Starvert: Leader in Electrics & Automation
Starvert: Leader in Electrics & Automation
Starvert iH
30 - 55kW(40 -75HP) 3 phase 200 - 230Volts
Leader in Electrics & Automation 30 - 220kW(40 - 300HP) 3 phase 380 - 400Volts, 440 - 460Volts
• For your safety, please read user's manual thoroughly before operating.
• Contact the nearest authorized service facility for examination, repair, or adjustment.
• Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions • Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Standard features
KW / Voltage Ratings:
30-55kW, 200-230VAC, 3 phase
30-220kW, 380-460VAC, 3 phase
Inverter Type : PWM with IGBT
CPU : 32bits high speed DSP
Control method: Volts/Hertz with
Space Vector PWM Technology
CT, VT dual ratings
Enclosure : IP00
2-10kHz Carrier Frequency
0.5-400 Output Frequency
Removable Keypad(Able to read & write parameters)
Dual rated iH, 6 Multi-function Inputs
Contents
fits for HVAC applications 5 Multi-function Outputs (3 Open-collectors, 2 Relays)
Overview 02 4-20mA Analog Output
with Space Vector Control. DC Injection Braking
Features & Selection Guide 04
Specifications 06 Options
Wiring & Terminal Configuration 08 Dynamic Braking Units
Communication Board
Keypad & Procedure of Setting Data 10
RS485
Program Parameter Descriptions 12 F-Net
ModBus-RTU
Dimension & Braking unit 16 Device Net
Profibus
Driveview 2.0 & Peripheral devices & RFI Filters 18
Window based operating software(Driveview 2.0)
Application
Fan/Blower
Water/Waste Water Pump
Conveyor
Parking System
Material Handling
Industrial Washing Machine
Packaging machine
ISO9001 ISO14000
02
Overview
Standard features
KW / Voltage Ratings:
30-55kW, 200-230VAC, 3 phase
30-220kW, 380-460VAC, 3 phase
Inverter Type : PWM with IGBT
CPU : 32bits high speed DSP
Control method: Volts/Hertz with
Space Vector PWM Technology
CT, VT dual ratings
Enclosure : IP00
2-10kHz Carrier Frequency
0.5-400 Output Frequency
Removable Keypad(Able to read & write parameters)
Dual rated iH, 6 Multi-function Inputs
Contents
fits for HVAC applications 5 Multi-function Outputs (3 Open-collectors, 2 Relays)
Overview 02 4-20mA Analog Output
with Space Vector Control. DC Injection Braking
Features & Selection Guide 04
Specifications 06 Options
Wiring & Terminal Configuration 08 Dynamic Braking Units
Communication Board
Keypad & Procedure of Setting Data 10
RS485
Program Parameter Descriptions 12 F-Net
ModBus-RTU
Dimension & Braking unit 16 Device Net
Profibus
Driveview 2.0 & Peripheral devices & RFI Filters 18
Window based operating software(Driveview 2.0)
Application
Fan/Blower
Water/Waste Water Pump
Conveyor
Parking System
Material Handling
Industrial Washing Machine
Packaging machine
ISO9001 ISO14000
02
Starvert iH Features & Selection Guide
Space vector PWM technology User friendly easy straight line programming
The Space vector technology is being adopted in all LG drives. It features outstanding performance in its The iH has simple grouping programming flow. It enables quick and easy parameter change
control characteristics. It has low total harmonic distortion, low current ripple, low torque ripple, low motor and monitoring through 32 character two line LCD display keypad.
temperature rise, and better voltage utilization. It is a basic control platform of the iH. The advantages of
Space vector PWM technology are being provided in many applications.
High torque in overall speed range
The iH has 150% torque at low speed. Thus, its torque performance is proved in high duty applications.
30 40 SV030iH-2 SV030iH-4
37 50 SV037iH-2 SV037iH-4
Built-in PI control 45 60 SV045iH-2 SV045iH-4
It is valuable in process control. The built-in PI controller controls flow, temperature, pressure, etc. through 55 75 SV055iH-2 SV055iH-4
the proportional and integral calculus between the feedback value and reference value in closed loop. 75 100 SV075iH-4
90 125 SV090iH-4
110 150 SV110iH-4
Convenient and Various Communication Interface 132 175 SV132iH-4
The iH can be operated with communication interface such as RS485, ModBus-RTU, DeviceNet, Profibus, 160 215 SV160iH-4
and F-Net, in order to be operated in various circumstances. Driveview 2.0 software is a Window based 220 300 SV220iH-4
tool that provides convenience of monitoring and controlling to user. The Driveview 2.0 features a graph
monitor, keypad emulator, parameter editor, and text monitor, to help user`s monitoring and controlling of
drive. It is applicable for all LG drives. Drive type nomenclature
SV 30 iH -4
LG Starvert drive
03 04
Starvert iH Features & Selection Guide
Space vector PWM technology User friendly easy straight line programming
The Space vector technology is being adopted in all LG drives. It features outstanding performance in its The iH has simple grouping programming flow. It enables quick and easy parameter change
control characteristics. It has low total harmonic distortion, low current ripple, low torque ripple, low motor and monitoring through 32 character two line LCD display keypad.
