IEC 61968-9

®
Edition 2.0 2013-10
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

INTERNATIONAL
STANDARD
NORME
INTERNATIONALE colour
inside

Application integration at electric utilities – System interfaces for distribution


management –
Part 9: Interfaces for meter reading and control

Intégration d'applications pour les services électriques – Interfaces système


pour la gestion de distribution –
Partie 9: Interfaces pour le relevé et la commande des compteurs
IEC 61968-9:2013
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright © 2013 IEC, Geneva, Switzerland
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les
microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11


3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 [email protected]
Switzerland www.iec.ch

About the IEC


The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.

Useful links:

IEC publications search - www.iec.ch/searchpub Electropedia - www.electropedia.org


The advanced search enables you to find IEC publications The world's leading online dictionary of electronic and
by a variety of criteria (reference number, text, technical electrical terms containing more than 30 000 terms and
committee,…). definitions in English and French, with equivalent terms in
It also gives information on projects, replaced and additional languages. Also known as the International
withdrawn publications. Electrotechnical Vocabulary (IEV) on-line.

IEC Just Published - webstore.iec.ch/justpublished Customer Service Centre - webstore.iec.ch/csc


Stay up to date on all new IEC publications. Just Published If you wish to give us your feedback on this publication
details all new publications released. Available on-line and or need further assistance, please contact the
also once a month by email. Customer Service Centre: [email protected].

A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.

Liens utiles:

Recherche de publications CEI - www.iec.ch/searchpub Electropedia - www.electropedia.org


La recherche avancée vous permet de trouver des Le premier dictionnaire en ligne au monde de termes
publications CEI en utilisant différents critères (numéro de électroniques et électriques. Il contient plus de 30 000
référence, texte, comité d’études,…). termes et définitions en anglais et en français, ainsi que
Elle donne aussi des informations sur les projets et les les termes équivalents dans les langues additionnelles.
publications remplacées ou retirées. Egalement appelé Vocabulaire Electrotechnique
International (VEI) en ligne.
Just Published CEI - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications de la CEI.
Just Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur
Disponible en ligne et aussi une fois par mois par email. cette publication ou si vous avez des questions
contactez-nous: [email protected].
IEC 61968-9
®
Edition 2.0 2013-10
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

INTERNATIONAL
STANDARD
NORME
INTERNATIONALE colour
inside

Application integration at electric utilities – System interfaces for distribution


management –
Part 9: Interfaces for meter reading and control

Intégration d'applications pour les services électriques – Interfaces système


pour la gestion de distribution –
Partie 9: Interfaces pour le relevé et la commande des compteurs

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION

COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE PRICE CODE
CODE PRIX XH
ICS 33.200 ISBN 978-2-8322-1165-6

Warning! Make sure that you obtained this publication from an authorized distributor.
Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission


Marque déposée de la Commission Electrotechnique Internationale
–2– 61968-9  IEC:2013

CONTENTS
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

FOREWORD ........................................................................................................................... 9
INTRODUCTION ................................................................................................................... 12
1 Scope ............................................................................................................................ 14
2 Normative references .................................................................................................... 15
3 Terms, definitions and abbreviations ............................................................................. 16
3.1 Terms and definitions ....................................................................................... 16
3.2 Abbreviations ................................................................................................... 17
4 Reference and information models ................................................................................ 18
4.1 General approach to metering systems ............................................................ 18
4.2 Reference Model .............................................................................................. 19
4.2.1 General .......................................................................................... 19
4.2.2 Metering system (MS) – Data collection .......................................... 22
4.2.3 Metering system (MS) – Control and reconfiguration ....................... 23
4.2.4 Load control ................................................................................... 23
4.2.5 Load management system (LMS) .................................................... 23
4.2.6 Meter asset management (MAM) system ........................................ 24
4.2.7 Meter data management (MDM) system .......................................... 24
4.2.8 Customer information system (CIS) ................................................ 24
4.2.9 Outage management system (OMS) ............................................... 24
4.2.10 Network operations (NO) ................................................................ 25
4.2.11 Meter maintenance (MM) ................................................................ 25
4.2.12 Planning ......................................................................................... 25
4.2.13 Work management (WM) ................................................................ 25
4.2.14 Point of sale (POS) ......................................................................... 25
4.2.15 Meter .............................................................................................. 25
4.2.16 Load control devices ....................................................................... 25
4.2.17 PAN devices ................................................................................... 26
4.2.18 Demand response management system (DRMS) ............................ 26
4.3 Interface reference model ................................................................................ 26
4.4 Meter reading and control functions and components ....................................... 26
4.5 Static information model .................................................................................. 27
4.5.1 General .......................................................................................... 27
4.5.2 Classes for meter reading and control ............................................ 28
4.5.3 Classes related to meter reading and control .................................. 32
5 Meter reading and control message types ...................................................................... 33
5.1 General ............................................................................................................ 33
5.2 End device event messages ............................................................................. 33
5.2.1 General .......................................................................................... 33
5.2.2 Applications .................................................................................... 34
5.2.3 Message format .............................................................................. 40
5.3 Meter reading messages .................................................................................. 42
5.3.1 General .......................................................................................... 42
5.3.2 Applications .................................................................................... 42
5.3.3 Message formats ............................................................................ 47
5.4 End device control messages ........................................................................... 58
5.4.1 General .......................................................................................... 58
61968-9  IEC:2013 –3–

5.4.2 Applications .................................................................................... 58


5.4.3 Message format .............................................................................. 65
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.5 Meter service requests ..................................................................................... 68


5.5.1 General .......................................................................................... 68
5.5.2 Applications .................................................................................... 69
5.5.3 Message format .............................................................................. 72
5.6 Metering system events ................................................................................... 73
5.6.1 General .......................................................................................... 73
5.6.2 Applications – Firmware upgrade .................................................... 74
5.6.3 Message formats ............................................................................ 74
5.7 Customer switching .......................................................................................... 74
5.7.1 General .......................................................................................... 74
5.7.2 Message formats ............................................................................ 75
5.8 Payment metering service messages ............................................................... 75
5.8.1 General .......................................................................................... 75
5.8.2 Auxiliary agreements ...................................................................... 75
5.8.3 Applications .................................................................................... 76
5.8.4 Message formats ............................................................................ 77
5.9 Premise area networks .................................................................................... 80
5.9.1 General .......................................................................................... 80
5.9.2 Applications .................................................................................... 81
5.9.3 Message formats ............................................................................ 83
5.10 Master data management messages ................................................................ 83
5.10.1 General .......................................................................................... 83
5.10.2 Applications .................................................................................... 84
5.10.3 Message formats ............................................................................ 91
6 Document conventions ................................................................................................ 104
6.1 UML diagrams................................................................................................ 104
6.2 Message definitions ....................................................................................... 105
6.2.1 General ........................................................................................ 105
6.2.2 Mandatory vs. optional .................................................................. 105
6.2.3 Verb tense .................................................................................... 105
6.3 Synchronous versus asynchronous messages ............................................... 105
6.4 Depiction of simple acknowledgment messages ............................................. 105
Annex A (normative) Description of message type verbs .................................................... 106
Annex B (informative) Reply error codes ............................................................................ 108
Annex C (normative) Procedure for the generation of a ReadingType name ....................... 115
Annex D (normative) Quality code enumerations ................................................................ 170
Annex E (normative) EndDeviceEventType enumerations .................................................. 183
Annex F (normative) EndDeviceControlType enumerations ................................................ 221
Annex G (normative) Conventions for naming and identifying objects ................................ 224
Annex H (normative) XML schemas for message payloads ................................................ 227
Annex I (informative) XML schemas for message payloads ................................................ 314
Annex J (normative) Request parameters .......................................................................... 389
Annex K (normative) Master data management transaction processing .............................. 395
Annex L (informative) Master data management use cases and sample XML ..................... 402
Annex M (informative) Notes on extended use of IEC 61968-100 ....................................... 438
–4– 61968-9  IEC:2013

Bibliography ........................................................................................................................ 440


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 1 – IEC 61968-9 scope .............................................................................................. 15


Figure 2 – Example of an end device with functions .............................................................. 20
Figure 3 – IEC 61968-9 reference model ............................................................................... 21
Figure 4 – IEC 61968-9 Reference model with customer information and billing system ........ 22
Figure 5 – Outage Detection, request/reply message exchange, example 1 .......................... 35
Figure 6 – Outage Detection, request / reply message exchange, Example 2 ........................ 36
Figure 7 – Outage Detection, publish/subscribe exchange, Example 1 .................................. 37
Figure 8 – Outage Detection, publish/subscribe exchange, Example 2 .................................. 37
Figure 9 – Meter Health Event exchange, Example 1 ............................................................ 38
Figure 10 – Meter Health Event exchange, Example 2 .......................................................... 39
Figure 11 – Power quality event exchange, Example 1 ......................................................... 39
Figure 12 – Power quality event exchange, Example 2 ......................................................... 40
Figure 13 – End device event message format ...................................................................... 41
Figure 14 – Example use of meter read schedule to create subscription ............................... 43
Figure 15 – Example manual meter reading exchange .......................................................... 44
Figure 16 – Example On-Request meter read ....................................................................... 45
Figure 17 – Historical MeterData exchange ........................................................................... 46
Figure 18 – Example billing inquiry message exchange ........................................................ 46
Figure 19 – Meter readings message format ......................................................................... 47
Figure 20 – Reading structure ............................................................................................... 48
Figure 21 – Timestamps assigned between systems ............................................................. 49
Figure 22 – Conventions for timeStamp and timePeriod ........................................................ 49
Figure 23 – IntervalBlock structure ....................................................................................... 50
Figure 24 – Interval data timestamp generation .................................................................... 51
Figure 25 – Time interval conventions ................................................................................... 51
Figure 26 – ReadingType structure ....................................................................................... 52
Figure 27 – Meter read schedule message format ................................................................. 57
Figure 28 – Example load control message exchange ........................................................... 59
Figure 29 – Example message exchange for LC unit installation ........................................... 60
Figure 30 – Example message exchange for change of customer program ........................... 61
Figure 31 – Example message exchange for change of customer program w/o MDM ............ 61
Figure 32 – Example for change of customer program with meter change out ....................... 62
Figure 33 – Example message exchange for meter connect/disconnect ................................ 63
Figure 34 – Example of remote connect/disconnect directly between CIS and MS ................ 64
Figure 35 – Example message exchange for real-time price signal ....................................... 65
Figure 36 – End device controls message format .................................................................. 66
Figure 37 – Example meter installation and removal message exchange .............................. 69
Figure 38 – Example end device event message exchange due to meter changeout ............. 70
Figure 39 – Example message exchange due to CIS alarms ................................................. 71
Figure 40 – Example message exchange when meter is changed out for recalibration .......... 72
Figure 41 – Meter service requests message format ............................................................. 73
61968-9  IEC:2013 –5–

Figure 42 – Example firmware upgrade message exchange .................................................. 74


Figure 43 – Example customer switching message exchange ............................................... 75
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 44 – Message exchange for transferring auxiliary agreement information ................... 76


Figure 45 – Message exchange for transferring receipt information ....................................... 77
Figure 46 – Message exchange for transferring transaction information ................................ 77
Figure 47 – Auxiliary agreement configuration message format............................................. 78
Figure 48 – ReceiptRecord message format ......................................................................... 79
Figure 49 – TransactionRecord message format ................................................................... 80
Figure 50 – Pairing of a PAN device ..................................................................................... 81
Figure 51 – PAN device events ............................................................................................. 82
Figure 52 – PAN device controls ........................................................................................... 83
Figure 53 – Master data linkages .......................................................................................... 85
Figure 54 – Message exchange for transferring supplier information ..................................... 86
Figure 55 – Message exchange for transferring customer information ................................... 87
Figure 56 – Message exchange for transferring customer agreement information ................. 87
Figure 57 – Message exchange for transferring customer account information ...................... 88
Figure 58 – Message exchange for transferring service category information ........................ 88
Figure 59 – Message exchange for transferring usage point information ............................... 89
Figure 60 – Message exchange for transferring meter information ........................................ 89
Figure 61 – Message exchange for transferring end device information ................................ 90
Figure 62 – Message exchange for transferring service location information ......................... 91
Figure 63 – Message exchange for transferring pricing structures ......................................... 91
Figure 64 – MasterDataLinkageConfig message format ........................................................ 92
Figure 65 – Service supplier configuration message format .................................................. 93
Figure 66 – Customer configuration message ....................................................................... 94
Figure 67 – Customer agreement configuration message ...................................................... 95
Figure 68 – Customer account configuration message .......................................................... 96
Figure 69 – ServiceCategoryConfig message format ............................................................. 96
Figure 70 – UsagePointConfig message format .................................................................... 97
Figure 71 – UsagePointLocationConfig message format ....................................................... 99
Figure 72 – End device config message format ................................................................... 100
Figure 73 – Meter configuration message ........................................................................... 101
Figure 74 – ComModuleConfig message format .................................................................. 102
Figure 75 – ServiceLocationConfig message format ............................................................ 103
Figure 76 – PricingStructureConfig message format ........................................................... 104
Figure B.1 – Reply Message States .................................................................................... 114
Figure C.1 – Typical enumerations for accumulation behaviour ........................................... 123
Figure C.2 – Typical enumerations for direction of flow ....................................................... 130
Figure C.3 – Voltage measurements ................................................................................... 137
Figure E.1 – Event data ...................................................................................................... 184
Figure G.1 – CIM naming .................................................................................................... 224
Figure G.2 – Example XML structure for names .................................................................. 225
Figure G.3 – Use of names for references........................................................................... 226
–6– 61968-9  IEC:2013

Figure J.1 – Message request structure .............................................................................. 389


Figure J.2 – GetMeterReadings .......................................................................................... 390
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure J.3 – GetEndDeviceConfig ....................................................................................... 391


Figure J.4 – GetCustomerMeterDataSet.............................................................................. 392
Figure J.5 – GetMeterServiceRequests ............................................................................... 393
Figure K.1 – Message Envelope Extension ......................................................................... 396
Figure K.2 – OperationSet .................................................................................................. 397
Figure K.3 – Pattern 1: Request/response (non-OperationSet) ............................................ 398
Figure K.4 – Pattern 2: published event (non-OperationSet) ............................................... 399
Figure K.5 – Pattern 3: Request/response (OperationSet) ................................................... 400
Figure K.6 – Pattern 4: published event (OperationSet) ...................................................... 401
Figure M.1 – Get/cancel pattern which is not recommended................................................ 438
Figure M.2 – Get/cancel pattern which is recommended ..................................................... 439

Table 1 – Document overview for IEC 61968-9 ..................................................................... 13


Table 2 – Business functions and abstract components ........................................................ 27
Table 3 – Classes for meter reading and control ................................................................... 28
Table 4 – Classes related to meter reading and control ......................................................... 32
Table 5 – IEC 61968-9 configuration profiles ........................................................................ 84
Table A.1 – Commonly used verbs ...................................................................................... 106
Table B.1 – ReplyCode Categories ..................................................................................... 108
Table B.2 – Error-free Enumerations ................................................................................... 109
Table B.3 – Missing-element Enumerations ........................................................................ 109
Table B.4 – Bad-value Enumerations .................................................................................. 109
Table B.5 – Too-many-values enumerations ....................................................................... 110
Table B.6 – Request-timed-out enumerations ..................................................................... 110
Table B.7 – Application-error enumerations ........................................................................ 111
Table B.8 – Business-rule-violation enumerations ............................................................... 111
Table B.9 – Security issue enumerations ............................................................................ 111
Table B.10 – Common enumerations .................................................................................. 112
Table C.1 – Time-period of interest enumerations ............................................................... 116
Table C.2 – Data qualifier enumerations ............................................................................. 116
Table C.3 – measuringPeriod enumerations ........................................................................ 117
Table C.4 – Demand normalization scalars ......................................................................... 119
Table C.5 – Accumulation behaviour enumerations ............................................................. 121
Table C.6 – Customary accumulation behaviour enumerations ........................................... 123
Table C.7 – Direction of flow enumeration ........................................................................... 124
Table C.8 – DirectionOfFlow enumeration equivalencies ..................................................... 130
Table C.9 – Commodity ...................................................................................................... 131
Table C.10 – measurementKind Index ................................................................................ 132
Table C.11 – Harmonic and Interharmonic enumerations .................................................... 138
Table C.12 – Argument enumerations ................................................................................. 138
Table C.13 – Time Of Use Enumerations ............................................................................ 139
61968-9  IEC:2013 –7–

Table C.14 – Critical Peak Period Enumerations ................................................................. 140


Table C.15 – Consumption Tier Enumerations .................................................................... 141
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table C.16 – Example Combinations of TOU and Consumption Tier Enumerations ............. 141
Table C.17 – Phase enumerations ...................................................................................... 142
Table C.18 – Power of ten enumerations ............................................................................ 146
Table C.19 – Historical concentration multiplier enumerations ............................................ 147
Table C.20 – Base SI units of measure ............................................................................... 149
Table C.21 – Derived SI units of measure with special names ............................................ 149
Table C.22 – Derived SI Units of Measure without Special Names ...................................... 151
Table C.23 – Non-SI Units of Measure accepted for use with the International System
of Units ............................................................................................................................... 154
Table C.24 – Dimensionless and Concentration Units of Measure ....................................... 155
Table C.25 – Non-SI units whose values in SI units shall be obtained experimentally ......... 157
Table C.26 – Other Non-SI Units of Measure ...................................................................... 158
Table C.27 – Non-SI Units Associated with the CGS and the CGS-Gaussian System of
Units ................................................................................................................................... 162
Table C.28 – Currency units of measure (from ISO 4217) ................................................... 163
Table C.29 – ReadingType Examples ................................................................................. 165
Table D.1 – System identifier .............................................................................................. 171
Table D.2 – Example quality code categories ...................................................................... 171
Table D.3 – Validity related codes ...................................................................................... 172
Table D.4 – Diagnostics related codes ................................................................................ 173
Table D.5 – Power quality related codes ............................................................................. 173
Table D.6 – Tamper / revenue protection related codes ...................................................... 174
Table D.7 – Data collection related codes ........................................................................... 174
Table D.8 – Failed reasonability testing related codes ........................................................ 176
Table D.9 – Failed validation testing related codes ............................................................. 176
Table D.10 – Edit related codes .......................................................................................... 177
Table D.11 – Estimation related codes ................................................................................ 178
Table D.12 – Questionable related codes............................................................................ 179
Table D.13 – Derived related codes .................................................................................... 180
Table D.14 – Projected related codes ................................................................................. 181
Table D.15 – Example Quality Codes .................................................................................. 182
Table E.1 – EndDeviceType codes ..................................................................................... 185
Table E.2 – EndDeviceDomain Codes ................................................................................. 187
Table E.3 – EndDeviceSubdomain codes ............................................................................ 188
Table E.4 – EndDeviceEventOrAction codes ....................................................................... 193
Table E.5 – Battery events .................................................................................................. 200
Table E.6 – Billing events ................................................................................................... 200
Table E.7 – Cartridge events .............................................................................................. 201
Table E.8 – Clock events .................................................................................................... 201
Table E.9 – Communication events ..................................................................................... 202
Table E.10 – Configuration events ...................................................................................... 203
Table E.11 – Demand events .............................................................................................. 204
–8– 61968-9  IEC:2013

Table E.12 – Firmware events ............................................................................................ 204


Table E.13 – GasSupply events .......................................................................................... 206
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table E.14 – Installation events .......................................................................................... 206


Table E.15 – LoadControl events ........................................................................................ 207
Table E.16 – LoadProfile events ......................................................................................... 207
Table E.17 – Logs events ................................................................................................... 208
Table E.18 – Memory events .............................................................................................. 208
Table E.19 – Metrology events ............................................................................................ 209
Table E.20 – MobileSecurity events .................................................................................... 210
Table E.21 – Modem events................................................................................................ 211
Table E.22 – ModuleFirmware events ................................................................................. 211
Table E.23 – Network events .............................................................................................. 211
Table E.24 – PAN / HAN events .......................................................................................... 212
Table E.25 – Power events ................................................................................................. 213
Table E.26 – Pressure events ............................................................................................. 216
Table E.27 – RCDSwitch events ......................................................................................... 217
Table E.28 – Security events .............................................................................................. 217
Table E.29 – Temperature events ....................................................................................... 219
Table E.30 – VideoDisplay events ....................................................................................... 219
Table E.31 – WaterSupply events ....................................................................................... 220
Table F.1 – Demand Controls ............................................................................................. 221
Table F.2 – LoadControl Controls ....................................................................................... 222
Table F.3 – PAN / HAN Controls ......................................................................................... 222
Table F.4 – RCDSwitch Controls ......................................................................................... 222
Table L.1 – Exemplary master data management / data synchronization use cases ............ 403
61968-9  IEC:2013 –9–

INTERNATIONAL ELECTROTECHNICAL COMMISSION


_____________
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

APPLICATION INTEGRATION AT ELECTRIC UTILITIES –


SYSTEM INTERFACES FOR DISTRIBUTION MANAGEMENT –

Part 9: Interfaces for meter reading and control

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.

International Standard IEC 61968-9 has been prepared by IEC technical committee 57: Power
systems management and associated information exchange.

This second edition cancels and replaces the first edition published in 2009. This edition
constitutes a technical revision and includes the following significant technical changes with
respect to the previous edition:

a) changes to and addition of new profiles to support PAN and UsagePoints;


b) extensions to support PAN devices generically as EndDevices;
c) extensions to the MeterReading model and profiles to support richer descriptions of
metered quantities and to accommodate coincident readings;
d) addition of CIM Name class and corresponding revisions to profiles to allow reference by
name instead of by mRID. Where the document may identify the use of mRID values as
references, Name.name values may be alternatively used. This is described in more detail
in Annex G;
– 10 – 61968-9  IEC:2013

e) reference of ReadingTypes, EndDeviceEventTypes and EndDeviceControlTypes using


name references;
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

f) definition of normative enumerations for ReadingTypes, EndDeviceEventTypes and


EndDeviceControlTypes in annexes;
g) various corrections to example sequence diagrams;
h) Removal of MeterAssetReading profile, where functionality is supported using the
MeterReading profile;
i) MeterAsset class is now named Meter;
j) MeterAssetConfig profile now named MeterConfig;
k) EndDeviceAssets profile now named EndDeviceConfig;
l) removal of EndDeviceFirmware profile, where functionality is supported using the
EndDeviceConfig profile;
m) use of new namespaces to reflect the new edition, where the namespaces is reflective of
the year in which a profile is defined;
n) adoption of UsagePoint as a replacement for and a generalization of ServiceDeliveryPoint;
o) SDPLocationConfig has been deprecated in favor of UsagePointLocationConfig;
p) some profiles previously defined have been moved into the new subclause 5.10 which is
focused on data linkages;
q) elimination of the MeterSystemEvents profile, as it provided no functionality that could not
be achieved with the EndDeviceEvents profile;
r) there were several profiles originally defined in support of prepayment use cases that
were identified to be more general in nature, and were consequentially moved to 5.10.
Subclause 5.8 now consists of only those profiles that are specific to prepayment. In all
cases there has been some refactoring of these profiles to reflect other necessary
changes that have been described;
s) supplierConfig has been renamed ServiceSupplierConfig;
t) messages using the SUBSCRIBE verb have been removed as these are related to the
underlying communication transport and do not reflect actual IEC 61968 messages.

The text of this standard is based on the following documents:

FDIS Report on voting


57/1377/FDIS 57/1394/RVD

Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.

A list of all parts in the IEC 61968 series, published under the general title Application
integration at electric utilities – System interfaces for distribution management, can be found
on the IEC website.
61968-9  IEC:2013 – 11 –

The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

related to the specific publication. At this date, the publication will be

• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.

IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
– 12 – 61968-9  IEC:2013

INTRODUCTION
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

The purpose of this document is to define a standard for the integration of Metering Systems
(MS), which would include traditional (one or two-way) Automated Meter Reading (AMR)
Systems, with other systems and business functions within the scope of IEC 61968. The
scope of this standard is the exchange of meter reading, transactions, event and control
information between systems within the utility enterprise and between enterprises. The
specific details of communication protocols those systems employ are outside the scope of
this standard. Instead, this standard will recognize and model the general capabilities that can
be potentially provided by advanced and/or legacy meter infrastructures, including two-way
communication capabilities such as load control, dynamic pricing, outage detection,
distributed energy resource (DER) control signals and on-request read. In this way, this
standard will not be impacted by the specification, development and/or deployment of next
generation meter infrastructures, either through the use of standards or proprietary means.

The IEC 61968 series of standards is intended to facilitate inter-application integration as


opposed to intra-application integration. Intra-application integration is aimed at programs in
the same application system, usually communicating with each other using middleware that is
embedded in their underlying runtime environment, and tends to be optimised for close, real-
time, synchronous connections and interactive request/reply or conversation communication
models. IEC 61968, by contrast, is intended to support the inter-application integration of a
utility enterprise that needs to connect disparate applications that are already built or new
(legacy or purchased applications), each supported by dissimilar runtime environments.
Therefore, these interface standards are relevant to loosely coupled applications with more
heterogeneity in languages, operating systems, protocols and management tools. This series
of standards is intended to support applications that need to exchange data every few
seconds, minutes, or hours rather than waiting for a nightly batch run. This series of
standards, which are intended to be implemented with middleware services that exchange
messages among applications, will complement, not replace utility data warehouses,
database gateways, and operational stores.

As used in IEC 61968, a Distribution Management System (DMS) consists of various


distributed application components for the utility to manage electrical distribution networks.
These capabilities include monitoring and control of equipment for power delivery,
management processes to ensure system reliability, voltage management, demand-side
management, outage management, work management, automated mapping and facilities
management. Standard interfaces are defined for each class of applications identified in the
Interface Reference Model (IRM), which is described in IEC 61968-1, Interface architecture
and general requirements.
61968-9  IEC:2013 – 13 –

This part of IEC 61968 contains the clauses listed in Table 1 below.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table 1 – Document overview for IEC 61968-9

Clause Title Purpose

1 Scope The scope and purpose of the document are described.


2 Normative References Documents that contain provisions which, through reference in
this text, constitute provisions of this International Standard.
3 Terms, Definitions and
Abbreviations
4 Reference and Information Description of general approach to metering system,
Models reference model, use cases, interface reference model, meter
reading and control functions and components, message type
terms and static information model.
5 Meter Reading and Control Message types related to the exchange of information for
Message Types documents related to meter reading and control.
6 Document Conventions
Annex A Message Type Verbs Description of the Verbs that are used for the message types
Annex B CIM Extensions CIM extensions to support the recommended message
structure for meter reading and control
Annex C Procedure for the generation of Technique for constructing, and offers recommended
a ReadingTypeId enumerations for the ReadingTypeId textual name and mRID.
Annex D QualityCode enumerations Technique for constructing, and offers recommended
enumerations for reading quality codes
Annex E EndDeviceEvent Code Defines EndDevice alarm and event codes
enumerations
Annex F EndDeviceControl code Defines EndDevice control codes.
enumerations
Annex G Maintaining Relationships Describes the use of the master resource identifier (mRID)
Between Objects and Names.
Annex H XML Schemas for message To provide xsd information for use by developers to create
payloads IEC 61968-9 messages.
Annex I Mappings To provide mappings between IEC 61968-9 MeterReadings
and other standards.
Annex J Request Parameters Describes the qualification of GET requests using Request
parameters.
Annex K Master Data Management Describes how complex Master data Management / Data
Transaction Processing Synchronization transactions are conveyed and the
associated processing rules.
Annex L Master Data Management Use Describes many of the common Master Data Management use
Cases and Sample XML cases and provides sample XML to illustrate intended usage
of the various Master Data Management related profiles.

Future editions of IEC 61968-9 will strive to have changes be 'non-breaking', where the
namespace of the previous version may be preserved, but the Revision attribute in the XSD is
incremented.
– 14 – 61968-9  IEC:2013

APPLICATION INTEGRATION AT ELECTRIC UTILITIES –


SYSTEM INTERFACES FOR DISTRIBUTION MANAGEMENT –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Part 9: Interfaces for meter reading and control

1 Scope

This part of IEC 61968 specifies the information content of a set of message types that can be
used to support many of the business functions related to meter reading and control. Typical
uses of the message types include meter reading, controls, events, customer data
synchronization and customer switching. Although intended primarily for electrical distribution
networks, IEC 61968-9 can be used for other metering applications, including non-electrical
metered quantities necessary to support gas and water networks.

The purpose of this part of IEC 61968is to define a standard for the integration of metering
systems (MS), which includes traditional manual systems, and (one or two-way) automated
meter reading (AMR) systems, and meter data management (MDM) systems with other
enterprise systems and business functions within the scope of IEC 61968. The scope of this
part of IEC 61968is the exchange of information between metering systems, MDM systems
and other systems within the utility enterprise. The specific details of communication protocols
those systems employ are outside the scope of this International Standard. Instead, this
International Standard will recognize and model the general capabilities that can be
potentially provided by advanced and/or legacy meter infrastructures, including two-way
communication capabilities such as load control, dynamic pricing, outage detection,
distributed energy resource (DER) control signals and on-request read. In this way, this
standard will not be impacted by the specification, development and/or deployment of next
generation meter infrastructures either through the use of standards or proprietary means.

The diagram in Figure 1 describes the scope of this part of IEC 61968 from the perspective of
direct and causal or indirect impacts of IEC 61968-9 messages. Where the focus of
IEC 61968-9 is to define standard messages for the integration of enterprise applications,
these messages may be directly or indirectly related to information flows within a broader
scope. Examples would include messaging between head end systems and meters or PAN
devices. The various components described later in this document will typically fall into either
the category of a metering system (MS) head end, an MDM or other enterprise application
(e.g. OMS, DRMS, CIS).
61968-9  IEC:2013 – 15 –

Area of Direct Impact using


Area Causally/Indirectly
IEC 61968-9
Impacted by or impacting
(and within scope
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

IEC 61968-9
of IEC 61968)
Customer

Electric Utility
Standard or Proprietary Meter
Communication
Enterprise Integration Infrastructures
Enterprise Infrastructure
Applications (e.g. ESB, SOA, …)
(e.g. CIS, WMS, Customer
PAN
GIS, MDMS) Device
IEC 61968-9 Messages
(or more broadly any Head End Meter or
PAN
61968 message) Gateway
Systems PAN
Operations Device

Applications
Messages defined by
(e.g. OMS, DMS)
IEC 61968-9 are based Customer
upon IEC CIM and PAN
conveyed using a variety of Device
integration technologies Messages defined by TC57
and IEC 61968-100 relevant standards or WG21 PAN
vendors. May use a wide Gateway PAN
variety of communication Device
technologies PAN
Device

Mappings, translations
and/or forwarding as Messages defined
needed Mapping, translations by PAN/HAN
and/or forwarding as specifications
needed

Figure 1 – IEC 61968-9 scope

The capabilities and information provided by a meter reading and meter data management
systems are important for a variety of purposes, including (but not limited to) interval data,
time-based demand data, time-based energy data (usage and production), outage
management, service interruption, service restoration, quality of service monitoring,
distribution network analysis, distribution planning, demand response, customer billing and
work management. This standard also extends the CIM (Common Information Model) to
support the exchange of meter data.

2 Normative references

The following documents, in whole or in part, are normatively referenced in this document and
are indispensable for its application. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any
amendments) applies.

IEC 60050-300, International Electrotechnical Vocabulary (IEV) – Electrical and electronic


measurements and measuring instruments – Part 311: General terms relating to
measurements – Part 312: General terms relating to electrical measurements – Part 313:
Types of electrical measuring instruments – Part 314: Specific terms according to the type of
instrument

IEC 61968-1, Application integration at electric utilities – System interfaces for distribution
management – Part 1: Interface architecture and general recommendations

IEC/TS 61968-2, Application integration at electric utilities – System interfaces for distribution
management – Part 2: Glossary

IEC 61968-11, Application integration at electric utilities – System interfaces for distribution
management – Part 11: Common information model (CIM) extensions for distribution
– 16 – 61968-9  IEC:2013

IEC 61968-100:2013, Application integration at electric utilities – System interfaces for


distribution management – Part 100: Implementation profiles
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

IEC 61970-301, Energy management system application program interface (EMS-API) – Part
301: Common information model (CIM) base

IEC/TR 62051-1, Electricity metering – Data exchange for meter reading, tariff and load
control – Glossary of terms – Part 1: Terms related to data exchange with metering
equipment using DLMS/COSEM

ISO 8601:2004, Data Elements and Interchange Formats – Information Interchange –


Representation of Dates and Times

3 Terms, definitions and abbreviations

3.1 Terms and definitions

For the purposes of this standard, the terms and definitions given in IEC 60050-300,
IEC/TS 61968-2, IEC/TR 62051-1, IEC 62055-31 and the following terms apply.

NOTE Where there is a difference between the definitions in this standard and those contained in other
referenced IEC standards, then those defined in IEC/TS 61968-2 shall take precedence over the others listed, and
those defined in IEC 61968-9 shall take precedence over those defined in IEC/TS 61968-2.

3.1.1
customer program
classification scheme for the sale of energy to consumers according to a particular tariff

Note 1 to entry: The program may specify the purpose, conditions on the time of use, the service voltage(s), the
volumes consumed, and/or other terms as a condition of the sale.

Note 2 to entry: Utilities may promote particular programs to their industrial, commercial, agricultural, and
residential customers in an effort to encourage a particular behaviour, or to make them aware of their options.

3.1.2
demand response
set of processes and programs that are used to reduce consumption

Note 1 to entry: This may be done on an economic, mandatory or emergency basis.

3.1.3
end device
equipment located at the end of the communication system, usually on the customer premises

Note 1 to entry: An end device may perform functions such as metrology, connect/disconnect, load control,
demand response, or other functions, and may have power relay and/or local communications capability. This is
represented within the CIM using the EndDevice class. Meters and PAN devices are examples of end devices.

3.1.4
head end
component of a metering system that collects data from and issues controls to end devices

Note 1 to entry: A head end may also manage the communication system used to communicate with the end
devices. From the prespective of enterprise integration, the head end acts as a proxy for end devices.

3.1.5
gateway
device that may be used to manage devices on a PAN and participate in internet-based
interactions

Note 1 to entry: A gateway may apply a transformation from one protocol to another.
61968-9  IEC:2013 – 17 –

3.1.6
load control device
type of EndDevice which can receive signals causing it to shed load for the purposes of
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

maintaining network reliability and/or commercial agreements

3.1.7
meter
type of end device which performs metrology and supports the tariffing of the distribution
and/or transmission network

Note 1 to entry: This is represented using the CIM Meter class, which is a subclass of EndDevice.

Note 2 to entry: As an end device, a meter will typically, but not always, have a communication link with a head
end system.

3.1.8
meter changeout
meter exchange
process of replacing an existing meter with a new meter

Note 1 to entry: The installer will customarily follow a work order which specifies a given location, and usually
requires that he or she capture readings from the old and new meters, and record the time and day in which the
work was performed.

3.1.9
meter data manager
system that manages meter data, and typically provides a variety of value added
functionalities such as VEE

3.1.10
premise area network
fully inclusive of the scope of a home area network (HAN) as it also covers commercial
premises

3.1.11
PAN device
type of end device that is located on a customer premise and communicates using a PAN

Note 1 to entry: A PAN device can typically accept controls and/or report events.

Note 2 to entry: PAN devices commonly use meters as communication gateways.

3.1.12
payment meter
electricity meter with additional functionalities that can be operated and controlled to allow the
flow of energy according to agreed payment modes

Note 1 to entry: Typically this involves prepayment for electricity.

3.1.13
prepayment mode
payment mode in which automatic interruption occurs when available credit is exhausted

3.2 Abbreviations
AM asset management
AMR automated meter reading
AMI advanced metering infrastructure
CIM common information model
CIS customer information system
– 18 – 61968-9  IEC:2013

COSEM companion specification for energy metering


DLMS UA device language message specification user association
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

DMS distribution management system


DR demand response
DRMS demand response management system
HAN home area network
IDR interval data recorder
IEC International Electrotechnical Commission
LC load control
LDC load control system
LMS load management system
MAM meter asset management
MDM meter data management
MDM master data management
MM meter maintenance
MR meter reading
MS metering system
NO network operations
OMS outage management system
POS point of sale
PAN premise area network (includes scope of HAN)
RF radio frequency
SM smart meter
UML unified modeling language
VEE validating, editing, and estimating
WM work management
XSD XML schema

4 Reference and information models

4.1 General approach to metering systems

The spinning disk in an electromechanical meter generally serves as a pulse initiator to the
meter recorder module. In a similar fashion, solid-state meters may also employ a metrology
unit that generates pulses which represent a fraction of a kWh, and if more sophisticated, the
solid-state meter may have a meter recorder which is able to accumulate many different kinds
of information and store it for presentation to the meter communications module using a
message and table-driven protocol such as ANSI C12.19 or IEC 62056.

The most common metered data element is kWh, but many electricity meters can also capture
kW, kVAr, kVArh, and other similar billing quantities. Some meters can also capture pure
engineering quantities such as voltage, current, power factor, etc.

Some AMR systems attempt to add value to meters by adding functionality that the meter may
lack. For simple meters (e.g. energy only) it is common for an AMR meter module to add the
capability to perform demand metering, Interval Data Recording (IDR), maintain an
energisation count, or even provide estimates of certain engineering quantities such as
voltage.
61968-9  IEC:2013 – 19 –

Commercial and Industrial meters often employ current transformers and voltage transformers
to meter the actual service. Primary voltages and currents are scaled down using potential
transformers (PTs) and current transformers (CTs) so that the meter does not have to be
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

constructed to withstand the high voltages and currents actually delivered to the load.
Secondary voltage or current values are those that are often measured directly by the meter.
Secondary values are small percentage of the primary values that may actually delivered to or
connected to the load. If secondary voltages and currents are measured by the meter, these
can be converted back to primary values using the PT and CT ratios, which are just the ratio
of primary to secondary values.

The metering system will convey meter data and other value-added data through the metering
system network to the destination. Depending on the system, the journey may involve multiple
steps through public or private networks, licensed or unlicensed RF spectrums, standardized
or proprietary systems, in a one-way or two-way fashion.

Some general operations or services can be defined for a metering system. These general
operations will translate to specific actions in the context of a given metering solution.

General operations can be scheduled or called on-demand. Each operation returns an answer
with an optional status. A message encapsulates a general operation.

Readers of IEC 61968-9 interested in additional information may refer to other standards
including IEC 62056, DLMS UA (Device Language Message Specification User Association)
and the COSEM model: COmpanion Specification for Energy Metering.

4.2 Reference Model

4.2.1 General

The following diagrams serve as reference models and provide examples of the logical
components and data flows related to this International Standard. Subclause 4.5.2 provides
references to terms that are defined by the CIM.

The “meter” is a specialization of an “end device”. The end device may contain a metrology
capability, it may contain a communications capability, it may be a load control unit, and it
may contain a mixture of many different types of functionality. Figure 2 attempts to describe
the concept of essentially a shopping-list of functionality which may be available in the (logical
or physical) end device.
– 20 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

End Device
- Metrology
- Communications
- Connect /disconnect
- Load control
- Demand response
- Relays
- Information display

Figure 2 – Example of an end device with functions

The end device itself, while presenting a myriad of functionality, is not the subject of this
standard. There are many interactions which ultimately affect the end device but occur as a
result of a communication between systems at a much higher level in the control architecture.
The interaction between systems is within the scope of this standard, and Figure 3 is an
informative view of the systems involved and provides an overview to the stakeholder
community.

From the perspective of this standard, an end device:

• has a unique identity (mRID and/or one or more instances of the Names class)
• is managed as a physical asset
• may issue events
• may receive control requests
• may collect and report measured values
• may participate in utility business processes

The following diagrams of Figures 3 and 4 describe the flows between the components in the
reference model. Two diagrams are used in order to reduce the complexity that would be
experienced by a single diagram. The numbers in brackets provide linkages to the flow
definitions.
61968-9  IEC:2013 – 21 –

Planning
Outage
and
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Management
Scheduling
61968-3 61968-5

Interface and protocol details of the


[ 17 ]
Service Point are outside the scope of [ 12 ]
IEC 61968-9
[ 19 ]

Meter
Service [ 13 ]
[ 18 ] Data Collection Data
Point
Management

Metering System
{ 16 }
{ 23 }
Control and [ 12 ]
[ 15 ] [4] [ 13 ]
Reconfiguration
[3] [ 22 ] [9]
Customer
Information
[2]
and
[7] Billing
{ 11 } 61968-8

Meter Maintenance [1]


and [ 21 ]
Asset Management
[ 20 ] [7]
[6] Point
of
Sale
Network 61968-10
Operations
[7]
61968-3 [6]
{ 12 }
[ 10 ]
{8} Load Analysis

Load
[3] Management
System

[ 18 ] Load Control
{ 14 }

{ 12 }

[5]
Work
Management
{ 14 }
61968-6

[ 1 ] Account information [ 13 ] Meter readings


[ 2 ] Configuration, installation etc. { 14 } Meter service request
[ 3 ] Controls and signals [ 15 ] On request read
[ 4 ] Customer data set [ 16 ] Outage and restoration verification
[ 5 ] Data obtained by special read [ 17 ] Power reliability and quality events
[ 6 ] Demand response signals [ 18 ] Readings, events and status
[ 7 ] Disconnect/reconnect, demand reset [ 19 ] Special read
{ 8 } Install, remove, repair, disconnect, reconnect [ 20 ] Tariffs, parameters
[ 9 ] Load curves, Measurement history, etc. [ 21 ] Transaction information 61968 Part 9
[ 10 ] Load scenarios [ 22 ] Transaction records Defined by other 61968 Parts
{ 11 } Meter health and tamper detection { 23 } Tokens
{ 12 } Meter history Key Outside the scope of 61968

Figure 3 – IEC 61968-9 reference model


– 22 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Interface and protocol details of the


Service Point are outside the scope of Meter
IEC 61968-9 Administration

Readings, events Scheduled


and status Read
Service Meter
Data Collection Scheduled
Point Data Scheduled
Read Read
Management
Metering System
Tokens Peak
Control and Price (1) Peak
Controls and signals Reconfiguration Price (1)
Load
Reduction

Exchange
Load
Portal
Reduction

Network Peak Scheduled


Operations Price Read
(1)
61968-3

Customer
Peak Information
Price and
(2) Billing
61968 Part 9 61968-8
Defined by other 61968 Parts
Key Outside the scope of 61968

Figure 4 – IEC 61968-9 Reference model with customer information and billing system

The reference architecture reflects five main logical components (potentially realized as
systems or subsystems) related to metering:

a) metering system, potentially including data collection and control and reconfiguration
functionality
b) meter data management, which may include meter administration functions
c) meter maintenance
d) load management, potentially including load control and load analysis functionality
e) meter asset management.

The metering system and meter maintenance system components may be bound to a specific
meter and associated communication technology or they may support multiple meters (and
more generically end devices) types and associated communication technology. The meter
data management system component may support and consolidate meter data from more than
one metering system. The metering system may also support consolidation of various
measurement and data collection implementations, providing a consistent interface to the
meter data management system component.

4.2.2 Metering system (MS) – Data collection

The tasks of the data collection sub-component within the metering system may include:

• readings and status collection. Readings and status may be obtained through either
manual or automated means, on a scheduled or on-request basis
• transmission of meter readings and status to a meter data management system
61968-9  IEC:2013 – 23 –

• transmission of power reliability and quality event data to outage management, network
operations, and capacity planning systems
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• transmission of communication network health information to those responsible for


maintaining the communications network.

It is important to note that metering systems are significantly diverse with respect to
technologies used, protocols used, capabilities and frequency of data collection. The details
of the internals of meters, communication transports and protocols are outside the scope of
this international standard.

A handheld device used by a human meter reader could be regarded as a metering system. In
a typical meter reading by human, a reader inputs meter data into a handheld device in a
field. The handheld device is not connected to a communication network in a field. At the end
of day work, the handheld device is connected to a communication network at reader’s home
(not in an office), and meter data is uploaded to a meter data management system. In this
case, this communication network should be part of a metering system. Data collection is
described in IEC 61968-1 as “MR-RMR.”

4.2.3 Metering system (MS) – Control and reconfiguration

The tasks of the control and reconfiguration subcomponent within the metering system are:

• primary interface in executing meter control commands


• communicating payment system information
• act as a communication gateway for load control devices
• service connect / disconnect
• configuration of tariff units of measure and calendar
• configuration of power quality measurement
• configuration of meter event recording
• relay of load control signals
• configuration of meter identity and security credentials
• fraud detection.

This subcomponent is identified separately within the metering system in order to recognize
the existence of metering systems that do not have the ability to send messages to meters.
IEC 61968-1 describes this subcomponent as “MR-MOP-Meter Configuration.” Metering
systems with these capabilities are oftern referred to as "AMI".

4.2.4 Load control

The Metering System Infrastructure may often be used as a communication gateway to load
control units. Load control units are end devices with load control (LC) capability. These are
wired to control individual, target devices. End devices with LC functionality can take on
different forms. Quite often a dedicated LC unit can be located at (or near) the device to be
controlled. Another approach is to use meters that have relays which are configured to serve
as LC devices. Still another approach is to interface with a customer energy management
system (which would be another type of end device).

4.2.5 Load management system (LMS)

A load management system is used to manage and control load by the utility in order to
promote system reliability. A load management system may perform load forecasting,
contingency analysis, and other simulations prior to issuing a load control command.
– 24 – 61968-9  IEC:2013

4.2.6 Meter asset management (MAM) system

Utilities will employ some form of asset management software in an effort to maintain detailed
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

records regarding their physical assets. Asset management is treated categorically in


IEC 61968-4. However, metering has such special requirements that it is common for a utility
to use specialized Meter Asset Management software. The software inventories the asset –
providing a record of its physical attributes as well as its location. For sake of discussion, the
IEC 61968-9 document will talk about a MAM system which is closely coupled to the MS and
MDM, though some implementations will successfully generalize the asset management
application sufficiently so that it can live within a more generic AM system.

4.2.7 Meter data management (MDM) system

From a historical perspective, it was common for a utility to have more than one automated
meter reading system. Alternatively, a utility might outsource meter reading services to one or
more third-party service providers who operate an AMR system and/or read the meters
manually. The meter data management (MDM) system is used to provide a common
repository, and point of management and access of meter data that is collected from disparate
metering systems. In addition to data aggregation, quite often the MDM will also make an
effort to scrutinize the data collected from the various metering systems, and provide a
validating, editing, and estimating (VEE) capability. MDM systems will frequently also provide
functionality involving issue, control, and tracking of EndDeviceControls and
endDeviceEvents.

4.2.8 Customer information system (CIS)

A CIS will typically encompass functionality related to customer care and billing. This is a
subject which is external to the IEC 61968-9 standard. The billing function is driven by
readings, typically demand or time-of-use, obtained from the meter. The CIS is also often
involved with processes related to billing inquires, meter disconnect and meter reconnect, rate
program changes.

The CIS is frequently the “source of record” in utility enterprises for master data defining key
entities such as meters, other end devices, usage points, service suppliers, customers,
pricing structures, etc. and the relationships between these entities. See 5.10 and Annexes K
and L for additional information related to master data management / data synchronization.

4.2.9 Outage management system (OMS)

An outage management system (OMS) is used by distribution operators to detect and track
outages, and to assist in the process of verification and/or restoration of service. An OMS
typically combines (or has ties to) functionality such as network operations fault management;
operational planning and optimisation, network operation simulation; maintenance and
construction; maintenance and inspection; and work scheduling and dispatching.

The metering system can be an important source of information for identifying the existence
and extent of outages, and can be used to verify the restoration of outages. The MS might
have the ability to publish outage and restoration data to the OMS as it finds it. This type of
information typically joins customer call-ins in the OMS to allow it to better predict the location
of the outage. However, due to the time-sensitive nature of outage detection, there is also the
potential need for a request/reply interface with the MS, where the OMS can ask for specific
equipment on the distribution network to be tested by the MS, and an energisation status
returned for analysis. The request/reply interface can be used by the OMS to supply critical
data needed to make an outage prediction, or by a dispatcher who would like to verify that
power has been restored to all of the metered endpoints downstream of a particular switch
prior to sending the lineman to the next location.

It is also relatively common for MDM systems to act as an intelligent agent in the brokering of
outage related messages between Metering Systems and Outage Management Systems.
61968-9  IEC:2013 – 25 –

4.2.10 Network operations (NO)

Network Operations (IEC 61968-3) may occasionally need to issue load control and pricing
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

signals to meters. This can be done for both economic and emergency reasons.

4.2.11 Meter maintenance (MM)

Meter Maintenance is responsible for functionality related to the configuration and installation
of meters. This type of functionality generally falls under Meter Asset Management, or Asset
Management in general. Performing meter maintenance may require exchanges with Work
Management.

4.2.12 Planning

The planning function is described as operational planning and optimisation, network


operation simulation.

4.2.13 Work management (WM)

A Work Management system is responsible for work that is performed by field resources. This
subject is covered in maintenance and construction maintenance and inspection
(IEC 61968-6).

With respect to metering, WM includes the installation, maintenance and replacement of


meters. This may also involve the process of special reads.

4.2.14 Point of sale (POS)

A Point of Sale (POS) system is used for the management of payment meters, where a
customer either purchases a token or makes a payment for service.

4.2.15 Meter

The meter records the data used for tariffing public networks, and data used for network
balancing mechanisms. Meters are a subtype of EndDevice.

Readings captured by the metering system are collected by a system such as the MDM before
being presented for billing purposes. Billing entities may correct the data, or, in some regions,
the energy supplier may perform validating, editing, and estimating (VEE) according to rules
established by the appropriate supervising regulatory agency. In any case, those corrections
are made available to the user who requests them.

Where this international standard refers to a "Meter", it should be realized that a "Meter" is an
end device that has metrology capability, it may or may not have communications capability, it
may or may not have connect/disconnect capability, or a host of other capabilities. Given that
a meter will have metrology capability, electricity meters will in all likelihood meter kWh, but
possibly also demand, reactive energy and demand, time of use quantities, interval data,
engineering quantities and more. In like manner, meters for other commodities such as gas
and water may monitor analogous quantities.

4.2.16 Load control devices

Load control devices are used to control loads at a UsagePoint. The metering system may
often have a communication network which can be used for transmitting load control signals
(EndDeviceControls) in order to control the load presented by the EndDevice(s). Alternatively,
the communication network could be used to communicate demand response (price) signals
to devices in order to affect the load presented by the EndDevice(s). PAN devices can also
provide load control functions.
– 26 – 61968-9  IEC:2013

4.2.17 PAN devices

PAN devices are used for a variety of purposes within a customer premise. The meter is often
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

used as a gateway for communication between the head end system and the PAN device.
PAN devices may react to control messages or generate EndDeviceEvents. Some PAN
devices, such as in-home displays, may also present information to consumers. PAN devices
may be configured to react to pricing or other demand response related signals that are
issued as EndDeviceControls. PAN devices are modelled as EndDevices in the CIM.

4.2.18 Demand response management system (DRMS)

Demand Response Management Systems are used to manage registration in DR programs,


send events to program participants and collect related performance information as needed
for settlements.

4.3 Interface reference model

It is not the intention of this standard to define the applications and systems that vendors
should produce. It is expected that a concrete (physical) application will provide the
functionality of one or more abstract (logical) components as listed in this standard. These
abstract components are grouped by the business functions of the Interface Reference Model.

In this standard, the term abstract component is used to refer to that portion of a software
system that supports one or more of the interfaces defined in Parts 3 to 9. It does not
necessarily mean that compliant software is delivered neither as separate modules nor as a
single system.

IEC 61968-1 describes infrastructure services common to all abstract components while
IEC 61968-3 to -9 define the details of the information exchanged for specific types of
abstract component.

IEC 61968 defines that:

a) An inter-application infrastructure is compliant if it supplies services defined in


IEC 61968-1 to support at least two applications with interfaces compliant to sections of
IEC 61968-3 to -9.
b) An application interface is compliant if it supports the interface standards defined in
IEC 61968-3 to -9 for the relevant abstract components defined in the Interface Reference
Model.
c) An application is only required to support interface standards of the applicable
components listed under abstract components. An application is not required to support
interfaces required by other abstract components of the same business sub-function or
within the same business function. While this standard primarily defines information
exchanged among components in different business functions, it will occasionally also
define information exchanged among components within a single business function when
a strong market need for this capability has been realised.

4.4 Meter reading and control functions and components

It should be noted that the message types defined in this "standard may be sent or received
by any type of component within a distribution management system (DMS) system.

Table 2 shows these functions and typical abstract components that are expected to be
producers of information for these message types. Typical consumers of the information
include, but are not restricted to, the other components as listed in IEC 61968-1.
61968-9  IEC:2013 – 27 –

Table 2 – Business functions and abstract components


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Business functions Business sub-functions Abstract components


Meter reading and control (MR) Metering system (MS) Data collection
End point controls
End point reconfiguration
Disconnect/reconnect
Demand reset
On request read
Point of sale
Outage detection and restoration
verification
Power reliability and quality events
Metering system events
Meter maintenance and asset End point install, configure, remove, repair,
management disconnect, reconnect
End point asset history
End point reconfiguration
Special read
Meter service request
Tariffs
Meter data management (MDM) Meter data repository
Usage history
Validation, estimation and editing
Customer billing data
End device controls and events
Demand response Real-time pricing
(DR) Emergency reductions
Economic reductions
Program registration
Load management (LM) Load analysis
Load control
Demand response
Performance measurements
Risk management

4.5 Static information model

4.5.1 General

The information model relevant to meter reading and control consists of classes that provide a
template for the attributes for each message.

The classes are defined in detail in IEC 61968-11, Common Information Model (CIM)
extensions for distribution' or in IEC 61970-301, Energy management system application
program interfaces – Common Information Model core.
– 28 – 61968-9  IEC:2013

4.5.2 Classes for meter reading and control

Table 3 lists classes used within message types. Usually all the attributes of these classes
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

are contained within a message type. The descriptions provided describe usage within this
part.

Classes described as type "Asset" are defined in the 61968/Assets package of the CIM.

Classes described as type "Customer" are defined in the 61968/Customers package of the
CIM.

Classes described as type "Metering" are defined in the 61968/Metering package of the CIM.

Classes described as type “PaymentMetering” are described in the 61968/PaymentMetering”


package of the CIM.

Classes described as type "Profile" are contextual profiles defined for 61968-9 that describe
message definitions defined using CIM objects.

Table 3 – Classes for meter reading and control

Class/Noun Type Description


AuxiliaryAccount PaymentMetering Variable and dynamic part of AuxiliaryAgreement, generally
representing the current state of the account related to the
outstanding balance defined in AuxiliaryAgreement.
AuxiliaryAgreement PaymentMetering An ad-hoc auxiliary account agreement associated with a
customer agreement, not part of the customer's account, but
typically subject to formal agreement between customer and
supplier (utility). Typically this is used to collect revenue owing
by the customer for other services or arrears accrued with the
utility for other services. It is typically linked to a prepaid token
purchase transaction, thus forcing the customer to make a
payment towards settlement of the auxiliary account balance
whenever he needs to purchase a prepaid token for electricity.
The present status of AuxiliaryAgreement can be defined in the
context of the utility's business rules, for example: enabled,
disabled, pending, over recovered, under recovered, written off,
etc.
AuxiliaryAgreementConfig Profile Message profile for AuxiliaryAgreements.
Card PaymentMetering Documentation of the tender when it is a type of card (credit,
debit, etc).
Cashier PaymentMetering The operator of the point of sale for the duration of CashierShift.
Cashier is under the exclusive management control of Vendor.
CashierShift PaymentMetering The operating shift for a cashier, during which he may transact
against the CashierShift, subject to VendorShift being open.
Channel Metering A single path for the collection or reporting of register values
over a period of time. For example, a register which measures
forward energy can have two channels, one providing bulk
quantity readings and the other providing interval readings of a
fixed interval size.
Charge PaymentMetering A charge element associated with other entities such as tariff
structures, auxiliary agreements or other charge elements. The
total charge amount applicable to this instance of Charge is the
sum of fixedPortion plus percentagePortion.
Cheque PaymentMetering The actual tender when it is a type of cheque. Cheque reference
number (as printed on the cheque) is specified in 'name.'
ComFunction Metering Communication function of communication equipment or a
device such as a meter.
ComModuleConfig Profile Profile for configuring communications modules.
61968-9  IEC:2013 – 29 –

Class/Noun Type Description


ConfigurationEvent Metering Used to report details on creation, change or deletion of an
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

entity or its configuration.


ConsumptionTariffInterval PaymentMetering One of a sequence of intervals defined in terms of consumption
quantity of a service such as electricity, water, gas, etc. It is
typically used in association with TariffProfile to define the steps
or blocks in a step tariff structure, where startValue
simultaneously defines the entry value of this step and the
closing value of the previous step. Where consumption is >=
startValue it falls within this interval and where consumption is
< startValue it falls within the previous interval.
Customer Customers Organisation receiving services from ServiceSupplier.
CustomerAccount Customers Assignment of a group of products and services purchased by
the Customer through a CustomerAgreement, used as a
mechanism for customer billing and payment. It contains
common information from the various types of
CustomerAgreements to create billings (invoices) for a Customer
and receive payment.
CustomerAccountConfig Profile Message profile for CustomerAccounts.
CustomerAgreement Customers Agreement between the Customer and the ServiceSupplier to
pay for service at a specific ServiceLocation. It records certain
billing information about the type of service provided at the
ServiceLocation and is used during charge creation to determine
the type of service.
CustomerAgreementConfig Profile Message profile for CustomerAgreements.
CustomerMeterDataSet Profile The CustomerMeterDataSet includes one or more
CustomerAccounts for one or more ServiceLocations for one or
more UsagePoints. TheCustomerMeterDataSet may include one
or more EndDeviceGroups.
DemandResponseProgram Metering Demand response program.
DeviceFunction Metering Function performed by a device such as a meter, communication
equipment, controllers, etc.
EndDevice Metering The EndDevice is equipment that performs the role of an end
device. It may contain functionality such as metrology,
communications, load control, connect/disconnect, or other
capabilities. It is known as “the meter”, “a smart meter”, an
“advanced meter”, ”air conditioner”, “refrigerator”, “pool pump”,
etc. that a CommModule and/or Meter may monitor and/or
control. The asset may be owned by a consumer, a service
provider, utility or other party.
EndDeviceConfig Profile Message used to convey descriptions of one or more
EndDevices.
EndDeviceControl Metering Used to issue commands to EndDevices such as meters. May be
addressed by EndDevice or by EndDeviceGroup.
EndDeviceControls may have control types and parameters.
EndDeviceControls Profile Message used to convey one or more EndDeviceControls
EndDeviceControlType Metering Defines types of EndDeviceControls
EndDeviceEvent Metering Used to report events detected by end devices such as meters.
Each EndDeviceEvent has an event type and a timestamp.
EndDeviceEvents Profile Message used to convey one or more EndDeviceEvents.
EndDeviceEventType Metering Defines types of EndDeviceEvents
EndDeviceFirmware Profile Profile for EndDevice firmware configuration messages.
EndDeviceGroup Metering An EndDeviceGroup is used for grouping end devices for a
variety of purposes including, but not limited to, load control and
other types of demand response. An EndDeviceGroup may
belong to another EndDeviceGroup, and an end device may
belong to zero or more EndDeviceGroups. In some cases the
group ID is maintained within the end device, but in other cases
it can be managed by a metering system.
EndDeviceGroups Profile Use to convey changes in group membership
GetCustomerMeterDataSet Profile Profile for GET requests. See annex J.
– 30 – 61968-9  IEC:2013

Class/Noun Type Description


GetEndDeviceConfig Profile Profile for GET requests. See annex J.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

GetMeterReadings Profile Profile for GET requests. See annex J.


GetMeterServiceRequests Profile Profile for GET requests. See annex J.
Get<ProfileName> Profile Each profile will have a corresponding ""Get" profile that is used
to convey parameters on GET requests.
IntervalBlock Metering Time sequence of Readings of the same ReadingType.
Contained IntervalReadings may need conversion through the
application of an offset and a scalar defined in associated
Pending.
IntervalReading Metering Data captured at regular intervals of time. Interval data could be
captured as incremental data, absolute data, or relative data.
The source for the data is usually a tariff quantity or an
engineering quantity. Data is typically captured in time-tagged,
uniform, fixed-length intervals of 5, 10, 15, 30, or 60 minutes.
Note: Interval Data is sometimes also called "Interval Data
Readings" (IDR).
MasterDataLinkageConfig Profile A message profile used to establish or modify relationships
between objects.
MerchantAccount PaymentMetering The operating account controlled by MerchantAgreement,
against which Vendor may vend tokens or receipt payments.
Transactions via VendorShift debit the account and bank
deposits via BankStatement credit the account.
MerchantAgreement PaymentMetering A formal controlling contractual agreement between Supplier and
Merchant, in terms of which Merchant is authorised to vend
tokens and receipt payments on behalf of Supplier. Merchant is
accountable to Supplier for revenue collected at PointOfSale.
Meter Metering The Meter class is used to describe meters. A Meter is a type of
EndDevice typically used to measure and potentially monitor a
customer load. The EndDevice class definition should be used
as the basis for Meter class.
MeterConfig Profile Message profile for Meter configuration messages.
MeterReading Metering A set of values obtained from the meter. Each MeterReading
may have multiple ReadingTypes, and each ReadingType may
contain multiple values.
MeterReadings Profile Profile for conveying MeterReadings.
MeterReadSchedule Profile A MeterReadSchedule message is used to schedule meter
readings.
MeterServiceRequests Profile A meter service request is a type of work that can be used for a
variety of meter service related activities. These activities would
include meter installation, meter change out, customer
disconnect/reconnect, , etc.
MeterServiceWork Metering Work involving meters.
ObjectNamesConfig Profile Used to add, change, or delete Names class identifiers of CIM
objects.
Pending Metering When present, a scalar conversion that is associatied with
IntervalBlock and which needs to be applied to every contained
IntervalReading value. This conversion results in a new
associated ReadingType, reflecting the true dimensions of
interval reading values after the conversion.
PointOfSale PaymentMetering Logical point where transactions take place with operational
interaction between Cashier and the payment system; in certain
cases PointOfSale interacts directly with the end customer, in
which case Cashier might not be a real person: for example a
self-service kiosk or over the internet.
PricingStructure Customer Grouping of pricing components and prices used in the creation
of customer charges and the eligibility criteria under which these
terms may be offered to a customer. The reasons for grouping
include state, customer classification, site characteristics,
classification (i.e. fee price structure, deposit price structure,
electric service price structure, etc.) and accounting
requirements.
61968-9  IEC:2013 – 31 –

Class/Noun Type Description


PricingStructureConfig Profile Profile for configuring pricing structures.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Reading Metering Specific value measured by a meter or other asset. Each


Reading is associated with a specific ReadingType.
ReadingQuality Metering Quality of a specific reading value or interval reading value.
Note that more than one Quality may be applicable to a given
Reading. Typically not unsed unless problems or unusual
conditions occur (i.e., quality for each Reading is assumed to be
'Good' unless stated otherwise in associated ReadingQuality).
ReadingQualityType Metering Defines types for qualities that can be associated with a reading
value.
ReadingType Metering Type of data conveyed by a specific Reading.
Receipt PaymentMetering Record of total receipted payment from customer.
ReceiptRecord Profile Profile for receipt messages.
ReceiptSummary PaymentMetering Record of detail of receipts pertaining to one shift of operation
(one record per 'tenderKind').
Register Metering Display for quantity that is metered on an end device such as a
meter.
ServiceCategory Customers Category of service provided to the customer.
ServiceCategoryConfig Profile Profile for ServiceCategory configuration messages.
ServiceLocationConfig Profile Profile for ServiceLocation configuration messages.
ServiceSupplier PaymentMetering Organisation that provides services to Customers.
ServiceSupplierConfig Profile Profile for service supplier configuration messages.
Shift PaymentMetering Generally referring to a period of operation or work performed.
Whether shift is open/closed can be derived from attributes
'activiryInterval.start' and 'activityInterval.end'.
The grand total for receipts (i.e., cumulative total of all actual
receipted amounts during this shift; bankable + non-bankable;
excludes rounding error totals) can be derived from Receipt
attributes:
=sum(Receipt.receiptAmount); includes bankable and non-
bankable receipts.
SimpleEndDeviceFunction Metering Simple end device function distinguished by 'kind'; use this class
for instances that cannot be represented by another end device
function subtype.
Tariff PaymentMetering Document, approved by the responsible regulatory agency,
listing the terms and conditions, including a schedule of prices,
under which utility services will be provided. It has a unique
number within the state or province. For Rate Schedules it is
frequently allocated by the affiliated Public Utilities Commission.
Tender PaymentMetering Tender is what is "offered" by the customer towards making a
payment and is often more than the required payment (hence
the need for 'change'). The payment is thus that part of the
Tender that goes towards settlement of a particular transaction.
Tender is modelled as an aggregation of Cheque and Card. Both
these tender types can exist in a single tender bid thus
'accountHolderName' shall exist separately in each of Cheque
and Card as each could have a different account holder name.
TimeTariffinterval PaymentMetering One of a sequence of time intervals defined in terms of real
time. It is typically used in association with TariffProfile to define
the intervals in a time of use tariff structure, where
startDateTime simultaneously determines the starting point of
this interval and the ending point of the previous interval.
Transaction PaymentMetering The record of details of payment for service or token sale.
TransactionRecord Profile Profile for Transactions messages.
TransactionSummary PaymentMetering The record of detail of payment transactions pertaining to one
shift of operation (one record per 'transactionKind').
– 32 – 61968-9  IEC:2013

Class/Noun Type Description


Transactor PaymentMetering The entity that ultimately executes the transaction and who is in
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

control of the process; typically this is embodied in secure


software running on a server that may employ secure hardware
encryption devices for secure transaction processing.
UsagePointLocation Metering Location of an individual usage point. For residential or most
businesses, it is typically the location of a meter on the
customer's premises. For transmission, it is the point(s) of
interconnection on the transmission provider's transmission
system where capacity and/or energy transmitted by the
transmission provider is made available to the receiving party.
The point(s) of delivery is specified in the service agreement.
UsagePointLocationConfig Profile Message used to establish associations to UsagePointLocations.
UsagePoint Metering Logical point on a Distribution Network to which Meter Readings
and/or End Device Events can be attributed. Used at the place
where a physical or virtual meter may be located; however, it is
not required that a Meter be present.
UsagePointConfig Profile Message used to establish associations to UsagePoints.
UsagePointGroup Metering Abstraction for management of group communications within a
two-way AMR system or the data for a group of related usage
points. Commands can be issued to all of the usage points that
belong to a usage point group using a defined group address
and the underlying AMR communication infrastructure.
UsagePointGroups Profile Message used to establish UsagePointGroups.
Vendor PaymentMetering The entity that owns PointOfSale and contracts with Cashier to
receipt payments and vend tokens using the payment system.
Vendor has a private contract with and is managed by Merchant
who is a type of Organisation. Vendor is accountable to
Merchant for revenue collected, who is in turn accountable to
Supplier.
VendorShift PaymentMetering The operating shift for a vendor during which he may transact
against the merchant's account. It aggregates transactions and
receipts during the shift and periodically debits a merchant
account. The totals in VendorShift should always = sum of totals
aggregated in all cashier shifts that were open under the
particular vendor shift.

NOTE The class definitions provided here are for convenience purposes only. The normative definitions are provided by
the CIM.

4.5.3 Classes related to meter reading and control

Table 4 lists those classes that are associated with meter reading and control classes but only
the name of an instance is given within messages defined in this standard. The detailed
attributes of these classes are used in message types defined in other parts of IEC 61968.

Table 4 – Classes related to meter reading and control

Related Class Reference Description


Organisation Common This class is used to identify companies or divisions within
companies. Organisations might have roles as utilities, contractors,
suppliers, manufacturers, etc.
PowerSystemResource Core An entity that describes the logical view of a component part of the
utility business. PowerSystemResources are further classified as
(IEC 61970-301) EquipmentContainers e.g. Substations, ConductingEquipment,
ProtectionEquipment etc.
Instances of type PowerSystemResource may be related to instances
of type Asset.
PowerTransformer Wires An electrical device consisting of two or more coupled windings, with
or without a magnetic core, for introducing mutual coupling between
(IEC 61970-301) electric circuits. Transformers can be used to control voltage and
phase shift (MW flow).
61968-9  IEC:2013 – 33 –

Related Class Reference Description


ServiceLocation Customers A customer ServiceLocation has one or more UsagePoint(s). Meters
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

are related to a UsagePoint. The location may be a point or a


polygon depending on the specific circumstances
For distribution, the ServiceLocation is typically the location of the
utility customer's premise. Because a customer"s premise may have
one or more meters, the UsagePoint is used to define the actual
conducting equipment that the EndDevice attaches to at the utility
customer"s ServiceLocation.
For transmission, it is the point(s) of interconnection on the
transmission provider's transmission system where capacity and/or
energy transmitted by the transmission provider is made available to
the receiving party.
TransformerTank Wires A transformer winding.
(IEC 61970-301)

NOTE The class definitions provided here are for convenience purposes only. The normative definitions are provided by
IEC 61968-11, which describes the distribution extesions to the IEC CIM.

5 Meter reading and control message types

5.1 General

The purpose of this Clause 5 is to describe the message types related to IEC 61968-9. It is
important to note that some of these message types may also be used by other parts of
IEC 61968. The general approach to the realization of message structures and XML schemas
for IEC 61968 messages is described in IEC 61968-1 and IEC 61968-100.

Although they may be represented in sequence diagrams for context and completeness, this
document does not describe message formats that are defined by other parts of IEC 61968.
The message payload structures defined by this part of IEC 61968 are described in Clause 5.

The normative XML schemas for messages defined by this part are provided in Annex H,
providing more detailed, annotated descriptions of the message structures. Annex I provides
XML schemas that are currently informative. Message structures are diagrammed within
Clause 5. The notation convention shows required elements with a solid outline, and optional
elements with dashed outlines.

It is also important to note that the use cases and sequence diagrams provided in this
standard are informative in nature, and are intended to provide examples of usage for the
normative messages definitions. There is no intent by this standard to standardize specific
business processes.

5.2 End device event messages

5.2.1 General

An event is a report of a change of state that may be of potential interest. End device event
messages are designed as a means to convey changes in the state of an end device, either
by the end device itself or by a proxy on behalf of an end device. End device events are
viewed as a potential data stream which is not necessarily synchronized to the collection of
meter reading for billing purposes. However, it may still be relevant to the billing process. A
meter health alarm might be so severe that all readings from the meter have to be considered
invalid. The data consumer (e.g. the MDM System) may receive the available relevant event
data, and consider such during the validation, editing, and estimation process. It may also
report event data to other enterprise systems and use the data to initiate actions such as
creation of a MeterServiceRequest to repair or exchange a faulty meter.
– 34 – 61968-9  IEC:2013

5.2.2 Applications

5.2.2.1 General
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

This standard views “events” as being different than “statuses.” Most MR systems don"t
guarantee a timely delivery of an EndDeviceEvent. A “status” on the other hand is only useful
if it is fresh. The status of an EndDevice is generally obtained using an “OnRequest”
GetMeterReadings. The report of an EndDeviceEvent will eventually arrive to the utility back
office and will be processed in turn. This implies that different applications will naturally fall
into different types of message exchanges depending on both the underlying communication
technology used by the MR system, as well as the need for having timely data. Some systems
may have the ability to report an outage as an event. Other systems may treat it as a status.
Most MR systems will report a change to meter health as an event, some may require it to be
read as a status. Similarly most MR systems will report power quality as an event although
some may treat it as a status.

5.2.2.2 Outage detection

When an outage is not due to a SCADA trip, electric utilities typically depend on the calls from
the customers to identify the location of the fault. However, the use of a MS can provide
another means to identify the location of trouble. It is often possible for a MS to determine
that it has lost contact with a meter, in which case this can be reported as an EndDeviceEvent
for potential use by an outage management system. It is important to note that loss of
communications with a meter may not be sufficient to identify the existence of an outage, as it
is common for some MS technologies to occasionally lose contact with meters for brief
periods of time.

Some MS systems may be prone to false alarms as a result of the particular technology used
to communicate with the meters. Many vendors are working to improve their technology and
the accuracy of the data. The MDM, much like the role it sometimes plays in cleaning up
metered data for billing applications, in many instances, can also play a role in cleaning up
outage data supplied by the MS before it is relayed to the OMS. Such a decision, to route
outage data through the MDM, depends on the capability of the MS to supply accurate data,
the ability of the MDM to clean up data without introducing excessive delays, and the ability of
the OMS to tolerate false alarms and delays. To support outage analysis and filtering of bad
data, the MS may supply audit-trail data and quality of measurement data for the outage
event, much like it supplies audit-trail data for billing reads. Figure 5 describes a deployment
in which the MDM is employed to broker outage information.
61968-9  IEC:2013 – 35 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 5 – Outage Detection, request/reply message exchange, example 1

Outage management systems analyze the circuit in terms of network topology. The
EndDeviceEventType can indicate an event as detected by an end device for consideration in
the analysis, as well as other information such as trouble tickets. Where an EndDeviceEvent
can indicate a condition of interest that may in fact be an outage, an outage is usually the
consequence of outage analysis within an OMS that will group potentially many events
together within a single outage.

The use of an MDM to broker outage data is at the discretion of the utility. In some
deployments, the outage detection request from the OMS may be issued directly to the MS as
in the example of Figure 6.
– 36 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 6 – Outage Detection, request / reply message exchange, Example 2

A reply (synchronous or asynchronous) from the MS will likely be in the form of zero or more
EndDeviceEvents. The mRID or names structure will identify the end devices (e.g. meters)
affected by the outage or restoration. Some data consumers that interact with the MS might
only know how to deal with meter ID"s. Depending on the deployment, it may be required to
limit the scope of exchanged mRID"s to that of meters ID"s using the Name class and not to
that of power system resources in general. EndDeviceEvent.status can indicate “live” or
“dead”. Some metering systems may supplement the status information with collaborative
evidence using the EndDeviceEventDetails class. EndDeviceEventType can be used to
indicate that the status applies to a meter or power transformer. The reason for the event can
be described (e.g. EndDeviceEvent.reason = “consecutiveFailCounter”) and quantified (e.g.
EndDeviceEvent.severity = ”3”).

While the request/reply exchange is useful whenever the OMS needs supplementary
information, some MS are able to self-detect outages. A pub/sub exchange is ideal in these
situations. Figure 7 shows such an exchange at a deployment where the MDM serves as an
information broker. Figure 8 shows a deployment with information going directly from the MS
to the OMS.
61968-9  IEC:2013 – 37 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 7 – Outage Detection, publish/subscribe exchange, Example 1

The following sequence diagram shows an example of event propagation without the use of
an MDM.

Figure 8 – Outage Detection, publish/subscribe exchange, Example 2

Some deployments may wish to limit the number of interfaces supported. The MeterReadings
message structure also provides the means to convey EndDeviceEvents.

The preceding examples reflect the exchange of end device event messages to support
outage management functions. As discussed previously, it is also frequently desirable to have
an Outage Management System or MDM System make an on-demand read request to the
Metering System to obtain the current energization status of a device. This is accomplished
using a get(MeterReadings) exchange as described in 5.3. In such cases, the ReadingType
(see Annex C) requested will indicate that it is the energization state that is being requested.

5.2.2.3 Meter Health Events

Some types of meters can sometimes generate meter health events, which can be used to
identify issues with meter hardware, configuration or connection that should be resolved. The
– 38 – 61968-9  IEC:2013

alarms include such things as diagnostic alarms, tamper alarms, or other unusual conditions.
The severity of the alarm might range from a simple notification to “fatal”. Often times,
resolution of meter health events require a site visit, so typically they result in the creation of
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

a MeterServiceRequest. Meter Health Events events are communicated using


EndDeviceEvent messages.

Figure 9 – Meter Health Event exchange, Example 1

In some deployments, the MDM will be present to broker meter health data for other
stakeholders and potentially take action to initiate corrective actions as described in the
scenario of Figure 9. Other installations however might not have an MDM or use it in this way.
It is possible for the MS to publish data directly to the stakeholders that are equipped to
receive it. Such an exchange is depicted in Figure 10.
61968-9  IEC:2013 – 39 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 10 – Meter Health Event exchange, Example 2

5.2.2.4 Power Quality Event

Meters may collect information related to power quality, including but not limited to,
momentary outage events, sustained outage events, low or high voltage events, and high
distortion events. This information could be used for outage analysis, maintenance scheduling
or capacity planning. Power quality events are a subtype of EndDeviceEvent.

Power quality events may be brokered (i.e. publications managed) by an MDM (as described
in Figure 11), or sent directly to the various stakeholders (as described in Figure 12).

Figure 11 – Power quality event exchange, Example 1


– 40 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 12 – Power quality event exchange, Example 2

5.2.3 Message format

Meter event messages are implemented using EndDeviceEvent structures in order to support
a wider variety of event sources than just meters. The EndDeviceEvent.EndDeviceEventType
(see Annex E) is a reference to an enumeration which indicates the type of event, such as
outage detection, meter health, or power quality. The timestamp and mRID or a unique name
of the end device are also required. The message format is described in Figure 13.
61968-9  IEC:2013 – 41 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 13 – End device event message format

As noted by Figure 13, only the timestamp and EndDeviceEventType elements are required,
along with either an mRID or a unique name of the end device. The EndDeviceEventType
element will allow different event types (e.g. meter health, outage detection, etc.) to be
differentiated. Different event types would allow for an EndDeviceEvent message to convey
events related (including but not limited) to:

Sustained outage detection


Momentary outage detection
Low voltage threshold detection
High voltage threshold detection
– 42 – 61968-9  IEC:2013

Distortion
Meter health
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tamper detection
Revenue event

The detailed XML schema is provided in Annex H. The following is an XML example for an
EndDeviceEvent.

<?xml version="1.0" encoding="UTF-8"?> <end:EndDeviceEvents


xmlns:end="http://iec.ch/TC57/2011/EndDeviceEvents#"
xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
<end:EndDeviceEvent>
<end:createdDateTime>2011-11-10T21:54:53.404+01:00</end:createdDateTime>
<end:issuerID>External System 1</end:issuerID>
<end:issuerTrackingID>123</end:issuerTrackingID>
<end:severity>5</end:severity>
<end:Assets>
<end:mRID>01f8b2e5-a677-4f2c-a6c0-1e79b409c55e</end:mRID>
<end:Names>
<end:name>Meter 123</end:name>
<end:NameType>
<end:name>Meter Name</end:name>
<end:NameTypeAuthority>
<end:name>Utility ABC</end:name>
</end:NameTypeAuthority>
</end:NameType>
</end:Names>
</end:Assets>
<end:EndDeviceEventType ref="3.12.0.257"/>
</end:EndDeviceEvent>
</end:EndDeviceEvents>

The EndDeviceEvent is logically generated by an EndDevice and/or a UsagePoint, either of


which can be identified by mRID and/or Name. As in IEC 61968-9:2009, an EndDeviceEvent
is associated with an Asset, where typically this will be an EndDevice.

5.3 Meter reading messages

5.3.1 General

Meter readings messages are designed to allow data collected by or calculated on behalf of a
meter to be conveyed. This may include measured quantities, calculated quantities, state
information or collected history. Whenever a “measurement” is required from an end device, a
MeterReading exchange is quite likely the appropriate tool for the job. The end device may
have metrology capability, and if so, is most likely called a “meter.” But there are other
potential applications for MeterReading. If a data consumer wishes to measure the position of
the switch on a connect/disconnect switch, this can be done as a MeterReading exchange. If
a data consumer wishes to measure the “energisation” status of the end device, this can be
done with a MeterReading exchange or alternatively, with an EndDeviceEvent exchange as
described in 5.2.

5.3.2 Applications

5.3.2.1 Periodic meter reads

It is necessary to periodically gather meter readings from a MS for billing through the
customer billing system. The request for meter reading should specify a meter or group of
meters, a type of reading to collect, and a frequency and duration of interest. The scheduled
frequency may consist of regular or irregular periods.

The MeterReadSchedule request may be initiated to the MS from any of the following:

• the CIS (in an effort to collect billing determinants);


61968-9  IEC:2013 – 43 –

• a planning and scheduling application (in an effort to acquire engineering data about the
distribution network);
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• an OMS (to establish a stream of status information);


• a meter data management system (in an effort to broker data for any or all of the above
applications);
• the MS itself may also self-initiate a MeterReadSchedule.

An example for one such exchange (this one using an MDM) is shown in Figure 14.

Figure 14 – Example use of meter read schedule to create subscription

Some metering systems may have the ability to decouple MeterReading collection from
MeterReading reporting. For Metering Systems without this capability, readings may be
reported immediately upon collection. In the MeterReadSchedule request, MeterReadings
may be requested using a variety of parameters, including:

• Specific meter, using the EndDevice mRID or Names.name (see Annex G for discussion of
the Names class)
• EndDeviceGroups, where a EndDeviceGroup identifies a group address used within the
Metering System
• UsagePoint where a meter is located, using UsagePoint mRID or Names.name
• UsagePointGroups, where UsagePointGroup identifies a groupAddress used within the
Metering System
• As specified using a TimeSchedule
• ReadingTypes can be specified to identify the desired reading types

5.3.2.2 Manual meter reading

Meter readings can be obtained manually by a meter reader. Data collected may be
maintained by the meter data manager. Meters may collect a number of different
measurement types. Some types of meters may measure more than one phase, or may collect
values for non-electrical measurements, such as water or gas.

A meter reader may input data shown on the panel of meter into a handheld device, which
could be regarded as a metering system. Data input may occur several hundred times per
– 44 – 61968-9  IEC:2013

day. A meter reader may present an account of the read to the customer. Note that this
account is not an invoice. Billing would be generated normally by the CIS even in the manual
reading case. Figure 15 shows such an exchange.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 15 – Example manual meter reading exchange

At the end of the day of work, all data stored in the handheld device is sent to the MDM via a
communication network. The MDM publishes a message to the CIS informing of the creation
of MeterReading.

Schedules for walking a manual meter reading route are decided well in advance of
performing the work.

5.3.2.3 On-Request meter read

Meter read requests are issued to a MS in order to obtain meter readings on a per request
basis. The MS will send a request to the desired meters. These can be used for billing
inquiries, outage extent verification, verification of restoration and other business purposes..

Many utilities have a policy of routing all revenue readings through the MDM so that all data
will receive the same level of validation. However, not all MDM systems are able to offer
validation services for outage data. For those that do, the utility shall weigh the value of MDM
validation over the time delay it may introduce, as well as the ability of the particular OMS
solution to reject incongruent data. For this reason, the example diagram shows revenue
readings routed through the MDM, but outage data routed around it.

It is important to note that not all metering systems support ""on request" readings. For those
that do, the implementation can also vary significantly.

On-request reads may be initiated to the MS from systems such as any of the following:

• The CIS (in an effort to collect billing determinants).


61968-9  IEC:2013 – 45 –

• A Planning and Scheduling application (in an effort to acquire engineering data about the
distribution network).
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• An OMS (in order to verify if a customer is affected by an outage or has been restored)
• A meter data management system (in an effort to broker data for any or all of the above
applications).
• The MS itself may also directly initiate a meter read.

An example for one such exchange (this one using an MDM) is shown in Figure 16.

Figure 16 – Example On-Request meter read

5.3.2.4 Historical meter data access

A distribution network planner may use historical meter reading values as load information for
capacity planning purposes. (See the request/reply example in Figure 17).This would permit
usage to be aggregated to determine loads for a transformer or feeder.
– 46 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 17 – Historical MeterData exchange

It is important to note the use of request parameters to qualify requests for meter data,
filtering the results to obtain data for specific meters within specific timeframes.

5.3.2.5 Billing inquiry

A customer or an internal source may identify a customer billing issue. A meter read request
in combination with historical meter reads may be used to resolve the billing issue. The top of
Figure 18 shows an inquiry being satisfied by data which recently arrived, while later on in the
day an inquiry is made which requires a fresh reading from the meter.

