A Doubly-Fed Induction Generator Adaptive Control
A Doubly-Fed Induction Generator Adaptive Control
Abstract: The extensive connection of distributed generation (DG) with the distribution network
(DN) is one of the core features of a smart grid, but in case of a large number, it may result in
problems concerning the DN-DG compatibility during fault isolation and service restoration, for
which no efficient and economic solutions have been developed. This paper proposes a
doubly-fed induction generator (DFIG) adaptive control strategy (ACS) and a coordination
technology to be compatible with the typical feeder automation (FA) protection logics in the ring
distribution system. First of all, an ACS simulating the inertia/damping characteristics and
excitation principles of synchronous generators is developed to achieve seamless switching
between DFIG grid-connection/island modes, and make distant synchronization possible. Next, a
technology coordinating the DFIG islands controlled by ACS and the remote tie-switches based on
local inspection of synchronization conditions for closing is developed to achieve the safety
grid-connection of DFIG islands in the absence of DN-DG communication. At the last, a detailed
simulation scenario with a ring DN accessed by five DFIGs is used to validate the effectiveness of
ACS and coordination technology compatible with FA in various faults scenes.
Keywords: distribution network (DN); doubly-fed induction generator (DFIG); feeder automation
(FA); compatibility; adaptive control strategy (ACS); coordination technology
1. Introduction
With more distributed generations (DGs) based on renewable energies integrating to the
distribution network (DN), traditional DNs are evolving into active ones with more prominent
DN-DG contradictions. Overall, the incompatibility and mutual repulsion between the DN and the
DG have hindered the upgrading of active DN to smart DN [1–3]. Traditional DNs are challenged
seriously by the compatibility between DG and DN in terms of topology structure, operating
standards, control modes and protection configuration [1,4]. From the perspective of protection,
traditional DN is generally a radiating structure from substations to users, and support fast fault
isolation and service restoration based on equipment such as relays, circuit breakers, reclosing
devices, sectionalizing switches and fuses [5–7]. Nevertheless, the application of DGs has changed
the topology structure of traditional radical DN, which may lead to serious problems in the normal
operation of protections to traditional DN, including false tripping of feeders, protection inaction,
raised or reduced failure level, unintentional islanding, asynchronous closing and failed automatic
reclosing [8,9]. Therefore, the reliability of traditional distribution systems are compromised by the
installation of DGs as it results in failure of protection coordination. In the meantime, the safety of
DGs is also challenged.
In recent years, researchers and institutions around the work have proposed various protection
strategies and specific control technologies for active DNs, aiming to fast isolate the failures in the
protection system at the grid side, and guarantee the safe operation of DGs at the DG side, while
power authorities and international power organizations have formulated protection standards and
specifications for DNs involving DGs to enhance the reliability of the DN [10,11]. Presently, the
mainstream engineering DN-side protection is fast and non-selective connection of all DGs in case
of any failure in the DN in any form, so that the existing protection will not be negatively affected
[12]. Where an islanding status is detected by an existing DG, its internal control system will, in
general cases, activate the anti-islanding protection mechanism to achieve disconnection and
shutdown of DGs quickly [10,13], while DGs with fault rid-through capacity can be removed from
the grid after a delay of a limited period in any failure [8]. For doubly-fed induction generator
(DFIG), it will start crowbar protection immediately under fault scenario [7]. Obviously, the
protection strategies at the DN and DG sides are comparatively conservative and weaken the
advantage of DGs in improving power supply reliability. Furthermore, the disconnection and
shutdown of DGs may affect stability of the grid, disadvantage service restoration, and result in
additional maintenance costs [12,14].
Therefore, some new strategies are put forward successively and can be categorized generally
into 2 types: ① DG improvements and reserved DG-side protection strategies; ② Improvements
in DG-side protections and reserved DG strategies. In the first solution, DG output is limited and
DG connecting position is optimized to avoid any impact on the DN protection [15,16]. Limiting
DG output is easy to implement, but deviates from the initial intention of sufficient and flexible
utilization of DG energies. Optimizing DG connecting position can reduce the power loss of the DN
and improve voltage distribution. However, the best DG connecting position is subject to natural
and geographical environments [17]. Therefore, optimizing the DG connecting position is not a
preferred strategy in an established active DN. The second solution achieves adaptation to the large
number of DGs by improving DG-side protection. It falls into six forms: voltage-based protection,
improved current protection, differential protection, distance protection, adaptive protection and
fault current compensation [2]. Those improved protection strategies have significantly improved
the reliability of protective device whenever the DGs are in grid-connected or island modes.
