Introduction Termination Board Solutions for Emerson DeltaV
The Catalog
This catalog presents the product portfolio of Termination Board solutions for Emerson DeltaV and, compiled by our inhouse
Termination Board experts, shares concise technical knowledge based on years of substantiated experience.
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels
Channels
Channels
Modules
DeltaV
Series
Series
Type
Type
Card
Digital Inputs
(NAMUR) HiD2844 66
S 32-channel DI simplex 32 HiDTB04-DVM-IDC1-SC-R1-DI16 4 16 32 HiD2844 4 66
(24 V DC, dry contact)
S 32-channel DI Plus 32 HiDTB04-DVM-IDC1-SC-R2-DI16 4 16 36 HiD2844 4 66
(24 V DC, dry contact) redundant
Digital Outputs
Digital Outputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels
Channels
Channels
Modules
Series
Type
Type
Type
Card
Analog Ouputs
Analog Inputs/
(24 V DC, high side) simplex HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2872 2 67
M 32-channel DO Series 2 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
The product data sheets contain all of the relevant data necessary to select and specify the equipment. It includes four major
(24 V DC, high side) simplex
M 32-channel DO Series 2 Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) redundant
sections: Features, Function, Technical Data, and Diagrams. Surrounding these key elements are navigation tools necessary to
S 8-channel DO
(24 V DC, high side)
simplex 8 HiDTB04-DVM-IDC3-SC-R2-DO08
HiDTB08-DVM-IDC4-SC-R1-SM32
4
8 16
8 40
52
HiD2872
HiD2872
2
2
67
67
help identify the product including special colors, markings, and symbols.
S 32-channel DO
(24 V DC, high side)
simplex 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
Universal
S 32-channel DO Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
Comprehensive product information can be found at www.pepperl-fuchs.com. (24 V DC, high side) redundant
Product highlights
08/2015
265151
HiD2844
Function description
Switch Amplifier
Edition
HiD2844
Color-coded
• Dry contact or NAMUR inputs Input
• System Board for Emerson
• 4 passive DeltaV
transistor outputs Rated values acc. to EN 60947-5-6 (NAMUR)
• For one 32-channel
• Line fault DI detection
card via 40-pin
(LFD)Mass Termination Connectable sensor types potential free contact or proximity sensor
navigation tabs
H-System
Block Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
• Up to SIL2 acc. to IEC 61508
• For 4 modules/16 channels Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum
• RecommendedFunctionmodule: HiD2844 (DI) value
Output
• Volt-free fault indication output
DeltaV
Termination Boards
safety applications. It transfers digital Rated current In 50 mA
daisychainable
signals (NAMUR sensors/mechanical Output one optocoupled transistor per channel
• Hazardous area: screw terminals, blue Signal level 1-signal: (external voltage) -1 V
contacts) from a hazardous area to a safe
• Safe area:area.
IDC connector, 20-pin 0-signal: blocked output (off-state current max. 50 A,
typical 5 A)
H-System
Function The proximity sensor or switch controls a Error message output
Digital Inputs
passive transistor for the safe area load. Output type open collector transistor (internal fault bus)
The
The function of themodule outputBoard
Termination changes state
as well aswhen
the connector
Transfer characteristics
pin assignmenttheexactly
input signal
fit thechanges state.
requirement ofThe normal
DeltaV Traditional
Switching frequency < 2 kHz
Digital Inputs
I/O systems. output state can be reversed with the Ambient conditions
selector switches on the side of the unit. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Information about line fault detection of the interface modules
Line
is available for thefault
systemdetection (LFD) contact.
as volt-free can be selected Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
or disabled via a selector switch. Mechanical specifications
The Termination Boards are supplied with a robust plastic Degree of protection IP20
During an error condition, the transistor
Digital Outputs
housing as standard. This design permits the fast and reliable Mass approx. 140 g
reverts to its de-energized state and the
installation on 35 mm DIN mounting rail acc. to EN 60715 inDimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
the cabinet. LEDs indicate the fault. A separate fault
Mounting on Termination Board
output bus is available. The fault
Digital Outputs
Diagrams
Connection
LED green:
24 V DC (I),
Universal
Power supply
HiD2844
24 V DC (II),
1.5 kΩ SL2 SL1
PWR
LEDs red:
Line fault
1.5 kΩ FAULT STATUS
LEDs yellow:
Status output I + 1 Fault
5a 8a 11 + I
1+ 10 kΩ
channel 1 ... 4 channel 1 ... 4
CH 1
I 10 kΩ CH 2 1.5 kΩ - 4 5b 7a 14 -
4- + 2 1a 10a 12 + II
II
Accessories
10 kΩ
1.5 kΩ
CH 3
2+
Connection diagram
- 5 1b 9a 15 -
CH 4
Amplifier
3+
III 10 kΩ
IV 3 10 kΩ
+ 7 7a 8b 17 + IV
08/2015
- 8 7b 7b 18 -
6-
1.5 kΩ
Place for 2 DeltaV 32DI
7+ labeling 1a, 1b - 24 V DC
IV 10 kΩ 1 2a, 2b +
FAULT
6b
265151
8-
08/2015
Zone 0, 1, 2
3 2 1
On the website, you can narrow your search and find the
product information you need in two different ways:
To find information about a specific product, use the
search function. Here, you can choose the following:
To find a product based on specific features, use the a list of products or
product selector.
4
3
2
1
8
X1
7
6
5
4
3
2
Figure 3 Cable CAB-DVM-**-S37I**-**-***** 1
Termination Boards
Marking The device is not suitable for isolating signals in power
installations unless this is noted separately in the
H-System, isolated barriers corresponding datasheet.
Device identification Mounting and Installation
Model number Do not mount a damaged or polluted device.
ATEX approval
Mount the device in a way that the device is protected against
Group, category, type of protection, temperature classification mechanical hazard. Mount the device in a surrounding
enclosure for example.
The exact designation of the device can be found on the name The device must be installed outside of the hazardous area.
plate on the device side.
Mount the device with at least a degree of protection of IP20
Pepperl+Fuchs GmbH according to IEC/EN 60529.
Lilienthalstraße 200, 68307 Mannheim, Germany The device must be installed and operated only in an
Description
environment that ensures a pollution degree 2 (or better)
System
Target Group, Personnel according to IEC/EN 60664-1.
Responsibility for planning, assembly, commissioning, If used in areas with higher pollution degree, the device needs
operation, maintenance, and dismounting lies with the plant to be protected accordingly.
operator. All circuits connected to the device must comply with the
Mounting, installation, commissioning, operation, maintenance overvoltage category II (or better) according to
and dismounting of the device may only be carried out by IEC/EN 60664-1.
appropriate trained and qualified personnel. The instruction Observe the installation instructions according to
manual must be read and understood. IEC/EN 60079-14.
Prior to using the device you should make yourself familiar with Requirements for Usage as Associated Apparatus
the device and carefully read the instruction manual.
If circuits with type of protection Ex i are operated with non-
Reference to Further Documentation intrinsically safe circuits, they must no longer be used as
circuits with type of protection Ex i.
Observe laws, standards, and directives applicable to the
intended use and the operating location. Intrinsically safe circuits of associated apparatus can be led
into hazardous areas. Observe the compliance of the
The corresponding datasheets, declarations of conformity,
separation distances to all non-intrinsically safe circuits
EC-type-examination certificates, certificates and control
according to IEC/EN 60079-14.
drawings if applicable supplement this document. You can find
this information under www.pepperl-fuchs.com. Observe the compliance of the separation distances between
two adjacent intrinsically safe circuits according to
Observe the instruction manuals for the respective
IEC/EN 60079-14.
Termination Boards.
Observe the maximum values of the device, when connecting
Intended Use the device to intrinsically safe apparatus.
The device is only approved for appropriate and intended use. When connecting intrinsically safe devices with intrinsically
Ignoring these instructions will void any warranty and absolve safe circuits of associated apparatus, observe the maximum
the manufacturer from any liability. peak values with regard to explosion protection (verification of
The device is used in control and instrumentation technology intrinsic safety). Observe the standards IEC/EN 60079-14 or
(C&I technology) for the galvanic isolation of signals such as IEC/EN 60079-25.
20 mA and 10 V standard signals or alternatively for adapting
or standardizing signals. The device has intrinsically safe
circuits that are used for operating intrinsically safe field
devices in hazardous areas.
Only use the module with the designated Termination Boards.
Use the device only within the specified ambient conditions.
Only use the device stationary.
The device is an associated apparatus according to
11/2015
IEC/EN 60079-11.
265151
Edition
If no Lo and Co values are specified for the simultaneous Instruction Manual Termination Boards
appearance of lumped inductances and capacitances, the
following rule applies. Marking
• The specified value for Lo and Co is used if one of the
Termination Boards
The devices must not be repaired, changed or manipulated. If Observe laws, standards, and directives applicable to the
there is a defect, the product must always be replaced with an intended use and the operating location.
original device. The corresponding datasheets, declarations of conformity,
EC-type-examination certificates, certificates and control
Delivery, Transport, Disposal
drawings if applicable supplement this document. You can find
Check the packaging and contents for damage. this information under www.pepperl-fuchs.com.
Check if you have received every item and if the items Observe the instruction manuals for the respective modules.
received are the ones you ordered.
Intended Use
Always store and transport the device in the original
packaging. The device is only approved for appropriate and intended use.
Ignoring these instructions will void any warranty and absolve
Store the device in a clean and dry environment. The permitted the manufacturer from any liability.
ambient conditions (see datasheet) must be considered.
The device is used in instrumentation and control technology
Disposing of device, packaging, and possibly contained (I&C technology). The device is used for the galvanic isolation
batteries must be in compliance with the applicable laws and of intrinsically safe circuits and non-intrinsically safe circuits.
guidelines of the respective country. The device is used as interface between modules, field circuits
and control circuits.
Only use the Termination Board with the designated modules.
Use the device only within the specified ambient conditions.
Only use the device stationary.
The device is an associated apparatus according to
IEC/EN 60079-11.
11/2015
265151
Edition
Termination Boards
The device is not suitable for isolating signals in power IEC/EN 60079-25.
installations unless this is noted separately in the
corresponding datasheet. If more channels of one device are connected in parallel,
ensure the parallel connection is made directly at the terminals
Mounting and Installation of the device. When verifying the intrinsic safety, observe the
Do not mount a damaged or polluted device. maximum values for the parallel connection.
Mount the device in a way that the device is protected against Operation, Maintenance, Repair
mechanical hazard. Mount the device in a surrounding The devices must not be repaired, changed or manipulated. If
enclosure for example. there is a defect, the product must always be replaced with an
The device must be installed outside of the hazardous area. original device.
Mount the device with at least a degree of protection of IP20 Delivery, Transport, Disposal
according to IEC/EN 60529.
Check the packaging and contents for damage.
The device must be installed and operated only in an
Check if you have received every item and if the items
Description
environment that ensures a pollution degree 2 (or better)
System
received are the ones you ordered.
according to IEC/EN 60664-1.
Always store and transport the device in the original
If used in areas with higher pollution degree, the device needs
packaging.
to be protected accordingly.
Store the device in a clean and dry environment. The permitted
All circuits connected to the device must comply with the
ambient conditions (see datasheet) must be considered.
overvoltage category II (or better) according to
IEC/EN 60664-1. Disposing of device, packaging, and possibly contained
batteries must be in compliance with the applicable laws and
Observe the installation instructions according to
guidelines of the respective country.
IEC/EN 60079-14.
Observe the corresponding documentation or the information
on the device for the correct assignment of the terminals to the
modules and their respective channels.
Requirements for Cables and Connection Lines
Observe the following points when installing cables and
connection lines:
Observe the permissible core cross-section of the conductor.
If you use stranded conductors, crimp wire end ferrules on the
conductor ends.
Use only one conductor per terminal.