In some cases the desired data may be accessible from the MDM. In other cases, it may be
necessary to issue a read request remotely through the MS, or manually through a meter
service request.

Figure 18 – Example billing inquiry message exchange


61968-9  IEC:2013 – 47 –

5.3.3 Message formats

The detailed XML schema for messages are described in Annex H. Figure 19 shows the
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

message format used to present meter readings from one or more end devices.

Figure 19 – Meter readings message format


– 48 – 61968-9  IEC:2013

The MeterReadings message structure allows for:

• readings from one or more meters


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• reading values each have an associated reading type, timestamp and value
• many quality values can be associated with each reading value.
• readings can be supplied in the form of interval blocks, where readings of a common
reading type are grouped together
• event histories can be returned with meter readings

Figure 20 shows the details of the structure used to convey Readings, where each Reading
identifies a specific ReadingType (by reference), value and optional quality codes.The
timeStamp is used to identify when the reading was captured. The timePeriod can be used to
identify a specific time interval. The optional reportedDateTime can be used to identify when
the reading was actually reported. The ReadingType is used to identify the meaning of the
reading, data type of the value and the meaning of the different time values.

Figure 20 – Reading structure

Within a reading, the timeStamp and timePeriod attributes can be used to identify time-related
aspects of the reading, with specific usage based upon reading type, where details are
described in Annex C as needed. The following examples illustrate the general conventions
for the use of timeStamp and timePeriod.
61968-9  IEC:2013 – 49 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 21 – Timestamps assigned between systems

Figure 21 shows the way that timestamps are assigned as values are created and passed
between systems. From the perspective of the CIS and MDMS, there exists a “timePeriod” of
interest for (perhaps) a billing period. A “get” request might specify this time range, and the
AMI or MDMS would “reply” with readings that fall within this range. Important points in time
regarding the generation and reporting of the value are also timestamped. All of these
timestamps are found within the meterReadings schema. Another view of the same example
(with real dates and times) is expressed below in Figure 22.

Figure 22 – Conventions for timeStamp and timePeriod

The IntervalBlock structure allows for a set of reading to be grouped by a common


ReadingType and as a convenience for representation of a time series.
– 50 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 23 – IntervalBlock structure

The following diagram shows the convention for use of a timeStamp for interval data where an
associated reading type identifies that the reading value is for a specified interval.

Different MR systems work in different ways, but for the purpose of the standard, timestamps
denote the end of the interval. The implied generation process is described below in
Figure 24.
61968-9  IEC:2013 – 51 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 24 – Interval data timestamp generation

When a timestamp is used, it shall fall within a time range from 00:00:00 to 23:59:59 as
depicted in Figure 25. A value of 23:59:59 plus 1 s places the time at midnight which is the
start of the next day.

Figure 25 – Time interval conventions

Note that as defined by ISO 8601, the time 24:00 of the current day is the same as 00:00 for
the next day. A day starts and ends at 00:00. It is important to note that interval data can be
conveyed using IntervalBlocks with IntervalReadings or simply using Readings. IntervalBlocks
shall be used in cases where the PendingCalculation elements are needed, otherwise they
simply allow for a reduced XML footprint over Readings, which may be important in some
situations.
– 52 – 61968-9  IEC:2013

Key to the reporting of a value from a meter is the reading type. The ReadingType class in the
CIM is defined to allow capture of the following information as related to the description of a
reading type, as is more thoroughly defined in Annex C.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 26 – ReadingType structure

While the ReadingType structure is present in the MeterReadings message, it should be


expected that in normal practice it will not be populated, as it is anticipated that the
consuming system will already be configured with the appropriate ReadingType definitions.
The details of this and other classes specific to metering are described in the Metering
package of the CIM. A more thorough discussion of reading types is provided in Annex C.
61968-9  IEC:2013 – 53 –

Readings are not limited to metering devices. Any EndDevice may potentially produce a
measurement. In this edition of IEC 61968-9, the asset producing the reading shall be
identified using the Meter class, even though the device may not be a meter. It is expected
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

that all assets have a unique mRID or Names.name so that meters can be distinguished from
remote connect/disconnect switches, and from other devices. It is expected that the future
edition of IEC 61968-9 will provide a more explicit method of dealing with readings from
devices other than Meters.

Interval data has unique timestamp requirements. The extended capabilities of ISO 8601
provide the means to specify both a formal interval length (as an ISO 8601 “period” of time),
as well as a fixed reference point.

The following XML provides some XML example payloads of MeterReadings messages.

<?xml version="1.0" encoding="UTF-8"?>


<mr:MeterReadings xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#">
<mr:MeterReading>
<mr:Meter>
<mr:Names>
<mr:name>63.89.98.184</mr:name>
<mr:NameType>
<mr:description>This is an endpoint serial number</mr:description>
<mr:name>EndpointID</mr:name>
<mr:NameTypeAuthority>
<mr:description>AssetManagementSystem</mr:description>
<mr:name>com.company.assets</mr:name>
</mr:NameTypeAuthority>
</mr:NameType>
</mr:Names>
</mr:Meter>
<mr:Readings>
<mr:timeStamp>2011-12-05T17:21:40.628Z</mr:timeStamp>
<mr:value>25.633</mr:value>
<mr:ReadingType ref = "0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0"/>
</mr:Readings>
<mr:Readings>
<mr:timeStamp>2011-12-05T17:21:40.628Z</mr:timeStamp>
<mr:value>10.0</mr:value>
<mr:ReadingType ref = "0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.38.0"/>
</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>

<?xml version="1.0" encoding="UTF-8"?>


<mr:MeterReadings xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#">
<mr:MeterReading>
<mr:Meter>
<mr:Names>
<mr:name>63.89.98.184</mr:name>
<mr:NameType>
<mr:description>This is an endpoint serial number</mr:description>
<mr:name>EndpointID</mr:name>
<mr:NameTypeAuthority>
<mr:description>AssetManagementSystem</mr:description>
<mr:name>com.company.assets</mr:name>
</mr:NameTypeAuthority>
</mr:NameType>
</mr:Names>
</mr:Meter>
<mr:IntervalBlocks>
<mr:IntervalReadings>
<mr:reportedDateTime>2001-12-17T09:30:47Z</mr:reportedDateTime>
<mr:timeStamp>2001-12-17T09:30:47Z</mr:timeStamp>
<mr:value>25.44</mr:value>
<mr:timePeriod>
<mr:end>2001-12-17T09:30:47Z</mr:end>
<mr:start>2001-12-17T09:30:47Z</mr:start>
</mr:timePeriod>
</mr:IntervalReadings>
<mr:ReadingType ref = "0.0.2.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0"/>
</mr:IntervalBlocks>
– 54 – 61968-9  IEC:2013

<mr:Readings>
<mr:timeStamp>2001-12-17T09:30:47Z</mr:timeStamp>
<mr:value>10.0</mr:value>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<mr:ReadingType ref = "0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.38.0"/>


</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>

The concept of “coincident readings” deserves some attention. A coincident reading is a


MeterReading that occurs at the same point in time as some other MeterReading or
EndDeviceEvent.

Some meters have the ability to report a reading that was coincident with a certain other
MeterReading or EndDeviceEvent (hereinafter referred to in IEC 61968-9 as the “trigger”). For
example, it might record the “power factor coincident with the billing period maximum demand.

Additionally, some processes call for a coincident read to be reported. For example, when a
meter is installed, it is common to capture an “initial reading.” Similarly, when a meter is
disconnected, it is common practice to capture a “final read” coincident with the disconnection
event.

Some systems may perform analysis of the data in storage to identify analytically derived
coincident readings. For example:

• the voltage at UsagePoint A at the time of the peak daily demand on the distribution
transformer (UsagePointB) that serves UsagePoint A. (UsagePoint “B” could be either a
real or a virtual UsagePoint.)
• the 15-minute interval consumption at UsagePoint A at the time of the peak demand on a
distribution network (UsagePoint C) on a hot, summer day
• a BulkQuantity kwh reading for a UsagePoint at the time of an EndDeviceEvent such as a
meter disconnect.

The MeterReading class has an optional Boolean element called “isCoincidentTrigger.” The
element doesn"t have to be used in a message, but if it is, there are rules for its
interpretation. If any instance of a MeterReading message is marked with the
isCoincidentTrigger Boolean set to “true”, then all other MeterReadings within the same
MeterReadings message are considered to be coincident with the so marked MeterReading.
Only one MeterReading element within a single MeterReadings message may have its
isCoincidentTrigger Boolean set to “true”. If the isCoincidentTrigger Boolean is absent, it is
defined to be “false”. It is recommended that the “trigger” MeterReading should have a
timeStamp if this information is available.

The GetMeterReadings profile can be used to request MeterReadings that are coincident with
a given MeterReading. This can be accomplished by including in the GetMeterReadings
message a MeterReadings element in which the isCoincidentTrigger Boolean is set to “true” –
in other words by specifying the “trigger” MeterReading in the GetMeterReadings filter criteria.

NOTE It is recognized that there may be small differences in time between a coincident trigger and the reading(s)
that are coincident with the trigger. For example, a reading taken in conjunction with a meter disconnect can
actually be taken several seconds after the operation of the disconnect switch. It is outside the scope of this
Standard to define the window for readings to be considered coincident.

In the following example, a metering system identifies a power factor measurement that is
coincident with the maximum demand for a given meter when the exact date and time of the
maximum demand is not known:
<mr:MeterReadings
xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterReadings#MeterReadings.xsd"
xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<mr:MeterReading>
<mr:Meter>
<mr:Names>
61968-9  IEC:2013 – 55 –

<mr:name>Meter_XYZ</mr:name>
</mr:Names>
</mr:Meter>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<mr:Readings>
<mr:value>0.0914159</mr:value>
<mr:ReadingType ref = "0.0.0.6.0.1.38.0.0.0.0.0.0.0.0.0.65.0"/>
<!--indicating electricitySecondaryMetered powerFactor (cos?)-->
</mr:Readings>
</mr:MeterReading>
<mr:MeterReading>
<mr:isCoincidentTrigger>true</mr:isCoincidentTrigger>
<mr:Meter>
<mr:Names>
<mr:name>Meter_ABCx1</mr:name>
</mr:Names>
</mr:Meter>
<mr:Readings>
<mr:ReadingType ref = "8.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0"/>
<!--billingPeriod maximum indicating forward electricitySecondaryMetered demand (kW)-->
</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>

In the next example, a metering system or MDMS identifies the final meter reading coincident
with disconnection of service via RCD:

<mr:MeterReadings
xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterReadings#
MeterReadings.xsd"
xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<mr:MeterReading>
<mr:isCoincidentTrigger>true</mr:isCoincidentTrigger>
<mr:EndDeviceEvents>
<mr:createdDateTime>2010-12-17T09:30:47Z</mr:createdDateTime>
<mr:reason>moveOut</mr:reason>
<mr:EndDeviceEventType ref = "3.31.0.68"/>
<!--ElectricityMeter RCDSwitch Disconnected -->
</mr:EndDeviceEvents>
<mr:Meter>
<mr:Names>
<mr:name>Meter1</mr:name>
</mr:Names>
</mr:Meter>
</mr:MeterReading>
<mr:MeterReading>
<mr:Meter>
<mr:Names>
<mr:name>Meter1</mr:name>
</mr:Names>
</mr:Meter>
<mr:Readings>
<mr:timeStamp>2010-12-17T09:30:49Z</mr:timeStamp>
<mr:value>123456</mr:value>
<mr:ReadingType ref = "0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0"/>
<!--billingQuantity net electricitySecondaryMetered energy (kWh)-->
</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>

The next example demonstrates a request to get meter readings from a metering system or
MDMS which are coincident with a disconnect that occurred within a specified time interval.
The request is an open-ended invitation to send any type of MeterReading data which is
coincident with an RCDSwitch disconnect for a given EndDevice (meter). The response to this
request could very well be nothing more than the “final meter reading” example provided
above. (If a more specific response was sought, it would be possible to filter for only the
desired ReadingType(s) by populating the ReadingType element in the GetMeterReadings
profile.)

<mr:GetMeterReadings
xsi:schemaLocation="http://iec.ch/TC57/2011/GetMeterReadings#GetMeterReadings.xsd"
– 56 – 61968-9  IEC:2013

xmlns:m="http://iec.ch/TC57/2011/GetMeterReadings#"
xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
<mr:EndDevice>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<mr:Names>
<mr:name>Meter1</mr:name>
</mr:Names>
</mr:EndDevice>
<mr:MeterReadings>
<mr:isCoincidentTrigger>true</mr:isCoincidentTrigger>
<mr:EndDeviceEvents>
<mr:EndDeviceEventType>
<mr:Names>
<mr:name>3.31.0.68</mr:name>
<!--ElectricityMeter RCDSwitch Disconnected -->
</mr:Names>
</mr:EndDeviceEventType>
</mr:EndDeviceEvents>
</mr:MeterReadings>
<mr:TimeSchedule>
<mr:scheduleInterval>
<mr:end>2010-12-31T23:59:59Z</mr:end>
<mr:start>2010-12-01T00:00:00Z</mr:start>
</mr:scheduleInterval>
</mr:TimeSchedule>
</mr:GetMeterReadings>

NOTE When using timestamps as filters, note that the TimeSchedule.scheduleInterval elements are used to frame
a request for data falling within a certain range. The MeterReadings response may populate the
MeterReadings.MeterReading.valuesInterval elements to identify the range of dates offered in the response. The
user will also find that interval data (which contains a time-ordered series of values) has no place in a discussion of
coincident data. Only one interval may be coincident with a given event or another MeterReading. It therefore
seems inappropriate to populate a series of MeterReading.IntervalBlocks.IntervalReadings elements. A single
value may be presented as an interval, or the single interval value may be presented as a stand alone
MeterReading.Readings instead.

The ability to schedule when meter readings are obtained is provided through the use of a
MeterReadSchedule request.The following is the structure used for the payload of a
MeterReadSchedule request message:
61968-9  IEC:2013 – 57 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 27 – Meter read schedule message format

Several elements in the TimeSchedule of the MeterReadSchedule are profile are unique to
that profile and deserve special definition. These include:

disabled – True if this schedule is deactivated (disabled)

offset – The offset for the recurring (periodic) times in the TimeSchedule. Each point in the
time series defined by scheduledInterval and either recurrencePeriod or recurrencePattern
will be shifted by adding the offset value. The use of TimeSchedule.offset is not applicable
when discrete TimePoints are specified in lieu of a recurrencePeriod or recurrencePattern.

recurrencePattern – Interval at which the scheduled action repeats, from the beginning of one
action to the beginning of the next action (e.g., first Monday of every month, last day of the
month, etc.). Used when the interval cannot be defined as a fixed number of seconds between
points in time. The use of recurrencePattern is not applicable when recurrencePeriod is
specified or when discrete TimePoints are specified in lieu of a recurrencePeriod or
recurrencePattern.

recurrencePeriod – Duration between time points, from the beginning of one action to the
beginning of the next action. Used when the interval can be defined as a fixed number of
– 58 – 61968-9  IEC:2013

seconds between points in time. The use of recurrencePeriod is not applicable when
recurrencePattern is specified or when discrete TimePoints are specified in lieu of a
recurrencePeriod or RecurrencePattern.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.4 End device control messages

5.4.1 General

There are many types of end device control messages. These are used to send instructions to
one or more end devices. EndDeviceControls may result in one or more consequential
EndDeviceEvent message.

5.4.2 Applications

5.4.2.1 Load control

Load control (a.k.a. direct load control) requests can often be made to a MS for the purpose
of load curtailment. This request would typically be initiated from network operations. Not all
MS will have load control capabilities.

It should also be noted that this is different from a disconnect, where a disconnect results in
the complete loss of power to a single customer.

A load control will typically result in the shedding of specifically configured loads (e.g. air
conditioning, pumps, etc.)

The load control function executes load shed commands which are computed by load
management software (contained in the network operations block). The load management
software is used to compute an appropriate load-shed amount, and could potentially include
many factors including the predicted duration of generation shortfalls, historical usage
patterns, real-time usage data, and weather.
61968-9  IEC:2013 – 59 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 28 – Example load control message exchange

The example in Figure 28 shows how load history may be obtained from the MDM in the form
of MeterReadings and used to perform load analysis. It also shows load control commands
being issued by the LMS to the load control system. Deployments that don"t support an MDM
would interact directly with the MS instead.

Load control commands are implemented as a type of EndDeviceControl, where the command
can be addressed by EndDeviceGroup (using a group address), by EndDevice (using mRID)
or by CustomerAgreement.

Load control may also be implemented using PAN devices.

5.4.2.2 Load control device installation

The installation of load control units is usually more labour intensive than installing a meter,
but the data exchange requirements are simpler. LC units are different from meters in the
sense that they don"t require periodic recalibration. Once an LC unit is installed it will
probably remain in place for the life of the unit, even if the customer withdraws from the LC
program, or if there is a change in tenancy.
– 60 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 29 – Example message exchange for LC unit installation

Before travelling to the service location, the installer will know the customer account data, the
type of load control unit to be installed, and the ratings of the device to be controlled. The
installation data can confirm device ratings, and where appropriate, document the port
number of the LC unit wired to the device. The results of the installation can be published to
all of stakeholders as depicted in Figure 29.

5.4.2.3 Change of customer program

Particular metering solutions are usually chosen to fulfil specific metering needs as a result of
customer program enrolment. In many cases, a flexible metering solution can provide
coverage for a range of customer programs. When a customer transitions from enrolment in
one program to another, it may simply require a change to the meter (or communication
module) configuration. In extreme cases it may require a meter change out. In other cases, it
may require no change at all. Changes to a configuration will need to be communicated
amongst the stakeholders. An example exchange in which the deployment involves an MDM
is described in Figure 30. Another example in which the deployment lacks an MDM is
described in Figure 31.
61968-9  IEC:2013 – 61 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 30 – Example message exchange for change of customer program

Changes to the meter configuration may be expressed as changes to the configuration of an


EndDevice.

Figure 31 – Example message exchange for change of customer program w/o MDM

In other cases, a change to the customer program might not be accommodated with a meter
reconfiguration. The program change may require a meter changeout (refer to 5.5 for more
information on meter changeouts). Meter changeouts entail a different workflow than meter
– 62 – 61968-9  IEC:2013

reconfigurations. This will be reflected in the message exchange between systems. An


example exchange is depicted in Figure 32.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 32 – Example for change of customer program with meter change out

See 5.6.2 on meter installation and removal for additional details on the MeterServiceRequest
message.

5.4.2.4 Meter disconnect and reconnect

For a variety of reasons, such as non-payment, it may be necessary to disconnect or


reconnect a customer. When disconnected, recorded usage should be zero and out of power
complaints should be ignored. When it is not possible to perform a disconnect or reconnect
remotely through an MS, a meter service request will typically be issued to perform the
disconnect or reconnect manually. Example message exchanges for remote operation are
depicted below in Figure 33 and Figure 34.
61968-9  IEC:2013 – 63 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 33 – Example message exchange for meter connect/disconnect


– 64 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 34 – Example of remote connect/disconnect directly between CIS and MS

5.4.2.5 Real-Time pricing

Real-time pricing signals and/or schedules can be sent to an end device via the MS. There
are several ways this can be accomplished, such as:

• price signal issued in real-time identifying a price for a given time interval
• time of use (TOU) schedules published, which cause changes in the accumulation for
each TOU Tier
• energy price schedules published in advance.

Often the EndDeviceGroup can be used to differentiate meters with different contracts or
tariffs.

The example in Figure 35 shows a price signal being sent from network operations, to the MS.
The MS then acts as a network service provider to communicate the price in real time to
meters and other equipment.
61968-9  IEC:2013 – 65 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 35 – Example message exchange for real-time price signal

Price signals are implemented as a subtype of EndDeviceControl, where the price is a


message parameter.

5.4.3 Message format

5.4.3.1 General

Figure 36 describes the structure of an EndDeviceControls message. The XML schema for
the EndDeviceControls message is defined in Annex H.
– 66 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 36 – End device controls message format

Within this message payload structure, specific meters may be addressed by EndDevice (e.g.
meter) EndDeviceGroup, UsagePoint and/or UsagePointGroup. Aside from at least one
address, the only required element is the EndDeviceControlType, which identifies the type of
control to be performed. Examples of the different control types that could be used include,
but are not limited to:

• load control signal


• price signal or schedule
• remote disconnect
• remote reconnect
• demand reset
61968-9  IEC:2013 – 67 –

• demand reduction signal


• sending a text message to a PAN device
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• sending pricing signals to a PAN device


• sending load control / demand response events to a PAN device.

The following subclauses 5.4.3.2 to 5.4.3.5 are representative XML examples for
EndDeviceControls.

5.4.3.2 Example of a demand reset payload

The following is an example for a demand reset. Note that in this example there are two
devices being addressed, each of these is in its own EndDevices element. One of them is
addressed by mrID and the other is addressed by Names.

<?xml version="1.0" encoding="UTF-8"?>


<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:m = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:EndDeviceControlType ref = "3.8.0.214"/>
<m:EndDevices>
<m:mRID>3dc53ee5-777e-50b4-8699-a1c224f45f3d</m:mRID>
</m:EndDevices>
<m:EndDevices>
<m:Names>
<m:name>MeterABC</m:name>
<m:NameType>
<m:name>MeterID</m:name>
</m:NameType>
</m:Names>
</m:EndDevices>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.4.3.3 Example of a meter disconnect by group

The following is an example of a meter disconnect by group.

<?xml version="1.0" encoding="UTF-8"?>


<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:m = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:EndDeviceControlType ref = "3.31.0.23"/>
<m:EndDeviceGroups>
<m:mRID>3dc53ee5-777e-50b4-8699-a1c224f45f3d</m:mRID>
</m:EndDeviceGroups>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.4.3.4 Example of a scheduled disconnect by group

The following is an example of a scheduled disconnect by group.

<?xml version="1.0" encoding="UTF-8"?>


<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:m = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:EndDeviceControlType ref = "3.31.0.23"/>
<m:EndDeviceGroups>
<m:Names>
<m:name>Disconnects in Region 123, May 2011</m:name>
– 68 – 61968-9  IEC:2013

<m:NameType>
<m:name>Regional Disconnect Group</m:name>
<m:NameTypeAuthority>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:name>Utility ABC</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:EndDeviceGroups>
<m:primaryDeviceTiming>
<m:interval>
<m:start>2001-12-17T09:30:47Z</m:start>
</m:interval>
</m:primaryDeviceTiming>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.4.3.5 Example of a meter connection by name

The following is an example of a meter connection, where the the meter is specified by name.

<?xml version="1.0" encoding="UTF-8"?>


<!--Connect Meters by Meter Name-->
<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:obj = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:mRID>76e7a0a3-3e33-4d21-b78f-b42227823ec7</m:mRID>
<m:issuerID>External System 1</m:issuerID>
<m:issuerTrackingID>123</m:issuerTrackingID>
<m:EndDeviceControlType ref = "3.31.0.18"/>
<m:EndDevices>
<m:mRID>45e7a0a3-3e99-4d17-b43f-b67221212ec0</m:mRID>
<m:Names>
<m:name>Meter 123</m:name>
<m:NameType>
<m:name>Meter Name</m:name>
<m:NameTypeAuthority>
<m:name>Utility ABC</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:EndDevices>
<m:EndDevices>
<m:mRID>09e7a0a3-3e50-4d10-b40f-b40980088ec3</m:mRID>
<m:Names>
<m:name>Meter 456</m:name>
<m:NameType>
<m:name>Meter Name</m:name>
<m:NameTypeAuthority>
<m:name>Utility ABC</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:EndDevices>
<m:primaryDeviceTiming>
<m:interval>
<m:start>2011-06-17T09:30:47.0Z</m:start>
</m:interval>
</m:primaryDeviceTiming>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.5 Meter service requests

5.5.1 General

Meter service requests are a subclass of Work, where an EndDevice is involved.


61968-9  IEC:2013 – 69 –

5.5.2 Applications

5.5.2.1 Meter installation and removal


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

It may be necessary to install, remove or configure meters as a consequence of the


registration of a new customer, removal of a customer or the switch of a customer from one
supplier to another. There may also be the need to change out a meter which involves the
removal of the old meter, installation of the new meter and configuration of the new meter as
needed by the metering system.

Prior to meter installation, subscriptions have been established between the MS and the MDM
to receive updates to customer data (see 5.10 on master data management’for more details).
The workflow for a meter change out is shown in Figure 37. This encompasses both the meter
installation and meter removal processes.

The OperationSet steps are included to synchronize the revised Master Data (the
configuration data for the new and old meters and the association changes with the
UsagePoint) with the MDM System and the Metering System. See 5.10 and Annexes K and L
for additional information related to Master Data Management.

Figure 37 – Example meter installation and removal message exchange

The initial reading of the new meter and final reading of the old meter are of type
MeterReading. MeterReading contains “UsagePoint” which is needed (in addition to
ServiceLocation) to help identify the location of the new and old meters.
– 70 – 61968-9  IEC:2013

5.5.2.2 Meter replaced due to end device event

EndDeviceEvents (as described in 5.2) can cause an evaluation to occur which results in a
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

request for a meter change out. Meter events may be published from the MS or MDM. Figure
38 describes an example exchange where the MDM has identified a problem, and brought it to
the attention of the WMS which decides to change out the meter.

Once again, the OperationSet steps are included to synchronize the revised Master Data (the
configuration data for the new and old meters and the association changes with the
UsagePoint) with the MDM System and the Metering System. See 5.10 and Annexes K and L
for additional information related to Master Data Management.

Figure 38 – Example end device event message exchange due to meter changeout

5.5.2.3 Meter changed-out due to CIS alarms or customer complaints

Data analysis by the CIS or customer billing complaints may cause the customer service
department to request a site-visit to the customer location and possibly a meter change out.
Figure 39 describes an example exchange where the CIS has identified a problem, and
brought it to the attention of the WMS which decides to change out the meter.

Once again, the OperationSet steps are included to synchronize the revised Master Data (the
configuration data for the new and old meters and the association changes with the
61968-9  IEC:2013 – 71 –

UsagePoint) with the MDM system and the metering system. See 5.10 and Annexes K and L
for additional information related to master data management.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 39 – Example message exchange due to CIS alarms

5.5.2.4 Meter changed-out for recalibration.

The WMS or other enterprise systems such as AM may track when meter recalibration is due,
and change-out the meter. Some utilities may view the actual meter change out as a WMS
issue as depicted in Figure 40, while others treat it as a MS issue.
– 72 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 40 – Example message exchange when meter is changed out for recalibration

The OperationSet steps are included to synchronize the revised Master Data (the
configuration data for the new and old meters and the association changes with the
UsagePoint) with the MDM system and the metering system. See 5.10 and Annexes K and L
for additional information related to MDM.

5.5.3 Message format

The message payload structure in Figure 41 describes MeterServiceRequests. It can be used


for zero or more MeterServiceWork objects.
61968-9  IEC:2013 – 73 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 41 – Meter service requests message format

The message may include more than one MeterServiceWork item. Each item may refer to up
to two meters to provide the means to replace a meter. Meter readings can be obtained as a
part of the work. In the case of a meter replacement, readings for the old meter can be
obtained as well as initial readings for the new meter. Location references can be supplied as
a part of the customer data or for the meter asset, as appropriate for the work being done.
The detailed, annotated XML schema is defined in Annex I.

5.6 Metering system events

5.6.1 General

There are different levels of need within the system for different kinds of messages.

The metering system (per se) may develop problems within its infrastructure which require a
work order to fix. The data requirements for communicating this event are similar to the
requirements of EndDeviceEvent as described in 5.2. With an EndDeviceEvent, a simple error
code can be used to report a problem. This mechanism works when the recipient is able to
look-up and interpret the meaning of the code. However, when a more detailed description of
– 74 – 61968-9  IEC:2013

the problem is required, a more elaborate schema shall be used. In some cases, the recipient
is a human and requires a human-readable description of the problem, and the particular
piece of equipment involved. When identifying the asset, it will probably be necessary to use
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

vendor-specific terminology to describe the hardware.

5.6.2 Applications – Firmware upgrade

For an automated Metering System capable of two-way communication, it may be possible to


upgrade the firmware of MS infrastructure in the field, or in some systems the communication
assets in the end devices. Changes to the metering system that materially affect its operation
shall be communicated to all of the relevant stakeholders. An example of such a publication
using an EndDeviceConfig message is depicted in Figure 42.

Figure 42 – Example firmware upgrade message exchange

The firmware upgrade may cause the EndDevice or CommEquipmentAsset to change in a


number of ways, including device functional characteristics, firmware version and revision
number, or configuration (expressed as a programId).

5.6.3 Message formats

Please refer to the EndDeviceConfig message format described in 5.10.3.

5.7 Customer switching

5.7.1 General

A customer in an open retail market can switch between energy suppliers. This may require
reconfiguration and/or reinstallation of the meter. The reconfiguration or meter replacement
may be a consequence of a customer changing energy programs at the time of the change of
energy supplier. This process would likely involve an on request read as needed for final
billing purposes. An example message exchange is provided below in Figure 43.

The OperationSet steps are included to synchronize the revised Master Data (the
configuration data for the new and old retailers and the association changes with the
Customer, CustomerAccount, and CustomerAgreement) with the MDM System and the
Metering System. See 5.10 and Annexes K and L for additional information related to Master
Data Management.
61968-9  IEC:2013 – 75 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 43 – Example customer switching message exchange

5.7.2 Message formats

The structure of a MeterServiceRequest was described by Figure 41. The structure of a


MeterReading message was described by Figure 19.

5.8 Payment metering service messages

5.8.1 General

Payment metering services typically involve prepayment meters installed at customers"


premises and token vending systems situated at convenient locations to serve the needs of
customers. For the purpose of this standard, vending systems are regarded as being part of
the metering system. Such vending systems typically require information about the meter,
customer, service location, usage point, tariff, customer account, customer agreement and the
supplier of the service that receives the revenue collected by the vending systems.

The information required by the vending systems usually originates in the CIS and billing
system and is then transferred to the vending systems by means of the messages provided in
5.8.3.

Transaction and receipt information on the other hand originate in the vending systems when
the customer makes a payment on an account or purchases a prepaid token at a point of sale.
This information periodically needs to be transferred to the CIS and billing system for further
processing, for which purpose the messages in 5.8.4 are provided.

In IEC 61968-9:2009, there were several profiles developed as a part of the efforts to support
payment metering, where some of these were more general in nature. In this edition, those
profiles are preserved in this subclause 5.8 where they are prefixed by "PrePay".It is hoped
that these will be fully harmonized in future editions of IEC 61968-9.

5.8.2 Auxiliary agreements

Information about customer debt for collection may be configured into MS by means of
AuxilaryAgreementConfig message payload.
– 76 – 61968-9  IEC:2013

An example of a message exchange is given in Figure 44 and the message format is given in
Figure 65.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 44 – Message exchange for transferring auxiliary agreement information

5.8.3 Applications

5.8.3.1 General

When a customer purchases a prepaid token at a point of sale or makes a payment on a billed
account, financial information is originated in MS relating to this transaction. Typically this
information is periodically transferred to the CIS and billing system for further processing.

The messages defined in 5.8.4 make provision for transferring this information to the CIS and
billing system.

5.8.3.2 Receipts

When MS receives a payment, a receipt is generated and the relevant information about the
payment is typically recorded as a receipt record. This information may be accessed by
means of ReceiptRecord message payload.

In the case where a specified range (by date or mRID) of the message payload is to be
specified in a particular contextual implementation, this may be realised by making use of the
optional elements in the message header (see Figure B.2).

An example of a message exchange is given in Figure 45 and the message format given in
Figure 48.
61968-9  IEC:2013 – 77 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 45 – Message exchange for transferring receipt information

5.8.3.3 Transactions

Information about the sale of a prepaid token or the receipt of an account payment is typically
also recorded by MS in the form a financial transaction record, capturing the relevant details
relating to the particular transaction. This information may be accessed by means of
TransactionRecord message payload.

An example of a message exchange is given in Figure 46 and the message format is given in
Figure 49.

Figure 46 – Message exchange for transferring transaction information

5.8.4 Message formats

The diagram in Figure 47 describes the structure of message used to configure auxiliary
agreements.
– 78 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 47 – Auxiliary agreement configuration message format

The message structure in Figure 48 is used to record receipts.


61968-9  IEC:2013 – 79 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 48 – ReceiptRecord message format

The message structure in Figure 49 is used to record transactions.


– 80 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 49 – TransactionRecord message format

5.9 Premise area networks

5.9.1 General

The metering system has been expanded to include devices that have been deployed within
homes and businesses that are managed using the metering infrastructure. Within IEC 61968-
9, these devices exist within a premise area network (PAN). This is inclusive of the commonly
used term home area network (HAN). The PAN/HAN devices themselves are a special type of
EndDevice.

Given the evolving nature of the underlying devices and communication protocols, IEC 61968-
9 attempts to take a view that can be mapped as needed into a variety of device standards.
61968-9  IEC:2013 – 81 –

5.9.2 Applications

5.9.2.1 General
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

The applications for PAN devices primarily include dynamic pricing, demand response and
providing information to customers. There are many types of PAN devices, including smart
thermostats, in home displays, relays, etc.

5.9.2.2 PAN device pairing and unpairing

The pairing of a PAN device with a meter is required before the PAN device can be sent
commands by the Metering System.

PAN device pairing (and un-pairing) is performed using an EndDeviceControls message as


shown in the example of Figure 50. The following special conventions relative to the
EndDeviceControl message apply to pairing a PAN device with a meter:

• The appropriate EndDeviceControlType code for pairing a PAN device should be


selected from Annex F.
• Two (and only two) EndDevices are identified by mRid or the Names class – one is the
meter and the other is the PAN device. The isPan Boolean will be set to true for the
PAN device and the install code and electronicAddress.macAddress are also normally
required.
• Successful or unsuccessful results for the pairing operation are reported using
EndDeviceEvents messages, with the appropriate EndDeviceEventType enumerations
found in Table E.24 of Annex E. It is possible for more than one EndDeviceEvent to be
reported as a result of the EndDeviceControl.

Figure 50 – Pairing of a PAN device


– 82 – 61968-9  IEC:2013

5.9.2.3 PAN Events

PAN device events are generated by a PAN device, where they are typically communicated
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

through a meter or gateway to the metering system head end. The metering system head end
will then publish the message to other enterprise applications that have subscribed. These
events are conveyed using the EndDeviceEvents message. An example is shown in
Figure 51.

Figure 51 – PAN device events

5.9.2.4 PAN controls

Additional PAN device controls for purposes other than pairing may be initiated by an
enterprise application such as a demand response management system to a metering system
head end. These controls also use the EndDeviceControls message. Given that there are a
variety of ways that the control can be addressed, there may be many target PAN devices. An
example is shown in Figure 52.

EndDeviceControls messages intended for PAN devices will typically include one of the
following special structures within the EndDeviceControl profile:

PanDemandResponse
PanDisplay
PanPricing

The appropriate EndDeviceControlType and EndDeviceEventType enumerations for these


functions can be found in Table E.24 and Table F.3.
61968-9  IEC:2013 – 83 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 52 – PAN device controls

5.9.3 Message formats

There are no unique messages defined specifically for PAN devices. PAN devices are simply
types of EndDevices.

5.10 Master data management messages

5.10.1 General

Enterprise systems exchanging messages in the Meter Reading and Control domain require a
means of managing the non-transactional data that defines assets, other CIM objects and the
relationships (or associations between them). Master Data Management (MDM) is the term
used to describe the practice of creating, changing, and deleting these objects and
relationships.

For IEC 61968-9 purposes, the CIM classes that fall within the scope of Master Data
Management and the IEC 61968-9 profiles used to create/change/delete these objects (and
their “configurations”) are included in Table 5:
– 84 – 61968-9  IEC:2013

Table 5 – IEC 61968-9 configuration profiles


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

CIM object IEC 61968-9 profile


ComModule ComModuleConfig
Customer CustomerConfig
CustomerAccount CustomerAccountConfig
CustomerAgreement CustomerAgreementConfig
EndDevice EndDeviceConfig
EndDeviceGroup EndDeviceGroups
Meter MeterConfig
PricingStructure PricingStructureConfig
ServiceCategory ServiceCategoryConfig
ServiceLocation ServiceLocationConfig
ServiceSupplier ServiceSupplierConfig
a
TransformerTank
UsagePoint UsagePointConfig
UsagePointGroup UsagePointGroups
UsagePointLocation UsagePointLocationConfig
a For IEC 61968-9 purposes, the TransformerTank object has
applicability to use cases involving Outage Management.
The TransformerTank is technically outside the scope of
IEC 61968-9, and there is no IEC 61968-9 profile for
creation, modification or deletion of a TransformerTank.
However, the TransformerTank can be referenced within the
UsagePointConfig profile to identify the transformer that
supplies power to the UsagePoint.

ConfigurationEvents occur each time a create, change, or delete operation is performed using
any of the “config” operations using the IEC 61968-9 profiles in Table 5 as well as any time
that a MasterDataLinkageConfig transaction is executed to manage the relationships of MDM
objects or an ObjectNamesConfig transaction is executed to add, delete, or change Names
class identifiers for these objects.

The ConfigurationEvent class in the CIM is associated with each of the CIM classes in the
first column of Table 5 and is incorporated into each of the IEC 61968-9 Profiles in column 2
of that table. It is also included in the MasterDataLinkageConfig and ObjectNamesConfig
profiles. The function of the ConfigurationEvent class is to provide important business details
about each “config” operation, including:

• the date and time at which the configuration or configuration change became effective or
is to become effective,
• the entity performing the configuration operation, and
• free-form remarks providing additional business information related to the configuration
event.

Refer to Annexes K and L for detailed descriptions of Master Data Management Use Cases
and sample XML messages that clarify the intended use of the messages in this 5.10.

5.10.2 Applications

5.10.2.1 General

For the purposes of this standard, there are two methods used for managing the relationships
between the CIM objects identified in 5.10.1. These are the MasterDataLinkage profile
(described in 5.10.1) and, for a limited number of CIM objects, the relationships are explicitly
61968-9  IEC:2013 – 85 –

managed using profiles identified in 5.10.1. The following diagram identifies the object
relationships that are critical to master data management within the scope of this standard
and the specific method that is recommended to be used for managing each relationship.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 53 – Master data linkages

To fully comprehend Figure 53, it is necessary to understand that the IEC 61968-9 standard
provides normative messages by which enterprise systems can exchange information;
however there is no requirement that any given system implement an internal data model that
is based upon or even consistent with the CIM. Accordingly, the above diagram presents the
possibility of reflecting relationships in a variety of ways. For example, two systems may
recognize the concepts of Customer, CustomerAccount and CustomerAgreement and choose
to express the relationships between these entities and a UsagePoint by linking a Customer to
a CustomerAccount (relationship Q), then linking the CustomerAccount to
CustomerAgreement (relationship R) and finally linking the CustomerAgreement to the
UsagePoint (relationship H). In this scenario, there may never be a need to utilize
relationships K, L or U.

On the other hand, there may be two enterprise systems that do not materialize the concept of
a CustomerAgreement in their internal data models. These systems may utilize messages that
link a Customer to a CustomerAccount (relationship Q), and then link the CustomerAccount to
the UsagePoint (relationship K). It is outside the scope of the IEC 61968-9 standard to be
prescriptive on which of the relationships illustrated in Figure 53 are permissible or preferred.
The MasterDataLinkageConfig profile may be used in a flexible manner to support the needs
of any enterprise and its enterprise systems.

It is recommended that relationships E, F, I, J, M and V be managed by the “Config” profiles


called out in the legend of the figure, rather than via the MasterDataLinkageConfig profile;
however this is not a requirement and enterprises may choose to use the
MasterDatalinkageConfig profile to manage these relationships as well. The reason for the
– 86 – 61968-9  IEC:2013

recommendation that these specific relationships be handled by the identified profiles rather
than the MasterDataLinkageConfig is twofold:
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• these specific relationships seldom change, and


• these specific relationships are viewed by almost all enterprise systems in a consistent
way.

The converse is also true. Enterprises may choose to manage relationships depicted as red
lines as if they were depicted by black lines provided that the relationship is supported by the
CIM and is reflected in the appropriate IEC 61968-9 profile.

There is one additional IEC 61968-9 profile called the CustomerMeterDataSet. This profile is
used only with a Header verb of get, and the resulting response provides a meter-centric
detailed representation of all of the relationships in the above diagram.

Figure 53 is informative. Entities and relationships in Figure 53 may evolve over time as use
of IEC 61968 IEC 61968-9 is extended to support new and revised business use cases.

5.10.2.2 Service Suppliers

Information about the supplier (retailer or utility for example) of the service may be configured
into MS by means of SupplierConfig message payload.

An example of a message exchange is given in Figure 54 and the message format is given in
5.10.3.3.

Figure 54 – Message exchange for transferring supplier information

5.10.2.3 Customers

Information about customers of the supplier of the service may be configured into MS by
means of CustomerConfig message payload.

An example of a message exchange is given in Figure 55 and the message format is given in
5.10.3.4.
61968-9  IEC:2013 – 87 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 55 – Message exchange for transferring customer information

5.10.2.4 Customer agreements

Information about customer agreements may be configured into MS by means of


CustomerAgreementConfig message payload.

An example of a message exchange is given in Figure 56 and the message format is given in
5.10.3.5.

Figure 56 – Message exchange for transferring customer agreement information

5.10.2.5 Customer accounts

Information about customer accounts may be configured into MS by means of


CustomerAccountConfig message payload.
– 88 – 61968-9  IEC:2013

An example of a message exchange is given in Figure 57 and the message format is given in
5.10.3.6.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 57 – Message exchange for transferring customer account information

5.10.2.6 Service categories

Information about the categories of service (electricity, water, gas for example) may be
configured into MS by means of ServiceCategoryConfig message payload.

An example of a message exchange is given in Figure 58 and the message format is given in
5.10.3.7.

Figure 58 – Message exchange for transferring service category information


61968-9  IEC:2013 – 89 –

5.10.2.7 Usage points

Information about the usage points may be configured into MS by means of a


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

UsagePointConfig message payload.

An example of a message exchange is given in Figure 59 and the message format is given in
5.10.3.8.

Figure 59 – Message exchange for transferring usage point information

5.10.2.8 Meters

Information about the meters in service may be configured into MS by means of MeterConfig
message payload.

An example of a message exchange is given in Figure 60 and the message format is given in
5.10.3.11.

Figure 60 – Message exchange for transferring meter information


– 90 – 61968-9  IEC:2013

5.10.2.9 End devices

Information about end devices in service may be configured into MS by means of an


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceConfig message payload.

An example of a message exchange is given in Figure 61 and the message format is given
5.10.3.10.

Figure 61 – Message exchange for transferring end device information

5.10.2.10 Service locations

Information about the service locations may be configured into MS by means of


ServiceLocationConfig message payload.

An example of a message exchange is given in Figure 62 and the message format is given in
5.10.2.10.
61968-9  IEC:2013 – 91 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 62 – Message exchange for transferring service location information

5.10.2.11 Pricing structure and tariffs

Information about pricing structures may be configured into MS by means of


PricingStructureConfig message payload.

An example of a message exchange is given in Figure 63 and the message format is given in
5.10.3.14.

Figure 63 – Message exchange for transferring pricing structures

5.10.3 Message formats

5.10.3.1 General

This subclause 5.10.3 describes the message formats for the MasterDataLinkageConfig and
other Master Data Management “config” messages. The detailed specification for each class
– 92 – 61968-9  IEC:2013

and attribute can be found in IEC 61968-11 and IEC 61970-301. The detailed, annotated XML
schema is defined in Annex H.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.10.3.2 MasterDataLinkageConfig

Figure 64 describes the top level structure of the Master Data Linkage Config message used
to configure relationships between objects.

Figure 64 – MasterDataLinkageConfig message format


61968-9  IEC:2013 – 93 –

An example of MasterDataLinkageConfig is shown below. This message illustrates the “non-


in-line” method of establishing an association between two CIM objects – in this case between
the Meter and the UsagePoint are associated with each other using a
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

MasterDataLinkageConfig command. This is the normative way to reflect the installation of a


Meter at a UsagePoint.

<?xml version="1.0" encoding="UTF-8"?>


<m:MasterDataLinkageConfig
xsi:schemaLocation = "http://iec.ch/TC57/2011/MasterDataLinkageConfig#
MasterDataLinkageConfig.xsd"
xmlns:m = "http://iec.ch/TC57/2011/MasterDataLinkageConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:ConfigurationEvent>
<m:createdDateTime>2011-11-09T19:55:43.699Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
<m:reason>MeterInstallation</m:reason>
</m:ConfigurationEvent>
<m:Meter>
<m:Names>
<m:name>1234LG</m:name>
</m:Names>
</m:Meter>
<m:UsagePoint>
<m:Names>
<m:name>SDP1234E001001</m:name>
</m:Names>
</m:UsagePoint>
</m:MasterDataLinkageConfig>

5.10.3.3 SupplierConfig

The message structure in Figure 65 is used to configure service suppliers, replacing the
SupplierConfig message defined in IEC 61968-9:2009.

Figure 65 – Service supplier configuration message format


– 94 – 61968-9  IEC:2013

5.10.3.4 CustomerConfig

The message structure in Figure 66 is used to configure customers.


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 66 – Customer configuration message

5.10.3.5 CustomerAgreementConfig

The message structure in Figure 67 is used to configure customer agreements.


61968-9  IEC:2013 – 95 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 67 – Customer agreement configuration message

5.10.3.6 CustomerAccountConfig

The message structure in Figure 68 is used to configure customer accounts.


– 96 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 68 – Customer account configuration message

5.10.3.7 ServiceCategoryConfig

The message structure in Figure 69 is used to configure service categories.

Figure 69 – ServiceCategoryConfig message format

5.10.3.8 UsagePointConfig

The message structure in Figure 70 is used to configure usage points. This replaces the
service delivery points message defined in IEC 61968-9:2009.
61968-9  IEC:2013 – 97 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 70 – UsagePointConfig message format


– 98 – 61968-9  IEC:2013

An example of UsagePointConfig payload is shown below.


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<?xml version="1.0" encoding="UTF-8"?>


<m:UsagePointConfig xsi:schemaLocation="http://iec.ch/TC57/2011/UsagePointConfig#
UsagePointConfig.xsd" xmlns:m="http://iec.ch/TC57/2011/UsagePointConfig#"
xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
<m:UsagePoint>
<m:isSdp>true</m:isSdp>
<m:ConfigurationEvents>
<m:createdDateTime>2011-11-09T10:58:03.616Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
</m:ConfigurationEvents>
<m:Names>
<m:name>SDP1234E001001</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
<m:UsagePointLocation>
<m:Names>
<m:name>LOC1234</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
</m:UsagePointLocation>
</m:UsagePoint>
</m:UsagePointConfig>

5.10.3.9 UsagePointLocation

The diagram in Figure 71 describes the structure of the message used to define
UsagePointLocations.
61968-9  IEC:2013 – 99 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 71 – UsagePointLocationConfig message format

An example payload of UsagePointLocationConfig is shown below.

<?xml version="1.0" encoding="UTF-8"?>


<m:UsagePointLocationConfig
xsi:schemaLocation = "http://iec.ch/TC57/2011/UsagePointLocationConfig#
UsagePointLocationConfig.xsd"
xmlns:m = "http://iec.ch/TC57/2011/UsagePointLocationConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:UsagePointLocation>
<m:ConfigurationEvents>
<m:createdDateTime>2011-11-09T10:57:02.583Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
</m:ConfigurationEvents>
<m:mainAddress>
<m:streetDetail>
<m:name>Main Street</m:name>
<m:number>1234</m:number>
</m:streetDetail>
<m:townDetail>
<m:country>US</m:country>
– 100 – 61968-9  IEC:2013

<m:name>Austin</m:name>
<m:stateOrProvince>TX</m:stateOrProvince>
</m:townDetail>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</m:mainAddress>
<m:Names>
<m:name>LOC1234</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
</m:UsagePointLocation>
</m:UsagePointLocationConfig>

5.10.3.10 EndDeviceConfig

The diagram in Figure 72 describes the top level of the EndDeviceConfig message, which is
used to provide for basic configuration of end devices.

Figure 72 – End device config message format

5.10.3.11 MeterConfig

The message structure in Figure 73 is used to configure meters, where it is possible to supply
information more specific to meters.
61968-9  IEC:2013 – 101 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 73 – Meter configuration message

An example of a MeterConfig payload is shown below.


<?xml version="1.0" encoding="UTF-8"?>
<m:MeterConfig
– 102 – 61968-9  IEC:2013

xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterConfig# MeterConfig.xsd"


xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:Meter>
<m:amrSystem>CCTR</m:amrSystem>
<m:serialNumber>82000001</m:serialNumber>
<m:ConfigurationEvents>
<m:createdDateTime>2011-11-09T13:55:02.776Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
<m:reason>AssetCreation</m:reason>
</m:ConfigurationEvents>
<m:EndDeviceInfo>
<m:AssetModel>
<m:modelNumber>F60</m:modelNumber>
<m:Manufacturer>
<m:Names>
<m:name>LG</m:name>
</m:Names>
</m:Manufacturer>
</m:AssetModel>
</m:EndDeviceInfo>
<m:Names>
<m:name>1234LG</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
</m:Meter>
</m:MeterConfig>

5.10.3.12 ComModuleConfig

The diagram in Figure 74 provides the top level structure of the message used to configure
communication modules.

Figure 74 – ComModuleConfig message format

5.10.3.13 ServiceLocationConfig

The message structure in Figure 75 is used to configure service locations.


61968-9  IEC:2013 – 103 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 75 – ServiceLocationConfig message format

5.10.3.14 PricingStructureConfig

The message structure in Figure 76 is used to configure pricing structures.


– 104 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 76 – PricingStructureConfig message format

6 Document conventions

6.1 UML diagrams

All UML-based sequence diagrams contained herein are to be considered as informative


examples of how a message exchange could occur.

One of the strengths of the CIM is its flexibility. As technology advances, and new needs
develop, new messages can be created. These new messages might involve additional
systems (not pictured.) These new messages may leverage different options than the ones
depicted in the example.

All UML-based communication diagrams and message flow diagrams contained herein are to
be considered informative.
All UML-based class diagrams contained herein are to be considered informative. The reader
is referred to IEC 61968-1 to locate the document that contains the normative definitions of
the classes used in the CIM.
61968-9  IEC:2013 – 105 –

6.2 Message definitions

6.2.1 General
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Message format diagrams contained in the body of this document are to be considered as
either normative or informative, with the normative XML schemas being supplied in Annex H,
and informative XML schemas being provided by Annex I.

Use cases and sequence diagrams presented in this document are for informative purposes
only, and represent usage examples for the normative message definitions.

6.2.2 Mandatory vs. optional

The messages described within this standard were derived from use cases which satisfy an
underlying business need for a specific information exchange. Each use case provides a
given context for the use of the CIM. Message format diagrams describe the elements which
are passed. The elements depicted in dashed-line boxes are to be considered optional in a
given context. The elements depicted in solid boxes are to be considered mandatory in a
given context. If a diagram should depict an entire class as mandatory or optional, the reader
should interpret this to mean that the use of the class is either mandatory or optional, but not
that every element within the class is now mandatory or optional. The reader shall refer to the
normative definition of the class to determine this.

6.2.3 Verb tense

CIM verbs illustrated in some of the sequence diagrams within this standard are shown in
UPPER CASE; however, the verbs in the headers of all IEC 61968-9 CIM messages are
required to be in lower case.

6.3 Synchronous versus asynchronous messages

The use of asynchronous or synchronous messages in the sequence diagrans in this


document is for illustrative purposes only and is not prescriptive.

6.4 Depiction of simple acknowledgment messages

In web services implementations, there is always a synchronous acknowledgment to request


messages even if the overall exchange pattern is asynchronous. This synchronous
acknowledgment is performed using a simple IEC 61968-9 response stereotype message
having:

An IEC 61968-100 header


An IEC 61968-100 reply structure with:
Reply.Result = “OK”
Reply.Error.code = “0.3” (refer to Annex B)

When using JMS messaging, this simple acknowledgment is also included in the messaging
pattern if the AckRequired Boolean is set to “true” in the 61968-100 Header of the request
message. However; this simple acknowledgment is suppressed if the AckRequired Boolean is
set to “false”.

The depiction or lack of depiction of these simple acknowledgment messages in sequence


diagrams within this document is intentionally inconsistent as the sequence diagrams are
informative and no assumption is made as to whether JMS or web services are being used or
whether the AckRequired Boolean is set to “true”. Refer to IEC 61968-100 for further
information on this subject.
– 106 – 61968-9  IEC:2013

Annex A
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Description of message type verbs

Table A.1 is copied here from Annex B of IEC 61968-100:2013 for convenience purposes
only.

Table A.1 – Commonly used verbs

Verbs Meaning Message structure


create The "create" verb is used to publish a request to the master system Request message will include
to create a new object. The master system may in turn publish the HeaderType and Payload
new object as an event using the verb "created". The master system structures.
may also use the verb "reply" to respond to the "create" request,
indicating whether the request has been processed successfully or
not.
change The "change" verb is used to publish a request to the master Request message will include
system to make a change to an object based on the information in HeaderType, RequestType
the message. The master system may in turn publish the changed and optionally Payload
object as an event using the verb "changed" to notify that the object structures. The requestType
has been changed since last published. The master system may structure will potentially
also use the verb "reply" to respond to the "change" request, identify specific object IDs.
indicating whether the request has been processed successfully or
not.
cancel The"cancel" verb is used to publish a request to the master system Request message will include
to cancel the object, most commonly in the cases where the object HeaderType, RequestType
represents a business document. The master system may in turn and optionally Payload
publish the cancelled message as an event using the verb structures. The requestType
"canceled" to notify that the document has been cancelled since last structure will potentially
published. The master system may also use the verb "reply" to identify specific object IDs.
respond to the "cancel" request, indicating whether the request has
been processed successfully or not. The "cancel" verb is used when
the business content of the document is no longer valid due to
error(s).
close The "close" verb is used to publish a request to the master system Request message will include
to close the object, most commonly in cases where the object HeaderType, RequestType
represents a business document. The master system may in turn and optionally Payload
publish the closed message as an event using the verb "closed" to structures. The requestType
notify that the document has been closed since last published. The structure will potentially
master system may also use the verb "reply" to respond to the identify specific object IDs.
"close" request, indicating whether the request has been processed
successfully or not. The "close" verb is used when the business
document reaches the end of its life cycle due to successful
completion of a business process.
delete The "delete" verb is used to publish a request to the master system Request message will include
to delete one or more objects. The master system may in turn HeaderType, RequestType
publish the closed message as an event using the verb "deleted" to and optionally Payload
notify that the object has been deleted since last published. The structures. The requestType
master system may also use the verb "reply" to respond to the structure will potentially
"delete" request, indicating whether the request has been identify specific object IDs.
processed successfully or not. The "delete" verb is used when the
business object should no longer be kept in the integrated systems
either due to error(s) or due to archiving needs. However, the
master system will most likely retain a historical record of the object
after deletion.
execute This is used when the message is conveying a transaction that See OperationSet in
involves a variety of create, delete and/or change operations. See Message.xsd.
Annexes K and L.
61968-9  IEC:2013 – 107 –

Verbs Meaning Message structure


get The "get" verb is used to issue a query request to the master Request message will include
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

system to return a set of zero or more objects that meet a specified HeaderType and
criteria. The master system may in turn return zero or more objects RequestType structures. The
using the "reply" verb in a response message. requestType structure will
potentially identify specific
parameters to qualify the
request, such as object IDs.
created The "created" verb is used to publish an event that is a notification Event message will include
of the creation of a object as a result of either an external request HeaderType and Payload
or an internal action within the master system of that object. This structures.
message type is usually subscribed by interested systems and
could be used for mass updates. There is no need to reply to this
message type.
changed The "changed" verb is used to publish an event that is a notification Event message will include
of the change of an objectt as a result of either an external request HeaderType and Payload
or an internal action within the master system of that object. This structures.
could be a generic change in the content of the object or a specific
status change such as “approved”, “issued” etc. This message type
is usually subscribed by interested systems and could be used for
mass updates. There is no need to reply to this message type.
closed The "closed" verb is used to publish an event that is a notification of Event message will include
the normal closure of an objectt as a result of either an external HeaderType and Payload
request or an internal action within the master system of that object. structures.
This message type is usually subscribed by interested systems and
could be used for mass updates. There is no need to reply to this
message type.
canceled The "canceled" verb is used to publish an event that is a notification Event message will include
of the cancellation of an objectt as a result of either an external HeaderType and Payload
request or an internal action within the master system of that object. structures.
This message type is usually subscribed by interested systems and
could be used for mass updates. There is no need to reply to this
message type.
deleted The "deleted" verb is used to publish an event that is a notification Event message will include
of the deletion of an object as a result of either an external request HeaderType and Payload
or an internal action within the master system of that object. This structures.
message type is usually subscribed by interested systems and
could be used for mass updates. There is no need to reply to this
message type.
executed This provides for an event that indicates the execution of a See OperationSet in
transaction. Message.xsd.
reply There are two primary usages of the "reply" verb, but in both cases Used only for response
it is only used in response to request messages, whether the messages. For responses to
pattern used is synchronous or asynchronous. The first usage is to transactional requests, the
indicate the success, partial success or failure of a transactional message will contain
request to the master system to create, change, delete, cancel, or HeaderType and ReplyType
close a document. The second usage is in response to a "get" structures. For responses to
request, where objects of interest may be returned in the response. get requests, the message will
contain HeaderType,
ReplyType and potentially
Payload structures.

NOTE 1 Verbs are listed in this standard for convenience purposes and also to reflect changes that may be
reflected in future versions of IEC 61968-1.

NOTE 2 Within this standard (e.g. on sequence diagrams), verbs are case insensitive. However, within the
standard Message they shall be lower case. The verb SUBSCRIBE has been deprecated. Any usage of
SUBSCRIBE is an indication that transport level (e.g. JMS) messages may be conveyed between parties, but
these are not IEC 61968-9 messages.
– 108 – 61968-9  IEC:2013

Annex B
(informative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Reply error codes

B.1 Overview

The message structure to carry Reply.Error.Codes is defined in IEC 61968-1. Additional detail
may be provided in supportive documents such as IEC 61968-100. Application specific codes
are provided by individual parts. The application specific reply codes for IEC 61968-9 are
defined here.

The normative reply codes are defined by IEC 61968-100.

B.2 Reply code categories

The ReplyCodes can be categorized into families as described in Table B.1:

Table B.1 – ReplyCode Categories

ReplyCode Error Normative


Category Status

0 Error free N

1 Bad or Missing element N


2 Parameter invalid N

3 Too many values N

4 Request aborted N

5 Application Error N

6 Business rule violation N

7 Security issue N

N Normative
I Informative
D Deprecated

B.3 Code Construction

These categories can serve as the basis for a numbering scheme to form codes such as those
described by the formula below.

ReplyCode::= <ReplyCode Category> “.” <ReplyCode Index>


61968-9  IEC:2013 – 109 –

B.4 Code Indexes


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

The indexes for each category are described in Tables B.2 through B.9 below.

Table B.2 – Error-free Enumerations

ReplyCode ReplyCode Error Normative


Category Index Status

0 0 Success / No errors N
Partial result (additional results conveyed in separate
0 1 messages) N
0 2 Partial result (no further results to follow) N
0 3 Simple acknowledgement N

Table B.3 – Missing-element Enumerations

ReplyCode ReplyCode Error Normative


Category Index Status

1 1 Noun element(s) not found in message N


1 2 Revision element not found in message N
1 3 Verb element(s) not found in message N
1 5 Mandatory Header elements missing N
1 6 Mandatory Request elements missing N
1 7 Mandatory Payload elements missing N
1 8 Format of request does not validate against schema N
1 9 Unsupported Revision in message Header N

Table B.4 – Bad-value Enumerations

ReplyCode ReplyCode Error Normative


Category Index Status

2 1 Meter / RCD switch mismatch Na


2 2 Invalid Feeder(s) I
a
2 3 Feeder / Substation mismatch I
2 4 Invalid Meter(s) N
2 5 Invalid Noun N
2 6 Invalid ReadingType(s) N
2 7 Invalid Substation(s) I
a
2 8 Switch / Substation mismatch I
2 9 Invalid Verb N
2 10 Unsupported Reading Type(s) N
2 11 Payload mismatch I
2 12 Invalid UsagePoint(s) N
2 13 Meter / UsagePoint mismatch Na
2 14 Invalid Source N
2 15 Invalid Request ID(s) N
– 110 – 61968-9  IEC:2013

ReplyCode ReplyCode Error Normative


Category Index Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

2 16 Invalid ServiceLocation(s) N
2 17 Meter / ServiceLocation mismatch* N
2 18 ComModule / Meter mismatch* Na
2 19 Invalid CustomerAccount(s) N
2 20 Invalid ServiceSupplier(s) N
2 21 CustomerAccount / ServiceSupplier mismatch Na
2 22 Invalid Customer(s) N
2 23 Customer / CustomerAccount mismatch Na
2 24 Invalid CustomerAgreement(s) N
2 25 CustomerAccount / CustomerAgreement mismatch Na
2 26 CustomerAgreement / UsagePoint mismatch Na
2 27 CustomerAccount / UsagePoint mismatch Na
2 28 ServiceSupplier / UsagePoint mismatch Na
2 29 Object relationship mismatch N
2 30 Invalid ComModule(s) N
2 31 Invalid Service Category(ies) N
2 32 Invalid UsagePointLocation(s) N
2 33 Invalid PricingStructure(s) N
a Retained for backward compatibility. Intended for deprecation in the future edition of IEC 61968-9
and 2.29 will be used instead.

Table B.5 – Too-many-values enumerations

ReplyCode ReplyCode Error Normative


Category Index Status

3 1 Too many items in request N


3 2 Too many pending requests N
3 3 Too many ReadingTypes in request I

Table B.6 – Request-timed-out enumerations

ReplyCode ReplyCode Error Normative


Category Index Status

4 1 Request timed out N

4 2 Service not available I

4 3 Local error in processing I


61968-9  IEC:2013 – 111 –

Table B.7 – Application-error enumerations


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

ReplyCode ReplyCode Error Normative


Category Index Status
Unable to process the request - high
5 1 system activity level N
Unable to process request -transaction
5 2 not attempted N
Unable to process the request -
5 3 transaction attempted and failed N
Unable to process the request - multiple
5 4 error types encountered N
Some or all of the requested reading
5 5 types are unavailable in MDMS N
Some or all of the requested reading
5 6 types are unavailable in AMI N
Some or all of the requested data is
5 7 unavailable N
Unable to process the request –
5 8 mandatory field(s) missing N
Transaction aborted to maintain
5 9 transactional integrity N
Unable to process request –
5 10 functionality not supported N
5 11 Failure due to security N

Table B.8 – Business-rule-violation enumerations

ReplyCode ReplyCode Error Normative


Category Index Status

6 1 Request canceled per business rule N


6 2 Request placed on hold per business rule N
Request released from business rule
6 3 hold N
6 4 Request rescheduled per business rule N
6 5 Request canceled by user N

Table B.9 – Security issue enumerations

ReplyCode ReplyCode Error Normative


Category Index Status

7 1 Temporary authentication failure I

7 2 Authentication Required I
7 3 Authentication mechanism insufficient I
7 4 Authentication failure I
7 5 Action not authorized for user I
Authentication mechanism requires
7 6 encryption I
7 7 Policy violation I
– 112 – 61968-9  IEC:2013

B.5 Reply.Error.code examples


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Reply codes are constructed according to a formula that creates a dot notation which is
expressed in the form a string. Example Reply.Error.codes are provided in Table B.10.

Table B.10 – Common enumerations

Reply Code Description

0.0 Success / No errors

0.1 Partial result (additional results conveyed in separate messages)

0.2 Partial result (no further results to follow)

0.3 Simple acknowledgment

1.5 Mandatory Header elements missing

1.6 Mandatory Request elements missing

1.7 Mandatory Payload elements missing

1.8 Format of request does not validate against schema

1.9 Unsupported message revision in Header

2.4 Invalid Meter(s)

2.5 Invalid Noun

2.6 Invalid ReadingType(s)

2.9 Invalid Verb

2.10 Unsupported ReadingType(s)

2.12 Invalid UsagePoint(s)

2.13 Meter / UsagePoint mismatch

2.14 Invalid Source

2.15 Invalid Request ID(s)

2.16 Invalid ServiceLocation(s)

2.17 Meter / ServiceLocation mismatch*

2.18 ComModule / Meter mismatch*

2.19 Invalid CustomerAccount(s)

2.20 Invalid ServiceSupplier(s)

2.21 CustomerAccount / ServiceSupplier mismatch

2.22 Invalid Customer(s)

2.23 Customer / CustomerAccount mismatch

2.24 Invalid CustomerAgreement(s)

2.25 CustomerAccount / CustomerAgreement mismatch

2.26 CustomerAgreement / UsagePoint mismatch

2.27 CustomerAccount / UsagePoint mismatch

2.28 ServiceSupplier / UsagePoint mismatch

2.29 Object relationship mismatch

2.30 Invalid ComModule(s)

2.31 Invalid ServiceCategory(ies)

2.32 Invalid UsagePointLocation(s)

2.33 Invalid PricingStructure(s)

3.1 Too many items in request


61968-9  IEC:2013 – 113 –

Reply Code Description

3.2 Too many pending requests


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

4.1 Request timed out

5.1 Unable to process the request - high system activity level

5.2 Unable to process request -transaction not attempted

5.3 Unable to process the request - transaction attempted and failed

5.4 Unable to process the request - multiple error types encountered

5.5 Some or all of the requested ReadingTypes are unavailable in MDMS

5.6 Some or all of the requested ReadingTypes are unavailable in AMI

5.7 Some or all of the requested data is unavailable

5.8 Unable to process the request – mandatory field(s) missing

5.9 Transaction aborted to maintain transactional integrity

6.1 Request canceled per business rule

6.2 Request placed on hold per business rule

6.3 Request released from business rule hold

6.4 Request rescheduled per business rule

6.5 Request canceled by user

7.1 Temporary authentication failure

7.2 Authentication required

7.3 Authentication mechanism insufficient

7.4 Authentication failure

7.5 Action not authorized for user

7.6 Authentication mechanism requires encryption

7.7 Policy violation

The standard message envelope also has a single Reply.Result value. This should be
populated in the following manner:

"OK" if there are no errors and all results have been returned. There is no requirement
that a Reply.Error record with code of "0.0" be present.
"PARTIAL" if only a partial set of results has been returned, with or without errors. A
Reply.Error record with code of "0.1" may be present, as well as records that indicate
errors.
"ERROR" if any Error records with a code other than "0.*" are returned, indicating actual
errors.

This is represented by the following state transition diagram in Figure B.1.


– 114 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure B.1 – Reply Message States


61968-9  IEC:2013 – 115 –

Annex C
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Procedure for the generation of a ReadingType name

C.1 General

The ReadingType enumeration is an important identifier in MeterReading messages. This


standard specifies a profile which will be considered normative. IEC 61968-9 was developed
with several design principles in mind:

The messages should be simple and general purposed.

A “Readings” message should be able to carry any type of value that might be in a meter, e.g.
Power, Energy, Relay actuation counts, Status information, and Currency. The
Readings.ReadingType should be able to describe whatever the Readings.value is.

It is easier for a data consumer to throw away information it has but does not need, than it is
for it to recreate information it needs but does not have.

This third principle implies that data producers should be as explicit as possible when
publishing data. The data therefore should be entirely self-describing so that other consumers
who access the data (perhaps when it is residing in a data warehouse) can determine for
themselves the suitability for use of the data. This will help avoid the need for the data
consumer to attempt to reconstruct any implicit agreements which were in place at the time of
publication.

It is understood that there will be occasions in which a data consumer (making a request for
information) might not know all of the specific details regarding what is being asked. For
example, a requestor may wish to obtain the “voltage” at a given location. It may not know if
the service is single-phase or poly-phase. It should be able to make the request with the
knowledge it has, and the data producer attempt to fulfil it and in the response supply
additional detail as appropriate. This may result in the ReadingType(s) used in the response
to differ slightly from the ReadingType used in the request.

C.2 Understanding the important attributes of a data element name

C.2.1 General

Data elements can be described in terms of 18 key attributes (several of which are compound
attributes.) Every attribute has the feature that a value of zero (“0”) represents that it is not
applicable to the description. The only exception to this rule is in the compound attributes. In
this case dual zeros represent that the attribute is not applicable.

C.2.2 Attribute #1, macroPeriod

The macroPeriod describes an aspect of the data that reflects how it is viewed or captured
over a long period of time. These are enumerated in Table C.1.
– 116 – 61968-9  IEC:2013

Table C.1 – Time-period of interest enumerations


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Enumeration Comments
Status
0 none Not Applicable N

8 billingPeriod Captured during the billing period starting at midnight of the first N
day of the billing period (as defined by the billing cycle day). If
during the current billing period, it specifies a period from the
start of the current billing period until "now".

11 daily Daily Period starting at midnight. If for the current day, this N
specifies the time from midnight to "now".

13 monthly Monthly period starting at midnight on the first day of the month. N
If within the current month, this specifies the period from the
start of the month until "now."

22 seasonal A season of time spanning multiple months. E.g. "Summer," N


"Spring," "Fall," and "Winter" based cycle. If within the current
season, it specifies the period from the start of the current
season until "now."
24 weekly Weekly period starting at midnight on the first day of the week N
and ending the instant before midnight the last day of the week.
If within the current week, it specifies the period from the start of
the week until "now."

32 specifiedPeriod For the period defined by the start and end of the TimePeriod N
element in the message.

C.2.3 Attribute #2, aggregate

C.2.3.1 General

The way in which a reading is viewed in the aggregate (compared to others) serves as the
second attribute. Possible enumerations include those described in Table C.2. This attribute
may be used to define a mathematical operation carried out over the period of interest defined
by attribute #1.

Table C.2 – Data qualifier enumerations

Normative
Code Enumeration Comments
Status
0 none Not Applicable N
2 average N
The value represents an amount over which a threshold was
4 excess I
exceeded.
5 highThreshold The value represents a programmed threshold. I
7 lowThreshold The value represents a programmed threshold. I
8 maximum The highest value observed N
9 minimum The smallest value observed N
11 nominal I
12 normal I
16 secondMaximum The second highest value observed N
17 secondMinimum The second smallest value observed N
23 thirdMaximum The third highest value observed N
24 fourthMaximum The fourth highest value observed N
61968-9  IEC:2013 – 117 –

Normative
Code Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

25 fifthMaximum The fifth highest value observed N


26 sum The accumulated sum N
Typically used to identify the high volume flow port of a
27 high I
compound water meter.
Typically used to identify the low volume flow port of a
28 low I
compound water meter.

N = Normative

I = Informative

D = Deprecated since last edition

C.2.3.2 Changes with this edition

In IEC 61968-9:2009, it was suggested that “TestData” could be used as an enumeration to


indicate that a value was not a real billing value. In this edition of IEC 61968-9, we encourage
instead the use of ReadingQuality codes to identify test data. In a similar fashion, “missing” or
“unstable” data should be identified by a suitable ReadingQuality code. Information on
ReadingQuality codes may be found in Annex D.

In this edition of IEC 61968-9, attribute #2 is used strictly for range qualifiers. Terms such as
“absolute” which may be used to qualify a pressure reading, or to qualify interval data are
instead handled elsewhere. Separate units of measure have been created to differentiate
gauge pressure from absolute pressure. Furthermore, the distinction between “absolute
intervalData” and “incremental intervalData” is now handled by the message schema.
Individual readings (of a “bulkQuantity” or “indicating” nature) are simply presented as
readings with the “absolute” attribute being implied. “Incremental intervalData” is now
described by the “DeltaData” term, and by presentation of the data in the “intervalReadings”
portion of the message.

C.2.4 Attribute #3, measuringPeriod

C.2.4.1 General

The measuringPeriod supplies an “adjective” to describe aspects of a “time period” with


regard to the measurement. This attribute describes a “time attribute” which is inherent or
fundamental to the reading value. The attribute refers to the way the value was originally
measured and not to the frequency at which it is reported or presented. For example, an
hourly interval of consumption data would have “hourly” as an attribute. However in the case
of an hourly sampled voltage value the meterReadings schema would carry the “hourly”
interval size information. Enumerated values include the values described in Table C.3. When
compared to attribute #1, the measuringPeriod is a small interval of time which is
characteristic of the way the reading was captured, while the macroPeriod is a long interval of
time related to the way in which the reading is reported. Either of these attributes are invoked
only as needed to describe the data. Many dial readings need only the accompanying
timestamp to be meaningful.

Table C.3 – measuringPeriod enumerations

Normative
Code Enumeration Comments
Status

0 none Not Applicable N

1 tenMinute 10 min N
2 fifteenMinute 15 min N
3 oneMinute 1 min N
– 118 – 61968-9  IEC:2013

Normative
Code Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

4 twentyfourHour 24 min N
5 thirtyMinute 30 min N
6 fiveMinute 5 min N
7 sixtyMinute 60 min N
10 twoMinute 2 min N
14 threeMinute 3 min N
15 present Within the present period of time I
Shifted within the previous monthly cycle and I
16 previous
data set
31 twentyMinute 20 min interval N
50 fixedBlock60Min 60 min Fixed Block N
51 fixedBlock30Min 30 min Fixed Block N
52 fixedBlock20Min 20 min Fixed Block N
53 fixedBlock15Min 15 min Fixed Block N
54 fixedBlock10Min 10 min Fixed Block N
55 fixedBlock5Min 5 min Fixed Block N
56 fixedBlock1Min 1 min Fixed Block N
60 min Rolling Block with 30-minute sub- N
57 rollingBlock60MinIntvl30MinSubIntvl
intervals
60 min Rolling Block with 20-minute sub- N
58 rollingBlock60MinIntvl20MinSubIntvl
intervals
60 min Rolling Block with 15-minute sub- N
59 rollingBlock60MinIntvl15MinSubIntvl
intervals
60 min Rolling Block with 12-minute sub- N
60 rollingBlock60MinIntvl12MinSubIntvl
intervals
60 min Rolling Block with 10-minute sub- N
61 rollingBlock60MinIntvl10MinSubIntvl
intervals
60 min Rolling Block with 6-minute sub- N
62 rollingBlock60MinIntvl6MinSubIntvl
intervals
60 min Rolling Block with 5-minute sub- N
63 rollingBlock60MinIntvl5MinSubIntvl
intervals
60 min Rolling Block with 4-minute sub- N
64 rollingBlock60MinIntvl4MinSubIntvl
intervals
30 min Rolling Block with 15-minute sub- N
65 rollingBlock30MinIntvl15MinSubIntvl
intervals
30 min Rolling Block with 10-minute sub- N
66 rollingBlock30MinIntvl10MinSubIntvl
intervals
30 min Rolling Block with 6-minute sub- N
67 rollingBlock30MinIntvl6MinSubIntvl
intervals
30 min Rolling Block with 5-minute sub- N
68 rollingBlock30MinIntvl5MinSubIntvl
intervals
30 min Rolling Block with 3-minute sub- N
69 rollingBlock30MinIntvl3MinSubIntvl
intervals
30 min Rolling Block with 2-minute sub- N
70 rollingBlock30MinIntvl2MinSubIntvl
intervals
15 min Rolling Block with 5-minute sub- N
71 rollingBlock15MinIntvl5MinSubIntvl
intervals
15 min Rolling Block with 3-minute sub- N
72 rollingBlock15MinIntvl3MinSubIntvl
intervals
15 min Rolling Block with 1-minute sub- N
73 rollingBlock15MinIntvl1MinSubIntvl
intervals
61968-9  IEC:2013 – 119 –

Normative
Code Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

10 min Rolling Block with 5-minute sub- N


74 rollingBlock10MinIntvl5MinSubIntvl
intervals
10 min Rolling Block with 2-minute sub- N
75 rollingBlock10MinIntvl2MinSubIntvl
intervals
10 min Rolling Block with 1-minute sub- N
76 rollingBlock10MinIntvl1MinSubIntvl
intervals
5 min Rolling Block with 1-minute sub- N
77 rollingBlock5MinIntvl1MinSubIntvl
intervals
78 twelveMinute 12 min N
79 twoHour 2h N
80 fourHour 4h N
81 sixHour 6h N
82 twelveHour 12 h N
83 threeHour 3h N
The interval length is described in attribute N
100 specifiedInterval #10 in seconds. Attribute #11 should be "1"
for whole seconds.
The fixed block duration is described in N
101 specifiedFixedBlock attribute #10 in seconds. Attribute #11 should
be "1" for whole seconds.
The rolling block size is described by attribute N
102 specifiedRollingBlock #10 in seconds, and the sub-interval size by
attribute #11 in seconds.

N = Normative

I = Informative

D = Deprecated since last edition

It is common for meters to report demand in a form that is measured over the course of a
portion of an hour. In Enterprise Applications however, it is commonly understood that
demand (which has a unit of measure of “kW” or “kVAr”) has been normalized to 1 h. The
Metering System shall perform this transformation before publication and use by the other
systems. The scalar used is chosen based on the block size (not any sub-interval size). These
scalars are listed in Table C.4

Table C.4 – Demand normalization scalars

Demand block size Normalization scalar


1h 1
30 min 2
20 min 3
15 min 4
10 min 6
1 min 60

For example, before normalization, “15minuteFixedBlock” data might be said to have units of
“kilo quarter-watt-hours” (kWh). After normalization, the unit of measure would become “kilo-
watt-hours.” Since “kilo quarter-watt-hours” is not a usable unit of measure, systems that find
the need to communicate raw data in this form should use a unit of measure such as “count”
and the PendingCalculation element to carry the scalar (or multiplier) needed and the
resulting unit of measure when applied,
– 120 – 61968-9  IEC:2013

C.2.4.2 Common Usages (Informative)

Interval data is commonly found in 60 min, 30 min, and 15 min sizes. Larger sizes such as
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

24 h and smaller sizes down to 1 min are also possible but are less common. Users of the
standard should leverage existing interval enumerations where they exist, but if the needed
interval size does "not exist, a “specifiedInterval” may be used. This allows the enumeration
itself to imbed the size of the interval in the enumeration. Similarly, uncommon fixed block
and rolling block sizes may be specified.

IEC 61968-9:2009 offered the terms “Shifted,” “Present,” and “Previous” as adjectives that
might be used to describe the state of the meter. While this works well for publishing data
from a Metering System, it may be difficult to use between other enterprise applications. It
seems that while “present” and “previous” are important attributues of the data while it is at
the meter, the further one gets away from the meter, the less important these attributes
become. With this edition of IEC 61968-9 we propose that the timespan over which the data
is recorded be relied upon to determine if a value belongs to the “present” billing period or the
“previous” billing period rather than the enumerations “present” or “previous.” Furthermore,
the rules used to compute demand are quite important. A single “Daily” demand is usually not
adequate to compute a customer’s bill. A complete collection of “Daily” demands or a single
“Billing” demand are usually required. A distinction in the Daily/Billing/Seasonal observation
period should be made in the ReadingType. In all cases, the timestamp associated with the
maximum demand could be used to resolve which day, month, or season a “daily,” “billing,” or
“seasonal” demand fell into.

In a utility where multiple techniques for capturing demand exist, it becomes important to
communicate between systems the definition by which demand data is captured.
Enumerations are provided in this edition which enable the data producer to be as specific as
it knows how in describing the type of demand data being passed.

C.2.5 Attribute #4, accumulation

C.2.5.1 General

The “accumulation” attribute indicates how the value is represented to accumulate over time.
Enumerated values include those described in Table C.5.

One benefit to explicitly declaring the accumulation behaviour as part of the readingType in
an exchange between a MS and MDM is to help the MDM ensure that appropriate validation
rules are applied to the data supplied by the MS.
61968-9  IEC:2013 – 121 –

Table C.5 – Accumulation behaviour enumerations


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Enumeration Comments
status

0 none Not Applicable, or implied by the unit of measure. N

A value from a register which represents the bulk


quantity of a commodity. This quantity is computed as
the integral of the commodity usage rate. This value is
typically used as the basis for the dial reading at the
meter, and as a result, will roll over upon reaching a
maximum dial value.
NOTE 1 With the metering system, the roll-over
behaviour typically implies a roll-under behavior so that
1 bulkQuantity N
the value presented is always a positive value (e.g.
unsigned integer or positive decimal.) However, when
communicating data between enterprise applications a
negative value might occur in a case such as net
metering.
NOTE 2 A BulkQuantity refers primarily to the dial
reading and not the consumption over a specific period
of time.
The sum of the previous billing period values and the
present period value. Note: “ContinuousCumulative” is
commonly used in conjunction with “demand.” The
“ContinuousCumulative Demand” would be the
2 continuousCumulative N
cumulative sum of the previous billing period maximum
demand values (as occurring with each demand reset)
summed with the present period maximum demand value
(which has yet to be reset.)
The sum of the previous billing period values. Note:
“Cumulative” is commonly used in conjunction with
“demand.” Each demand reset causes the maximum
demand value for the present billing period (since the
3 cumulative last demand reset) to accumulate as an accumulative N
total of all maximum demands. So instead of “zeroing”
the demand register, a demand reset has the affect of
adding the present maximum demand to this
accumulating total.
The difference between the value at the end of the
prescribed interval and the beginning of the interval. This
is used for incremental interval data.
NOTE 3 One common application would be for load
4 deltaData profile data, another use might be to report the number N
of events within an interval (such as the number of
equipment energizations within the specified period of
time.)

As if a needle is swung out on the meter face to a value


to indicate the current value. (Note: An “indicating” value
is typically measured over hundreds of milliseconds or
6 indicating N
greater, or may imply a “pusher” mechanism to capture a
value. Compare this to “instantaneous” which is
measured over a shorter period of time.)
A form of accumulation which is selective with respect to
time.
NOTE 4 “Summation” could be considered a
9 summation specialization of “Bulk Quantity” according to the rules of I
inheritance where “Summation” selectively accumulates
pulses over a timing pattern, and “BulkQuantity”
accumulates pulses all of the time.

A form of computation which introduces a time delay


10 timeDelay I
characteristic to the data value
– 122 – 61968-9  IEC:2013

Normative
Code Enumeration Comments
status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Typically measured over the fastest period of time


allowed by the definition of the metric (usually
12 instantaneous milliseconds or tens of milliseconds.) (Note: N
“Instantaneous” was moved to attribute #4 in 61968-
9Ed2 from attribute #1 in 61968-9:2009.)
When this description is applied to a metered value, it
implies that the value is a time-independent cumulative
quantity much a BulkQuantity, except that it latches upon
the maximum value upon reaching that value. Any
additional accumulation (positive or negative) is
discarded until a reset occurs.
NOTE 5 A LatchingQuantity may also occur in the
downward direction – upon reaching a minimum value.
The terms “maximum” or “minimum” will usually be
included as an attribute when this type of accumulation
13 latchingQuantity behaviour is present. N
When this description is applied to an encoded value
(UOM= “Code”), it implies that the value has one or more
bits which are latching. The condition that caused the bit
to be set may have long since evaporated.
In either case, the timestamp that accompanies the value
may not coincide with the moment the value was initially
set.
In both cases a system will need to perform an operation
to clear the latched value.
A time-independent cumulative quantity much a
BulkQuantity or a LatchingQuantity, except that the
accumulation stops at the maximum or minimum values.
When the maximum is reached, any additional positive
14 boundedQuantity accumulation is discarded, but negative accumulation N
may be accepted (thus lowering the counter.) Likewise,
when the negative bound is reached, any additional
negative accumulation is discarded, but positive
accumulation is accepted (thus increasing the counter.)

N = Normative

I = Informative

D = Deprecated since last edition

C.2.5.2 Types of IntervalReadings

In IEC 619689:2009, it was said IntervalReadings might be expressed in a number of styles


qualfied by attribute #2 (i.e. “Incremental,” “Relative,” or “Absolute”) and also described
“RecordedData” and “DeltaData”.