Essentially, they are developed against problems in the active DNs, such as fault identification,
location and isolation, and fail to take into consideration the safe operation of DGs when the
topology structure of the DN is changing dynamically. In particular, the specific strategies DG
follow to withstanding the abnormal DN-side interruptions and service restoration in the
continuous process from sudden tripping of circuit breakers to the closing of tie-switches are
seldom referred. Reference [18] suggests closing the tie-switch 15 ms before circuit breakers trip to
isolate the fault segments, to make sure DGs can maintain grid-connected power generation during
and after faults, but, closing the tie-switch at the presence of faults may result in overvoltage or
overcurrent, and the coordination between protection devices for actions in a ms places high
requirements on the communication system and the circuit breakers. Reference [19] proposed a
strategy of output matching of DGs through the local controllable load bank when they are
disconnected, in order to maintain their status before the fault without immediate stopping, and
realize fast reconnection by reclosing as the power is recovered. Instead of changing the structures
and settings of existing DN-side protection system, this strategy further expands the application
level of DGs, and directly reduces the costs of DG stopping and restart. However, it is a
conservative disconnection strategy essentially that the DGs fail to continuously supply powers to
local loads during a fault, and an additional controllable load bank is required.
It should be noted that in case of a fault, active DNs have achieved a lot in fault isolation, but
the compatibility between DGs and DN-side protection devices is still a challenge in a true sense.
The existing active DNs lack experience in technology docking and integration in terms of DN-DG
coordination, and the strategies adopted are more conservative, while standards and operation
guides concerning the deployments of DGs to the DN are based on the technical level at present,
Energies 2019, 12, 4463 3 of 21
which will surely be removed through the technical route and utmost goals of smart DN to achieve
the real integration of DGs and the DN.
Therefore, this paper gives a solution and the contributions of this paper which are
emphasized in the following points:
① This paper proposes a doubly-fed induction generator (DFIG) adaptive control strategy
(ACS) which possesses the capabilities of dual-mode operation, restraining sudden
changes of rotor current and distant synchronization, making seamless switching between
grid-connection and island can be achieved and making distant synchronization possible
without switching control strategies.
② This paper proposes a coordination technology which combines the DFIG islanding
controlled by ACS with remote tie-switches based on local inspection of synchronization
conditions for closing to achieve the safety grid-connection of DFIG islands in absence of
communication between DFIG and DN.
③ The ACS and coordination technology allows DFIG (not limited to a single wind turbine)
continuously supply power to partial local loads during the dynamic process of feeder
automation (FA) fault isolation and power recovery without shutdown and restart of
DFIG, realizing the compatibility between DFIG and feeder automation (FA).
This paper consists of Section 2, which summarizes the active distribution system studied
herein, and analyzes the contradictions between existing FA protection logics and DFIG, Section 3,
which specifies the solution for DN-DFIG compatibility, Section 4, which describes and analyzes
the proposed DFIG ACS and coordination technology in details, and Section 5, which exhibits the
simulation results in various scenes and some discussions are given. Conclusions can be found in
Section 6.
Three feeders are led out via S1, S2 and S3, and interconnected through the ring main unit
(RMU). All inlet and outlet switches of the RMU are circuit breakers, while the tie-switches L41 and
L62 are normally opened. The tie-line 1 connects with feeders 1 and 3, and the tie-line 2 connects
with the feeders 2 and 3. All feeders are underground cables. Five DFIGs connect to the DN
through RMUs at different positions. The secondary system is configured as a typical intelligent
Energies 2019, 12, 4463 4 of 21
distributed FA independent from the overall information from the master stations or slave stations,
and exchanges fault information by peer-to-peer communication between intelligent electronic
devices (IEDs), to realize fast isolation of feeder faults and service restoration [21–23]. The
communication network supports optical fiber Ethernet structures according to IEC 61850, while
the IEDs at the substations and the RMUs communicate with each other through the core switchers.
The generic object oriented substation event (GOOSE), a fast message communication mechanism,
is adopted for communications between IEDs [20].
where ωm∗ is the reference angular velocity of the wind turbine, and Pe is the actual output
electromagnetic power. Therefore, in the MPPT, the speed of the wind turbine depends on the
actual output electromagnetic power.
Whene the rotor follows motor convention and the stator applies generator convention, the
space vector model of the DFIG in the stator static reference frame can be expressed as:
ur = Rr ir − jωm ( Lr ir − Lm is ) + D ( Lr ir − Lm is ) (3)
where all quantities are in per unit. D is the differential operator ( d / dt ); ωm the electric angular
frequency of rotor; Rs and Rr are resistances of stator and rotor, respectively; Ls , Lr and are
stator self-inductance, rotor self-inductance and mutual inductance, respectively; us and ur , is
and ir are voltage and current space vectors of stator and rotor under stator static reference frame
respectively.
