Chapter 1 Safety and Precautions
If the external voltage for the ME series 1.2.13 About supporting motor
inverter is not within the operating voltage The ME series elevator-specific inverter
range specified in this manual, the devices adopts four-pole squirrel-cage asynchronous
inside the inverter will be damaged. When induction motor as standard, the IP series
necessary, use the corresponding adopts permanent magnetic synchronous
step-up/step-down instrument to change the motor. Please ensure that the rated
voltage. current of the motor is within the range of the
1.2.8 Three-phase input changed to inverter when selecting the motor.
two-phase input The cooling fan and the rotor shaft of the
It is not allowed to use the ME series non-variable-frequency motor adopt coaxial
three-phase inverter under two-phase input. connection. When the rotating speed is
Otherwise, failure may be caused, or the reduced, the cooling effect will also be
inverter may be damaged. reduced. Therefore, forced cooling fan shall
1.2.9 Surge protection be installed, or the motor shall be replaced
The series inverter has surge protection with variable-frequency motor to avoid the
device, and has certain self-protection over-temperature of the motor.
capacity against the lightning. For the place If the asynchronous motor inverter has been
with frequent lightning, the user also needs set with motor parameter, it is necessary to
to install protection device at the front-end of identify or modify the default value according
the inverter. to the actual situation, otherwise, the running
1.2.10 Altitude and derating effect and protection performance may be
At the place with the altitude higher than affected. Dynamic parameter identification
1000 meters, since the heatsink efficiency must be conducted for the permanent
will be reduced because of the tenuous air, it magnetic synchronous motor.
is not necessary for derating. For this case, The short circuit of the cable or motor may
please contact our company for technical cause alarm or explosion of the inverter.
consultation. Therefore, please conduct insulation and
1.2.11 Some special use short circuit test on the newly installed motor
If the user needs to use the inverter with the and cable. Such test shall also be conducted
method other than the recommended wiring during routine maintenance. Please note
diagram in this manual, please consult our that the inverter and the test part shall be
company. completely disconnected during the test.
1.2.12 Matters for attention upon inverter
disposal
The electrolytic capacitors on the main
circuit and the PCB may explode when they
are burnt. Toxic gas will be given out when
burning the plastic parts. Please dispose of
the inverter as industrial waste.
4
Chapter 2 Product Information
ME320L - 4011 - IP
ME series Elevator-specific inverter Three-phase 400V Synchronous motor
motor power
Mark
Applicable
motor
2.2 Nameplate
Nameplate of the ME320L inverter applicable to asynchronous motor:
-5-
Chapter 2 Product Information
Power
Output Supporting
Inverter supply Input current
Input voltage current motor
model capacity (A)
(A) (KW)
(KVA)
ME320L-4002 4.0 5.8 5.1 2.2
ME320L-4003 5.9 10.5 9.0 3.7
ME320L-4005 8.9 14.6 13.0 5.5
ME320L-4007 11.0 20.5 18.0 7.5
Three-phase
ME320L-4011 17.0 29.0 27.0 11
380V
ME320L-4015 21.0 36.0 33.0 15
Range:
ME320L-4018 24.0 41.0 39.0 18.5
-15%~20%
ME320L-4022 30.0 49.5 48.0 22
ME320L-4030 40.0 62.0 60.0 30
ME320L-4037 57.0 77.0 75.0 37
ME320L-4045 69.0 93.0 91.0 45
2.4 Technical specification
Item Specification
Basic specification
carrier wave 0.5K~16K(Hz), the carrier wave frequency will be automatically adjusted
frequency according to the load characteristics
Control mode Open loop vector control (SVC) /closed loop vector control(VC) /VF
control
Overload capacity 150% rated current: 60 seconds; 180% rated current: 1 second
-6-
Chapter 2 Product Information
Item Specification
Auto voltage Even when the mains voltage changes, constant output voltage can be
regulation (AVR) maintained automatically.
display and operation
parameter copy Quick parameter copy can be realized through LCD operation panel
Key locking and Parts or all of the keys can be locked, and the functional range of the keys
function selection can be defined to prevent mistaken operation
Speed deviation With built-in speed deviation judgment function, able to detect the
judgment incipient fault of the elevator
Forced throw-over With forced throw-over detection function, able to effectively prevent the
function elevator from bumping at the top or bottom due to overspeed
-7-
Chapter 2 Product Information
Item Specification
Motor temperature Able to judge the motor temperature in time, eliminating the incipient fault
detection
running command Three channels: Operation panel reference, control terminal reference,
Input and output characteristics
10-way digital input terminal, with 1 way used as high-speed pulse input,
compatible with active PNP or NPN input mode
Input terminal
3-way analog input terminal, with 1 way used only as voltage input,
another way used as voltage or current input
2
Vibration less than 5.9m/s (0.6g)
-8-
Chapter 2 Product Information
Operation panel
Upper cover
Lower cover
Barcode
information
Input/output port
Bottom
mounting hole
Fan
Inverter
nameplate
B
H
A
D
Fig. 2-2 Schematic Diagram of Inverter Outline Dimensions and Mounting Dimensions
-9-
Chapter 2 Product Information
- 10 -
Chapter 2 Product Information
Note
The filter capacitor still has high voltage after the power supply is disconnected. Do not repair or
maintain the inverter immediately after the power supply is disconnected. The repair or
maintenance can be conducted only after the charge LED is off and the bus voltage measured
with multimeter is less than 36V.
1. Items for daily inspection:
1) whether there is any abnormal change in the running sound of the motor
2) whether the motor has vibration during the running
3) whether there is any change to the installation environment of the inverter
4) whether the inverter heatsink fan works normally
5) whether the inverter has over temperature
2. Daily cleaning:
1) the inverter shall be kept clean.
2) the dust on the surface of the inverter shall be effectively removed, so as to prevent the dust
falling into the inverter, especially the metal dust.
3) the oil stain on the inverter heatsink fan shall be effectively removed.
2.7.2 Periodical inspection
The places hard to be inspected during the operation of the inverter shall be inspected
periodically.
1. Items for periodical inspection:
1) Check and clean the duct periodically
2) check if the screws are loosened
3) check if the inverter is corroded
4) check if the wire connector has arc signs
- 11 -
Chapter 2 Product Information
above units, external braking units and braking resistors are needed.
Specification of braking Supporting motor
Inverter model Braking unit
resistor (KW)
ME320L-4002(-IP) 660W, 220 Ω
ME320L-4003(-IP) 1100W, 130 Ω
ME320L-4005(-IP) 1600W, 90 Ω
ME320L-4007(-IP) 2500W, 65 Ω
Built-in as
ME320L-4011(-IP) 3500W, 43 Ω
standard No special
ME320L-4015(-IP) 4500W, 32 Ω
specification
ME320L-4018(-IP) 5500W, 25Ω
ME320L-4022(-IP) 6500W, 22Ω
ME320L-4030(-IP) 9000W, 16Ω
ME320L-4037(-IP) 11000W, 13Ω
external
ME320L-4045(-IP) 13500W, 10Ω
- 13 -
Chapter 3 Installation and Wiring of Inverter
- 14 -
Chapter 3 Installation and Wiring of Inverter
Heatsink shall be taken into account during the installation. The following items shall be paid
attention to:
1) Install the inverter vertically so that the heat may be expelled from the top.However, the
equipment cannot be installed upside down.
2) The mounting space shall be as indicated as the above figure, so as to ensure the heatsink
space of the inverter. However, the heatsink of other devices in the carriageet shall also be
considered.
3) The installation bracket must be flame retardant.
4) If the inverter is installed in the area with metal powder, the space inside the sealed
carriageet shall be big enough for heatsink.
3.1.3 Panel disassembly and installation
1. The 15KW below ME series inverters adopt plastic enclosure. The disassembly and
installation method for the lower cover of the plastic enclosure is as shown in Fig.3-2.
1) Disassembly: Push out inboard the hook bayonets at the two sides of the upper cover with
tools.
2) Installation: Place the upper bayonet of the upper cover into the hole of the lower upper
and press down until the “click” sound is heard.
Do not disassemble the plastic enclosure body. Please contact our company for repair.
Upper
cover
Hook
Hook
groove
Fig.3-2 Disassembly and installation of the lower cover of the plastic enclosure
2. The 18.5KW above ME series inverters adopt sheet-metal enclosures. The disassembly
procedures for the upper cover of the sheet-metal enclosure are as follows:
1) Loosen the screws of the upper cover with tools.
2) Gently lift the upper cover.
3) Draw out the cover backward gently.
The installation procedures of the upper cover are the reverse of the above procedures.
Note: When disassembling the upper cover, avoid the falling of the upper cover, which may
cause human injury or damage to the equipment.
- 15 -
Chapter 3 Installation and Wiring of Inverter
- 16 -
Chapter 3 Installation and Wiring of Inverter
reactor inverter adopts 2) effectively reduce the influence of higher harmonic at the
7.5~45KW DC input side on the inverter and provide effective protection to
reactor as the whole bridge;
standard 3) eliminate the input current unbalancedness caused by the
unbalanced power phases to certain degree. However, it is
not so effective as the AC input reactor.
The DC reactor has small size and will not cause voltage
drop in the circuit. It is recommended to use the DC reactor.
The DC reactor is the standard configuration of our company.
The inverter output side generally has higher
harmonic.When the motor is far from the inverter, since there
are many capacitors in the circuit, the harmonic will cause
Between the
resonance in the circuit and bring in the following results:
inverter output
AC output 1) degrade the motor insulation performance and damage
side and the
reactor the motor for the long run
motor, close to
2) generate large leakage current and cause frequent
the inverter
inverter protection action
In general, if the distance between the inverter and the motor
exceeds 100 meters, output AC reactor shall be installed.
3.2.3 Electric wiring
Danger
The wiring operation shall be carried out only when the power supply switch is in OFF
position. Otherwise, electric shock may be caused!
The wiring operation shall be carried out only by the trained professionals, Otherwise,
equipment damage and human injury may be caused.
The grounding must be reliable, otherwise electric shock or fire may be caused.
The DC bus terminals shall not connected to the braking resistors, otherwise, severe accident
may be caused.
Danger
The input power supply for the inverter and the power provided shall be consistent. otherwise,
the inverter may be damaged.
The motors connected shall match the inverter. Otherwise, the motor may be damaged or
inverter protection may be caused.
Do not connect the power supply to the U, V, W terminals. otherwise, the inverter may be
damaged.
1. Wiring mode (including IP type)
- 17 -
Chapter 3 Installation and Wiring of Inverter
Braking resistor
(-) P(+) PB
R U
S V M
T ME320L W
series control
+24V PE
board wiring Grounding
- 18 -
Chapter 3 Installation and Wiring of Inverter
DO
+10V
Analog Digital output
input AI3
terminal CME
DC
0~10V/
4~20mA T/A
GND
T/B Relay output
T/C
PE
Fig.3-4 Wiring of the I/O expansion board for ME320L series2. Main circuit terminals and
wiring
1) Function description of main circuit terminals
Terminals Name Description
R, S, T Three-phase power Power input terminal for three-phase 380V inverter
input terminal
(+), (-) Negative and The common DC bus input point; the connecting
positive terminals terminal for external braking unit of 37KW above
of DC bus inverter
P(+), PB Connecting connecting terminal of braking resistor for 30KW
terminal of braking and below inverters
resistor
U, V, W Output terminal of To connect to the three-phase motor
inverter
PE Grounding terminal Grounding terminal
2) Notes on Wiring:
A. DC bus (+) and(-) terminals:
The DC bus (+) and(-) terminals still have residual voltage at the time of power-off. Do not
touch the equipment until the charge LED is off and the voltage measured with multimeter is
less than 36V.
To release the energy fed back during the brake operation, external braking unit shall be
- 19 -
Chapter 3 Installation and Wiring of Inverter
connected to the DC bus (+) and(-) terminals for the ME320L inverter whose power is more
than 37KW, and the P and PB terminals of the braking unit shall be connected with braking
resistor. Please note that the connecting polarity must be correct, otherwise, the inverter may
be damaged, and fire may be caused. The wire length between the braking unit and the DC bus
terminals (+) and(-) shall not exceed 5 meters, and the wire length between the braking unit
and braking resistor shall not exceed 10 meters. Twisted wires or pair wires shall be used and
connected in parallel.
Do not connect the braking resistor directly to the DC bus, otherwise, the inverter may be
damaged, and fire may be caused.
B. Braking resistor terminals (+), PB:
The 30KW below ME320L inverters have built-in braking unit. To release the energy fed bank
during the braking operation, the (+), PB terminals must be connected to braking resistors.
For the lectotype of the braking resistor, please refer to the recommended value in braking
resistor lectotype table in chapter 2.
The wire length of the braking resistor shall be less than 5 meters.
The temperature of the braking resistor will increase because of the release of energy.
Relevant protection and heatsink shall be provided.
C. Inverter output side U, V, W:
The inverter output side is connected to the three-phase motor. When the rotation direction of
the motor is different from the actual requirement, the connection any two pieces of the U, V
and W wires can be exchanged to change the rotation direction of the motor.
