Technical Data: 3-Phase N/A Factor Cos Φ = 0.8 50Hz/1500rpm Power Factor Emissions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Technical Data

April 2018
Engine Alternator Generator Model
Cummins KTA19-G3A Leroy-Somer LSA47.2M7 FB500-C1 / Open FC500-C1 / Silent

Power Factor Emissions


50Hz/1500rpm 3-Phase
Factor Cos Φ = 0.8 N/A

Prime Power Standby Power Rated Current Fuel Consumption


RATINGS
(PRP) (ESP) Amps @100% Load

Voltage (V) kWe kVA kWe kVA (A) L/h

380/220 400 500 450 563 759.7 109.2

400/230 400 500 450 563 721.7 109.2

415/240 400 500 450 563 695.6 109.2

Key Features:
- High efficient water cooled diesel engine.
- Single bearing with brushless alternators (Class H, with AVR).
- Radiator with pressure cap and drain point.
- Fully guarded engine-driven fan.
- Fully welded steel skid base with lifting holes and fork lift legs.
- Integral fuel tank with filler cap and gauge (≤650kVA).
- Heavy duty rubber anti-vibration mountings.
- 12V or 24V maintenance free starter battery and connecting cables.
- Separate engine-driven battery charging alternator.
- Spin on oil and fuel filters and dry type air filter element.
- Industrial silencer (15dBA reduction) supplied loose.
- Auto start control system with LCD show.
- Battery charger provided.
- Main line 3P circuit breaker.
- Rigorous factory test wiring with IEC standard.
- Operation & Maintenance manual & Wiring diagrams.
- Wide range of optional extra features available.

Overall Dimensions & Weights - Open Set


Length (L)-mm: 3250

H Width (W)-mm: 1300


Height (H)-mm: 2100
Dry Weight-kg: 4000

L W
Ratings: All three phase generator sets are rated at 0.8 power factor. All single-phase generator sets are rated at 0.8 or 1.0 power factor.
Prime Power: Available continuously at variable load in lieu of commercially purchased power for an unlimited number of hours per year
accordance with ISO8528-1, and an overload of 10% permitted for one hour in every twelve hours of operation in accordance with ISO 3046-1.
Standby Power: Emergency Standby Power in variable load applications in accordance with ISO8528-1 in the event of a utility power failure.
No overload available for this service as relevant alternators are peak continuous rated at 27 ℃ .
TIDE Power reserves the right to change the design or specifications without notice and without any obligation or liability.

Tide Power Technology Co., Ltd. NO.1 Building, YiXu Mechanical & Electrical Park, Gaishan Town, Cangshan District, Fuzhou, Fujian, China.
Our Tel: +86-591-28068999, Fax: +86-591-28068900 Email: [email protected] www.tpshk.com Page 1
Engine Cummins KTA19-G3A
Units Prime Standby
Frequency Hz 50
Engine Speed r/min 1500
Cylinders / Type 6 cyl / In-line / 4-stroke
Aspiration Turbocharge , Aftercooled
Governor Type Electronic Governor
General
Bore / Stroke mm 159/159
Performance
Displacement Litres 19
Compression Ratio 13.9:1
Piston Speed m/s 7.9
Brake Mean Effective Pressure kPa 1889 2125
Engine Power kWm 448 504
Fuel Consumption at 110% Prime Power Litres/hour 123.6
Fuel Consumption at 100% Prime Power Litres/hour 109.2
Fuel Consumption at 75% Prime Power Litres/hour 84
Fuel System
Fuel Consumption at 50% Prime Power Litres/hour 57.6
Fuel Consumption at 25% Prime Power Litres/hour 31.2
Standard Fuel Tank Capacity Litres 660
Maximum Intake Air Restriction with Heavy Duty Air Cleaner
- With Clean Filter Element kPa 3.73
Air System
- With Dirty Filter Element kPa 6.23
Intake Air Flow Litres/s 531 579
Maximum Back Pressure kPa 10
Exhaust Exhaust Outlet Size mm 127
System Exhaust Gas Flow Litres/sec. 1434 1604
Exhaust Gas Temperature °C 538 557
Total Oil System Capacity Litres 50
Oil Pan Capacity - Low Litres 32.2
Oil System
Oil Pan Capacity - High Litres 37.9
Maximum Oil Temperature °C 121
Coolant Capacity - With Radiator Litres 112
Cooling
Standard Thermostat (Modulating) Range °C 82-93
System
Maximum Allowable Top Tank Temperature °C 100 104
Electrical System Voltage V 24
Electric
Battery Maintenance-free
System
Connecting Cables Auailable
Radiated Heat to Ambient kW 64 72
Energy
Heat Rejection to Coolant kW 319 361
Balance
Heat Rejection to Exhaust kW N/A N/A