When installing the conductors the insulation must reach up to
the terminal.
Observe the tightening torque of the terminal screws.
Requirements for Usage as Associated Apparatus
If circuits with type of protection Ex i are operated with non-
intrinsically safe circuits, they must no longer be used as
circuits with type of protection Ex i.
Intrinsically safe circuits of associated apparatus can be led
into hazardous areas. Observe the compliance of the
separation distances to all non-intrinsically safe circuits
according to IEC/EN 60079-14.
Observe the compliance of the separation distances between
two adjacent intrinsically safe circuits according to
IEC/EN 60079-14.
The intrinsically safe circuits are provided by the connected
11/2015
modules.
Observe the maximum values of the device, when connecting
265151
STATUS
FAULT
CH 2 CH 1
HiD
Description
2872
2 ch
Solenoid
System
Driver
Termination Boards
refer to the documentation for the respective device for the
control side via the Termination Boards. Once the isolated specific connection layout.
barrier is mounted, the signal circuit between the field and
control side is closed. Connecting the Field Side
The field devices can be connected to the Termination Board
1 2 3 via screw terminals:
4 CN4 CN3
mA CN2
4 3
6 5 4
X20
CN3 CN2 CN1
9 8 7
3 2 1
3 2
2
1
1 S1
Description
Figure 4 Screw terminals, three-row
System
Connecting the Power Supply and Fault Indication
Output
Figure 3 Connection example Termination Board with 4 slots Isolated Barriers
1 Field side connection The isolated barriers are supplied via the Termination Board.
2 Connection power supply and fault indication output The isolated barriers are therefore attached to the Termination
3 Control side connection Board.
Use Termination Boards
• For HiD isolated barriers The Termination Boards are supplied with power via screw
• With 4 or 8 slots terminals in accordance with their design.
• For back-up fused power supply The supply voltage range depends on
• For fault monitoring and diagnostics • The values used for the isolated barriers
• The voltage drop of the decoupling diodes on the
Termination Board
1+ 2- 3+ 4- 5 6
Power Fault
Supply
1+ 2- 3+ 4-
Power
Supply
+2- +1-
Fault Power
Supply
4
3 PWR PWR PWR PWR PWR
2 CH 1 CH 1
FAULT
CH 1
CH 2 CH 2 CH 2 CH 1 FAULT
1 CH 3 CH 3 CH 2
CH 4 CH 4
ADJUST
CH 1
CH 2
CH 3
CH 4
4
Description
3
System
2
1
1 2 3 4 5
Digital Input
Figure 7 Connection via IDC connector, 20-pin
• Orange identifier (1) for switch amplifiers with a relay
output
4 • Blue identifier (2) for switch amplifiers with a transistor
3 output
2 Digital Output
1 • Purple identifier (3) for solenoid drivers
Analog Output
• Green identifier (4) for current drivers
Analog Input/Analog Output
Figure 8 Connection via IDC connector, 24-pin
• Magenta identifier (5) for transmitter power supplies,
measuring transmitters, and repeaters
Note!
For more information see the corresponding data
sheets.
11/2015
265151
Edition
Termination Boards
LED Display function Display Meaning
Green LED Power supply On Power supply OK
Off Power failure or insufficient power supply – device faulty
Red LED Device fault, device failure On Internal fault signal, failure signal – fault/failure display of causes detected
inside the device, device needs replacing
Line fault Flashing External fault signal, failure signal – fault/failure display of causes detected
outside the device, inspection and elimination of fault required
No fault Off No malfunction, device is operating properly
Yellow LED Switching states of binary inputs On Possible causes of the output:
and outputs • The relay is energized.
• The NO contact (also a change-over contact) is actively closed.
• The open collector is switched through.
Description
• The switching voltage generated inside the device is applied.
System
Possible causes of the input:
• An external contact is closed.
• A NAMUR sensor is undamped (OK range according to closed-circuit
current principle).
• A switching signal is actively applied.
Off Possible causes of the output:
• The relay is de-energized.
• The NO contact (also a change-over contact) is actively opened.
• The open collector is not switched through.
• The switching voltage generated inside the device is not applied.
Possible causes of the input:
• An external contact is opened.
• A NAMUR sensor is damped (fault range according to closed-circuit
current principle).
• A switching signal is not applied.
1 2 3
messages, binary switching states). Standard LED colors are The devices are mounted on a 35 mm DIN mounting rail
assigned to the status display according to NAMUR NE44. according to EN 60715.
LED Display Display Meaning
function
Green Power supply On Power supply OK
LED Off No power
"PWR"
Red LED Device fault, On Internal fault signal,
"FAULT" device failure failure signal –
fault/failure display of
causes detected inside
the device
Off No fault
Power supply Flashing Insufficient power
Description
failure 1 supply or power supply Figure 13 Example: DIN mounting rail UPR-MR (35 mm x 15 mm)
System
failure
Table 2 Meaning of status indicators
Mounting
1 only for Termination Board with 8 slots Warning!
Risk of short circuit
Injuries and damage to the device are possible when
1 working with live parts.
• Before working on the device, always disconnect
2
the supply voltage.
• Connect the device to the supply voltage only after
completion of the work.
Figure 11 Example status indicators
Label Carriers
The isolated barriers are fitted with a label carrier ex works for
individual identification.
11/2015
Termination Boards
the Termination Board.
1. Clip the Termination Board (2) onto the DIN mounting
rail (1).
2. Tighten the mounting screws (3).
The Termination Board (2) is now properly mounted
and secured.
Description
Figure 16
System
1 Mounting the Isolated Barriers on the Termination
Board
Figure 14 Termination Board mounting 1. Push the Quick Lok bar (1) into the upper position.
1 DIN mounting rail 2. Center the pins (2) above the contact elements of the
2 Termination Board Termination Board. Note the connection direction of the
device.
3. Center the locking pins (3) above the locking elements of
1 2 3
the Termination Board.
4. Carefully push the device into the contacts and locking
elements.
5. Push the red Quick Lok bar (1) down on either side of the
device.
The device is now mounted.
1
Figure 15 Termination Board fixing
Connection Operation
Note! Fault Monitoring
Observe the tightening torque of the terminal screws.
Termination Boards
IDC connectors.
System
• Device faults
Note! The isolators are designed so that internal faults are
detected and reported. In the case of a power failure, the
For more information see the corresponding data
outputs are switched to a de-energized state.
sheets.
Fault Output
Device Parameterization
Several H-System isolators monitor the field leads for lead
The devices are parameterized using DIP switches. breakage and short circuits. This means that faults are
immediately identified in the system, and that lead faults are
Configuration of the isolated barriers not interpreted as a signal. Depending on the parameterization
of the devices, these lead faults are output on the control-side
Parameterize the DIP switches on the device side as follows:
outputs.
1. Remove the isolated barriers from the Termination Board
by pulling the red Quick Lok Bar up on either side of the Fault Signal Output
device. If the device has a fault indication output (FAULT), lead and
2. Parameterize the DIP switches as described in the device faults are output. The fault indication output is active in
"Configuration" section of the data sheet. normal status and is deactivated in fault status (closed-circuit
3. Mount the device as described in the section on mounting. principle). In the case of fault indication output, it is not
possible to reverse the direction of operation.
Note!
Information about line fault detection of the interface modules
For more information see the corresponding data is available for the system as volt-free contact.
sheets.
SL2 SL1
1b 8a
5a 7a
5b
1a, 1b 24 V DC
2a, 2b
6b FAULT
Figure 18
Termination Boards
• the 0/4 mA to 20 mA current signal Electrical Data
• the 0/2 V to 10 V voltage signal Power Supply to the Isolated Barriers
The 0/1 V to 5 V voltage signal is also occasionally • HiD devices: 20.4 V DC to 30 V DC
encountered in addition to the 0/2 V to 10 V voltage signal.
The voltage drop on the Termination Board via the decoupling
Analog sensor signals and digital frequency signals are diodes must be considered.
converted into one of the two standard signals for processing
Non-Ex Signals or Signals in the Drive Circuit
in a wide variety of measurement, regulatory and control tasks.
This offers the measurement and control technician an easy- • 0/4 mA to 20 mA signal level according to NE43
to-measure standard signal common to all manufacturers. • Current output HART compatible
Sensor signals are converted into standard signals via signal
• Current input HART compatible
converters.
• Digital output: active or passive electronic output
For more diagnostic options, the NAMUR organization 100 mA/30 V, short-circuit protected
published NAMUR recommendation NE43, dividing the value
Description
range of the signal (e. g. current signal) into several areas. • Logic level 24 V according to IEC 60946
System
Valid, defined measurement value information is transferred • Functional isolation or safe isolation according to
within the range from 3.8 mA to 20.5 mA. Failure information is IEC 61140 and NAMUR NE23
available when the signal current is < 3.6 mA or > 21 mA i. e. Ex Signals or Signals in the Field Circuit
outside of the range for measured value information. The same
• Transmitter power supply up to 17 V DC
applies to the voltage signal.
• Current output HART compatible
• Digital input according to NAMUR EN 60947-5-6
• Digital output for standard Ex-i valves, short circuit-
0% 100 % protected
Characteristic Safety Values
1 2 1
• MTBF: Mean Time Between Failures
Conformity
3.6 3.8 4 20 20.5 21 I [mA] General
Figure 19 Signal ranges according to NAMUR NE43 • Isolated barriers with explosion protection, preferably
(e. g. current signal) Ex ia IIC/Class I, Div. 1, international approvals
1 Failure information
• EMV according to
2 Measuring information – EN 61326-1
– EN 61326-3-2, only for devices with SIL rating, where
the data sheet mentions this standard.
If you operate the device with a DC supply voltage, you
must ensure that the bridging of the 20 ms voltage
interruption is realized by the power supply.
– NAMUR NE21
If you operate the device with a DC supply voltage, you
must ensure that the bridging of the 20 ms voltage
interruption is realized by the power supply.
• LEDs according to NAMUR NE44
• Software according to NAMUR NE53
11/2015
265151
Edition
• German standard (old): DIN 19234: Electrical distance according to EN 60715. Can be mounted horizontally or
sensors – DC interface for distance sensors and switch vertically.
amplifiers; 1990-06
• Isolated barriers: mounting on Termination Board via
• European standard (old): EN 50227: Low voltage switch Quick Lok Bar
gear and control gear – control devices and switching
Housing Material
elements – proximity switches, DC interface for proximity
sensors and switch amplifiers (NAMUR), 1996-10 • Termination Boards: Polycarbonate (PC)
• German version (old): DIN EN 50227: Low voltage switch • Isolated barriers: Polycarbonate (PC)
gear – control devices and switching elements – proximity Dimensions
switches, DC interface for proximity sensors and switch
• Dimension drawings please refer to chapter Dimensions.
amplifiers (NAMUR), 1997
Degree of Protection
• Current designation: EN 60947-5-6: Low voltage switch
gear – control devices and switching elements – proximity • Termination Boards:
Description
switches, DC interface for proximity sensors and switch – without isolated barriers IP00 according to EN 60529
System
Termination Boards
Hi 2
Description
8 Digital devices
System
2820 to 2860 Switch amplifiers
2871 to 2890 Solenoid drivers
2891 to 2900 Converters
Housing type
C HiC device, housing width 12.5 mm
D HiD device, housing width 18 mm
System
Hi H-System
Number of channels
08 8 channels
16 16 channels
32 32 channels
Signal types
AI Analog In
AO Analog Out
AM Analog Mix
DI Digital In
DO Digital Out
DM Digital Mix
SM Signal Mix
Termination Board fault output
NO No fault output
R1 1 relay output
R2 2 relay outputs
Number of connectors
1 1 connector
2 2 connectors
3 3 connectors
4 4 connectors
Number of positions
265151
04 4 module slots
08 8 module slots
System
Edition
Warning!