The inverter output side cannot connect to the capacitor or surge absorber, otherwise, frequent
inverter protection may be caused, or the inverter may be damaged.
It is prohibited to short circuit or ground the output side.
The inverter output wires of U, V, W shall penetrate into the grounding metal pipe and laid out
separate from or vertical to the control circuit signal line.
If the wire between the motor and the inverter is too long, because of the influence of the
distribution capacitor, the high-frequency current of the circuit may cause resonance, which
may damage the motor insulation or produce large leakage current to trigger inverter
overcurrent protection. In general, the length shall be no more than 100 meters. When the
distance is longer than 100 meters, AC output reactor shall be installed.
D. Grounding terminal:
The grounding terminal of the inverter must be well grounded. The grounding wire shall be wide
and short. It is recommended to use the yellow green 4mm2 above stranded copper core
grounding wire, and ensure that the grounding resistance is no more than 5Ω. The grounding
terminal must be exclusively used for grounding. It is not allowed to share the grounding
terminal and the zero line of the power supply.
3. Control terminals and wires
1) The main control panel terminal layout is as shown in the following diagram:
- 20 -
Chapter 3 Installation and Wiring of Inverter
GND GND AO1 CME COM D01 FM +24V OP T/A T/B T/C
- 21 -
Chapter 3 Installation and Wiring of Inverter
- 22 -
Chapter 3 Installation and Wiring of Inverter
- 23 -
Chapter 3 Installation and Wiring of Inverter
Terminal
Type Terminal Function description
name
Optical coupling isolation, dual polarity open
collector output
Output voltage range: 0~24V
Output current range: 0~50mA
Digital Digital output Note: The digital output grounding CME and
DO2-CME
output 2 digital input grounding COM are internally
isolated. The users must connected them
externally. When DO2 needs to be driven by the
external power, the connection between CME
and COM must be disconnected.
normally
T/A-T/B closed
Contact driving capacity:
Relay terminal
AC250V, 3A, COSφ=0.4
output normally
DC 30V, 1A
T/A-T/C open
terminal
Communi Communicat The input/output signal terminal for RS-485
CNK2
cation ion terminal communication
Control
Auxiliary 28-core terminal, connecting to control panel of
JK1 panel
interface ME320L series inverter
interface
5) Wiring of control terminal:
A. digital input terminals:
Shielded wire or twisted wire shall be used for wiring (please refer to 3.2.1 wiring of peripheral
electric devices). The wiring distance shall be as short as possible, and less than 20 meters. If
shielded wire is used, the shielding layer shall be connect to the PE terminal at the location
close to the inverter side.
When active driving is adopted, necessary filtering measures shall be taken to prevent the
interference to the power supply. It is recommended to use the contact control mode.
The ME320L series elevator has 10 digital input terminals, which is divided into two groups: 5
for main control board, and the other 5 for expansion board. The two groups can adopt external
power supply, internal 24V supply, high input level action, low input level action separately or
simultaneously. Such flexible combinations make it convenient for the user to use the
equipment. For any doubts, please consult the manufacturer.
B. digital output terminals:
DO1 and DO2 can adopt external or internal power supply, and the output mode can be set as
NPN or PNP.
- 24 -
Chapter 3 Installation and Wiring of Inverter
when the digital output terminal needs the drive relay, absorption diode shall be installed at the
two sides of the relay coil. Otherwise, DC 24V power supply or output circuit may be damaged.
Note: The absorption diode shall be installed with correct polarity, as shown in the following
figure. Otherwise, there the digital output terminal has output, the DC 24V power supply and
output circuit will be damaged immediately.
R
P24
Relay diode
DO1
CME
Fig. 3-8 Wiring diagram of analog input terminal Fig.3-9 Wiring diagram for analog
input signal processing
3.2.4 Elevator-specific rotary encoder interface board – wiring and description of PG
card
1. MCTC-PG-A (applicable to asynchronous unit’s open collector output, push-pull output,
incremental encoder)
1) Technical specification
- 25 -
Chapter 3 Installation and Wiring of Inverter
Frequency
Response Output Output
Function division
speed resistance current
range
Providing
About 300ohm
+15V, COM encoder power --- 300mA ---
supply
Encoder signal
PGA, PGB access 0~80KHz --- --- ---
Frequency
1~62 (even
OUT-A division signal About 30ohm
0~80KHz 100mA number)
OUT-B output
Dial switch
PGA PGB
OUT-B
OUT-A COM
COM +15PG PE
22
Fig. 3-10 PG Card for MCTC-PG-A asynchronous unit (push-pull output, open collector
output incremental encoder)
The frequency division coefficient is decided by the dial switch of the PG card. The dial switch
has 5 digits. The frequency division coefficient can be determined by multiplying its binary
number with 2. “1” on the dial switch is the binary low order bit, while “5” is the high order bit.
When dial switch is toggled to ON, the bit is effective and indicates “1” . Otherwise, it indicates
“0”. The look-up table for dial switch bits and frequency division coefficient is as follows:
- 26 -
Chapter 3 Installation and Wiring of Inverter
15V+
+15VPG
0V
PGM
PG A
A
B
B
PE
ME320L
- 27 -
Chapter 3 Installation and Wiring of Inverter
A+, B+, A-, B-, U+, Encoder signal 0~80KHz --- --- ---
V+, W+, U-, V-, W- access
A- VCC V+
B- W+ U+
OUT-A
COM OUT-B
22
- 28 -
Chapter 3 Installation and Wiring of Inverter
B. The PG cable must penetrate the pipe separately, and the enclosure of the metal pipe shall
be grounded reliably.
5V+
VCC
GND
A+ GND
A+
P A-
A-
ME-PG-B
B+
B+
B-
B-
U+
U+
U-
U-
V+
V+
G V-
V-
W +
W +
W -
W -
- 29 -
Chapter 3 Installation and Wiring of Inverter
When the inverter has mistaken action the inverter, they may have mistaken action
because of the interference, the following because of the interference. It is
measures can be taken: recommended to adopt the following
A. Install surge suppressor on the devices measures for resolution: Keep far away
generating interference from the interference source; do not lay out
B. Install filter at the signal input side of the the signal cables and power cables in
inverter parallel mode, use shielded cables as signal
2) Handling method for interference to the cable and power cable, install linear filter or
surrounding equipment by the inverter noise: radio noise filter at the input and output sides
The preconditions for solving such problem of the inverter.
are as follows: B. When the affected equipment and the
A. the grounding wires of the inverter and inverter use the same power supply, if the
other electric equipment shall well grounded, above methods cannot eliminate the
and the grounding resistance shall be no interference, linear filter or radio noise filter
more than 5ohm. shall be installed between the inverter and
B. The power cable of the inverter shall not the power supply.
be parallel with the control cable, and they C. Grounding the surrounding equipment
shall be vertical to each other when possible. separately can avoid the interference caused
C. For the places with high interference by the leakage current of the inverter’s
immunity requirements, the power cable grounding wire when common grounding
between the inverter to the motor shall use mode is adopted.
the shielded cable, and the shielding layer 3.3.3 Leakage current and handling
shall be reliably grounded. There are two types of leakage current when
D. For the wire of the affected equipment, using the inverter: The leakage current to
the twisted shielded control wire shall be the ground and the leakage current between
used, and the shielding layer shall be reliably the lines.
grounded. 1. Factors influencing the leakage current to
There are two types of noise: The noise the ground and the solutions:
radiated by the inverter, and the noise There are distribution capacitors between
radiated by the wire connecting the inverter the cables and the ground. The larger the
and the motor. Such radiation will cause the distribution capacitance is, the larger the
electromagnetic and static induction of the leakage current will be. The distribution
wire of the surrounding electric equipment. capacitance can be reduced by effectively
A. The instruments for measurement, reducing the distance between the inverter
receivers and sensors generally have weak and the motor. The higher the carrier wave
signals. If they are close to the inverter or frequency is, the larger the leakage current
located in the same control carriageet with will be. The leakage current can be reduced
- 30 -
Chapter 3 Installation and Wiring of Inverter
by reducing the carrier wave frequency. The solution is to reduce the carrier wave
However, please note that reducing carrier frequency or install output reactor. It is
wave frequency will increase the motor recommended not to install the thermal relay
noise.Installing reactor is also an effective in front of the motor when using the inverter.
method to solve the leakage current The electronic overcurrent protection
problem. function of the inverter shall be used.
2. The leakage current increases with the
circuit current. Therefore, when the motor
power is increased, the corresponding
leakage current will be increased.
3. Factors influencing the leakage current
between the lines and the solutions:
There exist distribution capacitors between
the output lines of the inverter. If the current
passing the lines has higher harmonic,
resonance may be resulted in, which may
cause leakage current. If thermal relay is
used, it may have mistaken action.
- 31 -
Chapter 4 Inverter Operation and Trial Running
- 32 -
Chapter 4 Inverter Operation and Trial Running
When the user checks and sets the parameters of the inverter through the operation panel, it is
in programming status.
Running status (elevator in operation):
When the inverter is in running status, the RUN LED is on. The LED display does not flash.
Alarm status:
When the inverter has failure and displays failure code, it is in alarm status.
4.2 Operation and display interface
The operation keyboard with LED display is the standard configuration of ME320L inverter. The
user can modify the function parameter, monitor the operating status, control the running of the
inverter (start, stop) through the keyboard.
Its appearance and function zone are as shown in Fig.4-1.
4.2.1 Function LED description:
When the RUN LED is on, it indicates that the inverter is in running status.
LOCAL/REMOT is the keyboard operation and remote (terminal) operation LED. When it is on,
it indicates that the inverter is in remote control mode.
FWD/REV is the elevator upward/downward LED. When it is
on, the FWD command is effective, and the elevator goes
upward. When it is off, the REV command is effective, and
the elevator goes downward. The LED is invalid when it is in
STOP status.
TUNE is the tuning LED. When it is on, it indicates that the
inverter is in tuning status.
4.2.2 Digital display zone:
Five-digit LED display, able to display various monitor data
(including set frequency and output frequency) and alarm
code.
4.2.1 UNIT LED description:
HZ frequency unit A current unit
V voltage unit RPM rotation speed unit Fig.4-1 operation panel interface
% percentage
4.2.4 Keyboard button description:
Button Name Function
programming entry and exit of primary menu, deletion of shortcut
PRG
key parameter
confirmation enter the menu interfaces level by level, confirm the set
ENTER
key parameters
∧ Increase key increase of the data or function code
∨ decrease key decrease of the data or function code
- 33 -
Chapter 4 Inverter Operation and Trial Running
- 34 -
Chapter 4 Inverter Operation and Trial Running
STOP
display
PRG ENTER ∧ ENTER >>
0.000 F0 F0-00 F0-05 50.00 50.00
Load speed
When the inverter has failure, the panel will display the failure information code. The failure
cause can be judged through the failure code, so as to quickly remove the failure.
The inverter can save the last three failure codes and recode the frequency, current, bus
voltage, digital input terminal status and digital output terminal status of the last failure. the
schematic diagram is as follows:
STOP display
Fig.4-5 view failure information
4.3.4 Monitor the digital input terminal status:
The digital input terminal status shall be monitored during the operation. For details, please
refer to chapter six F8-00 parameter description.
4.4 Shortcut menu operation mode
The shortcut menu of the ME320L inverter is to facilitate the users to check and modify the
frequently used function parameters. The display mode of the parameters in shortcut menu is
“uF3-02”, it indicates that the function parameter is F3-02. changing parameter in shortcut
menu has the same effect as changing parameter in common mode.
The shortcut menu can contain 16 function parameters at most. If there are 16 parameters and
the user wants to add more, it will display “FULL”. If “NULL” is displayed when entering the
menu, it indicates that the shortcut menu is null. The shortcut menu has stored the 16 common
parameters for the convenience of the user:
F0-00: Control mode F3-00: Startup frequency
F0-01: Command selection F3-01: startup frequency retention
time
F0-02: Speed selection F4-13: Multi-speed filtering time
F1-11: Motor tuning selection F8-00: terminal status display
F2-00: scale 1 coefficient F8-03: Load speed display
F2-01: integral 1 time F9-16: the last failure
F2-03: scale 2 coefficient FA-00: Number of PG pulse
F2-04: integral 2 time FC-00: Command abnormal action
selection
The users can edit such parameters according to their needs.
