Design of Reinforced Concrete: University of Wasit-College of Engineering Civil Engineering Department
Design of Reinforced Concrete: University of Wasit-College of Engineering Civil Engineering Department
THIRD CLASS
2017-2018
Design of Reinforced Concrete Lec.1 Introduction
Syllabus:
Syllabus Semester
Introduction 1st
Materials 1st
Flexural Analysis & Design of Beams (Working Stress Design Method) 1st
Flexural Analysis & Design of Beams (Ultimate Strength Design
1st
Method)
Shear & Diagonal Tension in Beams 1st
Analysis & Design of Torsion 1st
Bond, Anchorage & Development Length 1st
Units
SI Metric British
N gm lb
Force kN = 1000 N kg = 1000 g kip = 1000 lb
1 kg = 9.81 N Ton = 1000 kg 1 lb = 4.448 N
mm cm in
Length m = 1000 mm cm = 10 mm ft = 12 in (˝)
mm = 0.1 cm m = 100 cm 1 in = 25.4 mm
Force N gm lb
Stress Pa psi
Area m 2 cm 2 in 2
kN kg kip
Stress kPa ksi 1000 psi
m2 cm 2 in 2
N Ton
MPa
mm 2 m2 1ksi 6.895 MPa
3
Kilo Pascal = kPa = 10 Pa
Mega Pascal = MPa= 106 Pa
Gega Pascal = GPa = 109 Pa
Tera Pascal = TPa = 1012 Pa
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 1
Design of Reinforced Concrete Lec.1 Introduction
Fundamentals
Whenever two different materials, such as steel and concrete, are acting together it is
understandable that the analysis for strength of a reinforced concrete member has to be partial
empirical although rational. These semi-rational principles and methods are being continuously
revised and improved as a result of theoretical and experimental research accumulates. The
American Concrete Institute (ACI) serves as clearing house for these changes and issues
building code requirements.
Design Philosophy:
In the strength method, the service loads are increased sufficiently by factors to obtain the load
at which failure is considered to be “imminent”. This load is called the factored load or
factored service load.
strength required to
strength provided
carry factored loads
The provided strength is computed in accordance with rules and assumptions of behavior
prescribed by the building code and the strength required is obtained by performing a structural
analysis using factored loads.
The “strength provided” has commonly referred to as “ultimate strength”, however, it is a code
defined value for strength and not necessarily “ultimate”. The ACI Code uses a conservative
definition of strength.
Safety Provisions:
Structures and structural members must always be designed to carry some reserve load above
what is expected under normal use.
There are three main reasons why some sorts of safety factor are necessary in structural design.
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 2
Design of Reinforced Concrete Lec.1 Introduction
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 3
Design of Reinforced Concrete Lec.1 Introduction
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 4
Design of Reinforced Concrete Lec.1 Introduction
Figure (4) Construction of footings shown in Figure (3) (Note that dowels of columns from
footings should be included in this stage)
Figure (6) Columns of ground floor on footing with tie beams and different shapes of columns
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 5
Design of Reinforced Concrete Lec.1 Introduction
Figure (7) Illustration of beams of ground floor (Note that beams are cast monolithically with
slabs)
Figure (8) Illustration of floor slab of ground floor (Note that beams are cast monolithically with
slabs as one continuous system and that dowels of the above level columns should be included in
this stage)
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 6
Design of Reinforced Concrete Lec.1 Introduction
Figure (10) Illustration of floor slab of first floor (Note that beams are cast monolithically with
slabs as one continuous system and that dowels of the above level columns should be included in
this stage)
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 7
Design of Reinforced Concrete Lec.1 Introduction
Figure (12) Illustration of roof slab (Note that beams are cast monolithically with slabs as one
continuous system)
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 8
Design of Reinforced Concrete Lec.1 Introduction
Under gravity loads, slabs are mainly designed for flexure and shear. Shear should be carried out
by the concrete section only (except special cases of flat slabs with high punching stresses),
while the flexure is designed to be carried out by both the concrete section and the reinforcing
steel. The amount of required reinforcement depends mainly on the amount of the applied loads
on the slab and hence on the applied bending moment, while the distribution of reinforcement
depends on the boundary conditions, i.e. the degree of restraint at each end of the slab. Figure
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 9
Design of Reinforced Concrete Lec.1 Introduction
(13) illustrates an example of the formwork and reinforcement of a slab panel and its
corresponding edge beam. As shown, the reinforcement of the slab is distributed as a grid of
bars along the two directions.
Beams are designed to resist three main loading types; flexure, shear, and torsion. The flexural
reinforcement are distributed longitudinally as number of bars at the bottom and top of the
section as shown in Figures (14) to (16). To resist shear forces, the beam is reinforced with
vertical bars (U-shape or closed) called “stirrups” as clearly shown in Figure (14) and Figure
(15). On the other hand, resistance of twist from the torsional moment requires both stirrups and
longitudinal bars.
Columns are subjected to axial compression loads with or without bending moments. Therefore,
columns main reinforcement composes of vertical bars distributed either on two sides or on all
sides of the section. Moreover, sufficient lateral reinforcement should be provided to resist any
possible shearing forces. This reinforcement is similar to the stirrups of beams; however, it is
called “ties” instead. Spirals maybe used also as lateral reinforcement in circular columns.
Figures (14) and (16) show the vertical and lateral reinforcement of columns.
Footings are generally designed as slabs with inverted loads. Note that the word footing in this
text lecture refers to shallow foundations only. In general, footing design is not included in this
course. Students are to take lectures to design the different types of foundations in the fourth
class.
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 11
Design of Reinforced Concrete Lec.1 Introduction
Figure (16) Picture of the formwork of slab-beam system and the reinforcements of slab, beams,
and a column
Asst. Prof. Dr. Sallal R. Abid Wasit University - Civil Engineering Department. 11