temperature rise, and better voltage utilization. It is a basic control platform of the iH. The advantages of
Space vector PWM technology are being provided in many applications.
High torque in overall speed range
The iH has 150% torque at low speed. Thus, its torque performance is proved in high duty applications.
30 40 SV030iH-2 SV030iH-4
37 50 SV037iH-2 SV037iH-4
Built-in PI control 45 60 SV045iH-2 SV045iH-4
It is valuable in process control. The built-in PI controller controls flow, temperature, pressure, etc. through 55 75 SV055iH-2 SV055iH-4
the proportional and integral calculus between the feedback value and reference value in closed loop. 75 100 SV075iH-4
90 125 SV090iH-4
110 150 SV110iH-4
Convenient and Various Communication Interface 132 175 SV132iH-4
The iH can be operated with communication interface such as RS485, ModBus-RTU, DeviceNet, Profibus, 160 215 SV160iH-4
and F-Net, in order to be operated in various circumstances. Driveview 2.0 software is a Window based 220 300 SV220iH-4
tool that provides convenience of monitoring and controlling to user. The Driveview 2.0 features a graph
monitor, keypad emulator, parameter editor, and text monitor, to help user`s monitoring and controlling of
drive. It is applicable for all LG drives. Drive type nomenclature
SV 30 iH -4
LG Starvert drive
03 04
Starvert iH Specifications
1) Constant Torque [HP] 40 50 60 75 Constant Torque [HP] 125 150 175 215 300
Motor rating* 1) Constant Torque [kW] 90 110 132 160 220
Constant Torque [kW] 30 37 45 55 Motor rating*
Constant Torque FLA [A] 46 55 68 83 Variable Torque [HP] 150 200 250 300 350
Output ratings
Constant Torque [kVA]*2) 122 146 180 220 Variable Torque [kW] 110 132 185 220 280
Voltage 3phase, 200to 230V( 10%) Constant Torque FLA [A] 183 223 264 325 432
Input ratings 4)
Frequency 50 to 60Hz( 5%) Constant Torque [kVA]* 136 166 197 242 322
Output ratings
Weight[kg(lbs)] 42(93) 42(93) 56(123) 56(123) Variable Torque FLA [A] 228 264 330 361 477
4)
Variable Torque [kVA]* 170 200 246 270 356
Voltage 3phase, 440 to 460V( 10%)
Input ratings
Frequency 50 to 60Hz( 5%)
Weight[kg(lbs)] 98(216) 98(216) 122(269) 122(269) 175(386)
Specifications 380 ~ 400V Class(40~ 300HP)
Type SV030iH-4 SV037iH-4 SV045iH-4 SV055iH-4 SV075iH-4
Constant Torque [HP] 40 50 60 75 100
Motor rating*
1) Constant Torque [kW] 30 37 45 55 75 Common Specifications
Variable Torque [HP] 50 60 75 100 125
Max. Frequency 0.5 to 400 Hz
Variable Torque [kW] 37 45 55 75 90 Output ratings
Output Voltage 3 Phase, 0 to Input Voltage
Constant Torque FLA [A] 61 75 91 110 152
3) Control Method Space Vector PWM
Constant Torque [kVA]* 40 50 60 70 100
Output ratings Frequency Setting Resolution Digital Reference: 0.01 Hz (Below 100Hz), 0.1 Hz (Over 100Hz)
Variable Torque FLA [A] 80 96 115 125 160
3)
Variable Torque [kVA]* 52 62 74 80 103 Analog Reference: 0.03 Hz / 60Hz
Voltage 3phase, 380 to 400V( 10%) Frequency Accuracy Digital: 0.01% of Maximum Output Frequency
Input ratings
Frequency 50 to 60Hz( 5%) Analog: 0.1% of Maximum Output Frequency
Control
Weight[kg(lbs)] 45(99) 45(99) 63(139) 63(139) 68(150) V/F Ratio Linear, Non-Linear, User Programmable
Braking Torque (w/o DB) About 20%
Overload Capacity CT 150% of Rated Current for 1 Minute, 200% for 0.5 Second
Type SV090iH-4 SV110iH-4 SV132iH-4 SV160iH-4 SV220iH-4
Overload Capacity VT 110% of Rated Current for 1 Minute, 150% for 0.5 Second