In this edition of IEC 61968-9 we have made an effort to simplify the presentation of data. A
sampled value which would have been called an “absolute interval” reading in IEC 61968-
9:2009may be presented without the word “absolute.” Indeed such readings may be published
in the MeterReading.Readings portion of the message as ordinary readings rather than in the
MeterReading.IntervalBlock.IntervalReadings portion of the message. The concept of
“Relative IntervalData” is no longer found in the enumerations because the concept is
supported in the message schema as a form of “pending” data scalars.

C.2.5.3 Common usages

The attributes described in Table C.5 are customarily used in particular ways to describe
energy and demand values. These customs are described in Table C.6.
61968-9  IEC:2013 – 123 –

Table C.6 – Customary accumulation behaviour enumerations

Metrology data type Common usages


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Energy (Measured by simple counting and displayed to BulkQuantity


the user on the face of the meter.)
Demand (Ordinarily measured by integrating a power Indicating, Cumulative,
value over a specific period of time.) ContinuousCumulative
Power (Ordinarily measured in real time in solid-state Instantaneous, TimeDelay
meters.)
Time Of Use (TOU) Energy data (Measured by Summation
accumulating values in assorted registers depending
on the time of day and day of the week.)
Time Of Use (TOU) Demand data (Derived by Indicating, Cumulative, or
integrating energy values over a specified demand ContinuousCumulative
interval, with additional dependencies on the TOU
calendar.)
Counters BulkQuantity, LatchingQuantity

Typical sampled
value
«enumeration»
EngineeringData
«enumeration»
Consumption Indicating = 6
Instantaneous = 12
DeltaData = 4
TimeDelay = 10
LatchingQuantity = 13
BoundedQuantity = 14

Commonly used for


interval data.
«enumeration»
AccumulatingMeterDialRegister
«enumeration»
BulkQuantity = 1 Demand
Summation = 9
Indicating = 6
Cumulative = 3
ContinuousCumulative = 2

Commonly used for


billing quantities.

Figure C.1 – Typical enumerations for accumulation behaviourAttribute #5,


flowDirection

C.2.6.1 General

Anything involving current might have a flow direction. Flow direction is very important, but
when it is unknown, it should remain unspecified. Possible enumerations include those
described in Table C.7.

The “flow direction” encompases the electrical concept of four quadrant metering as well as
the needs of various regional tariffs to describe how energy is billed.

It should be recognized that different parts of the world operate according to different frames
of reference for their tariff practices. Most regions define power delivery according to a
– 124 – 61968-9  IEC:2013

Producer"s Reference Frame. Power is generated by the utility, flows through the utility grid,
through the meter, and into the customer"s wiring. The meter captures the energy sold to the
customer. Some regions however take a customer-centric view. A Consumer Reference
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Frame says that power may be purchased by a consumer from the grid. Any forward flow
through the meter registers the energy purchased by the consumer.

This standard attempts to circumnavigate the frame-of-reference issue by recognizing that


these two views are equivalent. The energy bought is the energy sold. The “forward” flow from
the meter’s “source” side to the meter’s “load” side (or equivalent terminology such as “V+”
and a “V–”) creates a measurement that can be used for either tariff definition. This standard
will leverage the numeric code for a given semantic concept to be “normative,” while the text
used to name the concept is considered “informative.”

A second reason to keep the textual descriptions informative is due to the genuine language
differences among the various participating countries in the IEC.

Table C.7 – Direction of flow enumeration

Enumeration Normative
Code Name Comments status of
(informative) code

0 none Not Applicable (N/A) N

Also known as "Delivered," or "Imported" as defined in


IEC/TS 61968-2.
Forward Active Energy is a positive kWh value as one
would naturally expect to find as energy is supplied by
the utility and consumed at the service.
Forward Active Energy is accumulated in a single
phase service by observing the power flow (+P) in
quadrants I and IV.

1 forward N

Forward Reactive Energy is a positive VArh value as


one would naturally expect to find in the presence of
inductive loading.
Forward Reactive Energy is accumulated in a single
phase service by observing the power flow (+Q) in
quadrants I and II.
61968-9  IEC:2013 – 125 –

Enumeration Normative
Code Name Comments status of
(informative) code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Forward Apparent Energy is a positive VAh value much


like Forward Active Energy. It is accumulated in a
single phase service by observing the power flow (S =
P + jQ) in quadrants I and IV.

In polyphase metering, the forward energy register is


incremented when the sum of the phase energies is
greater than zero:
Energy A + Energy B + Energy C > 0

Typically used to describe that a power factor is lagging


the reference value (or to say that the current is lagging
the voltage.)

NOTE 1 When used to describe power factor, the term


“Lagging” implies that the PF is negative. The term
2 lagging “lagging” in this case takes the place of the negative N
sign. If a signed PF value is to be passed by the data
producer, then the direction of flow enumeration zero
(none) should be used in order to avoid the possibility
of creating an expression that employs a double
negative. The data consumer should be able to tell from
the sign of the data if the PF is leading or lagging. This
– 126 – 61968-9  IEC:2013

Enumeration Normative
Code Name Comments status of
(informative) code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

principle is analogous to the concept that “Reverse”


energy is an implied negative value, and to publish a
negative reverse value would be ambiguous.

NOTE 2 Lagging power factors typically indicate


inductive loading.

Typically used to describe that a power factor is leading


the reference value (or to say that the current is leading
the voltage.)
3 leading N
NOTE 3 Leading power factors typically indicate
capacitive loading.

Defined as |Forward| - |Reverse|, See IEC/TS 61968-2.

NOTE 4 In some systems, the value passed as a “net”


4 net value could become negative. In other systems the N
value passed as a “net” value is always a positive
number, and rolls-over and rolls-under as needed.

5 q1plusQ2 Reactive positive quadrants. I

7 q1plusQ3 Quadrants 1 and 3 I

Quadrants 1 and 4 usually represent forward active


8 q1plusQ4 I
energy

9 q1minusQ4 Q1 minus Q4 I

Quadrants 2 and 3 usually represent reverse active


10 q2plusQ3 I
energy

11 q2plusQ4 Quadrants 2 and 4 I

12 q2minusQ3 Q2 minus Q3 I

13 q3plusQ4 Reactive negative quadrants. I

14 q3minusQ2 Q3 minus Q2 I

Q1 only

15 quadrant1 I
61968-9  IEC:2013 – 127 –

Enumeration Normative
Code Name Comments status of
(informative) code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Q2 only

16 quadrant2 I

Q3 only

17 quadrant3 I

Q4 only

18 quadrant4 I
– 128 – 61968-9  IEC:2013

Enumeration Normative
Code Name Comments status of
(informative) code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Reverse Active Energy is equivalent to "Received," or


"Exported" as defined in IEC/TS 61968-2.
Reverse Active Energy is a positive kWh value as one
would expect to find when energy is produced and
backfed by the service onto the utility network.
Reverse Active Energy is accumulated in a single
phase service by observing the power flow (-P) in
quadrants II and III.

19 reverse Reverse Reactive Energy is a positive VArh value as N


one would expect to find in the presence of capacitive
loading and a leading Power Factor.
Reverse Reactive Energy is accumulated in a single
phase service by observing the power flow (-Q) in
quadrants III and IV.

Reverse Apparent Energy is a positive VAh value much


as reverse active energy. It is accumulated in a single
phase service by observing the power flow (S = P + jQ)
in quadrants II and III.
61968-9  IEC:2013 – 129 –

Enumeration Normative
Code Name Comments status of
(informative) code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

In polyphase metering, the reverse energy register is


incremented when the sum of the phase energies is
less than zero:
Energy A + Energy B + Energy C < 0
NOTE 5 The value passed as a reverse value is
always a positive value. It is understood by the label
“reverse” that it represents negative flow.
|Forward| + |Reverse|, See IEC/TS 61968-2.
The sum of the commodity in all quadrants
Q1+Q2+Q3+Q4.
20 total In polyphase metering, the total energy register is N
incremented when the absolute value of the sum of the
phase energies is greater than zero:
| Energy A + Energy B + Energy C | > 0

In polyphase metering, the total by phase energy


register is incremented when the sum of the absolute
values of the phase energies is greater than zero:
| Energy A | + | Energy B | + | Energy C | > 0
21 totalByPhase N
In single phase metering, the formulas for “Total” and
“Total by phase” collapse to the same expression. For
communication purposes however, the “Total”
enumeration should be used with single phase meter
data.

N = Normative

I = Informative

D = Deprecated since last edition

C.2.6.2 Common usages

The terminology used to specify the flow direction for reactive energy and reactive power is
varies considerably by vendor. Table C.8 describes a number of equivalent flow directions by
power (or energy) type, and recommends a preferred flow direction enumeration for
communication.
– 130 – 61968-9  IEC:2013

Table C.8 – DirectionOfFlow enumeration equivalencies

Type of
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Unit Of Equivalent flow directions commonly used Preferred flow direction for
energy or
Measure in industry messaging
power
Active or W or Wh Forward, Delivered, Positive, Q1+Q4 Forward
Real
Reverse, Received, Negative, Q2+Q3 Reverse
Net, Q1+Q4-(Q2+Q3) Net
Total, Q1+Q2+Q3+Q4 Total
Reactive VAr or Forward, Delivered, Positive, Lagging, Q1+Q2 Forward
VArh
Reverse, Received, Negative, Leading, Q3+Q4 Reverse
Net, Q1+Q2-(Q3+Q4) Net
Total, Q1+Q2+Q3+Q4 Total
Apparent VA or VAh Forward, Delivered Forward
Reverse, Received Reverse
Net Net
Total Total

class 4-DirectionOfFlow

Typical sampled
value

«enumeratio...
Not Applicable

none = 0

Measurement
Measurement
involving current
involving Power
Four-quadrant Factor
- Current
metering is a
- Energy
competing method of
- Power
describing flow
- Demand
directions.

«enumeration»
DirectionOfFlow Singlephase «enumeration»
DirectionOfFlow Polyphase «enumeration»
Forward = 1 P.F.
Net = 4 Forward = 1
Reverse = 19 Net = 4 Leading = 3
Total = 20 Reverse = 19 Lagging = 2
Total = 20
TotalByPhase = 21

Figure C.2 – Typical enumerations for direction of flow

C.2.7 Attribute #6, commodity

In this standard, the commodity which is being measured has been isolated to become an
attribute by itself. It is enumerated in Table C.9.
61968-9  IEC:2013 – 131 –

Table C.9 – Commodity


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Enumeration Comments
status

0 none Not Applicable N


All types of metered quantities. This type of reading
electricity
1 comes from the meter and represents a “secondary” N
SecondaryMetered
metered value.
It is possible for a meter to be outfitted with an
external VT and/or CT. The meter might not be aware
of these devices, and the display not compensate for
electricity
2 their presence. Ultimately, when these scalars are N
PrimaryMetered
applied, the value that represents the service value is
called the “primary metered” value. The “index” in
sub-category 3 mirrors those of sub-category 0.
A measurement of the communication infrastructure
3 communication N
itself.
4 air N
5 insulativeGas (SF 6 is found separately below.) N
6 insulativeOil N
7 naturalGas N
8 propane N
9 potableWater Drinkable water N
10 steam Water in steam form, usually used for heating. N
11 wasteWater (Sewerage) N
This fluid is likely in liquid form. It is not necessarily
water or water based. The warm fluid returns cooler
12 heatingFluid N
than when it was sent. The heat conveyed may be
metered.
The cool fluid returns warmer than when it was sent.
13 coolingFluid N
The heat conveyed may be metered.
Reclaimed water – possibly used for irrigation but not
14 nonpotableWater sufficiently treated to be considered safe for drinking. N
Moisture in oil
15 nox Nitrous Oxides, NO X N
16 so2 Sulfur Dioxide, SO 2 N
17 ch4 Methane, CH 4 N
18 co2 Carbon Dioxide, CO 2 N
19 carbon C I
20 hch Hexachlorocyclohexane, HCH N
21 pfc Perfluorocarbons, PFC N
22 sf6 Sulfurhexafluoride, SF 6 N
23 tvLicence Television N
24 internet Internet service N
25 refuse Trash N
26 h2 Hydrogen, H 2 N
27 c2h2 Acetylene, C 2 H 2 N
28 c2h4 Ethylene, C 2 H 4 N
29 c2h6 Ethane, C 2 H 6 N
30 co Carbon monoxide, CO N
31 o2 Oxygen, O 2 N
– 132 – 61968-9  IEC:2013

Normative
Code Enumeration Comments
status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Dissolved Combustible Gas (A combination of


dissolvedCombustibleG
32 combustible gasses such as H 2 , CH 4 , C 2 H 2 , C 2 H 4 , N
as
C 2 H 6 , and/or CO in some mixture.)
33 co2e Carbon Dioxide CO 2 Equivalent N
34 lead Lead, Pb N
35 mercury Mercury, Hg N
36 ozone Ozone, O 3 N
37 pm10 Particulate matter whose maximum size is 10 µm. N

38 pm25 Particulate matter whose maximum size is 2,5 µm. N


39 sox Sulfur Oxides, SO X N
40 weather Weather or meteorological conditions. N
Condition of the meter or end device itself. For
example, this enumeration might be used in
41 device N
combination with an enumeration for temperature to
represent the internal temperature of a meter.

N = Normative

I = Informative

D = Deprecated since last edition

C.2.8 Attribute #7, measurementKind

The “measurementKind” helps identify “what” is being measured. It further refines the
commodity to provide a reading category. This attribute works in conjunction with the units
attribute in creative ways to provide detail to the unit of measure. For example, “Energy” with
a unit of measure of “kWh” indicates to the user that active energy is being measured,
“Energy” with “kVAh” indicates apparent energy, and “Energy” with “kVArh” indicates reactive
energy. “Power” can be combined in a similar way with various power units of measure.
Distortion power (“DistortionVoltAmperes”) with “kVA” is different from “Power” with “kVA”.
More information can be found by studying the examples at the end of this annex.
Measurement kinds are enumerated in Table C.10.

Table C.10 – measurementKind Index

Normative
Code Enumeration Comments
Status

0 none Not Applicable N

2 apparentPowerFactor N
3 currency funds N
4 current N
5 currentAngle N
6 currentImbalance N
7 date N
8 demand N
9 distance N
10 distortionVoltAmperes N
11 energization N
12 energy N
61968-9  IEC:2013 – 133 –

Normative
Code Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

13 energizationLoadSide N
14 fan N
15 frequency N
Dup with
16 Funds D
“currency”
17 ieee1366ASAI N
18 ieee1366ASIDI N
19 ieee1366ASIFI N
20 ieee1366CAIDI N
21 ieee1366CAIFI N
22 ieee1366CEMIn N
23 ieee1366CEMSMIn N
24 ieee1366CTAIDI N
25 ieee1366MAIFI N
26 ieee1366MAIFIe N
27 ieee1366SAIDI N
28 ieee1366SAIFI N
31 lineLosses N
32 losses N
33 negativeSequence N
34 phasorPowerFactor N
35 phasorReactivePower N
36 positiveSequence N
37 power N
38 powerFactor N
40 quantityPower N
41 sag or Voltage Dip N
42 swell N
43 switchPosition N
44 tapPosition I
45 tariffRate N
46 temperature N
47 totalHarmonicDistortion N
48 transformerLosses N
49 unipedeVoltageDip10to15 N
50 unipedeVoltageDip15to30 N
51 unipedeVoltageDip30to60 N
52 unipedeVoltageDip60to90 N
53 unipedeVoltageDip90to100 N
54 Voltage (rms) N
55 voltageAngle N
56 voltageExcursion N
57 voltageImbalance N
– 134 – 61968-9  IEC:2013

Normative
Code Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Clarified from
IEC 61968-
58 volume 9:2009 to N
indicate fluid
volume
59 zeroFlowDuration N
60 zeroSequence N
64 distortionPowerFactor N
Usually
81 frequencyExcursion expressed as a N
“count”
90 applicationContext I
91 apTitle I
92 assetNumber I
93 bandwidth I
94 batteryVoltage N
95 broadcastAddress I
96 deviceAddressType1 I
97 deviceAddressType2 I
98 deviceAddressType3 I
99 deviceAddressType4 I
100 deviceClass I
101 electronicSerialNumber I
102 endDeviceID I
103 groupAddressType1 I
104 groupAddressType2 I
105 groupAddressType3 I
106 groupAddressType4 I
107 ipAddress I
108 macAddress I
109 mfgAssignedConfigurationID I
110 mfgAssignedPhysicalSerialNumber I
111 mfgAssignedProductNumber I
112 mfgAssignedUniqueCommunicationAddress I
113 multiCastAddress I
114 oneWayAddress I
115 signalStrength I
116 twoWayAddress I
Moved here from
117 signaltoNoiseRatio Attribute #9 I
UOM
118 alarm I
119 batteryCarryover I
120 dataOverflowAlarm I
121 demandLimit N
61968-9  IEC:2013 – 135 –

Normative
Code Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Usually
expressed as a
122 demandReset N
count as part of
a billing cycle
123 diagnostic I
124 emergencyLimit I
125 encoderTamper I
126 ieee1366MomentaryInterruption N
127 ieee1366MomentaryInterruptionEvent N
128 ieee1366SustainedInterruption N
129 interruptionBehaviour I
130 inversionTamper I
131 loadInterrupt I
132 loadShed I
133 maintenance I
134 physicalTamper I
135 powerLossTamper I
136 powerOutage I
137 powerQuality I
138 powerRestoration I
139 programmed I
140 pushbutton N
141 relayActivation N
Usually
142 relayCycle expressed as a N
count
143 removalTamper I
144 reprogrammingTamper I
145 reverseRotationTamper I
146 switchArmed I
147 switchDisabled I
148 tamper I
149 watchdogTimeout I
Customer’s bill
for the previous
150 billLastPeriod billing period N
Expressed as
currency.
Customer’s bill,
as known thus
far within the
151 billToDate present billing N
period.
Expressed as
currency.
– 136 – 61968-9  IEC:2013

Normative
Code Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Customer’s bill,
part of a
previous
obligation
152 billCarryover carried over N
from a previous
billing period.
Expressed as
currency.
Monthly fee for
153 connectionFee connection to I
commodity.
154 audibleVolume Sound I
155 volumetricFlow I
Most common
usage is in
expressing
156 relativeHumidity N
weather or
meteorological
conditions
Degree of sky
cover. Used in
expressing
157 skyCover N
weather or
meteorological
conditions.
158 voltage Unspecified I
159 dcVoltage I
160 acVoltagePeak Vp=√2 × Vrms I
161 acVoltagePeakToPeak Vpp=2 × Vp I

N = Normative

I = Informative

D = Deprecated since last edition

NOTE In this edition of IEC 61968-9 additional distinction has been made with respect to the
voltage frame of reference. The original enumeration for “voltage” is now explicitly used to identify
Volts RMS . This is because the most common type of measurement passed between systems is a
Volts RMS value. However, it is not the only way to measure a voltage. New enumerations have been
created to also identify Volts-peak, Volts-peak-to-peak, Volts DC, and unspecified voltage
waveforms. A number of voltage measurements are defined in figure C.3. When combined with the
accumulation attribute it is possible to show an “indicating Volts RMS ” which is measured over the
course of many cycles, an “instantaneous Volts RMS ” which is measured over a single cycle, or an
“instantaneous voltage” which is a single point sample on the waveform captured in an instant of
time.
61968-9  IEC:2013 – 137 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure C.3 – Voltage measurements

C.2.9 Attributes #8 interharmonicNumerator

See C.2.10.

C.2.10 Attribute #9 interharmonicDenominator

Interharmonics are represented as a rational number with a numerator and a denominator.


Harmonics are represented using the same mechanism, and identified by having a
denominator of “1.”

This is represented formulaically as:

and

where the equals "1".

The harmonic or interharmonic enumeration is determined by a compound element:

<interharmonic>::= <interharmonicNumerator> <interharmonicDenominator>

The normative interharmonic numerator and denominators are defined in Table C.11.
Additional values may be freely created using this approach and would be considered
“informative” rather than “normative” values.
– 138 – 61968-9  IEC:2013

Table C.11 – Harmonic and Interharmonic enumerations


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Interharmonic Interharmonic Normative


Enumeration Comments
Numerator Denominator Status
0 0 none Not Applicable N
1 2 interharmonic1/2 Interharmonic of ½ N
1 1 fundamental fundamental N
2 1 harmonic2 second harmonic N
3 1 harmonic3 third harmonic N
4 1 harmonic4 fourth harmonic N
5 1 harmonic5 fifth harmonic N
6 1 harmonic6 sixth harmonic N
7 1 harmonic7 seventh harmonic N

N = Normative

I = Informative

D = Deprecated since last edition

C.2.11 Attributes #10 argumentNumerator

See C.2.12.

C.2.12 Attribute #11 argumentDenominator

The argument elements are used to introduce numbers into the unit of measure description
where they are needed. The definition supports a rational number with a numerator and a
denominator. Most arguments used in practice however will be integers. Integers will all have
a “1” as their denominator.

numerator
argument =
denominato r

The argument enumeration is determined by a compound element:

<argument>::= <numerator> <denominator>

The normative numerator and denominators are defined in Table C.12. Additional values may
be freely created using this approach. For test purposes, values not shown in the table would
be considered “informative” rather than “normative” values.

Table C.12 – Argument enumerations

Normative
Numerator Denominator Enumeration Comments
Status
0 0 none Not Applicable N
1 2 n½ One-half I
“Zero” (for systems that use zero based N
0 1 n0 numbering schemes)
"One,” where the measure needs an N
1 1 n1 argument such as CEMI(n=1)
"Two" where the measure needs an N
2 1 n2 argument such as CEMI(n=2)
61968-9  IEC:2013 – 139 –

Normative
Numerator Denominator Enumeration Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

"Three" where the measure needs an N


3 1 n3 argument such as CEMI(n=3)
"Four" where the measure needs an N
4 1 n4 argument such as CEMI(n=4)
"Five" where the measure needs an N
5 1 n5 argument
6 1 n6 Six N
7 1 n7 Seven N
8 1 n8 Eight N
9 1 n9 Nine N
10 1 n10 Ten N
15 1 n15 Fifteen N
30 1 n30 Thirty N
45 1 n45 Fourtyfive N
60 1 n60 Sixty N
120 1 n120 2 × 60 = 120 N
155 1 n155 One hundred fifty five N
240 1 n240 4 × 60 = 240 N
305 1 n305 Three hundred and five. N
360 1 n360 6 × 60 = 360 N
480 1 n480 8 × 60 = 480 N
720 1 n720 12 × 60 = 720 N
720 60 n720/60 12 × 60/1 × 60 N
720 120 n720/120 12 × 60/2 × 60 N
720 180 n720/180 12 × 60/3 × 60 N
720 240 n720/240 12 × 60/4 × 60 N
720 360 n720/360 12 × 60/6 × 60 N

N = Normative

I = Informative

D = Deprecated since last edition

C.2.13 Attribute #12, tou

The Time Of Use (TOU) element is used to describe any attribution of the value to a specific
TOU bucket. The TOU enumerations are defined in Table C.13.

Table C.13 – Time Of Use Enumerations

Code Enumeration Comments


Normative
Status
0 none Not Applicable N
1 touA Usage in the first defined TOU bucket N
2 touB Usage in the second defined TOU bucket N
3 touC Usage in the third defined TOU bucket N
4 touD Usage in the fourth defined TOU bucket N
5 touE Usage in the fifth defined TOU bucket N
– 140 – 61968-9  IEC:2013

Code Enumeration Comments


Normative
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

6 touF Usage in the sixth defined TOU bucket N


7 touG Etc. I

N = Normative

I = Informative

D = Deprecated since last edition

C.2.14 Attribute #13, cpp

The Critical Peak Period (CPP) element is used to describe any attribution of the value to a
specific CPP bucket. Even though CPP is usually considered a specialized form of TOU, it is
separated from TOU enumerations to facilitate modelling. The CPP enumerations are defined
in Table C.14.

Table C.14 – Critical Peak Period Enumerations

Code Enumeration Comments


Normative
Status
0 none Not Applicable N
1 cppA Consumption associated with critical peak period A N
2 cppB Consumption associated with critical peak period B N
3 cppC Consumption associated with critical peak period C N
4 cppD Consumption associated with critical peak period D N
5 cppE Consumption associated with critical peak period E N
6 cppF Consumption associated with critical peak period F N
7 cppG Etc. I

N = Normative

I = Informative

D = Deprecated since last edition

C.2.15 Attribute #14, consumptionTier

Consumption tier pricing refers to the method of billing in which a certain “block” of energy is
purchased (or sold) at one price, after which the next block of energy is purchased at another
price, and so on, all throughout a defined period. At the start of the defined period,
consumption is initially zero, and any usage is measured against ConsumptionTier1. If this
block of energy is consumed before the end of the period, energy consumption moves to be
reconed against ConsumptionTier2. If this block of energy is consumed before the end of the
period, energy consumption moves to ConsumptionTier3, and so on. At the end of the defined
period the consumption accumulator is reset, and usage within ConsumptionTier1 restarts.

This is in contrast to the common “flat rate” for power, in which all purchases are at a given
rate. When flat-rate pricing is used, a consumptionTier of “not applicable” should be specified.

Enumerations for Consumption Tiers are defined in Table C.15.


61968-9  IEC:2013 – 141 –

Table C.15 – Consumption Tier Enumerations

Normative
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Code Enumeration Comments


Status
0 none Not applicable N
1 consumptionTier1 Usage in the first defined consumption bucket N
2 consumptionTier2 Usage in the second defined consumption bucket N
3 consumptionTier3 Usage in the third defined consumption bucket N
4 consumptionTier4 Usage in the fourth defined consumption bucket N
5 consumptionTier5 Usage in the fifth defined consumption bucket N
6 consumptionTier6 Usage in the sixth defined consumption bucket N
Additional consumption tiers may be created as I
7 consumptionTier7
necessary.

N = Normative

I = Informative

D = Deprecated since last edition

TOU or CPP pricing may be used in conjunction with consumption tier pricing. The examples
provided in Table C.16 may be useful:

Table C.16 – Example Combinations of TOU and Consumption Tier Enumerations

Tou Consumption
Comments
Code Tier Code
1 0 TOU Period A with flat rate pricing
1 1 TOU Period A with Consumption Tier 1
1 2 TOU Period A with Consumption Tier 2
1 3 TOU Period A with Consumption Tier 3
2 1 TOU Period B with Consumption Tier 1
2 2 TOU Period B with Consumption Tier 2
2 3 TOU Period B with Consumption Tier 3
3 1 TOU Period C with Consumption Tier 1
3 2 TOU Period C with Consumption Tier 2
3 3 TOU Period C with Consumption Tier 3
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C.2.16 Attribute #15, phases

The metering phase enumerations are described in Table C.17.

Table C.17 – Phase enumerations

Position 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Normative
Code Enumeration Comments S1 S2 A1 B1 C1 N1 A2 B2 C2 N2

Wye
Status

Delta

Open
High leg

Networked
0 none Not applicable to any phase 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N
16 phaseN Neutral 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 N
17 phaseNtoGnd Neutral to ground 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 N
32 phaseC Phase C 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 N
33 phaseCtoN Phase C to Neutral 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 N
Phase C current or voltage relative to
40 phaseCtoAv 0 0 0 0 0 0 0 0 0 1 0 1 0 0 0 N
Phase A voltage
– 142 –

41 phaseCAtoN CA to Neutral 0 0 0 0 0 0 0 0 0 1 0 1 0 0 1 N
64 phaseB Phase B 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 N
65 phaseBtoN Phase B to Neutral 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 N
66 phaseBtoC Phase B to C 0 0 0 0 0 0 0 0 1 0 0 0 0 1 0 N
Phase B current or voltage relative to
72 phaseBtoAv 0 0 0 0 0 0 0 0 1 0 0 1 0 0 0 N
Phase A voltage
97 phaseBCtoN BC to Neutral 0 0 0 0 0 0 0 0 1 1 0 0 0 0 1 N
128 phaseA Phase A 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 N
129 phaseAtoN Phase A to Neutral 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 N
132 phaseAtoB Phase A to B 0 0 0 0 0 0 0 1 0 0 0 0 1 0 0 N
Phase A current relative to Phase A
136 phaseAtoAv 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 N
voltage
61968-9  IEC:2013

193 phaseABtoN AB to Neutral 0 0 0 0 0 0 0 1 1 0 0 0 0 0 1 N

224 phasesABC Involving all phases 0 0 0 0 0 0 0 1 1 1 0 0 0 0 0 N


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Position 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Normative
Code Enumeration Comments S1 S2 A1 B1 C1 N1 A2 B2 C2 N2

Wye
Status

Delta

Open
High leg

Networked
225 phaseABCtoN ABC to Neutral 0 0 0 0 0 0 0 1 1 1 0 0 0 0 1 N
61968-9  IEC:2013

256 s2 Phase S2 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 N

257 s2N Phase S2 to Neutral 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 N

512 s1 Phase S1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 N

513 s1N Phase S1 to Neutral 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 N

768 s12 Phase S1 to S2 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 N


– 143 –

769 s12N Phase S1, S2 to Neutral 0 0 0 0 0 1 1 0 0 0 0 0 0 0 1 N

1248 threeWireWye 3W Wye 0 0 0 0 1 0 0 1 1 1 0 0 0 0 0 N

1249 fourWireWye 4W Wye 0 0 0 0 1 0 0 1 1 1 0 0 0 0 1 N

2272 threeWireDelta 3W Delta 0 0 0 1 0 0 0 1 1 1 0 0 0 0 0 N

2273 fourWireDelta 4W Delta 0 0 0 1 0 0 0 1 1 1 0 0 0 0 1 N

6369 fourWireHLDelta 4W High-leg Delta 0 0 1 1 0 0 0 1 1 1 0 0 0 0 1 N

10465 fourWireOpenDelta 4W Open Delta 0 1 0 1 0 0 0 1 1 1 0 0 0 0 1 N

17153 networked Networked meter 1 0 0 0 0 1 1 0 0 0 0 0 0 0 1 N

NOTE 1 The code values were computed by:

Code = Networked × 214 + Open × 2 13 + HighLeg × 212 + Delta × 2 11 + Wye × 210 + S 1 × 29 + S 2 × 28 + A 1 × 27 + B 1 × 2 6 + C 1 × 25 + N 1 × 24 + A 2 × 2 3 + B 2 × 22 + C1 × 21 + N 2

NOTE 2 Directional vectors (such as V AB vs. V BA ) are created in the phase code by invoking the involved phase (left to right in the matrix) in the order in which they are to be
described in the enumeration (left to right as one reads).
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

When current is measured, it is often simple a single phase conductor indicated such as:

• A
• B
• C
• N

The Neutral-to-ground “phase” can be used to indicate current flowing from the neutral wire to ground. In this case select both N 1 and N 2 . When only
neutral is selected choose N 1 . In all other cases when referencing neutral select N 2 . The main goal is readability. These rules should provide the
necessary readability.

When voltage is measured, it may contain a simple description of the phase conductor, or if measured relative to something else, an indication of the
measurement being “line-to-neutral” or “line-to-line” measured. Common voltage measurements include:

• A
• B
• C
• AN
• BN
– 144 –

• CN
• AB
• BC
• CA
• ABC

When phase angles are measured, it is usually relative to a fixed reference such as voltage phase A. The word “angle” has already been described in a
previous field. This field may therefore contain an angle designation such as:

• A current A volts
• B current A volts
61968-9  IEC:2013

• C current A volts

Where the first phase listed is understood to describe the current or voltage phase being measured, and the second phase (the “A”) describes what it is
being measured against (voltage phase A.) Since the fact that the measurement is an angle can be determined from the context (provided by the unit of
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

measure), and the point of reference is always the second phase, there is no need to provide additional indications within the phase lettering. This allows
the same code (such as “Phase-CA”) to often be used as a line-to-line voltage descriptor, a voltage phase-angle descriptor, as well as a current phase-
angle descriptor.

Residential or other two-phase secondary voltages may be identified as “S1” or “S2”. These labels may be used when the “ABC” names of the phase(s)
that feed the service are unknown or unimportant.

The various polyphase network wirings may be identified as:


61968-9  IEC:2013

• Wye
• Delta
• High-leg delta
• Open delta
• Networked

The use of 3 wires or 4 wires may be determined by simply counting the number of phases (including neutral) involved in the service.
– 145 –
– 146 – 61968-9  IEC:2013

C.2.17 Attribute #16, multiplier


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

The ReadingType encoding offers a field to describe a power-of-ten multiplier against the data
value. This is not quite the same as the customary SI-prefix, though in many cases it creates
the same result. The user will have to decide what the appropriate displayable symbol is
based on the dimensions of the unit of measure. The multiplier enumerations are described in
Table C.18 for units of measure that have a single dimension (e.g. “V” not “V 2 ”). The index
value represents the power of ten.

Table C.18 – Power of ten enumerations

Displayable symbol
Code for single- Comments Normative status
dimensioned UOM
–24 y yocto = ×10 –24 N
–21 z zepto = ×10 –21 N
–18 a atto = ×10 –18 N
–15 f femto = ×10 –15 N
–12 p pico = ×10 –12 N
–9 n nano = ×10 –9 N
–6 µ micro = ×10 –6 N

–3 m milli= ×10 –3 N
–2 c centi = ×10 –2 N
–1 d deci = ×10 –1 N
0 Not applicable or "×1" N
1 da deca = ×10 1 N
2 h hecto = ×10 2 N
3 k kilo = ×10 3 N
6 M Mega = ×10 6 N
9 G Giga = ×10 9 N
12 T Tera = ×10 12 N
15 P Peta = ×10 15 N
18 E Exa = ×10 18 N
21 Z Zetta = ×10 21 N
24 Y Yotta = ×10 24 N

N = Normative

I = Informative

D = Deprecated since last edition

It should be remembered that this power-of-ten multiplier does not work the same way as the
SI prefix. The SI prefix is considered to be part of the unit of measure. A power-of-ten
multiplier is not part of the unit of measure. When a SI-Prefix is used, it is understood that
“10 –3 ” is represented as “milli”, and a mm 3 is the same as (mm) 3 which is the same as
(0,001 m) 3 or 10 –9 m 3 . This is not the same result as 0,001 × m 3 (which is what a power-of-
ten multiplier yields.).

Rules for the use of SI prefixes may be found in IEC 60050-112:2010, 02-03.
61968-9  IEC:2013 – 147 –

When the unit of measure being described is a ratio which is rendered as a dimensionless
quantity (such as a concentration), it is sometimes customary to display a symbol other than
the standard metric prefix symbol. The modern convention however is to use the SI-prefix
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

symbols infront of the dimensionless ratio being described. For example, a ppm concentration
by volume (“ppmv”) should instead be described as “µL/L”. A few historical dimensionless
scalars are provided in Table C.19 for reference.

Table C.19 – Historical concentration multiplier enumerations

Displayable Normative
Code Comments
Symbol Status
0 PU per unit = ×1 = 10 0 I

–2 % percent = ×0,01 = ×10 –2 I

–3 ‰ permille = ×0,001 = ×10 –3 I

–6 ppm parts per million, ×0,000 001 = ×10 –6 I

–9 ppb parts per billion, ×0,000 000 001 = ×10 –9 I

N = Normative

I = Informative

D = Deprecated since last edition


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C.2.18 Attribute #17, unit

In IEC 61968-9:2009, a “ppm” unit of measure was supported. In this edition this support was moved from the UOM attribute to the Power-of-ten multiplier
attribute, and a number of “concentration” units of measure were introduced.

Tables C.20 through C.27 describe the unit of measure enumerations. They are organized by their relationships to the SI units of measure. SI-units are
the preferred unit of measure, but as an international standard, it is understood that other units of measure shall also be supported in some regions.

In these tables, the “code” column is a unique value. The “normative status” indicates if the “code” is normative or informative. The “quantity” column
indicates the category of measure. The “unit name” suppolies the official name for the unit, and possibly comments regarding its use or relationship to
other units. The “symbol” column indicates in most cases the official displayable symbol for the unit. Where there were cases for conflict because different
measurement systems have been combined, preference is given to the SI unit of measure. (This happened in the case of rad (rd) and rod (rd).) The
“enumeration” column creates a unique string which could be used by CIM modelers to capture a string value for the unit. The enumeration was created
based on the following rules:

• A lower camel-case transformation of the symbol column is attempted. All spaces are removed from the symbol to create the enumeration.
• The symbol set is restricted to alpha-numeric characters.
• The symbols “-“, “(“, and “)” are removed.
• The symbol “/” is replaced by the string “Per”.
• The symbol “°” is replaced by the string “Deg”.
– 148 –

• Other special symbols such as “¤”, “’”, “µ” and “ħ” are replaced with alternative alpha text strings.
• Digits are not allowed as the first character in the enumeration.
• Text that is superscripted or subscripted is used as normal text in the enumeration (if conflicts are avoidable).
• If two different symbols would result in the same enumeration (due to capitalization rules) then one of them is changed (with preference being given to

the base SI units). Exceptions were created for the symbols “A”, “B”, “G”, “H”, “ħ”, “M”, “m e , “S”, and “T”.
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table C.20 – Base SI units of measure

Unit name Normative


Code Quantity Symbol Enumeration
(and comments) Status

2 Length metre m m N
3 Mass gram g g N
5 Current ampere A a N
61968-9  IEC:2013

6 Temperature Kelvin K degK I


7 Amount of substance mole mol mol I
8 Luminous intensity candela cd cd I
27 Time second s s N

N = Normative

I = Informative
– 149 –

D = Deprecated since last edition

NOTE The British spelling “metre” and American spelling “meter” are equivalent.

Table C.21 – Derived SI units of measure with special names

Displayable Normative
Code Quantity Unit name (and comments) Enumeration
Symbol Status
10 Plane angle Radian (m/m) rad rad N
11 Solid angle Steradian (m 2 /m 2 ) sr sr I
21 Absorbed dose Gray (J/kg) Gy gy I
22 Radioactivity Becquerel (1/s) Bq bq I
23 Temperature degrees Celsius °C degC N
24 Dose equivalent Sievert (J/kg) Sv sv I
25 Electric capacitance Farad (C/V) F f N
26 Electric charge Coulomb (Amp second) C c I
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Displayable Normative
Code Quantity Unit name (and comments) Enumeration
Symbol Status
28 Electric inductance Henry (Wb/A) H h N
29 Electric potential Volt (W/A) V v N
30 Electric resistance Ohm (V/A) Ω ohm N

31 Energy joule (N·m = C·V = W·s) J j N


32 Force newton (kg m/s 2 ) N n N
33 Frequency Cycles per second or (1/s) Hz hz N
34 Illuminance lux (lm/m 2 ) lx lx I
35 Luminous flux lumen (cd sr) lm lm I
36 Magnetic flux Weber (V s) Wb wb I
37 Magnetic flux density Tesla (Wb/m 2 ) T t I
Watt. By definition, one Watt equals oneJoule per second.
Electrical power may have real and reactive components. The real
38 Real power W w N
portion of electrical power (I 2 R) or VIcosθ, is expressed in Watts.
(See also apparent power and reactive power.)
Pascal (N/m 2 )
39 Pressure Note: the absolute or relative measurement of pressure is implied Pa pa N
with this entry. See below for more explicit forms.
– 150 –

53 Electric Conductance Siemens (A / V = 1 / Ω) S siemens N


155 Pressure Pascal, absolute pressure PaA paA N
140 Pressure Pascal, gauge pressure PaG paG N
158 Catalytic activity katal = mol / s kat kat I

N = Normative

I = Informative

D = Deprecated since last edition

NOTE The British spelling “litre” and American spelling “liter” are equivalent.
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table C.22 – Derived SI Units of Measure without Special Names

Displayable Normative
Code Quantity Unit name (and comments) Enumeration
Symbol Status
rotations per second
4 Rotational speed rev/s revPerS I
NOTE Compare to cycles per second, Hz
41 Area square metre m2 m2 N
61968-9  IEC:2013

42 Volume cubic metre m3 m3 N


43 Velocity metre per second (m/s) m/s mPerS N
44 Acceleration metre per second squared m/s 2 mPerS2 I
45 Volumetric flow rate cubic metres per second m 3 /s m3PerS N
46 Fuel efficiency metre / cubic metre m/m 3 mPerM3 I
kilogram metre (kg·m) (first moment of mass)
47 Moment of mass gm gM I
NOTE 1 Users shall supply the “k” prefix to obtain “kg m”.
– 151 –

gram/cubic metre
48 Density g/m 3 gPerM3 I
NOTE 2 Users shall supply the prefix multiplier “k” to form kg/m 3
49 Viscosity metre squared / second m 2 /s m2PerS I
50 Thermal conductivity Watt/metre Kelvin W/(m K) wPerMK I
51 Heat capacity Joule/Kelvin J/K jPerK I
54 Angular velocity radians per second rad/s radPerS I
61 Apparent power Volt Ampere (See also real power and reactive power.) VA vA N
Volt Ampere reactive. The “reactive” or “imaginary” component of
electrical power (VISinθ). (See also real power and apparent
power).

63 Reactive power NOTE 3 Different meter designs use different methods to arrive at VAr vAr N
their results. Some meters may compute reactive power as an
arithmetic value, while others compute the value vectorially. The
data consumer should determine the method in use and the
suitability of the measurement for the intended purpose.
66 Volt seconds Volt seconds (Ws/A) Vs vS N
67 Volts squared Volt squared (W 2 /A 2 ) V2 v2 N
68 Amp seconds Amp seconds As aS N

69 Amps squared Amp squared A2 a2 N


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Displayable Normative
Code Quantity Unit name (and comments) Enumeration
Symbol Status

70 Amps squared time square Amp second A2s a2S I

71 Apparent energy Volt Ampere hours VAh vAH N


72 Real energy Watt hours Wh wH N
73 Reactive energy Volt Ampere reactive hours VArh vArH N
74 Magnetic flux Volt per Hertz V/Hz vPerHz I
Rate of change of
75 Hertz per second Hz/s hzPerS I
frequency
kg m 2 (Second moment of mass, commonly called the moment of
78 Moment of mass interia) gm 2 gM2 I
NOTE 4 Users shall supply the “k” prefix to obtain “kg m 2 ”.

81 Ramp rate Watt per second W/s wPerS I


82 Volumetric flow rate litre per second L/s lPerS I
100 Quantity power Q Q q I
101 Quantity energy Qh Qh qh I
102 resistivity Ohm metre, ρ (rho) Ωm ohmM I
103 A/m magnetic field strength, Ampere per metre A/m aPerM I
– 152 –

104 volt-squared hour Volt-squared-hours V2 h v2H I


105 ampere-squared hour Ampere-squared hour A2 h a2H I
106 Ampere-hours Ampere-hours Ah aH I
3
107 Wh/m energy per volume Wh/m3 wHPerM3 I
108 Timestamp time and date per ISO 8601 format timeStamp timeStamp N
115 Kh-Wh active energy metering constant Wh/rev wHPerRev N
116 Kh-VArh reactive energy metering constant VArh/rev vArHPerRev N
117 Kh-Vah apparent energy metering constant VAh/rev vAHPerRev N
125 Volumetric flow rate cubic metre per hour m 3 /h m3PerH N
126 Volumetric flow rate compensated cubic metre per hour m3 (compensated) /h m3CompensatedPerH N
127 Volumetric flow rate uncompensated cubic metre per hour m3 m3UncompensatedPerH N
61968-9  IEC:2013

(uncompensated) /h

137 Volumetric flow rate litre per hour L/h lPerH N


139 Volumetric flow rate litre (uncompensated) per hour L (uncompensated) /h lUncompensatedPerH N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Displayable Normative
Code Quantity Unit name (and comments) Enumeration
Symbol Status
138 Volumetric flow rate litre (compensated) per hour L (compensated) /h lCompensatedPerH N
161 Quantity power Q measured at 45º Q45 q45 I
162 Quantity power Q measured at 60º Q60 q60 I
163 Quantity energy Qh measured at 45º Q45 h q45H I
164 Quantity energy Qh measured at 60º Q60 h q60H I
61968-9  IEC:2013

165 Specific energy Joule / kg J/kg jPerKg I


166 Volume cubic metre, with the value uncompensated for weather effects. m3 (uncompensated) m3Uncompensated N
167 Volume cubic metre, with the value compensated for weather effects. m3 (compensated) m3Compensated N

173 Wavenumber reciprocal metre, (1/m) M–1 m1 I

174 Specific volume cubic metre per kilogram, v m3 /kg m3PerKg I


175 Dynamic viscosity Pascal second Pa s paS I
176 Moment of force Newton metre Nm nM I
– 153 –

177 Surface tension Newton per metre N/m nPerM I


178 Angular acceleration radian per second squared rad/s2 radPerS2 I
Heat flux density,
179 Watt per square metre W/m2 wPerM2 I
irradiance
Specific heat
180 capacity, specific Joule per kilogram kelvin J/(kg K) jPerKgK I
entropy
181 energy density Joule per cubic metre J/m3 jPerM3 I
182 electric field strength Volt per metre V/m vPerM I
electric charge
183 Coulomb per cubic metre C/m3 cPerM3 I
density

surface charge
184 Coulomb per square metre C/m2 cPerM2 I
density

185 permittivity Farad per metre F/m fPerM I


186 permeability Henry per metre H/m hPerM I
187 molar energy Joule per mole J/mol jPerMol I
molar entropy, molar
188 Joule per mole kelvin J/(mol K) jPerMolK I
heat capacity
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Displayable Normative
Code Quantity Unit name (and comments) Enumeration
Symbol Status
189 exposure (x rays) Coulomb per kilogram C/kg cPerKg I
190 absorbed dose rate Gray per second Gy/s gyPerS I
191 radiant intensity Watt per steradian W/sr wPerSr I
192 radiance Watt per square metre steradian W/(m 2 sr) wPerM2Sr I
catalytic activity
193 katal per cubic metre kat/m 3 katPerM3 I
concentration
280 Volt-hour Volt hours Vh vH N

N = Normative

I = Informative

D = Deprecated since last edition

Table C.23 – Non-SI Units of Measure accepted for use with the International System of Units

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
159 Time minute = 60 s min min I
– 154 –

160 Time hour = 60 min = 3 600 s h hr I


195 Time day = 24 h = 86 400 s d d I
9 Plane angle degree º deg N
196 Plane angle minute " angleMin I
197 Plane angle second “ angleSec I
198 Area hectare ha ha I
134 Volume litre = dm 3 = m 3 /1 000 L l N
199 mass “tonne” or “metric ton” (1 000 kg = 1 Mg) t tonne I

N = Normative
61968-9  IEC:2013

I = Informative

D = Deprecated since last edition

NOTE The British spelling “litre” and American spelling “liter” are equivalent.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table C.24 – Dimensionless and Concentration Units of Measure

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status

0 N/A none (not applicable) none N

dimensionless
61968-9  IEC:2013

NOTE 1 This definition of power factor only holds for balanced


65 Power factor systems. See the alternative definition under code 153. cosθ cosTheta N
NOTE 2 Beware of differing sign conventions in use between the IEC
and EEI. It is assumed that the data consumer understands the type of
meter in use and the sign convention in use by the utility.
Bel
79 Logrithmic ratio NOTE 3 Users shall combine this unit with the multiplier prefix “d” to B bel I
form decibels (dB)
status, where:
– 155 –

"1" = "true", "live", "on", "high", "set";


109 State "0" = "false", "dead", "off", "low", "cleared" status status N
NOTE 4 A Boolean value is preferred but other values may be
supported
Amount of
111 Counter value count count N
substance
Logrithmic ratio of Bel-mW, normalized to 1mW. Note: to form “dBm” combine “Bm” with
113 Bm bm N
signal strength multiplier “d”.
114 Application Value Encoded value code code N
118 EndDeviceEvent Value to be interpreted as a EndDeviceEventCode meCode meCode N
The ratio of the volume of a solute divided by the volume of the
solution.
143 Concentration L/L lPerL N
NOTE 5 Users may need use a prefix such a "µ" to express a
quantitye such as "µL/L"
The ratio of the mass of a solute divided by the mass of the solution.
144 Concentration NOTE 6 Users may need use a prefix such a "µ" to express a quantity g/g gPerG N
such as "µg/g"
The amount of substance concentration, (c), the amount of solvent in
145 Concentration mol/m³ molPerM3 I
moles divided by the volume of solution in m³.
Molar fraction (χ), the ratio of the molar amount of a solute divided by
146 Concentration mol/mol molPerMol I
the molar amount of the solution.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
Molality, the amount of solute in moles and the amount of solvent in
147 Concentration mol/kg molPerKg I
kilograms.
148 Length Ratio of length m/m mPerM I
Ratio of time
149 Time NOTE 7 Users may need to supply a prefix such as "µ" to show rates s/s sPerS N
such as "µs/s"
Rate of frequency change
150 Frequency NOTE 8 Users may need to supply a prefix such as "m" to show rates Hz/Hz hzPerHz N
such as "mHz/Hz"
Ratio of voltages
151 Voltage NOTE 9 Users may need to supply a prefix such as "m" to show rates V/V vPerV N
such as "mV/V"
Ratio of Amperages
152 Current NOTE 10 Users may need to supply a prefix such as "m" to show A/A aPerA I
rates such as "mA/A"
PF, the ratio of the active power to the apparent power.
NOTE 11 The sign convention used for power factor will differ
153 Power factor between IEC meters and EEI (ANSI) meters. It is assumed that the W/VA wPerVA I
– 156 –

data consumers understand the type of meter being used and agree on
the sign convention in use at any given utility.
154 Amount of rotation Revolutions rev rev I
Ratio of power
168 Signal Strength NOTE 12 Users may need to supply a prefix such as "m" to show W/W wPerW I
rates such as "mW/W"
170 Refractive Index n n refractiveIndexN I
Relative
171 µr µr relativePermeabilityMur I
Permeability
172 Logarithmic ratio Neper Np np I
Relative humidity espressed as the ratio of partial pressure of water
281 Humidity vapor in the air-water mixture to the saturated vapor pressure of water φ realtiveHumidity N
at the prescribed temperature.
61968-9  IEC:2013

282 Sky Cover Ratio of covered sky to total sky. skyCover skyCover N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

N = Normative

I = Informative

D = Deprecated since last edition

Table C.25 – Non-SI units whose values in SI units shall be obtained experimentally
61968-9  IEC:2013

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status

200 energy electronvolt (1 eV = 1,602 176 × 10 –19 J) eV eV I

201 mass –27 Da da I


dalton (1 Da = 1,660 538 × 10 kg)
202 mass unified atomic mass unit (1 u = 1 Da) u u I
203 length 11 ua ua I
astronomical unit (1ua = 1,495 978 × 10 m)
natural unit of speed (speed of light in a vacuum)
– 157 –

204 speed c0 c0 I
= 299 792 458 m/s
natural unit of action (reduced planck constant)
205 action ħ nuH I
= 1,054 571 × 10 –34 J s
natural unit of mass (electron mass)
206 mass me nuMe I
= 9,109 382 × 10 –31 kg
207 time natural unit of time ħ/(m e c 0 2 ) nuHPerNuMeC02 I
atomic units of charge (elementary charge)
208 charge e auE I
= 1,602 176 × 10 –19 C
atomic units of mass (electron mass)
209 mass me auMe I
= 9,109 382 × 10 –31 kg
atomic unit of action (reduced planck constant)
210 action ħ auH I
= 1,054 571 × 10 –34 J s
atomic unit of length, bohr ( Bohr radius)
211 length a0 auA0 I
= 0,529 177 × 10 –10 m
atomic unit of energy, hartree
212 energy Eh auEh I
= 4,359 744
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
213 time atomic unit of time ħ/Eh auHPerAuEh I

N = Normative

I = Informative

D = Deprecated since last edition

Table C.26 – Other Non-SI Units of Measure

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
Number of
76 characters char char N
characters
77 Data rate characters per second char/s charPerSec I
Generic money
80 Monetary unit NOTE Specific monetary units are identified the currency ¤ money I
class
119 Volume cubic foot ft 3 ft3 N
– 158 –

120 Volume cubic foot compensated for weather ft 3 (compensated) ft3Compensated N


3
121 Volume cubic foot uncompensated for weather ft (uncompensated) ft3Uncompensated N
122 Volumetric flow rate cubic foot per hour ft 3 /h ft3PerH N
123 Volumetric flow rate compensated cubic feet per hour ft 3 (compensated)/h ft3CompensatedPerH N
124 Volumetric flow rate uncompensated cubic feet per hour ft 3 (uncompensated)/h ft3UncompensatedPerH N
128 Volume US gallon (1 gal = 231 in 3 = 128 fl oz.) US gal uSGal N
129 Volumetric flow rate US gallon per hour US gal/h uSGalPerH N
130 Volume Imperial gallon imp gal impGal N
131 Volumetric flow rate Imperial gallon per hour imp gal/h impGalPerH N
132 Energy British Thermal Unit BTU btu N
133 Power BTU per hour BTU/h btuPerH N
61968-9  IEC:2013

141 Pressure Pound per square inch, absolute psiA psiA I


142 Pressure Pound per square inch, gauge psiG psiG I
156 Volume Litre, with the value uncompensated for weather effects L (uncompensated) lUncompensated N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
157 Volume Litre, with the value compensated for weather effects L (compensated) lCompensated N
169 Energy Therm therm therm N
214 Pressure bar (1 bar = 100 kPa) bar bar I
215 Pressure millimeter of mercury (1 mmHg ≈ 133,3 Pa) mmHg mmHg I
216 Length ångström (1Å = 10 –10 m) Å angstrom I
61968-9  IEC:2013

217 Length nautical mile (1 M = 1852 m) M nmi I


218 Area barn (1 b = 100 fm 2 = 10 –28 m 2) b barn I
219 Speed knot (1 kn = 1852/3600) m/s kn kn I
220 Activity 10 Ci ci I
curie (1 Ci = 3,7 × 10 Bq)
221 exposure –4 R r I
roentgen (1 R = 2,58 × 10 C/kg)
222 absorbed dose rad (1 rd = 1 cGy) rd doseRad I
223 dose equivalent rem (1 rem = 10 –2 Sv) rem rem I
– 159 –

224 length inch in in I


225 length foot (1 ft = 12 in) ft ft I

226 length rod (1 rod = 16,5 ft) rod rod I

227 length furlong (1 fur = 660 ft) fur fur I


mile (1 statute mile = 8 fur = 80 chains = 320 rods = 5280
228 length mi mi I
feet)
229 area square foot (1 ft 2 = 144 in 2 ) ft 2 ft2 I
230 area square yard (1 yd 2 = 9 ft 2 ) yd 2 yd2 I
231 area square rod (1 rod 2 = 272,25 ft 2 ) rod 2 rod2 I
232 area acre (1 acre = 160 rd 2 = 43 560 ft 2 ) acre acre I
233 area square mile (1 mi 2 = 640 acres) mi 2 mi2 I
234 area section of land (1 mi 2 = 1 section of land) section of land sectionOfLand I
235 area township (1 township = 6 miles square) township township I
237 Volume cubic yard (1 yd 3 = 27 ft 3 ) yd 3 yd3 I
238 length link (1 li = 0,66 ft) li li I
239 length chain (1 ch = 100 links = 4 rods = 66 ft) ch ch I
3
240 Volume US liquid pint (1 pt = 28,875 in = 128 fl dr) US liq pt uSLiqPt I
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
241 Volume US liquid quart (1 qt = 2 pt) US liq qt uSLiqQt I
242 Volume Apothecaries fluid dram fl dr ap flDrAp I
243 Volume Apothecaries fluid ounce (1 fl oz ap = 8 fl dr ap) fl oz ap flOzAp I
244 Volume US dry pint (1 pt = 67,2 in 3 ) US dry pt usDryPt I
245 Volume US dry quart (1 qt = 2 pints) US dry qt usDryQt I
246 Volume US peck (1 pk = 8 qt) US pk usPk I
247 Volume US bushel (1 bu = 4 pk) US bu usBu I
grain (1 grain = 1/7000 avdp lb)
248 Mass NOTE The “grain” is the same in the avoirdupois, troy, and gr gr I
apothecaries units of mass.
Avoirdupois dram (1 Avdp dr = 27-11/32 gr)

249 Mass NOTE The abbreviation “dr” may be used if there is no avdp dr avdpDr I
chance of confusing the avoirdupois dram with the troy or
apothecaries dram.
Avoirdupois ounce (1 Avdp oz = 16 Avdp dr)

250 Mass NOTE The abbreviation “oz” may be used if there is no avdp oz avdpOz I
chance of confusing the avoirdupois ounce with the troy or
– 160 –

apothecaries ounce.
Avoirdupois pound (1 lb = 16 oz)
NOTE Although the term “pound” is commonly used in many
countries simply as “pound (lb)”, the historical term
251 Mass “avoirdupois” is added to provide context and distinguish it in avdp lb avdpLb I
this setting from the troy and apothecaries systems of
measure which use the same names. The abbreviation “lb”
may be used instead of “avdp lb” if no confusion is possible
with the pound named in these other systems.
252 Mass Avoirdupois hundredweight (1 cwt = 100 lbs) short cwt shortCwt I
253 Mass Avoirdupois ton (1 short ton = 2000 lbs) short ton shortTon I
Avoirdupois gross or long hundredweight
254 Mass long cwt longCwt I
(1 long cwt = 112 lbs)
Avoirdupois gross or long ton
61968-9  IEC:2013

255 Mass long ton longTon I


(1 long ton = 20 long cwt)
256 Mass Troy pennyweight (1 dwt = 24 grains) dwt dwt I
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
257 Mass Troy ounce (1 oz t = 20 dwt) oz t ozT I
258 Mass Troy pound (1 lb t = 12 oz t) lb t lbT I
259 Mass Apothecaries scruple (1 s ap = 20 grains) s ap sAp I
260 Mass Apothecaries dram (1 dr ap = 3 s ap) dr ap drAp I
261 Mass Apothecaries ounce (1 oz ap = 8 dr ap) oz ap ozAp I
61968-9  IEC:2013

262 Mass Apothecaries pound (1 lp ap = 12 oz ap) lb ap lbAp I


263 Fuel economy mile per imperial gallon mpg (Imp) mpgImp I
264 Fuel economy mile per US gallon mpg (US) mpgUS I
265 Fuel economy mile per US gallon equivalent MPGe (US) mPGeUS I
266 Fuel economy litre per 100 km l/(100 km) lPer100km I
killowatt-hour per mile (Note: users shall supply the “k” prefix
267 Fuel economy Wh/mi wHPerMi I
to create “kWh/mi”)
– 161 –

kilowatt-hour per 100 mile (Note: users shall supply the “k”
268 Fuel economy Wh/(100 mi) wHPer100Mi I
prefix to create “kWh/(100 mi)”)
279 Temperature degrees Fahrenheit ºF degF I

N = Normative

I = Informative

D = Deprecated since last edition


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table C.27 – Non-SI Units Associated with the CGS and the CGS-Gaussian System of Units

Normative
Code Quantity Unit name (and comments) Symbol Enumeration
Status
269 Energy erg (1 erg = 10 –7 J) erg erg I
270 Force dyne (1 dyn = 10 –5 N) dyn dyn I
271 Dynamic viscosity poise (1 P = 0,1 Pa s) P p I
272 Kinematic viscosity stokes (1 St = 1 cm 2 /s) St st I
273 Luminance stilb (1 sb = 10 4 cd/m 2 ) sb sb I
274 Illuminance phot (1 ph = 10 4 lx) ph ph I
–2
gal (1 Gal = 10 m s –2 )
275 Acceleration Gal gal I
NOTE This “Gal” is an abbreviation for “Galileo” not “gallon”
276 Magnetic flux Maxwell (1 Mx = 10 –8 Wb) Mx mx I
277 Magnetic flux density Gauss (1 G = 10 –4 T) G gauss I
278 Magnetic field Œrsted (1 Oe = (10 3 /4π) A/m) Oe oe I

N = Normative

I = Informative
– 162 –

D = Deprecated since last edition


61968-9  IEC:2013
61968-9  IEC:2013 – 163 –

C.2.19 Attribute #18, currency


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Currency codes are defined in ISO 4217. A handful of codes have been repeated in
Table C.28 for reference. Additional currency codes may be drawn freely from ISO 4217.

Table C.28 – Currency units of measure (from ISO 4217)

Displayable Normative
Code Unit name
Symbol Status
0 None N
36 AUD Australian Dollar I
124 CAD Canadian Dollar I
156 CNY Chinese Yuan Renminbi I
208 DKK Danish Crown I
356 INR India Rupee I
392 JPY Japanese Yen I
578 NOK Norwegian Crown I
643 RUB Russian Ruble I
710 ZAR South African Rand I
752 SEK Swedish Krona I
756 CHF Swiss Franc I
826 GBP British Pound I
840 USD US Dollar I
978 EUR Euro I

N = Normative

I = Informative

D = Deprecated since last edition

C.3 Using data element attributes to define the ReadingType name –


Construction formula with example ReadingType codes

The “ReadingType” may be automatically generated by judiciously populating each of the


attributes and presenting them in order side-by-side. It is recommended that attributes be as
explicit as possible to identify a data element, but on the other hand, not become so explicit
that it overspecifies the data element.

A ReadingType Name may be generated by presenting the numeric form of each attribute in
side-by-side fashion separated by dots.

<ReadingType.Name.name>::= <macroPeriod> “.” <aggregate> “.”<measuringPeriod>”,”


<accumulation> “.” <flowDirection> “.” <commodity> ”.” <measurementKind> “.”
<interharmonicNumerator> “.” <interharmonicDenominator> “.” <argumentNumerator> “.”
<argumentDenominator> “.” <tou> “.” <cpp> “.” <consumptionTier> “.” <phases> “.”
<multiplier> “.” <unit> “.” <currency>

These fields can be converted to a regionalized pronounceable name by using the regional
text form for each non-zero attribute, and presenting them in order, side-by-side, separated by
spaces and other symbols as appropriate. For most applications, this usually provides more
information than needs to be said (verbally) about the data. It is accepted practice in common
speech to suppress descriptive adjectives which are mutually understood by the context of the
– 164 – 61968-9  IEC:2013

communication. Table C.29 provides examples of such conversions into English. One will note
that in the EBNF formula below, that symbols such as "(", and ")" are introduced to improve
readability. Spaces around the unit of measure are also omitted to improve readability.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<Name.description>::= [<macroPeriod> “ ”] [<aggregate> “ ”] [<measuringPeriod> “ ”]


[<accumulation> “ ”] [<flowDirection> “ ”] [<commodity> ” ”] [<measurementKind> “ ”]
[<interharmonicNumerator> “ ”] [<interharmonicDenominator> “ ”] [<argumentNumerator> “ ”]
[<argumentDenominator> “ ”] [<tou> “ “] [<cpp> “ ”] [<consumptionTier> “ ”] [<phases> “ ”] “(”
[<multiplier>] [<unit>] [<currency>] “)”

While a good interface will eliminate ambiguity, and not publish “anonymous” data, a good
interface will also not go to the other extreme and overspecify the data it publishes. The
concept is similar to the practice of publishing an appropriate number of digits of resolution for
a numerical value. One system may know (for example) the phase on which a voltage was
measured and supply it as an attribute of the measurement. Another system might not know
the phase with good authority and simply publish the voltage measured at a given meter. The
ReadingTypeIDs used in a response may (therefore) differ slightly than the ReadingTypeIDs
used in a request. The ReadingType codes used by a data publisher should be appropriate for
the data supplied.

The examples listed below are by no means an exhaustive list of what can be constructed
given the enumeration values listed above. After searching the examples (below), and
searching the lists of enumerations (above), and a needed enumeration cannot be found,
custom made enumerations may be made. Some of the fields (such a “numerator”) are
naturally an integer field. If the needed enumeration is merely an integer, then the user should
supply the integer required. However, if the field is a list-type enumeration, some care should
be used. Rather than merely using the next available number on the list, custom user
enumerations should be created numbered 9,000 or above.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table C.29 – ReadingType Examples

Normative
ReadingType ID Code Description
Status
8.0.0.0.0.1.152.0.0.0.0.0.0.0.0.0.0.840 billingPeriod electricitySecondaryMetered billCarryover (USD) N
8.0.0.0.0.1.150.0.0.0.0.0.0.0.0.0.0.840 billingPeriod electricitySecondaryMetered billLastPeriod (USD) N
8.8.0.3.1.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum cumulative forward electricitySecondaryMetered demand (kW) N
61968-9  IEC:2013

8.8.53.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum fixedBlock15Min indicating forward electricitySecondaryMetered demand (kW) N


8.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.63.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand (kVAr) N
8.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand (kW) N
8.8.0.6.1.1.8.0.0.0.0.1.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touA (kW) N
8.8.0.6.1.1.8.0.0.0.0.2.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touB (kW) N
8.8.0.6.1.1.8.0.0.0.0.3.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touC (kW) N
8.8.0.6.1.1.8.0.0.0.0.4.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touD (kW) N
– 165 –

8.8.0.6.19.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum indicating reverse electricitySecondaryMetered demand (kW) N


billingPeriod maximum rollingBlock15MinIntvl5MinSubIntvl indicating forward electricitySecondaryMetered
8.8.71.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 N
demand (kW)
8.8.101.6.1.1.8.0.0.720.1.0.0.0.0.3.38.0 billingPeriod maximum specifiedFixedBlock indicating forward electricitySecondaryMetered demand n720 (kW) N
billingPeriod maximum specifiedRollingBlock indicating forward electricitySecondaryMetered demand n720/240
8.8.102.6.1.1.8.0.0.720.240.0.0.0.0.3.38.0 N
(kW)
8.0.0.9.1.1.12.0.0.0.0.1.0.0.0.3.72.0 billingPeriod summation forward electricitySecondaryMetered energy touA (kWh) N
8.0.0.9.1.1.12.0.0.0.0.2.0.0.0.3.72.0 billingPeriod summation forward electricitySecondaryMetered energy touB (kWh) N
8.0.0.9.1.1.12.0.0.0.0.3.0.0.0.3.72.0 billingPeriod summation forward electricitySecondaryMetered energy touC (kWh) N
0.0.0.1.0.1.122.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered demandReset (count) N
0.0.0.1.0.1.11.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered energization (count) N
0.0.0.1.0.1.131.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered loadInterrupt (count) N
0.0.0.1.0.1.141.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered relayActivation (count) N
0.0.0.1.0.1.142.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered relayCycle (count) N
0.0.0.1.1.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity forward electricitySecondaryMetered energy (kVArh) N
0.0.0.1.1.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity forward electricitySecondaryMetered energy (kWh) N
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.2.120.0 bulkQuantity forward naturalGas volume (hft³(compensated)) N
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.2.121.0 bulkQuantity forward naturalGas volume (hft³(uncompensated)) N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
ReadingType ID Code Description
Status
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.3.120.0 bulkQuantity forward naturalGas volume (kft³(compensated)) N
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.3.121.0 bulkQuantity forward naturalGas volume (kft³(uncompensated)) N
0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity net electricitySecondaryMetered energy (kVArh) N
0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity net electricitySecondaryMetered energy (kWh) N
0.0.0.1.19.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity reverse electricitySecondaryMetered energy (kVArh) N
0.0.0.1.19.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity reverse electricitySecondaryMetered energy (kWh) N
0.0.0.1.20.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity total electricitySecondaryMetered energy (kVArh) N
0.0.0.1.20.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity total electricitySecondaryMetered energy (kVArh) N
0.0.0.1.20.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity total electricitySecondaryMetered energy (kWh) N
0.0.0.0.0.3.97.0.0.0.1.0.0.0.0.0.114.0 communication deviceAddressType2 n0 (code) N
0.0.0.0.0.3.123.0.0.0.0.0.0.0.0.0.114.0 communication diagnostic (code) N
0.0.0.0.0.3.104.0.0.0.1.0.0.0.0.0.114.0 communication groupAddressType2 n0 (code) N
0.0.0.0.0.3.133.0.0.0.0.0.0.0.0.0.114.0 communication maintenance (code) N
0.0.0.0.0.3.114.0.0.0.1.0.0.0.0.0.114.0 communication oneWayAddress n0 (code) N
– 166 –

0.0.0.0.0.3.114.0.0.1.1.0.0.0.0.0.114.0 communication oneWayAddress n1 (code) N


11.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0 daily bulkQuantity net electricitySecondaryMetered energy (kWh) N
11.0.0.4.0.1.126.0.0.0.0.0.0.0.0.0.111.0 daily deltaData electricitySecondaryMetered ieee1366MomentaryInterruption (count) N
11.0.0.4.0.1.127.0.0.0.0.0.0.0.0.0.111.0 daily deltaData electricitySecondaryMetered ieee1366MomentaryInterruptionEvent (count) N
11.0.0.4.0.1.128.0.0.0.0.0.0.0.0.0.111.0 daily deltaData electricitySecondaryMetered ieee1366SustainedInterruption (count) N
11.0.0.4.0.1.128.0.0.0.0.0.0.0.0.0.27.0 daily deltaData electricitySecondaryMetered ieee1366SustainedInterruption (s) N
11.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 daily maximum indicating forward electricitySecondaryMetered demand (kW) N
11.0.0.9.4.1.12.0.0.0.0.1.0.0.0.3.72.0 daily summation net electricitySecondaryMetered energy touA (kWh) N
0.0.0.4.1.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData forward electricitySecondaryMetered energy (kVArh) N
0.0.0.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData forward electricitySecondaryMetered energy (kWh) N
0.0.0.4.4.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData net electricitySecondaryMetered energy (kVArh) N
0.0.0.4.4.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData net electricitySecondaryMetered energy (kWh) N
61968-9  IEC:2013

0.0.0.4.19.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData reverse electricitySecondaryMetered energy (kVArh) N


0.0.0.4.19.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData reverse electricitySecondaryMetered energy (kWh) N
0.0.0.4.20.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData total electricitySecondaryMetered energy (kVArh) N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
ReadingType ID Code Description
Status
0.0.0.4.20.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData total electricitySecondaryMetered energy (kWh) N
0.0.0.0.0.1.5.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered currentAngle (count) N
0.0.0.0.0.1.6.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered currentImbalance (count) N
0.0.0.0.0.1.11.0.0.0.0.0.0.0.0.0.109.0 electricitySecondaryMetered energization (status) N
0.0.0.0.0.1.13.0.0.0.0.0.0.0.0.0.109.0 electricitySecondaryMetered energizationLoadSide (status) N
61968-9  IEC:2013

0.0.0.0.0.1.43.0.0.0.0.0.0.0.0.0.109.0 electricitySecondaryMetered switchPosition (status) N


0.0.0.0.0.1.57.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered voltageImbalance (count) N
0.0.0.0.0.1.59.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered zeroFlowDuration (count) N
0.4.0.0.0.1.55.0.0.0.0.0.0.0.0.0.111.0 excess electricitySecondaryMetered voltageAngle (count) N
0.0.2.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0 fifteenMinute deltaData forward electricitySecondaryMetered energy (kWh) N
0.0.0.6.0.1.4.0.0.0.0.0.0.0.0.0.5.0 indicating electricitySecondaryMetered current (A) N
0.0.0.6.0.1.4.0.0.0.0.0.0.0.128.0.5.0 indicating electricitySecondaryMetered current phaseA (A) N
– 167 –

0.0.0.6.0.1.4.0.0.0.0.0.0.0.64.0.5.0 indicating electricitySecondaryMetered current phaseB (A) N


0.0.0.6.0.1.4.0.0.0.0.0.0.0.32.0.5.0 indicating electricitySecondaryMetered current phaseC (A) N
0.0.0.6.0.1.5.0.0.0.0.0.0.0.136.0.9.0 indicating electricitySecondaryMetered currentAngle phaseAtoAv (deg) N
0.0.0.6.0.1.5.0.0.0.0.0.0.0.72.0.9.0 indicating electricitySecondaryMetered currentAngle phaseBtoAv (deg) N
0.0.0.6.0.1.5.0.0.0.0.0.0.0.40.0.9.0 indicating electricitySecondaryMetered currentAngle phaseCtoAv (deg) N
0.0.0.6.0.1.15.0.0.0.0.0.0.0.0.0.33.0 indicating electricitySecondaryMetered frequency (Hz) N
0.0.0.6.0.1.38.0.0.0.0.0.0.0.0.0.65.0 indicating electricitySecondaryMetered powerFactor (cosθ) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.0.0.29.0 indicating electricitySecondaryMetered voltage (V) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.128.0.29.0 indicating electricitySecondaryMetered voltage phaseA (V) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.64.0.29.0 indicating electricitySecondaryMetered voltage phaseB (V) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.32.0.29.0 indicating electricitySecondaryMetered voltage phaseC (V) N
0.0.0.6.0.1.55.0.0.0.0.0.0.0.72.0.9.0 indicating electricitySecondaryMetered voltageAngle phaseBtoAv (deg) N
0.0.0.6.0.1.55.0.0.0.0.0.0.0.40.0.9.0 indicating electricitySecondaryMetered voltageAngle phaseCtoAv (deg) N
0.0.0.6.19.1.8.0.0.0.0.0.0.0.0.3.38.0 indicating reverse electricitySecondaryMetered demand (kW) N
0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.63.0 instantaneous forward electricitySecondaryMetered power (kVAr) N
0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.38.0 instantaneous forward electricitySecondaryMetered power (kW) N
0.0.0.12.20.1.37.0.0.0.0.0.0.0.0.3.38.0 instantaneous total electricitySecondaryMetered power (kW) N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Normative
ReadingType ID Code Description
Status
0.0.0.13.0.1.140.0.0.0.0.0.0.0.0.0.108.0 latchingQuantity electricitySecondaryMetered pushbutton (timeStamp) N
0.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 maximum indicating forward electricitySecondaryMetered demand (kW) N
0.9.0.6.0.1.38.0.0.0.0.0.0.0.0.0.65.0 minimum indicating electricitySecondaryMetered powerFactor (cosθ) N
0.0.0.0.19.1.4.0.0.0.0.0.0.0.0.0.111.0 reverse electricitySecondaryMetered current (count) N
22.0.0.1.1.1.12.0.0.0.0.0.0.0.0.3.73.0 seasonal bulkQuantity forward electricitySecondaryMetered energy (kVArh) N
22.8.0.6.1.1.8.0.0.0.0.1.0.0.0.3.38.0 seasonal maximum indicating forward electricitySecondaryMetered demand touA (kW) N
22.8.0.6.1.1.8.0.0.0.0.2.0.0.0.3.38.0 seasonal maximum indicating forward electricitySecondaryMetered demand touB (kW) N
22.8.0.6.1.1.8.0.0.0.0.3.0.0.0.3.38.0 seasonal maximum indicating forward electricitySecondaryMetered demand touC (kW) N
22.0.0.9.1.1.12.0.0.0.0.1.0.0.0.3.72.0 seasonal summation forward electricitySecondaryMetered energy touA (kWh) N
22.0.0.9.1.1.12.0.0.0.0.2.0.0.0.3.72.0 seasonal summation forward electricitySecondaryMetered energy touB (kWh) N
22.0.0.9.1.1.12.0.0.0.0.3.0.0.0.3.72.0 seasonal summation forward electricitySecondaryMetered energy touC (kWh) N
0.0.7.4.1.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData forward electricitySecondaryMetered energy (kVArh) N
0.0.7.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData forward electricitySecondaryMetered energy (kWh) N
0.0.7.4.4.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData net electricitySecondaryMetered energy (kVArh) N
– 168 –

0.0.7.4.4.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData net electricitySecondaryMetered energy (kWh) N


0.0.7.4.19.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData reverse electricitySecondaryMetered energy (kVArh) N
0.0.7.4.19.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData reverse electricitySecondaryMetered energy (kWh) N
0.0.7.4.20.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData total electricitySecondaryMetered energy (kVArh) N
0.0.7.4.20.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData total electricitySecondaryMetered energy (kWh) N
0.0.100.4.1.1.12.0.0.30.1.0.0.0.0.3.72.0 specifiedInterval deltaData forward electricitySecondaryMetered energy n30 (kWh) N
32.0.0.4.0.1.12.0.0.0.0.0.0.0.0.3.72.0 specifiedPeriod deltaData electricitySecondaryMetered energy (kWh) N
32.0.0.0.0.1.151.0.0.0.0.0.0.0.0.0.0.840 specifiedPeriod electricitySecondaryMetered billToDate (USD) N
0.0.0.9.20.1.12.0.0.0.0.1.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touA (kWh) N
0.0.0.9.20.1.12.0.0.0.0.2.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touB (kWh) N
0.0.0.9.20.1.12.0.0.0.0.3.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touC (kWh) N
0.0.0.9.20.1.12.0.0.0.0.4.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touD (kWh) N
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

N = Normative

I = Informative

D = Deprecated since last edition


61968-9  IEC:2013
– 169 –
– 170 – 61968-9  IEC:2013

Annex D
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Quality code enumerations

D.1 General

Quality codes may be returned with a Reading.value to indicate that there is something
remarkable about the data. This Annex D describes a North American profile of enumerations
for quality codes to be used in this context.

The presence of a quality code is optional. A missing element implies that no assertion
regarding the goodness of the data is being offered by the data producer. Some systems
(such as a MS) may have a policy of "no news is good news" and only add quality codes when
problems are found. This keeps the volume of data to a minimum. Other systems (such a
MDM) will add value to the data by validating it. At this point quality codes may be added to
the data to explicitly declare that the data is “valid” or has passed formal “validation” tests.

The quality code values defined by this Annex D are conveyed within a message using the
ReadingQuality.quality element.

D.2 Identification of the system offering commentary on the data

Concievably, any piece of equipment which touches the data could introduce error, or offer
remarks regarding the veracity of the data. For example, a meter might record interval data,
and offer this data to the data collection system, but in doing so also indicate that something
remarkable (such as a power outage or clock adjustment) occurred during some of the
intervals. A meter data collection system might obtain readings from the field, but perform a
sanity check on the values to find that some of them are unreasonable. A meter data
management system, armed with a knowledge of the account history and usage patterns
might scrutinize the data to find that certain values are suspect or possibly suggest that
tampering may have occurred. All of these systems need an opportunity to comment on the
data without (necessarily) changing it. When a system does change the data, this too can be
noted in the quality codes.

D.3 Construction

The North American profile defines the ReadingQuality.quality code to be built from a three
part field:

ReadingQuality.quality::= <System Identifier> ”.” <Categorization> “.” <Index>

This creates a name with 3 fields. The mappings to CIM ReadingQualityType are defined by
IEC 61968-11 as follows:

System Identifier = ReadingQualityType.systemId


Categorization = ReadingQualityType.category
Index = ReadingQualityType.subCategory

D.4 Quality code system identifier

The first of the three fields provides an identification of the system which has declared the
issue with the data. This is described in Table D.1. Other systems, outside of an IEC 61968-9
subsystem, may also identify problems with data.
61968-9  IEC:2013 – 171 –

Table D.1 – System identifier


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

System
Normative
Identifier Description
Status
Code

0 Not Applicable N
1 End Device N
Metering system (data collection)
2 N
network
3 Meter Data Management System N
4 Other system (not listed) N
Externally specified (see
5 I
accompany data)

I = Informative

N = Normative

D = Deprecated

D.5 Quality code categorization

The second of the three fields in the quality code identifies a category for the issue. These are
described individually in Table D.2.

Table D.2 – Example quality code categories

Normative
Category Description Comment
Status

0 Valid Data valid N

The equipment producing or


handling the data has identified a
1 Diagnostics related diagnostics related issue which N
may have some effect on this
value.
The equipment producing the
data has identified power quality
Power quality related issues at
2 related issues which may have N
the data collection point
some effect on the veracity of the
data.
A system identifies that the data
Tamper / Revenue Protection is questionable due to tamper or
3 N
related revenue-protection related
reasons.
A significant event or condition
has occurred (which is not
tamper related, power quality
4 Data collection related N
related, or diagnostics related)
which may effect the veracity of
the data.
Data at first blush appears to be
5 Failed reasonability testing N
invalid.
Data fails one or more validation
6 Failed validation testing N
rules.
Replaced or approved by a
7 Edited N
human.
Replaced by a machine computed
value based on analysis of
8 Estimated N
historical data using the same
type of measurement.
– 172 – 61968-9  IEC:2013

Normative
Category Description Comment
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

This category appears to be


9 Oscillatory covered by other categories in D
this standard.
The veracity of the data is
suspect for a reason other than
10 Questionable N
those described by categories 1
to 6.
Value has been calculated (using
logic or mathematical operations)
based upon one or more readings
from the meter or device to which
11 Derived the value is attributed and/or N
readings from meter(s) or
device(s) other than the meter or
device to which the value is
attributed.
12 Projected Forecasted value. N

I = Informative

N = Normative

D = Deprecated

D.6 Quality code index

Each category provides the context with which to understand a particular index.

Table D.3 elaborates on the “category 0” defined in Table D.2.

Table D.3 – Validity related codes

Normative
Category Index Description Definition
Status
No data quality problems have
been detected; however, the data
0 0 Data Valid has not been processed by a N
formal Validation, Editing, and
Estimation (VEE) process.
Reading has successfully passed
the validation portion of a formal
0 1 Validated Validation, Editing and Estimation N
(VEE) process and has not been
subsequently edited or estimated.

I = Informative

N = Normative

D = Deprecated

Table D.4 elaborates on the “category 1” defined in Table D.2..


61968-9  IEC:2013 – 173 –

Table D.4 – Diagnostics related codes

Normative
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Category Index Description Comments


Status
One or more diagnostics
1 0 DiagnosticsFlag have been generated from N
the originating equipment.
1 1 BatteryLow N
1 3 SensorFailure N
A timeout of the watchdog
timer or another failure of
1 4 WatchdogFlag the watchdog function has N
occurred in the originating
equipment.
A parity error has been
1 5 ParityError generated from the N
originating equipment.
A cyclic redundancy check
error has been generated
1 6 CRCError N
from the originating
equipment.
A checksum error has been
detected in the random
1 7 RAMChecksumError N
access memory of the
equipment.
A checksum error has been
1 8 ROMChecksumError detected in the read only N
memory of the equipment.
A failure or abnormality has
1 9 ClockError been detected with the clock N
in the equipment.

I = Informative

N = Normative

D = Deprecated

NOTE Diagnostic related codes may produce corresponding EndDeviceEvents to be generated.

Table D.5 elaborates on the “category 2” defined in Table D.2.

Table D.5 – Power quality related codes

Normative
Category Index Description Comments
Status
Look for related
2 0 PowerQualityFlag N
MeterEvent(s)
Power outage threshold
2 1 ExcessiveOutageCount N
count exceeded
Power quality threshould
2 2 PqCounter N
count exceeded
Service Disconnect
2 3 ServiceDisconnectSwitching operation during data N
collection interval
– 174 – 61968-9  IEC:2013

Normative
Category Index Description Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Power fail occurred during


or at the start of this
interval.
ANSI C12.19.
2 32 PowerFail N
If power is out for the
entire interval, the data
value presented should be
zero.

I = Informative

N = Normative

D = Deprecated

Table D.6 elaborates on the “category 3” defined in Table D.2.

Table D.6 – Tamper / revenue protection related codes

Category Index Description Comments Normative Status


3 0 RevenueProtection Generic N
The meter reports that a
3 1 CoverOpened sealed cover has been N
opened.
Value originates from a
meter which (in theory)
3 2 LogicalDisconnect N
should have no flow or
very minimal flow.
3 3 RevenueProtectionSuspect N
Reverse flow of the
measured commodity has
been detected. This may
indicate tampering at sites
3 4 ReverseRotation N
which have not been
identified as being
capable of customer-side
generation.
The meter shows very
3 5 StaticDataFlag little (if any) historical N
usage.

I = Informative

N = Normative

D = Deprecated

Table D.7 elaborates on the “category 4” defined in Table D.2.

