0% found this document useful (0 votes)
428 views141 pages

DTSC-200 Configuration Manual - 37386 PDF

Uploaded by

Stu Crespi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
428 views141 pages

DTSC-200 Configuration Manual - 37386 PDF

Uploaded by

Stu Crespi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 141

37386D

DTSC-200
ATS Controller

Configuration
Software Version 1.0008

Manual 37386D
Manual 37386D DTSC-200 - ATS Controller

WARNING
Read this entire manual and all other publications pertaining to the work to be performed before
installing, operating, or servicing this equipment. Practice all plant and safety instructions and
precautions. Failure to follow instructions can cause personal injury and/or property damage.
The engine, turbine, or other type of prime mover should be equipped with an overspeed
(overtemperature, or overpressure, where applicable) shutdown device(s), that operates totally
independently of the prime mover control device(s) to protect against runaway or damage to the
engine, turbine, or other type of prime mover with possible personal injury or loss of life should the
mechanical-hydraulic governor(s) or electric control(s), the actuator(s), fuel control(s), the driving
mechanism(s), the linkage(s), or the controlled device(s) fail.
Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical,
or other operating limits may cause personal injury and/or property damage, including damage to the
equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or "negligence" within
the meaning of the product warranty thereby excluding warranty coverage for any resulting damage,
and (ii) invalidate product certifications or listings.

CAUTION
To prevent damage to a control system that uses an alternator or battery-charging device, make sure
the charging device is turned off before disconnecting the battery from the system.
Electronic controls contain static-sensitive parts. Observe the following precautions to prevent
damage to these parts.
• Discharge body static before handling the control (with power to the control turned off, contact a
grounded surface and maintain contact while handling the control).
• Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards.
• Do not touch the components or conductors on a printed circuit board with your hands or with
conductive devices.

OUT-OF-DATE PUBLICATION
This publication may have been revised or updated since this copy was produced. To verify that you
have the latest revision, be sure to check the Woodward website:
http://www.woodward.com/pubs/current.pdf
The revision level is shown at the bottom of the front cover after the publication number. The latest
version of most publications is available at:
http://www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get the latest
copy.

Important definitions

WARNING
Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.

CAUTION
Indicates a potentially hazardous situation that, if not avoided, could result in damage to equipment.

NOTE
Provides other helpful information that does not fall under the warning or caution categories.

Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be
correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.

© Woodward
All Rights Reserved.

Page 2/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Revision History

Rev. Date Editor Changes


NEW 07-12-12 TP Release
A 08-11-25 TE Implementation of the changes starting with SW version 1.0006
B 09-09-17 TE Implementation of the changes starting with SW version 1.0008
• S1 & S2 Start fail delay time: configuration range expanded from 100 s to 6500 s.
• New LogicManager command variable 20.22 added
C 09-12-02 TE Minor corrections
D 11-06-17 TE Minor corrections

Content

CHAPTER 1. GENERAL INFORMATION ....................................................................................... 8


CHAPTER 2. CONFIGURATION .................................................................................................. 9
Configuration Via The Front Panel ........................................................................................................... 9
Configuration Using The PC .................................................................................................................. 10
General Information ............................................................................................................................... 11
Important Designations ................................................................................................................ 11
Signal and Command Abbreviations ........................................................................................... 11
Monitoring Functions.................................................................................................................... 12
Function Of The Inputs And Outputs ..................................................................................................... 13
CHAPTER 3. PARAMETERS..................................................................................................... 15
Language ............................................................................................................................................... 16
Password................................................................................................................................................ 16
Event History .......................................................................................................................................... 17
Measuring............................................................................................................................................... 18
Measuring: Rated Values ............................................................................................................ 18
Measuring: Transformers ............................................................................................................. 22
Application .............................................................................................................................................. 24
Application: Application Mode ...................................................................................................... 24
Application: Transfer Timers ........................................................................................................ 25
Application: Transfer Logics (LogicsManager) ............................................................................ 29
Application: Elevator Pre-Signal .................................................................................................. 33
Application: Motor Load Disconnect ............................................................................................ 35
Application: Source Priority Selection .......................................................................................... 36
Breaker ................................................................................................................................................... 42
Breaker: Transfer Switch Type .................................................................................................... 42
Test Modes............................................................................................................................................. 50

© Woodward Page 3/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring .............................................................................................................................................. 51
Monitoring: Alarm Acknowledgement .......................................................................................... 51
Monitoring: Limit Switch Monitoring............................................................................................. 51
Monitoring: Source 1 Monitoring ................................................................................................. 52
Monitoring: Source 2 Monitoring ................................................................................................. 57
Monitoring: In-Phase Monitoring (Synch Check)......................................................................... 62
Monitoring: Overcurrent ............................................................................................................... 68
Monitoring: Overload ................................................................................................................... 70
Monitoring: Engine, Start Failure Source 1 ................................................................................. 72
Monitoring: Engine, Start Failure Source 2 ................................................................................. 72
Monitoring: Battery, Overvoltage ................................................................................................. 73
Monitoring: Battery, Undervoltage ............................................................................................... 75
Monitoring: CANopen Interface ................................................................................................... 77
Discrete Inputs ....................................................................................................................................... 78
Discrete Outputs (LogicsManager) ........................................................................................................ 80
Counters ................................................................................................................................................ 82
Configure Counters: Operation Hours, kWh, and kvarh.............................................................. 82
LogicsManager ...................................................................................................................................... 83
LogicsManager: Internal Flags .................................................................................................... 83
LogicsManager: Timer ................................................................................................................. 84
Interfaces ............................................................................................................................................... 86
Interfaces: CAN Bus (FlexCAN) .................................................................................................. 86
Interfaces: Serial Interface 1 (RS-232) ........................................................................................ 94
Interfaces: Serial Interface 2 (RS-485) ........................................................................................ 94
System ................................................................................................................................................... 95
System: Configure Display Backlight .......................................................................................... 95
System: Configure Daylight Saving Time .................................................................................... 96
System: Password System .......................................................................................................... 97
System: Real-Time Clock Set ..................................................................................................... 99
System: Versions....................................................................................................................... 100

Page 4/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

APPENDIX A. LOGICSMANAGER ........................................................................................... 101


Logical Symbols ................................................................................................................................... 103
Logical Outputs .................................................................................................................................... 104
Logical Outputs: Internal Flags .................................................................................................. 104
Logical Outputs: Internal functions ............................................................................................ 104
Logical Outputs: Relay Outputs ................................................................................................. 105
Logical Command Variables ................................................................................................................ 106
Logical Command Variables: [00.00] - Internal Flags ................................................................ 106
Logical Command Variables: [01.00] - Alarm Classes .............................................................. 107
Logical Command Variables: [03.00] - Engine Control.............................................................. 107
Logical Command Variables: [04.00] - Operating Status .......................................................... 108
Logical Command Variables: [06.00] - Alarms of the Load ....................................................... 108
Logical Command Variables: [08.00] - Alarms of the System ................................................... 109
Logical Command Variables: [09.00] - Discrete Inputs ............................................................. 109
Logical Command Variables: [11.00] - Time Functions ............................................................. 110
Logical Command Variables: [12.00] - External Discrete Inputs (Expansion Board) ................ 110
Logical Command Variables: [13.00] - Status Of The Internal Relay Outputs .......................... 111
Logical Command Variables: [14.00] - Status Of The External Relay Outputs ......................... 111
Logical Command Variables: [19.00] - ATS Status Flags ......................................................... 112
Logical Command Variables: [20.00] - ATS Status Flags ......................................................... 112
Logical Command Variables: [21.00] - ATS Alarms .................................................................. 113
Logical Command Variables: [98.00] - LogicsManager Outputs ............................................... 113
Factory Setting ..................................................................................................................................... 114
Factory Setting: Functions ......................................................................................................... 114
Factory Setting: Relay Outputs .................................................................................................. 119
Factory Setting: Internal Flags ................................................................................................... 121
Discrete Inputs ........................................................................................................................... 122
APPENDIX B. GETEVENTLOG ............................................................................................... 123
GetEventLog Software ......................................................................................................................... 123
Installing GetEventLog ............................................................................................................... 123
Starting GetEventLog................................................................................................................. 123
Resetting the Event Logger ....................................................................................................... 125
APPENDIX C. LIST OF PARAMETERS .................................................................................... 126
APPENDIX D. SERVICE OPTIONS .......................................................................................... 136
Product Service Options ...................................................................................................................... 136
Returning Equipment For Repair ......................................................................................................... 136
Packing A Control ...................................................................................................................... 137
Return Authorization Number RAN ............................................................................................ 137
Replacement Parts ............................................................................................................................... 137
How To Contact Woodward ................................................................................................................. 138
Engineering Services ........................................................................................................................... 139
Technical Assistance ........................................................................................................................... 140

© Woodward Page 5/141


Manual 37386D DTSC-200 - ATS Controller

Illustrations And Tables

Illustrations
Figure 3-1: Event history- display............................................................................................................................................. 17
Figure 3-2: Source stable and outage timers ............................................................................................................................. 28
Figure 3-3: External timer bypass - push button ....................................................................................................................... 31
Figure 3-4: Elevator pre-signal - example 1 .............................................................................................................................. 34
Figure 3-5: Elevator pre-signal - example 2 .............................................................................................................................. 34
Figure 3-6: Elevator pre-signal - example 3 .............................................................................................................................. 34
Figure 3-7: Source priority selection - S1 preferred .................................................................................................................. 37
Figure 3-8: Source priority selection - S2 preferred .................................................................................................................. 37
Figure 3-9: Load shed relay wiring - standard transition switch ............................................................................................... 41
Figure 3-10: Load shed relay wiring - delayed or closed transition switch ............................................................................... 41
Figure 3-11: Open transition switch - connected to source 1 .................................................................................................... 42
Figure 3-12: Open transition switch - connected to source 2 .................................................................................................... 42
Figure 3-13: Delayed transition switch - connected to source 1 ............................................................................................... 43
Figure 3-14: Delayed transition switch - neutral position ......................................................................................................... 43
Figure 3-15: Delayed transition switch - connected to source 2 ............................................................................................... 43
Figure 3-16: Closed transition switch - connected to source 1 .................................................................................................. 44
Figure 3-17: Closed transition switch - neutral position ........................................................................................................... 44
Figure 3-18: Closed transition switch - connected to source 1 and 2 (overlap position) ........................................................... 44
Figure 3-19: Closed transition switch - connected to source 2 .................................................................................................. 44
Figure 3-20: Breaker - transition pulse ..................................................................................................................................... 47
Figure 3-21: Inphase monitoring............................................................................................................................................... 62
Figure 3-22: Switch reaction time ............................................................................................................................................. 65
Figure 3-23: Monitoring - load time-overcurrent ...................................................................................................................... 68
Figure 3-24: Monitoring - overload .......................................................................................................................................... 70
Figure 3-25: Monitoring - battery overvoltage.......................................................................................................................... 73
Figure 3-26: Monitoring - battery undervoltage........................................................................................................................ 75
Figure 3-27: Discrete inputs - control inputs - operation logic ................................................................................................. 78
Figure 3-28: Interfaces - Principle of PDO mapping ................................................................................................................ 89
Figure 3-29: LogicsManager - function overview .................................................................................................................. 102
Figure 3-30: LogicsManager - display in LeoPC .................................................................................................................... 103
Figure 3-31: LogicsManager - display in LCD ....................................................................................................................... 103
Figure 3-32: GetEventLog - interface configuration ............................................................................................................... 123
Figure 3-33: GetEventLog - event logger content................................................................................................................... 124
Figure 3-34: GetEventLog - event logger content in Excel..................................................................................................... 124

Page 6/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Tables
Table 1-1: Manual - overview ..................................................................................................................................................... 8
Table 3-1: Application - load shed with standard transition switch .......................................................................................... 40
Table 3-2: Application - load shed with delayed or closed transition switch ............................................................................ 41
Table 3-3: Calculation of the phase angle deviation ................................................................................................................. 66
Table 3-4: Monitoring - standard values - load time-overcurrent.............................................................................................. 68
Table 3-5: Monitoring - standard values - overload .................................................................................................................. 70
Table 3-6: Monitoring - standard values - battery overvoltage ................................................................................................. 73
Table 3-7: Monitoring - standard values - battery undervoltage ............................................................................................... 75
Table 3-8: Discrete inputs - assignment .................................................................................................................................... 78
Table 3-9: Discrete inputs - parameter IDs ............................................................................................................................... 79
Table 3-10: External discrete inputs - parameter IDs ................................................................................................................ 79
Table 3-11: Relay outputs - Assignment ................................................................................................................................... 80
Table 3-12: Discrete outputs - parameter IDs ........................................................................................................................... 81
Table 3-13: External discrete outputs - parameter IDs .............................................................................................................. 81
Table 3-14: Internal flags - parameter IDs ................................................................................................................................ 83
Table 3-15: Daylight saving time - configuration example ....................................................................................................... 96
Table 3-16: LogicsManager - command overview ................................................................................................................. 102
Table 3-17: LogicsManager - logical symbols ........................................................................................................................ 103
Table 3-18: Event logger - event texts and numbers ............................................................................................................... 125

© Woodward Page 7/141


Manual 37386D DTSC-200 - ATS Controller

Chapter 1.
General Information

Type English German

DTSC-200 Series
DTSC-200 - Installation 37385 -
DTSC-200 - Configuration this manual  37386 -
DTSC-200 - Operation 37387 -
DTSC-200 - Application 37388 -
DTSC-200 - Interfaces 37389 -

Additional Manuals
IKD 1 - Manual 37135 GR37135
Discrete expansion board with 8 discrete inputs and 8 relay outputs that can be coupled via the CAN bus to the control unit.
Evaluation of the discrete inputs as well as control of the relay outputs is done via the control unit.
LeoPC1 - User Manual 37146 GR37146
PC program for visualization, configuration, remote control, data logging, language upload, alarm and user management, and
management of the event recorder. This manual describes the set up of the program and interfacing with the control unit.
LeoPC1 - Engineering Manual 37164 GR37164
PC program for visualization, configuration, remote control, data logging, language upload, alarm and user management, and
management of the event recorder. This manual describes the configuration and customization of the program.
Table 1-1: Manual - overview

Intended Use The unit must only be operated for the uses described in this manual. The prerequisite for a proper
and safe operation of the product is correct transportation, storage, and installation as well as careful operation
and maintenance.

NOTE
This manual has been developed for a unit fitted with all available options. Inputs/outputs, functions,
configuration screens and other details described, which do not exist on your unit may be ignored.
The present manual has been prepared to enable the installation and commissioning of the unit. On
account of the large variety of parameter settings, it is not possible to cover every possible
combination. The manual is therefore only a guide. In case of incorrect entries or a total loss of
functions, the default settings can be taken from the enclosed list of parameters at the rear of this
manual.

Page 8/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Chapter 2.
Configuration

Configuration Via The Front Panel


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
How to operate the unit via the front panel is explained in the operation manual 37387. Please familiarize
yourself with the unit, the buttons and their meaning/operation and the display monitoring using this manual. The
display of parameters via the front panel will differ from the display of the parameters via the LeoPC1 program
described in this manual. The sequence, the meaning and the setting limits are identical.

© Woodward Page 9/141


Manual 37386D DTSC-200 - ATS Controller

Configuration Using The PC


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
CAUTION
For the configuration of the unit via the PC please use the LeoPC1 software with the following software
version:
LeoPC1 from 3.1.xxx

NOTE
Please note that configuration using the direct configuration cable DPC (product number 5417-557) is
possible starting with revision B of the DPC (first delivered July 2003). If you have an older model
please contact our sales department.

For configuration of the unit via PC program please proceed as follows:

• Install the PC program on your laptop/PC according to the installation manual.


• Before the end of the installation you are requested to select the language with which you want to start the PC
program. You can change the language at any time. The selection of the language refers only to language with
which the menus and subprograms of the PC program works. This setting will not change the language of the
control unit being configured.
• After the installation of the PC program reboot your laptop/PC.
• Establish the connection between your laptop/PC and the unit via the DPC. Plug one side to the configuration
plug of the unit and the other side to the COM1 port of your laptop/PC (other possibilities are described in the
installation manual).
• You may start the PC program as follows:
- by "Start/Program/Woodward/LeoPC" (starting at version 3.1.xxx), or
- by a double click on a file ending ".cfg" in the subdirectory "/LeoPC".
• After the PC program was started, establish the communication by pressing the "F2" button. This will
establish a data link between the unit and the laptop/PC.
• Start the sub program "Device Parameterization" and adjust the parameter of the unit to your application using
this manual.

NOTE
The connection cables delivered with the DPC must be used to connect to the DTSC to ensure that the
controller functions properly. An extension or utilization of different cable types for the connection
between DTSC and DPC may result a malfunction of the DTSC. This may possibly result in damage to
components of the system. If an extension of the data connection line is required, only the serial cable
between DPC and laptop/PC may be extended.

NOTE
If the laptop/PC fails to communicate with the control unit being configured, refer to LeoPC1 manual
37146.

NOTE
Depending on the used computer and the installed operation system, problems with the
communication via an infrared connection may occur.

NOTE
If you want to read or write parameters using a [LeoPC1 Gateway-RS-232 via GW4] connection, you
must configure the parameter "Visualization" to "not active" in LeoPC1. The parameter "Visualization"
may be configured back to "active" after reading and/or writing.

Page 10/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

General Information
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The DTSC-200 has been developed to control ATS (Automatic Transfer Switch) units.

The main purpose of the ATS controller is to control and monitor the transfer switch as well as issuing an engine
start signal to a connected genset control. The controller is continuously monitoring the presence of a source. If
the preferred source fails, it attempts to transfer to a second source (emergency power supply, etc.).

It is NOT the task of an ATS controller to monitor a start/stop sequence. Start and stop failures will be displayed,
but have no effect on the functionality of the controller. Only switch failures or problems with connected position
limit switches, which signal the actual position of the ATS (connected with utility or connected with emergency
power supply, etc.) to the controller, block the ATS controller for further automatic functions.

Important Designations
• Source 1 Usually the preferred power source, e.g. utility supply (depends on application)
• Source 2 Usually the emergency power source, e.g. genset (depends on application)
• Transfer Change from one source to the other

Signal and Command Abbreviations


• S1 Signal: breaker in source 1 position
• S2 Signal: breaker in source 2 position
• S1O Signal: breaker in source 1 OPEN position
• S2O Signal: breaker in source 2 OPEN position
• C1 Command: close to source 1
• C2 Command: close to source 2
• C1O Command: open from source 1
• C2O Command: open from source 2

© Woodward Page 11/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring Functions
Source Monitoring
• Overvoltage / undervoltage
• Overfrequency / underfrequency
• Voltage imbalance
• Rotation field monitoring

NOTE
If one of these monitoring functions is triggered, the ATS controller attempts to change to the non-
preferred source.

Load Monitoring
• Overload
• Overcurrent

Switch Monitoring
• Monitoring for plausible position feedback
• Monitoring for transfer failure

NOTE
If one of these monitoring functions is triggered, the all automatic transfers are blocked.

Generator Monitoring
• Unintended stop
• Start failure

Battery Monitoring
• Overvoltage / undervoltage

Interface Monitoring
• Monitoring of the CANopen communication

Page 12/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Function Of The Inputs And Outputs


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡

Discrete Inputs
The discrete inputs may be grouped into two categories:

• programmable
The programmable discrete input has been programmed with a factory default function using the
LogicsManager. The following text describes how these functions may be changed using the LogicsManager.

• fixed
The discrete input has a specific function that cannot be changed. The discrete input cannot be used in the
LogicsManager.

NOTE
Depending on the configured transfer switch type (parameter 3424), the discrete inputs can be
"programmable" or "fixed". Please refer to Table 3-8 on page 78.

Reply from ATS limit switch: Breaker in source 1 position fixed to discrete input [DI 1], terminal 51/50
 Note: Normally closed (break) contact!

This discrete input indicates to the control that the breaker is closed to source 1 position if it is de-
energized (logic "0").

Reply from ATS limit switch: Breaker in source 2 position fixed to discrete input [DI 2], terminal 52/50
 Note: Normally closed (break) contact!

This discrete input indicates to the control that the breaker is closed to source 2 position if it is de-
energized (logic "0").

Reply from ATS limit switch: Breaker in source 1 open position fixed to discrete input [DI 3], terminal 53/50
 Note: Normally closed (break) contact!

This discrete input indicates to the control that the breaker is in source 1 open position if it is de-
energized (logic "0"). This discrete input is programmable with standard transfer switch type.

Reply from ATS limit switch: Breaker in source 2 open position fixed to discrete input [DI 4], terminal 54/50
 Note: Normally closed (break) contact!

This discrete input indicates to the control that the breaker is in source 2 open position if it is de-
energized (logic "0"). This discrete input is programmable with standard transfer switch type.

Disconnect switch: Inhibit ATS programmable to discrete input [DI 5], terminal 55/50
 Note: Normally closed (break) contact!

This discrete input indicates to the control that the disconnect switch is actuated. If this discrete input is
de-energized (logic "0"), the "Inhibit ATS" function is enabled.

Control Inputs programmable to discrete inputs [DI 6] through [DI 12], terminals 56 through 62 / 50
These discrete inputs may be used as control signals for functions, like priority selection, remote peak
shave, inhibit transfer, etc. The control inputs can be configured freely. Please refer to Discrete Inputs
on page 68.

© Woodward Page 13/141


Manual 37386D DTSC-200 - ATS Controller

Relay Outputs
The discrete outputs can be grouped into two categories:

• programmable
The relay output is freely programmable using the LogicsManager (which is described in the following text).

• pre-defined
The relay output has been pre-defined (programmed) with this function using the LogicsManager (which is
described in the following text). The function may be changed by using the LogicsManager.

NOTE
The relay outputs can be "programmable" or "pre-defined" for a specific function required for the
configured transfer switch type (parameter 3424). Please refer to Table 3-11 on page 80.

LogicsManager Relay {all} programmable to relay [R1] through [R3], terminals 32 through 34 / 31
 Note: Normally open (make) contact!

All relays not assigned a defined function, may be configured via the LogicsManager.

LogicsManager Relay {all} programmable to relay [R4], terminals 35/36/37


 Note: Change-over contact!

All relays not assigned a defined function, may be configured via the LogicsManager.

Start engine {all} pre-defined to relay [R5], terminals 39/40/41


 Note: Change-over contact!

By energizing (or de-energizing, depending on the utilized contact) this relay an engine start signal will
be issued to the genset control.

Command: close to source 1 position {all} pre-defined to relay [R6], terminals 42/43
 Note: Normally open (make) contact!

By energizing this relay, a "close to source 1 position" command will be issued to the ATS.

Command: close to source 2 position {all} pre-definedto relay [R7], terminals 44/45
 Note: Normally open (make) contact!

By energizing this relay, a "close to source 2 position" command will be issued to the ATS.

Command: open from source 1 position to neutral position{all} pre-defined to relay [R8], terminals 46/47
 Note: Normally open (make) contact!

By energizing this relay, an "open from source 1 position to neutral position" command will be issued
to the ATS.

Command: open from source 2 position to neutral position{all} pre-defined to relay [R9], terminals 48/49
 Note: Normally open (make) contact!

By energizing this relay, an "open from source 2 position to neutral position" command will be issued
to the ATS.

Page 14/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Chapter 3.
Parameters

The description of the parameters is confined to the illustration via the PC-program. The parameters are thereby
described as follows.

Language and parameter text


EN: English parameter text
DE: German parameter text

Caption
Brief description of the parameter.

Setting range
Setting limits, valid for these parameter.

Text English Caption Setting range


EN

Text German
DE

CSx {0} {1} {2}


Explanations.
p   

Explanations
Exact description of the parameter, its settings as well
as their effects.

Validity
{0}: Valid for Util-Util application mode (0 gens)
{1}: Valid for Util-Gen application mode (1 gens)
{2}: Valid for Gen-Gen application mode (2 gens)

 Present in this mode.


 Present in this mode, if the function was
configured accordingly.
--- Not present in this mode.

Parameter Display
[CSx] = Visible in code level x
[p] = Parameter number
[L] = Only displayed in LeoPC1 for configuration

© Woodward Page 15/141


Manual 37386D DTSC-200 - ATS Controller

Language
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The following parameter is used to set the unit display language.

Language Set language English / Deutsch


EN

Language
DE

CS0 {0} {1} {2} The desired language for the unit display text is configured here.
1700   

Password
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The DTSC-200 utilizes a password protected multi-level configuration access hierarchy. This permits varying
degrees of access to the parameters being granted by assigning unique passwords to designated personnel. A
distinction is made between the access levels as follows:

Code level CL0 (User Level) Standard password = none


This code level permits for monitoring of the system and limited access to the parameters. Configuration of the
control is not permitted. Only the parameters for setting the language, the date, the time, and the horn reset time
are accessible. The unit powers up in this code level.

Code level CL1 (Basic Level) Standard password = "0 0 0 1"


This code level entitles the user to change selected non-critical parameters, such as setting the parameters
accessible in CL0 plus Bar/PSI, °C/°F. The user may also change the password for level CL1. Access granted by
this password expires two hours after the password has been entered and the user is returned to the CL0 level.

Code level CL2 (Temporary Commissioning Level) No standard password available


This code level grants temporary access to most of the parameters. The password is calculated from the random
number generated when the password is initially accessed. It is designed to grant a user one-time access to a
parameter without having to give him a reusable password. The user may also change the password for
level CL1. Access granted by this password expires two hours after the password has been entered and the user is
returned to the CL0 level. The password for the temp. commissioning level may be obtained from the vendor.

Code level CL3 (Commissioning Level) Standard password = "0 0 0 3"


This code level grants complete and total access to most of the parameters. In addition, the user may also change
the passwords for levels CL1, CL2 and CL3. Access granted by this password expires two hours after the
password has been entered and the user is returned to the CL0 level.

NOTE
Once the code level is entered, access to the configuration menus will be permitted for two hours or
until another password is entered into the control. If a user needs to exit a code level then code level,
CL0 should be entered. This will block unauthorized configuration of the control. A user may return to
CL0 by allowing the entered password to expire after two hours or by changing any one digit on the
random number generated on the password screen and entering it into the unit.
It is possible to disable expiration of the password by entering "0000" after the CL1 or CL3 password
has been entered. Access to the entered code level will remain enabled until another password is
entered. Otherwise, the code level would expire when loading the standard values (default 0000) via
LeoPC 1.

Password Password: Entry via front panel 0000 to 9999


EN

Passwort
DE

CS0 {0} {1} {2} The password for configuring the control via the front panel must be entered here.
10416   

Page 16/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Event History
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The event history is a FIFO (First In/First Out) memory for logging alarm events and operation states of the unit.
The capacity of the event history is 300 entries. As new event messages are entered into the history, the oldest
messages are deleted once 300 events have occurred.
The individual alarm messages, which are stored in the event history, are described in detail in Appendix A:
Operation of manual 37387. The operation states, which are stored in the event history, are listed in the table
below.
The event history display is password-protected.
Refer to Appendix B: GetEventLog starting at page 123 for a description about reading out the event logger using
a software tool.

Figure 3-1: Event history- display

NOTE
The button deletes the highlighted entry!

A date/time stamp is added to each entry. Additional characters (+ and -) indicate the state of the alarm. The
"+" character indicates an alarm condition that is still active. If the alarm conditions are no longer present
anymore, the "+" character will be changed to "-".

Event history display Event history: Display event history Info


EN

Ereignisspeicher anzeigen
DE

CL2 {0} {1} {2} Individual entries can be selected with the or keys and deleted from the event
   history with the key.

NOTE
Refer to Table 3-18 on page 125 for a complete list of all entries, which may appear in the event history.

Clear event log Event history: Clear event history YES / NO


EN

Ereignisspeicher löschen
DE

CL2 {0} {1} {2} YES .............. The complete event history will be deleted. After the event history
1706    has been deleted, this parameter changes back to "NO" automatically.
NO................ The event history will not be deleted.

© Woodward Page 17/141


Manual 37386D DTSC-200 - ATS Controller

Measuring
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
This controller is available in two different hardware version with either 1A [../1] or 5A [../5] current
transformer inputs. Both versions are discussed in this manual. The set points for specific parameters
will differ depending upon the hardware version.

NOTE
It is absolutely necessary for correct rated voltage values to be entered, as many measurement and
monitoring functions refer to these values.

Measuring: Rated Values

Rated system frequency Rated system frequency 50/60 Hz


EN

Nennfrequenz im System
DE

CL2 {0} {1} {2} The rated frequency of the system is used as a reference figure for all frequency
  
1750
related functions, which use a percentage value, like frequency monitoring or
breaker operation windows.

Rated voltage S1 Rated voltage source 1 50 to 650,000 V


EN

Nennspannung S1
DE

CL2 {0} {1} {2}  This value refers to the rated voltage of source 1 and is the voltage
1774    measured on the potential transformer primary.

The source 1 potential transformer primary voltage is entered in this parameter. The
source 1 rated voltage is used as a reference figure for all source 1 voltage related
functions, which use a percentage value, like utility voltage monitoring or breaker
operation windows.

Rated voltage S2 Rated voltage source 2 50 to 650,000 V


EN

Nennspannung S2
DE

CL2 {0} {1} {2}  This value refers to the rated voltage of source 2 and is the voltage
1772    measured on the potential transformer primary.

The source 2 potential transformer primary voltage is entered in this parameter. The
source 2 rated voltage is used as a reference figure for all source 2 voltage related
functions, which use a percentage value, like utility voltage monitoring or breaker
operation windows.

Page 18/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

S1 voltage measuring Measurement principle: Source 1 3Ph 4W / 3Ph 3W / 1Ph 2W / 1Ph 3W

EN
S1 Spannungsmessung

DE
CL2 {0} {1} {2}  Please refer to the comments on measuring principles in the installation
1862    manual (37385).

3Ph 4W ........ Measurement is performed Line-Neutral (WYE connected system).


Phase voltages and the neutral must be connected for proper
calculation. The measurement, display and protection are adjusted
according to the rules for WYE connected systems. Monitoring refers
to the following voltages:
• VL12, VL23, and VL31, or
• VL1N, VL2N and VL3N.
3Ph 3W ........ Measurement is performed Line-Line (Delta connected system).
Phase voltages must be connected for proper calculation. The
measurement, display and protection are adjusted according to the
rules for Delta connected systems. Monitoring refers to the following
voltages:
• VL12, VL23, VL31.
1Ph 2W ........ Measurement is performed for single-phase systems. The
measurement, display and protection are adjusted according to the
rules for single-phase systems. Monitoring refers to the following
voltages:
• VL1N, VL12
1Ph 3W ........ Measurement is performed Line-Neutral (WYE connected system).
The measurement, display, and protection are adjusted according to
the rules for single-phase systems. Monitoring refers to the following
voltages:
• VL1N, VL3N.

© Woodward Page 19/141


Manual 37386D DTSC-200 - ATS Controller

EN
S2 voltage measuring Measurement principle: Source 2 3Ph 4W / 3Ph 3W / 1Ph 2W / 1Ph 3W
S2 Spannungsmessung
DE

CL2 {0} {1} {2}  Please refer to the comments on measuring principles in the installation
1861    manual (37385).

3Ph 4W ........ Measurement is performed Line-Neutral (WYE connected system).


