3RV10414KA10 Datasheet en
3RV10414KA10 Datasheet en
3RV10414KA10 Datasheet en
Ambient conditions
Main circuit
number of poles for main current circuit 3
adjustable pick-up value current of the current- 57 ... 75 A
dependent overload release
operating voltage
● rated value 690 V
● at AC-3 rated value maximum 690 V
operating current
● at AC-3
— at 400 V rated value 75 A
operating power
● at AC-3
— at 400 V rated value 37 kW
operating frequency
● at AC-3 maximum 15 1/h
Auxiliary circuit
number of CO contacts
● for auxiliary contacts 0
Short-circuit protection
design of the overcurrent release and short-circuit thermomagnetic
release
Connections/ Terminals
product function
● removable terminal for auxiliary and control No
circuit
type of electrical connection
● for main current circuit screw-type terminals with box terminals
● for auxiliary and control current circuit screw-type terminals
arrangement of electrical connectors for main current front side
circuit
type of connectable conductor cross-sections
● for main contacts
— solid 2x (2.5 ... 16 mm²)
— stranded 2x (10 ... 50 mm²), 1x (10 ... 70 mm²)
— finely stranded with core end processing 2x (2.5 ... 35 mm²), 2.5 ... 50 mm²
● at AWG conductors for main contacts 2x (10 ... 1), 1x (10 ... 2)
Certificates/ approvals
other Railway
Special Test Certi-
ficate
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV1041-4KA10
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV1041-4KA10
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV1041-4KA10
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV1041-4KA10&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV1041-4KA10/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV1041-4KA10&objecttype=14&gridview=view1
∅5
SIEMENS
129
165
155
45
70 5
8
82
169
3/L2
5/L3
-F
4/T2
6/T3