Termination Boards
1 2 34 4321
B –
+
1 2 34 4321
C HiD2096
+
1 2 34 4321
D –
+
1 2 34 4321
E HiD2881
+
1 2 34 4321
I –
++
1 2 34 4321
J HiD2081, HiD2082
+ +
1 2 34 4321
K HiD2025ES
++
1 2 34 4321
L HiD2012
+++
11/2015
1 2 34 4321
M HiD2891
265151
+ ++
1 2 34 4321
Edition
Termination Boards
N –
++ +
1 2 34 4321
O –
+++
1 2 34 4321
P HiD2862
Empty position
++++
1 2 34 4321
Description
System
4 3 21
Table 3
Note!
For more information see the corresponding data sheets.
11/2015
265151
Edition
Dimensions
Housing Designs for H-System HiD Isolated Barriers
Termination Boards
18 mm 128 mm (5.04")
(0.71")
106 mm (4.17")
Description
System
Figure 20
Figure 21
11/2015
265151
Figure 22
Edition
Termination Boards
Description
System
11/2015
265151
Edition
Termination Boards
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
Digital Inputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Digital Outputs
DeltaV
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Digital Inputs
Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Universal
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Digital Outputs
Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Accessories
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition
11/2015
265151
Edition
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels
Channels
Channels
Modules
DeltaV
Series
Series
Type
Type
Card
Digital Inputs
(NAMUR) HiD2844 66
S 32-channel DI simplex 32 HiDTB04-DVM-IDC1-SC-R1-DI16 4 16 32 HiD2844 4 66
(24 V DC, dry contact)
S 32-channel DI Plus 32 HiDTB04-DVM-IDC1-SC-R2-DI16 4 16 36 HiD2844 4 66
(24 V DC, dry contact) redundant
Digital Outputs
Digital Outputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels
Channels
Channels
Modules
Series
Type
Type
Type
Card
Analog Ouputs
Analog Inputs/
(24 V DC, high side) simplex HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2872 2 67
M 32-channel DO Series 2 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) simplex
M 32-channel DO Series 2 Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) redundant
S 8-channel DO simplex 8 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2872 2 67
S 32-channel DO simplex 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side)
Universal
S 32-channel DO Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) redundant
Accessories
11/2015
265151
Edition
Analog Inputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels
Channels
Channels
Modules
Series
Type
Type
Type
Card
DeltaV
Analog Outputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels
Channels
Channels
Modules
Series
Type
Type
Type
Card
Digital Outputs
(4 mA to 20 mA) redundant
Universal
Accessories
11/2015
265151
Edition
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page
Channels
Channels
Channels
Channels
Modules
DeltaV
Series
Series
Type
Type
Type
Card
Digital Inputs
(24 V DC, dry Plus HiC2841 01010
contact) redundant
S 8-channel DI simplex 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2831 1 CAB-DVM-**-S37I16-MX- 8 58
(NAMUR) 01000
S 32-channel DI simplex 32 HiCTB32-SDC-24C-SC-RA 32 32 HiC2821 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, dry HiC2841 01010
contact)
S 32-channel DI Plus 32 HiCTB32-SDC-24C-SC-RA 32 32 HiC2821 1 CAB-DVM-**-S37I20-DX- 16 58
Digital Outputs
(24 V DC, dry redundant HiC2841 01010
contact)
Digital Outputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page
Analog Ouputs
Analog Inputs/
Channels
Channels
Channels
Channels
Modules
Series
Type
Type
Type
Type
Card
Universal
M 32-channel DO Series 2 32 HiCTB32-SDC-24A-SC-RA 32 32 HiC2873 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, high Plus 01010
side) redundant
S 8-channel DO simplex 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2873 1 CAB-DVM-**-S37I16-DO- 8 58
(24 V DC, high 01000
side)
S 32-channel DO simplex 32 HiCTB32-SDC-24A-SC-RA 32 32 HiC2873 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, high 01010
Accessories
side)
S 32-channel DO Plus 32 HiCTB32-SDC-24A-SC-RA 32 32 HiC2873 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, high redundant 01010
side)
11/2015
265151
Edition
Analog Inputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page
Channels
Channels
Channels
Channels
Modules
Series
Type
Type
Type
Type
Card
DeltaV
Analog Outputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page
Channels
Channels
Channels
Channels
Modules
Series
Type
Type
Type
Type
Card
Digital Outputs
11/2015
265151
Edition
DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition
Features
• System Board for Emerson DeltaV
• For one 32-channel DI card via 40-pin Mass Termination
Block
• For 4 modules/16 channels
• Recommended module: HiD2844 (DI)
• Volt-free fault indication output
DeltaV
Function
I/O systems.
Information about line fault detection of the interface modules
is available for the system as volt-free contact.
The Termination Boards are supplied with a robust plastic
housing as standard. This design permits the fast and reliable
installation on 35 mm DIN mounting rail acc. to EN 60715 in
the cabinet.
Digital Outputs
Application
Connection
Universal
24 V DC (I),
24 V DC (II),
1.5 kΩ Fault
1+
I 10 kΩ
4-
1.5 kΩ
2+
II 10 kΩ
1.5 kΩ
5- 4 X20
Accessories
CN1
3+
III 10 kΩ
3
6-
1.5 kΩ 2 DeltaV 32DI
7+
IV 10 kΩ 1
11/2015
8-
9
265151
6 5 4
9 8 7
3 2 1
Zone 0, 1, 2
Edition
Div. 1, 2
Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple 10 %
Fusing 3.15 A with back-up fuse
Power dissipation 500 mW , without modules
Reverse polarity protection yes
DeltaV
Electrical specifications
volt-free fault indication output max. 30 V AC/30 V DC, 1 A
Indicators/settings
Display elements LED PWR (power supply), one green LED
LED FAULT (fault indication), one red LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Conformity
Digital Inputs
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
safe area connection (control side): IDC plug, 20-pin
Digital Outputs
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X
Group, category, type of protection see certificate
Analog Ouputs
Analog Inputs/
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate
Application Universal
DeltaV M-series 32-channel DI Series 2 simplex card (24 V DC, dry contact):
• Termination Board 1: channel 1 ... 16
• Termination Board 2: channel 17 ... 32
DeltaV S-series 32-channel DI simplex card (24 V DC, dry contact):
Accessories
Application
Typical loop
FAULT 24 V DC
+ -
DeltaV
5 6 1 3 2 4 X20
FAULT
&
+
24 V DC
-
1.5 kΩ Module 1
1+
HiD2844
1 10 kΩ SL2
1
5a 7a RTN
4- 4
1.5 kΩ 5b 8a
2+ 2
Digital Inputs
1.5 kΩ Module 4
1+
HiD2844
13 10 kΩ 1
SL2
4- 5a 7a RTN
1.5 kΩ 4
5b 8a 13 13 13 CH13+/CH29+
2+ 2
1a 9a RTN 14 14 14 CH14+/CH30+
14 10 kΩ 5
1b 10a 15 15 15 CH15+/CH31+
5- 3 SL1
1.5 kΩ 3a 10b RTN 16 16 16 CH16+/CH32+
3+ 6
3b 9b 17,19 17,19 17,19 n.c.
7
15 10 kΩ 7a 7b RTN RTN 18,20 18,20 18,20 Return
8
6- 7b 8b
1.5 kΩ 9
7+ 1a, 1b 24 V DC
16 10 kΩ 2a, 2b
FAULT
8- 6b
Analog Ouputs
Analog Inputs/
Screen 9
S4 ON
S5 ON
S6 ON
S7 ON
S8 ON
The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Accessories
11/2015
265151
Edition
DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition
Features
• System Board for Emerson DeltaV
• For one 32-channel DI card via 40-pin Mass Termination
Block
• For 4 modules/16 channels
• Recommended module: HiD2844 (DI)
• Volt-free fault indication output
DeltaV
Function
I/O systems.
Information about line fault detection of the interface modules
is available for the system as volt-free contact.
The Termination Boards are supplied with a robust plastic
housing as standard. This design permits the fast and reliable
installation on 35 mm DIN mounting rail acc. to EN 60715 in
the cabinet.
Digital Outputs
Application
Connection
Universal
24 V DC (I),
24 V DC (II),
1.5 kΩ Fault
1+
I 10 kΩ
4-
1.5 kΩ
2+
II 10 kΩ
1.5 kΩ
5- 4 X20
Accessories
CN1
3+ K1
III 10 kΩ
3
6-
1.5 kΩ 2 DeltaV 32DI
7+ K2
IV 10 kΩ 1 S1
11/2015
8-
9
265151
6 5 4
9 8 7
3 2 1
Zone 0, 1, 2
Edition
Div. 1, 2
Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple 10 %
Fusing 3.15 A with back-up fuse
Power dissipation 500 mW , without modules
Reverse polarity protection yes
DeltaV
Electrical specifications
volt-free fault indication output max. 30 V AC/30 V DC, 1 A
DeltaV specific output: max. 24 V DC, 25 mA
Indicators/settings
Display elements LED PWR (power supply), one green LED
LED FAULT (fault indication), one red LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Digital Inputs
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
Digital Outputs
safe area connection (control side): IDC plug, 20-pin
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X
Analog Ouputs
Analog Inputs/
Group, category, type of protection see certificate
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate
Universal
Application
DeltaV M-series 32-channel DI Series 2 Plus redundant card (24 V DC, dry contact):
• Termination Board 1: channel 1 ... 16
• Termination Board 2: channel 17 ... 32
DeltaV S-series 32-channel DI Plus redundant card (24 V DC, dry contact):
Accessories
Application
Typical loop
FAULT 24 V DC
+ -
DeltaV
5 6 1 3 2 4 X20
K1, K2
FAULT
& K1
+
24 V DC
-
1.5 kΩ Module 1
1+
HiD2844
1 10 kΩ 1
SL2
4- 5a 7a
4
1.5 kΩ 5b 8a RTN 20-pin flat
2+ 2 CN1
Digital Inputs
1a 9a ribbon cable
2 10 kΩ 5
1b 10a RTN 1 1 1 CH1-/CH17-
5- 3 SL1
3a 10b 2 2 2 CH2-/CH18-
1.5 kΩ 6
3+ 3b 9b RTN 3 3 3 CH3-/CH19-
7
3 10 kΩ 7a 7b 4 4 4 CH4-/CH20-
8
6- 7b 8b RTN
1.5 kΩ 9
7+ 1a, 1b 24 V DC
2a, 2b
4 10 kΩ FAULT DeltaV
6b
8- Mass
Screen 9 Termination
Block
32DI
Digital Outputs
1.5 kΩ Module 4
1+
HiD2844
13 10 kΩ 1
SL2
4- 5a 7a 13 13 13 CH13-/CH29-
1.5 kΩ 4
5b 8a RTN 14 14 14 CH14-/CH30-
2+ 2
1a 9a 15 15 15 CH15-/CH31-
14 10 kΩ 5
1b 10a RTN 16 16 16 CH16-/CH32-
5- 3 SL1
1.5 kΩ 3a 10b RTN 18,20 18,20 18,20 Return
3+ 6
3b 9b RTN 17 17 17 FAULT
7 S1.1 K2
15 10 kΩ 7a 7b 19 19 19 FAULT
8
6- 7b 8b RTN
1.5 kΩ 9
7+ 1a, 1b 24 V DC
16 10 kΩ 2a, 2b
FAULT
8- 6b
Analog Ouputs
Analog Inputs/
Screen 9
S4 ON
S5 ON • DeltaV M-series 32-channel T2_FAULT_DETECT True
S6 ON DI Series 2 Plus card
• DeltaV S-series 32-channel
S7 ON
DI Plus card
S8 ON
The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
265151
Edition
DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition
Features
• System Board for Emerson DeltaV
• For one 8-channel DO card via 16-pin Mass Termination
Block
• For one 32-channel DO card via 40-pin Mass
Termination Block
• For 4 modules/8 channels
DeltaV
Function
Digital Inputs
Application
Connection
Universal
24 V DC (I),
24 V DC (II),
Fault
7+
1+
4-
4 X20
Accessories
9
265151
6 5 4
9 8 7
3 2 1
Zone 0, 1, 2
Edition
Div. 1, 2
Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple 10 %
Fusing 3.15 A with back-up fuse
Power dissipation 500 mW , without modules
Reverse polarity protection yes
DeltaV
Electrical specifications
volt-free fault indication output max. 30 V AC/30 V DC, 1 A
DeltaV specific output: max. 24 V DC, 25 mA
Indicators/settings
Display elements LED PWR (power supply), one green LED
LED FAULT (fault indication), one red LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Digital Inputs
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
Digital Outputs
safe area connection (control side): IDC plug, 16-pin and 20-pin
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X
Analog Ouputs
Analog Inputs/
Group, category, type of protection see certificate
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate
Universal
Accessories
11/2015
265151
Edition
Application
11/2015
265151
Edition
Application
FAULT 24 V DC
+ -
DeltaV
5 6 1 3 2 4 X20
FAULT
&
+
24 V DC
-
Module 1
7+
HiD2872
Digital Inputs
4- 5a 7a RTN RTN 1 1 1 CH1-
4
5b 8a 2 2 2 CH1+
9a RTN RTN 3 3 3 CH2-
6
3b 10a 4 4 4 CH2+
6+ 2
1a
5
1b
2 2+ 9
1a, 1b 24 V DC
2a, 2b
5-
6b
FAULT DeltaV
Mass
Screen 9 Termination
Block
8DO
Digital Outputs
Module 4
7+
HiD2872
1+ SL2
7 7
7a SL1
1
4- 5a 7a RTN RTN 13 13 13 CH7-
4
5b 8a 14 14 14 CH7+
9a RTN RTN 15 15 15 CH8-
6
3b 10a 16 16 16 CH8+
6+ 2
1a
5
1b
8 2+ 9
1a, 1b 24 V DC
2a, 2b
5- FAULT
6b
Analog Ouputs
Analog Inputs/
Screen 9
Universal
S4 OFF
S5 ON
S6 OFF
S7 ON
S8 ON
S1.1 n.a.
