LabPlanningManual 02 en
LabPlanningManual 02 en
LabPlanningManual 02 en
2.0
Chapter 2.0
LabSystem
Fume hood monitors
Table of contents
5.1 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Introduction
Safety in the laboratory The actual value of the volume flow is measured in the
exhaust air outlet at regular intervals.
Safe operation of the laboratory makes high demands on
the monitoring components: After internal linearisation of the actual value, an arithmetic
mean value is calculated. This ensures accurate analysis,
Monitoring with optical and acoustic alarm when the since disturbance variables, such as air turbulence, are
minimum air volume is underrun, in accordance with eliminated to a very large degree.
DIN EN 14175
Monitoring and malfunction notification of the internal The linearised actual value is now constantly compared
device functions and the sensor with a freely programmable setpoint volume flow.
Volume flow measurement in exhaust air outlets,
therefore independent of the construction and model
of the sash or the fume hood
All system parameters are saved mains voltage failure-
safe (in the EEPROM)
Monitoring of reduced operation (night-time operation)
Recognition and optical alarm in the case of a mains
voltage failure (operating LED flashes)
Relay outputs with potential-free contacts for external
signalling of malfunction and operating notifications
2.1.2 Acoustic and optical malfunction alarm Okay Fault Okay Overflow
Monitoring of a face velocity speed in the front area of the The SCHEIDER FM100 and FM500 monitoring systems
fume hood is done with an air flow sensor. Measurement work perfectly with both measuring systems and safely
takes place in the bypass, i.e. an air flow sensor mounted and reliably monitor fume hoods and extraction systems
in the fume hood roof measures the speed of the air flowing with variable or constant volume flows.
into the fume hood, which corresponds to the speed of the
air flow in the sash area. The dynamic sensor operates The iM50 monitoring system includes an integrated flow
in accordance with the calorimetric measuring principle. sensor and is therefore only suitable for monitoring the
A thermal element is heated to a specific temperature, constant face velocity.
which, depending on the air speed, is cooled more or less
by the air that flows by.
Battery backup
Exhaust
air
2
1 Fume hood 230 VAC Power
- monitor Day/Night operation
p
+ FM100 Digital In-/Outputs 4
3
Analogue Output 5
Functional
Fume hood display Air volume display
High
m3 6
Okay h
Low
Reset
RS 232
Monitoring according to
EN 14175
With the SVM100 service module or a laptop with the signalled by the LEDs on the function display. Thus all
PC2500 software installed, all parameters, such as valid standards are fulfilled.
setpoint volume flows (normal operation, night-time
operation, etc.), alarm delay time, alarm threshold, etc.,
can be programmed. 5.1 Interfaces
The exhaust air volume flow or optionally the face The potential-free relay contacts for malfunction and
velocity is continuously measured and compared with the operating notifications make it possible to easily connect
programmed setpoints. When the exhaust air setpoint to the building services management (BMS).
is underrun, an optical and acoustic alarm is activated.
The acoustic alarm can be acknowledged with the Reset Analogue actual value outputs of the exhaust air volume
button, while the optical alarm is only switched off when flow make it possible to integrate with the supply and
the exhaust air setpoint is either reached or exceeded. exhaust air controller for one or more laboratories.
The Close sash LED flashes when the fume hood sash is FM100 and FM500 also have a serial or LON interface
opened more than 50 cm (working height exceeded). (optional) for BMS monitoring/control as well as a standards-
compliant analogue output 2 ...10V (corresponds to 0m3/
The emergency power pack guarantees a supply of power h...1000m3/h).
in the case of a mains voltage failure. This status is
All system data are freely programmable via the SVM100
service module.
Figure 2.4 shows the schematic diagram of the entire Output-Ports and an A/D (Analogue/Digital converter).
FM100 fume hood controller.
In addition to a CPU kernel, there is also a D/A (Digital/
Analogue converter) as well as an input and an output
1.6.1 Power supply interface on the control board. The peripheral sensors are
connected to the corresponding port cables.
All SCHNEIDER products have their own 230V AC power
supply, which eliminates the need for a 24V AC power The parameters are saved mains voltage failure-free in
supply via an external transformer. The integrated power the EE-PROM.
supply makes planning easier, generates no additional
costs and considerably improves system safety and
stability of the electronics. With an external 24 V power 1.6.3 Two independent watchdogs circuits
supply the entire supply line would fail in the case of a
short circuit or other defect. The FM100 fume hood monitor has two independent
watchdog circuits. The microcontroller is checked for errors
The external emergency power pack is installed when the at regular intervals and in the case of an error in the CPU,
mains supply does not provide an uninterrupted power one or both of the watchdog circuits trigger a hardware
supply (UPS). In the case of a mains voltage failure, this is reset, which restarts the CPU. This extended watchdog
reported and the monitoring function is maintained via the concept additionally increases operating safety.
emergency power pack.