The proposed DFIG ACS is shown in Figure 4 and consists of power control, voltage control
and current inner loop, of which, the power control simulates the inertia/damping characteristics of
the synchronous generator [32]. 1 ( 2H As ) is the inertial link of power control; H A inertia time
constant of power control; K A proportional coefficient of power control. The electromagnetic
power reference Pe∗ is produced by torque control in the mechanical control part. Where the actual
power output losses its balance with the reference, ACS will regulate the inner potential angular
frequency of the stator ωsi through the inertial link and the proportional link, based on which, the
inner potential control phase of the stator θsi is obtained through the integral. ωb = 50Hz is the
angular frequency of fundamental wave and the rotor’s excitation current phase θIr is obtained by
θsi minus the rotor phase θ m = ω m dt . In the meantime, damping negative feedback control is
introduced to inhibit the frequency oscillations in the DFIG. The damping power PD is
determined by the difference between the inner potential angular frequency of the stator ωsi and
the reference angular frequency of the grid ωg∗ after the damping link. D A is the power control
damping coefficient.
The voltage control simulates the excitation principles of the synchronous generator. The
reference of rotor’s excitation current amplitude I r∗ is obtained through a typical PI controller
based on the difference of Us∗ , the reference of stator voltage amplitude, and Us , the actual stator
Energies 2019, 12, 4463 7 of 21
voltage amplitude. PUs,A and I Us ,A are respectively the voltage control proportion and integral
coefficient.
A three-phase independent control mode is adopted for the current inner loop, in which, “r”
(superscript) represents the value in the rotor reference frame. The space vector reference of the
r∗
rotor excitation currents i r is defined by the phase and amplitude obtained by power and voltage
controls, and converted to abc coordinate to obtain the reference of three-phase rotor excitation
currents ( irra∗ , irrb∗ and irrc∗ ), which correspond to the actual excitation currents of rotor ( irra , irrb and
ircr ), different between which is based on to obtain the three-phase excitation voltages of the rotor
( urar , urbr and urcr ) through the GQPR ( s ) control. GQPR ( s ) , quasi-proportional resonant controller
(QPR), better fits for precision control of sinusoidal signal as compared with traditional PI
controllers, and the transfer function can be expressed as [33,34]:
2 K QPR ωi s
GQPR ( s ) = PQPR + (4)
s 2 + 2ωi s + ωr2
where PQPR is the proportional coefficient, K QPR the resonance term gain, ωi the resonance term
bandwidth (actual value), and ωr the slip angular frequency (actual value). The design of QPR
parameters can be found in [33,34].
es = jX m ir = us + jX s is , (5)
where Es is the inner potential amplitude of the stator, and θ Es , the inner potential phase of the
stator. According to formula (6), the difference between θ Es and θsi is π 2 , and the amplitude
reference of rotor’s excitation current I r∗ is proportional to the inner potential amplitude of the
stator. Therefore, the inner potential of stator is subject to the direct control of ACS. When the DFIG
is grid-connected, the stator voltage is clamped down by the grid voltage, and the power control
Energies 2019, 12, 4463 8 of 21
will adjust the inner potential of stator based on the grid voltage, and transmit power to the grid.
Thus power control plays a leading role, and the voltage control plays an auxiliary role. When the
DFIG is suddenly islanded, and supply power to partial loads, the loss of supports from grid
voltage will result in the voltage control at the dominating role and the power control automatically
adjust the speed of the wind turbine and output energy to serve the island loads under the MPPT in
formula (1). By damping negative feedback control and frequency amplitude limitation, the island
frequency is controlled within a certain range. Instead of tracking the maximal wind energy, the
MPPT under islanding mode guides the wind turbine to adjust its speed based on the loads. The
particular case is that multiple DFIGs are suddenly islanded when the slow dynamic response of
DFIG mechanical control will lead to the gradually balance between the mechanical energy
absorbed by each wind turbine and the loads to jointly supply power for loads. Therefore, ACS can
transmit the power captured to the grid during grid-connection mode, and supply power to loads
by controlling the voltage of stators in the island mode. Furthermore, when the system switches
between grid-connection/island modes, the ACS can directly produce the inner potential phase θ Es
of the stator by power control to avoid sudden change in the stator’s voltage phase and facilitate the
seamless switching between the two modes.
The small signal equivalent model of DFIG in the Figure 5 is properly converted to obtain the
equivalent inertia/damping model of DFIG as shown in Figure 6, where, Teq and Deq represent the
equivalent inertia and equivalent damping of DFIG under ACS control. Equations (7) and (8) are
the expressions of Teq and Deq, respectively.
