0% found this document useful (0 votes)
138 views21 pages

Project Standard Specification: Testing, Adjusting, and Balancing 15990 - Page 1/21

This document provides specifications for testing, adjusting, and balancing (TAB) HVAC systems on a project. It outlines the scope of TAB work to balance airflow and water flow within HVAC distribution systems and adjust systems to provide indicated quantities. It specifies requirements for instrument calibration and qualified TAB agents to perform TAB procedures, prepare reports, and certify results. It also requires coordination and scheduling of TAB work with other contractors and building occupancy.

Uploaded by

adel rihana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views21 pages

Project Standard Specification: Testing, Adjusting, and Balancing 15990 - Page 1/21

This document provides specifications for testing, adjusting, and balancing (TAB) HVAC systems on a project. It outlines the scope of TAB work to balance airflow and water flow within HVAC distribution systems and adjust systems to provide indicated quantities. It specifies requirements for instrument calibration and qualified TAB agents to perform TAB procedures, prepare reports, and certify results. It also requires coordination and scheduling of TAB work with other contractors and building occupancy.

Uploaded by

adel rihana
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 21

<Project Title>

PROJECT STANDARD SPECIFICATION

SECTION 15990 - TESTING, ADJUSTING, AND BALANCING

PART 1 - GENERAL

0.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.

0.2 SUMMARY

A. This Section includes testing, adjusting, and balancing HVAC systems to produce design
objectives, including the following:

1. Balancing airflow and water flow within distribution systems, including submains,
branches, and terminals, to indicated quantities according to specified tolerances.
2. Adjusting total HVAC systems to provide indicated quantities.
3. Measuring electrical performance of HVAC equipment.
4. Setting quantitative performance of HVAC equipment.
5. Verifying that automatic control devices are functioning properly.
6. Measuring sound and vibration.
7. Reporting results of the activities and procedures specified in this Section.

B. Related Sections include the following:

1. Testing and adjusting requirements unique to particular systems and equipment are
included in the Sections that specify those systems and equipment.
2. Field quality-control testing to verify that workmanship quality for system and
equipment installation is specified in system and equipment Sections.

0.3 DEFINITIONS

A. Adjust: To regulate fluid flow rate and air patterns at the terminal equipment, such as to
reduce fan speed or adjust a damper.

B. Balance: To proportion flows within the distribution system, including submains, branches,
and terminals, according to design quantities.

C. Draft: A current of air, when referring to localized effect caused by one or more factors of
high air velocity, low ambient temperature, or direction of airflow, whereby more heat is
withdrawn from a person's skin than is normally dissipated.

D. Procedure: An approach to and execution of a sequence of work operations to yield


repeatable results.

E. Report Forms: Test data sheets for recording test data in logical order.

F. Static Head: The pressure due to the weight of the fluid above the point of measurement. In
a closed system, static head is equal on both sides of the pump.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 1/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

G. Suction Head: The height of fluid surface above the centerline of the pump on the suction
side.

H. System Effect: A phenomenon that can create undesired or unpredicted conditions that
cause reduced capacities in all or part of a system.

I. System Effect Factors: Allowances used to calculate a reduction of the performance ratings
of a fan when installed under conditions different from those presented when the fan was
performance tested.

J. Terminal: A point where the controlled medium, such as fluid or energy, enters or leaves
the distribution system.

K. Test: A procedure to determine quantitative performance of a system or equipment.

L. Testing, Adjusting, and Balancing Agent: The entity responsible for performing and
reporting the testing, adjusting, and balancing procedures.

M. AABC: Associated Air Balance Council.

N. AMCA: Air Movement and Control Association.

O. CTI: Cooling Tower Institute.

P. NEBB: National Environmental Balancing Bureau.

Q. SMACNA: Sheet Metal and Air Conditioning Contractors' National Association.

0.4 SUBMITTALS

A. Quality-Assurance Submittals: Within 30 days from the Engineer's Notice to Commence,


submit 2 copies of evidence that the testing, adjusting, and balancing Agent and this
Project's testing, adjusting, and balancing team members meet the qualifications specified in
the "Quality Assurance" Article below.

B. Contract Documents Examination Report: Within 45 days from the Engineer's Notice to
Commence, submit 2 copies of the Contract Documents review report as specified in Part  3
of this Section.

C. Strategies and Procedures Plan: Within 60 days from the Engineer's Notice to Commence,
submit 2 copies of the testing, adjusting, and balancing strategies and step-by-step
procedures as specified in Part 3 "Preparation" Article below. Include a complete set of
report forms intended for use on this Project.

D. Certified Testing, Adjusting, and Balancing Reports: Submit 2 copies of reports prepared,
as specified in this Section, on approved forms certified by the testing, adjusting, and
balancing Agent.

E. Sample Report Forms: Submit 2 sets of sample testing, adjusting, and balancing report
forms.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 2/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

0.5 QUALITY ASSURANCE

A. Agent Qualifications: Engage a testing, adjusting, and balancing agent certified by either
AABC or NEBB, or another agency acceptable to the Engineer.

B. Testing, Adjusting, and Balancing Conference: Meet with the Employer's and the
Engineer's representatives on approval of the testing, adjusting, and balancing strategies and
procedures plan to develop a mutual understanding of the details. Ensure the participation
of testing, adjusting, and balancing team members, equipment manufacturers' authorized
service representatives, HVAC controls Installer, and other support personnel. Provide 7
days' advance notice of scheduled meeting time and location.