Watchdog 2 EE-PROM
Analogue output
for room control D/A ROM/RAM
I/O
CPU
Differential pressure transmitter
or A/D Timer
Air velocity sensor
TTL TTL: Display
Night
Watchdog 1 UART
Input
GND +5V +12V
OC: On/Off
Optocoupler
RS 232
Voltage supply
Main voltage
230/115 V AC Battery
backup
Power supply
Serial interface
Measuring tube
FLOW SENSOR
- (optional)
+
Monitoring FUNCTIONAL
according DISPLAY
to EN 14175 standard or
Fume hood customer version
High
Okay
Low
Reset Servicemodule
SVM-100
F1 F2 F3
1 2 3
4 5 6 Laptop
7 8 9
Supply air * 0 ,
+ = overpressure
X10
In1
In2
JP2 Exhaust air actual value
X7 FAZ 1 X8 2...10V DC ANALOGUE OUTPUT
GND 2...10V DC, 10mA
0...5/10V DC ANALOGUE INPUT
X6 FAZ 2
GND 0...5/10V DC, 1mA
JP1 In 1 On/Off
X5
Serial
Parallel Day/Night DIGITAL INPUTS
X4 - (black) In 2 monitoring Max. cable length <5m
Operation NO
FAULT LED-Sash
+ (red) In 3
K1: max. 3A/250V AC Fault NC position >50cm
K1
COM X9 Run
X2
3
VENTILATOR ON/OFF MOTOR ON NO
K2: max. 3A/250V AC
NC 2 TRANSFORMER
K2
COM PRIM: 230 VAC, 50/60Hz
1
LIGHT FUME HOOD SEK I: 9 V~/5 VA
ON/OFF K3 L
K3: max. 12A/250V AC L N N
X1
MAKE SURE TO EARTH X3
USE THE RIGHT
FUSES EARTH
N L
N L
A typical function display is shown in Figure 2.6. We also provide customer-specific function displays which
SCHNEIDER offers various standard versions (see harmonise with the design of the fume hood.
Technical data sheets, Function displays on the Internet).
RESET button
LED OK The acoustic alarm (malfunction due
This green LED lights up in the normal to insufficient exhaust air volume flow)
operating state, i.e. the fume hood is can be acknowledged by pressing the
operating with sufficient exhaust air Reset button. The optical alarm cannot
volume flow and is therefore within a be acknowledged and is only switched off
safe range. when sufficient exhaust air volume flow
can be regulated and the fume hood is
operated in a safe range.
LED LOW
This red LED lights up to signal a
malfunction, i.e. the fume hood is
operating with insufficient exhaust
LED close sash
This LED flashes as a warning signal
air volume flow and is therefore not
when the sash is open (> 50 cm). When
containment-safe.
the sash is shut the LED goes out.
Pressure nipple
Air direction
L
The valid shield factor for the installation size used must be
-
programmed in the FM100 or FM500 monitoring system.
+
shown in Figure 2.8 and is available in lengths from 160 to
800 mm. It is suitable for fitting in pipes or angled air ducts.
The appropriate shield factor S, which is dependent on the
fitting situation, must be determined.
Microprocessor controlled monitoring system Figure 2.9: FM100 fume hood monitor
Low cost system
Integrated power supply 230V AC
All system data are saved mains voltage failure-safe
in the EEPROM
Programming of all system values via service module
SVM100 or laptop computer software PC2500
Monitoring of supply air and exhaust air systems
Static differential pressure transmitter with long-
term stability. Measuring range: 6...240 pascal or
20...640 pascal. Optionally with air flow sensor (face
velocity)
Monitoring of fume hood operation in accordance
with EN 14175 with acoustic and optical alarms
Optional monitoring of exceedance of a
programmable volume flow with optical alarm
Optical and optionally acoustic alarm for the
operating status “Sash > 50cm”
Programming of a second monitoring value (reduced
volume flow during night-time operation)
Emergency power pack (optional) for mains voltage
failure-safe operation
Suitable for all fume hood constructions
Microprocessor controlled monitoring system Figure 2.10: FM500 fume hood monitor
Integrated power supply 230V AC
All system data are saved mains voltage failure-safe
in the EEPROM
Separate terminal board for fast, simple cable
connection
Pluggable mainboard for easy setup and servicing
Programming and retrieval of all system values via
the service module SVM100 or software PC2500
Monitoring of supply air and exhaust air systems
static differential pressure transmitter with long-
term stability. Measuring range: 6...240 pascal or
20...640 pascal. Optionally with air flow sensor (face
velocity)
Monitoring of fume hood operation in accordance
with
Monitoring of fume hood operation to EN 14175 with
acoustic and optical alarms
Optional monitoring of exceedance of a
programmable volume flow with optical alarm
Optical and optionally acoustic alarm for the
operating status “Sash > 50cm”
Programming of a second monitoring value (reduced
volume flow during night-time operation)
Emergency power pack (optional) for mains voltage
failure-safe operation
Integrated battery pack charging connection with low
voltage disconnect
Suitable for all fume hood constructions
Microprocessor controlled monitoring system Figure 2.11: iM50 fume hood monitor
Low cost airflow monitor as a compact fitted version
External mains adapter 100...230V AC/24V DC
All system data are saved mains voltage failure-safe
in the EEPROM
Integrated password protected operating interface for
programming the face velocity alarm values (daytime
and night-time operation) and the alarm delay time
Programming of all system values via laptop with
PC2500 software
Monitoring of supply air and exhaust air systems
Integrated air flow sensor 0.2...1 m/s for measuring
the face velocity
Monitoring of fume hood operation in accordance
with EN 14175 with acoustic and optical alarms
LED bar graph for displaying the actual value of the
face velocity in m/s and ft/min
Optical and optionally acoustic alarm for the
operating status “Sash > 50cm”
Programming of a second monitoring value (reduced
face velocity during night-time operation)
Button light ON/OFF (fume hood interior)
ON/OFF button for direct actuation of a fan
Suitable for all fume hood constructions
The diagram shows an overview of the products that are Technical data sheets, further information and tender
available from SCHNEIDER in the product group Fume specifications for the FM100, FM500 and iM50 fume hood
hood controllers. controllers are available for download on the Internet at
www.schneider-elektronik.de.
See Chapter 1, Section 6.1 for the full LabSystem product
overview.
Measuring device M-xxx Maintenance-free, self-cleaning measuring device with annuli that form 2.0
for volume flow the mean value for volume flow measurement.
MT-xxx Measuring tube, suitable for retrofitting in pipes and rectangular ducts 2.0