ADQ
Four way ceiling diffuser
Description
ADQ is a 4-way ceiling diffuser. It can be used as a terminal
ventilation element for supply and return air. It is ideal
for offices, shops or similar premises. The diffuser
is suitable for heating or cooling with ΔT of ± 10K.
Mounting frame R
Adjustment damper D
RAL9010
RAL9006
Colour RALXXXX
NOTES:
1. For the ADQ types with 2 sizes (600/xxx):
The first size (600) is the overall diffuser size. The second size determines
the boundary dimensions of the diffuser effective area. This type
of diffusers is foreseen for installation in the T-bar suspended ceiling.
2/9 | Diffusers
Design Q-50
35
ADQ front face is manufactured from aluminium painted
Q
white 9010 or silver RAL 9006 profiles.
It is available in six sizes from 250 to 625 mm. The ADQ Fig. 2: Product ADQ
fixed in the hole by two screws. The size of such diffuser 300 40601 40607
is then defined e.g. 600/300 (overall size 600 / effective 400 40602 40608
area size 300). All accessories are manufactured 500 40603 40609
from galvanized steel sheet. 600 40604 40610
Dimensions
Q Free area AV
Size
(mm) (m2)
250 248 0,0095
Technical parameters
Terminology Legend
70
50
Tuning damper
50
Size
position 45°
30
Pressure drop ΔPt (Pa)
45
Δpt × 1,1
20 250
40
LWA 1
Δpt × 1,1
(A)
35
300
dB
LWA -
10 Δpt × 1,2
30 400
wA LWA 1
25
7
Δpt
L
× 1,3
500
LWA 1
20
5
Δpt × 1,2
600
LWA 2
3
100 200 300 500 1000 2000 Δpt × 1,2
625
qV0 (m3 • h-1) LWA -
Diagram 1: Determination of volume flow and pressure drop for supply air Tab. 3: Corrections to Diagram 1
ADQ with VVKU plenum box
70
600
50 625
Tuning damper
Size
position 45°
Pressure drop ΔPt (Pa)
30
50
Δpt × 1,1
250
20 LWA -
45
Δpt × 1,2
300
40
LWA 2
Δpt × 1,3
35
10
400
LWA 1
30
(A)
7 Δpt × 1,5
dB
500
LWA 1
25
wA
5
L
Δpt × 1,8
600
20
LWA 1
3
100 200 300 500 1000 2000 Δpt × 1,9
625
qV0 (m3 • h-1) LWA -1
Diagram 2: Determination of volume flow and pressure drop for return air Tab. 4: Corrections to Diagram 2
ADQ with VVKU plenum box
60
40
Pressure drop ΔPt (Pa)
Damper R1
50
30 Size
50% 25%
45
LWA 17 34
15 Δpt
35
× 3,1 × 10,9
A)
400
dB(
LWA 21 39
30
A
Δpt
Lw
10 × 4,0 × 13,5
500
LWA 24 42
25
8
Δpt × 3,5 × 14,4
600
20
6
LWA 23 45
5
200 400 600 1000 2000 3000 5000 Δpt × 3,5 × 17,4
625
qV0 (m3 • h-1) LWA 24 47
Diagram 3: Determination of volume flow and pressure drop for ADQ-R1 Tab. 5: Corrections to Diagram 3
4/9 | Diffusers
Size 400
250 300 400 500 H1= 1,0 1,2 1,3 2,0 m
80 600
qV0 = m3 • h-1
0,80
60 625 900
720
40
540
0,60
360
270
50
0,50
50
Pressure drop ΔPt (Pa)
30
0,
VH1 (m • s-1)
45
VL (m • s-1)
0,40
40
0,
20
40
30
0,30
15
0,
dB(A 5
3
)
30
10
20
0,
0,20
A
8 LW
25
15
0,
6 0,15
20
5
100 200 400 600 1000 2000 4000 2 3 4 5 6 8 10
10
0,
qV0 (m3 • h-1) L (m)
Diagram 8: Determination of volume flow and pressure drop for ADQ Diagram 6: Average air flow velocity in occupied zone
50
0,
0,
VH1 (m • s-1)
VH1 (m • s-1)
VL (m • s-1)
VL (m • s-1)
0,40 0,40
40
40
0,
0,
30
30
0,30 0,30
0,
0,
20
20
0,
0,
0,20 0,20
15
15
0,
0,
0,15 0,15
2 3 4 5 6 8 10 2 3 4 5 6 8 10
10
10
0,
0,
L (m) L (m)
Diagram 4: Average air flow velocity in occupied zone Diagram 9: Average air flow velocity in occupied zone
50
0,
0,
VH1 (m • s-1)
VH1 (m • s-1)
VL (m • s-1)
VL (m • s-1)
0,40 0,40
40
40
0,
0,
30
30
0,30 0,30
0,
0,
20
20
0,
0,
0,20 0,20
15
15
0,
0,
0,15 0,15
2 3 4 5 6 8 10 2 3 4 5 6 8 10
10
10
0,
0,
L (m) L (m)
Diagram 5: Average air flow velocity in occupied zone Diagram 7: Average air flow velocity in occupied zone
Diffusers | 5/9
Temperature differential
Size 625
H1= 1,0 1,2 1,3 2,0 m
0,6
qV0 = m3 • h-1
1800 0,80
1440
0,4