Alternator 50Hz/1500rpm
Units
Manufacture / Brand Leroy-Somer
Model LSA47.2M7
Coupling / No. of Bearings Direct / Single Bearing
Phase / Poles 3-Phase / 4-Pole
Power Factor Cos Φ = 0.8
AVR Regulation Yes
General Data
Voltage Regulation ± 0,5 %
Insulation Class H
Drip Proof IP23
Excitation Shunt
Altitude m ≤1000
Overspeed min -1 2250

Tide Power Technology Co., Ltd. NO.1 Building, YiXu Mechanical & Electrical Park, Gaishan Town, Cangshan District, Fuzhou, Fujian, China.
Our Tel: +86-591-28068999, Fax: +86-591-28068900 Email: [email protected] www.tpshk.com
Page 2
Tide Power Easycon Function Summary
EC 2.0 / EC 3.0 / EC 4.0 / EC 5.0 /
Controller Model / ComAp
Nano Plus AMF20 AMF25 IG-NT

Controller Photos

Standard Supply × ● ○ ○

Viewable Parameters
Phase Voltage × 3 3 3
Current Instrumentation ● ● ●
Frequency ● ● ● ●
Active Power × ● ● ●
Reactive Power × ● ● ●
Apparent Power × ● ● ●
Power Factor × ● ● ●
Electric Energy Metering × ● ● ●

Generator Protection
Abnormal Voltage ● ● ● ●
Over-current Warning × ● ● ●
Over current Protection ● ● ● ●
Over Frequency Protection ● ● ● ●
Short Circuit Protection MCCB / ● MCCB / ● MCCB / ● MCCB / ●

Engine Figure
Oil Pressure ● ● ● ●
Water Temperature ● ● ● ●
Fuel Meter / Fuel Sensor ●/○ ●/○ ●/○ ●/○
Speed ● ● ● ●
Battery Voltage ● ● ● ●
Elapsed Time ● ● ● ●

Engine Protection
Low Oil Pressure Warning × ● ● ●
Low Oil Pressure Protection ● ● ● ●
High Temperature Warning × ● ● ●
High Temperature Protection ● ● ● ●
Overspeed Warning × ● ● ●
Overspeed Protection × ● ● ●
Alternator Charger ● ● ● ●

Functions
Remote Start ● ● ● ●
AMF (Auto Main Failure) ● ● ● ●
Programmable Intput ● ● ● ●
Programmable Output ● ● ● ●
Expand Module × ○ ○ ○
Communication Function × ○ ○ ●/ RS232 / 485
Communication Port USB ○ ○ RS232 / 485
CAN ● × ● ●
Service Indicate × × ● ●
Fault History ● ● ● ●
Gen-Gen Synchronising × × × ●
Gen-Mains Synchronising × × × ●

Remark: ● Standard Supply ○ Available as Optional × Not Available

Tide Power Technology Co., Ltd. NO.1 Building, YiXu Mechanical & Electrical Park, Gaishan Town, Cangshan District, Fuzhou, Fujian, China.
Our Tel: +86-591-28068999, Fax: +86-591-28068900 Email: [email protected] www.tpshk.com
Page 3
Enclosure / Canopy (Sound-attenuated & Weather Protective)
“Ensure a quieter life with our sound attenuation system.”
Features:
Extremely Rugged & Highly Corrosion Resistant Construction
▪ Body made from 2.0mm sheet steel components with powder coating
▪ 6-8 hours built-in fuel tank integrated into the skid-mount base
▪ Excellent design and craftmanship
▪ Compact structure and longer service life
▪ Residential silcencer to made sure the sound level.
▪ Zinc alloy with black powder coated locks and hinges and
proven to withstand corrosive conditions.

