Mechanical Vibration Controls and Seismic Restraints
Mechanical Vibration Controls and Seismic Restraints
Mechanical Vibration Controls and Seismic Restraints
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.
0.2 SUMMARY
A. This Section includes vibration isolators, vibration isolation bases, vibration isolation roof
curbs, and seismic restraints and snubbers.
0.3 SUBMITTALS
A. Product Data: Indicate types, styles, materials, and finishes for each type of isolator
specified. Include load deflection curves.
B. Shop Drawings: Show designs and calculations, certified by a professional engineer, for the
following:
A. General Requirements: The requirements for seismic protection measures described in this
section shall be applied to the mechanical equipment and systems listed below.
C. Mechanical Systems: The following mechanical systems shall be installed as required on the
Drawings and other Sections of the Specification and shall be seismically protected in
accordance with this Specification:
1. All Piping Inside the Building Except as Specifically Stated Below Under "Items Not
Covered By This Section".
2. Chilled water distribution systems outside of buildings.
3. Fuel piping outside of buildings.
4. All water supply systems.
5. Storm and sanitary sewer systems.
6. Condenser water piping outside the building.
7. Fuel storage tanks.
8. Water storage tanks.
D. Contractor Designed Bracing: The Contractor shall design the bracing in accordance with
SMACNA Seismic Restraint Manual. Design shall be performed by a certified engineer.
Resistance to lateral forces induced by earthquakes shall be accomplished without
consideration of friction resulting from gravity loads.
E. Items Not Covered By This Section: Fire Protection Systems. Seismic protection of piping
for fire protection systems shall be installed as specified in Division 13.
F. Items Requiring No Seismic Restraints: Seismic restraints are not required for the following
items:
0.7 COORDINATION
A. Coordinate layout and installation of vibration isolation and seismic-restraint devices with
other construction that penetrates ceilings or is supported by them, including light fixtures,
HVAC equipment, fire-suppression-system components, and partition assemblies.
B. Coordinate size and location of concrete housekeeping and vibration isolation bases. Cast
anchor-bolt inserts into base. Concrete, reinforcement, and formwork requirements are
specified in Division 3 Sections.
C. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These
items are specified in Division 7 Sections.
PART 2 - PRODUCTS
A. Noise Criteria:
1. Noise levels in all 8 octave bands due to equipment and duct systems shall not exceed
following NC levels:
2. For equipment which has no sound power ratings scheduled on the plans, the
Contractor shall select equipment such that the foregoing noise criteria, local
ordinance noise levels, and ASHRAE requirements are not exceeded. Selection
procedure shall be in accordance with ASHRAE Fundamentals Handbook 2001,
Chapter 7, Sound and Vibration.
3. An allowance, not to exceed 5db, may be added to the measured value to compensate
for the variation of the room attenuating effect between room test condition prior to
occupancy and design condition after occupancy which may include the addition of
sound absorbing material, such as furniture. This allowance may not be taken after
occupancy. The room attenuating effect is defined as the difference between sound
power level emitted to room and sound pressure level in room.
4. In the absence of specified measurement requirements, measure equipment noise
levels 0.914 m from equipment and at an elevation of maximum noise generation.
B. Machinery Airborne Sound Level Criteria: For each piece of machinery in the human work
environment, the maximum airborne sound levels shall not exceed 84 dB A-weighted scale,
continuous or intermittent, or 140 dB peak sound pressure-level, impact or impulse, noise.
Unless otherwise specified the maximum equipment airborne sound power level in dB shall
not exceed the following data:
1. All mechanical equipment not supported with isolators external to the unit shall be
securely anchored to the structure. Such mechanical equipment shall be properly
supported to resist a horizontal force of 50 percent of the weight of the equipment
furnished.
2. All mechanical equipment mounted on vibration isolators shall be provided with
seismic restraints capable of resisting a horizontal force of 100 percent of the weight
of the equipment furnished.