Table D.7 – Data collection related codes

Normative
Category Index Description Comments
Status
4 0 AlarmFlag Generic alarm N
A numeric overflow condition for
4 1 OverflowConditionDetected a reading value or pulse counter N
was detected.
Partial (short) interval due to
4 2 PartialInterval clock change, power outage, or N
some similar event.
61968-9  IEC:2013 – 175 –

Normative
Category Index Description Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Long interval recorded due to a


4 3 LongInterval clock change or some similar N
event.
Skipped interval by the meter
4 4 SkippedInterval due to a clock change or similar N
event.
Data value was obtained while
4 5 TestData N
the equipment was in test mode.
A configuration change has
occurred that may affect the
4 6 ConfigurationChanged N
reading value or its
interpretation.
4 7 NotRecording Load profile recording stopped N
A reset has occurred that may
4 8 ResetOccurred affect the reading value or its N
interpretation.
A change in the clock time has
4 9 ClockChanged N
occurred.
Data value was obtained at a
4 10 LoadControlOccurred time when load control was in N
effect.
Daylight saving time in effect
4 16 DstInEffect N
during or at start of this interval
Clock set forward during or at
4 64 ClockSetForward the start of this interval. The N
interval may be short.
Clock set backward during or at
4 128 ClockSetBackward the start of this interval. The N
interval may be long.
A failure occurred that
prevented the reading from
4 129 FailedProbeAttempt N
being obtained through a
manual probe.
The reading value was provided
4 130 CustomerRead N
by a customer.
The reading value was obtained
4 131 ManualRead by a utility employee performing N
a manual read.
Data has been adversely
affected by a change in Daylight
Saving Time. Timestamps
and/or data values may be
incorrect.
NOTE Compared to the ANSI
4 259 DstChangeOccurred N
C12.19 approach in which the
DST flag is set for the entire
Summer, this flag is only set for
the affected data when the DST
change occurs in the Spring and
Fall.

I = Informative

N = Normative

D = Deprecated

Table D.8 elaborates on the “category 5” defined in Table D.2.


– 176 – 61968-9  IEC:2013

Table D.8 – Failed reasonability testing related codes

Category Index Description Comments Normative Status


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Presented data was


5 256 DataOutsideExpectedRange identified as "invalid" by N
the originating system.
Data was identified as
"invalid" by the originating
5 257 ErrorCode system and replaced with N
a special coded value to
indicate an error.
Data should be
5 258 Suspect scrutinized and N
considered suspect
NOTE 1 The “value”
element should be empty
when the quality code
indicates that it is
(obviously) missing.
5 259 KnownMissingRead N
NOTE 2 If a reason is
known, this can be
supplied in the
MeterReadings.Reason
element.

I = Informative

N = Normative

D = Deprecated

Table D.9 elaborates on the “category 6” defined in Table D.2.

Table D.9 – Failed validation testing related codes

Category Index Enumeration Comments Normative Status


The reading failed one or
more unspecified validation
Failed validation – checks. This is a generic
6 0 N
Generic code that can be used if a
more specific code is not
available in this table.
Failed validation – The reading failed validation
6 1 ZeroUsageOn due to zero usage on an N
ActiveMeter active meter.
The reading failed validation
Failed validation –
6 2 due to non-zero usage on an N
UsageOn InactiveMeter
inactive meter.
The reading failed validation
Failed validation – because it represents usage
6 3 N
UsageAbove Maximum greater than an allowed
absolute maximum.
The reading failed validation
Failed validation – because it represents usage
6 4 N
UsageBelow Minimum less than a required absolute
minimum.
The reading failed validation
Failed validation –
because it represents usage
6 5 UsageAbove N
greater than an allowed
MaximumPct
maximum percentage.
Failed validation – The reading failed validation
6 6 UsageBelow because it represents usage N
MinimumPct less than a required minimum
61968-9  IEC:2013 – 177 –

Category Index Enumeration Comments Normative Status


percentage.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

The reading failed validation


because the sum of interval
Failed Validation – values failed a comparison
6 9 N
TOU SumCheck Failure with the corresponding
difference in register
readings.
The reading failed one or
more defined validation
checks.
“y” is to be replaced by a
positive integer indicating
which validation rule was
failed.
It is recommended that
values for y begin at 1001 to
Failed Validation Rule allow for the build-out over
6 y I
Y time of the list of normative
enumerations in the IEC
standard up to 1000.
There is no limit to how large
a number can be used for “y”;
however; the parties
exchanging this code shall
have a common
understanding of what each
validation rule #y means.

I = Informative

N = Normative

D = Deprecated

Individual deployments will subscribe to particular sets of formal validation rules. While there
is no one worldwide standard regarding validation rules, this standard provides a placeholder
where the first rule for a given deployment can be defined as “rule #1,” the second rule “rule
#2,” and so on as necessary until all of the rules are numbered. Each system then, operating
at a given utility under a given set of rules, will all be subject to the same set of rules which
have been formally listed and numbered.

Table D.10 describes the “category 7” defined in Table D.2.

Table D.10 – Edit related codes

Normative
Category Index Description Comments
Status
The reading value was edited
by a person using an
unspecified manual
Manually Edited –
7 0 estimation method. This is a N
Generic
generic code that can be
used if a more specific code
is not available in this table.
A reading value was added
7 1 Manually Added N
by a person.
A value was proposed by the
system or failed some level
7 3 Manually Rejected of quality checking. The N
value was reviewed and
rejected by a human user
The reading value was edited
Manually Edited –
7 Y by a person using a defined I
Method Y
manual estimation method.
– 178 – 61968-9  IEC:2013

Normative
Category Index Description Comments
Status
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

“y” is to be replaced by a
positive integer indicating
which manual estimation
method was used.
It is recommended that
values for y begin at 1001 to
allow for the build-out over
time of the list of normative
enumerations in the IEC
standard up to 1 000.
There is no limit to how large
a number can be used for “y”;
however; the parties
exchanging this code shall
have a common
understanding of what each
manual editing method #y
means.

I = Informative

N = Normative

D = Deprecated

The concept of “edited” means that a human was involved in creating the value. It may be
hand-keyed into the system. It may be suggested by the system using one of many
approaches, but ultimately approved by a human. Values that are computer generated and
never approved by a human belong to the “estimated” category. Values that are originally
from a meter, identified as suspect, yet nonetheless accepted for use by a human fall into the
“questionable” category.

Different systems may find different ways to assist the user in creating a new value. The
numbering scheme allows the various ways to be listed and formally identified for a given
deployment.

Table D.11 describes describes the “category 8” defined in Table D.2.

Table D.11 – Estimation related codes

Normative
Category Index Enumeration Comments
Status
The reading value was
machine-estimated by a
computing algorithm using an
unspecified estimation
8 0 Estimated – Generic N
method. This is a generic
code that can be used if a
more specific code is not
available in this table.
The reading value was
machine-estimated by a
computing algorithm using a
defined estimation method.

Machine Estimated – “y” is to be replaced by a


8 Y I
Method Y positive integer indicating
which estimation method was
used.
It is recommended that
values for y begin at 1001 to
allow for the build-out over
time of the list of normative
61968-9  IEC:2013 – 179 –

Normative
Category Index Enumeration Comments
Status
enumerations in the IEC
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

standard up to 1000.
There is no limit to how large
a number can be used for “y”;
however; the parties
exchanging this code shall
have a common
understanding of what each
estimation method #y means.

I = Informative

N = Normative

D = Deprecated

There are a number of ways in which estimates may be generated. For example, an estimate
might be based on a combination of historical usage, trend analysis, and weather patterns.
Another approach would be to create a value for one meter by leveraging a measurement of
equivalent information from a different different meter. (For example there may be multiple
feeder voltage measurement sources available. When the preferred source fails, a different
source could be used with an equivalent outcome.) Some of the techniques used may be
proprietary. Other estimation techniques may be a matter of public record and may be legally
required by certain regulators in certain locations. The numbering scheme “approach #1,”
“approach #2,” etc. provides a placeholder in which the approaches used may be formally
listed at a given deployment and identified as a specific technique.

Table D.12 describes the “category 10” defined in Table D.2.

Table D.12 – Questionable related codes

Category Index Description Comments Normative Status


Quality is unknown or cannot
be determined.
NOTE 1 This is similar to the
case in which no quality codes
are supplied at all, but in this
case other codes may be
present which cast doubt on
the veracity of the data, or a
situation may have arisen
which prevents any kind of
analysis from being performed
on the data or the equipment
which supplied the data.
10 0 Indeterminate N
NOTE 2 When used in
response to a request for
Power (Energization) Status
or Switch Position, an
“Indeterminate” quality means
that the energization state or
switch position is unknown or
cannot be determined. When
used in response to a request
for other reading types,
“Indeterminate” means that
the quality of the value
supplied is explicitly unknown.
Indicates that a value failed
some level of quality checking,
10 1 Manually accepted N
but the failure was overridden
by a human user.

I = Informative
– 180 – 61968-9  IEC:2013

Category Index Description Comments Normative Status

N = Normative
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

D = Deprecated

Table D.13 describes the “category 11” defined in Table D.2..

Table D.13 – Derived related codes

Category Index Enumeration Comments Normative Status


“Derived” indicates that the
value has been calculated
(using logic or mathematical
operations) based upon one or
more readings from the meter
or device to which the value is
attributed and/or readings from
meter(s) or device(s) other than
the meter or device to which
the value is attributed.
“Deterministic” (as
Derived -
11 0 differentiated from “Inferred” – N
Deterministic
see next entry) is used when a
significant degree of
uncertainty in the resulting
value does not exist.
For example, a quality of
“x.11.0” or “Derived -
Deterministic” can be used
when a value for a virtual meter
is computed as the sum of the
values from two or more other
meters.
“Derived” indicates that the
value has been calculated
(using logic or mathematical
operations) based upon one or
more readings from the meter
or device to which the value is
attributed and/or readings from
meter(s) or device(s) other than
the meter or device to which
the value is attributed.
“Inferred” (as differentiated
from “Deterministic” – see
previous entry) is used when a
significant degree of
uncertainty in the resulting
value may exist.
11 1 Derived - Inferred N
When used in response to
Power (Energization) Status
Checks, “x.11.1” or “Derived –
Inferred” is synonymous with
“Inferred”.
For example, a UsagePoint may
be determined to have a value
of “De-energized” and a
Reading Quality of “Derived-
Inferred” if it is being inferred
as de-energized because one
or more other UsagePoints on
the same distribution
transformer are confirmed to be
“De-Energized”. In this case,
there is a more than a
negligible probability that the
61968-9  IEC:2013 – 181 –

Category Index Enumeration Comments Normative Status


inference is incorrect.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

I = Informative

N = Normative

D = Deprecated

Table D.14 describes the “category 12” defined in Table D.2.

Table D.14 – Projected related codes

Normative
Category Index Enumeration Comments
Status
The reading value was
projected (forecast) by a
computing algorithm using an
unspecified projection
12 0 Projected – Generic N
(forecast) method. This is a
generic code that can be
used if a more specific code
is not available in this table.
The reading value was
projected (forecast) by a
computing algorithm using a
defined projection (forecast)
method.
“y” is to be replaced by a
positive integer indicating
which projection (forecast)
method was used.
It is recommended that
12 Y Projected – Method Y values for y begin at 1001 to I
allow for the build-out over
time of the list of normative
enumerations in the IEC
standard up to 1000.
There is no limit to how large
a number can be used for “y”;
however; the parties
exchanging this code shall
have a common
understanding of what each
projection method #y means.

I = Informative

N = Normative

D = Deprecated

Much like in the way “estimated” creates a computer generated value based on a historical
view of the data for an event that has occurred in the past, “projected” creates a computer
generated value which is forecast into the future. The numbering scheme “approach #1,”
“approach #2,” etc. provides a placeholder in which the approaches used may be formally
listed at a given deployment and identified as a specific technique.

D.7 Example quality codes

Some of the codes described in Table D.15 have been found to be in use in systems since the
publication of IEC 61968-9:2009.
– 182 – 61968-9  IEC:2013

Table D.15 – Example Quality Codes

Origin
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Quality Category (From Normative


(From Table Index (From Tables D.3 to D.15)
Code Table D.2) Status
D.1)
Not
Not provided Not provided AssumedValid none N
provided
End
1.0.0 1 0 Validity DataValid 0 N
Device
End
1.1.4 1 1 Diag WatchdogFlag 4 N
Device
End
1.4.1 1 4 Data Collection OverflowConditionDetected 1 N
Device
End
1.4.16 1 4 Data Collection DstInEffect 16 N
Device
End
1.4.2 1 4 Data Collection Partial (short) Interval 2 N
Device
End
1.4.3 1 4 Data Collection LongInterval 3 N
Device
End
1.4.4 1 4 Data Collection SkippedInterval 4 N
Device
End
1.4.5 1 4 Data Collection TestData 5 N
Device
End
1.5.257 1 5 Reasonablity ErrorCode 257 N
Device
Ms
2.0.0 2 0 Validity DataValid 0 N
Network
Ms
2.3.4 2 3 Tamper ReverseRotation 4 N
Network
Ms
2.3.5 2 3 Tamper StaticDataFlag 5 N
Network
Ms
2.4.259 2 4 Data Collection DstChangeOccurred 259 N
Network
Ms
2.5.256 2 5 Reasonablity DataOutsideExpectedRange 256 N
Network
Ms
2.5.257 2 5 Reasonablity ErrorCode 257 N
Network
3.0.0 MDM 3 0 Validity DataValid 0 N
3.10.0 MDM 3 10 Questionable Indeterminate 0 N
3.10.1 MDM 3 7 Edited Manually accepted 1 N
3.11.0 MDM 3 11 Derived Derived – generic 0 N
3.11.1 MDM 3 11 Derived Derived – inferred 1 N
3.3.3 MDM 3 3 Tamper RevenueProtectionSuspect 3 N
3.3.5 MDM 3 3 Tamper StaticDataFlag 5 N
3.5.259 MDM 3 5 Reasonablity Known missing read 259 N
3.6.0 MDM 3 6 Validation Failed validation – Generic 0 N
3.7.0 MDM 3 7 Edited Manually edited – Generic 0 N
3.8.0 MDM 3 8 Estimated Estimated – Generic 0 N
61968-9  IEC:2013 – 183 –

Annex E
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceEventType enumerations

E.1 General

Metering systems not only collect readings from meters, but also report events. This annex
describes recommended codes to be used for properly idenifying IEC 61968 events.

Codes for EndDeviceEventTypes are categorized in a manner that divides the enumerated
code into 4 parts:

EndDeviceEventType:=
<EndDeviceType>.<EndDeviceDomain>.<EndDeviceSubdomain>.<EndDeviceEventOrAction>

where
<EndDeviceType> = a numeric value from the EndDeviceType enumeration (see
EndDeviceType section)
<EndDeviceDomain> = a numeric value from the EndDeviceDomain enumeration (see
EndDeviceDomain section)
<EndDeviceSubdomain> = a numeric value from the EndDeviceSubdomain enumeration
(see EndDeviceSubdomain section)
<EndDeviceEventOrAction> = a numeric value from the EndDeviceEventOrAction
enumeration (see EndDeviceEventOrAction section)

E.2 Alarm conditions

E.2.1 General

While the EndDeviceEventType defines the event that has occurred, there is also a need to
specify the severity of an event (Alarm, Advisory, Normal, etc.). These values should be set in
the EndDeviceEvent.severity field. This allows each system implementing CIM events to
classify the severity of its events specific to its intentions, rather than being forced to classify
it according to something rigidly defined by IEC 61968-9.

E.2.2 Clearing alarm conditions and communicating state/condition changes

There are scenarios where the state change for a particular setting shall be communicated to
an external system. In the small number of cases that we have uncovered, we have simply
added a concise EndDeviceEventOrAction to describe it. The following events support this
method of communication.

EndDeviceEvent
Event or Control Description
Category (using enum mnemonics)
*.Power.NeutralCurrent.
Diagnostic 8 Condition High Neutral Current Cleared
MaxLimitReachedCleared
Leading kvarh cleared
*.Power.PowerFactor.OutofRangeCleared
Caution 040000 Leading kvarh Condition Cleared
High Distortion Cleared
*.Power.PowerQuality.HighDistortionCleared
Diagnostic 5 High Distortion Cleared
Voltage Imbalance Cleared
*.Power.Voltage.ImbalanceCleared
Diagnostic 2 Voltage Imbalance Cleared
Phase alert cleared, Condition Phase Angle Alert Cleared *.Power.PhaseAngle.OutofRangeCleared
Cross phase cleared
*.Power.Phase.CrossPhaseCleared
Diagnostic 1 Condition Polarity, Cross Phase, Rv Energy Flow
– 184 – 61968-9  IEC:2013

EndDeviceEvent
Event or Control Description
Category (using enum mnemonics)
Cleared
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Inactive phase cleared


*.Power.Phase.InactiveCleared
Diagnostic 3 Inactive Phase Current Condition Cleared
Voltage Swell Started (Phase A) *.Power.PhaseAVoltage.SwellStarted
Voltage Swell Started (Phase B) *.Power.PhaseBVoltage.SwellStarted
Voltage Swell Started (Phase C) *.Power.PhaseCVoltage.SwellStarted
Voltage swell cleared
*.Power. Voltage.SwellStopped
Caution 004000 Demand Overload Condition Cleared
Voltage Swell Stopped (Phase A);
*.Power.PhaseAVoltage.SwellStopped
Diagnostic 7 Condition Over Voltage, Phase A Cleared

Voltage Swell Stopped (Phase B) *.Power.PhaseBVoltage.SwellStopped

Voltage Swell Stopped (Phase C) *.Power.PhaseCVoltage.SwellStopped


Voltage Sag Started (Phase A) *.Power.PhaseAVoltage.SagStarted
Voltage Sag Started (Phase B) *.Power.PhaseBVoltage.SagStarted
Voltage Sag Started (Phase C) *.Power.PhaseCVoltage.SagStarted
Voltage sag cleared
*.Power.Voltage.SagStopped
Caution 000400 Under Voltage Condition Cleared
Voltage Sag Stopped (Phase A);Diagnostic 6 Condition
*.Power.PhaseAVoltage.SagStopped
UnderVoltage, Phase A Cleared

Voltage Sag Stopped (Phase B) *.Power.PhaseBVoltage.SagStopped

Voltage Sag Stopped (Phase C) *.Power.PhaseCVoltage.SagStopped

E.3 Event data

Certain events require or contain more details than just a description and a category. For
example, specification of a particular channel number, alarm number, relay number, port
number, formula number, version number, etc. These should be set on the
EndDeviceEvent.EndDeviceEventDetails name/value pair element.

However, this construct should not be overused or misused. The intention for this construct is
only to capture some ancilliary data related to the event. It should not be used in place of
sending a full set of EndDeviceEvent information, for example (see Figure E.1).

Figure E.1 – Event data

Some examples of its use:

A [PAN Pairing Completed] event may also provide the following data.

<m:EndDeviceEvent>
:
<m:EndDeviceEventDetails>
<m:name>InstallDate</m:dateTime>
<m:value>2001-12-17</m:value>
</m:EndDeviceEventDetails>
61968-9  IEC:2013 – 185 –

<m:EndDeviceEventDetails>
<m:name>ShortId</m:dateTime>
<m:value>1002</m:value>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</m:EndDeviceEventDetails>
:
</m:EndDeviceEvent>

A [Firmware Downloaded] event may also provide the following data.

<m:EndDeviceEvent>
:
<m:EndDeviceEventDetails>
<m:name>FirmwareVersion</m:dateTime>
<m:value>1.2345</m:value>
</m: EndDeviceEventDetails>
:
</m:EndDeviceEvent>

A [Voltage Exception] event may also provide the following data.

<m:EndDeviceEvent>
:
<m:EndDeviceEventDetails>
<m:name>VoltageThreshold</m:dateTime>
<m:value>3</m:value>
</m:EndDeviceEventDetails>
:
</m:EndDeviceEvent>

E.4 The 4-Part ID: EndDeviceEventType

Clauses E.5 to E.8 describe each part of the EndDeviceEventType enumeration:

• <EndDeviceType>
• <EndDeviceDomain>
• <EndDeviceSubdomain>
• <EndDeviceEventOrAction>

E.5 EndDeviceType

At the highest level, it is helpful to identify the type of device from which the event was
created. Each of these should represent a physical device, although a value of zero (0) can
be used in special cases. EndDeviceType codes are enumerated and described in Table E.1.

Table E.1 – EndDeviceType codes

EndDeviceType Enumeration
mnemonic Value Description
n/a 0 Not applicable. Use when a device type is not known.
A device that acts as a central point of communication between HES
Collector 10
and devices located on premises.
ComDevice 26 A communication device
DAPDevice 1 A data aggregation point device
DERDevice 2 A demand response device
DSPDevice 6 A digital signal processing device
ElectricMeter 3 A device located on premises to measure electricity usage.
ElectricVehicle 58 (or Plug-in Electric Vehicle, PEV) a vehicle that can be plugged into the
– 186 – 61968-9  IEC:2013

EndDeviceType Enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

grid.

An energy router, analogous to the familiar data and communications


router, automatically detects demand for power and delivers processed
EnergyRouter 23
electricity in the required form (AC or DC) at the correct voltage and
frequency on an electrical power system.
Feeders carry three-phase power, and tend to follow the major streets
Feeder 13
near the substation.
GasMeter 4 A device located on premises to measure gas usage.
Gateway 5 A gateway device.
Typically a spinning electrical generator. Something has to spin the
Generator 14 generator -- it might be a water wheel in a hydroelectric dam, a large
diesel engine or a gas turbine.
The In-Premises (In-Home) Display (IPD/IHD) allows utility customers
InPremisesDisplay(IPD/IHD) 15 to track their energy usage in chart or graph form based upon kwH
used.
A device used to implement “deferrable” services – commonly referred
LoadControlDevice 16
to as “off-peak”.
A router distributes Digital computer information that is contained within
NetworkRouter 11
a data packet on a network.
A “premises area network” device that is not specifically described in
PANDevice 12
further detail.
A PAN gateway connects an external communications network to
PANGateway 7
energy management devices within the premises.
A “premises area network” device whose function is to measure (e.g.
PANMeter 17
electricity usage).
A device that enables the customer to make advance payment before
PrepaymentTerminal 18
energy can be used.
A thermostat device whose settings can be controlled via an API (ie.
ProgCtlThermostat(PCT) 19
without human intervention).
Wireless range-extenders or wireless repeaters can extend the range of
RangeExtender 20
an existing wireless network.
A voltage regulator is an electrical regulator designed to automatically
Regulator 21
maintain a constant voltage level.
An electrical substation is a subsidiary station of an electricity
Substation 22 generation, transmission and distribution system where voltage is
transformed from high to low or the reverse using transformers.
A device that converts a generator's voltage (which is at the thousands
Transformer 8 of volts level) up to extremely high voltages for long-distance
transmission on the transmission grid.
WasteWaterMeter 25 A device that measures waste water usage.
WaterMeter 24 A device that measures water usage.

E.6 EndDeviceDomain

After the type of device is known, the event should be classified by an EndDeviceDomain
code. This code provides an indication as to the high-level nature of the event. Careful
consideration shall given to the EndDeviceDomain in which an event is classified By properly
classifying events by a small set of EndDeviceDomain codes, a system can more easily run
reports based on the types of events that have occurred or been received. EndDeviceDomain
codes are enumerated and described in Table E.2.
61968-9  IEC:2013 – 187 –

Table E.2 – EndDeviceDomain Codes


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceDomain Enumeration
mnemonic Value Description
Not applicable. Use when a domain is not needed. This should rarely
n/a 0
be used.
A device (for example, a relay) that can be associated with an end
AssociatedDevice 39
device.
Battery 2 Any events or controls related to a device battery.
Events or controls related to cost of energy (Including Pricing, Tariff,
Billing 20
TOU, etc.).
Cartridge 3 Events or controls related to cartridge fuses.
Clock 36 Events or controls related to a device internal clock.
Events or controls related to purely communication isssues. Consider
Communication 1
other domains before using this one.
Configuration 7 Events or controls related to device configuration.
Events or controls related to demand (ie. kW) and demand settings (as
Demand 8
opposed to consumption (ie. kWh).
Firmware 11 Events or controls related to device firmware.
GasSupply 4 Events or controls related to the supply of natural gas or propane.
Installation 6 Events or controls related to device installation.
KYZPulseCounter 38 Pulse counting function inside a meter or other end device.
Events or controls related to the automatic restriction or control of a
LoadControl 15
customer’s energy consumption.
Events or controls related to the energy consumption (ie. “load”) over
LoadProfile 16
time on a device.
Logs 17 Events or controls related to device internal logs.
Memory 18 Events or controls related to device memory.
Events or controls related to any type of measurement captured by a
Metrology 21
device.
Events or controls related to device security when the device is
MobileSecurity 14
accessed via a mobile tool or device.
Modem 19 Events or controls related to a device’s modem.
Events or controls related to firmware on a module contained by a
ModuleFirmware 9
device.
Events or controls generally related to a device’s status on the network.
Network 23 Also used for general network events, such as commissioning of a PAN
Area network.
Events or controls related to linking devices together (e.g. PANDevice
Pairing 10
to Meter, ComDevice to Meter, etc.).
Power 26 Events or controls related to device energization status.
Pressure 29 Events or controls related to device pressure thresholds.
Events or controls related to device remote connect/disconnect
RCDSwitch 31
activities.
Recoder 41 A device for encoding
Events or controls related to device security (including SecurityKey,
Security 12
HMAC, Parity, Rotation, other TamperDetection, etc.).
Temperature 35 Events or controls related to device
VideoDisplay 13 Events or controls related to device CRT/display.
A quantity of 3-dimensional space enclosed by a boundary; the space
Volume 40
occupied by a liquid or gas.
Watchdog 37 A hardware or software function triggered by a timer expiring.
WaterSupply 5 Events or controls related to the supply of water.
– 188 – 61968-9  IEC:2013

E.7 EndDeviceSubDomain
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceDomain can be subcategorized by EndDeviceSubdomain codes.


EndDeviceSubdomain codes are enumerated and described in Table E.3.

Table E.3 – EndDeviceSubdomain codes

EndDeviceSubdomain enumeration
mnemonic Value Description
Not applicable. Use when a subdomain is not needed.
n/a 0
This should rarely be used
Related to physical security (ie. Accessability) or
Access 1
electronic permission to read/write digital media
Activation 283 Initiation of a function
AlarmTable 285 A table in a device for the tracking of alarms
ADConverter 142 Related to analog-to-digital conversion
Related to a set of events (typically used in a Load
AllEvents 148
Control Cancel All Events scenario)
The magnitude of the complex power measured in volt-
ApparentPower 290
amps
Related to designation or allotment; Typically related to
Allocation 2
memory (RAM/ROM)
Related to the linking/pairing of one device/object to
Association 74
another device/object
Related to Always Up To Date processes; watchdog or
AUTDProcess 3
keep-alive processes
AutoRegistration 5 Related to automatic registration process
AutoTime 7 Related to automatic setting of time
BTU 13 Related to British Thermal Units
Buffer 14 Related to temporary data storage
Cable 15 Related to a physical cable
Calculation 16 Related to mathematical computation
Related to a set of gradations that show positions or
Calibration 18
values
Related to a document testifying to the truth of
Certificate 21
something; typically a security certificate
Charge 22 Related to electrical charge; Related to billing charge
A fixed-size datum computed from an arbitrary
Checksum 284 block of digital data for the purpose of detecting
accidental errors
Concentration 39 Related to the density or composition of something
Constants 23 Related to statically defined values
ControlPoint 26 Related to load control settings
Cover 29 Related to something that provides shelter; a covering
CRC 30 Related to cyclical redundancy check
Credit 8 Related to the right-hand side of an account; billing
Current 6 Related to electrical power measured in amperes
Data 31 Related to factual information
DataLog 33 Related to a record (ie. Log) of factual information
Date 34 Related to calendar time
Day 35 Related to the day portion of calendar time
61968-9  IEC:2013 – 189 –

EndDeviceSubdomain enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Related to the practice of setting the clock forward one


DaylightSavingsTime 56
hour in the spring.
DayLimit 299 A limit established for a daily period
Decryption 36 Related to making encrypted data readable
Display 143 Related to a CRT, LED, or other form of video device
Related to a moveable barrier used to cover an opening;
Door 128
as in a door to a meter or collector
EmergencySupplyCapacityLimit 138 Related to emergency supply capacity limits
Related to the thing that converts information from one
Encoder 40
format to another
EncoderRegister 41 Related to the encoder register (ie. On a meter)
EPROM 42 Related to erasable programmable read-only memory
Related to something that has happened; other, more
Event 43 specific subdomains should be used before using this
one
EventLog 44 Related to a record (ie. Log) of event data
EWM 45 Related to an external wireless module
Feature 46 Related to a non-specific characteristic
FirmwareReset 47 Related to reverting of firmware to original state
Related to the movement of a substance (electricity, gas,
Flow 48
water, etc.)
FPV 49 Related to a form of super-compressibility
Frames 50 Related to fixed-sized blocks; as in memory
Frequency 4 Related to the number of cycles per unit of time
Related to gas chromatograph analyzer which is use to
GCAnalyzer 51 measure the component mixture of the natural gas
delivers to a site
HeadEndSystem 52 Related to the metering/AMI system
HistoryLog 53 Related to a record (ie. Log) of historical data
Related to hash-based message authentication code; a
HMAC 54
specific method for calculated a MAC
Holiday 97 Related to days set aside having special significance
Identity 10 Related to a unique identifier
Initialisation 298 Start-up function
Input 55 Related to data entered into the system
InstallDate 57 Related to the prepared for use date
IntelligentRegister 58 Related to a specific register on a device
Related to interval energy data; the time between to
Interval 59
events
IO 60 Related to general input/output
IPAddress 127 Related to an IP Address (Internet Protocol Address)
Related to a unique identification of a device on a
LANAddress 61
network of devices
LastRead 62 Related to the final reading from a meter
Related to an internal list [contained in memory or on
List 63
firmware]
ListPointers 64 Related to a specific set of values kept by a meter
Login 65 Related to the process by which access is gained to a
– 190 – 61968-9  IEC:2013

EndDeviceSubdomain enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

device, computer, or system

Related to a circuit that connects CPU with other


LowSpeedBus 145
devices; low-speed transmission
MagneticSwitch 66 Related to any type of magnetic switch
Related to a specific mode of operation into which a
MaintMode 11
device can be set
Measurement 67 Relating to the magnitude of a quantity
MeasurementType 286 A code defining the kind of data under measurement
Mesh 68 Typically related to the type of meter network
Related to a circuit that connects a devices or module to
MeterBus 147
a meter
Related to a specific mode of operation into which a
MeteringMode 12
device can be set
Mobile 69 Related to devices that are not confined to one place
MOL% 70 Related to percentage of moles
Related to a unique identification of a device on a
NetworkId 71
network of devices
NeutralCurrent 137 Related to the essential part of electroweak unification
NVRAM 72 Related to non-volatile random access memory
OptionBoard 146 Related to a type of module in a meter
Parameter 75 Related to a variable passed to a function
ParentDevice 76 Related to a device’s owner
Typically related to an odd/even or on/off state; a
Parity 77
symmetry property
Password 24 Related to a secret word used for authentication
Typically related to a means of distributing alternating
Phase 25 current; When the specific phase is irrelevant, this should
be used as the EndDeviceSubdomain
Related to the angular component of the polar
PhaseAngle 130
coordinates
PhaseA 126 Related to the A phase of a multi-phase circuit
PhaseAApparentPower 291 The apparent power on phase A of a multi-phase circuit
Related to the current of the first phase of 3-phase
PhaseACurrent 287
power
PhaseAReactivePower 295 The reactive power on phase A of a multi-phase circuit
Related to the voltage of the first phase of 3-phase
PhaseAVoltage 131
power
Related to the voltage potential of the first phase of 3-
PhaseAVoltagePotential 126
phase power
PhaseB 134 Related to the B phase of a multi-phase circuit
PhaseBApparentPower 292 The apparent power on phase B of a multi-phase circuit
Related to the current of the second phase of 3-phase
PhaseBCurrent 288
power
PhaseBReactivePower 296 The reactive power on phase B of a multi-phase circuit
Related to the voltage of the second phase of 3-phase
PhaseBVoltage 132
power
Related to the voltage potential of the second phase of
PhaseBVoltagePotential 134
3-phase power
PhaseC 135 Related to the C phase of a multi-phase circuit
61968-9  IEC:2013 – 191 –

EndDeviceSubdomain enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

PhaseCApparentPower 293 The apparent power on phase C of a multi-phase circuit


Related to the current of the third phase of 3-phase
PhaseCCurrent 289
power
PhaseCReactivePower 297 The reactive power on phase C of a multi-phase circuit
Related to the voltage of the third phase of 3-phase
PhaseCVoltage 133
power
Related to the voltage potential of the third phase of 3-
PhaseCVoltagePotential 135
phase power
PhaseSequence 78 Related to the order of the phases in multi-phase power
In single-phase or in situations where the specific phase
PhaseVoltage 79
is irrelevant, this is related to voltage across the phase
Related to the ratio of the real power flowing to the load
PowerFactor 27
to the apparent power in the circuit
Related to the set of limits of electrical properties that
PowerQuality 28 allows electrical systems to function in their intended
manner without significant loss of performance
PowerQualityRecording 80 Related to the capture and storage of power quality data
Related to the right-hand side of an account; billing for
PrepaymentCredit 81
prepayment accounts
Pricing 9 Related to billing
Processor 82 Related to a CPU, typically
Program 83 Related to a pre-defined set of instructions
Pulse 84 Related to a means by which energy is measured
Related to a relatively temporary storage area used to
Queue 197
hold requests or tasks until they can be processed
Radio 136 Related to a physical device that processes radio signals
RAM 85 Related to random access memory
Rate 86 Related to the speed or velocity
Related to the permission level one has; as in read,
ReadAccess 202
write, update
Related to the collection of consumption, diagnostic, and
Readings 87
status data from a meter
Power that does not perform work measured in VA
ReactivePower 294
reactive (VAr)
Recoder 300 A device for encoding
Recovery 88 Related to a process of restoring from a broken state
Register 89 Related to a placeholder for information
Related to a process by which a device is recognized or
Registration 90
added
Relay 91 Related to an electrically operated switch
Related to physical security (ie. accessability) or
electronic permission to read/write digital media from a
RemoteAccess 211
mobile device or from a location other than where the
object being accessed is
ROM 92 Related to read-only memory
Rotation 93 Related to the movement of an object in a circular motion
RTP 94 Related to real-time pricing
Schedule 95 Related to a timetable or plan of future events
Related to the division of a year marked by changes in
Season 228
weather; typically winter, spring, summer, and fall
– 192 – 61968-9  IEC:2013

EndDeviceSubdomain enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

SecondaryCredit 96 Related to a non-primary amount of credit


SecuredRegister 98 Related to a specific register on a device
Related a table that requires authorization prior to
SecuredTable 99
access being granted
Related to a piece of information that determines the
SecurityKey 32
functional output of a cryptographic cipher
SecurityKeyLength 119 Related to the length of a security key
SecurityKeyVersion 120 Related to the version of a security key
SelfRead 231 Related to a process where a device will read itself
Related to a process where a device will run an internal
SelfTest 100
test on itself
Related to a mechanical device that transmits a signal to
Sensor 144
a measuring device
Session 129 Related to a communication session, typically
Related to the threshold at which a feature is engaged;
SetPoint 101
typically related to load control
SigmaticMessage 102 Related to sigmatic messages
Signature 103 Related to electronic security and signing of messages
SignatureLength 104 Related to the length of a security signature
Related to the timeframe within which a security
SignatureTimestamp 105
signature is valid
SignatureUsage 106 Related to how a signature is being used
Related to the ratio of the density of a substance to the
SpecificGravity 240
density of water
StandardTime 107 Related to the opposite of daylight savings time
Related to a specific mode of operation into which a
StandbyMode 108
device can be set
Status 17 Related to the current state of something
Related to the medium on which information is kept; also
Storage 109
related to the act of storing information
SupplyCapacityLimit 139 Related to supply capacity limits
Table 110 Relating to a structure containing rows and columns
Tariff 140 Billing term relating to cost or amount chaged
Test 111 Related to a classification that specifies non-production
Related to a specific mode of operation into which a
TestMode 19
device can be set
Related to a message or set of characters that are sent
TextMessage 112
to a device
Related to a level or point at which something will
Threshold 261
happen
Tier 113 Related to a level
Related to time of day, as in
Time 114
hours:minutes:seconds:miliseconds
Related to a specific threshold specifying when to
Timeout 125
automatically return after having received no response
TimeReset 115 Related to the resetting of the time of day
Related to the process of adjusting the time of day value
TimeSync 116 on a device to match that of a trusted source for time of
day
TimeVariance 117 Related to the acceptable difference of a device time of
61968-9  IEC:2013 – 193 –

EndDeviceSubdomain enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

day as compared to a trusted source for time of day

Related to the time regions around the Earth defined by


TimeZone 118
the lines of longitude
TOU 121 Related to time of use
Related to a device that has both a transmitter and a
Tranceiver 122
receiver
Usage 123 Related to how something is used
Version 124 Related to a specific iteration or translation
Related to the electrical force that would drive an electric
Voltage 38
current between two points
Related to a period of time during which a device can be
Window 73
linked/paired with a meter or other device
Related to the permission level one has; as in read,
WriteAccess 282
write, update

E.8 EndDeviceEventOrAction

The most specific part of the EndDeviceEventType is its EndDeviceEventOrAction value. This
part of the EndDeviceEventType enumeration is generally in the form of a verb that gives
action to the event that just occurred.

EndDeviceEventOrAction codes are enumerated and described in Table E.4.

Table E.4 – EndDeviceEventOrAction codes

EndDeviceEventOrAction enumeration
mnemonic Value Description
Not applicable. Use when a EndDeviceEventOrAction is not
n/a 0
needed. This should rarely be used.
An event that occurs when some intervention causes the item
Aborted 1
(identified by the EndDeviceDomain/EndDeviceSubdomain) to stop.
Typically a security event that occurs when physical access or
Accessed 2
access to data has been obtained (whether permitted or not).
An event that indicates the receipt of the item (identified by the
Acknowledged 3
EndDeviceDomain/EndDeviceSubdomain).
An event that indicates that the item (identified by the
Activated 4 EndDeviceDomain/EndDeviceSubdomain) that was inactive is now
active.
AlmostFull 283 An event to indicate that a resource is near capacity
An event that indicates that an ArmForClosure command has been
ArmedForClosure 11
completed successfully.
An event that indicates that an ArmForOpen command has been
ArmedForOpen 12
completed successfully.
ArmForClosure 5 A command to indicate a request to arm a switch for closure.
ArmForClosureFailed 226 An event that indicates that an ArmForClosure has failed.
ArmForOpen 6 A command to indicate a request to arm a switch for open.
ArmForOpenFailed 222 An event that indicates that an ArmFor Open has failed.
An event that indicates that the item (identified by the
EndDeviceDomain/EndDeviceSubdomain), based on the
Attempted 7
EndDeviceDomain and EndDeviceSubdomain combination, has
been tried.
– 194 – 61968-9  IEC:2013

EndDeviceEventOrAction enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

An event that indicates that the item (identified by the


EndDeviceDomain/EndDeviceSubdomain), based on the
Calculated 21
EndDeviceDomain and EndDeviceSubdomain combination, has
been computed.
A command to indicate a request to terminate a prior issued
Cancel 8
command.
CancelFailed 86 An event that indicates that a Cancel has failed.
An event that indicates that a prior issued command or set of
Cancelled 10
commands was terminated successfully.
Change 13 A command to indicate a request to make modifications.
An event that indicates that a related Change request has
Changed 24
completed successfully.
ChangedOut 284 An event to indicate that an asset has been replaced
A command to request that a device is replaced by a new device of
ChangeOutRequired 27
the same kind.
ChangePending 14 An event that indicates that an update has not yet been performed.
An event that can indicate a billing-related state or in the form of
Charged 15
being electrically charged.
An event that indicates that the item (identified by the
Cleared 28 EndDeviceDomain/EndDeviceSubdomain) on the device has been
either resolved or emptied.
A control command for the item described by
EndDeviceDomain/EndDeviceSubdomain.
Close 299 NOTE This command might be used to close a pairing window. It
should not be used to close a switch. The “Connect” command
should be used instead.
An event that indicates the item (identified by the
Closed 16 EndDeviceDomain/EndDeviceSubdomain) on the device that had
been open is not open anymore.
An event that indicates the item (identified by the
EndDeviceDomain/EndDeviceSubdomain) has been started from a
ColdStarted 31
stopped state (as opposed to a WarmStart which implies that it was
started from an already started state).
An event that indicates the receipt and agreement of the item
Confirmed 17
(identified by the EndDeviceDomain/EndDeviceSubdomain).
A command to request that a device be put into service.
Connect 18 NOTE This would effectively “close” an electrical switch or “open”
a water valve.
Connected 42 An event to indicate that a device has been put into service.
ConnectFailed 67 An event that indicates a Connect request has failed.
An event to indicate that the item (identified by the
Corrupted 43 EndDeviceDomain/EndDeviceSubdomain) has been altered from a
correct state to an incorrect state.
CorruptionCleared 281 An event to indicate that a corruption condition has been cleared
Create 82 A command to request that something be created.
Created 83 An event that indicates that a Create request succeeded.
CreateFailed 297 An event that indicates that a Create request failed.
An event that indicates that instability due to cross-phase
CrossPhaseCleared 70
modulation has been corrected.
CrossPhaseDetected 45 An event that indicates instability due to cross-phase modulation.
An event that indicates that the item (identified by the
Deactivated 19 EndDeviceDomain/EndDeviceSubdomain) on the device that had
previously been in an active state is no longer active.
61968-9  IEC:2013 – 195 –

EndDeviceEventOrAction enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

An event that indicates that the item (identified by the


Decreased 57 EndDeviceDomain/EndDeviceSubdomain) has a lower value or
magnitude.
An event that indicates the item (identified by the
Delayed 20 EndDeviceDomain/EndDeviceSubdomain) is slower than expected
or will complete later than expected.
A command to request that the item (identified by the
Disable 22
EndDeviceDomain/EndDeviceSubdomain) be rendered incapable.
An event to indicate that the item (identified by the
Disabled 66 EndDeviceDomain/EndDeviceSubdomain) was successfully
rendered incapable.
DisableFailed 220 An event that indicates that a Disable request has failed.
An event to indicate that the item (identified by the
Disallowed 161
EndDeviceDomain/EndDeviceSubdomain) was not allowed.
A command to request that a device be pulled from service; can
also mean a request to sever connection to the item (identified by
Disconnect 23 the EndDeviceDomain/EndDeviceSubdomain).
NOTE This would effectively “open” an electrical switch or “close”
a water valve.
An event to indicate that a device was successfully pulled from
service; can also mean that connection to the item (identified by the
Disconnected 68
EndDeviceDomain/EndDeviceSubdomain) has been severed or
terminated.
DisconnectFailed 84 An event that indicates that a Disconnect request has failed.
A command to request the display of something (as in a
Display 77
TextMessage).
An event that indicates that a Display request completed
Displayed 78
successfully.
DisplayFailed 87 An event that indicates that a Display request failed.
An event to indicate that the item (identified by the
Distorted 91 EndDeviceDomain/EndDeviceSubdomain) has been altered from
its expected state.
An event to indicate that the item (identified by the
Downloaded 25 EndDeviceDomain/EndDeviceSubdomain) transmitted from the
network to the device.
A command to request that the item (identified by the
Enable 26
EndDeviceDomain/EndDeviceSubdomain) be rendered capable.
An event to indicate that the item (identified by the
Enabled 76 EndDeviceDomain/EndDeviceSubdomain) was successfully
rendered capable.
EnableFailed 221 An event that indicates that an Enable request failed.
An event to indicate that the item (identified by the
Error 79 EndDeviceDomain/EndDeviceSubdomain) did not complete
successfully.
ErrorCleared 279 An event to indicate that an error condition has been cleared
An event to indicate that the item (identified by the
Established 29
EndDeviceDomain/EndDeviceSubdomain) has been recognized.
An event to indicate that an event (for example, demand response
EventStarted 287
event) has begun
An event to indicate that an event (for example, demand response
EventStopped 288
event) has halted
An event to indicate that the item (identified by the
Exceeded 139 EndDeviceDomain/EndDeviceSubdomain) has gone higher than its
expected value.
A command to request that the item (identified by the
Execute 30
EndDeviceDomain/EndDeviceSubdomain) be performed.
– 196 – 61968-9  IEC:2013

EndDeviceEventOrAction enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

An event to indicate that the item (identified by the


Expired 64 EndDeviceDomain/EndDeviceSubdomain) has come to an end,
typically by date or time.
An event to indicate that the item (identified by the
Failed 85
EndDeviceDomain/EndDeviceSubdomain) has not succeeded.
An event to indicate that the item (identified by the
Frozen 88
EndDeviceDomain/EndDeviceSubdomain) is in a static state.
An event to indicate that the item (identified by the
Full 32
EndDeviceDomain/EndDeviceSubdomain) is at capacity.
An event to indicate that the item (identified by the
HighDistortion 69 EndDeviceDomain/EndDeviceSubdomain) has had an undesired
change in the waveform of a signal.
An event to indicate that the item (identified by the
HighDistortionCleared 71 EndDeviceDomain/EndDeviceSubdomain) is back to normal after
having been in a HighDistortion state.
An event to indicate that the item (identified by the
ImbalanceCleared 75 EndDeviceDomain/EndDeviceSubdomain) is back in balance after
having been in an imbalanced state.
An event to indicate that the item (identified by the
Imbalanced 98
EndDeviceDomain/EndDeviceSubdomain) is not balanced.
An event to indicate that the item (identified by the
Inactive 100
EndDeviceDomain/EndDeviceSubdomain) is at a dormant state.
An event to indicate that the item (identified by the
InactiveCleared 72 EndDeviceDomain/EndDeviceSubdomain) is now in an active state
after having been in a dormant state.
An event to indicate that the item (identified by the
Increased 102
EndDeviceDomain/EndDeviceSubdomain) has gotten larger.
An event to indicate that the item (identified by the
Initialized 33 EndDeviceDomain/EndDeviceSubdomain) has been set to starting
values.
An event to indicate that the item (identified by the
InProgress 34 EndDeviceDomain/EndDeviceSubdomain) is currently advancing
toward a goal or an end.
An event to indicate that the item (identified by the
Installed 105 EndDeviceDomain/EndDeviceSubdomain) has been prepared for
use.
An event to indicate that the item (identified by the
Invalid 35
EndDeviceDomain/EndDeviceSubdomain) is in a faulty state.
LimitChanged 296 An event to indicate that the set point for a limit has been changed
LimitReached 286 An event to indicate that an upper or lower limit has been breached
An event to indicate that the item (identified by the
Loaded 36
EndDeviceDomain/EndDeviceSubdomain) is now engaged.
An event to indicate that the item (identified by the
EndDeviceDomain/EndDeviceSubdomain) has experienced a
LossDetected 47
deprived condition. This is typically used in relation to power,
voltage, or current.
An event to indicate that the set point for a maximum limit has been
MaxLimitChanged 295
changed
An event to indicate that a previous MaxLimitReached event has
MaxLimitCleared 293
been cleared
An event to indicate that the item (identified by the
MaxLimitReached 93 EndDeviceDomain/EndDeviceSubdomain) has reached a maximum
acceptable value.
An event to indicate that the item (identified by the
MaxLimitReachedCleared 73 EndDeviceDomain/EndDeviceSubdomain) has returned to an
acceptable state after having been as a MaxLimitReached state.
MinLimitChanged 294 An event to indicate that the set point for a minimum limit has been
61968-9  IEC:2013 – 197 –

EndDeviceEventOrAction enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

changed

An event to indicate that a previous MinLimitReached event has


MinLimitCleared 292
been cleared
An event to indicate that the item (identified by the
MinLimitReached 150 EndDeviceDomain/EndDeviceSubdomain) has reached a minimum
acceptable value.
An event to indicate that the item (identified by the
Mismatched 159 EndDeviceDomain/EndDeviceSubdomain) is not compatible with
itself or something within its environment.
An event to indicate that an entity (for example, asset,
Missing 285
measurement, etc.) is missing
An event to indicate that the item (identified by the
Normal 37 EndDeviceDomain/EndDeviceSubdomain) is in its typical state (or
norm).
NotArmed 290 An event to indicate that a device is longer in an armed state
An event to indicate that the item (identified by the
NotAuthorized 38 EndDeviceDomain/EndDeviceSubdomain) has been accessed
without permission.
An event to indicate that the item (identified by the
NotFound 160
EndDeviceDomain/EndDeviceSubdomain) is lost or missing.
A control command for the item described by
EndDeviceDomain/EndDeviceSubdomain.
Open 298 NOTE This command might be used to open a pairing window. It
should not be used to open a switch. The “Disconnect” command
should be used instead.
An event to indicate that the item (identified by the
Opened 39
EndDeviceDomain/EndDeviceSubdomain) is accessible.
An event that indicates that a consumer has agreed to join a
Opted-In 80
program.
An event that indicates that a consumer does not want to join a
Opted-Out 81
program.
An event to indicate that the item (identified by the
OutofRange 40 EndDeviceDomain/EndDeviceSubdomain) has gone outside of
acceptable values.
An event to indicate that the item (identified by the
OutofRangeCleared 74 EndDeviceDomain/EndDeviceSubdomain) has gone back to
acceptable values.
An event to indicate that the item (identified by the
Overflow 177 EndDeviceDomain/EndDeviceSubdomain) has exceeded its size or
volume.
An event to indicate that the item (identified by the
Preempted 41 EndDeviceDomain/EndDeviceSubdomain) been replaced by
another that has precedence over it.
An event to indicate that the item (identified by the
Processed 44 EndDeviceDomain/EndDeviceSubdomain) has been successfully
been put through the steps of a prescribed procedure.
This can be an event (if treated as the past-tense of the verb, read)
Read 46
or a command (if treated as the verb, read).
An event that indicates that a ready condition has been reached on
Ready 48
a device.
ReadyForActivation 280 An event to indicate that a device has been made ready
An event that indicates that a condition, typically a connection, has
Re-established 49
achieved after having been lost.
An event that indicates that a device or condition of a device has
Registered 50
been recorded.
Released 51 An event to indicate that the item (identified by the
– 198 – 61968-9  IEC:2013

EndDeviceEventOrAction enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceDomain/EndDeviceSubdomain) has been freed.

An event to indicate that the item (identified by the


Removed 212 EndDeviceDomain/EndDeviceSubdomain) has been pulled out of
service.
An event to indicate that the item (identified by the
Replaced 52 EndDeviceDomain/EndDeviceSubdomain) replaced by an new
item, usually as a consequence of being old or worn out.
An event to indicate that the item (identified by the
Reprogrammed 213 EndDeviceDomain/EndDeviceSubdomain) has had a change to its
directions or program.
A command to request that the item (identified by the
Reset 214 EndDeviceDomain.EndDeviceSubdomain) should be set back to a
zero-state or original-state.
ResetFailed 65 An event that indicates that a Reset request has failed.
An event that indicates that a Reset request has completed
ResetOccurred 215
successfully.
An event to indicate that the item (identified by the
Restarted 53 EndDeviceDomain/EndDeviceSubdomain) has started again
typically from an already started state.
An event to indicate that the item (identified by the
Restored 216 EndDeviceDomain/EndDeviceSubdomain) has been put back to its
prior state.
An event to indicate that the item (identified by the
Reversed 219 EndDeviceDomain/EndDeviceSubdomain) has changed to be the
opposite of its normal state. This is typically used for rotation.
An event to indicate that the item (identified by the
SagStarted 223 EndDeviceDomain/EndDeviceSubdomain) has dipped or shrunk
from its expected state.
An event to indicate that the item (identified by the
SagStopped 224 EndDeviceDomain/EndDeviceSubdomain) has stopped sagging.
Typically used in conjunction with the SagStarted event.
A control command to ask that the item (identified by the
Schedule 300 EndDeviceDomain/EndDeviceSubdomain) will be set to execute at
a future date.
An event to indicate that the item (identified by the
Scheduled 225 EndDeviceDomain/EndDeviceSubdomain) has been set to execute
at a future date.
An event to indicate that the command to ask that the item
ScheduleFailed 301 (identified by the EndDeviceDomain/EndDeviceSubdomain) to
execute at a future date failed to schedule.
An event to indicate that the item (identified by the
Sealed 227 EndDeviceDomain/EndDeviceSubdomain) is in an airtight enclosure
or cannot be accessed directly.
A command to request that the item (identified by the
Start 54
EndDeviceDomain/EndDeviceSubdomain) be triggered or begun.
An event to indicate that the item (identified by the
Started 242
EndDeviceDomain/EndDeviceSubdomain) has started.
StartFailed 217 An event that indicates that a Start request has failed.
A command to request that the item (identified by the
Stop 55
EndDeviceDomain/EndDeviceSubdomain) be shut down normally.
StopFailed 218 An event that indicates that a Stop request has failed.
An event to indicate that the item (identified by the
EndDeviceDomain/EndDeviceSubdomain) has ceased. When this
Stopped 243
has resulted from a Stop command, it is assumed that things have
stopped normally (ie. With no errors).

Substituted 56 An event to indicate that the item (identified by the


EndDeviceDomain/EndDeviceSubdomain) replaced by an alternate
61968-9  IEC:2013 – 199 –

EndDeviceEventOrAction enumeration
mnemonic Value Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

item.

An event to indicate that the item (identified by the


Succeeded 58
EndDeviceDomain/EndDeviceSubdomain) was accomplished.
An event to indicate that the item (identified by the
SwellStarted 248 EndDeviceDomain/EndDeviceSubdomain) has grown from its
expected state.
An event to indicate that the item (identified by the
SwellStopped 249 EndDeviceDomain/EndDeviceSubdomain) has stopped swelling.
Typically used in conjunction with the SwellStarted event.
SwitchPositionChanged 289 An event to indicate that a switch position has changed
TamperCleared 291 An event to indicate that a tamper alarm has been cleared
An event to indicate that the item (identified by the
EndDeviceDomain/EndDeviceSubdomain) has been secretly
TamperDetected 257
modified or altered. These events are typically associated with
security or billing.
A control command to request that the item (identified by the
Terminate 302 EndDeviceDomain/EndDeviceSubdomain) end immediately and
abruptly.
An event to indicate that the item (identified by the
Terminated 59
EndDeviceDomain/EndDeviceSubdomain) has ended abruptly.
An event to indicate that the attempt to terminate the item (identified
TerminateFailed 303
by the EndDeviceDomain/EndDeviceSubdomain) has failed.
An event to indicate that the item (identified by the
Tilted 263 EndDeviceDomain/EndDeviceSubdomain) has been caused to
lean, incline, slope, or slant.
An event to indicate that the item (identified by the
Uninitialized 61 EndDeviceDomain/EndDeviceSubdomain) has all its values in their
starting state.
An event to indicate that the item’s (identified by the
Unlocked 62 EndDeviceDomain/EndDeviceSubdomain) lock, physical or
software, is undone.
An event to indicate that the item (identified by the
Unsealed 269
EndDeviceDomain/EndDeviceSubdomain) is not sealed.
An event to indicate that the item (identified by the
Unsecure 63 EndDeviceDomain/EndDeviceSubdomain) is in an unprotected
state.
An event to indicate that the item (identified by the
Unstable 270
EndDeviceDomain/EndDeviceSubdomain) is in an irregular state.
An event to indicate that the item (identified by the
Uploaded 60 EndDeviceDomain/EndDeviceSubdomain) has been transmitted
from the device to the network.
An event that indicates the item (identified by the
EndDeviceDomain/EndDeviceSubdomain) has been started from
WarmStarted 278
an already started state (as opposed to a ColdStart which implies
that it was started from a stopped state).
WriteFailed 282 An event to indicate that a write operation has failed

E.9 Normative EndDeviceEventTypes

EndDeviceType, EndDeviceDomain, EndDeviceSubdomain, and EndDeviceEventOrAction


fields are combined and presented as a single string. The normative events are listed in the
following Tables E.5 through E.31, grouped by EndDeviceDomain.
– 200 – 61968-9  IEC:2013

Table E.5 – Battery events


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Battery low condition


detected
Module Low Battery
Detected *.2.22.150 * Battery Charge MinLimitReached
Low Battery
Module Low Battery
Detected
Battery OK
*.2.22.37 * Battery Charge Normal
Rf Battery OK
Battery failed *.2.0.85 * Battery n/a Failed
Battery installed *.2.0.105 * Battery n/a Installed

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.6 – Billing events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Adjusted the remaining


*.20.8.24 * Billing Credit Changed
credit
Subtracted from
*.20.8.57 * Billing Credit Decreased
remaining credit
Added to remaining
*.20.8.102 * Billing Credit Increased
credit
Pre-payment
*.20.81.102 * Billing PrepaymentCredit Increased
emergency credit
Tariff program changed *.20.83.24 * Billing Program Changed
RTP activation *.20.94.4 * Billing RTP Activated
RTP deactivation *.20.94.19 * Billing RTP Deactivated
Special schedule
*.20.95.4 * Billing Schedule Activated
activation
Secondary emergency
*.20.96.102 * Billing SecondaryCredit Increased
credit
Daily tariff changed
Week tariff changed *.20.140.24 * Billing Tariff Changed
Rate change
Unscheduled billing
reset *.20.140.214 * Billing Tariff Reset
Billing reset
Tier changed *.20.113.24 * Billing Tier Changed
TOU start mismatch
TOU mismatch *.20.121.159 * Billing TOU Mismatched
TOU years mismatch

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.
61968-9  IEC:2013 – 201 –

Table E.7 – Cartridge events


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Cartridge error *.3.17.79 * Cartridge Status Error


Cartridge frozen *.3.17.88 * Cartridge Status Frozen
Cartridge installed *.3.17.105 * Cartridge Status Installed
No cartridge inserted *.3.17.160 * Cartridge Status NotFound
Cartridge removed *.3.17.212 * Cartridge Status Removed
Cartridge changed
Pushbutton cartridge
changed
Handheld terminal *.3.17.52 * Cartridge Status Replaced
cartridge
Cartridge change
mode, unable to read

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.8 – Clock events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Auto time set


*.36.7.58 * Clock AutoTime Succeeded
performed
Date setting changed *.36.34.24 * Clock Date Changed
Invalid execution date
and time
*.36.34.35 * Clock Date Invalid
Invalid complete date
and time range
Day change error *.36.35.79 * Clock Day Error
Day of wrong length *.36.35.35 * Clock Day Invalid
DST change to new
*.36.56.24 * Clock DaylightSavingsTime Changed
time
Daylight savings or
standard time variance *.36.56.40 * Clock DaylightSavingsTime OutofRange
error
DST change to
*.36.56.214 * Clock DaylightSavingsTime Reset
previous time
Change to Spring
*.36.56.242 * Clock DaylightSavingsTime Started
daylight savings time
Holiday changed
*.36.97.24 * Clock Holiday Changed
Holidays changed
Invalid installation date *.36.57.35 * Clock InstallDate Invalid
Temporary clock
*.36.0.79 * Clock n/a Error
problem
Clock malfunction
*.36.0.85 * Clock n/a Failed
E-clock failure
Season changed *.36.228.24 * Clock Season Changed
Change to Fall
*.36.107.242 * Clock StandardTime Started
standard time
Time setting changed
to new time
Working register time *.36.114.24 * Clock Time Changed
set to new time
Time setting changed
– 202 – 61968-9  IEC:2013

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

(old time)
Time setting changed
Collector Radio Set
TimeKeeper
Meter Time Adjustment
Time change > 10
*.36.114.40 * Clock Time OutofRange
seconds
Time setting reset to
previous time
Working register time *.36.114.214 * Clock Time Reset
set to previous time
Time reset
Unable to reset time *.36.115.85 * Clock TimeReset Failed
Time synchronization
*.36.116.79 * Clock TimeSync Error
error
Time sync failed:Meter
*.36.116.85 * Clock TimeSync Failed
I/O/clock failure(38)
Time synchronization
*.36.116.58 * Clock TimeSync Succeeded
of recorder
Time variance
exceeded limits even
after module tries to
correct it
*.36.117.139 * Clock TimeVariance Exceeded
Time variance
exceeded limits without
attempt to correct
automatically
Invalid time zone ID *.36.118.35 * Clock TimeZone Invalid

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of
these events will be relevant to the device that is actually sending this event.

Table E.9 – Communication events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Watch dog or keep-alive


*.1.3.85 * Communication AUTDProcess Failed
failure detected
Cut cable *.1.15.85 * Communication Cable Failed
Encoder register
*.1.41.85 * Communication EncoderRegister Failed
communication failure
RF HES Comm Established *.1.52.29 * Communication HeadEndSystem Established
Rf No HES Comm *.1.52.85 * Communication HeadEndSystem Failed
Intelligent register
*.1.58.85 * Communication IntelligentRegister Failed
communication failure
Communications between
*.1.60.85 * Communication IO Failed
modules within a meter lost
I/O board definition
*.1.60.159 * Communication IO Mismatched
mismatch
Rf No Mesh Comm *.1.68.85 * Communication Mesh Failed
Call-in failure
*.1.0.85 * Communication n/a Failed
Communications failure
Communications re-
*.1.0.49 * Communication n/a Re-established
established
Communication terminated
*.1.0.59 * Communication n/a Terminated
normally
61968-9  IEC:2013 – 203 –

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Queue alarm *.1.197.85 * Communication Queue Failed


Collector Communication
*.1.17.20 * Communication Status Delayed
Delay
Rf Tranceiver Reset *.1.122.214 * Communication Tranceiver Reset

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of these
events will be relevant to the device that is actually sending this event.

Table E.10 – Configuration events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Constants changed
Primary constant
changed
Secondary constant *.7.23.24 * Configuration Constants Changed
changed
Output constant
changed
Meter hard ID changed *.7.10.24 * Configuration Identity Changed
Invalid gateway ID
*.7.10.35 * Configuration Identity Invalid
Invalid Transformer ID
Missing node *.7.10.160 * Configuration Identity NotFound
Collector Radio Set IP
*.7.127.24 * Configuration IPAddress Changed
List
Maintenance mode
Meter shop mode *.7.11.242 * Configuration MaintMode Started
started
Meter shop mode
*.7.11.243 * Configuration MaintMode Stopped
stopped
Begin recording meter
readings *.7.12.242 * Configuration MeteringMode Started
Begin idle mode
Metering mode stopped *.7.12.243 * Configuration MeteringMode Stopped
Request customer
*.7.0.13 * Configuration n/a Change
configuration
Collector Radio Set
*.7.0.24 * Configuration n/a Changed
Network Settings
Configuration error
*.7.0.79 * Configuration n/a Error
detected
Configuration Initialized *.7.0.33 * Configuration n/a Initialized
Gateway reprogrammed *.7.0.213 * Configuration n/a Reprogrammed
Sum definition changed
Sum type changed
Meter counts synch
Sum counts synch *.7.75.24 * Configuration Parameter Changed
Output link changed
Energy format changed
Power format changed
Meter program change
*.7.83.24 * Configuration Program Changed
complete
Rate changed *.7.86.24 * Configuration Rate Changed
Setpoint exceeded,
*.7.101.139 * Configuration SetPoint Exceeded
channel #
Standby mode started *.7.108.242 * Configuration StandbyMode Started
– 204 – 61968-9  IEC:2013

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Storage medium
*.7.109.24 * Configuration Storage Changed
changed
Test button pushed *.7.19.76 * Configuration TestMode Enabled
Test mode started *.7.19.242 * Configuration TestMode Started
Test mode ended *.7.19.243 * Configuration TestMode Stopped
Invalid timeout date
*.7.125.35 * Configuration Timeout Invalid
and time

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use
of these events will be relevant to the device that is actually sending this event.

Table E.11 – Demand events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Unable to reset demand *.8.0.65 * Demand n/a ResetFailed


Demand reset detected *.8.0.215 * Demand n/a ResetOccurred
Demand definitions
*.8.0.159 * Demand n/a Mismatched
mismatch
Demand overload
*.8.261.139 * Demand Threshold Exceeded
threshold
Demand threshold
*.8.261.93 * Demand Threshold MaxLimitReached
caution

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.12 – Firmware events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

A/D converter error *.11.142.79 * Firmware ADConverter Error


Constants invalid *.11.23.35 * Firmware Constants Invalid
Unknown in analysis
*.11.31.79 * Firmware Data Error
Diagnostic marker
Unrecognized recorder
event code
*.11.31.35 * Firmware Data Invalid
Unintelligible message
received
Frozen error display *.11.143.88 * Firmware Display Frozen
Alarm acknowledged,
*.11.43.3 * Firmware Event Acknowledged
alarm #
Alarm activated, alarm #
*.11.46.4 * Firmware Feature Activated
Area alarm
Alarm disabled, alarm #
Remote setup disabled *.11.46.66 * Firmware Feature Disabled
Remote synch disabled
Alarm enabled, alarm #
Remote setup enabled
*.11.46.76 * Firmware Feature Enabled
Remote synch enabled
Alarm value set, alarm #
Delayed command failure *.11.46.85 * Firmware Feature Failed
61968-9  IEC:2013 – 205 –

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Illegal command *.11.46.35 * Firmware Feature Invalid


Unable to reset *.11.47.85 * Firmware FirmwareReset Failed
Internal device ID
*.11.10.159 * Firmware Identity Mismatched
mismatch
Unstable input, input # *.11.55.270 * Firmware Input Unstable
Read item list error *.11.63.79 * Firmware List Error
No protocol list, unable
to find type *.11.63.160 * Firmware List NotFound
No read items in list
Low speed bus error *.11.145.79 * Firmware LowSpeedBus Error
Meter bus alarm *.11.147.79 * Firmware MeterBus Error
Cold start *.11.0.31 * Firmware n/a ColdStarted
Firmware image
*.11.0.43 * Firmware n/a Corrupted
corrupted
Configuration lost *.11.0.79 * Firmware n/a Error
Collector Radio Load
*.11.0.85 * Firmware n/a Failed
DCW
Meter reprogram
End device programmed
Configuration
written/changed
*.11.0.213 * Firmware n/a Reprogrammed
Reprogrammed
Meter reconfigured
Device has been
synchronized
Last reset by watchdog
*.11.0.214 * Firmware n/a Reset
Metering equipment reset
Unscheduled restart *.11.0.53 * Firmware n/a Restarted
Meter not programmed *.11.0.61 * Firmware n/a Uninitialized
Warm start *.11.0.278 * Firmware n/a WarmStarted
Option board error *.11.146.79 * Firmware OptionBoard Error
Parameter error
*.11.75.79 * Firmware Parameter Error
Configuration error
Invalid re-programming
data
*.11.75.35 * Firmware Parameter Invalid
Invalid device type, e.g.
not TOU
Miscellaneous
*.11.75.159 * Firmware Parameter Mismatched
configuration mismatch
Alternate phone number
*.11.75.56 * Firmware Parameter Substituted
used
Register processor failed *.11.82.85 * Firmware Processor Failed
Illegal command
*.11.82.35 * Firmware Processor Invalid
processor state
Processor reset *.11.82.214 * Firmware Processor Reset
Un-programmed caution *.11.83.79 * Firmware Program Error
Program malfunction *.11.83.85 * Firmware Program Failed
Self-check error
*.11.100.79 * Firmware SelfTest Error
Diagnostic failure
Self test failure *.11.100.85 * Firmware SelfTest Failed
Sensor malfunction *.11.144.85 * Firmware Sensor Failed
– 206 – 61968-9  IEC:2013

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Alter option command


*.11.17.24 * Firmware Status Changed
executed
Firmware update pending *.11.17.14 * Firmware Status ChangePending
Firmware downloaded *.11.17.25 * Firmware Status Downloaded
Firmware download
status *.11.17.37 * Firmware Status Normal
Meter health checked
Firmware replaced
Zigbee firmware change *.11.17.52 * Firmware Status Replaced
complete
Device reset occurred *.11.17.214 * Firmware Status Reset
End of data event table
*.11.110.79 * Firmware Table Error
reached
Display table mismatch *.11.110.159 * Firmware Table Mismatched
Test call-in *.11.111.58 * Firmware Test Succeeded
Test mode display
*.11.19.159 * Firmware TestMode Mismatched
mismatch
Invalid down limit *.11.261.35 * Firmware Threshold Invalid
Calculation correction
*.11.261.40 * Firmware Threshold OutofRange
factor > max
Invalid meter software
*.11.124.35 * Firmware Version Invalid
version

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use
of these events will be relevant to the device that is actually sending this event.

Table E.13 – GasSupply events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Complete loss of gas


*.4.0.85 * GasSupply n/a Failed
supply
Gas supply restored *.4.0.216 * GasSupply n/a Restored

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.14 – Installation events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Auto registration status *.6.5.34 * Installation AutoRegistration InProgress


Auto registration
*.6.5.58 * Installation AutoRegistration Succeeded
confirmation
Meter change-out *.6.0.27 * Installation n/a ChangeOut

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.
61968-9  IEC:2013 – 207 –

Table E.15 – LoadControl events


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Control point changed


by condition
Control point changed
by command
*.15.26.24 * Loadcontrol ControlPoint Changed
Control point changed
due to prepayment
Control point changed
by schedule
Abort command
*.15.0.1 * Loadcontrol n/a Aborted
executed
Load Control User opt-
*.15.83.4 * LoadControl Program Activated
in
Load control relay
momentary closure,
relay # *.15.91.24 * Loadcontrol Relay Changed
Output control relay
toggled, relay #
Switch schedule
*.15.95.1 * Loadcontrol Schedule Aborted
aborted
Schedule loaded *.15.95.36 * Loadcontrol Schedule Loaded
Load control restore *.15.17.216 * Loadcontrol Status Restored
Load control initiate
Load control relay
closed
Load control relay
*.15.17.242 * Loadcontrol Status Started
permanent closure,
relay #
Load control pattern
started
Load control relay
opened
*.15.17.243 * Loadcontrol Status Stopped
Load control relay
opened, relay #

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.16 – LoadProfile events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

List Pointers reset *.16.64.214 * Loadprofile ListPointers Reset


Load survey readings
*.16.87.85 * Loadprofile Readings Failed
failed
Load profile data
*.16.109.43 * Loadprofile Storage Corrupted
corrupt
Load profile data area
*.16.109.32 * Loadprofile Storage Full
almost full

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.
– 208 – 61968-9  IEC:2013

Table E.17 – Logs events


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Data log uploaded *.17.33.60 * Logs DataLog Transmitted


Event log last read
*.17.44.24 * Logs EventLog Changed
entry updated
Event log cleared *.17.44.28 * Logs EventLog Cleared
Event log error *.17.44.79 * Logs EventLog Error
Event log full *.17.44.32 * Logs EventLog Full
Event log uploaded
*.17.44.60 * Logs EventLog Transmitted
Event call-in
History log last read
*.17.53.24 * Logs HistoryLog Changed
entry updated
History log cleared *.17.53.28 * Logs HistoryLog Cleared
An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.18 – Memory events

Event or Control EndDeviceEven EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Memory allocation error *.18.2.79 * Memory Allocation Error


Buffer overflow/overrun
*.18.14.177 * Memory Buffer Overflow
error
EPROM read *.18.42.2 * Memory EPROM Accessed
EPROM written *.18.42.24 * Memory EPROM Changed
EPROM failure *.18.42.85 * Memory EPROM Failed
Framing error *.18.50.79 * Memory Frames Error
Interval overflow –
*.18.59.177 * Memory Interval Overflow
pulses > 65,535
Data corruption
*.18.0.43 * Memory n/a Corrupted
detection
Mass memory
*.18.0.159 * Memory n/a Mismatched
mismatch
NVRAM failure *.18.72.85 * Memory NVRAM Failed
Family definitions
*.18.75.159 * Memory Parameter Mismatched
mismatch
Redundant pulse
*.18.84.79 * Memory Pulse Error
monitoring error
RAM error *.18.85.79 * Memory RAM Error
RAM failure *.18.85.85 * Memory RAM Failed
RAM memory full *.18.85.32 * Memory RAM Full
Data recovery error *.18.88.85 * Memory Recovery Failed
ROM error *.18.92.79 * Memory ROM Error
ROM failure *.18.92.85 * Memory ROM Failed
Disk almost full *.18.109.32 * Memory Storage Full
Data table full *.18.110.32 * Memory Table Full
Table slot overflow *.18.110.177 * Memory Table Overflow
An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.
61968-9  IEC:2013 – 209 –

Table E.19 – Metrology events


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

BTU alarm
*.21.13.40 * Metrology BTU OutofRange
BTU out of range
Corrected volume
*.21.16.79 * Metrology Calculation Error
calculation error
Calibration change
*.21.18.24 * Metrology Calibration Changed
Calibration value set, #
Calibration over-
*.21.18.40 * Metrology Calibration OutofRange
deviation, #
Calibration expired *.21.18.64 * Metrology Calibration Expired
Concentration alarm *.21.39.40 * Metrology Concentration OutofRange
Event Log Cleared *.21.44.28 * Metrology EventLog Cleared
EWM potential failure *.21.45.85 * Metrology EWM Failed
FPV calculated
*.21.49.40 * Metrology FPV OutofRange
unreasonably
GC analyzer failure *.21.51.85 * Metrology GCAnalyzer Failed
History Log Cleared *.21.53.28 * Metrology HistoryLog Cleared
Form C error, input # *.21.55.79 * Metrology Input Error
Invalid value, channel # *.21.55.35 * Metrology Input Invalid
Interval read
*.21.59.58 * Metrology Interval Succeeded
succeeded
Last read entry updated *.21.62.24 * Metrology LastRead Changed
Update list pointers *.21.63.24 * Metrology List Changed
List cleared *.21.63.28 * Metrology List Cleared
Reset list pointers *.21.63.214 * Metrology List Reset
Measurement error
*.21.67.79 * Metrology Measurement Error
detected
Measurement failed *.21.67.85 * Metrology Measurement Failed
Total MOL % out of
*.21.70.40 * Metrology MOL% OutofRange
range
Measurement error
*.21.0.79 * Metrology n/a Error
detected
Meter return within
*.21.0.37 * Metrology n/a Normal
limits, channel #
Meter reprogrammed
End Device *.21.0.213 * Metrology n/a Reprogrammed
Programmed
Nonvolatile memory
*.21.72.85 * Metrology NVRAM Failed
failure detected
Turbine Pulse Error *.21.84.79 * Metrology Pulse Error
Pulse initiator *.21.84.85 * Metrology Pulse Failed
Pulse overflow, channel
*.21.84.177 * Metrology Pulse Overflow
#
Meter readings failed *.21.87.85 * Metrology Readings Failed
kWh received – alarm
*.21.87.37 * Metrology Readings Normal
cleared
Expected read missed *.21.87.160 * Metrology Readings NotFound
Scheduled call-in *.21.87.225 * Metrology Readings Scheduled
Register error *.21.89.79 * Metrology Register Error
– 210 – 61968-9  IEC:2013

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Previous kW > register


*.21.89.139 * Metrology Register Exceeded
capacity
Register full *.21.89.32 * Metrology Register Full
Register definitions
*.21.89.159 * Metrology Register Mismatched
mismatch
Register read
*.21.89.58 * Metrology Register Succeeded
succeeded
Self meter read *.21.231.58 * Metrology SelfRead Succeeded
Invalid sigmatic
*.21.102.35 * Metrology SigmaticMessage Invalid
message
Specific gravity alarm *.21.240.40 * Metrology SpecificGravity OutofRange
Self check error
*.21.17.79 * Metrology Status Error
detected
Pending table
*.21.110.4 * Metrology Table Activated
activation
Table written to *.21.110.24 * Metrology Table Changed
Pending table clear *.21.110.28 * Metrology Table Cleared
Meter over hi-hi
threshold, channel #
Meter over threshold,
*.21.261.139 * Metrology Threshold Exceeded
channel #
Delta rate over
threshold, channel #
Limit alarm reported *.21.261.93 * Metrology Threshold MaxLimitReached
Meter under threshold,
channel #
Meter over lo-lo *.21.261.150 * Metrology Threshold MinLimitReached
threshold, channel #
Low limit alarm
Meter over/under
*.21.261.40 * Metrology Threshold OutofRange
threshold
Gas day high limit
*.21.123.139 * Metrology Usage Exceeded
exceeded

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.20 – MobileSecurity events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

MAT Token Random


Data or Target LAN *.14.31.79 * MobileSecurity Data Error
Error
MAT Token Invalid
*.14.61.35 * MobileSecurity LANAddress Invalid
LAN Address Block
MAT Token Invalid
*.14.71.35 * MobileSecurity NetworkId Invalid
Network ID
MAT Token Message
*.14.32.79 * MobileSecurity SecurityKey Error
Generation Error
MAT Token Expired
MAT Token Expired,
*.14.32.64 * MobileSecurity SecurityKey Expired
Keep Alive Timeout
Exceeded
61968-9  IEC:2013 – 211 –

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

MAT Token Invalid


*.14.32.35 * MobileSecurity SecurityKey Invalid
Options
MAT Token pre-
*.14.32.41 * MobileSecurity SecurityKey Preempted
empted
MAT Token Processed *.14.32.44 * MobileSecurity SecurityKey Processed
MAT Token released *.14.32.51 * MobileSecurity SecurityKey Released
MAT Token Invalid
*.14.119.35 * MobileSecurity SecurityKeyLength Invalid
Length
MAT Token Invalid
*.14.120.35 * MobileSecurity SecurityKeyVersion Invalid
Version
Prior session already
*.14.129.161 * MobileSecurity Session Disallowed
established

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of
these events will be relevant to the device that is actually sending this event.

Table E.21 – Modem events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Power outage modem


*.19.22.150 * Modem Charge MinLimitReached
battery low
Modem failure detected *.19.17.85 * Modem Status Failed
Modem initialized *.19.17.33 * Modem Status Initialized
Modem change-out *.19.17.105 * Modem Status Installed
No modem *.19.17.160 * Modem Status NotFound

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.22 – ModuleFirmware events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Module firmware ModuleFirmwar


*.9.17.52 * Status Replaced
replaced e

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use
of these events will be relevant to the device that is actually sending this event.

Table E.23 – Network events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Network association
*.23.74.85 * Network Association Failed
failure
Collector First Connect *.23.52.42 * Network HeadEndSystem Connected
Parent device not
*.23.76.66 * Network ParentDevice Disabled
enabled
Radio faults *.23.136.85 * Network Radio Failed
– 212 – 61968-9  IEC:2013

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Collector Radio
*.23.136.50 * Network Radio Registered
Registration Data
Optional input closure,
*.23.17.42 * Network Status Connected
generator
Device not enabled
*.23.17.66 * Network Status Disabled
Gateway not enabled
Optional input opening,
generator *.23.17.68 * Network Status Disconnected
Device disconnected
DAP error
*.23.17.79 * Network Status Error
DSP error
Node failure
*.23.17.85 * Network Status Failed
Node link failure
Meter installed
*.23.17.105 * Network Status Installed
Gateway installed
End device sealed *.23.17.227 * Network Status Sealed
End device unsealed *.23.17.269 * Network Status Unsealed

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.24 – PAN / HAN events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

PAN pairing window


*.10.73.16 * Pairing Window Closed
closed
PAN pairing window
*.10.73.39 * Pairing Window Opened
opened (Ready To Pair)
PAN pairing succeeded *.10.0.58 * Pairing n/a Succeeded
PAN pairing failed *.10.0.85 * Pairing n/a Failed
PAN text message
*.13.112.10 * VideoDisplay TextMessage Canceled
canceled
PAN text message
*.13.112.78 * VideoDisplay TextMessage Displayed
displayed
PAN pricing succeeded *.20.9.58 * Billing Pricing Succeeded
PAN pricing failed *.20.9.85 * Billing Pricing Failed

PAN load control all *.15.148.86 * LoadControl AllEvents CancelFailed


events cancel failed

PAN load control all *.15.148.10 * LoadControl AllEvents Canceled


events canceled
PAN load control event
*.15.43.86 * LoadControl Event CancelFailed
ancel failed
PAN load control event
*.15.43.10 * LoadControl Event Canceled
canceled
PAN load control event
*.15.43.225 * LoadControl Event Scheduled
scheduled
PAN load control event
*.15.43.80 * LoadControl Event Opt-In
opt-in
PAN load control event
*.15.43.81 * LoadControl Event Opt-Out
opt-out
61968-9  IEC:2013 – 213 –

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

PAN device removed


PAN load control device
*.0.0.212 * n/a n/a Removed
removed
PAN gateway removed
PAN network enabled *.23.0.76 * Network n/a Enabled
PAN network disabled *.23.0.66 * Network n/a Disabled

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.25 – Power events

Event or
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
Control
Type Type Domain SubDomain EventOrAction
Description
Low current
*.26.6.150 * Power Current MinLimitReached
limit exceeded
Line
Frequency *.26.4.270 * Power Frequency Unstable
Unstable
High neutral
*.26.137.93 * Power NeutralCurrent MaxLimitReached
current
High neutral
MaxLimitReachedClea
current *.26.137.y3 * Power NeutralCurrent
red
Cleared
Cross phase
*.26.25.45 * Power Phase CrossPhaseDetected
condition
Cross phase
condition *.26.25.70 * Power Phase CrossPhaseCleared
Cleared
Loss of phase,
Phase drop *.26.25.85 * Power Phase Failed
out
Inactive phase
condition
(voltage is *.26.25.100 * Power Phase Inactive
present,
current is not)
Inactive phase
condition *.26.25.72 * Power Phase InactiveCleared
Cleared
Phase alert
*.26.25.37 * Power Phase Normal
cleared
Phase
*.26.25.40 * Power Phase OutofRange
threshold
Phase
*.26.25.216 * Power Phase Restored
restoration
Phase angle
limit
*.26.130.40 * Power PhaseAngle OutofRange
above/below
threshold
Phase angle
limit
above/below *.26.130.74 * Power PhaseAngle OutofRangeCleared
threshold
Cleared
– 214 – 61968-9  IEC:2013

Event or
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
Control
Type Type Domain SubDomain EventOrAction
Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Phase angle
*.26.130.139 * Power PhaseAngle Exceeded
limit exceeded
Voltage Sag
Started *.26.131.223 * Power PhaseAVoltage SagStarted
(PhaseA)
Voltage Sag
Stopped *.26.131.224 * Power PhaseAVoltage SagStopped
(PhaseA)
Voltage Swell
Started *.26.131.248 * Power PhaseAVoltage SwellStarted
(PhaseA)
Voltage Swell
Stopped *.26.131.249 * Power PhaseAVoltage SwellStopped
(PhaseA)
Phase A
*.26.126.100 * Power PhaseA Inactive
inactive
Voltage Sag
Started *.26.132.223 * Power PhaseBVoltage SagStarted
(PhaseB)
Voltage Sag
Stopped *.26.132.224 * Power PhaseBVoltage SagStopped
(PhaseB)
Voltage Swell
Started *.26.132.248 * Power PhaseBVoltage SwellStarted
(PhaseB)
Voltage Swell
Stopped *.26.132.249 * Power PhaseBVoltage SwellStopped
(PhaseB)
Phase B
*.26.134.100 * Power PhaseB Inactive
inactive
Voltage Sag
Started *.26.133.223 * Power PhaseCVoltage SagStarted
(PhaseC)
Voltage Sag
Stopped *.26.133.224 * Power PhaseCVoltage SagStopped
(PhaseC)
Voltage Swell
Started *.26.133.248 * Power PhaseCVoltage SwellStarted
(PhaseC)
Voltage Swell
Stopped *.26.133.249 * Power PhaseCVoltage SwellStopped
(PhaseC)
PhaseC
*.26.135.100 * Power PhaseC Inactive
inactive
Phase
Sequence *.26.78.79 * Power PhaseSequence Error
Error
Loss of
voltage
transducer on
one phase *.26.79.47 * Power PhaseVoltage LossDetected
Loss of
voltage per
phase
Power factor
exceeded *.26.27.139 * Power PowerFactor Exceeded
limits
61968-9  IEC:2013 – 215 –

Event or
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
Control
Type Type Domain SubDomain EventOrAction
Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Leading kvarh
cleared
Leading kvarh *.26.27.24 * Power PowerFactor OutofRangeCleared
Condition
Cleared
Leading kvarh
caution
*.26.27.40 * Power PowerFactor OutofRange
Leading kvarh
Condition
High distortion
*.26.28.69 * Power PowerQuality HighDistortion
detected
High
Distortion *.26.28.71 * Power PowerQuality HighDistortionCleared
Cleared
Generic Power
*.26.28.40 * Power PowerQuality OutofRange
Quality Event
Recording PowerQualityReco
*.26.80.66 * Power Disabled
disabled rding
Recording PowerQualityReco
*.26.80.76 * Power Enabled
enabled rding
Verify Section
Power
Verify Meter
Power
Verify Feeder *.26.17.68 * Power Status Disconnected
Power
Verify
Transformer
Power
Rf Collector
Power Outage
Power outage
Power out
Undetected
*.26.0.85 * Power n/a Failed
power outage
Last gasp
outage alarm
Transformer
Outage
Loss of power
or voltage on *.26.126.85 * Power PhaseA Failed
phase A
Loss of power
or voltage on *.26.134.85 * Power PhaseB Failed
phase B
Loss of power
or voltage on *.26.135.85 * Power PhaseC Failed
phase C
Meter
Restoration
Power on /
*.26.0.216 * Power n/a Restored
restored
Transformer
Restoration
Restoration of
power or
*.26.126.216 * Power PhaseA Restored
voltage on
phase A
– 216 – 61968-9  IEC:2013

Event or
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
Control
Type Type Domain SubDomain EventOrAction
Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Restoration of
power or
*.26.134.216 * Power PhaseB Restored
voltage on
phase B
Restoration of
power or
*.26.135.216 * Power PhaseC Restored
voltage on
phase C
Voltage
*.26.38.139 * Power Voltage Exceeded
exception
Voltage
Imbalance *.26.38.98 * Power Voltage Imbalanced
Condition
Voltage
Imbalance
*.26.38.75 * Power Voltage ImbalanceCleared
Condition
Cleared
Loss of
voltage
transducer VT
*.26.38.47 * Power Voltage LossDetected
Low loss
potential
detected
High Voltage *.26.38.93 * Power Voltage MaxLimitReached
Low voltage *.26.38.150 * Power Voltage MinLimitReached
Voltage
Imbalance *.26.38.37 * Power Voltage Normal
Cleared
Voltage swell
*.26.38.37 * Power Voltage Normal
cleared
Voltage sag *.26.38.223 * Power Voltage SagStarted
Voltage sag
*.26.38.224 * Power Voltage SagStopped
cleared
Voltage swell
*.26.38.248 * Power Voltage SwellStarted
condition
Voltage swell
*.26.38.249 * Power Voltage SwellStopped
cleared

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of
these events will be relevant to the device that is actually sending this event.

