You are on page 1/ 102

Alliance Member

Interface Technology
Termination Board Solution

H-System for Emerson DeltaV


Termination Board Solutions for Emerson DeltaV Table of Contents

Introduction 2

Termination Board Solutions 6

System Description 7

Termination Boards 24

H-System Isolated Barriers 60

Appendix 74
Glossary 77
General Notes 91
Model Number Index 98

1
Introduction Termination Board Solutions for Emerson DeltaV

The Catalog
This catalog presents the product portfolio of Termination Board solutions for Emerson DeltaV and, compiled by our inhouse
Termination Board experts, shares concise technical knowledge based on years of substantiated experience.

Product Selection Tables


Product selection tables are located at the beginning of each section, making it easy to find the product you need.

Termination Board Solutions for Emerson DeltaV Selection Tables

Multi Channel Applications


Digital Inputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page

Channels

Channels

Channels
Modules

DeltaV
Series

Series

Type

Type
Card

M 8-channel DI Series 2 8 HiDTB08-DVM-IDC4-SC-R1-SM32 8 32 52 HiD2824 4 65


(24 V DC, dry contact) simplex HiD2844 66
M 32-channel DI Series 2 32 HiDTB04-DVM-IDC1-SC-R1-DI16 4 16 32 HiD2844 4 66
(24 V DC, dry contact) simplex
M 32-channel DI Series 2 Plus 32 HiDTB04-DVM-IDC1-SC-R2-DI16 4 16 36 HiD2844 4 66
(24 V DC, dry contact) redundant
S 8-channel DI simplex 8 HiDTB08-DVM-IDC4-SC-R1-SM32 8 32 52 HiD2824 4 65

Digital Inputs
(NAMUR) HiD2844 66
S 32-channel DI simplex 32 HiDTB04-DVM-IDC1-SC-R1-DI16 4 16 32 HiD2844 4 66
(24 V DC, dry contact)
S 32-channel DI Plus 32 HiDTB04-DVM-IDC1-SC-R2-DI16 4 16 36 HiD2844 4 66
(24 V DC, dry contact) redundant

Digital Outputs

Digital Outputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels

Channels

Channels
Modules
Series

Type

Type

Type
Card

Product Data Pages M 8-channel DO Series 2 8 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67

Analog Ouputs
Analog Inputs/
(24 V DC, high side) simplex HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2872 2 67
M 32-channel DO Series 2 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67

The product data sheets contain all of the relevant data necessary to select and specify the equipment. It includes four major
(24 V DC, high side) simplex
M 32-channel DO Series 2 Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) redundant

sections: Features, Function, Technical Data, and Diagrams. Surrounding these key elements are navigation tools necessary to
S 8-channel DO
(24 V DC, high side)
simplex 8 HiDTB04-DVM-IDC3-SC-R2-DO08
HiDTB08-DVM-IDC4-SC-R1-SM32
4
8 16
8 40
52
HiD2872
HiD2872
2
2
67
67

help identify the product including special colors, markings, and symbols.
S 32-channel DO
(24 V DC, high side)
simplex 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67

Universal
S 32-channel DO Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67

Comprehensive product information can be found at www.pepperl-fuchs.com. (24 V DC, high side) redundant

Model number Primary function


Accessories

Product highlights
08/2015
265151

HiD2844
Function description
Switch Amplifier
Edition

HiD2844

Refer to "General Notes Relating to Pepperl+Fuchs Product Information". HiDTB04-DVM-IDC1-SC-R1-DI16


Features Technical data Termination Board
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
HiDTB04-DVM-IDC1-SC-R1-DI16
• Singapore:
4-channel+65 6779 9091 barrier
isolated
[email protected]
Supply 27
Rated voltage Un 20.4 ... 30 V DC via Termination Board
• 24 V DC supply (bus powered)
Features Power dissipation 0.35 W at 24 V (per channel)

Color-coded
• Dry contact or NAMUR inputs Input
• System Board for Emerson
• 4 passive DeltaV
transistor outputs Rated values acc. to EN 60947-5-6 (NAMUR)
• For one 32-channel
• Line fault DI detection
card via 40-pin
(LFD)Mass Termination Connectable sensor types potential free contact or proximity sensor

navigation tabs
H-System

Block Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
• Up to SIL2 acc. to IEC 61508
• For 4 modules/16 channels Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum
• RecommendedFunctionmodule: HiD2844 (DI) value
Output
• Volt-free fault indication output
DeltaV

This isolated barrier is used for intrinsic Rated voltage Un 30 V


• 24 V DC supply, reverse polaritiy protected, optional

Termination Boards
safety applications. It transfers digital Rated current In 50 mA
daisychainable
signals (NAMUR sensors/mechanical Output one optocoupled transistor per channel
• Hazardous area: screw terminals, blue Signal level 1-signal: (external voltage) -1 V
contacts) from a hazardous area to a safe
• Safe area:area.
IDC connector, 20-pin 0-signal: blocked output (off-state current max. 50 A,
typical 5 A)

H-System
Function The proximity sensor or switch controls a Error message output
Digital Inputs

passive transistor for the safe area load. Output type open collector transistor (internal fault bus)
The
The function of themodule outputBoard
Termination changes state
as well aswhen
the connector
Transfer characteristics
pin assignmenttheexactly
input signal
fit thechanges state.
requirement ofThe normal
DeltaV Traditional
Switching frequency < 2 kHz
Digital Inputs

I/O systems. output state can be reversed with the Ambient conditions
selector switches on the side of the unit. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Information about line fault detection of the interface modules
Line
is available for thefault
systemdetection (LFD) contact.
as volt-free can be selected Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
or disabled via a selector switch. Mechanical specifications
The Termination Boards are supplied with a robust plastic Degree of protection IP20
During an error condition, the transistor
Digital Outputs

housing as standard. This design permits the fast and reliable Mass approx. 140 g
reverts to its de-energized state and the
installation on 35 mm DIN mounting rail acc. to EN 60715 inDimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
the cabinet. LEDs indicate the fault. A separate fault
Mounting on Termination Board
output bus is available. The fault
Digital Outputs

Coding pin 1 and 2 trimmed


Application conditions can be monitored via a Fault
Data for application in connection see page 72 for entity parameters
Indication Board.
with Ex-areas
This module
For detailed listing mounts on
of connectable a HiD
cards Termination
see application EC-Type Examination Certificate CESI 02 ATEX 086
section. Board. Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC
Statement of conformity PF 11 CERT 2109 X
Analog Inputs

Group, category, type of protection, E II 3G Ex nA IIC T4 Gc [device in zone 2]


temperature class

Hazardous area products


CSA approval
Analog Ouputs
Analog Inputs/

Control drawing 366-005CS-12B (cCSAus)


Analog Outputs

Diagrams
Connection

Front view drawing


Front view

LED green:
24 V DC (I),
Universal

Power supply
HiD2844
24 V DC (II),
1.5 kΩ SL2 SL1
PWR

LEDs red:
Line fault
1.5 kΩ FAULT STATUS
LEDs yellow:
Status output I + 1 Fault
5a 8a 11 + I
1+ 10 kΩ
channel 1 ... 4 channel 1 ... 4
CH 1

I 10 kΩ CH 2 1.5 kΩ - 4 5b 7a 14 -
4- + 2 1a 10a 12 + II
II
Accessories

10 kΩ
1.5 kΩ
CH 3

2+

Connection diagram
- 5 1b 9a 15 -
CH 4

Switch 1 ... 8 1.5 kΩ


HiD
II 10 kΩ + 3 3a 9b 13 +
Edition 265151 11/2015

2844 III 10 kΩ III


1.5 kΩ
5- 4 ch 4 X20 - 6 3b 10b 16 -
CN11.5 kΩ
Switch
Accessories

Amplifier
3+
III 10 kΩ
IV 3 10 kΩ
+ 7 7a 8b 17 + IV
08/2015

- 8 7b 7b 18 -
6-
1.5 kΩ
Place for 2 DeltaV 32DI
7+ labeling 1a, 1b - 24 V DC
IV 10 kΩ 1 2a, 2b +
FAULT
6b
265151

8-
08/2015

Zone 0, 1, 2

SIL rating designator


9 Div. 1, 2 Termination Board
Edition
265151
6 5 4
9 8 7

3 2 1

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Zone 0, 1,Pepperl+Fuchs
2
66 Group
Div. 1, 2 www.pepperl-fuchs.com
USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
Edition

[email protected] [email protected] [email protected]

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


32 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


2 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Introduction

The Website The Product Selector


For the most up-to-date and comprehensive product Use the product selector to navigate to the required product
information, please visit our website: group.
www.pepperl-fuchs.com

On the website, you can narrow your search and find the
product information you need in two different ways:
„„To find information about a specific product, use the
search function. Here, you can choose the following:
„„To find a product based on specific features, use the „„a list of products or
product selector.

The Search Function


In the search field on our website enter either of the following: „„a table with a list of attributes
„„Product name if known
„„Part of the product name, e. g., from the catalog
„„Part number, e. g., from the type label of a product you
have already purchased
Now select the required product feature. Each time you make
Note: The search function is not case sensitive. You can also a selection, the number of products that meet the criteria is
carry out a wildcard search, using *. displayed. The more features you define, the fewer suitable
products will be displayed.
Finally, click on Product Selector Tool Results to access
the product list and view the required product.

Depending on the completeness of the product name or part


number you entered, the search result displays a hit list with
a short description of each product from which you can select
the required product.
Edition 265151 11/2015

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
3
Introduction Termination Board Solutions for Emerson DeltaV

The Pepperl+Fuchs and Emerson Typical Cabinet Layout


Termination Board Solutions Similar to the DeltaV M-series and S-series based traditional
I/O cards, the DeltaV specific Termination Boards and
H-System isolated barriers can be mounted in horizontal and
Introduction vertical orientation. The most condensed cabinet layout can
be achieved by following the vertical orientation approach, as
The H-System offers a collection of high density channel
cable ducts for IS signals can be easily separated from cable
barriers which are highly reliable with low power dissipation
ducts for non-IS Signals, as shown below.
characteristics. It is the ideal solution with DeltaV traditional
I/O cards for hazardous area location applications where
field signals are coming out of a Class I/Div.1 or Zone1
environment.
To fully leverage the high channel density advantage of the
H-System, DeltaV specific Termination Boards have been
developed, which can be connected to DeltaV M-series
and S-series based traditional I/O cards, using off-the-shelf
1:1 pin compatible cables. Together, they offer a low footprint,
reliable and tightly integrated isolated barrier solution, which
is quick and easy to install.

HiD Multi-Channel IS Solutions


Isolated Barriers and Termination Boards
The H-System isolated barriers provide line fault monitoring
as well as optimized, native HART communication to
the DeltaV I/O cards and are supported by the DeltaV
Engineering Tools and AMS Device Manager.
DeltaV Series 2 Plus traditional I/O cards do also provide a
termination fault detection feature, sensing the Termination
Boards and providing information about the status of the
connected Termination Board, isolated barriers on the board,
field signals as well as the cables and connectors between
the board and the DeltaV I/O card. The DeltaV specific
Termination Boards are optimized in footprint, as they have
exactly the same width as two DeltaV I/O cards while holding
a maximum of 4 isolated barriers (16 channels). On top, no
additional 24 V DC power distribution is required because
the Termination Boards draw power from the same source as
the DeltaV I/O cards. In case of redundant DeltaV I/O cards,
power redundancy feeding of the Termination Boards and
isolated barriers occurs naturally.
4
3
2
1

4
3
2
1

Figure 2 800 mm wide cabinet with vertical orientated DeltaV Carrier


System and Termination Boards with H-System isolated barriers
Edition 265151 11/2015

Figure 1 2 Termination Boards with 8 H-System isolated barriers =


32 Channel of IS DI inputs

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


4 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Introduction

HiC Single-Channel IS Solutions


(Cable Solutions) 8 X20
7
For 1-channel H-System isolated barriers offering highest 6
signal integrity SUB-D-Boards with pre-assembled cable 5
solutions. They are adapted to the respective DeltaV I/O card. 4
The plug and play solution reduces the effort for mounting 3
and factory acceptance test to a minimum. So the 1-channel 2
portfolio for highest signal integrity is complete. 1 X1
The pictures show some exemplary components of cable
solutions.
The relationship between Emerson DeltaV I/O cards, Figure 4 Example HiCTB08-SDC-44C-SC-RA
cables and Termination Boards of Pepperl+Fuchs is
shown in the selection table on page 29 f.
16
X20
15
1-channel Solution X2
14
13
12
11
10
9

8
X1
7
6
5
4
3
2
Figure 3 Cable CAB-DVM-**-S37I**-**-***** 1

Figure 5 Example HiCTB16-SDC-44C-SC-RA


Edition 265151 11/2015

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
5
Termination Board
Solutions for Emerson
DeltaV

Edition 265151 11/2015

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


6 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description

Safety Improper Use


Protection of the personnel and the plant is not ensured if the
Instruction Manual Isolated Barriers device is not being used according to its intended use.

Termination Boards
Marking The device is not suitable for isolating signals in power
installations unless this is noted separately in the
H-System, isolated barriers corresponding datasheet.
Device identification Mounting and Installation
Model number Do not mount a damaged or polluted device.
ATEX approval
Mount the device in a way that the device is protected against
Group, category, type of protection, temperature classification mechanical hazard. Mount the device in a surrounding
enclosure for example.
The exact designation of the device can be found on the name The device must be installed outside of the hazardous area.
plate on the device side.
Mount the device with at least a degree of protection of IP20
Pepperl+Fuchs GmbH according to IEC/EN 60529.
Lilienthalstraße 200, 68307 Mannheim, Germany The device must be installed and operated only in an

Description
environment that ensures a pollution degree 2 (or better)

System
Target Group, Personnel according to IEC/EN 60664-1.
Responsibility for planning, assembly, commissioning, If used in areas with higher pollution degree, the device needs
operation, maintenance, and dismounting lies with the plant to be protected accordingly.
operator. All circuits connected to the device must comply with the
Mounting, installation, commissioning, operation, maintenance overvoltage category II (or better) according to
and dismounting of the device may only be carried out by IEC/EN 60664-1.
appropriate trained and qualified personnel. The instruction Observe the installation instructions according to
manual must be read and understood. IEC/EN 60079-14.
Prior to using the device you should make yourself familiar with Requirements for Usage as Associated Apparatus
the device and carefully read the instruction manual.
If circuits with type of protection Ex i are operated with non-
Reference to Further Documentation intrinsically safe circuits, they must no longer be used as
circuits with type of protection Ex i.
Observe laws, standards, and directives applicable to the
intended use and the operating location. Intrinsically safe circuits of associated apparatus can be led
into hazardous areas. Observe the compliance of the
The corresponding datasheets, declarations of conformity,
separation distances to all non-intrinsically safe circuits
EC-type-examination certificates, certificates and control
according to IEC/EN 60079-14.
drawings if applicable supplement this document. You can find
this information under www.pepperl-fuchs.com. Observe the compliance of the separation distances between
two adjacent intrinsically safe circuits according to
Observe the instruction manuals for the respective
IEC/EN 60079-14.
Termination Boards.
Observe the maximum values of the device, when connecting
Intended Use the device to intrinsically safe apparatus.
The device is only approved for appropriate and intended use. When connecting intrinsically safe devices with intrinsically
Ignoring these instructions will void any warranty and absolve safe circuits of associated apparatus, observe the maximum
the manufacturer from any liability. peak values with regard to explosion protection (verification of
The device is used in control and instrumentation technology intrinsic safety). Observe the standards IEC/EN 60079-14 or
(C&I technology) for the galvanic isolation of signals such as IEC/EN 60079-25.
20 mA and 10 V standard signals or alternatively for adapting
or standardizing signals. The device has intrinsically safe
circuits that are used for operating intrinsically safe field
devices in hazardous areas.
Only use the module with the designated Termination Boards.
Use the device only within the specified ambient conditions.
Only use the device stationary.
The device is an associated apparatus according to
11/2015

IEC/EN 60079-11.
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
7
System Description Termination Board Solutions for Emerson DeltaV

If no Lo and Co values are specified for the simultaneous Instruction Manual Termination Boards
appearance of lumped inductances and capacitances, the
following rule applies. Marking
• The specified value for Lo and Co is used if one of the
Termination Boards

H-System, Termination Boards


following conditions applies:
Device identification
– The circuit has distributed inductances and
Model number
capacitances only, e. g., in cables and connection
lines. ATEX approval
– The total value of Li (excluding cable) of the circuit Group, category, type of protection, temperature classification
is < 1 % of the specified Lo value.
– The total value of Ci (excluding cable) of the circuit The exact designation of the device can be found on the name
is < 1 % of the specified Co value. plate on the device side.

• A maximum of 50 % of the specified value for Lo and Co is Pepperl+Fuchs GmbH


used if the following condition applies: Lilienthalstrasse 200, 68307 Mannheim, Germany

The total value of Li (excluding cable) of the circuit is  1 %


of the specified Lo value. Target Group, Personnel
Description

The total value of Ci (excluding cable) of the circuit is  1 %


System

Responsibility for planning, assembly, commissioning,


of the specified Co value. operation, maintenance, and dismounting lies with the plant
The reduced capacitance for gas groups I, IIA and IIB must operator.
not exceed the value of 1 µF (including cable). The Mounting, installation, commissioning, operation, maintenance
reduced capacitance for gas group IIC must not exceed and dismounting of the device may only be carried out by
the value of 600 nF (including cable). appropriate trained and qualified personnel. The instruction
If more channels of one device are connected in parallel, manual must be read and understood.
ensure the parallel connection is made directly at the terminals
of the device. When verifying the intrinsic safety, observe the Prior to using the device you should make yourself familiar with
maximum values for the parallel connection. the device and carefully read the instruction manual.

Operation, Maintenance, Repair Reference to Further Documentation

The devices must not be repaired, changed or manipulated. If Observe laws, standards, and directives applicable to the
there is a defect, the product must always be replaced with an intended use and the operating location.
original device. The corresponding datasheets, declarations of conformity,
EC-type-examination certificates, certificates and control
Delivery, Transport, Disposal
drawings if applicable supplement this document. You can find
Check the packaging and contents for damage. this information under www.pepperl-fuchs.com.
Check if you have received every item and if the items Observe the instruction manuals for the respective modules.
received are the ones you ordered.
Intended Use
Always store and transport the device in the original
packaging. The device is only approved for appropriate and intended use.
Ignoring these instructions will void any warranty and absolve
Store the device in a clean and dry environment. The permitted the manufacturer from any liability.
ambient conditions (see datasheet) must be considered.
The device is used in instrumentation and control technology
Disposing of device, packaging, and possibly contained (I&C technology). The device is used for the galvanic isolation
batteries must be in compliance with the applicable laws and of intrinsically safe circuits and non-intrinsically safe circuits.
guidelines of the respective country. The device is used as interface between modules, field circuits
and control circuits.
Only use the Termination Board with the designated modules.
Use the device only within the specified ambient conditions.
Only use the device stationary.
The device is an associated apparatus according to
IEC/EN 60079-11.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


8 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description
Improper Use When connecting intrinsically safe devices with intrinsically
safe circuits of associated apparatus, observe the maximum
Protection of the personnel and the plant is not ensured if the
peak values with regard to explosion protection (verification of
device is not being used according to its intended use.
intrinsic safety). Observe the standards IEC/EN 60079-14 or

Termination Boards
The device is not suitable for isolating signals in power IEC/EN 60079-25.
installations unless this is noted separately in the
corresponding datasheet. If more channels of one device are connected in parallel,
ensure the parallel connection is made directly at the terminals
Mounting and Installation of the device. When verifying the intrinsic safety, observe the
Do not mount a damaged or polluted device. maximum values for the parallel connection.