4H m H A s 2 + 2 Dm H A s
Teq = ,
4H mωm0 K A H A s + ( 2 Dmωm0 K A H A + 2 Pv K A H A + 2 H mωm0 ) s 2
3
(7)
+ ( 2I v K A H A + Dmωm0 + Pv ) s + I v
Equations (7) and (8) reflect the equivalent inertia’s association with the inertia time constant
H A and the proportional coefficient K A , while the equivalent damping is related with the inertia
time constant H A , the proportional coefficient K A and the damping coefficient DA . It is assumed
that the wind speed is 15 m/s, then the stable speed ωm0 = 1.2 pu , the inherent inertia/damping of
the wind turbine are H m = 4.96 s , Dm = 1.5 , and the parameters of the torque control are Pv = 3
and I v = 0.6 [32]. The maximal equivalent inertia of different inertia time constant H A and
proportional coefficient K A are as shown in Figure 7(a). When K A ∈ ( 0, 0.5) , the equivalent inertia
significantly increases with H A and when K A ≥ 0.5 , the increase slows down. Under the same
operation conditions, the maximal equivalent damping of different inertia time constant H A ,
damping coefficient DA and proportional coefficient K A are shown in Figure 7(b). Overall, when
the proportional coefficient satisfies the relation of K A ∈ ( 0, 0.5) , the equivalent damping
significantly increases with the coefficient of damping DA , and a smaller inertia time constant H A
corresponds to a larger equivalent damping. Obviously, ACS can have large equivalent inertia and
damping by choosing appropriate parameters. In this paper, the parameters selected are H A = 4.96 ,
DA = 151 and K A = 0.11 .
Figure 7. ACS control parameter’s impact on DFIG equivalent inertia/damping: (a) Maximal
equivalent inertia with different inertia time constant and proportional coefficient; (b) Maximal
equivalent damping with different inertia time constant, damping and proportional coefficient.
5. Case Analysis
To validate the effectiveness of the DFIG ACS and coordination technology compatible with
FA, the simulation scenario as shown in Figure 1 and detailed models of DFIGs and converters
[30,35] are established in MATLAB/Simulink. The selecting of five DFIGs in Figure 1 is to simulate
the situation of multiple DGs connected to DN from different locations, the probabilities of multiple
DGs unintentional island and multiple DGs reconnecting to grid. For parameters of DFIG, ACS and
the DN, please refer to Table A2 (Appendix A). The first test target is the effectiveness of ACS in
grid-connection mode, followed by the effectiveness of ACS and coordination technology after the
tripping of circuit breakers under FA control in different DN fault scenes.
Figure 10. Electromagnetic power waveforms of DFIG under PQ control and proposed ACS control.
that the FA can isolate faults instantaneously. It is assumed that the maximal allowable transient
frequency of the DN is 51 Hz, and the error between the voltage phases by both sides of the
tie-switches is 180 .
Figure 11. Changes in electrical quantity at the grid side after a F1 fault.
① Grid-connection/Island Switching: the power supply from feeder 3 is cut off at 30 s, DFIG4,
RMU4, tie-line 2 and loads constitute single island. DFIG3 enters into the islanding mode
under ACS control, while the voltage uT2 of the tie-line 2 jitters to 1.1 pu for within 1 cycle.
No sudden change in phase is observed. However, mainly due to the sudden change of
power (from 1.5 MW to 1.12 MW), the voltage frequency f T2 of tie-line 2 shows a peak of
50.6 Hz less than allowed (51 Hz); the rotor current amplitude of DFIG4, I r-DFIG4 rapidly
reduces from 0.8 pu to 0.65 pu without overcurrent; the electromagnetic power Pe-DFIG4 of
DFIG4 also rapidly adapts to the island loads of 1.12 MW. It can be seen that the DFIG4
under ACS control can seamlessly enter into the single island mode.
② Distant Synchronization Process: when the DFIG4 enters into the islanding mode with
imbalanced power, the amplitude of uT2 remains relatively stable while I r-DFIG4 fluctuates
at a frequency of 1.5 Hz with a decreasing tendency; Pe-DFIG4 matches with the island loads
of 1.12 MW without significant fluctuation basically; f T2 fluctuates around 50.1 Hz to
cause the error of voltage phase Δθ L62 between both sides of the tie-switch L62 reducing
Energies 2019, 12, 4463 13 of 21
from 180 to 0 . It is obvious that the DFIG4 under ACS control can maintain the island
stability and automatically create distant synchronization conditions.
③ Island Grid-connection Process: the tie-switch L62 receives the FIS GOOSE message
through FA as the circuit breakers L42 and L51 trip. Δθ L62 reduces to 0 at 34.9 s, and
L62 immediately closes to passive feeder 2 as the synchronization conditions are inspected
locally through the synchronization check device, when the DFIG4 turns to the
grid-connection status, and I r-DFIG4 and Pe-DFIG4 rise gradually, during which, no vibrant
fluctuation is experienced. The stable status before fault is recovered in about 10s. In the
meantime, uT2 and f T2 remain constant as they are clamped down by the voltage of
feeder 2 after grid-connection, and Δθ L62 reserves 0 ; Current amplitude I L62 of
tie-switch L62 rises from 0pu after closing without dash current, and enters into a stable
status about 10 s later. It is obvious that the DFIG4 island under ACS control can securely
recover the grid-connection status through coordination with L62 for local synchronous
closing.
Figure 12. Changes in electrical quantity at the wind turbine side after a F1 fault.
