Tpsada: Digital Autozero & Span Option

The TPSADA pressure transmitter features digital autozero and autospan functions. It allows for coarse and fine magnetic autozeroing as well as calibration signal generation and partial or total reset functions. The autozero and autospan processes can be activated simply by touching the sensor body with a magnetic pen and take only a few seconds to complete without opening the instrument.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views2 pages

Tpsada: Digital Autozero & Span Option

The TPSADA pressure transmitter features digital autozero and autospan functions. It allows for coarse and fine magnetic autozeroing as well as calibration signal generation and partial or total reset functions. The autozero and autospan processes can be activated simply by touching the sensor body with a magnetic pen and take only a few seconds to complete without opening the instrument.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TPSADA

DIGITAL AUTOZERO & SPAN OPTION

Main Features

• Coarse Magnetic Autozero


• Fine Magnetic Autozero
• Calibration Signal 80% FS
• Magnetic Autospan
• Partial reset function
• Total reset function

Digital “Autozero & Span” option makes the pressure transmit-


ter TPSA Series a product extremely innovative and versatile.
Designed thanks to the advanced electronics used by TPSA,
this function allows zero and span adjustment in a simple, fast
and reliable way, avoiding to use analogue trimmer, potential
weak point and source of possible drifts or failures. The starting
is user friendly, simply touching the specific target marked on
the sensor body with a pen with magnetic head (included as
standard). Within few seconds the operation is concluded,
without the need to dismantle or to open the instrument.

TECHNICAL DATA
Autozero ±10%FS max with zero setting within the sensor accuracy class, @ °T Amb.
Autozero Setting Time 1…10 seconds
Fine Autozero Adjustment Resolution 6 mV (voltage output); 12 µA (current output)
Fine Autozero Adjustment Amplitude ±100 mV (voltage output), ±0.16 mA (current output) by successive steps with
maximum setting time 5 sec. per step
Calibration Function Signal output generation of 80% FS @ °T Amb.
Calibration Function Setting Time >1 sec. (by contacts closed in CAL position)
Autospan ±5%FS max with span setting within the sensor accuracy class, @ °T Amb.
Autospan Setting Time 1…10 sec. (by contacts closed in CAL position)
Partial Reset Restore of zero factory setting
Partial Reset Setting Time 30…60 sec
Total Reset Restore of complete factory setting
Total Reset Setting Time >60 sec
Function Activation By pen with magnetic head (PKIT 312)

INSTALLATION DRAWINGS
89
Dimensions: mm [inches]
[3.504]
Ch 22
[0.709]
[1.043]
ø 26.5

G 1/4

ø 18

15 2 12
[0.591] [0.079] [0.472]
L = 75
[2.95]
Dimensions: TPSADA, due to the autozero & span board, is 5 mm (0.197 in) longer, so dimension “L” on TK data sheet
becames 75 mm (2.95 in).

CAL function pin: The activation of CAL function (Calibration and Autospan) is made by closing the contact between the
following pin: - 6 pole connector version (V) pin E-F
- 7 pole connector version (P) pin 5-6

Please refer to the standard data sheet for all the remaining mechanical and electrical specifications.

SensorsONE Ltd [email protected] www.SensorsONE.co.uk


ORDERING INFORMATION

Pressure transmitter TPSADA

OUTPUT SIGNAL
Standard Mechanical and/or electrical characteristics
differing from standard may be arranged on
0.1 .. 10.1 Vdc C request.
4 .. 20 mA E
0 .. 10 Vdc N
On request RESPONSE TIME
0.1 .. 5.1 Vdc B V Fast (< 1 msec)
0 .. 5 Vdc M
1 .. 5 Vdc P ACCURACY
1 .. 10 Vdc Q T ± 0.1% FSO typical ≥100bar/1500psi
1 .. 6 Vdc R ± 0.15% FSO typical <100bar/1500psi

PRESSURE CONNECTION
MEASUREMENT RANGE
Standard
bar psi
G 1/4 gas male 1
B05D 0..50 P75D 0..750
On request
7/16-20 UNF-2A male B01C 0..100 P15C 0..1500
2
(SAE 4 for AS4395-E) B16D 0..160 P20C 0..2000
G 1/2A (DIN 16288) 3 B02C 0..200 P25C 0..2500
G 1/4 gas female 4 B25D 0..250 P03M 0..3000
1/8-27 NPT female 5 B35D 0..350 P05M 0..5000
1/4-18 NPT female 6 B04C 0..400 P75C 0..7500
1/4-18 NPT male 7 B05C 0..500 P10M 0..10000
M14 x 1.5 male B06C 0..600 P15M 0..15000
8
B07C 0..700
1/8-27 NPT male 9
G 1/4 male (DIN 3852-E) B01M 0..1000
E
M12 x 1.5 male R CALIBRATION STANDARDS
7/16-20 UNF-2A male Instruments are calibrated against precision
(SAE 4 for J1926-2) (*)
K
pressure calibration equipment which is
7/16-20 UNF-2A female traceable to International Standards.
(SAE 4)
F

(*) Max. working pressure:


630 bar (9137 psi)

ELECTRICAL CONNECTION
4-pole connector solenoid E (°)
shielded cable F (°)
4-pole connector Z (°)
4-pole connector microsolenoid M (°)
7 pole connector P
6 pole connector V

(°) With this kind of connector is availa-


ble the “Autozero” function only.

Ex.: TPSADA - N - 1 - P - B35D - T - V


Pressure transmitter TPSA digital autozero & span, 0...10Vdc output signal, G 1/4 male pressure connection, 7 pole connector,
0...350 bar measurement range, ± 0.1% FSO accuracy, 1msec response time.

cod. TPSADA - 04/06

SensorsONE Ltd [email protected] www.SensorsONE.co.uk