n.a.
S1.2 n.a.
n.a.
11/2015
265151
Edition
FAULT 24 V DC
+ -
5 6 1 3 2 4 X20
K1, K2
FAULT
& K1
DeltaV
+
24 V DC
-
Module 1
7+
HiD2872
2 2+ 9 8 8 8 CH8+/CH24+
1a, 1b 24 V DC
2a, 2b CH9 9 9 9 CH9+/CH25+
5- FAULT CH10 10 10 10 CH10+/CH26+
6b
Screen 9
CH15 15 15 15 CH15+/CH31+
CH16 16 16 16 CH16+/CH32+
17 17 17 FAULT
Module 4 19 19 19 FAULT
7+
HiD2872 RTN 18,20 18,20 18,20 Return
1+ SL2
7 7
7a SL1
1
5a
K2 S1.1 CN2
4- 7a RTN
4
Digital Outputs
5b 8a CH9 1 1
9a RTN CH10 2 2
6
3b 10a
6+ 2
1a to
5 CH15 7 7
1b Termination Board 2
8 2+ 9 CH16 8 8 via 20-pin flat
1a, 1b 24 V DC
17 17 ribbon cable
2a, 2b
5- FAULT S1.2
6b 19 19
Screen 9 n.c. 9-16 9-16
RTN 18,20 18,20
Analog Ouputs
Analog Inputs/
S7 ON
S8 ON
n.a.
11/2015
265151
Edition
FAULT 24 V DC
+ -
5 6 1 3 2 4 X20
K1, K2
FAULT
& K1
DeltaV
+
24 V DC
-
Module 1
7+
HiD2872
Digital Inputs
2 2+ 9 8 8 8 CH8+/CH24+
1a, 1b 24 V DC
2a, 2b CH9 9 9 9 CH9+/CH25+
5- FAULT CH10 10 10 10 CH10+/CH26+
6b
Screen 9
CH15 15 15 15 CH15+/CH31+
CH16 16 16 16 CH16+/CH32+
17 17 17 FAULT
Module 4 19 19 19 FAULT
7+
HiD2872 RTN 18,20 18,20 18,20 Return
1+ SL2
7 7
7a SL1
1
5a
K2 S1.1 CN2
4- 7a RTN
4
Digital Outputs
5b 8a CH9 1 1
9a RTN CH10 2 2
6
3b 10a
6+ 2
1a to
5 CH15 7 7
1b Termination Board 2
8 2+ 9 CH16 8 8 via 20-pin flat
1a, 1b 24 V DC
17 17 ribbon cable
2a, 2b
5- FAULT S1.2
6b 19 19
Screen 9 n.c. 9-16 9-16
RTN 18,20 18,20
Analog Ouputs
Analog Inputs/
Module switch settings Card software settings
Type DIP switch Position Type Parameter Setting
HiD2872 (DO) S1 ON • DeltaV M-series 32-channel T1_FAULT_DETECT True
• Bus powered S2 OFF DO Series 2 Plus card
• Control input: logic signal • DeltaV S-series 32-channel
S3 ON
• Line fault detection enable DO Plus card
S4 OFF
S5 ON • DeltaV M-series 32-channel T2_FAULT_DETECT True
S6 OFF DO Series 2 Plus card
• DeltaV S-series 32-channel
S7 ON
Universal
DO Plus card
S8 ON
Schematic diagram
• Connection between Termination Board 2 and Termination Board 1 (channel 1 ... 16)
• Connection between Termination Board 4 and Termination Board 3 (channel 17 ... 32)
DeltaV 32DO
20-pin flat
ribbon cable
DeltaV
S1 S1
CN1 CN1
CN2 CN2
CN3 CN3
20-pin flat
ribbon cable
4
3
2
1
4
3
2
1
Digital Inputs
Digital Outputs
The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Accessories
11/2015
265151
Edition
DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition
Features
• System Board for Emerson DeltaV
• For two 8-channel AI/AO cards via 16-pin Mass
Termination Block
• For one 16-channel AI/AO card via 48-pin Mass
Termination Block
• For 4 modules/16 channels
DeltaV
Function
Application
Connection
Universal
24 V DC (I),
1+ 24 V DC (II)
HART
HART
P
I I 4-
2+
HART
HART
P
II I 5- X20
4 CN4 CN3 DeltaV 8AI, 8AO
Accessories
CN2 CN1
3+
HART
HART
P 3
III I DeltaV 8AI, 8AO
6-
2
7+ DeltaV 16AI, 16AO
HART
HART
P 1
IV I
11/2015
8-
DeltaV 16AI, 16AO
9
265151
6 5 4
9 8 7
3 2 1
Zone 0, 1, 2
Edition
Div. 1, 2
Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple 10 %
Fusing 3.15 A with back-up fuse
Power dissipation 500 mW , without modules
Reverse polarity protection yes
DeltaV
Indicators/settings
Display elements LED PWR (power supply), one green LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Digital Inputs
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
safe area connection (control side): IDC plug, 16-pin and 24-pin
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g
Digital Outputs
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X
Group, category, type of protection see certificate
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Analog Ouputs
Analog Inputs/
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate
Universal
Accessories
11/2015
265151
Edition
Application
11/2015
265151
Edition
Application
Typical loop
24 V DC
DeltaV
+ -
1 3 2 4 X20
+
24 V DC 24-pin flat
- CN3
ribbon cable DeltaV
1 1 1 CH1-
Mass
2 2 2 CH1+
Termination
3 3 3 CH2-
Block
4 4 4 CH2+
16AI
5 5 5 CH3-
16AO
6 6 6 CH3+
Digital Inputs
7 7 7 CH4-
8 8 8 CH4+
15 15 15 CH8-
16 16 16 CH8+
n.c. 17-24 17-24 17-24 n.c.
1+
HART
HART
P Module 1
1 I 16-pin flat
4- HiD2024 CN1
1
SL2 ribbon cable DeltaV
5a 7a 1 1 1 CH1-
2+ 4
5b
Mass
HART
HART
P 8a 2 2 2 CH1+
2 2 Termination
I 1a 9a 3 3 3 CH2-
5- 5 Block
Digital Outputs
1b 10a 4 4 4 CH2+
3
3a SL1 8AI
10b 5 5 5 CH3-
3+ 6 8AO
HART
HART
P 3b 9b 6 6 6 CH3+
3 I 7
7a
6- 7b 7 7 7 CH4-
8
7b 8b 8 8 8 CH4+
9
7+
HART
HART
P 1a, 1b 24 V DC
4 I 2a, 2b 15 15 15 CH8-
8-
16 16 16 CH8+
Analog Ouputs
SL2
Analog Inputs/
1+ 1
HART
HART
P 5a 7a 9 9 9 CH5- 8AI
13 I 4
4- 5b 8a 10 10 10 CH5+ 8AO
2
1a 9a 11 11 11 CH6-
5
1b 10a 12 12 12 CH6+
2+
HART
HART
P 3
3a SL1
10b 13 13 13
14 I CH7-
5- 6
3b 9b 14 14 14 CH7+
7
7a 7b 15 15 15 CH8-
8
3+ 7b 8b 16 16 16 CH8+
HART
HART
P 9
15 I 6- 1a, 1b 24 V DC
2a, 2b
7+ CN4 24-pin flat
HART
HART
P ribbon cable
16 I DeltaV
8- 1 1 1 CH9-
Mass
2 2 2 CH9+
Termination
Screen 9
Universal
Block
9 9 9 CH13- 16AI
10 10 10 CH13+ 16AO
11 11 11 CH14-
12 12 12 CH14+
13 13 13 CH15-
14 14 14 CH15+
15 15 15 CH16-
16 16 16 CH16+
n.c. 17-24 17-24 17-24 n.c.
Accessories
The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Edition
Features
• System Board for Emerson DeltaV
• For two 8-channel AI/AO/DO cards via 16-pin Mass
Termination Block
• For four 8-channel DI cards via 16-pin Mass
Termination Block
• For 8 modules/16 or 32 channels
DeltaV
Function
Digital Inputs
Application
Connection
Universal
6 5 4
24 V DC (I),
9 8 7
3 2 1
M8
24 V DC (II),
Fault
1.5 kΩ
1, 2, 3, 7
10 kΩ 8 X20
4, 5, 6, 8
7
1, 2 6 DeltaV
HART
Accessories
+ 4, 5
5 AO, AI, DO
mA 7, 6
-
4 CN4 CN2
1, 2
HART
P -
I 3
4, 5
DeltaV
11/2015
+ 2
7, 6 DI
1 CN3 CN1
250499
6 5 4
9 8 7
3 2 1
M1
Zone 0, 1, 2
Edition
Div. 1, 2
Technical data
Supply
Connection X20: terminals 3, 5 (+); 4, 6 (-)
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple 10 %
Fusing 2 A , in each case for 8 modules
Power dissipation 500 mW , without modules
DeltaV
Reverse polarity protection yes
Redundancy
Supply Redundancy available. The supply for the modules is decoupled, monitored and fused.