① Grid-connection/Island Switching: as L52 and S3 trip, DFIG4, DFIG5, RMU4 and RMU5,
tie-line 2 and loads constitute an island with two wind turbines. DFIG4 and DFIG5 enter
into the islanding mode under ACS control, while the voltage uT2 of the tie-line 2 jitters
slightly with a continuous waveform. Similarly, mainly due to the sudden change of
power (from 2.3 MW to 2 MW), the voltage frequency f T2 of tie-line 2 shows a peak of
50.26 Hz below allowable; the rotor current amplitudes of DFIG4 and DFIG5 ( I r-DFIG4 and
I r-DFIG5 ) rapidly change without overcurrent; the total electromagnetic power of DFIG4 and
DFIG5 ( PC = Pe-DFIG4 + Pe-DFIG5 ) also rapidly adapts to the island loads of 2 MW. It can be seen
that the DFIG4 and DFIG5 under ACS control can seamlessly enter into the multiple
islands mode.
② Distant Synchronization Process: when the DFIG4 and DFIG5 enter into the islanding
mode with imbalanced power, the amplitude of uT2 remains relatively stable while
I r-DFIG4 and I r-DFIG5 ; DFIG4 and DFIG5 automatically allocate Pe-DFIG4 and Pe-DFIG5 to
maintain PC at 2 MW constantly; f T2 fluctuates around 50.05 Hz and its undulatory
property gradually weakens to cause the error of voltage phase Δθ L62 between both sides
of the tie-switch L62 reducing to 0 . It is obvious that the island with DFIG4 and DFIG5
under ACS control can automatically create distant synchronization conditions.
Energies 2019, 12, 4463 14 of 21
③ Island Grid-connection Process: the tie-switch L62 receives the FIS GOOSE message
through FA as the circuit breakers L52 and S3 trip. Δθ L62 reduces to 0 at 39.6 s, and L62
immediately closes to passive feeder 2 as DFIG4 and DFIG5 switch to grid-connection
mode, I r-DFIG4 and I r-DFIG5 rise gradually. The pre-fault stable status is recovered in about
15 s for Pe-DFIG4 and Pe-DFIG5 (1.5 MW and 0.8 MW). In the meantime, uT2 and f T2
remain constant as they are clamped down by the voltage of feeder 2 after grid-connection,
and Δθ L62 maintains at 0 ; I L62 rises rapidly after closing without dash current, and
enters into a stable status about 15 s later. It is obvious that the island with DFIG4 and
DFIG5 under ACS control can securely recover the grid-connection status through
coordination with L62 for local synchronous closing.
Figure 13. Changes in electrical quantity at the grid side after a F2 fault.
Figure 14. Changes in electrical quantity at the wind turbine side after a F2 fault.
Energies 2019, 12, 4463 15 of 21
Figure 15. Changes in electrical quantity at the grid side after a F3 fault.
DFIG2, and DFIG3 under ACS control can automatically create distant synchronization
conditions.
③ Island Grid-connection Process: the tie-switch L41 receives the FIS GOOSE message
through FA as the circuit breakers L11 and S1 trip, and immediately closes to active feeder
3 as the synchronization conditions ( Δθ L41 = 0 ) are detected locally through the
synchronization check device at 54.7 s, when the DFIG1, DFIG2 and DFIG3 switch to the
grid-connection status, and I r-DFIG1 , I r-DFIG2 and I r-DFIG3 recover in an undulatory manner,
during which, I r-DFIG2 and I r-DFIG3 fluctuate significantly; I r-DFIG4 and I r-DFIG5 fluctuate
transitorily (about 5 s) when L41 closes, and then stabilizes; Pe-DFIG1 , Pe-DFIG2 and Pe-DFIG3
show the similar change tendency as the rotor currents, while Pe-DFIG2 and Pe-DFIG1 are
subject to larger fluctuation as compared with the Pe-DFIG1 during grid-connection
recovery, and Pe-DFIG4 and Pe-DFIG5 are shocked to a certain degree when L41 closes. In the
meantime, uT1 and f T1 remain constant as they are clamped down by the voltage of
feeder 3 after grid-connection, and Δθ L41 maintains at 0 ; Current amplitude I L41 of
tie-switch L41 rises rapidly without dash current, and enters into a stable status after slight
fluctuation. It is obvious that the DFIG1, DFIG2 and DFIG3 islands under ACS control can
securely recover the grid-connection status through coordination with L41 for local
synchronous closing, while DFIG4 and DFIG5 stabilize rapidly after temporary and
limited shocks.
It can be seen from three fault scenes: the magnitude and fluctuation of the island system
frequency are closely related to the power variation rate. The greater the power changes, the bigger
the frequency magnitude changes (including the overshoot), the larger the frequency fluctuates.
