Extended Range Outdoor Combined Transformer: Type CVC-200ER

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Instrument transformers and sensors

Type CVC-200ER
Extended range outdoor combined transformer

Product features
−− For outdoor use
−− 36 kV, 60 Hertz (50 Hertz available)
−− 200 kV BIL
−− Electrical characteristics:
Strike: 27.0" (686 mm)
Creep: 38.7" (983 mm)
−− Approximate weight: 274 lbs. (124 kg)

Application
The CVC-200ER is a combination unit that consists of a current
transformer (CT) and voltage transformer (VT) in one body. It is
designed for metering applications and can be pole-mounted or
used in substations. The combined unit provides the customer
with both cost and space savings, as well as reduced installati-
on time.

The optional highly accurate current transformer element is ideal


for use in cogeneration and in applications where there are large
power exchanges, as it preserves stated accuracies with loads
ranging from one percent of the full rated current through the
rating factor. Due to its wide operating range in conventional
metering applications, the CVC-200ER provides greater value Junction box
for the utility customer by reducing inventory requirements. The junction box, provided with 1" conduit connections on three
sides, encloses the secondary terminals.
Construction
In the current transformer, primary and secondary windings are Baseplate
assembled around a toroidal wound core. The voltage trans- The baseplate is constructed of corrosion-resistant aluminum
former primary and secondary coils are wound using special and is secured to the encapsulated base support.
winding and shielding techniques for improved voltage stress
distribution. Each coil is insulated with mylar film to provide a Test reports
high dielectric strength between layers. The coils and core are Test reports are stored electronically and can be e-mailed in
combined to create a complete winding structure that is assem- various formats at the time of shipment.
bled to a support frame. The entire assembly is vacuum cast in
polyurethane for insulation and protection. Standards
This unit can be tested to all applicable IEEE, CSA, or IEC stan-
Terminals dards as requested. This unit is tested in accordance with IEEE
Primary terminals are NEMA, two-hole type electro-tin pla- C57.13.6-2005 for high accuracy instrument transformers.
ted copper. The current transformer secondary connections
are clamp-type and accommodate #14 to #1 AWG wire. The
voltage transformer secondary connections are clamp-type and
accommodate #13 to #3 AWG wire.
Selection guide
Current transformer Voltage transformer
Rating Rated
Frequency factor Accuracy voltage Accuracy Thermal
Style number (Hz) Ratio @ 30°C C1-C2 Ratio factor (RVF) V1-V2 rating (VA)
923A512G01 60 200:5 1.5 0.15B-1.8 20125/34500GY to 115 1.9 0.3Y 750
923A512G02 60 200:5 1.5 0.15B-1.8 20125/34500GY to 115/67.08 1.9 0.3Y/0.3Y 750
923A512G03 60 400:5 2.0 0.3B-1.8 20125/34500GY to 115 1.9 0.3Y 750
923A512G04 60 300:5 3.0 0.3B-1.8 20125/34500GY to 115 1.9 0.3Y 750

1VAP429996-DB June 2014 Rev. B


923A512G05 60 200:5 1.5 0.15B-1.8 19053/33000GY to 120 1.9 0.3Y 750
923A512G06 60 600:5 1.5 0.15B-1.8 20125/34500GY to 120 1.9 0.3Y 750
923A459G01 50 150/300:1 1.5 10 VA, CL 0.2 19050/33000 GY to 63.5 1.9 10 VA, CL 0.2 750
923A459G02 50 150/300:1 1.5 10 VA, CL 0.2 19050/33000 GY to 63.5 1.9 10 VA, CL 0.2 750
923A459G03 50 150/300:1 1.5 10 VA, CL 0.2 17320/30000 GY to 63.5 1.9 10 VA, CL 0.2 750
923A459G04 50 150/300:1 1.5 10 VA, CL 0.2 19050/33000 GY to 69.3 1.9 10 VA, CL 0.2 750
923A459G05 50 200/400:1 2.0 15 VA, CL 0.5 19053/33000 GY to 110 1.2 15 VA, CL 0.5 750

Additional styles available upon request. Contact your ABB sales representative or call +1-252-827-3212 for more information.

Dimensions
For more information please contact:
9.24
[235] GROUND LUG AND
GROUND STRAP
ABB Inc.
NAMEPLATE
12.25
16.64
Medium Voltage Distribution Components
[311]

H1
H2
[423]
3022 NC 43 North
1.95
Pinetops, NC 27864
[49]
USA
1.00 Phone: +1 252 827 3212
[25] 2.00 .37
.05
[1] [51] [10] Fax: +1 252 827 4286
Ø.56
.10 [Ø14] www.abb.com/mediumvoltage
[3] 2-TOTAL
1.31 [33] X .56 [14]
SLOTS
2-TOTAL
31.00 Note:
[787] 1" STD PIPE
TAP ON BOTH ENDS.
1" KNOCKOUT ON
The information contained in this document is for general information purposes
H0
BOTTOM OF only. While ABB strives to keep the information up to date and correct, it makes
JUNCTION BOX.
no representations or warranties of any kind, express or implied, about the
completeness, accuracy, reliability, suitability, or availability with respect to the
.38 2.50
15.62 [10]
1.75 2.61
[63] information, products, services, or related graphics contained in the document for
[44] [66]
[397] any purpose. Any reliance placed on such information is therefore strictly at your
Type CVC-200ER own risk. ABB reserves the right to discontinue any product or service at any time.

Copyright 2013 ABB.


All rights reserved.
1.13 x .44 SLOTS 4-TOTAL
[29] x [11]
GROUND LUG

NAMEPLATE

10.00 12.25
[254] [311]

4.62 10.00
[117] [254]
1.12
[29]
15.62
[397]

Baseplate