Easy Commissioning and Maintenance


▪ Separate & Standing control room at end side, easy reachable
electrical power connections board.
▪ Side doors allowing 180°opening rotation .
▪ Radiator fill access through cover in canopy roof.
▪ Lube oil drain and radiator drain.
▪ Manual lube oil pump provided.

Security and Safety


▪ Earth leakage protection.
▪ 40-50mm non-inflammable sponge inside.
▪ Control panel viewing window in a lockable access door.
▪ Emergency stop button mounted on canopy exterior.
▪ Fuel fill and battery can only be reached via lockable access doors.
▪ Exhaust silencing system enclosed for operator safety
▪ Efficient management of cooling air to avoid high water temperature,
reliable operation under harshest conditions.

L W

Transportability
▪ Lifting points on top to move genset easily.
▪ Fork lift legs provided and easy to loose to fix the genset. H

Overall Dimensions & Weight & Noice


Dimensions Weight Noice Level Base Tank @100% Load

( L x W x H ) mm kg dB(A) at 7m Hours Litres

4800x1600x2250 5800 65-78 8 930

Tide Power Technology Co., Ltd. NO.1 Building, YiXu Mechanical & Electrical Park, Gaishan Town, Cangshan District, Fuzhou, Fujian, China.
Our Tel: +86-591-28068999, Fax: +86-591-28068900 Email: [email protected] www.tpshk.com
Page 4
Automatic Transfer Switch A.T.S - 4 Poles
Tide Power offers not only a changeover switch but also an integrated mains
detection and switch system for your 24 Hour Power Protection. The system
enables automatic start-up and operation of the generating set in the event of a
mains power failure, overvoltage or loss of a mains automatic re-transfer once it
come back.

System Advantages
▪ Automatically transfer and re-transfer load from main power to gen-power without
operator intervention.operation(Both automatic and manual).
▪ ATS Controller (AMF function), seamless integration with AMF25
▪ Available from 32 – 4000A, better protection for 4 pole switch.
▪ Available in standard, bypass isolation and service-entrance configurations.
▪ Configurable in open, closed and programmed transition operating modes.
▪ Designed to interface seamlessly with TIDE POWER generators and switchgear.
▪ Drip proof IP42 enclosure.
▪ Easy installation: wall-mounted & floor standing
▪ Comes fully loaded with the technology to do the job.

50/60 Hz, 32-4000 Amps

Dimensions : mm
A:400×200×500 B:500×300×650 C:600×400×1200 D:800×600×1400 E:1000×800×1600

Optionals (All depends) Custom-Made solutions

Genset: Genset:

Materials & Miscellaneous Materials & Miscellaneous


Ÿ- Marine class painting and other special painting -Ÿ
On road trailer (EU) type
Ÿ- Standard accoustic enclosure genset Ÿ- Rental type genset
Ÿ- Extended warranty Ÿ- Mining type genset
Ÿ- Extended factory test Ÿ- Marine type genset
Ÿ- Additional sensors Ÿ- High temp. Radiator for silenttype genset
Ÿ- Off road trailer type Ÿ- EPA series gensets
Ÿ- Standard ATS
Ÿ- Mounted fire extinguisher
Ÿ- Additional vibration isolation
Ÿ- Wooden case packaging
Ÿ- Tide Power tool kit
Ÿ- Additional operation manual
Ÿ- Nylon canvas wrapped packaging

Iron shelf for double stack shipping
Ÿ- Water jacket heater
- Additional CE features selection.

Tide Power Technology Co., Ltd. NO.1 Building, YiXu Mechanical & Electrical Park, Gaishan Town, Cangshan District, Fuzhou, Fujian, China.
Our Tel: +86-591-28068999, Fax: +86-591-28068900 Email: [email protected] www.tpshk.com
Page 5
Optionals (All depends) Custom-Made solutions

Diesel Engine/ Baseframe Mounted Accessories: Diesel Engine/ Baseframe Mounted Accessories:

Cooling System Cooling System


Ÿ- Engine heat guards Ÿ- Anti-erosion radiator for silent type genset
Ÿ- Low coolant level alarm & shutdown (Depends on Ÿ- Remote radiator with heat exchanger
engine series) Ÿ- Remote cooling tower with heat exchanger
Ÿ- High temp. & Anti-erosion radiator upgrade for open
type genset
Ÿ- 50% antifreeze @-36°C

