part 2” Register you have to indicate, in the high
byte of register, the third byte of the PGN.
In the “Source Address” Register you have to indicate the Source Address of the request in the high part of the register.

Only when you write the “Souce Address” register the request will be send to the J1939 network.

For example if you want to request the PGN 0x00FEE5 at device with address 5 you have to write:
1st reg = 0x0605
2nd reg = 0xE5FE
3rd reg = 0x0000
4th reg = 0x0100

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 16 of 21
Industrial Electronic Devices Page 16 of 21

UPDATE DEVICE TCP

Section “UP Date Device TCP” (Fig. 8):


In order to load the parameters after they are set, Insert the IP of
your Device, and click on “Ping button”. After you click on “Next”
button, in the window that appears, you select which object
update.

Figure 8: Update Device TCP

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 17 of 21
Industrial Electronic Devices Page 17 of 21

UPDATE DEVICE SERIAL

Section “Update device Serial” (Fig. 9):


In order to load the parameters or update the firmware in the
gateway, follow these instructions:

• Turn off the Device;


• Connect the Null Modem Cable Form your PC to the
Gateway;
• Insert the Boot Jumper (see the Fig. 1 for more info);
• Select COM port and press the “Connect” Button;
• Turn on the device;
• Press the “Next” Button;
• Select which operations you want to do. Can select only
Firmware or only Project or both;
• Press the “Execute update firmware” to start the upload;
• When all the operation are “OK” turn off the device;
• Disconnect the Boot jumper;
• Disconnect the RS232 Cable;
• Turn on the device.

Figure 9: Update Device Serial

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 18 of 21
Industrial Electronic Devices Page 18 of 21

CHARACTERISTICS OF THE CABLES:

The connection from RS232 socket to a serial port (example one from a personal computer), must be made with a Null Modem cable (a
serial cable where the pins 2 and 3 are crossed).
It is recommended that the RS232C Cable not exceed 15 meters.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 19 of 21
Industrial Electronic Devices Page 19 of 21

MECHANICAL DIMENSIONS:

Figure 10: Mechanical dimensions scheme for HD67215-A1 Figure 10: Mechanical dimensions scheme for HD67215

ORDER CODE:

Order Code: HD67215 - Gateway – J1939 to Modbus TCP


Order Code: HD67215-A1 - Gateway – J1939 to Modbus TCP (Different Enclosure)

ACCESSORIES:

Order Code: AC34107 - Null Modem Cable Fem/Fem DSub 9 Pin 1,5 m

Order Code: AC34114 - Null Modem Cable Fem/Fem DSub 9 Pin 5 m

Order Code: AC34001 - Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V AC

Order Code: AC34002 - Rail DIN - Power Supply 110V AC 50/60Hz – 12 V AC

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 20 of 21
Industrial Electronic Devices Page 20 of 21

DISCLAIMER

All technical content within this document can be modified without notice. The content of the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead,
it should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and human health, which could otherwise be caused by
inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about recycling this
product, please contact your local city office, your household waste disposal service or the shop where you purchased the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual J1939 to Modbus TCP
Document code: MN67215_ENG Revision 1.015 Page 21 of 21
Industrial Electronic Devices Page 21 of 21

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at
www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
1) Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the
request, you need to provide detailed information about the problem.
2) Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs
billed to us will not be accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks.
If the product is no longer under warranty, you will receive a repair estimate.

PRODUCTS AND RELATED DOCUMENTS:

Part Description URL


HD67121 Gateway CANopen / Canopen www.adfweb.com?product=HD67121
HD67002 Gateway CANopen / Modbus - RTU www.adfweb.com?product=HD67002
HD67004
Gateway CANopen / Modbus – Ethernet TCP www.adfweb.com?product=HD67004