However, the frequency fluctuation during island operation will gradually decrease over time (e.g.,
Figure 13). Moreover, the more the frequency of the island system changes, the faster the
synchronization conditions are met, so the islanding time of DFIG is closely related to the power
change rate too. In addition, the DFIG under ACS control is a temporary island during the
coordination with FA, which, on the one hand, helps solve the problem of power quality arising
from the long-term islanding of the DFIG, and on the other hand, upgrades the traditional one-way
power supply recovery mechanism from feeders to loads to the two-way power supply recovery
mechanism from DG and feeders to loads. Therefore, the solution proposed in this paper can make
the DFIG truly non-off-grid and more economical than other existing solutions.
Energies 2019, 12, 4463 17 of 21
Figure 16. Changes in electrical quantity at the wind turbine side after a F6 fault.
It should be noted that, however, this paper mainly focuses on a situation that the total island
loads are smaller than the total real-time capacity of all wind power generations in island, without
consideration to other cases, including equivalent or larger relations. The underlying reasons shall
be when the output of the wind turbine matches with the load, the wind turbine experiencing
switching between grid-connection and island will not have obvious changes in status while the
output of the wind turbine is smaller than the load, it has to coordinate with other power
generation units (such as energy storage) to stabilize islands. Moreover, the compatibility between
the FA technology and DFIG of the DN based on underground cables is another focus in this paper,
while the FA technology for DN with overhead lines requires repeated reclosing, and different
strategies to achieve compatibility with DFIG. In addition, this paper only studies DFIG, a type of
DG. From the thought of DN-DG coordination, the solution proposed in this paper should have
similar effect when applied to other types of DGs, such as photovoltaic, energy storage, permanent
magnet synchronous generator, etc. However, if ACS proposed in this paper is to be applied to
other DGs, appropriate modifications and adjustments may be required. Furthermore, for devices
such as energy hub and energy router [36,37], which may be used in future smart grid, the idea in
this paper should be helpful in solving the coordination problem between them and protection
devices.
6. Conclusions
An adaptive control strategy of DFIG and coordination technology compatible with FA is
proposed in this paper. The simulation is carried out based on MATLAB/Simulink and the results
reveal that:
① The ACS proposed herein has similar power control characteristics as found in traditional
PQ control that the DFIG can work effectively in grid-connection mode.
② As the FA isolates a feeder fault, one or multiple DFIGs under different wind speeds can
achieve seamless switching between grid-connection/island modes under ACS control, and
continuously supply power to partial local loads.
Energies 2019, 12, 4463 18 of 21
③ During DFIG islanding, ACS’s differential regulation to frequency and power imbalance
result in the automatic satisfaction of synchronization conditions at remote tie-switches.
④ After FA fault isolation, the tie-switches can close based on local detection of
synchronization conditions and the DFIG under ACS control can be securely
grid-connected without establishing an additional communication system with the DN.
In general, the ACS and coordination technology in this paper realize the compatibility
between DFIG and FA without DFIG shutdown and restart.
Author Contributions: Z.H. contributed to the project idea, the results discussion and conclusions. P.T.
contributed to specific strategy, theoretical analysis, simulation experiment design and data analysis. Z.L.
reviewed the final manuscript and the results discussion.
Funding: This research was funded by the National Natural Science Foundation of China (51567005), in part by
the Guizhou Province Science and Technology Platform and Talent Project of China ([2017]5788/LH Word
[2017]7230), in part by the Guizhou Province Science and Technology Plan Project of China ([2018]5615), in part
by the National Natural Science Foundation of China (61963009).
Conflicts of Interest: The authors declare that there is no conflict of interests regarding the publication of this
paper.
Appendix A
Variable Description
Pe∗ Electromagnetic power reference
Pe Actual output electromagnetic power
PC Total electromagnetic power of DFIG island
Pe,PQ Electromagnetic power under traditional PQ control
Pe,ACS Electromagnetic power under ACS control
PD Damping power
Pe-DFIGx Electromagnetic power of DFIGx
ωm Electric angular frequency of rotor
ωm ∗ Reference angular velocity of wind turbine
ωb Angular frequency of fundamental wave
ωg ∗
Angular frequency reference of grid
ωg Grid voltage angular frequency
ωr Slip angular frequency
ωm0 Stable speed of wind turbine at a certain operation point
ωs Synchronous angular frequency/ Stator voltage angular frequency
ωi Resonance term bandwidth of quasi-proportional resonant controller
ωsi Island voltage angular frequency/ Inner potential angular frequency of stator