Constant Torque [HP] 125 150 175 215 300
Torque Boost Manual Torque Boost (0 to 20%), Auto Torque Boost
1) Constant Torque [kW] 90 110 132 160 220
Motor Rating* Operation Method Keypad / Terminal / Remote (Optional)
Variable Torque [HP] 150 175 215 250 350
Variable Torque [kW] 110 132 160 185 280 Frequency Setting Analog: 0 to 10 V / 4 to 20mA, Digital: Keypad
Constant Torque FLA [A] 183 223 264 325 432 Accel / Decel Time 0.1 to 6,000 sec, 8 Pre-Defined (Programmable)
Constant Torque [kVA]*3) 120 145 170 200 280 Multi-Step 8 Preset Operational Speed
Output ratings
Variable Torque FLA [A] 228 264 330 361 477 Operating Jog Jog Operation
Variable Torque [kVA]*3) 147 170 213 233 307 Operating Function DC Braking, Frequency Limit, Frequency Jump, Slip Compensation, PI Control, Stall Prevention
Voltage 3phase, 380 to 400V( 10%) Operating Status Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Under Voltage,
Input ratings
Frequency 50 to 60Hz( 5%)
Drive Overheat, Run, Stop, Constant Speed, Speed Searching
Weight[kg(lbs)] 98(216) 98(216) 122(269) 122(269) 175(386)
Start Signal Forward, Reverse
Programmable Input 6 Programmable Inputs
Programmable Output 5 Programmable Outputs: 2 Form A Contact (N.O.)
Fault Contact Output (A, C, B) - 250VAC 1A, 30VDC 1A
Programmable I/O
3 Open Collector Outputs: 24V, 50mA
05 06
Starvert iH Specifications
1) Constant Torque [HP] 40 50 60 75 Constant Torque [HP] 125 150 175 215 300
Motor rating* 1) Constant Torque [kW] 90 110 132 160 220
Constant Torque [kW] 30 37 45 55 Motor rating*
Constant Torque FLA [A] 46 55 68 83 Variable Torque [HP] 150 200 250 300 350
Output ratings
Constant Torque [kVA]*2) 122 146 180 220 Variable Torque [kW] 110 132 185 220 280
Voltage 3phase, 200to 230V( 10%) Constant Torque FLA [A] 183 223 264 325 432
Input ratings 4)
Frequency 50 to 60Hz( 5%) Constant Torque [kVA]* 136 166 197 242 322
Output ratings
Weight[kg(lbs)] 42(93) 42(93) 56(123) 56(123) Variable Torque FLA [A] 228 264 330 361 477
4)
Variable Torque [kVA]* 170 200 246 270 356
Voltage 3phase, 440 to 460V( 10%)
Input ratings
Frequency 50 to 60Hz( 5%)
Weight[kg(lbs)] 98(216) 98(216) 122(269) 122(269) 175(386)
Specifications 380 ~ 400V Class(40~ 300HP)
Type SV030iH-4 SV037iH-4 SV045iH-4 SV055iH-4 SV075iH-4
Constant Torque [HP] 40 50 60 75 100
Motor rating*
1) Constant Torque [kW] 30 37 45 55 75 Common Specifications
Variable Torque [HP] 50 60 75 100 125
Max. Frequency 0.5 to 400 Hz
Variable Torque [kW] 37 45 55 75 90 Output ratings
Output Voltage 3 Phase, 0 to Input Voltage
Constant Torque FLA [A] 61 75 91 110 152
3) Control Method Space Vector PWM
Constant Torque [kVA]* 40 50 60 70 100
Output ratings Frequency Setting Resolution Digital Reference: 0.01 Hz (Below 100Hz), 0.1 Hz (Over 100Hz)
Variable Torque FLA [A] 80 96 115 125 160
3)
Variable Torque [kVA]* 52 62 74 80 103 Analog Reference: 0.03 Hz / 60Hz
Voltage 3phase, 380 to 400V( 10%) Frequency Accuracy Digital: 0.01% of Maximum Output Frequency
Input ratings
Frequency 50 to 60Hz( 5%) Analog: 0.1% of Maximum Output Frequency
Control
Weight[kg(lbs)] 45(99) 45(99) 63(139) 63(139) 68(150) V/F Ratio Linear, Non-Linear, User Programmable
Braking Torque (w/o DB) About 20%
Overload Capacity CT 150% of Rated Current for 1 Minute, 200% for 0.5 Second
Type SV090iH-4 SV110iH-4 SV132iH-4 SV160iH-4 SV220iH-4
Overload Capacity VT 110% of Rated Current for 1 Minute, 150% for 0.5 Second
Constant Torque [HP] 125 150 175 215 300