Error message output
Connection X20: terminals 1, 2
Output type volt-free contact
Contact loading 30 V AC/40 V DC, 2 A
Indicators/settings
Display elements LEDs PWR ON (Termination Board power supply)
Digital Inputs
- LED power supply I, green LED
- LED power supply II, green LED
LED FAULT (fault indication), red LED
- LED lits: module failure
- LED flashes: power supply failure
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Conformity
Digital Outputs
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
safe area connection (control side): IDC plug, 16-pin
Analog Ouputs
Analog Inputs/
power supply connection: pluggable screw terminals, black
Core cross-section 0.25 ... 1.5 mm2 (24 ... 12 AWG)
Material housing: polycarbonate, 10 % glass fiber reinforced
Mass approx. 600 g
Dimensions 150 x 200 x 163 mm (5.9 x 7.9 x 6.42 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate CESI 11 ATEX 062
Group, category, type of protection E II (1)G [Ex ia Ga] IIC, E II (1)D [Ex ia Da] IIIC, E I (M1) [Ex ia Ma] I
Universal
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000
CSA approval
Control drawing see control drawing of correspoding modules
IECEx approval IECEx CES 11.0022
Accessories
Application
• Card 4 and CN4: channel 25 ... 32, field side: M5 ... M8 terminals 3, 6, 7, 8
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
250499
Edition
Application
Typical loop for analog inputs, analog outputs and digital outputs
Fault 24 VDC
+ -
DeltaV
1 2 3 5 4 6 X20
Fault
& F2 F1
1
HART
+ 4
mA 7
- +
1 24 V DC
1 -
HART
P -
I
4 Module 1
+ M1 HiD2030SK
7 HiD2038 16-pin flat
SL2
1 HiD2872 SL1 CN1 ribbon cable
5a
4 DeltaV
Digital Inputs
5b 7a 1 1 1 CH1-
2 Mass
HART
7
7a 8a 2 2 2 CH1+
+ 5 2
Termination
1a 9a 3 3 3 CH2- Block
mA 6 5
- 1b 10a 4 4 4 CH2+ 8AI
2 6 8AO
3b
2
HART
P 1a, 1b 24 V DC
- 8DO
I 2a, 2b
5 Fault 15 15 15 CH8-
6b
+ 16 16 16 CH8+
6
16-pin flat
1 CN2 ribbon cable
HART
+ DeltaV
4 Module 8 1 1 1 CH1-
Mass
Digital Outputs
mA 7 M8 HiD2030SK 2 2 2 CH1+ Termination
- SL2 HiD2038
15 1 HiD2872 Block
5a SL1
1
HART
P - 4
8AI
I 5b 7a 13 13 13 CH7- 8AO
4 7
+ 7a 8a 14 14 14 CH7+ 8DO
7 2
1a 9a 15 15 15 CH8-
5
1b 10a 16 16 16 CH8+
6
3b
2 1a, 1b 24 V DC
HART
+ 2a, 2b
5 Fault
6b
mA 6
-
16
2
HART
Analog Ouputs
Analog Inputs/
P -
I
5
+
6
Universal
S5 ON
S6 OFF
S7 ON
S8 ON
HiD2030SK (AI) No user configuration available.
HiD2038 (AO) No user configuration available.
Accessories
11/2015
250499
Edition
Fault 24 V DC
+ -
1 2 3 5 4 6 X20
Fault
& F2 F1 16-pin flat
CN1 ribbon cable
DeltaV
DeltaV
1 1 1 CH1-
+ Mass
1.5 kΩ 2 2 2 CH1+
1 24 V DC Termination
- 3 3 3 CH2-
1 10 kΩ Block
4 4 4 CH2+
4 Module 1 8DI
1.5 kΩ M1 HiD2824
2 SL2
1 15 15 15 CH8-
5a 7a
2 10 kΩ 4 16 16 16 CH8+
5b 8a
5 2
1a 9a
1.5 kΩ 5 CN3
3 1b 10a
3 SL1 DeltaV
3 10 kΩ 3a 10b 1 1 1 CH1-
6 Mass
6 3b 9b 2 2 2 CH1+
1.5 kΩ
7
7a
Termination
7b 3 3 3 CH2-
7 8
7b
Block
8b 4 4 4 CH2+
8DI
Digital Inputs
4 10 kΩ
8 1a, 1b 24 V DC
2a, 2b
Fault 15 15 15 CH8-
6b
16 16 16 CH8+
CN2
1.5 kΩ
1 DeltaV
1 1 1 CH1-
29 10 kΩ Mass
Module 8 2 2 2 CH1+
4 Termination
M8
1.5 kΩ SL2 HiD2824 Block
2 1
5a 7a 13 13 13 CH7- 8DI
30 10 kΩ 4
5b 8a 14 14 14 CH7+
5 2
1a 9a 15 15 15 CH8-
1.5 kΩ 5
Digital Outputs
1b 10a 16 16 16 CH8+
3 3 SL1
3a 10b
31 10 kΩ 6
3b 9b CN4
6 7
7a 7b DeltaV
1.5 kΩ 8 1 1 1 CH1-
7 7b 8b Mass
2 2 2 CH1+
32 10 kΩ 1a, 1b
Termination
24 V DC
8 2a, 2b Block
Fault 13 13 13 CH7- 8DI
6b
14 14 14 CH7+
15 15 15 CH8-
16 16 16 CH8+
Analog Ouputs
Analog Inputs/
S8 ON
The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Accessories
11/2015
250499
Edition
DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
250499
Edition
connector on H-System
Connection Sub-D plug , 37 pins/37 pins
Termination Boards IDC plug, 16-pin, 20-pin and 24-pin
• Preconfigured lengths Material
Connector Zinc die cast, nickel plated
Sheathing PVC
Core insolation PVC
Cable LiYCY
Diameter 18 cores: 7.3 mm (0.29 in)
Bending radius min. 6 x external diameter, fixed cable
Digital Inputs
Assembly
Universal
IDC ...
(siehe
Accessories
Tabelle)
11/2015
250499
Edition
Application
DeltaV
S3 OFF
S4 OFF
HiC2031 (AO) S1 ON – – –
Open loop voltage of the control S2 ON
system < 23 V
S3 OFF
S4 OFF
Digital Inputs
• Open – energized S2 I Series 2 Plus card T2_FAULT_DETECT False
• Line fault detection enable • DeltaV S-series 32-channel DI
S3 – Plus card
S4 –
Digital Outputs
S4 –
Analog Ouputs
Analog Inputs/
S7 ON Plus card
S8 ON
Universal
Accessories
11/2015
250499
Edition
H-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Accessories
Digital Inputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
H-System
Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Digital Outputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Digital Inputs
Analog Inputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Digital Outputs
Analog Outputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Analog Inputs
Accessories
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Analog Outputs
Accessories
11/2015
265151
Edition
11/2015
265151
Edition
Digital Inputs
20 V DC ... 31 V DC
Zone 2/Division 2
(Active/Passive)
NAMUR Sensor/
(Bus Powered)
H-System
Dry Contact
Transistor
Line Fault
Detection
Channels
Mounting
24 V DC
Relay
HiD
SIL
HiD2824 4 4 2 65
HiD2844 4 4 4 2 66
Digital Outputs
Digital Inputs
Model Number Housing Input Output (Field) Specials Supply Page
(Control System)
(Loop Powered)
(Bus Powered)
Loop powered
Contact Input
Voltage (V)
Channels
Digital Outputs
24 V DC
24 V DC
LED
HiD
SIL
HiD2872 2 12 40 3 67
Analog Inputs
Analog Inputs
Model Number
(Control System)
(1 Input – 2 Outputs)
2-wire Transmitter
Zone 2/Division 2
0/4 mA ... 20 mA
0/4 mA ... 20 mA
Current Source
Signal Splitting
(Bus Powered)
Channels
Mounting
(Source)
24 V DC
SMART
(Sink)
Analog Outputs
HiD
SIL
HiD2024 4 68
HiD2030SK 2 2 69
Analog Outputs
Zone 2/Division 2
0/4 mA ... 20 mA
0/4 mA ... 20 mA
(Bus Powered)
11/2015
Channels
Mounting
24 V DC
SMART
265151
HiD
HiD2038 2 2 70
Edition
Accessories
11/2015
265151
Edition
H-System
Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA • Up to SIL2 acc. to IEC 61508
Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum
value Function
Output
Output signal: relay SPST per channel, phase selectable This isolated barrier is used for intrinsic
Error message output safety applications. It transfers digital
Output type open collector transistor (internal fault bus) signals (NAMUR sensors/mechanical
Transfer characteristics contacts) from a hazardous area to a safe
Switching frequency < 10 Hz area.
Ambient conditions
The proximity sensor or switch controls
Digital Inputs
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
two form A normally open relay outputs for
Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
the safe area load. The module output
Mechanical specifications
changes state when the input signal
Degree of protection IP20
changes state. The normal output state
Mass approx. 140 g
can be reversed with the selector switches
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
on the side of the unit.
Mounting on Termination Board
Coding pin 1 and 2 trimmed Line fault detection (LFD) can be selected
Data for application in connection see page 72 for entity parameters or disabled via a selector switch.
Digital Outputs
with Ex-areas During an error condition, the relay reverts
EC-Type Examination Certificate CESI 02 ATEX 086 to its de-energized state and the LEDs
Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC indicate the fault. A separate fault output
Statement of conformity PF 11 CERT 2109 X bus is available. The fault conditions can
Group, category, type of protection, E II 3G Ex nA nC IIC T4 Gc be monitored via a Fault Indication Board.
temperature class
CSA approval
This module mounts on a HiD Termination
Control drawing 366-005CS-12B (cCSAus)
Board.
Analog Inputs
Analog Outputs
Diagrams
Front view
LED green:
Power supply
HiD2824
PWR
1.5 kΩ SL2 SL1 LEDs yellow:
+ 1 5a 8a 11 LEDs red:
FAULT STATUS
Status output
I 10 kΩ I CH 1
+ 2 1a 10a 12 CH 3
II 10 kΩ II
CH 4
- 5 1b 9a 15 Switch 1 ... 8
1.5 kΩ HiD
+ 3 3a 9b 13 2824
III 10 kΩ III
4 ch
Switch
1.5 kΩ
- 6 3b 10b 16 Amplifier
+ 7 7a 8b 17
IV 10 kΩ IV
11/2015
- 8 7b 7b 18 Place for
1a, 1b - 24 V DC labeling
2a, 2b +
FAULT
265151
6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition
• Up to SIL2 acc. to IEC 61508 Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum
Function value
Output
This isolated barrier is used for intrinsic Rated voltage Un 30 V
safety applications. It transfers digital Rated current In 50 mA
signals (NAMUR sensors/mechanical Output one optocoupled transistor per channel
contacts) from a hazardous area to a safe Signal level 1-signal: (external voltage) -1 V
0-signal: blocked output (off-state current max. 50 A,
area.
typical 5 A)
The proximity sensor or switch controls a Error message output
Digital Inputs
passive transistor for the safe area load. Output type open collector transistor (internal fault bus)
The module output changes state when Transfer characteristics
the input signal changes state. The normal Switching frequency < 2 kHz
output state can be reversed with the Ambient conditions
selector switches on the side of the unit. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Line fault detection (LFD) can be selected Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
or disabled via a selector switch. Mechanical specifications
Degree of protection IP20
During an error condition, the transistor
Digital Outputs
Diagrams
Front view
LED green:
Power supply
HiD2844
PWR
CH 3
II 10 kΩ II
CH 4
1.5 kΩ - 5 1b 9a 15 -
Switch 1 ... 8 HiD
2844 + 3 3a 9b 13 +
III 10 kΩ III
4 ch
Switch
Amplifier 1.5 kΩ - 6 3b 10b 16 -
+ 7 7a 8b 17 +
IV 10 kΩ IV
11/2015
- 8 7b 7b 18 -
Place for
labeling 1a, 1b - 24 V DC
2a, 2b +
FAULT
265151
6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition
H-System
Control input external switch (dry contact or open collector) non • Contact or logic control input
isolated or logic signal input fully floating
• Entity parameter Io/Isc = 110 mA
Signal level 1-signal: 15...30 V DC (current limited at 3 mA) or
contact close (internal 10 k pull-up) • Line fault detection (LFD)
0-signal: 0...5 V DC or contact open • Up to SIL2 acc. to IEC 61508
Power loss 1 W at 24 V, 300 load (per channel) for loop powered (bus powered)
Inrush current 0.2 A , 15 ms loop powered • Up to SIL3 acc. to IEC 61508
Output (loop powered)
Internal resistor Ri approx. 240
Current Ie 40 mA Function
Voltage Ue 12 V
Digital Inputs
Current limit Imax 55 mA This isolated barrier is used for intrinsic
Open loop voltage Us approx. 22.5 V safety applications.