1. Agenda Items: Include at least the following:

a. Submittal distribution requirements.


b. Contract Documents examination report.
c. Testing, adjusting, and balancing plan.
d. Work schedule and Project site access requirements.
e. Coordination and cooperation of trades and subcontractors.
f. Coordination of documentation and communication flow.

C. Certification of Testing, Adjusting, and Balancing Reports: Certify the testing, adjusting,
and balancing field data reports. This certification includes the following:

1. Review field data reports to validate accuracy of data and to prepare certified testing,
adjusting, and balancing reports.
2. Certify that the testing, adjusting, and balancing team complied with the approved
testing, adjusting, and balancing plan and the procedures specified and referenced in
this Specification.

D. Testing, Adjusting, and Balancing Reports: Use testing, adjusting, and balancing Agent's
report forms as approved by the Engineer.

E. Instrumentation Type, Quantity, and Accuracy: As described in [AABC national


standards] [NEBB's "Procedural Standards for Testing, Adjusting, and Balancing of
Environmental Systems," Section II, "Required Instrumentation for NEBB
Certification"].

F. Instrumentation Calibration: Calibrate instruments at least every 6 months or more


frequently if required by the instrument manufacturer.

0.6 PROJECT CONDITIONS

A. Employer Occupancy: The Employer may occupy completed areas of the building before
Substantial Completion. Cooperate with the Employer during testing, adjusting, and
balancing operations to minimize conflicts with the Employer's operations.

0.7 COORDINATION

A. Coordinate the efforts of factory-authorized service representatives for systems and


equipment, HVAC controls installers, and other mechanics to operate HVAC systems and
equipment to support and assist testing, adjusting, and balancing activities.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 3/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

B. Notice: Provide 7 days' advance notice for each test. Include scheduled test dates and
times.

C. Perform testing, adjusting, and balancing after leakage and pressure tests on air and water
distribution systems have been satisfactorily completed.

PART 2 - PRODUCTS (Not Applicable)

PART 3 - EXECUTION

0.1 EXAMINATION

A. Examine Contract Documents to become familiar with project requirements and to discover
conditions in systems' designs that may preclude proper testing, adjusting, and balancing of
systems and equipment.

1. Contract Documents are defined in the Conditions of Contract.


2. Verify that balancing devices, such as test ports, gage cocks, thermometer wells,
flow-control devices, balancing valves and fittings, and manual volume dampers, are
required by the Contract Documents. Verify that quantities and locations of these
balancing devices are accessible and appropriate for effective balancing and for
efficient system and equipment operation.

B. Examine approved submittal data of HVAC systems and equipment.

C. Examine project record documents described in Division 1 Section " Record (As-Built)
Documents."

D. Examine the Engineer's design data, including HVAC system descriptions, statements of
design assumptions for environmental conditions and systems' output, and statements of
philosophies and assumptions about HVAC system and equipment controls.

E. Examine equipment performance data, including fan and pump curves. Relate performance
data to project conditions and requirements, including system effects that can create
undesired or unpredicted conditions that cause reduced capacities in all or part of a system.
Calculate system effect factors to reduce the performance ratings of HVAC equipment when
installed under conditions different from those presented when the equipment was
performance tested at the factory. To calculate system effects for air systems, use tables and
charts found in AMCA 201, "Fans and Systems," Sections 7 through 10; or in SMACNA's
"HVAC Systems--Duct Design," Sections 5 and 6. Compare this data with the design data
and installed conditions.

F. Examine system and equipment installations to verify that they are complete and that
testing, cleaning, adjusting, and commissioning specified in individual Specification
Sections have been performed.

G. Examine system and equipment test reports.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 4/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

H. Examine HVAC system and equipment installations to verify that indicated balancing
devices, such as test ports, gage cocks, thermometer wells, flow-control devices, balancing
valves and fittings, and manual volume dampers, are properly installed, and their locations
are accessible and appropriate for effective balancing and for efficient system and
equipment operation.

I. Examine systems for functional deficiencies that cannot be corrected by adjusting and
balancing.

J. Examine air-handling equipment to ensure clean filters have been installed, bearings are
greased, belts are aligned and tight, and equipment with functioning controls is ready for
operation.

K. Examine terminal units, such as variable-air-volume boxes and mixing boxes, to verify that
they are accessible and their controls are connected and functioning.

L. Examine plenum ceilings, utilized for supply air, to verify that they are airtight. Verify that
pipe penetrations and other holes are sealed.

M. Examine strainers for clean screens and proper perforations.

N. Examine valves for proper installation for their intended function.

O. Examine heat-transfer coils for correct piping connections and for clean and straight fins.

P. Examine open-piping-system pumps to ensure absence of entrained air in the suction piping.

Q. Examine equipment for installation and for properly operating safety interlocks and
controls.

R. Examine automatic temperature system components to verify the following:

1. Dampers, valves, and other controlled devices operate by the intended controller.
2. Dampers and valves are in the position indicated by the controller.
3. Integrity of valves and dampers for free and full operation and for tightness of fully
closed and fully open positions. This includes dampers in multizone units, mixing
boxes, and variable-air-volume terminals.
4. Automatic modulating and shutoff valves, including 2-way valves and 3-way mixing
and diverting valves, are properly connected.
5. Thermostats and humidistats are located to avoid adverse effects of sunlight, drafts,
and cold walls.
6. Sensors are located to sense only the intended conditions.
7. Sequence of operation for control modes is according to the Contract Documents.
8. Controller set points are set at design values. Observe and record system reactions to
changes in conditions. Record default set points if different from design values.
9. Interlocked systems are operating.
10. Changeover from heating to cooling mode occurs according to design values.