Torque Boost Manual Torque Boost (0 to 20%), Auto Torque Boost
1) Constant Torque [kW] 90 110 132 160 220
Motor Rating* Operation Method Keypad / Terminal / Remote (Optional)
Variable Torque [HP] 150 175 215 250 350
Variable Torque [kW] 110 132 160 185 280 Frequency Setting Analog: 0 to 10 V / 4 to 20mA, Digital: Keypad
Constant Torque FLA [A] 183 223 264 325 432 Accel / Decel Time 0.1 to 6,000 sec, 8 Pre-Defined (Programmable)
Constant Torque [kVA]*3) 120 145 170 200 280 Multi-Step 8 Preset Operational Speed
Output ratings
Variable Torque FLA [A] 228 264 330 361 477 Operating Jog Jog Operation
Variable Torque [kVA]*3) 147 170 213 233 307 Operating Function DC Braking, Frequency Limit, Frequency Jump, Slip Compensation, PI Control, Stall Prevention
Voltage 3phase, 380 to 400V( 10%) Operating Status Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Under Voltage,
Input ratings
Frequency 50 to 60Hz( 5%)
Drive Overheat, Run, Stop, Constant Speed, Speed Searching
Weight[kg(lbs)] 98(216) 98(216) 122(269) 122(269) 175(386)
Start Signal Forward, Reverse
Programmable Input 6 Programmable Inputs
Programmable Output 5 Programmable Outputs: 2 Form A Contact (N.O.)
Fault Contact Output (A, C, B) - 250VAC 1A, 30VDC 1A
Programmable I/O
3 Open Collector Outputs: 24V, 50mA
05 06
Starvert iH Keypad & Procedure of Setting Data
RESET The Reset Button is used to reset faults. DRV Manual K/K
STOP Press UP key 5 time.
00 REV 30.50Hz
The Reverse Run Button blinks when
REV
the reverse drive accels or decels.
DRV Manual K/K Press SHIFT key once to shift the cursor to next digit.
00 REV 30.50Hz
Drive Group DRV Command frequency, Accel/Decel time Etc. Basic parameters
Function Group FUN Maximum frequency, amount of torque boost etc. Basic Related Parameters
DRV Manual K/K
Press SHIFT key once to shift the cursor to next digit.
Input/Output Group I/O Multi-Function terminal settings. Parameters needed for sequence operation 00 REV 35.50Hz
Operation method
Operation Method Function Function Setting
DRV Manual K/K
Operation using keypad Run/Stop command and frequency are set only through the keypad. FUN 01: Key ENTER Press ENTER key to store new value.
00 REV 45.50Hz
FUN 02: Key
Operation using Control Terminals Closing FX or RX terminal performs Run/Stop. FUN 01: Terminal
Option Operation using RS485 communication between drive and computer. FUN 01: Remote
Operation using ModBus RTU communication between drive and PLC. FUN 01: Remote
Operation using FNet communication between drive and computer. FUN 01: Remote
09 10
Starvert iH Keypad & Procedure of Setting Data
RESET The Reset Button is used to reset faults. DRV Manual K/K
STOP Press UP key 5 time.
00 REV 30.50Hz
The Reverse Run Button blinks when
REV
the reverse drive accels or decels.
DRV Manual K/K Press SHIFT key once to shift the cursor to next digit.
00 REV 30.50Hz
Drive Group DRV Command frequency, Accel/Decel time Etc. Basic parameters
Function Group FUN Maximum frequency, amount of torque boost etc. Basic Related Parameters
DRV Manual K/K
Press SHIFT key once to shift the cursor to next digit.
Input/Output Group I/O Multi-Function terminal settings. Parameters needed for sequence operation 00 REV 35.50Hz
Operation method
Operation Method Function Function Setting
DRV Manual K/K
Operation using keypad Run/Stop command and frequency are set only through the keypad. FUN 01: Key ENTER Press ENTER key to store new value.