Load nominal 0.1 ... 5 k
It supplies power to solenoids, LEDs, and
Error message output
audible alarms, located in a hazardous
Output type open collector transistor (internal fault bus)
area.
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) It is controlled with a loop-powered control
Mechanical specifications signal, switch contact, transistor, or logic
signal.
Digital Outputs
Degree of protection IP20
Mass approx. 140 g At full load, 12 V at 40 mA (with 55 mA
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in) current limit) is available for the hazardous
Mounting on Termination Board area application.
Coding pin 1 and 4 trimmed An alternative low current output is
Data for application in connection see page 72 for entity parameters available for driving a single LED without
with Ex-areas
installing an external current limiting
EC-Type Examination Certificate CESI 10 ATEX 036
resistor.
Group, category, type of protection E II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in
Line fault detection of the field circuit is
Analog Inputs
zone 0/1/2/20/21/22]
Statement of conformity PF 10 CERT 1729 X indicated by a red LED and an output on
Group, category, type of protection, E II 3G Ex nA II T4 the fault bus.
temperature class This device mounts on a HiD Termination
CSA approval Board.
Control drawing 366-005CS-12B (cCSAus)
IECEx approval IECEx CES 10.0013
Analog Outputs
Diagrams
Front view
V
- - 5b (4)
(18) 7b - Switch 1 ... 8 HiD
(12) 10a + channel 2 2872
+ V
+ 3b (6) 2 ch
Solenoid
II (15) 9a - II Driver
+ 1a (2)
(13) 9b + V
11/2015
- - 1b (5)
(16) 10b - Place for
1a, 1b - 24 V DC labeling
2a, 2b +
ERR
265151
6b Switch 1 ... 8
Zone 0, 1, 2 channel 1
Div. 1, 2 Termination Board
Edition
Available voltage 15 V at 20 mA
Function Output signal 4 ... 20 mA
Output load 0 ... 650
This isolated barrier is used for intrinsic Safe area connection
safety applications. It operates as a Input signal 4 ... 20 mA
SMART transmitter power supply or as a Input resistance > 100 k at max. 23 V, with field wiring open
repeater. Voltage drop approx. 6 V or internal resistance 300 at 20 mA
Bi-directional communication is supported Output signal 4 ... 20 mA or 1 ... 5 V (on 250 , 0.1 % internal shunt)
for SMART transmitters that use current 4 ... 20 mA (sink mode), operating voltage 15 ... 26 V
Output load 0 ... 300 (source mode)
modulation to transmit data and voltage
Digital Inputs
Mechanical specifications
Board.
Degree of protection IP20
Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
Mounting on Termination Board
Coding pin 1 and 3 trimmed
Data for application in connection see page 72 for entity parameters
with Ex-areas
EC-Type Examination Certificate CESI 02 ATEX 086
Analog Inputs
Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC
Statement of conformity PF 11 CERT 2109 X
Group, category, type of protection, E II 3G Ex nA IIC T4 Gc
temperature class
Analog Outputs
Diagrams
Front view
LED green:
Power supply
HiD2024
PWR
SL2 SL1
HART
HART
HART
P + 5a (1) (11) 8a +
I I V mA I
- 5b (4) (14) 7a -
Switch 1 ... 4
HART
HART
HART
P
Accessories
HART
P + 3a (3) (13) 9b +
4 ch
III I V mA III
Transmitter
Power - 3b (6) (16) 10b -
Supply/
Current
HART
HART
HART
Driver
P + 7a (7) (17) 8b +
IV mA IV
11/2015
ADJUST
I V
CH 1
Potentiometer for calibration: Place for - 7b (8) (18) 7b -
CH 2
channel 1 ... 4 labeling
CH 3 1a, 1b - 24 V DC
2a, 2b +
265151
CH 4
Zone 0, 1, 2 Zone 2
Div. 1, 2 Termination Board Div. 2
Edition
H-System
Input resistance 40 , for current source 2 outputs)
Ripple 10 mV eff • Dual output 4 mA ... 20 mA, current
Voltage min. 15.5 V at 20 mA sink
Output
• Line fault detection (LFD)
Output sink mode from external supply
• Up to SIL2 acc. to IEC 61508
Output signal 4 ... 20 mA , current limit 24 mA
Voltage working voltage 7 ... 30 V
Function
Response time 70 ms , 10 ... 90 % step change
Signal level no fault: 1 mA ... 23.5 mA input current
This isolated barrier is used for intrinsic
fault detection: < 0.2 mA or > 24 mA input current
safety applications. It provides a fully
Digital Inputs
Error message output
floating supply to power 2-wire SMART
Output type open collector transistor (common to both channels)
fault bus signal, collective error message transmitters in the hazardous area, and
Ambient conditions repeats the current to drive a safe area
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) load. It is also used with 2-wire current
Mechanical specifications sources. It is designed to provide a sink
Degree of protection IP20 mode output on the safe area terminals
Mass approx. 140 g Digital signals may be superimposed on
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in) the analog values in the hazardous or safe
Digital Outputs
Mounting on Termination Board area, which are transferred bi-
Coding pin 1 and 3 trimmed directionally.
Data for application in connection see page 72 for entity parameters A separate fault output on the bus is
with Ex-areas
signaled if the input signal is outside the
EC-Type Examination Certificate CESI 02 ATEX 086
range 0.2 mA ... 24 mA. The fault
Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC
conditions can be monitored via a Fault
Statement of conformity PF 11 CERT 2109 X
Indication Board.
Group, category, type of protection, E II 3G Ex nA IIC T4 Gc [device in zone 2]
temperature class This module mounts on a HiD Termination
Board.
Analog Inputs
CSA approval
Control drawing 366-005CS-12B (cCSAus)
Analog Outputs
Diagrams
Front view
LED green:
Power supply
HiD2030SK
PWR
SL2
SL1
HART
FAULT
+ 8a 11 + CH 2 CH 1
I I Fault channel 2 Fault channel 1
4 5b
mA 7a 14 -
Accessories
- - 7 7a
HART
+ 2 1a V HiD
HART
+ 10a 12 + 2030
II II
5 1b SK
mA 9a 15 - 2 ch
Transmitter
- - 6 3b Power
Supply
11/2015
Place for
1a, 1b - 24 V DC labeling
2a, 2b +
FAULT
265151
6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition
Input
• Up to SIL2 acc. to IEC 61508
Input current 4 ... 20 mA , reverse polarity protected
Function Signal level input voltage drop < 4 V with field wiring intact
input current < 1.2 mA with field wiring open
Output
This isolated barrier is used for intrinsic
Load 0 ... 750
safety applications. It repeats a
Output signal 4 ... 20 mA
4 mA ... 20 mA input signal from a control
Ripple 15 mV eff
system to drive SMART I/P converters,
Response time 50 ms , 10 ... 90 % step change
valve actuators, and displays located in a
Line fault detection breakage, load > 100 k, short-circuit, load < 70
hazardous area.
Digital Inputs
Line fault detection of the field circuit is Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
indicated by a red LED and an output on Mechanical specifications
the fault bus. The fault conditions can be Degree of protection IP20
monitored via a Fault Indication Board. Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
This module mounts on a HiD Termination
Mounting on Termination Board
Board.
Coding pin 1 and 3 trimmed
Data for application in connection see page 72 for entity parameters
with Ex-areas
Analog Inputs
Diagrams
Front view
LED green:
Power supply
HiD2038
PWR
FAULT
CH 1
LED red: SL2 SL1
HART
HART
Fault channel 1 P
FAULT I + 1 5a 8a 11 + mA I
LED red: I
Accessories
CH 2 - 4 5b 7a 14 -
Fault channel 2
HiD
2038
HART
HART
2 ch II P + 2 1a 10a 12 + mA II
Current I
Driver
- 5 1b 9a 15 -
11/2015
Place for
labeling 1a, 1b - 24 V DC
2a, 2b +
FAULT
265151
6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition
H-System
Material Polycarbonate
This barrier is a non functioning HiD
Mass approx. 140 g
module designed to be a place holder for
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
system expansions.
Mounting on Termination Board
This barrier mounts on a HiD termination
board.
Configuration
No user configuration available for this device.
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Diagrams
Front view
HiD2000 Blank
Accessories
HiD
2000
Blank
Module
11/2015
250499
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition
11/2015
265151
Edition
H-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Accessories
11/2015
265151
Edition
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
General Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Model Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition
11/2015
265151
Edition
A Associated Apparatus
Apparatus in which the circuits are not necessarily intrinsically
Active Zener Barrier safe themselves, but which affect the energy in the intrinsically
safe circuits and are relied upon to maintain intrinsic safety.
A Zener Barrier with additional active components (i. e.,
Associated electrical apparatus may be either
transistors, integrated circuits, etc.) that provides special
functions or features. 1. electrical apparatus that have an alternative type of
protection, for use in the appropriate hazardous (classified)
Appendix
AIT location; or
2. electrical apparatus that are not protected and therefore
Abbreviation for autogenous ignition temperature. cannot be used within a hazardous (classified) location.
Glossary
Analog type signal from a hazardous area instrument (i. e., Associated Safe-Location Equipment
transmitter) to the safe area controller.
Equipment designed to form part of an intrinsically safe
system, in which not all the circuits are of an intrinsically
Analog Output
safe system, in which not all the circuits are intrinsically safe,
Analog type signal from the safe area controller to the but which affects the safety of the intrinsically safe system of
hazardous area instrument (i. e., I/P positioner). which it forms a part. Such equipment may not be installed in a
General Notes
hazardous location unless provided with appropriate
ANSI protection, such as the installation of an explosion-proof
enclosure in a Class I hazardous location. Examples of
Abbreviation for American National Standards Institute. associated safe-location equipment are
Model Number
Acceptable to the authority having jurisdiction. Authority Having Jurisdiction
Index
The organization, office, or individual that has the
Arcing Device responsibility and authority for approving equipment,
installations, or procedures.
A device, such as make/break component, that under normal
conditions produces an arc with energy sufficient to cause
ignition of an ignitable mixture. See also "non-incendive Autogenous Ignition Temperature
circuit." The temperature at which a mixture of a specified gas or vapor
in air will spontaneously ignite under specified test conditions,
Asset Management without any source of ignition.
Asset Management functionality often includes the monitoring
of devices like flow meters, analyzers, actuators, and control Automation System
valves. It detects faults and sometimes even recommends The system that provides overall control and monitoring
corrective actions. functions of a specific process or application. Generally
consists of a network of computers, controllers, and I/O
modules.
11/2015
265151
Edition
B Certified Equipment
Equipment that has been evaluated by a recognized testing
Barrier Specification agency and confirmed to be in compliance with the applicable
standard(s).
The typical way of describing a barrier, for example 28 V,
300 93 mA. This is a reference to the maximum voltage of
the terminating zener diode during the period of time it takes CESI
for the fuse to break, the minimum value of the terminating
Appendix
safety standards.
