Star Exercise 4A

Purpose:
Determine the settings of protective devices.
Evaluate the coordination curves
Run PD Sequence-of-Operation for various locations and evaluate the results.

Procedure

Size Phase \ Ground CTs


Given the protection determine the size \ setting of PDs for phase and ground protection.
Use the standard \ recommended guidelines for determining the settings.

Low Voltage Motor Protection

LV_Mtr1
100 HP
0.46 kV
FLA: 110 A
LRC: 625.2%
1800 rpm
Hot Stall Time: 25 sec
Cold Stall Time: 30 sec
No Load Acceleration Time: 7 sec
Full Load Acceleration Time: 9 sec

PDs:
MCP: Cutler Hammer, HMCP-F
Overload Heater: Allen Bradley Bulletin520 Type J (Curve - Typical Class 20)

LV_Mtr2
30 HP
0.46 kV
FLA: 40 A
LRC: 600%
3600 rpm
Hot Stall Time: 18 sec
Cold Stall Time: 20 sec
No Load Acceleration Time: 3 sec
Full Load Acceleration Time: 5 sec

PDs:
Thermal Magnetic: Cutler Hammer, HFD
Overload Heater: General Electric, CR324

ETAP Workshop Notes ©1996-2009 Operation Technology, Inc. Page 1 of 3


Star Exercise 4A

Medium Voltage Motor Protection

MV-Mtr1
500 HP
4 kV
FLA: 60.58
LRC: 650%
3600 rpm
Hot Stall Time: 18 sec
Cold Stall Time: 23 sec
No Load Acceleration Time: 6 sec
Full Load Acceleration Time: 8 sec

PDs:
Relay (Siemens, 7SJ600: 49, 50)
400 A Contactor/Starter

MV_Mtr2
1500 HP
4 kV
FLA: 185.5 A
LRC: 510%
1800 rpm
Hot \ Cold Stall Time: 18 \ 23 sec
NL \ FL Acceleration Time: 6 \ 8 sec

PDs:
R-rated fuse (Westinghouse CLS)
Motor Relay (GE, 469: 49, 50, 50G)
400 A Contactor/Starter

Transformer Protection

T1 R11 ABB CO
T2 Fuse4 S&C SM-4
T3 Fuse2 ERMCO 9F54WLD
T4 Relay41 ABB DPU-2000R
T5 Fuse1-1 S&C SM-4

ETAP Workshop Notes ©1996-2009 Operation Technology, Inc. Page 2 of 3


Star Exercise 4A

Feeder Protection

Cable2 R12 ABB CO

Cable3 CB1-1 Cutler-Hammer DS-420


(Carriere LVSST) (FB600E)
Cable4 Relay32 GE Multilin IFC
Relay33 GE Multilin IAC-51N
(residual)
Syn1Fdr SR469 GE Multilin 469

All Equipment Cables (refer to motor protection)

Generator Protection

Gen1
13.8 kV
4 MW
85% PF
4 Pole

PD: GE G60 Relay