00 REV 45.50Hz
FUN 02: Key
Operation using Control Terminals Closing FX or RX terminal performs Run/Stop. FUN 01: Terminal
Option Operation using RS485 communication between drive and computer. FUN 01: Remote
Operation using ModBus RTU communication between drive and PLC. FUN 01: Remote
Operation using FNet communication between drive and computer. FUN 01: Remote
09 10
Starvert iH Program Parameter descriptions
00 Output Frequency(During Run)or Cmd. Freq 0 to FUN04 0.01 0.00 [Hz] Yes
MODE Reference Frequency(During Stop)
01 Acceleration Time Acc.time 0 to 6000 [sec] 0.1 30.0 [sec] Yes
02 Deceleration Time Dec. time 0 to 6000 [sec] 0.1 60.0 [sec] Yes
03 Output Current Current The load current in RMS - - [A] -
DRV Manual K/K MODE
FUN Jump code MODE
I/O Jump code 04 Output Speed Speed The motor speed in RPM - - [rpm] -
00 FWD 60.00Hz 00 41 00 1 05 Output Power Display Power Inverter Output Power - -[kW] -
06 Fault Display Fault - - - -
2. Function Group
MODE MODE MODE
Factory Adjustable
Code [FUN] Description of Function Group Keypad Display Setting Range Units
Default during run
DRV Acc. time FUN Freq. set I/O P1 input
00 Jump Code
01 30.0sec 01 Key 01 SPD_L Jump to Desired Code # 1 to 98 1 41 Yes
01 Frequency Setting Mode Freq.set Key,Terminal, Remote - Key No
02 Run / Stop Mode Selection Run/Stop set Key, Terminal-1,Terminal-2, Remote - Key No
03 Run Prevention Run prohibit None, FWD disable, REV disable - None No
04 Maximum Frequency Output Set Point Freq.max 40 to 400 [Hz] 0.01 60 [Hz] No
MODE MODE MODE 05 Base Frequency Freq.base 40 to FUN 04 0.01 60 [Hz] No
06 Starting Frequency Freq.start 0.5 to 5[Hz] 0.01 0.5 [Hz] No
DRV Dec. time FUN Run/stop set I/O P2 input 07 Starting Frequency Hold Time Hold time 0 to 10 [sec] 0.1 0.0 [sec] Yes
02 60.0sec 02 Key 02 SPD_M 08 Volts / Hz Pattern V/F pattern Linear, 2.0(Squared), User, Auto - Linear No
09 Torque Boost in Forward Direction Fwd boost 0 to 20 [%] 1 2 [%] Yes
10 Torque Boost in Reverse Direction Rev boost 0 to 20 [%] 1 2 [%] Yes
11 Acceleration Pattern Acc. pattern Linear, S-curve,U-curve - Linear No
12 Deceleration Pattern Dec. pattern Linear, S-curve,U-curve - Linear No
MODE MODE MODE 13 Output Voltage Adjustment Volt control 40 to 110 [%] 1 100 [%] No
14 Energy Savings Level Energy save 30 to 100 [%] 1 100 [%] Yes
DRV Current FUN Run prohibit I/O P3 input 15 Stop Mode Selection Stop mode Decel, DCBR, Free Run - Decel No
03 x.x A 03 None 03 SPD_H 16 User V/F - Frequency 1 User-1f 0 to 30 [Hz] 0.01 10.00 [%] No
17 User V/F - Voltage 1 User-1v 0 to 50 [%] 1 15 [%] No
18 User V/F - Frequency 2 User-2f FUN 16 to FUN 04 1 30.00 [%] No
19 User V/F - Voltage 2 User-2v FUN 17 to 100 [%] 1 50 [%] No
20 Analog Speed Input Selection V-I mode V1, I, V1+I, V2 - V1 No
MODE MODE MODE 21 Analog Speed Input Filter Gain Filter gain 1 to 100 [%] 1 25 [%] Yes
22 Analog Speed Input Gain Analog gain 50 to 250 [%] 1 100 [%] Yes
DRV Speed FUN Freq. max I/O P4 input 23 Analog Speed Input Bias Analog bias 0 to 200 [%] 1 0 [%] Yes
04 xxxrpm 04 60.00Hz 04 ACCT_L 24 Analog Speed Input Direction Analog dir Direct, Invert - Direct Yes
25 Frequency Limit Selection Freq. limit No, Yes - No No
26 Frequency High Limit Selection F-limit high 0 to FUN 04 0.01 60.00 [Hz] No
27 Frequency Low Limit Selection F-limit low 0 to FUN26 0.01 0.00 [Hz] No
28 Jump Frequency Selection Freq. jump No, Yes - No No
MODE MODE MODE
29 Jump Frequency 1 Freq. jump 1f 0 to FUN 04 0.01 10.00 [Hz] No
30 Jump Frequency 2 Freq. jump 2f 0 to FUN 04 0.01 20.00 [Hz] No
DRV Power FUN Freq. base I/O P5 input 31 Jump Frequency 3 Freq. jump 3f 0 to FUN 04 0.01 30.00 [Hz] No
05 57.5kW 05 60.00 Hz 05 ACCT_M 32 Jump Frequency Bandwidth Freq. band 0 to 30 [Hz] 0.01 5.00 [Hz] No
33 DC Injection Braking Frequency DC-br freq 0 to 60 [Hz] 0.01 0.5 [Hz] Yes
. . 34 DC Injection Braking On-Delay Time DC-br block 0.5 to 5[sec] 0.1 2 [sec] Yes
. . 35 DC Injection Braking Time DC-br time 0.1 to 25.0 [sec] 0.1 0.5 [sec] Yes
. . 36 DC Injection Braking Voltage DC-br value 1 to 20 [%] 1 1 [%] Yes
MODE . . 37 Slip Compensation Slip compen. No, Yes - No Yes
38 Rated Motor Slip Rated slip 0 to 5 [Hz] 0.01 0.00 [Hz] Yes
DRV Fault 39 Rated Motor Current (in RMS) M-rated cur. 0.1 to 999[A] 0.1 103.0 [A]*
9)
Yes
06 No fault 40 No Load Motor Current in RMS No-load cur. 0.1 to 300 [A] 0.1 0.1 [A] Yes
10)
MODE MODE
41 Inverter Capacity Inv Capacity SV030iH-2 - SV030iH-2* No
SV037iH-2
FUN Para. lock I/O FN:St.ID ......