Rs & Rr Resistances of stator and rotor
Ls & Lr Self-inductance of stator and rotor
Lm Mutual inductance
f T1 Voltage frequency of tie-line 1
f T2 Voltage frequency of tie-line 2
es Inner potential of stator
Es Inner potential amplitude of stator
uI Space vectors of island voltage
ug Space vectors of grid voltage
uT1 Voltage of the tie-line 1
Energies 2019, 12, 4463 19 of 21
DFIG machine
Parameter Value Parameter Value
Rs 0.023 pu U dc 1150 V
Rr 0.016 pu Rated power 1.5 MW
Ls 3.08 pu Stator voltage 690 V
Lr 3.06 pu Pole pairs 3
Lm 2.9 pu Normal speed 1.2 pu
H m 4.96 DC-link capacitor 10000 uF
Dm 1.5 Rated frequency 50 Hz
Energies 2019, 12, 4463 20 of 21
ACS
Pv 3 PQPR 20
Iv 0.6 K QPR 33
KA 0.11 ωi π
HA 4.96 PUs,A 1
DA 151 I Us,A 40
DN
Rated voltage 10 KV Line inductance 0.9337×10-3 H/km
Rated frequency 50 Hz Line capacitance 12.74×10-9 F/km
Line resistance 0.01273 Ω/km
Reference
1. João, P.S.; Catalão, S.; Rahimi, E.; Javadi, M.S.; Nezhad, A.E.; Lotfi, M.; Shafie-khah, M.; Catalão, J.P.S.
Impact of distributed generation on protection and voltage regulation of distribution systems: A review.
Renew. Sustain. Energy Rev. 2019, 105, 157–167.
2. Blaabjerg, F.; Yang, Y.; Yang, D.; Wang, X. Distributed Power-Generation Systems and Protection. Proc.
IEEE 2017, 105, 1311–1331.
3. Roy, N.K.; Pota, H.R. Current Status and Issues of Concern for the Integration of Distributed Generation
into Electricity Networks. IEEE Syst. J. 2015, 9, 933–944.
4. Monadi, M.; Amin Zamani, M.; Ignacio Candela, J.; Luna, A.; Rodriguez, P. Protection of AC and DC
distribution systems Embedding distributed energy resources: A comparative review and analysis. Renew.
Sustain. Energy Rev. 2015, 51, 1578–1593.
5. Kennedy, J.; Ciufo, P.; Agalgaonkar, A. A review of protection systems for distribution networks
embedded with renewable generation. Renew. Sustain. Energy Rev. 2016, 58, 1308–1317.
6. Nikolaidis, V.C.; Papanikolaou, E.; Safigianni, A.S. A Communication-Assisted Overcurrent Protection Scheme
for Radial Distribution Systems with Distributed Generation. IEEE Trans. Smart Grid. 2016, 7, 114–123.
7. Bansal, R. Power System Protection in Smart Grid Environment, 1st ed.; CRC Press: Boca Raton, FL, USA, 2019.
8. Norshahrani, M.; Mokhlis, H.; Abu Bakar, A.; Jamian, J.; Sukumar, S. Progress on Protection Strategies to
Mitigate the Impact of Renewable Distributed Generation on Distribution Systems. Energies 2017, 10, 1864.
9. Sajadi, A.; Strezoski, L.; Strezoski, V.; Prica, M.; Loparo, K.A. Integration of renewable energy systems
and challenges for dynamics, control, and automation of electrical power systems. Wires Energy Environ.
2019, 8, e321.
10. Vyas, S.; Kumar, R.; Kavasseri, R. Data analytics and computational methods for anti-islanding of renewable
energy based Distributed Generators in power grids. Renew. Sustain. Energy Rev. 2017, 69, 493–502.
11. Peixin, Y.; Peichao, Z. A Survey on Interconnection Protection of Distributed Resource. Power Syst. Techn.
2016, 06, 1888–1895.
12. Manditereza, P.T.; Bansal, R. Renewable distributed generation: The hidden challenges—A review from
the protection perspective. Renew. Sustain. Energy Rev. 2016, 58, 1457–1465.
13. Motter, D.; de Melo Vieira, J.C. The Setting Map Methodology for Adjusting the DG Anti-Islanding
Protection Considering Multiple Events. IEEE Trans. Power Deliv. 2018, 33, 2755–2764.
14. Zidan, A.; Khairalla, M.; Abdrabou, A.M.; Khalifa, T.; Shaban, K.; Abdrabou, A.; El Shatshat, R.; Gaouda,
A.M. Fault Detection, Isolation, and Service Restoration in Distribution Systems: State-of-the-Art and
Future Trends. IEEE Trans. Smart Grid 2017, 8, 2170–2185.
15. Zhan, H.; Wang, C.; Wang, Y.; Yang, X.; Zhang, X.; Wu, C.; Chen, Y. Relay Protection Coordination
Integrated Optimal Placement and Sizing of Distributed Generation Sources in Distribution Networks.
IEEE Trans. Smart Grid 2016, 7, 55–65.
16. Abdel-Ghany, H.A.; Azmy, A.M.; Elkalashy, N.I.; Rashad, E.M. Optimizing DG penetration in
distribution networks concerning protection schemes and technical impact. Electr. Power Syst. Res. 2015,
128, 113–122.
Energies 2019, 12, 4463 21 of 21
17. Badran, O.; Mekhilef, S.; Mokhlis, H.; Dahalan, W. Optimal reconfiguration of distribution system
connected with distributed generations: A review of different methodologies. Renew. Sustain. Energy Rev.