S. Report deficiencies discovered before and during performance of testing, adjusting, and
balancing procedures.

0.2 PREPARATION

TESTING, ADJUSTING, AND BALANCING 15990 - Page 5/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

A. Prepare a testing, adjusting, and balancing plan that includes strategies and step-by-step
procedures.

B. Complete system readiness checks and prepare system readiness reports. Verify the
following:

1. Permanent electrical power wiring is complete.


2. Hydronic systems are filled, clean, and free of air.
3. Automatic temperature-control systems are operational.
4. Equipment and duct access doors are securely closed.
5. Balance, smoke, and fire dampers are open.
6. Isolating and balancing valves are open and control valves are operational.
7. Ceilings are installed in critical areas where air-pattern adjustments are required and
access to balancing devices is provided.
8. Windows and doors can be closed so design conditions for system operations can be
met.

0.3 GENERAL TESTING AND BALANCING PROCEDURES

A. Perform testing and balancing procedures on each system according to the procedures
contained in SMACNA's "HVAC Systems--Testing, Adjusting, and Balancing" and this
Section.

B. Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the
minimum extent necessary to allow adequate performance of procedures. After testing and
balancing, close probe holes and patch insulation with new materials identical to those
removed. Restore vapor barrier and finish according to the insulation Specifications for this
Project.

C. Mark equipment settings with paint or other suitable, permanent identification material,
including damper-control positions, valve indicators, fan-speed-control levers, and similar
controls and devices, to show final settings.

0.4 FUNDAMENTAL AIR SYSTEMS' BALANCING PROCEDURES

A. Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and
recommended testing procedures. Crosscheck the summation of required outlet volumes
with required fan volumes.

B. Prepare schematic diagrams of systems' "as-built" duct layouts.

C. For variable-air-volume systems, develop a plan to simulate diversity.

D. Determine the best locations in main and branch ducts for accurate duct airflow
measurements.

E. Check the airflow patterns from the outside-air louvers and dampers and the return- and
exhaust-air dampers, through the supply-fan discharge and mixing dampers.

F. Locate start-stop and disconnect switches, electrical interlocks, and motor starters.

G. Verify that motor starters are equipped with properly sized thermal protection.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 6/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

H. Check dampers for proper position to achieve desired airflow path.

I. Check for airflow blockages.

J. Check condensate drains for proper connections and functioning.

K. Check for proper sealing of air-handling unit components.

0.5 CONSTANT-VOLUME AIR SYSTEMS' BALANCING PROCEDURES

A. The procedures in this Article apply to constant-volume supply-, return-, and exhaust-air
systems. Additional procedures are required for variable-air-volume, multizone, dual-duct,
induction-unit supply-air systems and process exhaust-air systems. These additional
procedures are specified in other articles in this Section.

B. Adjust fans to deliver total design airflows within the maximum allowable rpm listed by the
fan manufacturer.

1. Measure fan static pressures to determine actual static pressure as follows:

a. Measure outlet static pressure as far downstream from the fan as practicable
and upstream from restrictions in ducts such as elbows and transitions.
b. Measure static pressure directly at the fan outlet or through the flexible
connection.
c. Measure inlet static pressure of single-inlet fans in the inlet duct as near the fan
as possible, upstream from flexible connection and downstream from duct
restrictions.
d. Measure inlet static pressure of double-inlet fans through the wall of the
plenum that houses the fan.

2. Measure static pressure across each air-handling unit component.

a. Simulate dirty filter operation and record the point at which maintenance
personnel must change filters.

3. Measure static pressures entering and leaving other devices such as sound traps, heat
recovery equipment, and air washers under final balanced conditions.
4. Compare design data with installed conditions to determine variations in design static
pressures versus actual static pressures. Compare actual system effect factors with
calculated system effect factors to identify where variations occur. Recommend
corrective action to align design and actual conditions.
5. Adjust fan speed higher or lower than design with the approval of the Engineer.
Make required adjustments to pulley sizes, motor sizes, and electrical connections to
accommodate fan-speed changes.
6. Do not make fan-speed adjustments that result in motor overload. Consult equipment
manufacturers about fan-speed safety factors. Modulate dampers and measure fan-
motor amperage to ensure that no overload will occur. Measure amperage in full
cooling, full heating, and economizer modes to determine the maximum required
brake horsepower.

C. Adjust volume dampers for main duct, submain ducts, and major branch ducts to design
airflows within specified tolerances.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 7/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

1. Measure static pressure at a point downstream from the balancing damper and adjust
volume dampers until the proper static pressure is achieved.

a. Where sufficient space in submains and branch ducts is unavailable for Pitot-
tube traverse measurements, measure airflow at terminal outlets and inlets and
calculate the total airflow for that zone.

2. Remeasure each submain and branch duct after all have been adjusted. Continue to
adjust submains and branch ducts to design airflows within specified tolerances.

D. Measure terminal outlets and inlets without making adjustments.

1. Measure terminal outlets using a direct-reading hood or the outlet manufacturer's


written instructions and calculating factors.

E. Adjust terminal outlets and inlets for each space to design airflows within specified
tolerances of design values. Make adjustments using volume dampers rather than extractors
and the dampers at the air terminals.