A. Floor Mountings:
1. Double Deflection Neoprene (Type N): Shall include neoprene covered steel support
plated (top and bottom), friction pads, and necessary bolt holes.
2. Spring Isolators (Type S): Shall be freestanding, laterally stable and include
acoustical friction pads and leveling bolts. Isolators shall have a minimum ratio of
spring diameter-to-operating spring height of 1.0 and an additional travel to solid
equal to 50 percent of rated deflection.
3. Pads (Type D), Washers (Type W), and Bushings (Type L): Pads shall be felt, cork,
neoprene waffle, neoprene and cork sandwich, neoprene and fiberglass, neoprene and
steel waffle, or reinforced duck and neoprene. Washers and bushings shall be
reinforced duck and neoprene. Size pads for a maximum load of 345 kPa (50 pounds
per square inch).
B. Hangers: Shall be combination neoprene and springs unless otherwise noted and shall allow
for expansion of pipe.
1. Combination Neoprene and Spring (Type H): Vibration hanger shall contain a spring
and double deflection neoprene element in series. Spring shall have a diameter not
less than 0.8 of compressed operating spring height. Spring shall have a minimum
additional travel of 50 percent between design height and solid height. Spring shall
permit a 15-degree angular misalignment without rubbing on hanger box.
2. Spring Position Hanger (Type HP): Similar to combination neoprene and spring
hanger except hanger shall hold piping at a fixed elevation during installation and
include a secondary adjustment feature to transfer load to spring while maintaining
same position.
3. Neoprene (Type HN): Vibration hanger shall contain a double deflection type
neoprene isolation element. Hanger rod shall be separated from contact with hanger
bracket by a neoprene grommet.
4. Spring (Type HS): Vibration hanger shall contain a coiled steel spring in series with a
neoprene grommet. Spring shall have a diameter not less than 0.8 of compressed
operating spring height. Spring shall have a minimum additional travel of 50 percent
between design height and solid height. Spring shall permit a 15 degree angular
misalignment without rubbing on hanger box.
5. Hanger supports for piping 50 mm (2 inches) and larger shall have a pointer and scale
deflection indicator.
1. Design mounts to resiliently resist seismic forces in all directions. Snubbing shall take
place in all modes with adjustment to limit upward, downward, and horizontal travel
to a maximum of 6 mm (1/4-inch) before contacting snubbers. Mountings shall have
a minimum rating of one G coefficient of gravity as calculated and certified by a
registered structural engineer.
2. All mountings shall have leveling bolts that must be rigidly bolted to the equipment.
Spring diameters shall be no less than 0.8 of the compressed height of the spring at
rated load. Springs shall have a minimum additional travel to solid equal to 50
percent of the rated deflection. Mountings shall have ports for spring inspection.
Provide an all directional neoprene cushion collar around the equipment bolt.
B. Spring Isolators with Vertical Limit Stops (Type SP): Similar to spring isolators noted
above, except include a vertical limit stop to limit upward travel if weight is removed and
also to reduce movement and spring extension due to wind loads. Provide clearance around
restraining bolts to prevent mechanical short-circuiting. Isolators shall have a minimum
seismic rating as described above.
C. Seismic Pad (Type DS): Pads shall be felt, cork neoprene waffle, neoprene and cork
sandwich, neoprene and fiberglass, neoprene and steel waffle, or reinforced duck and
neoprene, with steel top plate and drilled for an anchor bolt. Washers and bushings shall be
reinforced duck and neoprene. Size pads for a maximum load of 345 kPa.
D. Thrust Restraints Type (THR): Combination spring and elastomeric restraints with coil
spring and elastomeric insert in compression. Factory set for thrust.
1. Frame: Formed steel, fabricated for connection to threaded rods and to allow for 30
degrees of angular hanger rod misalignment without binding or reducing isolation
efficiency.
2. Outside Spring Diameter: Not less than 80 percent of the compressed height of the
spring at rated load.
