0% found this document useful (1 vote)
706 views13 pages

Cold Vent Stack Foundation Design

Foundation Analysis & Design to ACI 318 with checks on bearing pressure, overturning, shear, sliding & settlement

Uploaded by

doverman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
706 views13 pages

Cold Vent Stack Foundation Design

Foundation Analysis & Design to ACI 318 with checks on bearing pressure, overturning, shear, sliding & settlement

Uploaded by

doverman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)

COLD VENT STACK FOUNDATION DESIGN

Fig. 7.1: Foundation Plan & Section


Materials
Concrete unit weight (density) wc = = 156 pcf 25 kN/m3
Maximum aggregate am = = 0.75 in 19 mm
Sec. 10.4, Concrete compressive strength f'c = = 4,000 psi 27.6 N/mm2
10481-BCL-AKSX-ST-
REP-0001 Reinforcement yield strength fy = = 60,870 psi 420 N/mm2
ACI 19.2.4.2 Modification factor (normal weight concrete) λ = = 1.0
ACI 19.2.2.1 Modulus of elasticity for concrete Ec = wc1.5*33*SQRT(f'c) = 4,076 ksi 28,105 MPa
ACI 20.2.2.2 Modulus of elasticity for steel Es = = 29,000 ksi 200,000 MPa
Poisson's ratio ν = = 0.2
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
A S D S uppor t R e act i ons LR F D S uppor t R e act i ons
N ode L/ C F x kN F y kN F z kN Mx kN m My kN m Mz kN m N ode L/ C F x kN F y kN F z kN Mx kN m My kN m Mz kN m
30 102: 1.0DL + 1.0LL 0.00 73.78 0.00 0.00 0.00 0.00 30 201: 1.4DL 0.00 94.89 0.00 0.00 0.00 0.00
30 105: 1.0DL + 0.75LL + 0.75WL(X) 15.67 73.78 0.00 0.00 0.00 -120.92 30 206: 1.2DL + 1.6LL + 0.8WL(Z) 0.00 90.93 12.53 96.74 0.00 0.00
30 106: 1.0DL + 0.75LL + 0.75WL(Z) 0.00 73.78 15.67 120.92 0.00 0.00 30 205: 1.2DL + 1.6LL + 0.8WL(X) 12.53 90.93 0.00 0.00 0.00 -96.74
30 104: 1.0DL + 1.0WL(Z) 0.00 67.78 15.67 120.92 0.00 0.00 30 202: 1.2DL + 1.6LL 0.00 90.93 0.00 0.00 0.00 0.00
30 103: 1.0DL + 1.0WL(X) 15.67 67.78 0.00 0.00 0.00 -120.92 30 204: 1.2DL + 1.0LL + 1.6WL(Z) 0.00 87.33 25.07 193.48 0.00 0.00
30 101: 1.0DL 0.00 67.78 0.00 0.00 0.00 0.00 30 203: 1.2DL + 1.0LL + 1.6WL(X) 25.07 87.33 0.00 0.00 0.00 -193.48