4.4.1 Add shortcut menu parameters:
PRG ∧ ENTER
- 36 -
Chapter 4 Inverter Operation and Trial Running
Data display
QUICK
0.000 uF8.11
- 37 -
Chapter 4 Inverter Operation and Trial Running
∧ >> ∧ >>
12300 12000 12000 10000 10000
>>
∧ >> ∧ ENTER
12300 12340 12340 12345 FP-00
- 38 -
Chapter 5 Function Parameter Table
- 39 -
Chapter 5 Function Parameter Table
F0——basic function
0: Vector control without speed
sensor (SVC)
F0-00 Control mode 1: Vector control with speed 1 1 ★
sensor (VC)
2: V/F control
0: Operation panel running
command channel (LED off)
Command 1: terminal running command
F0-01 1 1 ★
selection channel (LED on)
2: communication control
(special card used)
0: Digital setting
1: Multi-speed
2: AI1
F0-02 Speed selection 1 1 ★
3: AI2
4: communication setting
(special card used)
Digital setting
F0-03 0.00~ maximum frequency 0.01Hz 00.00Hz ☆
frequency
0: consistent direction 1:
F0-04 running direction 1 0 ★
reverse direction
maximum
F0-05 10.00~90.00Hz 0.01Hz 50.00Hz ★
frequency
carrier wave model
F0-06 0.5~16.0kHz 0.1kHz ☆
frequency dependent
- 40 -
Chapter 5 Function Parameter Table
- 41 -
Chapter 5 Function Parameter Table
- 42 -
Chapter 5 Function Parameter Table
Running
F3-08 contactor 0.00~10.00s 0.01s 0.00s ★
release delay
0: no pre-torque
startup 1: DI setting
F3-09 pre-torque 2: AI1 setting 1 0 ★
setting selection 3: AI2 setting
4: use pre-torque initial offset
F3-10 pre-torque offset 0.0%~100.0% 0.1% 48.0 ☆
F3-11 pre-torque gain 0.00~1.50 0.01 0.60 ★
pre-torque initial
F3-12 -100.0%~100.0% 0.1% 10.0% ★
offset
DI weighing
F3-13 0%~100.0% 0.1% 10.0% ★
signal 1
DI weighing
F3-14 0%~100.0% 0.1% 30.0% ★
signal 2
DI weighing
F3-15 0%~100.0% 0.1% 70.0% ★
signal 3
DI weighing
F3-16 0%~100.0% 0.1% 90.0% ★
signal 4
weighing analog
F3-17 model input filter 0.00~1.00s 0.01s 0.10s ☆
time
weighing analog
no-load
F3-18 0.00~10.00V 0.01V 0.00V ☆
corresponding
input
weighing analog
full load
F3-19 0.00~10.00V 0.01V 10.00V ☆
corresponding
input
analog weighing 0~100
F3-20 1 0 ☆
self learning
analog weighing 0: no operation
F3-21 1 0 ☆
self learning 1: self learning allowed
- 43 -
Chapter 5 Function Parameter Table
- 44 -
Chapter 5 Function Parameter Table
invalid.
For instance: 106 indicates
F4-11 reserved that the terminal function is 1 0 ★
failure reset function, and the
signal type is normally closed.
F4-12 reserved 0.000~0.200s 0.001 0.005 ★
Multi-speed
F4-13 combination 0.000~0.200s 0.001 0.020s ☆
filtering time
F5――output terminal
FMR output 0: no output
F5-00 1 15 ★
selection 1: in running
DO1 output 2: in zero speed running
F5-01 1 3 ☆
selection (effective in zero speed and
DO2 output Run conditions)
F5-02 1 0 ☆
selection 3: zero speed signal (output
RELAY1 output even at stop status)
F5-03 1 4 ☆
selection 4: failure signal
0: running frequency
1: set frequency
2: Output current
AO output
F5-07 3: output torque 1 0 ☆
selection
4: Output voltage
5: AI1
6: AI2
F5-08 AO zero offset -100.0%~100.0% 0.1% 0.0% ☆
F5-09 AO gain -10.00~10.00 0.01 1.00 ☆
F6――speed parameters
F6-00 Multi-speed 0 0.00~ maximum frequency 0.01Hz 0.00Hz ★
F6-01 Multi-speed 1 0.00~ maximum frequency 0.01Hz 0.00Hz ★
F6-02 Multi-speed 2 0.00~ maximum frequency 0.01Hz 0.00Hz ★
F6-03 Multi-speed 3 0.00~ maximum frequency 0.01Hz 0.00Hz ★
F6-04 Multi-speed 4 0.00~ maximum frequency 0.01Hz 0.00Hz ★
F6-05 Multi-speed 5 0.00~ maximum frequency 0.01Hz 0.00Hz ★
F6-06 Multi-speed 6 0.00~ maximum frequency 0.01Hz 0.00Hz ★
F6-07 Multi-speed 7 0.00~ maximum frequency 0.01Hz 0.00Hz ★
Multi-speed 0
acceleration/
F6-08 1~4 1 1 ★
deceleration
time selection
Multi-speed 1
acceleration/
F6-09 1~4 1 1 ★
deceleration
time selection
Multi-speed 2
acceleration/
F6-10 1~4 1 1 ★
deceleration
time selection
Multi-speed 3
acceleration/
F6-11 1~4 1 1 ★
deceleration
time selection
- 46 -
Chapter 5 Function Parameter Table
Multi-speed 4
acceleration/
F6-12 1~4 1 1 ★
deceleration
time selection
Multi-speed 5
acceleration/
F6-13 1~4 1 1 ★
deceleration
time selection
Multi-speed 6
acceleration/
F6-14 1~4 1 1 ★
deceleration
time selection
Multi-speed 7
acceleration/
F6-15 1~4 1 1 ★
deceleration
time selection
Maintenance
F6-16 0~7 1 0 ★
speed selection
emergency 0: motor has no operation
F6-17 solution 1: UPS supply for operation 1 0 ★
selection 2: 48V battery supply
F6-18 Min analog input 0.00~10.00V 0.01V 0.00V ☆
Corresponding
F6-19 setting of min 0.0~100.0% 0.1% 0.0% ☆
analog input
Max analog
F6-20 0.00~10.00V 0.01V 10.00V ☆
input
Corresponding
F6-21 setting of max 0.0~100.0% 0.1% 100.0% ☆
analog input
Filter time of
F6-22 0.00~10.00s 0.01s 0.10s ☆
analog input
F7――curve parameters
Acceleration
F7-00 1.0~100.0s 0.1s 4.0s ☆
time 1
- 47 -
Chapter 5 Function Parameter Table
Deceleration
F7-01 1.0~100.0s 0.1s 4.0s ☆
time 1
Start segment
F7-02 10.0~40.0% 0.1% 40.0% ★
time of S curve 1
End segment
F7-03 10.0~40.0% 0.1% 40.0% ★
time of S curve 1
Acceleration
F7-04 1.0~100.0s 0.1s 4.0s ☆
time 2
Deceleration
F7-05 1.0~100.0s 0.1s 4.0s ☆
time 2
Start segment
F7-06 10.0~40.0% 0.1% 40.0% ★
time of S curve 2
End segment
F7-07 10.0~40.0% 0.1% 40.0% ★
time of S curve 2
Acceleration
F7-08 1.0~100.0s 0.1s 4.0s ☆
time 3
Deceleration
F7-09 1.0~100.0s 0.1s 20.0s ☆
time 3
Start segment
F7-10 10.0~50.0% 0.1% 40.0% ★
time of S curve 3
End segment
F7-11 10.0~50.0% 0.1% 40.0% ★
time of S curve 3
Acceleration
F7-12 0.5~100.0s 0.1s 1.0s ☆
time 4
Deceleration
F7-13 0.5~100.0s 0.1s 1.0s ☆
time 4
Start segment
F7-14 10.0~50.0% 0.1% 40.0% ★
time of S curve 4
End segment
F7-15 10.0~50.0% 0.1% 40.0% ★
time of S curve 4
F8――keyboard and display
Input/output
F8-00 terminal status - - - ●
indication
- 48 -
Chapter 5 Function Parameter Table
0~32767
Bit0: load speed
Bit1: running frequency
Bit2: destination frequency
Bit3: DC bus voltage
Bit4: Output voltage
Bit5: Output current
LED operation
Bit6: AI1
F8-01 indication 1 32767 ☆
Bit7: AI2
parameter
Bit8: carriage load (%)
Bit9: startup compensation
current (%)
Bit10: running torque current
(%)
Bit11: input status
Bit12: output status
1~255
Bit0: destination load speed
Bit1: destination frequency
LED stop Bit2: DC bus voltage
F8-02 indication Bit3: AI1 1 255 ☆
parameter Bit4: AI2
Bit5: carriage load (%)
Bit6: input status
Bit7: output status
Load speed
F8-03 display 0.01~100.00 0.01 0.32 ☆
coefficient
heatsink
F8-04 0.0~100℃ 1℃ - ●
temperature
software version
F8-05 0~99.99 1 - ●
no.1
software version
F8-06 0~99.99 1 - ●
no.2
- 49 -
Chapter 5 Function Parameter Table
0~65535h
F8-07 Set running time 0: indicating that this function 1h 0h ☆
is inactive
Accumulated 1h 0h
F8-08 0~65535h ●
operating time
accumulated 1 0
F8-09 timing (in 0~3600s ●
second)
0~9999 1 0
high order of
F8-10 Note: 1 indicates that the ●
running times
actual running times are 10000
low order of 1 0
F8-11 0~9999 ●
running times
Ground short
circuit protection 0: inactive
F8-12 1 0 ☆
detection upon 1: active
power-up
F9――failure and protection
motor overload 0: prohibited
F9-00 protection 1: allowed 1 1 ☆
selection
motor overload 0.20~10.00
F9-01 0.01 1.00 ☆
protection gain
motor overload 50%~100%
F9-02 prealarm 1% 80% ☆
coefficient
overvoltage stall 0(no overvoltage stall) ~100
F9-03 1 0 ☆
gain
overvoltage stall 120~150%
F9-04 protection 1% 130% ☆
voltage
overcurrent stall 0~100
F9-05 1 20 ☆
gain
- 50 -
Chapter 5 Function Parameter Table
- 51 -
Chapter 5 Function Parameter Table
- 52 -
Chapter 5 Function Parameter Table
Frequency upon -
F9-17 - - ●
failure
Current upon -
F9-18 - - ●
failure
bus voltage -
F9-19 - - ●
upon failure
Input terminal -
F9-20 - - ●
upon failure
Output terminal -
F9-21 - - ●
upon failure
FA――PG parameters
Number of PG 100~10000
FA-00 1 1024 ★
pulses
0~10.0s (the detection function 0.1.0s 3.0s
PG wire-break
FA-01 is inactive when it is less than ★
detection time
2s)
FA-02 reserved - - - -
PG magnetic 0.0~359.9 0.1 0.0
FA-03 ★
pole angle
current angle of
FA-04 PG magnetic 0.0~359.9 0.1 0.0 ●
pole
- 53 -
Chapter 5 Function Parameter Table
UVW wiring
FA-05 0~3 1 0 ★
mode
FB――communication parameters
0: 300BPS
1: 600BPS
2: 1200BPS
3: 2400BPS
FB-00 baud rate 1 5 ☆
4: 4800BPS
5: 9600BPS
6: 19200BPS
7: 38400BPS
0: no parity check
FB-01 data format 1: even parity check 1 0 ☆
2: odd parity check
1~126, 127 is the broadcast
FB-02 Local address 1 1 ☆
address
FB-03 response delay 0~20ms 1 2 ☆
Communication 0.0(inactive) , 0.1~100.0s
FB-04 0.1s 0.0 ☆
timeout time
FC――Special enhanced function
Command 0: Deceleration running
FC-00 abnormal action 1: Locking output immediately 1 1 ★
selection
Deceleration 0.1~300.0s
time selection for
FC-01 0.1s 3.0s ★
abnormal
situation
Ascending 0.00~ maximum frequency
FC-02 frequency 0.01Hz 45.00Hz ★
detection level
Descending 0.00~ maximum frequency
FC-03 frequency 0.01Hz 45.00Hz ★
detection level
- 54 -
Chapter 5 Function Parameter Table
- 55 -
Chapter 5 Function Parameter Table
- 56 -
Chapter 6 Parameter Description
the running command is sent by the upstream equipment or special communication card. When
this option is selected, special communication card (option) shall be installed.
Leave-factory
F0-02 Speed selection 1
value
Set 0: Digital setting
range 1: Multi-speed
2: AI1
3: AI2
4: communication setting (special card used)
Select the inverter speed input channel. There are 4 channels:
0: Digital setting
The speed of ME320L adopts the digital set value of the inverter. The initial value is the setting
of F0-03 “digital set frequency”.
1: Multi-speed
When this parameter is selected, the inverter adopts the multi-speed running mode. the
correspondence relation between the reference signal and reference frequency shall be
determined by group F4 “input parameters” and group F6 “speed parameters”.
2: AI1 3: AI2
It means that the frequency is determined by the analog input terminal. The ME320L series
inverter provides 2 analog input terminals as standard. AI1 is for 0~10V voltage input. AI2 can
be used for 0~10V voltage input or 4~20mA current input, which can be selected by the J3
jumper on the control panel.
4: communication setting (special card used)
With the special expansion card, the ME320L can receive the speed reference through
communication mode.
Leave-factory
F0-03 Digital setting frequency 0.00Hz
value
Set 0.00Hz~ maximum frequency
range
The ME320L speed setting adopts the destination frequency after digital setting.
Leave-factory
F0-04 running direction 0
value
Set range 0: consistent direction
1: reverse direction
By changing this function code, the rotation direction can be changed without changing the
wiring.
