VENTILATION SYSTEM

Adjustable louvers grill (Supply air grill) with volume control damper

1.25 mm MS sheet shall be used for the manufacture of grill. All grills shall be true to shape and
shall be checked with a level gauge before being secured in position. No distortion or warping is
permitted.

All duct mounted grill shall be complete with rubber gaskets and flanged holding frames of
suitable design for the intended installation. They shall be mounted on collar extending from the
duct. No part of grilles shall project into the main duct. The adjustable louver grill shall be provided
with volume control damper as well as double deflection flap / grill for direction control.

AC SYSTEM

Supply air diffuser with volume control damper

Thickness of Grills, Diffuser, Damper shall be as follows: -

(a) Frame : 16 gauge


(b) Louvers : 18 gauge

Supply air diffusers shall be circular / rectangular in shape as per detailed engineering
requirement. The throat of a diffuser shall be connected with collar piece provided at the duct
bottom for holding the diffuser as well as for supply of air. Each diffuser shall be provided with
volume control damper. Each diffuser shall comprise of fixed plate, damper blade, damper blade
operating knob, spindle, connecting rod etc. The diffuser should flush with the false ceiling. False
ceiling shall not bear the load of any diffuser. The load of diffuser shall be borne by the duct and
collar. Each diffuser shall be painted with appropriate colour to match with the colour of the false
ceiling. Diffuser shall be placed considering light fittings position and false ceiling runner position.
Diffusers / grills shall be of extruded aluminum powder coated / Anodized aluminum.

Return air grill

In general, the return air opening shall be provided above false ceiling in the wall between served
premises and A.C. plant room. The return air grill of suitable size shall be provided at the A.C.
plant room side face of the said opening for smooth flow of return air. The air supplied in the
served premises shall come/return above false ceiling through the return air slit of 50~100 mm all
around false ceiling along the walls of the served premises. From there it shall pass into the A.C.
plant room through the return air passage.

The return grill shall comprise of horizontal fixed louvers made of 2 mm thick MS sheet, 50x6 thick
MS flat placed vertically at middle of the louvers, 50x50x6 size angle frame all around. Spacing of
the fixed louvers in the grill shall be 25 mm.