Column Pedestal Design


Pedestal sizing
Width of pedestal Bp = = 70.9 in 1,800 mm
Length of pedestal Lp = = 70.9 in 1,800 mm
Depth of pedestal hp = = 51.2 in 1,300 mm
Volume of column pedestal Vp = Bp x Lp x hp = 257,032.0 in3 4,212,000,000 mm3
Weight of pedestal Wp = Vped x wc = 23.7 kips 105.3 kN
Gross area of concrete section Ag = Bp x Lp = 5,022.0 in2 3,240,000 mm2
Ties for column pedestal # = = 4 #
Diameter of ties dt = = 0.50 in 12 mm
Main reinforcement for column pedestal # = = 8 #
Diameter of main reinforcement ds = = 1.00 in 25 mm
Main reinforcement spacing ratio γ = (h - 2dc - 2dt - ds)/h = 0.89 0.89
Kn = Pu/Ag = 0.02 ksi 155 kN/m2
Rn = Mu/AgLp = 0.00080
ACI 6.6.4.2 Reinforcement ratio ρ = = 0.010 1.0%
ACI 10.6.1.1 Minimum area of reinforcement required As,req = ρ x Ag = 50.2 in2 32,400 mm2
Number of bars n = = 66 No.
As,prov = n x ds = 51.8 in2 33,443 mm2
UC = 0.97 Rebar provision OK
Provide main reinforcement 66No - 8# bars 66No - 25mm bars
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
ACI 25.4.2.3 Maximum spacing of tie rebar smax = 47 x dt = 23.5 in 564 mm
Minimum spacing of tie rebar smin = 16 x dt = 8.0 in 192 mm
Provide tie bar spacing s = = 10.0 in 250 mm
Concrete Base Design
Preliminary footing dimension
Minimum area of base required Af = Ntot/qa = 45.5 ft2 4.21 m2
Concrete base length (required) ℓ = √Af = 6.7 ft 2,053 mm
Adopt a square base of length ℓ = = 9.9 ft 3,000 mm
UC = 0.68 Preliminary base size OK
Base sizing
Width of base Bb = = 118.1 in 3,000 mm
Length of base Lb = = 118.1 in 3,000 mm
Thickness of base hb = = 19.7 in 500 mm
Volume of base Vb = Bb x Lb x hb = 274,606.8 in3 4,500,000,000 mm3
Weight of base Wb = Vb x wc = 25.3 kips 112.5 kN
Staad.PRO Reaction (ASD)
Maximum vertical reaction Fy = = 16.6 kips 73.8 kN
Maximum horizontal reaction (X) Fx = = 3.5 kips 15.7 kN
Maximum horizontal reaction (Z) Fz = = - kips - kN
Maximum moment (X) Mx = = - kip-ft - kNm
Maximum moment (Z) Mz = = 89.6 kip-ft 120.9 kNm
Staad.PRO Reaction (LRFD)
Maximum vertical reaction Fy = = 19.6 kips 87.3 kN
Maximum horizontal reaction (X) Fx = = 5.6 kips 25.1 kN
Maximum horizontal reaction (Z) Fz = = - kips - kN
Maximum moment (X) Mx = = - kip-ft - kNm
Maximum moment (Z) Mz = = 143.3 kip-ft 193.5 kNm
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Weight of soil
Width of base Bb = = 118.1 in 3,000 mm
10481-BCL-AKGE- Height of soil above top of base hs = hp - 300 = 39.4 in 1,000 mm
GT-REP-0024
Unit weight of soil (Zaria PS) γs = = 125 pcf 20.0 kN/m3
3
Volume of base Vs = [(Bb x Lb) x (Bp x Lp)] x hs = 351,496.8 in 5,760,000,000 mm3
Weight of soil on foundation base Ws = Vs x γs = 25.9 kips 115.2 kN
Surcharge

Sec. 9.1.11, 10481-


Minimum surcharge pressure Ls = = 10.0 kPa 10.0 kN/m2
2
BCL-AKSX-ST-REP- Area of concrete base Ab = Bb x Lb = 13,950.0 in 9.00 m2
0001
Surcharge load Ns = Ls x Ab = 20.3 kips 90.0 kN
Weight of base plate Wbp = = 1.1 kips 4.7 kN
Total axial load Ntot = Fy,ASD + Wb + Wp + Wbp + Ws + Ns = 112.8 kips 501.5 kN
Assume reinforcement diameter Ø = = 1.0 in 25 mm
ACI 20.6.1.3.1 Concrete cover dc = = 3.0 in 75 mm
Lever arm ℓa (hp + hb) - dc - Ø/2 = 67.4 in 1.7 m
Maximum resultant moment (Z) Mzz = Mz + Fx*ℓa = 109.4 kip-ft 147.8 kNm
Maximum resultant moment (X) Mxx = Mx + Fz*ℓa = - kip-ft - kNm
Bearing Pressures
10481-BCL-AKGE- = = 2,485 psf
GT-REP-0024
Allowable soil bearing pressure (Zaria PS) qa 119.0 kN/m2
= = 2.485 ksf
Width of base Bb = = 118.1 in 3.0 m
Length of base Lb = = 118.1 in 3.0 m
2 2
Maximum pressure p1 = Ns/BL + 6Mxx/BL + 6Mzz/B L = 88.6 kN/m2
2 2
Minimum pressure p2 = Ns/BL - 6Mxx/BL - 6Mzz/B L = 22.9 kN/m2
UC = 0.74 Bearing capacity OK
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Moment at Column Face
Factored design load qf = Fy,LRFD + Wb + Wp +Wbp + Ws + Ns = 115.9 kips 515.0 kN
Bearing pressure qp = qf/Ap = 1.2 ksf 57.3 kN/m2
2
Ultimate design moment (LRFD) Mu = qp*[(ℓ - c)/2] *b/2 = 23.6 kip-ft 31.9 kNm
ACI 22.2.2.4.1 Compressive force acting on a nodal zone C = 0.85f'cba
Tension force acting on a nodal zone T = Asfy
Set concrete compression force equal to the steel tension force at the
ACI 22.2.1.1 C=T
column face: C = T
Distance between neutral axis and fiber of max. compressive strain a = Asfy/0.85f'cb = 1.5 As
ACI 21.2.1(a) Moment strength reduction factor ɸ = = 0.9
ACI 8.5.1.1(a) ϕMn ≥ Mu ɸMn ≥ 0.9 x 60.9As (1.3 - 1.492As/2)
A = = 40.9
Solve quadratic equation to determine As,req B = = - 71.2
C = = 23.6
Area of reinforcement required As,req = [-B + SQRT(B2 - 4AC)]/2A = 2.0 in2 1,308 mm2
Number of bars n = = 20 No.
Bar size # = = 6 #
Reinforcement diameter Ø = = 0.75 in 20 mm
Area of reinforcement provided As,prov = Provide 20-#6 bars @6in (T&B) on 10ft base 15.0 in2 9,677 mm2
20No. 20mm bars at 150mm on 3,000mm base UC = 0.14 Footing rebar OK