A location (1) in which ignitable concentrations of flammable
BSI gases or vapors can exist under normal operating conditions;
(2) in which ignitable concentrations of such gases or vapors
Abbreviation for British Standards Institute. may exist frequently because of repair or maintenance
operations or because of leakage; or (3) in which breakdown
Bus Technology or faulty operation of equipment or processes might release
ignitable concentrations of flammable gases or vapors and
A variety of bus technologies are employed throughout the
General Notes
permits the storage of electrically separated charges when of equipment; (2) in which ignitable concentrations of gases or
potential differences exist between the conductors. The vapors are normally prevented by positive mechanical
greater the capacitance, the greater the charge that can be ventilation and might become hazardous through failure or
stored. The practical difference between capacitance and abnormal operation of the ventilating equipment; or (3) that is
inductance in an intrinsically safe circuit is minimal. Both store adjacent to a Class I, Division 1 location and to which ignitable
energy but a capacitor will release energy when a circuit is concentrations of gases or vapors might occasionally be
made and an inductor will release energy when the circuit is communicated unless such communication is prevented by
broken. adequate positive-pressure ventilation from a source of clean
air and effective safeguards against ventilation failure are
CENELEC provided. Electrical conduits and their associated enclosures
separated from process fluids by a single seal or barrier are
Abbreviation for European Electrotechnical Committee for
classified as a Class I, Division 2 location if the outside of the
Standardization. The standard for the European Economic
conduit and enclosures is a non-hazardous (unclassified)
Community (EEC) nations and the European Free Trade
location.
Association. Legally, certification to the CENELEC standard is
sufficient to permit sale in any European country. If IEC
standards are available, CENELEC tries to utilize them
because these standards are already adopted by the
European community.
11/2015
265151
Edition
Appendix
normal operating conditions in quantities sufficient to produce
Com Unit and Gateway
explosive or ignitable mixtures; (2) in which mechanical failure
or abnormal operation of machinery or equipment might cause Bus systems employ communication units (Com Units) to
such explosive or ignitable mixtures to be produced and might interface the DCS or PLC master with the Remote I/O slaves.
also provide a source of ignition through simultaneous ( the Their properties depend on the protocol they support.
word "simultaneous" is not included in the Canadian definition)
failure of electric equipment, operation of protection devices, Configuration in Run (CiR or HCiR)
or from other causes; or (3) in which combustible dusts of an
electrically conductive nature may be present in hazardous Online Remote I/O changes are made possible by means of
quantities. (hot) configuration in run (HCiR) methods. This is based on
freezing output data during the bus reset period or by offering
redundancy rings.
Class II, Division 2 Location
Glossary
A location in which combustible dust is not normally in the air in Converter
quantities sufficient to produce explosive or ignitable mixtures
and dust accumulations are normally insufficient to interfere A type of isolated barrier that receives a signal from the
with the normal operation of electrical equipment or other hazardous area instrument (i. e. transmitter, thermocouples,
apparatus, but combustible dust may be in suspension in the etc.) and converts it into an equivalent signal
air as a result of infrequent malfunctioning of handling or (i. e. 4 mA ... 20 mA, 1 V ... 5 V, etc.).
processing equipment and where combustible dust
General Notes
accumulations on, in, or in the vicinity of the electrical or may Control Drawing
be ignitable by abnormal operation or failure of electrical A drawing or other document provided by the manufacturer of
equipment. the intrinsically safe or associated apparatus that details the
allowed interconnections between the intrinsically safe and
Class III Location associated apparatus.
A location that is hazardous because of the presence of easily
ignitable fibers or flyings but in which such fibers or flyings are CSA
not likely to be in suspension in the air in quantities sufficient to
Model Number
Abbreviation for Canadian Standards Association. A third
produce ignitable mixtures. party certification agency headquartered in Canada and
Index
recognized by OSHA as a Nationally Recognized Test
Class III, Division 1 Location Laboratory in the United States. The presence of CSA, UL, or
A location in which easily ignitable fibers or materials FM certification marks on equipment is normally sufficient to
producing flyings are handled, manufactured, or used. the local inspector that the product is designed to recognized
safety standards.
Class III, Division 2 Location
A location in which easily ignitable fibers are stored or handled
(except in the process of manufacture).
Clearance Distance
The shortest distance measured in air between conductive
parts.
11/2015
265151
Edition
D Dust-Ignition Proof
A term used in the United States to describe an enclosure that
Definition of Contamination Level 2 per will exclude ignitable amounts of dusts that might affect
EN 50178 performance or rating and that, when installed and protected in
accordance with the original design intent, will not permit arcs,
Under normal circumstances, only non-conductive sparks, or heat otherwise generated or liberated inside the
contamination occurs. Occasionally however, short-term enclosure to cause ignition of exterior accumulations or
Appendix
conductance may be expected through condensation when atmospheric suspensions of a specified dust.
the device is not being operated. This applies to the immediate
surrounding conditions of the electronic device. Dust-Protected Enclosure
Device Type Manager (DTM) An international term describing an enclosure in which the
ingress of dust is not totally prevented, but dust does not enter
Manufacturers supply DTMs for their devices to allow a in sufficient quantity to interfere with the safe operation of the
FDT frame application in the DCS or master to configure and equipment or accumulate in a position within the enclosure
service their equipment. where it is possible to cause an ignition hazard.
Signal from a hazardous area instrument that is an on/off type An enclosure so constructed that dust will not enter the
electrical input to the safe area (i. e., contact closure, proximity enclosing case under specified test conditions.
sensor).
Digital Output E
On/Off type signal from the safe area to the hazardous area
(i. e., signal to a solenoid or LED cluster). EC-Type Examination Certificate
General Notes
Appendix
protection.
Entity Parameters
The four categories that are set by the certification agency in Ex "q"
order to properly match the intrinsic safety barrier to the
hazardous area instrument. These four parameters are Designation for the powder-filling (segregation) method of
voltage, current, capacitance and inductance. protection.
Ethernet Ex "s"
High speed bus, which lends itself to various protocols. Most Designation for the special (special protection) method of
commonly used protocols are MODBUS TCP and Ethernet IP. protection. This method is standardized only in Great Britain
Redundancy solutions are in place. Slaves are often and Germany.
Glossary
connected to the bus via switches.
Explosion-Proof Enclosure
Ex "d" An enclosure that is capable of withstanding an explosion of a
Designation for the flame-proof (explosion containment) gas or vapor within it and of preventing the ignition of an
method of protection. explosive gas or vapor that may surround it and that operates
at such an external temperature that a surrounding explosive
gas or vapor will not be ignited. This type of enclosure is similar
Ex "e"
General Notes
to a flame-proof enclosure.
Designation for the increased safety (prevention) method of
protection. Explosion-Proof Equipment (apparatus)
Equipment or apparatus enclosed in an explosion-proof
Ex "i"
enclosure.
Designation for the intrinsic safety (prevention) method of
protection. This method consists of two categories-"ia" and
"ib." F
Model Number
Ex "ia" Fault
Index
This intrinsic safety category is limited to low power circuits A defect or electrical breakdown of any component, spacing or
and is suitable for process instrumentation. Up to two faults are insulation that alone or in combination with other faults may
allowed and can be used in Zones 0, 1, and 2. adversely affect the electrical or thermal characteristics of the
intrinsically safe circuit. If a defect or breakdown leads to
Ex "ib" defects or breakdowns in other components, the primary and
This intrinsic safety category is similar to the Ex "ia" method, subsequent defects and breakdowns are considered to be a
except that category "ib" allows only one fault and can only be single fault.
used in Zones 1 and 2. Countable Fault
A fault that is applied to a part of the electrical apparatus that
Ex "m" meets the constructional requirements of this standard.
Designation for the encapsulation (segregation) method of Uncountable Fault
protection.
A fault that is applied to areas of the electrical apparatus that
do not meet the constructional requirements of this standard. If
Ex "n" application of a countable fault leads to subsequent defects
Designation for the simplified (prevention) method of and breakdowns, they are considered to be uncountable
protection. faults.
FAT
11/2015
FieldConnex
Abbreviation for good automated manufacturing practices.
FieldConnex is a comprehensive fieldbus infrastructure that
connects the control system to intelligent field instruments via
a two wire bus.
Gateway and Com Unit
Bus systems employ gateways to interface the DCS or PLC
Field Device Tool (FDT) master with the Remote I/O slaves. Their properties depend on
the protocol they support.
FDT is the name of an interface specification. It offers the
frame application for DTM (drivers) supplied by device
manufacturers.
Grounding Device
An impedance device used to connect conductors of an
Glossary
Flame-Proof Enclosure electric system to ground for the purpose of controlling the
ground current or voltages to ground, or a nonimpedance
An International term describing an enclosure that can
device used to temporarily ground conductors for the purpose
withstand the pressure developed during an internal explosion
of the safety of workmen. The grounding device may consist of
of an explosive mixture and that prevents the transmission of
a grounding transformer or a neutral grounding device, or a
the explosion to the explosive atmosphere surrounding the
combination of these. Protective devices, such as surge
enclosure and that operates at such an external temperature
arresters, may also be included as an integral part of the
that a surrounding explosive gas or vapor will not be ignited.
device.
General Notes
I Inductance
The property of an electric circuit by virtue of which a varying
I.S. Ground current induces an electromotive force in that circuit or in a
neighboring circuit. The practical difference between
A dedicated ground system to which zener barriers are
capacitance and inductance in an intrinsically safe circuit is
connected. The resistance to ground path must be less than or
minimal. Both store energy, but an inductor will release energy
equal to 1 from any zener barrier to designated ground
when a circuit is broken, and a capacitor will release energy
electrode.
Appendix
when the circuit is made.
I.S. Insulation coordination
Abbreviation for intrinsic safety.
The assignment of the insulation characteristics of an
apparatus in accordance with:
I/O Module
1. the expected overvoltages
A module that provides basic input and output functions 2. the characteristic values of the overvoltage precautions
between the automation system and the field devices.
3. the expected surrounding conditions
Disregarding specialty modules, there are four basic types
4. the protective measures against contamination
available from various vendors - analog input, analog output,
discrete input, and discrete output.
Glossary
Insulator
IEC A material that conducts electrons slowly. The importance to
intrinsic safety is that air (a spatial distance) is often an
Abbreviation for International Electrotechnical Commission.
insulator.
An international commission of which most nations are
members. IEC standards directly affect equipment for sale
internationally. The benefit of participation in the IEC is that Internal Wiring
costly differences in plant or equipment design can be avoided
General Notes
Wiring and electrical connections that are made within the
by designing equipment consistent with IEC documents where apparatus by the manufacturer. Within racks or panels,
feasible. interconnections between separate pieces of apparatus made
in accordance with detailed instructions from the apparatus
Ignitable Gas Mixture manufacturer are considered to be internal wiring.
A gas -air mixture that is capable of being ignited by an open
flame, arc or spark or high temperature. Intrinsic Safety Barrier
A component containing a network designed to limit the
Ignition (Autoignition) Temperature
Model Number
energy (voltage and current) available to the protected circuit
in the hazardous (classified) location under specified fault
The minimum uniform temperature required to initiate or cause
Index
conditions.
self-sustained combustion of a solid, liquid, or gaseous
substance (independent of any other ignition source).
Intrinsic Safety Ground Bus
Increased Safety A grounding system that has a dedicated conductor separate
from the power system so that ground currents will not
An international term that describes a type of protection in
normally flow and that is reliably connected to a ground
which various measures are applied so as to reduce the
electrode (e. g., in accordance with Article 250 of NEC,
probability of excessive temperatures and the occurrence of
ANSI/NFPA 70, or Section 10 of CEC Part I, CSA C22.1).
arcs or sparks in the interior and on the external parts of
electrical apparatus that do not produce them in normal
service. This type of protection is referred to by IEC as "Ex e."
11/2015
265151
Edition
normally or in specified fault conditions, is incapable, under the be removed readily by a hammer, screwdriver, and pliers at
prescribed test conditions, of causing ignition of a mixture of the time of installation in order to provide a hole for the
flammable or combustible material in air in the mixture's most attachment of an auxiliary device or raceway, cable, or fitting.
easily ignited concentration.
which all the circuits are intrinsically safe, or that is designed to Labeled Equipment
form part of an intrinsically safe system.