Phase voltages and the neutral must be connected for proper
calculation. The measurement, display and protection are adjusted
according to the rules for WYE connected systems. Monitoring
refers to the following voltages:
• VL12, VL23, and VL31, or
• VL1N, VL2N and VL3N.
3Ph 3W ........ Measurement is performed Line-Line (Delta connected system).
Phase voltages must be connected for proper calculation. The
measurement, display and protection are adjusted according to the
rules for Delta connected systems. Monitoring refers to the
following voltages:
• VL12, VL23, VL31.
1Ph 2W ........ Measurement is performed for single-phase systems. The
measurement, display and protection are adjusted according to the
rules for single-phase systems. Monitoring refers to the following
voltages:
• VL1N, VL12
1Ph 3W ........ Measurement is performed Line-Neutral (WYE connected system).
The measurement, display, and protection are adjusted according to
the rules for single-phase systems. Monitoring refers to the
following voltages:
• VL1N, VL3N.

1Ph2W voltage measuring Measurement principle: 1Ph 2voltage measuring Ph – Ph / Phase - N


EN

Art der 1Ph2W Messung


DE

CL2 {0} {1} {2}  Please refer to the comments on measuring principles in the installation
1858    manual (37385).

This parameter is only visible, if parameter 1862 and/or parameter 1861 is


configured as "1Ph 2W".

Ph – Ph ........ The phase-phase voltages are monitored for 1Ph 2W measuring.


Phase - N ..... The phase-neutral voltages are monitored for 1Ph 2W measuring.

1Ph2W phase rotation Measurement principle: 1Ph 2W phase rotation CW / CCW


EN

Art der 1Ph2W Drehrichtung


DE

CL2 {0} {1} {2}  Please refer to the comments on measuring principles in the installation
1859    manual (37385).

This parameter is only visible, if parameter 1862 and/or parameter 1861 is


configured as "1Ph 2W".

CW ............... A clockwise rotation field is considered for 1Ph 2W measuring .


CCW ............ A counter-clockwise rotation field is considered for 1Ph 2W
measuring.

Page 20/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

S1 Load current measuring Measurement principle: S1 Load current L1 L2 L3 / Phase L1 / Phase L2 / Phase L3

EN
S1 Last Strommessung

DE
CL2 {0} {1} {2}  Please refer to the comments on measuring principles in the installation
1863    manual (37385).

L1 L2 L3 ...... All three phases are monitored. The measurement, display and
protection are adjusted according to the rules for 3-phase
measurement. Monitoring refers to the following currents:
• IL1, IL2, IL3.
Phase L{1/2/3} Only one phase is monitored. The measurement, display and
protection are adjusted according to the rules for single-phase
measurement. Monitoring refers to the selected phase.

Current and power from source 1 to the load are only measured, if the transfer
switch is closed to source 1 position (S1).
The parameters 1860 and 1863 must be configured identical because they share one
common CT set at the load connection.

S2 Load current measuring Measurement principle: S2 Load current L1 L2 L3 / Phase L1 / Phase L2 / Phase L3
EN

S2 Last Strommessung
DE

CL2 {0} {1} {2}  Please refer to the comments on measuring principles in the installation
1860    manual (37385).

L1 L2 L3 ...... All three phases are monitored. The measurement, display and
protection are adjusted according to the rules for 3-phase
measurement. Monitoring refers to the following currents:
• IL1, IL2, IL3.
Phase L{1/2/3} Only one phase is monitored. The measurement, display and
protection are adjusted according to the rules for single-phase
measurement. Monitoring refers to the selected phase.

Current and power from source 2 to the load are only measured, if the transfer
switch is closed to source 2 position (S2).
The parameters 1860 and 1863 must be configured identical because they share one
common CT set at the load connection.

NOTE
It is absolutely necessary for correct rated power and current values to be entered, as many
measurement and monitoring functions refer to these values.

Rated active power [kW] Rated active power 0.5 to 99,999.9 kW


EN

Nennwirkleistung [kW]
DE

CL2 {0} {1} {2} This value specifies the rated power.
1752   

Rated current Rated current 5 to 32,000 A


EN

Nennstrom
DE

CL2 {0} {1} {2} This value specifies the rated current.
1754   

© Woodward Page 21/141


Manual 37386D DTSC-200 - ATS Controller

Measuring: Transformers
Voltage Transformer

S1 voltage transf. primary Voltage transformer, source 1, primary 50 to 650,000 V


EN

S1 Spannungswandler primär
DE

CL2 {0} {1} {2} Some applications may require the use of potential transformers to facilitate
  
1819
measuring the source voltages. The rating of the primary side of the potential
transformer on source 1 must be entered into this parameter.
If the application does not require potential transformers (i.e. the generated voltage
is 480 V or less), then the source volt. will be entered into this parameter.

S1 voltage transf. secondary Voltage transformer, source 1, secondary 50 to 480 V


EN

S1 Spannungswandler sekund.
DE

CL2 {0} {1} {2}  The control is equipped with dual voltage measuring inputs. The voltage
1818    range of these measurement inputs is dependent upon input terminals are
used (see below). This value refers to the secondary voltages of the
potential transformers, which are directly connected to the control.

Some applications may require the use of potential transformers to facilitate


measuring the source voltages. The rating of the secondary side of the potential
transformer on source 1 must be entered into this parameter.
If the application does not require potential transformers (i.e. the generated voltage
is 480 V or less), then the source volt. will be entered into this parameter.

• Rated voltage: 100 Vac (this parameter configured between 50 and 130 V)
- Source 1 voltage: Terminals 15/17/19/21
• Rated voltage: 400 Vac (this parameter configured between 131 and 480 V)
- Source 1 voltage: Terminals 16/18/20/22

S2 volt. transf. primary Voltage transformer, source 2, primary 50 to 650,000 V


EN

S2 Spannungswandler primär
DE

CL2 {0} {1} {2} Some applications may require the use of potential transformers to facilitate
1816    measuring the source voltages. The rating of the primary side of the potential
transformer on source 2 must be entered into this parameter.
If the application does not require potential transformers (i.e. the generated voltage
is 480 V or less), then the source volt. will be entered into this parameter.

S2 volt. transf. secondary Voltage transformer, source 2, secondary 50 to 480 V


EN

S2 Spannungswandler sekund.
DE

CL2 {0} {1} {2}  The control is equipped with dual voltage measuring inputs. The voltage
1815    range of these measurement inputs is dependent upon input terminals are
used (see below). This value refers to the secondary voltages of the
potential transformers, which are directly connected to the control.

Some applications may require the use of potential transformers to facilitate


measuring the source voltages. The rating of the secondary side of the potential
transformer on source 2 must be entered into this parameter.
If the application does not require potential transformers (i.e. the generated voltage
is 480 V or less), then the source volt. will be entered into this parameter.

• Rated voltage: 100 Vac (this parameter configured between 50 and 130 V)
- Source 2 voltage: Terminals 23/25/27/29
• Rated voltage: 400 Vac (this parameter configured between 131 and 480 V)
- Source 2 voltage: Terminals 24/26/28/30

Page 22/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Current Transformer

NOTE
This controller is available in two different hardware version with either 1A [../1] or 5A [../5] current
transformer inputs. Both versions are discussed in this manual. The set points for specific parameters
will differ depending upon the hardware version, indicated on the data plate.
• [1] DTSC-200-1 = Current transformer with ../1 A rated current
• [5] DTSC-200-5 = Current transformer with ../5 A rated current

Load Current transformer Current transformer, load 1 to 32,000/5 A


EN

Last Stromwandler
DE

CL2 {0} {1} {2} This screen only applies to controls equipped with 5 A CT inputs. This
  
1821
will not be displayed in the controller screen of a unit equipped with 1 A
CT inputs.

The input of the current transformer ratio is necessary for the indication and
control of the actual monitored value. The current transformers ratio should be
selected so that at least 60% of the secondary current rating can be measured
when the monitored system is at 100% of operating capacity (i.e. at 100% of
system capacity a 5 A CT should output 3 A). If the current transformers are sized
so that the percentage of the output is lower, the loss of resolution may cause
inaccuracies in the monitoring and control functions and affect the functionality
of the control.

Load Current transformer Current transformer, load 1 to 32,000/1 A


EN

Last Stromwandler
DE

CL2 {0} {1} {2} This screen only applies to controls equipped with 1 A CT inputs. This
1822    will not be displayed in the controller screen of a unit equipped with 5 A
CT inputs.

The input of the current transformer ratio is necessary for the indication and
control of the actual monitored value. The current transformers ratio should be
selected so that at least 60% of the secondary current rating can be measured
when the monitored system is at 100% of operating capacity (i.e. at 100% of
system capacity a 5 A CT should output 3 A). If the current transformers are sized
so that the percentage of the output is lower, the loss of resolution may cause
inaccuracies in the monitoring and control functions and affect the functionality
of the control.

© Woodward Page 23/141


Manual 37386D DTSC-200 - ATS Controller

Application
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Application: Application Mode

Application mode Application mode Util-Gen / Gen-Gen / Util-Util


EN

Betriebsmodus
DE

CL2 {0} {1} {2} This parameter selects the basic function of the unit. If the unit is used to transfer
4148    the load between two utility sources (setting "Util-Util"), no engine start signals are
issued.

Util-Util ........Application "utility-utility" {0}


No engine start signals will be issued.

Source 1 Source 2
Util-Gen .......Standard application "utility-generator" {1}
Engine start signals will be issued for source 2 only.

G
Source 1 Source 2
Gen-Gen .......Application "generator-generator" {2}
Engine start signals will be issued for source 1 and source 2.

G G
Source 1 Source 2

NOTE
In Util-Gen application, source S2 is considered as the generator.

Page 24/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Application: Transfer Timers

Transfer commit Transfer commit YES / NO

EN
Transfer zustimmen
DE
CL2 {0} {1} {2} This function is only effective if a transfer from the preferred source to the non-
4146 ---  --- preferred source is requested.

YES .............. A transfer to the non-preferred source is committed as soon as the


non-preferred source stable timer has started to count. The transfer
will be performed after the stable timer has expired, even if the
preferred source restores.
NO................ A transfer to the non-preferred source is only committed, if the non-
preferred source stable timer has expired completely.
If the preferred source restores while the non-preferred source stable
timer is still counting, the whole process will be aborted and the
transfer switch remains on the preferred source.

S1 start delay time Source 1 start delay time 1 to 300 s


EN

S1 Startverzögerung
DE

CL2 {0} {1} {2} This parameter delays the de-energizing of the start relay (and thus the engine start)
4149 --- ---  if source 2 is considered as "not OK" or a start, "Load Test", " No Load Test",
remote peak shave or interruptible power rates request is performed.
The counter starts as soon as source 2 is considered as "not OK" or the start request
is initiated.
If source 2 returns before this counter has expired, the timer will be terminated and
the controller returns to standby mode (since it is not intended that the engine starts
with every short temporary line fault).
If the timer has expired and source 2 has not been considered as "OK", the engine
start relay will be de-energized, the engine will be started, and flag 20.05 "S1 Start
Signal" will be enabled.

If this timer is running, the "S1 start delay" message and the Bypass softkey are
displayed.

S2 start delay time Source 2 start delay time 1 to 300 s


EN

S2 Startverzögerung
DE

CL2 {0} {1} {2} This parameter delays the de-energizing of the start relay (and thus the engine start)
3330 ---   if source 1 is considered as "not OK" or a start, "Load Test", " No Load Test",
remote peak shave or interruptible power rates request is performed.
The counter starts as soon as source 1 is considered as "not OK" or the start request
is initiated.
If source 1 returns before this counter has expired, the timer will be terminated and
the controller returns to standby mode (since it is not intended that the engine starts
with every short temporary line fault).
If the timer has expired and source 1 has not been considered as "OK", the engine
start relay will be de-energized, the engine will be started, and flag 20.06 "S2 Start
Signal" will be enabled.

If this timer is running, the "S2 start delay" message and the Bypass softkey are
displayed.

© Woodward Page 25/141


Manual 37386D DTSC-200 - ATS Controller

EN
S1 Source Stable time Source 1 source stable time 1 to 6500 s
S1 Stabilisierzeit
DE

CL2 {0} {1} {2} This parameter configures the delay before source 1 is considered as OK. This
3333    timer starts after the last monitored value has returned within the restore limits
following a source 1 outage. Source 1 will be considered as OK again after this
timer has expired. If the voltage and/or frequency exceeds the restore limits again
before the timer expires, the timer will be reset (refer to Figure 3-2).
The source 1 stable timer is automatically bypassed if source 1 is the preferred
source and the outage delay of source 2 (non-preferred) has expired.
If source 1 fails unexpectedly before this timer has expired, it will be terminated
and the load will still be supplied by source 2.
This timer is intended to delay the transfer to ensure that source 1 voltage and
frequency are definitely stable before the ATS switch is operated to perform a
transfer to source 1.

If this timer is running, the "S1 stable timer" message and the Bypass softkey are
displayed.

NOTE
In case a "load test" is being performed (i.e. the load is supplied by source 2, but source 1 is present as
well and OK) and source 2 fails, the "S1 source stable timer" will be bypassed completely to be able to
change back (OK) to source 1 immediately. This is intended to ensure that the load is not de-energized
if a genset failure takes place during a load test.

S2 Source Stable time Source 2 source stable time 1 to 6500 s


EN

S2 Stabilisierzeit
DE

CL2 {0} {1} {2} This parameter configures the delay before source 2 is considered as OK. This
3332    timer starts after the last monitored value has returned within the restore limits
following a source 2 outage. Source 2 will be considered as OK again after this
timer has expired. If the voltage and/or frequency exceeds the restore limits again
before the timer expires, the timer will be reset (refer to Figure 3-2).
The source 2 stable timer is automatically bypassed if source 2 is the preferred
source and the outage delay of source 1 (non-preferred) has expired.
If source 2 fails unexpectedly before this timer has expired, it will be terminated
and the load will still be supplied by source 1.
This timer is intended to delay the transfer to ensure that source 2 voltage and
frequency are definitely stable before the ATS switch is operated to perform a
transfer to source 2.

If this timer is running, the "S2 stable timer" message and the Bypass softkey are
displayed.

Page 26/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

S1 outage delay Source 1 outage delay 0.1 to 10.0 s

EN
S1 Ausfallverzögerung

DE
CL2 {0} {1} {2} This timer defines the maximum time before source 1 (voltage, frequency and
2804 --- ---  phase rotation) is considered as "not OK" to initiate a transfer to source 2. This
timer starts if one of the monitored source 1 values exceeds the fail limits. Source 1
will be considered as "not OK", after this timer has expired. If the voltage and/or
frequency returns within the fail limits before the timer expires, the timer will be
reset (refer to Figure 3-2).
This timer is intended to prevent an immediate transfer to source 2 in case of a
temporary voltage or frequency drop during a load test due to a short temporary
failure of source 1 (i.e. ignition miss of a genset, etc.).

If this timer has expired, the alarm "Unint. stop S1" is issued.

Note: If source 2 is the "preferred source" and the "S1 outage delay" timer has
expired (i.e. source 1 is considered as "not OK"), the "S2 source stable timer" will
be bypassed.

S2 outage delay Source 2 outage delay 0.1 to 10.0 s


EN

S2 Ausfallverzögerung
DE

CL2 {0} {1} {2} This timer defines the maximum time before source 2 (voltage, frequency and
2803 ---   phase rotation) is considered as "not OK" to initiate a transfer to source 1. This
timer starts if one of the monitored source 2 values exceeds the fail limits. Source 2
will be considered as "not OK", after this timer has expired. If the voltage and/or
frequency returns within the fail limits before the timer expires, the timer will be
reset (refer to Figure 3-2).
This timer is intended to prevent an immediate transfer to source 1 in case of a
temporary voltage or frequency drop during a load test due to a short temporary
failure of source 2 (i.e. ignition miss of a genset, etc.).

If this timer has expired, the alarm "Unint. stop S2" is issued.

Note: If source 1 is the "preferred source" and the "S2 outage delay" timer has
expired (i.e. source 2 is considered as "not OK"), the "S1 source stable timer" will
be bypassed.

© Woodward Page 27/141


Manual 37386D DTSC-200 - ATS Controller

[V], [f]
rated
value source stable timer source stable timer

restore
value

source source OK
not OK

outage outage
delay delay
timer timer

fail
value

source is stable [t]


stable timer start outage timer start source has failed
stable timer start outage timer start

Figure 3-2: Source stable and outage timers

NOTE
Figure 3-2 describes the principle of stable and outage timers for an example where a threshold needs
to be exceeded to consider the source as "OK" (like underfrequency or undervoltage).
In case, a threshold needs to be fallen below to consider the source as "OK" (like overfrequency,
voltage imbalance or overvoltage), the restore value is lower than the fail value.

S1 cooldown time Engine 1 cooldown time 1 to 6500 s


EN

S1 Nachlaufzeit
DE

CL2 {0} {1} {2} This parameter configures the duration of the cool down phase of engine 1 after the
3343 --- ---  load has been disconnected.

If this timer is running, the "S1 cooldown" message and the Bypass softkey are
displayed.

S2 cooldown time Engine 2 cooldown time 1 to 6500 s


EN

S2 Nachlaufzeit
DE

CL2 {0} {1} {2} This parameter configures the duration of the cool down phase of engine 2 after the
3344 ---   load has been disconnected.

If this timer is running, the "S2 cooldown" message and the Bypass softkey are
displayed.

Page 28/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Application: Transfer Logics (LogicsManager)

NOTE
All functions which are described in the following text may be assigned by the LogicsManager to any
relay which is available via the LogicsManager and not assigned to another function. The assignment
of the defined relays to defined functions occurs by selection of the application mode. The same way
some relays are designated to specific functions, others may be assigned to different functions. These
are listed as "programmed" relays. If a relay is "programmable" the function may be assigned to other
relays via the LogicsManager by configuration.

Inhibit ATS
If this logical output becomes TRUE, the ATS controller is blocked against automatic transfers and the "ATS
Inhibit" message is displayed. Usually, a selected relay output is configured to this LogicsManager function,
which may be used to block the ATS controller when a disconnect switch is connected to this "Inhibit ATS" relay
output.
All automatic transfers will be blocked. Only the "Engine start" signal will still be issued.

Inhibit ATS Inhibit ATS LogicsManager


EN

Blockiere ATS
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
  
12600
A: "LogicsManager".

NOTE
The disconnect switch is ALWAYS inside the ATS cabinet. If the ATS shall be operated manually, the
disconnect switch will be switched to the "Inhibit ATS" position. This blocks the ATS controller against
the automatic initiation of a transfer and the switch may easily be operated manually.

WARNING
If the ATS controller performs a transfer during a service technician switches the ATS with a manual
handle, this may cause serious injuries.
Always inhibit automatic ATS transfers before performing a manual transfer!

© Woodward Page 29/141


Manual 37386D DTSC-200 - ATS Controller

Inhibit Transfer to Source 1


If this logical output becomes TRUE, the transfer back to source 1 will be blocked temporarily and the "Inhib.
XFR to S1" message is displayed.

Application example:
Supposed, there is a failure of source 1 (preferred source) in a hospital. Then, source 2 will be started and a
transfer to source 2 will be performed. Now, the load is supplied by source 2.
If source 1 would return, a transfer back to source 1 would be initiated. This may be prevented by making this
LogicsManager function TRUE (by energizing a DI for example) because a transfer back to source 1 may cause
some risks if a difficult surgery is in progress for example. A mechanical failure of the transfer switch during
transferring back would be a serious risk for the patient.

Inhib. XFR to S1 Inhibit transfer to source 1 LogicsManager


EN

Trans S1 sperren
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12610    A: "LogicsManager".

Inhibit Transfer to Source 2


If this logical output becomes TRUE, the transfer to source 2 will be blocked temporarily and the "Inhib. XFR to
S2" message is displayed.

This function has the same behavior as the "Inhibit XFR to source 1" function, except that a transfer to source 2
will be prevented.

Inhib. XFR to S2 Inhibit transfer to source 2 LogicsManager


EN

Trans S2 sperren
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
  
12620
A: "LogicsManager".

Remote Peak Shave


If this logical output becomes TRUE, the non-preferred source will be started, a transfer to the non-preferred
source will be performed, and the "Rem.peak shave" message is displayed as soon as the non-preferred source
supplies the load. Now, the load will be supplied by the non-preferred source. If the logical output becomes
FALSE again, a regular transfer sequence back to the preferred source will be performed including the expiry of
all timers belonging to this sequence.
If the non-preferred source fails during a remote peak shave request and the preferred source is available, an
immediate transfer back to the preferred source will be performed.

This function may be used to initiate a load test.

Remote peak shave Remote peak shave LogicsManager


EN

Spitzenlast Modus
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
  
12630
A: "LogicsManager".

Page 30/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Interruptible Power Rate Provisions


If this logical output becomes TRUE, the non-preferred source will be started, a transfer to the non-preferred
source will be performed, and the "Pwr.rate.prov." message is displayed as soon as the non-preferred source
supplies the load. Now, the load will be supplied by the non-preferred source. If the logical output becomes
FALSE again, a regular transfer sequence back to the preferred source will be performed including the expiry of
all timers belonging to this sequence.
If the non-preferred source fails during an interruptible power rate provisions request and the preferred source is
available, an immediate transfer back to the preferred source will be performed.

This function may be used in some countries where the provider offers contracts, which contain provisions for the
customer to disconnect from the utility during peak load times and change to a different power supply (e.g.
genset), like the United States. In case the alternative (genset) supply fails during a "Interruptible power rate
provisions" request, a transfer to the preferred source will be performed with the effect that the customer must
pay a reimbursement to the provider.

Int. pow. rates Interruptible power rate provisions LogicsManager


EN

Anforder. Netzbetr.
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12660    A: "LogicsManager".

External Timer Bypass


If this logical output becomes TRUE (by energizing a DI for example), all timers, which are in progress at the
moment and can be bypassed, are bypassed. This has the same effect as pressing the "Bypass" softkey.

Ext. bypass External timer bypass LogicsManager


EN

Ext. Zeit Bypass


DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
  
12820
A: "LogicsManager".

NOTE
If another timer becomes active immediately after the previous timer has been bypassed, the discrete
input must be de-energized before it may be energized again to bypass the next timer. We recommend
to use a momentary push-to-make button for this function.

Push button

Discrete input

Figure 3-3: External timer bypass - push button

© Woodward Page 31/141


Manual 37386D DTSC-200 - ATS Controller

Gen-Gen Enable
This function is only enabled if the application mode (parameter 4148) is configured to "Gen-Gen". If this logical
output becomes TRUE (by energizing a DI for example), the gen-gen mode will be enabled.

The behavior of the function depends on the source priority:

• Only the LogicsManager function "Source priority S1" (parameter 12680) is TRUE:
The source 1 genset will be started. If source 1 doesn't start or fails, source 2 genset will be started
automatically.

• Only the LogicsManager function "Source priority S2" (parameter 12810) is TRUE:
The source 2 genset will be started. If source 2 doesn't start or fails, source 1 genset will be started
automatically.

• Both source priority LogicsManager functions (parameters 12680 and 12810) are TRUE or both are FALSE:
Source 1 has priority, i.e. the source 1 genset will be started. If source 1 doesn't start, source 2 genset will be
started automatically.

If the gen-gen mode will be disabled again, all start requests are terminated and the genset, which is currently in
operation, will be shut down with a cool down.

Gen-Gen enable Generator-Generator mode enable LogicsManager


EN

Gen-Gen Aktivieren
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12830 --- ---  A: "LogicsManager".

Page 32/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Application: Elevator Pre-Signal

The elevator pre-signal flag (20.01) may be assigned to any output relay using the LogicsManager.

The elevator pre-signal is important for buildings which are equipped with elevators. This signal will be enabled
before any transfer in order to signal a transfer to an elevator control. If this signal is received by an elevator
control, the elevator stops at the next floor and opens the doors. This signal is enabled until the transfer is
completed. Then, the signal will be disabled and the elevator is able to operate regularly again.

This function may be used if there is a load test performed during regular hospital operation. A load test means
that two sources are available. This signal will not be set in case of a utility failure. In this case, the elevator
might get stuck between two floors and it makes no sense to enable the elevator pre-signal. Possibly stuck
elevators are accepted and the main target is to attempt to supply the load. As soon as the supply returns, the
elevators are ready to operate again.

NOTE
The elevator pre signal (EPS) may be enabled in parallel with a motor load disconnect signal (MLD) if a
MLD signal is configured. EPS and MLD are two functions, which operate completely independent and
don't affect each other.
If the EPS timer will be bypassed, the MLD signal will be processed consequently (if configured).
Otherwise, the transfer sequence will be continued. If the transfer has been performed, the EPS signal
will be reset. This is also valid, if the EPS signal has been bypassed prior to the transfer and a MLD
timer was configured additionally.
This timer is automatically bypassed, if not both sources are available (and stable) for transfer.
If, for example, a load test has been requested and cancelled again while the EPS signal is active, the
EPS relay will be reset automatically and the complete process will be terminated.

Elevator Pre Signal Elevator pre-signal ON / OFF


EN

Aufzugswarnsignal
DE

CL2 {0} {1} {2} OFF.............. No elevator pre-signal is issued, no elevator pre-signal timer starts
4490    and the LogicsManager flag 20.01 is not enabled.
ON................ The elevator pre-signal will be issued before any transfer and the
LogicsManager flag 20.01 will be enabled. The remaining elevator
pre-signal time is displayed.

Elevator pre-signal duration Elevator pre-signal duration 1 to 6500 s


EN

Warnsignal Dauer
DE

CL2 {0} {1} {2} The time configured here determines how long the elevator pre-signal is enabled
4491    before the transfer process will be continued. The signal will be disabled again if
the transfer process has been completed.
If this timer is running, the "Pre signal timer" message is displayed.

© Woodward Page 33/141


Manual 37386D DTSC-200 - ATS Controller

The following examples show the behavior of the elevator pre-signal for different applications.

Example 1 (elevator pre-signal disabled):

Transfer to non-preferred
source is requested &
non-preferred source non-preferred source
has been started stable timer Transfer initiated

non-preferred source is stable timer has expired


within the restore limits and transfer is initiated
and stable timer starts
Figure 3-4: Elevator pre-signal - example 1

Example 2 (elevator pre-signal enabled):

Transfer to non-preferred non-preferred source


source is requested & stable timer
non-preferred source
has been started Transfer initiated
EPS timer

non-preferred source is stable AND EPS timers


within the restore limits have expired and
and stable timer starts transfer is initiated
Figure 3-5: Elevator pre-signal - example 2

This example assumes that the non-preferred source stable timer is configured higher than the EPS timer. If the
EPS timer would be configured higher, it would start together with the stable timer and the transfer is initiated if
all timers have expired.

Example 3 (elevator pre-signal and motor load disconnect enabled):

Transfer to non-preferred non-preferred source


source is requested & stable timer
non-preferred source
has been started Transfer initiated
MLD timer

EPS timer

non-preferred source is stable, MLD AND EPS


within the restore limits timers have expired and
and stable timer starts transfer is initiated
Figure 3-6: Elevator pre-signal - example 3

This example assumes that the non-preferred source stable timer is configured higher than the EPS and the MLD
timer. If the EPS or the MLD timer would be configured higher, they would start together with the stable timer
and the transfer is initiated if all timers have expired.

Page 34/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Application: Motor Load Disconnect

The motor load disconnect flag (20.02) may be assigned to any output relay using the LogicsManager.

The motor load disconnect function is intended for sequential load shedding before a transfer and sequential load
addition after a transfer. This shall prevent the addition of the complete load at once.
The loads will be disconnected one after the other before a transfer. Then, the loads will be connected again in the
same order following the transfer.

In contrast to the elevator pre-signal, this signal will also be enabled in case of a preferred source failure. No
automatic or manual bypass of this signal will be performed.

Motor Load Disconnect Motor load disconnect ON / OFF


EN

Lastabwurf
DE

CL2 {0} {1} {2} OFF .............. No motor load disconnect signal is issued, no motor load disconnect
4550    signal timer starts and the LogicsManager flag 20.02 is not enabled.
It will be proceeded with the operation of the transfer switch.
ON ................ The motor load disconnect signal will be issued before any transfer
and the LogicsManager flag 20.02 will be enabled. The remaining
motor load disconnect signal time is displayed with the "Motor Load
Disc." message. After the motor load disconnect timer expires, the
transfer switch will be operated. The signal will be disabled again if
the transfer process has been completed.

Active direction Active direction S1->S2 / S1<-S2 / Both


EN

Aktive Richtung für Lastabwurf


DE

CL2 {0} {1} {2} This parameter configures the transfer direction into which the motor load
4553    disconnect signal is enabled.
S1->S2 ......... The motor load disconnect signal is only enabled in this transfer
direction. The LogicsManager flag 20.02 will not be enabled when
transferring from source 2 to source 1.
S1<-S2 ......... The motor load disconnect signal is only enabled in this transfer
direction. The LogicsManager flag 20.02 will not be enabled when
transferring from source 1 to source 2.
Both ............. The motor load disconnect signal is always enabled in both transfer
directions.

Disconnect time S1->S2 Disconnect time S1 -> S2 1 to 6500 s


EN

Lastabwurfszeit S1
DE

CL2 {0} {1} {2} This parameter configures the maximum duration of the motor disconnect signal
4551    in source 1 to source 2 transfer direction. After the timer has expired, the transfer
to source 2 will be performed

Disconnect time S2->S1 Disconnect time S2 -> S1 1 to 6500 s


EN

Lastabwurfszeit S2
DE

CL2 {0} {1} {2} This parameter configures the maximum duration of the motor disconnect signal
4552    in source 2 to source 1 transfer direction. After the timer has expired, the transfer
to source 1 will be performed

© Woodward Page 35/141


Manual 37386D DTSC-200 - ATS Controller

Application: Source Priority Selection

The two LogicsManager functions "Source Priority S1" and "Source Priority S2" are used to determine which
source is to be considered as preferred. The LogicsManager enables to use a discrete input for example to select
the preferred source externally using a source priority selector switch, which is usually on the operation panel.

In general, the preferred source is the one, which is permanently available. The NON-preferred source serves as
second source, which will be enabled if the preferred source fails or if a remote start signal is present.

The following constellations are possible:

• One utility supply, one generator (Util-Gen application)


If the utility (source 1) is defined as preferred source, the genset (source 2) will be started if the utility fails.
If the genset is defined as preferred source, the engine start signal is permanently enabled until the source
priority changes to the other source.

NOTE
Changing the priority during a load test (parameter 12640), remote peak shave (parameter 12630) or
interruptible power rates (parameter 12660) operation is enabled, results in a transfer to the selected
non-preferred source.

• Two utility supply networks (Util-Util application)


In this case, the customer might select one utility supply as preferred source. In case of a failure of the
preferred source, the load will be transferred to the other source.

• Two generators (Gen-Gen application)


In this case, the customer might select one generator as preferred source. In case of a failure of the preferred
source, the other genset will be started and the load will be transferred to the other source.

If the LogicsManager function "Source Priority S1" becomes TRUE, source 1 will be considered as preferred.

S1 Priority Source Priority S1 LogicsManager


EN

S1 Priorität
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12680    A: "LogicsManager".

If the LogicsManager function "Source Priority S2" becomes TRUE, source 2 will be considered as preferred.

S2 Priority Source Priority S2 LogicsManager


EN

S2 Priorität
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12810    A: "LogicsManager".

NOTE
If no source is preferred (both LogicsManager functions are FALSE or both LogicsManager functions
are TRUE), source 1 will be the preferred source.