98 0 61 1 SV220iH-4
42 Number of Auto Restart Retry number 0 to 10 1 0 Yes
43 Delay Time Before Auto Restart Retry time 0 to 10 [sec] 0.1 1.0[sec] Yes
44 Fault Output Relay(A, B, C) Relay mode Retry0, All Trips, - Retry 0 Yes
LV+Retry0, LV+All Trips
11 12
Starvert iH Program Parameter descriptions
00 Output Frequency(During Run)or Cmd. Freq 0 to FUN04 0.01 0.00 [Hz] Yes
MODE Reference Frequency(During Stop)
01 Acceleration Time Acc.time 0 to 6000 [sec] 0.1 30.0 [sec] Yes
02 Deceleration Time Dec. time 0 to 6000 [sec] 0.1 60.0 [sec] Yes
03 Output Current Current The load current in RMS - - [A] -
DRV Manual K/K MODE
FUN Jump code MODE
I/O Jump code 04 Output Speed Speed The motor speed in RPM - - [rpm] -
00 FWD 60.00Hz 00 41 00 1 05 Output Power Display Power Inverter Output Power - -[kW] -
06 Fault Display Fault - - - -
2. Function Group
MODE MODE MODE
Factory Adjustable
Code [FUN] Description of Function Group Keypad Display Setting Range Units
Default during run
DRV Acc. time FUN Freq. set I/O P1 input
00 Jump Code
01 30.0sec 01 Key 01 SPD_L Jump to Desired Code # 1 to 98 1 41 Yes
01 Frequency Setting Mode Freq.set Key,Terminal, Remote - Key No
02 Run / Stop Mode Selection Run/Stop set Key, Terminal-1,Terminal-2, Remote - Key No
03 Run Prevention Run prohibit None, FWD disable, REV disable - None No
04 Maximum Frequency Output Set Point Freq.max 40 to 400 [Hz] 0.01 60 [Hz] No
MODE MODE MODE 05 Base Frequency Freq.base 40 to FUN 04 0.01 60 [Hz] No
06 Starting Frequency Freq.start 0.5 to 5[Hz] 0.01 0.5 [Hz] No
DRV Dec. time FUN Run/stop set I/O P2 input 07 Starting Frequency Hold Time Hold time 0 to 10 [sec] 0.1 0.0 [sec] Yes
02 60.0sec 02 Key 02 SPD_M 08 Volts / Hz Pattern V/F pattern Linear, 2.0(Squared), User, Auto - Linear No
09 Torque Boost in Forward Direction Fwd boost 0 to 20 [%] 1 2 [%] Yes
10 Torque Boost in Reverse Direction Rev boost 0 to 20 [%] 1 2 [%] Yes
11 Acceleration Pattern Acc. pattern Linear, S-curve,U-curve - Linear No
12 Deceleration Pattern Dec. pattern Linear, S-curve,U-curve - Linear No
MODE MODE MODE 13 Output Voltage Adjustment Volt control 40 to 110 [%] 1 100 [%] No
14 Energy Savings Level Energy save 30 to 100 [%] 1 100 [%] Yes
DRV Current FUN Run prohibit I/O P3 input 15 Stop Mode Selection Stop mode Decel, DCBR, Free Run - Decel No
03 x.x A 03 None 03 SPD_H 16 User V/F - Frequency 1 User-1f 0 to 30 [Hz] 0.01 10.00 [%] No
17 User V/F - Voltage 1 User-1v 0 to 50 [%] 1 15 [%] No
18 User V/F - Frequency 2 User-2f FUN 16 to FUN 04 1 30.00 [%] No
19 User V/F - Voltage 2 User-2v FUN 17 to 100 [%] 1 50 [%] No
20 Analog Speed Input Selection V-I mode V1, I, V1+I, V2 - V1 No
MODE MODE MODE 21 Analog Speed Input Filter Gain Filter gain 1 to 100 [%] 1 25 [%] Yes
22 Analog Speed Input Gain Analog gain 50 to 250 [%] 1 100 [%] Yes
DRV Speed FUN Freq. max I/O P4 input 23 Analog Speed Input Bias Analog bias 0 to 200 [%] 1 0 [%] Yes
04 xxxrpm 04 60.00Hz 04 ACCT_L 24 Analog Speed Input Direction Analog dir Direct, Invert - Direct Yes