Filters Filters
Ÿ- Extra air filters for time-maintenance -Ÿ
Mounted heavy duty air filter
- Double heavy duty air filters
Ÿ- Extra fuel filters for time-maintenance
Ÿ- Extra oil filters for time-maintenance

Exhaust Exhaust
Ÿ- Residential silencer for open type genset Ÿ- Mounted heavy duty air filter
Ÿ- Stainless steel silencer and kits
- Heat protection guard

Fuel & Oil Fuel & Oil


Ÿ- Separated / External fuel tank -Ÿ
Bulk base fuel tank
Ÿ- Water - fuel separator -Ÿ
Bunded base fuel tank
Ÿ- 3 way fuel valve
Ÿ- Manual bypass valve
Ÿ- Lub oil make up tank

Lub oil drain pump
Ÿ- Fuel level sensor
Ÿ- Fuel cooler
Ÿ- Automatic remote fuel supply with fuel level switch
& low fuel level alarmshutdown.

Coolant heater 220/240V
Ÿ- Lub-oil heater for severe cold weather

Starting & Charging Starting & Charging


Ÿ- Bulk starting battery -17°C below Ÿ- None
Ÿ- Battery removal switch
Ÿ- Battery heater

Control System & Power Termination: Control System & Power Termination:

Control System & Breakers Control System & Breakers


Ÿ- Different functional modules with - Ÿ
Various standard sockets mounted outside the enclosure
- Tide Easycon refer to other table
Ÿ- Mounted audible and visable Ilighting
Ÿ- Control panel cover (80kva or below)
Ÿ- Motorized circuit breaker 3 Poles
Ÿ- Motorized circuit breaker 4 Poles
Ÿ- ACB 3 Poles
Ÿ- MCCB 4 poles
Ÿ- Different breaker brands, like ABB etc
Ÿ- Leakage protection switch

Tide Power Technology Co., Ltd. NO.1 Building, YiXu Mechanical & Electrical Park, Gaishan Town, Cangshan District, Fuzhou, Fujian, China.
Our Tel: +86-591-28068999, Fax: +86-591-28068900 Email: [email protected] www.tpshk.com
Page 6
Optionals (All depends) Custom-Made solutions

Brushless Alternator: Brushless Alternator:

Ÿ- 12 Lead stator (change voltage depends) -Ÿ


Temperature rise class F Ÿ
Marine type alternator Ÿ
IP upgrade Ÿ
HV

Interchangeable S.A.E flanges and drive discs
Ÿ- Convenient filters on air inlets and outlets
Ÿ- Coastal type [ ] Alternator painting color Ÿ
P.M.G or auxiliary
Ÿ- AREP for Leroy-Somer only
Ÿ- Shunt trip
Ÿ- Exterior potentiometer
Ÿ- Auxiliary contacts and double bearing

Anti-condensation heater
Ÿ- Stator thermal protection
Ÿ- Quadrature droop kits

Enclosure & Canopy: Enclosure & Canopy:

Weather protective & Sound proof Weather protective & Sound proof
Ÿ- R series -Ÿ
Super silent enclosure

ISO 20ft containerized Ÿ- Weather proof enclosure
Ÿ- ISO 40ft containerized -Ÿ
Flat sponge sound absorber enclosure
- Stainless steel locks and hinges -Ÿ
Porous sheet with rockwool sound absorber enclosure

Please refer to Tide Power sales department for full details of the above options.

Warranty

Tide Power distributor, dealer, or authorized representative p- Warranty Coverage


erforms startup within 6 months of the date of shipment from Generators used to commercial utility source:
the factory, warranty coverage will begin on the startup date One (1) year or 1000 hours (whichever occurs
(Register the startup date to Tide with in 6 month is essential first) from date of shipment from the factory or
and can be enforced). This warranty does not apply to malfun- registered startup date.
ctions caused by damages, unreasonable use, misuse, repair
or service by unauthorized persons, or normal wear and tear.

Tide Power Technology Co., Ltd. NO.1 Building, YiXu Mechanical & Electrical Park, Gaishan Town, Cangshan District, Fuzhou, Fujian, China.
Our Tel: +86-591-28068999, Fax: +86-591-28068900 Email: [email protected] www.tpshk.com
Page 7

You might also like