Table E.26 – Pressure events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Sensed pressure
*.29.261.93 * Pressure Threshold MaxLimitReached
equals P max
Sensed pressure
*.29.261.150 * Pressure Threshold MinLimitReached
equals P min
Pressure is out of
*.29.261.40 * Pressure Threshold OutofRange
range

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.
61968-9  IEC:2013 – 217 –

Table E.27 – RCDSwitch events

EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Event or Control
Description Type Type Domain SubDomain EventOrAction
Service turn-on
Status input closure, #
*.31.0.42 * RCDswitch n/a Connected
Meter connected
Connect executed
Connect failed *.31.0.67 * RCDSwitch n/a ConnectFailed
Service turn-off
Status input opening, #
Meter disconnected *.31.0.68 * RCDswitch n/a Disconnected
Breaker operation
Disconnect executed
Connect failed
*.31.0.84 * RCDswitch n/a DisconnectFailed
Disconnect failed

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.28 – Security events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Unauthorized
*.12.1.38 * Security Access NotAuthorized
access attempted
Unit accessed
Unit accessed by
reader *.12.1.58 * Security Access Succeeded
Unit accessed by
recorder
Certificate expiration
alert *.12.21.64 * Security Certificate Expired
Certificate expiration
Cover removal
*.12.29.212 * Security Cover Removed
detected
CRC error *.12.30.79 * Security CRC Error
Decryption Error
*.12.31.63 * Security Data Unsecure
Plain Text
Decryption Error
*.12.36.79 * Security Decryption Error
General
Decryption Failure *.12.36.85 * Security Decryption Failed
Collector Door Event *.12.128.2 * Security Door Accessed
Door closed *.12.141.16 * Security Enclosure Closed
Door opened *.12.141.39 * Security Enclosure Opened
Encoder tamper *.12.40.257 * Security Encoder TamperDetected
Crypto Init Failure *.12.298.85 * Security Initialisation Failed
Reverse flow
*.12.48.219 * Security Flow Reversed
detected
Decryption Error
*.12.54.85 * Security HMAC Failed
HMAC Failure
User login failure
Gateway login *.12.65.85 * Security Login Failed
failure
Magnetic switch
*.12.66.257 * Security MagneticSwitch TamperDetected
alarm
– 218 – 61968-9  IEC:2013

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Physical tamper
Tamper indication
*.12.0.257 * Security n/a TamperDetected
Tamper attempt
suspected
Tilt detected *.12.0.263 * Security n/a Tilted
Configuration Token
*.12.71.35 * Security NetworkId Invalid
Invalid Network ID
Parity error *.12.77.79 * Security Parity Error
Password changed *.12.24.24 * Security Password Changed
Invalid password *.12.24.35 * Security Password Invalid
Unit accessed
*.12.211.58 * Security RemoteAccess Succeeded
remotely
Inverted meter or
reverse rotation
detected *.12.93.219 * Security Rotation Reversed
Reverse Rotation
detected
Read secured
register *.12.98.2 * Security SecuredRegister Accessed
Read secured table
Local key disable *.12.32.66 * Security SecurityKey Disabled
Local key enable *.12.32.76 * Security SecurityKey Enabled
Configuration Token
Message Generation *.12.32.79 * Security SecurityKey Error
Error
Invalid security key *.12.32.35 * Security SecurityKey Invalid
Configuration Token
*.12.32.35 * Security SecurityKey Invalid
Invalid Options
Previous Key Used *.12.32.41 * Security SecurityKey Preempted
Configuration Token
*.12.32.44 * Security SecurityKey Processed
Processed
Local key unlock *.12.32.62 * Security SecurityKey Unlocked
Configuration Token
*.12.119.35 * Security SecurityKeyLength Invalid
Invalid Length
Configuration Token
*.12.120.35 * Security SecurityKeyVersion Invalid
Invalid Version
Signature General
*.12.103.79 * Security Signature Error
Error
Signature Algorithm
Error
Signature Verify
Failure
Signature Algorithm
Error
*.12.103.85 * Security Signature Failed
Signature Verify
Failure
Signature Algorithm
Error
Signature Verify
Failure
61968-9  IEC:2013 – 219 –

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Invalid Signature
Key Specified
Signature
Verification Error
Invalid Signature
Key Specified
*.12.103.35 * Security Signature Invalid
Signature
Verification Error
Invalid Signature
Key Specified
Signature
Verification Error
Signature Missing *.12.103.160 * Security Signature NotFound
Invalid Length *.12.104.35 * Security SignatureLength Invalid
Invalid Signature SignatureTimestam
*.12.105.35 * Security Invalid
Timestamp p
Signature Usage
*.12.106.79 * Security SignatureUsage Error
Error
End device
*.12.282.58 * Security WriteAccess Succeeded
accessed for write

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use
of these events will be relevant to the device that is actually sending this event.

Table E.29 – Temperature events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Temperature returns
*.35.0.37 * Temperature n/a Normal
within range
Temperature is out of
*.35.0.40 * Temperature n/a OutofRange
range
Sensed temperature
*.35.261.93 * Temperature Threshold MaxLimitReached
equals T max
Sensed temperature
*.35.261.150 * Temperature Threshold MinLimitReached
equals T min

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.

Table E.30 – VideoDisplay events

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Display failure *.13.17.85 * VideoDisplay Status Failed

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use
of these events will be relevant to the device that is actually sending this event.
– 220 – 61968-9  IEC:2013

Table E.31 – WaterSupply events


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Event or Control EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


Description Type Type Domain SubDomain EventOrAction

Complete loss of water


*.5.0.47 * WaterSupply n/a Failed
supply
Water supply restored *.5.0.270 * WaterSupply n/a Restored

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production
use of these events will be relevant to the device that is actually sending this event.
61968-9  IEC:2013 – 221 –

Annex F
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceControlType enumerations

F.1 General

Many metering systems have the capability to issue a command to equipment in the field that
takes an action. The action might be to perform a demand-reset, open or close a switch, or a
number of other activities. This Annex F describes example codes that may be used for such
applications.

EndDeviceControlType enumerations are categorized in the same manner as the


EndDeviceEventType enumerations described in Annex E. The code is divided into 4 parts:

EndDeviceControl.type:=
<EndDeviceType>.<EndDeviceDomain>.<EndDeviceSubdomain>.<EndDeviceEventOrAction>

where
<EndDeviceType> a numeric value from the EndDeviceType enumeration (see
EndDeviceType section in Annex E)
<EndDeviceDomain> a numeric value from the EndDeviceDomain enumeration (see
EndDeviceDomain section in Annex E)
<EndDeviceSubdomain> a numeric value from the EndDeviceSubdomain enumeration
(see EndDeviceSubdomain section in Annex E)
<EndDeviceEventOrAction> a numeric value from the EndDeviceEventOrAction enumeration
(see EndDeviceEventOrAction section in Annex E)

These control types are inclusive of the control types used for PAN device controls. Controls
may cause an event to be generated by the end device, which would then be reported using a
EndDeviceEvents message.

F.2 Normative EndDeviceControlType Enumerations

EndDeviceType, EndDeviceDomain, EndDeviceSubdomain, and EndDeviceEventOrAction


fields are combined and presented as a single string. The normative events are listed in the
following Tables F.1 through F.4, grouped by EndDeviceDomain.

Table F.1 – Demand Controls

Event or Control EndDeviceControl Expected EndDevice EndDevice EndDevice


Description Type Events Domain SubDomain EventOrAction
*.8.0.214 *.8.0.215
Reset Demand Demand n/a Reset
*.8.0.65

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of these
events will be relevant to the device that is actually sending this event.
– 222 – 61968-9  IEC:2013

Table F.2 – LoadControl Controls

Event or Control EndDeviceControl Expected EndDevice EndDevice EndDevice


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Description Type Events Domain SubDomain EventOrAction


*.15.17.242
Load control initiate, port 0 *.15.0.54 LoadControl n/a Start
*.15.17.217

Load control *.15.0.55 *.15.17.216


LoadControl n/a Stop
stop/terminate, port 1 *.15.17.218

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of these
events will be relevant to the device that is actually sending this event.

Table F.3 – PAN / HAN Controls

Event or Control EndDeviceControl Expected EndDevice EndDevice EndDevice


Description Type Events Domain SubDomain EventOrAction
PAN Pairing Window Open *.10.73.298 *.10.73.39 Pairing Window Open
PAN Pairing Window
*.10.73.299 *.10.73.16 Pairing Window Close
Close
PAN Text Message
*.13.112.77 *.13.112.78 VideoDisplay TextMessage Display
Display
PAN Text Message Cancel *.13.112.8 *.13.112.10 VideoDisplay TextMessage Cancel
PAN Price Signal Create *.20.9.82 *.20.9.58 Billing Pricing Create

PAN Load Control All *.15.148.8


*.15.148.10 LoadControl AllEvents Cancel
Event Cancel

PAN Load Control Event *.15.43.8 *.15.43.10


LoadControl Event Cancel
Cancel

PAN Load Control Event *.15.43.300 *.15.43.225


LoadControl Event Schedule
Schedule

PAN Network Enable *.23.0.26 *.23.0.76 Network n/a Enable


PAN Network Disable *.23.0.22 *.23.0.66 Network n/a Disable

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of these
events will be relevant to the device that is actually sending this event.

Table F.4 – RCDSwitch Controls

Event or Control EndDeviceControl Expected EndDevice EndDevice EndDevice


Description Type Events Domain SubDomain EventOrAction

Disable RCD Emergency *.31.138.22 *.31.138.66


RCDSwitch EmergencySupplyCapacityLimit Disable
Supply Capacity Limit *.31.138.220

Enable RCD Emergency *.31.138.26 *.31.138.76


RCDSwitch EmergencySupplyCapacityLimit Enable
Supply Capacity Limit *.31.138.221
Arm Remote *.31.0.5 *.31.0.11
Connect/Disconnect RCDSwitch n/a ArmForClosure
Switch for Closure *.31.0.226

Arm Remote *.31.0.6 *.31.0.12


Connect/Disconnect RCDSwitch n/a ArmForOpen
Switch for Open *.31.0.222

Close Remote *.31.0.18 *.31.0.42


Connect/Disconnect RCDSwitch n/a Connect
Switch *.31.0.67
61968-9  IEC:2013 – 223 –

Event or Control EndDeviceControl Expected EndDevice EndDevice EndDevice


Description Type Events Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Disable Demand Limiting


formula #1 for RCD *.31.0.22 *.31.0.66
RCDSwitch n/a Disable
Switch *.31.0.220
Disable RCD Switch
Open Remote *.31.0.23 *.31.0.68
Connect/Disconnect RCDSwitch n/a Disconnect
Switch *.31.0.84

Enable Demand Limiting


formula #2 for RCD *.31.0.26 *.31.0.76
RCDSwitch n/a Enable
Switch *.31.0.221
Enable RCD Switch

Disable RCD Supply *.31.139.22 *.31.139.66


RCDSwitch SupplyCapacityLimit Disable
Capacity Limit *.31.139.220

Enable RCD Supply *.31.139.26 *.31.139.76


RCDSwitch SupplyCapacityLimit Enable
Capacity Limit *.31.139.221

An asterisk (*) denotes any of the EndDeviceType values. It is assumed that the value used in any production use of these events
will be relevant to the device that is actually sending this event.
– 224 – 61968-9  IEC:2013

Annex G
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Conventions for naming and identifying objects

G.1 General

This Annex G describes an example of the use of object identifiers as needed by IEC 61968
messages to maintain synchronization and correlation of information between systems.

G.2 Object identifiers

Figure G.1 – CIM naming

The CIM recognizes that an object can be known by many names. Objects should be given a
“name” by the system of record by using one of the naming elements. Where the mRID value
should be a globally unique identifier using a GUID, the name values are typically more
human friendly and human useful. The uniqueness constraints may also be relaxed, as defned
for rules by a given name type. Uniqueness rules may range from:

• globally unique
• globally unique within a name type and associated name type authority
• unique within a device (e.g. a meter)
• physical location (e.g. a substation)
• no uniqueness constraint.

In all cases, consuming applications need to be aware of uniqueness limitations for a given
name type if any exist.

G.3 Object identifiers within messages

Figure G.1 shows the CIM models used for names. In Figure G.2, the model is seen from the
perspective of an example XML structure that would be realized within a messge profile.
61968-9  IEC:2013 – 225 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure G.2 – Example XML structure for names

Using the above example as a reference, there are a number of important rules that shall be
followed:

An object may be identified using a globally unique mRID

An object may be identified using one or more Name.name values

Both mRID and Name.name values may be supplied

If more than one Name.name value is supplied, each Name should identify a corresponding
NameType.name value

While the IdenitifiedObject.name value is defined in the CIM, it is not used within IEC 61968-9
profiles in order to avoid ambiguities where a producer could choose to use
IdentifiedObject.name, but a consumer could expect IdentifiedObject.Name.name. Therefore,
from the perspective of IEC 61968-9 IdentifiedObject.name is deprecated.

Producers and consumers shall agree upon the use of mRID or Name.name values to be used
for object correlation, where this can vary for a given implementation although the use of
Name.name values is strongly recommended.

In the implementation cases where multiple consumers may exist, a producer may need to
supply multiple Name.name values, each with a different NameType.name in order to support
the specific needs of each consumer.

G.4 Object References within messages

Within message profiles, it is possible to refer to an object "by reference" as well as the
common (nested) 'by value'. These references may be done using mRID or Name.name
values. A common example of this for IEC 61968-9 can be seen for the reference of
ReadingTypes (see Figure G.3).
– 226 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure G.3 – Use of names for references

Within an XML message the "ref" attribute would then identify a specific ReadingType using a
Name.name value for the reading type.This scheme has many benefits, such as reducing the
size of the XML message and allowing for aliasing of objects, where an object can be known
by more than one name.

References are also used to identify specific types of EndDeviceControls or


EndDeviceEvents, using references to an EndDeviceControlType or EndDeviceEventType as
appropriate.
61968-9  IEC:2013 – 227 –

Annex H
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

XML schemas for message payloads

H.1 General

The purpose of this Annex H is to provide XML schemas for message payloads to augment
the descriptions provided earlier in this document. These XML schemas were defined using
profile definitions within CIMTool. These schemas may be extended as needed for specific
implementation needs. This Annex H is supplemented by the informative XML schemas
provided in Annex I.

H.2 CustomerAccountConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerAccountConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/CustomerAccountConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">

<xs:element name="CustomerAccountConfig" type="m:CustomerAccountConfig"/>


<xs:complexType name="CustomerAccountConfig">
<xs:sequence>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="billingCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.billingCycle"/>
<xs:element name="budgetBill" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.budgetBill"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
– 228 – 61968-9  IEC:2013

<xs:element name="revisionNumber" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.ConfigurationEvents"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.3 CustomerAgreementConfig

<?xml version="1.0" encoding="UTF-8"?>


<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerAgreementConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/CustomerAgreementConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="CustomerAgreementConfig" type="m:CustomerAgreementConfig"/>
<xs:complexType name="CustomerAgreementConfig">
61968-9  IEC:2013 – 229 –

<xs:sequence>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="loadMgmt" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.loadMgmt"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="signDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.signDate"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.ConfigurationEvents"/>
<xs:element name="DemandResponsePrograms" type="m:DemandResponseProgram" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement.DemandResponsePrograms"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
– 230 – 61968-9  IEC:2013

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.ServiceCategory"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="validityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.validityInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DemandResponseProgram" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DemandResponseProgram">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
61968-9  IEC:2013 – 231 –

<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.4 CustomerConfig

<?xml version="1.0" encoding="UTF-8"?>


<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/CustomerConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="CustomerConfig" type="m:CustomerConfig"/>
<xs:complexType name="CustomerConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="pucNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.pucNumber"/>
<xs:element name="specialNeed" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.specialNeed"/>
<xs:element name="vip" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.vip"/>
– 232 – 61968-9  IEC:2013

<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.ConfigurationEvents"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.Organisation"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 233 –

<xs:complexType name="Organisation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#Organisation">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone2"/>
<xs:element name="postalAddress" type="m:PostalAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.postalAddress"/>
<xs:element name="streetAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.streetAddress"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PostalAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PostalAddress">
<xs:sequence>
<xs:element name="poBox" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.poBox"/>
<xs:element name="postalCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.postalCode"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
– 234 – 61968-9  IEC:2013

<xs:element name="type" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.5 EndDeviceConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/EndDeviceConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/EndDeviceConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="EndDeviceConfig" type="m:EndDeviceConfig"/>
<xs:complexType name="EndDeviceConfig">
<xs:sequence>
<xs:element name="ComFunction" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ConnectDisconnectFunction" type="m:ConnectDisconnectFunction" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="SimpleEndDeviceFunction" type="m:SimpleEndDeviceFunction" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ActivityRecord" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord">
<xs:sequence>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 235 –

<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Channel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Channel">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.isVirtual"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingType" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Channel.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
– 236 – 61968-9  IEC:2013

<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConnectDisconnectFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConnectDisconnectFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="eventCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction.eventCount"/>
<xs:element name="isConnected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isConnected"/>
<xs:element name="isDelayedDiscon" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isDelayedDiscon"/>
<xs:element name="isLocalAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoDisconOp"/>
<xs:element name="isLocalAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoReconOp"/>
<xs:element name="isRemoteAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoDisconOp"/>
<xs:element name="isRemoteAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoReconOp"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="rcdInfo" type="m:RemoteConnectDisconnectInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction.rcdInfo"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
61968-9  IEC:2013 – 237 –

<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="start" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="installCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.installCode"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:element name="ActivityRecords" type="m:ActivityRecord" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ActivityRecords"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ConfigurationEvents"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="ConnectDisconnectFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
– 238 – 61968-9  IEC:2013

<xs:element name="SimpleEndDeviceFunction" sawsdl:modelReference="">


<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SimpleEndDeviceFunction">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:attribute name="ref" type="xs:string"/>


</xs:complexType>
</xs:element>
</xs:choice>
<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceCapability" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability">
<xs:sequence>
<xs:element name="autonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.autonomousDst"/>
<xs:element name="communication" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.communication"/>
<xs:element name="connectDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.connectDisconnect"/>
<xs:element name="demandResponse" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.demandResponse"/>
<xs:element name="electricMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.electricMetering"/>
<xs:element name="gasMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.gasMetering"/>
<xs:element name="metrology" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.metrology"/>
<xs:element name="onRequestRead" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.onRequestRead"/>
<xs:element name="outageHistory" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.outageHistory"/>
<xs:element name="pressureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pressureCompensation"/>
<xs:element name="pricingInfo" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pricingInfo"/>
<xs:element name="pulseOutput" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pulseOutput"/>
<xs:element name="relaysProgramming" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.relaysProgramming"/>
<xs:element name="reverseFlow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.reverseFlow"/>
<xs:element name="superCompressibilityCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.superCompressibilityCompensation"/>
<xs:element name="temperatureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.temperatureCompensation"/>
<xs:element name="textMessage" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.textMessage"/>
<xs:element name="waterMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.waterMetering"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="EndDeviceFunctionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceFunctionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="autonomousDst"/>
<xs:enumeration value="demandResponse"/>
<xs:enumeration value="electricMetering"/>
<xs:enumeration value="gasMetering"/>
<xs:enumeration value="metrology"/>
<xs:enumeration value="onRequestRead"/>
<xs:enumeration value="outageHistory"/>
<xs:enumeration value="relaysProgramming"/>
61968-9  IEC:2013 – 239 –

<xs:enumeration value="reverseFlow"/>
<xs:enumeration value="waterMetering"/>
</xs:restriction>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:simpleType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="isSolidState" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.isSolidState"/>
<xs:element name="phaseCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.phaseCount"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedCurrent"/>
<xs:element name="ratedVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedVoltage"/>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
<xs:element name="capability" type="m:EndDeviceCapability" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.capability"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.installationDate"/>
<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.manufacturedDate"/>
<xs:element name="purchaseDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
– 240 – 61968-9  IEC:2013

<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#ProductAssetModel">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
<xs:element name="modelNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelNumber"/>
<xs:element name="modelVersion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelVersion"/>
<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingInterharmonic" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 241 –

<xs:complexType name="Register" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#Register">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.isVirtual"/>
<xs:element name="leftDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.leftDigitCount"/>
<xs:element name="rightDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.rightDigitCount"/>
<xs:element name="touTierName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTierName"/>
<xs:element name="Channels" type="m:Channel" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.Channels"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="touTier" type="m:TimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTier"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RemoteConnectDisconnectInfo"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RemoteConnectDisconnectInfo">
<xs:sequence>
<xs:element name="armedTimeout" type="m:Seconds" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.armedTimeout"/>
<xs:element name="customerVoltageLimit" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.customerVoltageLimit"/>
<xs:element name="energyLimit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyLimit"/>
<xs:element name="energyUsageStartDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageStartDateTime"/>
<xs:element name="energyUsageWarning" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageWarning"/>
<xs:element name="isArmConnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmConnect"/>
<xs:element name="isArmDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmDisconnect"/>
<xs:element name="isEnergyLimiting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isEnergyLimiting"/>
<xs:element name="needsPowerLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsPowerLimitCheck"/>
<xs:element name="needsVoltageLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsVoltageLimitCheck"/>
<xs:element name="powerLimit" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.powerLimit"/>
<xs:element name="usePushbutton" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.usePushbutton"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Seal" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal">
<xs:sequence>
<xs:element name="appliedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.appliedDateTime"/>
<xs:element name="condition" type="m:SealConditionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.condition"/>
<xs:element name="kind" type="m:SealKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.kind"/>
<xs:element name="sealNumber" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.sealNumber"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SealConditionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealConditionKind">
– 242 – 61968-9  IEC:2013

<xs:restriction base="xs:string">
<xs:enumeration value="broken"/>
<xs:enumeration value="locked"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="missing"/>
<xs:enumeration value="open"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="SealKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealKind">
<xs:restriction base="xs:string">
<xs:enumeration value="lead"/>
<xs:enumeration value="lock"/>
<xs:enumeration value="other"/>
<xs:enumeration value="steel"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="SimpleEndDeviceFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SimpleEndDeviceFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="kind" type="m:EndDeviceFunctionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction.kind"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Registers" type="m:Register" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.Registers"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.end"/>
<xs:element name="start" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Voltage">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
61968-9  IEC:2013 – 243 –

<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#ActivePower">
<xs:restriction base="xs:float"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:simpleType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Seconds" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seconds">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

H.6 EndDeviceControls
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/EndDeviceControls#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/EndDeviceControls#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="EndDeviceControls" type="m:EndDeviceControls"/>
<xs:complexType name="EndDeviceControls">
<xs:sequence>
<xs:element name="EndDeviceControl" type="m:EndDeviceControl" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceControlType" type="m:EndDeviceControlType"
minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ControlledAppliance" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ControlledAppliance">
<xs:sequence>
<xs:element name="isElectricVehicle" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isElectricVehicle"/>
<xs:element name="isExteriorLighting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isExteriorLighting"/>
<xs:element name="isGenerationSystem" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isGenerationSystem"/>
<xs:element name="isHvacCompressorOrFurnace" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isHvacCompressorOrFurnace"/>
<xs:element name="isInteriorLighting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isInteriorLighting"/>
<xs:element name="isIrrigationPump" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ControlledAppliance.isIrrigationPump"/>
<xs:element name="isManagedCommercialIndustrialLoad" type="xs:boolean"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isManagedCommercialIndustrialLoad"/>
<xs:element name="isPoolPumpSpaJacuzzi" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isPoolPumpSpaJacuzzi"/>
<xs:element name="isSimpleMiscLoad" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ControlledAppliance.isSimpleMiscLoad"/>
<xs:element name="isSmartAppliance" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ControlledAppliance.isSmartAppliance"/>
<xs:element name="isStripAndBaseboardHeater" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isStripAndBaseboardHeater"/>
<xs:element name="isWaterHeater" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ControlledAppliance.isWaterHeater"/>
</xs:sequence>
– 244 – 61968-9  IEC:2013

</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence/>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="installCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.installCode"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceAction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceAction">
<xs:sequence>
<xs:element name="command" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.startDateTime"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControl" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceControl">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="drProgramLevel" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.drProgramLevel"/>
<xs:element name="drProgramMandatory" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.drProgramMandatory"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.issuerTrackingID"/>
61968-9  IEC:2013 – 245 –

<xs:element name="priceSignal" type="m:FloatQuantity" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.priceSignal"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.reason"/>
<xs:choice minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceControl.EndDeviceAction">
<xs:element name="PanDemandResponse" type="m:PanDemandResponse"
sawsdl:modelReference=""/>
<xs:element name="PanDisplay" type="m:PanDisplay"
sawsdl:modelReference=""/>
<xs:element name="PanPricing" type="m:PanPricing"
sawsdl:modelReference=""/>
</xs:choice>
<xs:element name="EndDeviceControlType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.EndDeviceControlType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="EndDeviceGroups" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.EndDeviceGroups"/>
<xs:element name="EndDevices" type="m:EndDevice" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.EndDevices"/>
<xs:element name="primaryDeviceTiming" type="m:EndDeviceTiming" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.primaryDeviceTiming"/>
<xs:element name="secondaryDeviceTiming" type="m:EndDeviceTiming" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.secondaryDeviceTiming"/>
<xs:element name="UsagePointGroups" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.UsagePointGroups"/>
<xs:element name="UsagePoints" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.UsagePoints"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControlType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceControlType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="domain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType.domain"/>
<xs:element name="eventOrAction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType.eventOrAction"/>
<xs:element name="subDomain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType.subDomain"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType.type"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceInfo">
<xs:sequence/>
</xs:complexType>
<xs:complexType name="EndDeviceTiming" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceTiming">
<xs:sequence>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceTiming.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceTiming.durationIndefinite"/>
– 246 – 61968-9  IEC:2013

<xs:element name="randomisation" type="m:RandomisationKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceTiming.randomisation"/>
<xs:element name="interval" type="m:DateTimeInterval" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceTiming.interval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanDemandResponse" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PanDemandResponse">
<xs:sequence>
<xs:element name="avgLoadAdjustment" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.avgLoadAdjustment"/>
<xs:element name="cancelControlMode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.cancelControlMode"/>
<xs:element name="cancelDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.cancelDateTime"/>
<xs:element name="cancelNow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.cancelNow"/>
<xs:element name="command" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="coolingOffset" type="m:Temperature" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.coolingOffset"/>
<xs:element name="coolingSetpoint" type="m:Temperature" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.coolingSetpoint"/>
<xs:element name="criticalityLevel" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.criticalityLevel"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="dutyCycle" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.dutyCycle"/>
<xs:element name="enrollmentGroup" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.enrollmentGroup"/>
<xs:element name="heatingOffset" type="m:Temperature" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.heatingOffset"/>
<xs:element name="heatingSetpoint" type="m:Temperature" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.heatingSetpoint"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.startDateTime"/>
<xs:element name="appliance" type="m:ControlledAppliance" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.appliance"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanDisplay" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDisplay">
<xs:sequence>
61968-9  IEC:2013 – 247 –

<xs:element name="command" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="confirmationRequired" type="xs:boolean" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDisplay.confirmationRequired"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="priority" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDisplay.priority"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.startDateTime"/>
<xs:element name="textMessage" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDisplay.textMessage"/>
<xs:element name="transmissionMode" type="m:TransmissionModeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDisplay.transmissionMode"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanPricing" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricing">
<xs:sequence>
<xs:element name="command" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="providerID" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricing.providerID"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.startDateTime"/>
<xs:element name="PanPricingDetails" type="m:PanPricingDetail" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricing.PanPricingDetails"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanPricingDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PanPricingDetail">
<xs:sequence>
<xs:element name="alternateCostDelivered" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.alternateCostDelivered"/>
<xs:element name="alternateCostUnit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.alternateCostUnit"/>
<xs:element name="currentTimeDate" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.currentTimeDate"/>
<xs:element name="generationPrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.generationPrice"/>
<xs:element name="generationPriceRatio" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.generationPriceRatio"/>
<xs:element name="price" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.price"/>
<xs:element name="priceRatio" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.priceRatio"/>
<xs:element name="priceTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.priceTier"/>
<xs:element name="priceTierCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.priceTierCount"/>
<xs:element name="priceTierLabel" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.priceTierLabel"/>
<xs:element name="rateLabel" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.rateLabel"/>
<xs:element name="registerTier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.registerTier"/>
<xs:element name="unitOfMeasure" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.unitOfMeasure"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RandomisationKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#RandomisationKind">
<xs:restriction base="xs:string">
<xs:enumeration value="default"/>
<xs:enumeration value="end"/>
<xs:enumeration value="none"/>
<xs:enumeration value="start"/>
– 248 – 61968-9  IEC:2013

<xs:enumeration value="startAndEnd"/>
</xs:restriction>
</xs:simpleType>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#ServiceLocation">
<xs:sequence/>
</xs:complexType>
<xs:simpleType name="TransmissionModeKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TransmissionModeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="anonymous"/>
<xs:enumeration value="both"/>
<xs:enumeration value="normal"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="FloatQuantity" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#FloatQuantity">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
<xs:simpleType name="Temperature" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Temperature">
<xs:restriction base="xs:float"/>
</xs:simpleType>
</xs:schema>

H.7 EndDeviceEvents
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/EndDeviceEvents#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/EndDeviceEvents#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="EndDeviceEvents" type="m:EndDeviceEvents"/>
<xs:complexType name="EndDeviceEvents">
<xs:sequence>
<xs:element name="EndDeviceEvent" type="m:EndDeviceEvent" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Asset" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset">
61968-9  IEC:2013 – 249 –

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerTrackingID"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.userID"/>
<xs:element name="Assets" type="m:Asset" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.Assets"/>
<xs:element name="EndDeviceEventDetails" type="m:EndDeviceEventDetail" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.EndDeviceEventDetails"/>
<xs:element name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.EndDeviceEventType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventDetail">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventDetail.name"/>
<xs:element name="value" type="m:StringQuantity" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="domain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.domain"/>
<xs:element name="eventOrAction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.eventOrAction"/>
<xs:element name="subDomain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.subDomain"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.type"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
– 250 – 61968-9  IEC:2013

</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="StringQuantity" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StringQuantity">
<xs:restriction base="xs:string"/>
</xs:simpleType>
</xs:schema>

H.8 GetCustomerAccountConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetCustomerAccountConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetCustomerAccountConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetCustomerAccountConfig" type="m:GetCustomerAccountConfig"/>
<xs:complexType name="GetCustomerAccountConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
61968-9  IEC:2013 – 251 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
– 252 – 61968-9  IEC:2013

<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.9 GetCustomerAgreementConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetCustomerAgreementConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetCustomerAgreementConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetCustomerAgreementConfig" type="m:GetCustomerAgreementConfig"/>
<xs:complexType name="GetCustomerAgreementConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
61968-9  IEC:2013 – 253 –

</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
– 254 – 61968-9  IEC:2013

<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.10 GetCustomerConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetCustomerConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetCustomerConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetCustomerConfig" type="m:GetCustomerConfig"/>
<xs:complexType name="GetCustomerConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  IEC:2013 – 255 –

<xs:element name="kind" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#Customer.kind">
<xs:simpleType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerKind">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
– 256 – 61968-9  IEC:2013

</xs:sequence>
</xs:complexType>
</xs:schema>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

H.11 GetEndDeviceConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetEndDeviceConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetEndDeviceConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetEndDeviceConfig" type="m:GetEndDeviceConfig"/>
<xs:complexType name="GetEndDeviceConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
61968-9  IEC:2013 – 257 –

<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 258 – 61968-9  IEC:2013

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.12 GetEndDeviceControls
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetEndDeviceControls#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetEndDeviceControls#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetEndDeviceControls" type="m:GetEndDeviceControls"/>
<xs:complexType name="GetEndDeviceControls">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceControl" type="m:EndDeviceControl" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceControlType" type="m:EndDeviceControlType"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 259 –

<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#CustomerAccount">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControl" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceControl">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.issuerTrackingID"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.reason"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControlType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceControlType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
– 260 – 61968-9  IEC:2013

</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 261 –

<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#TimeSchedule">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="scheduleInterval" type="m:DateTimeInterval"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.13 GetEndDeviceEvents
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetEndDeviceEvents#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetEndDeviceEvents#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetEndDeviceEvents" type="m:GetEndDeviceEvents"/>
<xs:complexType name="GetEndDeviceEvents">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceEvent" type="m:EndDeviceEvent" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
– 262 – 61968-9  IEC:2013

</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerTrackingID"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
61968-9  IEC:2013 – 263 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 264 – 61968-9  IEC:2013

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.14 GetMeterConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetMeterConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/GetMeterConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetMeterConfig" type="m:GetMeterConfig"/>
<xs:complexType name="GetMeterConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
61968-9  IEC:2013 – 265 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
– 266 – 61968-9  IEC:2013

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.15 GetMeterReadings
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetMeterReadings#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/GetMeterReadings#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetMeterReadings" type="m:GetMeterReadings"/>
<xs:complexType name="GetMeterReadings">
<xs:sequence>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="MeterReadings" type="m:MeterReadings" minOccurs="0"/>
<xs:element name="Reading" type="m:Reading" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingQuality" type="m:ReadingQuality" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="TransformerTank" type="m:TransformerTank" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CoincidentReading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Reading">
<xs:sequence>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.reason"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="ReadingType" type="m:ReadingType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.ReadingType"/>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
61968-9  IEC:2013 – 267 –

<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="start" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.EndDeviceEventType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterReadings" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading">
<xs:sequence>
<xs:element name="isCoincidentTrigger" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.isCoincidentTrigger"/>
<xs:element name="EndDeviceEvents" type="m:EndDeviceEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.EndDeviceEvents"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Meter"/>
<xs:element name="Readings" type="m:CoincidentReading" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Readings"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
– 268 – 61968-9  IEC:2013

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Reading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Reading">
<xs:sequence>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.reason"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingQuality" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQuality">
<xs:sequence>
<xs:element name="ReadingQualityType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQuality.ReadingQualityType">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQualityType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.scheduleInterval"/>
61968-9  IEC:2013 – 269 –

</xs:sequence>
</xs:complexType>
<xs:complexType name="TransformerTank" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#TransformerTank">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.16 GetServiceCategoryConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetServiceCategoryConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetServiceCategoryConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetServiceCategoryConfig" type="m:GetServiceCategoryConfig"/>
<xs:complexType name="GetServiceCategoryConfig">
<xs:sequence>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
– 270 – 61968-9  IEC:2013

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
</xs:schema>

H.17 GetServiceLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetServiceLocationConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetServiceLocationConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetServiceLocationConfig" type="m:GetServiceLocationConfig"/>
<xs:complexType name="GetServiceLocationConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
61968-9  IEC:2013 – 271 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 272 – 61968-9  IEC:2013

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.18 GetServiceSupplierConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetServiceSupplierConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetServiceSupplierConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetServiceSupplierConfig" type="m:GetServiceSupplierConfig"/>
<xs:complexType name="GetServiceSupplierConfig">
<xs:sequence>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
61968-9  IEC:2013 – 273 –

<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
</xs:schema>

H.19 GetUsagePointConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetUsagePointConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetUsagePointConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetUsagePointConfig" type="m:GetUsagePointConfig"/>
<xs:complexType name="GetUsagePointConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
– 274 – 61968-9  IEC:2013

<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
61968-9  IEC:2013 – 275 –

<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.20 GetUsagePointLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetUsagePointLocationConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetUsagePointLocationConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetUsagePointLocationConfig" type="m:GetUsagePointLocationConfig"/>
<xs:complexType name="GetUsagePointLocationConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
– 276 – 61968-9  IEC:2013

<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"


maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 277 –

<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#NameTypeAuthority">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
– 278 – 61968-9  IEC:2013

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.21 MasterDataLinkageConfig

<?xml version="1.0" encoding="UTF-8"?>


<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/MasterDataLinkageConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/MasterDataLinkageConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="MasterDataLinkageConfig" type="m:MasterDataLinkageConfig"/>
<xs:complexType name="MasterDataLinkageConfig">
<xs:sequence>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ComModule" type="m:ComModule" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ConfigurationEvent" type="m:ConfigurationEvent" minOccurs="0"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="TransformerTank" type="m:TransformerTank" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComModule">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
61968-9  IEC:2013 – 279 –

<xs:element name="remark" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
– 280 – 61968-9  IEC:2013

<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#NameTypeAuthority">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TransformerTank" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TransformerTank">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 281 –

</xs:schema>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

H.22 MeterConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/MeterConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/MeterConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="MeterConfig" type="m:MeterConfig"/>
<xs:complexType name="MeterConfig">
<xs:sequence>
<xs:element name="ComFunction" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ConnectDisconnectFunction" type="m:ConnectDisconnectFunction" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="SimpleEndDeviceFunction" type="m:SimpleEndDeviceFunction" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ActivityRecord" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord">
<xs:sequence>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Channel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Channel">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.isVirtual"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingType" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Channel.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
– 282 – 61968-9  IEC:2013

<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#ComFunction">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConnectDisconnectFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConnectDisconnectFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
61968-9  IEC:2013 – 283 –

<xs:element name="eventCount" type="xs:integer" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction.eventCount"/>
<xs:element name="isConnected" type="xs:boolean" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isConnected"/>
<xs:element name="isDelayedDiscon" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isDelayedDiscon"/>
<xs:element name="isLocalAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoDisconOp"/>
<xs:element name="isLocalAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoReconOp"/>
<xs:element name="isRemoteAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoDisconOp"/>
<xs:element name="isRemoteAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoReconOp"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="Names" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
<xs:element name="rcdInfo" type="m:RemoteConnectDisconnectInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction.rcdInfo"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
– 284 – 61968-9  IEC:2013

</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceCapability" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability">
<xs:sequence>
<xs:element name="autonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.autonomousDst"/>
<xs:element name="communication" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.communication"/>
<xs:element name="connectDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.connectDisconnect"/>
<xs:element name="demandResponse" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.demandResponse"/>
<xs:element name="electricMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.electricMetering"/>
<xs:element name="gasMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.gasMetering"/>
<xs:element name="metrology" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.metrology"/>
<xs:element name="onRequestRead" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.onRequestRead"/>
<xs:element name="outageHistory" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.outageHistory"/>
<xs:element name="pressureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pressureCompensation"/>
<xs:element name="pricingInfo" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pricingInfo"/>
<xs:element name="pulseOutput" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pulseOutput"/>
<xs:element name="relaysProgramming" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.relaysProgramming"/>
<xs:element name="reverseFlow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.reverseFlow"/>
<xs:element name="superCompressibilityCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.superCompressibilityCompensation"/>
<xs:element name="temperatureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.temperatureCompensation"/>
<xs:element name="textMessage" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.textMessage"/>
<xs:element name="waterMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.waterMetering"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="EndDeviceFunctionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceFunctionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="autonomousDst"/>
<xs:enumeration value="demandResponse"/>
<xs:enumeration value="electricMetering"/>
<xs:enumeration value="gasMetering"/>
<xs:enumeration value="metrology"/>
61968-9  IEC:2013 – 285 –

<xs:enumeration value="onRequestRead"/>
<xs:enumeration value="outageHistory"/>
<xs:enumeration value="relaysProgramming"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="reverseFlow"/>
<xs:enumeration value="waterMetering"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="isSolidState" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.isSolidState"/>
<xs:element name="phaseCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.phaseCount"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedCurrent"/>
<xs:element name="ratedVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedVoltage"/>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
<xs:element name="capability" type="m:EndDeviceCapability" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.capability"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.installationDate"/>
<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.manufacturedDate"/>
<xs:element name="purchaseDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="formNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.formNumber"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
– 286 – 61968-9  IEC:2013

<xs:element name="ActivityRecords" type="m:ActivityRecord" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ActivityRecords"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ConfigurationEvents"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="ConnectDisconnectFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="SimpleEndDeviceFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SimpleEndDeviceFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:choice>
<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="MeterMultipliers" type="m:MeterMultiplier" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.MeterMultipliers"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:MeterMultiplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.kind"/>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="MeterMultiplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="kE"/>
<xs:enumeration value="kH"/>
<xs:enumeration value="kR"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
61968-9  IEC:2013 – 287 –

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel">
<xs:sequence>
<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
<xs:element name="modelNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelNumber"/>
<xs:element name="modelVersion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelVersion"/>
<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingInterharmonic" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
– 288 – 61968-9  IEC:2013

<xs:element name="multiplier" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Register" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Register">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.isVirtual"/>
<xs:element name="leftDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.leftDigitCount"/>
<xs:element name="rightDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.rightDigitCount"/>
<xs:element name="touTierName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTierName"/>
<xs:element name="Channels" type="m:Channel" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.Channels"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="touTier" type="m:TimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTier"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RemoteConnectDisconnectInfo"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RemoteConnectDisconnectInfo">
<xs:sequence>
<xs:element name="armedTimeout" type="m:Seconds" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.armedTimeout"/>
<xs:element name="customerVoltageLimit" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.customerVoltageLimit"/>
<xs:element name="energyLimit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyLimit"/>
<xs:element name="energyUsageStartDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageStartDateTime"/>
<xs:element name="energyUsageWarning" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageWarning"/>
<xs:element name="isArmConnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmConnect"/>
<xs:element name="isArmDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmDisconnect"/>
<xs:element name="isEnergyLimiting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isEnergyLimiting"/>
<xs:element name="needsPowerLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsPowerLimitCheck"/>
<xs:element name="needsVoltageLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsVoltageLimitCheck"/>
<xs:element name="powerLimit" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.powerLimit"/>
<xs:element name="usePushbutton" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.usePushbutton"/>
61968-9  IEC:2013 – 289 –

</xs:sequence>
</xs:complexType>
<xs:complexType name="Seal" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="appliedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.appliedDateTime"/>
<xs:element name="condition" type="m:SealConditionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.condition"/>
<xs:element name="kind" type="m:SealKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.kind"/>
<xs:element name="sealNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.sealNumber"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SealConditionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealConditionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="broken"/>
<xs:enumeration value="locked"/>
<xs:enumeration value="missing"/>
<xs:enumeration value="open"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="SealKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealKind">
<xs:restriction base="xs:string">
<xs:enumeration value="lead"/>
<xs:enumeration value="lock"/>
<xs:enumeration value="other"/>
<xs:enumeration value="steel"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="SimpleEndDeviceFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SimpleEndDeviceFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="kind" type="m:EndDeviceFunctionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction.kind"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Registers" type="m:Register" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.Registers"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
– 290 – 61968-9  IEC:2013

<xs:complexType name="TimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#TimeInterval">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="end" type="xs:time" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.end"/>
<xs:element name="start" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Voltage">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivePower">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Seconds" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seconds">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

H.23 MeterReadings
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/MeterReadings#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/MeterReadings#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="MeterReadings" type="m:MeterReadings"/>
<xs:complexType name="MeterReadings">
<xs:sequence>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="MeterReading" type="m:MeterReading" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingQualityType" type="m:ReadingQualityType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Asset" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
61968-9  IEC:2013 – 291 –

<xs:element name="start" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="EndDeviceEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerTrackingID"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.userID"/>
<xs:element name="Assets" type="m:Asset" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.Assets"/>
<xs:element name="EndDeviceEventDetails" type="m:EndDeviceEventDetail" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.EndDeviceEventDetails"/>
<xs:element name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.EndDeviceEventType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventDetail">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventDetail.name"/>
<xs:element name="value" type="m:StringQuantity" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="domain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.domain"/>
<xs:element name="eventOrAction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.eventOrAction"/>
<xs:element name="subDomain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.subDomain"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.type"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="IntervalBlock" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IntervalBlock">
<xs:sequence>
<xs:element name="IntervalReadings" type="m:IntervalReading" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IntervalBlock.IntervalReadings"/>
<xs:element name="PendingCalculation" type="m:PendingCalculation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IntervalBlock.PendingCalculation"/>
<xs:element name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IntervalBlock.ReadingType">
<xs:complexType sawsdl:modelReference="">
– 292 – 61968-9  IEC:2013

<xs:attribute name="ref" type="xs:string"/>


</xs:complexType>
</xs:element>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:sequence>
</xs:complexType>
<xs:complexType name="IntervalReading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IntervalReading">
<xs:sequence>
<xs:element name="reportedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.reportedDateTime"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeasurementValue.timeStamp"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.value"/>
<xs:element name="ReadingQualities" type="m:ReadingQuality" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.ReadingQualities"/>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterReading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading">
<xs:sequence>
<xs:element name="isCoincidentTrigger" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.isCoincidentTrigger"/>
<xs:element name="EndDeviceEvents" type="m:EndDeviceEvent" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.EndDeviceEvents"/>
<xs:element name="IntervalBlocks" type="m:IntervalBlock" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.IntervalBlocks"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Meter"/>
<xs:element name="Readings" type="m:Reading" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Readings"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.UsagePoint"/>
<xs:element name="valuesInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.valuesInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
61968-9  IEC:2013 – 293 –

<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="PendingCalculation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PendingCalculation">
<xs:sequence>
<xs:element name="multiplyBeforeAdd" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PendingCalculation.multiplyBeforeAdd"/>
<xs:element name="offset" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PendingCalculation.offset"/>
<xs:element name="scalarDenominator" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PendingCalculation.scalarDenominator"/>
<xs:element name="scalarFloat" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PendingCalculation.scalarFloat"/>
<xs:element name="scalarNumerator" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PendingCalculation.scalarNumerator"/>
<xs:element name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PendingCalculation.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Reading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Reading">
<xs:sequence>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.reason"/>
<xs:element name="reportedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.reportedDateTime"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeasurementValue.timeStamp"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.value"/>
<xs:element name="ReadingQualities" type="m:ReadingQuality" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.ReadingQualities"/>
<xs:element name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Reading.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingInterharmonic" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingQuality" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQuality">
<xs:sequence>
<xs:element name="comment" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.comment"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.source"/>
– 294 – 61968-9  IEC:2013

<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.timeStamp"/>
<xs:element name="ReadingQualityType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#ReadingQuality.ReadingQualityType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingQualityType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQualityType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="category" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType.category"/>
<xs:element name="subCategory" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType.subCategory"/>
<xs:element name="systemId" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType.systemId"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
61968-9  IEC:2013 – 295 –

<xs:element name="argument" type="m:RationalNumber" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="StringQuantity" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StringQuantity">
<xs:restriction base="xs:string"/>
</xs:simpleType>
</xs:schema>

H.24 ServiceCategoryConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ServiceCategoryConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/ServiceCategoryConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="ServiceCategoryConfig" type="m:ServiceCategoryConfig"/>
<xs:complexType name="ServiceCategoryConfig">
<xs:sequence>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
– 296 – 61968-9  IEC:2013

</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.ConfigurationEvents"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
</xs:schema>
61968-9  IEC:2013 – 297 –

H.25 ServiceLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"


xmlns:m="http://iec.ch/TC57/2011/ServiceLocationConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/ServiceLocationConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="ServiceLocationConfig" type="m:ServiceLocationConfig"/>
<xs:complexType name="ServiceLocationConfig">
<xs:sequence>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CoordinateSystem" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CoordinateSystem">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="crsUrn" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CoordinateSystem.crsUrn"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
– 298 – 61968-9  IEC:2013

<xs:element name="NameType" type="m:NameType" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PositionPoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PositionPoint">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.sequenceNumber"/>
<xs:element name="xPosition" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PositionPoint.xPosition"/>
<xs:element name="yPosition" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PositionPoint.yPosition"/>
<xs:element name="zPosition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.zPosition"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.accessMethod"/>
<xs:element name="direction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.direction"/>
<xs:element name="geoInfoReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.geoInfoReference"/>
<xs:element name="needsInspection" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.needsInspection"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.siteAccessProblem"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.ConfigurationEvents"/>
<xs:element name="CoordinateSystem" type="m:CoordinateSystem" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.CoordinateSystem"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.electronicAddress"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone2"/>
<xs:element name="PositionPoints" type="m:PositionPoint" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.PositionPoints"/>
<xs:element name="secondaryAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.secondaryAddress"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.status"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 299 –

<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#Status">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
– 300 – 61968-9  IEC:2013

<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
</xs:schema>

H.26 ServiceSupplierConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ServiceSupplierConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/ServiceSupplierConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="ServiceSupplierConfig" type="m:ServiceSupplierConfig"/>
<xs:complexType name="ServiceSupplierConfig">
<xs:sequence>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 301 –

<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#NameType">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Organisation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Organisation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone2"/>
<xs:element name="postalAddress" type="m:PostalAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.postalAddress"/>
<xs:element name="streetAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.streetAddress"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PostalAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PostalAddress">
<xs:sequence>
<xs:element name="poBox" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.poBox"/>
<xs:element name="postalCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.postalCode"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerIdentificationNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier.issuerIdentificationNumber"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.ConfigurationEvents"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.Organisation"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
– 302 – 61968-9  IEC:2013

<xs:element name="reason" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
61968-9  IEC:2013 – 303 –

<xs:element name="section" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.27 UsagePointConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/UsagePointConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/UsagePointConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="UsagePointConfig" type="m:UsagePointConfig"/>
<xs:complexType name="UsagePointConfig">
<xs:sequence>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AmiBillingReadyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AmiBillingReadyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="amiCapable"/>
<xs:enumeration value="amiDisabled"/>
<xs:enumeration value="billingApproved"/>
<xs:enumeration value="enabled"/>
<xs:enumeration value="nonAmi"/>
<xs:enumeration value="nonMetered"/>
<xs:enumeration value="operable"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MetrologyRequirement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MetrologyRequirement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.reason"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingTypes" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.ReadingTypes">
<xs:complexType sawsdl:modelReference="">
– 304 – 61968-9  IEC:2013

<xs:attribute name="ref" type="xs:string"/>


</xs:complexType>
</xs:element>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="PhaseCode" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PhaseCode">
<xs:restriction base="xs:string">
<xs:enumeration value="A"/>
<xs:enumeration value="AB"/>
<xs:enumeration value="ABC"/>
<xs:enumeration value="ABCN"/>
<xs:enumeration value="ABN"/>
<xs:enumeration value="AC"/>
<xs:enumeration value="ACN"/>
<xs:enumeration value="AN"/>
<xs:enumeration value="B"/>
<xs:enumeration value="BC"/>
<xs:enumeration value="BCN"/>
<xs:enumeration value="BN"/>
<xs:enumeration value="C"/>
<xs:enumeration value="CN"/>
<xs:enumeration value="N"/>
<xs:enumeration value="s1"/>
<xs:enumeration value="s12"/>
<xs:enumeration value="s12N"/>
<xs:enumeration value="s1N"/>
<xs:enumeration value="s2"/>
<xs:enumeration value="s2N"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
61968-9  IEC:2013 – 305 –

<xs:element name="numerator" type="xs:integer"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="ReadingInterharmonic" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 306 – 61968-9  IEC:2013

<xs:element name="kind" type="m:ServiceKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceMultiplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.kind"/>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceMultiplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 307 –

<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#SupplierKind">
<xs:restriction base="xs:string">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="TransformerTank" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TransformerTank">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amiBillingReady" type="m:AmiBillingReadyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.amiBillingReady"/>
<xs:element name="checkBilling" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.checkBilling"/>
<xs:element name="connectionState" type="m:UsagePointConnectedKind"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.connectionState"/>
<xs:element name="estimatedLoad" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.estimatedLoad"/>
<xs:element name="grounded" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.grounded"/>
<xs:element name="isSdp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isSdp"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isVirtual"/>
<xs:element name="minimalUsageExpected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.minimalUsageExpected"/>
<xs:element name="nominalServiceVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.nominalServiceVoltage"/>
<xs:element name="outageRegion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.outageRegion"/>
<xs:element name="phaseCode" type="m:PhaseCode" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.phaseCode"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedCurrent"/>
<xs:element name="ratedPower" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedPower"/>
<xs:element name="readCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.readCycle"/>
<xs:element name="readRoute" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.readRoute"/>
<xs:element name="serviceDeliveryRemark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.serviceDeliveryRemark"/>
<xs:element name="servicePriority" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.servicePriority"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.ConfigurationEvents"/>
<xs:element name="Equipments" type="m:TransformerTank" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.Equipments"/>
<xs:element name="MetrologyRequirements" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.MetrologyRequirements">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MetrologyRequirement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="reason" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.reason">
<xs:simpleType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration
value="billing"/>
– 308 – 61968-9  IEC:2013

<xs:enumeration
value="demandReset"/>
<xs:enumeration
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

value="inquiry"/>
<xs:enumeration
value="installation"/>
<xs:enumeration
value="loadManagement"/>
<xs:enumeration
value="loadResearch"/>
<xs:enumeration
value="moveIn"/>
<xs:enumeration
value="moveOut"/>
<xs:enumeration
value="other"/>
<xs:enumeration
value="removal"/>
<xs:enumeration
value="serviceConnect"/>
<xs:enumeration
value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
</xs:element>
<xs:element name="Names" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name"
type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType">
<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>

<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#NameType.name"/>

<xs:element name="NameTypeAuthority" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority">

<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">

<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>

</xs:sequence>

</xs:complexType>

</xs:element>

</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
<xs:element name="ReadingTypes" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.ReadingTypes">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref"
type="xs:string"/>
61968-9  IEC:2013 – 309 –

</xs:complexType>
</xs:element>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="PricingStructures" type="m:PricingStructure" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.PricingStructures"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceCategory"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceLocation"/>
<xs:element name="ServiceMultipliers" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceMultipliers">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.kind">
<xs:simpleType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration
value="ctRatio"/>
<xs:enumeration
value="ptRatio"/>
<xs:enumeration
value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
</xs:element>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.value"/>
<xs:element name="Names" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name"
type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType">
<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>

<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#NameType.name"/>

<xs:element name="NameTypeAuthority" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority">

<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">

<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>

</xs:sequence>

</xs:complexType>

</xs:element>
– 310 – 61968-9  IEC:2013

</xs:sequence>
</xs:complexType>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceSupplier"/>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.UsagePointLocation"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="UsagePointConnectedKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointConnectedKind">
<xs:restriction base="xs:string">
<xs:enumeration value="connected"/>
<xs:enumeration value="logicallyDisconnected"/>
<xs:enumeration value="physicallyDisconnected"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePointLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Voltage">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivePower">
<xs:restriction base="xs:float"/>
</xs:simpleType>
</xs:schema>

H.28 UsagePointLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/UsagePointLocationConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/UsagePointLocationConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="UsagePointLocationConfig" type="m:UsagePointLocationConfig"/>
<xs:complexType name="UsagePointLocationConfig">
<xs:sequence>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
61968-9  IEC:2013 – 311 –

<xs:element name="reason" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CoordinateSystem" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CoordinateSystem">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="crsUrn" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CoordinateSystem.crsUrn"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PositionPoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PositionPoint">
– 312 – 61968-9  IEC:2013

<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.sequenceNumber"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="xPosition" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#PositionPoint.xPosition"/>
<xs:element name="yPosition" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PositionPoint.yPosition"/>
<xs:element name="zPosition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.zPosition"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 313 –

<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#TownDetail">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="code" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointLocation.accessMethod"/>
<xs:element name="direction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.direction"/>
<xs:element name="geoInfoReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.geoInfoReference"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointLocation.remark"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointLocation.siteAccessProblem"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.ConfigurationEvents"/>
<xs:element name="CoordinateSystem" type="m:CoordinateSystem" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.CoordinateSystem"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.electronicAddress"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone2"/>
<xs:element name="PositionPoints" type="m:PositionPoint" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.PositionPoints"/>
<xs:element name="secondaryAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.secondaryAddress"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.status"/>
</xs:sequence>
</xs:complexType>
</xs:schema>
– 314 – 61968-9  IEC:2013

Annex I
(informative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

XML schemas for message payloads

I.1 General

The purpose of this Annex I is to provide informative XML schemas for message payloads to
augment the descriptions provided earlier in this document. These XML Schemas were
defined using profile definitions within CIMTool. These schemas may be extended as needed
for specific implementation needs. These schemas may be revised or promoted to a
normative status in a future edition.

I.2 AuxiliaryAgreementConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch C57/2011/AuxiliaryAgreementConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch
C57/2011/AuxiliaryAgreementConfig#" elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="AuxiliaryAgreementConfig" type="m:AuxiliaryAgreementConfig"/>
<xs:complexType name="AuxiliaryAgreementConfig">
<xs:sequence>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AccountMovement" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AccountMovement">
<xs:sequence>
<xs:element name="amount" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AccountMovement.amount"/>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountMovement.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AccountMovement.reason"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AccountingUnit" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AccountingUnit">
<xs:sequence>
<xs:element name="energyUnit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountingUnit.energyUnit"/>
<xs:element name="monetaryUnit" type="m:Currency" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountingUnit.monetaryUnit"/>
<xs:element name="multiplier" type="m:UnitMultiplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountingUnit.multiplier"/>
<xs:element name="value" type="xs:float" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AccountingUnit.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAccount" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="balance" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAccount.balance"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="principleAmount" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.principleAmount"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.subject"/>
61968-9  IEC:2013 – 315 –

<xs:element name="title" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch


C57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="Charges" type="m:Charge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.Charges"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="due" type="m:Due" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAccount.due"/>
<xs:element name="lastCredit" type="m:AccountMovement" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.lastCredit"/>
<xs:element name="lastDebit" type="m:AccountMovement" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.lastDebit"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="arrearsInterest" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAgreement.arrearsInterest"/>
<xs:element name="auxCycle" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.auxCycle"/>
<xs:element name="auxPriorityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAgreement.auxPriorityCode"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="fixedAmount" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.fixedAmount"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="minAmount" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.minAmount"/>
<xs:element name="payCycle" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.payCycle"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="signDate" type="xs:date" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Agreement.signDate"/>
<xs:element name="subject" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="subType" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.subType"/>
<xs:element name="title" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="vendPortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAgreement.vendPortion"/>
<xs:element name="vendPortionArrear" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement.vendPortionArrear"/>
<xs:element name="AuxiliaryAccounts" type="m:AuxiliaryAccount" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement.AuxiliaryAccounts"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.ConfigurationEvents"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement.CustomerAgreement"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="validityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Agreement.validityInterval"/>
</xs:sequence>
</xs:complexType>
– 316 – 61968-9  IEC:2013

<xs:complexType name="Charge" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-


cim15#Charge">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch


C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="ChildCharges" type="m:ChildCharge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.ChildCharges"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ChargeKind" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#ChargeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="auxiliaryCharge"/>
<xs:enumeration value="consumptionCharge"/>
<xs:enumeration value="demandCharge"/>
<xs:enumeration value="other"/>
<xs:enumeration value="taxCharge"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ChildCharge" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Currency" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#Currency">
<xs:restriction base="xs:string">
<xs:enumeration value="AUD"/>
<xs:enumeration value="CAD"/>
<xs:enumeration value="CHF"/>
<xs:enumeration value="CNY"/>
<xs:enumeration value="DKK"/>
61968-9  IEC:2013 – 317 –

<xs:enumeration value="EUR"/>
<xs:enumeration value="GBP"/>
<xs:enumeration value="INR"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="JPY"/>
<xs:enumeration value="NOK"/>
<xs:enumeration value="RUR"/>
<xs:enumeration value="SEK"/>
<xs:enumeration value="USD"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Due" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Due">
<xs:sequence>
<xs:element name="arrears" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.arrears"/>
<xs:element name="charges" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.charges"/>
<xs:element name="current" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.current"/>
<xs:element name="interest" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.interest"/>
<xs:element name="principle" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.principle"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch C57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch C57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch C57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Status.dateTime"/>
– 318 – 61968-9  IEC:2013

<xs:element name="reason" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch


C57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="UnitMultiplier" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#UnitMultiplier">
<xs:restriction base="xs:string">
<xs:enumeration value="G"/>
<xs:enumeration value="M"/>
<xs:enumeration value="T"/>
<xs:enumeration value="c"/>
<xs:enumeration value="d"/>
<xs:enumeration value="k"/>
<xs:enumeration value="m"/>
<xs:enumeration value="micro"/>
<xs:enumeration value="n"/>
<xs:enumeration value="none"/>
<xs:enumeration value="p"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

I.3 ComModuleConfig

<?xml version="1.0" encoding="UTF-8"?>


<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ComModuleConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/ComModuleConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="ComModuleConfig" type="m:ComModuleConfig"/>
<xs:complexType name="ComModuleConfig">
<xs:sequence>
<xs:element name="ComFunction" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ComModule" type="m:ComModule" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ActivityRecord" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
61968-9  IEC:2013 – 319 –

<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComModule">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="supportsAutonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.supportsAutonomousDst"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:element name="ActivityRecords" type="m:ActivityRecord" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ActivityRecords"/>
<xs:element name="AssetInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.AssetInfo"/>
– 320 – 61968-9  IEC:2013

<xs:element name="ComFunctions" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.ComFunctions">
<xs:complexType sawsdl:modelReference="">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:attribute name="ref" type="xs:string"/>


</xs:complexType>
</xs:element>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ConfigurationEvents"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
61968-9  IEC:2013 – 321 –

<xs:element name="mac" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.installationDate"/>
<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.manufacturedDate"/>
<xs:element name="purchaseDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel">
<xs:sequence>
– 322 – 61968-9  IEC:2013

<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="modelNumber" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelNumber"/>
<xs:element name="modelVersion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelVersion"/>
<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

I.4 CustomerMeterDataSet
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerMeterDataSet#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/CustomerMeterDataSet#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="CustomerMeterDataSet" type="m:CustomerMeterDataSet"/>
<xs:complexType name="CustomerMeterDataSet">
<xs:sequence>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AccountingUnit" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AccountingUnit">
<xs:sequence>
<xs:element name="energyUnit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.energyUnit"/>
<xs:element name="monetaryUnit" type="m:Currency" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.monetaryUnit"/>
<xs:element name="multiplier" type="m:UnitMultiplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.multiplier"/>
<xs:element name="value" type="xs:float" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AccountingUnit.value"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AmiBillingReadyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AmiBillingReadyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="amiCapable"/>
<xs:enumeration value="amiDisabled"/>
<xs:enumeration value="billingApproved"/>
<xs:enumeration value="enabled"/>
61968-9  IEC:2013 – 323 –

<xs:enumeration value="nonAmi"/>
<xs:enumeration value="nonMetered"/>
<xs:enumeration value="operable"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:restriction>
</xs:simpleType>
<xs:complexType name="AssetInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AssetInfo">
<xs:sequence>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Channel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Channel">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.isVirtual"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingType" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Channel.ReadingType">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Charge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="ChildCharges" type="m:ChildCharge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.ChildCharges"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ChargeKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ChargeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="auxiliaryCharge"/>
<xs:enumeration value="consumptionCharge"/>
<xs:enumeration value="demandCharge"/>
<xs:enumeration value="other"/>
<xs:enumeration value="taxCharge"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ChildCharge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
– 324 – 61968-9  IEC:2013

<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="fixedPortion" type="m:AccountingUnit"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComModule">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="supportsAutonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.supportsAutonomousDst"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:element name="AssetInfo" type="m:AssetInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.AssetInfo"/>
<xs:element name="ComFunctions" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.ComFunctions"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
61968-9  IEC:2013 – 325 –

<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConnectDisconnectFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConnectDisconnectFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="eventCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.eventCount"/>
<xs:element name="isConnected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isConnected"/>
<xs:element name="isDelayedDiscon" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isDelayedDiscon"/>
<xs:element name="isLocalAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoDisconOp"/>
<xs:element name="isLocalAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoReconOp"/>
<xs:element name="isRemoteAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoDisconOp"/>
<xs:element name="isRemoteAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoReconOp"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="rcdInfo" type="m:RemoteConnectDisconnectInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction.rcdInfo"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConsumptionTariffInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConsumptionTariffInterval">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConsumptionTariffInterval.sequenceNumber"/>
<xs:element name="startValue" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConsumptionTariffInterval.startValue"/>
<xs:element name="Charges" type="m:Charge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConsumptionTariffInterval.Charges"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CoordinateSystem" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CoordinateSystem">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 326 – 61968-9  IEC:2013

<xs:element name="crsUrn" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CoordinateSystem.crsUrn"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="Currency" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Currency">
<xs:restriction base="xs:string">
<xs:enumeration value="AUD"/>
<xs:enumeration value="CAD"/>
<xs:enumeration value="CHF"/>
<xs:enumeration value="CNY"/>
<xs:enumeration value="DKK"/>
<xs:enumeration value="EUR"/>
<xs:enumeration value="GBP"/>
<xs:enumeration value="INR"/>
<xs:enumeration value="JPY"/>
<xs:enumeration value="NOK"/>
<xs:enumeration value="RUR"/>
<xs:enumeration value="SEK"/>
<xs:enumeration value="USD"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="pucNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.pucNumber"/>
<xs:element name="specialNeed" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.specialNeed"/>
<xs:element name="vip" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.vip"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.Organisation"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="billingCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.billingCycle"/>
<xs:element name="budgetBill" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.budgetBill"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
61968-9  IEC:2013 – 327 –

<xs:element name="docStatus" type="m:Status" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="loadMgmt" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.loadMgmt"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="signDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.signDate"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.Customer"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.CustomerAccount"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.ServiceCategory"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="validityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.validityInterval"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
– 328 – 61968-9  IEC:2013

<xs:element name="email2" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="installCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.installCode"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="ConnectDisconnectFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="SimpleEndDeviceFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SimpleEndDeviceFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:choice>
<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
61968-9  IEC:2013 – 329 –

</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceCapability" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#EndDeviceCapability">
<xs:sequence>
<xs:element name="autonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.autonomousDst"/>
<xs:element name="communication" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.communication"/>
<xs:element name="connectDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.connectDisconnect"/>
<xs:element name="demandResponse" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.demandResponse"/>
<xs:element name="electricMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.electricMetering"/>
<xs:element name="gasMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.gasMetering"/>
<xs:element name="metrology" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.metrology"/>
<xs:element name="onRequestRead" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.onRequestRead"/>
<xs:element name="outageHistory" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.outageHistory"/>
<xs:element name="pressureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pressureCompensation"/>
<xs:element name="pricingInfo" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pricingInfo"/>
<xs:element name="pulseOutput" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pulseOutput"/>
<xs:element name="relaysProgramming" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.relaysProgramming"/>
<xs:element name="reverseFlow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.reverseFlow"/>
<xs:element name="superCompressibilityCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.superCompressibilityCompensation"/>
<xs:element name="temperatureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.temperatureCompensation"/>
<xs:element name="textMessage" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.textMessage"/>
<xs:element name="waterMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.waterMetering"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="EndDeviceFunctionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceFunctionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="autonomousDst"/>
<xs:enumeration value="demandResponse"/>
<xs:enumeration value="electricMetering"/>
<xs:enumeration value="gasMetering"/>
<xs:enumeration value="metrology"/>
<xs:enumeration value="onRequestRead"/>
<xs:enumeration value="outageHistory"/>
<xs:enumeration value="relaysProgramming"/>
<xs:enumeration value="reverseFlow"/>
<xs:enumeration value="waterMetering"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="isSolidState" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.isSolidState"/>
<xs:element name="phaseCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.phaseCount"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedCurrent"/>
<xs:element name="ratedVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedVoltage"/>
– 330 – 61968-9  IEC:2013

<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
<xs:element name="capability" type="m:EndDeviceCapability" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.capability"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.installationDate"/>
<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.manufacturedDate"/>
<xs:element name="purchaseDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="formNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.formNumber"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Assets">
<xs:element name="ComModule" type="m:ComModule" sawsdl:modelReference=""/>
<xs:element name="EndDevice" type="m:EndDevice" sawsdl:modelReference=""/>
</xs:choice>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" type="m:ComFunction" sawsdl:modelReference=""/>
<xs:element name="ConnectDisconnectFunction" type="m:ConnectDisconnectFunction"
sawsdl:modelReference=""/>
<xs:element name="SimpleEndDeviceFunction" type="m:SimpleEndDeviceFunction"
sawsdl:modelReference=""/>
</xs:choice>
<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
61968-9  IEC:2013 – 331 –

<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="MeterMultipliers" type="m:MeterMultiplier" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.MeterMultipliers"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
<xs:element name="UsagePoint" type="m:UsagePoint"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:MeterMultiplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.kind"/>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="MeterMultiplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="kE"/>
<xs:enumeration value="kH"/>
<xs:enumeration value="kR"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="MetrologyRequirement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MetrologyRequirement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.reason"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingTypes" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.ReadingTypes">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
– 332 – 61968-9  IEC:2013

<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Organisation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Organisation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone2"/>
<xs:element name="postalAddress" type="m:PostalAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.postalAddress"/>
<xs:element name="streetAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.streetAddress"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="PhaseCode" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PhaseCode">
<xs:restriction base="xs:string">
<xs:enumeration value="A"/>
<xs:enumeration value="AB"/>
<xs:enumeration value="ABC"/>
<xs:enumeration value="ABCN"/>
<xs:enumeration value="ABN"/>
<xs:enumeration value="AC"/>
<xs:enumeration value="ACN"/>
<xs:enumeration value="AN"/>
<xs:enumeration value="B"/>
<xs:enumeration value="BC"/>
<xs:enumeration value="BCN"/>
<xs:enumeration value="BN"/>
<xs:enumeration value="C"/>
<xs:enumeration value="CN"/>
<xs:enumeration value="N"/>
<xs:enumeration value="s1"/>
<xs:enumeration value="s12"/>
<xs:enumeration value="s12N"/>
<xs:enumeration value="s1N"/>
<xs:enumeration value="s2"/>
<xs:enumeration value="s2N"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="PositionPoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PositionPoint">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.sequenceNumber"/>
<xs:element name="xPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.xPosition"/>
<xs:element name="yPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.yPosition"/>
<xs:element name="zPosition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.zPosition"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PostalAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PostalAddress">
<xs:sequence>
<xs:element name="poBox" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.poBox"/>
61968-9  IEC:2013 – 333 –

<xs:element name="postalCode" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.postalCode"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="dailyCeilingUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.dailyCeilingUsage"/>
<xs:element name="dailyEstimatedUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure.dailyEstimatedUsage"/>
<xs:element name="dailyFloorUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.dailyFloorUsage"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revenueKind" type="m:RevenueKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.revenueKind"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="taxExemption" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.taxExemption"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.ServiceCategory"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="Tariffs" type="m:Tariff" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.Tariffs"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel">
<xs:sequence>
<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
<xs:element name="modelNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelNumber"/>
<xs:element name="modelVersion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelVersion"/>
<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
</xs:complexType>
– 334 – 61968-9  IEC:2013

<xs:complexType name="ReadingInterharmonic" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#ReadingInterharmonic">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="denominator" type="xs:integer"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Register" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Register">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.isVirtual"/>
<xs:element name="leftDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.leftDigitCount"/>
61968-9  IEC:2013 – 335 –

<xs:element name="rightDigitCount" type="xs:integer" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.rightDigitCount"/>
<xs:element name="touTierName" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTierName"/>
<xs:element name="Channels" type="m:Channel" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.Channels"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="touTier" type="m:TimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTier"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RemoteConnectDisconnectInfo"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RemoteConnectDisconnectInfo">
<xs:sequence>
<xs:element name="armedTimeout" type="m:Seconds" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.armedTimeout"/>
<xs:element name="customerVoltageLimit" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.customerVoltageLimit"/>
<xs:element name="energyLimit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyLimit"/>
<xs:element name="energyUsageStartDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageStartDateTime"/>
<xs:element name="energyUsageWarning" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageWarning"/>
<xs:element name="isArmConnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmConnect"/>
<xs:element name="isArmDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmDisconnect"/>
<xs:element name="isEnergyLimiting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isEnergyLimiting"/>
<xs:element name="needsPowerLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsPowerLimitCheck"/>
<xs:element name="needsVoltageLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsVoltageLimitCheck"/>
<xs:element name="powerLimit" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.powerLimit"/>
<xs:element name="usePushbutton" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.usePushbutton"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RevenueKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RevenueKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercial"/>
<xs:enumeration value="industrial"/>
<xs:enumeration value="irrigation"/>
<xs:enumeration value="nonResidential"/>
<xs:enumeration value="other"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="streetLight"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Seal" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal">
<xs:sequence>
<xs:element name="appliedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.appliedDateTime"/>
<xs:element name="condition" type="m:SealConditionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.condition"/>
<xs:element name="kind" type="m:SealKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.kind"/>
<xs:element name="sealNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.sealNumber"/>
</xs:sequence>
– 336 – 61968-9  IEC:2013

</xs:complexType>
<xs:simpleType name="SealConditionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealConditionKind">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:restriction base="xs:string">
<xs:enumeration value="broken"/>
<xs:enumeration value="locked"/>
<xs:enumeration value="missing"/>
<xs:enumeration value="open"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="SealKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealKind">
<xs:restriction base="xs:string">
<xs:enumeration value="lead"/>
<xs:enumeration value="lock"/>
<xs:enumeration value="other"/>
<xs:enumeration value="steel"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.accessMethod"/>
<xs:element name="direction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.direction"/>
<xs:element name="geoInfoReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.geoInfoReference"/>
<xs:element name="needsInspection" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.needsInspection"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.siteAccessProblem"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.type"/>
<xs:element name="CoordinateSystem" type="m:CoordinateSystem" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.CoordinateSystem"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.electronicAddress"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone2"/>
61968-9  IEC:2013 – 337 –

<xs:element name="PositionPoints" type="m:PositionPoint" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.PositionPoints"/>
<xs:element name="secondaryAddress" type="m:StreetAddress" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.secondaryAddress"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceMultiplierKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.kind"/>
<xs:element name="value" type="xs:float" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceMultiplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerIdentificationNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier.issuerIdentificationNumber"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.Organisation"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="SimpleEndDeviceFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SimpleEndDeviceFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="kind" type="m:EndDeviceFunctionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction.kind"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Registers" type="m:Register" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.Registers"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
– 338 – 61968-9  IEC:2013

<xs:element name="reason" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Tariff" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Tariff">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="endDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.endDate"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="startDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.startDate"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
61968-9  IEC:2013 – 339 –

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="TariffProfiles" type="m:TariffProfile" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.TariffProfiles"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TariffProfile" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TariffProfile">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="tariffCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TariffProfile.tariffCycle"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ConsumptionTariffIntervals" type="m:ConsumptionTariffInterval" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TariffProfile.ConsumptionTariffIntervals"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="TimeTariffIntervals" type="m:TimeTariffInterval" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TariffProfile.TimeTariffIntervals"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.end"/>
<xs:element name="start" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeTariffInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeTariffInterval">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeTariffInterval.sequenceNumber"/>
<xs:element name="startTime" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeTariffInterval.startTime"/>
<xs:element name="Charges" type="m:Charge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeTariffInterval.Charges"/>
</xs:sequence>
</xs:complexType>
– 340 – 61968-9  IEC:2013

<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#TownDetail">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="code" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TransformerTank" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TransformerTank">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="UnitMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UnitMultiplier">
<xs:restriction base="xs:string">
<xs:enumeration value="G"/>
<xs:enumeration value="M"/>
<xs:enumeration value="T"/>
<xs:enumeration value="c"/>
<xs:enumeration value="d"/>
<xs:enumeration value="k"/>
<xs:enumeration value="m"/>
<xs:enumeration value="micro"/>
<xs:enumeration value="n"/>
<xs:enumeration value="none"/>
<xs:enumeration value="p"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amiBillingReady" type="m:AmiBillingReadyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.amiBillingReady"/>
<xs:element name="checkBilling" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.checkBilling"/>
<xs:element name="connectionState" type="m:UsagePointConnectedKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.connectionState"/>
<xs:element name="estimatedLoad" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.estimatedLoad"/>
<xs:element name="grounded" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.grounded"/>
<xs:element name="isSdp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isSdp"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isVirtual"/>
<xs:element name="minimalUsageExpected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.minimalUsageExpected"/>
<xs:element name="nominalServiceVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.nominalServiceVoltage"/>
<xs:element name="outageRegion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.outageRegion"/>
<xs:element name="phaseCode" type="m:PhaseCode" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.phaseCode"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedCurrent"/>
<xs:element name="ratedPower" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedPower"/>
<xs:element name="readCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.readCycle"/>
<xs:element name="readRoute" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.readRoute"/>
61968-9  IEC:2013 – 341 –

<xs:element name="serviceDeliveryRemark" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.serviceDeliveryRemark"/>
<xs:element name="servicePriority" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.servicePriority"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.CustomerAgreement"/>
<xs:element name="Equipments" type="m:TransformerTank" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.Equipments"/>
<xs:element name="MetrologyRequirements" type="m:MetrologyRequirement" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.MetrologyRequirements"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="PricingStructures" type="m:PricingStructure" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.PricingStructures"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceCategory"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceLocation"/>
<xs:element name="ServiceMultipliers" type="m:ServiceMultiplier" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.ServiceMultipliers"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceSupplier"/>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.UsagePointLocation"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="UsagePointConnectedKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointConnectedKind">
<xs:restriction base="xs:string">
<xs:enumeration value="connected"/>
<xs:enumeration value="logicallyDisconnected"/>
<xs:enumeration value="physicallyDisconnected"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePointLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointLocation.accessMethod"/>
<xs:element name="direction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.direction"/>
<xs:element name="geoInfoReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.geoInfoReference"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointLocation.remark"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointLocation.siteAccessProblem"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.type"/>
<xs:element name="CoordinateSystem" type="m:CoordinateSystem" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.CoordinateSystem"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.electronicAddress"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone2"/>
<xs:element name="PositionPoints" type="m:PositionPoint" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.PositionPoints"/>
<xs:element name="secondaryAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.secondaryAddress"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Voltage">
– 342 – 61968-9  IEC:2013

<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivePower">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Seconds" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seconds">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

I.5 EndDeviceGroups
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/EndDeviceGroups#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/EndDeviceGroups#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="EndDeviceGroups" type="m:EndDeviceGroups"/>
<xs:complexType name="EndDeviceGroups">
<xs:sequence>
<xs:element name="DemandResponseProgram" type="m:DemandResponseProgram" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DemandResponseProgram" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DemandResponseProgram">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DemandResponseProgram.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  IEC:2013 – 343 –

<xs:element name="DemandResponsePrograms" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceGroup.DemandResponsePrograms">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DemandResponseProgram">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="EndDevices" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceGroup.EndDevices"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.6 GetAuxiliaryAgreementConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetAuxiliaryAgreementConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetAuxiliaryAgreementConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetAuxiliaryAgreementConfig" type="m:GetAuxiliaryAgreementConfig"/>
<xs:complexType name="GetAuxiliaryAgreementConfig">
<xs:sequence>
<xs:element name="AuxiliaryAccount" type="m:AuxiliaryAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAccount">
<xs:sequence>
– 344 – 61968-9  IEC:2013

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="subType" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AuxiliaryAgreement.subType"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
61968-9  IEC:2013 – 345 –

<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
</xs:schema>

I.7 GetComModuleConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetComModuleConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmln
s:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/GetComModuleConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetComModuleConfig" type="m:GetComModuleConfig"/>
<xs:complexType name="GetComModuleConfig">
<xs:sequence>
<xs:element name="ComModule" type="m:ComModule" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComModule">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
/TC57/2010/CIM-schema-cim15#ComModule.amrSystem"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
– 346 – 61968-9  IEC:2013

<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#EndDevice">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57


/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0" sawsdl:modelReference="http://iec.ch
/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.
ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0" sawsdl:modelRefere
nce="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.
ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.8 GetCustomerMeterDataSet
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetCustomerMeterDataSet#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetCustomerMeterDataSet#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetCustomerMeterDataSet" type="m:GetCustomerMeterDataSet"/>
<xs:complexType name="GetCustomerMeterDataSet">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
61968-9  IEC:2013 – 347 –

<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"


maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
– 348 – 61968-9  IEC:2013

<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="NameType" type="m:NameType" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
61968-9  IEC:2013 – 349 –

<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.9 GetEndDeviceGroups
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetEndDeviceGroups#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetEndDeviceGroups#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetEndDeviceGroups" type="m:GetEndDeviceGroups"/>
<xs:complexType name="GetEndDeviceGroups">
<xs:sequence>
<xs:element name="DemandResponseProgram" type="m:DemandResponseProgram" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DemandResponseProgram" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DemandResponseProgram">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DemandResponseProgram.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
– 350 – 61968-9  IEC:2013

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.10 GetMeterReadSchedule
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetMeterReadSchedule#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetMeterReadSchedule#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetMeterReadSchedule" type="m:GetMeterReadSchedule"/>
<xs:complexType name="GetMeterReadSchedule">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
61968-9  IEC:2013 – 351 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 352 – 61968-9  IEC:2013

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 353 –

<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#UsagePoint">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.11 GetMeterServiceRequests
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetMeterServiceRequests#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetMeterServiceRequests#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetMeterServiceRequests" type="m:GetMeterServiceRequests"/>
<xs:complexType name="GetMeterServiceRequests">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="MeterServiceWork" type="m:MeterServiceWork" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
– 354 – 61968-9  IEC:2013

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterServiceWork" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MeterServiceWork">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
61968-9  IEC:2013 – 355 –

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.12 GetPricingStructureConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetPricingStructureConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetPricingStructureConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetPricingStructureConfig" type="m:GetPricingStructureConfig"/>
<xs:complexType name="GetPricingStructureConfig">
<xs:sequence>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
– 356 – 61968-9  IEC:2013