25 Frequency Limit Selection Freq. limit No, Yes - No No
26 Frequency High Limit Selection F-limit high 0 to FUN 04 0.01 60.00 [Hz] No
27 Frequency Low Limit Selection F-limit low 0 to FUN26 0.01 0.00 [Hz] No
28 Jump Frequency Selection Freq. jump No, Yes - No No
MODE MODE MODE
29 Jump Frequency 1 Freq. jump 1f 0 to FUN 04 0.01 10.00 [Hz] No
30 Jump Frequency 2 Freq. jump 2f 0 to FUN 04 0.01 20.00 [Hz] No
DRV Power FUN Freq. base I/O P5 input 31 Jump Frequency 3 Freq. jump 3f 0 to FUN 04 0.01 30.00 [Hz] No
05 57.5kW 05 60.00 Hz 05 ACCT_M 32 Jump Frequency Bandwidth Freq. band 0 to 30 [Hz] 0.01 5.00 [Hz] No
33 DC Injection Braking Frequency DC-br freq 0 to 60 [Hz] 0.01 0.5 [Hz] Yes
. . 34 DC Injection Braking On-Delay Time DC-br block 0.5 to 5[sec] 0.1 2 [sec] Yes
. . 35 DC Injection Braking Time DC-br time 0.1 to 25.0 [sec] 0.1 0.5 [sec] Yes
. . 36 DC Injection Braking Voltage DC-br value 1 to 20 [%] 1 1 [%] Yes
MODE . . 37 Slip Compensation Slip compen. No, Yes - No Yes
38 Rated Motor Slip Rated slip 0 to 5 [Hz] 0.01 0.00 [Hz] Yes
DRV Fault 39 Rated Motor Current (in RMS) M-rated cur. 0.1 to 999[A] 0.1 103.0 [A]*
9)
Yes
06 No fault 40 No Load Motor Current in RMS No-load cur. 0.1 to 300 [A] 0.1 0.1 [A] Yes
10)
MODE MODE
41 Inverter Capacity Inv Capacity SV030iH-2 - SV030iH-2* No
SV037iH-2
FUN Para. lock I/O FN:St.ID ......
98 0 61 1 SV220iH-4
42 Number of Auto Restart Retry number 0 to 10 1 0 Yes
43 Delay Time Before Auto Restart Retry time 0 to 10 [sec] 0.1 1.0[sec] Yes
44 Fault Output Relay(A, B, C) Relay mode Retry0, All Trips, - Retry 0 Yes
LV+Retry0, LV+All Trips
11 12
Starvert iH Program Parameter descriptions
W3
W2 D2
W1 D1
RS-485 / Modbus-RTU
Category Item Specifications
Performance Communication method RS485
Transmission form Multi-drop Link System
Applicable type iH series
Computer PC or FA computer (needs RS232-485 converter)
Number of drives Maximum 32 drives connectable
Transmission distance Max. 1200m
Hardware Installation On control PCB inside the drives
Power Supply Control 5V DC from drive main PCB
Communication 5V DC. Max.100mA (contained in Communication card)
Communication Communication speed 19200/9600/4800/2400/1200 bps selectable
Control procedure Asynchronous communication system
Communication system Half duplex system
Character system RS485 : ASCII (8 bit) / ModBus-RTU : Binary
Stop bit length 1 bit
(unit : mm) Sum check 2 bytes
Parity check None
Class Type W1 W2 W3 H1 H2 D1 D2
SV030iH-2 375 360 275 615 593.5 277.5 230.5
SV037iH-2 375 360 275 615 593.5 277.5 230.5
200-230V
SV045iH-2 375 360 275 780 758.5 300.7 230.5
SV055iH-2 375 360 275 780 758.5 300.7 230.5 F-net
SV030iH-4 350 319.2 270 680 662 308.2 256.6
SV037iH-4 350 319.2 270 680 662 308.2 256.6 Item Specifications
Communication speed 1M bps
SV045iH-4 375 359.6 275 780 760.5 326 259
Communication type Manchester Biphase-L, Frame Synchronous type
SV055iH-4 375 359.6 275 780 760.5 326 259
Cable Twisted Pair Shielded Cable
SV075iH-4 375 359.6 275 780 760.5 326 259 Name : LIREC-AMESB 1ø(PC 717 6705)