Page 36/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Application example 1 (source priority = S1):

Transfer direction
upon loss of S1

S1 S2
preferred source non-preferred source
(emergency source)
Load
Figure 3-7: Source priority selection - S1 preferred

Application example 2 (source priority = S2):

Transfer direction
upon loss of S2

S1 S2
non-preferred source preferred source
(emergency source)
Load
Figure 3-8: Source priority selection - S2 preferred

If the preferred source is available, the load will automatically be connected to the preferred source (except a
transfer to the non-preferred source is forced by a load test or remote peak shave, etc.).

It is also possible to change the source priority while the load is connected to the preferred or non-preferred
source.

If the load is connected to the non-preferred source and this non-preferred source will be declared as the preferred
source, the load remains connected to this source.
If the load is connected to the preferred source and this preferred source will be declared as the non-preferred
source, the load will be transferred to the "new" preferred source.

© Woodward Page 37/141


Manual 37386D DTSC-200 - ATS Controller

Extended Parallel Time

NOTE
This function is only effective if the transfer switch type (parameter 3424) is configured to "Closed" and
in-phase monitoring (parameter 4570) is enabled.

If a closed transition is performed, the overlap time of the make-before-break process, in which both sources are
parallel, is as configured in parameter 4577 (Max. overlap time). If this time is to be extended, a LogicsManager
function is available to keep the transition switch in overlap position. This may be achieved by a digital signal of
an external synchronization device for example.

If the LogicsManager function "Ext. para. time" becomes TRUE, the transfer switch will remain in overlap
position. If it becomes FALSE again, the source, from which the transfer has been initiated, will be disconnected
and the load will be supplied by the new source.

Ext. para. time Extended parallel time LogicsManager


EN

Erweiterte para. Zeit


DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12860    A: "LogicsManager".

NOTE
As long as this function is TRUE, parameter 4577 (Max. overlap time) is not effective.
Exception: If parameter 4577 (Max. overlap time) is configured to 0.1 s, an extended parallel time is not
possible regardless of the state of this function.

NOTE
If one source fails as long as this function is TRUE, the failed source will automatically be
disconnected.

WARNING
Both sources remain in overlap position as long as this function is TRUE.
Both sources are not decoupled if
• a load test (parameter 12640 on page 50) is disabled
• a remote peak shave request (parameter 12630 on page 30) is disabled
• an interruptible power rate request (parameter 12660 on page 31) is disabled
• the priority is changed
An overlap situation is only decoupled if
• the "Extended parallel time" function becomes FALSE again
• the phase angle during overlap position is > 2.0° or < -2.0°

Page 38/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

The following example shows a typical transfer sequence from source 1 to source 2 with extended parallel time:

Initial situation:
S1 S2 Load is supplied by source 1

A transfer is initiated (e.g. by a load test):


S1 S2 As soon as source 2 is detected as stable and synchronicity is
achieved, the transfer switch is closed to source 2.
2

Extended parallel time is active:


S1 S2 As long as the LogicsManager function is TRUE, the transfer
switch remains in overlap position and load is supplied by both
3 sources.

Extended parallel time expires:


S1 S2 As soon as the LogicsManager function becomes FALSE, the
transfer switch opens from source 2.
4

Final situation:
S1 S2 Load is supplied by source 1

© Woodward Page 39/141


Manual 37386D DTSC-200 - ATS Controller

Load Shed

NOTE
Load shed is inactive as long as an "Extended parallel time" (parameter 12860) is enabled.
The load shed function bypasses the in-phase monitoring function. This can cause an asynchronous
transfer in case a standard transition switch is used.

The load shed function is intended to shed the load from the non-preferred source if a load shed signal is received
from a master controller (e.g. SCADA system) via a discrete input.

If a load shed signal is received from a master control, the DTSC disconnects the load from the non-preferred
source immediately. The following rules are valid for the load shed function:

• The load must be supplied by the non-preferred source. The load shed function can only trigger to disconnect
the load from the non-preferred source. If the load is supplied by the preferred source while a load shed
signal is triggered, the load will not be disconnected.
• Possible timers for pre-transfer signals like motor load disconnect or elevator pre-signal, which are enabled
prior to the transfer will be ignored in case of a load shed request.
• If in-phase monitoring is enabled, this will be ignored in case of a load shed request.
• If the LogicsManager function "Inhibit XFR to S1" or "Inhibit XFR to S2" is TRUE and would prevent a
transfer to the preferred source, this function will be ignored on case of a standard transition switch. If a
delayed or closed transition switch is used, the switch will open to neutral position.
• If transfer switches are used, which may only be operated in case a measuring voltage is present, a transfer to
the preferred source may only be possible, when it is present. If only the non-preferred source is present, the
LogicsManager flag "Load shed" (20.11) will be enabled. This flag enables to close a load shed relay, which
connects the voltage of the non-preferred source to the preferred source side of the transfer switch to operate
it. If the neutral position (delayed / closed switch) or the preferred source position (standard switch) is
detected by the DTSC, the load shed signal will be reset again. Refer to Figure 3-9 and Figure 3-10 for more
detailed information.

If the LogicsManager function "Load shed" becomes TRUE, a load shed from the non-preferred source will be
performed.

Load shed Load shedding enabled LogicsManager


EN

Nicht prio. LS auf


DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12870    A: "LogicsManager".

Table 3-1 defines the behavior in case of a load shed request when utilizing a standard transition switch
depending on the system conditions.

Load is connected to Pre-transfer In-phase Preferred source Behavior on load shed request
signals monitoring available
Non-preferred source Bypassed Bypassed Yes Immediate transfer to preferred source
Non-preferred source Bypassed Bypassed No LogicsManager flag "Load shed" (20.11) is set to transfer to the
preferred source
Preferred source N/A N/A Yes No action performed - load remains connected to preferred source
Table 3-1: Application - load shed with standard transition switch

Page 40/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Table 3-2 defines the behavior in case of a load shed request when utilizing a delayed or closed transition switch
depending on the system conditions.

Load is connected to Pre-transfer In-phase Preferred source Behavior on load shed request
signals monitoring available
Non-preferred source Bypassed Bypassed Yes Immediate transfer to preferred source
Non-preferred source Bypassed Bypassed No LogicsManager flag "Load shed" (20.11) is immediately set to
open to neutral position
If the preferred source restores while the switch is in neutral
position, a transfer to the preferred source is initiated without
waiting for the preferred source stable timer to expire
Preferred source N/A N/A Yes No action performed - load remains connected to preferred source
Table 3-2: Application - load shed with delayed or closed transition switch

Figure 3-9 shows how to wire a load shed relay for applications, which use a standard transition switch (S1 is the
preferred source and S2 is the non-preferred source with this application).

Load Shed Relay


(LM Flag 20.11)

Transfer
Switch
S1 Close S1 Circuit Close S2
S2
(Relay 6) Breaker (Relay 7)
Pair
Figure 3-9: Load shed relay wiring - standard transition switch

Figure 3-10 shows how to wire a load shed relay for applications, which use a delayed or closed transition switch
(S1 is the preferred source and S2 is the non-preferred source with this application).

Load Shed Relay


(LM Flag 20.11)

Open S2 Open S1
(Relay 9) (Relay 8)
Transfer
Switch
S1 Circuit S2
Breaker
Close S1 Pair Close S2
(Relay 6) (Relay 7)
Figure 3-10: Load shed relay wiring - delayed or closed transition switch

NOTE
The load shed relay must always be operated at the non-preferred source side with the power of the
non-preferred source.
If a load shed relay is used, preferred and non-preferred source must not be changed since this would
lead to a malfunction of the load shed function.

© Woodward Page 41/141


Manual 37386D DTSC-200 - ATS Controller

Breaker
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Breaker: Transfer Switch Type

Transfer switch type Transfer switch type Standard / Delayed / Closed


EN

Transfer Schalter Typ


DE

CL2 {0} {1} {2} This parameter configures the type of ATS switch, which is connected to the
3424    controller. The switch logic behavior depends on the setting configured here.
Standard ......An "open transition" switch is selected.
Delayed ........A "delayed transition" switch is selected.
Closed...........A "closed transition" switch is selected.

Standard Transfer Switch


If an open transition switch is used, "Standard" transfer switch type must be selected.
This switch type may only take on two states:

• Position 1: Connected to source 1


Transfer Switch
Source 1 Source 2

Load
Figure 3-11: Open transition switch - connected to source 1

• Position 2: Connected to source 2


Transfer Switch
Source 1 Source 2

Load
Figure 3-12: Open transition switch - connected to source 2

The following switch commands are enabled in this mode:


• LogicsManager flag (20.07) : Command: Close to Source 1
• LogicsManager flag (20.09) : Command: Close to Source 2
These signals may be configured to relay outputs to operate the ATS switch mechanics.

The following feedback signals are evaluated in this mode:


• Discrete input 1 (ATS breaker in Source 1 position) = signal designation: S1
• Discrete input 2 (ATS breaker in Source 2 position) = signal designation: S2
These feedback signals are evaluated by the ATS controller for monitoring the actual switch position.

The following additional features are recommended for this mode:


• In-phase monitor (refer to the In-Phase Monitor section)
• Motor load disconnect

Page 42/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Delayed Transfer Switch


If an delayed transition switch is used, "Delayed" transfer switch type must be selected.
This switch type may take on three states:

• Position 1: Connected to source 1


Transfer Switch
Source 1 Source 2

Load
Figure 3-13: Delayed transition switch - connected to source 1

• Position 2: Neutral
Transfer Switch
Source 1 Source 2

Load
Figure 3-14: Delayed transition switch - neutral position

• Position 3: Connected to source 2


Transfer Switch
Source 1 Source 2

Load
Figure 3-15: Delayed transition switch - connected to source 2

The following switch commands are enabled in this mode:


• LogicsManager flag (20.07) : Command: Close to Source 1
• LogicsManager flag (20.08) : Command: Open Source 1
• LogicsManager flag (20.09) : Command: Close to Source 2
• LogicsManager flag (20.10) : Command: Open Source 2
These signals may be configured to relay outputs to operate the ATS switch mechanics.

The following feedback signals are evaluated in this mode:


• Discrete input 1 (ATS breaker in Source 1 position) = signal designation: S1
• Discrete input 2 (ATS breaker in Source 2 position) = signal designation: S2
• Discrete input 3 (ATS breaker in Source 1 OPEN position) = signal designation: S1O
• Discrete input 4 (ATS breaker in Source 2 OPEN position) = signal designation: S2O
These feedback signals are evaluated by the ATS controller for monitoring the actual switch position.

The following additional features are recommended for this mode:


• In-phase monitor (refer to the In-Phase Monitor section)
• Motor load disconnect

© Woodward Page 43/141


Manual 37386D DTSC-200 - ATS Controller

Closed Transfer Switch


If an closed transition switch is used, "Closed" transfer switch type must be selected.
This switch type may take on four states:

• Position 1: Connected to source 1


Transfer Switch
Source 1 Source 2

Load
Figure 3-16: Closed transition switch - connected to source 1

• Position 2: Neutral
Transfer Switch
Source 1 Source 2

Load
Figure 3-17: Closed transition switch - neutral position

• Position 3: Synchronized
Transfer Switch
Source 1 Source 2

Load
Figure 3-18: Closed transition switch - connected to source 1 and 2 (overlap position)

• Position 4: Connected to source 2


Transfer Switch
Source 1 Source 2

Load
Figure 3-19: Closed transition switch - connected to source 2

The following switch commands are enabled in this mode:


• LogicsManager flag (20.07) : Command: Close to Source 1
• LogicsManager flag (20.08) : Command: Open Source 1
• LogicsManager flag (20.09) : Command: Close to Source 2
• LogicsManager flag (20.10) : Command: Open Source 2
These signals may be configured to relay outputs to operate the ATS switch mechanics.

The following feedback signals are evaluated in this mode:


• Discrete input 1 (ATS breaker in Source 1 position) = signal designation: S1
• Discrete input 2 (ATS breaker in Source 2 position) = signal designation: S2
• Discrete input 3 (ATS breaker in Source 1 OPEN position) = signal designation: S1O
• Discrete input 4 (ATS breaker in Source 2 OPEN position) = signal designation: S2O
These feedback signals are evaluated by the ATS controller for monitoring the actual switch position.

The following additional features are recommended for this mode:


• In-phase monitor (refer to the In-Phase Monitor section)
• Motor load disconnect

Page 44/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Use Limit Switch Open Replies

This function is used to define the limit switch reply signals, which are evaluated for determining the current
ATS switch position.

The following four signals are available for determining the ATS switch position:
• Discrete input 1 (ATS breaker in Source 1 position) = signal designation: S1
• Discrete input 2 (ATS breaker in Source 2 position) = signal designation: S2
• Discrete input 3 (ATS breaker in Source 1 OPEN position) = signal designation: S1O
• Discrete input 4 (ATS breaker in Source 2 OPEN position) = signal designation: S2O

NOTE
All reply signals, which are selected for determining the current ATS switch position must be
connected to the discrete inputs of the DTSC to ensure a correct evaluation of the switch replies.
These discrete inputs have an N.C. logic, i.e. the breaker is considered as "in position" if the respective
DI is de-energized.

Use Limit sw. OPEN replies Use limit switch open replies YES / NO
EN

Schalter RM OFFEN verwenden


DE

CL2 {0} {1} {2} This parameter may only be enabled (setting "YES") if parameter 3424 on
3434    page 42 is configured to "Delayed" or "Closed". If it is configured to
"Standard", this parameter is always disabled (setting "NO").

This parameter defines whether the limit switch open signals are also used to
determine the ATS switch position.
YES .............. The signals S1, S2, S1O, and S2O are used to determine the ATS
switch position.
This setting provides a higher system safety because the "Switch
Open" replies are also evaluated besides the "Switch Closed"
replies.
NO ............... Only the signals S1 and S2 are used to determine the ATS switch
position.
This setting does not use the DIs 3 and 4 for determining the ATS
switch position and makes them available for other functions.

Delayed Mode Active

This function is only effective if parameter 3424 (Transfer switch type) is configured to "Closed". If the
LogicsManager function "Delayed mode act." becomes TRUE, the transfer switch type will be set to "Delayed"
temporarily.

Delayed mode act. Enable delayed mode LogicsManager


EN

Verzög. modus akt.


DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in
12850    Appendix A: "LogicsManager".

© Woodward Page 45/141


Manual 37386D DTSC-200 - ATS Controller

Transition Timers
The "Neutral Time S2 -> S1" parameter is only enabled, if "Delayed" or "Closed" is configured as "Transfer
switch type" (parameter 3424) and inphase monitoring is disabled (parameter 4570).

Neutral Time S2->S1 Neutral Time S2 -> S1 0 to 6500 s


EN

Neutral Verweilzeit S2->S1


DE

CL2 {0} {1} {2} This parameter configures the residence time in neutral position when transferring
3426    the load in this transfer direction.
After this timer has expired, the transfer to source 1 will be performed.

If this timer is running, the "Neutral S1 -> S2" message is displayed.

The "Neutral Time S2 <- S1" parameter is only enabled, if "Delayed" or "Closed" is configured as "Transfer
switch type" (parameter 3424) and inphase monitoring is disabled (parameter 4570).

Neutral Time S1->S2 Neutral Time S1 -> S2 0 to 6500 s


EN

Neutral Verweilzeit S1->S2


DE

CL2 {0} {1} {2} This parameter configures the residence time in neutral position when transferring
3425    the load in this transfer direction.
After this timer has expired, the transfer to source 2 will be performed.

If this timer is running, the "Neutral S1 <- S2" message is displayed.

Limit switch reply timeout Limit switch reply timeout 0.1 to 99.9 s
EN

Zeitüberschreitung Rückmeld.
DE

CL2 {0} {1} {2} This parameter configures the maximum waiting time for a feedback signal from
  
3428
the ATS switch. If no reply is detected within the configured time, a new transition
attempt will be performed after the "Wait time until next XFR attempt"
(parameter 3429) has expired (refer to Figure 3-20 on page 47). If the "Max. of
transfer attempts" (parameter 3427) is exceeded, a switch failure will be issued.

If this timer is running, the Bypass softkey is not displayed. The display message
while the timer is running indicates that a reply is expected and depends on the
command issued:
• If source 1 is to be opened : "Wait S1 open"
• If source 2 is to be opened : "Wait S2 open"
• If source 1 is to be closed : "Wait S1 close"
• If source 2 is to be closed : "Wait S2 close"

Note: The operator coils may be damaged. if this timer is configured too long (i.e.
the maximum time, for which the transition pulse may be enabled must not be
exceeded).

NOTE
The limit switch reply timeout monitoring is only enabled if a transfer command (C2, C1, C2O, or C1O)
has been issued from the ATS controller.

Page 46/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Wait time until next XFR Waiting time until next transition attempt 0.1 to 99.9 s

EN
attempt
Wartezeit vor neuem Transfer This parameter configures the interval following an unsuccessful transition

DE
CL2 {0} {1} {2}
attempt before a new transition attempt is being performed.
3429   
This time allows the relay coil to cool down between the open/close signals.

Limit switch reply timeout Wait time until next XFR attempt
open/close
pulse

Figure 3-20: Breaker - transition pulse

Max. of Transfer attempts Maxímum number of unsuccessful transition attempts 1 to 10


EN

Max. Anzahl Fehlzuschaltungen


DE

CL2 {0} {1} {2} This parameter configures the maximum number of unsuccessful transition
3427    attempts before a switch failure will be issued. The counter for the number of
unsuccessful transition attempts will be increased with the start of each waiting
time period (parameter 3429)

© Woodward Page 47/141


Manual 37386D DTSC-200 - ATS Controller

Triggering of the "Fail to close S1" failure


This failure is triggered if the following conditions are met:
• Source 1 is available
• The ATS controller has issued the C1 signal (LogicsManager flag (20.07)) to close to source 1

As soon as the C1 signal (command: close to source 1) is issued, the "Limit switch reply timeout" timer
(parameter 3428) starts to count and the period for monitoring whether the S1 reply (closed to source 1) is fed
back from the ATS switch to the controller starts. The C1 signal is enabled until the "Limit switch reply timeout"
timer has expired. Thus, this defines maximum permissible pulse duration for the transfer command. If the "Limit
switch reply timeout" timer has expired, the C1 signal will be disabled. If the "Wait time until next XFR attempt"
timer (parameter 3429) has expired, the C1 signal will be enabled again and the "Limit switch reply timeout"
timer is re-started. If the timer expires again without detecting the S1 reply, the "Fail to close S1" failure is
issued. The message "Fail to close S1" will be displayed and entered into the event logger.

If the reply from the ATS controller is detected while the "Limit switch reply timeout" timer is still counting, the
C1 signal will be disabled immediately since the transfer was successful. The message is not be displayed
anymore and the reply monitoring is terminated.

NOTE
Closing the ATS switch will be attempted until the maximum number of unsuccessful transition
attempts (parameter 3427) is reached. The failure will be issued after the last failed transfer attempt.

Triggering of the "Fail to close S2" failure


This failure is triggered if the following conditions are met:
• Source 2 is available
• The ATS controller has issued the C2 signal (LogicsManager flag (20.09)) to close to source 2

As soon as the C2 signal (command: close to source 2) is issued, the "Limit switch reply timeout" timer
(parameter 3428) starts to count and the period for monitoring whether the S2 reply (closed to source 2) is fed
back from the ATS switch to the controller starts. The C2 signal is enabled until the "Limit switch reply timeout"
timer has expired. Thus, this defines maximum permissible pulse duration for the transfer command. If the "Limit
switch reply timeout" timer has expired, the C2 signal will be disabled. If the "Wait time until next XFR attempt"
timer (parameter 3429) has expired, the C2 signal will be enabled again and the "Limit switch reply timeout"
timer is re-started. If the timer expires again without detecting the S2 reply, the "Fail to close S2" failure is
issued. The message "Fail to close S2" will be displayed and entered into the event logger.

If the reply from the ATS controller is detected while the "Limit switch reply timeout" timer is still counting, the
C2 signal will be disabled immediately since the transfer was successful. The message is not be displayed
anymore and the reply monitoring is terminated.

NOTE
Closing the ATS switch will be attempted until the maximum number of unsuccessful transition
attempts (parameter 3427) is reached. The failure will be issued after the last failed transfer attempt.

NOTE
If a closure failure occurs, the system always tries to close the second breaker to a good source.

Page 48/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Triggering of the "Fail to open S1" failure


This failure is triggered if the following conditions are met:
• Source 2 is available
• The ATS controller has issued the C1O signal (LogicsManager flag (20.08)) to open source 1

As soon as the C1O signal (command: open source 1) is issued, the "Limit switch reply timeout" timer
(parameter 3428) starts to count and the period for monitoring whether the S1O reply (source 1 is open) is fed
back from the ATS switch to the controller starts. The C1O signal is enabled until the "Limit switch reply
timeout" timer has expired. Thus, this defines maximum permissible pulse duration for the transfer command. If
the "Limit switch reply timeout" timer has expired, the C1O signal will be disabled. If the "Wait time until next
XFR attempt" timer (parameter 3429) has expired, the C1O signal will be enabled again and the "Limit switch
reply timeout" timer is re-started. If the timer expires again without detecting the S1O reply, the "Fail to open S1"
failure is issued. The message "Fail to open S1" will be displayed and entered into the event logger.

If the reply from the ATS controller is detected while the "Limit switch reply timeout" timer is still counting, the
C1O signal will be disabled immediately since the transfer was successful. The message is not be displayed
anymore and the reply monitoring is terminated.

NOTE
Opening the ATS switch will be attempted until the maximum number of unsuccessful transition
attempts (parameter 3427) is reached. The failure will be issued after the last failed transfer attempt.

Triggering of the "Fail to open S2" failure


This failure is triggered if the following conditions are met:
• Source 1 is available
• The ATS controller has issued the C2O signal (LogicsManager flag (20.10)) to open source 2

As soon as the C2O signal (command: open source 2) is issued, the "Limit switch reply timeout" timer
(parameter 3428) starts to count and the period for monitoring whether the S2O reply (source 2 is open) is fed
back from the ATS switch to the controller starts. The C2O signal is enabled until the "Limit switch reply
timeout" timer has expired. Thus, this defines maximum permissible pulse duration for the transfer command. If
the "Limit switch reply timeout" timer has expired, the C2O signal will be disabled. If the "Wait time until next
XFR attempt" timer (parameter 3429) has expired, the C2O signal will be enabled again and the "Limit switch
reply timeout" timer is re-started. If the timer expires again without detecting the S2O reply, the "Fail to open S2"
failure is issued. The message "Fail to open S2" will be displayed and entered into the event logger.

If the reply from the ATS controller is detected while the "Limit switch reply timeout" timer is still counting, the
C2O signal will be disabled immediately since the transfer was successful. The message is not be displayed
anymore and the reply monitoring is terminated.

NOTE
Opening the ATS switch will be attempted until the maximum number of unsuccessful transition
attempts (parameter 3427) is reached. The failure will be issued after the last failed transfer attempt.

© Woodward Page 49/141


Manual 37386D DTSC-200 - ATS Controller

Test Modes
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
There are two different types of system tests:

• Load Test
This is a test with load transfer. If a load test is requested, a failure of the preferred source will be simulated.
The non-preferred source will be started and load will be transferred to the non-preferred source.
This test serves to ensure that the complete system is ready for operation in case of a real failure of the
preferred source.

• No Load Test
This is an engine test. If a no load test is requested, only the non-preferred source will be started, but no load
transfer will be performed.
This test serves to ensure that the non-preferred source is starting and running properly.

NOTE
A "No Load Test" may only be performed if the non-preferred source is a generator.

If the LogicsManager function "Load Test" becomes TRUE (by energizing a DI for example), a load test will be
performed.

Load Test Load Test LogicsManager


EN

Lastprobe
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12640    A: "LogicsManager".

If the LogicsManager function "No Load Test" becomes TRUE (by energizing a DI for example), a no load test
will be performed.

No Load Test No Load Test LogicsManager


EN

Motor Test
DE

CL2 {0} {1} {2} The LogicsManager and its default settings are explained on page 101 in Appendix
12650 ---   A: "LogicsManager".

Page 50/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Monitoring: Alarm Acknowledgement

Time until horn reset Self acknowledgment of the centralized alarm (horn) 0 to 1,000 s
EN

Zeit Hupenreset
DE

CL2 {0} {1} {2} After each alarm occurs, the alarm LED flashes and the command variable 03.05
1756    (horn) is issued. After the delay time 'time until horn reset' has expired, the flashing
LED changes into a steady light and the command variable 03.05 (horn) is reset.
The alarm LED is illuminated continuously until the alarm has been acknowledged.

Note: If this parameter is configured to 0, the horn will remain active until it will be
acknowledged.

External acknowledge Protection: External acknowledgment of alarms LogicsManager


EN

Ext. Quittierung
DE

CL2 {0} {1} {2} It is possible to acknowledge all alarms simultaneously from remote, e.g. with a
12490    discrete input. The command variables of the LogicsManager have to become
TRUE twice.

 The first high signal into the discrete input acknowledges the command
variable 03.05 (horn). The second high signal acknowledges all inactive
alarm messages.

The ON-delay time is the minimum time the input signals have to be "1". The OFF-
delay time is the time how long the input conditions have to be "0" before the next
high signal is accepted.

The LogicsManager and its default settings are explained on page 101 in Appendix
A: "LogicsManager".

Monitoring: Limit Switch Monitoring

Limit switch monitoring Limit switch monitoring ON / OFF


EN

Rückmeldungswächter
DE

CL2 {0} {1} {2} Limit switch monitoring evaluates the ATS limit switch replies and checks them for
3430    plausibility with reference to the operating state. If the replies are not plausible, the
"Actual" and "Expected" replies are displayed.
Meanwhile, the status of the breaker replies cannot be reset with the Reset button
and all further transfers are inhibited.

A table with the actual and expected replies may be found in the Operation Manual
37387.
ON................ The replies of the ATS limit switch are evaluated and compared with
the expected replies.
OFF.............. The replies of the ATS limit switch are not evaluated.

Note: Do not enable this monitoring function before the system is commissioned
and fully operational. Otherwise, missing reply signals would lead to a limit switch
failure, which blocks the control unit. This can only be solved by wiring the reply
signals correctly or disabling this function using LeoPC1.

© Woodward Page 51/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 1 Monitoring

Voltage monitoring S1 Voltage monitoring source 1 Ph - Ph / Phase - N


EN

Spg.-Überwachung S1
DE

CL2 {0} {1} {2} The unit can either monitor the wye voltages (phase-neutral: 3ph-4w, 1ph-3w and
1787    1ph-2w) or the delta voltages (phase-phase: 3ph-3w and 3ph-4w).

! WARNING:
This parameter influences the protective functions.

Ph - Ph .........The phase-phase voltage will be measured and all subsequent


parameters concerning voltage monitoring "source 1" are referred to
this value (VL-L).
Phase - N ......The phase-neutral voltage will be measured and all subsequent
parameters concerning voltage monitoring "source 1" are referred to
this value (VL-N).

Monitoring: Source 1 Monitoring: Undervoltage


Voltage is monitored depending on parameter 1787 "Voltage monitoring S1".

S1 undervoltage restore Source 1 undervoltage restore 50.0 to 125.0 %


EN

S1 Unterspannung rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 1 (parameter 1774 on
  
4450
page 18).

This parameter configures the threshold, which must be exceeded to consider


source 1 as "OK" again.

S1 undervoltage fail Source 1 undervoltage fail 50.0 to 125.0 %


EN

S1 Unterspannung auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 1 (parameter 1774 on
4451    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 1 as "not OK".

Page 52/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 1 Monitoring: Underfrequency


Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value.
This permits a very rapid and accurate frequency measurement. The frequency however will be measured
properly even if voltage is applied to one phase only.

S1 underfrequency monitoring Source 1 underfrequency monitoring ON / OFF


EN

S1 Unterfrequenz Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether underfrequency monitoring for source 1 is
4452    performed.
OFF ..............No underfrequency monitoring is performed for source 1.
ON ................Underfrequency monitoring is performed for source 1.

S1 underfrequency restore Source 1 underfrequency restore 50.0 to 130.0 %


EN

S1 Unterfrequenz rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4453    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 1 as "OK" again..

S1 underfrequency fail Source 1 underfrequency fail 50.0 to 130.0 %


EN

S1 Unterfrequenz auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4454    page 18)

This parameter configures the threshold, which must be fallen below to consider
source 1 as "not OK".

Monitoring: Source 1 Monitoring: Overvoltage


Voltage is monitored depending on parameter 1787 "Voltage monitoring S1".

S1 overvoltage monitoring Source 1 overvoltage monitoring ON / OFF


EN

S1 Überspannung Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether overvoltage monitoring for source 1 is
4455    performed.
OFF ..............No overvoltage monitoring is performed for source 1.
ON ................Overvoltage monitoring is performed for source 1.

S1 overvoltage restore Source 1 overvoltage restore 50.0 to 125.0 %


EN

S1 Überspannung rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 1 (parameter 1774 on
4456    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 1 as "OK" again..

S1 overvoltage fail Source 1 overvoltage fail 50.0 to 125.0 %


EN

S1 Überspannung auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 1 (parameter 1774 on
4457    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 1 as "not OK".

© Woodward Page 53/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 1 Monitoring: Overfrequency


Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value.
This permits a very rapid and accurate frequency measurement. The frequency however will be measured
properly even if voltage is applied to one phase only.

S1 overfrequency monitoring Source 1 overfrequency monitoring ON / OFF


EN

S1 Überfrequenz Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether overfrequency monitoring for source 1 is
4458    performed.
OFF ..............No overfrequency monitoring is performed for source 1.
ON ................Overfrequency monitoring is performed for source 1.

S1 overfrequency restore Source 1 overfrequency restore 50.0 to 130.0 %


EN

S1 Überfrequenz rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4459    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 1 as "OK" again..

S1 overfrequency fail Source 1 overfrequency fail 50.0 to 130.0 %


EN

S1 Überfrequenz auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4460    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 1 as "not OK".

Page 54/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 1 Monitoring: Voltage Imbalance


The voltage imbalance monitoring is practically used to detect defective fuses in certain phases. The voltage
imbalance monitoring measures voltage differences between the phases of source 1. The voltage is measured
three-phase. If the phase-to-phase voltage difference between the three phases exceeds the configured imbalance
limit the alarm will be issued.

S1 voltage imbalance monitoring Source 1 voltage imbalance monitoring ON / OFF


EN

S1 Asymmetrie Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether voltage imbalance monitoring for source 1 is
4461    performed.
OFF ..............No voltage imbalance monitoring is performed for source 1.
ON ................Voltage imbalance monitoring is performed for source 1.

S1 volt. Imbalance restore Source 1 voltage imbalance restore 0.5 to 99.9 %


EN

S1 Asymmetrie rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 1 (parameter 1774 on
4462    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 1 as "OK" again..

S1 volt. Imbalance fail Source 1 voltage imbalance fail 0.5 to 99.9 %


EN

S1 Asymmetrie auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 1 (parameter 1774 on
4463    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 1 as "not OK".

Delay Source 1 voltage imbalance delay 0.02 to 99.99 s


EN

Verzögerung
DE

CL2 {0} {1} {2} If the monitored voltage imbalance of source 1 exceeds the threshold value for the
3914    delay time configured here, an alarm will be issued.