1080
900 0,60
0,3
790
0,50
50
0,
0,2
Si
VH1 (m • s-1)
VL (m • s-1)
ze
0,40
ΔTL / ΔT0
40
0,
62
0,15
5
60
0
30
50
0,30
0,
0
40
0,1
0
20
0,08
0,
30
0,20
0
25
0,06
15
0
0,
0,15
0,04
2 3 4 5 6 8 10 2 3 4 5 6 8 10
10
0,
L (m) Lt (m)
Diagram 10: Average air flow velocity in occupied zone Diagram 11: Temperature differential
250
3 10 5 3 -3 -7 -17 -24 -27
300
Return air 400
ADQ with VVKU 4 8 3 2 -3 -5 -13 -20 -24
plenum box 500
250
3 9 2 3 1 -12 -15 -31 -35
300
Supply air, 400
ADQ with mounting 4 9 3 2 0 -7 -19 -28 -30
frame ADQ-UR 500
250
3 10 2 3 0 -10 -26 -31 -35
300
Supply air, 400
ADQ with ADQ-R1 4 8 2 2 0 -6 -19 -27 -30
damper 500
Accessories
• PB-ADQ: Plenum box • ADQ-UR-xxx: Mounting frame for fixing by central bolt.
• PB-VVKU: Universal plenum box • ADQ-R1-xxx: Opposed blade damper
(fitting for most of Systemair products) for easy air flow adjustment.
For details please see the VVKU catalogue.
PB-ADQ
2
Plenum box 1
4
Ordering Codes
PB-ADQ-
H1
I2 □A
Internal insulation 14 mm 2
External insulation 2 J
B
□A□A
+ 24 □A
A
□A + 24 □A + 24
A + 24
Ordering code example: Fig. 5: Main dimensions of the PB-ADQ
PB-ADQ - 300 - S - H - I2
1. If no spigot type defined, the type D1 will be delivered.
The plenum boxes with vertical spigot D2 are delivered without screen.
2. If no insulation type defined, the product will be delivered
without insulation.
Diffusers | 7/9
Legend
The Zeus damper
D1 - Untight socket with a sheet-metal control damper
The Zeus control damper contains impulse tubes D2 - Pressed tight socket with a Zeus damper
for measuring differential pressure using a portable xxxx - Defined selection option
• - Option to add a position to the selection
measuring device. It can be adjusted manually using — - Not possible to add a position to the selection
a cable gearing.
Mounting Frame R
Mesh screen S
Connection type Spigot and socket joint U
No Sealing A
Sealing B
The PB-VVKU is a universal box which is possible Spigot type Sealing and Damper C
to use for installation on various types of air terminal
devices. The PB-VVKU is manufactured from galvanized
sheet. Upon customer’s request it is possible to apply Ordering codes example:
a powderpaint RAL surface finish. The box is optimized PB-VVKU - 0H - 300 - 100 - S - B
for use with both horizontal and vertical connection.
Universal plenum box, not insulated with horizontal supply,
When in storage, the PB-VVKU provides the advantage nominal size 300, connection dimension 100, mesh screen, sealed socket.
of stacking, thus saving storage space.
NOTE: When using the PB-VVKU plenum box, it is recommended to read
the technical documentation for the product TPI-07.
8/9 | Diffusers
ød1 ød2 K1 K2 K3 K4 H m
Size
(mm) (kg)
300 98 126 250 200 278 292 190 1,95
ød1
317
H
Fig. 6: Main dimensions of the PB-VVKU plenum box Tab. 8: Main dimensions and weight of the PB-VVKU plenum box
(Table for Fig. 7)
Q-6 50
K
Q K H øD
Size
(mm)
øD
H+4
Q
625 623 540 385 313
Fig. 7: ADQ with the PB-VVKU plenum box Tab. 9: Dimensions of the product ADQ with the PB-VVKU plenum box
(Table for Fig. 8)
Other accessories
Q-36
50
Size
Q (mm)
250 248
Fig. 8: ADQ-UR
300 298
500 498
100
600 598
625 623
Q
35
Tab. 10: Dimensions of the product ADQ with the ADQ-UR or the ADQ-R1
Fig. 9: ADQ-R1 (Table for Fig. 9 and Fig. 10)
NOTE:
It is not possible to use plenum box PB-ADQ or PB-VVKU if the mounting
frame ADQ-UR or damper ADQ-R1 is used.
Mounting
The front face can be either inserted into T-bar ceiling
or screwed with a central screw to the plenum box.
The screw is supplied with a plastic cap.
VDQ
Diffusion grilles