Equipment or materials, to which has been attached a label,
Intrinsically Safe Ground symbol, or other identifying mark of an organization concerned
with product evaluation, that may maintain periodic inspection
A clearly identified conductor of not less than 12 AWG/4 mm2 of the production of labeled equipment or materials, and by
cross-sectional area with a total impedance from barrier whose labeling the manufacturer indicates compliance with
ground bus bar to main power system earth of not more than appropriate standards or performance in a specified manner.
1 .
Model Number
LEL
Intrinsically Safe System
Index
Listed
Equipment or materials, included in a list published by an
organization concerned with product evaluation, that maintains
periodic inspection of production of listed equipment or
materials and whose listing states either that the equipment or
materials meets appropriate standards or has been tested and
found suitable for use in the specified manner.
11/2015
265151
Edition
Appendix
The maximum power that can be applied to the terminals of an
activities typically include locating causes of faulty
intrinsically safe device without invalidating the intrinsic safety
performance, replacement of defective components,
of the device.
adjustment of internal controls, and the like.
Glossary
the like.
The total unprotected internal capacitance of the intrinsically
safe apparatus that must be considered as appearing across
Make/Break Components the terminals of the intrinsically safe apparatus.
Components having contacts that can interrupt a circuit (even
if the interruption is transient in nature). Examples of Maximum Internal Inductance (Li)
make/break components are relays, circuit breakers,
servo potentiometers, adjustable resistors, switches, The total unprotected internal inductance of the intrinsically
General Notes
connectors, and motor brushes. safe apparatus that must be considered as appearing across
the terminals of the intrinsically safe apparatus.
Maximum External Capacitance (Co; Ca)
Maximum Internal Inductance to
Maximum capacitance in an intrinsically safe circuit that can be Resistance Ratio (Li/Ri)
connected to the connection facilities of the apparatus without
invalidating intrinsic safety. Ratio of inductance (Li) to resistance (Ri) which is considered
as appearing at the external connection facilities of the
Maximum External Inductance (Lo; La) electrical apparatus.
Model Number
Maximum value of inductance in an intrinsically safe circuit that Maximum Output Current (Io, Isc)
Index
can be connected to the connection facilities of the apparatus
without invalidating intrinsic safety. Maximum current (peak AC or DC) in an intrinsically safe
circuit that can be taken from the connection facilities of the
Maximum External Inductance to apparatus.
Resistance Ratio (Lo/Ro)
Maximum Output Power (Po)
Ratio of inductance (Lo) to resistance (Ro) of any external
circuit that can be connected to the connection facilities of the Maximum electrical power in an intrinsically safe circuit that
electrical apparatus without invalidating intrinsic safety. can be taken from the apparatus.
Non-Incendive Component
Minimum Igniting Voltage A component having contacts for making or breaking a
Minimum voltage of capacitive circuits that causes the ignition specified incendive circuit in which the contacting mechanism
of the explosive test mixture in the spark-test apparatus. is constructed so that the component is not capable of ignition
of the specified flammable gas or vapor-in-air mixture when
MODBUS tested as specified by appropriate test procedure. The housing
of a non-incendive component is not intended to exclude the
Legacy medium speed master/slave bus protocol based on flammable atmosphere or contain an explosion.
Model Number
Appendix
Abbreviation for Nationally Recognized Testing Laboratory.
This recognition indicates that the Occupational Safety & source.
Health Administration has accredited certain organizations to
evaluate products according to consensus based safety Polarity
standards.
Zener barriers are available in polarized (DC) and non-
polarized (AC) versions. Positive polarity types have the
negative side of the circuit grounded, while negative polarity
O types have the positive side of the circuit grounded. Non-
polarized barriers have zener diodes connected in inverse
Operational Maintenance series pairs and can be used in both AC and DC circuits.
Any maintenance activity, other than corrective maintenance,
Glossary
intended to be performed by the operators and which is
PROFIBUS DP, DP V1
required in order for the equipment to serve its intended Widely popular master/slave bus protocol based on RS485
purpose. Such activities typically include the correcting of hardware architecture. Offers fast and deterministic data
"zero" on a panel instrument, changing charts, making exchange. Standard also covers redundancy. Slaves are
records, adding ink, etc. connected to the bus in parallel.
General Notes
Abbreviation for Occupational Safety and Health Assembly
Administration. The OSHA Act was passed by the U.S. A component or assembly which is so unlikely to become
Congress in 1971. Part 1910 of the OSHA regulations adopted defective in a manner that will lower the intrinsic safety of the
the 1968 NEC and defined "approved" to mean "listed by UL or circuit it may be considered not subject to fault when analysis
FM." "Approved" was redefined in 1972, providing exceptions or tests for intrinsic safety are made.
to FM or UL listing; however, in practice the emphasis on
listing remained unchanged. Listing requirements increased
PTB
interest in developing standards for certain categories of
Model Number
apparatus, such as process control instrumentation. Third- Abbreviation for Physikalisch-Technische Bundesanstalt. An
party approval agencies (e. g., UL, FM, CSA) for electrical approval agency in Germany that has the authority to accept or
Index
equipment must be accredited by OSHA. reject the design of an electrical apparatus based on
recognized safety standards.
Overvoltage category
The assignment of an electrical apparatus in accordance with
the expected overvoltage.
R
Table:
Redundancy
The assignment of rated operating voltages to the rated surge
voltages Redundancy is used to ensure that a Remote I/O station can
continue to work even when there is a fault in a master, in a
Rated operating voltage (V) Rated surge voltages (V) for bus line, in a communication unit, or in a power supply.
for alternating voltage overvoltage category
systems in accordance with
I II III IV
Remote I/O
DIN IEC 38
A system of intrinsically safe galvanically isolated input and
230/400/277/4801) 1500 2500 4000 6000
output devices placed in various locations around a production
400/690 2500 4000 6000 8000 plant. They provide a way to communicate effectively with
1000 4000 6000 8000 12000 modern DCS systems and proven legacy field devices.
1)
Remote I/O connect a wide range of digital and analog sensors
Rated operating voltage of 500 V is set.
and actuators to process control systems over a fieldbus. A
variety of gateways are available to make use of different bus
11/2015
protocols.
265151
Edition
corresponding power lost by dissipation as heat or as other A fuse- or resistor- protected diode barrier.
permanent radiation or loss of electromagnetic energy from
the circuit. Signal Conditioning
Signal conditioning is an important part of any automation
RS 232 system where electrical isolation, electronic signal conversion,
An EIA standard that specifies the electrical, mechanical, and and measurement accuracy are critical characteristics of the
functional characteristics for serial communications. Used in control loop architecture. This is one of the tasks Remote I/O
General Notes
T Z
Temperature Code (Temperature Zener Barrier
Classification) An assembly consisting of a fuse, voltage-limiting shunt
A system of classification by which one of 14 temperature diodes, and a current-limiting resistor or other current-limiting
identification numbers (internationally, six temperature components.
Appendix
classes) is allocated to an electrical apparatus. The It is designed to limits current and voltage to the hazardous
temperature code represents the maximum surface area to a level below that which would ignite a specific gas/air
temperature of any component that may come in contact with mixture.
the flammable gas or vapor mixture.
The fuse protects the diodes from open circuiting when high
fault current flows.
Termination Panel
A mechanical assembly that resides in front of the I/O system Zener Diode
and performs signal conditioning, electrical isolation, and other
A class of silicon diodes that exhibit in the avalanche
functions.
breakdown region a large change in reverse current over a
very narrow range of reverse voltage. This characteristic
Thermistor
Glossary
permits a highly stable reference voltage to be maintained
An electron device that makes use of the change of resistivity across the diode despite a relatively wide range of current
of a semiconductor with change in temperature. through the diode.
General Notes
when the junctions are at different temperatures. presence, of flammable concentrations of gases and vapors.
The term Division is used in the United States and Canada.
TIB
Zone 0
Abbreviation for Transformer Isolated Barrier. A term used to
describe an isolated intrinsic safety barrier used for hazardous An area in which an explosive gas-air mixture is continuously
area applications. Although a typical TIB will employ multiple present or present for long periods. Equal to a Class I, Division
means of isolation, the term TIB is used to generically describe 1 hazardous location.
this type of barrier.
Zone 1
Model Number
Transmitter (Tx) An area in which an explosive gas-air mixture is likely to occur
Index
A device for transmitting a coded signal when operated by any in normal operation. Equal to a Class I, Division 1 hazardous
one of a group of actuating devices. location.
Zone 2
U An area in which an explosive gas-air mixture is not likely to
occur and if it does occur, will only exist for a short time. Equal
UEL to a Class I, Division 2 hazardous location.
Abbreviation for upper explosive limit (upper flammable limit).
Zone 20
UL An area in which a combustible dust cloud is part of the air
permanently, over long periods of time or frequently. Equal to a
Abbreviation for Underwriters Laboratories, Inc, a third party
Class II, Division 1 hazardous location.
certification agency that is an independent, self-supporting,
nonprofit testing laboratory and standards developer. It is
recognized by OSHA as a Nationally Recognized Testing
Zone 21
Laboratory in the United States. The presence of UL, CSA, or An area in which a combustible dust cloud in air is likely to
FM certification labels on equipment is normally sufficient occur in normal operation. Equal to a Class II, Division 1
evidence to the local inspector that the product is designed to hazardous location.
meet recognized safety standards.
Zone 22
11/2015
11/2015
265151
Edition
Appendix
3. The information and statements do not provide any guarantee or warrant any characteristics of the products.
4. The information and statements in the printed product information reflect the current status at the time of issue. Changes made
after the printed product information is issued are published in product data sheets on the Pepperl+Fuchs homepage. This
information is available at www.pepperl-fuchs.com.
5. All information, statements, and technical specifications contained therein are based on valid standards and comply with
relevant standardized measuring methods.
6. Customers are always responsible for independently determining the suitability of our products for the intended application.
Only customers are aware of all the boundary conditions and influencing factors associated with the intended purpose. Due
to the enormous number of potential application options offered by Pepperl+Fuchs products and the subsequent range of
Glossary
possible external influences and a potential overlap of these influences in the application of products, Pepperl+Fuchs cannot
accept liability for any aspect of the actual customer application. This applies in particular to, but not limited to, applications in
safety systems and explosion hazardous areas as well as environmental influences such as chemicals, pressure, temperature
fluctuations, moisture, mechanical influences, and incorrect installation.
7. Customers who intend to use Pepperl+Fuchs products in new applications or applications where they do not have adequate
experience can contact Technical Sales Support (service line) and discuss the suitability of the products for the intended
application with our specialists. Customers are obliged to provide realistic and complete information on all the relevant
conditions associated with the application in writing to prevent misunderstandings.
General Notes
8. All rights reserved. Reprint or reproduction of any material in part or in whole only with express written consent of
Pepperl+Fuchs.
Model Number
Index
11/2015
265151
Edition
11/2015
265151
Edition
Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition
11/2015
265151
Edition
Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition
11/2015
265151
Edition
Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition
C
CAB-DVM-**-S37I16-MX-01000. . . . . . . . . . . . . . . . 58
H
Appendix
HiD2000 Blank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
HiD2024 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
HiD2030SK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
HiD2038 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
HiD2824 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
HiD2844 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
HiD2872 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
HiDTB04-DVM-IDC1-SC-R1-DI16 . . . . . . . . . . . . . . 32
Glossary
HiDTB04-DVM-IDC1-SC-R2-DI16 . . . . . . . . . . . . . . 36
HiDTB04-DVM-IDC3-SC-R2-DO08 . . . . . . . . . . . . . 40
HiDTB04-DVM-IDC4-SC-NO-AM16. . . . . . . . . . . . . 48
HiDTB08-DVM-IDC4-SC-R1-SM32 . . . . . . . . . . . . . 52
General Notes
Model Number
Index
11/2015
265151
Edition