<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="NameType" type="m:NameType" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.13 GetReceiptRecord
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetReceiptRecord#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetReceiptRecord#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetReceiptRecord" type="m:GetReceiptRecord"/>
<xs:complexType name="GetReceiptRecord">
<xs:sequence>
<xs:element name="AuxiliaryAccount" type="m:AuxiliaryAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="PointOfSale" type="m:PointOfSale" minOccurs="0"
maxOccurs="unbounded"/>
61968-9  IEC:2013 – 357 –

<xs:element name="Receipt" type="m:Receipt" minOccurs="0"


maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
– 358 – 61968-9  IEC:2013

<xs:element name="start" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PointOfSale" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PointOfSale">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="location" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PointOfSale.location"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Receipt" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Receipt">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.14 GetTransactionRecord
<?xml version="1.0" encoding="UTF-8"?>

<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"


xmlns:m="http://iec.ch/TC57/2011/GetTransactionRecord#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetTransactionRecord#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetTransactionRecord" type="m:GetTransactionRecord"/>
<xs:complexType name="GetTransactionRecord">
<xs:sequence>
61968-9  IEC:2013 – 359 –

<xs:element name="AuxiliaryAccount" type="m:AuxiliaryAccount" minOccurs="0"


maxOccurs="unbounded"/>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="PointOfSale" type="m:PointOfSale" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Transaction" type="m:Transaction" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
– 360 – 61968-9  IEC:2013

<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PointOfSale" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PointOfSale">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="location" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PointOfSale.location"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Transaction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Transaction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>
61968-9  IEC:2013 – 361 –

I.15 GetUsagePointGroups
<?xml version="1.0" encoding="UTF-8"?>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"


xmlns:m="http://iec.ch/TC57/2011/GetUsagePointGroups#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetUsagePointGroups#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetUsagePointGroups" type="m:GetUsagePointGroups"/>
<xs:complexType name="GetUsagePointGroups">
<xs:sequence>
<xs:element name="DemandResponseProgram" type="m:DemandResponseProgram" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DemandResponseProgram" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DemandResponseProgram">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DemandResponseProgram.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
– 362 – 61968-9  IEC:2013

</xs:schema>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

I.16 MeterReadSchedule
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/MeterReadSchedule#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns
:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/MeterReadSchedule#" el
ementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="MeterReadSchedule" type="m:MeterReadSchedule"/>
<xs:complexType name="MeterReadSchedule">
<xs:sequence>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0" maxOccurs="unbounded"/
>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0" maxOccurs="unbound
ed"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0" maxOccurs="unbounded"/
>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC5
7/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0" sawsdl:modelReference="http://iec.ch/T
C57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
61968-9  IEC:2013 – 363 –

<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0" sawsdl:modelReference="http://iec.ch
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.
ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0" sawsdl:modelRefere
nce="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.
ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimePoint">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0" sawsdl:modelReference="http://iec.c
h/TC57/2010/CIM-schema-cim15#TimePoint.dateTime"/>
<xs:element name="relativeTimeInterval" type="m:Seconds" minOccurs="0" sawsdl:modelReference="ht
tp://iec.ch/TC57/2010/CIM-schema-cim15#TimePoint.relativeTimeInterval"/>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0" sawsdl:modelReference="http://
iec.ch/TC57/2010/CIM-schema-cim15#TimePoint.sequenceNumber"/>
<xs:element name="window" type="m:DateTimeInterval" minOccurs="0" sawsdl:modelReference="http://
iec.ch/TC57/2010/CIM-schema-cim15#TimePoint.window"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule">
<xs:sequence>
<xs:element name="disabled" type="xs:boolean" minOccurs="0" sawsdl:modelReference="http://iec.ch
/TC57/2010/CIM-schema-cim15#TimeSchedule.disabled"/>
<xs:element name="offset" type="m:Seconds" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC
57/2010/CIM-schema-cim15#TimeSchedule.offset"/>
<xs:element name="recurrencePattern" type="xs:string" minOccurs="0" sawsdl:modelReference="http:
//iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.recurrencePattern"/>
<xs:element name="recurrencePeriod" type="m:Seconds" minOccurs="0" sawsdl:modelReference="http:/
/iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.recurrencePeriod"/>
<xs:element name="scheduleInterval" type="m:DateTimeInterval" minOccurs="0" sawsdl:modelReferenc
e="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.scheduleInterval"/>
<xs:element name="TimePoints" type="m:TimePoint" minOccurs="0" maxOccurs="unbounded" sawsdl:mode
lReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeSchedule.TimePoints"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference
="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointGroup">
– 364 – 61968-9  IEC:2013

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57
/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference


="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Seconds" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seconds">
<xs:restriction base="xs:float"/>
</xs:simpleType>
</xs:schema>

I.17 MeterServiceRequest
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/MeterServiceRequests#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/MeterServiceRequests#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="MeterServiceRequests" type="m:MeterServiceRequests"/>
<xs:complexType name="MeterServiceRequests">
<xs:sequence>
<xs:element name="MeterServiceWork" type="m:MeterServiceWork"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingQualityType" type="m:ReadingQualityType"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ActivityRecord"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord">
<xs:sequence>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="pucNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.pucNumber"/>
<xs:element name="specialNeed" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.specialNeed"/>
<xs:element name="vip" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.vip"/>
<xs:element name="CustomerAgreements" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer.CustomerAgreements"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.status"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 365 –

<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="formNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.formNumber"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="MeterMultipliers" type="m:MeterMultiplier"
minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter.MeterMultipliers"/>
<xs:element name="MeterReadings" type="m:MeterReading" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter.MeterReadings"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterMultiplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:MeterMultiplierKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.kind"/>
<xs:element name="value" type="xs:float"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="MeterMultiplierKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
– 366 – 61968-9  IEC:2013

<xs:enumeration value="kE"/>
<xs:enumeration value="kH"/>
<xs:enumeration value="kR"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="MeterReading"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading">
<xs:sequence>
<xs:element name="Readings" type="m:Reading" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading.Readings"/>
<xs:element name="valuesInterval" type="m:DateTimeInterval"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading.valuesInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterServiceWork"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterServiceWork">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:WorkKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Work.kind"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Document.lastModifiedDateTime"/>
<xs:element name="priority" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Work.priority"/>
<xs:element name="requestDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Work.requestDateTime"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ActivityRecords" type="m:ActivityRecord"
minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Document.ActivityRecords"/>
<xs:element name="Customers" type="m:Customer" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Work.Customers"/>
<xs:element name="Meter" type="m:Meter"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterServiceWork.Meter"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
<xs:element name="OldMeter" type="m:Meter" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterServiceWork.OldMeter"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterServiceWork.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
61968-9  IEC:2013 – 367 –

<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="PhaseCode" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PhaseCode">
<xs:restriction base="xs:string">
<xs:enumeration value="A"/>
<xs:enumeration value="AB"/>
<xs:enumeration value="ABC"/>
<xs:enumeration value="ABCN"/>
<xs:enumeration value="ABN"/>
<xs:enumeration value="AC"/>
<xs:enumeration value="ACN"/>
<xs:enumeration value="AN"/>
<xs:enumeration value="B"/>
<xs:enumeration value="BC"/>
<xs:enumeration value="BCN"/>
<xs:enumeration value="BN"/>
<xs:enumeration value="C"/>
<xs:enumeration value="CN"/>
<xs:enumeration value="N"/>
<xs:enumeration value="s1"/>
<xs:enumeration value="s12"/>
<xs:enumeration value="s12N"/>
<xs:enumeration value="s1N"/>
<xs:enumeration value="s2"/>
<xs:enumeration value="s2N"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Reading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Reading">
<xs:sequence>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.reason"/>
<xs:element name="reportedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#BaseReading.reportedDateTime"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeasurementValue.timeStamp"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.value"/>
<xs:element name="ReadingQualities" type="m:ReadingQuality"
minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#BaseReading.ReadingQualities"/>
<xs:element name="ReadingType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingQuality"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality">
<xs:sequence>
<xs:element name="comment" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.comment"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.source"/>
<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.timeStamp"/>
<xs:element name="ReadingQualityType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQuality.ReadingQualityType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
– 368 – 61968-9  IEC:2013

</xs:element>
</xs:sequence>
</xs:complexType>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:complexType name="ReadingQualityType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="category" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType.category"/>
<xs:element name="subCategory" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQualityType.subCategory"/>
<xs:element name="systemId" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType.systemId"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
61968-9  IEC:2013 – 369 –

<xs:element name="interharmonic" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic">
<xs:complexType sawsdl:modelReference="">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:attribute name="ref" type="xs:string"/>


</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation.accessMethod"/>
<xs:element name="needsInspection" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation.needsInspection"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation.siteAccessProblem"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceMultiplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceMultiplierKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.kind"/>
<xs:element name="value" type="xs:float"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceMultiplierKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress">
<xs:sequence>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
– 370 – 61968-9  IEC:2013

<xs:complexType name="StreetDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="addressGeneral" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="checkBilling" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.checkBilling"/>
<xs:element name="grounded" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.grounded"/>
<xs:element name="isSdp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isSdp"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isVirtual"/>
<xs:element name="nominalServiceVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.nominalServiceVoltage"/>
<xs:element name="phaseCode" type="m:PhaseCode" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.phaseCode"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedCurrent"/>
<xs:element name="ratedPower" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedPower"/>
<xs:element name="serviceDeliveryRemark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.serviceDeliveryRemark"/>
<xs:element name="servicePriority" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.servicePriority"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.ServiceLocation"/>
61968-9  IEC:2013 – 371 –

<xs:element name="ServiceMultipliers" type="m:ServiceMultiplier"


minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.ServiceMultipliers"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:sequence>
</xs:complexType>
<xs:simpleType name="WorkKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#WorkKind">
<xs:restriction base="xs:string">
<xs:enumeration value="construction"/>
<xs:enumeration value="disconnect"/>
<xs:enumeration value="inspection"/>
<xs:enumeration value="maintenance"/>
<xs:enumeration value="meter"/>
<xs:enumeration value="other"/>
<xs:enumeration value="reconnect"/>
<xs:enumeration value="repair"/>
<xs:enumeration value="service"/>
<xs:enumeration value="test"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Voltage">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ActivePower">
<xs:restriction base="xs:float"/>
</xs:simpleType>
</xs:schema>

I.18 ObjectNamesConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ObjectNamesConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/ObjectNamesConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="ObjectNamesConfig" type="m:ObjectNamesConfig"/>
<xs:complexType name="ObjectNamesConfig">
<xs:sequence>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement"
minOccurs="0"/>
<xs:element name="ComModule" type="m:ComModule" minOccurs="0"/>
<xs:element name="ConfigurationEvent" type="m:ConfigurationEvent"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"/>
<xs:element name="Name" type="m:Name" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"/>
<xs:element name="TransformerTank" type="m:TransformerTank" minOccurs="0"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"/>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation"
minOccurs="0"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
– 372 – 61968-9  IEC:2013

<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#ComModule">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  IEC:2013 – 373 –

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TransformerTank" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TransformerTank">
<xs:sequence>
– 374 – 61968-9  IEC:2013

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

I.19 PricingStructureConfig

<?xml version="1.0" encoding="UTF-8"?>


<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/PricingStructureConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/PricingStructureConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="PricingStructureConfig" type="m:PricingStructureConfig"/>
<xs:complexType name="PricingStructureConfig">
<xs:sequence>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AccountingUnit" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AccountingUnit">
<xs:sequence>
<xs:element name="energyUnit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.energyUnit"/>
<xs:element name="monetaryUnit" type="m:Currency" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.monetaryUnit"/>
<xs:element name="multiplier" type="m:UnitMultiplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.multiplier"/>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Charge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="ChildCharges" type="m:SimpleChildCharge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.ChildCharges"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ChargeKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ChargeKind">
<xs:restriction base="xs:string">
61968-9  IEC:2013 – 375 –

<xs:enumeration value="auxiliaryCharge"/>
<xs:enumeration value="consumptionCharge"/>
<xs:enumeration value="demandCharge"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="other"/>
<xs:enumeration value="taxCharge"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConsumptionTariffInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConsumptionTariffInterval">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConsumptionTariffInterval.sequenceNumber"/>
<xs:element name="startValue" type="m:RealEnergy"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConsumptionTariffInterval.startValue"/>
<xs:element name="Charges" type="m:Charge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConsumptionTariffInterval.Charges"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Currency" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Currency">
<xs:restriction base="xs:string">
<xs:enumeration value="AUD"/>
<xs:enumeration value="CAD"/>
<xs:enumeration value="CHF"/>
<xs:enumeration value="CNY"/>
<xs:enumeration value="DKK"/>
<xs:enumeration value="EUR"/>
<xs:enumeration value="GBP"/>
<xs:enumeration value="INR"/>
<xs:enumeration value="JPY"/>
<xs:enumeration value="NOK"/>
<xs:enumeration value="RUR"/>
<xs:enumeration value="SEK"/>
<xs:enumeration value="USD"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
– 376 – 61968-9  IEC:2013

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="dailyCeilingUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.dailyCeilingUsage"/>
<xs:element name="dailyEstimatedUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure.dailyEstimatedUsage"/>
<xs:element name="dailyFloorUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.dailyFloorUsage"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revenueKind" type="m:RevenueKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.revenueKind"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="taxExemption" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.taxExemption"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.ConfigurationEvents"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.ServiceCategory"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="Tariffs" type="m:Tariff" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.Tariffs"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RevenueKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RevenueKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercial"/>
<xs:enumeration value="industrial"/>
<xs:enumeration value="irrigation"/>
<xs:enumeration value="nonResidential"/>
<xs:enumeration value="other"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="streetLight"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceCategory">
<xs:sequence>
61968-9  IEC:2013 – 377 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="SimpleChildCharge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Tariff" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Tariff">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="endDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.endDate"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="startDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.startDate"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
– 378 – 61968-9  IEC:2013

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="TariffProfiles" type="m:TariffProfile" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.TariffProfiles"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TariffProfile" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TariffProfile">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="tariffCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TariffProfile.tariffCycle"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ConsumptionTariffIntervals" type="m:ConsumptionTariffInterval" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TariffProfile.ConsumptionTariffIntervals"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="TimeTariffIntervals" type="m:TimeTariffInterval" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TariffProfile.TimeTariffIntervals"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeTariffInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeTariffInterval">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeTariffInterval.sequenceNumber"/>
<xs:element name="startTime" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeTariffInterval.startTime"/>
<xs:element name="Charges" type="m:Charge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeTariffInterval.Charges"/>
<xs:element name="ConsumptionTariffIntervals" type="m:ConsumptionTariffInterval" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeTariffInterval.ConsumptionTariffIntervals"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="UnitMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UnitMultiplier">
<xs:restriction base="xs:string">
<xs:enumeration value="G"/>
<xs:enumeration value="M"/>
<xs:enumeration value="T"/>
<xs:enumeration value="c"/>
<xs:enumeration value="d"/>
<xs:enumeration value="k"/>
<xs:enumeration value="m"/>
<xs:enumeration value="micro"/>
<xs:enumeration value="n"/>
<xs:enumeration value="none"/>
<xs:enumeration value="p"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
61968-9  IEC:2013 – 379 –

<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#PerCent">
<xs:restriction base="xs:float"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:simpleType>
</xs:schema>

I.20 ReceiptRecord
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ReceiptRecord#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/ReceiptRecord#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="ReceiptRecord" type="m:ReceiptRecord"/>
<xs:complexType name="ReceiptRecord">
<xs:sequence>
<xs:element name="Receipt" type="m:Receipt" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="BankAccountDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#BankAccountDetail">
<xs:sequence>
<xs:element name="accountNumber" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BankAccountDetail.accountNumber"/>
<xs:element name="bankName" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#BankAccountDetail.bankName"/>
<xs:element name="branchCode" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BankAccountDetail.branchCode"/>
<xs:element name="holderID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BankAccountDetail.holderID"/>
<xs:element name="holderName" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BankAccountDetail.holderName"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Card" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Card">
<xs:sequence>
<xs:element name="accountHolderName" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Card.accountHolderName"/>
<xs:element name="cvNumber" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Card.cvNumber"/>
<xs:element name="expiryDate" type="xs:date" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Card.expiryDate"/>
<xs:element name="pan" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Card.pan"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Cashier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Cashier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CashierShift" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CashierShift">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="activityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Shift.activityInterval"/>
<xs:element name="Cashier" type="m:Cashier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CashierShift.Cashier"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="PointOfSale" type="m:PointOfSale"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CashierShift.PointOfSale"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Cheque" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Cheque">
<xs:sequence>
– 380 – 61968-9  IEC:2013

<xs:element name="chequeNumber" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Cheque.chequeNumber"/>
<xs:element name="date" type="xs:date" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#Cheque.date"/>
<xs:element name="kind" type="m:ChequeKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Cheque.kind"/>
<xs:element name="micrNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Cheque.micrNumber"/>
<xs:element name="bankAccountDetail" type="m:BankAccountDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Cheque.bankAccountDetail"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ChequeKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ChequeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="bankOrder"/>
<xs:enumeration value="other"/>
<xs:enumeration value="postalOrder"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LineDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LineDetail">
<xs:sequence>
<xs:element name="amount" type="m:Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#LineDetail.amount"/>
<xs:element name="dateTime" type="xs:dateTime"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LineDetail.dateTime"/>
<xs:element name="note" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LineDetail.note"/>
<xs:element name="rounding" type="m:Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#LineDetail.rounding"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MerchantAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MerchantAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="currentBalance" type="m:Money"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.currentBalance"/>
<xs:element name="provisionalBalance" type="m:Money"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.provisionalBalance"/>
<xs:element name="MerchantAgreement" type="m:MerchantAgreement" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.MerchantAgreement"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Transactors" type="m:Transactor" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.Transactors"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MerchantAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MerchantAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 381 –

<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#NameType">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PointOfSale" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PointOfSale">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="location" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PointOfSale.location"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Receipt" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Receipt">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isBankable" type="xs:boolean"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Receipt.isBankable"/>
<xs:element name="CashierShift" type="m:CashierShift" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Receipt.CashierShift"/>
<xs:element name="line" type="m:LineDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Receipt.line"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Tenders" type="m:Tender" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Receipt.Tenders"/>
<xs:element name="VendorShift" type="m:VendorShift" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Receipt.VendorShift"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Tender" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Tender">
<xs:sequence>
<xs:element name="Card" type="m:Card" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tender.Card"/>
<xs:element name="Cheque" type="m:Cheque" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tender.Cheque"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Transactor" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Transactor">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Vendor" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Vendor">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
– 382 – 61968-9  IEC:2013

</xs:complexType>
<xs:complexType name="VendorShift" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#VendorShift">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="merchantDebitAmount" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#VendorShift.merchantDebitAmount"/>
<xs:element name="posted" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#VendorShift.posted"/>
<xs:element name="activityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Shift.activityInterval"/>
<xs:element name="MerchantAccount" type="m:MerchantAccount" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#VendorShift.MerchantAccount"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Vendor" type="m:Vendor" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#VendorShift.Vendor"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

I.21 TransactionRecord
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/TransactionRecord#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/TransactionRecord#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="TransactionRecord" type="m:TransactionRecord"/>
<xs:complexType name="TransactionRecord">
<xs:sequence>
<xs:element name="Transaction" type="m:Transaction" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AuxiliaryAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="balance" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AuxiliaryAccount.balance"/>
<xs:element name="principleAmount" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AuxiliaryAccount.principleAmount"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Cashier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Cashier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CashierShift" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CashierShift">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="cashFloat" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CashierShift.cashFloat"/>
<xs:element name="activityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Shift.activityInterval"/>
<xs:element name="Cashier" type="m:Cashier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CashierShift.Cashier"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
61968-9  IEC:2013 – 383 –

<xs:element name="PointOfSale" type="m:PointOfSale"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CashierShift.PointOfSale"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="Charge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="ChildCharges" type="m:ChildCharge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.ChildCharges"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ChargeKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ChargeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="auxiliaryCharge"/>
<xs:enumeration value="consumptionCharge"/>
<xs:enumeration value="demandCharge"/>
<xs:enumeration value="other"/>
<xs:enumeration value="taxCharge"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ChildCharge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="billingCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.billingCycle"/>
<xs:element name="budgetBill" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.budgetBill"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LineDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LineDetail">
<xs:sequence>
<xs:element name="amount" type="m:Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#LineDetail.amount"/>
<xs:element name="dateTime" type="xs:dateTime"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LineDetail.dateTime"/>
<xs:element name="note" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LineDetail.note"/>
<xs:element name="rounding" type="m:Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#LineDetail.rounding"/>
</xs:sequence>
</xs:complexType>
– 384 – 61968-9  IEC:2013

<xs:complexType name="MerchantAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#MerchantAccount">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="currentBalance" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.currentBalance"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="provisionalBalance" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.provisionalBalance"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="MerchantAgreement" type="m:MerchantAgreement" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.MerchantAgreement"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Transactors" type="m:Transactor" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MerchantAccount.Transactors"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MerchantAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MerchantAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
61968-9  IEC:2013 – 385 –

<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#NameTypeAuthority">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PointOfSale" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PointOfSale">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="location" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PointOfSale.location"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Tariffs" type="m:Tariff" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.Tariffs"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Receipt" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Receipt">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Tariff" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Tariff">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="endDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.endDate"/>
<xs:element name="startDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.startDate"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="TariffProfiles" type="m:TariffProfile" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Tariff.TariffProfiles"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TariffProfile" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TariffProfile">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Transaction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Transaction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="diverseReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.diverseReference"/>
<xs:element name="donorReference" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.donorReference"/>
<xs:element name="kind" type="m:TransactionKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.kind"/>
– 386 – 61968-9  IEC:2013

<xs:element name="receiverReference" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.receiverReference"/>
<xs:element name="reversedId" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.reversedId"/>
<xs:element name="serviceUnitsEnergy" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.serviceUnitsEnergy"/>
<xs:element name="serviceUnitsError" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.serviceUnitsError"/>
<xs:element name="AuxiliaryAccount" type="m:AuxiliaryAccount" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.AuxiliaryAccount"/>
<xs:element name="CashierShift" type="m:CashierShift" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.CashierShift"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.CustomerAccount"/>
<xs:element name="line" type="m:LineDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Transaction.line"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.Meter"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.PricingStructure"/>
<xs:element name="Receipt" type="m:Receipt" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.Receipt"/>
<xs:element name="UserAttributes" type="m:UserAttribute" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.UserAttributes"/>
<xs:element name="VendorShift" type="m:VendorShift" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Transaction.VendorShift"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="TransactionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TransactionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="accountPayment"/>
<xs:enumeration value="auxiliaryChargePayment"/>
<xs:enumeration value="diversePayment"/>
<xs:enumeration value="meterConfigurationToken"/>
<xs:enumeration value="other"/>
<xs:enumeration value="serviceChargePayment"/>
<xs:enumeration value="taxChargePayment"/>
<xs:enumeration value="tokenCancellation"/>
<xs:enumeration value="tokenExchange"/>
<xs:enumeration value="tokenFreeIssue"/>
<xs:enumeration value="tokenGrant"/>
<xs:enumeration value="tokenSalePayment"/>
<xs:enumeration value="transactionReversal"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Transactor" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Transactor">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UserAttribute" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UserAttribute">
<xs:sequence>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UserAttribute.name"/>
<xs:element name="sequenceNumber" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UserAttribute.sequenceNumber"/>
<xs:element name="value" type="m:StringQuantity"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UserAttribute.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Vendor" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Vendor">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
61968-9  IEC:2013 – 387 –

</xs:complexType>
<xs:complexType name="VendorShift" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#VendorShift">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="merchantDebitAmount" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#VendorShift.merchantDebitAmount"/>
<xs:element name="posted" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#VendorShift.posted"/>
<xs:element name="activityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Shift.activityInterval"/>
<xs:element name="MerchantAccount" type="m:MerchantAccount" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#VendorShift.MerchantAccount"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Vendor" type="m:Vendor" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#VendorShift.Vendor"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="StringQuantity" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StringQuantity">
<xs:restriction base="xs:string"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

I.22 UsagePointGroups
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/UsagePointGroups#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/UsagePointGroups#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="UsagePointGroups" type="m:UsagePointGroups"/>
<xs:complexType name="UsagePointGroups">
<xs:sequence>
<xs:element name="DemandResponseProgram" type="m:DemandResponseProgram" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DemandResponseProgram" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DemandResponseProgram">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DemandResponseProgram.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
– 388 – 61968-9  IEC:2013

</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="DemandResponsePrograms" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointGroup.DemandResponsePrograms">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DemandResponseProgram">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="UsagePoints" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup.UsagePoints"/>
</xs:sequence>
</xs:complexType>
</xs:schema>
61968-9  IEC:2013 – 389 –

Annex J
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Request parameters

J.1 General

The purpose of this Annex J is to describe filters that can be used for "GET" requests in order
to filter the contents of the payload that is returned on the REPLY message. This is in effect a
"query" pattern. If needed, these filters can be defined as contextual profiles in a manner
similar to those used to define payloads. Those structures are then realized as XML schemas.
The payloads would be used in the "any ##other" element of the request structure in a request
message (see Figure J.1).

Figure J.1 – Message request structure

The "StartTime" and "EndTime" tags are often used to narrow the results to a given time
interval. The "ID" tags can be used to specify the mRIDs for a set of objects of interest. The
"Option" parameter provides for name/value pairs that can also be used to meet specific
application needs.

Other qualifiers can be specified using the "any ##other" element as needed, which are
referred to as "Get" profiles. When "Get" profiles are used, the Request.ID elements should
not be used.A "Get" profile primarily is used to identify object Ids (by name or mRID) for
specific classes of objects.

Clauses J.2 to J.5 describe "Get" profiles, which are named as "Get<Noun>" and
corresponding XSD file name as "Get<Noun>.xsd". Except for "PrePay" profiles, the
– 390 – 61968-9  IEC:2013

convention for IEC 61968-9 is to define a "Get" profile for each noun. In the case of PrePay
profiles, it would be possible to rename one of the existing "Get" profiles if needed. In all
cases where a "Get" profile is used, the parameters defined within the "Get" profile shall be
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

used in preference over generic parameters defined in the Request package.

J.2 GetMeterReadings

The following structure in Figure J.2 is a contextual profile that can be used to qualify "GET
MeterReadings" requests. This provides a representative example of how mRIDs, names and
time may be specified within a "Get" profile to qualify a query.

Figure J.2 – GetMeterReadings

J.3 GetEndDeviceConfig

The following structure in Figure J.3 is a contextual profile that can be used to qualify "GET
EndDeviceConfig" requests.
61968-9  IEC:2013 – 391 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure J.3 – GetEndDeviceConfig

J.4 GetCustomerMeterDataSet

The following structure in Figure J.4 is a contextual profile that can be used to qualify "GET
CustomerMeterDataSet" requests.
– 392 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure J.4 – GetCustomerMeterDataSet

J.5 GetMeterServiceRequests

The following structure in Figure J.5 is a contextual profile that can be used to qualify "GET
MeterService" requests.
61968-9  IEC:2013 – 393 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure J.5 – GetMeterServiceRequests

The previous ""Get" profiles are representative examples that are commonly used. The
complete list of ""Get" profiles include the following:

• GetAuxiliaryAgreementConfig
• GetComModuleConfig
• GetCustomerAccountConfig
• GetCustomrAgreementConfig
• GetCustomerConfig
• GetCustomerMeterDataSet
• GetEndDeviceConfig
• GetEndDeviceControls
• GetEndDeviceEvents
• GetEndDeviceFirmware
• GetEndDeviceGroups
• GetMeterConfig
• GetMeterReadings
• GetMeterReadSchedule
– 394 – 61968-9  IEC:2013

• GetMeterServiceRequests
• GetPricingStructureConfig
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• GetReceiptRecord
• GetServiceCategoryConfig
• GetServiceLocationConfig
• GetServiceSupplierConfig
• GetTransactionRecord
• GetUsagePointConfig
• GetUsagePointGroups
• GetUsagePointLocationConfig

The XML schemas for ""Get" profiles are provides in Annexes H and I.
61968-9  IEC:2013 – 395 –

Annex K
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Master data management transaction processing

K.1 General

The purpose of this Annex K is to describe how transaction processing is performed in order
to support the master data management needs of IEC 61968-9.

For this edition of IEC 61968-9, the Message.xsd message envelope has been extended to
accommodate an OperationSet construct in both the payload and reply portions of
Message.xsd. Refer to Figures K.1 and K.2 for a depiction of the OperationSet constructs.

There are two circumstances where the use of OperationSet is normative in IEC 61968-9
master data management:

• When modifying the configuration of a CIM object related to master data management
(e.g. nouns including but not limited to: MeterConfig, CustomerConfig, UsagePointConfig,
PricingStructureConfig, etc.) and the modification involves deleting one or more attributes
or one or more instances of associated CIM objects. An example is removing a Register
configuration from a Meter.
• When performing two or more related Master Data Management actions that shall be
handled in a specific sequence and/or with overall transactional integrity (i.e. either all
actions shall succeed or all shall be rolled back).

An IEC 61968-9 message utilizing the OperationSet construct always has a Header verb of
either “execute” or “executed” and a noun of “OperationSet”. An OperationSet in turn contains
one or more Operations, and each Operation has an operationId which supplements the
overall message CorrelationID to provide a fine-grained ability to correlate the contents of one
or more reply messages with the individual Operations in an OperationSet. Individual
Operations within an OperationSet have OperationSet-level verbs and nouns. Allowable verbs
are create, created, change, changed, delete and deleted.

To support circumstance a) above, each Operation in an OperationSet includes an


elementOperation boolean. This boolean is to be set to “true” when the Operation verb is
either “delete” or “deleted” and the intent is to delete individual attributes or individual
instances of associated CIM classes from the object specified by the OperationSet noun (as
opposed to deleting the entire CIM object specified by the Operation noun). It is emphasized
that in this case (with an elementOperation boolean set to “true”), use of the Operation verb
“delete” or “deleted” effectively modifies rather than deletes the CIM object specified by the
Operation noun. If omitted, elementOperation is assumed to be “false”.

To support circumstance b) above, each OperationSet may have either an


enforceMsgSequence boolean or an enforceTransactionalIntegrity boolean, or both. The
enforceMsgSequence boolean is to be set to “true” when the Operations in the OperationSet
shall be executed in ascending order of their operationID. The enforceTransactionalIntegrity
boolean is to be set to “true” if all Operations in the OperationSet shall succeed. In this case,
if all such Operations do not succeed, all shall be aborted or rolled back. If either or both of
these booleans are omitted, they are assumed to be “false”.

When modifying the configuration of a CIM object related to IEC 61968-9 master data
management using any of the verbs “change”, “changed”, “delete” or “deleted”, only the ID of
the object being changed and the information that is being changed is to be included. This is
true whether or not an OperationSet is being used. It is for this reason that almost all
elements within the IEC 61968-9 Master Data Management Profiles are optional in the
profiles.
– 396 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure K.1 – Message Envelope Extension

Only one OperationSet may be included in a single IEC 61968-9 master data management
message.

It should also be noted that while this standard provides the means to convey master data
management transactions using XML schema-based data structures, it is also technically
possible to leverage IEC 61970-552 for transactions based upon RDF. Such capability may or
may not be provided in future editions of the IEC 61968-9 and IEC 61968-100 standards.

K.2 OperationSet

The diagram in Figure K.2 describes the OperationSet element in more detail. An
OperationSet can:

Require that each operation is sequentially executed by setting the enforceMsgSequence flag
to ""true".

Require that transactional integrity be maintained (i.e. all or nothing), by setting the
enforceTransactionalIntegrity flag to ""true".
61968-9  IEC:2013 – 397 –

Have one or more Operations, where each operation has a noun, verb and payload.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure K.2 – OperationSet

Within the Operation element, the noun will identify the type of the “any” element. The
elementOperation value will cause the transaction to either act upon the object or elements
within the object. Please refer also to examples provided at the end of Annex L.

K.3 Patterns

Any given IEC 61968-9 master data management transaction may be executed using either a
request-response message pattern (request stereotype and response stereotype messages)
or a published event message pattern (event stereotype messages). Four exemplary
sequence diagrams effectively illustrate the possible variations.

NOTE The “source of record” for IEC 61968-9 master data management information is frequently a Customer
Information System (IEC 61968-8). Recipients of this information are typically other enterprise systems such as
– 398 – 61968-9  IEC:2013

meter data management systems and metering systems. However, there are no restrictions on which systems may
issue and receive IEC 61968-9 master data management messages.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure K.3 – Pattern 1: Request/response (non-OperationSet)

This request / response pattern can be used for any of the Master Data Management “config”
transactions identified in 5.10.3 as well as for the MasterDataLinkageConfig and
ObjectNamesConfig transactions. Simply replace the occurrences of “xxxConfig” in the
diagram with the appropriate profile name (noun). Allowable verbs are “create”, “change” and
“delete”. Depending upon the scenario, there can be multiple replies to a given create,
change, or delete message. For example, a single create message can be issued to create
multiple meters. In this case, the responding system can send a single reply message for all
meters or multiple reply messages with the reply data for one or more meters in each
message.
61968-9  IEC:2013 – 399 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure K.4 – Pattern 2: published event (non-OperationSet)

This published event pattern can also be used for any of the Master Data Management
“config” transactions identified in 5.10.3 as well as for the MasterDataLinkageConfig and
ObjectNamesConfig transactions. Simply replace the occurrences of “xxxConfig” in the
diagram with the appropriate profile name (noun). Allowable verbs are “created”, “changed”
and “deleted”. Using this pattern, an enterprise system may notify one or more other
enterprise systems of Master Data Management events without requiring any
acknowledgment or confirmation of successful processing.
– 400 – 61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure K.5 – Pattern 3: Request/response (OperationSet)

This request / response pattern can be used for any Master Data Management transaction
involving an OperationSet. The verb in the message Header is always “execute”. The
individual Operation(s) within the Operation set can have verbs and nouns consistent with the
request / response transaction in Pattern 1. Depending upon the scenario, there can be
multiple replies to a given execute / OperationSet transaction. For example, a single reply
message can be sent for the entire OperationSet, or multiple reply messages can be sent,
each with the reply data for one or more Operations in each message. The operationID
element for each Operation in the request message is supplied in the reply message(s). This
is used, in conjunction with the overall CorrelationID in the message Header(s) to correlate
replies with their corresponding requests.
61968-9  IEC:2013 – 401 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure K.6 – Pattern 4: published event (OperationSet)

This published event pattern can also be used for any Master Data Management transaction
involving an OperationSet. The verb in the message Header is always “executed”. The
individual Operation(s) within the Operation set can have verbs and nouns consistent with the
published event transaction in Pattern 2. Using this pattern, an enterprise system may notify
one or more other enterprise systems of Master Data Management OperationSet events
without requiring any acknowledgment or confirmation of successful processing.
– 402 – 61968-9  IEC:2013

Annex L
(informative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Master data management use cases and sample XML

L.1 General

The purpose of this annex is to provide a description of informative use cases related to
master data management. It also provides sample XML to illustrate the intended usage of the
Master Data Management / Data Synchronization related profiles.

Table L.1 that follows identifies 53 exemplary Master Data Management / Data
Synchronization use cases and provides guidance on how to construct and populate the
request or event stereotype message for each use case.

In actual practice, use cases that utilize the request / response messaging pattern (See
Annex K) will have an optional simple acknowledgment message (verb = “reply”, Result =
“OK” and Reply.Error.code = “0.3) and one or more response messages (verb = “reply”)
indicating success or failure of each individual config operation in a given request message.

Following the table are sample XML examples that illustrate the messages exchanged for
several exemplary use cases utilizing the request / response pattern. While only a limited
number of use cases are presented with their sample XML, the examples provided are
sufficient to illustrate the intended usage of all of the IEC 61968-9 master data management
related profiles.

The sample XML provided includes population of the IEC 61968 elements from the Message
envelope (Message.xsd from IEC 61968-100) as well as the payloads described in this
standard. Including the content in the Header, Request, Reply and Payload sections of the
message is necessary to illustrate the intended use of the messages, especially in the cases
where OperationSet is employed.

The sample XML provided includes population of only a small subset of the attributes
available for fully describing the “configurations” of Meters, UsagePoints, and other CIM
objects. It is not the intent of these use cases to provide full configuration details for these
objects; it is simply to illustrate the techniques involved in creating, modifying, and deleting
these objects as well as the techniques for managing the relationships between these objects
using the MasterDataLinkageConfig profile. Also illustrated is the use of the OperationSet in
both if its two normative uses as described in 5.10 and Annex K:

• When modifying the configuration of a CIM object related to Master Data Management
(e.g. nouns including but not limited to: MeterConfig, CustomerConfig, UsagePointConfig,
PricingStructureConfig, etc.) and the modification involves deleting one or more attributes
or one or more instances of associated CIM objects. An example is removing a Register
configuration from a Meter.
• When performing two or more related Master Data Management actions that shall be
handled in a specific sequence and/or with overall transactional integrity (i.e. either all
actions shall succeed or all shall be rolled back).

Please refer also to 5.10, Annex K and IEC 61968-100 for additional information related to
master data management / data synchronization.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Table L.1 – Exemplary master data management / data synchronization use cases

Use Case # DS-1 DS-2 DS-3 DS-4


Use Case Create a meter and / or receive Add or update one or more simple Delete one or more simple Add an additional instance of a
Description meter into Inventory attributes for a meter in inventory attributes for a meter in inventory class such as Register to a meter
in inventory
Header Verb create/created change/changed execute/executed change/changed
61968-9  IEC:2013

Header Noun MeterConfig MeterConfig OperationSet MeterConfig


Enforce Seq n/a n/a n/a n/a
Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a delete/deleted n/a
Op Set Noun n/a n/a MeterConfig n/a
Element Flag n/a n/a “true” n/a
Payload 1) ID of the Meter 2) As many 1) ID of the Meter 2) Attributes that 1) ID of the Meter 2) Attributes that 1) ID of the Meter 2) ID and details
Description details about the Meter as are being added or modified 3) are being deleted 3) Effectivity of the Register being added 3)
– 403 –

available / desired 3) Effectivity Effectivity dates and reason as dates and reason as appropriate Effectivity dates and reason as
dates and reason as appropriate appropriate appropriate

Relationship n/a n/a n/a n/a


Line
Comments Meter ID can be either an mRID Simple attributes have only one An OperationSet is required (even An OperationSet is not required
and/or one or more Names.name. occurrence at any given location though there is only one operation because the change does not
Present tense of verbs used for within the schema. specified) because it is necessary involve the concept of a "reverse"
request/reply patterns; past tense to set the Element Flag; otherwise action.
used for published notifications (no the delete/deleted verb with the
reply). MeterConfig noun would be
interpreted as deleting the Meter
itself.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-5 DS-6 DS-7 DS-8


Use Case Delete an instance of a class such Configure meter to collect fwd kWh Re-configure meter to have Delete a meter from inventory
Description as Register from a meter in register and 15-minute interval Channel 2 of Register 1 collect 5-
inventory readings minute fwd kWh register readings
rather than 15-minute fwd kWh
interval readings
Header Verb execute/executed change/changed change/changed delete/deleted
Header Noun OperationSet MeterConfig MeterConfig MeterConfig
Enforce Seq n/a n/a n/a n/a
Enforce Trans n/a n/a n/a n/a
Op Set Verb delete/deleted n/a n/a n/a
Op Set Noun MeterConfig n/a n/a n/a
Element Flag “true” n/a n/a n/a
Payload 1) ID of the Meter 2) ID of the 1) ID of meter 2) ID of Register 1 1) ID of meter 2) ID of Register 1 1) ID of meter 2) Effectivity dates
Description Register being deleted 3) 3) As many details of Register 1 as 3) ID of Channel 2 of Register 1 4) and reason as appropriate
Effectivity dates and reason as available / desired 4) ID of Channel As many details of Channel 2 of
appropriate 1 of Register 1 5) As many details Register 1 as available / desired,
of Channel 1 of Register 1 as including ReadingType for 5minute
available / desired, including DeltaData fwd kWh 5) Effectivity
ReadingType for BulkQuantity fwd dates and reason as appropriate
– 404 –

kWh 6) ID of Channel 2 of Register


1 7) As many details of Channel 2
of Register 1 as available /
desired, including ReadingType for
15minute DeltaData fwd kWh 8)
Effectivity dates and reason as
appropriate
Relationship n/a n/a n/a n/a
Line
Comments An OperationSet is required (even An OperationSet is not required An OperationSet is not required Many systems may choose not to
though there is only one operation because the change does not because the change does not delete meters but to mark the
specified) because it is necessary involve the concept of a "reverse" involve the concept of a "reverse" meters as removed and/or retired.
to set the Element Flag; otherwise action. (This assumes that action. If Channel 2 was being
the delete/deleted verb with the registers and channels were not deleted and Channel 3 was being
MeterConfig noun would be previously configured for this added (rather than just modifying
interpreted as deleting the Meter Meter.) Channel 2), then an OperationSet
itself. would be required.
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-9 DS-10 DS-11 DS-12


Use Case Receive com module into inventory Create a service category Create a service supplier Create a service location
Description
Header Verb create/created create/created create/created create/created
Header Noun ComModuleConfig ServiceCategoryConfig SupplierConfig ServiceLocationConfig
61968-9  IEC:2013

Enforce Seq n/a n/a n/a n/a


Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the ComModule 2) As 1) ID of the ServiceCategory 2) As 1) ID of the ServiceSupplier 2) As 1) ID of the ServiceLocation 2) As
Description many details about the ComModule many details about the many details about the many details about the
as available / desired 3) Effectivity ServiceCategory as available / ServiceSupplier as available / ServiceLocation as available /
– 405 –

dates and reason as appropriate desired 3) Effectivity dates and desired 3) Effectivity dates and desired 3) Effectivity dates and
reason as appropriate reason as appropriate reason as appropriate

Relationship
n/a n/a n/a n/a
Line
Comments Follow the examples of Use Cases Follow the examples of Use Cases In de-regulated markets, the Follow the examples of Use Cases
DS-2 through DS-8 for changes to DS-2 through DS-8 for changes to distribution utility and the retailer DS-2 through DS-8 for changes to
or deletion of a ComModule after it or deletion of a ServiceCategory. may be separate ServiceSuppliers or deletion of a Servicelocation.
is in inventory. (having different
ServiceSupplier.kind) Follow the
examples of Use Cases DS-2
through DS-8 for changes to or
deletion of a ServiceSupplier.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-13 DS-14 DS-15


Use Case Create a usage point location Create a usage point Create a customer
Description
Header Verb create/created create/created create/created
Header Noun UsagePointLocationConfig UsagePointConfig CustomerConfig
Enforce Seq n/a n/a n/a
Enforce Trans n/a n/a n/a
Op Set Verb n/a n/a n/a
Op Set Noun n/a n/a n/a
Element Flag n/a n/a n/a
Payload 1) ID of the UsagePointLocation 2) 1) ID of the UsagePoint 2) As many 1) ID of the Customer 2) As many
Description As many details about the details about the UsagePoint as details about the Customer as
UsagePointLocation as available / available / desired 3) Effectivity available / desired 3) Effectivity
desired 3) Effectivity dates and dates and reason as appropriate dates and reason as appropriate
reason as appropriate

Relationship
n/a n/a n/a
Line
– 406 –

Comments Follow the examples of Use Cases If the UsagePoint is also a service Follow the examples of Use Cases
DS-2 through DS-8 for changes to delivery point (point of demarcation DS-2 through DS-8 for changes to
or deletion of a between utility and customer or deletion of a Customer.
UsagePointLocation. ownership), set the isSdp Boolean
to “true”. If any of the following are
to be included as part of the
creation of the UsagePoint, they
shall exist in advance of the create
/ created UsagePointConfig
message: ServiceSupplier,
ServiceCategory, ServiceLocation,
UsagePointLocation. Follow the
examples of Use Cases DS-2
through DS-8 for changes to or
deletion of a UsagePoint.
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-16 DS-17 DS-18 DS-19


Use Case Create a customer account Create a customer agreement Create a pricing structure Create a non-meter end device
Description (including a PAN device)
Header Verb create/created create/created create/created create/created
Header Noun CustomerAccountConfig CustomerAgreementConfig Pricing StructureConfig EndDeviceConfig
61968-9  IEC:2013

Enforce Seq n/a n/a n/a n/a


Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the CustomerAccount 2) 1) ID of the CustomerAgreement 2) 1) ID of the PricingStructure 2) As 1) ID of the EndDevice 2) As many
Description As many details about the As many details about the many details about the details about the EndDevice as
CustomerAccount as available / Customer Agreement as available / PricingStructure as available / available / desired 3) Effectivity
– 407 –

desired 3) Effectivity dates and desired 3) Effectivity dates and desired 3) Effectivity dates and dates and reason as appropriate
reason as appropriate reason as appropriate reason as appropriate

Relationship
n/a n/a n/a n/a
Line
Comments Follow the examples of Use Cases Follow the examples of Use Cases Follow the examples of Use Cases If the EndDevice is a PAN device,
DS-2 through DS-8 for changes to DS-2 through DS-8 for changes to DS-2 through DS-8 for changes to set the isPan Boolean to “true”or
or deletion of a CustomerAccount. or deletion of a or deletion of a PricingStructure. meters, see Use Case DS-1.
CustomerAgreement. Follow the examples of Use Cases
DS-2 through DS-8 for changes to
or deletion of an EndDevice.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-20 DS-21 DS-22 DS-23


Use Case Shop install a com module into a Remove a com module from a Reflect the pairing of an end Reflect the unpairing of an end
Description meter meter device (e.g., a PAN device) to a device (e.g., a PAN device) from a
meter meter
Header Verb create/created delete/deleted create/created delete/deleted
Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig
Enforce Seq n/a n/a n/a n/a
Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the ComModule 2) ID of 1) ID of the ComModule 2) ID of 1) ID of the EndDevice 2) ID of the 1) ID of the EndDevice 2) ID of the
Description the Meter 3) Effectivity dates and the Meter 3) Effectivity dates and Meter 3) Effectivity dates and Meter 3) Effectivity dates and
reason as appropriate reason as appropriate reason as appropriate reason as appropriate
Relationship
A A B B
Line
Comments Assumes the Meter and the ComModules may not exist for Assumes the EndDevice and the Multiple EndDevices may be paired
ComModule already exist. meters with integral Meter already exist. Multiple with a given meter. Un-pairing an
ComModules may not exist for communications capabilities. This EndDevices devices may be paired EndDevice does not delete the
meters with integral transaction accomplishes only the with a given meter. An EndDevice EndDevice but only takes it out-of-
communications capabilities. "delinkage" of these objects. If may optionally be "paired" with a service for that meter. This
– 408 –

Multiple com modules (e.g., one for there is a desire to update either or UsagePoint rather than a meter. transaction accomplishes only the
AMI network and a ZigBee module both of the object records, This would most typically be done "delinkage" of these objects. If
for Home Area Networking) may be additional messages can be when the communication with a there is a desire to update either or
installed into a meter. This created. Additionally, the multiple PAN device is not via the meter. both of the object records,
transaction accomplishes only the actions may be combined with See Use Case DS25. At any given additional messages can be
"linkage" of these objects. If there control over sequence and overall time, a EndDevice should not be created. Additionally, the multiple
is a desire to update either or both transaction integrity using the paired with both a Meter and a actions may be combined with
of the object records, additional OperationSet construct in UsagePoint. This transaction control over sequence and overall
messages can be created. Message.xsd. This approach is accomplishes only the "linkage" of transaction integrity using the
Additionally, the multiple actions illustrated in a number of separate these objects. If there is a desire to OperationSet construct in
may be combined with control over use cases. update either or both of the object Message.xsd. This approach is
sequence and overall transaction records, additional messages can illustrated in a number of separate
integrity using the OperationSet be created. Additionally, the use cases.
construct in Message.xsd. This multiple actions may be combined
approach is illustrated in a number with control over sequence and
of separate use cases. overall transaction integrity using
the OperationSet construct in
Message.xsd. This approach is
illustrated in a number of separate
61968-9  IEC:2013

use cases.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-24 DS-25 DS-26 DS-27


Use Case Reflect the pairing of an end Reflect the unpairing of an end Reflect the installation of a meter Reflect the removal of a meter
Description device (e.g., a PAN device) to a device (e.g., a PAN device) from a at usage point from a usage point
usage point a usage point
Header Verb create/created delete/deleted create/created delete/deleted
Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig
Enforce Seq n/a n/a n/a n/a
61968-9  IEC:2013

Enforce Trans n/a n/a n/a n/a


Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the EndDevice 2) ID of the 1) ID of the EndDevice 2) ID of the 1) ID of the Meter 2) ID of the 1) ID of the Meter 2) ID of the
Description UsagePoint 3) Effectivity dates and UsagePoint 3) Effectivity dates and UsagePoint 3) Effectivity dates and UsagePoint 3) Effectivity dates and
reason as appropriate reason as appropriate reason as appropriate reason as appropriate

Relationship
C C D D
– 409 –

Line
Comments Assumes the EndDevice and the Multiple end devices may be paired Assumes that both the Meter and Multiple meters may be installed at
UsagePoint already exist. Multiple with a given Usage Point. Un- the UsagePoint already exist. a given UsagePoint, although some
end devices may be paired with a pairing an EndDevice does not Multiple meters may be installed at enterprise systems do not support
given UsagePoint. A EndDevice delete the EndDevice but only a given UsagePoint, although some doing so. Removing (uninstalling) a
may optionally be "paired" with a takes it out-of-service for that enterprise systems do not support meter does not delete the Meter
meter rather than a UsagePoint. UsagePoint. This transaction doing so. This is the master data but only takes it out-of-service for
This would most typically be done accomplishes only the "delinkage" synchronization transaction that UsagePoint. This transaction
when the communication with a of these objects. If there is a desire reflecting the meter installation. It accomplishes only the "delinkage"
PAN device is via the meter. See to update either or both of the may be preceded by or of these objects. If there is a desire
Use Case DS-23. At any given object records, additional accompanied by another Part 9 to update either or both of the
time, an EndDevice should not be messages can be created. message associated with a service object records, additional
paired with both a Meter and a Additionally, the multiple actions request for the field work messages can be created.
UsagePoint. This transaction may be combined with control over associated with the installation. Additionally, the multiple actions
accomplishes only the "linkage" of sequence and overall transaction This transaction accomplishes only may be combined with control over
these objects. I there is a desire to integrity using the OperationSet the "linkage" of these objects. If sequence and overall transaction
update either or both of the object construct in Message.xsd. This there is a desire to update either or integrity using the OperationSet
records, additional messages can approach is illustrated in a number both of the object records, construct in Message.xsd. This
be created. Additionally, the of separate use cases. additional messages can be approach is illustrated in a number
multiple actions may be combined created. Additionally, the multiple of separate use cases.
with control over sequence and actions may be combined with
overall transaction integrity using control over sequence and overall
the OperationSet construct in transaction integrity using the
Message.xsd. This approach is OperationSet construct in
illustrated in a number of separate Message.xsd. This approach is
use cases. illustrated in a number of separate
use cases.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-28 DS-29 DS-30 DS-31


Use Case Associate a pricing structure with a Disassociate a pricing structure Associate a customer agreement Disassociate a customer
Description usage point from a usage point with a usage point agreement from a usage point
Header Verb create/created delete/deleted create/created delete/deleted
Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig
Enforce Seq n/a n/a n/a n/a
Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the PricingStructure 2) ID 1) ID of the PricingStructure 2) ID 1) ID of the CustomerAgreement 2) 1) ID of the CustomerAgreement 2)
Description of the UsagePoint 3) Effectivity of the UsagePoint 3) Effectivity ID of the UsagePoint 3) Effectivity ID of the UsagePoint 3) Effectivity
dates and reason as appropriate dates and reason as appropriate dates and reason as appropriate dates and reason as appropriate

Relationship
G G H H
Line
– 410 –

Comments Assumes that both the This transaction accomplishes only Assumes that both the This transaction accomplishes only
PricingStructure and the the "delinkage" of these objects. If CustomerAgreement and the the "delinkage" of these objects. If
UsagePoint already exist. This there is a desire to update either or UsagePoint already exist. This there is a desire to update either or
transaction accomplishes only the both of the object records, transaction accomplishes only the both of the object records,
"linkage" of these objects. If there additional messages can be "linkage" of these objects. If there additional messages can be
is a desire to update either or both created. Additionally, the multiple is a desire to update either or both created. Additionally, the multiple
of the object records, additional actions may be combined with of the object records, additional actions may be combined with
messages can be created. control over sequence and overall messages can be created. control over sequence and overall
Additionally, the multiple actions transaction integrity using the Additionally, the multiple actions transaction integrity using the
may be combined with control over OperationSet construct in may be combined with control over OperationSet construct in
sequence and overall transaction Message.xsd. This approach is sequence and overall transaction Message.xsd. This approach is
integrity using the OperationSet illustrated in a number of separate integrity using the OperationSet illustrated in a number of separate
construct in Message.xsd. This use cases. construct in Message.xsd. This use cases.
approach is illustrated in a number approach is illustrated in a number
of separate use cases. of separate use cases.
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-32 DS-33 DS-34 DS-35


Use Case Associate a customer account with Disassociate a customer account Associate a customer with a usage Disassociate a customer from a
Description a usage point from a usage point point usage point
Header Verb create/created delete/deleted create/created delete/deleted
Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig
Enforce Seq n/a n/a n/a n/a
61968-9  IEC:2013

Enforce Trans n/a n/a n/a n/a


Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the CustomerAccount 2) ID 1) ID of the CustomerAccount 2) ID 1) ID of the Customer 2) ID of the 1) ID of the Customer 2) ID of the
Description of the UsagePoint 3) Effectivity of the UsagePoint 3) Effectivity UsagePoint 3) Effectivity dates and UsagePoint 3) Effectivity dates and
dates and reason as appropriate dates and reason as appropriate reason as appropriate reason as appropriate
– 411 –

Relationship
K K L L
Line
Comments Assumes that both the This transaction accomplishes only Assumes that both the Customer This transaction accomplishes only
CustomerAccount and the the "delinkage" of these objects. If and the UsagePoint already exist. the "delinkage" of these objects. If
UsagePoint already exist. This there is a desire to update either or This transaction accomplishes only there is a desire to update either or
transaction accomplishes only the both of the object records, the "linkage" of these objects. If both of the object records,
"linkage" of these objects. If there additional messages can be there is a desire to update either or additional messages can be
is a desire to update either or both created. Additionally, the multiple both of the object records, created. Additionally, the multiple
of the object records, additional actions may be combined with additional messages can be actions may be combined with
messages can be created. control over sequence and overall created. Additionally, the multiple control over sequence and overall
Additionally, the multiple actions transaction integrity using the actions may be combined with transaction integrity using the
may be combined with control over OperationSet construct in control over sequence and overall OperationSet construct in
sequence and overall transaction Message.xsd. This approach is transaction integrity using the Message.xsd. This approach is
integrity using the OperationSet illustrated in a number of separate OperationSet construct in illustrated in a number of separate
construct in Message.xsd. This use cases. Message.xsd. This approach is use cases.
approach is illustrated in a number illustrated in a number of separate
of separate use cases. use cases.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-36 DS-37 DS-38 DS-39


Use Case Associate a pricing structure with a Disassociate a pricing structure Associate a service location with a Disassociate a service location
Description customer agreement from a customer agreement customer agreement from a customer agreement
Header Verb create/created delete/deleted create/created delete/deleted
Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig
Enforce Seq n/a n/a n/a n/a
Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the PricingStructure 2) ID 1) ID of the PricingStructure 2) ID 1) ID of the ServiceLocation 2) ID 1) ID of the ServiceLocation 2) ID
Description of the CustomerAgreement 3) of the CustomerAgreement 3) of the CustomerAgreement 3) of the CustomerAgreement 3)
Effectivity dates and reason as Effectivity dates and reason as Effectivity dates and reason as Effectivity dates and reason as
appropriate appropriate appropriate appropriate

Relationship
N N O O
Line
Comments Assumes that both the This transaction accomplishes only Assumes that both the This transaction accomplishes only
– 412 –

PricingStructure and the the "delinkage" of these objects. If ServiceLocation and the the "delinkage" of these objects. If
CustomerAgreement already exist. there is a desire to update either or CustomerAgreement already exist. there is a desire to update either or
This transaction accomplishes only both of the object records, This transaction accomplishes only both of the object records,
the "linkage" of these objects. If additional messages can be the "linkage" of these objects. If additional messages can be
there is a desire to update either or created. Additionally, the multiple there is a desire to update either or created. Additionally, the multiple
both of the object records, actions may be combined with both of the object records, actions may be combined with
additional messages can be control over sequence and overall additional messages can be control over sequence and overall
created. Additionally, the multiple transaction integrity using the created. Additionally, the multiple transaction integrity using the
actions may be combined with OperationSet construct in actions may be combined with OperationSet construct in
control over sequence and overall Message.xsd. This approach is control over sequence and overall Message.xsd. This approach is
transaction integrity using the illustrated in a number of separate transaction integrity using the illustrated in a number of separate
OperationSet construct in use cases. OperationSet construct in use cases.
Message.xsd. This approach is Message.xsd. This approach is
illustrated in a number of separate illustrated in a number of separate
use cases. use cases.
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-40 DS-41 DS-42 DS-43


Use Case Associate a usage point location Disassociate a usage point location Associate a customer account with Disassociate a customer account
Description with a service location from a service location a customer from a customer
Header Verb create/created delete/deleted create/created delete/deleted
Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig
Enforce Seq n/a n/a n/a n/a
61968-9  IEC:2013

Enforce Trans n/a n/a n/a n/a


Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the UsagePointLocation 2) 1) ID of the UsagePointLocation 2) 1) ID of the CustomerAccount 2) ID 1) ID of the CustomerAccount 2) ID
Description ID of the ServiceLocation 3) ID of the ServiceLocation 3) of the Customer 3) Effectivity dates of the Customer 3) Effectivity dates
Effectivity dates and reason as Effectivity dates and reason as and reason as appropriate and reason as appropriate
appropriate appropriate
– 413 –

Relationship
P P Q Q
Line
Comments Assumes that both the This transaction accomplishes only Assumes that both the This transaction accomplishes only
UsagePointLlocation and the the "delinkage" of these objects. If CustomerAccount and the the "delinkage" of these objects. If
ServiceLocation already exist. This there is a desire to update either or Customer already exist. This there is a desire to update either or
transaction accomplishes only the both of the object records, transaction accomplishes only the both of the object records,
"linkage" of these objects. If there additional messages can be "linkage" of these objects. If there additional messages can be
is a desire to update either or both created. Additionally, the multiple is a desire to update either or both created. Additionally, the multiple
of the object records, additional actions may be combined with of the object records, additional actions may be combined with
messages can be created. control over sequence and overall messages can be created. control over sequence and overall
Additionally, the multiple actions transaction integrity using the Additionally, the multiple actions transaction integrity using the
may be combined with control over OperationSet construct in may be combined with control over OperationSet construct in
sequence and overall transaction Message.xsd. This approach is sequence and overall transaction Message.xsd. This approach is
integrity using the OperationSet illustrated in a number of separate integrity using the OperationSet illustrated in a number of separate
construct in Message.xsd. This use cases. construct in Message.xsd. This use cases.
approach is illustrated in a number approach is illustrated in a number
of separate use cases. of separate use cases.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-44 DS-45 DS-46 DS-47


Use Case Associate a customer agreement Disassociate a customer Associate a service supplier with a Disassociate a service supplier
Description with a customer account agreement from a customer customer account from a customer account
account
Header Verb create/created delete/deleted create/created delete/deleted
Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig
Enforce Seq n/a n/a n/a n/a
Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the CustomerAgreement 2) 1) ID of the CustomerAgreement 2) 1) ID of the ServiceSupplier 2) ID 1) ID of the ServiceSupplier 2) ID
Description ID of the CustomerAccount 3) ID of the CustomerAccount 3) of the CustomerAccount 3) of the CustomerAccount 3)
Effectivity dates and reason as Effectivity dates and reason as Effectivity dates and reason as Effectivity dates and reason as
appropriate appropriate appropriate appropriate

Relationship
R R S S
Line
Comments Assumes that both the This transaction accomplishes only Assumes that both the This transaction accomplishes only
– 414 –

CustomerAgreement and the the "delinkage" of these objects. If ServiceSupplier and the the "delinkage" of these objects. If
Customer account already exist. there is a desire to update either or CustomerAccount already exist. there is a desire to update either or
This transaction accomplishes only both of the object records, This transaction accomplishes only both of the object records,
the "linkage" of these objects. If additional messages can be the "linkage" of these objects. If additional messages can be
there is a desire to update either or created. Additionally, the multiple there is a desire to update either or created. Additionally, the multiple
both of the object records, actions may be combined with both of the object records, actions may be combined with
additional messages can be control over sequence and overall additional messages can be control over sequence and overall
created. Additionally, the multiple transaction integrity using the created. Additionally, the multiple transaction integrity using the
actions may be combined with OperationSet construct in actions may be combined with OperationSet construct in
control over sequence and overall Message.xsd. This approach is control over sequence and overall Message.xsd. This approach is
transaction integrity using the illustrated in a number of separate transaction integrity using the illustrated in a number of separate
OperationSet construct in use cases. OperationSet construct in use cases.
Message.xsd. This approach is Message.xsd. This approach is
illustrated in a number of separate illustrated in a number of separate
use cases. use cases.
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-48 DS-49 DS-50 DS-51


Use Case Associate a service supplier with a Disassociate a service supplier Associate a customer agreement Disassociate a customer
Description customer agreement from a customer agreement with a customer agreement from a customer
account
Header Verb create/created delete/deleted create/created delete/deleted
61968-9  IEC:2013

Header Noun MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig MasterDataLinkageConfig


Enforce Seq n/a n/a n/a n/a
Enforce Trans n/a n/a n/a n/a
Op Set Verb n/a n/a n/a n/a
Op Set Noun n/a n/a n/a n/a
Element Flag n/a n/a n/a n/a
Payload 1) ID of the ServiceSupplier 2) ID 1) ID of the ServiceSupplier 2) ID 1) ID of the CustomerAgreement 2) 1) ID of the CustomerAgreement 2)
Description of the CustomerAgreement 3) of the CustomerAgreement 3) ID of the Customer 3) Effectivity ID of the Customer 3) Effectivity
– 415 –

Effectivity dates and reason as Effectivity dates and reason as dates and reason as appropriate dates and reason as appropriate
appropriate appropriate

Relationship
T T U U
Line
Comments Assumes that both the This transaction accomplishes only Assumes that both the This transaction accomplishes only
ServiceSupplier and the the "delinkage" of these objects. If CustomerAgreement and the the "delinkage" of these objects. If
CustomerAgreement already exist. there is a desire to update either or Customer already exist. This there is a desire to update either or
This transaction accomplishes only both of the object records, transaction accomplishes only the both of the object records,
the "linkage" of these objects. If additional messages can be "linkage" of these objects. If there additional messages can be
there is a desire to update either or created. Additionally, the multiple is a desire to update either or both created. Additionally, the multiple
both of the object records, actions may be combined with of the object records, additional actions may be combined with
additional messages can be control over sequence and overall messages can be created. control over sequence and overall
created. Additionally, the multiple transaction integrity using the Additionally, the multiple actions transaction integrity using the
actions may be combined with OperationSet construct in may be combined with control over OperationSet construct in
control over sequence and overall Message.xsd. This approach is sequence and overall transaction Message.xsd. This approach is
transaction integrity using the illustrated in a number of separate integrity using the OperationSet illustrated in a number of separate
OperationSet construct in use cases. construct in Message.xsd. This use cases.
Message.xsd. This approach is approach is illustrated in a number
illustrated in a number of separate of separate use cases.
use cases.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-52


Use Case Description Exchange meter 2 for meter 1 at a usage point and update the install date for meter 2 and the removal date for meter 1
Header Verb execute/executed
Header Noun OperationSet
Enforce Seq “true”
Enforce Trans “true”
Op Set Verb delete/deleted create/created change/changed change/changed
Op Set Noun MasterDataLinkageConfig MasterDataLinkageConfig MeterConfig MeterConfig
Element Flag “false” “false” “false” “false”
Payload Description 1) ID of Meter 1 2) ID of the 1) ID of Meter 2 2) ID of the 1) ID of Meter 1 2) Removal 1) ID of Meter 2 2) Installation date for
UsagePoint 3) Effectivity dates UsagePoint 3) Effectivity dates date for Meter 1 3) Effectivity Meter 2 3) Effectivity dates and reason
and reason as appropriate and reason as appropriate dates and reason as appropriate as appropriate
Relationship Line D D n/a n/a
Comments Assumes creation / configuration of meter 2 occurred in advance of ithe meter exchange transaction. The enforceMessageSequence flag is set to
“true” to ensure that meter 1 is removed before meter 2 is installed. The enforceTransactionalIntegrity flag is set to “true” to ensure that all
portions of this transaction are rolled back (voided) if any of the transactions fail. This ensures overall integrity of the database in the receiving
system.
– 416 –
61968-9  IEC:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Use Case # DS-53

Use Case Description Reflect the creation of a PAN device and its pairing with an existing meter

Header Verb execute/executed

Header Noun OperationSet


61968-9  IEC:2013

Enforce Seq “true”

Enforce Trans “true”

Op Set Verb create/created create/created

Op Set Noun EndDeviceConfig MasterDataLinkageConfig

Element Flag “false” “false”

Payload Description 1) ID of the EndDevice (PAN device) 2) As many details about the 1) ID of the EndDevice (PAN device) 2) ID of the Meter 3) Effectivity
EndDevice (PAN device) as available / desired 3) Effectivity dates dates and reason as appropriate
and reason as appropriate
– 417 –

Relationship Line n/a B

Comments For this Pan device example, the isPan Boolean in the EndDeviceConfig will be set to “true”. Assumes the meter was created in advance of
the this composite transaction. The enforceMessageSequence flag is set to “true” to ensure that the PAN device is created before it is
associated with the meter. The enforceTransactionalIntegrity flag is set to “true” to ensure that all portions of this transaction are rolled back
(voided) if any of the transactions fail. This ensures overall integrity of the database in the receiving system.
– 418 – 61968-9  IEC:2013

L.2 Sample XML for Exemplary Master Data management use cases
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

The remainder of this Annex provides sample XML for a set of use cases that illustrates the
intended use of the part 9 Master Data Management Transaction profile set.

Although only a small subset of the available profiles is included, the examples are applicable
to the remaining Master Data Management use cases and profiles.

In most of the examples below, there are 4 steps for each use case:

• a CIS system sends a create message to the Meter Data Management System (MDMS) to
synchronize certain master data,
• the MDMS sends a simple acknowledgment response message to the CIS to indicate it
has received the request. (This is an optional step that is bypassed when using JMS
messaging if the AckRequired in the Header of the Step 1 request message is set to
“false”),
• the MDMS sends a response message to the CIS to indicate that the request was
completed successfully, or
• the MDMS sends a response message to the CIS to indicate that the request failed to
complete successfully.
61968-9  IEC:2013 – 419 –

L.2.1 Create MeterConfig – Two Meters – Step 1


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<xsi:import namespace = "http://iec.ch/TC57/2011/MeterConfig#" schemaLocation =
"MeterConfig.xsd"/>
<Header>
<Verb>create</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:30:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>8B3EF3E8-C61C-4C91-BEF0-A1775570656A</MessageID>
<CorrelationID>8B3EF3E8-C61C-4C91-BEF0-A1775570656A</CorrelationID>
</Header>
<Payload>
<m:MeterConfig>
<m:ComFunction>
<m:mRID>14470EB8-F28F-433E-9A34-D61C845FD976</m:mRID>
<m:direction>biDirectional</m:direction>
<m:technology>cellular</m:technology>
</m:ComFunction>
<m:Meter>
<m:mRID>B95ED625-2EDB-437F-977C-6E2991EE61CB</m:mRID>
<m:amrSystem>AmrSystemName</m:amrSystem>
<m:formNumber>2S</m:formNumber>
<m:ConfigurationEvents>
<m:createdDateTime>2001-12-17T09:30:47Z</m:createdDateTime>
<m:effectiveDateTime>2001-12-19T00:00:00Z</m:effectiveDateTime>
</m:ConfigurationEvents>
<m:electronicAddress>
<m:mac>00:24:E8:A7:69:E7</m:mac>
</m:electronicAddress>
<m:ComFunction ref = "14470EB8-F28F-433E-9A34-D61C845FD976"/>
<m:EndDeviceInfo>
<m:isSolidState>true</m:isSolidState>
<m:phaseCount>1</m:phaseCount>
<m:capability>
<m:autonomousDst>true</m:autonomousDst>
<m:communication>true</m:communication>
<m:connectDisconnect>false</m:connectDisconnect>
<m:electricMetering>true</m:electricMetering>
<m:metrology>true</m:metrology>
<m:onRequestRead>true</m:onRequestRead>
</m:capability>
</m:EndDeviceInfo>
<m:Names>
<m:name>A47129</m:name>
<m:NameType>
<m:name>MeterBadgeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:Meter>
<m:Meter>
<m:mRID>ED04579E-FF0F-418E-92AC-B8BBE5721870</m:mRID>
<m:amrSystem>AmrSystemName</m:amrSystem>
<m:formNumber>2S</m:formNumber>
<m:ConfigurationEvents>
<m:createdDateTime>2001-12-17T09:30:47Z</m:createdDateTime>
<m:effectiveDateTime>2001-12-19T00:00:00Z</m:effectiveDateTime>
</m:ConfigurationEvents>
<m:electronicAddress>
<m:mac>00:24:E8:B7:79:E7</m:mac>
</m:electronicAddress>
<m:ComFunction ref = "14470EB8-F28F-433E-9A34-D61C845FD976"/>
<m:EndDeviceInfo>
<m:isSolidState>true</m:isSolidState>
<m:phaseCount>1</m:phaseCount>
– 420 – 61968-9  IEC:2013

<m:capability>
<m:autonomousDst>true</m:autonomousDst>
<m:communication>true</m:communication>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:connectDisconnect>false</m:connectDisconnect>
<m:electricMetering>true</m:electricMetering>
<m:metrology>true</m:metrology>
<m:onRequestRead>true</m:onRequestRead>
</m:capability>
</m:EndDeviceInfo>
<m:Names>
<m:name>C57129</m:name>
<m:NameType>
<m:name>MeterBadgeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:Meter>
</m:MeterConfig>
</Payload>
</RequestMessage>

L.2.2 Create MeterConfig – Two Meters – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:31:47Z</Timestamp>
<Source>MDMS</Source>
<MessageID>4AB99350-38CE-421C-8CD8-A0446D299E62</MessageID>
<CorrelationID>8B3EF3E8-C61C-4C91-BEF0-A1775570656A</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.3 Create MeterConfig – Two Meters – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:33:47Z</Timestamp>
<Source>MDMS</Source>
<MessageID>5624858B-9365-482E-8335-746A9A06F3FB</MessageID>
<CorrelationID>8B3EF3E8-C61C-4C91-BEF0-A1775570656A</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.0</code>
</Error>
</Reply>
</ResponseMessage>
61968-9  IEC:2013 – 421 –

L.2.4 Create MeterConfig – Two Meters – Step 4


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-17T09:30:47Z</Timestamp>
<Source>MDMS</Source>
<MessageID>3C42D9B1-65C5-4588-972B-AEF4D6B5B86C</MessageID>
<CorrelationID>8B3EF3E8-C61C-4C91-BEF0-A1775570656A</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
<Error>
<code>2.4</code>
<level>FATAL</level>
<details>Meter ID already exists</details>
<object>
<Name>
<name>C57129</name>
<NameType>
<name>MeterBadgeNumber</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
</NameTypeAuthority>
</NameType>
</Name>
<objectType>Meter</objectType>
</object>
</Error>
</Reply>
</ResponseMessage>

L.2.5 Change MeterConfig (add/change details) – Step 1

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>change</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-18T09:30:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>A98D203B-35CB-44F0-AE4F-026ECC771A76</MessageID>
<CorrelationID>A98D203B-35CB-44F0-AE4F-026ECC771A76</CorrelationID>
</Header>
<Payload>
<m:MeterConfig>
xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterConfig# MeterConfig.xsd"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:Meter>
<m:formNumber>12S</m:formNumber>
<m:ConfigurationEvents>
<m:createdDateTime>2001-12-18T09:30:47Z</m:createdDateTime>
<m:effectiveDateTime>2001-12-19T00:00:00Z</m:effectiveDateTime>
<m:Names>
<m:name>A47129</m:name>
<m:NameType>
<m:name>MeterBadgeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
– 422 – 61968-9  IEC:2013

</m:ConfigurationEvents>
<m:MeterMultipliers>
<m:kind>kH</m:kind>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:value>14.4</m:value>
</m:MeterMultipliers>
</m:Meter>
</m:MeterConfig>
</Payload>
</RequestMessage>

L.2.6 Change MeterConfig (add/change details) – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-18T09:30:48Z</Timestamp>
<Source>MDMS</Source>
<MessageID>FAD69463-6311-4A1E-89B4-0A22C76CA4B8</MessageID>
<CorrelationID>A98D203B-35CB-44F0-AE4F-026ECC771A76</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.7 Change MeterConfig (add/change details) – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-18T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>C0D5BF89-412B-43B7-8713-68993EB4B0C0</MessageID>
<CorrelationID>A98D203B-35CB-44F0-AE4F-026ECC771A76</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.0</code>
</Error>
</Reply>
</ResponseMessage>

L.2.8 Change MeterConfig (add/change details) – Step 4

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
61968-9  IEC:2013 – 423 –

<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-17T09:30:47Z</Timestamp>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<Source>MDMS</Source>
<MessageID>3C42D9B1-65C5-4588-972B-AEF4D6B5B86C</MessageID>
<CorrelationID>8B3EF3E8-C61C-4C91-BEF0-A1775570656A</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
<Error>
<code>2.4</code>
<level>FATAL</level>
<details>Meter ID not found</details>
<object>
<Name>
<name>C57129</name>
<NameType>
<name>MeterBadgeNumber</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
</NameTypeAuthority>
</NameType>
</Name>
<objectType>Meter</objectType>
</object>
</Error>
</Reply>
</ResponseMessage>

L.2.9 Change MeterConfig (delete details) – Step 1

This use case deletes information concerning a Meter – not the Meter itself
<?xml version="1.0" encoding="UTF-8"?>
<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>execute</Verb>
<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>07515735-060C-4125-9A1F-E75AEA19CA76</MessageID>
<CorrelationID>07515735-060C-4125-9A1F-E75AEA19CA76</CorrelationID>
</Header>
<Payload>
<OperationSet>
<Operation>
<operationId>1</operationId>
<noun>MeterConfig</noun>
<verb>delete</verb>
<elementOperation>true</elementOperation>
<m:MeterConfig>
xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterConfig#
MeterConfig.xsd"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:Meter>
<m:formNumber>12S</m:formNumber>
<m:ConfigurationEvents>
<m:createdDateTime>2001-12-18T09:30:47Z</m:createdDateTime>
<m:effectiveDateTime>2001-12-19T00:00:00Z</m:effectiveDateTime>
<m:Names>
<m:name>A47129</m:name>
<m:NameType>
<m:name>MeterBadgeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
– 424 – 61968-9  IEC:2013

</m:ConfigurationEvents>
<m:MeterMultipliers>
<m:kind>kH</m:kind>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:value>14.4</m:value>
</m:MeterMultipliers>
</m:Meter>
</m:MeterConfig>
</Operation>
</OperationSet>
</Payload>
</RequestMessage>

L.2.10 Change MeterConfig (delete details) – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:48Z</Timestamp>
<Source>MDMS</Source>
<MessageID>61BEB87B-490F-4108-A70A-FB25EA56BA0A</MessageID>
<CorrelationID>07515735-060C-4125-9A1F-E75AEA19CA76</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.11 Change MeterConfig (delete details) – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>280D0D3E-E899-49FE-A912-C2A4EB952546</MessageID>
<CorrelationID>07515735-060C-4125-9A1F-E75AEA19CA76</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.0</code>
</Error>
</Reply>
</ResponseMessage>

L.2.12 Change MeterConfig (delete details) – Step 4

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
61968-9  IEC:2013 – 425 –

<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:49Z</Timestamp>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<Source>MDMS</Source>
<MessageID>1D5C5DDE-9849-449A-8DF5-E8144585A9EC</MessageID>
<CorrelationID>07515735-060C-4125-9A1F-E75AEA19CA76</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
<Error>
<code>2.4</code>
<level>FATAL</level>
<details>Meter ID not found</details>
<object>
<Name>
<name>C57129</name>
<NameType>
<name>MeterBadgeNumber</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
</NameTypeAuthority>
</NameType>
</Name>
<objectType>Meter</objectType>
</object>
</Error>
<operationId>1</operationId>
</Reply>
</ResponseMessage>

L.2.13 Delete MeterConfig – Step 1

This use case deletes the Meter itself – not just information concerning a Meter. Note that this
may actually involve marking the meter as deleted rather than actually purging it from a
system.

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>delete</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-21T09:30:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>805C655B-4429-44C4-91C5-7692810627A7</MessageID>
<CorrelationID>805C655B-4429-44C4-91C5-7692810627A7</CorrelationID>
</Header>
<Payload>
<m:MeterConfig>
xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterConfig# MeterConfig.xsd"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:Meter>
<m:ConfigurationEvents>
<m:createdDateTime>2001-12-18T09:30:47Z</m:createdDateTime>
<m:effectiveDateTime>2001-12-24T00:00:00Z</m:effectiveDateTime>
<m:Names>
<m:name>A47129</m:name>
<m:NameType>
<m:name>MeterBadgeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:ConfigurationEvents>
</m:Meter>
</m:MeterConfig>
</Payload>
– 426 – 61968-9  IEC:2013

</RequestMessage>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

L.2.14 Delete MeterConfig – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-21T09:30:48Z</Timestamp>
<Source>MDMS</Source>
<MessageID>F5BA23D4-E1F7-4889-AB2A-CF3ED2BB06C9</MessageID>
<CorrelationID>805C655B-4429-44C4-91C5-7692810627A7</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.15 Delete MeterConfig – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-21T09:30:48Z</Timestamp>
<Source>MDMS</Source>
<MessageID>F5BA23D4-E1F7-4889-AB2A-CF3ED2BB06C9</MessageID>
<CorrelationID>805C655B-4429-44C4-91C5-7692810627A7</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.16 Delete MeterConfig – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
<Noun>MeterConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-21T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>E45F5726-A4A4-4FCD-A3F2-400675911D64</MessageID>
<CorrelationID>805C655B-4429-44C4-91C5-7692810627A7</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
61968-9  IEC:2013 – 427 –

<Error>
<code>2.4</code>
<level>FATAL</level>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<details>Meter ID not found</details>


<object>
<Name>
<name>C57129</name>
<NameType>
<name>MeterBadgeNumber</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
</NameTypeAuthority>
</NameType>
</Name>
<objectType>Meter</objectType>
</object>
</Error>
</Reply>
</ResponseMessage>

L.2.17 Create UsagePointConfig – Step 1

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/UsagePointConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>create</Verb>
<Noun>UsagePointConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:30:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>530E10E4-BE8D-4BE3-B346-72013D575395</MessageID>
<CorrelationID>530E10E4-BE8D-4BE3-B346-72013D575395</CorrelationID>
</Header>
<Payload>
<m:UsagePointConfig>
<m:UsagePoint>
<m:amiBillingReady>amiCapable</m:amiBillingReady>
<m:connectionState>connected</m:connectionState>
<m:isSdp>true</m:isSdp>
<m:isVirtual>false</m:isVirtual>
<m:phaseCode>A</m:phaseCode>
<m:readCycle>ReadCycleB</m:readCycle>
<m:ConfigurationEvents>
<m:createdDateTime>2012-12-17T09:30:47Z</m:createdDateTime>
<m:effectiveDateTime>2012-12-18T00:00:00Z</m:effectiveDateTime>
</m:ConfigurationEvents>
<m:Names>
<m:name>UP124179</m:name>
<m:NameType>
<m:name>ServiceDeliveryPointID</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:UsagePoint>
</m:UsagePointConfig>
</Payload>
</RequestMessage>

L.2.18 Create UsagePointConfig – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
– 428 – 61968-9  IEC:2013

xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">


<Header>
<Verb>reply</Verb>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<Noun>UsagePointConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:30:48Z</Timestamp>
<Source>MDMS</Source>
<MessageID>73767FEB-A962-44A0-B0D3-79E1F21EE307</MessageID>
<CorrelationID>530E10E4-BE8D-4BE3-B346-72013D575395</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.19 Create UsagePointConfig – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>UsagePointConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>AA31AE3A-1AA2-4016-96C7-548BB0688822</MessageID>
<CorrelationID>530E10E4-BE8D-4BE3-B346-72013D575395</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.0</code>
</Error>
</Reply>
</ResponseMessage>

L.2.20 Create UsagePointConfig – Step 4

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
<Noun>UsagePointConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>1A8A58DF-BDC9-47C6-9FDB-E86BCF726F77</MessageID>
<CorrelationID>530E10E4-BE8D-4BE3-B346-72013D575395</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
<Error>
<code>2.12</code>
<level>FATAL</level>
<details>UsagePoint ID already exists</details>
<object>
<Name>
<name>UP124179</name>
<NameType>
<name>ServiceDeliveryPointID</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
61968-9  IEC:2013 – 429 –

</NameTypeAuthority>
</NameType>
</Name>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<objectType>UsagePoint</objectType>
</object>
</Error>
</Reply>
</ResponseMessage>

L.2.21 Create MasterDataLinkageConfig – Step 1

This use case links the previously created Meter with the previously created UsagePoint
(reflecting a meter installation).

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/MasterDataLinkageConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>create</Verb>
<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T10:00:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>F47F3703-D16A-4D3C-901A-553E1E26EA03</MessageID>
<CorrelationID>F47F3703-D16A-4D3C-901A-553E1E26EA03</CorrelationID>
</Header>
<Payload>
<m:MasterDataLinkageConfig>
<m:ConfigurationEvent>
<m:createdDateTime>2012-01-17T10:00:47Z</m:createdDateTime>
<m:effectiveDateTime>2012-12-25T10:30:47Z</m:effectiveDateTime>
</m:ConfigurationEvent>
<m:Meter>
<m:Names>
<m:name>A47129</m:name>
<m:NameType>
<m:name>MeterBadgeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:Meter>
<m:UsagePoint>
<m:Names>
<m:name>UP124179</m:name>
<m:NameType>
<m:name>ServiceDeliveryPointID</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:UsagePoint>
</m:MasterDataLinkageConfig>
</Payload>
</RequestMessage>

L.2.22 Create MasterDataLinkageConfig – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
– 430 – 61968-9  IEC:2013

<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T10:00:48Z</Timestamp>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<Source>MDMS</Source>
<MessageID>86BDABD8-AA7F-4139-9292-050A93E3DA71</MessageID>
<CorrelationID>F47F3703-D16A-4D3C-901A-553E1E26EA03</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.23 Create MasterDataLinkageConfig – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>91C9B6B5-4915-4B4C-91DA-4820DD4E621F</MessageID>
<CorrelationID>F47F3703-D16A-4D3C-901A-553E1E26EA03</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.0</code>
</Error>
</Reply>
</ResponseMessage>

L.2.24 Create MasterDataLinkageConfig – Step 4

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>3A854405-BEB6-418B-B6BC-6EEE172D1A2A</MessageID>
<CorrelationID>F47F3703-D16A-4D3C-901A-553E1E26EA03</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
<Error>
<code>2.12</code>
<level>FATAL</level>
<details>UsagePoint ID not found</details>
<object>
<Name>
<name>UP124179</name>
<NameType>
<name>ServiceDeliveryPointID</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
</NameTypeAuthority>
</NameType>
</Name>
61968-9  IEC:2013 – 431 –

<objectType>UsagePoint</objectType>
</object>
</Error>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</Reply>
</ResponseMessage>

L.2.25 Delete MasterDataLinkageConfig – Step 1

This use case deletes the previously created linkage between a Meter and a UsagePoint
(reflecting a meter removal).