1. Adjust each outlet in the same room or space to within specified tolerances of design
quantities without generating noise levels above the limitations prescribed by the
Contract Documents.
2. Adjust patterns of adjustable outlets for proper distribution without drafts.

0.6 VARIABLE-AIR-VOLUME SYSTEMS' ADDITIONAL PROCEDURES

A. Compensating for Diversity: When the total airflow of all terminal units is more than the
fan design airflow volume, place a selected number of terminal units at a maximum set-
point airflow condition until the total airflow of the terminal units equals the design airflow
of the fan. Select the reduced airflow terminal units so that they are distributed evenly
among the branch ducts.

B. Pressure-Independent, Variable-Air-Volume Systems: After the fan systems have been


adjusted, adjust the variable-air-volume systems as follows:

1. Set outside-air dampers at minimum, and return- and exhaust-air dampers at a


position that simulates full-cooling load.
2. Select the terminal unit that is most critical to the supply-fan airflow and static
pressure. Measure static pressure. Adjust system static pressure so that the entering
static pressure for the critical terminal unit is not less than the sum of the terminal
unit manufacturer's recommended minimum inlet static pressure plus the static
pressure needed to overcome terminal-unit discharge duct losses.
3. Measure total system airflow. Adjust to within 10 percent of design airflow.
4. Set terminal units at maximum airflow and adjust controller or regulator to deliver the
designed maximum airflow. Use the terminal unit manufacturer's written instructions
to make this adjustment. When total airflow is correct, balance the air outlets
downstream from terminal units as described for constant-volume air systems.
5. Set terminal units at minimum airflow and adjust controller or regulator to deliver the
designed minimum airflow. Check air outlets for a proportional reduction in airflow
as described for constant-volume air systems.

a. If air outlets are out of balance at minimum airflow, report the condition but
leave the outlets balanced for maximum airflow.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 8/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

6. Remeasure the return airflow to the fan while operating at maximum return airflow
and minimum outside airflow. Adjust the fan and balance the return-air ducts and
inlets as described for constant-volume air systems.
7. Measure static pressure at the most critical terminal unit and adjust the static-pressure
controller at the main supply-air sensing station to ensure adequate static pressure is
maintained at the most critical unit.
8. Record the final fan performance data.

0.7 FUNDAMENTAL PROCEDURES FOR HYDRONIC SYSTEMS

A. Prepare test reports with pertinent design data and number in sequence starting at pump to
end of system. Check the sum of branch-circuit flows against approved pump flow rate.
Correct variations that exceed plus or minus 5 percent.

B. Prepare schematic diagrams of systems' "as-built" piping layouts.

C. Prepare hydronic systems for testing and balancing according to the following, in addition
to the general preparation procedures specified above:

1. Open all manual valves for maximum flow.


2. Check expansion tank liquid level.
3. Check makeup-water-station pressure gage for adequate pressure for highest vent.
4. Check flow-control valves for specified sequence of operation and set at design flow.
5. Set differential-pressure control valves at the specified differential pressure. Do not
set at fully closed position when pump is positive-displacement type, unless several
terminal valves are kept open.
6. Set system controls so that automatic valves are wide open to heat exchangers.
7. Check pump-motor load. If motor is overloaded, throttle main flow-balancing device
so that motor nameplate rating is not exceeded.
8. Check air vents for a forceful liquid flow exiting from vents when manually operated.

0.8 HYDRONIC SYSTEMS' BALANCING PROCEDURES

A. Determine water flow at pumps. Use the following procedures, except for positive-
displacement pumps:

1. Verify impeller size by operating the pump with the discharge valve closed. Verify
with the pump manufacturer that this will not damage pump. Read pressure
differential across the pump. Convert pressure to head and correct for differences in
gage heights. Note the point on the manufacturer's pump curve at zero flow and
confirm that the pump has the intended impeller size.
2. Check system resistance. With all valves open, read pressure differential across the
pump and mark the pump manufacturer's head-capacity curve. Adjust pump
discharge valve until design water flow is achieved.
3. Verify pump-motor brake horsepower. Calculate the intended brake horsepower for
the system based on the pump manufacturer's performance data. Compare calculated
brake horsepower with nameplate data on the pump motor. Report conditions where
actual amperage exceeds motor nameplate amperage.
4. Report flow rates that are not within plus or minus 5 percent of design.

B. Set calibrated balancing valves, if installed, at calculated presettings.

C. Measure flow at all stations and adjust, where necessary, to obtain first balance.
TESTING, ADJUSTING, AND BALANCING 15990 - Page 9/21
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

1. System components that have Cv rating or an accurately cataloged flow-pressure-


drop relationship may be used as a flow-indicating device.

D. Measure flow at main balancing station and set main balancing device to achieve flow that
is 5 percent greater than design flow.

E. Adjust balancing stations to within specified tolerances of design flow rate as follows:

1. Determine the balancing station with the highest percentage over design flow.
2. Adjust each station in turn, beginning with the station with the highest percentage
over design flow and proceeding to the station with the lowest percentage over design
flow.
3. Record settings and mark balancing devices.

F. Measure pump flow rate and make final measurements of pump amperage, voltage, rpm,
pump heads, and systems' pressures and temperatures, including outdoor-air temperature.

G. Measure the differential-pressure control valve settings existing at the conclusions of


balancing.

0.9 VARIABLE-FLOW HYDRONIC SYSTEMS' ADDITIONAL PROCEDURES

A. Balance systems with automatic 2- and 3-way control valves by setting systems at
maximum flow through heat-exchange terminals and proceed as specified above for
hydronic systems.