Note: After parameter initialization, the motor running direction will restore to original state.
Users shall be careful in using this function.
- 58 -
Chapter 6 Parameter Description
Leave-factory
F0-05 maximum frequency 50.00Hz
value
Set range 10.00Hz~90.00Hz
It is used to set the maximum output frequency of the inverter. When frequency above industrial
frequency is used for special needs, the mechanical load of the elevator shall be taken into
account.
Leave-factory Model
F0-06 carrier wave frequency
value dependent
Set range 0.5~16.0kHz
This function is used to adjust the carrier wave frequency of the inverter. By adjusting the
carrier wave frequency, the motor noise can be reduced, the resonance of the mechanical
system can be avoided, so that the leakage current to the ground and the interference of the
inverter can be reduced.
When the carrier wave frequency is low, the output current higher harmonic component will be
increased, the motor loss will be increased, and the motor temperature rise will also increase.
When the carrier wave frequency is high, the motor loss is reduced, and the motor temperature
is reduced also, but the inverter loss and inverter temperature rise will be increased, and thus
the interference will be increased.
The adjustment of carrier wave frequency will have the following influences on the
performance:
carrier wave frequency Low ~ high
motor noise high ~ low
output current waveform poor ~ good
motor temperature rise high ~ low
inverter temperature rise Low ~ high
leakage current low ~ high
radiation interference low ~ high
Leave-factory
F0-07 carrier wave adjustment selection 2
value
Set 0: fixed PWM, carrier wave temperature adjustment invalid
range 1: random PWM, carrier wave temperature adjustment invalid
2: fixed PWM, carrier wave temperature adjustment valid
3: random PWM, carrier wave temperature adjustment invalid
Two PWM carrier wave frequency adjustment modes, fixed and random, are provided. the
random PWM motor noise has wide frequency range, while the fixed PWM motor noise has
fixed frequency.
- 59 -
Chapter 6 Parameter Description
When the carrier temperature adjustment is effective, the inverter can automatically adjust the
carrier wave according to its temperature. This function can reduce the overtemperature alarms
of the inverter.
- 60 -
Chapter 6 Parameter Description
Leave-factory model
F1-01 rated power
value dependent
Set 0.4~1000.0kW
range
Leave-factory
rated voltage 380V
F1-02 value
Set 0~440V
range
Leave-factory model
rated current
F1-03 value dependent
Set 0.00~655.00A
range
Leave-factory model
rated frequency
F1-04 value dependent
Set 0.00~3000.0Hz
range
Leave-factory
rated rotation speed 1460rpm
F1-05 value
Set 0~30000rpm
range
When the motor autotune is normally completed, the set values of F1-06~F1-10 will be
automatically updated.
- 61 -
Chapter 6 Parameter Description
Please set the parameters according to the nameplate parameters of the motor.
Note: To ensure good vector control, correct motor parameters shall be provided. The
ME320L inverter provides parameter autotune function. The correct parameter autotune
depends on the correct setting of the motor ratings.
To ensure the control performance, the motor shall be configured according to the standard
configuration of the motor. If the motor power has significant difference with the configuration of
the standard motor, the control performance of the inverter will be degraded significantly.
Leave-factory model
stator resistance
F1-06 value dependent
Set 0.001~65.535Ω
range
Leave-factory model
rotator resistance
F1-07 value dependent
Set 0.001~65.535Ω
range
Leave-factory model
leakage inductive reactance
F1-08 value dependent
Set 0.01~655.35mH
range
Leave-factory model
mutual inductive reactance
F1-09 value dependent
Set 0.1~6553.5mH
range
Leave-factory model
No-load current
F1-10 value dependent
Set 0.01~650.00A
range
When the motor autotune is normally completed, the set values of F1-06~F1-10 will be
- 62 -
Chapter 6 Parameter Description
automatically updated.
If it is impossible to tune the motor on site, the user can manually input the parameters by
referring to the known parameters of the motors of the same type.
Note: Each time when the rated power of the motor F1-01 is changed, the inverter will
automatically recover the parameter values of F1-06~F1-10 to the default standard motor
parameters.
F1-11 Tuning selection Leave-factory value 0
Set range 0: no operation
1: static tuning
2: complete tuning
Note: Correct motor ratings (F1-01~F1-05) must be set before tuning.
0: no operation
1: static tuning, applicable to asynchronous motor and the applications where rotary tuning
cannot be conducted because it is not easy to remove the load.
action description: Set the function code as 1 and press RUN key for confirmation, and then
the inverter will conduct static tuning.
2: complete tuning action description: Set the function code as 2 and press RUN key for
confirmation, and then the inverter will conduct rotary tuning.
To ensure the dynamic control performance of the inverter, please select rotary tuning. During
the rotary tuning, the motor must be disconnected with the loads (i.e. no-load).
After selecting rotary tuning, the inverter will conduct static tuning first. After the static tuning is
finished, the asynchronous motor will accelerate to 80% of the rated frequency of the motor
according to the acceleration time set in F7-00 and maintain for a certain period of time, and
then decelerate to zero speed according to the deceleration time set in F7-01, and the rotary
tuning is finished. The synchronous motor will have forward and reverse stepping to judge the
PG origin.
tuning operation description:
Set F1-11 as 1 or 2 and press ENTER key, “TUNE” is displayed and flashes. And then press
Run key to conduct parameter tuning, and the displayed “TUNE” stops flash. After the tuning is
finished, the display will return to the stop status interface. The tuning can be stopped by
pressing the STOP key.
When the tuning is finished, the value of F1-11 will automatically restore to 0.
Note: When permanent magnetic synchronous motor is used, complete tuning shall be
conducted. The reason is that the tuning will identify the origin of the installed encoder in
addition to identifying the relevant parameters of the motor. It is prohibited to run the permanent
magnetic synchronous motor before the complete tuning.
▲ The autotune steps for the motor parameters of asynchronous motor are as follows:
Set F0-01 as 0: the control mode adopts the operation panel command channel control;
- 63 -
Chapter 6 Parameter Description
set F1-00 as 0 according to the actual motor type: asynchronous motor. Set F1-01, F1-02,
F1-03, F1-04 and F1-05 correctly according to the motor nameplate.
If the motor is completely disconnected with the load, select 2 (complete tuning) for F1-11, and
then press RUN key on the keyboard. The motor runs automatically, and the inverter
automatically calculates the following motor parameters:F1-06 (stator resistance), F1-07
(rotator resistance), F1-08 (leakage inductive reactance), F1-09 (mutual inductive reactance)
and F1-10 (no-load exciting current). After that, the motor tuning is finished. if overcurrent
appears, correspondingly increase the value of F7-00 and F7-01.
If the motor is not completely disconnected with the load, select 1 for F1-11 (static tuning), and
then press RUN key on the keyboard. The motor runs automatically, but the inverter will only
measures the stator resistance, rotator resistance and leakage inductive reactance in turn. The
mutual inductive reactance can be calculated according to the no-load current.
▲ The autotune steps for the motor parameters of permanent magnetic synchronous motor are
as follows:
(1) Set F0-01 as 0: the control mode adopts the operation panel command channel control;
set F1-00 as 1 according to the actual motor type: permanent magnetic synchronous motor
Set F1-01, F1-02, F1-03, F1-04 and F1-05 correctly according to the motor nameplate.
(3) disconnect the elevator traction motor completely with the load (steel rope), and select 2 for
F1-11. Press RUN key on the keyboard, the motor runs automatically, and the inverter
automatically calculates FA-04 and FA-05 (PG magnetic angle), and then the motor tuning is
finished.
(4) After the tuning is finished, set F0-03=10.00Hz, and press RUN key to check if it can run
normally. If there is any abnormality, change the PG signal direction and repeat steps 1, 2 and
3.
6.3 F2――vector control parameter
Leave-factory
F2-00 speed loop scale coefficient 1 35
value
Set range 0~100
Leave-factory
F2-01 speed loop integral time 1 0.60s
value
Set range 0.01~10.00s
Leave-factory
F2-02 switching frequency 1 2.00Hz
value
Set range 0.00~F2-05
Leave-factory
F2-03 speed loop scale coefficient 2 30
value
Set range 0~100
F2-04 speed loop integral time 2 Leave-factory 0.8s
- 64 -
Chapter 6 Parameter Description
value
Set range 0.01~10.00s
Leave-factory
F2-05 switching frequency 2 5.00Hz
value
· Set range F2-02~ maximum output frequency
F2-00 and F2-01 are the PI adjustment parameters when the running frequency is less than
switching frequency 1(F2-02). F2-03 and F2-04 are the PI adjustment parameters when the
running frequency is higher than switching frequency 2 (F2-05) . The PI adjustment parameters
for the frequency between switching frequency 1 and switching frequency 2 are the weighted
mean value of F2-00, F2-01 and F2-03, F2-04, as shown in the following figure.
PI
parameter
- 65 -
Chapter 6 Parameter Description
F3-00 t
0
FWD/REV
Contactor
output
Internal
operation
Brake
In zero-speed
running
F5-0 6
F3-0 1 F3-0 2 F3-0 3 F3-0 4
F3-0 5 F3-0 6 F3-0 7 F3-0 8
During the application, if the elevator has no weighing compensation, set F3-09 as 4, and then
adjust the pre-torque offset parameter of F3-12, so that before the brake is opened, ME320L
can fully perform pre-excitation to improve the startup comfortability. However, this parameter
cannot be set too large. In general it shall be within -15%~15%.
Counterweight
Fig.6-3
- 68 -
Chapter 6 Parameter Description
Set 0%~100.0%
range
F3-16 DI weighing signal 4 Leave-factory value 90.0%
Set 0%~100.0%
range
The ME320L series inverter has 3 pre-torque modes: digital weighing signal, analog weighing
signal and pre-torque offset. F3-13~F3-16 corresponds to the setting of digital weighing input
signal. The four settings correspond to weighing terminals 1~4 one by one, and they are used
in pairs. The setting of the four function parameters indicates the load percentage in the
carriage when the signal is valid. For example, if the load of certain carriage reaches 10%, the
signal of weighing terminal 1 is valid, the setting of parameter F3-13 will be 10%. When the load
in the carriage exceeds 10%, the ME320L inverter can identify the current carriage load through
the signal of weighing terminal 1 and completes the pre-torque function. When several
weighing signals are valid, the signal indicating larger load shall be used.
F3-17 weighing analog model input filter time Leave-factory value 0.10s
Set 0.00~1.00s
range
weighing analog no-load corresponding
F3-18 Leave-factory value 0.00V
input
Set 0.00~10.00V
range
weighing analog full load corresponding
F3-19 Leave-factory value 10.00V
input
Set 0.00~10.00V
range
When F3-08 selects analog AI1 or AI2 setting, it indicates that ME320L uses analog weighing
signal input. F3-17 is the filter time of the signal. The interference immunity of the weighing
signal can be effectively improved by properly increase the parameter value.
When using the analog weighing signal input, the corresponding analog input voltage upon
carriage no-load and full load shall be correctly set, so as to ensure the correct pre-torque
compensation.
The schematic diagram for the pre-torque is as follows:
- 69 -
Chapter 6 Parameter Description
DI1 F3-1 3
DI2 F3-1 4
DI3 F3-1 5
Digital input
0 F3-0 9
F3-1 8
1
AI1 F3-1 7 -
2
F3-1 9 F3-1 1 F2-0 8 F3-2 2 Output
Analog input 3
4 Gain Amplitude invert
F3-1 8 limit
AI2 F3-1 7
F3-1 9
F3-1 2
Fig.6-4
- 70 -
Chapter 6 Parameter Description
Start
N
F3-21=1?
N
F3-09=2/3?
F3-20=0?
N
Y
No-load self learning Full load self learning
End
Fig.6-5
Note: 1. If F3-21 is set as 1 during the self learning, F3-21 shall be restored to 0 after the self
learning is finished. 2. No-load self learning shall be carried out before full load self-learning.
Otherwise, the data will be incorrect.
F3-22 pre-torque direction invert Leave-factory value 0
Set 0: direction unchanged
range 1: direction inverted
This function code can be used to directly invert the direction without changing the pre-torque
value.
6.5 Group F4 Input terminal
The ME320L series inverter has 5 multi-function digital input terminals (DI5 can be used as
high-speed pulse input terminal) and 2 analog input terminals as standard.
If the system needs to use more input/output terminals, multi-function input/output expansion
card can be used. The multi-function input/output expansion card has 5 multi-function digital
input terminals and 1 analog input terminal.
Leave-factory
F4-00 DI filtering time 0.020s
value
Set range 0.000~0.200s
Set the sensitivity of DI terminal. If the digital input terminal is vulnerable to interface and may
cause mistaken action, increase the parameter value to enhance the interference immunity.