© Woodward Page 55/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 1 Monitoring: Phase Rotation

CAUTION
Please ensure during installation that all voltages applied to this unit are wired correctly to both sides
of the circuit breaker. Failure to do so may result in damage to the control unit and/or generation
equipment due to closing the breaker asynchronous or with mismatched phase rotations and phase
rotation monitoring enabled at all connected components (engine, generator, breakers, cable, busbars,
etc.).
This function may block a connection of systems with mismatched phases systems only under the
following conditions:
• The voltages being measured are wired correctly with respect to the phase rotation at the
measuring points (i.e. the voltage transformer in front and behind the circuit breaker)
• The measuring voltages are wired without angular phase shift or interruption from the measuring
point to the control unit
• The measuring voltages are wired to the correct terminals of the control unit (i.e. L1 of the
generator is connected with the terminal of the control unit which is intended for the L1 of the
generator)

Correct phase rotation of the phase voltages ensures that damage will not occur during a transfer to either source
1 or source 2. The voltage phase rotation monitoring checks the phase rotation of the voltages and the configured
phase rotation to ensure they are identical. The directions of rotation are differentiated as "clockwise" and
"counter-clockwise". With a clockwise field the direction of rotation is "L1-L2-L3"; with a counter clockwise
field the direction of rotation is "L1-L3-L2". If the control is configured for a clockwise rotation and the voltages
into the unit are calculated as counterclockwise the alarm will be initiated.
A connection to certain source is only possible if this source has the correct phase sequence. If a source has a
wrong phase sequence, a connection to this source is not possible.

S1 phase rotation monitoring Source 1 phase rotation monitoring ON / OFF


EN

S1 Drehfeldüberwachung
DE

CL2 {0} {1} {2} This parameter configures, whether phase rotation monitoring for source 1 is
4562    performed.

OFF ..............No phase rotation monitoring is performed for source 1.


ON ................Phase rotation monitoring is performed for source 1.

S1 phase rotation Source 1 phase rotation CW / CCW


EN

S1 Drehfeld
DE

CL2 {0} {1} {2} This parameter configures the phase rotation of the system. If a different phase
4563    rotation is detected at source 1, source 1 is considered as "not OK" and a transfer to
source 2 is initiated.

CW ...............The three-phase measured Source 1 voltage is rotating CW


(clockwise; that means the voltage rotates in direction L1-L2-L3;
standard setting).
CCW ............The three-phase measured Source 1 voltage is rotating CCW
(counter-clockwise; that means the voltage rotates in direction L1-
L3-L2; standard setting).

Page 56/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 2 Monitoring

Voltage monitoring S2 Voltage monitoring source 2 Ph - Ph / Phase - N

EN
Spg.-Überwachung S2
DE
CL2 {0} {1} {2} The unit can either monitor the wye voltages (phase-neutral: 3ph-4w, 1ph-3w and
1786    1ph-2w) or the delta voltages (phase-phase: 3ph-3w and 3ph-4w).

! WARNING:
This parameter influences the protective functions.

Ph - Ph ......... The phase-phase voltage will be measured and all subsequent


parameters concerning voltage monitoring "source 2" are referred to
this value (VL-L).
Phase - N ..... The phase-neutral voltage will be measured and all subsequent
parameters concerning voltage monitoring "source 2" are referred to
this value (VL-N).

Monitoring: Source 2 Monitoring: Undervoltage


Voltage is monitored depending on parameter 1786 "Voltage monitoring S2".

S2 undervoltage restore Source 2 undervoltage restore 50.0 to 125.0 %


EN

S2 Unterspannung rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 2 (parameter 1772 on
  
4465
page 18).

This parameter configures the threshold, which must be exceeded to consider


source 2 as "OK" again.

S2 undervoltage fail Source 2 undervoltage fail 50.0 to 125.0 %


EN

S2 Unterspannung auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 2 (parameter 1772 on
4466    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 2 as "not OK".

© Woodward Page 57/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 2 Monitoring: Underfrequency


Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value.
This permits a very rapid and accurate frequency measurement. The frequency however will be measured
properly even if voltage is applied to one phase only.

S2 underfrequency monitoring Source 2 underfrequency monitoring ON / OFF


EN

S2 Unterfrequenz Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether underfrequency monitoring for source 2 is
4467    performed.
OFF ............. No underfrequency monitoring is performed for source 2.
ON ............... Underfrequency monitoring is performed for source 2.

S2 underfrequency restore Source 2 underfrequency restore 50.0 to 130.0 %


EN

S2 Unterfrequenz rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4468    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 2 as "OK" again.

S2 underfrequency fail Source 2 underfrequency fail 50.0 to 130.0 %


EN

S2 Unterfrequenz auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4469    page 18)

This parameter configures the threshold, which must be fallen below to consider
source 2 as "not OK".

Monitoring: Source 2 Monitoring: Overvoltage


Voltage is monitored depending on parameter 1786 "Voltage monitoring S2".

S2 overvoltage monitoring Source 2 overvoltage monitoring ON / OFF


EN

S2 Überspannung Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether overvoltage monitoring for source 2 is
4470    performed.
OFF ............. No overvoltage monitoring is performed for source 2.
ON ............... Overvoltage monitoring is performed for source 2.

S2 overvoltage restore Source 2 overvoltage restore 50.0 to 125.0 %


EN

S2 Überspannung rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 2 (parameter 1772 on
4471    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 2 as "OK" again.

S2 overvoltage fail Source 2 overvoltage fail 50.0 to 125.0 %


EN

S2 Überspannung auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 2 (parameter 1772 on
4472    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 2 as "not OK".

Page 58/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 2 Monitoring: Overfrequency


Three-phase measurement of the frequency is performed, if all voltages are higher than 15 % of the rated value.
This permits a very rapid and accurate frequency measurement. The frequency however will be measured
properly even if voltage is applied to one phase only.

S2 overfrequency monitoring Source 2 overfrequency monitoring ON / OFF


EN

S2 Überfrequenz Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether overfrequency monitoring for source 2 is
4473    performed.
OFF.............. No overfrequency monitoring is performed for source 2.
ON................ Overfrequency monitoring is performed for source 2.

S2 overfrequency restore Source 2 overfrequency restore 50.0 to 130.0 %


EN

S2 Überfrequenz rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4474    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 2 as "OK" again..

S2 overfrequency fail Source 2 overfrequency fail 50.0 to 130.0 %


EN

S2 Überfrequenz auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated system frequency (parameter 1750 on
4475    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 2 as "not OK".

© Woodward Page 59/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 2 Monitoring: Voltage Imbalance


The voltage imbalance monitoring is practically used to detect defective fuses in certain phases. The voltage
imbalance monitoring measures voltage differences between the phases of source 2. The voltage is measured
three-phase. If the phase-to-phase voltage difference between the three phases exceeds the configured imbalance
limit the alarm will be issued.

S2 voltage imbalance monitoring Source 2 voltage imbalance monitoring ON / OFF


EN

S2 Asymmetrie Wächter
DE

CL2 {0} {1} {2} This parameter configures, whether voltage imbalance monitoring for source 1 is
4476    performed.
OFF.............. No voltage imbalance monitoring is performed for source 1.
ON................ Voltage imbalance monitoring is performed for source 1.

S2 volt. Imbalance restore Source 2 voltage imbalance restore 0.5 to 99.9 %


EN

S2 Asymmetrie rücksetzen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 2 (parameter 1772 on
4477    page 18).

This parameter configures the threshold, which must be fallen below to consider
source 2 as "OK" again..

S2 volt. Imbalance fail Source 2 voltage imbalance fail 0.5 to 99.9 %


EN

S2 Asymmetrie auslösen
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 2 (parameter 1772 on
4478    page 18).

This parameter configures the threshold, which must be exceeded to consider


source 2 as "not OK".

Delay Source 2 voltage imbalance delay 0.02 to 99.99 s


EN

Verzögerung
DE

CL2 {0} {1} {2} If the monitored voltage imbalance of source 2 exceeds the threshold value for the
3904    delay time configured here, an alarm will be issued.

Page 60/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Source 2 Monitoring: Phase Rotation

CAUTION
Please ensure during installation that all voltages applied to this unit are wired correctly to both sides
of the circuit breaker. Failure to do so may result in damage to the control unit and/or generation
equipment due to closing the breaker asynchronous or with mismatched phase rotations and phase
rotation monitoring enabled at all connected components (engine, generator, breakers, cable, busbars,
etc.).
This function may block a connection of systems with mismatched phases systems only under the
following conditions:
• The voltages being measured are wired correctly with respect to the phase rotation at the
measuring points (i.e. the voltage transformer in front and behind the circuit breaker)
• The measuring voltages are wired without angular phase shift or interruption from the measuring
point to the control unit
• The measuring voltages are wired to the correct terminals of the control unit (i.e. L1 of the
generator is connected with the terminal of the control unit which is intended for the L1 of the
generator)

Correct phase rotation of the phase voltages ensures that damage will not occur during a transfer to either source
1 or source 2. The voltage phase rotation monitoring checks the phase rotation of the voltages and the configured
phase rotation to ensure they are identical. The directions of rotation are differentiated as "clockwise" and
"counter-clockwise". With a clockwise field the direction of rotation is "L1-L2-L3"; with a counter clockwise
field the direction of rotation is "L1-L3-L2". If the control is configured for a clockwise rotation and the voltages
into the unit are calculated as counterclockwise the alarm will be initiated.
A connection to certain source is only possible if this source has the correct phase sequence. If a source has a
wrong phase sequence, a connection to this source is not possible.

S2 phase rotation monitoring Source 2 phase rotation monitoring ON / OFF


EN

S2 Drehfeldüberwachung
DE

CL2 {0} {1} {2} This parameter configures, whether phase rotation monitoring for source 2 is
4566    performed.

OFF.............. No phase rotation monitoring is performed for source 2.


ON................ Phase rotation monitoring is performed for source 2.

S2 phase rotation Source 2 phase rotation CW / CCW


EN

S2 Drehfeld
DE

CL2 {0} {1} {2} This parameter configures the phase rotation of the system. If a different phase
4567    rotation is detected at source 2, source 2 is considered as "not OK" and a transfer to
source 1 is initiated.

CW ............... The three-phase measured Source 2 voltage is rotating CW


(clockwise; that means the voltage rotates in direction L1-L2-L3;
standard setting).
CCW ............ The three-phase measured Source 2 voltage is rotating CCW
(counter-clockwise; that means the voltage rotates in direction L1-
L3-L2; standard setting).

© Woodward Page 61/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: In-Phase Monitoring (Synch Check)

The in-phase monitoring function is used to determine whether the phase angles of the preferred source and the
non-preferred source are in phase, i.e. whether the relative phase difference of the two sources is within specified
limits.
Whenever one power source fails, the control follows the programmed transition operation sequence. If in-phase
monitoring is enabled and both sources are available as determined by the "restore value" levels, the control shall
follow the in-phase monitoring operation sequence.

In-phase Monitoring may be used to improve the transfer with open transition switches. An open (standard)
transition transfer switch is the most simple and commonly used ATS. It may only take on two positions,
connected with source 1, or connected with source 2. If it transfers a load, this will be performed according to the
break-before-make process, i.e. the load will be disconnected from the previous source before it will be
connected with the next source. This results a dead time of approximately 160 ms (depending on the ATS) during
which the load is not connected to a source. Most of the load consumers are not effected by this dead time in the
transfer phase (lamps may only flicker, etc.), but some appliances may be effected seriously, like computers and
motor loads, etc. This may lead to damages of the equipment or data loss in the worst case. The problem is that
the consumers behave like generators during this dead time and supply power. While some consumers are
running out when changing to the other source, very high current may flow between generator and load because
the phase angles between the two systems are not synchronous.

This high equalizing current may be minimized with two means:

• Using a transfer switch with neutral position


If a delayed transition switch is used, the residence time in neutral position may be timed as long until the
voltages at the load are settled so far that a transfer to the other source is possible.
• Using inphase monitoring
Inphase monitoring checks the phase angle between source 1 and source 2 prior to a transfer and enables the
transfer signal only if the phase angle has fallen below a configured threshold. Moreover, the unit calculates
the leading angle for the closing commands by entering the "Switch reaction time" to enable a transfer with
almost 0° phase shift. This ensures a nearly synchronous transfer to the other source and reduces the
equalizing current to a minimum. Compared with the neutral position of a delayed transition switch, the
advantage is that the load must not be shut down completely prior to a transfer.

Inphase monitoring may be used with open, delayed, and closed transition switches. As mentioned above, high
equalizing current after a transfer may be minimized when utilizing inphase monitoring. However, the behavior
of the ATS in case of a failed inphase transition must be considered. This may happen if the generator is
equipped with a poorly adjusted frequency controller. Then, it may happen that it is not possible to achieve
synchronicity. But the load must be transferred to the other source in any case.

NOTE
Refer to parameter 4582 "Outcome on in-phase timeout" for the ATS behavior in case of a failed
inphase transition.

Acceptable Unacceptable Acceptable


switch transfer switch transfer switch transfer
Source 2 power Source 2 power Source 2 power
Source 1 power

Phase window Time delay in neutral


Source 1 power

Figure 3-21: Inphase monitoring

Page 62/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Inphase Monitoring: Parameters

In-Phase monitor Inphase monitoring ON / OFF

EN
Synchrocheck

DE
CL2 {0} {1} {2} This parameter configures, whether inphase monitoring is performed.
  
4570
OFF.............. No inphase monitoring is performed prior to a transfer.
ON................ Inphase monitoring is performed prior to a transfer. If the phase angle
between both systems is within the permissible limits, the transfer
will be performed.

NOTE
The following voltages are monitored by the inphase monitoring function depending on the
configuration of the measurement principle (parameter 1862 or 1861):
• 4Ph 3W : VL12
• 3Ph 3W : VL12
• 4Ph 3W : VL12 or VL1N depending on the configuration of parameter 1858
• 1Ph 3W : VL1N
If inphase monitoring enabled and the measurement principle for source 1 (parameter 1862) is
configured as "1Ph 2W", the measurement principle for source 2 (parameter 1861) must also be
configured as "1Ph 2W".

Voltage window Voltage window for synchronization 0.50 to 10.00 %


EN

Spannungsdifferenz
DE

CL2 {0} {1} {2}  This value refers to the Rated voltage Source 1/2 (parameters 1774/1772 on
4571    page 18).

This parameter configures the maximum permissible voltage difference in each of


the three phases. The voltage differences in all three phases (VL1 (Source 1) - VL1 (Source
2) / VL2 (Source 1) - VL2 (Source 2) / VL3 (Source 1) - VL3 (Source 2)) must be within the limit
configured here to be able to synchronize.
If the voltage difference in at least one phase exceeds this limit, the synchronization
will not be enabled.

Positive frequency window Positive frequency window for synchronization 0.02 to 0.49 Hz
EN

Maximaler 63escry63e
DE

Schlupf This parameter configures the maximum permissible positive frequency difference
CL2 {0} {1} {2}
between source 2 and source 1 (Δf = S2-S1).
4572   
If the frequency difference is not within the limits configured here, the
synchronization will not be enabled because the frequency difference of the source
to be connected to is too high.

Negative frequency window Negative frequency window for synchronization -0.02 to -0.49 Hz
EN

Maximaler 63escry63e
DE

Schlupf This parameter configures the minimum permissible negative frequency difference
CL2 {0} {1} {2}
between source 2 and source 1 (Δf = S2-S1).
4573   
If the frequency difference is not within the limits configured here, the
synchronization will not be enabled because the frequency difference of the source
to be connected to is too low.

© Woodward Page 63/141


Manual 37386D DTSC-200 - ATS Controller

Maximum Overlap Time

NOTE
This function is only effective if the transfer switch type (parameter 3424) is configured to "Closed" and
in-phase monitoring (parameter 4570) is enabled.

NOTE
If the LogicsManager function "Extended parallel time" (parameter 12860) is TRUE, the maximum
overlap time is not effective.
Exception: If the maximum overlap time is configured to 0.1 s, an extended parallel time is not possible
regardless of the state of this function.

If a closed transition is performed, the overlap time of the make-before-break process, in which both sources are
parallel, is less than 100 ms. If this time is to be extended, an overlap timer is available to keep the transition
switch in overlap position for a configured time. The timer starts as soon as the transition switch is in overlap
position. The source, from which the transfer has been initiated, will be disconnected and the load will be
supplied by the new source as soon as this timer has expired.

Max. overlap time Maximum overlap time 0.1 to 9.99 s


EN

Max. Synchronzeit
DE

CL2 {0} {1} {2} 0.10 ...............If the maximum overlap time is configured to 0.10 s, an overlap time
  
4577
below 100 ms, which depends on the used transfer switch, will be
effective and "Extended parallel time" (parameter 12860) is disabled.
0.11 - 9.99 .....The time for which the transfer switch shall remain in overlap
position is configured here.

NOTE
If one source fails before this timer expires, the failed source will automatically be disconnected.

The following example shows a typical transfer sequence from source 1 to source 2 with overlap timer:

Initial situation:
S1 S2 Load is supplied by source 1.

A transfer is initiated (e.g. by a load test):


S1 S2 As soon as source 2 is detected as stable and synchronicity is
achieved, the transfer switch is closed to source 2.
2

Overlap timer is active:


S1 S2 The transfer switch remains in overlap position as long as the
overlap timer has not expired and load is supplied by both
3 sources.

Maximum overlap time expires:


S1 S2 As soon as the configured maximum overlap time has expired,
the transfer switch opens from source 1.
4

Final situation:
S1 S2 Load is supplied by source 2.

Page 64/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Switch Reaction Time Configuration

Open trans. Switch reac. Time Open transition switch reaction time 15 to 300 ms

EN
Schaltzeit bei nicht Überlapp.

DE
CL2 {0} {1} {2} The time, which is required by the switch in open transition mode to open from
  
4578
one source and close to the other source, is configured here.
This time is required for calculating the lead angle for inphase transfers.

Closed trans. Switch reac. Time Closed transition switch reaction time 15 to 300 ms
EN

Schalterzeit bei Überlapp.


DE

CL2 {0} {1} {2} The time, which is required by the switch in closed transition mode to close to the
4583    other source to get parallel, is configured here.
This time is required for calculating the lead angle for inphase transfers.

t Transfer

Figure 3-22: Switch reaction time

Vector Group Angle Adjustment

WARNING
Ensure the following parameters are configured correctly to prevent wrong synchronization settings.
Incorrect wiring of the system cannot be compensated with this parameter!

Vector group angle adjustment Vector group angle adjustment -180° to 180°
EN

Schaltgruppe Winkel Anpassung


DE

CL2 {0} {1} {2} This parameter compensates for phase angle deviations, which can be caused by
  
4581
transformers (i.e. a delta to wye transformer) located within the electrical system.
Ensure the following parameters are configured correctly to prevent wrong
synchronization settings. Incorrect wiring of the system cannot be compensated
for with this parameter!

Please act as follows: If a transformer is not located between systems [A] and [B]
or if the transformer has a vector group without a phase angle deviation, then a
phase angle deviation of 0° should be configured in this parameter.

20 Interconnection of the mains voltage possible


With a phase angle deviation of 0° and the generator not running and source 1 energized, close both breakers.
This will result in system [A] and system [B] being at the same voltage potential. The phase angle deviation will
now be displayed on the DTSC-200 Counters screen (refer to the Navigation section of the Operation manual
37387). Enter the displayed value into this parameter.

CAUTION
The correct setting must be validated in every control unit with a differential voltage measurement!

© Woodward Page 65/141


Manual 37386D DTSC-200 - ATS Controller

2. Interconnection of the mains voltage not possible but the vector group of the transformer is known
The vector group of the transformer is known and states the phase angle deviation in multiplies of 30°. Out of the
vector group the phase angle deviation α can be calculated as an angle from 0° to 360°. For this value the
voltage of the low voltage side is behind the voltage of the high voltage side  phase angle deviation α!
When calculating the resulting value, the low voltage side of the transformer always lags behind the high
voltage side (phase angle deviation α).

The phase difference is to be calculated as follows:

High voltage side = System [A] High voltage side = System [B]
α < 180 ° α -α
α > 180 ° -360 ° + α 360 ° - α
Table 3-3: Calculation of the phase angle deviation

Source 1 Example 1
System [B] is connected to source 2. Source 2 voltage is connected to the low voltage
side of a transformer with the vector group Dyn5. The source 1 breaker is connected to
[A] the high voltage side, which connects the transformer to the mains. System [A] is
connected to source 1. Because of the transformer the phase angles at the breaker differ
on/off

DTSC-200
between the measuring voltages of system [A] and system [B]. A phase angle deviation
CB

[B]
High voltage side exists which can be compensated with the DTSC-200.

Dyn5 Using the vector group 5 (Dyn5) it counts α = 5 × 30 ° = 150 °. Because 150 ° < 180 °
∆:Y and system [A] is connected to the high voltage side this results into α to be used as
phase difference. Enter 150 ° into as parameter for the phase difference.
Low voltage side

Vector group angle


adjustment +150°
Source 2

Source 1 Example 2
Data identical with example 1, but the vector group is Yd11.

[A] Using the vector group 11 (Yd11) it counts α = 11 × 30 ° = 330 °. Because


330 ° > 180 ° and system [A] is connected to the high voltage side this results into (-
on/off

DTSC-200
360 ° + α) to be used as phase difference. Enter -30 ° into as parameter for the phase
CB

[B]
High voltage side difference.

Yd11 Vector group angle


Y:∆ adjustment -030°
Low voltage side

Source 2

CAUTION
The correct setting must be validated in every control unit with a differential voltage measurement!

Page 66/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Outcome on Inphase Timeout

In-phase timeout after Inphase timeout after 0 to 6,500 s

EN
Synchr. Zeitüberschr.

DE
CL2 {0} {1} {2} This parameter configures the maximum time for attempting to detect
  
4576
synchronicity. This timer starts to count as soon as inphase monitoring is enabled
prior to a transfer. If synchronicity is detected between the two sources, the transfer
command will be issued. The timer will be bypassed.

Outcome on In-phase timeout Outcome on inphase timeout Abort / Delayed


EN

Aktion bei Sync. Zeitüberschr.


DE

CL2 {0} {1} {2} This parameter determines the behavior of the unit following an unsuccessful
4582    synchronicity detection using the following options:

Abort ........... The transfer will be aborted.


Delayed ........ A delayed transition will be performed.

Example:
If a load test is requested and inphase monitoring is enabled (parameter 4570 is
configured to "ON"), the inphase timeout timer (parameter 4576) starts prior to a
transfer and the unit attempts to detect a synchronicity between the two sources. If
no synchronicity can be detected before the timer expires (because of a misadjusted
voltage or speed controller at the engine for example), the behavior configured here
determines the further transfer proceeding.

If Abort is configured here, the complete transfer request will be aborted. This
means that all remote start requests (like load test) will be ignored if they are still
present and the system will remain on the available source.

If Delayed is configured here, a delayed transition will be performed. This means


that the switch changes to neutral position for a configured time to ramp down
connected motor loads before it changes to the other source. This is important
because motors, which are running down, may act as generators, which may lead to
a detection of a failed synchronization in case of a too early transfer.

Note: This function may only be used, if "Delayed" or "Closed" is configured as


"Transfer switch type" (parameter 3424). If "Standard" is configured as "Transfer
switch type" (parameter 3424) and "Outcome on In-phase timeout" is configured to
"Delayed", the unit behaves as if "Abort" would have been configured here.

© Woodward Page 67/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Overcurrent
Current is monitored depending on the parameters 1860 "S2 Load current measuring" and 1863 "S1 Load current
measuring". Only the current of the source, which is connected to the load, is measured, because the CT is
located at the load connection. The load overcurrent alarm contains three limits and can be setup as a step definite
time overcurrent alarm as illustrated in the figure below. Monitoring of the maximum phase current is performed
in three steps. Every step can be provided with a delay time independent of the other steps.
If this protective function is triggered, the alarm list indicates "Overcurrent 1", "Overcurrent 2", or
"Overcurrent 3".

IRated [%]
Lim.1 < Lim.2 < Lim.3
t[Lim.1] > t[Lim.2] > t[Lim.3]
Lim.3 [%/IRated]
Protected Area

Lim.2 [%/IRated]

Lim.1 [%/IRated]

t[Lim.3] t[Lim.2] t[Lim.1] t [s]


Figure 3-23: Monitoring - load time-overcurrent

Parameter table Level Text Setting range Standard value


Overcurrent (the hysteresis is 1 % of the rated value)
The parameters represented in Level 1 Monitoring ON / OFF ON
this table are specified in the Limit 50.0 to 300.0 % 110.0 %
following, whereas the Delay 0.02 to 99.99 s 30.00 s
description is identical for all Self-acknowledgment YES / NO NO
levels; the levels may only Level 2 Monitoring ON / OFF ON
differ in their setting ranges. Limit 50.0 to 300.0 % 150.0 %
Delay 0.02 to 99.99 s 1.00 s
Self-acknowledgment YES / NO NO
Level 3 Monitoring ON / OFF ON
Limit 50.0 to 300.0 % 250.0 %
Delay 0.02 to 99.99 s 0.40 s
Self-acknowledgment YES / NO NO
Table 3-4: Monitoring - standard values - load time-overcurrent

Page 68/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring Load overcurrent, TOC: Monitoring (Level 1/Level 2/Level 3) ON / OFF

EN
Überwachung

DE
CL2 {0} {1} {2} ON................ Overcurrent monitoring is carried out according to the following
2200    parameters. Monitoring is performed at three levels. All three values
2206
2212 may be configured independent from each other (prerequisite:
Level 1 < Level 2 < Level 3).
OFF.............. Monitoring is disabled for level 1, level 2, and/or level 3.

Limit Load overcurrent, TOC: Threshold value (Level 1/Level 2/Level 3) 50.0 to 300.0 %
EN

Limit
DE

CL2 {0} {1} {2}  This value refers to the Rated current (parameter 1754, see page 18).
2204   
2210
2216 The percentage values that are to be monitored for each threshold limit are defined
here. If this value is reached or exceeded for at least the delay time without
interruption, an alarm is issued.

Delay Load overcurrent, TOC: Delay (Level 1/Level 2/Level 3) 0.02 to 99.99 s
EN

Verzögerung
DE

CL2 {0} {1} {2} If the monitored load current exceeds the threshold value for the delay time
2205    configured here, an alarm will be issued. If the monitored load current falls below
2211
2217 the threshold (minus the hysteresis) before the delay expires the time will be reset.

Self acknowledge Load overcurrent, TOC: Self acknowledgment (Level 1/Level 2/Level 3) ON / OFF
EN

Selbstquittierend
DE

CL2 {0} {1} {2} YES .............. The control automatically clears the alarm if it is no longer valid.
  
2202
2208
NO................ An automatic reset of the alarm does not occur. The reset occurs
2214 manually by pressing the appropriate buttons, by activating the
LogicsManager output "External acknowledgement" via an discrete
input, or via an interface.

© Woodward Page 69/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Overload
Power is monitored depending on the parameters 1861 "S2 voltage measuring", 1862 "S1 voltage measuring",
1860 "S2 Load current measuring" and 1863 "S1 Load current measuring". Only the power of the source, which
is connected to the load, is measured, because the CT is located at the load connection. If the real power is above
the configured limit an alarm will be issued.
If this protective function is triggered, the alarm list indicates "Overload 1" or "Overload 2".

[%] delay level 2 delay level 2

Limit level 2
Limit level P2Hysteresis

Limit level 1
Limit level 1Hysteresis

Rated value
[100 %]
delay level 1 delay level 1 delay level 1 delay level 1

Alarm level 1
(Alarm limit 1)

Alarm level 2
(Alarm limit 2)

Figure 3-24: Monitoring - overload

Parameter table Level Text Setting range Standard value


Overload (the hysteresis is 1 % of the rated value)
The parameters represented in Level 1 Monitoring ON / OFF ON
this table are specified in the Limit 50.0 to 300.0 % 110.0 %
following, whereas the Delay 0.02 to 99.99 s 11.00 s
description is identical for all Self-acknowledgment YES / NO NO
levels; the levels may only Level 2 Monitoring ON / OFF ON
differ in their setting ranges. Limit 50.0 to 300.0 % 120.0 %
Delay 0.02 to 99.99 s 0.10 s
Self-acknowledgment YES / NO NO
Table 3-5: Monitoring - standard values - overload

Page 70/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring Overload: Monitoring (Level 1/Level 2) ON / OFF

EN
Überwachung

DE
CL2 {0} {1} {2} ON................ Overload monitoring is carried out according to the following
2300    parameters. Monitoring is performed at two levels. Both values may
2306
be configured independent from each other (prerequisite: limit 1
< limit 2).
OFF.............. Monitoring is disabled for level 1 and/or level 2.

Limit Overload: Threshold value (Level 1/Level 2) 50.0 to 300.00 %


EN

Limit
DE

CL2 {0} {1} {2}  This value refers to the Rated active power (parameter 1752, see page 18).
2304   
2310
The percentage values that are to be monitored for each threshold limit are defined
here. If this value is reached or exceeded for at least the delay time without
interruption, an alarm is issued.

Delay Overload: Delayed (Level 1/Level 2) 0.02 to 99.99 s


EN

Verzögerung
DE

CL2 {0} {1} {2} If the monitored load exceeds the threshold value for the delay time configured
2305    here, an alarm will be issued. If the monitored load falls below the threshold (minus
2311
the hysteresis) before the delay expires the time will be reset.

Self acknowledge Overload: Self acknowledgment (Level 1/Level 2) YES / NO


EN

Selbstquittierend
DE

CL2 {0} {1} {2} YES .............. The control automatically clears the alarm if it is no longer valid.
  
2302
2308
NO................ An automatic reset of the alarm does not occur. The reset occurs
manually by pressing the appropriate buttons, by activating the
LogicsManager output "External acknowledgement" via an discrete
input, or via an interface.

© Woodward Page 71/141


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Engine, Start Failure Source 1


If this protective function is triggered, the alarm list indicates "Start Fail S1".

S1 start fail delay time Source 1 start fail: delay time 1 to 6500 s
EN

S1 Startfehler Zeit
DE

CL2 {0} {1} {2} If the "S1 start delay" timer has expired, the engine start signal will be issued. If the
3341 --- --- 
"engine start" relay de-energizes, "Source 1 start fail delay" timer starts to count.
Now, the controller expects the engine to start within the time configured here. If
this time will be exceeded, a "Start Fail" alarm will be issued.

If this timer is running, the "Starting S1" message is displayed.

This parameter is only visible, if the application mode (parameter 4148) is


configured to "Gen-Gen".

Monitoring: Engine, Start Failure Source 2


If this protective function is triggered, the alarm list indicates "Start Fail S2".

S2 start fail delay time Source 2 start fail: delay time 1 to 6500 s
EN

S2 Startfehler Zeit
DE

CL2 {0} {1} {2} If the "S2 start delay" timer has expired, the engine start signal will be issued. If the
3331    "engine start" relay de-energizes, "Source 2 start fail delay" timer starts to count.
Now, the controller expects the engine to start within the time configured here. If
this time will be exceeded, a "Start Fail" alarm will be issued.

If this timer is running, the "Starting S2" message is displayed.

Page 72/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Battery, Overvoltage


There are two battery overvoltage alarm levels available in the control. Both alarms are definite time alarms and
are illustrated in the below figure. The figure diagrams a frequency trend and the associated pickup times and
length of the alarms. It should be noted that this figure illustrates a level 1 alarm that is self-acknowledged.
Monitoring of the voltage is done in two steps.
If this protective function is triggered, the alarm list indicates "Batt.overvolt.1" or
"Batt.overvolt.2".