0.10 PRIMARY-SECONDARY-FLOW HYDRONIC SYSTEMS' ADDITIONAL


PROCEDURES

A. Balance the primary system crossover flow first, then balance the secondary system.

0.11 MOTORS

A. Motors, 1/2 HP and Larger: Test at final balanced conditions and record the following data:

1. Manufacturer, model, and serial numbers.


2. Motor horsepower rating.
3. Motor rpm.
4. Efficiency rating if high-efficiency motor.
5. Nameplate and measured voltage, each phase.
6. Nameplate and measured amperage, each phase.
7. Starter thermal-protection-element rating.

B. Motors Driven by Variable-Frequency Controllers: Test for proper operation at speeds


varying from minimum to maximum. Test the manual bypass for the controller to prove
proper operation. Record observations, including controller manufacturer, model and serial
numbers, and nameplate data.

0.12 CHILLERS

TESTING, ADJUSTING, AND BALANCING 15990 - Page 10/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

A. Balance water flow through each evaporator and condenser to within specified tolerances of
design flow with all pumps operating. With only one chiller operating in a multiple chiller
installation, do not exceed the flow for the maximum tube velocity recommended by the
chiller manufacturer. Measure and record the following data with each chiller operating at
design conditions:

1. Evaporator water entering and leaving temperatures, pressure drop, and water flow.
2. Condenser water entering and leaving temperatures, pressure drop, and water flow.
3. Evaporator and condenser refrigerant temperatures and pressures, using instruments
furnished by the chiller manufacturer.
4. Power factor if factory-installed instrumentation is furnished for measuring kW.
5. The kW input if factory-installed instrumentation is furnished for measuring kW.
6. Capacity: Calculate in tons of cooling.

0.13 COOLING TOWERS

A. Shut off makeup water for the duration of the test, and then make sure the makeup and
blow-down systems are fully operational after tests and before leaving the equipment.
Perform the following tests and record the results:

1. Measure condenser water flow to each cell of the cooling tower.


2. Measure entering- and leaving-water temperatures.
3. Measure wet- and dry-bulb temperatures of entering air.
4. Measure wet- and dry-bulb temperatures of leaving air.
5. Measure condenser water flow rate recirculating through the cooling tower.
6. Measure cooling tower pump discharge pressure.
7. Adjust water level and feed rate of makeup-water system.

0.14 CONDENSING UNITS

A. Verify proper rotation of fans and measure entering- and leaving-air temperatures. Record
compressor data.

0.15 BOILERS

A. Measure entering- and leaving-water temperatures and water flow.

0.16 HEAT-TRANSFER COILS

A. Water Coils: Measure the following data for each coil:

1. Entering- and leaving-water temperatures.


2. Water flow rate.
3. Water pressure drop.
4. Dry-bulb temperatures of entering and leaving air.
5. Wet-bulb temperatures of entering and leaving air for cooling coils designed for less
than 3540 L/s.
6. Airflow.
7. Air pressure drop.

B. Electric-Heating Coils: Measure the following data for each coil:

TESTING, ADJUSTING, AND BALANCING 15990 - Page 11/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

1. Nameplate data.
2. Airflow.
3. Entering- and leaving-air temperatures at full load.
4. Voltage and amperage input of each phase at full load and at each incremental stage.
5. Calculated kW at full load.
6. Fuse or circuit-breaker rating for overload protection.

0.17 TEMPERATURE TESTING

A. During testing, adjusting, and balancing, report need for adjustment in temperature
regulation within the automatic temperature-control system.

B. Measure indoor wet- and dry-bulb temperatures every other hour for a period of 2
successive 8-hour days, in each separately controlled zone, to prove correctness of final
temperature settings. Measure when the building or zone is occupied.

C. Measure outside-air, wet- and dry-bulb temperatures.

0.18 TEMPERATURE-CONTROL VERIFICATION

A. Verify that controllers are calibrated and commissioned.

B. Check transmitter and controller locations and note conditions that would adversely affect
control functions.

C. Record controller settings and note variances between set points and actual measurements.

D. Verify operation of limiting controllers (i.e., high- and low-temperature controllers).

E. Verify free travel and proper operation of control devices such as damper and valve
operators.

F. Verify sequence of operation of control devices. Note air pressures and device positions
and correlate with airflow and water-flow measurements. Note the speed of response to
input changes.

G. Confirm interaction of electrically operated switch transducers.

H. Confirm interaction of interlock and lockout systems.

I. Verify main control supply-air pressure and observe compressor and dryer operations.

J. Record voltages of power supply and controller output. Determine if the system operates on
a grounded or nongrounded power supply.

K. Note operation of electric actuators using spring return for proper fail-safe operations.

0.19 TOLERANCES

A. Set HVAC system airflow and water flow rates within the following tolerances:

1. Supply, Return, and Exhaust Fans: Plus 5 to plus 10 percent.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 12/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

2. Air Outlets and Inlets: 0 to minus 10 percent.


3. Cooling-Water Flow Rate: 0 to minus 5 percent.

0.20 REPORTING

A. Initial Construction-Phase Report: Based on examination of the Contract Documents as


specified in "Examination" Article above, prepare a report on the adequacy of design for
systems' balancing devices. Recommend changes and additions to systems' balancing
devices to facilitate proper performance measuring and balancing. Recommend changes
and additions to HVAC systems and general construction to allow access for performance
measuring and balancing devices.