Mount the device in a way that the device is protected against Operation, Maintenance, Repair
mechanical hazard. Mount the device in a surrounding The devices must not be repaired, changed or manipulated. If
enclosure for example. there is a defect, the product must always be replaced with an
The device must be installed outside of the hazardous area. original device.
Mount the device with at least a degree of protection of IP20 Delivery, Transport, Disposal
according to IEC/EN 60529.
Check the packaging and contents for damage.
The device must be installed and operated only in an
Check if you have received every item and if the items

Description
environment that ensures a pollution degree 2 (or better)

System
received are the ones you ordered.
according to IEC/EN 60664-1.
Always store and transport the device in the original
If used in areas with higher pollution degree, the device needs
packaging.
to be protected accordingly.
Store the device in a clean and dry environment. The permitted
All circuits connected to the device must comply with the
ambient conditions (see datasheet) must be considered.
overvoltage category II (or better) according to
IEC/EN 60664-1. Disposing of device, packaging, and possibly contained
batteries must be in compliance with the applicable laws and
Observe the installation instructions according to
guidelines of the respective country.
IEC/EN 60079-14.
Observe the corresponding documentation or the information
on the device for the correct assignment of the terminals to the
modules and their respective channels.
Requirements for Cables and Connection Lines
Observe the following points when installing cables and
connection lines:
Observe the permissible core cross-section of the conductor.
If you use stranded conductors, crimp wire end ferrules on the
conductor ends.
Use only one conductor per terminal.
When installing the conductors the insulation must reach up to
the terminal.
Observe the tightening torque of the terminal screws.
Requirements for Usage as Associated Apparatus
If circuits with type of protection Ex i are operated with non-
intrinsically safe circuits, they must no longer be used as
circuits with type of protection Ex i.
Intrinsically safe circuits of associated apparatus can be led
into hazardous areas. Observe the compliance of the
separation distances to all non-intrinsically safe circuits
according to IEC/EN 60079-14.
Observe the compliance of the separation distances between
two adjacent intrinsically safe circuits according to
IEC/EN 60079-14.
The intrinsically safe circuits are provided by the connected
11/2015

modules.
Observe the maximum values of the device, when connecting
265151

the device to intrinsically safe apparatus.


Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
9
System Description Termination Board Solutions for Emerson DeltaV

Product Specifications System Components


Isolated Barriers
Function
HiD isolated barriers are mounted on HiD Termination Boards.
Termination Boards

Isolated barriers are used to protect intrinsically safe circuits in


explosive areas. In addition to the required current and voltage The Termination Board can be coded together with the
limitation, the isolated barriers have a galvanic isolation isolated barriers. This prevents the isolated barriers being
between the field circuit and the controller. mixed up on the Termination Board. The safety-relevant data
for the connected field devices is backed up.
The H-System isolated barriers are mounted on Termination
Boards. Pre-wiring is possible on Termination Boards. To HiD Device Housing
close the signal circuit, the isolated barriers are simply plugged
in. The isolated barriers can be replaced during live operation
when the wiring is connected.
PWR

STATUS

FAULT

CH 2 CH 1

HiD
Description

2872
2 ch
Solenoid
System

Driver

Figure 2 HiD device housing (18 mm)

Used for high channel density


• Compact 18 mm housing
• Highest channel density on the market
• Only 4.5 mm per channel (for 4-channel devices)
• For mounting on HiD Termination Boards

Figure 1 H-System Termination Board with isolated barriers for


Emerson DeltaV

Universal and control system-specific Termination Boards are


available in the H-System. Termination Boards can be
adapted to specific input/output requirements. These
requirements can be implemented via
• Various connecting plugs to the controller
• Various terminals to the field device
• A large selection of isolated barriers
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


10 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description
Termination Boards Connection Options
Termination Boards form the wiring level for field and control A variety of Termination Boards is available with different
signals. The isolated barriers are mounted on Termination methods of connecting to the field and control side. Please
Boards. The isolated barriers are connected with the field and

Termination Boards
refer to the documentation for the respective device for the
control side via the Termination Boards. Once the isolated specific connection layout.
barrier is mounted, the signal circuit between the field and
control side is closed. Connecting the Field Side
The field devices can be connected to the Termination Board
1 2 3 via screw terminals:

4 CN4 CN3
mA CN2
4 3

6 5 4
X20
CN3 CN2 CN1

9 8 7

3 2 1
3 2
2
1
1 S1

Description
Figure 4 Screw terminals, three-row

System
Connecting the Power Supply and Fault Indication
Output
Figure 3 Connection example Termination Board with 4 slots Isolated Barriers
1 Field side connection The isolated barriers are supplied via the Termination Board.
2 Connection power supply and fault indication output The isolated barriers are therefore attached to the Termination
3 Control side connection Board.
Use Termination Boards
• For HiD isolated barriers The Termination Boards are supplied with power via screw
• With 4 or 8 slots terminals in accordance with their design.
• For back-up fused power supply The supply voltage range depends on
• For fault monitoring and diagnostics • The values used for the isolated barriers
• The voltage drop of the decoupling diodes on the
Termination Board

1+ 2- 3+ 4- 5 6
Power Fault
Supply

1+ 2- 3+ 4-
Power
Supply

+2- +1-
Fault Power
Supply

Figure 5 Possible connections of power supply and fault indication


output via screw terminals
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
11
System Description Termination Board Solutions for Emerson DeltaV

Connecting the Control Side Color Coding of the Isolated Barriers


The Termination Board on the control side can be connected The color coding of the devices has the following meaning:
via IDC connectors:
Termination Boards

4
3 PWR PWR PWR PWR PWR

FAULT STATUS FAULT STATUS STATUS FAULT

2 CH 1 CH 1
FAULT
CH 1

CH 2 CH 2 CH 2 CH 1 FAULT

1 CH 3 CH 3 CH 2

CH 4 CH 4

HiD HiD HiD HiD HiD


2824 2844 2872 2038 2024
4 ch 4 ch 2 ch 2 ch 4 ch
Switch Switch Solenoid Current Transmitter
Amplifier Amplifier Driver Driver Power
Supply/
Current

Figure 6 Connection via IDC connector, 16-pin


Driver

ADJUST

CH 1

CH 2

CH 3

CH 4

4
Description

3
System

2
1
1 2 3 4 5

Figure 9 Color identification of devices

Digital Input
Figure 7 Connection via IDC connector, 20-pin
• Orange identifier (1) for switch amplifiers with a relay
output
4 • Blue identifier (2) for switch amplifiers with a transistor
3 output
2 Digital Output
1 • Purple identifier (3) for solenoid drivers
Analog Output
• Green identifier (4) for current drivers
Analog Input/Analog Output
Figure 8 Connection via IDC connector, 24-pin
• Magenta identifier (5) for transmitter power supplies,
measuring transmitters, and repeaters
Note!
For more information see the corresponding data
sheets.

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


12 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description
Status Indicators with LEDs
LEDs are often used on isolators to indicate different statuses (e. g. for power supply, device failure, status messages, binary
switching states). Standard LED colors are assigned to the status display according to NAMUR NE44.

Termination Boards
LED Display function Display Meaning
Green LED Power supply On Power supply OK
Off Power failure or insufficient power supply – device faulty
Red LED Device fault, device failure On Internal fault signal, failure signal – fault/failure display of causes detected
inside the device, device needs replacing
Line fault Flashing External fault signal, failure signal – fault/failure display of causes detected
outside the device, inspection and elimination of fault required
No fault Off No malfunction, device is operating properly
Yellow LED Switching states of binary inputs On Possible causes of the output:
and outputs • The relay is energized.
• The NO contact (also a change-over contact) is actively closed.
• The open collector is switched through.

Description
• The switching voltage generated inside the device is applied.

System
Possible causes of the input:
• An external contact is closed.
• A NAMUR sensor is undamped (OK range according to closed-circuit
current principle).
• A switching signal is actively applied.
Off Possible causes of the output:
• The relay is de-energized.
• The NO contact (also a change-over contact) is actively opened.
• The open collector is not switched through.
• The switching voltage generated inside the device is not applied.
Possible causes of the input:
• An external contact is opened.
• A NAMUR sensor is damped (fault range according to closed-circuit
current principle).
• A switching signal is not applied.

Table 1 Meaning of status indicators

1 2 3

OUT CHK PWR

Figure 10 Example status indicators

1 Yellow LED "OUT"


Switching state of the output
2 Red LED "CHK"
Lead breakage and short circuit status indicator
3 Green LED "PWR"
Power supply status indicator
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
13
System Description Termination Board Solutions for Emerson DeltaV

Status Indicators of Termination Boards Installation


LEDs are often used on Termination Boards to indicate
different statuses (e. g. for power supply, device failure, status DIN Mounting Rail
Termination Boards

messages, binary switching states). Standard LED colors are The devices are mounted on a 35 mm DIN mounting rail
assigned to the status display according to NAMUR NE44. according to EN 60715.
LED Display Display Meaning
function
Green Power supply On Power supply OK
LED Off No power
"PWR"
Red LED Device fault, On Internal fault signal,
"FAULT" device failure failure signal –
fault/failure display of
causes detected inside
the device
Off No fault
Power supply Flashing Insufficient power
Description

failure 1 supply or power supply Figure 13 Example: DIN mounting rail UPR-MR (35 mm x 15 mm)
System

failure
Table 2 Meaning of status indicators
Mounting
1 only for Termination Board with 8 slots Warning!
Risk of short circuit
Injuries and damage to the device are possible when
1 working with live parts.
• Before working on the device, always disconnect
2
the supply voltage.
• Connect the device to the supply voltage only after
completion of the work.
Figure 11 Example status indicators

1 Green LED "PWR" Status indicator power supply


2 Red LED "FAULT" Device fault, device failure, power supply
failure

Label Carriers
The isolated barriers are fitted with a label carrier ex works for
individual identification.

11/2015

Figure 12 Label carrier on the front


265151

1 Label carrier on HiD devices for 35 mm x 10.5 mm labels


Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


14 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description
Vertical and Horizontal Mounting
Mounting the Termination Boards
Both mounting options are possible. Unrestricted operation is
The Termination Boards are mounted on the 35 mm possible across the entire temperature range of the system in
DIN mounting rail. The DIN mounting rail runs centrally below each mounting direction.

Termination Boards
the Termination Board.
1. Clip the Termination Board (2) onto the DIN mounting
rail (1).
2. Tighten the mounting screws (3).
The Termination Board (2) is now properly mounted
and secured.

Vertical mounting Horizontal mounting

Description
Figure 16

System
1 Mounting the Isolated Barriers on the Termination
Board
Figure 14 Termination Board mounting 1. Push the Quick Lok bar (1) into the upper position.
1 DIN mounting rail 2. Center the pins (2) above the contact elements of the
2 Termination Board Termination Board. Note the connection direction of the
device.
3. Center the locking pins (3) above the locking elements of
1 2 3
the Termination Board.
4. Carefully push the device into the contacts and locking
elements.
5. Push the red Quick Lok bar (1) down on either side of the
device.
The device is now mounted.

1
Figure 15 Termination Board fixing

1 DIN mounting rail


2 Termination Board
3 Fastening screw
3

Figure 17 Mounting of an H-System isolated barrier

1 Quick Lok Bar


2 Coding pins
3 Adjustment pins
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
15
System Description Termination Board Solutions for Emerson DeltaV

Connection Operation
Note! Fault Monitoring
Observe the tightening torque of the terminal screws.
Termination Boards

Numerous faults can occur between measurement of the


The tightening torque is 0.5 Nm to 0.6 Nm.
process variable and evaluation in the control system. This can
lead to undesirable process statuses under certain
Connecting the Field Side
circumstances. These process statuses may result in plant
Connect the field devices to the Termination Board via the downtime or quality problems or even present a hazard to
screw terminals. persons and the environment. Depending on the device
version, the isolators enable monitoring of the following faults:
Connecting the Power Supply and Fault Indication
Output • Line faults
Here, the connection cables between the isolator and field
Connect the power supply and fault indication output via the device are monitored for lead breakages or short circuits. If
screw terminals. a fault is detected, it is output at the fault message output
Connecting the Control Side or collective fault message. The relevant switching outputs
are then switched to a de-energized state. The red fault
Connect the Termination Board on the control side via the indication LEDs signal the fault.
Description

IDC connectors.
System

• Device faults
Note! The isolators are designed so that internal faults are
detected and reported. In the case of a power failure, the
For more information see the corresponding data
outputs are switched to a de-energized state.
sheets.
Fault Output
Device Parameterization
Several H-System isolators monitor the field leads for lead
The devices are parameterized using DIP switches. breakage and short circuits. This means that faults are
immediately identified in the system, and that lead faults are
Configuration of the isolated barriers not interpreted as a signal. Depending on the parameterization
of the devices, these lead faults are output on the control-side
Parameterize the DIP switches on the device side as follows:
outputs.
1. Remove the isolated barriers from the Termination Board
by pulling the red Quick Lok Bar up on either side of the Fault Signal Output
device. If the device has a fault indication output (FAULT), lead and
2. Parameterize the DIP switches as described in the device faults are output. The fault indication output is active in
"Configuration" section of the data sheet. normal status and is deactivated in fault status (closed-circuit
3. Mount the device as described in the section on mounting. principle). In the case of fault indication output, it is not
possible to reverse the direction of operation.
Note!
Information about line fault detection of the interface modules
For more information see the corresponding data is available for the system as volt-free contact.
sheets.

SL2 SL1
1b 8a
5a 7a
5b
1a, 1b 24 V DC
2a, 2b
6b FAULT

Figure 18

Line Fault Transparency (LFT)


If the device has a signal output with line fault transparency,
the fault message can be transmitted on the signal lead. This
saves additional wiring and delivers channel-selective fault
messages.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


16 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description
Current and Voltage Standard Signals Technical specifications
The following signals have established themselves as the
standard: Technical Data

Termination Boards
• the 0/4 mA to 20 mA current signal Electrical Data
• the 0/2 V to 10 V voltage signal Power Supply to the Isolated Barriers
The 0/1 V to 5 V voltage signal is also occasionally • HiD devices: 20.4 V DC to 30 V DC
encountered in addition to the 0/2 V to 10 V voltage signal.
The voltage drop on the Termination Board via the decoupling
Analog sensor signals and digital frequency signals are diodes must be considered.
converted into one of the two standard signals for processing
Non-Ex Signals or Signals in the Drive Circuit
in a wide variety of measurement, regulatory and control tasks.
This offers the measurement and control technician an easy- • 0/4 mA to 20 mA signal level according to NE43
to-measure standard signal common to all manufacturers. • Current output HART compatible
Sensor signals are converted into standard signals via signal
• Current input HART compatible
converters.
• Digital output: active or passive electronic output
For more diagnostic options, the NAMUR organization 100 mA/30 V, short-circuit protected
published NAMUR recommendation NE43, dividing the value

Description
range of the signal (e. g. current signal) into several areas. • Logic level 24 V according to IEC 60946

System
Valid, defined measurement value information is transferred • Functional isolation or safe isolation according to
within the range from 3.8 mA to 20.5 mA. Failure information is IEC 61140 and NAMUR NE23
available when the signal current is < 3.6 mA or > 21 mA i. e. Ex Signals or Signals in the Field Circuit
outside of the range for measured value information. The same
• Transmitter power supply up to 17 V DC
applies to the voltage signal.
• Current output HART compatible
• Digital input according to NAMUR EN 60947-5-6
• Digital output for standard Ex-i valves, short circuit-
0% 100 % protected
Characteristic Safety Values

1 2 1
• MTBF: Mean Time Between Failures

Conformity
3.6 3.8 4 20 20.5 21 I [mA] General
Figure 19 Signal ranges according to NAMUR NE43 • Isolated barriers with explosion protection, preferably
(e. g. current signal) Ex ia IIC/Class I, Div. 1, international approvals

1 Failure information
• EMV according to
2 Measuring information – EN 61326-1
– EN 61326-3-2, only for devices with SIL rating, where
the data sheet mentions this standard.
If you operate the device with a DC supply voltage, you
must ensure that the bridging of the 20 ms voltage
interruption is realized by the power supply.
– NAMUR NE21
If you operate the device with a DC supply voltage, you
must ensure that the bridging of the 20 ms voltage
interruption is realized by the power supply.
• LEDs according to NAMUR NE44
• Software according to NAMUR NE53
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
17
System Description Termination Board Solutions for Emerson DeltaV

Digital Inputs and Outputs according to NAMUR Mechanical Data


The standards references for this interface have changed Mounting
many times:
• Termination Boards: Snap-on 35 mm DIN mounting rail
Termination Boards

• German standard (old): DIN 19234: Electrical distance according to EN 60715. Can be mounted horizontally or
sensors – DC interface for distance sensors and switch vertically.
amplifiers; 1990-06
• Isolated barriers: mounting on Termination Board via
• European standard (old): EN 50227: Low voltage switch Quick Lok Bar
gear and control gear – control devices and switching
Housing Material
elements – proximity switches, DC interface for proximity
sensors and switch amplifiers (NAMUR), 1996-10 • Termination Boards: Polycarbonate (PC)
• German version (old): DIN EN 50227: Low voltage switch • Isolated barriers: Polycarbonate (PC)
gear – control devices and switching elements – proximity Dimensions
switches, DC interface for proximity sensors and switch
• Dimension drawings please refer to chapter Dimensions.
amplifiers (NAMUR), 1997
Degree of Protection
• Current designation: EN 60947-5-6: Low voltage switch
gear – control devices and switching elements – proximity • Termination Boards:
Description

switches, DC interface for proximity sensors and switch – without isolated barriers IP00 according to EN 60529
System

amplifiers (NAMUR), 2000 – with isolated barriers plugged IP20 according to


• Current IEC designation: IEC 60947-5-6: Low voltage EN 60529
switch gear and control gear – part 5-6: Control devices • Isolated barriers: IP20 according to EN 60529
and switching elements – DC interface for proximity Connection to Termination Board
sensors and switch amplifiers (NAMUR), 1999
• Field side:
Ambient Conditions – Screw terminals, three-row:
Ambient Temperature 0.2 ... 2.5 mm2 (22 ... 12 AWG)
• -20 °C to 60 °C (-4 °F to 140 °F), exceptions see data • Power supply and fault indication output:
sheets – Screw terminals: max. 1 x 2.5 mm2 (12 AWG)
Storage Temperature – Observe the tightening torque of the terminal screws.
The tightening torque is 0.5 Nm to 0.6 Nm.
• -40 °C to 70 °C (-40 °F to 158 °F), exceptions see data
• Control side:
sheets
– IDC connector, 16-pin
Reference Conditions for Adjustment
– IDC connector, 20-pin
• 20 °C (68 °F) – IDC connector, 24-pin
Relative Humidity Fire Protection Class
• max. 95 % without moisture condensation • Housing: V2 according to UL 94 standard. Unless stated
Vibration Resistance otherwise all details relate to the reference conditions.
• according to EN 60068-2-6, 10 Hz to 150 Hz, 1 g, high Note!
crossover frequency
For more information see the corresponding data
Shock Resistance sheets.
• according to EN 60068-2-27, 15 g, 11 ms, half-sine
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


18 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description
Model Number Description
Model Number Description Isolated Barriers

Termination Boards
Hi 2

Special functions, if available


ES Version with increased safety
HC Versions for long field wiring
R1 Version with DCS specific line fault transparency (LFT)
R2 Version with DCS specific line fault transparency (LFT)
SK Version with current sink output
Signal type
0 Analog devices
2010 to 2020 Converters
2020 to 2030 Transmitter power supplies
2031 to 2040 Current drivers
2060 to 2090 Temperature converter
2091 to 2100 Repeater

Description
8 Digital devices

System
2820 to 2860 Switch amplifiers
2871 to 2890 Solenoid drivers
2891 to 2900 Converters
Housing type
C HiC device, housing width 12.5 mm
D HiD device, housing width 18 mm
System
Hi H-System

Model Number description Termination Boards

HiDTB - DVM - IDC - - -

Number of channels
08 8 channels
16 16 channels
32 32 channels

Signal types
AI Analog In
AO Analog Out
AM Analog Mix
DI Digital In
DO Digital Out
DM Digital Mix
SM Signal Mix
Termination Board fault output
NO No fault output
R1 1 relay output
R2 2 relay outputs

Field side connection


SC Screw terminals
SP Spring terminals

Number of connectors
1 1 connector
2 2 connectors
3 3 connectors
4 4 connectors

Control side connection


IDC IDC connector
11/2015

Product family name


DVM Emerson DeltaV M-Series and S-Series

Number of positions
265151

04 4 module slots
08 8 module slots
System
Edition

HiDTB H-System Termination Board

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
19
System Description Termination Board Solutions for Emerson DeltaV

Pin Assignment and Device Coding


The isolated barriers are coded in accordance with their function.