2017, 73, 854–867.
18. Xyngi, I.; Popov, M. An Intelligent Algorithm for the Protection of Smart Power Systems. IEEE Trans.
Smart Grid 2013, 4, 1541–1548.
19. Wheeler, K.A.; Elsamahy, M.; Faried, S.O. A Novel Reclosing Scheme for Mitigation of Distributed
Generation Effects on Overcurrent Protection. IEEE Trans. Power Deliv. 2018, 33, 981–991.
20. Zhu, Z.; Xu, B.; Brunner, C.; Yip, T.; Chen, Y. IEC 61850 Configuration Solution to Distributed Intelligence
in Distribution Grid Automation. Energies 2017, 10, 528.
21. Ling, W.; Liu, D.; Yang, D.; Sun, C. The situation and trends of feeder automation in China. Renew. Sust.
Energy Rev. 2015, 50, 1138–1147.
22. Chenghong, T.; Zhihong, Y.; Bin, S.; Yajun, Z. A Method of Intelligent Distributed Feeder Automation for
Active Distribution Network. Autom. Electr. Power Syst. 2015, 9, 101–106.
23. Wanshui, L.; Dong, L.; Yiming, L.; Wenpeng, Y. Model of intelligent distributed feeder automation based
on IEC 618510. Autom. Electr. Power Syst. 2012, 36, 90–95.
24. Tanvir, A.; Merabet, A.; Beguenane, R. Real-Time Control of Active and Reactive Power for Doubly Fed
Induction Generator (DFIG)-Based Wind Energy Conversion System. Energies 2015, 8, 10389–10408.
25. Shukla, R.D.; Tripathi, R.K. A novel voltage and frequency controller for standalone DFIG based Wind
Energy Conversion System. Renew. Sustain. Energy Rev. 2014, 37, 69–89.
26. Lin, L.; Xibin, S.; Zongxun, S. Operation mode analysis of micro-grid grid-connected and island based on
DFIG control method. Power Syst. Protect. Control 2017, 45, 158–163.
27. Hosseini, S.M.; Carli, R.; Dotoli, M. Robust Day-Ahead Energy Scheduling of a Smart Residential User
Under Uncertainty. In Proceedings of the 2019 18th European Control. Conference, Naples, Italy, 25–28
June 2019; pp. 935–940.
28. Sperstad, I.; Korpås, M. Energy Storage Scheduling in Distribution Systems Considering Wind and
Photovoltaic Generation Uncertainties. Energies 2019, 12, 1231.
29. Sitharthan, R.; Karthikeyan, M.; Sundar, D.S.; Rajasekaran, S. Adaptive hybrid intelligent MPPT controller
to approximate effectual wind speed and optimal rotor speed of variable speed wind turbine. ISA. Trans.
2019 (in press).
30. Miller, N.W.; Sanchez-Gasca, J.J.; Price, W.W.; Delmerico, R.W. Dynamic modeling of GE 1.5 and 3.6 MW
wind turbine-generators for stability simulations. In Proceedings of the IEEE Power Engineering Society
General Meeting (IEEE Cat. No.03CH37491), Toronto, ON, Canada,13–17 July 2003; pp. 1977–1983.
31. Pena, R.; Clare, J.C.; Asher, G.M. Doubly fed induction generator uising back-to-back PWM converters
and its application to variable- speed wind-energy generation. IEE Proc. Electr. Power Appl. 1996, 3,
231–241.
32. Wang, S.; Hu, J.; Yuan, X. Virtual Synchronous Control for Grid-Connected DFIG-Based Wind Turbines.
IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 932–944.
33. Ye, T.; Dai, N.; Lam, C.; Wong, M.; Guerrero, J.M. Analysis, Design, and Implementation of a
Quasi-Proportional-Resonant Controller for a Multifunctional Capacitive-Coupling Grid-Connected
Inverter. IEEE Trans. Ind. Appl. 2016, 52, 4269–4280.
34. Holmes, D.G.; Lipo, T.A.; McGrath, B.P.; Kong, W.Y. Optimized Design of Stationary Frame Three Phase
AC Current Regulators. IEEE Trans. Power Electr. 2009, 24, 2417–2426.
35. Clark, K.; Miller, N.W.; Sanchez-Gasca, J.J. Modeling of GE Wind Turbine-Generators for Grid Studies.
General Electric International, Inc. 2009.
36. Carli, R.; Dotoli, M. Decentralized control for residential energy management of a smart users microgrid
with renewable energy exchange. IEEE/CAA J. Autom. Sin. 2019, 6, 641–656.
37. Geidl, M.; Koeppel, G.; Favre-Perrod, P.; Klockl, B.; Andersson, G.; Frohlich, K. Energy hubs for the future.
IEEE Power Energy Mag. 2007, 5, 24–30.
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).