B. Status Reports: As Work progresses, prepare reports to describe completed procedures,


procedures in progress, and scheduled procedures. Include a list of deficiencies and
problems found in systems being tested and balanced. Prepare a separate report for each
system and each building floor for systems serving multiple floors.

0.21 FINAL REPORT

A. General: Typewritten, or computer printout in letter-quality font, on standard bond paper, in


3-ring binder, tabulated and divided into sections by tested and balanced systems.

B. Include a certification sheet in front of binder signed and sealed by the certified testing and
balancing engineer.

1. Include a list of the instruments used for procedures, along with proof of calibration.

C. Final Report Contents: In addition to the certified field report data, include the following:

1. Pump curves.
2. Fan curves.
3. Manufacturers' test data.
4. Field test reports prepared by system and equipment installers.
5. Other information relative to equipment performance, but do not include approved
Shop Drawings and Product Data.

D. General Report Data: In addition to the form titles and entries, include the following data in
the final report, as applicable:

1. Title page.
2. Name and address of testing, adjusting, and balancing Agent.
3. Project name.
4. Project location.
5. Engineer's name and address.
6. Contractor's name and address.
7. Report date.
8. Signature of testing, adjusting, and balancing Agent who certifies the report.
9. Summary of contents, including the following:

a. Design versus final performance.


b. Notable characteristics of systems.
c. Description of system operation sequence if it varies from the Contract
Documents.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 13/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

10. Nomenclature sheets for each item of equipment.


11. Data for terminal units, including manufacturer, type size, and fittings.
12. Notes to explain why certain final data in the body of reports vary from design
values.
13. Test conditions for fans and pump performance forms, including the following:

a. Settings for outside-, return-, and exhaust-air dampers.


b. Conditions of filters.
c. Cooling coil, wet- and dry-bulb conditions.
d. Face and bypass damper settings at coils.
e. Fan drive settings, including settings and percentage of maximum pitch
diameter.
f. Inlet vane settings for variable-air-volume systems.
g. Settings for supply-air, static-pressure controller.
h. Other system operating conditions that affect performance.

E. System Diagrams: Include schematic layouts of air and hydronic distribution systems.
Present with single-line diagrams and include the following:

1. Quantities of outside, supply, return, and exhaust airflows.


2. Water and steam flow rates.
3. Duct, outlet, and inlet sizes.
4. Pipe and valve sizes and locations.
5. Terminal units.
6. Balancing stations.

F. Air-Handling Unit Test Reports: For air-handling units with coils, include the following:

1. Unit Data: Include the following:

a. Unit identification.
b. Location.
c. Make and type.
d. Model number and unit size.
e. Manufacturer's serial number.
f. Unit arrangement and class.
g. Discharge arrangement.
h. Sheave make, size in mm, and bore.
i. Sheave dimensions, center-to-center and amount of adjustments in mm.
j. Number of belts, make, and size.
k. Number of filters, type, and size.

2. Motor Data: Include the following:

a. Make and frame type and size.


b. Horsepower and rpm.
c. Volts, phase, and hertz.
d. Full-load amperage and service factor.
e. Sheave make, size in mm, and bore.
f. Sheave dimensions, center-to-center and amount of adjustments in mm.

3. Test Data: Include design and actual values for the following:

a. Total airflow rate in L/s.


b. Total system static pressure in Pa.
TESTING, ADJUSTING, AND BALANCING 15990 - Page 14/21
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

c. Fan rpm.
d. Discharge static pressure in Pa.
e. Filter static-pressure differential in Pa.
f. Cooling coil static-pressure differential in Pa.
g. Heating coil static-pressure differential in Pa.
h. Outside airflow in L/s.
i. Return airflow in L/s.
j. Outside-air damper position.
k. Return-air damper position.
l. Vortex damper position.

G. Apparatus-Coil Test Reports: For apparatus coils, include the following:

1. Coil Data: Include the following:

a. System identification.
b. Location.
c. Coil type.
d. Number of rows.
e. Fin spacing in mm o.c..
f. Make and model number.
g. Face area in sq. m.
h. Tube size in DN.
i. Tube and fin materials.
j. Circuiting arrangement.

2. Test Data: Include design and actual values for the following:

a. Airflow rate in L/s.


b. Average face velocity in m/s.
c. Air pressure drop in Pa.
d. Outside-air, wet- and dry-bulb temperatures in deg. C.
e. Return-air, wet- and dry-bulb temperatures in deg. C.
f. Entering-air, wet- and dry-bulb temperatures in deg. C.
g. Leaving-air, wet- and dry-bulb temperatures in deg. C.
h. Water flow rate in L/s.
i. Water pressure differential in kPa.
j. Entering-water temperature in deg. C.
k. Leaving-water temperature in deg. C.
l. Refrigerant expansion valve and refrigerant types.
m. Refrigerant suction pressure in kPa.
n. Refrigerant suction temperature in deg. C.
o. Inlet steam pressure in kPa.

H. Electric-Coil Test Reports: For electric furnaces, duct coils, and electric coils installed in
central-station air-handling units, include the following:

1. Unit Data: Include the following:

a. System identification.
b. Location.
c. Coil identification.
d. Capacity in kW.
e. Number of stages.
f. Connected volts, phase, and hertz.
TESTING, ADJUSTING, AND BALANCING 15990 - Page 15/21
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

g. Rated amperage.
h. Airflow rate in L/s.
i. Face area in sq. m.
j. Minimum face velocity in m/s.