Warning!
Termination Boards

Possible Device Failure


Changes in the pin configuration may lead to device failure. To polarize the device in accordance with its safety
parameters, the pins are shortened at the factory.
• Do not change the factory setting!

Device Coding of HiD Devices and HiD Termination Boards

No. Termination Board Isolated barrier Type


Top view Bottom view
Safe area Hazardous Hazardous Safe area
area area
A HiD2000
Description

all non-intrinsically safe devices


System

1 2 34 4321

B –
+
1 2 34 4321

C HiD2096
+
1 2 34 4321

D –
+
1 2 34 4321

E HiD2881
+
1 2 34 4321

F HiD2061, HiD2062, HiD2071, HiD2072, HiD2821,


HiD2822, HiD2824, HiD2842, HiD2844
++
1 2 34 4321

G HiD2024, HiD2025, HiD2025SK, HiD2026,


HiD2026SK, HiD2029, HiD2029SK, HiD2030,
HiD2030SK, HiD2031, HiD2032, HiD2033,
+ +
1 2 34 4321
HiD2034, HiD2035, HiD2036, HiD2037, HiD2038,
HiD2038Y, HiD2875, HiD2876, HiD2877, HiD2878
H HiD2871, HiD2872, HiD2873, HiD2874
+ +
1 2 34 4321

I –
++
1 2 34 4321

J HiD2081, HiD2082
+ +
1 2 34 4321

K HiD2025ES
++
1 2 34 4321

L HiD2012
+++
11/2015

1 2 34 4321

M HiD2891
265151

+ ++
1 2 34 4321
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


20 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV System Description
No. Termination Board Isolated barrier Type
Top view Bottom view
Safe area Hazardous Hazardous Safe area
area area

Termination Boards
N –
++ +
1 2 34 4321

O –
+++
1 2 34 4321

P HiD2862
Empty position
++++
1 2 34 4321

Insert polarizing pin Pin to be trimmed


Don't insert polarizing pin Pin untrimmed

Device side view

Description
System
4 3 21

Table 3

Note!
For more information see the corresponding data sheets.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
21
System Description Termination Board Solutions for Emerson DeltaV

Dimensions
Housing Designs for H-System HiD Isolated Barriers
Termination Boards

HiD device housings

18 mm 128 mm (5.04")
(0.71")

106 mm (4.17")
Description
System

Figure 20

Housing Types Termination Boards


HiD Termination Board for 4 Modules
247 mm (9.72")

157 mm (6.18") 82 mm (3.22")


205 mm (8.1")

Figure 21

HiD Termination Board for 8 Modules


253 mm (9.96")

163 mm (6.42") 150 mm (5.9")


200 mm (7.9")

11/2015
265151

Figure 22
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


22 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Notes

Termination Boards
Description
System
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
23
Termination Boards Termination Board Solutions for Emerson DeltaV
DeltaV

Termination Boards
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories

Edition 265151 11/2015

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


24 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Table of Contents

Digital Inputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Digital Outputs

DeltaV
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Analog Inputs and Outputs


Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Digital Inputs
Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Universal
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Digital Outputs
Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Accessories
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
25
Notes Termination Board Solutions for Emerson DeltaV
DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


26 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Selection Tables

HiD Multi-Channel IS Solutions


Digital Inputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page

Channels

Channels

Channels
Modules

DeltaV
Series

Series

Type

Type
Card

M 8-channel DI Series 2 8 HiDTB08-DVM-IDC4-SC-R1-SM32 8 32 52 HiD2824 4 65


(24 V DC, dry contact) simplex HiD2844 66
M 32-channel DI Series 2 32 HiDTB04-DVM-IDC1-SC-R1-DI16 4 16 32 HiD2844 4 66
(24 V DC, dry contact) simplex
M 32-channel DI Series 2 Plus 32 HiDTB04-DVM-IDC1-SC-R2-DI16 4 16 36 HiD2844 4 66
(24 V DC, dry contact) redundant
S 8-channel DI simplex 8 HiDTB08-DVM-IDC4-SC-R1-SM32 8 32 52 HiD2824 4 65

Digital Inputs
(NAMUR) HiD2844 66
S 32-channel DI simplex 32 HiDTB04-DVM-IDC1-SC-R1-DI16 4 16 32 HiD2844 4 66
(24 V DC, dry contact)
S 32-channel DI Plus 32 HiDTB04-DVM-IDC1-SC-R2-DI16 4 16 36 HiD2844 4 66
(24 V DC, dry contact) redundant

Digital Outputs

Digital Outputs
Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels

Channels

Channels
Modules
Series

Type

Type

Type
Card

M 8-channel DO Series 2 8 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67

Analog Ouputs
Analog Inputs/
(24 V DC, high side) simplex HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2872 2 67
M 32-channel DO Series 2 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) simplex
M 32-channel DO Series 2 Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) redundant
S 8-channel DO simplex 8 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2872 2 67
S 32-channel DO simplex 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side)

Universal
S 32-channel DO Plus 32 HiDTB04-DVM-IDC3-SC-R2-DO08 4 8 40 HiD2872 2 67
(24 V DC, high side) redundant
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
27
Selection Tables Termination Board Solutions for Emerson DeltaV

Analog Inputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page

Channels

Channels

Channels
Modules
Series

Type

Type

Type
Card
DeltaV

M 8-channel AI Series 2 8 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68


(4 mA to 20 mA) simplex HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2030SK 2 69
S 8-channel AI simplex 8 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68
(4 mA to 20 mA) HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2030SK 2 69
S 16-channel AI Plus 16 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68
(4 mA to 20 mA) simplex
S 16-channel AI Plus 16 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68
(4 mA to 20 mA) redundant
Digital Inputs

Analog Outputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Page Module Page
Channels

Channels

Channels
Modules
Series

Type

Type

Type
Card
Digital Outputs

M 8-channel AO Series 2 8 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68


(4 mA to 20 mA) simplex HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2038 2 70
S 8-channel AO simplex 8 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68
(4 mA to 20 mA) HiDTB08-DVM-IDC4-SC-R1-SM32 8 16 52 HiD2038 2 70
S 16-channel AO Plus 16 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68
(4 mA to 20 mA) simplex
Analog Ouputs

S 16-channel AO Plus 16 HiDTB04-DVM-IDC4-SC-NO-AM16 4 16 48 HiD2024 4 68


Analog Inputs/

(4 mA to 20 mA) redundant
Universal
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


28 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Selection Tables

HiC Single-Channel IS Solutions


Digital Inputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page

Channels

Channels

Channels

Channels
Modules

DeltaV
Series

Series

Type

Type

Type
Card

M 8-channel DI Series 2 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2831 1 CAB-DVM-**-S37I16-MX- 8 58


(24 V DC, dry simplex 01000
contact)
M 32-channel DI Series 2 32 HiCTB32-SDC-24C-SC-RA 32 32 HiC2821 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, dry simplex HiC2841 01010
contact)
M 32-channel DI Series 2 32 HiCTB32-SDC-24C-SC-RA 32 32 HiC2821 1 CAB-DVM-**-S37I20-DI- 16 58

Digital Inputs
(24 V DC, dry Plus HiC2841 01010
contact) redundant
S 8-channel DI simplex 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2831 1 CAB-DVM-**-S37I16-MX- 8 58
(NAMUR) 01000
S 32-channel DI simplex 32 HiCTB32-SDC-24C-SC-RA 32 32 HiC2821 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, dry HiC2841 01010
contact)
S 32-channel DI Plus 32 HiCTB32-SDC-24C-SC-RA 32 32 HiC2821 1 CAB-DVM-**-S37I20-DX- 16 58

Digital Outputs
(24 V DC, dry redundant HiC2841 01010
contact)

Digital Outputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page

Analog Ouputs
Analog Inputs/
Channels

Channels

Channels

Channels
Modules
Series

Type

Type

Type

Type
Card

M 8-channel DO Series 2 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2873 1 CAB-DVM-**-S37I16-DO- 8 58


(24 V DC, high simplex 01000
side)
M 32-channel DO Series 2 32 HiCTB32-SDC-24A-SC-RA 32 32 HiC2873 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, high simplex 01010
side)

Universal
M 32-channel DO Series 2 32 HiCTB32-SDC-24A-SC-RA 32 32 HiC2873 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, high Plus 01010
side) redundant
S 8-channel DO simplex 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2873 1 CAB-DVM-**-S37I16-DO- 8 58
(24 V DC, high 01000
side)
S 32-channel DO simplex 32 HiCTB32-SDC-24A-SC-RA 32 32 HiC2873 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, high 01010
Accessories

side)
S 32-channel DO Plus 32 HiCTB32-SDC-24A-SC-RA 32 32 HiC2873 1 CAB-DVM-**-S37I20-DX- 16 58
(24 V DC, high redundant 01010
side)
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
29
Selection Tables Termination Board Solutions for Emerson DeltaV

Analog Inputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page

Channels

Channels

Channels

Channels
Modules
Series

Type

Type

Type

Type
Card
DeltaV

M 8-channel AI Series 2 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2025 1 CAB-DVM-**-S37I16-MX- 8 58


(4 mA to 20 mA) simplex 01000
S 8-channel AI simplex 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2025 1 CAB-DVM-**-S37I16-MX- 8 58
(4 mA to 20 mA) 01000
S 16-channel AI Plus 16 HiCTB16-SDC-44C-SC-RA 16 16 HiC2025 1 CAB-DVM-**-S37I24-AX- 8 58
(4 mA to 20 mA) simplex 01000
S 16-channel AI Plus 16 HiCTB16-SDC-44C-SC-RA 16 16 HiC2025 1 CAB-DVM-**-S37I24-AX- 8 58
(4 mA to 20 mA) redundant 01000
Digital Inputs

Analog Outputs

Emerson Pepperl+Fuchs
Emerson DeltaV Termination Board Module Cable Page
Channels

Channels

Channels

Channels
Modules
Series

Type

Type

Type

Type
Card
Digital Outputs

M 8-channel AO Series 2 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2031 1 CAB-DVM-**-S37I16-MX- 8 58


(4 mA to 20 mA) simplex 01000
S 8-channel AO simplex 8 HiCTB08-SDC-44C-SC-RA 8 8 HiC2031 1 CAB-DVM-**-S37I16-MX- 8 58
(4 mA to 20 mA) 01000
S 16-channel AO Plus 16 HiCTB16-SDC-44C-SC-RA 16 16 HiC2031 1 CAB-DVM-**-S37I24-AX- 8 58
(4 mA to 20 mA) simplex 01000
S 16-channel AO Plus 16 HiCTB16-SDC-44C-SC-RA 16 16 HiC2031 1 CAB-DVM-**-S37I24-AX- 8 58
Analog Ouputs
Analog Inputs/

(4 mA to 20 mA) redundant 01000


Universal
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


30 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Notes

DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
31
HiDTB04-DVM-IDC1-SC-R1-DI16 Termination Board
HiDTB04-DVM-IDC1-SC-R1-DI16

Features
• System Board for Emerson DeltaV
• For one 32-channel DI card via 40-pin Mass Termination
Block
• For 4 modules/16 channels
• Recommended module: HiD2844 (DI)
• Volt-free fault indication output
DeltaV

• 24 V DC supply, reverse polaritiy protected, optional


daisychainable
• Hazardous area: screw terminals, blue
• Safe area: IDC connector, 20-pin

Function

The function of the Termination Board as well as the connector


pin assignment exactly fit the requirement of DeltaV Traditional
Digital Inputs

I/O systems.
Information about line fault detection of the interface modules
is available for the system as volt-free contact.
The Termination Boards are supplied with a robust plastic
housing as standard. This design permits the fast and reliable
installation on 35 mm DIN mounting rail acc. to EN 60715 in
the cabinet.
Digital Outputs

Application

For detailed listing of connectable cards see application


section.
Analog Ouputs
Analog Inputs/

Connection
Universal

24 V DC (I),
24 V DC (II),
1.5 kΩ Fault
1+
I 10 kΩ
4-
1.5 kΩ
2+
II 10 kΩ

1.5 kΩ
5- 4 X20
Accessories

CN1
3+
III 10 kΩ
3
6-
1.5 kΩ 2 DeltaV 32DI
7+
IV 10 kΩ 1
11/2015

8-

9
265151
6 5 4
9 8 7

3 2 1

Zone 0, 1, 2
Edition

Div. 1, 2

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


32 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC1-SC-R1-DI16

Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple  10 %
Fusing 3.15 A with back-up fuse
Power dissipation  500 mW , without modules
Reverse polarity protection yes

DeltaV
Electrical specifications
volt-free fault indication output max. 30 V AC/30 V DC, 1 A
Indicators/settings
Display elements LED PWR (power supply), one green LED
LED FAULT (fault indication), one red LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Conformity

Digital Inputs
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
safe area connection (control side): IDC plug, 20-pin

Digital Outputs
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X
Group, category, type of protection see certificate

Analog Ouputs
Analog Inputs/
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate

Application Universal

DeltaV M-series 32-channel DI Series 2 simplex card (24 V DC, dry contact):
• Termination Board 1: channel 1 ... 16
• Termination Board 2: channel 17 ... 32
DeltaV S-series 32-channel DI simplex card (24 V DC, dry contact):
Accessories

• Termination Board 1: channel 1 ... 16


• Termination Board 2: channel 17 ... 32
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
33
HiDTB04-DVM-IDC1-SC-R1-DI16 Termination Board

Application

Typical loop

Field side Termination Board Control side

FAULT 24 V DC
+ -
DeltaV

5 6 1 3 2 4 X20

FAULT
&

+
24 V DC
-

1.5 kΩ Module 1
1+
HiD2844
1 10 kΩ SL2
1
5a 7a RTN
4- 4
1.5 kΩ 5b 8a
2+ 2
Digital Inputs

1a 9a RTN 20-pin flat


2 10 kΩ 5
1b
CN1
10a ribbon cable
5- 3 SL1
3a 10b RTN 1 1 1 CH1+/CH17+
1.5 kΩ 6
3+ 3b 9b 2 2 2 CH2+/CH18+
7
3 10 kΩ 7a 7b RTN 3 3 3 CH3+/CH19+
8
6- 7b 8b 4 4 4 CH4+/CH20+
9
1.5 kΩ 1a, 1b 24 V DC
7+
2a, 2b
4 10 kΩ 6b
FAULT
8- DeltaV
Screen 9
Mass
Termination
Block
32DI
Digital Outputs

1.5 kΩ Module 4
1+
HiD2844
13 10 kΩ 1
SL2
4- 5a 7a RTN
1.5 kΩ 4
5b 8a 13 13 13 CH13+/CH29+
2+ 2
1a 9a RTN 14 14 14 CH14+/CH30+
14 10 kΩ 5
1b 10a 15 15 15 CH15+/CH31+
5- 3 SL1
1.5 kΩ 3a 10b RTN 16 16 16 CH16+/CH32+
3+ 6
3b 9b 17,19 17,19 17,19 n.c.
7
15 10 kΩ 7a 7b RTN RTN 18,20 18,20 18,20 Return
8
6- 7b 8b
1.5 kΩ 9
7+ 1a, 1b 24 V DC
16 10 kΩ 2a, 2b
FAULT
8- 6b
Analog Ouputs
Analog Inputs/

Screen 9

Module switch settings


Type DIP switch Position
HiD2844 (DI) S1 ON
• open (energized)/ S2 ON
close (de-energized) S3 ON
• Line fault detection enable
Universal

S4 ON
S5 ON
S6 ON
S7 ON
S8 ON

The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


34 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC1-SC-R1-DI16

DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
35
HiDTB04-DVM-IDC1-SC-R2-DI16 Termination Board
HiDTB04-DVM-IDC1-SC-R2-DI16

Features
• System Board for Emerson DeltaV
• For one 32-channel DI card via 40-pin Mass Termination
Block
• For 4 modules/16 channels
• Recommended module: HiD2844 (DI)
• Volt-free fault indication output
DeltaV

• 24 V DC supply, reverse polaritiy protected, optional


daisychainable
• Hazardous area: screw terminals, blue
• Safe area: IDC connector, 20-pin

Function

The function of the Termination Board as well as the connector


pin assignment exactly fit the requirement of DeltaV Traditional
Digital Inputs

I/O systems.
Information about line fault detection of the interface modules
is available for the system as volt-free contact.
The Termination Boards are supplied with a robust plastic
housing as standard. This design permits the fast and reliable
installation on 35 mm DIN mounting rail acc. to EN 60715 in
the cabinet.
Digital Outputs

Application

For detailed listing of connectable cards see application


section.
Analog Ouputs
Analog Inputs/

Connection
Universal

24 V DC (I),
24 V DC (II),
1.5 kΩ Fault
1+
I 10 kΩ
4-
1.5 kΩ
2+
II 10 kΩ

1.5 kΩ
5- 4 X20
Accessories

CN1
3+ K1
III 10 kΩ
3
6-
1.5 kΩ 2 DeltaV 32DI
7+ K2
IV 10 kΩ 1 S1
11/2015

8-

9
265151
6 5 4
9 8 7

3 2 1

Zone 0, 1, 2
Edition

Div. 1, 2

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


36 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC1-SC-R2-DI16

Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple  10 %
Fusing 3.15 A with back-up fuse
Power dissipation  500 mW , without modules
Reverse polarity protection yes

DeltaV
Electrical specifications
volt-free fault indication output max. 30 V AC/30 V DC, 1 A
DeltaV specific output: max. 24 V DC, 25 mA
Indicators/settings
Display elements LED PWR (power supply), one green LED
LED FAULT (fault indication), one red LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013

Digital Inputs
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue

Digital Outputs
safe area connection (control side): IDC plug, 20-pin
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X

Analog Ouputs
Analog Inputs/
Group, category, type of protection see certificate
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate

Universal
Application

DeltaV M-series 32-channel DI Series 2 Plus redundant card (24 V DC, dry contact):
• Termination Board 1: channel 1 ... 16
• Termination Board 2: channel 17 ... 32
DeltaV S-series 32-channel DI Plus redundant card (24 V DC, dry contact):
Accessories

• Termination Board 1: channel 1 ... 16


• Termination Board 2: channel 17 ... 32
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
37
HiDTB04-DVM-IDC1-SC-R2-DI16 Termination Board

Application

Typical loop

Field side Termination Board Control side

FAULT 24 V DC
+ -
DeltaV

5 6 1 3 2 4 X20
K1, K2
FAULT
& K1

+
24 V DC
-
1.5 kΩ Module 1
1+
HiD2844
1 10 kΩ 1
SL2
4- 5a 7a
4
1.5 kΩ 5b 8a RTN 20-pin flat
2+ 2 CN1
Digital Inputs

1a 9a ribbon cable
2 10 kΩ 5
1b 10a RTN 1 1 1 CH1-/CH17-
5- 3 SL1
3a 10b 2 2 2 CH2-/CH18-
1.5 kΩ 6
3+ 3b 9b RTN 3 3 3 CH3-/CH19-
7
3 10 kΩ 7a 7b 4 4 4 CH4-/CH20-
8
6- 7b 8b RTN
1.5 kΩ 9
7+ 1a, 1b 24 V DC
2a, 2b
4 10 kΩ FAULT DeltaV
6b
8- Mass
Screen 9 Termination
Block
32DI
Digital Outputs

1.5 kΩ Module 4
1+
HiD2844
13 10 kΩ 1
SL2
4- 5a 7a 13 13 13 CH13-/CH29-
1.5 kΩ 4
5b 8a RTN 14 14 14 CH14-/CH30-
2+ 2
1a 9a 15 15 15 CH15-/CH31-
14 10 kΩ 5
1b 10a RTN 16 16 16 CH16-/CH32-
5- 3 SL1
1.5 kΩ 3a 10b RTN 18,20 18,20 18,20 Return
3+ 6
3b 9b RTN 17 17 17 FAULT
7 S1.1 K2
15 10 kΩ 7a 7b 19 19 19 FAULT
8
6- 7b 8b RTN
1.5 kΩ 9
7+ 1a, 1b 24 V DC
16 10 kΩ 2a, 2b
FAULT
8- 6b
Analog Ouputs
Analog Inputs/

Screen 9

Module switch settings Card software settings


Type DIP switch Position Type Parameter Setting
HiD2844 (DI) S1 ON • DeltaV M-series 32-channel T1_FAULT_DETECT True
• open (energized)/ S2 ON DI Series 2 Plus card
close (de-energized) • DeltaV S-series 32-channel
S3 ON
• Line fault detection enable DI Plus card
Universal

S4 ON
S5 ON • DeltaV M-series 32-channel T2_FAULT_DETECT True
S6 ON DI Series 2 Plus card
• DeltaV S-series 32-channel
S7 ON
DI Plus card
S8 ON

Termination Board switch settings

DIP switch Position Description


Accessories

S1.1 ON Fault monitoring at CN1 inactive


OFF Fault monitoring at CN1 active
S1.2 n.a.
11/2015

The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


38 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC1-SC-R2-DI16

DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
39
HiDTB04-DVM-IDC3-SC-R2-DO08 Termination Board
HiDTB04-DVM-IDC3-SC-R2-DO08

Features
• System Board for Emerson DeltaV
• For one 8-channel DO card via 16-pin Mass Termination
Block
• For one 32-channel DO card via 40-pin Mass
Termination Block
• For 4 modules/8 channels
DeltaV

• Recommended module: HiD2872 (DO)


• Volt-free fault indication output
• 24 V DC supply, reverse polaritiy protected, optional
daisychainable
• Hazardous area: screw terminals, blue
• Safe area: IDC connector, 16 pin and 20-pin

Function
Digital Inputs

The function of the Termination Board as well as the connector


pin assignment exactly fit the requirement of DeltaV Traditional
I/O systems.
Information about line fault detection of the interface modules
is available for the system as volt-free contact.
The Termination Boards are supplied with a robust plastic
housing as standard. This design permits the fast and reliable
Digital Outputs

installation on 35 mm DIN mounting rail acc. to EN 60715 in


the cabinet.