- 71 -
Chapter 6 Parameter Description
Leave-factory 1 (Run
F4-01 DI1 terminal function selection
value forward)
Leave-factory 2 (Run
F4-02 DI2 terminal function selection
value reverse)
3
Leave-factory
F4-03 D13 terminal function selection (multi-speed
value
1)
4
Leave-factory
F4-04 D14 terminal function selection (multi-speed
value
2)
5
Leave-factory
F4-05 DI5 terminal function selection (multi-speed
value
3)
Leave-factory 6 (failure
F4-06 DI6 terminal function selection
value reset)
Leave-factory 7(enable
F4-07 DI7 terminal function selection
value control)
Leave-factory
F4-08 DI8 terminal function selection 0
value
Leave-factory
F4-09 DI9 terminal function selection 0
value
Leave-factory
F4-10 DI10 terminal function selection 0
value
Parameters F4-01~F4-10 are used to set the corresponding functions of the digital
multi-function input terminals. The functions of the relevant options are detailed as follows:
Set Function Description
value
0 No function Even when there is signal input, the inverter still have no action.
The no operation function can be set on the unused terminal
to prevent mistaken action.
1 Run forward control the REV Command
command (FWD) forward or reverse meaning
- 72 -
Chapter 6 Parameter Description
- 73 -
Chapter 6 Parameter Description
5 Multi-speed realized by
terminal 3(K3) the
combinations
of the digital
status of the
three
terminals.
For details
about the
combination,
please refer
to the
following
table:
K3
OFF OFF OFF Multi-speed 0 F6-00
OFF OFF ON Multi-speed 1 F6-01
OFF ON OFF Multi-speed 2 F6-02
OFF ON ON Multi-speed 3 F6-03
ON OFF OFF Multi-speed 4 F6-04
ON OFF ON Multi-speed 5 F6-05
ON ON OFF Multi-speed 6
F6-06
ON ON ON Multi-speed 7 F6-07
6 Failure reset External failure reset function. same as the function of RESET
input key on the keyboard The auto reset from the elevator failure can
be realized with this function.
7 enable control The run enable terminal is set. If the run enable signal
input disappears during the operation of the inverter, the inverter will
stop immediately and output the brake close command.
8 maintenance When the maintenance input is valid, the ME320L adopts the
input non-zero parameters set in F6-16 for multi-speed selection.
During the stop process, if the maintenance input signal is
removed, the ME320L will decelerate to 0 according to the
multi-speed deceleration time set in F6-16 until the run
forward/reverse command is canceled. If the run
forward/reverse command is canceled directly during the
maintenance operation, the ME320L will stop output
- 74 -
Chapter 6 Parameter Description
immediately.
9 emergency input Emergency input indicates that the elevator enters emergency
running state. The operation is powered by external 48V battery
or 220V UPS input.
10 running if contactor feedback signal terminal and brake feedback signal
contactor terminal are set, when 2 seconds has passed after the unit is
feedback input stopped (the output contactor disconnection signal is provided),
11 Brake feedback the contactor feedback signal terminal and brake feedback
input signal will be detected. If the two feedback signals still exist, the
inverter will output “Conglutination signal active”.
Select the feedback signals, and then ME320L will monitor
these signals during the operation.
12 weighing The weighing signal corresponding to digital setting. The
terminal 1 input relevant setting parameters are in F3-12~F3-15.
13 weighing
terminal 2 input
14 weighing
terminal 3 input
15 weighing
terminal 4 input
16 external failure external failure input point. When the signal is active, the
input system generates alarm and stops operation.
17 Motor When the signal is active, it indicates that the motor
overtemperature temperature is too high, and the ME320L will generate alarm
input output and stop operation.
18 Upward speed With the two signals, the deceleration function can be realized
judgment input forcefully with function codes FC-02 and FC-03. During the
19 Downward upward operation, if the upward speed judgment switch (forced
speed judgment deceleration switch) acts, the ME320L will compare the current
input running frequency with the FC-02. If it is more than FC-02, the
ME320L will decelerate to stop immediately (according to the
time set in FC-01) to ensure the safety of the elevator. it is the
same case with downward operation. For details, please refer to
the description of group FC.
Note: The terminal input range is 0~119. if the hundred bit is 1, it indicates that the signal is
normally closed type. If it is 0, it indicates that the signal is normally open type. The lower 2 bits
are for the terminal input function selection. When the value is more than 19, it indicates that
the function is invalid. For instance: 106 indicates that the terminal function is failure reset
- 75 -
Chapter 6 Parameter Description
Multi-speed
terminal 1
Multi-speed
terminal 2
Multi-speed
terminal 3
Fig.6-6
6.6 Group F5 Output terminal
The ME320L series inverter has 1 multi-function digital output terminal (open collector), 1 FM
terminal (open collector), 1 multi-function relay output terminal and 1 multi-function analog
output terminal as standard. If more relay output terminals are needed, multi-function
input/output expansion card shall be used. The expansion card has 1 multi-function analog
output terminal.
FMR output selection (open collector output Leave-factory
F5-00 15 (RUN ready)
terminal) value
DO1 output selection (open collector output Leave-factory 3 (zero speed
F5-01
terminal) value signal)
DO2 output selection (open collector output Leave-factory
F5-02 0 (no output)
terminal) value
RELAY1 output selection (relay 1 output Leave-factory
F5-02 4 (failure signal)
terminal) value
RELAY2 output selection (relay 2 output Leave-factory
F5-03 0 (no output)
terminal) value
- 76 -
Chapter 6 Parameter Description
Set
Function Description
value
Conglutination output.
output control
Leave-factory
F5-06 zero speed output hysteresis time 0.000
value
When the output function selection value is 2 (in zero speed operation), the hysteresis time of
the output signal is determined by F5-06. The correspondence relation is as shown in Fig.6-2.
Leave-factory
F5-07 AO output selection 1
value
The main control board of ME320L has an analog output port(AO1) . F5-07 is used to select
this analog output.
The standard output (zero offset is 0, gain is 1) of the analog output is 0~20mA(or 0~10V) . The
range of the corresponding values is as shown in the following table:
Set value Function Range
0 running 0~ maximum output frequency
frequency
1 set frequency 0~ maximum output frequency
2 Output current 0 ~ 200% of the rated current of the inverter
3 output torque 0 ~ 200% of the rated torque of the inverter
4 Output voltage 0 ~ 120% of the rated current of the inverter
5 AI1 0~10V
6 AI2 0~10V/0~20mA
Leave-factory
F5-08 AO zero offset coefficient 0.00%
value
Set range -100.0%~100.0%
Leave-factory
F5-09 AO gain 1.00
value
Set range -10.00~10.00
If b represents zero offset, k represents k, Y represents actual output, X represents standard
output, the actual output is:
Y=kX+b,
AO zero offset coefficient 100% corresponds to 10V(20mA) .
The standard output means to output 0~10V(20mA) , and the corresponding analog output is
0~maximum.
- 78 -
Chapter 6 Parameter Description
It is generally used to correct the zero drift of the analog output and the output amplitude
deviation. it can also be defined as any necessary output curve.
For instance: If the analog output is the running frequency, and it is expected to output
8V(16mA) when the frequency is 0, and output 3V(6mA) at the maximum frequency, the gain
shall be set as “-0.50”, and the zero offset shall be set as “80%”.
6.7 Group F6 Speed parameters
When the ME320L adopts the multi-speed running mode, F6-00~F6-15 shall be set to
determine the running curve characteristics.
Leave-factory
F6-00 Multi-speed 0 0.0Hz
value
Set 0.00Hz~ maximum frequency
range
Leave-factory
F6-01 Multi-speed 1 0.0Hz
value
Set 0.00Hz~ maximum frequency
range
Leave-factory
F6-02 Multi-speed 2 0.0Hz
value
Set 0.00Hz~ maximum frequency
range
Leave-factory
F6-03 Multi-speed 3 0.0Hz
value
Set 0.00Hz~ maximum frequency
range
Leave-factory
F6-04 Multi-speed 4 0.0Hz
value
Set 0.00Hz~ maximum frequency
range
Leave-factory
F6-05 Multi-speed 5 0.0Hz
value
Set 0.00Hz~ maximum frequency
range
Leave-factory
F6-06 Multi-speed 6 0.0Hz
value
Set 0.00Hz~ maximum frequency
range
Leave-factory
F6-07 Multi-speed 7 0.0Hz
value
- 79 -
Chapter 6 Parameter Description
- 80 -
Chapter 6 Parameter Description
Set 1~4
range
Multi-speed 4 acceleration/ Leave-factory
F6-12 1
deceleration time selection value
Set 1~4
range
Multi-speed 5 acceleration/ Leave-factory
F6-13 1
deceleration time selection value
Set 1~4
range
Multi-speed 6 acceleration/ Leave-factory
F6-14 1
deceleration time selection value
Set 1~4
range
Multi-speed 7 acceleration/ Leave-factory
F6-15 1
deceleration time selection value
Set 1~4
range
The ME320L inverter provides four groups of acceleration/deceleration time for selection. For
details, please refer to the description of group F7. Function codes F6-08~F6-15 can be used
to set the corresponding acceleration/deceleration time of each speed, 1~4. In this way, when
the motor is in different running status, different curve has different acceleration/deceleration
time.
Special note: In acceleration situation, the acceleration time of the destination speed and S
curve setting of the acceleration time are adopted. In deceleration situation, the acceleration
time of the initial speed and S curve setting of the acceleration time are adopted.
For instance: F6-01=0 HZ, F6-03=8 HZ, F6-05=48 HZ, F6-09=2, F6-11=3, F6-13=4, when the
speed needs to accelerate from F6-01 to the high speed of F6-05, the acceleration time used is
the acceleration time selected byF6-13, 4(F7-12) ; when the speed needs to decelerate from
F6-05 to F6-03, the deceleration time used is the deceleration time selected by F6-13,
4(F7-13) ; when the speed decelerates from F6-03 to F6-01, the deceleration time used is the
deceleration time selected by F6-11, 3(F7-09) .
It is the process for the elevator to complete one round of operation in the multi-speed control.
In this process, the acceleration/deceleration time of the high speed is generally set as 3~4
seconds. However, in the deceleration process from creeping to zero speed, the deceleration
time parameter value can be different with the normal deceleration time. In this case, increasing
the value of F7-05 properly can ensure the smooth speed transition during the stop process.
see the following figure:
- 81 -
Chapter 6 Parameter Description
speed
Fig.6-7
Through the combination of 8 multi-speed and 4 time parameters, the ME320L can give
different acceleration/deceleration curves.
Leave-factory
F6-16 Maintenance speed selection 0
value
Set range 0~7
This function code is used to set the speed upon maintenance. For details, please refer to
chapter 7 Maintenance operation.
Leave-factory
F6-17 emergency solution selection 0
value
Set 0: motor has no operation
range 1: UPS supply for operation
2: 48V battery supply
For details, please refer to emergency operation in chapter 7.
Leave-factory
F6-18 Min analog input 0.00V
value
Set 0.00~10.00V
range
Leave-factory
F6-19 Corresponding setting of min analog input 0.0%
value
Set 0.0%~100.0%
range
Leave-factory
F6-20 Max analog input 10.00V
value
Set 0.00~10.00V
range
Leave-factory
F6-21 Corresponding setting of max analog input 100.0%
value
Set 0.0%~100.0%
range
- 82 -
Chapter 6 Parameter Description
Leave-factory
F6-22 Filter time of analog input 0.10s
value
Set 0.00~1.00s
range
The above function codes define the speed references of the ME320L series inverter in analog
control mode, and the relation between the analog input voltage and the analog input set value.
If the analog input voltage exceeds the maximum input voltage or is less than the minimum
voltage, the maximum input voltage or minimum input voltage shall be used.
When the analog input is the current input, 1mA current equals to 0.5V voltage.
If the function selection for F0-02 is AI1 or AI2. The speed channel will form the percentage of
the speed to maximum frequency through the processing of F6-18~F6-22. The parameter is the
current speed reference.
6.8 Group F7 curve parameters
The ME320L series elevator-specific inverter has four groups acceleration/deceleration time to
correspond to four groups of S curve. Each group of S curve can be flexibly set according to the
needs of the users.
Leave-factory
F7-00 Acceleration time 1 4.0s
value
Set 1.0~100.0s
range
Leave-factory
F7-01 Deceleration time 1 4.0s
value
Set 1.0~100.0s
range
Leave-factory
F7-02 Start segment time of S curve 1 40.0%
value
Set 10.0%~40.0%
range
Leave-factory
F7-03 End segment time of S curve 1 40.0%
value
Set 10.0%~40.0%
range
Leave-factory
F7-04 Acceleration time 2 4.0s
value
Set 1.0~100.0s
range
- 83 -
Chapter 6 Parameter Description
Leave-factory
F7-05 Deceleration time 2 4.0s
value
Set 1.0~100.0s
range
Leave-factory
F7-06 Start segment time of S curve 2 40.0%
value
Set 10.0%~40.0%
range
Leave-factory
F7-07 End segment time of S curve 2 40.0%
value
Set 10.0%~40.0%
range
Leave-factory
F7-08 Acceleration time 3 4.0s
value
Set 1.0~100.0s
range
Leave-factory
F7-09 Deceleration time 3 20.00s
value
Set 1.0~100.0s
range
Leave-factory
F7-10 Start segment time of S curve 3 40.0%
value
Set 10.0%~50.0%
range
Leave-factory
F7-11 End segment time of S curve 3 40.0%
value
Set 10.0%~50.0%
range
Leave-factory
F7-12 Acceleration time 4 1.0s
value
Set 0.5.0~100.0s
range
Leave-factory
F7-13 Deceleration time 4 1.0s
value
Set 0.5~100.0s
- 84 -
Chapter 6 Parameter Description
range
Leave-factory
F7-14 Start segment time of S curve 4 40.0%
value
Set 10.0%~50.0%
range
Leave-factory
F7-15 End segment time of S curve 4 40.0%
value
Set 10.0%~50.0%
range
The four groups of acceleration/deceleration time have the same meaning. F6-08~F6-15 can
be used to select the acceleration/deceleration time and S curve characteristics in speech
segment (multi-speed combination) during the operation of the inverter.