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/MasterDataLinkageConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>delete</Verb>
<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-02-01T10:00:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>D0DAF9E1-D62F-4711-9C05-8698EBEC5D77</MessageID>
<CorrelationID>D0DAF9E1-D62F-4711-9C05-8698EBEC5D77</CorrelationID>
</Header>
<Payload>
<m:MasterDataLinkageConfig>
<m:ConfigurationEvent>
<m:createdDateTime>2012-02-01T10:00:47Z</m:createdDateTime>
<m:effectiveDateTime>2012-02-02T00:00:00Z</m:effectiveDateTime>
</m:ConfigurationEvent>
<m:Meter>
<m:Names>
<m:name>A47129</m:name>
<m:NameType>
<m:name>MeterBadgeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:Meter>
<m:UsagePoint>
<m:Names>
<m:name>UP124179</m:name>
<m:NameType>
<m:name>ServiceDeliveryPointID</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:UsagePoint>
</m:MasterDataLinkageConfig>
</Payload>
</RequestMessage>

L.2.26 Delete MasterDataLinkageConfig – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
– 432 – 61968-9  IEC:2013

<Timestamp>2012-02-01T10:00:48Z</Timestamp>
<Source>MDMS</Source>
<MessageID>D83D7899-51D8-437D-AB28-328B78E57827</MessageID>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<CorrelationID>D0DAF9E1-D62F-4711-9C05-8698EBEC5D77</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.27 Delete MasterDataLinkageConfig – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-02-01T10:00:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>61C7969C-1F72-4E82-ADA5-AA7813C4E09C</MessageID>
<CorrelationID>D0DAF9E1-D62F-4711-9C05-8698EBEC5D77</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.0</code>
</Error>
</Reply>
</ResponseMessage>

L.2.28 Delete MasterDataLinkageConfig – Step 4

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
<Noun>MasterDataLinkageConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-02-01T10:00:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>C31A2527-0DEC-476B-B10B-DAB9F2D8AC26</MessageID>
<CorrelationID>D0DAF9E1-D62F-4711-9C05-8698EBEC5D77</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
<Error>
<code>2.13</code>
<level>FATAL</level>
<details>Meter not installed at Usage Point</details>
<object>
<Name>
<name>UP124179</name>
<NameType>
<name>ServiceDeliveryPointID</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
</NameTypeAuthority>
</NameType>
</Name>
<objectType>UsagePoint</objectType>
</object>
61968-9  IEC:2013 – 433 –

<relatedObject>
<Name>
<name>A47129</name>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<NameType>
<name>MeterBadgeNumber</name>
<NameTypeAuthority>
<name>UtilityXYZ</name>
</NameTypeAuthority>
</NameType>
</Name>
<objectType>Meter</objectType>
</relatedObject>
</Error>
</Reply>
</ResponseMessage>

L.2.29 Execute OperationSet – Step 1

This use case utilizes an Operation Set to first create a Meter, then create a UsagePoint, and
then link the Meter and the usagePoiint (reflecting a meter installation). In essence, it
performs the same functions as several of the previous uases, but does so in a single
message. This example uses the appropriate Booleans to ensure that the steps are executed
in the prescribed order and that all three steps shall succeed or the entire transaction shall
fail.

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:up = "http://iec.ch/TC57/2011/UsagePointConfig#"
xmlns:mdlc = "http://iec.ch/TC57/2011/MasterDataLinkageConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>execute</Verb>
<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>D921A053-80C1-4DB6-960E-2603127B7B92</MessageID>
<CorrelationID>D921A053-80C1-4DB6-960E-2603127B7B92</CorrelationID>
</Header>
<Payload>
<OperationSet>
<enforceMsgSequence>true</enforceMsgSequence>
<enforceTransactionalIntegrity>true</enforceTransactionalIntegrity>
<Operation>
<operationId>1</operationId>
<noun>MeterConfig</noun>
<verb>create</verb>
<mdlc:MeterConfig>
<mdlc:Meter>
<mdlc:formNumber>2S</mdlc:formNumber>
<mdlc:ConfigurationEvents>
<mdlc:createdDateTime>2012-12-20T09:30:47Z</mdlc:createdDateTime>
<mdlc:effectiveDateTime>2012-12-
21T00:00:00Z</mdlc:effectiveDateTime>
<mdlc:Names>
<mdlc:name>C34531</mdlc:name>
<mdlc:NameType>
<mdlc:name>MeterBadgeNumber</mdlc:name>
<mdlc:NameTypeAuthority>
<mdlc:name>UtilityXYZ</mdlc:name>
</mdlc:NameTypeAuthority>
</mdlc:NameType>
</mdlc:Names>
</mdlc:ConfigurationEvents>
</mdlc:Meter>
</mdlc:MeterConfig>
</Operation>
<Operation>
<operationId>2</operationId>
– 434 – 61968-9  IEC:2013

<noun>UsagePointConfig</noun>
<verb>create</verb>
<up:UsagePointConfig>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<up:UsagePoint>
<up:amiBillingReady>amiCapable</up:amiBillingReady>
<up:connectionState>connected</up:connectionState>
<up:isSdp>true</up:isSdp>
<up:isVirtual>false</up:isVirtual>
<up:phaseCode>B</up:phaseCode>
<up:readCycle>ReadCycleJ</up:readCycle>
<up:ConfigurationEvents>
<up:createdDateTime>2012-12-20T09:30:47Z</up:createdDateTime>
<up:effectiveDateTime>2012-12-21T00:00:00Z</up:effectiveDateTime>
</up:ConfigurationEvents>
<up:Names>
<up:name>UP43639</up:name>
<up:NameType>
<up:name>ServiceDeliveryPointID</up:name>
<up:NameTypeAuthority>
<up:name>UtilityXYZ</up:name>
</up:NameTypeAuthority>
</up:NameType>
</up:Names>
</up:UsagePoint>
</up:UsagePointConfig>
</Operation>
<Operation>
<operationId>3</operationId>
<noun>MasterDataLinkageConfig</noun>
<verb>create</verb>
<mdlc:MasterDataLinkageConfig>
<mdlc:ConfigurationEvent>
<mdlc:createdDateTime>2012-12-17T09:30:47Z</mdlc:createdDateTime>
<mdlc:effectiveDateTime>2012-12-21T00:00:00Z</mdlc:effectiveDateTime>
</mdlc:ConfigurationEvent>
<mdlc:Meter>
<mdlc:Names>
<mdlc:name>C34531</mdlc:name>
<mdlc:NameType>
<mdlc:name>MeterBadgeNumber</mdlc:name>
<mdlc:NameTypeAuthority>
<mdlc:name>UtilityXYZ</mdlc:name>
</mdlc:NameTypeAuthority>
</mdlc:NameType>
</mdlc:Names>
</mdlc:Meter>
<mdlc:UsagePoint>
<mdlc:Names>
<mdlc:name>UP43639</mdlc:name>
<mdlc:NameType>
<mdlc:name>ServiceDeliveryPointID</mdlc:name>
<mdlc:NameTypeAuthority>
<mdlc:name>UtilityXYZ</mdlc:name>
</mdlc:NameTypeAuthority>
</mdlc:NameType>
</mdlc:Names>
</mdlc:UsagePoint>
</mdlc:MasterDataLinkageConfig>
</Operation>
</OperationSet>
</Payload>
</RequestMessage>

L.2.30 Execute OperationSet – Step 2

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:48Z</Timestamp>
61968-9  IEC:2013 – 435 –

<Source>MDMS</Source>
<MessageID>08A2E193-F5D3-4672-B26D-A99A55591799</MessageID>
<CorrelationID>D921A053-80C1-4DB6-960E-2603127B7B92</CorrelationID>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.3</code>
</Error>
</Reply>
</ResponseMessage>

L.2.31 Execute OperationSet – Step 3

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">
<Header>
<Verb>reply</Verb>
<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>A8E8FE70-6960-4724-BF1C-CE2804EEA633</MessageID>
<CorrelationID>D921A053-80C1-4DB6-960E-2603127B7B92</CorrelationID>
</Header>
<Reply>
<Result>OK</Result>
<Error>
<code>0.0</code>
</Error>
</Reply>
</ResponseMessage>

L.2.32 Execute OperationSet – Step 4

<?xml version="1.0" encoding="UTF-8"?>


<ResponseMessage
xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd"
xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<Header>
<Verb>reply</Verb>
<Noun>OperationSet</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-12-20T09:30:49Z</Timestamp>
<Source>MDMS</Source>
<MessageID>929BFC21-06FA-4D7E-94FE-C58B3C94EFAC</MessageID>
<CorrelationID>D921A053-80C1-4DB6-960E-2603127B7B92</CorrelationID>
</Header>
<Reply>
<Result>FAILED</Result>
<Error>
<code>2.12</code>
<level>FATAL</level>
<details>UsagePoint ID already exists</details>
<ID idType=”ServiceDeliveryPointID”
idAuthority=”UtilityXYZ” objectType=”UsagePoint”>UP43639</ID>
<operationId>2</operationId>
</Error>
<Error>
<code>5.9</code>
<level>FATAL</level>
<details>Transaction aborted to maintain transactional integrity</details>
<ID> idType=”MeterBadgeNumber”
idAuthority=”UtilityXYZ” objectType=”Meter”>C34531</ID>
<operationId>1</operationId>
</Error>
<Error>
<code>5.9</code>
<level>FATAL</level>
– 436 – 61968-9  IEC:2013

<details>Transaction aborted to maintain transactional integrity</details>


<ID idType=”ServiceDeliveryPointID”
idAuthority=”UtilityXYZ” objectType=”UsagePoint”>UP43639</ID>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<relatedID> idType=”MeterBadgeNumber”
idAuthority=”UtilityXYZ” objectType=”Meter”>C34531</relatedID>
<operationId>3</operationId>
</Error>
</Reply>
</ResponseMessage>

L.2.33 Change ObjectNamesConfig

This use case utilizes the ObjectNamesConfig profile to request that the Meter identified by
mRID = “B9BCE6FE-763D-4AFB-A229-79FA885AEDC1” and MfgSerialNumber = “43531” (a
Names.name value with associated NameType and NameTypeAuthority) be changed in the
following way:

• the MfgSerialNumber be changed to “43532”, and


• a new, additional Names.name be assigned with:
• Names.name = “A1473922”
• Names.NameType.name = “BarcodeNumber”, and,
• Names.NameType.NameTypeAuthority.name = “UtilityXYZ”

The usage of the ObjectNamesConfig profile can be confusing.

The rules are as follows:

• The CIM object that is to have one or more instances of its Names class information
added, changed, or deleted is identified by mRID and/or one or more existing Names in
the element that corresponds to the object"s type (in this example use case this is the
Meter structure).
• If the verb in the request message is “create”, then any Names (along with NameType and
NameTypeAuthority) that appear in the Names structure (at the root level) of the message
become new Names class identifier(s) for the CIM object.
• If the verb in the request message is “change”, then
• any Names (along with NameType and NameTypeAuthority) that appear in the element
that corresponds to the object’s type (in this example use case this is the Meter structure)
are deleted, and
• any Names (along with NameType and NameTypeAuthority) that appear in the Names
structure (at the root level) of the message become new Names class identifier(s) for the
CIM object.
• If the verb in the request message is “delete”, then
• nothing is to be placed in the Names structure (at the root level) of the message, and
• any Names (along with NameType and NameTypeAuthority) that appear in the element
that corresponds to the object’s type (in this example use case this is the Meter structure)
are deleted.

mRIDs are immutable and cannot be changed.

Any attempt to use ObjectNamesConfig that leaves a CIM object with no valid identifiers (an
mRID and/or one or more Names class identifiers) will fail. Similarly, any attempt to use
ObjectNamesConfig that leaves a CIM object with conflicting or ambiguous Names class
identifiers will fail.

<?xml version="1.0" encoding="UTF-8"?>


<RequestMessage
61968-9  IEC:2013 – 437 –

xmlns = "http://iec.ch/TC57/2011/schema/message"
xmlns:m = "http://iec.ch/TC57/2011/ObjectNamesConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

xsi:schemaLocation = "http://iec.ch/TC57/2011/schema/message Message.xsd">


<Header>
<Verb>change</Verb>
<Noun>ObjectNamesConfig</Noun>
<Revision>2.0</Revision>
<Timestamp>2012-01-17T10:00:47Z</Timestamp>
<Source>CIS</Source>
<AckRequired>true</AckRequired>
<MessageID>1B37B91F-FE63-464A-A9FA-B239EB402169</MessageID>
<CorrelationID>1B37B91F-FE63-464A-A9FA-B239EB402169</CorrelationID>
</Header>
<Payload>
<m:ObjectNamesConfig>
<m:ConfigurationEvent>
<m:createdDateTime>2012-01-17T10:00:47Z</m:createdDateTime>
<m:effectiveDateTime>2012-01-17T10:00:47Z</m:effectiveDateTime>
</m:ConfigurationEvent>
<m:Meter>
<m:mRID>B9BCE6FE-763D-4AFB-A229-79FA885AEDC1</m:mRID>
<m:Names>
<m:name>43531</m:name>
<m:NameType>
<m:name>MfgSerialNumber</m:name>
<m:NameTypeAuthority>
<m:name>ManufacturerABC</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:Meter>
<m:Name>
<m:name>43532</m:name>
<m:NameType>
<m:name>MfgSerialNumber</m:name>
<m:NameTypeAuthority>
<m:name>ManufacturerABC</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Name>
<m:Name>
<m:name>A1473922</m:name>
<m:NameType>
<m:name>BarcodeNumber</m:name>
<m:NameTypeAuthority>
<m:name>UtilityXYZ</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Name>
</m:ObjectNamesConfig>
</Payload>
</RequestMessage>

The above sample XML is for a change/ObjectNamesConfig. The rules identified above
explain the usage for create/ObjectNamesConfig and delete/ObjectNamesConfig.

The acknowledgment and response messages for each ObjectNamesConfig use case follow
the pattern used throughout the other use case examples in this Annex.
– 438 – 61968-9  IEC:2013

Annex M
(informative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Notes on extended use of IEC 61968-100

The purpose of this Annex M is to describe some extended uses of IEC 61968-100 by
IEC 61968-9. The usages in this Annex M are informative only, and may be subject to
deprecation in the future.

In the case of "get MeterReadings", the current "GetMeterReadings" profile allows a request
to be scheduled for a future time. There may sometimes be the need to cancel this request.

Figure M.1 – Get/cancel pattern which is not recommended

While the message structures support this "get/cancel" pattern shown in Figure M.1, a
recommended approach would be through the use of a "create/cancel" pattern. In this pattern
a request object is created in the target, which may be canceled. This is illustrated by the
pattern in the sequence diagram in Figure M.2.
61968-9  IEC:2013 – 439 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure M.2 – Get/cancel pattern which is recommended


– 440 – 61968-9  IEC:2013

Bibliography
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

IEC 60050-112:2010, International Electrotechnical Vocabulary – Part 112: Quantities and


units

IEC 61970-552, Energy management system application program interface (EMS-API) –


Part 552: CIM XML model exchange format

IEC 62056 (all parts), Electricity metering data exchange

ISO 4217, Codes for the representation ofcurrencies and funds

ANSI C12.19, American National Standard for Utility Industry End Device Data Tables

_____________
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION
– 442 – 61968-9  CEI:2013

SOMMAIRE
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

AVANT-PROPOS ................................................................................................................ 449


INTRODUCTION ................................................................................................................. 452
1 Domaine d'application .................................................................................................. 454
2 Références normatives ................................................................................................. 456
3 Termes, définitions et abréviations ............................................................................... 456
3.1 Termes et définitions ........................................................................................... 456
3.2 Abréviations ........................................................................................................ 458
4 Modèles de référence et d'informations ........................................................................ 459
4.1 Approche générale aux systèmes de comptage ................................................... 459
4.2 Modèle de référence ........................................................................................... 460
4.2.1 Généralités .............................................................................................. 460
4.2.2 Système de comptage (MS) – Collecte de données (Metering system
– Data collection) .................................................................................... 465
4.2.3 Système de comptage (MS) – Commande et reconfiguration
(Metering system – Control and reconfiguration) ...................................... 466
4.2.4 Régulation de la charge ........................................................................... 466
4.2.5 Système de gestion de la charge (LMS) .................................................. 466
4.2.6 Système de gestion de biens de compteur (MAM) ................................... 466
4.2.7 Système de gestion de données de compteur (MDM) .............................. 467
4.2.8 Système d'informations clients (CIS) ....................................................... 467
4.2.9 Système de gestion des interruptions de service (OMS) .......................... 467
4.2.10 Exploitation du réseau (NO)..................................................................... 468
4.2.11 Maintenance de compteur (MM)............................................................... 468
4.2.12 Planification ............................................................................................. 468
4.2.13 Gestion des travaux (WM) ....................................................................... 468
4.2.14 Point de vente (POS) ............................................................................... 468
4.2.15 Compteur (Meter) .................................................................................... 468
4.2.16 Appareils de régulation de charge ........................................................... 468
4.2.17 Appareils PAN ......................................................................................... 469
4.2.18 Système de gestion de réponse à la demande (DRMS) ........................... 469
4.3 Modèle d'interface de référence .......................................................................... 469
4.4 Fonctions de relevé et de commande de compteurs et composants ..................... 470
4.5 Modèle statique d'informations ............................................................................ 471
4.5.1 Généralités .............................................................................................. 471
4.5.2 Classes pour le relevé et la commande des compteurs ............................ 471
4.5.3 Classes relatives au relevé et à la commande des compteurs ................. 476
5 Types de messages de relevé et de commande des compteurs .................................... 477
5.1 Généralités.......................................................................................................... 477
5.2 Messages d'événements de dispositif terminal .................................................... 478
5.2.1 Généralités .............................................................................................. 478
5.2.2 Applications ............................................................................................. 478
5.2.3 Format des messages ............................................................................. 484
5.3 Messages de relevé de compteur ........................................................................ 486
5.3.1 Généralités .............................................................................................. 486
5.3.2 Applications ............................................................................................. 486
5.3.3 Format des messages ............................................................................. 491
61968-9  CEI:2013 – 443 –

5.4 Messages de commande de dispositif terminal .................................................... 505


5.4.1 Généralités .............................................................................................. 505
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.4.2 Applications ............................................................................................. 505


5.4.3 Format des messages ............................................................................. 513
5.5 Demande de services de compteur ...................................................................... 516
5.5.1 Généralités .............................................................................................. 516
5.5.2 Applications ............................................................................................. 517
5.5.3 Format des messages ............................................................................. 522
5.6 Evénements relatifs au système de comptage ..................................................... 523
5.6.1 Généralités .............................................................................................. 523
5.6.2 Applications – Mise à niveau du firmware (microprogramme) ................... 523
5.6.3 Format des messages ............................................................................. 524
5.7 Commutation clientèle ......................................................................................... 524
5.7.1 Généralités .............................................................................................. 524
5.7.2 Format des messages ............................................................................. 524
5.8 Messages de service de comptage de paiement .................................................. 525
5.8.1 Généralités .............................................................................................. 525
5.8.2 Accords auxiliaires .................................................................................. 525
5.8.3 Applications ............................................................................................. 526
5.8.4 Format des messages ............................................................................. 527
5.9 Réseaux dans un local (Premise area networks) ................................................. 530
5.9.1 Généralités .............................................................................................. 530
5.9.2 Applications ............................................................................................. 531
5.9.3 Formats des messages ............................................................................ 534
5.10 Messages de gestion de données de référence ................................................... 534
5.10.1 Généralités .............................................................................................. 534
5.10.2 Applications ............................................................................................. 536
5.10.3 Format des messages ............................................................................. 547
6 Conventions du document ............................................................................................ 560
6.1Diagrammes UML ................................................................................................ 560
6.2Définitions des messages .................................................................................... 561
6.2.1 Généralités .............................................................................................. 561
6.2.2 Obligatoire par opposition à optionnel...................................................... 561
6.2.3 Temps des verbes (Verbs) ....................................................................... 561
6.3 Messages synchrones par opposition à asynchrones........................................... 561
6.4 Représentation des messages simples d'accusé de réception ............................. 561
Annexe A (normative) Description des verbes de types de messages ................................ 563
Annexe B (informative) Codes d'erreur de réponse ............................................................ 565
Annexe C (normative) Procédure pour la création d'un nom de ReadingType .................... 572
Annexe D (normative) Enumérations de codes de qualité .................................................. 632
Annexe E (normative) Enumérations EndDeviceEventType ................................................ 645
Annexe F (normative) Enumérations EndDeviceControlType.............................................. 690
Annexe G (normative) Conventions de désignation et d'identification des objets ................ 693
Annexe H (normative) Schémas XML pour les charges utiles de message ......................... 696
Annexe I (informative) Schémas XML pour les charges utiles de message ......................... 788
Annexe J (normative) Paramètres de demande .................................................................. 863
Annexe K (normative) Traitement des transactions de gestion de données de
référence ............................................................................................................................ 870
– 444 – 61968-9  CEI:2013

Annexe L (informative) Cas d'utilisation de gestion de données de référenceet


exemple de code XML ........................................................................................................ 879
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Annexe M (informative) Notes sur l'utilisation étendue de la norme CEI 61968-100 ........... 917
Bibliographie ....................................................................................................................... 919

Figure 1 – Domaine d'application de la norme CEI 61968-9 ................................................ 455


Figure 2 – Exemple d'un dispositif terminal avec des fonctions ........................................... 461
Figure 3 – Modèle de référence de la CEI 61968-9 ............................................................. 463
Figure 4 – Modèle de référence avec informations de clients et système de facturation
de la CEI 61968-9 ............................................................................................................... 464
Figure 5 – Détection d'interruptions de service, échange de message de
demande/réponse, exemple 1 ............................................................................................. 479
Figure 6 – Détection d'interruptions de service, échange de message de
demande/réponse, exemple 2 ............................................................................................. 480
Figure 7 – Détection d'interruptions de service, échange de publication/abonnement,
exemple 1 ........................................................................................................................... 481
Figure 8 – Détection d'interruptions de service, échange de publication/abonnement,
exemple 2 ........................................................................................................................... 481
Figure 9 – Echange d'événements liés à la santé des compteurs, exemple 1 ...................... 482
Figure 10 – Echange d'événements liés à la santé des compteurs, exemple 2 .................... 483
Figure 11 – Echange d'événements liés à la qualité de l'énergie, exemple 1 ....................... 483
Figure 12 – Echange d'événements liés à la qualité de l'énergie, exemple 2 ....................... 484
Figure 13 – Format des messages d'événements de dispositif terminal............................... 485
Figure 14 – Exemple d'utilisation d'un programme de relevé de compteur pour créer un
abonnement ........................................................................................................................ 487
Figure 15 – Exemple d'échange de relevé manuel .............................................................. 488
Figure 16 – Exemple de relevé de compteur sur demande .................................................. 490
Figure 17 – Echange de MeterData d'historique .................................................................. 490
Figure 18 – Exemple d'échange de message de demande de renseignements de
facturation .......................................................................................................................... 491
Figure 19 – Format de message pour les relevés de compteur............................................ 492
Figure 20 – Structure Reading ............................................................................................ 493
Figure 21 – Horodatages affectés entre les systèmes ......................................................... 494
Figure 22 – Conventions pour timeStamp et timePeriod ...................................................... 495
Figure 23 – Structure IntervalBlock ..................................................................................... 496
Figure 24 – Production d’horodatages pour les données d'intervalle ................................... 497
Figure 25 – Conventions relatives aux intervalles de temps ................................................ 498
Figure 26 – Structure ReadingType .................................................................................... 499
Figure 27 – Format de message pour le relevé de compteur ............................................... 504
Figure 28 – Exemple d'échange de message de régulation de charge................................. 506
Figure 29 – Exemple d'échange de message pour l'installation de l'unité de LC .................. 507
Figure 30 – Exemple d'échange de message en vue de changer le programme client ......... 508
Figure 31 – Exemple d'échange de message en vue de changer le programme client
sans la MDM ....................................................................................................................... 509
Figure 32 – Exemple de changement du programme client avec un remplacement du
compteur ............................................................................................................................ 510
61968-9  CEI:2013 – 445 –

Figure 33 – Exemple d'échange de messages pour le branchement/débranchement de


compteur ............................................................................................................................ 511
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 34 – Exemple de branchement/débranchement à distance entre le CIS et le MS ...... 512


Figure 35 – Exemple d'échange de message pour le signal de prix en temps réel ............... 513
Figure 36 – Format des messages de commandes de dispositif terminal ............................ 514
Figure 37 – Exemple d'échange de messages de pose et dépose de compteur ................... 518
Figure 38 – Exemple d'échange de messages d'événement de dispositif terminal en
raison d'un changement de compteur .................................................................................. 519
Figure 39 – Exemple d'échange de messages suite à des alarmes du CIS .......................... 520
Figure 40 – Exemple d'échange de message lorsque le compteur est remplacé pour
réétalonnage....................................................................................................................... 521
Figure 41 – Format de message de demandes de service de compteur .............................. 522
Figure 42 – Exemple d'échange de message de mise à niveau du firmware ........................ 523
Figure 43 – Exemple d'échange de message de commutation clientèle ............................... 524
Figure 44 – Echange de messages pour transférer des informations relatives aux
accords auxiliaires .............................................................................................................. 525
Figure 45 – Echange de messages pour transférer des informations d'acquit ...................... 526
Figure 46 – Echange de messages pour transférer des informations de transaction ............ 527
Figure 47 – Format de message de configuration des accords auxiliaires ........................... 528
Figure 48 – Format de message ReceiptRecord .................................................................. 529
Figure 49 – Format de message TransactionRecord ........................................................... 530
Figure 50 – Pairage d'un appareil PAN ............................................................................... 532
Figure 51 – Evénements de l'appareil PAN ......................................................................... 533
Figure 52 – Commandes de l'appareil PAN ......................................................................... 534
Figure 53 – Liens de données de référence ........................................................................ 536
Figure 54 – Echange de messages pour transférer des informations de fournisseur ........... 538
Figure 55 – Echange de messages pour transférer des informations client ......................... 539
Figure 56 – Echange de messages pour transférer des informations d'accord client ........... 540
Figure 57 – Echange de messages pour transférer des informations de compte client ........ 541
Figure 58 – Echange de messages pour transférer des informations de catégorie de
service ................................................................................................................................ 542
Figure 59 – Echange de messages pour transférer des informations de point d'usage ........ 543
Figure 60 – Echange de messages pour transférer des informations de compteur .............. 544
Figure 61 – Echange de messages pour transférer des informations de dispositif
terminal .............................................................................................................................. 545
Figure 62 – Echange de messages pour transférer des informations d'emplacement de
service ................................................................................................................................ 546
Figure 63 – Echange de messages pour transférer des structures tarifaires ........................ 547
Figure 64 – Format de message MasterDataLinkageConfig ................................................ 548
Figure 65 – Format de message de configuration des fournisseurs de service .................... 549
Figure 66 – Message de configuration client ....................................................................... 550
Figure 67 – Message de configuration des accords client ................................................... 551
Figure 68 – Message de configuration des comptes client .................................................. 552
Figure 69 – Format de message ServiceCategoryConfig ..................................................... 552
Figure 70 – Format de message UsagePointConfig............................................................. 553
– 446 – 61968-9  CEI:2013

Figure 71 – Format de message UsagePointLocationConfig ............................................... 555


Figure 72 – Format des messages de configuration de dispositif terminal ........................... 556
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 73 – Message de configuration du compteur ............................................................ 557


Figure 74 – Format de message ComModuleConfig ............................................................ 558
Figure 75 – Format de message ServiceLocationConfig ...................................................... 559
Figure 76 – Format de message PricingStructureConfig ...................................................... 560
Figure B.1 – Etats des messages de réponse ..................................................................... 571
Figure C.1 – Enumérations typiques des comportements d'accumulation ............................ 580
Figure C.2 – Enumérations typiques des sens d'écoulement ............................................... 589
Figure C.3 – Mesures de tension ........................................................................................ 594
Figure E.1 – Données d'événement .................................................................................... 647
Figure G.1 – Désignation CIM ............................................................................................. 693
Figure G.2 – Structure XML exemple pour les noms ........................................................... 694
Figure G.3 – Utilisation de noms comme références ........................................................... 695
Figure J.1 – Structure de demande de message ................................................................. 863
Figure J.2 – GetMeterReadings .......................................................................................... 865
Figure J.3 – GetEndDeviceConfig ....................................................................................... 866
Figure J.4 – GetCustomerMeterDataSet.............................................................................. 867
Figure J.5 – GetMeterServiceRequests ............................................................................... 868
Figure K.1 – Extension de l'enveloppe de message ............................................................ 871
Figure K.2 – OperationSet .................................................................................................. 874
Figure K.3 – Modèle 1: demande/réponse (autre qu'OperationSet) ..................................... 875
Figure K.4 – Modèle 2: événement publié (autre qu'OperationSet) ...................................... 876
Figure K.5 – Modèle 3: demande/réponse (OperationSet) ................................................... 877
Figure K.6 – Modèle 4: événement publié (OperationSet) ................................................... 878
Figure M.1 – Modèle Get/cancel non recommandé .............................................................. 917
Figure M.2 – Modèle Get/cancel recommandé .................................................................... 918

Tableau 1 – Vue d'ensemble du document CEI 61968-9 ..................................................... 453


Tableau 1 – Fonctions métier et composants abstraits ........................................................ 470
Tableau 3 – Classes pour le relevé et la commande des compteurs .................................... 471
Tableau 4 – Classes relatives au relevé et à la commande des compteurs ......................... 477
Tableau 5 – Profils de configuration de la CEI 61968-9 ....................................................... 535
Tableau A.1 – Verbes généralement utilisés ....................................................................... 563
Tableau B.1 – Catégories ReplyCode ................................................................................. 565
Tableau B.2 – Enumérations exemptes d'erreur .................................................................. 566
Tableau B.3 – Enumérations des éléments absents ............................................................ 566
Tableau B.4 – Enumérations des mauvaises valeurs........................................................... 566
Tableau B.5 – Enumérations des valeurs trop nombreuses ................................................. 567
Tableau B.6 – Enumérations des délais de demande expirés .............................................. 567
Tableau B.7 – Enumérations des erreurs d'application ........................................................ 567
Tableau B.8 – Enumérations des violations de règles métier............................................... 568
Tableau B.9 – Enumérations des problèmes de sécurité ..................................................... 568
61968-9  CEI:2013 – 447 –

Tableau B.10 – Enumérations communes ........................................................................... 569


Tableau C.1 – Enumérations des périodes intéressantes .................................................... 573
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.2 – Enumérations des qualificateurs de données ............................................... 573


Tableau C.3 – Enumérations de measuringPeriod ............................................................... 575
Tableau C.4 – Scalaires de normalisation de la demande ................................................... 576
Tableau C.5 – Enumérations des comportements d'accumulation ....................................... 578
Tableau C.6 – Enumérations des comportements habituels d'accumulation ........................ 580
Tableau C.7 – Enumération des sens d'écoulement ............................................................ 582
Tableau C.8 – Equivalences des énumérations de sens d'écoulement ................................ 588
Tableau C.9 – Produit ......................................................................................................... 589
Tableau C.10 – Index measurementKind ............................................................................. 590
Tableau C.11 – Enumérations des harmoniques et interharmoniques ................................. 595
Tableau C.12 – Enumérations des arguments ..................................................................... 596
Tableau C.13 – Enumérations de temps d'utilisation ........................................................... 597
Tableau C.14 – Enumérations des tarifications pour période critique .................................. 597
Tableau C.15 – Enumérations des niveaux de consommation ............................................. 598
Tableau C.16 – Exemples de combinaison des énumérations de TOU et de niveaux de
consommation .................................................................................................................... 598
Tableau C.17 – Enumérations de phases ............................................................................ 600
Tableau C.18 – Enumérations de puissances de dix ........................................................... 604
Tableau C.19 – Enumérations de multiplicateurs de concentration historiques .................... 605
Tableau C.20 – Unités de mesure SI de base ..................................................................... 607
Tableau C.21 – Unités de mesure SI dérivées ayant des noms spéciaux ............................ 607
Tableau C.22 – Unités de mesure SI dérivées sans nom spécial ......................................... 609
Tableau C.23 – Unités de mesure non SI acceptées à utiliser avec le système d'unités
international ........................................................................................................................ 613
Tableau C.24 – Unités de mesure sans dimension et de concentration ............................... 614
Tableau C.25 – Unités non SI dont les valeurs dans les unités SI doivent être obtenues
expérimentalement ............................................................................................................. 617
Tableau C.26 – Autres unités de mesure non SI ................................................................. 618
Tableau C.27 – Unités non SI associées au système d'unités CGS et CGS gaussien.......... 624
Tableau C.28 – Unités de mesure des devises (issues de l'ISO 4217) ................................ 625
Tableau C.29 – Exemples de ReadingType ......................................................................... 627
Tableau D.1 – Identificateur système (System Identifier)..................................................... 633
Tableau D.2 – Exemples de catégories de codes de qualité ................................................ 633
Tableau D.3 – Codes relatifs à la validité ............................................................................ 634
Tableau D.4 – Codes relatifs aux diagnostics ...................................................................... 635
Tableau D.5 – Codes relatifs à la qualité de l'énergie ......................................................... 635
Tableau D.6 – Codes relatifs à la protection des Recettes / contre la falsification ............... 636
Tableau D.7 – Codes relatifs à la collecte de données ........................................................ 636
Tableau D.8 – Codes relatifs à Ayant échoué aux essais de bon sens ................................ 638
Tableau D.9 – Codes relatifs à Ayant échoué aux essais de validation ............................... 638
Tableau D.10 – Codes relatifs à l'édition ............................................................................. 640
Tableau D.11 – Codes relatifs à l'estimation ....................................................................... 641
– 448 – 61968-9  CEI:2013

Tableau D.12 – Codes relatifs à Douteux ............................................................................ 641


Tableau D.13 – Codes relatifs à Dérivé ............................................................................... 642
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau D.14 – Codes relatifs à la projection ...................................................................... 643


Tableau D.15 – Exemples de codes de qualité .................................................................... 644
Tableau E.1 – Codes EndDeviceType ................................................................................. 648
Tableau E.2 – Codes EndDeviceDomain ............................................................................. 649
Tableau E.3 – Codes EndDeviceSubdomain ....................................................................... 650
Tableau E.4 – Codes EndDeviceEventorAction ................................................................... 656
Tableau E.5 – Evénements de Battery (batterie) ................................................................. 662
Tableau E.6 – Evénements de Billing (facturation) .............................................................. 662
Tableau E.7 – Evénements de Cartridge (cartouche) .......................................................... 663
Tableau E.8 – Evénements de Clock (horloge).................................................................... 664
Tableau E.9 – Evénements de Communication ................................................................... 666
Tableau E.10 – Evénements de Configuration..................................................................... 667
Tableau E.11 – Evénements de Demand (demande) ........................................................... 668
Tableau E.12 – Evénements de Firmware (microprogramme) ............................................. 669
Tableau E.13 – Evénements GasSupply ............................................................................. 672
Tableau E.14 – Evénements d'Installation ........................................................................... 672
Tableau E.15 – Evénements LoadControl ........................................................................... 672
Tableau E.16 – Evénements LoadProfile ............................................................................ 673
Tableau E.17 – Evénements de Logs (journaux) ................................................................. 674
Tableau E.18 – Evénements de Memory (mémoire) ............................................................ 674
Tableau E.19 – Evénements de Metrology (métrologie) ...................................................... 675
Tableau E.20 – Evénements MobileSecurity ....................................................................... 678
Tableau E.21 – Evénements de modem .............................................................................. 679
Tableau E.22 – Evénements ModuleFirmware .................................................................... 679
Tableau E.23 – Evénements Network (réseau) ................................................................... 679
Tableau E.24 – Evénements PAN / HAN ............................................................................. 680
Tableau E.25 – Evénements de Power (puissance) ............................................................. 682
Tableau E.26 – Evénements de Pressure (pression) ........................................................... 686
Tableau E.27 – Evénements RCDSwitch ............................................................................. 686
Tableau E.28 – Evénements de Security (sécurité) ............................................................. 686
Tableau E.29 – Evénements de Temperature (température) ............................................... 689
Tableau E.30 – Evénements VideoDisplay .......................................................................... 689
Tableau E.31 – Evénements WaterSupply .......................................................................... 689
Tableau F.1 – Commandes de demande ............................................................................. 690
Tableau F.2 – Commandes LoadControl ............................................................................. 691
Tableau F.3 – Commandes PAN/HAN ................................................................................. 691
Tableau F.4 – Commandes RCDSwitch .............................................................................. 691
Tableau L.1 – Cas d'utilisation de gestion de données de référence / synchronisation
des données ....................................................................................................................... 881
61968-9  CEI:2013 – 449 –

COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE


_____________
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

INTÉGRATION D'APPLICATIONS POUR LES SERVICES ÉLECTRIQUES –


INTERFACES SYSTÈME POUR LA GESTION DE DISTRIBUTION –

Partie 9: Interfaces pour le relevé et la commande des compteurs

AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI elle-même ne fournit aucune attestation de conformité. Des organismes de certification indépendants
fournissent des services d'évaluation de conformité et, dans certains secteurs, accèdent aux marques de
conformité de la CEI. La CEI n'est responsable d'aucun des services effectués par les organismes de
certification indépendants.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de brevet. La CEI ne saurait être tenue pour responsable de ne pas avoir identifié de tels droits
de brevets et de ne pas avoir signalé leur existence.

La Norme internationale CEI 61968-9 a été établie par le comité d'études 57 de la CEI:
Gestion des systèmes de puissance et échanges d'informations associés.

Cette deuxième édition annule et remplace la première édition parue en 2009. Cette édition
constitue une révision technique et inclut les modifications techniques majeures suivantes par
rapport à l'édition précédente:

a) modifications apportées à et ajout de nouveaux profils pour prendre en charge PAN et les
UsagePoints;
b) extensions pour prendre en charge les appareils PAN génériquement en tant
qu'EndDevices;
c) extensions du modèle et des profils MeterReading pour prendre en charge les descriptions
plus riches des grandeurs comptées et pour assurer les relevés coïncidents;
– 450 – 61968-9  CEI:2013

d) ajout de la classe CIM Name et des révisions correspondantes aux profils afin de
permettre le référencement par nom et non par mRID. Lorsque le document peut identifier
l'utilisation de valeurs mRID en tant que références, les valeurs Name.name peuvent
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

également être utilisées. Cela est décrit de manière plus détaillée à l'Annexe G;
e) référence de ReadingTypes, EndDeviceEventTypes et EndDeviceControlTypes à l'aide
des références par nom;
f) définition des énumérations normatives pour ReadingTypes, EndDeviceEventTypes et
EndDeviceControlTypes dans les annexes;
g) plusieurs corrections apportées aux diagrammes d'exemple de séquence;
h) retrait du profil MeterAssetReading, lorsque la fonctionnalité est prise en charge en
utilisant le profil MeterReading;
i) la classe MeterAsset est désormais nommée Meter;
j) le profil MeterAssetConfig est désormais nommé MeterConfig;
k) le profil EndDeviceAssets est désormais nommé EndDeviceConfig;
l) retrait du profil EndDeviceFirmware, lorsque la fonctionnalité est prise en charge en
utilisant le profil EndDeviceConfig;
m) utilisation de nouveaux espaces de noms pour refléter la nouvelle édition, lorsque les
espaces de noms représentent l'année de définition d'un profil;
n) adoption d'UsagePoint comme remplacement et généralisation de ServiceDeliveryPoint;
o) SDPLocationConfig a été déconseillé au bénéfice d'UsagePointLocationConfig;
p) certains profils précédemment définis ont été déplacés à la nouvelle section 5.10 qui est
axée sur les liens de données;
q) suppression du profil MeterSystemEvents, car il ne fournissait aucune fonctionnalité que
le profil EndDeviceEvents ne pouvait atteindre;
r) plusieurs profils avaient été définis à l'origine pour soutenir les cas d'utilisation du
prépaiement qui ont été identifiés pour être de nature plus générale et ont par conséquent
été déplacés en 5.10. Le paragraphe 5.8 ne comporte désormais que lesdits profils
spécifiques au prépaiement. Dans tous les cas, ces profils ont été remaniés en vue de
refléter d'autres modifications nécessaires qui ont été décrites;
s) SupplierConfig a été renommé ServiceSupplierConfig;
t) les messages qui utilisent le verb SUBSCRIBE (souscrire) ont été supprimés puisqu'ils
sont relatifs au transport de communication sous-jacent et ne reflètent pas les messages
réels CEI 61968.

Le texte de cette norme est issu des documents suivants:

FDIS Rapport de vote


57/1377/FDIS 57/1394/RVD

Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.

Une liste de toutes les parties de la série CEI 61968, publiées sous le titre général Intégration
d'applications pour les services électriques – Interfaces système pour la gestion de
distribution, peut être consultée sur le site web de la CEI.
61968-9  CEI:2013 – 451 –

Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
stabilité indiquée sur le site web de la CEI sous "http://webstore.iec.ch" dans les données
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

relatives à la publication recherchée. A cette date, la publication sera

• reconduite,
• supprimée,
• remplacée par une édition révisée, ou
• amendée.

IMPORTANT – Le logo "colour inside" qui se trouve sur la page de couverture de cette
publication indique qu'elle contient des couleurs qui sont considérées comme utiles à
une bonne compréhension de son contenu. Les utilisateurs devraient, par conséquent,
imprimer cette publication en utilisant une imprimante couleur.
– 452 – 61968-9  CEI:2013

INTRODUCTION
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Le but du présent document est de définir une norme pour l'intégration des systèmes de
comptage (MS, Metering Systems) qui incluraient les systèmes de relevés de compteur
automatisés (AMR, Automated Meter Reading) traditionnels (à une seule voie ou à deux
voies) avec d'autres systèmes et fonctions métier s'inscrivant dans le domaine d'application
de la CEI 61968. Le domaine d'application de la présente norme est l'échange d'informations
concernant les transactions, les événements et les commandes liées au relevé des compteurs
entre des systèmes au sein de l'entreprise de distribution et entre d'autres entreprises. Les
détails spécifiques des protocoles de communications qu'utilisent les systèmes en question
ne relèvent pas du domaine d'application de la présente norme. En revanche, la présente
norme reconnaît et modélise les capacités générales qui peuvent être potentiellement
assurées par des infrastructures de compteurs avancées et/ou héritées, y compris les
capacités de communication bidirectionnelle telles que régulation de la charge, tarification
dynamique, détection d'interruptions de service, signaux de commande de ressources
énergétiques réparties (DER, distributed energy resource) et lecture sur demande. Ainsi, la
présente norme ne subit pas l'impact de la spécification, du développement et/ou du
déploiement d'infrastructures de compteurs de prochaine génération, et ce, ni par l'utilisation
de normes ni par des moyens propriétaires.

La série des normes CEI 61968 est prévue pour faciliter l'intégration inter-applications, par
opposition à l'intégration intra-applications. L'intégration intra-applications est destinée aux
programmes d'un même système, qui communiquent habituellement les uns avec les autres
via des intergiciels (middleware) intégrés dans leur environnement d'exécution sous-jacent et
tendent à être optimisés pour des connexions proches, en temps réel et synchrones, ainsi
que des interrogations/réponses interactives ou des modèles de communication
conversationnels. La CEI 61968, en revanche, est prévue pour prendre en charge l'intégration
inter-applications d'une entreprise de Distribution qui a besoin de relier des systèmes
disparates existants ou futurs (applications héritées ou achetées), chacun supporté par des
environnements d'exécution différents. Par conséquent, ces normes d'interface sont
appropriées pour les applications faiblement couplées avec une plus grande hétérogénéité
dans le langage, les systèmes d'exploitation, les protocoles et des outils de gestion. Cette
série de normes est prévue pour prendre en charge des applications qui nécessitent
l'échange de données environ toutes les secondes, minutes ou heures, plutôt que d'attendre
un traitement de nuit par lot. Cette série de normes, qui est destinée à être mise en œuvre
avec des services d'intergiciel, qui échangent des messages parmi des applications,
complète, mais ne remplace pas, les entrepôts de données de l'entreprise de distribution, les
passerelles de base de données et les archives opérationnelles.

Au sens de la CEI 61968, un Système de Gestion de Distribution (DMS, Distribution


Management System) est constitué de divers composants d'application distribués permettant
à l'entreprise de Distribution de gérer des réseaux de distribution électriques. Ces capacités
incluent la surveillance et la commande des équipements de fourniture d'énergie, les
processus de gestion qui assurent la fiabilité du système, la gestion de la tension, la gestion
de la demande, la gestion des interruptions de service, la gestion des travaux, la mise en
correspondance automatisée et la gestion des équipements. Des interfaces normalisées sont
définies pour chaque classe d'applications identifiée dans le modèle d'interface de
référence (IRM, Interface Reference Model), qui est décrit dans la CEI 61968-1: Architecture
des interfaces et exigences générales.
61968-9  CEI:2013 – 453 –

La présente partie de la CEI 61968 contient les articles énumérés dans le Tableau 1 ci-
dessous.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau 1 – Vue d'ensemble du document CEI 61968-9

Article Titre Objectif

1 Domaine d'application Le domaine d'application et l'objet du document sont décrits.


2 Références normatives Documents qui contiennent des stipulations qui, par référence
dans ce texte, constituent des conditions pour cette Norme
Internationale.
3 Termes, définitions et abréviations
4 Modèles de référence et Description de l'approche générale au système de comptage,
d'informations modèle de référence, cas d'utilisation, modèle d'interface de
référence, fonctions et composants de lecture et de commande
des compteurs, termes de types de messages et modèle
statique d'informations.
5 Types de messages de relevé et de Types de messages relatifs à l'échange d'informations
commande des compteurs concernant des documents relatifs à la relève et à la
commande de compteurs.
6 Conventions du document
Annexe A Verbes de types de message Description des verbes (Verbs) utilisés pour les types de
messages
Annexe B Extensions du CIM Extensions du CIM pour la prise en charge de la structure des
messages recommandée pour la lecture et le contrôle de
compteurs
Annexe C Procédure pour la création d'un Technique de construction, et offre des énumérations
ReadingTypeId recommandées de nom textuel ReadingTypeId et mRID.
Annexe D Enumérations des codes qualité Technique de construction, et offre des énumérations
recommandées pour les codes qualité de relevé
Annexe E Enumérations des codes Définit les codes d'alarme et d'événement de EndDevice
d'EndDeviceControl
Annexe F Enumérations des codes Définit les codes de commande de EndDevice.
EndDeviceControl
Annexe G Maintenir les relations entre objets Décrit l'utilisation de l'identificateur de ressources de référence
(mRID, master resource identifier) et des Names ( noms).
Annexe H Schémas XML pour les charges Fournir des informations xsd utilisables par les développeurs
utiles de message pour créer des messages de la CEI 61968-9.
Annexe I Mises en correspondance Fournir des mises en correspondance entre les MeterReadings
(relevés de compteur) CEI 61968-9 et les autres normes.
Annexe J Paramètres de demande Décrit la qualification des demandes GET à l'aide de
paramètres de Request.
Annexe K Traitement des transactions de Décrit la manière dont les transactions complexes de Gestion
Gestion de données de de données de référence/ synchronisation de données sont
référence(Master Data transmises, ainsi que les règles de traitement associées.
Management)
Annexe L Cas d'utilisation de la Gestion de Décrit nombre de cas courants d'utilisation de la Gestion de
données de référenceet données de référenceet fournit un échantillon XML pour
échantillon XML illustrer l'utilisation prévue des divers profils relatifs à la
gestion de données de référence.

Les futures editions de la CEI 61968-9 veilleront à comporter des modifications "liées", avec
l'espace de noms de la version précédente qui peut être conservé, mais l'attribut de révision
dans le XSD est incrémenté.
– 454 – 61968-9  CEI:2013

INTÉGRATION D'APPLICATIONS POUR LES SERVICES ÉLECTRIQUES –


INTERFACES SYSTÈME POUR LA GESTION DE DISTRIBUTION –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Partie 9: Interfaces pour le relevé et la commande des compteurs

1 Domaine d'application

La présente partie de la CEI 61968 spécifie le contenu informationnel d'un ensemble de types
de messages qui peuvent être utilisés pour prendre en charge de nombreuses fonctions
métier relatives au relevé et à la commande des compteurs. Les utilisations typiques des
types de messages comprennent le relevé de compteurs, les commandes, les événements, la
synchronisation des données client et la commutation de clientèle. Bien qu'elle soit
principalement destinée aux réseaux de distribution électrique, la CEI 61968-9 peut être
utilisée pour d'autres applications de comptage, y compris les grandeurs comptées non
électriques qui sont nécessaires pour supporter les réseaux de gaz et d'eau.

Le but du présent document est de définir une norme pour l'intégration des systèmes de
comptage (MS, Metering Systems) qui inclut les systèmes manuels traditionnels et les
systèmes de relevés de compteur automatisés (AMR, Automated Meter Reading) (à une seule
voie ou à deux voies), ainsi que les systèmes de gestion de données de compteur (MDM,
Meter Data Management) avec d'autres systèmes et fonctions métier s'inscrivant dans le
domaine d'application de la CEI 61968. Le domaine d'application de la présente norme est
l'échange d'informations entre les systèmes de comptage, les systèmes MDM et d'autres
systèmes au sein de l'entreprise de distribution. Les détails spécifiques des protocoles de
communications qu'utilisent les systèmes en question ne relèvent pas du domaine
d'application de la présente norme. En revanche, la présente norme reconnaît et modélise les
capacités générales qui peuvent être potentiellement assurées par des infrastructures de
compteurs avancées et/ou héritées, y compris les capacités de communication
bidirectionnelle telles que régulation de la charge, tarification dynamique, détection
d'interruptions de service, signaux de commande de ressources énergétiques réparties (DER,
distributed energy resource) et lecture sur demande. Ainsi, la présente norme ne subit pas
l'impact de la spécification, du développement et/ou du déploiement d'infrastructures de
compteurs de prochaine génération, et ce, ni par l'utilisation de normes ni par des moyens
propriétaires.

Le diagramme suivant décrit le domaine d'application de la présente spécification du point de


vue des impacts directs et causals ou indirects des messages CEI 61968-9. Alors que l'axe
de la norme CEI 61968-9 est de définir les messages standard pour l'intégration des
applications d'entreprise, les dits messages peuvent être directement ou indirectement relatifs
aux flux d'information d'un domaine d'application plus large. Des exemples peuvent inclure la
messagerie entre les systèmes de tête de réseau et les compteurs ou les appareils PAN. Les
différents composants décrits ultérieurement dans le présent document se rangeront en
général dans la catégorie d'une tête de réseau de système de comptage (MS), d'un MDM ou
de toute autre application d'entreprise (par exemple, OMS, DRMS, CIS).
61968-9  CEI:2013 – 455 –

Area of Direct Impact using


Area Causally/Indirectly
IEC 61968-9
Impacted by or impacting
(and within scope
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

IEC 61968-9
of IEC 61968)
Customer

Electric Utility
Standard or Proprietary Meter
Communication
Enterprise Integration Infrastructures
Enterprise Infrastructure
Applications (e.g. ESB, SOA, …)
(e.g. CIS, WMS, Customer
PAN
GIS, MDMS) Device
IEC 61968-9 Messages
(or more broadly any Head End Meter or
PAN
61968 message) Gateway
Systems PAN
Operations Device

Applications
Messages defined by
(e.g. OMS, DMS)
IEC 61968-9 are based Customer
upon IEC CIM and PAN
conveyed using a variety of Device
integration technologies Messages defined by TC57
and IEC 61968-100 relevant standards or WG21 PAN
vendors. May use a wide Gateway PAN
variety of communication Device
technologies PAN
Device

Mappings, translations
and/or forwarding as Messages defined
needed Mapping, translations by PAN/HAN
and/or forwarding as specifications
needed

Légende
Anglais Français
Area of Direct Impact using IEC 61968-9 (and Zone d'impact direct de l'utilisation de la
within scope of IEC 61968) CEI 61968-9 (et relevant du domaine
d’application de la CEI 61968)
Area Causally/Indirectly Impacted by or Zone directement/indirectement impactée par ou
impacting IEC 61968-9 impactant la CEI 61968-9
Electric Utility Entreprise d’électricité
Enterprise Integration Infrastructure (e.g. ESB, Infrastructure d'intégration d’entreprise (par
SOA,) exemple, ESB, SOA, ...)
Enterprise Applications Applications d'entreprise
Head End Systems Systèmes finaux de tête
IEC 61968-9 Messages (or more broadly any Messages CEI 61968-9 (ou plus largement, tout
61968 messages) messages 61968)
operations Applications Applications d’exploitation (par exemple
OMS,DMS)
Messages defined by IEC 61968-9 and based Messages définis par la CEI 61968-9 et basés
upon IEC CIM and conveyed using a variety of sur le CIM de la CEI et acheminés via différentes
integration technologies and IEC 61968-100 technologies d'intégration et la CEI 61968-100
Mappings, translations and/or forwarding as Mises en correspondance, traductions et/ou
needed transferts comme nécessaire
Customer Client
Meter Compteur
Standard or Proprietary Communication Infrastructure de communication standard ou
Infrastructure propriétaire
Meter or Gateway Compteur ou passerelle
PAN device Appareil PAN
Messages defined by relevant standards or Messages définis par les fournisseurs ou les
vendors. May use a wide variety of normes correspondants. Peut utiliser une large
communication technologies palette de technologies de communication
Messages defined by PAN/HAN specifications Messages définis par les spécifications
PAN/HAN

Figure 1 – Domaine d'application de la norme CEI 61968-9


– 456 – 61968-9  CEI:2013

Les capacités et les informations fournies par des systèmes de lecture de compteurs et de
gestion de données de compteur sont importantes pour une diversité d'applications, y compris
(mais de manière non exhaustive) les données d'intervalles, les données de demande basées
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sur la durée, les données d'énergie basées sur la durée (utilisation et production), la gestion
des interruptions de service, l'interruption de service, le rétablissement du service, la
surveillance de la qualité de service, l'analyse du réseau de distribution, la planification de la
distribution, service de demande/réponse, la facturation des clients et la gestion des travaux.
La présente norme étend également le CIM (Common Information Model, c'est-à-dire Modèle
d'Information Commun) pour prendre en charge l'échange des données de compteurs.

2 Références normatives

Les documents suivants sont cités en référence de manière normative, en intégralité ou en


partie, dans le présent document et sont indispensables pour son application. Pour les
références datées, seule l’édition citée s’applique. Pour les références non datées, la
dernière édition du document de référence s’applique (y compris les éventuels
amendements).

CEI 60050-300, Vocabulaire Electrotechnique International (VEI) – Mesures et appareils de


mesure électriques et électroniques – Partie 311: Termes généraux concernant les mesures –
Partie 312: Termes généraux concernant les mesures électriques – Partie 313: Types
d'appareils électriques de mesure – Partie 314: Termes spécifiques selon le type d'appareil

CEI 61968-1, Intégration d'applications pour les services électriques – Interfaces système
pour la gestion de distribution – Partie 1: Architecture des interfaces et recommandations
générales

CEI/TS 61968-2, Application integration at electric utilities – System interfaces for distribution
management – Part 2: Glossary (disponible en anglais seulement)

CEI 61968-11, Intégration d’applications pour les services électriques – Interfaces système
pour la gestion de distribution – Partie 11: Extensions du modèle d'information commun (CIM)
pour la distribution

CEI 61968-100:2013, Application integration at electric utilities – System interfaces for


distribution management – Part 100: Implementation profiles

CEI 61970-301, Interface de programmation d'application pour système de gestion d'énergie


(EMS-API) – Partie 301: Base de modèle d'information commun (CIM)

CEI/TR 62051-1, Electricity metering – Data exchange for meter reading, tariff and load
control – Glossary of terms – Part 1: Terms related to data exchange with metering equipment
using DLMS/COSEM (disponible en anglais seulement)

ISO 8601:2004, Éléments de données et formats d'échange – Échange d'information –


Représentation de la date et de l'heure (disponible en anglais seulement)

3 Termes, définitions et abréviations

3.1 Termes et définitions

Pour les besoins de la présente norme, les termes et définitions donnés dans les normes
CEI 60050-300, CEI/TS 61968-2, CEI/TR 62051-1, CEI 62055-31, ainsi que les termes
suivants, s'appliquent.

NOTE En cas de différence entre les définitions de la présente norme et les définitions contenues dans d'autres
normes CEI référencées, les définitions contenues dans la CEI/TS 61968-2 doivent alors être prioritaires par
61968-9  CEI:2013 – 457 –

rapport aux définitions répertoriées ailleurs et les définitions contenues dans la CEI 61968-9 doivent être
prioritaires par rapport aux définitions répertoriées dans la CEI/TS 61968-2.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

3.1.1
programme client
plan de classification pour la vente d'énergie aux clients selon une tarification particulière

Note 1 à l'article: Le programme peut spécifier le but, les conditions relatives à la durée d'utilisation, la/les
tension(s) de service, les volumes consommés et/ou autres termes comme une condition de vente.

Note 2 à l'article: Des entreprises de distribution peuvent promouvoir des programmes particuliers à l'attention de
leurs clients industriels, commerciaux, agriculteurs et résidentiels dans un effort visant à encourager un
comportement particulier ou à les informer de leurs options.

3.1.2
demande réponse (en anglais demand response)
ensemble de processus et de programmes utilisés pour réduire la consommation

Note 1 à l'article: Cela peut être effectué sur une base économique, obligatoire ou d'urgence.

3.1.3
dispositif terminal (en anglais end device)
équipement situé à l'extrémité du système de communication, habituellement dans les locaux
du client

Note 1 à l'article: Dispositif terminal qui peut accomplir des fonctions telles que les fonctions de métrologie,
connexion / déconnexion, régulation de la charge, réponse à la demande ou autres fonctions, et peut avoir une
capacité de relais de puissance et/ou de communications locales. Cela est représenté au sein du CIM par
l'utilisation de la classe EndDevice. Les compteurs et les appareils PAN sont des exemples de dispositifs
terminaux.

3.1.4
tête de réseau (en anglais head end)
composant d'un système de comptage qui collecte les données à partir de et émet des
commandes pour les dispositifs terminaux

Note 1 à l'article: Une tête de réseau peut également gérer le système de communication utilisé pour
communiquer avec les dispositifs terminaux. Du point de vue de l'intégration d'entreprise, la tête de réseau sert de
proxy aux dispositifs terminaux.

3.1.5
passerelle (en anglais gateway)
appareil qui peut être utilisé pour gérer les appareils sur un PAN et participer aux interactions
basées sur Internet. Une passerelle peut appliquer une transformation d'un protocole à un
autre

3.1.6
dispositif de régulation de la charge (en anglais load control device)
type de EndDevice qui peut recevoir des signaux l'amenant à délester la charge aux fins de
maintenir la fiabilité du réseau et/ou des accords commerciaux

3.1.7
compteur (en anglais meter)
type de dispositif terminal qui accomplit la métrologie et prend en charge la tarification du
réseau de distribution et/ou de transport

Note 1 à l'article: Cela est représenté par l’utilisation de la classe Meter du CIM, qui est une sous-classe de la
classe EndDevice.

Note 2 à l'article: En tant que dispositif terminal, un compteur aura généralement, mais pas toujours, un lien de
communication avec un système de tête de réseau.
– 458 – 61968-9  CEI:2013

3.1.8
remplacement de compteur
échange de compteur
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

processus consistant à remplacer un compteur existant par un nouveau compteur

Note 1 à l'article: La personne chargée de l'installation suivra habituellement un bon de travail (ordre d'exécution)
qui spécifie un emplacement donné et exige habituellement qu'elle saisisse les relevés de lecture des anciens et
nouveaux compteurs et enregistre l'heure et la date d'exécution du travail.

3.1.9
gestionnaire des données de compteur (en anglais meter data manager)
système qui gère les données de compteur et fournit généralement diverses fonctionnalités à
valeur ajoutée telles que VEE

3.1.10
réseau dans un local PAN (en anglais premise area network)
comprend l'ensemble du domaine d'application d'un réseau domestique (HAN), car il couvre
également les locaux commerciaux

3.1.11
appareil PAN
type de dispositif terminal situé sur un local de client qui communique à l'aide d'un PAN

Note 1 à l'article: En général, un appareil PAN peut accepter des commandes et/ou des événements de rapport.

Note 2 à l'article: Les appareils PAN utilisent couramment les compteurs comme passerelles de communication.

3.1.12
compteur à paiement
compteur électrique avec des fonctionnalités supplémentaires qui peut être exploité et
commandé pour permettre le flux d'énergie conformément à des modes de paiement
convenus d'un commun accord

Note 1 à l'article: Cela implique en général le prépaiement de l'électricité.

3.1.13
mode de prépaiement
mode de paiement dans lequel l'interruption automatique se produit lorsque le crédit
disponible est épuisé

3.2 Abréviations
Abbréviation Anglais Français
AM asset management gestion des biens
AMR automated meter reading relevé de compteur automatisé
AMI advanced metering infrastructure infrastructure de comptage avancée
CIM common information model modèle d'information commun
CIS customer information system système d'informations clients
COSEM companion specification for energy metering spécification d'accompagnement pour le
comptage d'énergie
DLMS UA device language message specification user spécification de message de langue d'appareil
association – association des utilisateurs
DMS distribution management system système de gestion de distribution
DR demand response réponse à la demande
DRMS demand response management system système de gestion de réponse à la demande
HAN home area network réseau domestique
IDR interval data recorder enregistreur de données d'intervalles
61968-9  CEI:2013 – 459 –

Abbréviation Anglais Français


IEC / CEI International Electrotechnical Commission Commission Electrotechnique Internationale
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

LC load control régulation de la charge


LDC load control system système de régulation de la charge
LMS load management system système de gestion de la charge
MAM meter asset management gestion de biens de compteur
MDM meter data management gestion de données de compteur
MDM master data management gestion de données de référence
MM meter maintenance maintenance de compteur
MR meter reading relevés de compteur
MS metering system système de comptage
NO network operations exploitation du réseau
OMS outage management system système de gestion des interruptions de service
POS point of sale point de vente
PAN premise area network (includes scope of HAN) réseau dans un local (comprend le domaine
d'application du HAN)
RF radio frequency fréquence radio
SM smart meter compteur intelligent
UML unified modeling language langage de modélisation unifié
VEE validating, editing, and estimating validation, édition et estimation
WM work management gestion des travaux
XSD XML schema schéma XML

4 Modèles de référence et d'informations

4.1 Approche générale aux systèmes de comptage

Le disque rotatif dans un compteur électromécanique sert généralement d'initiateur


d'impulsions pour le module enregistreur du compteur. De même, les compteurs à semi-
conducteurs peuvent aussi utiliser une unité de métrologie qui génère des impulsions
représentant une fraction de kWh. En outre, s'il est plus sophistiqué, le compteur à semi-
conducteurs peut comporter un enregistreur de comptage capable d'accumuler un grand
nombre de différentes sortes d'informations et de les stocker en vue de les présenter au
module de communications du compteur en utilisant un protocole piloté par des messages et
des tableaux tel que l'ANSI C12.19 ou la CEI 62056.

L'élément de donnée compté le plus commun est le kWh, mais de nombreux compteurs
d'électricité peuvent aussi saisir les kW, kVAr, kVArh et autres grandeurs de facturation
similaires. Certains compteurs peuvent aussi saisir des grandeurs techniques pures telles que
tension, courant, facteur de puissance, etc.

Certains systèmes AMR tentent d'ajouter de la valeur à des compteurs en ajoutant la


fonctionnalité dont le compteur peut manquer. Pour les compteurs simples (par exemple,
compteur d'énergie seulement), il est courant pour un module de compteur AMR d'ajouter la
capacité d'accomplir le comptage à la demande, l'enregistrement de données d'intervalle
(IDR), de maintenir un compte d'alimentation en énergie ou même de fournir des estimations
de certaines grandeurs techniques telles que la tension.

Les compteurs commerciaux et industriels utilisent souvent des transformateurs de courant et


des transformateurs de tension pour compter le service réel. Les courants et tensions
primaires sont réduits en proportion à l'aide de transformateurs de potentiel (PT, potential
transformer) et de transformateurs de courant (CT, current transformer) et, de ce fait, il n'est
pas obligatoire de construire le compteur pour qu'il supporte les forts courants et tensions
– 460 – 61968-9  CEI:2013

réellement délivrés à la charge. Les valeurs des tensions ou des courants secondaires sont
souvent mesurées directement par le compteur. Les valeurs secondaires représentent un petit
pourcentage des valeurs primaires qui peuvent être effectivement délivrées ou connectées
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

à la charge. Si les tensions et courants secondaires sont mesurés par le compteur, ils
peuvent être reconvertis en valeurs primaires à l'aide des rapports de transformation PT
et CT, qui sont juste le rapport des valeurs primaires sur secondaires.

Le système de comptage achemine les données des compteurs et autres données à valeur
ajoutée jusqu'à la destination en passant par le réseau du système de comptage. En fonction
du système, le trajet peut impliquer plusieurs étapes à travers des réseaux publics ou privés,
des spectres RF sous licence ou sans licence, des systèmes normalisés ou propriétaires,
d'une façon unidirectionnelle ou bidirectionnelle.

Certains services ou opérations généraux peuvent être définis pour un système de comptage.
Ces opérations générales se traduiront en des actions spécifiques dans le contexte d'une
solution de comptage donnée.

Les opérations générales peuvent être programmées ou appelées sur demande. Chaque
opération retourne une réponse avec un statut facultatif. Un message encapsule une
opération générale.

Les lecteurs de la CEI 61968-9 intéressés par des informations complémentaires peuvent se
référer à d'autres normes, y compris la CEI 62056, la DLMS UA (spécification de message de
langue d'appareil – association des utilisateurs) et le modèle COSEM: Spécification
d'accompagnement pour le comptage d'énergie (COmpanion Specification for
Energy Metering, en anglais).

4.2 Modèle de référence

4.2.1 Généralités

Les diagrammes suivants servent de modèles de référence et donnent des exemples des
composants logiques et flots de données relatifs à la présente Norme internationale. Le
paragraphe 4.5.2 fournit les références à des termes définis par le CIM.

Le "compteur" est traité comme un "dispositif terminal". Le dispositif terminal peut contenir
une capacité de métrologie, il peut contenir une capacité de communications, il peut être une
unité de régulation de la charge et il peut contenir une combinaison d'un grand nombre de
types différents de fonctionnalités. La Figure 2 tente de décrire essentiellement le concept de
liste de choix possibles de fonctionnalités qui peuvent être disponibles dans le dispositif
terminal (logique ou physique).
61968-9  CEI:2013 – 461 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Dispositif terminal
- Métrologie
- Communications
- Branchement
/débranchement
- Régulation de la charge
- Réponse à la demande
- Relais
- Affichage des informations

Figure 2 – Exemple d'un dispositif terminal avec des fonctions

Le dispositif terminal proprement dit, tout en présentant une myriade de fonctionnalités, n'est
pas le sujet de la présente norme. Il existe de nombreuses interactions qui affectent in fine le
dispositif terminal mais elles résultent d'une communication entre les systèmes à un niveau
beaucoup plus élevé dans l'architecture de commande. L'interaction entre les systèmes
relève du domaine d'application de la présente norme et la Figure 3 donne une vue
informative des systèmes impliqués et une vue d'ensemble au paysage des parties prenantes.

Du point de vue de la présente norme, un dispositif terminal:

• a une identité unique (mRID et/ou un ou plusieurs cas de la classe Name)


• est géré comme un bien physique;
• peut émettre des événements;
• peut recevoir des demandes de commande;
• peut recueillir et rapporter des valeurs mesurées;
• peut participer à des processus métier de l'entreprise de distribution.

Les diagrammes des Figures 3 et 4 décrivent les flux entre les composants dans le modèle de
référence. Deux diagrammes sont utilisés pour réduire la complexité que présenterait un seul
diagramme. Les nombres entre crochets donnent les liens aux définitions des flux.
– 462 – 61968-9  CEI:2013

Planning
Outage
and
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Management
Scheduling
61968-3 61968-5

Interface and protocol details of the


[ 17 ]
Service Point are outside the scope of [ 12 ]
IEC 61968-9
[ 19 ]

Meter
Service [ 13 ]
[ 18 ] Data Collection Data
Point
Management

Metering System
{ 16 }
{ 23 }
Control and [ 12 ]
[ 15 ] [4] [ 13 ]
Reconfiguration
[3] [ 22 ] [9]
Customer
Information
[2]
and
[7] Billing
{ 11 } 61968-8

Meter Maintenance [1]


and [ 21 ]
Asset Management
[ 20 ] [7]
[6] Point
of
Sale
Network 61968-10
Operations
[7]
61968-3 [6]
{ 12 }
[ 10 ]
{8} Load Analysis

Load
[3] Management
System

[ 18 ] Load Control
{ 14 }

{ 12 }

[5]
Work
Management
{ 14 }
61968-6

[ 1 ] Account information [ 13 ] Meter readings


[ 2 ] Configuration, installation etc. { 14 } Meter service request
[ 3 ] Controls and signals [ 15 ] On request read
[ 4 ] Customer data set [ 16 ] Outage and restoration verification
[ 5 ] Data obtained by special read [ 17 ] Power reliability and quality events
[ 6 ] Demand response signals [ 18 ] Readings, events and status
[ 7 ] Disconnect/reconnect, demand reset [ 19 ] Special read
{ 8 } Install, remove, repair, disconnect, reconnect [ 20 ] Tariffs, parameters
[ 9 ] Load curves, Measurement history, etc. [ 21 ] Transaction information 61968 Part 9
[ 10 ] Load scenarios [ 22 ] Transaction records Defined by other 61968 Parts
{ 11 } Meter health and tamper detection { 23 } Tokens
{ 12 } Meter history Key Outside the scope of 61968
61968-9  CEI:2013 – 463 –

Légende

Anglais Français
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Outage Management Gestion des interruptions de service


Planning and Scheduling Planification et programmation
Interface and protocol details of the Service Les détails relatifs à l'interface et au protocole du point de service ne
Point are outside the scope of IEC 61968-9 relèvent pas du domaine d'application de la CEI 61968-9
Service Point Point de service
Data Collection Collecte de données
Metering System Système de comptage
Control and Reconfiguration Commande et reconfiguration
Meter Data Management Gestion de données de compteur
Customer Information and Billing Informations et facturation client
Meter Maintenance and Asset Management Maintenance de compteur et Gestion de biens
Network Operations Exploitation du réseau
Point of Sale Point de vente
Load Analysis Analyse de la charge
Load Management System Système de gestion de la charge
Load Control Régulation de la charge
Work Management Gestion des travaux
Account information Informations de compte
Configuration, installation, etc. Configuration, installation, etc.
Controls and signals Commandes et signaux
Customer data set Jeu de données client
Data obtained by special read Données obtenues par une lecture spéciale
Demand response signals Signaux de réponse à une demande
Disconnect/reconnect, demand reset Débranchement/rebranchement, réinitialisation de demande
Install, remove, repair, disconnect, reconnect Installer, retirer, réparer, débrancher, rebrancher
Load curves, Measurement history, etc. Courbes de charge, historique des mesures, etc.
Load scenarios Scenarii de charge
Meter health and tamper detection Détection de santé et de falsification du compteur
Meter history Historique du compteur
Meter readings Relevés de compteur
Meter service request Demande de service compteur
On request read Relevé sur demande
Outage and restoration verification Interruption de service et vérification du rétablissement
Power reliability and quality events Événements relatifs à la fiabilité et à la qualité de l'énergie
Readings, events and status Relevés, événements et statut
Special read Relevé spécial
Tariffs, parameters Tarifs, paramètres
Transaction information Informations sur la transaction
Transaction records Enregistrements des transactions
Tokens Jetons
61968 Part 9 61968 Partie 9
Defined by other IEC 61968 Parts Défini par d'autres parties de la CEI 61968
Outside the scope of 61968 Hors du domaine d'application de la 61968
Key Légende

Figure 3 – Modèle de référence de la CEI 61968-9


– 464 – 61968-9  CEI:2013

Interface and protocol details of the


Service Point are outside the scope of Meter
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

IEC 61968-9 Administration

Readings, events Scheduled


and status Read
Service Meter
Data Collection Scheduled
Point Data Scheduled
Read Read
Management
Metering System
Tokens Peak
Control and Price (1) Peak
Controls and signals Reconfiguration Price (1)
Load
Reduction

Exchange
Load
Portal
Reduction

Network Peak Scheduled


Operations Price Read
(1)
61968-3

Customer
Peak Information
Price and
(2) Billing
61968 Part 9 61968-8
Defined by other 61968 Parts
Key Outside the scope of 61968

Légende

Anglais Français
Interface and protocol details of the Service Point Les détails relatifs à l'interface et au protocole
are outside the scope of IEC 61968-9 du point de service ne relèvent pas du domaine
d'application de la CEI 61968-9
Service Point Point de service
Readings, events and status Relevés, événements et statut
Tokens Jetons
Controls and signals Commandes et signaux
Data Collection Collecte de données
Metering System Système de comptage
Control and Reconfiguration Commande et reconfiguration
Scheduled Read Lecture programmée
Peak Price (1) Prix de pointe (1)
Load Reduction Réduction de charge
Meter Administration Administration de compteur
Meter Data Management Gestion de données de compteur
Exchange Portal Portail d'échange
Network Operations Exploitation du réseau
Customer Information and Billing Informations et facturation client
Key Légende
61968 Part 9 61968 Partie 9
Defined by other 61968 Parts Défini par d'autres parties de la CEI 61968
Outside the scope of 61968 Hors du domaine d'application de la 61968

Figure 4 – Modèle de référence avec informations de clients


et système de facturation de la CEI 61968-9
61968-9  CEI:2013 – 465 –

L'architecture de référence reflète cinq principaux composants logiques (potentiellement


réalisés sous forme de systèmes ou sous-systèmes) relatifs au comptage:
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

a) système de comptage, incluant potentiellement la fonctionnalité de collecte, contrôle et


reconfiguration des données
b) gestion de données de compteur, qui peut inclure les fonctions d'administration de
compteur
c) maintenance de compteur
d) gestion de la charge, incluant potentiellement la fonctionnalité de régulation de la charge
et d'analyse de la charge
e) gestion de biens de compteur.

Les composants système de comptage et système de maintenance de compteur peuvent être


liés à un compteur spécifique et à la technologie de communication associée ou bien ils
peuvent prendre en charge plusieurs types de compteurs (et plus génériquement de
dispositifs terminaux) et la technologie de communication associée. Le composant système
de gestion de données de compteur peut prendre en charge et consolider les données de
comptage provenant de plus d'un système de comptage. Le système de comptage peut
également prendre en charge la consolidation de diverses mises en œuvre de mesures et de
collecte de données, assurant une interface cohérente au composant système de gestion de
données de compteur.

4.2.2 Système de comptage (MS) – Collecte de données (Metering system – Data


collection)

Les tâches du sous-composant de collecte de données dans le système de comptage peuvent


comprendre:

• la collecte des relevés et des statuts. Les relevés et les statuts peuvent être obtenus par
des moyens manuels ou automatisés, sur programmation ou à la demande
• transmission des relevés et du statut des compteurs vers un système de gestion de
données de compteur
• transmission des données d'événements de qualité et de fiabilité de l'énergie vers des
systèmes de gestion des interruptions de service, d'exploitation de réseau et de
planification de capacité
• transmission d'informations de santé du réseau de communications vers les personnes
responsables de la maintenance du réseau de communications.

Il est important de noter que les systèmes de comptage sont considérablement divers quant
aux technologies utilisées, aux protocoles utilisés, aux capacités et à la fréquence de la
collecte de données. Les détails des organes internes des compteurs, des transports et des
protocoles de communication ne relèvent pas du domaine d'application de la présente Norme
internationale.

Un appareil portable utilisé par un releveur de compteur humain pourrait être considéré
comme un système de comptage. Dans un relevé typique de compteur par un humain, un
lecteur injecte les données de compteur dans un appareil portable sur un terrain. L'appareil
portable n'est pas relié à un réseau de communications sur un terrain. A la fin de la journée
de travail, l'appareil portable est relié à un réseau de communications au domicile du releveur
(et non à son bureau) et les données du compteur sont téléchargées vers l'amont vers un
système de gestion de données de compteur. Dans ce cas, il convient que le réseau de
communications soit partie intégrante d'un système de comptage. La collecte de données est
décrite dans la CEI 61968-1 comme "MR-RMR."
– 466 – 61968-9  CEI:2013

4.2.3 Système de comptage (MS) – Commande et reconfiguration (Metering system –


Control and reconfiguration)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les tâches du sous-composant "Commande et reconfiguration" dans le système de comptage


sont:

• interface principale pour l'exécution de commandes de commande du compteur


• communication d'informations relatives au système de paiement
• agir comme passerelle de communication pour des appareils de régulation de charge
• connexion/déconnexion de service;
• configuration des unités de mesure des tarifs et du calendrier
• configuration de la mesure de la qualité de l'énergie
• configuration de l'enregistrement d'événements du compteur
• relais des signaux de régulation de charge
• configuration des authentifiants d'identité et de sécurité du compteur
• détection de fraude.

Ce sous-composant est identifié séparément dans le système de comptage afin de


reconnaître l'existence de systèmes de comptage qui n'ont pas la capacité d'envoyer des
messages aux compteurs. La CEI 61968-1 décrit ce sous-composant comme "MR-MOP-Meter
Configuration". Les systèmes de comptage qui comportent ces capacités sont souvent
désignés par l'abréviation AMI.

4.2.4 Régulation de la charge

L'infrastructure du système de comptage peut souvent être utilisée comme passerelle de


communication aux unités de régulation de la charge. Les unités de régulation de la charge
sont des dispositifs terminaux avec capacité de régulation de la charge (LC). Ceux-ci sont
câblés pour commander des appareils cibles individuels. Les dispositifs terminaux avec
fonctionnalité LC peuvent prendre différentes formes. Le plus souvent, une unité LC
spécialisée peut être située au niveau (ou à proximité) de l'appareil devant être commandé.
Une autre approche consiste à utiliser des compteurs qui ont des relais configurés pour servir
d'appareils LC. Une autre approche encore consiste à interfacer à un système de gestion
d'énergie client (qui serait un autre type de dispositif terminal).

4.2.5 Système de gestion de la charge (LMS)

Un système de gestion de la charge est utilisé pour gérer et réguler la charge par l'entreprise
de distribution afin de favoriser la fiabilité du système. Un système de gestion de la charge
peut accomplir la prévision de charge, l'analyse de contingence et autres simulations avant
de produire une commande de régulation de la charge.

4.2.6 Système de gestion de biens de compteur (MAM)

Des entreprises de distribution utiliseront une certaine forme de logiciels de gestion des biens
dans un effort visant à maintenir des enregistrements détaillés concernant leurs biens
physiques. La gestion des biens est traitée de manière catégorique dans la CEI 61968-4.
Cependant, le comptage a des exigences tellement spéciales qu'il est commun pour une
entreprise de distribution d'utiliser un logiciel spécialisé de gestion des biens de compteur. Le
logiciel fait l'inventaire du bien, fournissant un enregistrement de ses attributs physiques ainsi
que son emplacement. Pour les besoins du débat, le document de la CEI 61968-9 parlera
d'un système MAM étroitement couplé au MS et à la MDM, mais certaines mises en œuvre
réussiront à généraliser suffisamment l'application de gestion de biens pour qu'elle puisse
s'inscrire dans un système AM plus générique.
61968-9  CEI:2013 – 467 –

4.2.7 Système de gestion de données de compteur (MDM)

D'un point de vue historique, il était commun pour une entreprise de distribution d'avoir plus
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

d'un système automatisé de relevé de compteur. En variante, une entreprise de distribution


pourrait externaliser les services de relevé de compteur à un ou plusieurs fournisseurs de
services tiers qui exploitent un système AMR et/ou relèvent les compteurs manuellement. Le
système de gestion de données de compteur (MDM) est utilisé pour fournir un référentiel
commun, et point de gestion et d'accès de données de compteur recueillies qui proviennent
de systèmes de comptage disparates. En plus de l'agrégation des données, très souvent la
MDM fera aussi un effort pour examiner méticuleusement les données recueillies provenant
des divers systèmes de comptage et fournir une capacité de validation, édition et estimation
(VEE). Les systèmes MDM fourniront également souvent une fonctionnalité impliquant
l'émission, la commande et le suivi des EndDeviceControls et endDeviceEvents.

4.2.8 Système d'informations clients (CIS)

Un CIS englobera typiquement les fonctionnalités relatives au service clientèle et à la


facturation. Il s'agit d'un sujet externe à la norme CEI 61968-9. La fonction de facturation
s'appuie sur les relevés, typiquement la demande ou la durée d'utilisation, obtenus du
compteur. Le CIS est également souvent impliqué à des processus relatifs aux demandes de
renseignements de facturation, à la déconnexion du compteur et à sa reconnexion, aux
changements de programme de tarifs.

Le CIS est souvent la "source d'enregistrement" dans les entreprises de distribution pour les
données de référence qui définissent les entités clés telles que les compteurs, d'autres
dispositifs terminaux, les points d'usage, les fournisseurs de service, les clients, les
structures de tarification, etc. et les relations entre lesdites entités. Voir 5.10 et les Annexes K
et L pour obtenir des informations complémentaires relatives à la Gestion de données de
référence/ synchronisation de données.

4.2.9 Système de gestion des interruptions de service (OMS)

Un système de gestion des interruptions de service (OMS) est utilisé par les opérateurs de
distribution pour détecter et suivre les interruptions de service et pour aider au processus de
vérification et/ou de rétablissement de service. Un système OMS combine typiquement (ou a
des attaches à) la fonctionnalité telle que la gestion des défauts dans l'exploitation du réseau,
la planification opérationnelle et l'optimisation, la simulation de l'exploitation du réseau, la
maintenance et la construction, la maintenance et l'inspection, et la programmation et la
répartition du travail.

Le système de comptage peut être une importante source d'informations pour identifier
l'existence et l'étendue des interruptions de service et il peut servir à vérifier le rétablissement
des interruptions de service. Le MS pourrait avoir la capacité d'éditer des données relatives
aux interruptions de service et au rétablissement à l'attention de l'OMS à mesure qu'il les
trouve. Ce type d'informations s'ajoute typiquement aux appels téléphoniques entrants des
clients dans l'OMS pour permettre à celui-ci de mieux prédire l'emplacement de l'interruption
de service. Cependant, en raison de la nature sensible au temps de la détection des
interruptions de service, il existe aussi le besoin potentiel d'une interface de
demande/réponse avec le MS, dans laquelle l'OMS peut demander qu'un équipement
spécifique sur le réseau de distribution soit soumis à essai par le MS et un statut
d'alimentation en énergie retourné pour analyse. L'interface de demande/réponse peut être
utilisée par l'OMS pour fournir les données critiques nécessaires pour prédire une interruption
de service ou par un "dispatcheur" qui souhaiterait vérifier que la puissance a été rétablie sur
tous les points d'extrémité comptés à l'aval d'un commutateur particulier avant d'envoyer le
monteur de ligne à l'emplacement suivant.

Les systèmes MDM servent aussi couramment d'agent intelligent dans le cadre des messages
relatifs aux interruptions de service entre les systèmes de comptage et les systèmes de
gestion des interruptions de service.
– 468 – 61968-9  CEI:2013

4.2.10 Exploitation du réseau (NO)

L'exploitation du réseau (CEI 61968-3) peut avoir occasionnellement besoin d'émettre des
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

signaux de régulation de charge et de tarification vers les compteurs. Cela peut être réalisé
pour des raisons économiques et aussi pour des raisons d'urgence.

4.2.11 Maintenance de compteur (MM)

La maintenance des compteurs est responsable de la fonctionnalité relative à la configuration


et à la pose des compteurs. Ce type de fonctionnalité s'inscrit en général dans la gestion de
biens de compteur ou dans la gestion de biens plus généralement. L'accomplissement de la
maintenance des compteurs peut exiger des échanges avec la gestion des travaux.

4.2.12 Planification

La fonction de planification est décrite en tant que planification opérationnelle et optimisation,


simulation de l'exploitation du réseau.