Fig. 7.2: Rebar arrangement on Footing


REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Two-way Shear Design

Fig. 7.3: Critical section in punching shear


Footing width bw = ℓ = 9.90 ft 3000 mm
Base area of footing Ap = ℓxℓ = 98.0 ft2 9.11 m2
Ultimate soil bearing pressure qt = qu/Ap = 1.2 ksf 55.0 kN/m2

ACI 21.2.1(b) Shear reduction factor ɸ = = 0.75


ACI 22.5.1.1 Nominal shear strength Vn = Vc + Vs =
Assume Vs = 0, no shear reinforcement ∴ Vn = Vc
Assume footing thickness h = = 19.7 in 500 mm
With 20No - #6 bars in both directions:
Reinforcement diameter Ø = = 0.75 in 20 mm
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
15.6 in
Effective depth d = h - dc - Ø - Ø/2 = 395 mm
1.3 ft
ACI 22.5.5.1 Nominal shear strength provided by concrete, Vc = Vn = 2√(f'c)bwd = 234.5 kips 1,043.2 kN
ɸVn 175.9 kips 782.7 kN
Column pedestal width b = = 70.9 in 1,800 mm
Factored shear force at section Vu = (ℓ/2 - b/2 - d)*bwqp = 15.4 kips 68.3 kN
UC = 0.09 Two-way shear OK
ACI 7.5.1.1 Criteria: ϕVn ≥ Vu ɸVn > Vu ∴ Footing depth OK

Overturning Check
Width of base Bb = = 118.1 in 3,000 mm
Length of base Lb = = 118.1 in 3,000 mm
Width of pedestal Bp = = 70.9 in 1,800 mm
Length of pedestal Lp = = 70.9 in 1,800 mm
Height of soil above top of base hs = hp - 300 = 39.4 in 1,000 mm

Table 8, 10481- Criteria for overturning:


BCL-AKSX-ST-REP- 1.0 x Mrest ≥ FS x Mover
0001 Factor of safety against overturning FS = = 1.5
Take moment of all forces about Point A below:
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)

T otal Ove r tur ning Mome nt, M o v e r


Ove r tur ning
De scr iption Action ( kN, kNm) F .S . Le ve r Ar m ( m)
Mome nt ( kNm)
Max. lateral force Fx = 15.67 1.5 L1 = 1.80 42.31
Max. moment Mz = 120.92 1.5 181.38
2 2 3 .6 9