The acceleration time means the time needed for the inverter to accelerate from 0Hz to the
maximum output frequency (F0-05) , t1.
The deceleration time means the time needed for the inverter to decelerate from the maximum
output frequency (F0-05) to 0Hz, t2.
See the following figure.
Output frequency
fmax
Set frequency
Time
frequency change gradually decreases to 0. In the time between T1 and T2, the output
frequency change slope is fixed.
f max
t1 t2 t2 t1 t
Acceleration time Deceleration time
Fig.6-9 schematic diagram of S curve acceleration/deceleration
Therefore, the ME320L series inverter in multi-speed running mode can realize different S
curves in different running time of the elevator by switching the multi-speed combinations, so as
to ensure the reasonable speed change of the elevator and enhance the comfortability.
6.9 Group F8 Keyboard parameters
Leave-factory
F8-00 Input/output terminal status indication none
value
Set range none
F8-00 indicates the input/output terminal status. The nixie tubes on the keyboard are arranged
as 5, 4, 3, 2, 1 from left to right. And the relevant definitions are as follows:
3, 4, 5 are used to indicate the terminal input/output status of the inverter, which is represented
with digital field. 1 adopts digital mode to indicate program running state. 2 is reserved.
The fields of the nixie tubes are as follows:
sequence of Marks on the
Meaning of “ON”
nixie tube nixie tube
1 0 Stop status
1 contactor brake control
2 torque output delay
3 abnormal speed handling
4 normal curve operation
5 reserved
- 86 -
Chapter 6 Parameter Description
- 87 -
Chapter 6 Parameter Description
If the above parameters need to be displayed during the operation, change the binary numbers
in the corresponding position 1 into decimal numbers and set them to F8-01.
F8-02 LED stop indication parameter Leave-factory value 0
Set range 1~255
Cabin load
Input Status
Output status
If the above parameters need to be displayed when the ME320L stops, change the binary
numbers in the corresponding position 1 into decimal numbers and set them to F8-01.
Leave-factory
F8-03 Load speed display coefficient 0.32
value
Set 0.01~100.00
range
The output frequency of the inverter and the load speed are related through this parameter.In
the elevator applications, the users are more familiar with the unit m/s. therefore, this parameter
can be set according to the relevant scale. For example, for the elevator with the speed of
1.600m/s, the maximum output frequency of the traction motor is 50.00Hz, thus F8-03=1600 ÷
5000=0.32.
- 88 -
Chapter 6 Parameter Description
Leave-factory
F8-04 heatsink temperature
value
Set 0.0~100.0ºC
range
It displays the temperature of the heatsink contacting the inverting module IGBT. IGBTs of
different models have different overtemperature protection values, and the ME320L series
inverter has built-in automatic processing programs.
Leave-factory
F8-05 software version no.1
value
Set 0~99.99
range
Leave-factory
F8-06 software version no.2
value
Set 0~99.99
range
F8-05 indicates the software version no. of the control board.
F8-06 indicates the software version no. of the motor.
Leave-factory
F8-07 Set running time 0
value
Set 0~65535h
range
It presets the running time of the inverter.
When the accumulated running time (F8-08) reaches this set running time, the multi-function
digital DO of the inverter outputs the running time reached signal and the inverter stops
running.
If F8-07 is set as 0, this function is inactive.
Leave-factory
F8-08 Accumulated operating time 0
value
Set 0~65535h
range
Leave-factory
F8-09 accumulated timing (in second) 0
value
Set 0~3600s
range
The accumulated operating time is the accumulated operating time of the ME320L series
inverter.
- 89 -
Chapter 6 Parameter Description
Leave-factory
F8-10 high order of running times 0
value
Set 0~9999
range
Leave-factory
F8-11 low order of running times 0
value
Set 0~9999
range
When the ME320L series inverter runs for once in the elevator running mode (non operation
panel control), the running times will be increased by 1.When the low order of the running times
exceeds 9999, it will carry to high order of running times. Therefore, 1 in F8-10 indicates that
the actual running times are 10000.
Ground short circuit protection detection
F8-12 Leave-factory value 0
upon power-up
Set range 0: inactive
1: active
It determines whether the inverter will check if the motor has ground short circuit failure upon
power-up. If this function is active, the inverter has short-time output at the instance of
power-up.
6.10 Group F9 failure and protection
Leave-factory
F9-00 motor overload protection selection 1
value
Set range 0: prohibited
1: allowed
0: The inverter has no overload protection for the motor, and thermal relay is installed before
the motor.
1: The inverter has overload protection function for the motor. For the protection value, refer to
F9-01.
Leave-factory
F9-01 motor overload protection gain 1
value
Set range 0.20~10.00
The overload protection on motor forms an inverse time-lag curve. 150% of the motor rated
current 1 minute; 220% of the motor rated current 1 hour.
This value should be the rated current of the motor/inverter. When the inverter output current
exceeds F9.01× inverter’s rated output current and lasts for a certain period of time, the inverter
will report motor overload failure.
- 90 -
Chapter 6 Parameter Description
Leave-factory
F9-02 motor overload prealarm coefficient 80.0%
value
Set range 50~100%
The reference for this value is the motor overload current. When the inverter detects that the
output current reaches F9.02×motor overload current, it will output prealarm signal from DO or
RELAY.
Leave-factory
F9-03 Overvoltage stall capacity 0
value
Set range 0(no overvoltage stall) ~100
It adjusts the inverter’s capacity in suppressing the overvoltage stall. The bigger the value is,
the stronger the capacity is.
For the load with small inertia, the value should be small. Otherwise, the dynamic response of
the system will be slow.
For the load with large inertia, the value should be large. Otherwise, the suppressing result will
be poor, and overvoltage failure may be caused.
Leave-factory
F9-04 overvoltage stall protection voltage 130.0%
value
Set range 120~150%
Select the protection point for overvoltage stall function. When the value is exceeded, the
inverter starts to execute the overvoltage stall protection function.
Leave-factory
F9-05 Overcurrent stall capacity 20
value
Set range 0~100
It adjusts the inverter’s capacity in suppressing the current stall. The bigger the value is, the
stronger the capacity is.
For the load with small inertia, the value should be small. Otherwise, the dynamic response of
the system will be slow.
For the load with large inertia, the value should be large. Otherwise, the suppressing result will
be poor, and overcurrent failure may be caused.
Leave-factory
F9-06 overcurrent stall protection current 150.0%
value
Set range 100~200%
Select the protection point for overcurrent stall function. When the value is exceeded, the
inverter starts to execute the overcurrent stall protection function.
- 91 -
Chapter 6 Parameter Description
Leave-factory
F9-07 Instantaneous stop non-stop function 0
value
Set range 0: prohibited
1: allowed
It means that the inverter will not stop at the install of power-off. When the power is cut off or the
voltage is reduced suddenly, the inverter will reduce the output speed and compensate the
reduced voltage with the load feedback energy, so as to support the continuous operation of
the inverter in a short time.
instantaneous stop non-stop frequency Leave-factory
F9-08 10.00Hz/s
reduction rate value
Set range 0.00Hz~ maximum frequency/s
It is used to set the value of the reduced output frequency of the inverter when the
instantaneous stop non-stop function is enabled.
If the value is too small, the load feedback energy is not enough to provide effective
compensation for the low voltage.
if the value is too large, the load feedback energy will be too high and cause overvoltage
protection.
Please adjust the parameter according to the load inertia.
Leave-factory
F9-09 Failure auto reset times 0
value
Set range 0~3
It indicates the times for auto reset within 1 hour after the failure when the inverter selects
failure auto reset. If this value is exceeded, the inverter will stop because of failure and wait
for maintenance.
failure relay action selection during failure auto Leave-factory
F9-10 0
reset period value
Set range 0: no action
1: action
After the failure auto reset function is selected, this parameter can be set to determine if it
needs the action of the failure relays needs to shield the failure alarm caused for the continuous
operation of the equipment during the failure reset.
Leave-factory
F9-11 failure auto reset interval 1s
value
Set range 0.1~100.0s
- 92 -
Chapter 6 Parameter Description
The waiting time of the inverter from the failure alarm to auto reset.
Leave-factory
F9-12 input phase loss protection selection 1
value
Set range 0: no protection
1: protection
select whether to provide protection for input phase loss. (applicable to 7.5kW above units only)
Leave-factory
F9-13 output phase loss protection selection 1
value
Set range 0: no protection
1: protection
select whether to provide protection for output phase loss.
Leave-factory
F9-14 The first failure type -
value
Leave-factory
F9-15 The second failure type -
value
Leave-factory
F9-16 the last failure type -
value
Set range 0~24
For details, please refer to chapter 8.
Leave-factory
F9-17 Frequency upon failure -
value
Leave-factory
F9-18 Current upon failure -
value
Leave-factory
F9-19 bus voltage upon failure -
value
It displays the frequency, current and bus voltage of the last failure.
Leave-factory
F9-20 Input terminal upon failure -
value
This value is a decimal number. It displays the status of all the digital terminals of the last failure
in the following sequence:
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
9 8 7 6 5 4 3 2 1 0
DI10 DI9 DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1
When the input terminal is ON, the corresponding value is 1. When the input terminal is OFF,
the value is 0. The bit status can be converted to decimal number, which can be used to check
the status of the digital input signals.
- 93 -
Chapter 6 Parameter Description
Leave-factory
F9-21 Output terminal upon failure -
value
This value is a decimal number. It displays the status of all the output terminals of the last
failure in the following sequence:
BIT4 BIT3 BIT2 BIT1 BIT0
DO2 DO1 REL2 REL1 FMP
When the input terminal is ON, the corresponding value is 1. When the input terminal is OFF,
the value is 0. The bit status can be converted to decimal number, which can be used to check
the status of the digital output signals.
6.11 Group FA PG parameters
The ME320L series inverter may adopt asynchronous motor vector control or permanent
magnetic motor vector control. However, because of the different control principles of the
motors, different rotary encoders (PGs) shall be used. The asynchronous motor may use the
push-pull or open collector type encoder, while the synchronous motor may use the long-cable
driven UVW rotary encoder.
Leave-factory
FA-00 Number of PG pulses 1024
value
Set range 0~65535
In general elevator application, the motor’s rotary encoder is a necessary component. FA-00 is
the number of pulses per revolution of the rotary encoder. During the use, this parameter must
be set correctly. Otherwise, overcurrent may be caused.
Leave-factory
FA-01 PG wire-break detection time 3.0s
value
Set range 0~10.0S
If the PG pulse signal is lost during the operation of the motor, it is impossible to correctly
control the motor. The ME32O series inverter will detect the pulse signal of the rotary encoder
all the time. When the pulse signal abnormality is found to exceed the time setting in FA-01, the
ME320L will immediately generate alarm (PG failure) and stop operation. When the FA-01
setting is less than 2.0s, the alarm function will be cancelled.
Leave-factory
FA-02 PG type selection 0
value
Set range 0: reserved
1: reserved
The output signal of the rotary encoder is the quadrature pulse signal. The inverter can identify
the rotation speed as well as the rotation direction of the motor from the signal. If the wiring of
the rotary encoder is inconsistent with the motor wiring, control overcurrent or PG failure may
- 94 -
Chapter 6 Parameter Description
be caused. If normal operation cannot be realized after correct pulse number of the encoder is
set, exchange the output phase sequence of line A and line B of the encoder.
The judgment of the ME320L inverter on the PG direction can be changed through FA-02. when
wiring inconsistency occurs, the user only needs to change FA-02.
The direction invert of FA-02 is equivalent to the exchange of line A and line B of the actual
rotary encoder.
Leave-factory
FA-03 PG magnetic pole angle 0
value
Set range 0~359.9
When conducting permanent magnetic synchronous motor control, the ME320L series inverter
needs the initial angle of the UVW rotary encoder to judge the rotator position of the motor, so
as to ensure the high-precision control of the directions. The ME320L records the initial angle of
PG through FA-03. The parameter of this function code is set according to the position of the
rotary encoder. If the user knows about the configuration of the system, he may set the
parameter by himself.
Only when this parameter is correctly set can the ME320L series inverter realize the control of
synchronous motor. The control of asynchronous motor does not need this parameter.