2. Test Data: Include design and actual values for the following:

a. Heat output in kW.


b. Airflow rate in L/s.
c. Air velocity in m/s.
d. Entering-air temperature in deg. C.
e. Leaving-air temperature in deg. C.
f. Voltage at each connection.
g. Amperage for each phase.

I. Fan Test Reports: For supply, return, and exhaust fans, include the following:

1. Fan Data: Include the following:

a. System identification.
b. Location.
c. Make and type.
d. Model number and size.
e. Manufacturer's serial number.
f. Arrangement and class.
g. Sheave make, size in mm, and bore.
h. Sheave dimensions, center-to-center and amount of adjustments in mm.

2. Motor Data: Include the following:

a. Make and frame type and size.


b. Horsepower and rpm.
c. Volts, phase, and hertz.
d. Full-load amperage and service factor.
e. Sheave make, size in mm , and bore.
f. Sheave dimensions, center-to-center and amount of adjustments in mm.
g. Number of belts, make, and size.

3. Test Data: Include design and actual values for the following:

a. Total airflow rate in L/s.


b. Total system static pressure in Pa.
c. Fan rpm.
d. Discharge static pressure in Pa.
e. Suction static pressure in Pa.

J. Round, Flat-Oval, and Rectangular Duct Traverse Reports: Include a diagram with a grid
representing the duct cross-section and record the following:

1. Report Data: Include the following:

a. System and air-handling unit number.


b. Location and zone.
c. Traverse air temperature in deg. C.
d. Duct static pressure in Pa.
TESTING, ADJUSTING, AND BALANCING 15990 - Page 16/21
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

e. Duct size in mm.


f. Duct area in sq. m.
g. Design airflow rate in L/s.
h. Design velocity in m/s.
i. Actual airflow rate in L/s.
j. Actual average velocity in m/s.
k. Barometric pressure in Pa.

K. Air-Terminal-Device Reports: For terminal units, include the following:

1. Unit Data: Include the following:

a. System and air-handling unit identification.


b. Location and zone.
c. Test apparatus used.
d. Area served.
e. Air-terminal-device make.
f. Air-terminal-device number from system diagram.
g. Air-terminal-device type and model number.
h. Air-terminal-device size.
i. Air-terminal-device effective area in sq. m.

2. Test Data: Include design and actual values for the following:

a. Airflow rate in L/s.


b. Air velocity in m/s.
c. Preliminary airflow rate as needed in L/s.
d. Preliminary velocity as needed in m/s.
e. Final airflow rate in L/s.
f. Final velocity in m/s.
g. Space temperature in deg. C.

L. System-Coil Reports: For reheat coils and water coils of terminal units, include the
following:

1. Unit Data: Include the following:

a. System and air-handling unit identification.


b. Location and zone.
c. Room or riser served.
d. Coil make and size.
e. Flowmeter type.

2. Test Data: Include design and actual values for the following:

a. Airflow rate in L/s.


b. Entering-water temperature in deg. C.
c. Leaving-water temperature in deg. C.
d. Water pressure drop in kPa.
e. Entering-air temperature in deg. C.
f. Leaving-air temperature in deg. C.

M. Packaged Chiller Reports: For each chiller, include the following:

1. Unit Data: Include the following:


TESTING, ADJUSTING, AND BALANCING 15990 - Page 17/21
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

a. Unit identification.
b. Make and model number.
c. Manufacturer's serial number.
d. Refrigerant type and capacity in L.
e. Starter type and size.
f. Starter thermal protection size.

2. Condenser Test Data: Include design and actual values for the following:

a. Refrigerant pressure in kPa.


b. Refrigerant temperature in deg. C.
c. Entering-water temperature in deg. C.
d. Leaving-water temperature in deg. C.
e. Entering-water pressure in kPa.
f. Water pressure differential in kPa.

3. Evaporator Test Reports: Include design and actual values for the following:

a. Refrigerant pressure in kPa.


b. Refrigerant temperature in deg. C.
c. Entering-water temperature in deg. C.
d. Leaving-water temperature in deg. C.
e. Entering-water pressure in kPa.
f. Water pressure differential in kPa.

4. Compressor Test Data: Include design and actual values for the following:

a. Make and model number.


b. Manufacturer's serial number.
c. Suction pressure in kPa.
d. Suction temperature in deg. C.
e. Discharge pressure in kPa.
f. Discharge temperature in deg. C.
g. Oil pressure in kPa.
h. Oil temperature in deg. C.
i. Voltage at each connection.
j. Amperage for each phase.
k. The kW input.
l. Crankcase heater kW.
m. Chilled water control set point in deg. C.
n. Condenser water control set point in deg. C.
o. Refrigerant low-pressure-cutoff set point in kPa.
p. Refrigerant high-pressure-cutoff set point in kPa.

5. Refrigerant Test Data: Include design and actual values for the following:

a. Oil level.
b. Refrigerant level.
c. Relief valve setting in kPa.
d. Unloader set points in kPa.
e. Percentage of cylinders unloaded.
f. Bearing temperatures in deg. C.
g. Vane position.
h. Low-temperature-cutoff set point in deg. C.

TESTING, ADJUSTING, AND BALANCING 15990 - Page 18/21


STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

N. Compressor and Condenser Reports: For refrigerant side of unitary systems, stand-alone
refrigerant compressors, air-cooled condensing units, or water-cooled condensing units,
include the following:

1. Unit Data: Include the following:

a. Unit identification.
b. Location.
c. Unit make and model number.
d. Manufacturer's compressor serial numbers.
e. Compressor make.
f. Compressor model and serial numbers.
g. Refrigerant weight in kg.
h. Low ambient temperature cutoff in deg. C.

2. Test Data: Include design and actual values for the following:

a. Inlet-duct static pressure in Pa.


b. Outlet-duct static pressure in Pa.
c. Entering-air, dry-bulb temperature in deg. C.
d. Leaving-air, dry-bulb temperature in deg. C.
e. Condenser entering-water temperature in deg. C.
f. Condenser leaving-water temperature in deg. C.
g. Condenser water temperature differential in deg. C.
h. Condenser entering-water pressure in kPa.
i. Condenser leaving-water pressure in kPa.
j. Condenser water pressure differential in kPa.
k. Control settings.
l. Unloader set points.
m. Low-pressure-cutout set point in kPa.
n. High-pressure-cutout set point in kPa.
o. Suction pressure in kPa.
p. Suction temperature in deg. C.
q. Condenser refrigerant pressure in kPa.
r. Condenser refrigerant temperature in deg. C.
s. Oil pressure in kPa.
t. Oil temperature in deg. C.
u. Voltage at each connection.
v. Amperage for each phase.
w. The kW input.
x. Crankcase heater kW.
y. Number of fans.
z. Condenser fan rpm.
aa. Condenser fan airflow rate in L/s.
bb. Condenser fan motor make, frame size, rpm, and horsepower.
cc. Condenser fan motor voltage at each connection.
dd. Condenser fan motor amperage for each phase.

O. Cooling Tower or Condenser Test Reports: For cooling towers or condensers, include the
following:

1. Unit Data: Include the following:

a. Unit identification.
b. Make and type.
TESTING, ADJUSTING, AND BALANCING 15990 - Page 19/21
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

c. Model and serial numbers.


d. Nominal cooling capacity in kW.
e. Refrigerant type and weight in kg.
f. Water-treatment chemical feeder and chemical.
g. Number and type of fans.
h. Fan motor make, frame size, rpm, and horsepower.
i. Fan motor voltage at each connection.
j. Sheave make, size in mm, and bore.
k. Sheave dimensions, center-to-center and amount of adjustments in mm.
l. Number of belts, make, and size.

2. Pump Test Data: Include design and actual values for the following:

a. Make and model number.


b. Manufacturer's serial number.
c. Motor make and frame size.
d. Motor horsepower and rpm.
e. Voltage at each connection.
f. Amperage for each phase.
g. Water flow rate in L/s .

3. Water Test Data: Include design and actual values for the following:

a. Entering-water temperature in deg. C.


b. Leaving-water temperature in deg. C.
c. Water temperature differential in deg. C.
d. Entering-water pressure in kPa.
e. Leaving-water pressure in kPa.
f. Water pressure differential in kPa.
g. Water flow rate in L/s.
h. Bleed water flow rate in L/s.

4. Air Data: Include design and actual values for the following:

a. Duct airflow rate in L/s.


b. Inlet-duct static pressure in Pa.
c. Outlet-duct static pressure in Pa.
d. Average entering-air, wet-bulb temperature in deg. C.
e. Average leaving-air, wet-bulb temperature in deg. C.
f. Ambient wet-bulb temperature in deg. C.

P. Pump Test Reports: For pumps, include the following data. Calculate impeller size by
plotting the shutoff head on pump curves.

1. Unit Data: Include the following:

a. Unit identification.
b. Location.
c. Service.
d. Make and size.
e. Model and serial numbers.
f. Water flow rate in L/s.
g. Water pressure differential in kPa.
h. Required net positive suction head in kPa.
i. Pump rpm.
TESTING, ADJUSTING, AND BALANCING 15990 - Page 20/21
STD-SPC-DCA(A1)-ME-DCA REV A
<Project Title>

PROJECT STANDARD SPECIFICATION

j. Impeller diameter in mm.


k. Motor make and frame size.
l. Motor horsepower and rpm.
m. Voltage at each connection.
n. Amperage for each phase.
o. Full-load amperage and service factor.
p. Seal type.

2. Test Data: Include design and actual values for the following:

a. Static head in kPa.


b. Pump shutoff pressure in kPa.
c. Actual impeller size in mm.
d. Full-open flow rate in L/s.
e. Full-open pressure in kPa.
f. Final discharge pressure in kPa.
g. Final suction pressure in kPa.
h. Final total pressure in kPa.
i. Final water flow rate in L/s.
j. Voltage at each connection.
k. Amperage for each phase.

Q. Instrument Calibration Reports: For instrument calibration, include the following:

1. Report Data: Include the following:

a. Instrument type and make.


b. Serial number.
c. Application.
d. Dates of use.
e. Dates of calibration.

0.22 ADDITIONAL TESTS

A. Within 90 days of completing testing, adjusting, and balancing, perform additional testing
and balancing to verify that balanced conditions are being maintained throughout and to
correct unusual conditions.

B. Seasonal Periods: If initial testing, adjusting, and balancing procedures were not performed
during near-peak summer and winter conditions, perform additional inspections, testing, and
adjusting during near-peak summer and winter conditions.

END OF SECTION 15990

TESTING, ADJUSTING, AND BALANCING 15990 - Page 21/21


STD-SPC-DCA(A1)-ME-DCA REV A

You might also like