Application

For detailed listing of connectable cards see application


section.
Analog Ouputs
Analog Inputs/

Connection
Universal

24 V DC (I),
24 V DC (II),
Fault
7+

1+

4-

4 X20
Accessories

CN3 CN2 CN1


6+ 3
DeltaV 8DO
2+ 2
DeltaV 32DO
5- 1 S1
11/2015

9
265151
6 5 4
9 8 7

3 2 1

Zone 0, 1, 2
Edition

Div. 1, 2

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


40 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC3-SC-R2-DO08

Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple  10 %
Fusing 3.15 A with back-up fuse
Power dissipation  500 mW , without modules
Reverse polarity protection yes

DeltaV
Electrical specifications
volt-free fault indication output max. 30 V AC/30 V DC, 1 A
DeltaV specific output: max. 24 V DC, 25 mA
Indicators/settings
Display elements LED PWR (power supply), one green LED
LED FAULT (fault indication), one red LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013

Digital Inputs
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue

Digital Outputs
safe area connection (control side): IDC plug, 16-pin and 20-pin
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X

Analog Ouputs
Analog Inputs/
Group, category, type of protection see certificate
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate

Universal
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
41
HiDTB04-DVM-IDC3-SC-R2-DO08 Termination Board

Application

DeltaV M-series 8-channel DO Series 2 simplex card (24 V DC, high-side):


• Termination Board 1: channel 1 ... 8
DeltaV M-series 32-channel DO Series 2 simplex card (24 V DC, high-side) and
DeltaV M-series 32-channel DO Series 2 Plus redundant card (24 V DC, high-side):
DeltaV

• Termination Boards 1 and 2: channel 1 ... 16


• Termination Boards 3 and 4: channel 17 ... 32
DeltaV S-series 8-channel DO simplex card (24 V DC, high-side):
• Termination Board 1: channel 1 ... 8
DeltaV S-series 32-channel DO simplex card (24 V DC, high-side) and
DeltaV S-series 32-channel DO Plus redundant card (24 V DC, high-side):
• Termination Boards 1 and 2: channel 1 ... 16
• Termination Boards 3 and 4: channel 17 ... 32
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


42 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC3-SC-R2-DO08

Application

Typical loop for connection of 8-channel DO cards

Field side Termination Board Control side

FAULT 24 V DC
+ -

DeltaV
5 6 1 3 2 4 X20

FAULT
&

+
24 V DC
-

Module 1
7+
HiD2872

1+ SL2 16-pin flat


1 7 CN1
7a SL1 ribbon cable
1

Digital Inputs
4- 5a 7a RTN RTN 1 1 1 CH1-
4
5b 8a 2 2 2 CH1+
9a RTN RTN 3 3 3 CH2-
6
3b 10a 4 4 4 CH2+
6+ 2
1a
5
1b
2 2+ 9
1a, 1b 24 V DC
2a, 2b
5-
6b
FAULT DeltaV
Mass
Screen 9 Termination
Block
8DO

Digital Outputs
Module 4
7+
HiD2872

1+ SL2
7 7
7a SL1
1
4- 5a 7a RTN RTN 13 13 13 CH7-
4
5b 8a 14 14 14 CH7+
9a RTN RTN 15 15 15 CH8-
6
3b 10a 16 16 16 CH8+
6+ 2
1a
5
1b
8 2+ 9
1a, 1b 24 V DC
2a, 2b
5- FAULT
6b

Analog Ouputs
Analog Inputs/
Screen 9

Module switch settings Card software settings


Type DIP switch Position Type Parameter Setting
HiD2872 (DO) S1 ON • DeltaV M-series 8-channel LINEFAULT_DETECT False
• Bus powered S2 OFF DO Series 2 card
• Control input: logic signal • DeltaV S-series 8-channel
S3 ON
• Line fault detection enable DO card

Universal
S4 OFF
S5 ON
S6 OFF
S7 ON
S8 ON

Termination Board switch settings

DIP switch Description


Accessories

S1.1 n.a.
n.a.
S1.2 n.a.
n.a.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
43
HiDTB04-DVM-IDC3-SC-R2-DO08 Termination Board

Typical loop for connection of 32-channel DO cards

Field side Termination Board Control side

FAULT 24 V DC
+ -
5 6 1 3 2 4 X20
K1, K2
FAULT
& K1
DeltaV

+
24 V DC
-

Module 1
7+
HiD2872

1 1+ SL2 DeltaV Mass


7
7a SL1 20-pin flat Termination Block
1 CN3
4- 5a 7a RTN ribbon cable 32DO
4
5b 8a 1 1 1 CH1+/CH17+
9a RTN 2 2 2 CH2+/CH18+
6
3b 10a
6+ 2
1a
5 7 7 7 CH7+/CH23+
1b
Digital Inputs

2 2+ 9 8 8 8 CH8+/CH24+
1a, 1b 24 V DC
2a, 2b CH9 9 9 9 CH9+/CH25+
5- FAULT CH10 10 10 10 CH10+/CH26+
6b
Screen 9
CH15 15 15 15 CH15+/CH31+
CH16 16 16 16 CH16+/CH32+
17 17 17 FAULT
Module 4 19 19 19 FAULT
7+
HiD2872 RTN 18,20 18,20 18,20 Return
1+ SL2
7 7
7a SL1
1
5a
K2 S1.1 CN2
4- 7a RTN
4
Digital Outputs

5b 8a CH9 1 1
9a RTN CH10 2 2
6
3b 10a
6+ 2
1a to
5 CH15 7 7
1b Termination Board 2
8 2+ 9 CH16 8 8 via 20-pin flat
1a, 1b 24 V DC
17 17 ribbon cable
2a, 2b
5- FAULT S1.2
6b 19 19
Screen 9 n.c. 9-16 9-16
RTN 18,20 18,20
Analog Ouputs
Analog Inputs/

Module switch settings Card software settings


Type DIP switch Position Type Parameter Setting
HiD2872 (DO) S1 ON • DeltaV M-series 32-channel n.a. n.a.
• Bus powered S2 OFF DO Series 2 card
• Control input: logic signal • DeltaV S-series 32-channel
S3 ON
• Line fault detection enable DO card
S4 OFF
S5 ON
S6 OFF
Universal

S7 ON
S8 ON

Termination Board switch settings

DIP switch Description


S1.1 n.a.
n.a.
S1.2 n.a.
Accessories

n.a.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


44 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC3-SC-R2-DO08
Typical loop for connection of 32-channel DO Plus cards

Field side Termination Board Control side

FAULT 24 V DC
+ -
5 6 1 3 2 4 X20
K1, K2
FAULT
& K1

DeltaV
+
24 V DC
-

Module 1
7+
HiD2872

1 1+ SL2 DeltaV Mass


7
7a SL1 20-pin flat Termination Block
1 CN3
4- 5a 7a RTN ribbon cable 32DO
4
5b 8a 1 1 1 CH1+/CH17+
9a RTN 2 2 2 CH2+/CH18+
6
3b 10a
6+ 2
1a
5 7 7 7 CH7+/CH23+
1b

Digital Inputs
2 2+ 9 8 8 8 CH8+/CH24+
1a, 1b 24 V DC
2a, 2b CH9 9 9 9 CH9+/CH25+
5- FAULT CH10 10 10 10 CH10+/CH26+
6b
Screen 9
CH15 15 15 15 CH15+/CH31+
CH16 16 16 16 CH16+/CH32+
17 17 17 FAULT
Module 4 19 19 19 FAULT
7+
HiD2872 RTN 18,20 18,20 18,20 Return
1+ SL2
7 7
7a SL1
1
5a
K2 S1.1 CN2
4- 7a RTN
4

Digital Outputs
5b 8a CH9 1 1
9a RTN CH10 2 2
6
3b 10a
6+ 2
1a to
5 CH15 7 7
1b Termination Board 2
8 2+ 9 CH16 8 8 via 20-pin flat
1a, 1b 24 V DC
17 17 ribbon cable
2a, 2b
5- FAULT S1.2
6b 19 19
Screen 9 n.c. 9-16 9-16
RTN 18,20 18,20

Analog Ouputs
Analog Inputs/
Module switch settings Card software settings
Type DIP switch Position Type Parameter Setting
HiD2872 (DO) S1 ON • DeltaV M-series 32-channel T1_FAULT_DETECT True
• Bus powered S2 OFF DO Series 2 Plus card
• Control input: logic signal • DeltaV S-series 32-channel
S3 ON
• Line fault detection enable DO Plus card
S4 OFF
S5 ON • DeltaV M-series 32-channel T2_FAULT_DETECT True
S6 OFF DO Series 2 Plus card
• DeltaV S-series 32-channel
S7 ON

Universal
DO Plus card
S8 ON

Termination Board switch settings

DIP switch Position Description


S1.1 ON Fault monitoring at CN3 inactive
OFF Fault monitoring at CN3 active
S1.2 ON Termination active
OFF Termination inactive
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
45
HiDTB04-DVM-IDC3-SC-R2-DO08 Termination Board

Schematic diagram
• Connection between Termination Board 2 and Termination Board 1 (channel 1 ... 16)
• Connection between Termination Board 4 and Termination Board 3 (channel 17 ... 32)

DeltaV 32DO

20-pin flat
ribbon cable
DeltaV

S1 S1
CN1 CN1
CN2 CN2
CN3 CN3

20-pin flat
ribbon cable
4
3
2
1

4
3
2
1
Digital Inputs
Digital Outputs

Termination Board 1/3 Termination Board 2/4

Settings for use with 32-channel DO cards


Switch settings Termination Board 1/3 Switch settings Termination Board 2/4
DIP switch Position DIP switch Position
S1.1 n.a. S1.1 n.a.
Analog Ouputs
Analog Inputs/

S1.2 n.a. S1.2 n.a.

Settings for use with 32-channel DO Plus cards


Switch settings Termination Board 1/3 Switch settings Termination Board 2/4
DIP switch Position DIP switch Position
S1.1 ON or OFF S1.1 ON or OFF
S1.2 OFF S1.2 ON
Universal

The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


46 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC3-SC-R2-DO08

DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
47
HiDTB04-DVM-IDC4-SC-NO-AM16 Termination Board
HiDTB04-DVM-IDC4-SC-NO-AM16

Features
• System Board for Emerson DeltaV
• For two 8-channel AI/AO cards via 16-pin Mass
Termination Block
• For one 16-channel AI/AO card via 48-pin Mass
Termination Block
• For 4 modules/16 channels
DeltaV

• Recommended module: HiD2024 (AI/AO)


• Line fault transparency (LFT)
• HART compatible
• 24 V DC supply, reverse polaritiy protected, optional
daisychainable
• Hazardous area: screw terminals, blue
• Safe area: IDC connector, 16 pin and 24-pin
Digital Inputs

Function

The function of the Termination Board as well as the connector


pin assignment exactly fit the requirement of DeltaV Traditional
I/O systems.
The Termination Boards are supplied with a robust plastic
housing as standard. This design permits the fast and reliable
installation on 35 mm DIN mounting rail acc. to EN 60715 in
the cabinet.
Digital Outputs

Application

For detailed listing of connectable cards see application


section.
Analog Ouputs
Analog Inputs/

Connection
Universal

24 V DC (I),
1+ 24 V DC (II)
HART
HART

P
I I 4-

2+
HART
HART

P
II I 5- X20
4 CN4 CN3 DeltaV 8AI, 8AO
Accessories

CN2 CN1
3+
HART
HART

P 3
III I DeltaV 8AI, 8AO
6-
2
7+ DeltaV 16AI, 16AO
HART
HART

P 1
IV I
11/2015

8-
DeltaV 16AI, 16AO
9
265151
6 5 4
9 8 7

3 2 1

Zone 0, 1, 2
Edition

Div. 1, 2

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


48 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC4-SC-NO-AM16

Technical data
Supply
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple  10 %
Fusing 3.15 A with back-up fuse
Power dissipation  500 mW , without modules
Reverse polarity protection yes

DeltaV
Indicators/settings
Display elements LED PWR (power supply), one green LED
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions

Digital Inputs
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
safe area connection (control side): IDC plug, 16-pin and 24-pin
Core cross-section 0.2 ... 2.5 mm2 (22 ... 12 AWG)
Material housing: polycarbonate
Mass approx. 350 g

Digital Outputs
Dimensions 82 x 205 x 157 mm (3.23 x 8.1 x 6.2 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate SIRA 13 ATEX 2388X
Group, category, type of protection see certificate
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation

Analog Ouputs
Analog Inputs/
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx approval IECEx CSA 13.0040X
Approved for see certificate

Universal
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
49
HiDTB04-DVM-IDC4-SC-NO-AM16 Termination Board

Application

DeltaV M-series 8-channel AI Series 2 simplex card (4 mA to 20 mA):


• HiD2024 configured to AI operation
• Card 1 and CN1: channel 1 ... 8
• Card 2 and CN2: channel 9 ... 16
DeltaV

DeltaV M-series 8-channel AO Series 2 simplex card (4 mA to 20 mA):


• HiD2024 configured to AO operation
• Card 1 and CN1: channel 1 ... 8
• Card 2 and CN2: channel 9 ... 16
DeltaV S-series 8-channel AI simplex card (4 mA to 20 mA):
• HiD2024 configured to AI operation
• Card 1 and CN1: channel 1 ... 8
• Card 2 and CN2: channel 9 ... 16
DeltaV S-series 8-channel AO simplex card (4 mA to 20 mA):
Digital Inputs

• HiD2024 configured to AO operation


• Card 1 and CN1: channel 1 ... 8
• Card 2 and CN2: channel 9 ... 16
DeltaV S-series 16-channel AI Plus simplex or redundant card (4mA to 20 mA):
• HiD2024 configured to AI operation
• Card 1 and CN3: channel 1 ... 8
• Card 1 and CN4: channel 9 ... 16
Digital Outputs

DeltaV S-series 16-channel AO Plus simplex or redundant card (4mA to 20 mA):


• HiD2024 configured to AO operation
• Card 1 and CN3: channel 1 ... 8
• Card 1 and CN4: channel 9 ... 16
Analog Ouputs
Analog Inputs/
Universal
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


50 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB04-DVM-IDC4-SC-NO-AM16

Application

Typical loop

Field side Termination Board Control side

24 V DC

DeltaV
+ -
1 3 2 4 X20

+
24 V DC 24-pin flat
- CN3
ribbon cable DeltaV
1 1 1 CH1-
Mass
2 2 2 CH1+
Termination
3 3 3 CH2-
Block
4 4 4 CH2+
16AI
5 5 5 CH3-
16AO
6 6 6 CH3+

Digital Inputs
7 7 7 CH4-
8 8 8 CH4+

15 15 15 CH8-
16 16 16 CH8+
n.c. 17-24 17-24 17-24 n.c.
1+
HART
HART

P Module 1
1 I 16-pin flat
4- HiD2024 CN1
1
SL2 ribbon cable DeltaV
5a 7a 1 1 1 CH1-
2+ 4
5b
Mass
HART
HART

P 8a 2 2 2 CH1+
2 2 Termination
I 1a 9a 3 3 3 CH2-
5- 5 Block

Digital Outputs
1b 10a 4 4 4 CH2+
3
3a SL1 8AI
10b 5 5 5 CH3-
3+ 6 8AO
HART
HART

P 3b 9b 6 6 6 CH3+
3 I 7
7a
6- 7b 7 7 7 CH4-
8
7b 8b 8 8 8 CH4+
9
7+
HART
HART

P 1a, 1b 24 V DC
4 I 2a, 2b 15 15 15 CH8-
8-
16 16 16 CH8+

Screen 9 CN2 16-pin flat


ribbon cable DeltaV
1 1 1 CH1-
Mass
Module 4 2 2 2 CH1+
Termination
HiD2024 Block

Analog Ouputs
SL2

Analog Inputs/
1+ 1
HART
HART

P 5a 7a 9 9 9 CH5- 8AI
13 I 4
4- 5b 8a 10 10 10 CH5+ 8AO
2
1a 9a 11 11 11 CH6-
5
1b 10a 12 12 12 CH6+
2+
HART
HART

P 3
3a SL1
10b 13 13 13
14 I CH7-
5- 6
3b 9b 14 14 14 CH7+
7
7a 7b 15 15 15 CH8-
8
3+ 7b 8b 16 16 16 CH8+
HART
HART

P 9
15 I 6- 1a, 1b 24 V DC
2a, 2b
7+ CN4 24-pin flat
HART
HART

P ribbon cable
16 I DeltaV
8- 1 1 1 CH9-
Mass
2 2 2 CH9+
Termination
Screen 9

Universal
Block
9 9 9 CH13- 16AI
10 10 10 CH13+ 16AO
11 11 11 CH14-
12 12 12 CH14+
13 13 13 CH15-
14 14 14 CH15+
15 15 15 CH16-
16 16 16 CH16+
n.c. 17-24 17-24 17-24 n.c.
Accessories

Module switch settings


Type DIP switch Position Type DIP switch Position
HiD2024 (AI) S1 OFF HiD2024 (AO) S1 ON
Analog input with S2 OFF Analog output S2 OFF
11/2015

sink output 4 mA ... 20 mA


S3 ON S3 ON
S4 OFF S4 OFF
265151

The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
51
HiDTB08-DVM-IDC4-SC-R1-SM32 Termination Board
HiDTB08-DVM-IDC4-SC-R1-SM32

Features
• System Board for Emerson DeltaV
• For two 8-channel AI/AO/DO cards via 16-pin Mass
Termination Block
• For four 8-channel DI cards via 16-pin Mass
Termination Block
• For 8 modules/16 or 32 channels
DeltaV

• Recommended modules: HiD2030SK (AI), HiD2038


(AO), HiD2824 (DI), HiD2844 (DI), HiD2872 (DO)
• Volt-free fault indication output
• 24 V DC supply
• Hazardous area: screw terminals, blue
• Safe area: IDC connector, 16-pin

Function
Digital Inputs

The function of the Termination Board as well as the connector


pin assignment exactly fit the requirement of DeltaV Traditional
I/O systems.
Information about missing supply voltage of the interface
modules is available for the system as potential-free contact.
Wiring errors from field will be reported via the same relay
contact if the interface module supports this function.
Digital Outputs

The Termination Boards are supplied with a robust glass fiber


reinforced plastic housing as standard. This design permits the
fast and reliable installation on 35 mm DIN mounting rail
acc. to EN 60715 in the cabinet.

Application

For detailed listing of connectable cards see application


section.
Analog Ouputs
Analog Inputs/

Connection
Universal

6 5 4

24 V DC (I),
9 8 7

3 2 1

M8

24 V DC (II),
Fault
1.5 kΩ
1, 2, 3, 7
10 kΩ 8 X20
4, 5, 6, 8
7
1, 2 6 DeltaV
HART
Accessories

+ 4, 5
5 AO, AI, DO
mA 7, 6
-
4 CN4 CN2
1, 2
HART

P -
I 3
4, 5
DeltaV
11/2015

+ 2
7, 6 DI
1 CN3 CN1
250499
6 5 4
9 8 7

3 2 1

M1

Zone 0, 1, 2
Edition

Div. 1, 2

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


52 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB08-DVM-IDC4-SC-R1-SM32

Technical data
Supply
Connection X20: terminals 3, 5 (+); 4, 6 (-)
Rated voltage Un 24 V DC , in consideration of rated voltage of used isolated barriers
Voltage drop 0.9 V , voltage drop across the series diode on the Termination Board must be considered
Ripple  10 %
Fusing 2 A , in each case for 8 modules
Power dissipation  500 mW , without modules

DeltaV
Reverse polarity protection yes
Redundancy
Supply Redundancy available. The supply for the modules is decoupled, monitored and fused.
Error message output
Connection X20: terminals 1, 2
Output type volt-free contact
Contact loading 30 V AC/40 V DC, 2 A
Indicators/settings
Display elements LEDs PWR ON (Termination Board power supply)

Digital Inputs
- LED power supply I, green LED
- LED power supply II, green LED
LED FAULT (fault indication), red LED
- LED lits: module failure
- LED flashes: power supply failure
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2013
Conformity

Digital Outputs
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection hazardous area connection (field side): screw terminals, blue
safe area connection (control side): IDC plug, 16-pin

Analog Ouputs
Analog Inputs/
power supply connection: pluggable screw terminals, black
Core cross-section 0.25 ... 1.5 mm2 (24 ... 12 AWG)
Material housing: polycarbonate, 10 % glass fiber reinforced
Mass approx. 600 g
Dimensions 150 x 200 x 163 mm (5.9 x 7.9 x 6.42 in) , height including module assembly
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-
areas
EC-Type Examination Certificate CESI 11 ATEX 062
Group, category, type of protection E II (1)G [Ex ia Ga] IIC, E II (1)D [Ex ia Da] IIIC, E I (M1) [Ex ia Ma] I

Universal
Safe area
Maximum safe voltage 250 V (Attention! Um is no rated voltage.)
Electrical isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000
CSA approval
Control drawing see control drawing of correspoding modules
IECEx approval IECEx CES 11.0022
Accessories

Approved for [Ex ia Ga] IIC


[Ex ia Da] IIIC
[Ex ia Ma] I
Accessories
11/2015

Designation optional accessories: Label Carrier HiALC-Hi*TB-SET-1**


250499
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
53
HiDTB08-DVM-IDC4-SC-R1-SM32 Termination Board

Application

DeltaV M-series 8-channel AI Series 2 simplex card (4 mA to 20 mA) and


DeltaV S-series 8-channel AI simplex card (4 mA to 20 mA):
• HiD2030SK
• Card 1 and CN1: channel 1 ... 8
• Card 2 and CN2: channel 9 ... 16
DeltaV

DeltaV M-series 8-channel AO Series 2 simplex card (4 mA to 20 mA) and


DeltaV S-series 8-channel AO simplex card (4 mA to 20 mA):
• HiD2038
• Card 1 and CN1: channel 1 ... 8
• Card 2 and CN2: channel 9 ... 16
DeltaV M-series 8-channel DO Series 2 simplex card (24 V DC, high-side) and
DeltaV S-series 8-channel DO simplex card (24 V DC, high-side):
• HiD2872
Digital Inputs

• Card 1 and CN1: channel 1 ... 8


• Card 2 and CN2: channel 9 ... 16
DeltaV M-series 8-channel DI Series 2 simplex card (24 V DC, dry contact) and
DeltaV S-series 8-channel DI simplex card (24 V DC, dry contact):
• HiD2824, HiD2844
• Card 1 and CN1: channel 1 ... 8, field side: M1 ... M4 terminals 1, 2, 4, 5
• Card 2 and CN2: channel 9 ... 16, field side: M5 ... M8 terminals 1, 2, 4, 5
• Card 3 and CN3: channel 17 ... 24, field side: M1 ... M4 terminals 3, 6, 7, 8
Digital Outputs

• Card 4 and CN4: channel 25 ... 32, field side: M5 ... M8 terminals 3, 6, 7, 8
Analog Ouputs
Analog Inputs/
Universal
Accessories

11/2015
250499
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


54 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB08-DVM-IDC4-SC-R1-SM32

Application

Typical loop for analog inputs, analog outputs and digital outputs

Field side Termination Board Control side

Fault 24 VDC
+ -

DeltaV
1 2 3 5 4 6 X20

Fault
& F2 F1
1
HART

+ 4

mA 7
- +
1 24 V DC
1 -
HART

P -
I
4 Module 1
+ M1 HiD2030SK
7 HiD2038 16-pin flat
SL2
1 HiD2872 SL1 CN1 ribbon cable
5a
4 DeltaV

Digital Inputs
5b 7a 1 1 1 CH1-
2 Mass
HART

7
7a 8a 2 2 2 CH1+
+ 5 2
Termination
1a 9a 3 3 3 CH2- Block
mA 6 5
- 1b 10a 4 4 4 CH2+ 8AI
2 6 8AO
3b
2
HART

P 1a, 1b 24 V DC
- 8DO
I 2a, 2b
5 Fault 15 15 15 CH8-
6b
+ 16 16 16 CH8+
6

16-pin flat
1 CN2 ribbon cable
HART

+ DeltaV
4 Module 8 1 1 1 CH1-
Mass

Digital Outputs
mA 7 M8 HiD2030SK 2 2 2 CH1+ Termination
- SL2 HiD2038
15 1 HiD2872 Block
5a SL1
1
HART

P - 4
8AI
I 5b 7a 13 13 13 CH7- 8AO
4 7
+ 7a 8a 14 14 14 CH7+ 8DO
7 2
1a 9a 15 15 15 CH8-
5
1b 10a 16 16 16 CH8+
6
3b
2 1a, 1b 24 V DC
HART

+ 2a, 2b
5 Fault
6b
mA 6
-
16
2
HART

Analog Ouputs
Analog Inputs/
P -
I
5
+
6

Module switch settings Card software settings


Type DIP switch Position Type Parameter Setting
HiD2872 (DO) S1 ON • DeltaV M-series 8-channel LINEFAULT_DETECT False
S2 OFF DO Series 2 card
• Bus powered • DeltaV S-series 8-channel
S3 ON
• Control input: logic signal DO card
• Line fault detection enable S4 OFF

Universal
S5 ON
S6 OFF
S7 ON
S8 ON
HiD2030SK (AI) No user configuration available.
HiD2038 (AO) No user configuration available.
Accessories
11/2015
250499
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
55
HiDTB08-DVM-IDC4-SC-R1-SM32 Termination Board

Typical loop for digital inputs

Field side Termination Board Control side

Fault 24 V DC
+ -
1 2 3 5 4 6 X20

Fault
& F2 F1 16-pin flat
CN1 ribbon cable
DeltaV

DeltaV
1 1 1 CH1-
+ Mass
1.5 kΩ 2 2 2 CH1+
1 24 V DC Termination
- 3 3 3 CH2-
1 10 kΩ Block
4 4 4 CH2+
4 Module 1 8DI
1.5 kΩ M1 HiD2824
2 SL2
1 15 15 15 CH8-
5a 7a
2 10 kΩ 4 16 16 16 CH8+
5b 8a
5 2
1a 9a
1.5 kΩ 5 CN3
3 1b 10a
3 SL1 DeltaV
3 10 kΩ 3a 10b 1 1 1 CH1-
6 Mass
6 3b 9b 2 2 2 CH1+
1.5 kΩ
7
7a
Termination
7b 3 3 3 CH2-
7 8
7b
Block
8b 4 4 4 CH2+
8DI
Digital Inputs

4 10 kΩ
8 1a, 1b 24 V DC
2a, 2b
Fault 15 15 15 CH8-
6b
16 16 16 CH8+

CN2
1.5 kΩ
1 DeltaV
1 1 1 CH1-
29 10 kΩ Mass
Module 8 2 2 2 CH1+
4 Termination
M8
1.5 kΩ SL2 HiD2824 Block
2 1
5a 7a 13 13 13 CH7- 8DI
30 10 kΩ 4
5b 8a 14 14 14 CH7+
5 2
1a 9a 15 15 15 CH8-
1.5 kΩ 5
Digital Outputs

1b 10a 16 16 16 CH8+
3 3 SL1
3a 10b
31 10 kΩ 6
3b 9b CN4
6 7
7a 7b DeltaV
1.5 kΩ 8 1 1 1 CH1-
7 7b 8b Mass
2 2 2 CH1+
32 10 kΩ 1a, 1b
Termination
24 V DC
8 2a, 2b Block
Fault 13 13 13 CH7- 8DI
6b
14 14 14 CH7+
15 15 15 CH8-
16 16 16 CH8+
Analog Ouputs
Analog Inputs/

Module switch settings Card software settings


Type DIP switch Position Type Parameter Setting
HiD2824 (DI), HiD2844 (DI) S1 ON • DeltaV M-series 8-channel LINEFAULT_DETECT False
S2 ON DI Series 2 card
• open – energized/close – de- • DeltaV S-series 8-channel DI
S3 ON
energized card
• Line fault detection enable S4 ON
S5 ON
S6 ON
S7 ON
Universal

S8 ON

The pin-out configuration has to be observed. For information see corresponding pin-out table on
www.pepperl-fuchs.com.
Accessories

11/2015
250499
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


56 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board HiDTB08-DVM-IDC4-SC-R1-SM32

DeltaV
Digital Inputs
Digital Outputs
Analog Ouputs
Analog Inputs/
Universal
Accessories
11/2015
250499
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
57
CAB-DVM-**-S37I**-**-***** H-System Custom Cable
CAB-DVM-**-S37I**-**-****

Features Technical data


• Emerson specific cable for Electrical specifications
DeltaV M- and S-series to Rated voltage Un 500 V
Pepperl+Fuchs H-System Standard conformity
Termination Boards Flammability IEC 60332-1-2 , flame-resistant
Ambient conditions
• Connects IDC plug on Emerson
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) , fixed
baseplates to a 37-pin-SuB-D
Mechanical specifications
DeltaV

connector on H-System
Connection Sub-D plug , 37 pins/37 pins
Termination Boards IDC plug, 16-pin, 20-pin and 24-pin
• Preconfigured lengths Material
Connector Zinc die cast, nickel plated
Sheathing PVC
Core insolation PVC
Cable LiYCY
Diameter 18 cores: 7.3 mm (0.29 in)
Bending radius min. 6 x external diameter, fixed cable
Digital Inputs

Cores 18 x 0.14 mm2


Conductor construction stranded wire , fine-strand
Shield Tinned copper braiding
Digital Outputs
Analog Ouputs
Analog Inputs/

Assembly
Universal

IDC ...
(siehe
Accessories

Tabelle)
11/2015
250499
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


58 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
H-System Custom Cable CAB-DVM-**-S37I**-**-*****

Application

Module switch settings Card software settings

Type DIP switch Position Type Parameter Setting


HiC2025 (AI) S1 OFF – – –
Current sink 4 mA ... 20 mA S2 ON

DeltaV
S3 OFF
S4 OFF

HiC2031 (AO) S1 ON – – –
Open loop voltage of the control S2 ON
system < 23 V
S3 OFF
S4 OFF

HiC2821/HiC2841 (DI) S1 I • DeltaV M-series 32-channel DI T1_FAULT_DETECT False

Digital Inputs
• Open – energized S2 I Series 2 Plus card T2_FAULT_DETECT False
• Line fault detection enable • DeltaV S-series 32-channel DI
S3 – Plus card
S4 –

HiC2831 (DI) S1 II • DeltaV M-series 8-channel LINEFAULT_DETECT True


• Mode of operation: normal S2 I DI Series 2 card
• Input line fault detection: on • DeltaV S-series 8-channel
S3 – DI card

Digital Outputs
S4 –

HiC2873 (DO) S1 ON • DeltaV M-series 8-channel LINEFAULT_DETECT False


• Bus powered S2 OFF DO Series 2 card
• Control input: logic signal • DeltaV S-series 8-channel DO
• Line fault detection enable S3 ON card
• Filter disable S4 OFF
S5 ON • DeltaV M-series 32-channel T1_FAULT_DETECT False
S6 OFF DO Series 2 Plus card T2_FAULT_DETECT False
• DeltaV S-series 32-channel DO

Analog Ouputs
Analog Inputs/
S7 ON Plus card
S8 ON

Universal
Accessories
11/2015
250499
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
59
H-System Isolated Barriers
H-System

H-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Accessories

Edition 265151 11/2015

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


60 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Isolated Barriers Table of Contents

Digital Inputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

H-System
Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Digital Outputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Digital Inputs
Analog Inputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Digital Outputs
Analog Outputs
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Analog Inputs
Accessories
Selection Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Product Data Sheets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Analog Outputs
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
61
Notes Isolated Barriers
H-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


62 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Isolated Barriers Selection Tables

Digital Inputs

Model Number Housing Input (Field) Output Supply Page


(Control System)

20 V DC ... 31 V DC

Zone 2/Division 2
(Active/Passive)
NAMUR Sensor/

(Bus Powered)

H-System
Dry Contact

Transistor
Line Fault
Detection
Channels

Mounting
24 V DC
Relay
HiD

SIL
HiD2824  4   4   2 65

HiD2844  4   4 4   2 66

Digital Outputs

Digital Inputs
Model Number Housing Input Output (Field) Specials Supply Page
(Control System)

Max. Current (mA)

(Loop Powered)
(Bus Powered)
Loop powered

Contact Input

Voltage (V)
Channels

Digital Outputs
24 V DC

24 V DC
LED
HiD

SIL
HiD2872  2   12 40    3 67

Analog Inputs

Housing Input (Field) Output Specials Supply Page

Analog Inputs
Model Number
(Control System)
(1 Input – 2 Outputs)
2-wire Transmitter

Zone 2/Division 2
0/4 mA ... 20 mA

0/4 mA ... 20 mA
Current Source

Signal Splitting

(Bus Powered)
Channels

Mounting
(Source)

24 V DC
SMART
(Sink)

Analog Outputs
HiD

SIL

HiD2024  4        68

HiD2030SK  2        2 69

Analog Outputs

Model Number Housing Input Output Specials Supply Page


Accessories

(Control System) (Field)


Line Fault Detection

Zone 2/Division 2
0/4 mA ... 20 mA

0/4 mA ... 20 mA

(Bus Powered)
11/2015

Channels

Mounting
24 V DC
SMART
265151

HiD

HiD2038  2      2 70
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
63
Selection Tables Isolated Barriers

Accessories

Model Number Description Page

HiD2000 Blank Place Holder Barrier 71


H-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


64 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Switch Amplifier HiD2824
HiD2824

Technical data Features


Supply • 4-channel isolated barrier
Rated voltage Un 20.4 ... 30 V DC via Termination Board
• 24 V DC supply (bus powered)
Power dissipation 0.35 W at 24 V (per channel)
Input • Dry contact or NAMUR inputs
Rated values acc. to EN 60947-5-6 (NAMUR) • 4 relay contact outputs
Connectable sensor types potential free contact or proximity sensor • Line fault detection (LFD)

H-System
Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA • Up to SIL2 acc. to IEC 61508
Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum
value Function
Output
Output signal: relay SPST per channel, phase selectable This isolated barrier is used for intrinsic
Error message output safety applications. It transfers digital
Output type open collector transistor (internal fault bus) signals (NAMUR sensors/mechanical
Transfer characteristics contacts) from a hazardous area to a safe
Switching frequency < 10 Hz area.
Ambient conditions
The proximity sensor or switch controls

Digital Inputs
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
two form A normally open relay outputs for
Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
the safe area load. The module output
Mechanical specifications
changes state when the input signal
Degree of protection IP20
changes state. The normal output state
Mass approx. 140 g
can be reversed with the selector switches
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
on the side of the unit.
Mounting on Termination Board
Coding pin 1 and 2 trimmed Line fault detection (LFD) can be selected
Data for application in connection see page 72 for entity parameters or disabled via a selector switch.

Digital Outputs
with Ex-areas During an error condition, the relay reverts
EC-Type Examination Certificate CESI 02 ATEX 086 to its de-energized state and the LEDs
Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC indicate the fault. A separate fault output
Statement of conformity PF 11 CERT 2109 X bus is available. The fault conditions can
Group, category, type of protection, E II 3G Ex nA nC IIC T4 Gc be monitored via a Fault Indication Board.
temperature class
CSA approval
This module mounts on a HiD Termination
Control drawing 366-005CS-12B (cCSAus)
Board.

Analog Inputs
Analog Outputs
Diagrams

Front view

LED green:
Power supply
HiD2824
PWR
1.5 kΩ SL2 SL1 LEDs yellow:
+ 1 5a 8a 11 LEDs red:
FAULT STATUS
Status output
I 10 kΩ I CH 1

Fault channel 1 ... 4 channel 1 ... 4


1.5 kΩ - 4 5b 7a 14 CH 2
Accessories

+ 2 1a 10a 12 CH 3
II 10 kΩ II
CH 4

- 5 1b 9a 15 Switch 1 ... 8
1.5 kΩ HiD
+ 3 3a 9b 13 2824
III 10 kΩ III
4 ch
Switch

1.5 kΩ
- 6 3b 10b 16 Amplifier

+ 7 7a 8b 17
IV 10 kΩ IV
11/2015

- 8 7b 7b 18 Place for
1a, 1b - 24 V DC labeling
2a, 2b +
FAULT
265151

6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
65
HiD2844 Switch Amplifier
HiD2844

Features Technical data


• 4-channel isolated barrier Supply
Rated voltage Un 20.4 ... 30 V DC via Termination Board
• 24 V DC supply (bus powered)
Power dissipation 0.35 W at 24 V (per channel)
• Dry contact or NAMUR inputs Input
• 4 passive transistor outputs Rated values acc. to EN 60947-5-6 (NAMUR)
• Line fault detection (LFD) Connectable sensor types potential free contact or proximity sensor
H-System

• Up to SIL2 acc. to IEC 61508 Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum
Function value
Output
This isolated barrier is used for intrinsic Rated voltage Un 30 V
safety applications. It transfers digital Rated current In 50 mA
signals (NAMUR sensors/mechanical Output one optocoupled transistor per channel
contacts) from a hazardous area to a safe Signal level 1-signal: (external voltage) -1 V
0-signal: blocked output (off-state current max. 50 A,
area.
typical 5 A)
The proximity sensor or switch controls a Error message output
Digital Inputs

passive transistor for the safe area load. Output type open collector transistor (internal fault bus)
The module output changes state when Transfer characteristics
the input signal changes state. The normal Switching frequency < 2 kHz
output state can be reversed with the Ambient conditions
selector switches on the side of the unit. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Line fault detection (LFD) can be selected Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
or disabled via a selector switch. Mechanical specifications
Degree of protection IP20
During an error condition, the transistor
Digital Outputs

reverts to its de-energized state and the Mass approx. 140 g


LEDs indicate the fault. A separate fault Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
Mounting on Termination Board
output bus is available. The fault
conditions can be monitored via a Fault Coding pin 1 and 2 trimmed
Indication Board. Data for application in connection see page 72 for entity parameters
with Ex-areas
This module mounts on a HiD Termination EC-Type Examination Certificate CESI 02 ATEX 086
Board. Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC
Statement of conformity PF 11 CERT 2109 X
Analog Inputs

Group, category, type of protection, E II 3G Ex nA IIC T4 Gc [device in zone 2]


temperature class
CSA approval
Control drawing 366-005CS-12B (cCSAus)
Analog Outputs

Diagrams

Front view

LED green:
Power supply
HiD2844
PWR

LEDs red: LEDs yellow: 1.5 kΩ SL2 SL1


Line fault
FAULT STATUS
Status output + 1 5a 8a 11 +
CH 1
I 10 kΩ I
channel 1 ... 4 channel 1 ... 4
CH 2 1.5 kΩ - 4 5b 7a 14 -
+ 2 1a 10a 12 +
Accessories

CH 3
II 10 kΩ II
CH 4

1.5 kΩ - 5 1b 9a 15 -
Switch 1 ... 8 HiD
2844 + 3 3a 9b 13 +
III 10 kΩ III
4 ch
Switch
Amplifier 1.5 kΩ - 6 3b 10b 16 -
+ 7 7a 8b 17 +
IV 10 kΩ IV
11/2015

- 8 7b 7b 18 -
Place for
labeling 1a, 1b - 24 V DC
2a, 2b +
FAULT
265151

6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


66 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Solenoid Driver HiD2872
HiD2872

Technical data Features


Supply • 2-channel isolated barrier
Rated voltage 20.4 ... 30 V via Termination Board or
20.4 ... 30 V via loop powered input , reverse polarity
• 24 V DC supply (bus or loop
protected powered)
Power loss 1 W at 24 V, 300  load (per channel) • Output 40 mA at 12 V DC, 55 mA
Input current limit

H-System
Control input external switch (dry contact or open collector) non • Contact or logic control input
isolated or logic signal input fully floating
• Entity parameter Io/Isc = 110 mA
Signal level 1-signal: 15...30 V DC (current limited at 3 mA) or
contact close (internal 10 k pull-up) • Line fault detection (LFD)
0-signal: 0...5 V DC or contact open • Up to SIL2 acc. to IEC 61508
Power loss 1 W at 24 V, 300  load (per channel) for loop powered (bus powered)
Inrush current 0.2 A , 15 ms loop powered • Up to SIL3 acc. to IEC 61508
Output (loop powered)
Internal resistor Ri approx. 240 
Current Ie  40 mA Function
Voltage Ue  12 V

Digital Inputs
Current limit Imax 55 mA This isolated barrier is used for intrinsic
Open loop voltage Us approx. 22.5 V safety applications.
Load nominal 0.1 ... 5 k
It supplies power to solenoids, LEDs, and
Error message output
audible alarms, located in a hazardous
Output type open collector transistor (internal fault bus)
area.
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) It is controlled with a loop-powered control
Mechanical specifications signal, switch contact, transistor, or logic
signal.

Digital Outputs
Degree of protection IP20
Mass approx. 140 g At full load, 12 V at 40 mA (with 55 mA
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in) current limit) is available for the hazardous
Mounting on Termination Board area application.
Coding pin 1 and 4 trimmed An alternative low current output is
Data for application in connection see page 72 for entity parameters available for driving a single LED without
with Ex-areas
installing an external current limiting
EC-Type Examination Certificate CESI 10 ATEX 036
resistor.
Group, category, type of protection E II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in
Line fault detection of the field circuit is

Analog Inputs
zone 0/1/2/20/21/22]
Statement of conformity PF 10 CERT 1729 X indicated by a red LED and an output on
Group, category, type of protection, E II 3G Ex nA II T4 the fault bus.
temperature class This device mounts on a HiD Termination
CSA approval Board.
Control drawing 366-005CS-12B (cCSAus)
IECEx approval IECEx CES 10.0013

Analog Outputs
Diagrams
Front view

LED green: LED green:


Power supply channel 2 Power supply channel 1
HiD2872
LED yellow: LED yellow:
SL2 SL1 Status output channel 2 PWR
Status output channel 1
(11) 8a + V STATUS
+ + 7a (7) LED red: FAULT LED red:
I (14) 7a - I Fault channel 2 Fault channel 1
CH 2 CH 1
+ 5a (1)
(17) 8b +
Accessories

V
- - 5b (4)
(18) 7b - Switch 1 ... 8 HiD
(12) 10a + channel 2 2872
+ V
+ 3b (6) 2 ch
Solenoid
II (15) 9a - II Driver
+ 1a (2)
(13) 9b + V
11/2015

- - 1b (5)
(16) 10b - Place for
1a, 1b - 24 V DC labeling
2a, 2b +
ERR
265151

6b Switch 1 ... 8
Zone 0, 1, 2 channel 1
Div. 1, 2 Termination Board
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
67
HiD2024 SMART Transmitter Power Supply/Current Driver
HiD2024

Features Technical data


• 4-channel isolated barrier Supply
Rated voltage 20.4 ... 30 V DC via Termination Board
• 24 V DC supply (bus powered)
Power dissipation  1.8 W at 20 mA
• Analog in or analog out signals Power consumption  3.3 W at 20 mA
• Sink and source mode outputs Hazardous area connection
• SMART pass-through Input signal 4 ... 20 mA , limited to approx. 30 mA
H-System

Available voltage  15 V at 20 mA
Function Output signal 4 ... 20 mA
Output load 0 ... 650 
This isolated barrier is used for intrinsic Safe area connection
safety applications. It operates as a Input signal 4 ... 20 mA
SMART transmitter power supply or as a Input resistance > 100 k at max. 23 V, with field wiring open
repeater. Voltage drop approx. 6 V or internal resistance 300  at 20 mA
Bi-directional communication is supported Output signal 4 ... 20 mA or 1 ... 5 V (on 250 , 0.1 % internal shunt)
for SMART transmitters that use current 4 ... 20 mA (sink mode), operating voltage 15 ... 26 V
Output load 0 ... 300  (source mode)
modulation to transmit data and voltage
Digital Inputs

modulation to receive data. Ripple 20 mV rms


Transfer characteristics
The outputs are fully isolated from the Frequency range field side into the control side: bandwidth with
inputs, the power supply, and each other. 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
An open field circuit presents a high control side into the field side: bandwidth with
impedance to the control side to allow 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
alarm conditions to be monitored by Rise time 10 to 90 %  20 ms
control systems. Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
This module mounts on a HiD Termination
Digital Outputs

Mechanical specifications
Board.
Degree of protection IP20
Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
Mounting on Termination Board
Coding pin 1 and 3 trimmed
Data for application in connection see page 72 for entity parameters
with Ex-areas
EC-Type Examination Certificate CESI 02 ATEX 086
Analog Inputs

Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC
Statement of conformity PF 11 CERT 2109 X
Group, category, type of protection, E II 3G Ex nA IIC T4 Gc
temperature class
Analog Outputs

Diagrams

Front view

LED green:
Power supply
HiD2024
PWR
SL2 SL1
HART
HART

HART

P + 5a (1) (11) 8a +
I I V mA I
- 5b (4) (14) 7a -
Switch 1 ... 4
HART
HART

HART

P
Accessories

II + 1a (2) (12) 10a + V mA II


I
- 1b (5) (15) 9a -
HiD
2024
HART
HART

HART

P + 3a (3) (13) 9b +
4 ch
III I V mA III
Transmitter
Power - 3b (6) (16) 10b -
Supply/
Current
HART
HART

HART

Driver
P + 7a (7) (17) 8b +
IV mA IV
11/2015

ADJUST
I V
CH 1
Potentiometer for calibration: Place for - 7b (8) (18) 7b -
CH 2
channel 1 ... 4 labeling
CH 3 1a, 1b - 24 V DC
2a, 2b +
265151

CH 4

Zone 0, 1, 2 Zone 2
Div. 1, 2 Termination Board Div. 2
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


68 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
SMART Transmitter Power Supply HiD2030SK
HiD2030SK

Technical data Features


Supply • 2-channel isolated barrier
Rated voltage Un 20.4 ... 30 V via Termination Board
• 24 V DC supply (bus powered)
Power dissipation 1.05 W at 20 mA and 24 V external from PCS or PLC
(per channel) • 2-wire SMART transmitters or
Input current sources
Input current 4 ... 20 mA , current limit 26 mA • Usable as signal splitter (1 input and

H-System
Input resistance 40  , for current source 2 outputs)
Ripple 10 mV eff • Dual output 4 mA ... 20 mA, current
Voltage min. 15.5 V at 20 mA sink
Output
• Line fault detection (LFD)
Output sink mode from external supply
• Up to SIL2 acc. to IEC 61508
Output signal 4 ... 20 mA , current limit 24 mA
Voltage working voltage 7 ... 30 V
Function
Response time 70 ms , 10 ... 90 % step change
Signal level no fault: 1 mA ... 23.5 mA input current
This isolated barrier is used for intrinsic
fault detection: < 0.2 mA or > 24 mA input current
safety applications. It provides a fully

Digital Inputs
Error message output
floating supply to power 2-wire SMART
Output type open collector transistor (common to both channels)
fault bus signal, collective error message transmitters in the hazardous area, and
Ambient conditions repeats the current to drive a safe area
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) load. It is also used with 2-wire current
Mechanical specifications sources. It is designed to provide a sink
Degree of protection IP20 mode output on the safe area terminals
Mass approx. 140 g Digital signals may be superimposed on
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in) the analog values in the hazardous or safe

Digital Outputs
Mounting on Termination Board area, which are transferred bi-
Coding pin 1 and 3 trimmed directionally.
Data for application in connection see page 72 for entity parameters A separate fault output on the bus is
with Ex-areas
signaled if the input signal is outside the
EC-Type Examination Certificate CESI 02 ATEX 086
range 0.2 mA ... 24 mA. The fault
Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC
conditions can be monitored via a Fault
Statement of conformity PF 11 CERT 2109 X
Indication Board.
Group, category, type of protection, E II 3G Ex nA IIC T4 Gc [device in zone 2]
temperature class This module mounts on a HiD Termination
Board.

Analog Inputs
CSA approval
Control drawing 366-005CS-12B (cCSAus)

Analog Outputs
Diagrams

Front view

LED green:
Power supply
HiD2030SK
PWR
SL2
SL1
HART

FAULT

+ 1 5a V LED red: LED red:


HART

+ 8a 11 + CH 2 CH 1
I I Fault channel 2 Fault channel 1
4 5b
mA 7a 14 -
Accessories

- - 7 7a
HART

+ 2 1a V HiD
HART

+ 10a 12 + 2030
II II
5 1b SK
mA 9a 15 - 2 ch
Transmitter
- - 6 3b Power
Supply
11/2015

Place for
1a, 1b - 24 V DC labeling
2a, 2b +
FAULT
265151

6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
69
HiD2038 SMART Current Driver
HiD2038

Features Technical data


• 2-channel isolated barrier General specifications
Signal type Analog output
• 24 V DC supply (bus powered)
Supply
• Current output up to 750  load Rated voltage Un 20.4 ... 30 V via Termination Board
• SMART I/P and valve positioners
• Line fault detection (LFD) Power dissipation 0.85 W at 24 V (per channel)
H-System

Input
• Up to SIL2 acc. to IEC 61508
Input current 4 ... 20 mA , reverse polarity protected
Function Signal level input voltage drop < 4 V with field wiring intact
input current < 1.2 mA with field wiring open
Output
This isolated barrier is used for intrinsic
Load 0 ... 750 
safety applications. It repeats a
Output signal 4 ... 20 mA
4 mA ... 20 mA input signal from a control
Ripple 15 mV eff
system to drive SMART I/P converters,
Response time 50 ms , 10 ... 90 % step change
valve actuators, and displays located in a
Line fault detection breakage, load > 100 k, short-circuit, load < 70 
hazardous area.
Digital Inputs

Error message output


Digital signals may be superimposed on Output type open collector transistor (internal fault bus)
the analog values in the hazardous or safe Transfer characteristics
area, which are transferred bi- Calibrated accuracy < ± 0.1 % of full-scale value
directionally. Influence of temperature < ± 0.01 %/K
An open field circuit presents a high Influence of load < ± 0.1 % of full-scale value from 0 ... 750 
impedance to the control side to allow Linearity < ± 0.1 % of full-scale value
alarm conditions to be monitored by Ambient conditions
control systems. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Digital Outputs

Line fault detection of the field circuit is Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
indicated by a red LED and an output on Mechanical specifications
the fault bus. The fault conditions can be Degree of protection IP20
monitored via a Fault Indication Board. Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
This module mounts on a HiD Termination
Mounting on Termination Board
Board.
Coding pin 1 and 3 trimmed
Data for application in connection see page 72 for entity parameters
with Ex-areas
Analog Inputs

EC-Type Examination Certificate CESI 02 ATEX 086


Group, category, type of protection E II (1)G [Ex ia Ga] IIC , E II (1)D [Ex ia Da] IIIC
Statement of conformity PF 11 CERT 2109 X
Group, category, type of protection, E II 3G Ex nA IIC T4 Gc [device in zone 2]
temperature class
CSA approval
Control drawing 366-005CS-12B (cCSAus)
Analog Outputs

Diagrams

Front view

LED green:
Power supply
HiD2038
PWR

FAULT

CH 1
LED red: SL2 SL1
HART

HART

Fault channel 1 P
FAULT I + 1 5a 8a 11 + mA I
LED red: I
Accessories

CH 2 - 4 5b 7a 14 -
Fault channel 2
HiD
2038
HART

HART

2 ch II P + 2 1a 10a 12 + mA II
Current I
Driver
- 5 1b 9a 15 -
11/2015

Place for
labeling 1a, 1b - 24 V DC
2a, 2b +
FAULT
265151

6b
Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


70 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Place Holder Barrier HiD2000 Blank
HiD2000 Blank

Technical data Features


Conformity • H-System place holder module
Degree of protection IEC 60529
• Housing width 18 mm
Ambient conditions
Ambient temperature -20 ... 70 °C (-4 ... 158 °F) • Blank module, non-functional
Mechanical specifications
Degree of protection IP20
Function

H-System
Material Polycarbonate
This barrier is a non functioning HiD
Mass approx. 140 g
module designed to be a place holder for
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
system expansions.
Mounting on Termination Board
This barrier mounts on a HiD termination
board.
Configuration
No user configuration available for this device.

Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Diagrams

Front view

HiD2000 Blank
Accessories

HiD
2000
Blank
Module
11/2015
250499

Zone 0, 1, 2
Div. 1, 2 Termination Board
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
71
Entity Parameters Isolated Barriers

ATEX Entity Parameters

Model Number Terminals Uo (V) Io (mA) Po (mW)


HiD2024 5a, 5b; 1a, 1b 25.2 93 586
3a, 3b; 7a, 7b
HiD2030SK 5a, 5b; 1a, 1b 26 93 605
H-System

5b, 7a; 1b, 3b 1.2 50 15


HiD2038 5a, 5b; 1a, 1b 26 93 605
HiD2824 5a, 5b; 1a, 1b 13.2 20 66
3a, 3b; 7a, 7b
HiD2844 5a, 5b; 1a, 1b 13.2 20 66
3a, 3b; 7a, 7b
HiD2872 5a; 7a, 5b 26 110 715
1a; 3b, 1b
Digital Inputs

CSA Entity Parameters

Model Number Terminals Voc (V) Isc (mA)


HiD2030SK 5a, 5b; 1a, 1b 26 93
5b, 7a; 1b, 3b 1.2 50
5a, 5b, 7a; 1a, 1b, 3b 27.2 143
HiD2038 5a, 5b; 1a, 1b 26 93
Digital Outputs

HiD2824 5a, 5b; 1a, 1b 13.2 20


3a, 3b; 7a, 7b
HiD2844 5a, 5b; 1a, 1b 13.2 20
3a, 3b; 7a, 7b
HiD2872 5a; 7a, 5b 26 110
1a; 3b, 1b
Analog Inputs
Analog Outputs
Accessories

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


72 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Isolated Barriers Notes

H-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Accessories
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
73
Appendix

Edition 265151 11/2015

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


74 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Table of Contents

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
General Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Model Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
75
Notes Termination Board Solutions for Emerson DeltaV
Appendix
Glossary
General Notes
Model Number
Index

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


76 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Glossary

A Associated Apparatus
Apparatus in which the circuits are not necessarily intrinsically
Active Zener Barrier safe themselves, but which affect the energy in the intrinsically
safe circuits and are relied upon to maintain intrinsic safety.
A Zener Barrier with additional active components (i. e.,
Associated electrical apparatus may be either
transistors, integrated circuits, etc.) that provides special
functions or features. 1. electrical apparatus that have an alternative type of
protection, for use in the appropriate hazardous (classified)

Appendix
AIT location; or
2. electrical apparatus that are not protected and therefore
Abbreviation for autogenous ignition temperature. cannot be used within a hazardous (classified) location.

Amplifier Associated Non-Incendive Field Wiring


A device that enables an input signal to control power from a Apparatus
source independent of the signal and thus be capable of
delivering an output that bears some relationship to, and is Apparatus in which the circuits are not necessarily non-
generally greater than, the input signal. incendive themselves but that affect the energy in non-
incendive field wiring circuits and are relied upon to maintain
non-incendive energy levels.
Analog Input

Glossary
Analog type signal from a hazardous area instrument (i. e., Associated Safe-Location Equipment
transmitter) to the safe area controller.
Equipment designed to form part of an intrinsically safe
system, in which not all the circuits are of an intrinsically
Analog Output
safe system, in which not all the circuits are intrinsically safe,
Analog type signal from the safe area controller to the but which affects the safety of the intrinsically safe system of
hazardous area instrument (i. e., I/P positioner). which it forms a part. Such equipment may not be installed in a

General Notes
hazardous location unless provided with appropriate
ANSI protection, such as the installation of an explosion-proof
enclosure in a Class I hazardous location. Examples of
Abbreviation for American National Standards Institute. associated safe-location equipment are

API 1. a line-connected power unit supplying power to intrinsically


safe equipment in a hazardous location and
Abbreviation for American Petroleum Institute. 2. a recorder in a safe location actuated by a transducer
situated in a hazardous location.
Approved

Model Number
Acceptable to the authority having jurisdiction. Authority Having Jurisdiction

Index
The organization, office, or individual that has the
Arcing Device responsibility and authority for approving equipment,
installations, or procedures.
A device, such as make/break component, that under normal
conditions produces an arc with energy sufficient to cause
ignition of an ignitable mixture. See also "non-incendive Autogenous Ignition Temperature
circuit." The temperature at which a mixture of a specified gas or vapor
in air will spontaneously ignite under specified test conditions,
Asset Management without any source of ignition.
Asset Management functionality often includes the monitoring
of devices like flow meters, analyzers, actuators, and control Automation System
valves. It detects faults and sometimes even recommends The system that provides overall control and monitoring
corrective actions. functions of a specific process or application. Generally
consists of a network of computers, controllers, and I/O
modules.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
77
Glossary Termination Board Solutions for Emerson DeltaV

B Certified Equipment
Equipment that has been evaluated by a recognized testing
Barrier Specification agency and confirmed to be in compliance with the applicable
standard(s).
The typical way of describing a barrier, for example 28 V,
300  93 mA. This is a reference to the maximum voltage of
the terminating zener diode during the period of time it takes CESI
for the fuse to break, the minimum value of the terminating
Appendix

Abbreviation for Centro Elettronico Sperimentale Italiano. A


resistor and the resulting maximum short circuit current. The governmental body in Italy that has the authority to accept or
description does not refer to the working voltage or the end-to- reject the design of an electrical apparatus based on
end resistance, but is purely an indication of the potential fault recognized safety standards.
energy that could be generated in the hazardous area.
Class I Location
BASEEFA
A location in which flammable gases or vapors are or may be
Abbreviation for British Approvals Service for Electrical present in the air in quantities sufficient to produce explosive or
Equipment in Flammable Atmospheres. A governmental body ignitable mixtures.
in the United Kingdom that has the authority to accept or reject
the design of an electrical apparatus based on recognized Class I, Division 1 Location
Glossary

safety standards.
A location (1) in which ignitable concentrations of flammable
BSI gases or vapors can exist under normal operating conditions;
(2) in which ignitable concentrations of such gases or vapors
Abbreviation for British Standards Institute. may exist frequently because of repair or maintenance
operations or because of leakage; or (3) in which breakdown
Bus Technology or faulty operation of equipment or processes might release
ignitable concentrations of flammable gases or vapors and
A variety of bus technologies are employed throughout the
General Notes

might also cause simultaneous failure of electrical equipment


industry. PROFIBUS, MODBUS, FOUNDATION fieldbus, and
that could act as a source of ignition.
Ethernet ensure reliable exchange of digital information
between the control system and Remote I/O.
Class I, Division 2 Location
A location (1) in which volatile flammable liquids or flammable
C gases are handled, processed, or used, but in which the
liquids, vapors, or gases will normally be confined within
Capacitance closed containers or closed systems from which they can
Model Number

escape only in case of accidental rupture or breakdown of


The property of a system of conductors and dielectrics that such containers or systems, or in case of abnormal operation
Index

permits the storage of electrically separated charges when of equipment; (2) in which ignitable concentrations of gases or
potential differences exist between the conductors. The vapors are normally prevented by positive mechanical
greater the capacitance, the greater the charge that can be ventilation and might become hazardous through failure or
stored. The practical difference between capacitance and abnormal operation of the ventilating equipment; or (3) that is
inductance in an intrinsically safe circuit is minimal. Both store adjacent to a Class I, Division 1 location and to which ignitable
energy but a capacitor will release energy when a circuit is concentrations of gases or vapors might occasionally be
made and an inductor will release energy when the circuit is communicated unless such communication is prevented by
broken. adequate positive-pressure ventilation from a source of clean
air and effective safeguards against ventilation failure are
CENELEC provided. Electrical conduits and their associated enclosures
separated from process fluids by a single seal or barrier are
Abbreviation for European Electrotechnical Committee for
classified as a Class I, Division 2 location if the outside of the
Standardization. The standard for the European Economic
conduit and enclosures is a non-hazardous (unclassified)
Community (EEC) nations and the European Free Trade
location.
Association. Legally, certification to the CENELEC standard is
sufficient to permit sale in any European country. If IEC
standards are available, CENELEC tries to utilize them
because these standards are already adopted by the
European community.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


78 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Glossary
Class II Location Code of Practice
A location that is hazardous because of the presence of An international term referring to a document that describes
combustible dust. basic safety features and methods of protection and
recommends the selection, installation, and maintenance
Class II, Division 1 Location procedures that should be followed to ensure the safe use of
electrical apparatus.
A location (1) in which combustible dust is in the air under

Appendix
normal operating conditions in quantities sufficient to produce
Com Unit and Gateway
explosive or ignitable mixtures; (2) in which mechanical failure
or abnormal operation of machinery or equipment might cause Bus systems employ communication units (Com Units) to
such explosive or ignitable mixtures to be produced and might interface the DCS or PLC master with the Remote I/O slaves.
also provide a source of ignition through simultaneous ( the Their properties depend on the protocol they support.
word "simultaneous" is not included in the Canadian definition)
failure of electric equipment, operation of protection devices, Configuration in Run (CiR or HCiR)
or from other causes; or (3) in which combustible dusts of an
electrically conductive nature may be present in hazardous Online Remote I/O changes are made possible by means of
quantities. (hot) configuration in run (HCiR) methods. This is based on
freezing output data during the bus reset period or by offering
redundancy rings.
Class II, Division 2 Location

Glossary
A location in which combustible dust is not normally in the air in Converter
quantities sufficient to produce explosive or ignitable mixtures
and dust accumulations are normally insufficient to interfere A type of isolated barrier that receives a signal from the
with the normal operation of electrical equipment or other hazardous area instrument (i. e. transmitter, thermocouples,
apparatus, but combustible dust may be in suspension in the etc.) and converts it into an equivalent signal
air as a result of infrequent malfunctioning of handling or (i. e. 4 mA ... 20 mA, 1 V ... 5 V, etc.).
processing equipment and where combustible dust

General Notes
accumulations on, in, or in the vicinity of the electrical or may Control Drawing
be ignitable by abnormal operation or failure of electrical A drawing or other document provided by the manufacturer of
equipment. the intrinsically safe or associated apparatus that details the
allowed interconnections between the intrinsically safe and
Class III Location associated apparatus.
A location that is hazardous because of the presence of easily
ignitable fibers or flyings but in which such fibers or flyings are CSA
not likely to be in suspension in the air in quantities sufficient to

Model Number
Abbreviation for Canadian Standards Association. A third
produce ignitable mixtures. party certification agency headquartered in Canada and

Index
recognized by OSHA as a Nationally Recognized Test
Class III, Division 1 Location Laboratory in the United States. The presence of CSA, UL, or
A location in which easily ignitable fibers or materials FM certification marks on equipment is normally sufficient to
producing flyings are handled, manufactured, or used. the local inspector that the product is designed to recognized
safety standards.
Class III, Division 2 Location
A location in which easily ignitable fibers are stored or handled
(except in the process of manufacture).

Clearance Distance
The shortest distance measured in air between conductive
parts.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
79
Glossary Termination Board Solutions for Emerson DeltaV

D Dust-Ignition Proof
A term used in the United States to describe an enclosure that
Definition of Contamination Level 2 per will exclude ignitable amounts of dusts that might affect
EN 50178 performance or rating and that, when installed and protected in
accordance with the original design intent, will not permit arcs,
Under normal circumstances, only non-conductive sparks, or heat otherwise generated or liberated inside the
contamination occurs. Occasionally however, short-term enclosure to cause ignition of exterior accumulations or
Appendix

conductance may be expected through condensation when atmospheric suspensions of a specified dust.
the device is not being operated. This applies to the immediate
surrounding conditions of the electronic device. Dust-Protected Enclosure
Device Type Manager (DTM) An international term describing an enclosure in which the
ingress of dust is not totally prevented, but dust does not enter
Manufacturers supply DTMs for their devices to allow a in sufficient quantity to interfere with the safe operation of the
FDT frame application in the DCS or master to configure and equipment or accumulate in a position within the enclosure
service their equipment. where it is possible to cause an ignition hazard.

Digital Input Dust-Tight


Glossary

Signal from a hazardous area instrument that is an on/off type An enclosure so constructed that dust will not enter the
electrical input to the safe area (i. e., contact closure, proximity enclosing case under specified test conditions.
sensor).

Digital Output E
On/Off type signal from the safe area to the hazardous area
(i. e., signal to a solenoid or LED cluster). EC-Type Examination Certificate
General Notes

The manufacturer certifies that the product meets the


Distance Through Casting Compound fundamental safety requirements under EC regulations by the
The shortest distance between two conductive parts application of a registration number to this product.
separated by a casting compound. The following regulations apply to Pepperl+Fuchs products:

Distance Through Solid Insulation 73/23/EWG Low Voltage Directive


89/336/EWG EMC Directive
The shortest distance between two conductive parts
separated by solid insulation. 89/392/EWG Machine Directive
Model Number

94/9/EG Devices and Safety Systems for


Driver Hazardous Areas
Index

A type of active or transformer isolated barrier that receives a


signal from a safe area source (i. e., DCS, process controller, Encapsulation
etc.) and drives that signal to the hazardous area instrument An international term describing a type of protection in which
(i. e., I/P positioner). the parts that could ignite an explosive atmosphere by either
sparking or heating are enclosed in an encapsulant in such a
Dust, Combustible way that this explosive atmosphere cannot be ignited. This
type of protection is referred to by CENELEC as "Ex m" in
Dust that (when mixed with air in certain proportions) can be
Standard EN 60079-18.
ignited and will propagate a flame. The combustible properties
of dust are dependent upon test conditions and dust particle
size, chemical structure, and other particle characteristics. End-to-End Resistance
The resistance between both ends of a barrier channel. It is the
sum of the resistor itself and the resistance of the fuse at an
ambient temperature of 20 °C.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


80 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Glossary
Entity Concept Ex "o"
The entity concept provides more flexibility in selecting Designation for the oil immersion (segregation) method of
equipment to form an intrinsically safe system. The entity protection.
concept allows the user to identify acceptable combinations of
intrinsically safe apparatus and associated apparatus that Ex "p"
have not been examined as a system.
Designation for the pressurization (segregation) method of

Appendix
protection.
Entity Parameters
The four categories that are set by the certification agency in Ex "q"
order to properly match the intrinsic safety barrier to the
hazardous area instrument. These four parameters are Designation for the powder-filling (segregation) method of
voltage, current, capacitance and inductance. protection.

Ethernet Ex "s"
High speed bus, which lends itself to various protocols. Most Designation for the special (special protection) method of
commonly used protocols are MODBUS TCP and Ethernet IP. protection. This method is standardized only in Great Britain
Redundancy solutions are in place. Slaves are often and Germany.

Glossary
connected to the bus via switches.
Explosion-Proof Enclosure
Ex "d" An enclosure that is capable of withstanding an explosion of a
Designation for the flame-proof (explosion containment) gas or vapor within it and of preventing the ignition of an
method of protection. explosive gas or vapor that may surround it and that operates
at such an external temperature that a surrounding explosive
gas or vapor will not be ignited. This type of enclosure is similar
Ex "e"

General Notes
to a flame-proof enclosure.
Designation for the increased safety (prevention) method of
protection. Explosion-Proof Equipment (apparatus)
Equipment or apparatus enclosed in an explosion-proof
Ex "i"
enclosure.
Designation for the intrinsic safety (prevention) method of
protection. This method consists of two categories-"ia" and
"ib." F

Model Number
Ex "ia" Fault

Index
This intrinsic safety category is limited to low power circuits A defect or electrical breakdown of any component, spacing or
and is suitable for process instrumentation. Up to two faults are insulation that alone or in combination with other faults may
allowed and can be used in Zones 0, 1, and 2. adversely affect the electrical or thermal characteristics of the
intrinsically safe circuit. If a defect or breakdown leads to
Ex "ib" defects or breakdowns in other components, the primary and
This intrinsic safety category is similar to the Ex "ia" method, subsequent defects and breakdowns are considered to be a
except that category "ib" allows only one fault and can only be single fault.
used in Zones 1 and 2. Countable Fault
A fault that is applied to a part of the electrical apparatus that
Ex "m" meets the constructional requirements of this standard.
Designation for the encapsulation (segregation) method of Uncountable Fault
protection.
A fault that is applied to areas of the electrical apparatus that
do not meet the constructional requirements of this standard. If
Ex "n" application of a countable fault leads to subsequent defects
Designation for the simplified (prevention) method of and breakdowns, they are considered to be uncountable
protection. faults.

FAT
11/2015

Abbreviation for factory acceptance tests.


265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
81
Glossary Termination Board Solutions for Emerson DeltaV

Fibers and Flyings, Easily Ignitable G


Fibers and flyings that are easily ignitable including rayon,
cotton (including cotton linters and cotton waste), sisal or Galvanic Isolation
henequen, jute, hemp, tow, cocoa fiber, oakum, baled waste
A form of isolation that meets stringent standards for
kapok, Spanish moss, excelsior, and other materials of similar
intrinsically safe circuits.
nature.
GAMP
Appendix

FieldConnex
Abbreviation for good automated manufacturing practices.
FieldConnex is a comprehensive fieldbus infrastructure that
connects the control system to intelligent field instruments via
a two wire bus.
Gateway and Com Unit
Bus systems employ gateways to interface the DCS or PLC
Field Device Tool (FDT) master with the Remote I/O slaves. Their properties depend on
the protocol they support.
FDT is the name of an interface specification. It offers the
frame application for DTM (drivers) supplied by device
manufacturers.
Grounding Device
An impedance device used to connect conductors of an
Glossary

Flame-Proof Enclosure electric system to ground for the purpose of controlling the
ground current or voltages to ground, or a nonimpedance
An International term describing an enclosure that can
device used to temporarily ground conductors for the purpose
withstand the pressure developed during an internal explosion
of the safety of workmen. The grounding device may consist of
of an explosive mixture and that prevents the transmission of
a grounding transformer or a neutral grounding device, or a
the explosion to the explosive atmosphere surrounding the
combination of these. Protective devices, such as surge
enclosure and that operates at such an external temperature
arresters, may also be included as an integral part of the
that a surrounding explosive gas or vapor will not be ignited.
device.
General Notes

This enclosure is similar to an explosion-proof enclosure. This


type of protection is referred to by IEC as "Ex d."
Group
FM A classification of flammable materials of similar hazard.
Consists of Groups A, B, C, D, E, F, and G to NEC and CEC
Abbreviation for Factory Mutual Approvals, a third party
standards and Groups I, IIA, IIB, and IIC to IEC standards.
certification agency that is recognized by OSHA as a
Nationally Recognized Testing Laboratory in the United
States. It is a division of Factory Mutual Global, which
H
Model Number

specializes in property insurance. For marketing in the U.S.,


FM, CSA, and UL provide testing, listing and labeling services
HART
Index

for industrial and safety products. Generally, certifications by


FM, CSA, and UL are recognized in most jurisdictions;
HART (Highway Addressable Remote Transducer) is a
however, there are exceptions.
popular digital fieldbus protocol that solves a wide range of
applications. It is used to communicate with field devices,
FOUNDATION Fieldbus configure and monitor the status of the system, and indicate
FOUNDATION fieldbus is a digital communications system process variables.
that serves as the base-level network in a plant or factory
automation environment. It is an open architecture, developed Hazardous (Classified) Location
and administered by the Fieldbus Foundation.
A location where fire or explosion hazards may exist due to the
Fieldbus permits the use of spurs and chicken foot structures presence of flammable gases or vapors, flammable liquids,
based on IEC 61158-2 standards. combustible dust, or easily ignitable fibers or flyings.

Fuse Rating Hazardous Materials


This is the maximum current that can flow continuously Gases, vapors, combustible dusts, fibers, or flyings that are
through the fuse (approx. 1000 hours at 35 °C). The rated explosive under certain conditions.
current may be exceeded for short periods at temperatures up
to approximately 55 °C. Hermetically Sealed Device
A device that is sealed against the entrance of an external
11/2015

atmosphere and in which the seal is made by fusion.


Continuous soldering, brazing, welding, and the fusion of glass
to metal are examples of recognized methods.
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


82 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Glossary

I Inductance
The property of an electric circuit by virtue of which a varying
I.S. Ground current induces an electromotive force in that circuit or in a
neighboring circuit. The practical difference between
A dedicated ground system to which zener barriers are
capacitance and inductance in an intrinsically safe circuit is
connected. The resistance to ground path must be less than or
minimal. Both store energy, but an inductor will release energy
equal to 1  from any zener barrier to designated ground
when a circuit is broken, and a capacitor will release energy
electrode.

Appendix
when the circuit is made.
I.S. Insulation coordination
Abbreviation for intrinsic safety.
The assignment of the insulation characteristics of an
apparatus in accordance with:
I/O Module
1. the expected overvoltages
A module that provides basic input and output functions 2. the characteristic values of the overvoltage precautions
between the automation system and the field devices.
3. the expected surrounding conditions
Disregarding specialty modules, there are four basic types
4. the protective measures against contamination
available from various vendors - analog input, analog output,
discrete input, and discrete output.

Glossary
Insulator
IEC A material that conducts electrons slowly. The importance to
intrinsic safety is that air (a spatial distance) is often an
Abbreviation for International Electrotechnical Commission.
insulator.
An international commission of which most nations are
members. IEC standards directly affect equipment for sale
internationally. The benefit of participation in the IEC is that Internal Wiring
costly differences in plant or equipment design can be avoided

General Notes
Wiring and electrical connections that are made within the
by designing equipment consistent with IEC documents where apparatus by the manufacturer. Within racks or panels,
feasible. interconnections between separate pieces of apparatus made
in accordance with detailed instructions from the apparatus
Ignitable Gas Mixture manufacturer are considered to be internal wiring.
A gas -air mixture that is capable of being ignited by an open
flame, arc or spark or high temperature. Intrinsic Safety Barrier
A component containing a network designed to limit the
Ignition (Autoignition) Temperature

Model Number
energy (voltage and current) available to the protected circuit
in the hazardous (classified) location under specified fault
The minimum uniform temperature required to initiate or cause

Index
conditions.
self-sustained combustion of a solid, liquid, or gaseous
substance (independent of any other ignition source).
Intrinsic Safety Ground Bus
Increased Safety A grounding system that has a dedicated conductor separate
from the power system so that ground currents will not
An international term that describes a type of protection in
normally flow and that is reliably connected to a ground
which various measures are applied so as to reduce the
electrode (e. g., in accordance with Article 250 of NEC,
probability of excessive temperatures and the occurrence of
ANSI/NFPA 70, or Section 10 of CEC Part I, CSA C22.1).
arcs or sparks in the interior and on the external parts of
electrical apparatus that do not produce them in normal
service. This type of protection is referred to by IEC as "Ex e."
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
83
Glossary Termination Board Solutions for Emerson DeltaV

Intrinsic Safety ISA


A type of protection in which a portion of the electrical system Abbreviation for the Instrumentation, Systems and Automation
contains only intrinsically safe equipment (apparatus, circuits, Society. ISA Committee SP12, established in 1949, has been
and wiring) that is incapable of causing ignition in the influential in establishing the recognition of intrinsic safety and
surrounding atmosphere. No single device or wiring is non-incendive circuits in the NEC.
intrinsically safe by itself (except for battery-operated self-
contained apparatus such as portable pagers, transceivers, Isolated Barriers
Appendix

gas detectors, etc., which are specifically designed as


intrinsically safe self-contained devices) but is intrinsically safe A type of barrier with additional active components and
only when employed in a properly designed intrinsically safe galvanic isolation to separate the hazardous area instrument
system. This type of protection is referred to by IEC as "Ex i." from the safe area controller providing advantages over the
traditional zener barrier.
Intrinsically Safe Apparatus
Apparatus in which all the circuits are intrinsically safe. K
Intrinsically Safe Circuit Knock-Out
A circuit in which any spark or thermal effect, produced either A portion of the wall of an enclosure so fashioned that it may
Glossary

normally or in specified fault conditions, is incapable, under the be removed readily by a hammer, screwdriver, and pliers at
prescribed test conditions, of causing ignition of a mixture of the time of installation in order to provide a hole for the
flammable or combustible material in air in the mixture's most attachment of an auxiliary device or raceway, cable, or fitting.
easily ignited concentration.

Intrinsically Safe Equipment L


Equipment that may be installed in a hazardous location, in
General Notes

which all the circuits are intrinsically safe, or that is designed to Labeled Equipment
form part of an intrinsically safe system.
Equipment or materials, to which has been attached a label,
Intrinsically Safe Ground symbol, or other identifying mark of an organization concerned
with product evaluation, that may maintain periodic inspection
A clearly identified conductor of not less than 12 AWG/4 mm2 of the production of labeled equipment or materials, and by
cross-sectional area with a total impedance from barrier whose labeling the manufacturer indicates compliance with
ground bus bar to main power system earth of not more than appropriate standards or performance in a specified manner.
1 .
Model Number

LEL
Intrinsically Safe System
Index

Abbreviation for lower explosive limit (lower flammable limit).