Leave-factory
FA-04 current angle of PG 0.0
value
Set range 0~359.9
During the control of permanent magnetic synchronous motor, the UVW encoder will feed back
the rotary position of the motor to FA-04 of the inverter in time. This parameter is a key
parameter for the high-precision control of the permanent magnetic synchronous motor.
The FA-04 has mains loss save function and is only related to the synchronous motor control. It
is unrelated with the asynchronous motor control.
Leave-factory
FA-05 UVW wiring mode 0
value
Set range 0~3(reserved)
FA-05 is only valid for synchronous motor. It indicates the combination mode of the motor
wiring.
6.12 Group FB communication parameters
For details, please refer to Serial Communication Protocol of ME320L.
6.13 Group FC Special enhanced function
Leave-factory
FC-00 Command abnormal action selection 0
value
Set range 0: decelerate to stop
1: Lock output immediately
Command abnormal means that the running command provided to ME320L fails suddenly
- 95 -
Chapter 6 Parameter Description
during the operation of the elevator (see the following figure).Relevant action can be conducted
according to the selection of FC-00. “Decelerate to stop” means to stop according to the normal
logic deceleration, and to maintain stable deceleration without jumping of the elevator speed.
“Lock output immediately” means to close the brake immediately and cut off the operation
contactor output.
FWD REV Command
meaning
OFF OFF inactive
ON OFF Run forward
OFF ON Run reverse
ON ON inactive
Leave-factory
FC-01 Abnormal deceleration time 3.0
value
Set range 0~300.0s
It is to set the time for abnormal deceleration of the inverter.
Leave-factory
FC-02 Ascending frequency detection level 45.00Hz
value
Set range 0.00Hz~ maximum frequency
Leave-factory
FC-03 Descending frequency detection level 45.00Hz
value
Set range 0.00Hz~ maximum frequency
FC-02 and FC-03 are the modes in which the ME320L inverter realizes forced deceleration.
These two function codes are for judgment of the ascending and descending of the elevator
respectively (note: When the inverter receives RUN forward command, the elevator ascends.
When it receives Run reverse command, the elevator descends) At the input instance of the
upward (downward) frequency judgment signal (forced deceleration switch signal), the ME320L
checks if the running frequency of the inverter exceeds the detection level of FC-02(FC-03) . If
it exceeds, the inverter will decelerate to stop according to the time set in FC-01. Besides,
during the ascending period, the downward frequency judgment signal is inactive, and vice
versa.
the principle for the forced deceleration running of the ME320L is shown as the following figure:
- 96 -
Chapter 6 Parameter Description
v
FC-02/
FC-03
FC-01
Upward/downward
forced deceleration ON t
switch
Fig.6-10
Leave-factory
FC-04 Advance door opening judgment 5.00Hz
value
Set range 0.00Hz~ maximum frequency
With ME320L inverter, it is convenient to realize the advance door opening function: During
the normal decelerating operation of the motor, if the output frequency is less than the
parameter set in FC-04, the ME320L inverter will output advance door opening signal through
the output terminal until it stops.
Leave-factory
FC-05 Frequency detection level 1 (FDT level 1) 50.00Hz
value
Set 0.00~ maximum frequency
range
Leave-factory
FC-06 Frequency detection level 2 (FDT level 2) 50.00Hz
value
Set 0.00~ maximum frequency
range
frequency detection hysteresis (FDT Leave-factory
FC-07 5.0%
hysteresis) value
Set 0.0~100.0%(FDT level)
range
As shown in the following figure, FC-05~FC-07 are the relevant parameters of the FDT output
signal. FDT1 and FDT2 may have two different settings.
- 97 -
Chapter 6 Parameter Description
Output frequency
FDT1 Level
FDT1 Hysteresis
Time
Frequency
detection signal
ON
(DO1 and RELAY1 )
Time
Fig.6-11
Leave-factory
FC-08 Frequency arrival detection width 1.00Hz
value
Set 0.00~50.00Hz
range
When the output frequency of the inverter reaches the set frequency value, this function can be
used to adjust the detection amplitude, as shown the following figure.
Output frequency
Set
Detection
frequency
amplitude
Frequency
detection signal Time
(DO1 and RELAY1 )
ON
Time
Fig.6-12
Leave-factory
FC-09 Overspeed judgment level 115%
value
Set range 80~120%
Leave-factory
FC-10 overspeed detection delay 1.0s
value
Set range 0.0~5.0s
FC-11 overspeed action selection Leave-factory 1
- 98 -
Chapter 6 Parameter Description
value
Set range 0: abnormally decelerate to stop
1: generate alarm and lock output immediately
2: continue to run
The ME320L series inverter has overspeed detection function, and it can judge if the running
frequency exceeds the limit according to the function parameter setting of FC-09. If the
accumulated overspeed time exceeds FC-10, it can be considered that it is in overspeed status.
In this way, the ME320L will have corresponding actions according to the function setting of
FC-11. The “abnormally decelerate to stop ” means to decelerate to stop according to the time
of FC-01.
The overspeed judgment level is the percentage of the maximum frequency, i.e. 100%
corresponds to the maximum frequency.
Leave-factory
FC-12 Speed deviation judgment level 30%
value
Set range 0~50%
Leave-factory
FC-13 speed deviation detection delay 1.0s
value
Set range 0.0~5.0s
Action selection for too large speed Leave-factory
FC-14 2
deviation value
Set range 0: abnormally decelerate to stop
1: generate alarm and lock output immediately
2: continue to run
The ME320L series inverter has speed deviation detection function, and it can judge if the
current running speed and frequency deviation are too large according to the function
parameter setting of FC-12. If the accumulated time with too large deviation exceeds FC-13, it
can be considered that it is in the status with too large speed deviation. In this way, the ME320L
will have corresponding actions according to the function setting of FC-14. The “decelerate to
stop upon abnormal situation” means to decelerate to stop according to the time of FC-01.
The speed deviation judgment level is the percentage of the maximum frequency.
braking and running time sequence Leave-factory
FC-15 0
selection value
Set 0: Output running signal first, and then output braking control
range 1: Output braking control first, and then output running signal
In general, the elevator-specific inverter will output zero speed running before opening the
brake. In this way, at the instance of brake opening, the motor excitation has been completed,
which can effectively avoid the carriage rolling upon startup. However, since some elevator
traction motors have too long braking action time, if there is pre-torque output at this time,
- 99 -
Chapter 6 Parameter Description
Vb
V1
f1 fb Output frequency
- 100 -
Chapter 6 Parameter Description
Leave-factory
FD-02 slip compensation 100.0%
setting
Set range 0.0%~200.0%
Leave-factory
FD-03 oscillation suppression gain 20
setting
Set range 0~100
The FD-02 slip compensation is valid for V/F control. The V/F control slip caused by the load
can be compensated by setting this parameter, so that the motor running speed will decrease
following the decrease of the load change for V/F control. In general, 100% corresponds to the
rated slip of the motor with rated load. The following principles shall be observed for slip
coefficient adjustment: When the load is rated load, and the slip compensation coefficient is
set as 100%, the rotation speed of the motor is close to the reference speed. If the load is less
than the rated load, the coefficient can be less than 100%. If the load is more than the rated
load, the coefficient can be larger than 100%.
FD-03 indicates the oscillation suppression gain. When the motor has no oscillation, set this
parameter as 0. Only when the motor has obvious oscillation and does run normally can the
gain be properly increased. The bigger the gain is, the better oscillation suppression result will
be. Parameter Setting method: The value should be as small as possible while effective motor
oscillation suppression shall be ensured.
6.15 Group FP user shortcut parameters
Leave-factory
FP-00 user password 0
value
Set 0~65535
range
Any non-zero number can be set, and then the password protection function will be enabled.
00000: clear the password set by the previous users and disable the password protection
function.
After the user password is set and enabled, when the user enters the parameter setting status
again, if the password is incorrect, he cannot view or modify the parameters. Please keep your
password in mind. If you set the password mistakenly or forget the password, please contact
the manufacturer.
Leave-factory
FP-01 parameter initialization 0
value
Set 0: no operation
range 1: Restore to leave-factory set value
2: clear the failure record
- 101 -
Chapter 6 Parameter Description
- 102 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
DI 1 FWD
DI 2 REV
DI 3
Multi-speed
PG
DI 4
DI 5 combination
Command COM
reference
Speed F M
RUN ready
reference DO 1 Zero-speed signal
CME
Elevator controller
Failure output
RELAY 1
RELAY 2
DI 6 Failure reset
DI 7
Enable signal
- 103 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
F1-00=0
Select asynchronous
motor
In the static tuning, the motor does In the dynamic tuning, the motor is
not run, with howling noise generated. running. The parameters obtained i
The parameters obtained in the tuning: n the tuning: F1-06,F1-07,F1-08,
F1-06,F1-07,F1-08,F1-09,F1-10 F1-09,F1-10.
can be got through auto calculation.
Fig.7-2
- 104 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
2) Maintenance operation
When the commissioning of the elevator enters maintenance operation stage, the inverter shall
be set before the maintenance operation:
A. If it runs in the closed-loop status, set FA-00 as the corresponding pulse count. If it runs in
the open-loop status, set as F0-00=0.
B. The corresponding frequency of maintenance speed combination (Set one parameter in
F6-00~F6-07 according to the speed combination adopted by the system, such as F6-0N )
C. The corresponding curve of maintenance operation (Set F6-M, M=N+8, and range from 1 to
4)
D. Acceleration/deceleration time of maintenance operation (Set the corresponding
acceleration/deceleration time according to the selected curve. The set value is determined by
elevator speed).
Note: If the system wires the inverter through adding expansion card, or the terminal function is
not consistent with the schematic diagram, please set the corresponding parameters of F4 and
F5 before the maintenance operation.
3) Acceleration operation
When the elevator enters acceleration commissioning stage, the commissioning of the inverter
shall consider if it is comfortable to use the elevator. The parameters are set as follows:
A. Confirm that the drive and encoder is well connected and the pulse count of FA-00 PG is
correctly set, and ensure that F0-00=1 has speed sensor vector control.
B. Set all frequencies of corresponding speed combination.
C. Set the corresponding curves of all frequencies. (It is recommended to use curve 1 for
acceleration operation. If there are several speeds in the acceleration operation, it is
recommended to be used in the min speed.))
D. On the basis of comfortable feeling, set acceleration/deceleration time of each curve and the
time of start/end segments of the curve.
E. Adjust F2 and F3 parameters according to the comfortable feeling of operation and
start/stop.
4) Application example
For example, Fig.7-1, if the elevator adopts 1m/s, multi-speed 2 as maintenance, 3 as creep, 7
as high-speed, no weighing device, the final set parameters(List parameters that are different
from the leave-factory ones, excluding the motor parameter):
Function Name Set Function Name Set Function Name Set
code value code value code value
- 105 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
- 106 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
FP-01= 1
Recover leave-
factory parameter
Fig. 7-3
2) Maintenance operation
When the commissioning of the elevator enters maintenance operation stage, the inverter shall
be set before the maintenance operation:
A. Before the operation, please confirm the encoder wiring and inverter output to U, V and W
phases of motor side have not changed the sequence after the finish of motor auto-learning.
B. The corresponding frequency of maintenance speed combination (Set one parameter in
F6-00~F6-07 according to the speed combination adopted by the system, such as F6-0N )
C. The corresponding curve of maintenance operation (Set F6-M, M=N+8, and range from 1 to
4)
D. Acceleration/deceleration time of maintenance operation (Set the corresponding
acceleration/deceleration time according to the selected curve. The set value is determined by
elevator speed).
Note: If the system wires the inverter through adding expansion card, or the terminal function is
- 107 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
not consistent with the schematic diagram, please set the corresponding parameters of F4 and
F5 before the maintenance operation.
3) Acceleration operation
When the elevator enters acceleration commissioning stage, the commissioning of the inverter
shall consider if it is comfortable to use the elevator. The parameters are set as follows:
A. Before the operation, please confirm the encoder wiring and inverter output to U, V and W
phases of motor side have not changed the sequence after the finish of motor auto-learning.
B. Set all frequencies of corresponding speed combination.
C. Set the corresponding curves of all frequencies. (It is recommended to use curve 1 for
acceleration operation. If there are several speeds in the acceleration operation, it is
recommended to be used in the min speed.))
D. On the basis of comfortable feeling, set acceleration/deceleration time of each curve and the
time of start/end segments of the curve.
E. Adjust F2 and F3 parameters according to the comfortable feeling of operation and
start/stop.
4) Application example
For example, Fig.7-1, if the elevator adopts 1m/s, multi-speed 2 as maintenance, 3 as creep, 7
as high-speed, no weighing device, the final set parameters(List parameters that are different
from the leave-factory ones, excluding the motor and PG parameter):
Function Set Function Set Function
Name Name Name Set value
code value code value code
- 108 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
segment
time of S
curve 1
F7-03 End
segment
time of S
curve 1
Note: For emergency leveling function of synchronous motor, refer to section 7.4.