SV090iH-4 530 507 430 780 762 335 286.2 Manufacturer : LG Cable
SV110iH-4 530 507 430 790 762 335 286.2 No. of node Max. 64 per line
380-460V
Distance Max. 750m
SV132iH-4 530 507 430 1000 982 345 298
Frame Format FieldBus (IEC TC65/SC65C/WG6 65C 90.8)
SV160iH-4 530 507 430 1000 982 345 298
SV220iH-4 680 649 540 998 968.5 403 343
15 16
Starvert iH Dimension & Braking unit
W3
W2 D2
W1 D1
RS-485 / Modbus-RTU
Category Item Specifications
Performance Communication method RS485
Transmission form Multi-drop Link System
Applicable type iH series
Computer PC or FA computer (needs RS232-485 converter)
Number of drives Maximum 32 drives connectable
Transmission distance Max. 1200m
Hardware Installation On control PCB inside the drives
Power Supply Control 5V DC from drive main PCB
Communication 5V DC. Max.100mA (contained in Communication card)
Communication Communication speed 19200/9600/4800/2400/1200 bps selectable
Control procedure Asynchronous communication system
Communication system Half duplex system
Character system RS485 : ASCII (8 bit) / ModBus-RTU : Binary
Stop bit length 1 bit
(unit : mm) Sum check 2 bytes
Parity check None
Class Type W1 W2 W3 H1 H2 D1 D2
SV030iH-2 375 360 275 615 593.5 277.5 230.5
SV037iH-2 375 360 275 615 593.5 277.5 230.5
200-230V
SV045iH-2 375 360 275 780 758.5 300.7 230.5
SV055iH-2 375 360 275 780 758.5 300.7 230.5 F-net
SV030iH-4 350 319.2 270 680 662 308.2 256.6
SV037iH-4 350 319.2 270 680 662 308.2 256.6 Item Specifications
Communication speed 1M bps
SV045iH-4 375 359.6 275 780 760.5 326 259
Communication type Manchester Biphase-L, Frame Synchronous type
SV055iH-4 375 359.6 275 780 760.5 326 259
Cable Twisted Pair Shielded Cable
SV075iH-4 375 359.6 275 780 760.5 326 259 Name : LIREC-AMESB 1ø(PC 717 6705)
SV090iH-4 530 507 430 780 762 335 286.2 Manufacturer : LG Cable
SV110iH-4 530 507 430 790 762 335 286.2 No. of node Max. 64 per line
380-460V
Distance Max. 750m
SV132iH-4 530 507 430 1000 982 345 298
Frame Format FieldBus (IEC TC65/SC65C/WG6 65C 90.8)
SV160iH-4 530 507 430 1000 982 345 298
SV220iH-4 680 649 540 998 968.5 403 343
15 16
Starvert iH Driveview 2.0 & RFI Filter
H
H
Y
CARGA
X
RED
W
W X
L
L
Peripheral devices
Type kW Breaker Magnetic contactor
Power Earth Line
DC reactor AC reactor Fuse FS Series (output chokes)
terminal wire(mm2) (mm2)
17 18
Starvert iH Driveview 2.0 & RFI Filter
H
H
Y
CARGA
X
RED
W
W X
L
L
Peripheral devices
Type kW Breaker Magnetic contactor
Power Earth Line
DC reactor AC reactor Fuse FS Series (output chokes)
terminal wire(mm2) (mm2)
17 18
Leader in Electrics & Automation
Starvert iH
30 - 55kW(40 -75HP) 3 phase 200 - 230Volts
Leader in Electrics & Automation 30 - 220kW(40 - 300HP) 3 phase 380 - 400Volts, 440 - 460Volts
• For your safety, please read user's manual thoroughly before operating.
• Contact the nearest authorized service facility for examination, repair, or adjustment.
• Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions • Any maintenance and inspection shall be performed by the personnel having expertise concerned.