An assembly of interconnected intrinsically safe apparatus,
associated apparatus, and interconnecting cables in which Life Cycle Management
those parts of the system that may be used in hazardous
(classified) locations are intrinsically safe circuits. The product life cycle ensures that products or compatible
replacements are available to cover the life of an industrial
plant.

Listed
Equipment or materials, included in a list published by an
organization concerned with product evaluation, that maintains
periodic inspection of production of listed equipment or
materials and whose listing states either that the equipment or
materials meets appropriate standards or has been tested and
found suitable for use in the specified manner.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


84 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Glossary

M Maximum Input Current (Ii; Imax)


Maximum current (peak AC or DC) that can be applied to the
Maintenance, Corrective connection facilities for intrinsically safe circuits without
Any maintenance activity that is not normal in the operation of invalidating intrinsic safety.
the equipment and requires access to the equipment's interior.
Such activities are expected to be performed by qualified Maximum Input Power (Pi)
personnel who are aware of the hazards involved. Such

Appendix
The maximum power that can be applied to the terminals of an
activities typically include locating causes of faulty
intrinsically safe device without invalidating the intrinsic safety
performance, replacement of defective components,
of the device.
adjustment of internal controls, and the like.

Maintenance, Operational Maximum Input Voltage (Ui; Vmax)


Any maintenance activity, excluding corrective maintenance, Maximum voltage (peak AC or DC) that can be applied to the
intended to be performed by the operator and required in order connection facilities for intrinsically safe circuits without
for the equipment to serve its intended purpose. Such invalidating intrinsic safety.
activities typically include the correcting of "zero" on a panel
instrument, changing charts, record keeping, adding ink, and Maximum Internal Capacitance (Ci)

Glossary
the like.
The total unprotected internal capacitance of the intrinsically
safe apparatus that must be considered as appearing across
Make/Break Components the terminals of the intrinsically safe apparatus.
Components having contacts that can interrupt a circuit (even
if the interruption is transient in nature). Examples of Maximum Internal Inductance (Li)
make/break components are relays, circuit breakers,
servo potentiometers, adjustable resistors, switches, The total unprotected internal inductance of the intrinsically

General Notes
connectors, and motor brushes. safe apparatus that must be considered as appearing across
the terminals of the intrinsically safe apparatus.
Maximum External Capacitance (Co; Ca)
Maximum Internal Inductance to
Maximum capacitance in an intrinsically safe circuit that can be Resistance Ratio (Li/Ri)
connected to the connection facilities of the apparatus without
invalidating intrinsic safety. Ratio of inductance (Li) to resistance (Ri) which is considered
as appearing at the external connection facilities of the
Maximum External Inductance (Lo; La) electrical apparatus.

Model Number
Maximum value of inductance in an intrinsically safe circuit that Maximum Output Current (Io, Isc)

Index
can be connected to the connection facilities of the apparatus
without invalidating intrinsic safety. Maximum current (peak AC or DC) in an intrinsically safe
circuit that can be taken from the connection facilities of the
Maximum External Inductance to apparatus.
Resistance Ratio (Lo/Ro)
Maximum Output Power (Po)
Ratio of inductance (Lo) to resistance (Ro) of any external
circuit that can be connected to the connection facilities of the Maximum electrical power in an intrinsically safe circuit that
electrical apparatus without invalidating intrinsic safety. can be taken from the apparatus.

Maximum Inductance to Resistance Ratio Maximum Output Voltage (Uo, Voc)


(L/R) Maximum output voltage (peak AC or DC) in an intrinsically
As an alternative value to La, the ratio of inductance (L) to safe circuit that can appear under open circuit conditions at the
resistance (R) of any external circuit that can be connected to connection facilities of the apparatus at any applied voltage up
the terminals of intrinsically safe apparatus without invalidating to the maximum voltage, including Um and Ui.
the intrinsic safety of the apparatus.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
85
Glossary Termination Board Solutions for Emerson DeltaV

Maximum RMS Voltage Um NFPA


Maximum voltage that can be applied to the non-intrinsically Abbreviation for National Fire Protection Association. The
safe connection facilities of associated apparatus without NFPA has acted as a sponsor and publisher of the National
invalidating intrinsic safety. The value of Um may be different at Electrical Code since 1911. Most of the NFPA standards tend
different sets of connection facilities. to emphasize recommendations for the safe use of electrical
apparatus, area classification, fire protection, and hazards of
Maximum Surface Temperature materials.
Appendix

The highest temperature attained by a surface accessible to Non-Hazardous Location


flammable gases, vapors, or combustible dusts under
conditions of operation within the ratings of the apparatus A location utilizing drying, curing, or fusion apparatus and
(including recognized overloads and defined fault conditions. provided with positive mechanical ventilation adequate to
prevent accumulation of flammable concentrations of vapors,
MEIC and provided with effective interlocks to deenergize all electric
equipment (other than equipment approved for Class I
Abbreviation for most easily ignited concentration. locations) in case the ventilating equipment is inoperative,
shall be permitted to be classified as non-hazardous where the
MESG authority having jurisdiction so judges.
Glossary

Abbreviation for maximum experimental safe gap.


Non-Incendive Circuit
MIC A circuit in which any arc or thermal effect produced in normal
operating conditions of the equipment is not capable, under
Abbreviation for minimum ignition current.
prescribed conditions, of igniting the specified flammable gas,
vapor-in-air mixture, combustible dusts, or ignitable fibers or
MIE flyings.
Abbreviation for minimum ignition energy.
General Notes

Non-Incendive Component
Minimum Igniting Voltage A component having contacts for making or breaking a
Minimum voltage of capacitive circuits that causes the ignition specified incendive circuit in which the contacting mechanism
of the explosive test mixture in the spark-test apparatus. is constructed so that the component is not capable of ignition
of the specified flammable gas or vapor-in-air mixture when
MODBUS tested as specified by appropriate test procedure. The housing
of a non-incendive component is not intended to exclude the
Legacy medium speed master/slave bus protocol based on flammable atmosphere or contain an explosion.
Model Number

RS485 hardware architecture. Offers easily understandable


data address modes. Standard does not cover redundancy but Non-Incendive Equipment
Index

individual solutions are in place. Slaves are connected to the


bus in parallel. Equipment having electrical/electronic circuitry and
components that are incapable under normal conditions, of
causing ignition of a specified flammable gas or vapor-in-air
N mixture due to arcing or thermal effect.

NEMA Non-Incendive Field Wiring


Wiring that enters or leaves an equipment enclosure and,
Abbreviation for National Electrical Manufacturers Association.
under normal operating conditions of the equipment, is not
Provides a rating system to identify an enclosure's ability to
capable, due to arcing or thermal effects, of igniting a specified
repel the outside environment. Unlike organizations such as
flammable gas or vapor-in-air mixture or combustible dust-in-
UL, FM, and CSA, NEMA does not require independent testing
air mixture. Normal operation includes opening, shorting, or
and leaves compliance to its rating system completely up to
grounding the field wiring.
the manufacturer.
Non-Incendive Field Wiring Apparatus
Apparatus intended to be connected to non-incendive field
wiring.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


86 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Glossary
Normal Operational Conditions P
Conditions that conform electrically and mechanically with its
design specifications and is used within the limits specified by Passive Transistor Output
the manufacturer.
A transistor in which the emitter and collector are not
connected to an internal power source. Only the base is
NRTL connected so that it may be switched on and off. The emitter
and collector may be connected to the customer's power

Appendix
Abbreviation for Nationally Recognized Testing Laboratory.
This recognition indicates that the Occupational Safety & source.
Health Administration has accredited certain organizations to
evaluate products according to consensus based safety Polarity
standards.
Zener barriers are available in polarized (DC) and non-
polarized (AC) versions. Positive polarity types have the
negative side of the circuit grounded, while negative polarity
O types have the positive side of the circuit grounded. Non-
polarized barriers have zener diodes connected in inverse
Operational Maintenance series pairs and can be used in both AC and DC circuits.
Any maintenance activity, other than corrective maintenance,

Glossary
intended to be performed by the operators and which is
PROFIBUS DP, DP V1
required in order for the equipment to serve its intended Widely popular master/slave bus protocol based on RS485
purpose. Such activities typically include the correcting of hardware architecture. Offers fast and deterministic data
"zero" on a panel instrument, changing charts, making exchange. Standard also covers redundancy. Slaves are
records, adding ink, etc. connected to the bus in parallel.

OSHA Protective (Infallible) Component or

General Notes
Abbreviation for Occupational Safety and Health Assembly
Administration. The OSHA Act was passed by the U.S. A component or assembly which is so unlikely to become
Congress in 1971. Part 1910 of the OSHA regulations adopted defective in a manner that will lower the intrinsic safety of the
the 1968 NEC and defined "approved" to mean "listed by UL or circuit it may be considered not subject to fault when analysis
FM." "Approved" was redefined in 1972, providing exceptions or tests for intrinsic safety are made.
to FM or UL listing; however, in practice the emphasis on
listing remained unchanged. Listing requirements increased
PTB
interest in developing standards for certain categories of

Model Number
apparatus, such as process control instrumentation. Third- Abbreviation for Physikalisch-Technische Bundesanstalt. An
party approval agencies (e. g., UL, FM, CSA) for electrical approval agency in Germany that has the authority to accept or

Index
equipment must be accredited by OSHA. reject the design of an electrical apparatus based on
recognized safety standards.
Overvoltage category
The assignment of an electrical apparatus in accordance with
the expected overvoltage.
R
Table:
Redundancy
The assignment of rated operating voltages to the rated surge
voltages Redundancy is used to ensure that a Remote I/O station can
continue to work even when there is a fault in a master, in a
Rated operating voltage (V) Rated surge voltages (V) for bus line, in a communication unit, or in a power supply.
for alternating voltage overvoltage category
systems in accordance with
I II III IV
Remote I/O
DIN IEC 38
A system of intrinsically safe galvanically isolated input and
230/400/277/4801) 1500 2500 4000 6000
output devices placed in various locations around a production
400/690 2500 4000 6000 8000 plant. They provide a way to communicate effectively with
1000 4000 6000 8000 12000 modern DCS systems and proven legacy field devices.
1)
Remote I/O connect a wide range of digital and analog sensors
Rated operating voltage of 500 V is set.
and actuators to process control systems over a fieldbus. A
variety of gateways are available to make use of different bus
11/2015

protocols.
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
87
Glossary Termination Board Solutions for Emerson DeltaV

Repeater Serial Interface


A type of active or transformer isolated barrier that receives a A method of digitally transmitting data between devices over a
signal from the hazardous area instrument (i. e., transmitter, pair of conductors. See RS 232 and RS 485.
thermocouple, etc.) and repeats that signal into the safe area
while providing Intrinsic Safety. Short Circuit Protected
The ability of an intrinsic safety barrier or isolator to withstand
Resistance Temperature Detector (RTD)
Appendix

the shorting of its' intrinsically safe connections to ground.


A resistor made of some material for which the electrical Determined by dividing the rated voltage by its' internal
resistivity is a known function of the temperature and that is resistance. If the resulting value is less than the fuse rating, the
intended for use with a resistance thermometer. It is usually in barrier is said to be short circuit protected.
such a form that it can be placed in the region where the
temperature is to be determined. Short Circuit Protection
The ability of the solid-state output to withstand a direct short
Resistance
without damage to itself.
That physical property of an element, device, branch, network
or system that is the factor by which the mean-square Shunt Diode Barrier Assembly
conduction current must be multiplied to give the
Glossary

corresponding power lost by dissipation as heat or as other A fuse- or resistor- protected diode barrier.
permanent radiation or loss of electromagnetic energy from
the circuit. Signal Conditioning
Signal conditioning is an important part of any automation
RS 232 system where electrical isolation, electronic signal conversion,
An EIA standard that specifies the electrical, mechanical, and and measurement accuracy are critical characteristics of the
functional characteristics for serial communications. Used in control loop architecture. This is one of the tasks Remote I/O
General Notes

point-to-point applications. fulfill.

RS 485 Simple Apparatus


An EIA standard that specifies the electrical characteristics of An electrical component or combination of components of
a balanced-voltage digital interface. Used in multi-point simple construction with well-defined electrical parameters
applications. that is compatible with the intrinsic safety of the circuit in which
it is used. A device that will neither generate nor store more
than 1.5 V, 0.1 A and 25 mW. Examples are switches,
Model Number

S thermocouples (TCs), light-emitting diodes (LEDs), and


resistance temperature devices (RTDs).
Index

Safe Area SIT


A non-hazardous location. Abbreviation for spontaneous ignition temperature.

Seal, Cable, Explosionproof Switch Amplifier


A cable terminator filled with compound and designed to Term used for the type of transformer isolated barrier that is
contain an explosion in the enclosure to which it is attached or used to repeat signals from discrete inputs (i. e., contact
to minimize passage of flammable gases or vapors from one closures, proximity sensors.)
location to another. A conduit seal may also be used as a
cable seal. This method differs from the international practice, System Integration
which requires cable glands.
System integration forms a vital part of Remote I/O technology.
Seal, Conduit, Explosionproof The user can configure both the Remote I/O and the field
devices from the system's own workstation or a secondary
A sealed fitting, poured with a cement-like potting compound, central operating console.
designed to contain an explosion in the enclosure to which it is
attached and to minimize passage of flammable gases or
vapors from one location to another.
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


88 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Glossary

T Z
Temperature Code (Temperature Zener Barrier
Classification) An assembly consisting of a fuse, voltage-limiting shunt
A system of classification by which one of 14 temperature diodes, and a current-limiting resistor or other current-limiting
identification numbers (internationally, six temperature components.

Appendix
classes) is allocated to an electrical apparatus. The It is designed to limits current and voltage to the hazardous
temperature code represents the maximum surface area to a level below that which would ignite a specific gas/air
temperature of any component that may come in contact with mixture.
the flammable gas or vapor mixture.
The fuse protects the diodes from open circuiting when high
fault current flows.
Termination Panel
A mechanical assembly that resides in front of the I/O system Zener Diode
and performs signal conditioning, electrical isolation, and other
A class of silicon diodes that exhibit in the avalanche
functions.
breakdown region a large change in reverse current over a
very narrow range of reverse voltage. This characteristic
Thermistor

Glossary
permits a highly stable reference voltage to be maintained
An electron device that makes use of the change of resistivity across the diode despite a relatively wide range of current
of a semiconductor with change in temperature. through the diode.

Thermocouple (TC) Zone


A pair of dissimilar conductors so joined at two points that an The international method of specifying the probability that a
electromotive force is developed by the thermoelectric effects location is made hazardous by the presence, or potential

General Notes
when the junctions are at different temperatures. presence, of flammable concentrations of gases and vapors.
The term Division is used in the United States and Canada.
TIB
Zone 0
Abbreviation for Transformer Isolated Barrier. A term used to
describe an isolated intrinsic safety barrier used for hazardous An area in which an explosive gas-air mixture is continuously
area applications. Although a typical TIB will employ multiple present or present for long periods. Equal to a Class I, Division
means of isolation, the term TIB is used to generically describe 1 hazardous location.
this type of barrier.
Zone 1

Model Number
Transmitter (Tx) An area in which an explosive gas-air mixture is likely to occur

Index
A device for transmitting a coded signal when operated by any in normal operation. Equal to a Class I, Division 1 hazardous
one of a group of actuating devices. location.

Zone 2
U An area in which an explosive gas-air mixture is not likely to
occur and if it does occur, will only exist for a short time. Equal
UEL to a Class I, Division 2 hazardous location.
Abbreviation for upper explosive limit (upper flammable limit).
Zone 20
UL An area in which a combustible dust cloud is part of the air
permanently, over long periods of time or frequently. Equal to a
Abbreviation for Underwriters Laboratories, Inc, a third party
Class II, Division 1 hazardous location.
certification agency that is an independent, self-supporting,
nonprofit testing laboratory and standards developer. It is
recognized by OSHA as a Nationally Recognized Testing
Zone 21
Laboratory in the United States. The presence of UL, CSA, or An area in which a combustible dust cloud in air is likely to
FM certification labels on equipment is normally sufficient occur in normal operation. Equal to a Class II, Division 1
evidence to the local inspector that the product is designed to hazardous location.
meet recognized safety standards.
Zone 22
11/2015

An area in which a combustible dust cloud in air may occur


briefly or during abnormal operation. Equal to a Class II,
265151

Division 2 hazardous location


Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
89
Notes Termination Board Solutions for Emerson DeltaV
Appendix
Glossary
General Notes
Model Number
Index

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


90 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV General Notes

General Notes Relating to Pepperl+Fuchs Product Information


1. All information and statements in the product information (both in printed and electronic form), in particular, but not limited to
descriptions, illustrations, drawings, statements concerning quality, workmanship, service and use as well as dimensions, are
current at the time the printed product information is issued or published in electronic media.
2. Pepperl+Fuchs reserves the right to unilaterally amend all information and statements at any time. Despite careful editing by
Pepperl+Fuchs, type or printing errors cannot be excluded completely.

Appendix
3. The information and statements do not provide any guarantee or warrant any characteristics of the products.
4. The information and statements in the printed product information reflect the current status at the time of issue. Changes made
after the printed product information is issued are published in product data sheets on the Pepperl+Fuchs homepage. This
information is available at www.pepperl-fuchs.com.
5. All information, statements, and technical specifications contained therein are based on valid standards and comply with
relevant standardized measuring methods.
6. Customers are always responsible for independently determining the suitability of our products for the intended application.
Only customers are aware of all the boundary conditions and influencing factors associated with the intended purpose. Due
to the enormous number of potential application options offered by Pepperl+Fuchs products and the subsequent range of

Glossary
possible external influences and a potential overlap of these influences in the application of products, Pepperl+Fuchs cannot
accept liability for any aspect of the actual customer application. This applies in particular to, but not limited to, applications in
safety systems and explosion hazardous areas as well as environmental influences such as chemicals, pressure, temperature
fluctuations, moisture, mechanical influences, and incorrect installation.
7. Customers who intend to use Pepperl+Fuchs products in new applications or applications where they do not have adequate
experience can contact Technical Sales Support (service line) and discuss the suitability of the products for the intended
application with our specialists. Customers are obliged to provide realistic and complete information on all the relevant
conditions associated with the application in writing to prevent misunderstandings.

General Notes
8. All rights reserved. Reprint or reproduction of any material in part or in whole only with express written consent of
Pepperl+Fuchs.

Model Number
Index
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
91
Notes Termination Board Solutions for Emerson DeltaV
Appendix
Glossary
General Notes
Model Number
Index

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


92 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Notes

Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
93
Notes Termination Board Solutions for Emerson DeltaV
Appendix
Glossary
General Notes
Model Number
Index

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


94 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Notes

Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
95
Notes Termination Board Solutions for Emerson DeltaV
Appendix
Glossary
General Notes
Model Number
Index

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


96 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Termination Board Solutions for Emerson DeltaV Notes

Appendix
Glossary
General Notes
Model Number
Index
11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
97
Model Number Index Termination Board Solutions for Emerson DeltaV

C
CAB-DVM-**-S37I16-MX-01000. . . . . . . . . . . . . . . . 58

H
Appendix

HiD2000 Blank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
HiD2024 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
HiD2030SK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
HiD2038 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
HiD2824 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
HiD2844 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
HiD2872 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
HiDTB04-DVM-IDC1-SC-R1-DI16 . . . . . . . . . . . . . . 32
Glossary

HiDTB04-DVM-IDC1-SC-R2-DI16 . . . . . . . . . . . . . . 36
HiDTB04-DVM-IDC3-SC-R2-DO08 . . . . . . . . . . . . . 40
HiDTB04-DVM-IDC4-SC-NO-AM16. . . . . . . . . . . . . 48
HiDTB08-DVM-IDC4-SC-R1-SM32 . . . . . . . . . . . . . 52
General Notes
Model Number
Index

11/2015
265151
Edition

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


98 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
www.pepperl-fuchs.com
Subject to modifications · © Pepperl+Fuchs
Printed in Germany · Part. No. 265151 11/15 01