7.2 Analog Control Mode
There is another common mode for ME320L series inverter application in elevator: Analog
speed reference.In the control mode, the speed reference of inverter adopts analog input,
running command adopts terminal input. The following is the simple introduction to the control.
7.2.1 Wiring Diagram of Analog Control System
K1
R
S ME320 Elevator Specific Inverter
U
T V M
W
AI1 Analog
COM input PG
Speed
DI 1 FWD
Failure signal
reference
DI 2 REV
TA
DI 3 Enable signal
Elevator DI 4
Failure reset TB
controller COM
DO 1
Zero-speed signal
F M RUN ready
CME
Fig.7-4
7.2.2 Parameter Setting
In the analog controlled system, as an executor, inverter completely follow the command of
controller. As the use of the above diagram, assume that the analog input signal is from 0 to
+10V input, the parameters needed to be adjusted are as follows:
- 109 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
- 110 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
K1
R
combination
Multi-speed
DI 3
Failure output
DI 4
DI 5 TA
COM
Elevator TB
controller
DO 1 Zero-speed signal
F M RUN ready
CME
Fig. 7-5
7.3.2 Parameter Setting and Operation Curve Diagram
As a special operating situation, there is strict national standard requirement for maintenance
operation. It is operation curve is greatly different from the acceleration operating of elevator.
In the multi-speed control mode, if the maintenance input is effective, ME320L series drive will
judge the maintenance operation speed according to F6-16 function code set. For example, If
F6-16=3, the elevator receives forward(reverse) running command and there is maintenance
input terminal signal, ME320L will run at the target frequency of multi-speed 3. The acceleration
time is determined according to the corresponding time of multi-speed 3. During the stop
process, if remove the maintenance input signal first, the system will reduce the speed to 0
according to the speed-reduction time of multi-speed 3 until the removal of forward/reverse
command(As shown in the diagram, the speed reduction time can be very short during the
speed-down process, such as 1s, which is able to ensure fast stop).
- 111 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
Forward
(reverse)
running
Maintenance
command
Fig 7-6
If directly remove the forward/reverse command during the maintenance operation, ME320L
will stop output immediately.as shown in the following figure.
Forward
(reverse)
running
Maintenance
command
Fig.7-7
It is assumed that the speed of the elevator is 1m/s, the maintenance operation adopts
multi-speed 5 with acc./dec. time 4 setting, the set maintenance operation speed parameters
are as follows:
- 112 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
- 113 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
K3
Battery
K1
R1
R
S1
S U
T1
N1 T V M
N W
K2
RO
UPS
TO
ME320L
Power input
Battery operation
FWD
Elevator controller REV
Fig.7-8
7.4.2 Operation sequence
In the multi-speed combination mode, ME320L performs the wiring according to the above
diagram, wherein, DO1 is the port of normal bus output. Adopt multi-speed combination 2 as
the emergency operation speed combination. Therefore, in the multi-speed control mode, it is
necessary to set the following function code:
Function Set Leave-factory
Name Remark
code value value
F5-01 DO1 output selection 8 3 Under-voltage of bus
Rated motor speed:
F6-02 Multi-speed 2 2. 00Hz 0.00Hz
50.00Hz
Multi-speed 2
acceleration/
F6-10 3 1
deceleration time
selection
Lengthen the acceleration
F7-08 Acceleration time 3 30.0s 20.0s time to avoid over impulse
current
Take the up-direction as an example, the operation sequence is as follows:
- 114 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
AC power
Motor speed
K1
K2、K3
FWD/REV
Multi-speed 5 2
combination
Inverter voltage:
normal
Leveling signal
Battery running 5s 3s
Battery power
DC bus voltage
Fig.7-9
The operation signal of battery is the one provided by elevator controller, which is connected to
ME320L through DI terminal to judge whether the current operation is battery operation.
Contactor K1, K2 and K3 are controlled by elevator controller.
7.4.3 Precautions
1. Reasonably set the operation speed, battery operation acc./dec. time according to the
practical situation of the elevator. It is recommended that the acc./dec. time shall be over 10s.
Set the battery operation speed according to the following formula:
Battery operation speed <(48V-5V)* motor rated frequency/(1.414*rated voltage)
2. Input DC voltage 48V to main circuit through battery and input operation power through
auxiliary power, such as UPS.
3. It is recommended that the stable output current of the battery shall be over the no-load
current of traction machine.
4. ME320L judges whether it is the battery operation according to input terminal(DI). At the
moment, the operation speed of ME320L is multi-speed, and the corresponding acc./dec. time
of multi-speed is the acc./dec. time of battery. The part that is different from the normal
operation: During the operation process of battery, curve acc./dec. are straight line acc./dec.;
5. During the battery operation process, ME320L inverter will not perform DC bus voltage test.
Therefore, when opening the brake, ensure that ME320L inverter main circuit has input 48V
voltage.
6. During the battery operation process, ME320L will monitor the speed. If the speed is over
8Hz, failure protection (E032) is required.
7. When the battery is operating, the drive load operation shall be avoided. Therefore, the outer
- 115 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
Load
percentage
of cabin
0
100%
-B
Fig.7-10
As shown in the above figure, set F3-10 as 50% and perform no-load auto-learning under the
no-load situation of the carriage; then move the elevator up and down and adjust F3-11,
observe whether there is carriage rolling when the brake starts the motor suddenly. If there is
no carriage rolling or over-torque compensation when the elevator moves up/down caused by
- 116 -
Chapter 7 Application and Commissioning of ME320L Series
Elevator-Specific Inverter
the motor torque compensation, take down F3-11=B; Apply full-load to the carriage and perform
full-load auto-learning, move the elevator up and down and adjust F3-11, if the compensation is
proper, take down F3-11=A.
In the diagram, it shows the slanting line is the correct compensation curve of the elevator. The
point for the curve to pass through the horizontal axis is the balanced compensation point of the
elevator, which corresponds with the balanced coefficient of the elevator. On the basis of the
above test, calculate:
F3-10=100*B/(A+B) , F3-11=(A+B) /2,
For example, if it is B=0.7 in the no-load test, A=0.4 in the full-load test, the corresponding
balanced coefficient shall be set as F3-10=36.4%, F3-11=0.55.
7.5.3 Commissioning under Different Operating Directions
If it is set that the forward running corresponds with down movement, the reverse running
corresponds with up movement on the site, the above method will make the compensation
worse. Because the compensation direction is wrong. Under this situation, record sampling
value F3-18, F3-19 when the carriage is no-load and full-load and the balanced coefficient
F3-10, such as: F3-18=X,F3-19=Y,F3-10=Z, then, F3-19=X,F3-18=Y,F3-10=100-Z
- 117 -
Chapter 8 Failure Diagnosis and Solution
- 118 -
Chapter 8 Failure Diagnosis and Solution
Display of
Failure
operation Possible failure cause Treatment
description
panel
4. The PG interference is too 4. Select proper PG and shield
big; PG line;
1. Over high input voltage
1. Adjust input voltage;
2. Severe anti-movement of
2. Adjust the start sequence of
elevator;
acceleration elevator;
Err05 3. The brake resistor is too big,
overvoltage 3. Select proper brake
or the brake unit is abnormal;
resistor;
4. The acceleration curve is
4. Adjust the curve parameter;
too steep;
1. Over high input voltage
1. Adjust input voltage;
2. The brake resistor is too big,
deceleration 2. Select proper brake
Err06 or the brake unit is abnormal;
overvoltage resistor;
3. The deceleration curve is
3. Adjust the curve parameter;
too steep;
Constant 1. Over high input voltage 1. Adjust input voltage;
Err07 speed 2. The brake resistor is too big, 2. Select proper brake
overvoltage or the brake unit is abnormal; resistor;
1. Over high input voltage 1. Adjust input voltage;
control power
Err08 2. Abnormal drive control 2. Please contact the agent or
supply failure
board; manufacturer;
1. Sudden power-off of input
1. Eliminate the external
power
undervoltage power problem;
Err09 2. Over low input voltage
failure 2. Please contact the agent or
3. Abnormal drive control
manufacturer;
board;
1. Check brake circuit and
inverter 1. Abnormal brake circuit;
Err10 power supply;
overload 2. Overload;
2. Reduce the load;
1. improper setting of F9-01; 1. Adjust parameter;
motor
Err11 2. Abnormal brake circuit; 2. Check brake circuit and
overload
3. Overload; power supply;
Input phase 1. Asymmetric input power; 1. Adjust input voltage;
Err12 lose 2. Abnormal drive control 2. Please contact the agent or
protection board; manufacturer;
Err13 Output phase 1. Wiring loose of main circuit 1. Check the wiring;
- 119 -
Chapter 8 Failure Diagnosis and Solution
Display of
Failure
operation Possible failure cause Treatment
description
panel
lose output; 2. Eliminate motor failure;
protection 2. Damage of motor;
1) ambient over-temperature: 1. Lower ambient temperature
heatsink
Err14 2. Damage of fan; 2. Clear ventilation;
overheat
3. Blockage of ventilation; 3. Replace fan;
external Check whether the elevator
Err15 Elevator controller failure
failure controller works normally
Communicati
Err16
on failure
Err17 reserved
Current
Please contact the agent or
Err18 detection Abnormal drive control board;
manufacturer;
failure
1. Wrong setting of motor
1. Enter correct motor
motor tuning parameter;
Err19 parameter;
failure 2. Overtime of parameter
2. Check motor lead wire;
tuning;
1. Whether PG models are 1. Select PG with push-pull
Err20 PG failure matched; output or open collector;
2. PG connection wrong; 2. Eliminate wiring problem;
rotary
Err21 encoder
failure
Err22 reserved
Check whether the motor or
Short circuit output side contactor are short
Err23 protection to Output short circuit to ground; circuit to ground;
ground Please contact the agent or
manufacturer;
Data storage
Err25
failure
Check whether the battery
Battery
The battery speed is over 8Hz voltage is correct;
Err32 running
during the running process Check whether the wire is
overspeed
loose;
- 120 -
Chapter 8 Failure Diagnosis and Solution
Display of
Failure
operation Possible failure cause Treatment
description
panel
1. Check whether the power of
The speed of inverter passes the motor is matched;
Overspeed the overspeed judgment level 2. Check whether the elevator
Err33
failure and the total time is over the is over loaded;
overspeed judgment time. 3. Check whether the rotary
encoder signal is correct;
1. Check whether the
When open the brake, the contactor contact and
motor current is zero; feedback contact are normal
If the elevator continues to run 2. Check whether the output
contactor
Err36 1s, the feedback signal of the U, V and W of the elevator
failure
contactor will loose; integrated controller is normal;
There is no feedback signal 3. Check whether the control
after the close of the contactor; circuit power of contactor is
normal;
1. Check whether the brake
coil and feedback contact are
normal;
The brake output and 2. Confirm the signal features
Err37 Brake failure feedback signal interval is over of the feedback contact(N.O.,
2s. N.C.);
3. Check whether the control
circuit power of brake coil is
normal;
when stopping, the feedback Check the wiring;
Contact
signal for contactor braking Check contactor braking and
Err38 Conglutinatio
and running will continued to running;
n
be over 2s.
1. Check whether the motor is
motor
Motor over-temp, effective properly used or damaged;
Err39 overtemperat
relay input 2. Improve the cooling
ure
condition of motor
The running 1. The elevator runs too slow
Setting time of elevator
Err40 condition of or the building is too high;
running is up
elevator 2. The operation time of the
- 121 -
Chapter 8 Failure Diagnosis and Solution
Display of
Failure
operation Possible failure cause Treatment
description
panel
cannot be elevator is too long,
met. maintenance is required;
- 122 -
Warranty Agreement
The warranty period of the product is 18 months(refer to the barcode of the equipment body).
During the warranty period, if the product fails or is damaged under the condition of normal use
by following the instruction, Our company will be responsible for free maintenance.
Within the warranty period, maintenance will be charged for the damages caused by the
following reasons:
a. The damage caused by improper use or repair/modification without prior permission;
b. The damage caused by fire, flood, abnormal voltage, other disasters and second disaster;
c. The damage caused by dropping or transportation after the purchase;
d. The damage caused by the improper operation;
e. The damage or failure caused by the trouble out of the equipment(e.g. external device)
If there is any failure or damage to the product, please correctly fill out the Product Warranty
Card in detail.
The maintenance fee is charged according to the newly adjusted Maintenance Price List by our
company.
In general, the warranty card will not be re-issued. Please keep the card and present it to the
maintenance personnel when asking for maintenance.
If there is any problem during the service, please contact the agent of our company or our
company directly.
The final explanation of the agreement belongs to MCTC.
MCTC(service department)
Add. Of unit:
Customer Name of unit: Contact person:
information P.C.: Tel.:
Product Product model:
information Body barcode(Attached it here):
Name of agent:
Failure (Maintenance time and content):
information Maintenance personnel:
Daily Note:
Function Set Function Set Function Set Function Set
code value code value code value code value
F - F - F - F -
F - F - F - F -
F - F - F - F -
F - F - F - F -
F - F - F - F -
Date:
Add.: