This document provides the design data for the hydraulic fire protection calculation of the Schlumberger OFS Base Dhahran project. It specifies an occupancy classification of light hazards for an area of 1500 square feet. A minimum residual pressure of 20 psi is required at the design flow. The average protection area per sprinkler is 100 square feet based on a 10 foot spacing. A total of 15 sprinklers need to be calculated. The fire hose cabinets have a total design water capacity of 100 gpm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
827 views1 page

Hydraulic Fire Protection Calculation: Schlumberger OFS Base Dhahran

This document provides the design data for the hydraulic fire protection calculation of the Schlumberger OFS Base Dhahran project. It specifies an occupancy classification of light hazards for an area of 1500 square feet. A minimum residual pressure of 20 psi is required at the design flow. The average protection area per sprinkler is 100 square feet based on a 10 foot spacing. A total of 15 sprinklers need to be calculated. The fire hose cabinets have a total design water capacity of 100 gpm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

HYDRAULIC FIRE PROTECTION CALCULATION

NAME OF PROJECT : Schlumberger OFS Base Dhahran


DATE : November 10, 2020
DESIGN BY : RCMANGILIT

DESIGN DATA

OCCUPANCY CLASSIFICATION = Light Hazards


CALCULATED AREA = 1500 sq. ft.
MINIMUM RESIDUAL PRESSURE AT DESIGN FLOW = 20 psig (as per SAES-B-017, section 5)
AVERAGE PROTECTION AREA PER SPRINKLER :
Distance from sprinkler head to next sprinkler head, S = 10 ft
Distance perpendicular to sprinkler head on branch line, L = 10 ft
SPRINKLER COVERAGE AREA = 100 sq.ft.
TOTAL NO. OF SPRINKLERS TO CALCULATE = 15 pcs.
NO. OF SPRINKLERS TO CALCULATE ON A BRANCH LINE = 5 pcs.
FIRE HOSE CABINET :
No. of fire hose cabinet = 2 pcs.
Fire hose cabinet total design water capacity = 100 gpm (NFPA 13, Section 5-2.3 & 5-2.3.1.3)

5 4

6 15 24 3

14 23 32 33
FHC
7 16 25
50 gpm
2
13 22 31

8 17 26

12 21 30

9 18 27
34
1 20 29
1

FHC
10 19 28
50 gpm
35

Fire Water line pipe riser from first floor 1

LEGEND:

Lateral pipe reference point no.

Sprinkler Head

NOTES: Fire Hose Cabinet

1. This drawing shall be read with the attached computer calculation sheets. Pipe Riser
2. References are NFPA 13, 1999 Edition, NFPA 14, 2000 Edition.

rcm 11/10/2020 498577418.xls