[%] delay level 2 delay level 2

Limit level 2
Limit level P2Hysteresis

Limit level 1
Limit level 1Hysteresis

Rated value
[100 %]
delay level 1 delay level 1 delay level 1 delay level 1

Alarm level 1
(Alarm limit 1)

Alarm level 2
(Alarm limit 2)

Figure 3-25: Monitoring - battery overvoltage

Parameter table Level Text Setting range Standard value


Battery overvoltage (the hysteresis is 0,7 % of the rated value.)
The parameters represented in Level 1 Monitoring ON / OFF ON
this table are specified in the Limit 8.0 to 42.0 V 32.0 V
following, whereas the Delay 0.02 to 99.99 s 5.00 s
description is identical for all
levels; the levels may only Self-acknowledgment YES / NO NO
differ in their setting ranges. Level 2 Monitoring ON / OFF OFF
Limit 8.0 to 42.0 V 35.0 V
Delay 0.02 to 99.99 s 1.00 s
Self-acknowledgment YES / NO NO
Table 3-6: Monitoring - standard values - battery overvoltage

© Woodward Page 73/141


Manual 37386D DTSC-200 - ATS Controller

EN
Monitoring Battery overvoltage: Monitoring (Level 1/Level 2) ON / OFF
Überwachung
DE

CL2 {0} {1} {2} ON ................Overvoltage monitoring of the battery voltage is carried out
3450    according to the following parameters.
3456
OFF ..............Monitoring is disabled for level 1 and/or level 2.

Limit Battery overvoltage: Threshold value (Level 1/Level 2) 8.0 to 42.0 V


EN

Limit
DE

CL2 {0} {1} {2} The threshold values that are to be monitored are defined here. If the monitored
3454    battery voltage reaches or exceeds this value for at least the delay time without
3460
interruption, an alarm is issued.

Delay Battery overvoltage: Delay time (Level 1/Level 2) 0.02 to 99.99 s


EN

Verzögerung
DE

CL2 {0} {1} {2} If the monitored battery voltage exceeds the threshold value for the delay time
3455    configured here, an alarm will be issued. If the monitored battery voltage falls
3461
below the threshold (minus the hysteresis) before the delay expires the time will be
reset.

Self acknowledge Battery overvoltage: Self acknowledgment (Level 1/Level 2) YES / NO


EN

Selbstquittierend
DE

CL2 {0} {1} {2} YES ..............The control automatically clears the alarm if it is no longer valid.
3452    NO ................An automatic reset of the alarm does not occur. The reset occurs
3458
manually by pressing the appropriate buttons, by activating the
LogicsManager output "External acknowledgement" via an discrete
input, or via an interface.

Page 74/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: Battery, Undervoltage


There are two battery undervoltage alarm levels available in the control. Both alarms are definite time alarms and
are illustrated in the below figure. The figure diagrams a frequency trend and the associated pickup times and
length of the alarms. It should be noted that this figure illustrates a level 1 alarm that is self-acknowledged.
Monitoring of the voltage is done in two steps.
If this protective function is triggered, the alarm list indicates "Batt.undervolt.1" or
"Batt.undervolt.2".

[%]
Rated value
[100 %]

Limit level 1Hysteresis


Limit level 1
Limit level 2Hysteresis
Limit level 2

delay level 2 delay level 2

Alarm level 1
(Alarm limit 1)

Alarm level 2
(Alarm limit 2)

Figure 3-26: Monitoring - battery undervoltage

Parameter table Level Text Setting range Standard value


Battery undervoltage (The hysteresis is 0,7 % of the rated value).
The parameters represented in Level 1 Monitoring ON / OFF ON
this table are specified in the Limit 8.0 to 42.0 V 24.0 V
following, whereas the Delay 0.02 to 99.99 s 60.00 s
description is identical for all
levels; the levels may only Self-acknowledgment YES / NO NO
differ in their setting ranges. Level 2 Monitoring ON / OFF ON
Limit 8.0 to 42.0 V 20.0 V
Delay 0.02 to 99.99 s 10.00 s
Self-acknowledgment YES / NO NO
Table 3-7: Monitoring - standard values - battery undervoltage

© Woodward Page 75/141


Manual 37386D DTSC-200 - ATS Controller

EN
Monitoring Battery undervoltage: Monitoring (Level 1/Level 2) ON / OFF
Überwachung
DE

CL2 {0} {1} {2} ON ................Undervoltage monitoring of the battery voltage is carried out
3500    according to the following parameters.
3506
OFF ..............Monitoring is disabled for level 1 and/or level 2.

Limit Battery undervoltage: Threshold value (Level 1/Level 2) 8.0 to 42.0 V


EN

Limit
DE

CL2 {0} {1} {2} The threshold values that are to be monitored are defined here. If the monitored
3504    battery voltage reaches or falls below this value for at least the delay time without
3510
interruption, an alarm is issued..

Note:
The default monitoring limit for battery undervoltage is 24 Vdc after 60 seconds.
This is because in normal operation the terminal voltage is approximately 26 Vdc
(alternator charged battery).

Delay Battery undervoltage: Delay time (Level 1/Level 2) 0.02 to 99.99 s


EN

Verzögerung
DE

CL2 {0} {1} {2} If the battery voltage falls below the threshold value for the delay time configured
3505    here, an alarm will be issued. If the battery voltage exceeds the threshold (plus the
3511
hysteresis) again before the delay expires the time will be reset.

Self acknowledge Battery undervoltage: Self acknowledgment (Level 1/Level 2) YES / NO


EN

Selbstquittierend
DE

CL2 {0} {1} {2} YES ..............The control automatically clears the alarm if it is no longer valid.
3502    NO ................An automatic reset of the alarm does not occur. The reset occurs
3508
manually by pressing the appropriate buttons, by activating the
LogicsManager output "External acknowledgement" via an discrete
input, or via an interface.

Page 76/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Monitoring: CANopen Interface


The CANopen interface is monitored. If the interface does not receive a CANopen protocol message before the
delay expires, an alarm will be initiated.
If this protective function is triggered, the alarm list indicates "CAN Open Fault".

Monitoring CANopen Interface: Monitoring ON / OFF


EN

Überwachung
DE

CL2 {0} {1} {2} ON................ Monitoring of the CANopen interface is carried out according to the
3150    following parameters.
OFF.............. Monitoring is disabled.

Delay CANopen Interface: Delay 0.1 to 650.0 s


EN

Verzögerung
DE

CL2 {0} {1} {2} The delay is configured with this parameter. If the interface does not receive a
3154    CANopen protocol message before the delay expires, an alarm is issued. The delay
timer is re-initialized after every message is received.

Self acknowledge CANopen Interface: Self acknowledgment YES / NO


EN

Selbstquittierend
DE

CL2 {0} {1} {2} YES .............. The control automatically clears the alarm if it is no longer valid.
3152    NO................ An automatic reset of the alarm does not occur. The reset occurs
manually by pressing the appropriate buttons, by activating the
LogicsManager output "External acknowledgement" via an discrete
input, or via an interface.

NOTE
This protection is only available if an external digital I/O board (e.g. IKD 1) is connected.

© Woodward Page 77/141


Manual 37386D DTSC-200 - ATS Controller

Discrete Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Number Terminal Function
Internal discrete inputs
[DI 1] 51 Reply from ATS limit switch: Breaker in source 1 position [S1]
[DI 2] 52 Reply from ATS limit switch: Breaker in source 2 position [S2]
[DI 3] 53 Reply from ATS limit switch: Breaker in source 1 open position [S1O] #1
[DI 4] 54 Reply from ATS limit switch: Breaker in source 2 open position [S2O] #1
[DI 5] 55 Control input (LogicsManager), pre-assigned with Inhibit ATS
[DI 6] 56 Control input (LogicsManager)
[DI 7] 57 Control input (LogicsManager)
[DI 8] 58 Control input (LogicsManager)
[DI 9] 59 Control input (LogicsManager)
[DI 10] 60 Control input (LogicsManager)
[DI 11] 61 Control input (LogicsManager)
[DI 12] 62 Control input (LogicsManager)
External discrete inputs (via CANopen; not included in DTSC delivery; can be e.g. IKD1, etc.)
[Dex01] --- Control input (LogicsManager)
[Dex02] --- Control input (LogicsManager)
[Dex03] --- Control input (LogicsManager)
[Dex04] --- Control input (LogicsManager)
[Dex05] --- Control input (LogicsManager)
[Dex06] --- Control input (LogicsManager)
[Dex07] --- Control input (LogicsManager)
[Dex08] --- Control input (LogicsManager)
[Dex09] --- Control input (LogicsManager)
[Dex10] --- Control input (LogicsManager)
[Dex11] --- Control input (LogicsManager)
[Dex12] --- Control input (LogicsManager)
[Dex13] --- Control input (LogicsManager)
[Dex14] --- Control input (LogicsManager)
[Dex15] --- Control input (LogicsManager)
[Dex16] --- Control input (LogicsManager)
#1..If the transfer switch type (parameter 3424) is configured to "Standard", this DI may be used as control input (LogicsManager)
Table 3-8: Discrete inputs - assignment

Discrete inputs may be configured to normally open (N.O.) or normally closed (N.C.) states. In the state N.O., no
potential is present during normal operation; if a control operation is performed, the input is energized. In the
state N.C., a potential is continuously present during normal operation; if a control operation is performed, the
input is de-energized.

Vdc (GND)
Discrete input (N.O.)
GND (Vdc)

Vdc (GND)
Discrete input (N.C.)
GND (Vdc)
Figure 3-27: Discrete inputs - control inputs - operation logic

NOTE
The discrete inputs for the breaker position reply messages (DIs 1 through 4) are fixed to N.C. and are
evaluated as N.C., i.e. the breaker is considered as "in position" if the respective DI is de-energized.

Page 78/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

DI {x} operation Discrete input: Operation N.O. / N.C.

EN
DI {x} Funktion

DE
CL2 {0} {1} {2} The discrete inputs may be operated by an normally open (N.O.) or normally closed
1281    (N.C.) contact. The idle circuit current input can be used to monitor for a wire
break. A positive or negative voltage polarity referred to the reference point of the
DI may be applied.
N.O............... The discrete input is analyzed as "enabled" by energizing the input
(normally open).
N.C. .............. The discrete input is analyzed as "enabled" by de-energizing the input
(normally closed).

DI {x} delay Discrete input: Delay 0.08 to 650.00 s


EN

DI {x} Verzögerung
DE

CL2 {0} {1} {2} A delay time in seconds can be assigned to each alarm or control input. The discrete
1280    input must be enabled without interruption for the delay time before the unit reacts.
If the discrete input is used within the LogicsManager this delay is taken into
account as well.

The preceding parameters are used to configure the discrete inputs 5 through 12. The parameter IDs refer to DI 5.
Refer to Table 3-9 for the parameter IDs of the parameters DI 6 through DI 12. The DIs 1 through 4 are fixed for
breaker position feedback signals to the settings, which are indicated in the List Of Parameters starting on
page 126 and cannot be configured. However, the may still be used for other purposes if the breaker position
feedback signals are not used.

DI 5 DI 6 DI 7 DI 8 DI 9 DI 10 DI 11 DI 12
Operation 1281 1301 1321 1341 1361 1381 1206 1226
Delay 1280 1300 1320 1340 1360 1380 1205 1225
Table 3-9: Discrete inputs - parameter IDs

If a Woodward IKD 1 or other external expansion board (Phoenix BK 16DiDo/Co 16DiDo) is connected to the
DTSC via the CAN bus, it is possible to use 16 additional discrete inputs.
The configuration of these external DIs is performed in a similar way like for the internal DIs. Refer to Table
3-10 for the parameter IDs of the parameters for external DIs 1 through 16.

External DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8
Operation 16001 16011 16021 16031 16041 16051 16061 16071
Delay 16000 16010 16020 16030 16040 16050 16060 16070
External DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16
Operation 16081 16091 16101 16111 16121 16131 16141 16151
Delay 16080 16090 16100 16110 16120 16130 16140 16150
Table 3-10: External discrete inputs - parameter IDs

© Woodward Page 79/141


Manual 37386D DTSC-200 - ATS Controller

Discrete Outputs (LogicsManager)


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The discrete outputs are controlled via the LogicsManager.

 Please note the description of the LogicsManager starting on page 101.

Some outputs are assigned a function according to the application mode (see following table).

Relay Function
Number Term.
Internal relay outputs
[R 1] 31/32 LogicsManager
[R 2] 31/33 LogicsManager
[R 3] 31/34 LogicsManager
[R 4] 35/36/37 LogicsManager
[R 5] 39/40/41 LogicsManager (pre-defined with engine 2 start)
[R 6] 42/43 LogicsManager (pre-defined with command: close to source 1 position) [C1]
[R 7] 44/45 LogicsManager (pre-defined with command: close to source 2 position) [C2]
[R 8] 46/47 LogicsManager (pre-defined with command: open from source 1 to neutral position) [C1O]
[R 9] 48/49 LogicsManager (pre-defined with command: open from source 2 to neutral position) [C2O]
External relay output (via CANopen; not included in DTSC-200 delivery; can be an expansion card like IKD1)
[Rex01] --- LogicsManager
[Rex02] --- LogicsManager
[Rex03] --- LogicsManager
[Rex04] --- LogicsManager
[Rex05] --- LogicsManager
[Rex06] --- LogicsManager
[Rex07] --- LogicsManager
[Rex08] --- LogicsManager
[Rex09] --- LogicsManager
[Rex10] --- LogicsManager
[Rex11] --- LogicsManager
[Rex12] --- LogicsManager
[Rex13] --- LogicsManager
[Rex14] --- LogicsManager
[Rex15] --- LogicsManager
[Rex16] --- LogicsManager
Table 3-11: Relay outputs - Assignment

Page 80/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Relay {x} Digital outputs: LogicsManager for relay {x} LogicsManager

EN
Relais {x}

DE
CL2 {0} {1} {2} Once the conditions of the LogicsManager have been fulfilled, the relay will be
12100    energized. The LogicsManager and its default settings are explained on page 101 in
Appendix A: "LogicsManager".

Above parameter IDs refers to R 1. Refer to Table 3-12 for the parameter IDs of the parameters for R 2 to R 9.

R1 R2 R3 R4 R5 R6 R7 R8 R9
Parameter ID 12100 12110 12310 12320 12130 12140 12150 12160 12170
Table 3-12: Discrete outputs - parameter IDs

If a Woodward IKD 1 or other external expansion board (Phoenix BK 16DiDo/Co 16DiDo) is connected to the
DTSC via the CAN bus, it is possible to use 16 additional discrete outputs.
The configuration of these external DOs is performed in a similar way like for the internal DOs. Refer to Table
3-13 for the parameter IDs of the parameters for external DOs 1 through 16.

DO 1 DO 2 DO 3 DO 4 DO 5 DO 6 DO 7 DO 8
Parameter ID 12330 12340 12350 12360 12370 12380 12390 12400
DO 9 DO 10 DO 11 DO 12 DO 13 DO 14 DO 15 DO 16
Parameter ID 12410 12420 12430 12440 12450 12460 12470 12480
Table 3-13: External discrete outputs - parameter IDs

© Woodward Page 81/141


Manual 37386D DTSC-200 - ATS Controller

Counters
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Configure Counters: Operation Hours, kWh, and kvarh

Counter value preset Counter: Set point value for counters 0 to 99,999,999
EN

Zähler-Setzwert
DE

CL2 {0} {1} {2} This value is utilized to set the hours in the following parameters:
2515   
• kWh counter
• kvarh counter

The number entered into this parameter is the number that will be set to the
parameters listed above when they are enabled.

S1 active power [0.00MWh] Counter: Set Source 1 kWh counter YES / NO


EN

S1 Wirkarbeit [0,00MWh]
DE

CL2 {0} {1} {2} YES .............. The current value of this counter is overwritten with the value
2514    configured in "set point value for counters". After the counter has
been (re)set, this parameter changes back to "NO" automatically.
NO ............... The value of this counter is not changed.

S1 react. power [0.00Mvarh] Counter: Set Source 1 kvarh counter YES / NO


EN

S1 Blindarbeit [0,00Mvarh]
DE

CL2 {0} {1} {2} YES .............. The current value of this counter is overwritten with the value
2516    configured in "set point value for counters". After the counter has
been (re)set, this parameter changes back to "NO" automatically.
NO ............... The value of this counter is not changed.

S2 active power [0.00MWh] Counter: Set Source 2 kWh counter YES / NO


EN

S2 Wirkarbeit [0,00MWh]
DE

CL2 {0} {1} {2} YES .............. The current value of this counter is overwritten with the value
2510    configured in "set point value for counters". After the counter has
been (re)set, this parameter changes back to "NO" automatically.
NO ............... The value of this counter is not changed.

S2 react. power [0.00Mvarh] Counter: Set Source 2 kvarh counter YES / NO


EN

S2 Blindarbeit [0,00Mvarh]
DE

CL2 {0} {1} {2} YES .............. The current value of this counter is overwritten with the value
2511    configured in "set point value for counters". After the counter has
been (re)set, this parameter changes back to "NO" automatically.
NO ............... The value of this counter is not changed.

NOTE
Example: The counter value preset (parameter 2515 on page 82) is configured to "3456".
If parameter 2510 will be configured to YES, the S2 active power counter will be set to 34.56MWh.

Page 82/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

LogicsManager
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
LogicsManager: Internal Flags

Internal flags within the LogicsManager logical outputs may be programmed and used for multiple functions. For
conditions and explanation of programming please refer to page 101 in chapter "LogicsManager").

Flag {x] Internal flags: Flag {x} [x = 1 to 8] LogicsManager


EN

Merker {x]
DE

CL2 {0} {1} {2} The flags may be used as auxiliary flags for complex combinations by using the
yyyyy    logical output of these flags as command variable for other logical outputs.

Parameter ID yyyyy Flag {x}


12230 Flag 1
12240 Flag 2
12250 Flag 3
12260 Flag 4
12270 Flag 5
12280 Flag 6
12290 Flag 7
12300 Flag 8
Table 3-14: Internal flags - parameter IDs

NOTE
Flag 1 is also used as placeholder in other logical combinations. Flag 8 is preset with a timer start.

© Woodward Page 83/141


Manual 37386D DTSC-200 - ATS Controller

LogicsManager: Timer
LogicsManager: Daily Time Set Point
Utilizing the LogicsManager it is possible to establish specific times of the day that functions (i.e. generator
exerciser) can be enabled. The two daily time set points are activated each day at the configured time. Using the
LogicsManager these set points may be configured individually or combined to create a time range.

Setpoint {x}: Hour Timer: Daily time set point {x} [x = 1/2]: hour 0 to 23 h
EN

Setpoint {x}: Stunde


DE

CL2 {0} {1} {2} Enter the hour of the daily time set point here. Example:
1652    0 ....................0th hour of the day (midnight).
1657
23 ..................23rd hour of the day (11pm).

Setpoint {x}: Minute Timer: Daily time set point {x} [x = 1/2]: minute 0 to 59 min
EN

Setpoint {x}: Minute


DE

CL2 {0} {1} {2} Enter the minute of the daily time set point here. Example:
1651    0 ....................0th minute of the hour.
1656
59 ..................59th minute of the hour.

Setpoint {x}: Second Timer: Daily time set point {x} [x = 1/2]: second 0 to 59 s
EN

Setpoint {x}: Sekunde


DE

CL2 {0} {1} {2} Enter the second of the daily time set point here. Example
1650    0 ....................0th second of the minute.
1655
59 ..................59th second of the minute.

LogicsManager: Active Time Set Point


Utilizing the LogicsManager it is possible to establish specific days (or hours, minutes, seconds) that functions
(i.e. generator exerciser) can be enabled. The active switching point is activated only on a specified day (or hour,
minute, second). The set points may be configured individually or combined via the LogicsManager. You may
configure monthly, daily, hourly, minutely, or even secondly time set points depending on how you combine the
set points in the LogicsManager.

Active day Timer: Active time set point: day 1 to 31


EN

Aktiver Tag
DE

CL2 {0} {1} {2} Enter the day of the active switch point here. Example:
1663    01 ..................1st day of the month.
31 ..................31st day of the month.
The active time set point is enabled during the indicated day from 0:00:00 hours to
23:59:59 hours.

Active hour Timer: Active time set point: hour 0 to 23 h


EN

Aktive Stunde
DE

CL2 {0} {1} {2} Enter the hour of the active switch point here. Example:
1662    0 ....................0th hour of the day.
23 ..................23rd hour if the day.
The active time set point is enabled every day during the indicated hour from
minute 0 to minute 59.

Active minute Timer: Active time set point: minute 0 to 59 min


EN

Aktive Minute
DE

CL2 {0} {1} {2} Enter the minute of the active switch point here. Example:
1661    0 ....................0th minute of the hour.
59 ..................59th minute of the hour.
The active time set point is enabled every hour during the indicated minute from
second 0 to second 59.

Page 84/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Active second Timer: Active time set point: second 0 to 59 s

EN
Aktive Sekunde

DE
CL2 {0} {1} {2} Enter the second of the active switch point here. Example:
1660    0.................... 0th second of the minute.
59.................. 59th second the minute.
The active time set point is enabled every minute during the indicated second.

LogicsManager: Weekly Time Set Point


Utilizing the LogicsManager it is possible to establish specific days of the week that functions (i.e. generator
exerciser) can be enabled. The weekly time set point is enabled during the indicated day from 0:00:00 hours to
23:59:59 hours.

Monday active Timer: Weekly time set points Monday: days YES / NO
EN

Montag aktiv
DE

CL2 {0} {1} {2} Please enter the days of the weekly workdays.
1670    Monday ........... YES - The switch point is enabled every Monday
NO - The switch point is disabled every Monday

Tuesday active Timer: Weekly time set points Tuesday: days YES / NO
EN

Dienstag aktiv
DE

CL2 {0} {1} {2} Please enter the days of the weekly workdays.
1671    Tuesday ........... YES - The switch point is enabled every Tuesday
NO - The switch point is disabled every Tuesday

Wednesday active Timer: Weekly time set points Wednesday: days YES / NO
EN

Mittwoch aktiv
DE

CL2 {0} {1} {2} Please enter the days of the weekly workdays.
1672    Wednesday ...... YES - The switch point is enabled every Wednesday
NO - The switch point is disabled every Wednesday

Thursday active Timer: Weekly time set points Thursday: days YES / NO
EN

Donnerstag aktiv
DE

CL2 {0} {1} {2} Please enter the days of the weekly workdays.
1673    Thursday ......... YES - The switch point is enabled every Thursday
NO - The switch point is disabled every Thursday

Friday active Timer: Weekly time set points Friday: days YES / NO
EN

Freitag aktiv
DE

CL2 {0} {1} {2} Please enter the days of the weekly workdays.
1674    Friday .............. YES - The switch point is enabled every Friday
NO - The switch point is disabled every Friday

Saturday active Timer: Weekly time set points Saturday: days YES / NO
EN

Samstag aktiv
DE

CL2 {0} {1} {2} Please enter the days of the weekly workdays.
1675    Saturday .......... YES - The switch point is enabled every Saturday
NO - The switch point is disabled every Saturday

Sunday active Timer: Weekly time set points Sunday: days YES / NO
EN

Sonntag aktiv
DE

CL2 {0} {1} {2} Please enter the days of the weekly workdays.
  
1676
Sunday ............. YES - The switch point is enabled every Sunday
NO - The switch point is disabled every Sunday

© Woodward Page 85/141


Manual 37386D DTSC-200 - ATS Controller

Interfaces
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
Please refer to the Interface Manual 37389 for a detailed description of the interface parameters.

Device number Interfaces: Device address 1 to 127


EN

Gerätenummer
DE

CL2 {0} {1} {2} So that this control unit may be positively identified on the CAN bus, the unit
1702    address must be set in this parameter. The address may only be represented once on
the CAN bus. All other addresses on the CAN bus are calculated on the basis of the
address entered in this parameter.

Interfaces: CAN Bus (FlexCAN)

NOTE
The CAN bus is a field bus and subject to various disturbances. Therefore, it cannot be guaranteed that
every request will be answered. We recommend to repeat a request, which is not answered within
reasonable time.

Protocol CAN bus: Protocol OFF / CANopen / LeoPC


EN

Protokoll
DE

CL2 {0} {1} {2} The CAN bus of this unit may be operated with different protocols and Baud rates.
3155    This parameter defines the protocol to be utilized. Please note, that all participants
on the CAN bus must use the same protocol.

OFF ..............The CAN bus is disconnected. Values are not sent or received.
CANopen .....The CANopen protocol is used. More information may be found in
the interface manual 37262 under CANopen.
LeoPC ..........The CAN CAL protocol is used. More information may be found in
the interface manual 37262 under CAN (CAL).

Baudrate CAN bus: Baud rate 20 / 50 / 100 / 125 / 250 / 500 / 800 / 1,000 kBaud
EN

Baudrate
DE

CL2 {0} {1} {2} This parameter defines the used Baud rate. Please note, that all participants on the
3156    CAN bus must use the same Baud rate.

Page 86/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Interfaces: CAN BUS: CANopen

CAN-Open Master CANopen Master YES / NO

EN
CAN-open Master
DE
CL2 {0} {1} {2} YES .............. The DTSC-200 is the CANopen Master.
  
9000
The unit automatically changes into operational mode and transmits
Remote Start messages since Broadcast
Attached external devices were configured from the unit with SDO
messages. The unit sends a SYNC message all 20ms on COB ID 80
Hex.
NO................ The DTSC-200 is a CANopen Slave.

Producer heartbeat time CAN bus: Producer heartbeat time 20 to 65,530 ms


EN

Producer heartbeat time


DE

CL2 {0} {1} {2} Independent from the CANopen Master configuration, the unit transmits a heartbeat
9120    message with this configured heartbeat cycle time. If the producer heartbeat time is
equal 0, the heartbeat will only be sent as response to a remote frame request. The
time configured here will be rounded up to the next 20 ms step.

COB-ID SYNC Message COB-ID SYNC Message 1 to FFFFFFFF


EN

COB-ID SYNC Message


DE

CL2 {0} {1} {2} This parameter defines whether the unit generates the SYNC message or not.
9100   
Complies with CANopen specification: object 1005, subindex 0; defines the COB ID of the
synchronization object (SYNC). The structure of this object is shown in the following tables:

UNSIGNED 32 MSB LSB


bits bits 31 30 29 28-11 10-0
11 bit ID 11 bit ID X 0/1 X 000000000000000000 11 bit identifier

bit number value meaning


31 (MSB) X N/A
30 0 Unit does not generate SYNC message
1 Unit generates SYNC message
29 X N/A
28-11 0 always
10-0 (LSB) X bits 10-0 of SYNC COB ID

Max. answer time ext. devices Max response time ext. devices 0.1 to 9.9 s
EN

Max. Antwortzeit ext. Geräte


DE

CL2 {0} {1} {2} The maximum time that an attached external device has to answer an SDO
9010    message. If the external device fails to answer before this time expires, an abort
message is sent and the SDO message will be sent again. This is only effective, if
DTSC-200 CAN open master is enabled.

Time re-init. Ext. devices Time re-init (re-initialization) ext. devices 0 to 9,999 s
EN

Zeit Re-init. Ext- Geräte


DE

CL2 {0} {1} {2} An external device will be configured again with SDO messages after the time set
  
9009
for this parameter.
If 0 is input in this parameter, the external device will not be configured again with
SDO messages
This only functions if DTSC-200 CAN open master is enabled.

© Woodward Page 87/141


Manual 37386D DTSC-200 - ATS Controller

Interfaces: CAN BUS: CANopen: Additional Server SDOs

2nd Client->Server COB-ID (rx) CAN bus: Client->Server COB-ID (rx) 1 to FFFFFFFF
EN

2. Client->Server COB-ID (rx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
  
9020
the unit. In order to send remote signals (i.e. acknowledge) to the unit. The
additional SDO channel will be made available by configuring this Node ID to a
value different than zero. This is the additional CAN ID for the PLC.

2nd Server->Client COB-ID (tx) CAN bus: Server-> Client COB-ID (tx) 1 to FFFFFFFF
EN

2. Server->Client COB-ID (tx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
9022    the unit. In order to receive remote signals (i.e. acknowledge). The additional SDO
channel will be made available by configuring this Node ID to a value different
than zero. This is the additional CAN ID for the unit.

3rd Client->Server COB-ID (rx) CAN bus: Client->Server COB-ID (rx) 1 to FFFFFFFF
EN

3. Client->Server COB-ID (rx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
9024    the unit. In order to send remote signals (i.e. acknowledge) to the unit. The
additional SDO channel will be made available by configuring this Node ID to a
value different than zero. This is the additional CAN ID for the PLC.

3rd Server->Client COB-ID (tx) CAN bus: Server-> Client COB-ID (tx) 1 to FFFFFFFF
EN

3. Server->Client COB-ID (tx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
9026    the unit. In order to receive remote signals (i.e. acknowledge). The additional SDO
channel will be made available by configuring this Node ID to a value different
than zero. This is the additional CAN ID for the unit.

4th Client->Server COB-ID (rx) CAN bus: Client->Server COB-ID (rx) 1 to FFFFFFFF
EN

4. Client->Server COB-ID (rx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
9028    the unit. In order to send remote signals (i.e. acknowledge) to the unit. The
additional SDO channel will be made available by configuring this Node ID to a
value different than zero. This is the additional CAN ID for the PLC.

4th Server->Client COB-ID (tx) CAN bus: Server-> Client COB-ID (tx) 1 to FFFFFFFF
EN

4. Server->Client COB-ID (tx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
9030    the unit. In order to receive remote signals (i.e. acknowledge). The additional SDO
channel will be made available by configuring this Node ID to a value different
than zero. This is the additional CAN ID for the unit.

5th Client->Server COB-ID (rx) CAN bus: Client->Server COB-ID (rx) 1 to FFFFFFFF
EN

5. Client->Server COB-ID (rx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
9032    the unit. In order to send remote signals (i.e. acknowledge) to the unit. The
additional SDO channel will be made available by configuring this Node ID to a
value different than zero. This is the additional CAN ID for the PLC.

5th Server->Client COB-ID (tx) CAN bus: Server-> Client COB-ID (tx) 1 to FFFFFFFF
EN

5. Server->Client COB-ID (tx)


DE

CL2 {0} {1} {2} In a multi-master application, each Master needs its own identifier (Node ID) from
9034    the unit. In order to receive remote signals (i.e. acknowledge). The additional SDO
channel will be made available by configuring this Node ID to a value different
than zero. This is the additional CAN ID for the unit.

Page 88/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

NOTE
The COB IDs must be entered in decimal numbers in LeoPC 1 and in hexadecimal numbers in the unit.
Here are some important conversions:
Hexadecimal value Decimal value
80h 128
181h 385
201h 513
281h 641
301h 769
381h 897
401h 1025
481h 1153
501h 1281
581h 1409
601h 1537
80000000h 2147483648

Interfaces: CAN BUS: CANopen: Receive PDO (RPDO) {x} ({x} = 1/2)

Figure 3-28 shows the principle of PDO mapping.

Object Dictionary
xxxxh Application Object 1
PDO Mapping
0 3
1 yyyyh 1
2 zzzzh 1 yyyyh Application Object 2
3 xxxxh 1

zzzzh Application Object 3

PDO: App. Object 2 Application Object 3 App. Object 1


Figure 3-28: Interfaces - Principle of PDO mapping

© Woodward Page 89/141


Manual 37386D DTSC-200 - ATS Controller

EN
COB-ID Receive PDO 1/2 - COB-ID 1 to FFFFFFFF
COB-ID
DE

CL2 {0} {1} {2} This parameter contains the communication parameters for the PDOs, the device is
9300    able to receive.
9310

Complies with CANopen specification: object 1400 (for RPDO 1 and 1401 for RPDO 2), subindex 1.
The structure of this object is shown in the following tables:

UNSIGNED 32 MSB LSB


bits 31 30 29 28-11 10-0
11 bit ID 0/1 X X 000000000000000000 11 bit identifier

bit number value meaning


31 (MSB) 0 PDO exists / is valid
1 PDO does not exist / is not valid
30 X N/A
29 X N/A
28-11 0 always
10-0 (LSB) X bits 10-0 of COB ID

PDO valid / not valid allows to select, which PDOs are used in the operational state.

CAUTION
The COB-IDs have to be configured different, even if one RPDO is configured to "no func."2.

Function Function for RPDO 1/2 no func. / 1st IKD /2nd IKD / Bk 16DIDO / Co 16DIDO
EN

Funktion
DE

CL2 {0} {1} {2} The unit provides pre-configured CAN bus settings for the connection of different
9050    units. The unit to be connected must be selected here.
9051

No func. ........No external unit is selected for connection. The CAN bus is disabled.
Values are not sent or received.
1st IKD ..........The unit is pre-configured for the connection of a Woodward IKD 1
expansion board.
2nd IKD .........The unit is pre-configured for the connection of a second Woodward
IKD 1 expansion board.
BK 16 DIDO The unit is pre-configured for the connection of a Phoenix Contact
BK 16 DIDO expansion board.
Co 16 DIDO .The unit is pre-configured for the connection of a Phoenix Contact
Co 16 DIDO expansion board.

The following table shows several possible functional combinations:

PDO1 PDO2 1st IKD 2nd IKD OFF


1st IKD NO YES YES
2nd IKD YES NO YES
Bk 16DIDO NO NO YES
Co 16DIDO NO NO YES
no func. YES YES YES

Read: If PDO1 is configured as 1. IKD, then PDO2 can only be configured as either 2. IKD or "no func.".

Node-ID of the device Node-ID of the device 1 to 127


EN

Node-ID des Gerätes


DE

CL2 {0} {1} {2} Node-ID of the attached device. The SDO messages were sent on the standard
9060    SDO-IDs or the answers were expected.
9061

Page 90/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

RPDO-COP-ID ext. device {x} RPDO-COB-ID ext. device 1 1 to FFFFFFFF

EN
RPDO-COP-ID ext. Gerät {x}

DE
CL2 {0} {1} {2} Value to be written in the object 1800h sub index 1h of the external device.
9070   
9072

CAUTION
COB-IDs already used in other PDOs should be used.
COB-IDs in a CANopen device after loading the standard values:
280h + Node-ID = 640 + Node-ID Object 1801h Subindex 1
380h + Node-ID = 896 + Node-ID Object 1802h Subindex 1
480h + Node-ID = 1152 + Node-ID Object 1803h Subindex 1
The receiving COB-IDs are preallocated:
300h + Node-ID = 768 + Node-ID Object 1401h Subindex 1
400h + Node-ID = 1024 + Node-ID Object 1402h Subindex 1
500h + Node-ID = 1280 + Node-ID Object 1403h Subindex 1.
Problems may be encountered if a COB-ID is assigned multiple times.

Interfaces: CAN Bus: CANopen: Transmit PDO (TPDO) {x} ({x} = 1 to 4)

COB-ID CAN bus 1: Transmit PDO 1 - COB ID 1 to FFFFFFFF


EN

COB-ID
DE

CL2 {0} {1} {2} This parameter contains the communication parameters for the PDOs the unit is
9600    able to transmit. The unit transmits data (i.e. visualization data) on the CAN ID
9610
9620 configured here.
9630

Complies with CANopen specification: object 1800 for (TPDO 1, 1801 for TPDO 2, 1802 for TPDO 3,
and 1803 for TPDO 4), subindex 1. The structure of this object is shown in the following tables:

UNSIGNED 32 MSB LSB


bits bits 31 30 29 28-11 10-0
11 bit ID 11 bit ID 0/1 X X 000000000000000000 11 bit identifier

bit number value meaning


31 (MSB) 0 PDO exists / is valid
1 PDO does not exist / is not valid
30 X N/A
29 X N/A
28-11 0 always
10-0 (LSB) X bits 10-0 of COB ID

PDO valid / not valid allows to select, which PDOs are used in the operational state.

© Woodward Page 91/141


Manual 37386D DTSC-200 - ATS Controller

EN
Transmission type CAN bus 1: Transmit PDO 1 - Transmission type 0 to 255
Transmission type
DE

CL2 {0} {1} {2} This parameter contains the communication parameters for the PDOs the unit is
9602    able to transmit. It defines whether the unit broadcasts all data automatically (value
9612
9622 254 or 255) or only upon request with the configured address of the COB ID SYNC
9632
message (parameter 9100).
Complies with CANopen specification: object 1800 (for TPDO 1, 1801 for TPDO 2, 1802 for TPDO 3,
and 1803 for TPDO 4), subindex 2. The description of the transmission type is shown in the following
table:

transmission type PDO transmission


cyclic acyclic synchronous asynchronous RTR only
0 will not be sent
1-240 X X
241-251 will not be sent
252 will not be sent
253 will not be sent
254 X
255 X

A value between 1 and 240 means that the PDO is transferred synchronously and cyclically. The
transmission type indicating the number of SYNC, which are necessary to trigger PDO transmissions.
Receive PDOs are always triggered by the following SYNC upon reception of data independent of the
transmission types 0 to 240. For TPDOs, transmission type 254 and 255 means, the application event is
the event timer.

Event-timer CAN bus 1: Transmit PDO 1 – Event timer 0 to 65000 ms


EN

Event-timer
DE

CL2 {0} {1} {2} This parameter contains the communication parameters for the PDOs the unit is
9604    able to transmit. The broadcast cycle for the transmitted data is configured here.
9614
9624 The time configured here will be rounded up to the next 5 ms step.
9634

Complies with CANopen specification: object 1800 (for TPDO 1, 1801 for TPDO 2, 1802 for TPDO 3,
and 1803 for TPDO 4), subindex 5

Number of Mapped Objects CAN bus 1: Transmit PDO 1 - Number of mapped objects 0 to 4
EN

Anzahl der Mapped Objekte


DE

CL2 {0} {1} {2} This parameter contains the mapping for the PDOs the unit is able to transmit. This
9609    number is also the number of the application variables, which shall be transmitted
9619
9629 with the corresponding PDO.
9639

Complies with CANopen specification: object 1A00 (for TPDO 1, 1A01 for TPDO 2, 1A02 for TPDO 3,
and 1A03 for TPDO 4), subindex 0

1. Mapped Object CAN bus 1: Transmit PDO 1 - 1. Mapped object 0 to 65535


EN

1. Mapped Objekt
DE

CL2 {0} {1} {2} This parameter contains the information about the mapped application variables.
9605    These entries describe the PDO contents by their index. The sub-index is always 1.
9615
9625 The length is determined automatically.
9635

Complies with CANopen specification: object 1A00 (for TPDO 1, 1A01 for TPDO 2, 1A02 for TPDO 3,
and 1A03 for TPDO 4), subindex 1

2. Mapped Object CAN bus 1: Transmit PDO 1 - 2. Mapped object 0 to 65535


EN

2. Mapped Objekt
DE

CL2 {0} {1} {2} This parameter contains the information about the mapped application variables.
9606    These entries describe the PDO contents by their index. The sub-index is always 1.
9616
9626 The length is determined automatically.
9636

Complies with CANopen specification: object 1A00 (for TPDO 1, 1A01 for TPDO 2, 1A02 for TPDO 3,
and 1A03 for TPDO 4), subindex 2

Page 92/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

3. Mapped Object CAN bus 1: Transmit PDO 1 - 3. Mapped object 0 to 65535

EN
3. Mapped Objekt

DE
CL2 {0} {1} {2} This parameter contains the information about the mapped application variables.
9607    These entries describe the PDO contents by their index. The sub-index is always 1.
9617
9627 The length is determined automatically.
9637

Complies with CANopen specification: object 1A00 (for TPDO 1, 1A01 for TPDO 2, 1A02 for TPDO 3,
and 1A03 for TPDO 4), subindex 3

4. Mapped Object CAN bus 1: Transmit PDO 1 - 4. Mapped object 0 to 65535


EN

4. Mapped Objekt
DE

CL2 {0} {1} {2} This parameter contains the information about the mapped application variables.
9608    These entries describe the PDO contents by their index. The sub-index is always 1.
9618
9628 The length is determined automatically.
9638

Complies with CANopen specification: object 1A00 (for TPDO 1, 1A01 for TPDO 2, 1A02 for TPDO 3,
and 1A03 for TPDO 4), subindex 4

NOTE
CANopen allows to send 8 byte of data with each Transmit PDO. These may be defined separately if no
pre-defined data protocol is used.
All data protocol parameters with a parameter ID may be sent as an object with a CANopen Transmit
PDO.
In this case, the data length will be taken from the data byte column (refer to the Data Protocols section
in the Interface Manual 37389):
• 1,2 UNSIGNED16 or SIGNED16
• 3,4 UNSIGNED16 or SIGNED16
• 5,6 UNSIGNED16 or SIGNED16
• 1,2,3,4 UNSIGNED32 or SIGNED32
• 3,4,5,6 UNSIGNED32 or SIGNED32
• etc.
The object ID is identical with the parameter ID when configuring via front panel or LeoPC 1.

© Woodward Page 93/141


Manual 37386D DTSC-200 - ATS Controller

Interfaces: Serial Interface 1 (RS-232)

Baudrate Serial interface: Baud rate 2.4 / 4.8 / 9.6 / 14.4 / 19.2 / 38.4 / 65 / 115 kBaud
EN

Baudrate
DE

CL2 {0} {1} {2}  A DPC (P/N 5417-557) must be used for connecting the control unit
3163    from the service interface to a PC or to another participant.

The serial interface of this unit connects to an RJ45-plug on the side of the
housing. This parameter defines the baud rate that communications will be
performed. Please note, that all participants on the service interface must use the
same Baud rate.

Parity Serial interface: Parity no / even / odd


EN

Parity
DE

CL2 {0} {1} {2} The used parity of the service interface is set here.
3161   

Stop Bits Serial interface: Stop bits one / two


EN

Stop Bits
DE

CL2 {0} {1} {2} The number of stop bits is set here.
3162   

Interfaces: Serial Interface 2 (RS-485)

Baudrate Serial interface 2: Baud rate 2.4 / 4.8 / 9.6 / 14.4 / 19.2 / 38.4 / 56 / 115 kBaud
EN

Baudrate
DE

CL2 {0} {1} {2} This parameter defines the baud rate for communications. Please note, that all
3170    participants on the service interface must use the same baud rate.

Parity Serial interface 2: Parity no / even / odd


EN

Parity
DE

CL2 {0} {1} {2} The used parity of the service interface is set here.
3171   

Stop bits Serial interface 2: Stop bits one / two


EN

Stop Bits
DE

CL2 {0} {1} {2} The number of stop bits is set here.
3172   

Full-, halfduplex mode Serial interface 2: Full-/halfduplex mode Fullduplex / Halfduplex


EN

Voll-, Halbduplex Modus


DE

CL2 {0} {1} {2} Fullduplex ... Fullduplex mode is enabled.


3173    Halfduplex ... Halfduplex mode is enabled.

ModBus Slave ID Serial interface: Modbus Slave ID 0 to 255


EN

ModBus Slave ID
DE

CL2 {0} {1} {2} The Modbus device address is entered here, which is used to identify the device
3185    via Modbus. If 0 is entered here, the Modbus Slave module is disabled.

Modbus Reply delay time Serial interface: Reply delay time 0.00 to 0.20 s
EN

Modbus Zeitverzöger. Der


DE

Antwort This is the minimum delay time between a request from the Modbus master and
CL2 {0} {1} {2}
the sent response of the slave. This time is also required if an external interface
3186   
converter to RS-485 is used for example. Please note that you also need the
DPC (refer to page 10) in this case.

Page 94/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

System
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
System: Configure Display Backlight

Configure display backlight Display backlight ON / OFF / Auto / Key actv.


EN

Konfig. Display Beleuchtung


DE

CL2 {0} {1} {2} This parameter determines the behavior of the display backlight. The following
4556    options are available:

ON................ The display backlight is always enabled.


OFF.............. The display backlight is always disabled.
Auto ............. The display backlight will be disabled if no voltage is detected
anymore at both connected sources.
Key actv....... The display backlight will be disabled if no softkey has been pressed
for the time configured in parameter 4557. It will be enabled again
after any softkey of the unit has been pressed.

Time until backlight shutdown Time until backlight shutdown 1 to 999 s


EN

Zeit bis Abschaltung


DE

CL2 {0} {1} {2}  This parameter is only visible if parameter 4556 has been configured to
4557    "Key actv.".

If no softkey has been pressed for the time configured here, the display backlight
will be disabled.

© Woodward Page 95/141


Manual 37386D DTSC-200 - ATS Controller

System: Configure Daylight Saving Time

It is possible to configure the real-time clock for an automatic change to daylight saving time. Start and end
date/time of the daylight saving time period have to be entered for this.

Example: If daylight saving time starts at 2:00 am on the 2nd Sunday in March and ends at 2:00 am on the 1st
Sunday in November, the unit has to be configured like shown in Table 3-15 to enable an automatic change to
daylight saving time and back to standard time.

ID Parameter Setting
4591 Daylight saving time ON
4593 DST begin month 3
4592 DST begin Sunday 2
4594 DST begin time 2
4596 DST end month 11
4595 DST end Sunday 1
4597 DST end time 2
Table 3-15: Daylight saving time - configuration example

Daylight saving time Daylight saving time ON / OFF


EN

Sommer-Winterzeit Erkennung
DE

CL2 {0} {1} {2} This parameter enables or disables daylight saving time.
4591   
ON ............... Daylight saving time is performed according to the following
parameters.
OFF ............. Daylight saving time is disabled.

DST begin month Daylight saving time start month 1 to 12


EN

Monat für Sommerzeitbeginn


DE

CL2 {0} {1} {2} Daylight saving time starts in the month configured here.
4593   

DST begin Sunday Daylight saving time start Sunday 1 to 4


EN

Sonntag für Sommerzeitbeginn


DE

CL2 {0} {1} {2} Daylight saving time starts on the Sunday configured here of the month configured
4592    in parameter 4593.

DST begin time Daylight saving time start time 0 to 23 h


EN

Uhrzeit für Sommerzeitbeginn


DE

CL2 {0} {1} {2} Daylight saving time starts at this time on the Sunday configured in
4594    parameter 4592.

DST end month Daylight saving time end month 1 to 12


EN

Monat für Sommerzeitende


DE

CL2 {0} {1} {2} Daylight saving time ends in the month configured here.
4596   

DST end Sunday Daylight saving time end Sunday 1 to 4


EN

Sonntag für Sommerzeitende


DE

CL2 {0} {1} {2} Daylight saving time ends on the Sunday configured here of the month configured
4595    in parameter 4596.

DST end time Daylight saving time end time 0 to 23 h


EN

Uhrzeit für Sommerzeitende


DE

CL2 {0} {1} {2} Daylight saving time ends at this time on the Sunday configured in
4597    parameter 4595.

Page 96/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

System: Password System


Refer to the Password section on page 16 for a detailed description of the password system.

Code level display Password system: Code level via display Info
EN
DE
Codeebene Display
CL2 {0} {1} {2} This value displays the code level, which is currently enabled for access via the
  
10405
front panel display.

Code level CAN port Password system: Code level via CAN-Bus Info
EN

Codeebene CAN Schnittstelle


DE

CL2 {0} {1} {2} This value displays the code level, which is currently enabled for access via the
10407    CAN interface.

Code level serial port/DPC Password system: Code level via serial RS-232 (DPC) interface Info
EN

Codeebene RS232/DPC
DE

CL2 {0} {1} {2} This value displays the code level, which is currently enabled for access via RS-
10406    232 serial interface #1.

Supercommissioning level code Password system: Password "Supercommissioning" (CL5) 0000 to 9999
EN

Code Supercommissioning Ebene


DE

CL5 {0} {1} {2} The password for the code level "Supercommissioning" is defined in this
10411    parameter. Refer to the Password section on page 16 for default values.

Temp. supercomm. Level code Password system: Password "Temporary Supercommissioning" (CL4) 0000 to 9999
EN

Code temp. Supercomm. Ebene


DE

CL5 {0} {1} {2} The algorithm for calculating the password for the code level "Temporary
10412    Supercommissioning" is defined in this parameter.

Commissioning level code Password system: Password "Commission" (CL3) 0000 to 9999
EN

Code Inbetriebnahme Ebene


DE

CL3 {0} {1} {2} The password for the code level "Commission" is defined in this parameter.
10413    Refer to the Password section on page 16 for default values.

Temp. commissioning level code Password system: Password "Temporary Commission" (CL2) 0000 to 9999
EN

Code temp. Inbetriebn. Ebene


DE

CL3 {0} {1} {2} The algorithm for calculating the password for the code level "Temporary
10414    Commissioning" is defined in this parameter.

Basic level code Password system: Password "Service Level" (CL1) 0000 to 9999
EN

Code Serviceebene
DE

CL1 {0} {1} {2} The password for the code level "Service" is defined in this parameter. Refer to
10415    the Password section on page 16 for default values.

Password Password system: Entry via front panel 0000 to 9999


EN

Passwort
DE

CS0 {0} {1} {2} To configure the control via the front panel bus enter the password.
10416   

Password CAN Password system: Entry via CAN bus 0000 to 9999
EN

Passwort CAN
DE

CS0 {0} {1} {2} To configure the control via CAN bus enter "password CAN".
10402   

Password DPC Password system: Entry via DPC 0000 to 9999


EN

Passwort RS232 / DPC


DE

CS0 {0} {1} {2} To configure the control via DPC please enter "password DPC".
10401   

© Woodward Page 97/141


Manual 37386D DTSC-200 - ATS Controller

EN
Factory Settings Factory settings: Factory settings CAN YES / NO
Werkseinstellung
DE

CL2 {0} {1} {2} YES ..............The resetting of the factory settings via CAN bus will be enabled.
1703    NO ................The resetting of the factory settings via CAN bus will not be enabled.

Factory Settings DPC/RS232 Factory settings: Factory settings DPC/RS-232 YES / NO


EN

Werkseinstellung DPC/RS232
DE

L {0} {1} {2} YES ..............The resetting of the factory settings via DPC/RS-232 will be enabled.
1704    NO ................The resetting of the factory settings via DPC/RS-232 will not be
enabled.

Factory Settings CAN Factory settings: Factory settings CAN YES / NO


EN

Werkseinstellung CAN
DE

L {0} {1} {2} YES ..............The resetting of the factory settings via CAN bus will be enabled.
1705    NO ................The resetting of the factory settings via CAN bus will not be enabled.

Set default values Factory settings: Set default values YES / NO


EN

Standardwerte
DE

CL2 {0} {1} {2} YES ..............The default values, which have been enabled with parameter 1703,
1701    1704 or parameter 1705, will be loaded by the unit.
NO ................The factory settings will not be loaded by the unit.

Start Bootloader Factory settings: Start Bootloader 00000


EN

Bootloader starten
DE

CL3 {0} {1} {2} This function may be used to start the Bootloader. In order to do this, the correct
10500    code must be entered here while the unit is in the code level required for this.

CAUTION
The Start Bootloader function is used to flash the software and may only be used by authorized
Woodward technicians!

NOTE
If the DTSC-200 parameters are read out via CAN / DPC and stored as standard values, all parameters
behind parameter 1701 (Set default values) will not be overwritten when writing back the standard
value file via CAN / DPC.
This prevents an unintentional start of the Bootloader or an overwriting of the time or date in the unit
with a wrong (old) value. The following version information is only for info anyway and cannot be
overwritten.

Page 98/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

System: Real-Time Clock Set


This screen shows the current date and time. The clock is implemented as
real time clock. In case of a voltage supply failure an internal battery
guarantees that the information is not lost. The data stand for:

XX:YY:ZZ ............. hour:minute:second.


AAAA-BBB-CC...... Year-month-day.

System: Adjust Clock


Hour Adjust clock: hour 0 to 23 h
EN

Stunden
DE

CL2 {0} {1} {2} The current hour of the clock time is set here. Example:
1762    0.................... 0th hour of the day.
23.................. 23th hour of the day.

Minute Adjust clock: minute 0 to 59 min


EN

Minuten
DE

CL2 {0} {1} {2} The current minute of the clock time is set here. Example:
1761    0.................... 0th minute of the hour.
59.................. 59th minute of the hour.

Second Adjust clock: second 0 to 59 s


EN

Sekunden
DE

CL2 {0} {1} {2} The current second of the clock time is set here. Example:
1760    0.................... 0th second of the minute.
59.................. 59th second of the minute.

System: Adjust Date


Day Adjust clock: day 1 to 31
EN

Tag
DE

CL2 {0} {1} {2} The current day of the date is set here. Example:
1763    1.................... 1st day of the month.
31.................. 31st day of the month.

Month Adjust clock: month 1 to 12


EN

Monat
DE

CL2 {0} {1} {2} The current month of the date is set here. Example:
1764    1.................... 1st month of the year.
12.................. 12th month of the year.

Year Adjust clock: year 0 to 99


EN

Jahr
DE

CL2 {0} {1} {2} The current year of the date is set here. Example:
1765    0.................... Year 2000.
99.................. Year 2099.

© Woodward Page 99/141


Manual 37386D DTSC-200 - ATS Controller

System: Versions
The parameters in this section are informational only and cannot be modified.

The control unit may be identified from the numbers located on the unit and in the software. The most important
technical information is located on the unit data plate. Technical data can be located in manual 37385.

1 S/N serial number (numeric)


2 S/N manufactured date (YYMM)
3 S/N serial number (as Barcode)
4 P/N part number
5 REV part number revision
6 Details technical data
7 Type description (long)
8 Type Description (short)
9 UL UL sign

Serial number Version: Serial number (S/N) info


EN

Seriennummer
DE

{0} {1} {2} The serial number (S/N) is utilized to identify individual control units. The number
900    can also be found on the data plate (items #1 & #3).

Boot item number Version: Part number of the firmware (P/N) info
EN

Boot Artikelnummer
DE

{0} {1} {2} The part number (P/N) is the firmware in the control unit.
950   

Boot revision Version: Revision of the item number of the firmware (REV) info
EN

Boot Revision
DE

{0} {1} {2} The revision number (REV) is the revision of the control unit firmware.
960   

Boot version Version: Version of the firmware info


EN

Boot Version
DE

{0} {1} {2} This number (Vx.xxxx) represents the version of the control unit firmware.
965   

Program item number Version: Item number of the application software (P/N) info
EN

Programm Artikelnummer
DE

{0} {1} {2} The part number (P/N) is the application software running the control unit.
930   

Program revision Version: Revision of the item number of the software (REV) info
EN

Programm Revision
DE

{0} {1} {2} The revision number (REV) is the revision of the application software running the
940    control unit.

Program version Version: Version of the application software info


EN

Programm Version
DE

{0} {1} {2} This number (Vx.xxxx) represents the version of the application software running
945    the control unit.

Page 100/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Appendix A.
LogicsManager

The LogicsManager is used to customize the sequence of events in the control unit such as the start command of
the engine or the operation of control unit relay outputs. For example, the start routine may be programmed so
that it requires the closing of a discrete input or a preset time of day. Two independent time delays are provided
for the configured action to take place and be reset. The following table shows the function of each relay in each
of the application modes.

Starting the engine can be carried out externally via a discrete input. With it the LogicsManager is used whose
conditions and programming is defined as follows.

Table 3-11 on page 80 shows the assignment of different functions to various discrete outputs.

© Woodward Page 101/141


Manual 37386D DTSC-200 - ATS Controller

Structure and description of the LogicsManager

Command [C1] Sign [S1]

Command [C2] Sign [S2]

Command [C3] Sign [S3]

Figure 3-29: LogicsManager - function overview

• Command (variable) - A list of over 100 parameters and functions is provided for the command inputs.
Examples of the parameters that may be configured into these commands are Source 1 undervoltage, Start
fail, and Cool down. These command variables are used to control the output function or relay. Refer to
Logical Command Variables starting on page 106 for a complete list of all command variables.
• Sign - The sign field can be used to invert the state of the command or to fix its output to a logical true or
false if the command is not needed. Setting the sign to the NOT state changes the output of the command
variable from true to false or vise versa.
• Operator - A logical device such as AND or OR.
• (Logical) output - The action or control sequence that occurs when all parameters set into the
LogicsManager are met.

[Cx] - Command {x} [Sx] - Sign {x} [Ox] - Operator {x} [Ax] - Output {x}
Value {[Cx]}
The value [Cx] is AND
Logical AND
passed 1:1.
NAND
NOT VALUE {[Cx]} Logical negated AND
The opposite of the
The description and the tables of value [Cx] is passed. OR The description and the tables of
all values, flags, and internal Logical OR all logical outputs, flags, and
functions that are able to functions that are able to
0 [always "0"]
combine via the LogicsManager NOR combine via the LogicsManager
The value [Cx] is ignored and
can be found in the Logical Logical negated OR can be found in the Logical
this logic path
Command Variables section Outputs section starting on
will always be FALSE.
starting on page 106. XOR page 104.
Exclusive OR
1 [always "1"]
The value [Cx] is ignored and NXOR
this logic path Exclusive negated OR
will always be TRUE.
(See Table 3-17 for symbols)

Table 3-16: LogicsManager - command overview

NOTE
A logical output may either be delayed when switching on or switching off. The time starts when all
logical functions of the operation have been met.

Page 102/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Configuration of the chain of commands


Using the values specified in the above table, the chain of commands of the LogicsManager (for example:
operating the relays, setting the flags, specification of the automatic functions) is configured as follows:

[Ax] = ( ( [C1] & [S1] ) & [O1] & ( [C2] & [S2] ) ) & [O2] & ( [C3] & [S3] )

Programming example for the LogicsManager:


Flag 8 shall become TRUE, whenever "Setpoint 1" is TRUE "AND" "Setpoint 2" is "NOT" TRUE "AND" the
"Active week day" is TRUE 

Figure 3-30: LogicsManager - display in LeoPC Figure 3-31: LogicsManager - display in LCD

Logical Symbols
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The following symbols are used for the graphical programming of the LogicsManager.

AND OR NAND NOR NXOR XOR


DTSC 1 1
1
1
1
1
1 1
1 1
1
1 1 1
1
1
1
1
1

1
1

1
1

1
1

1
1
1 1 1 1
1
1
1
1
1 1
1 1
1
1 1 1
1
1
1
1
1

1
1

1
1

1
1

1
1
1 1 1 1
1
1
1
1
1 1
1 1
1
1 1 1
1
1
1
1
1 1
1

1
1
1
1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

DIN 40 700

LeoPC1
ASA
US MIL
IEC617-12
& >=1 & >=1 = =1

Truth x1 x2 y x1 x2 y x1 x2 y x1 x2 y x1 x2 y x1 x2 y
table 0 0 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0
0 1 0 0 1 1 0 1 1 0 1 0 0 1 0 0 1 1
1 0 0 1 0 1 1 0 1 1 0 0 1 0 0 1 0 1
1 1 1 1 1 1 1 1 0 1 1 0 1 1 1 1 1 0
Table 3-17: LogicsManager - logical symbols

© Woodward Page 103/141


Manual 37386D DTSC-200 - ATS Controller

Logical Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The logical outputs or combinations may be grouped into three categories:

• internal logical flags


• Internal functions
• relay outputs

NOTE
The numbers of the logical outputs in the third column may again be used as input variable for other
outputs in the LogicsManager.

Logical Outputs: Internal Flags


8 internal logical flags may be programmed to activate/deactivate functions. This permits more than 3 commands
to be included in a logical function. The may be used like "auxiliary flags".

Name Function Number


Flag 1 Internal flag 1 00.01
Flag 2 Internal flag 2 00.02
Flag 3 Internal flag 3 00.03
Flag 4 Internal flag 4 00.04
Flag 5 Internal flag 5 00.05
Flag 6 Internal flag 6 00.06
Flag 7 Internal flag 7 00.07
Flag 8 Internal flag 8 00.08

Logical Outputs: Internal functions


The following logical functions may be used to activate/deactivate functions.

Name Function Number


External acknowledge The alarm acknowledgement is performed from an external source (refer to 00.15
parameter 12490 on page 51)
Operation mode AUTO Activation of the AUTOMATIC operating mode (always TRUE) 00.16

Page 104/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Logical Outputs: Relay Outputs


All relays may be controlled directly by the LogicsManager depending on the respective application mode.

Name Function Number


Relay 1 If this logical output becomes true, the relay output 1 will be activated 13.01
Relay 2 If this logical output becomes true, the relay output 2 will be activated 13.02
Relay 3 If this logical output becomes true, the relay output 3 will be activated 13.03
Relay 4 If this logical output becomes true, the relay output 4 will be activated 13.04
Relay 5 If this logical output becomes true, the relay output 5 will be activated 13.05
Relay 6 If this logical output becomes true, the relay output 6 will be activated 13.06
Relay 7 If this logical output becomes true, the relay output 7 will be activated 13.07
Relay 8 If this logical output becomes true, the relay output 8 will be activated 13.08
Relay 9 If this logical output becomes true, the relay output 9 will be activated 13.09
External DO 1 If this logical output becomes true, the external relay output 1 will be activated 14.01
External DO 2 If this logical output becomes true, the external relay output 2 will be activated 14.02
External DO 3 If this logical output becomes true, the external relay output 3 will be activated 14.03
External DO 4 If this logical output becomes true, the external relay output 4 will be activated 14.04
External DO 5 If this logical output becomes true, the external relay output 5 will be activated 14.05
External DO 6 If this logical output becomes true, the external relay output 6 will be activated 14.06
External DO 7 If this logical output becomes true, the external relay output 7 will be activated 14.07
External DO 8 If this logical output becomes true, the external relay output 8 will be activated 14.08
External DO 9 If this logical output becomes true, the external relay output 9 will be activated 14.09
External DO 10 If this logical output becomes true, the external relay output 10 will be activated 14.10
External DO 11 If this logical output becomes true, the external relay output 11 will be activated 14.11
External DO 12 If this logical output becomes true, the external relay output 12 will be activated 14.12
External DO 13 If this logical output becomes true, the external relay output 13 will be activated 14.13
External DO 14 If this logical output becomes true, the external relay output 14 will be activated 14.14
External DO 15 If this logical output becomes true, the external relay output 15 will be activated 14.15
External DO 16 If this logical output becomes true, the external relay output 16 will be activated 14.16

© Woodward Page 105/141


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The logical command variables are grouped into 14 categories:

• [00.00] Internal flags


• [01.00] Alarm classes
• [03.00] Engine control
• [04.00] Operating status
• [05.00] Alarms of the engine
• [08.00] Alarms of the system
• [09.00] Discrete inputs
• [11.00] Time functions
• [12.00] External discrete inputs
• [13.00] Status of the internal relay outputs
• [14.00] Status of the external relay outputs
• [19.00] ATS status flags
• [20.00] ATS status flags

Logical Command Variables: [00.00] - Internal Flags


Internal flag, Logic command variables 00.01-00.20
Internal Flags are the result of the output of the logic ladders from Flag 1 to 8. Flags are internal logic that can be
sent to other flags or Command variables.

No. Name Function Note


00.01 Flag 1 Internal flag 1 Internal calculation; 106escry.
Page 104
00.02 Flag 2 Internal flag 2 Internal calculation; 106escry.
Page 104
00.03 Flag 3 Internal flag 3 Internal calculation; 106escry.
Page 104
00.04 Flag 4 Internal flag 4 Internal calculation; 106escry.
Page 104
00.05 Flag 5 Internal flag 5 Internal calculation; 106escry.
Page 104
00.06 Flag 6 Internal flag 6 Internal calculation; 106escry.
Page 104
00.07 Flag 7 Internal flag 7 Internal calculation; 106escry.
Page 104
00.08 Flag 8 Internal flag 8 Internal calculation; 106escry.
Page 104
00.09 - - not used
00.10 - - not used
00.11 - - not used
00.12 - - not used
00.13 - - not used
00.14 - - not used
00.15 External acknowledge The alarm acknowledgement is performed from Internal calculation; 106escry.
an external source Page 51
00.16 Operation mode AUTO Activation of the AUTOMATIC operating mode always TRUE
00.18 - - not used
00.19 - - not used
00.20 - - not used

Page 106/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables: [01.00] - Alarm Classes


Alarm class commands, Logic command variables 01.01-01.10
Alarm classes may be configured as command variables for all logical outputs in the LogicsManager.

Number Name / Function Note


- - not used
- - not used
- - not used
- - not used
- - not used
- - not used
- - not used
- - not used
- - not used
01.10 Centralized alarm TRUE as long as at least one of the alarm classes B/C/D/E/F is active

Logical Command Variables: [03.00] - Engine Control


Engine control commands, Logic command variables 03.01-03.14
These variables may be used as command variable in a logical output to set parameters for customized
operations.

Number Name / Function Note


03.01 - not used
03.02 - not used
03.03 - not used
03.04 - not used
03.05 Horn (active) TRUE if alarm class B to F is activated until
the time until horn reset is expired or it is
acknowledged for the first time.
03.06 - not used
03.07 - not used
03.08 - not used
03.09 - not used
03.10 - not used
03.11 - not used
03.12 - not used
03.13 - not used
03.14 - not used
03.15 - not used
03.16 - not used
03.17 - not used
03.18 - not used
03.19 - not used
03.20 - not used

© Woodward Page 107/141


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables: [04.00] - Operating Status


Operating status commands, 4.01-04.15
These operating statuses may be used as command variable in a logical output to set parameters for customized
operations.

No. Name Function Note


04.01 Auto mode AUTOMATIC operating mode active
04.02 - - not used
04.03 Manual mode MANUAL operating mode active
04.04 Lamp test A lamp test is being performed TRUE if the lamp test is active
04.05 Acknowledge "Acknowledge" push button has been pressed Note: this condition is TRUE for approx.
or an external acknowledgment via 40 ms and must be extended utilizing a delay
LogicsManager time
04.06 - - not used
04.07 - - not used
04.08 - - not used
04.09 - - not used
04.10 - - not used
04.11 - - not used
04.12 - - not used
04.13 - - not used
04.14 Remote Request over remote control to acknowledge TRUE if the acknowledgement bit is set
acknowledge
04.15 - - not used
04.16 - - not used
04.17 - - not used
04.18 - - not used
04.19 - - not used
04.20 - - not used

Logical Command Variables: [06.00] - Alarms of the Load


Load alarm status commands, 06.01-06.15
These engine alarms may be used as command variable in a logical output to set parameters for customized
operations.

Number Name / Function Note


06.01 - not used
06.02 - not used
06.03 - not used
06.04 - not used
06.05 - not used
06.06 - not used
06.07 - not used
06.08 - not used
06.09 Overcurrent 1
06.10 Overcurrent 2
06.11 Overcurrent 3
06.12 - not used
06.13 - not used
06.14 Overload 1
06.15 Overload 2
06.16 - not used
06.17 - not used
06.18 - not used
06.19 - not used
06.20 - not used

Page 108/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables: [08.00] - Alarms of the System


System alarms status commands, 08.01-08.10
These system alarms may be used as command variable in a logical output n to set parameters for customized
operations.

Number Function Note


08.01 Battery overvoltage (limit) 1
08.02 Battery overvoltage (limit) 2
08.03 Battery undervoltage (limit) 1
08.04 Battery undervoltage (limit) 2
TRUE = limit value reached
08.05 -
FALSE = alarm acknowledged
08.06 -
08.07 -
08.08 -
08.09 CANopen fault
08.10 - not used
08.11 - not used
08.12 - not used
08.13 - not used
08.14 - not used
08.15 - not used
08.16 - not used
08.17 - not used
08.18 - not used
08.19 - not used
08.20 - not used

Logical Command Variables: [09.00] - Discrete Inputs


Control discrete input commands, 09.01-09.08
The discrete inputs may be used as command variable in a logical output to set parameters for customized
operations.

Number Function Note


09.01 DI 1 (Discrete input [D1])
09.02 DI 2 (Discrete input [D2])
09.03 DI 3 (Discrete input [D3])
09.04 DI 4 (Discrete input [D4]) TRUE = logical "1" (delay times and NO/NC
09.05 DI 5 (Discrete input [D5]) parameters are ignored)
09.06 DI 6 (Discrete input [D6]) FALSE = logical "0" (alarm has been
09.07 DI 7 (Discrete input [D7]) acknowledged or immediately after TRUE
09.08 DI 8 (Discrete input [D8]) condition is not present anymore, if Control is
09.09 DI 9 (Discrete input [D9]) configured as alarm class)
09.10 DI 10 (Discrete input [D10])
09.11 DI 11 (Discrete input [D11])
09.12 DI 12 (Discrete input [D12])
09.13 - not used
09.14 - not used
09.15 - not used
09.16 - not used
09.17 - not used
09.18 - not used
09.19 - not used
09.20 - not used

© Woodward Page 109/141


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables: [11.00] - Time Functions


Time function commands, 11.01-11.10
Time functions may be used as command variable in a logical output.

Number Name / Function Note


11.01 Set point 1 (exceeded) see page 84
11.02 Set point 2 (exceeded) see page 84
11.03 Active weekday (equal to setting) see page 84
11.04 Active day (equal to setting) see page 84
11.05 Active hour (equal to setting) see page 84
11.06 Active minute (equal to setting) see page 84
11.07 Active second (equal to setting) see page 84
11.08 - not used
11.09 - not used
11.10 - not used
11.11 - not used
11.12 - not used
11.13 - not used
11.14 - not used
11.15 - not used
11.16 - not used
11.17 - not used
11.18 - not used
11.19 - not used
11.20 - not used

Logical Command Variables: [12.00] - External Discrete Inputs (Expansion


Board)
External discrete input commands, 12.01-12.16
Additional discrete inputs from an expansion board (i.e. IKD 1 extension board) may be used as command
variable in a logical output.

Number Name / Function Note


12.01 External discrete input 1 [D.E01]
12.02 External discrete input 2 [D.E02]
12.03 External discrete input 3 [D.E03]
12.04 External discrete input 4 [D.E04]
12.05 External discrete input 5 [D.E05]
12.06 External discrete input 6 [D.E06] TRUE = logical "1" (delay times and NO/NC
12.07 External discrete input 7 [D.E07] parameters are ignored)
12.08 External discrete input 8 [D.E08] FALSE = logical "0" (alarm has been
12.09 External discrete input 9 [D.E09] acknowledged, or immediately after TRUE
12.10 External discrete input 10 [D.E10] condition is not present anymore, if Control is
12.11 External discrete input 11 [D.E11] configured as alarm class)
12.12 External discrete input 12 [D.E12]
12.13 External discrete input 13 [D.E13]
12.14 External discrete input 14 [D.E14]
12.15 External discrete input 15 [D.E15]
12.16 External discrete input 16 [D.E16]
12.17 - not used
12.18 - not used
12.19 - not used
12.20 - not used

Page 110/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables: [13.00] - Status Of The Internal Relay Outputs


Discrete output commands, 13.01-13.08
The discrete outputs may be used as command variable in a logical output.

Number Name / Function Note


13.01 Digital output DO1 [R01]
13.02 Digital output DO2 [R02]
13.03 Digital output DO3 [R03]
TRUE = logical "1" (this condition indicates
13.04 Digital output DO4 [R04]
the logical status of the internal relays)
13.05 Digital output DO5 [R05]
FALSE = logical "0" (this condition indicates
13.06 Digital output DO6 [R06]
the logical status of the internal relays)
13.07 Digital output DO7 [R07]
13.08 Digital output DO8 [R08]
13.09 Digital output DO9 [R09]
13.10 - not used
13.11 - not used
13.12 - not used
13.13 - not used
13.14 - not used
13.15 - not used
13.16 - not used
13.17 - not used
13.18 - not used
13.19 - not used
13.20 - not used

Logical Command Variables: [14.00] - Status Of The External Relay Outputs


Discrete output commands, 14.01-14.16
The external discrete outputs may be used as command variable in a logical output.

Number Name / Function Note


14.01 External digital output DO1 [R01]
14.02 External digital output DO2 [R02]
14.03 External digital output DO3 [R03]
14.04 External digital output DO4 [R04]
14.05 External digital output DO5 [R05]
14.06 External digital output DO6 [R06] TRUE = logical "1" (this condition indicates
14.07 External digital output DO7 [R07] the logical status of the relays, which are
14.08 External digital output DO8 [R08] connected via external expansion boards)
14.09 External digital output DO9 [R09] FALSE = logical "0" (this condition indicates
14.10 External digital output DO10 [R10] the logical status of the relays, which are
14.11 External digital output DO11 [R11] connected via external expansion boards)
14.12 External digital output DO12 [R12]
14.13 External digital output DO13 [R13]
14.14 External digital output DO14 [R14]
14.15 External digital output DO15 [R15]
14.16 External digital output DO16 [R16]
14.17 - not used
14.18 - not used
14.19 - not used
14.20 - not used

© Woodward Page 111/141


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables: [19.00] - ATS Status Flags


ATS status flags, 19.01-19.20
The external discrete outputs may be used as command variable in a logical output.

No. Name / Function Note


19.01 Source 1 OK (voltage and frequency are in range)
19.02 Source 1 voltage OK (in range)
19.03 Source 1 overvoltage (“fail” level exceeded)
19.04 Source 1 undervoltage (“fail” level exceeded)
19.05 Source 1 frequency OK (in range)
19.06 Source 1 overfrequency (“fail” level exceeded)
19.07 Source 1 underfrequency (“fail” level exceeded)
19.08 Source 1 voltage imbalance (“fail” level exceeded)
19.09 Source 1 rotation (field =) CCW
19.10 Source 1 rotation (field =) CW
19.11 Source 2 OK (voltage and frequency are in range)
19.12 Source 2 voltage OK (in range)
19.13 Source 2 overvoltage (“fail” level exceeded)
19.14 Source 2 undervoltage (“fail” level exceeded)
19.15 Source 2 frequency OK (in range)
19.16 Source 2 overfrequency (“fail” level exceeded)
19.17 Source 2 underfrequency (“fail” level exceeded)
19.18 Source 2 voltage imbalance (“fail” level exceeded)
19.19 Source 2 rotation (field =) CCW
19.20 Source 2 rotation (field =) CW

Logical Command Variables: [20.00] - ATS Status Flags


ATS status flags, 20.01-20.21
The external discrete outputs may be used as command variable in a logical output.

No. Name / Function Note


20.01 Status Flag: Elevator Pre Signal (is active)
20.02 Status Flag: Motor Load Disconnect (signal is active)
20.03 Status Flag: Load Test (is) active
20.04 Status Flag: No Load Test (is) active
20.05 Status Flag: S1 start signal
20.06 Status Flag: S2 start signal
20.07 Command: Close to S1
20.08 Command: Open from S1
20.09 Command: Close to S2
20.10 Command: Open from S2
20.11 Status Flag: Load shed (is active)
20.12 Status Flag: Shunt trip enable (is active)
20.13 Status Flag: S1 closed TRUE if S1 is closed and S2 is open
20.14 Status Flag: S2 closed TRUE if S2 is closed and S1 is open
20.15 Status Flag: S1 and S2 open
20.16 Status Flag: S1 and S2 closed
20.17 Status Flag: S1 is stabling (at the moment)
20.18 Status Flag: S2 is stabling (at the moment)
20.19 - not used
20.20 - not used
20.21 - not used
20.22 Sync Check active This flag is set as soon as the DTSC-200 starts to do
In-phase checking, and resets after the In-Phase
transfer to the other source has been accomplished.

Page 112/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Logical Command Variables: [21.00] - ATS Alarms


ATS alarms, 21.01-21.20
The external discrete outputs may be used as command variable in a logical output.

No. Name / Function Note


21.01 Engine Alarm: Start fail S1
21.02 Engine Alarm: Start fail S2
21.03 Engine Alarm: Unintended Stop S1
21.04 Engine Alarm: Unintended Stop S2
21.05 Alarm: S1 phase rotation mismatch (failure present)
21.06 Alarm: S2 phase rotation mismatch (failure present)
21.07 Switch alarm: Fail to open (from switch position) S1
21.08 Switch alarm: Fail to open (from switch position) S2
21.09 Switch alarm: Fail to close (to switch position) S1
21.10 Switch alarm: Fail to close (to switch position) S2
21.11 Switch alarm: Mechanical fail (not plausible limit switch
feedbacks have been detected by the DTSC-200)
21.12 In-Phase monitor alarm: In-phase timeout (the system was not
able to establish a "Sync" situation within the configured time)
21.13 Switch alarm: Overlap timeout (the contacts have been in a
"parallel" position for longer than the configured time)
21.14 - not used
21.15 - not used
21.16 - not used
21.17 - not used
21.18 - not used
21.19 - not used
21.20 - not used

Logical Command Variables: [98.00] - LogicsManager Outputs


LogicsManager outputs, 98.01-98.20
The external discrete outputs may be used as command variable in a logical output.

No. Name / Function Note


98.01 LogicsManager "Inhibit ATS" is TRUE
98.02 LogicsManager "Inhibit transfer to S1" is TRUE
98.03 LogicsManager "Inhibit transfer to S2" is TRUE
98.04 LogicsManager "Remote peak shave" is TRUE
98.05 LogicsManager "Interruptible power rate provisions" is TRUE
98.06 LogicsManager "Gen-Gen enable" is TRUE
98.07 LogicsManager "Delayed mode activation" is TRUE
98.08 LogicsManager "Extended parallel time" is TRUE
98.09 LogicsManager "Load Test" is TRUE
98.10 LogicsManager "No Load Test" is TRUE
98.11 LogicsManager "Source 1 priority" is TRUE
98.12 LogicsManager "Source 2 priority" is TRUE
98.13 LogicsManager "External bypass" is TRUE
98.14 LogicsManager "Load shed" is TRUE
98.15 - not used
98.16 - not used
98.17 - not used
98.18 - not used
98.19 - not used
98.20 - not used

© Woodward Page 113/141


Manual 37386D DTSC-200 - ATS Controller

Factory Setting
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The inputs, outputs, and internal flags, which may be programmed via the LogicsManager have the following
factory default settings when delivered:

simple (function) extended (configuration) result

Factory Setting: Functions

Inhibit ATS
(parameter 12600 on page 29)
{0}  If TRUE, the unit is blocked against
{1}  automatic transfers.
{2} 
TRUE, if DI 5 is NOT energized

dependent
on DI 5

Inhibit XFR to Source 1


(parameter 12610 on page 30)
{0}  If TRUE, the unit is blocked against a
{1}  transfer to source 1.
{2} 
Prepared for: -
Deactivated by default
FALSE

Inhibit XFR to Source 2


(parameter 12620 on page 30)
{0}  If TRUE, the unit is blocked against a
{1}  transfer to source 2.
{2} 
Prepared for: -
Deactivated by default
FALSE

Page 114/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

simple (function) extended (configuration) result

Remote peak shave


(parameter 12630 on page 30)
{0}  If TRUE, the remote peak shave
{1}  function will be performed.
{2} 
Prepared for: -
Deactivated by default
FALSE

Interruptible power rates


(parameter 12660 on page 31)
{0}  If TRUE, the interruptible power rate
{1}  provision function will be performed.
{2} 
Prepared for: -
Deactivated by default
FALSE

External timer bypass


(parameter 12820 on page 31)
{0}  If TRUE, all timers, which are
{1}  currently in progress, will be
{2}  bypassed.

Prepared for: -
Deactivated by default FALSE

Gen-Gen enable
(parameter 12830 on page 32)
{0} --- If TRUE, the gen-gen mode will be
{1} --- enabled.
{2} 
Prepared for: -
Deactivated by default
FALSE

© Woodward Page 115/141


Manual 37386D DTSC-200 - ATS Controller

simple (function) extended (configuration) result

Source 1 priority
(parameter 12680 on page 36)
{0}  If TRUE, source 1 is preferred.
{1} 
{2}  Prepared for: -
Activated by default

TRUE

Source 2 priority
(parameter 12810 on page 36)
{0}  If TRUE, source 2 is preferred.
{1} 
{2}  Prepared for: -
Deactivated by default

FALSE

Extended parallel time


(parameter 12860 on page 38)
{0}  If TRUE, the transfer switch remains
{1} --- in overlap position.
{2} 
Prepared for: -
Deactivated by default
FALSE

Load shed
(parameter 12870 on page 40)
{0}  If TRUE, a load shed from the non-
{1} --- preferred source will be performed.
{2} 
Prepared for: -
Deactivated by default
FALSE

Page 116/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

simple (function) extended (configuration) result

Delayed mode active


(parameter 12850 on page 45)
{0}  If TRUE, the transfer switch type will
{1}  be set to Delayed.
{2} 
Prepared for: -
Deactivated by default
FALSE

Load test
(parameter 12640 on page 50)
{0}  If TRUE, a load test will be
{1}  performed.
{2} 
Prepared for: -
Deactivated by default
FALSE

No load test
(parameter 12650 on page 50)
{0}  If TRUE, a no-load test will be
{1}  performed.
{2} 
Prepared for: -
Deactivated by default
FALSE

© Woodward Page 117/141


Manual 37386D DTSC-200 - ATS Controller

simple (function) extended (configuration) result

External acknowledge
(parameter 12490 on page 51)
{0}  If TRUE, alarms are acknowledged
{1}  from an external source.
{2} 
Prepared for: -
Remote acknowledgement
FALSE

Page 118/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

simple (function) extended (configuration) result

Factory Setting: Relay Outputs

Relay {x} [R0x]; {x} = 1 to 4


(parameters 12100, 12110, 12310, and 12320 on page 81)
{0}  If TRUE, relay 1 will be energized.
{1} 
{2}  Prepared for: -
Deactivated by default

FALSE

Relay 5 [R05]
(parameter 12130 on page 81)
{0}  If TRUE, relay 5 will be energized.
{1} 
{2}  True, if the Source 2 start signal is
issued dependent
on Logics
Command
Variable
[20.06]

Relay 6 [R06]
(parameter 12140 on page 81)
{0}  If TRUE, relay 6 will be energized.
{1} 
{2}  True, if the command: Close to
Source 1 is issued dependent
on Logics
Command
Variable
[20.07]

Relay 7 [R07]
(parameter 12150 on page 81)
{0}  If TRUE, relay 7 will be energized.
{1} 
{2}  True, if the command: Close to
Source 2 is issued dependent
on Logics
Command
Variable
[20.09]

© Woodward Page 119/141


Manual 37386D DTSC-200 - ATS Controller

simple (function) extended (configuration) result

Relay 8 [R08]
(parameter 12160 on page 81)
{0}  If TRUE, relay 8 will be energized.
{1} 
{2}  True, if the command: Open from
Source 1 is issued dependent
on Logics
Command
Variable
[20.08]

Relay 9 [R09]
(parameter 12170 on page 81)
{0}  If TRUE, relay 9 will be energized.
{1} 
{2}  True, if the command: Open from
Source 2 is issued dependent
on Logics
Command
Variable
[20.10]

External digital output {x] [REx{x}] - free (external expansion card, if connected; {x} = 1-16)
(refer to Table 3-13 on page 81 for the parameter IDs of the parameters for external DOs 1 through 16)
{0}  If TRUE, the external relay {x} will
{1}  be energized, if this is connected
{2} 
Prepared for: -
Deactivated by default
FALSE

Page 120/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

simple (function) extended (configuration) result

Factory Setting: Internal Flags

Internal flag {x}; {x} = 1 to 7


(refer to Table 3-14 on page 83 for the parameter IDs of the parameters for internal flags 1 through 7)
{0}  If TRUE, the internal flag {x} will be
{1}  enabled.
{2} 
Prepared for: -
Deactivated by default
FALSE
Note:
Internal flag 1 is used as default
setting in all logical outputs.

Internal flag 8
(parameter 12300 on page 83)
{0}  If TRUE, the internal flag 8 will be
{1}  enabled.
{2}  dependent
TRUE, once the configured time 1 has on Logics
been reached [11.01], and the Command
configured time 2 [11.02] has not Variables
been reached as well, if the current [11.01],
day is the configured day [11.03] [11.02], and
[11.03]

© Woodward Page 121/141


Manual 37386D DTSC-200 - ATS Controller

Discrete Inputs

[D1] {0}
{1} Reply from ATS switch: Breaker in source 1 position
{2}

[D2] {0}
{1} Reply from ATS switch: Breaker in source 2 position
{2}

[D3] {0}
{1} Reply from ATS switch: Breaker in source 1 open position
{2}

[D4] {0}
{1} Reply from ATS switch: Breaker in source 2 open position
{2}

[D5] {0}
{1} freely configurable discrete input (pre-configured to Inhibit ATS)
{2}

[D6] {0}
{1} freely configurable discrete input (unassigned)
{2}

[D7] {0}
{1} freely configurable discrete input (unassigned)
{2}

[D8] {0}
{1} freely configurable discrete input (unassigned)
{2}

[D9] {0}
{1} freely configurable discrete input (unassigned)
{2}

[D10] {0}
{1} freely configurable discrete input (unassigned)
{2}

[D11] {0}
{1} freely configurable discrete input (unassigned)
{2}

[D12] {0}
{1} freely configurable discrete input (unassigned)
{2}

NOTE
The discrete inputs for the breaker position reply messages (DIs 1 through 4) are fixed to N.C. and are
evaluated as N.C., i.e. the breaker is considered as "in position" if the respective DI is de-energized.

Page 122/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Appendix B.
GetEventLog

The event logger is a 300-entry FIFO (First In/First Out) memory for logging alarm events and operation states of
the unit. Refer to the Event History section on page 17 for more info about the event logger.

It is possible to read out the event logger using the direct configuration cable DPC and the GetEventLog software
tool.

GetEventLog Software
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Installing GetEventLog
GetEventLog can either be used as a stand alone or within LeoPC1. In order to call it up from LeoPC1, it must be
installed into the LeoPC1 installation path.

To install GetEventLog, start GetEventLog_vxxxxx.exe from the GetEventLog directory on the CD delivered
with the unit.
If you want to use GetEventLog from inside LeoPC1, it must be installed into the LeoPC1 installation directory.

Starting GetEventLog
Connect the DTSC to a free COM port on your computer using the DPC as described under Configuration Using
The PC on page 10.
Start GetEventLog directly or call it up by selecting GetEventLog from the menu Tools in LeoPC1.
After starting GetEventLog for the first time, you must configure the communication settings. To do this, select
the Interface tab, configure the COM port according to the port, to which you have connected the DPC, and enter
the other settings as represented in figure Figure 3-32 since these are the default settings of the DTSC.

Figure 3-32: GetEventLog - interface configuration

© Woodward Page 123/141


Manual 37386D DTSC-200 - ATS Controller

Reading Out GetEventLog


On the Eventlog tab of GetEventLog, click the Request Eventlog button to read out the content of the event
logger memory. The content of the event logger is displayed as shown in Figure 3-33.

Figure 3-33: GetEventLog - event logger content

The 300 latest events are displayed in chronological order and each entry is composed like this:

"sign";"event date and time";"event no.";"event text"

whereas the "sign" "+" indicates the occurrence and "-" indicates the disappearance or acknowledgement of
the alarm or state
"event date and time" serves as a timestamp and indicates the date and time of the event
occurred
"event no." indicates the event number that occurred
"event text" indicates the event that occurred in clear text

The event text is read out in the language, which is selected in the DTSC, like English or French. Some languages
may not be supported by LeoPC1, like Japanese or Chinese. Then you may change the language in the unit.
The event numbers are indicated in Table 3-18 at the end of this section. Please note that some event texts may be
configured freely (like analog inputs, etc.) and may not correspond with the original text. The event numbers are
unambiguous.

Example: The entry "+";"2005-June-15 13:23:05.69";"014710";"S1 underfrequency"


means that an Source 1 underfrequency condition "014710" occurred "+" at June 15, 2005 at 23 minutes, 5
seconds and 69 hundredths of a second after 1 o'clock in the afternoon "2005-June-15 13:23:05.69".

Storing Event Logger Data


Using the Save Eventlog button on the Eventlog tab, you are able to save the content of the event logger in
CSV format (comma separated values). You may open the saved file within Excel for example.

Figure 3-34: GetEventLog - event logger content in Excel

Page 124/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Resetting the Event Logger


The event logger can be reset using the parameter "Clear event log" via the front panel or LeoPC1 (deleted events
or empty entries are represented with a series of dashes in the event logger). To do this, perform the following
steps:

Resetting the Event Logger Using the Front Panel


Make sure that you are in code level CL2 (refer to the Password section on page 16).
Set the parameter "Clear event log" to YES (refer to the Event History section on page 17).
The complete event logger is now being cleared (single events may be cleared by pressing the button).

Resetting the Event Logger Using LeoPC1


Connect the DTSC with your PC and start LeoPC1 as described in Configuration Using The PC on page 10.
Set the parameter "Clear event log" to YES (refer to the Event History section on page 17).
The complete event logger is now being cleared.

Event Texts and Numbers

Event no. Event text Description


12680 S1 Priority Source 1 has priority
12810 S2 Priority Source 1 has priority
12820 Ext. bypass External bypass enabled
12830 Gen-Gen enable Gen-2-Gen mode enabled
12850 Delayed mode act. Delayed transition mode enabled
12860 Ext. para. time Extended parallel time enabled
12870 Load shed Load shed from non-preferred source requested
13226 Pre Signal timer Elevator pre-signal active
13227 Wait S1 to open Open transfer switch from S1 position
13228 Wait S2 to open Open transfer switch from S2 position
13229 Wait S1 to close Close transfer switch to S1 position
13230 Wait S2 to close Close transfer switch to S2 position
14353 Auto mode Auto mode is active
14418 Load test Load test active
14419 No load test No Load test active
14434 Rem. peak shave Remote peak shave active
14435 Motor Load Disc. Motor load disconnect signal active
14439 Inhib. XFR to S1 Inhibit transfer to Source 1
14440 Inhib. XFR to S2 Inhibit transfer to Source 2
14442 Pwr. rate. prov. Interruptible power rates active
14443 ATS inhibit ATS inhibit
14708 S1 undervoltage Source 1 undervoltage
14709 S1 overvoltage Source 1 overvoltage
14710 S1 underfrequency Source 1 underfrequency
14711 S1 overfrequency Source 1 overfrequency
14712 S1 voltage imbalance Source 1 voltage imbalance
14713 S2 undervoltage Source 2 undervoltage
14714 S2 overvoltage Source 2 overvoltage
14715 S2 underfrequency Source 2 underfrequency
14716 S2 overfrequency Source 2 overfrequency
14717 S2 voltage imbalance Source 2 voltage imbalance
Table 3-18: Event logger - event texts and numbers

© Woodward Page 125/141


Manual 37386D DTSC-200 - ATS Controller

Appendix C.
List Of Parameters

Unit number P/N _____________________________ Rev _______________________________

Version DTSC- ________________________________________________________________

Project ______________________________________________________________________

Serial number S/N _______________ Date ______________________________

Par.
Parameter Setting range Default value Customer setting Data type
ID.