T otal Re stor ing Mome nt, M r e s t


Ove r tur ning
De scr iption F or ce ( kN) F .S . Le ve r Ar m ( m)
Mome nt ( kNm)
Axial force (output) Fy = 73.78 1.0 L2 = 1.50 110.67
Wt. of pedestal Wp = 105.30 1.0 L2 = 1.50 157.95
Wt. of base Wb = 112.50 1.0 L2 = 1.50 168.75
Wt. of backfill 1 W1 = 36.00 1.0 L3 = 0.30 10.80
Wt. of backfill 2 W2 = 21.60 2.0 L2 = 0.30 12.96
Wt. of backfill 3 W3 = 36.00 1.0 L4 = 2.70 97.20
5 5 8 .3 3
Fig. 7.4: Overturning check
Total overturning moment Mover = = 165.7 kip-ft 223.69 kNm
Total restoring moment Mrest = = 413.6 kip-ft 558.33 kNm
UC = 0.40 Overturning OK
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Sliding Check
A S D S uppor t R e act i ons
N ode L/ C F x kN F y kN F z kN Mx kN m My kN m Mz kN m
30 102: 1.0DL + 1.0LL 0.00 73.78 0.00 0.00 0.00 0.00
30 105: 1.0DL + 0.75LL + 0.75WL(X) 15.67 73.78 0.00 0.00 0.00 -120.92
30 106: 1.0DL + 0.75LL + 0.75WL(Z) 0.00 73.78 15.67 120.92 0.00 0.00
30 104: 1.0DL + 1.0WL(Z) 0.00 67.78 15.67 120.92 0.00 0.00
30 103: 1.0DL + 1.0WL(X) 15.67 67.78 0.00 0.00 0.00 -120.92
30 101: 1.0DL 0.00 67.78 0.00 0.00 0.00 0.00

Maximum vertical reaction Fy = = 16.6 kips 73.8 kN

Table 9, 10481- Maximum horizontal reaction


Fx,z = = 3.5 kips 15.7 kN
BCL-AKSX-ST-REP- Factor of safety against sliding FS = = 1.5
0001
Weight of column pedestal Wp = = 23.7 kips 105.3 kN
Weight of concrete base Wb = = 25.3 kips 112.5 kN
Total weight of foundation WT = = 49.0 kips 217.8 kN

De scr iption F or ce ( kN)

Axial force (output) Fy = 73.78


Wt. of pedestal Wp = 105.30
Wt. of base Wb = 112.50
Wt. of backfill 1 W1 = 36.00
Wt. of backfill 2 W2 = 21.60
Wt. of backfill 3 W3 = 36.00
3 8 5 .1 8

Total vertical load Wv = = 86.7 kips 385.2 kN


Angle of internal friction φ = = 7.0 deg
Tan φ = = 0.12
Sliding resistance force FR = Wv * Tan φ = 47.3 kN
Fx,z * FS = 23.5 kN
UC = 0.50 Sliding OK
Uplift Check
The minimum ground water depth is 3.65 m above grade level, hence, no buoyancy effect envisaged on the foundation.
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Settlement Check
Immediate Settlement
Width of base Bb = = 118.1 in 3,000 mm
Length of base Lb = = 118.1 in 3,000 mm
Influence depth of stratum H = 2 x Bb = 236.2 in 6,000 mm

Fig. 7.5: Influence depth of stratum


Influence level Li = hs + h + H = 295.3 in 7,500 mm
Table 5, 10481-BCL- Influence level falls within Sandy Silty Clay
AKGE-GT-REP-0024 stratum
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Effective width of foundation B'b = Bb/2 = 59.1 in 1,500 mm
Ratio N = H/B'b = 4.0
M = Lb/Bb = 1.0

Table 5-2,
Foundation
Analysis & Design,
Bowles, 5th Ed.

I1 = = 0.408 = 0.408
Influence factors Table 5-2, Bowles
I2 = = 0.037 = 0.037
Poisson's Ratio μ = = 0.3 = 0.3
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Foundation depth D = hs + h = 59.1 = 1,500 mm

Fig. 7.6: Depth ratio


Depth ratio D/B = 0.5 = 0.5

Fig. 5-7,
Foundation
Analysis & Design,
Bowles, 5th Ed.

Fig. 7.7: Influence factor


Influence factor If = Fig. 5-7, Bowles = 0.775
REFERENCE COMPUTATION OUTPUT (imperial) OUTPUT (metric)
Maximum pressure qn = Ns/BL + 6Mxx/BL2 + 6Mzz/B2L = 88.6 kN/m2
Undrained modulus of soil Eu = = 19,000 kN/m2
2
Immediate settlement Se = qn x B x (1 - μ ) x If/Eu = = 9.86 mm

Consolidation Settlement
Sec. 10.6.2, 10481- Modulus of volume compressibility Mv = = 6.14E-05 m2/kN
BCL-AKGE-GT-REP-
0024 Vertical effective stress applied to the soil layer dp = = 111 kN/m2
Thickness of layer considered Hs = = 1.0 m
Consolidation settlement Sc = Mv x dp x Hs = 6.82 mm

Total Settlement
Total settlement St = Se + Sc = 16.68 mm
Allowable settlement Sall = = 25.00 mm
UC = 0.67 Settlement OK