3. Minimum Additional Travel: 50 percent of the required deflection at rated load.
4. Elastomeric Element: Molded, oil-resistant rubber or neoprene.
5. Finishes: Baked enamel for metal components. Color-code to indicate capacity
range.
A. Rails (Type R): Design rails with isolator brackets to reduce mounting height of equipment
and cradle machines having legs or bases that do not require a complete supplementary
base. To assure adequate stiffness, height of members shall be a minimum of 1/12 of longest
base dimension but not less than 100 mm (4 inches). Where rails are used with neoprene
MECHANICAL VIBRATION CONTROLS AND SEISMIC RESTRAINTS 15241 - Page 6/10
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>
mounts for small fans or close-coupled pumps, extend rails to compensate overhang of
housing.
B. Integral Structural Steel Base (Type B): Design base with isolator brackets to reduce
mounting height of equipment that require a complete supplementary rigid base. To assure
adequate stiffness, height of members shall be a minimum of 1/12 of longest base
dimension, but not less than 100 mm (4 inches).
C. Inertia Base (Type I): Base shall be a reinforced concrete inertia base. Pour concrete into a
welded steel channel frame, incorporating prelocated equipment anchor bolts and pipe
sleeves. Level the concrete to provide a smooth uniform bearing surface for equipment
mounting. Provide grout under uneven supports. Channel depth shall be a minimum of 1/12
of longest dimension of base but not less than 150 mm (6 inches). Form shall include 13-
mm (1/2-inch) reinforcing bars welded in place on minimum of 203 mm (8 inch) centers
running both ways in a layer 40 mm (1-1/2 inches) above bottom. Use height saving
brackets in all mounting locations. Weight of inertia base shall be equal to or greater than
weight of equipment supported to provide a maximum peak-to-peak displacement of 2 mm
(1/16 inch).
D. Curb Mounted Isolation Base (Type CB): Fabricate from aluminum to fit on top of standard
curb with overlap to allow water run-off and have wind and water seals which shall not
interfere with spring action. Provide resilient snubbers with 6 mm (1/4 inch) clearance for
wind resistance. Top and bottom bearing surfaces shall have sponge type weather seals.
Integral spring isolators shall comply with Spring Isolator (Type S) requirements.
1.
A. Description: Factory-assembled, fully enclosed, insulated, air- and watertight curb designed
to resiliently support roof-mounted equipment and to withstand 56 m/s wind impinging
laterally against the side of the equipment. Design restraints to meet seismic requirements.
PART 3 - EXECUTION
0.1 INSTALLATION
B. Anchor interior mounts, isolators, hangers, and snubbers to vibration isolation bases. Bolt
isolator baseplates to structural floors as required.
C. Anchor exterior mounts, isolators, hangers, and snubbers to vibration isolation bases. Bolt
isolator baseplates to structural supports as required.
D. Fill concrete inertia bases, after installing base frame, with 21 MPa concrete, and trowel to a
smooth, hard finish. Cast-in-place concrete is specified in Division 3.
B. Snubbers: Install the required number of seismic snubbers on each spring-mounted piece of
equipment. Locate snubbers as close as possible to the vibration isolators and bolt to
supporting structure.
A. Adjust limit stops on restrained spring isolators to mount equipment at normal operating
height. After equipment installation is complete, adjust limit stops so they are out of contact
during normal operations.
NOTES:
1. For suspended floors lighter than 100 mm thick concrete, select deflection requirements from
next higher span.
3. For separate chiller building on grade, pump isolators may be omitted.
4. Direct bolt fire pumps to concrete base. Provide pads (D) for domestic water booster pump
package.
5. For projects in seismic areas, use only SS & DS type isolators and snubbers.
6. Isolators not required where cooling tower is located on grade or on roof over mechanical
room.
7. Suspended: Use "H" isolators of same deflection as floor mounted.