MAIN MENU
1700 Language English / Deutsch English UNSIGNED 16
10416 Password 0000 to 9999 --- UNSIGNED 16

EVENT LOG
1706 Clear event log YES / NO NO Y N Y N UNSIGNED 16

MEASUREMENT
1750 Rated system frequency 50/60 Hz 50 Hz UNSIGNED 16
1774 Rated voltage S1 50 to 650000 V 400 V UNSIGNED 32
1772 Rated voltage S2 50 to 650000 V 400 V UNSIGNED 32
3Ph 4W  3Ph4W  3Ph4W
3Ph 3W  3Ph3W  3Ph3W
1862 S1 voltage measuring 3Ph 4W UNSIGNED 16
1Ph 2W  1Ph2W  1Ph2W
1Ph 3W  1Ph3W  1Ph3W
3Ph 4W  3Ph4W  3Ph4W
3Ph 3W  3Ph3W  3Ph3W
1861 S2 voltage measuring 3Ph 4W UNSIGNED 16
1Ph 2W  1Ph2W  1Ph2W
1Ph 3W  1Ph3W  1Ph3W
Phase - N  p-n  p-n
1858 1Ph2W voltage measuring Ph - Ph UNSIGNED 16
Ph - Ph  p-p  p-p
 CW  CW
1859 1Ph2W phase rotation CW / CCW CW UNSIGNED 16
 CCW  CCW
L1 L2 L3  L123  L123
Phase L1  Ph.L1  Ph.L1
1863 S1 Load current measuring L1 L2 L3 UNSIGNED 16
Phase L2  Ph.L2  Ph.L2
Phase L3  Ph.L3  Ph.L3
L1 L2 L3  L123  L123
Phase L1  Ph.L1  Ph.L1
1860 S2 Load current measuring L1 L2 L3 UNSIGNED 16
Phase L2  Ph.L2  Ph.L2
Phase L3  Ph.L3  Ph.L3
1752 Rated active power [kW] 0.5 to 99999.9 kW 200.0 kW UNSIGNED 32
1754 Rated current 5 to 32000 A 300 A UNSIGNED 16
Transformer
1819 S1 voltage transf. primary 50 to 650000 V 400 V UNSIGNED 32
1818 S1 voltage transf. secondary 50 to 480 V 400 V UNSIGNED 16
1816 S2 voltage transf. primary 50 to 650000 V 400 V UNSIGNED 32
1815 S2 voltage transf. secondary 50 to 480 V 400 V UNSIGNED 16
1821 Load current transformer 1 to 32000/5 A 500/5 A UNSIGNED 16
1822 Load current transformer 1 to 32000/1 A 500/1 A UNSIGNED 16

Page 126/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

APPLICATION
Util-Gen  Util-Gen  Util-Gen
4148 Application mode Gen-Gen Util-Gen  Gen-Gen  Gen-Gen UNSIGNED 16
Util-Util  Util-Util  Util-Util
4146 Transfer Commit YES / NO NO Y N Y N UNSIGNED 16
4149 S1 start delay time 1 to 300 s 10 s UNSIGNED 16
3330 S2 start delay time 1 to 300 s 10 s UNSIGNED 16
3333 S1 source stable time 1 to 6500 s 10 s UNSIGNED 16
3332 S2 source stable time 1 to 6500 s 10 s UNSIGNED 16
2804 S1 outage delay 0.1 to 10.0 s 1.0 s UNSIGNED 16
2803 S2 outage delay 0.1 to 10.0 s 1.0 s UNSIGNED 16
3343 S1 cooldown time 1 to 6500 s 20 s UNSIGNED 16
3344 S2 cooldown time 1 to 6500 s 20 s UNSIGNED 16
12600 Inhibit ATS see descr. in LogicsManager chap. starting p. 114; default: (!09.05 & 1) & 1 Logman
12610 Inhib. XFR to S1 see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12620 Inhib. XFR to S2 see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12630 Remote peak shave see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12660 Int. pow. rates see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12820 Ext. bypass see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12830 Gen-Gen enable see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
Elevator Pre Signal
4490 Elevator Pre signal ON / OFF OFF 1 0 1 0 UNSIGNED 16
4491 Elevator pre-signal duration 1 to 6500 s 5s UNSIGNED 16
Motor Load Disconnect
4550 Motor Load Disconnect ON / OFF OFF 1 0 1 0 UNSIGNED 16
S1->S2  S1->S2  S1->S2
4553 Active direction S2->S1 S1->S2  S2->S1  S2->S1 UNSIGNED 16
Both  Both  Both
4551 Disconnect time S1->S2 1 to 6500 s 5s UNSIGNED 16
4552 Disconnect time S2->S1 1 to 6500 s 5s UNSIGNED 16
Source Priority
12680 S1 Priority see descr. in LogicsManager chap. starting page 114; default: (1 & 1) & 1 Logman
12810 S2 Priority see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12860 Ext. para.time see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12870 Load shed see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman

BREAKER
Standard  Standard  Standard
3424 Transfer switch type Delayed Standard  Delayed  Delayed UNSIGNED 16
Closet  Closed  Closed
3434 Use limit sw. OPEN replies YES / NO YES Y N Y N UNSIGNED 16
12850 Delayed mode act. see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
3426 Neutral time S2->S1 0 to 6500 s 3s UNSIGNED 16
3425 Neutral time S1->S2 0 to 6500 s 3s UNSIGNED 16
3428 Limit switch reply timeout 0.1 to 99.9 s 1.0 s UNSIGNED 16
3429 Wait time until next XFR attempt 0.1 to 99.9 s 3.0 s UNSIGNED 16
3427 Max. of Transfer attempts 1 to 10 2 UNSIGNED 16

TESTMODES
12640 Load Test see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman
12650 No Load Test see descr. in LogicsManager chap. starting page 114; default: (0 & 1) & 1 Logman

© Woodward Page 127/141


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

MONITORING
1756 Time until horn reset 0 to 1000 s 180 s UNSIGNED 16
12490 External acknowledge see descr. in LogicsManager chap. starting page 114; default: (0 & 0)+ 0 Logman
3430 Limit switch monitoring ON / OFF OFF 1 0 1 0 UNSIGNED 16
S1 Monitoring
1787 Voltage monitoring S1 Ph – Ph/ Phase - N Ph - Ph 3 4 3 4 UNSIGNED 16
4450 S1 undervoltage restore 50.0 to 125.0 % 90.0 % UNSIGNED 16
4451 S1 undervoltage fail 50.0 to 125.0 % 80.0 % UNSIGNED 16
4452 S1 underfrequency monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4453 S1 underfrequency restore 50.0 to 130.0 % 95.0 % UNSIGNED 16
4454 S1 underfrequency fail 50.0 to 130.0 % 90.0 % UNSIGNED 16
4455 S1 overvoltage monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4456 S1 overvoltage restore 50.0 to 125.0 % 105.0 % UNSIGNED 16
4457 S1 overvoltage fail 50.0 to 125.0 % 110.0 % UNSIGNED 16
4458 S1 overfrequency monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4459 S1 overfrequency restore 50.0 to 130.0 % 102.0 % UNSIGNED 16
4460 S1 overfrequency fail 50.0 to 130.0 % 105.0 % UNSIGNED 16
4461 S1 voltage imbalance monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4462 S1 volt. imbalance restore 0.5 to 99.9 % 8.0 % UNSIGNED 16
4463 S1 volt. imbalance fail 0.5 to 99.9 % 10.0 % UNSIGNED v
3914 Delay 0.02 to 99.99 s 5.00 s UNSIGNED 16
4562 S1 phase rotation ON / OFF ON 1 0 1 0 UNSIGNED 16
CW  CW  CW
4563 S1 phase rotation CW UNSIGNED 16
CCW  CCW  CCW
S2 Monitoring
1786 Voltage monitoring S2 Ph - Ph/ Phase - N Ph - Ph 3 4 3 4 UNSIGNED 16
4465 S2 undervoltage restore 50.0 to 125.0 % 90.0 % UNSIGNED 16
4466 S2 undervoltage fail 50.0 to 125.0 % 80.0 % UNSIGNED 16
4467 S2 underfrequency monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4468 S2 underfrequency restore 50.0 to 130.0 % 95.0 % UNSIGNED 16
4469 S2 underfrequency fail 50.0 to 130.0 % 90.0 % UNSIGNED 16
4470 S2 overvoltage monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4471 S2 overvoltage restore 50.0 to 125.0 % 105.0 % UNSIGNED 16
4472 S2 overvoltage fail 50.0 to 125.0 % 110.0 % UNSIGNED 16
4473 S2 overfrequency monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4474 S2 overfrequency restore 50.0 to 130.0 % 102.0 % UNSIGNED 16
4475 S2 overfrequency fail 50.0 to 130.0 % 105.0 % UNSIGNED 16
4476 S2 voltage imbalance monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
4477 S2 volt. imbalance restore 0.5 to 99.9 % 8.0 % UNSIGNED 16
4478 S2 volt. imbalance fail 0.5 to 99.9 % 10.0 % UNSIGNED 16
3904 Delay 0.02 to 99.99 s 5.00 s UNSIGNED 16
4566 S2 phase rotation ON / OFF ON 1 0 1 0 UNSIGNED 16
CW  CW  CW
4567 S2 phase rotation CW UNSIGNED 16
CCW  CCW  CCW
In-Phase Monitoring
4570 In-Phase monitor ON / OFF ON 1 0 1 0 UNSIGNED 16
4571 Voltage window 0.50 to 9.99 % 1.00 % UNSIGNED 16
4572 Positive frequency window 0.02 to 0.49 Hz 0.18 Hz SIGNED 16
4573 Negative frequency window -0.02 to -0.49 Hz -0.18 Hz SIGNED 16
4577 Max. overlap time 0.1 to 9.99 s 0.10 s UNSIGNED 16
4578 Open trans. switch reac. time 15 to 300 ms 30 ms UNSIGNED 16
4583 Closed trans. switch reac. time 15 to 300 ms 30 ms UNSIGNED 16
4581 Vector group angle adjustment -180° to 180° 0° SIGNED 16
4576 In-phase timeout after 0 to 6500 s 60 s UNSIGNED 16
Abort  Abort  Abort
4582 Outcome on In-phase timeout Abort UNSIGNED 16
Delayed  Delayed  Delayed

Page 128/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

MONITORING
Load Monitoring
Overcurrent Monitoring level 1
2200 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
2204 Limit 50.0 to 300.0 % 110.0 % UNSIGNED 16
2205 Delay 0.02 to 99.99 s 30.00 s UNSIGNED 16
2202 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
Overcurrent Monitoring level 2
2206 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
2210 Limit 50.0 to 300.0 % 150.0 % UNSIGNED 16
2211 Delay 0.02 to 99.99 s 1.00 s UNSIGNED 16
2208 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
Overcurrent Monitoring level 3
2212 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
2216 Limit 50.0 to 300.0 % 250.0 % UNSIGNED 16
2217 Delay 0.02 to 99.99 s 0.40 s UNSIGNED 16
2214 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
Overload Monitoring level 1
2300 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
2304 Limit 50.0 to 300.0 % 110.0 % UNSIGNED 16
2305 Delay 0.02 to 99.99 s 11.00 s UNSIGNED 16
2302 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
Overload Monitoring level 2
2306 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
2310 Limit 50.0 to 300.0 % 120.0 % UNSIGNED 16
2311 Delay 0.02 to 99.99 s 0.10 s UNSIGNED 16
2308 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
Engine Monitoring
Start Failure S1 Monitoring
3341 S1 Start fail delay time 1 to 6500 s 8s UNSIGNED 16
Start Failure S2 Monitoring
3331 S2 Start fail delay time 1 to 6500 s 8s UNSIGNED 16
Battery Voltage Monitoring
Overvoltage Monitoring level 1
3450 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
3454 Limit 8.0 to 42.0 V 32.0 V UNSIGNED 16
3455 Delay 0.02 to 99.99 s 5.00 s UNSIGNED 16
3452 Self acknowledge level 1 YES / NO NO Y N Y N UNSIGNED 16
Overvoltage Monitoring level 2
3456 Monitoring ON / OFF OFF 1 0 1 0 UNSIGNED 16
3460 Limit 8.0 to 42.0 V 35.0 V UNSIGNED 16
3461 Delay 0.02 to 99.99 s 1.00 s UNSIGNED 16
3458 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
Undervoltage Monitoring level 1
3500 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
3504 Limit 8.0 to 42.0 V 24.0 V UNSIGNED 16
3505 Delay 0.02 to 99.99 s 60.00 s UNSIGNED 16
3502 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
Undervoltage Monitoring level 2
3506 Monitoring ON / OFF ON 1 0 1 0 UNSIGNED 16
3510 Limit 8.0 to 42.0 V 20.0 V UNSIGNED 16
3511 Delay 0.02 to 99.99 s 10.00 s UNSIGNED 16
3508 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16
CANopen Interface Monitoring
3150 Monitoring ON / OFF OFF 1 0 1 0 UNSIGNED 16
3154 Delay 0.1 to 650.0 s 2.0 s UNSIGNED 16
3152 Self acknowledge YES / NO NO Y N Y N UNSIGNED 16

© Woodward Page 129/141


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

DIGITAL INPUTS
Digital Input 1
N.O.
DI 1 operation N.C. UNSIGNED 16
N.C.
DI 1 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 2
N.O.
DI 2 operation N.C. UNSIGNED 16
N.C.
DI 2 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 3
N.O.
DI 3 operation N.C. UNSIGNED 16
N.C.
DI 3 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 4
N.O.
DI 4 operation N.C. UNSIGNED 16
N.C.
DI 4 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 5
N.O.  N.O.  N.O.
1281 DI 5 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1280 DI 5 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 6
N.O.  N.O.  N.O.
1301 DI 6 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1300 DI 6 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 7
N.O.  N.O.  N.O.
1321 DI 7 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1320 DI 7 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 8
N.O.  N.O.  N.O.
1341 DI 8 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1340 DI 8 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 9
N.O.  N.O.  N.O.
1361 DI 9 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1360 DI 9 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 10
N.O.  N.O.  N.O.
1381 DI 10 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1380 DI 10 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 11
N.O.  N.O.  N.O.
1206 DI 11 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1205 DI 11 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
Digital Input 12
N.O.  N.O.  N.O.
1226 DI 12 operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
1225 DI 12 delay 0.08 to 650.00 s 0.08 s UNSIGNED 16
External Digital Input 1
N.O.  N.O.  N.O.
16001 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16000 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 2
N.O.  N.O.  N.O.
16011 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16010 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16

Page 130/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

DIGITAL INPUTS
External Digital Input 3
N.O.  N.O.  N.O.
16021 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16020 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 4
N.O.  N.O.  N.O.
16031 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16030 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 5
N.O.  N.O.  N.O.
16041 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16040 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 6
N.O.  N.O.  N.O.
16051 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16050 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 7
N.O.  N.O.  N.O.
16061 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16060 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 8
N.O.  N.O.  N.O.
16071 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16070 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 9
N.O.  N.O.  N.O.
16081 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16080 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 10
N.O.  N.O.  N.O.
16091 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16090 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 11
N.O.  N.O.  N.O.
16101 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16100 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 12
N.O.  N.O.  N.O.
16111 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16110 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 13
N.O.  N.O.  N.O.
16121 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16120 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 14
N.O.  N.O.  N.O.
16131 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16130 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 15
N.O.  N.O.  N.O.
16141 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16140 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16
External Digital Input 16
N.O.  N.O.  N.O.
16151 Operation N.O. UNSIGNED 16
N.C.  N.C.  N.C.
16150 Delay 0.05 to 650.00 s 0.20 s UNSIGNED 16

© Woodward Page 131/141


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

DIGITAL OUTPUTS
12100 Relay 1 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12110 Relay 2 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12310 Relay 3 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12320 Relay 4 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12130 Relay 5 see descr. in LogicsManager chap. starting p. 119; default: (!20.06 & 1) & 1 Logman
12140 Relay 6 see descr. in LogicsManager chap. starting page 119; default: (20.07 & 1) & 1 Logman
12150 Relay 7 see descr. in LogicsManager chap. starting page 119; default: (20.09 & 1) & 1 Logman
12160 Relay 8 see descr. in LogicsManager chap. starting page 119; default: (20.08 & 1) & 1 Logman
12170 Relay 9 see descr. in LogicsManager chap. starting page 119; default: (20.10 & 1) & 1 Logman
12330 External DO 1 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12340 External DO 2 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12350 External DO 3 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12360 External DO 4 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12370 External DO 5 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12380 External DO 6 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12390 External DO 7 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12400 External DO 8 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12410 External DO 9 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12420 External DO 10 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12430 External DO 11 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12440 External DO 12 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12450 External DO 13 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12460 External DO 14 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12470 External DO 15 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12480 External DO 16 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman

COUNTERS
2515 Counter value preset 0 to 99999999 UNSIGNED 32
2514 S1 active power [0.00MWh] YES / NO NO Y N Y N UNSIGNED 16
2516 S1 reactive power [0.00Mvarh] YES / NO NO Y N Y N UNSIGNED 16
2510 S2 active power [0.00MWh] YES / NO NO Y N Y N UNSIGNED 16
2511 S2 reactive power [0.00Mvarh] YES / NO NO Y N Y N UNSIGNED 16

LOGICSMANAGER
Internal Flags
12230 Flag 1 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12240 Flag 2 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12250 Flag 3 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12260 Flag 4 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12270 Flag 5 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12280 Flag 6 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12290 Flag 7 see descr. in LogicsManager chap. starting page 119; default: (0 & 1) & 1 Logman
12300 Flag 8 see descr. in LogicsManager ch. start. p. 119; def.: (11.01 & !11.02) & 11.03 Logman
Set Timers
1652 Setpoint 1: Hour 0 to 23 h 8h UNSIGNED 8
1651 Setpoint 1: Minute 0 to 59 min 0 min UNSIGNED 8
1650 Setpoint 1: Second 0 to 59 s 0s UNSIGNED 8
1657 Setpoint 2: Hour 0 to 23 h 17 h UNSIGNED 8
1656 Setpoint 2: Minute 0 to 59 min 0 min UNSIGNED 8
1655 Setpoint 2: Second 0 to 59 s 0s UNSIGNED 8
1663 Active day 1 to 31 1 UNSIGNED 8
1662 Active hour 0 to 23 h 12 h UNSIGNED 8
1661 Active minute 0 to 59 min 0 min UNSIGNED 8
1660 Active second 0 to 59 s 0s UNSIGNED 8
1670 Monday active YES / NO YES Y N Y N UNSIGNED 16
1671 Tuesday active YES / NO YES Y N Y N UNSIGNED 16
1672 Wednesday active YES / NO YES Y N Y N UNSIGNED 16
1673 Thursday active YES / NO YES Y N Y N UNSIGNED 16
1674 Friday active YES / NO YES Y N Y N UNSIGNED 16
1675 Saturday active YES / NO NO Y N Y N UNSIGNED 16
1676 Sunday active YES / NO NO Y N Y N UNSIGNED 16

Page 132/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

COMMUNICATION INTERFACES
1702 Device number 1 to 127 1 UNSIGNED 16
CAN Interfaces
OFF  OFF  OFF
3155 Protocol CAN Open CAN Open  CAN O.  CAN O. UNSIGNED 16
LeoPC  LeoPC  LeoPC
20/50/100/125/250/500/
3156 Baudrate 125 kBd UNSIGNED 16
800/1000 kBd
CANopen Interfaces
9000 CAN-Open Master YES / NO YES Y N Y N UNSIGNED 16
9120 Producer Heartbeat Time 20 to 65530 ms 2000 ms UNSIGNED 16
9100 COB-ID SYNC Message 1 to FFFFFFFF 80 UNSIGNED 32
9010 Max. answer time ext. devices 0.1 to 9.9 s 3.0 s UNSIGNED 16
9009 Time re-init. ext. devices 0 to 9999 s 10 s UNSIGNED 16
Additional Server SDOs
9020 2nd Client->Server COB-ID (rx) 1 to FFFFFFFF 80000601 UNSIGNED 32
9022 2nd Server->Client COB-ID (tx) 1 to FFFFFFFF 80000581 UNSIGNED 32
9024 3rd Client->Server COB-ID (rx) 1 to FFFFFFFF 80000602 UNSIGNED 32
9026 3rd Server->Client COB-ID (tx) 1 to FFFFFFFF 80000582 UNSIGNED 32
9028 4th Client->Server COB-ID (rx) 1 to FFFFFFFF 80000603 UNSIGNED 32
9030 4th Server->Client COB-ID (tx) 1 to FFFFFFFF 80000583 UNSIGNED 32
9032 5th Client->Server COB-ID (rx) 1 to FFFFFFFF 80000604 UNSIGNED 32
9034 5th Server->Client COB-ID (tx) 1 to FFFFFFFF 80000584 UNSIGNED 32
Receive PDO 1
9300 COB-ID 1 to FFFFFFFF 201 UNSIGNED 32
no func.  no func.  no func.
1st IKD  1st IKD  1st IKD
9050 Function 2nd IKD no func.  2nd IKD  2nd IKD UNSIGNED 16
BK 16DIDO  BK 16  BK 16
Co 16DIDO  Co 16  Co 16
9060 Node-ID of the device 1 to 127 2 UNSIGNED 16
9070 RPDO-COB-ID ext. device 1 1 to FFFFFFFF 181 UNSIGNED 32
Receive PDO 2
9310 COB-ID 1 to FFFFFFFF 202 UNSIGNED 32
no func.  no func.  no func.
1st IKD  1st IKD  1st IKD
9051 Function 2nd IKD no func.  2nd IKD  2nd IKD UNSIGNED 16
BK 16DIDO  BK 16  BK 16
Co 16DIDO  Co 16  Co 16
9061 Node-ID of the device 1 to 127 3 UNSIGNED 16
9072 RPDO-COB-ID ext. device 2 1 to FFFFFFFF 182 UNSIGNED 32
Transmit PDO 1
9600 COB-ID 1 to FFFFFFFF 181 UNSIGNED 32
9602 Transmission type 0 to 255 255 UNSIGNED 8
9604 Event-timer 20 to 65000 ms 20 ms UNSIGNED 16
9609 Number of mapped objects 0 to 4 4 UNSIGNED 8
9605 1.Mapped Object 0 to 65535 8001 UNSIGNED 16
9606 2.Mapped Object 0 to 65535 8000 UNSIGNED 16
9607 3.Mapped Object 0 to 65535 8000 UNSIGNED 16
9608 4.Mapped Object 0 to 65535 8000 UNSIGNED 16
Transmit PDO 2
9610 COB-ID 1 to FFFFFFFF 182 UNSIGNED 32
9612 Transmission type 0 to 255 255 UNSIGNED 8
9614 Event-timer 20 to 65000 ms 20 ms UNSIGNED 16
9619 Number of mapped objects 0 to 4 4 UNSIGNED 8
9615 1.Mapped Object 0 to 65535 8002 UNSIGNED 16
9616 2.Mapped Object 0 to 65535 8000 UNSIGNED 16
9617 3.Mapped Object 0 to 65535 8000 UNSIGNED 16
9618 4.Mapped Object 0 to 65535 8000 UNSIGNED 16

© Woodward Page 133/141


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

COMMUNICATION INTERFACES
Transmit PDO 3
9620 COB-ID 1 to FFFFFFFF 381 UNSIGNED 32
9622 Transmission type 0 to 255 255 UNSIGNED 8
9624 Event-timer 20 to 65000 ms 20 ms UNSIGNED 16
9629 Number of mapped objects 0 to 4 1 UNSIGNED 8
9625 1.Mapped Object 0 to 65535 3196 UNSIGNED 16
9626 2.Mapped Object 0 to 65535 0 UNSIGNED 16
9627 3.Mapped Object 0 to 65535 0 UNSIGNED 16
9628 4.Mapped Object 0 to 65535 0 UNSIGNED 16
Transmit PDO 4
9630 COB-ID 1 to FFFFFFFF 481 UNSIGNED 32
9632 Transmission type 0 to 255 255 UNSIGNED 8
9634 Event-timer 20 to 65000 ms 20 ms UNSIGNED 16
9639 Number of mapped objects 0 to 4 1 UNSIGNED 8
9635 1.Mapped Object 0 to 65535 3190 UNSIGNED 16
9636 2.Mapped Object 0 to 65535 0 UNSIGNED 16
9637 3.Mapped Object 0 to 65535 0 UNSIGNED 16
9638 4.Mapped Object 0 to 65535 0 UNSIGNED 16
Serial Interface 1
2400 Bd  2400 Bd  2400 Bd
4800 Bd  4800 Bd  4800 Bd
9600 Bd  9600 Bd  9600 Bd
14.4 kBd  14.4 kBd  14.4 kBd
3163 Baudrate 9600 Bd UNSIGNED 16
19.2 kBd  19.2 kBd  19.2 kBd
38.4 kBd  38.4 kBd  38.4 kBd
56 kBd  56 kBd  56 kBd
115 kBd  115 kBd  115 kBd
No  No  No
3161 Parity Even No  Even  Even UNSIGNED 16
Odd  Odd  Odd
One  One  One
3162 Stop Bits One UNSIGNED 16
Two  Two  Two
Serial Interface 2
2400 Bd
4800 Bd  9600 Bd  9600 Bd
9600 Bd  14.4 kBd  14.4 kBd
14.4 kBd  19.2 kBd  19.2 kBd
3170 Baudrate 19200 Bd UNSIGNED 16
19.2 kBd  38.4 kBd  38.4 kBd
38.4 kBd  56 kBd  56 kBd
56 kBd  115 kBd  115 kBd
115 kBd
No  No  No
3171 Parity Even No  Even  Even UNSIGNED 16
Odd  Odd  Odd
One  One  One
3172 Stop Bits One UNSIGNED 16
Two  Two  Two
Fullduplex  Full  Full
3173 Full-, halfduplex mode Fullduplex UNSIGNED 16
Halfduplex  Half  Half
3185 ModBus Slave ID 0 to 255 1 UNSIGNED 16
3186 Modbus Reply delay time 0.00 to 0.20 s 0.00 s UNSIGNED 16

Page 134/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Par.
Parameter Setting range Default value Customer setting Data type
ID.

SYSTEM PARAMETER
Display Backlight
On  On  On
Off  Off  Off
4556 Configure display backlight On UNSIGNED 16
Auto  Auto  Auto
Key actv.  Key act.  Key act.
4557 Time until backlight shutdown 1 to 999 s 600 s UNSIGNED 16
Daylight saving time
On  On  On
4591 Daylight saving time Off UNSIGNED 16
Off  Off  Off
4593 DST begin month 1 to 12 1 UNSIGNED 8
4592 DST begin sunday 1 to 4 1 UNSIGNED 8
4594 DST begin time 1 to 23 h 0h UNSIGNED 8
4596 DST end month 1 to 12 1 UNSIGNED 8
4595 DST end sunday 1 to 4 1 UNSIGNED 8
4597 DST end time 1 to 23 h 0h UNSIGNED 8
Password System
10405 Code level display 0000 to 9999 --- UNSIGNED 16
10407 Code level CAN port 0000 to 9999 --- UNSIGNED 16
10406 Code level serial port / DPC 0000 to 9999 --- UNSIGNED 16
10411 Supercomm. level code 0000 to 9999 --- UNSIGNED 16
10412 Temp. supercomm. level code 0000 to 9999 --- UNSIGNED 16
10413 Commissioning level code 0000 to 9999 --- UNSIGNED 16
10414 Temp. commissioning level code 0000 to 9999 --- UNSIGNED 16
10415 Basic level code 0000 to 9999 --- UNSIGNED 16
1703 Factory settings YES / NO NO Y N Y N UNSIGNED 16
1704 Factory settings DPC/RS232 YES / NO NO Y N Y N UNSIGNED 16
1705 Factory settings CAN YES / NO NO Y N Y N UNSIGNED 16
1701 Set default values YES / NO NO Y N Y N UNSIGNED 16
10500 Start Bootloader 00000 to 99999 --- UNSIGNED 16
Clock Set
1762 Hour 0 to 23 h --- UNSIGNED 8
1761 Minute 0 to 59 min --- UNSIGNED 8
1760 Second 0 to 59 s --- UNSIGNED 8
1763 Day 1 to 31 --- UNSIGNED 8
1764 Month 1 to 12 --- UNSIGNED 8
1765 Year 0 to 99 --- UNSIGNED 8
Version
900 Serial number Info --- UNSIGNED 8
950 Boot item number Info --- UNSIGNED 8
960 Boot revision Info --- UNSIGNED 8
965 Boot version Info --- UNSIGNED 8
930 Program item number Info --- UNSIGNED 8
940 Program revision Info --- UNSIGNED 8
945 Program version Info --- UNSIGNED 8

NOTE
All parameters shaded in gray color are fixed parameters and cannot be configured by the operator.

© Woodward Page 135/141


Manual 37386D DTSC-200 - ATS Controller

Appendix D.
Service Options

Product Service Options


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
The following factory options are available for servicing Woodward equipment, based on the standard
Woodward Product and Service Warranty (5-01-1205) that is in effect at the time the product is purchased from
Woodward or the service is performed. If you are experiencing problems with installation or unsatisfactory
performance of an installed system, the following options are available:

• Consult the troubleshooting guide in the manual.


• Contact Woodward technical assistance (see "How to Contact Woodward" later in this chapter) and discuss
your problem. In most cases, your problem can be resolved over the phone. If not, you can select which
course of action you wish to pursue based on the available services listed in this section.

Returning Equipment For Repair


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
If a control (or any part of an electronic control) is to be returned to Woodward for repair, please contact
Woodward in advance to obtain a Return Authorization Number. When shipping the unit(s), attach a tag with the
following information:

• name and location where the control is installed;


• name and phone number of contact person;
• complete Woodward part numbers (P/N) and serial number (S/N);
• description of the problem;
• instructions describing the desired repair.

CAUTION
To prevent damage to electronic components caused by improper handling, read and observe the
precautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls,
Printed Circuit Boards, and Modules.

Page 136/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Packing A Control
Use the following materials when returning a complete control:

• protective caps on any connectors;


• antistatic protective bags on all electronic modules;
• packing materials that will not damage the surface of the unit;
• at least 100 mm (4 inches) of tightly packed, industry-approved packing material;
• a packing carton with double walls;
• a strong tape around the outside of the carton for increased strength.

Return Authorization Number RAN


When returning equipment to Woodward, please telephone and ask for the Customer Service Department in
Stuttgart [+49 (0) 711 789 54-0]. They will help expedite the processing of your order through our distributors or
local service facility. To expedite the repair process, contact Woodward in advance to obtain a Return
Authorization Number, and arrange for issue of a purchase order for the unit(s) to be repaired. No work can be
started until a purchase order is received.

NOTE
We highly recommend that you make arrangement in advance for return shipments. Contact a
Woodward customer service representative at +49 (0) 711 789 54-0 for instructions and for a
Return Authorization Number.

Replacement Parts
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
When ordering replacement parts for controls, include the following information:
• the part numbers P/N (XXXX-XXX) that is on the enclosure nameplate;
• the unit serial number S/N, which is also on the nameplate.

© Woodward Page 137/141


Manual 37386D DTSC-200 - ATS Controller

How To Contact Woodward


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Please contact following address if you have questions or if you want to send a product for repair:

Woodward GmbH
Handwerkstrasse 29
70565 Stuttgart - Germany

Phone: +49 (0) 711 789 54-0 (8.00 - 16.30 German time)
Fax: +49 (0) 711 789 54-100
e-mail: [email protected]

For assistance outside Germany, call one of the following international Woodward facilities to obtain the address
and phone number of the facility nearest your location where you will be able to get information and service.

Facility Phone number


USA +1 (970) 482 5811
India +91 (129) 409 7100
Brazil +55 (19) 3708 4800
Japan +81 (476) 93 4661
The Netherlands +31 (23) 566 1111

You can also contact the Woodward Customer Service Department or consult our worldwide directory on
Woodward’s website (www.woodward.com) for the name of your nearest Woodward distributor or service
facility. [For worldwide directory information, go to www.woodward.com/ic/locations.]

Page 138/141 © Woodward


Manual 37386D DTSC-200 - ATS Controller

Engineering Services
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Woodward Industrial Controls Engineering Services offers the following after-sales support for Woodward
products. For these services, you can contact us by telephone, by e-mail, or through the Woodward website.

• Technical support
• Product training
• Field service during commissioning

Technical Support is available through our many worldwide locations, through our authorized distributors, or
through GE Global Controls Services, depending on the product. This service can assist you with technical
questions or problem solving during normal business hours. Emergency assistance is also available during non-
business hours by phoning our toll-free number and stating the urgency of your problem. For technical
engineering support, please contact us via our toll-free or local phone numbers, e-mail us, or use our website and
reference technical support.

Product Training is available on-site from several of our worldwide facilities, at your location, or from GE
Global Controls Services, depending on the product. This training, conducted by experienced personnel, will
assure that you will be able to maintain system reliability and availability. For information concerning training,
please contact us via our toll-free or local phone numbers, e-mail us, or use our website and reference customer
training.

Field Service engineering on-site support is available, depending on the product and location, from our facility in
Colorado, or from one of many worldwide Woodward offices or authorized distributors. Field engineers are
experienced on both Woodward products as well as on much of the non-Woodward equipment with which our
products interface. For field service engineering assistance, please contact us via our toll-free or local phone
numbers, e-mail us, or use our website and reference field service.

© Woodward Page 139/141


Manual 37386D DTSC-200 - ATS Controller

Technical Assistance
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
If you need to telephone for technical assistance, you will need to provide the following information. Please write
it down here before phoning:

Contact
Your company ____________________________________________________

Your name _______________________________________________________

Phone number ____________________________________________________

Fax number ______________________________________________________

Control (see name plate)


Unit no. and revision: P/N: ____________________ REV: _____________

Unit type DTSC-200 __________________________________

Serial number S/N _______________________________________

Description of your problem


________________________________________________________________

________________________________________________________________

________________________________________________________________

________________________________________________________________

________________________________________________________________

________________________________________________________________

Please be sure you have a list of all parameters available. You can print this using LeoPC1 Additionally you can
save the complete set of parameters (standard values) and send them to our Service department via e-mail.

Page 140/141 © Woodward


We appreciate your comments about the content of our publications.
Please send comments to: [email protected]
Please include the manual number from the front cover of this publication.

Woodward GmbH
Handwerkstrasse 29 - 70565 Stuttgart - Germany
Phone +49 (0) 711 789 54-0 • Fax +49 (0) 711 789 54-100
[email protected]

Homepage

http://www.woodward.com/power

Woodward has company-owned plants, subsidiaries, and branches, as well as authorized


distributors and other authorized service and sales facilities throughout the world.

Complete address/phone/fax/e-mail information


for all locations is available on our website (www.woodward.com).

2011/06/Stuttgart

You might also like