4.2.13 Gestion des travaux (WM)

Un système de gestion des travaux est responsable des travaux accomplis par les ressources
de terrain. Ce sujet est traité dans "Maintenance et construction et Maintenance et inspection"
(CEI 61968-6).

Pour ce qui est du comptage, WM inclut la pose, la maintenance et le remplacement des


compteurs. Cela peut également impliquer le processus de lectures spéciales.

4.2.14 Point de vente (POS)

Un système de points de vente (POS) est utilisé pour gérer les compteurs de paiement,
lorsqu'un client achète un jeton ou effectue un paiement pour un service.

4.2.15 Compteur (Meter)

Le compteur enregistre les données utilisées pour tarifier l'utilisation des réseaux publics et
les données utilisées pour des mécanismes d'équilibrage de réseau. Les compteurs sont un
sous-type d'EndDevice.

Les relevés saisis par le système de comptage sont rassemblés par un système tel que la
MDM avant d'être présentés à des fins de facturation. Les entités de facturation peuvent
corriger les données ou, dans certaines régions, le fournisseur d'énergie peut accomplir la
validation, l'édition et l'estimation (VEE) selon des règles établies par l'organisme approprié
de réglementation et de surveillance. Dans tous les cas, ces corrections sont mises à la
disposition de l'utilisateur qui les demande.

Lorsque la présente Norme internationale se réfère à un "compteur", il convient de réaliser


qu'un "compteur" est un dispositif terminal qui est doté d'une capacité de métrologie, il peut
avoir ou peut ne pas avoir la capacité de communications; il peut en outre avoir ou peut ne
pas avoir la capacité de branchement/débranchement ou d'être l'hôte d'autres capacités.
Etant donné qu'un compteur aura une capacité de métrologie, il mesurera en toute
vraisemblance les kWh, mais éventuellement aussi la demande, l'énergie réactive et la
demande, les grandeurs de temps d'utilisation, les données d'intervalles, les grandeurs
techniques d'étude et plus. De la même manière, les compteurs d'autres produits comme le
gaz et l'eau peuvent surveiller des grandeurs analogues.

4.2.16 Appareils de régulation de charge

Les appareils de régulation de charge sont utilisés pour réguler les charges en un UsagePoint
(c'est-à-dire point d'usage). Le système de comptage peut souvent comporter un réseau de
communications qui peut être utilisé pour émettre des signaux de régulation de charge
61968-9  CEI:2013 – 469 –

(EndDeviceControls) afin de réguler la charge présentée par l'/les "EndDevice(s)". En


variante, le réseau de communications pourrait être utilisé pour communiquer des signaux de
réponse à la demande (prix) aux appareils afin d'affecter la charge présentée par l'/les
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

"EndDevice(s)". Les appareils PAN peuvent également fournir des fonctions de régulation de
charge.

4.2.17 Appareils PAN

Les appareils PAN sont utilisés à diverses fins dans les locaux d'un client. Le compteur est
souvent utilisé comme passerelle de communication entre le système de tête de réseau et
l'appareil PAN. Les appareils PAN peuvent réagir pour contrôler les messages ou générer des
EndDeviceEvents. Certains appareils PAN, comme dans les affichages domestiques, peuvent
également présenter des informations aux clients. Les appareils PAN peuvent être configurés
pour réagir aux signaux liés à la tarification ou à d'autres réponses à la demande qui sont
émis en tant que EndDeviceControls. Les appareils PAN sont modélisés en tant que
EndDevices dans le CIM.

4.2.18 Système de gestion de réponse à la demande (DRMS)

Les systèmes de gestion de réponse à la demande sont utilisés pour gérer l'enregistrement
dans les programmes DR, envoyer des événements aux participants du programme et
collecter des informations de performances liées telles que nécessaires pour les règlements.

4.3 Modèle d'interface de référence

Il n'est pas dans l'intention de la présente norme de définir les applications et les systèmes
qu'il convient que les fournisseurs proposent. On s'attend à ce qu'une application (physique)
concrète offre la fonctionnalité d'un ou plusieurs composants (logiques) abstraits tels qu'ils
sont énumérés dans cette norme. Ces composants abstraits sont regroupés par activité
fonctionnelle du Modèle d'Interface de Référence.

Dans la présente norme, le terme "composant abstrait" est utilisé en référence à la partie d'un
système logiciel qui prend en charge une ou plusieurs des interfaces définies dans les Parties
3 à 9. Il ne signifie pas nécessairement que le logiciel conforme soit livré sous forme de
modules séparés ou de système unique.

La CEI 61968-1 décrit des services d'infrastructure communs à tous les composants abstraits,
tandis que les parties CEI 61968-3 à -9 définissent le détail des informations échangées pour
des types spécifiques de composants abstraits.

La CEI 61968 définit que:

a) une infrastructure inter-applications est conforme si elle assure les services définis dans
la Partie 1 pour prendre en charge au moins deux applications avec des interfaces
conformes aux sections des Parties 3 à 9.
b) Une interface d'application est conforme si elle prend en charge les normes d'interface
définies dans les Parties 3 à 9 concernant les composants abstraits correspondants,
définis dans le Modèle d'Interface de Référence.
c) Une application doit seulement prendre en charge les normes d'interface de composants
applicables, mentionnées sous la rubrique Composants Abstraits. Une application n’est
pas nécessaire pour prendre en charge les interfaces devant être présentes pour d'autres
composants abstraits de la même sous-fonction métier ou au sein de la même fonction
métier. Alors que cette norme définit principalement les informations échangées entre des
composants dans différentes fonctions métier, elle définira également occasionnellement
les informations échangées entre des composants au sein d'une seule fonction métier,
lorsqu'une forte demande du marché concernant ces possibilités a été appréhendée.
– 470 – 61968-9  CEI:2013

4.4 Fonctions de relevé et de commande de compteurs et composants

Il convient de noter que les types de messages définis dans la présente norme peuvent être
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

envoyés ou reçus par tout type de composant au sein d'un système de gestion de distribution
(DMS).

Le Tableau 2 indique les fonctions et les composants abstraits habituels qui sont réputés être
des sources d'informations pour ces types de messages. Les consommateurs habituels
d'informations comprennent, mais de manière non exhaustive, les autres composants
énumérés dans la CEI 61968-1.

Tableau 2 – Fonctions métier et composants abstraits

Fonctions métier Sous-fonctions métier Composants abstraits


Relevé et commande des Système de comptage (MS) Collecte de données
compteurs (MR)
Commandes de points d'extrémité
Reconfiguration de points d'extrémité
Débranchement/rebranchement
Réinitialisation de la demande
Relevé sur demande
Point de vente
Détection des interruptions de service et
vérification du rétablissement
Evénements relatifs à la fiabilité et à la
qualité de l'énergie
Evénements relatifs au système de
comptage
Maintenance de compteur et Installation, configuration, suppression,
Gestion de biens réparation, débranchement,
rebranchement de point d'extrémité
Historique des biens de points
d'extrémité
Reconfiguration de points d'extrémité
Relevé spécial
Demande de service compteur
Tarifs
Gestion de données de compteur Référentiel de données de compteur
(MDM)
Historique d'utilisation
Validation, estimation et édition
Données de facturation client
Commandes et événements de dispositif
terminal
Réponse à la demande Tarification en temps réel
(DR) Réductions d'urgence
Réductions économiques
Enregistrement du programme
Gestion de charge (LM) Analyse de la charge
Régulation de la charge
Réponse à la demande
Mesures de performances
Gestion du risque
61968-9  CEI:2013 – 471 –

4.5 Modèle statique d'informations

4.5.1 Généralités
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Le modèle d'informations concernant le relevé et la commande des compteurs se compose de


classes qui fournissent un modèle relatif aux attributs de chaque message.

Les classes sont définies en détail dans la CEI 61968-11, Extensions du modèle d'information
commun (CIM) pour la distribution ou dans la CEI 61970-301 Interface de programmation
d'application pour système de gestion d'énergie (EMS-API) – Base de Modèle d'Information
Commun.

4.5.2 Classes pour le relevé et la commande des compteurs

Le Tableau 3 énumère les classes utilisées dans les types de messages. Habituellement tous
les attributs de ces classes sont contenus dans un type de message. Les descriptions
fournies décrivent l'utilisation qui en est faite dans la présente partie.

Les classes décrites comme type "Asset" sont définies dans le paquetage "61968/Assets"
du CIM.

Les classes décrites comme type "Customer" sont définies dans le paquetage
"61968/Customers" du CIM.

Les classes décrites comme type "Metering" sont définies dans le paquetage
"61968/Metering" du CIM.

Les classes décrites comme type "PaymentMetering" sont définies dans le paquetage
"61968/PaymentMetering" du CIM.

Les classes décrites comme type "Profile" sont des profils contextuels définis pour la
CEI 61968-9 qui décrivent les définitions de message établies en utilisant des objets du CIM.

Tableau 3 – Classes pour le relevé et la commande des compteurs

Classe/Nom Type Description


AuxiliaryAccount PaymentMetering Partie variable et dynamique d'AuxiliaryAgreement,
représentant généralement l'état courant du compte relatif au
solde impayé défini dans AuxiliaryAgreement.
AuxiliaryAgreement PaymentMetering Un accord de compte auxiliaire "ad-hoc" associé à un accord
client, ne faisant pas partie du compte client, mais typiquement
soumis à un accord formel entre client et fournisseur
(entreprise de distribution). Typiquement, il est utilisé pour
collecter un solde de recettes par le client pour d'autres
services ou arriérés accumulés avec l'entreprise de distribution
pour d'autres services. Il est typiquement lié à une transaction
d'achat de jetons prépayés, forçant ainsi le client à effectuer
un paiement en vue du règlement du solde de compte
auxiliaire chaque fois qu'il a besoin d'acheter un jeton prépayé
pour l'électricité.
Le présent statut de l'accord AuxiliaryAgreement peut être
défini dans le contexte des règles commerciales de l'entreprise
de distribution, par exemple: activé, désactivé, en suspens,
recouvré en trop, insuffisamment recouvré, radié, etc.
AuxiliaryAgreementConfig Profile Profil de messages pour les "AuxiliaryAgreement".
Card PaymentMetering Documentation de l'offre réelle lorsqu'il s'agit d'un type de
carte (crédit, débit, etc.).
Cashier PaymentMetering L'opérateur du point de vente pour la durée de CashierShift.
Cashier (c'est-à-dire le caissier) est sous le contrôle de
gestion exclusif de Vendor (c'est-à-dire du fournisseur).
– 472 – 61968-9  CEI:2013

Classe/Nom Type Description


CashierShift PaymentMetering Période de travail opérationnelle pour un caissier, pendant
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

laquelle il peut effectuer une transaction au débit de


CashierShift, à condition que VendorShift soit ouvert.
Channel Metering Chemin simple utilisé pour la collecte ou la consignation des
valeurs de registre sur une durée donnée. Par exemple, un
registre qui mesure la puissance active peut avoir deux
channels (canaux), un fournissant les relevés en quantité et
l'autre fournissant des relevés d'intervalle d'une taille fixe.
Charge PaymentMetering Un élément de prix associé à d'autres entités telles que
structures tarifaires, accords auxiliaires ou autres éléments de
charge. Le montant total des charges applicable à cette
instance de Charge est la somme de fixedPortion plus
percentagePortion.
Cheque PaymentMetering L'offre réelle lorsqu'il s'agit d'un type de chèque. Le numéro de
référence de chèque (tel qu'imprimé sur le chèque) est spécifié
dans "nom".
ComFunction Metering Fonction de communication du matériel de communication ou
d'un appareil tel qu'un compteur.
ComModuleConfig Profile Profil de configuration des modules de communications.
ConfigurationEvent Metering Utilisé pour consigner les détails sur la création, le
changement ou la suppression d'une entité ou de sa
configuration.
ConsumptionTariffInterval PaymentMetering L'une d'une séquence d'intervalles en termes de quantité de
consommation d'un service tel que l'électricité, l'eau, le gaz,
etc. Il est typiquement utilisé en association avec TariffProfile
pour définir les échelons ou tranches dans une structure
tarifaire à échelons, où startValue définit simultanément la
valeur d'entrée de cet échelon et la valeur de fermeture de
l'échelon précédent. Lorsque la consommation est >=
startValue, elle s'inscrit dans le présent intervalle et lorsque la
consommation est < startValue, elle s'inscrit dans l'intervalle
précédent.
Customer Customers Organisation recevant des services de la part de
ServiceSupplier.
CustomerAccount Customers Affectation d'un groupe de produits et de services achetés par
le client Customer par un accord client CustomerAgreement,
utilisée comme mécanisme de facturation et paiement client. Il
contient les informations communes issues de divers types
d'accords CustomerAgreements pour créer des facturations
(factures) pour un client Customer et recevoir un paiement.
CustomerAccountConfig Profile Profil de messages pour les "CustomerAccount".
CustomerAgreement Customers Accord entre le client Customer et le fournisseur de service
pour payer le service en un emplacement spécifique de
service. Il consigne certaines informations de facturation
concernant le type de service fourni en l'emplacement
ServiceLocation et est utilisé pendant la création du débit pour
déterminer le type de service.
CustomerAgreementConfig Profile Profil de messages pour les "CustomerAgreement".
CustomerMeterDataSet Profile Le "CustomerMeterDataSet" (jeu de données de compteur
client) comprend un ou plusieurs "CustomerAccount" (comptes
clients) pour un ou plusieurs "ServiceLocations"
(emplacements de service) pour un ou plusieurs "UsagePoint"
(points d'usage). Le CustomerMeterDataSet peut comprendre
un ou plusieurs EndDeviceGroup.
DemandResponseProgram Metering Programme de réponse à la demande.
DeviceFunction Metering Fonction accomplie par un appareil tel qu'un compteur, un
équipement de communication, des contrôleurs, etc.
EndDevice Metering L'EndDevice est l'équipement qui joue le rôle d'un dispositif
terminal. Il peut contenir des fonctionnalités telles que
métrologie, communications, régulation de charge,
branchement/débranchement, ou autres capacités. Il est connu
comme étant "le compteur", "un compteur intelligent", un
"compteur avancé", "climatiseur", "réfrigérateur", "pompe de
piscine", etc. qu'un CommModule et/ou Meter peut surveiller
61968-9  CEI:2013 – 473 –

Classe/Nom Type Description


et/ou commander. Le bien peut être la propriété d'un client,
d'un fournisseur de service, d'une entreprise de distribution ou
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

autre partie.
EndDeviceConfig Profile Message utilisé pour acheminer les descriptions d'un ou
plusieurs EndDevice.
EndDeviceControl Metering Sert à émettre des commandes vers les EndDevice tels que
les compteurs. Peut être traitée par EndDevice ou par
EndDeviceGroup. Les commandes EndDeviceControl peuvent
avoir des types et paramètres de commande.
EndDeviceControls Profile Message utilisé pour acheminer une ou plusieurs
EndDeviceControls
EndDeviceControlType Metering Définit les types d'EndDeviceControls
EndDeviceEvent Metering Sert à rapporter des événements détectés par les dispositifs
terminaux tels que les compteurs.
EndDeviceEvents Profile Message utilisé pour acheminer un ou plusieurs
EndDeviceEvents.
EndDeviceEventType Metering Définit les types d'EndDeviceEvents
EndDeviceFirmware Profile Profil pour les messages de configuration de microprogramme
d'EndDevice.
EndDeviceGroup Metering Un EndDeviceGroup est utilisé pour regrouper des dispositifs
terminaux pour une diversité de besoins, y compris, mais de
manière non exhaustive, la régulation de la charge et autres
types de réponse à la demande. Un EndDeviceGroup peut
appartenir à un autre EndDeviceGroup et un dispositif terminal
peut appartenir à zéro, à un ou à plusieurs EndDeviceGroup.
Dans certains cas, l'ID de groupe est maintenu au sein du
dispositif terminal; dans d'autres cas, il peut être géré par un
système de comptage.
EndDeviceGroups Profile Utiliser pour transmettre les modifications apportées aux
adhésions au groupe
GetCustomerMeterDataSet Profile Profil pour les demandes GET. Voir l'Annexe J.
GetEndDeviceConfig Profile Profil pour les demandes GET. Voir l'Annexe J.
GetMeterReadings Profile Profil pour les demandes GET. Voir l'Annexe J.
GetMeterServiceRequests Profile Profil pour les demandes GET. Voir l'Annexe J.
Get<ProfileName> Profile Chaque profil aura un profil "Get" correspondant utilisé pour
transmettre les paramètres des demandes GET.
IntervalBlock Metering Séquence temporelle de Readings du même ReadingType. Les
IntervalReading contenus peuvent nécessiter une conversion
par le biais de l'application d'un décalage et d'un scalaire
définis dans l'élément en attente associé.
IntervalReading Metering Données saisies à intervalles de temps réguliers. Des données
d'intervalles pourraient être saisies comme données
différentielles, données absolues ou données relatives. La
source pour les données est habituellement une grandeur
tarifaire ou une grandeur technique. Les données sont
typiquement saisies en des intervalles datés et uniformes, de
longueur fixe, de 5, 10, 15, 30 ou 60 min.
NOTE Les données d'intervalles sont parfois appelées
"Relevés de lecture d'intervalles" (IDR, "Interval Data
Readings").
MasterDataLinkageConfig Profile Un profil de message utilisé pour établir ou modifier les
relations entre les objets.
MerchantAccount PaymentMetering Le compte opérationnel contrôlé par MerchantAgreement, au
débit ou au crédit duquel chaque fournisseur Vendor peut
vendre des jetons ou recevoir des paiements. Les transactions
via VendorShift débitent le compte alors que les dépôts
bancaires via BankStatement créditent le compte.
MerchantAgreement PaymentMetering Accord contractuel de contrôle formel entre le fournisseur
Supplier et le marchand Merchant, aux termes duquel le
marchand est autorisé à vendre des jetons et recevoir des
paiements au nom du fournisseur. Le marchand Merchant est
– 474 – 61968-9  CEI:2013

Classe/Nom Type Description


comptable vis-à-vis du fournisseur Supplier des recettes
collectées au point de vente PointOfSale.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Meter Metering La classe Meter est utilisée pour décrire les compteurs. Un
Meter est un type d'EndDevice utilisé typiquement pour
mesurer et surveiller potentiellement une charge client. Il
convient d'utiliser la définition de la classe EndDevice comme
base pour la classe Meter.
MeterConfig Profile Profil de messages relatifs aux messages de configuration des
Meter.
MeterReading Metering Jeu de valeurs relevées du compteur. Chaque MeterReading
peut avoir plusieurs ReadingTypes, et chaque ReadingType
peut contenir plusieurs valeurs.
MeterReadings Profile Profil pour acheminer des MeterReadings.
MeterReadSchedule Profile Un message MeterReadSchedule est utilisé pour programmer
les relevés des compteurs.
MeterServiceRequests Profile Une demande de services de compteur est un type de tâche
qui peut être utilisé pour une diversité d'activités liées aux
services des compteurs. Ces activités incluraient la pose des
compteurs, le remplacement des compteurs, le
débranchement/rebranchement de client, etc.
MeterServiceWork Metering Tâches impliquant des compteurs.
ObjectNamesConfig Profile Utilisé pour ajouter, modifier ou supprimer les identificateurs
de la classe Names des objets CIM.
Pending Metering Lorsqu'il est présent, conversion scalaire qui est associée
à IntervalBlock et qu'il est nécessaire d'appliquer à chaque
valeur IntervalReading contenue. Cette conversion se traduit
en un nouveau ReadingType associé, reflétant les véritables
dimensions des valeurs de relevés d'intervalles après la
conversion.
PointOfSale PaymentMetering Point logique où les transactions ont lieu avec interaction
opérationnelle entre le caissier Cashier et le système de
paiement; dans certains cas, le point de vente PointOfSale
interagit directement avec le client final, auquel cas le caissier
Cashier pourrait ne pas être une personne réelle: par exemple
un kiosque self-service ou sur internet.
PricingStructure Client Regroupement de composantes de tarification et de prix utilisé
dans la création des débits client et les critères d'éligibilité
selon lesquels ces termes peuvent être proposés à un client.
Les raisons du regroupement sont notamment les exigences
relatives à l'état, à la classification des clients, aux
caractéristiques de site, à la classification (c'est-à-dire,
structure de tarification des droits, structure de tarification des
dépôts, structure de tarification des services d'électricité, etc.)
et à la comptabilité.
PricingStructureConfig Profile Profil de configuration des structures de tarification.
Reading Metering Valeur spécifique mesurée par un compteur ou autre dispositif
physique. Chaque Reading (relevé) est associé à un
ReadingType spécifique.
ReadingQuality Metering Qualité d'une valeur de relevé spécifique ou d'une valeur de
relevé d'intervalle. Note: plusieurs qualités peuvent être
applicables à un Reading donné. En général non utilisé sauf
s'il se produit des problèmes ou des conditions inhabituelles
(c'est-à-dire, la qualité pour chaque Reading est censée être
"Good" (bonne) sauf énoncé contraire dans le
ReadingQuality associé).
ReadingQualityType Metering Définit les types des qualités qui peuvent être associées à une
valeur de relevé de lecture.
ReadingType Metering Type de données véhiculé par un Reading spécifique.
Receipt PaymentMetering Enregistrement du paiement acquitté total de la part du client.
ReceiptRecord Profile Profil pour les messages de reçus.
ReceiptSummary PaymentMetering Enregistrement du détail des reçus (acquits) relatifs à une
période de travail d'exploitation (un enregistrement par
61968-9  CEI:2013 – 475 –

Classe/Nom Type Description


"tenderKind").
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Register Metering Affichage pour la grandeur qui est comptée sur un dispositif
terminal tel qu'un compteur.
ServiceCategory Customers Catégorie de service fourni au client.
ServiceCategoryConfig Profile Profil pour les messages de configuration de ServiceCategory.
ServiceLocationConfig Profile Profil pour les messages de configuration de ServiceLocation.
ServiceSupplier PaymentMetering Organisation qui fournit des services aux clients Customer.
ServiceSupplierConfig Profile Profil pour les messages de configuration de fournisseur de
service.
Shift PaymentMetering Se réfère généralement à une période de fonctionnement ou
à un travail accompli. Le fait qu'une période de travail soit
ouverte/fermée peut être dérivé des attributs
"activiryInterval.start" et "activityInterval.end".
Le total général pour les acquits (à savoir, total cumulé de tous
les montants réellement acquittés pendant cette période de
travail; bancables + non bancables; totaux des erreurs
d'arrondi exclus) peut être dérivé des attributs de Receipt:
=sum(Receipt.receiptAmount); inclut les acquits qui peuvent ou
non être déposés en banque.
SimpleEndDeviceFunction Metering Fonction simple d’un dispositif terminal qui se différencie par
"type", utilisation de cette classe pour des instances qui ne
peuvent pas être représentées par un autre sous-type de
fonction de dispositif terminal.
Tariff PaymentMetering Document, approuvé par l'agence de régulation responsable,
énumérant les termes et conditions, y compris un recueil des
prix, dans lesquels les services publics seront fournis. Il a un
numéro unique dans l'état ou la province. Pour les échelles
tarifaires, il est fréquemment alloué par la commission des
services publics (Public Utilities Commission) affiliée.
Tender PaymentMetering L'offre réelle, c'est-à-dire ce qui est "offert" par le client pour
effectuer un paiement, est souvent supérieure au paiement qui
doit être effectué (d'où le besoin de "change" c’est-à-dire
d’appoint). Le paiement est ainsi la partie de l'offre réelle
(c'est-à-dire Tender) qui tend vers le règlement d'une
transaction particulière.
L'offre réelle (c'est-à-dire Tender) est modélisée comme une
agrégation de Cheque (c'est-à-dire chèque) et de Card (c'est-
à-dire carte). Ces deux types d'offre peuvent coexister dans la
même soumission et donc "accountHolderName" doit exister
séparément dans chaque Cheque et Card car chacun de ceux-
ci pourrait avoir un nom de titulaire de compte différent.
TimeTariffinterval PaymentMetering L'une d'une séquence d'intervalles de temps définis en termes
de temps réel. Il est typiquement utilisé en association avec
TariffProfile pour définir les intervalles dans une structure de
tarifs fixés en fonction du temps d'utilisation, où startDateTime
détermine simultanément le point de départ de cet intervalle et
le point final de l'intervalle précédent.
Transaction PaymentMetering Enregistrement des détails du paiement pour le service ou la
vente de jetons.
TransactionRecord Profile Profil pour les messages de transactions.
TransactionSummary PaymentMetering Enregistrement du détail des transactions de paiement
relatives à une période de travail d'exploitation (un
enregistrement par "transactionKind").
Transactor PaymentMetering (agent de transaction) L'entité qui exécute en dernier ressort la
transaction et qui a le processus pour son contrôle;
typiquement, elle est incorporée dans un logiciel sécurisé
s'exécutant sur un serveur qui peut employer des appareils de
chiffrement matériel pour un traitement sécurisé des
transactions.
UsagePointLocation Metering Emplacement d'un point individuel d'usage. Pour les
résidences ou la plupart des entreprises, il s'agit typiquement
de l'emplacement d'un compteur dans les locaux d'un client.
– 476 – 61968-9  CEI:2013

Classe/Nom Type Description


Pour le transport, il s'agit des points d'interconnexion sur le
système de transport du fournisseur de transport où la
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

capacité et/ou l'énergie transmise par le fournisseur de


transport est mise à la disposition de la partie réceptrice. Les
points de livraison sont spécifiés dans l'accord de service.
UsagePointLocationConfig Profile Message utilisé pour établir les associations aux
UsagePointLocations.
UsagePoint Metering Point logique sur un réseau de distribution auquel les lectures
de compteurs et/ou les événements de dispositifs terminaux
peuvent être attribués. Utilisé à l'endroit où un compteur
physique ou virtuel peut être installé; un compteur ne doit
cependant pas être obligatoirement présent.
UsagePointConfig Profile Message utilisé pour établir les associations aux UsagePoints.
UsagePointGroup Metering Abstraction applicable à la gestion des communications de
groupe au sein d'un système AMR bidirectionnel ou des
données pour un groupe de points d'usage associés. Les
commandes peuvent être émises à tous les points d'usage qui
appartiennent à un groupe de points d'usage utilisant une
adresse de groupe définie et l'infrastructure de communication
AMR sous-jacente.
UsagePointGroups Profile Message utilisé pour établir les UsagePointGroups.
Vendor PaymentMetering Entité qui possède le point de vente PointOfSale et signe un
contrat avec le caissier Cashier pour acquitter des paiements
et vendre des jetons en utilisant le système de paiement. Le
fournisseur Vendor a un contrat privé avec le marchand
Merchant, et est géré par celui-ci, qui est un type
d'Organisation. Le fournisseur Vendor est comptable vis-à-vis
du marchand Merchant des recettes collectées, qui a son tour
est comptable vis-à-vis du fournisseur Supplier.
VendorShift PaymentMetering La période opérationnelle de travail pour un fournisseur
pendant laquelle il peut opérer des transactions portées au
débit d'un compte du marchand. Elle rassemble les
transactions et les acquits pendant la période de travail et
débite périodiquement le compte d'un marchand. Il convient
que les totaux dans VendorShift soient toujours égaux (=) à la
somme des totaux accumulés dans toutes les périodes de
travail de caissier qui étaient ouvertes pendant la période
particulière de travail du fournisseur.
NOTE Les définitions de classes fournies ici sont données pour des raisons pratiques uniquement. Les définitions
normatives sont fournies par le CIM.

4.5.3 Classes relatives au relevé et à la commande des compteurs

Le Tableau 4 énumère les classes qui sont associées aux classes relatives au relevé et à la
commande des compteurs, mais seul le nom d'une instance est donné dans les messages
définis dans la présente norme. Les attributs détaillés de ces classes sont utilisés dans les
types de messages définis dans d'autres parties de la CEI 61968.
61968-9  CEI:2013 – 477 –

Tableau 4 – Classes relatives au relevé et à la commande des compteurs


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Classe connexe Référence Description


Organisation Common Cette classe est utilisée pour identifier des sociétés ou des
divisions/départements au sein des sociétés. Les organisations
pourraient jouer des rôles tels que ceux des entreprises de
distribution, des entrepreneurs, des fournisseurs, des
constructeurs, etc.
PowerSystemResource Core (c'est-à- Une entité qui décrit la représentation logique d'une partie de
dire Cœur) composant d'une activité de Distribution. Les
PowerSystemResources sont classés en plus comme
(CEI 61970- EquipmentContainers, par exemple, Substations,
301) ConductingEquipment, ProtectionEquipment, etc.
Les instances de type PowerSystemResource peuvent être
relatives à des instances du type Asset.
PowerTransformer Wires (c'est-à- Appareil électrique constitué de deux enroulements couplés ou
dire Fils) plus, avec ou sans cœur magnétique, destiné à introduire un
couplage mutuel entre les circuits électriques. Les transformateurs
(CEI 61970- peuvent être utilisés pour contrôler la tension et le déplacement de
301) phase (flux MW).
ServiceLocation Customers Un ServiceLocation (emplacement de service) de client possède
un ou plusieurs UsagePoint. Les compteurs sont relatifs à un
UsagePoint. L'emplacement peut être un point ou un polygone,
selon les circonstances spécifiques.
Pour la distribution, le ServiceLocation est typiquement
l'emplacement du local du client du service public. Parce qu'un
local de client peut avoir un ou plusieurs compteurs, l'UsagePoint
est utilisé pour définir l'équipement conducteur réel auquel
l'EndDevice se fixe en l'emplacement ServiceLocation du client de
l'entreprise de distribution.
Pour le transport, il s'agit des points d'interconnexion sur le
système de transport du fournisseur de transport où la capacité
et/ou l'énergie transmise par le fournisseur de transport est mise
à la disposition de la Partie réceptrice.
TransformerTank Wires (c'est-à- Un enroulement du transformateur.
dire Fils)
(CEI 61970-
301)
NOTE Les définitions de classes fournies ici sont données uniquement pour des raisons pratiques. Les définitions
normatives sont fournies par la CEI 61968-11, qui décrit les extensions de distribution au CIM de la CEI.

5 Types de messages de relevé et de commande des compteurs

5.1 Généralités

Le présent Article 5 a pour but de décrire les types de messages relatifs à la CEI 61968-9. Il
est important de noter que certains de ces types de messages peuvent aussi être utilisés par
d'autres parties de la CEI 61968. L'approche générale relative à la réalisation des structures
de message et des schémas XML pour les messages CEI 61968 est décrite dans la
CEI 61968-1 et la CEI 61968-100.

Bien qu'ils puissent être représentés dans des diagrammes de séquences pour le contexte et
la complétude, le présent document ne décrit pas les formats de message qui sont définis par
d'autres parties de la CEI 61968. Les structures de la charge utile des messages qui sont
définies par la présente partie de la CEI 61968 sont décrites dans l'Article 5.

Les schémas XML normatifs pour les messages définis par la présente Partie sont donnés
dans l'Annexe H, fournissant des descriptions annotées plus détaillées des structures de
messages. L'Annexe I fournit les schémas XML qui sont informatifs. Les structures de
– 478 – 61968-9  CEI:2013

messages sont présentées dans l' Article 5. La convention de notation montre les éléments
requis avec un contour en trait plein et les éléments facultatifs avec des contours en traits
tiretés.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Il est également important de noter que les cas d'utilisation et les diagrammes de séquences
fournis dans la présente norme sont de nature informative et sont censés présenter des
exemples d'utilisation pour les définitions de message normatives. La présente norme ne vise
nullement à normaliser des processus métier spécifiques.

5.2 Messages d'événements de dispositif terminal

5.2.1 Généralités

Un événement est un rapport d'une modification d'état qui peut avoir un intérêt potentiel. Les
messages d'événement de dispositif terminal sont conçus comme étant un moyen de
transmettre les modifications d'état d'un dispositif terminal par le biais de l'appareil lui-même
ou d'un proxy pour le compte d'un dispositif terminal. Les événements de dispositif terminal
sont vus comme un flot potentiel de données qui n'est pas nécessairement synchronisé à la
collecte de relevés de compteur à des fins de facturation. Cependant, il peut encore être
pertinent pour le processus de facturation. Une alarme relative à la santé du compteur peut
être si sévère que tous les relevés du compteur sont à considérer comme non valides. Le
client de données (par exemple, le système MDM) peut recevoir les données d'un événement
pertinentes disponibles et les considérer lors du processus de validation, d'estimation et
d'édition. Il peut également rapporter les données d'un événement à d'autres systèmes
d'entreprise, puis les utiliser pour déclencher des actions telles que la création d'un
MeterServiceRequest en vue de réparer ou de changer un compteur défectueux.

5.2.2 Applications

5.2.2.1 Généralités

La présente norme considère les "événements" comme étant différents des "statuts". La
plupart des systèmes MR ne garantissent pas une livraison dans les délais d'un
EndDeviceEvent. Par ailleurs, un "statut" n'est utile que lorsqu'il est frais. Le statut d'un
EndDevice est généralement obtenu à l'aide d'un GetMeterReadings "OnRequest". Le rapport
d'un EndDeviceEvent arrivera finalement au service d'administration de l'entreprise de
distribution et sera traité à son tour. Cela implique que différentes applications seront
naturellement divisées en différents types d'échanges de messages selon la technologie de
communication sous-jacente utilisée par le système MR et le besoin d'avoir des données
opportunes. Certains systèmes peuvent avoir la capacité de rapporter une interruption de
service en tant qu'événement. D'autres systèmes peuvent la traiter en tant que statut. La
plupart des systèmes MR rapporteront un changement de la santé du compteur en tant
qu'événement, mais certains peuvent exiger qu'elle soit relevée en tant que statut. De la
même manière, la plupart des systèmes MR rapporteront la qualité de l'énergie en tant
qu'événement, bien que certains puissent la traiter en tant que statut.

5.2.2.2 Détection des interruptions de service

Lorsqu'une interruption de service n'est pas due à un déclenchement par le système SCADA
(Supervisory Control and Data Acquisition, système d'acquisition et de contrôle des données),
les entreprises de distribution d'électricité dépendent typiquement des appels émis par les
clients pour identifier l'emplacement du défaut. Cependant, l'utilisation d'un MS peut fournir
un autre moyen d'identifier l'emplacement du problème. Il est souvent possible pour un MS de
déterminer qu'il a perdu le contact avec le compteur, auquel cas cela peut être consigné dans
un rapport en tant qu'EndDeviceEvent afin d'être potentiellement utilisé par un système de
gestion des interruptions de service. Il est important de noter que la perte de communications
avec un compteur peut ne pas être suffisante pour identifier l'existence d'une interruption de
service, car il est courant que certaines technologies MS perdent occasionnellement le
contact avec les compteurs pendant de courtes périodes de temps.
61968-9  CEI:2013 – 479 –

Certains systèmes MS peuvent être enclins aux fausses alarmes à cause de la technologie
particulière utilisée pour communiquer avec les compteurs. De nombreux fournisseurs
travaillent à améliorer leur technologie et la précision de leurs données. Avec beaucoup de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

ressemblance avec le rôle qu'il joue parfois dans le nettoyage des données comptées pour
des applications de facturation, la MDM peut aussi jouer un rôle dans le nettoyage des
données relatives aux interruptions de service fournies par le MS avant qu'elles ne soient
relayées à l'OMS. Une telle décision, à savoir acheminer par le truchement de la MDM les
données relatives aux interruptions de service, dépend de la capacité du MS à fournir des
données exactes, de l'aptitude de la MDM à nettoyer les données sans introduire de retards
excessifs et de l'aptitude de l'OMS à tolérer les fausses alarmes et les retards. Afin de
prendre en charge l'analyse des interruptions de service et le filtrage des données de
mauvaise qualité, le MS peut fournir des données de vérification rétrospective et des données
relatives à la qualité des mesures pour l'événement d'interruption de service, de la même
manière qu'il fournit des données de vérification rétrospective pour les relevés pour
facturation. La Figure 5 décrit un déploiement dans lequel la MDM est utilisée pour diffuser
des informations relatives aux interruptions de service.

Légende

Anglais Français
Get queued events Obtenir les événements en file d'attente

Figure 5 – Détection d'interruptions de service, échange de message


de demande/réponse, exemple 1

Les systèmes de gestion des interruptions de service analysent le circuit en termes de


topologie de réseau. "EndDeviceEventType" peut indiquer un événement tel que détecté par
un dispositif terminal en vue de sa prise en compte dans l'analyse, ainsi que d'autres
informations telles que les tickets d'incident. Lorsqu'un EndDeviceEvent peut indiquer un état
intéressant qui peut s'avérer être une interruption de service, une interruption de service est
habituellement le résultat de l'analyse de l'interruption de service au sein d'un OMS qui
regroupera potentiellement plusieurs événements dans une seule interruption de service.

L'utilisation d'une MDM pour diffuser des données relatives aux interruptions de service est
à la discrétion de l'entreprise de distribution. Dans certains déploiements, la demande de
détection d'interruptions de service peut être émise directement de l'OMS vers le MS comme
dans l'exemple de la Figure 6.
– 480 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Get queued events Obtenir les événements en file d'attente

Figure 6 – Détection d'interruptions de service, échange de message


de demande/réponse, exemple 2

Une réponse (synchrone ou asynchrone) de la part du MS se présentera vraisemblablement


sous la forme de zéro, un ou plusieurs EndDeviceEvents. Le mRID ou la structure de noms
identifiera les dispositifs terminaux (par exemple:les compteurs) affectés par l'interruption de
service ou le rétablissement. Certains consommateurs de données qui interagissent avec
le MS pourraient savoir seulement comment traiter les ID des compteurs. Selon le
déploiement, il peut être requis de limiter l'étendue des mRID échangés à celle des ID de
compteurs à l'aide de la classe Nom, non à celle des ressources du réseau électrique en
général. Le statut "EndDeviceEvent.status" peut indiquer "live" (c'est-à-dire actif) ou "dead"
(c'est-à-dire hors tension). Certains systèmes de comptage peuvent compléter les
informations de statut avec une preuve de collaboration en utilisant la classe
EndDeviceEventDetails. EndDeviceEventType peut être utilisé pour indiquer que le statut
s'applique à un compteur ou à un transformateur de puissance. La raison de l'événement peut
être décrite (par exemple EndDeviceEvent.reason = "consecutiveFailCounter") et quantifiée
(par exemple EndDeviceEvent.severity = "3").

Alors que l'échange de demande/réponse est utilisable chaque fois que l'OMS a besoin
d'informations supplémentaires, certains MS sont capables de détecter automatiquement les
interruptions de service. Un échange pub/sub (c'est-à-dire publication/abonnement) est idéal
dans ces situations. La Figure 7 montre un tel échange en un déploiement où la MDM sert de
courtier d'informations. La Figure 8 montre un déploiement avec des informations allant
directement du MS à l'OMS.
61968-9  CEI:2013 – 481 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Detect Meter Events Détecter les événements de compteur
Validate and/or filter events Valider et/ou filtrer les événements

Figure 7 – Détection d'interruptions de service,


échange de publication/abonnement, exemple 1

Le diagramme de séquence suivant montre un exemple de propagation d'événements sans


avoir recours à une MDM.

Légende

Anglais Français
Detect Meter Events Détecter les événements de compteur

Figure 8 – Détection d'interruptions de service,


échange de publication/abonnement, exemple 2
– 482 – 61968-9  CEI:2013

Certains déploiements peuvent souhaiter limiter le nombre d'interfaces prises en charge. La


structure des messages MeterReadings fournit également le moyen d'acheminer des
EndDeviceEvents.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les exemples précédents reflètent l'échange de messages d'événement de dispositif terminal


afin de prendre en charge les fonctions de gestion des interruptions de service. Comme cela
a été expliqué auparavant, il est également souvent préférable de disposer d'un système de
gestion des interruptions de service ou un système MDM qui effectue une requête de lecture
sur demande au système de comptage en vue d'obtenir le statut d'excitation actuel d'un
dispositif. Cela est réalisé en utilisant un échange get(MeterReadings) tel que décrit en 5.3.
Dans de tels cas, le ReadingType (voir Annexe C) demandé indiquera que l'état d'excitation
fait l'objet de la demande en cours.

5.2.2.3 Evénements de santé des compteurs

Certains types de compteurs peuvent parfois générer des événements de santé de


compteurs, qui peuvent être utilisés pour identifier les problèmes de matériel, de configuration
ou de branchement de compteurs qu'il convient de résoudre. Les alarmes comprennent des
éléments tels que les alarmes de diagnostic, alarmes de fraude ou autres conditions
inhabituelles. La sévérité de l'alarme pourrait aller d'une simple notification à "fatal".
Fréquemment, la résolution des événements liés à la santé du compteur exige une visite sur
site et elle débouche sur la création d'un MeterServiceRequest. Les événements de santé des
compteurs (Meter Health Events) sont communiqués à l'aide des messages EndDeviceEvent.

Figure 9 – Echange d'événements liés à la santé des compteurs, exemple 1

Lors de certains déploiements, la MDM sera présente pour diffuser les données de santé des
compteurs pour d'autres parties prenantes et agira probablement en vue de déclencher des
actions correctives telles que décrites dans le scénario de la Figure 9. Par contre, d'autres
installations pourraient ne pas avoir une MDM ou l'utiliser de cette manière. Il est possible
pour le MS d'éditer des données directement à l'attention des parties prenantes qui sont
équipées pour les recevoir. Un tel échange est illustré à la Figure 10.
61968-9  CEI:2013 – 483 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 10 – Echange d'événements liés à la santé des compteurs, exemple 2

5.2.2.4 Evénement relatif à la qualité d'énergie

Les compteurs peuvent recueillir des informations relatives à la qualité de l'énergie, y compris
(mais de manière non exhaustive) les événements d'interruption momentanée du service,
événements d'interruption durable du service, événements de haute ou basse tension et
événements de forte distorsion. Ces informations pourraient être utilisées pour l'analyse des
interruptions de service, la programmation de la maintenance ou la planification de la
capacité. Les événements relatifs à la qualité de l'énergie sont un sous-type
d'EndDeviceEvent.

Les événements liés à la qualité de l'énergie peuvent être diffusés (c'est-à-dire les
publications gérées) par une MDM (comme décrit à la Figure 11), ou envoyés directement aux
diverses parties prenantes (comme décrit à la Figure 12).

Figure 11 – Echange d'événements liés à la qualité de l'énergie, exemple 1


– 484 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 12 – Echange d'événements liés à la qualité de l'énergie, exemple 2

5.2.3 Format des messages

Les messages d'événements compteur sont mis en œuvre à l'aide de structures


EndDeviceEvent afin de prendre en charge une plus vaste diversité de sources d'événements
que les seuls compteurs. EndDeviceEvent.EndDeviceEventType (voir Annexe E) est une
référence à une énumération qui indique le type d'événement, tel que détection d'interruption
de service, santé de compteur ou qualité de l'énergie. L'horodatage et le mRID ou un nom
unique du dispositif terminal sont également requis. Le format des messages est décrit à la
Figure 13.
61968-9  CEI:2013 – 485 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 13 – Format des messages d'événements de dispositif terminal

Comme noté par la Figure 13, seuls les éléments timestamp et EndDeviceEventType sont
requis, avec un mRID ou un nom unique du dispositif terminal. L'élément
EndDeviceEventType permettra de différencier différents types d'événements (par exemple
santé de compteur, détection d'interruption de service, etc.). Différents types d'événements
permettraient à un message EndDeviceEvent d'acheminer des événements liés (y compris
notamment) à:

La détection d'interruptions prolongées de service


La détection d'interruptions momentanées de service
La détection de seuil basse tension
La détection de seuil haute tension
– 486 – 61968-9  CEI:2013

La déformation
La santé du compteur
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

La détection de fraude
L'événement recettes

Le schéma XML détaillé est fourni à l'Annexe H. Le XML suivant est un exemple
d'EndDeviceEvent.
<?xml version="1.0" encoding="UTF-8"?> <end:EndDeviceEvents
xmlns:end="http://iec.ch/TC57/2011/EndDeviceEvents#" xmlns:xsi=
"http://www.w3.org/2001/XMLSchema-instance">
<end:EndDeviceEvent>
<end:createdDateTime>2011-11-10T21:54:53.404+01:00</end:createdDateTime>
<end:issuerID>External System 1</end:issuerID>
<end:issuerTrackingID>123</end:issuerTrackingID>
<end:severity>5</end:severity>
<end:Assets>
<end:mRID>01f8b2e5-a677-4f2c-a6c0-1e79b409c55e</end:mRID>
<end:Names>
<end:name>Meter 123</end:name>
<end:NameType>
<end:name>Meter Name</end:name>
<end:NameTypeAuthority>
<end:name>Utility ABC</end:name>
</end:NameTypeAuthority>
</end:NameType>
</end:Names>
</end:Assets>
<end:EndDeviceEventType ref="3.12.0.257"/>
</end:EndDeviceEvent>
</end:EndDeviceEvents>

L'EndDeviceEvent est généré logiquement par un EndDevice et/ou un UsagePoint, l'un ou


l'autre peut être identifié par mRID et/ou Name. Tout comme dans la première édition de la
CEI 61968-9, un EndDeviceEvent est associé à un Asset, qui sera généralement un
EndDevice.

5.3 Messages de relevé de compteur

5.3.1 Généralités

Les messages des relevés de compteur sont conçus pour pouvoir transmettre les données
collectées par ou calculées pour le compte d'un compteur. Cela peut inclure les grandeurs
mesurées, calculées, les informations d'état ou l'historique collecté. A chaque fois qu'un
"measurement" (une mesure) est à fournir par un dispositif terminal, un échange
MeterReading est vraisemblablement l'outil tout à fait approprié pour la tâche. Le dispositif
terminal peut avoir une capacité de métrologie et dans ce cas, est le plus probablement
appelé "compteur". Mais il existe d'autres applications potentielles pour MeterReading. Si un
consommateur de données souhaite mesurer la position du commutateur sur un commutateur
de branchement / débranchement, cela peut être accompli sous la forme d'un échange de
MeterReading. Si un consommateur de données souhaite mesurer le statut "energisation"
(c'est-à-dire alimentation en énergie ou non) du dispositif terminal, cela peut être accompli
avec un échange de MeterReading ou, en variante, avec un échange d'EndDeviceEvent
comme décrit en 5.2.

5.3.2 Applications

5.3.2.1 Relevés périodiques de compteur

Il est nécessaire de rassembler périodiquement les relevés de compteur d'un MS pour


facturation à travers un système de facturation client. Il convient que le relevé de compteur
spécifie un compteur ou un groupe de compteurs, un type de relevé à recueillir ainsi qu'une
fréquence et une durée d'intérêt. La fréquence programmée peut consister en des périodes
régulières ou irrégulières.
61968-9  CEI:2013 – 487 –

La demande de MeterReadSchedule peut être lancée vers le MS à partir d'un nombre


quelconque des éléments suivants:
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• Le CIS (dans un effort visant à recueillir les déterminants de facturation).


• Une application de planification et de programmation (dans un effort visant à acquérir des
données techniques relatives au réseau de distribution).
• Un OMS (afin d'établir un flot d'informations de statut).
• Un système de gestion de données de compteur (dans un effort visant à relayer les
données pour tout ou partie des applications ci-dessus).
• Le MS proprement dit, qui peut lancer de lui-même un MeterReadSchedule.

Un exemple d'un tel échange (celui-ci utilisant en l'occurrence une MDM) est montré à la
Figure 14.

Légende

Anglais Français
read meter relever le compteur

Figure 14 – Exemple d'utilisation d'un programme de relevé


de compteur pour créer un abonnement

Certains systèmes de comptage peuvent avoir la fonctionnalité permettant de dissocier


collecte de MeterReading et compte-rendu de MeterReading. Pour les systèmes de comptage
sans cette fonctionnalité, les relevés peuvent être communiqués immédiatement dès leur
collecte. Dans la demande de MeterReadSchedule, des MeterReadings peuvent être
demandés à l'aide d'une diversité de paramètres, y compris:

• Un compteur spécifique, en utilisant le mRID EndDevice ou Names.name (voir Annexe G


pour une analyse de la classe Names)
• Des EndDeviceGroups, où un EndDeviceGroup identifie une adresse de groupe utilisée au
sein du système de comptage
• Un UsagePoint où se situe un compteur, à l'aide du mRID UsagePoint ou de Names.name
• Les UsagePointGroups, où UsagePointGroup identifie un groupAddress utilisé au sein du
système de comptage
• Comme indiqué lors de l'utilisation d'un TimeSchedule
– 488 – 61968-9  CEI:2013

• Les ReadingTypes peuvent être précisés pour identifier les types de lecture souhaités.

5.3.2.2 Relevé manuel de compteur


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les relevés de compteur peuvent être obtenus manuellement par un releveur de compteur.
Les données recueillies peuvent être maintenues par le gestionnaire de données de
compteur. Les compteurs peuvent collecter plusieurs types de mesure différents. Certains
types de compteurs peuvent mesurer plus d'une phase ou peuvent recueillir des valeurs pour
des mesures non électriques, telles que l'eau ou le gaz.

Un releveur de compteur peut entrer les données montrées sur le panneau du compteur dans
un appareil portable qui pourrait être considéré comme un système de comptage. L'entrée de
données peut se produire plusieurs centaines de fois par jour. Un releveur de compteur peut
présenter un rapport du relevé au client. A noter que ce rapport n'est pas une facture. La
facturation serait générée normalement par le CIS même dans le cas du relevé manuel. La
Figure 15 montre un tel échange.

Légende

Anglais Français
Meter Reader Releveur de compteur
Handheld device Appareil portable
Customer Client
Input meter data Entrer les données relatives au compteur
Print receipt Imprimer une quittance
Leave accounting of usage with customer Laisser le décompte de l'utilisation au client
perform billing établir la facturation

Figure 15 – Exemple d'échange de relevé manuel

A la fin de la journée de travail, toutes les données stockées dans l'appareil portable sont
envoyées vers la MDM via un réseau de communications. La MDM édite un message
à l'attention du CIS informant de la création du MeterReading.
61968-9  CEI:2013 – 489 –

Les programmes pour emprunter un itinéraire de relevé manuel du compteur sont décidés
bien avant d'accomplir le travail.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.3.2.3 Relevé de compteur sur demande

Les demandes de relevé de compteur sont émises à l'attention du MS afin d'obtenir des
relevés de compteur sur demande. Le MS enverra une demande aux compteurs souhaités.
Celles-ci peuvent être utilisées pour des demandes de renseignements facturation, la
vérification de l'étendue des interruptions de service, la vérification du rétablissement et
à d'autres fins commerciales.

De nombreuses entreprises de distribution ont une politique qui consiste à acheminer, via
la MDM, tous les relevés générateurs de recettes; ainsi, toutes les données recevront le
même niveau de validation. Cependant, ce ne sont pas tous les systèmes MDM qui sont
capables de proposer des services de validation pour les données relatives aux interruptions
de service. Pour ceux qui en sont capables, l'entreprise de distribution doit pondérer la valeur
de validation de la MDM en fonction du retard qui peut être introduit et de la capacité d'une
solution OMS particulière de rejeter les données incohérentes. Pour cette raison, le
diagramme exemple montre les relevés générateurs de recettes acheminés en passant par la
MDM, mais les données relatives aux interruptions de service la contournent.

Il est important de noter que tous les systèmes de comptage ne prennent pas en charge les
relevés "sur demande". Pour ceux qui le font, la mise en œuvre peut également varier
considérablement.

Les relevés sur demande peuvent être lancés vers le MS à partir de systèmes tels que les
suivants:

• Le CIS (dans un effort visant à recueillir les déterminants de facturation).


• Une application de planification et de programmation (dans un effort visant à acquérir des
données techniques relatives au réseau de distribution).
• Un OMS (afin de vérifier si un client est affecté par une interruption de service ou s'il a été
rétabli).
• Un système de gestion de données de compteur (dans un effort visant à relayer les
données pour tout ou partie des applications ci-dessus).
• Le MS proprement dit, qui peut lancer de lui-même une lecture de compteur.

Un exemple d'un tel échange (celui-ci utilisant en l'occurrence une MDM) est montré à la
Figure 16.
– 490 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
read meter relever le compteur

Figure 16 – Exemple de relevé de compteur sur demande

5.3.2.4 Accès aux données historiques de compteur

Un planificateur de réseau de distribution peut utiliser les valeurs de relevés historiques de


compteur comme informations relatives à la charge à des fins de planification de la capacité.
(Voir l'exemple de demande/réponse présenté dans la Figure 17). Cela permettrait d'agréger
l'usage afin de déterminer les charges pour un transformateur ou un départ.

Légende

Anglais Français
collect and aggregate MeterReadings collecter et rassembler les relevés du compteur

Figure 17 – Echange de MeterData d'historique


61968-9  CEI:2013 – 491 –

Il est important de noter l'utilisation de paramètres de demande pour qualifier les demandes
de données de compteur, filtrant les résultats pour obtenir des données pour des compteurs
spécifiques dans les limites de délais spécifiques.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.3.2.5 Demande de renseignements de facturation

Un client ou une source interne peut identifier une question de facturation client. Une
demande de relevé de compteur en combinaison avec des relevés historiques de compteur
peut être utilisée pour résoudre le problème de facturation. Le haut de la Figure 18 montre
une demande de renseignements dans le processus d'être satisfaite par des données qui sont
arrivées récemment, alors que plus tard dans la journée, il est fait une demande de
renseignements qui exige une lecture fraîche du compteur.

Dans certains cas, les données souhaitées peuvent être accessibles depuis la MDM. Dans
d'autres cas, il peut être nécessaire d'émettre une demande de relevé, à distance par le
truchement du MS ou manuellement par le biais d'une demande de service compteur.

Légende

Anglais Français
read meter relever le compteur

Figure 18 – Exemple d'échange de message de demande


de renseignements de facturation

5.3.3 Format des messages

Le schéma XML détaillé pour les messages est décrit à l'Annexe H. La Figure 19 montre le
format de message pour présenter les lectures de compteur relevées sur un ou plusieurs
dispositifs terminaux.
– 492 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 19 – Format de message pour les relevés de compteur

La structure du message pour les MeterReadings permet de prendre en compte les éléments
suivants:

• les relevés provenant d'un ou plusieurs compteurs;


• les valeurs de relevé ont chacune un type de relevé, un horodatage et une valeur;
61968-9  CEI:2013 – 493 –

• plusieurs valeurs de qualité peuvent être associées à chaque valeur de relevé;


• les relevés peuvent être présentés sous la forme de blocs d'intervalles, où des relevés
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

d'un même type de relevé sont groupés ensemble;


• les historiques d'événements peuvent être retournés avec les relevés de compteur.

La Figure 20 montre les détails de la structure qui transmet les relevés, où chaque relevé
identifie un ReadingType spécifique (par référence), une valeur et des codes de qualité
optionnels. Le timeStamp est utilisé pour identifier le moment où le relevé a été capturé. La
timePeriod peut être utilisée pour identifier un intervalle de temps spécifique. Le
reportedDateTime optionnel peut être utilisé pour identifier le moment où le relevé a
réellement été rapporté. Le ReadingType est utilisé pour identifier la signification du relevé, le
type de données de la valeur et la signification des différentes valeurs temporelles.

Figure 20 – Structure Reading

Dans un relevé, les attributs timeStamp et timePeriod peuvent être utilisés pour identifier les
aspects temporels du relevé, avec un usage spécifique basé sur le type de relevé, dont les
détails sont décrits à l'Annexe C selon les besoins. Les exemples suivants illustrent les
conventions générales d'utilisation de timeStamp et timePeriod.
– 494 – 61968-9  CEI:2013

Calendar Meter AMI Network MDMS


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

timePeriod.start = time1 Begin


timeperiod of
interest The moment the value
is created is captured
as a timestamp

Maximum demand value


Readings.timeStamp = time2
observed

Readings.value;
{timePeriod} Readings.timeStamp;
Readings.reportedDateTime
Readings.reportedDateTime = time3 Readings.value;
Readings.timeStamp;
Readings.reportedDateTime

When the reading is


reported, it is time-
stamped.

timePeriod.end = time4 End time period of interest

Légende

Anglais Français
Calendar Calendrier
Meter Compteur
AMI Network Réseau AMI
Begin timeperiod of interest Début de la période étudiée
The moment the value is created is captured as a Le moment auquel la valeur est créée est
timestamp capturé sous forme d'horodatage
Maximum demand value observed Valeur de demande maximum observée
When the reading is reported, it is timestamped. Lorsque la lecture est relevée, elle fait l'objet
d'un horodatage.

Figure 21 – Horodatages affectés entre les systèmes

La Figure 21 montre la façon dont les horodatages sont affectés et dont les valeurs sont
créées et passées entre les systèmes. Du point de vue des CIS et MDMS, il existe une
"timePeriod" intéressante pour (peut-être) une période de facturation. Une demande "get"
pourrait préciser cette plage de temps, et l'AMI ou le MDMS "répondraient" à l'aide de relevés
qui correspondent à cette plage. Les points importants dans le temps concernant la
production et le compte-rendu de la valeur sont également marqués temporellement.
L'ensemble de ces horodatages sont donnés dans le schéma meterReadings. Une autre vue
du même exemple (avec des dates et des heures réelles) est présentée ci-dessous dans la
Figure 22.
61968-9  CEI:2013 – 495 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
maximum value requested valeur maximum demandée
demand maximum maximum demandé
timeStamp timeStamp (Horodatage)
timePeriod start Début de timePeriod
timePeriod end Fin de timePeriod

Figure 22 – Conventions pour timeStamp et timePeriod

La structure IntervalBlock permet de regrouper un ensemble de relevés selon un


ReadingType commun et sert d'exemple pour représenter une série chronologique.
– 496 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 23 – Structure IntervalBlock

Le diagramme suivant montre la convention d'utilisation d'un timeStamp pour les données
d'intervalles ayant un type de lecture associé qui identifie que la valeur de relevé correspond
à un intervalle précis.

Les différents systèmes MR fonctionnent de diverses manières, mais aux fins de la norme, les
horodatages représentent la fin de l'intervalle. Le processus de production implicite est décrit
ci-après dans la Figure 24.
61968-9  CEI:2013 – 497 –

Meter
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

t1 = now
Perform self read value 1

{Interval = t2-t1}

Capture self read 2 and compute deltaData


t2 = now "Readings.value = (value 2 - value 1)" ; and
set "Readings.timeStamp = t2"
{Interval = t3-t2}

Capture self read 3 and compute


t3 = now
"Readings.value = (value 3 - value 2)";
and set "Readings.timeStamp = t3"

loop
[forever]
tn = now Capture self read 'n' and compute
"Readings.value = (value 'n' - value 'n-1')"; and
set Readings.timeStamp = tn

Légende

Anglais Français
Meter Compteur
t1 = now t1 = maintenant
{Interval = t2-t1} {Intervalle = t2-t1}
t2 = now t2 = maintenant
{Interval = t3-t2} {Intervalle = t3-t2}
t3 = now t3 = maintenant
Perform self read value 1 Autorelevé de valeur 1
Capture self read 2 and compute deltaData Capturer autorelevé 2 et calculer deltaData
"Readings.value = (value 2 – value 1)"; and "Readings.value = (value 2 – value 1)"; et
set "Readings.timeStamp = t2" définir "Readings.timeStamp = t2"
Capture self read 3 and compute Capturer autorelevé 3 et calculer
"Readings.value = (value 3 – value 2)"; "Readings.value = (value 3 – value 2)";
and set "Readings.timeStamp = t3" et définir "Readings.timeStamp = t3"
loop boucle
tn = now tn = maintenant
Capture self read 'n' and compute Capturer autorelevé "n" et calculer
"Readings.value = (value 'n' – value 'n-1')"; and "Readings.value = (value 'n' – value 'n-1')"; et
set Readings.timeStamp = tn définir Readings.timeStamp = tn

Figure 24 – Production d’horodatages pour les données d'intervalle

Lorsqu'un horodatage est utilisé, il doit faire partie d'une plage temporelle allant de 00:00:00
à 23:59:59 telle que décrite à la Figure 25. Une valeur égale à 23:59:59 plus 1 s place l'heure
à minuit, ce qui correspond au début du jour suivant.
– 498 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Interval timeStamp Intervalle d'horodatage
15-minute Interval Intervalle de 15 minutes

Figure 25 – Conventions relatives aux intervalles de temps

A noter que conformément à l'ISO 8601, l'heure 24:00 du jour actuel est égale à 00:00 du jour
suivant. Une journée commence et finit à 00:00. Il est important de noter que les données
d'intervalle peuvent être transmises à l'aide des IntervalBlocks avec les IntervalReadings ou
en utilisant simplement les Readings. Les IntervalBlocks doivent être utilisés lorsque les
éléments PendingCalculation sont requis, sinon ils permettent simplement une empreinte XML
réduite sur Readings, ce qui peut s'avérer important dans certaines situations.

La clé pour le compte-rendu d'une valeur issue d'un compteur est le type de relevé. La classe
ReadingType dans le CIM est définie pour permettre la saisie des informations suivantes
relatives à la description d'un type de relevé, ce qui est défini en profondeur à l'Annexe C.
61968-9  CEI:2013 – 499 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 26 – Structure ReadingType

Tandis que la structure ReadingType est présente dans le message MeterReadings, il


convient de prévoir que dans le cadre d'une pratique normale elle ne sera pas remplie,
puisqu'il est anticipé que le système consommateur sera déjà configuré avec les définitions
ReadingType appropriées. Les détails relatifs à cette classe et à d'autres classes spécifiques
au comptage sont décrits dans le paquetage Metering du CIM. Un débat plus approfondi sur
les types de relevé est présenté dans l'Annexe C.

Les relevés ne sont pas limités aux appareils de comptage. Tout EndDevice peut
potentiellement produire une mesure. Dans cette édition de la CEI 61968-9, le bien
produisant le relevé doit être identifié en utilisant la classe Meter, bien que l'appareil ne
puisse pas nécessairement être un Meter. Il est prévu que tous les biens auront un mRID
– 500 – 61968-9  CEI:2013

unique ou un Names.name afin que les compteurs puissent être distingués par rapport aux
commutateurs de branchement/débranchement à distance et par rapport à d'autres appareils.
Il est convenu que future édition de la CEI 61968-9 fournira une méthode plus explicite de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

gestion des relevés issus d'appareils autres que les Meters.

Les données d'intervalle ont des exigences d’horodatage unique. Les fonctionnalités
étendues selon l'ISO 8601 fournissent le moyen de spécifier une longueur d'intervalle formelle
(telle qu'une "période" de temps selon l'ISO 8601) et aussi un point de référence fixe.

Le XML ci-après fournit certains exemples de charge utile en XML pour des messages
MeterReadings.
<?xml version="1.0" encoding="UTF-8"?>
<mr:MeterReadings xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#">
<mr:MeterReading>
<mr:Meter>
<mr:Names>
<mr:name>63.89.98.184</mr:name>
<mr:NameType>
<mr:description>This is an endpoint serial number</mr:description>
<mr:name>EndpointID</mr:name>
<mr:NameTypeAuthority>
<mr:description>AssetManagementSystem</mr:description>
<mr:name>com.company.assets</mr:name>
</mr:NameTypeAuthority>
</mr:NameType>
</mr:Names>
</mr:Meter>
<mr:Readings>
<mr:timeStamp>2011-12-05T17:21:40.628Z</mr:timeStamp>
<mr:value>25.633</mr:value>
<mr:ReadingType ref = "0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0"/>
</mr:Readings>
<mr:Readings>
<mr:timeStamp>2011-12-05T17:21:40.628Z</mr:timeStamp>
<mr:value>10.0</mr:value>
<mr:ReadingType ref = "0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.38.0"/>
</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>

<?xml version="1.0" encoding="UTF-8"?>


<mr:MeterReadings xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#">
<mr:MeterReading>
<mr:Meter>
<mr:Names>
<mr:name>63.89.98.184</mr:name>
<mr:NameType>
<mr:description>This is an endpoint serial number</mr:description>
<mr:name>EndpointID</mr:name>
<mr:NameTypeAuthority>
<mr:description>AssetManagementSystem</mr:description>
<mr:name>com.company.assets</mr:name>
</mr:NameTypeAuthority>
</mr:NameType>
</mr:Names>
</mr:Meter>
<mr:IntervalBlocks>
<mr:IntervalReadings>
<mr:reportedDateTime>2001-12-17T09:30:47Z</mr:reportedDateTime>
<mr:timeStamp>2001-12-17T09:30:47Z</mr:timeStamp>
<mr:value>25.44</mr:value>
<mr:timePeriod>
<mr:end>2001-12-17T09:30:47Z</mr:end>
<mr:start>2001-12-17T09:30:47Z</mr:start>
</mr:timePeriod>
</mr:IntervalReadings>
<mr:ReadingType ref = "0.0.2.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0"/>
</mr:IntervalBlocks>
<mr:Readings>
<mr:timeStamp>2001-12-17T09:30:47Z</mr:timeStamp>
<mr:value>10.0</mr:value>
<mr:ReadingType ref = "0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.38.0"/>
61968-9  CEI:2013 – 501 –

</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Le concept de "relevés coïncidents" mérite une certaine attention. Un relevé coïncident est un
MeterReading qui survient au même instant que certains autres MeterReading ou
EndDeviceEvent.

Certains compteurs ont la capacité de rapporter un relevé qui était coïncident avec un autre
MeterReading ou EndDeviceEvent (ci-après dénommé "déclencheur" à la CEI 61968-9). Par
exemple, il peut éventuellement enregistrer le "facteur de puissance coïncident avec la
demande maximale de période de facturation."

En outre, certains processus demandent de rapporter un relevé coïncident. Par exemple,


lorsqu'un compteur est installé, il est courant de capturer un "relevé initial." De même,
lorsqu'un compteur est déconnecté, il est courant de capturer un "relevé final" coïncidant avec
l'événement de déconnexion.

Certains systèmes peuvent réaliser des analyses de données stockées pour identifier
analytiquement les relevés coïncidents dérivés. Par exemple,

• la tension de l’UsagePoint A au moment de demande quotidienne maximale sur le


transformateur de distribution (UsagePointB) qui dessert UsagePoint A. (UsagePoint "B"
pourrait être un UsagePoint réel ou virtuel.)
• la consommation toutes les 15 min au UsagePoint A au moment de demande quotidienne
maximale sur le réseau de distribution (UsagePoint C) une chaude journée d'été.
• un relevé en kWh BulkQuantity pour un UsagePoint au moment où un EndDeviceEvent,
comme un compteur, se déconnecte.

La classe MeterReading dispose d'un élément booléen optionnel appelé


"isCoincidentTrigger." L'élément n’est pas à utiliser dans un message, mais si c'est le cas,
des règles existent aux fins de son interprétation. Si toute instance d'un message
MeterReading est marquée de l’isCoincidentTrigger booléen défini sur "vrai", tous les autres
MeterReadings du même message MeterReadings sont alors considérés comme étant
coïncidents avec le MeterReading marqué de la sorte. Un seul élément MeterReading au sein
d'un seul message MeterReadings peut avoir son isCoincidentTrigger booléen défini sur
"vrai". Si l’isCoincidentTrigger booléen est absent, il est défini comme étant "faux". Il est
recommandé que le "déclencheur" MeterReading dispose d'un horodatage si ces informations
sont disponibles.

Le profil GetMeterReadings peut être utilisé pour faire en sorte que MeterReadings soient
coïncidents avec un MeterReading donné. Cela peut être réalisé en incluant dans le message
GetMeterReadings un élément MeterReadings dans lequel le CoincidentTrigger booléen est
défini sur "vrai;" en d'autres termes, en spécifiant le "déclencheur" MeterReading dans les
critères de filtre du GetMeterReadings.

NOTE Il est admis que de légères différences temporelles peuvent exister entre un déclencheur coïncident et
le(s) relevé(s) qui sont coïncidents avec le déclencheur. Par exemple, un relevé pris conjointement au
débranchement d'un compteur peut être réellement pris plusieurs secondes après l'utilisation du commutateur de
débranchement. Définir la fenêtre des relevés qui seront considérés comme étant coïncidents ne relève pas du
domaine d'application de la présente norme.

Dans l'exemple suivant, un système de comptage identifie une mesure du facteur de


puissance qui est coïncident avec la demande maximale d'un compte donné, sans connaître
la date et l'heure exactes de la demande maximale:
<mr:MeterReadings
xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterReadings#MeterReadings.xsd"
xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<mr:MeterReading>
<mr:Meter>
– 502 – 61968-9  CEI:2013

<mr:Names>
<mr:name>Meter_XYZ</mr:name>
</mr:Names>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</mr:Meter>
<mr:Readings>
<mr:value>0.0914159</mr:value>
<mr:ReadingType ref = "0.0.0.6.0.1.38.0.0.0.0.0.0.0.0.0.65.0"/>
<!--indicating electricitySecondaryMetered powerFactor (cos?)-->
</mr:Readings>
</mr:MeterReading>
<mr:MeterReading>
<mr:isCoincidentTrigger>true</mr:isCoincidentTrigger>
<mr:Meter>
<mr:Names>
<mr:name>Meter_ABCx1</mr:name>
</mr:Names>
</mr:Meter>
<mr:Readings>
<mr:ReadingType ref = "8.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0"/>
<!--billingPeriod maximum indicating forward electricitySecondaryMetered demand (kW)-->
</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>

Dans l'exemple suivant, un système de comptage ou un MDMS identifie le relevé de compteur


final coïncident avec le débranchement du service via DCR:

<mr:MeterReadings
xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterReadings#
MeterReadings.xsd"
xmlns:mr = "http://iec.ch/TC57/2011/MeterReadings#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<mr:MeterReading>
<mr:isCoincidentTrigger>true</mr:isCoincidentTrigger>
<mr:EndDeviceEvents>
<mr:createdDateTime>2010-12-17T09:30:47Z</mr:createdDateTime>
<mr:reason>moveOut</mr:reason>
<mr:EndDeviceEventType ref = "3.31.0.68"/>
<!--ElectricityMeter RCDSwitch Disconnected -->
</mr:EndDeviceEvents>
<mr:Meter>
<mr:Names>
<mr:name>Meter1</mr:name>
</mr:Names>
</mr:Meter>
</mr:MeterReading>
<mr:MeterReading>
<mr:Meter>
<mr:Names>
<mr:name>Meter1</mr:name>
</mr:Names>
</mr:Meter>
<mr:Readings>
<mr:timeStamp>2010-12-17T09:30:49Z</mr:timeStamp>
<mr:value>123456</mr:value>
<mr:ReadingType ref = "0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0"/>
<!--billingQuantity net electricitySecondaryMetered energy (kWh)-->
</mr:Readings>
</mr:MeterReading>
</mr:MeterReadings>

Le prochain exemple montre une demande d'obtention de relevés de compteur à partir d'un
système de comptage ou MDMS qui sont coïncidents avec un débranchement survenu dans
un intervalle de temps précis. La demande est une invitation ouverte à envoyer tout type de
données MeterReading coïncidents avec un RCDSwitch Disconnect pour un EndDevice
donné (compteur). La réponse à cette demande pourrait parfaitement n'être rien de plus que
l'exemple de "relevé de compteur final" fourni ci-dessus. (Si une réponse plus spécifique était
souhaitée, il serait possible de filtrer uniquement le(s) ReadingType(s) désiré(s) en
remplissant l'élément ReadingType dans le profil GetMeterReadings.)

<mr:GetMeterReadings
xsi:schemaLocation="http://iec.ch/TC57/2011/GetMeterReadings#GetMeterReadings.xsd"
xmlns:m="http://iec.ch/TC57/2011/GetMeterReadings#"
61968-9  CEI:2013 – 503 –

xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
<mr:EndDevice>
<mr:Names>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<mr:name>Meter1</mr:name>
</mr:Names>
</mr:EndDevice>
<mr:MeterReadings>
<mr:isCoincidentTrigger>true</mr:isCoincidentTrigger>
<mr:EndDeviceEvents>
<mr:EndDeviceEventType>
<mr:Names>
<mr:name>3.31.0.68</mr:name>
<!--ElectricityMeter RCDSwitch Disconnected -->
</mr:Names>
</mr:EndDeviceEventType>
</mr:EndDeviceEvents>
</mr:MeterReadings>
<mr:TimeSchedule>
<mr:scheduleInterval>
<mr:end>2010-12-31T23:59:59Z</mr:end>
<mr:start>2010-12-01T00:00:00Z</mr:start>
</mr:scheduleInterval>
</mr:TimeSchedule>
</mr:GetMeterReadings>

NOTE Lors de l'utilisation des horodatages comme filtres, les éléments TimeSchedule.scheduleInterval sont
utilisés pour concevoir une demande de données s'inscrivant dans une certaine plage. La réponse MeterReadings
peut remplir les éléments MeterReadings.MeterReading.valuesInterval afin d'identifier la plage de dates proposée
dans la réponse. L'utilisateur trouvera également que les données d'intervalle (qui contiennent une série de
valeurs chronologiques) n'ont pas leur place dans une discussion traitant des données coïncidentes . Un seul
intervalle peut être coïncident avec un événement donné ou un autre MeterReading. Par conséquent, il paraît
inapproprié de remplir une série d'éléments MeterReading.IntervalBlocks.IntervalReadings. Une seule valeur peut
être présentée en tant qu'intervalle, ou bien l'unique valeur d'intervalle peut être présentée en tant que
MeterReading.Readings autonome.

L'aptitude à planifier lors de l'obtention des relevés de compteur est donnée par le biais de
l'utilisation d'une demande MeterReadSchedule. Ce qui suit est la structure utilisée pour la
charge utile d'un message de demande MeterReadSchedule:
– 504 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 27 – Format de message pour le relevé de compteur

Plusieurs éléments dans le TimeSchedule du profil MeterReadSchedule sont uniques pour ce


profil et méritent une définition spéciale. Notamment:

disabled – True (c'est-à-dire vrai) si ce programme est désactivé.

offset – Le décalage correspondant aux heures (périodiques) récurrentes dans le


TimeSchedule. Chaque instant dans la série chronologique définie par scheduledInterval, et
recurrencePeriod ou recurrencePattern sera décalé en ajoutant la valeur de décalage.
L'utilisation de TimeSchedule.offset n'est pas applicable lorsque les TimePoints discrets sont
spécifiés en lieu et place d'un recurrencePeriod ou recurrencePattern.

recurrencePattern – Intervalle auquel l'action programmée se répète, du début d'une action


au début de l'action suivante (par exemple, premier lundi de chaque mois, dernier jour du
mois, etc.). Utilisé lorsque l'intervalle ne peut pas être défini comme un nombre de secondes
fixe entre différents instants. L'utilisation de recurrencePattern n'est pas applicable lorsque
recurrencePeriod est spécifié ou lorsque les TimePoints discrets sont spécifiés en lieu et
place d'un recurrencePeriod ou d'un recurrencePattern.
61968-9  CEI:2013 – 505 –

recurrencePeriod – Durée entre les instants, du début d'une action au début de l'action
suivante. Utilisé lorsque l'intervalle peut être défini comme un nombre de secondes fixe entre
différents instants. L'utilisation de recurrencePeriod n'est pas applicable lorsque
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

recurrencePattern est spécifié ou lorsque les TimePoints discrets sont spécifiés en lieu et
place d'un recurrencePeriod ou d'un RecurrencePattern.

5.4 Messages de commande de dispositif terminal

5.4.1 Généralités

Il existe de nombreux types de messages de commande de dispositifs terminaux. Ils sont


utilisés pour envoyer des instructions à un ou plusieurs dispositifs terminaux.
EndDeviceControls peut produire un ou plusieurs messages EndDeviceEvent consécutifs.

5.4.2 Applications

5.4.2.1 Régulation de la charge

Les demandes de régulation de la charge (également appelé régulation directe de la charge)


peuvent souvent être faites à un MS à des fins de restriction des charges. Cette demande
serait typiquement lancée à partir de l'exploitation du réseau. Tous les MS n'auront pas les
fonctionnalités de régulation de la charge.

Il convient aussi de noter que cela diffère d'un débranchement, le débranchement donnant
lieu à la perte complète de puissance pour un seul client.

Une régulation de charge se traduira typiquement par le délestage de charges spécifiquement


configurées (par exemple, climatisation, pompes, etc.).

La fonction de régulation de la charge exécute des commandes de délestage de charge qui


sont calculées par le logiciel de gestion de charge (contenu dans le bloc d'exploitation du
réseau). Le logiciel de gestion de charge est utilisé pour calculer la quantité de charge
délestée et pourrait potentiellement inclure de nombreux facteurs, notamment la durée prévue
des déficits de production, les modèles d'utilisation historique, les données d'utilisation temps
réel, et les conditions météorologiques.
– 506 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Perform load control Accomplir la régulation de la charge

Figure 28 – Exemple d'échange de message de régulation de charge

L'exemple à la Figure 28 montre comment un historique de charge peut être obtenu de la


MDM sous la forme de MeterReadings et utilisé pour réaliser une analyse de charge. Il
montre également des commandes de régulation de charge émises par le LMS vers le
système de régulation de charge. Par contre, les déploiements qui ne prennent pas en charge
une MDM interagiraient directement avec le MS.

Les commandes de régulation de charge sont mises en œuvre comme un type de


EndDeviceControl, où la commande peut être traitée par EndDeviceGroup (en utilisant une
adresse de groupe), par EndDevice (en utilisant le mRID) ou par CustomerAgreement.

La régulation de la charge peut également être mise en place à l'aide des appareils PAN.

5.4.2.2 Installation d'un appareil de régulation de charge

L'installation d'unités de régulation de charge utilise habituellement plus de main-d'œuvre que


l'installation d'un compteur, mais les exigences relatives à l'échange de données sont plus
simples. Les unités LC diffèrent des compteurs en ce sens qu'elles ne nécessitent pas de
réétalonnage périodique. Une fois installée, l'unité LC restera probablement en place pendant
toute sa durée de vie, même si le client se retire du programme LC ou s'il y a changement de
locataire.
61968-9  CEI:2013 – 507 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Install load control unit Installer l'unité de régulation de la charge
Configure new LC unit for site specifics and Configurer la nouvelle unité de LC par rapport aux
record configuration data spécifications du site et enregistrer les données de
configuration

Figure 29 – Exemple d'échange de message pour l'installation de l'unité de LC

Avant de se rendre à l'emplacement du service, la personne chargée de l'installation


connaîtra les données du compte client, le type d'unité de régulation de charge à installer et
les caractéristiques assignées de l'appareil à commander. Les données d'installation peuvent
confirmer les caractéristiques nominales de l'appareil et, lorsque cela est approprié,
documenter le numéro de port de l'unité LC raccordée à l'appareil. Les résultats de
l'installation peuvent être publiés à l'attention de toutes les parties prenantes comme illustré
à la Figure 29.

5.4.2.3 Changement de programme client

Des solutions de comptage particulières sont habituellement choisies pour satisfaire à des
besoins de comptage spécifiques par suite de l'inscription des programmes client. Dans un
grand nombre de cas, une solution de comptage flexible peut assurer un traitement pour une
gamme de programmes client. Lorsqu'un client passe d'inscriptions à un certain programme
à un autre, cela peut simplement demander un changement de configuration du compteur (ou
du module de communication). Dans les cas extrêmes, cela peut exiger un remplacement du
compteur. Dans d'autres cas, cela peut ne pas exiger de changement du tout. Il sera
nécessaire de communiquer parmi les parties prenantes les modifications apportées à une
configuration. Un exemple d'échange dans lequel le déploiement implique une MDM est décrit
à la Figure 30. Un autre exemple dans lequel le déploiement manque d'une MDM est décrit
à la Figure 31.
– 508 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Request for program change Demande de changement de programme
read meter relever le compteur
reconfigure meter reconfigurer le compteur

Figure 30 – Exemple d'échange de message en vue de changer le programme client

Les modifications apportées à la configuration du compteur peuvent être exprimées comme


étant des modifications de la configuration d'un EndDevice.
61968-9  CEI:2013 – 509 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Request for program change Demande de changement de programme
read meter relever le compteur
reconfigure meter reconfigurer le compteur

Figure 31 – Exemple d'échange de message en vue de changer


le programme client sans la MDM

Dans d'autres cas, un changement du programme client pourrait ne pas être pris en charge
par une reconfiguration de compteur. Le changement du programme peut nécessiter un
remplacement du compteur (se référer à 5.5 pour plus d'informations sur les remplacements
de compteur.) Les remplacements de compteur impliquent un flux de travail différent de celui
des reconfigurations de compteur. Cela sera reflété dans l'échange de messages entre les
systèmes. Un exemple d'échange est illustré à la Figure 32.
– 510 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Request for program change Demande de changement de programme
exchange meter in field échange compteur dans champ

Figure 32 – Exemple de changement du programme client


avec un remplacement du compteur

Voir 5.6.2 sur la pose et dépose de compteur pour des détails complémentaires concernant le
message MeterServiceRequest.

5.4.2.4 Débranchement et rebranchement de compteur

Pour diverses raisons, telles que non-paiement, il peut être nécessaire de débrancher ou
rebrancher un client. Lorsqu'il est débranché, il convient que l'usage enregistré soit de zéro et
il convient d'ignorer les plaintes relatives aux coupures de courant. Lorsqu'il n'est pas
possible d'effectuer un débranchement ou un rebranchement à distance au moyen d'un MS,
une demande de service de compteur sera typiquement produite pour effectuer manuellement
le débranchement ou le rebranchement. Des exemples d'échanges de messages pour une
exploitation à distance sont illustrés à la Figure 33 et à la Figure 34.
61968-9  CEI:2013 – 511 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
perform remote disconnect effectuer un débranchement à distance
read meter relever le compteur

Figure 33 – Exemple d'échange de messages


pour le branchement/débranchement de compteur
– 512 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Sense position and voltage capter la position et la tension
perform remote connect / disconnect effectuer un branchement / débranchement à
distance
read meter relever le compteur

Figure 34 – Exemple de branchement/débranchement à distance entre le CIS et le MS

5.4.2.5 Tarification en temps réel

Les signaux et/ou bordereaux de prix peuvent être envoyés à un dispositif terminal via le MS.
Cela peut se faire de plusieurs façons, telles que:

• signal de prix émis en temps réel identifiant un prix pour une durée déterminée
• programmes selon le temps d'utilisation (TOU, time of use) publiés, qui entraînent des
changements dans l'accumulation pour chaque étage de TOU
• programmes de prix de l'énergie publiés à l'avance.
61968-9  CEI:2013 – 513 –

Souvent, l'EndDeviceGroup peut être utilisé pour différencier des compteurs avec des
contrats ou des tarifs différents.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

L'exemple de la Figure 35 montre un signal de prix envoyé vers le MS à partir de l'exploitation


du réseau. Le MS agit alors comme un fournisseur de service réseau pour communiquer le
prix en temps réel aux compteurs et autres équipements.

Légende
Anglais Français
price signal sent to PAN device signal de prix envoyé à l'appareil PAN

Figure 35 – Exemple d'échange de message pour le signal de prix en temps réel

Les signaux de prix sont mis en œuvre comme un sous-type d'EndDeviceControl, où le prix
est un paramètre de message.

5.4.3 Format des messages

5.4.3.1 Généralités

La Figure 36 décrit la structure d'un message EndDeviceControls message. Le schéma XML


du message EndDeviceControls est défini à l'Annexe H.
– 514 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 36 – Format des messages de commandes de dispositif terminal

Dans la structure de charge utile de message, des compteurs spécifiques peuvent être
adressés par EndDevice (par exemple, compteur), EndDeviceGroup, UsagePoint et/ou
UsagePointGroup. A part une adresse au moins, le seul élément requis est
l'EndDeviceControlType, qui identifie le type de commande à exécuter. Les exemples des
différents types de commandes qui pourraient être utilisés comprennent (mais de manière non
exhaustive):

• signal de commande de charge


• signal ou bordereau de prix
• débranchement à distance
• rebranchement à distance
• réinitialisation de la demande
61968-9  CEI:2013 – 515 –

• signal de réduction de demande


• envoyer un message textuel à un appareil PAN
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

• envoyer des signaux de prix vers un appareil PAN


• envoyer des événements de régulation de charge / réponse à la demande à un
appareil PAN

Les paragraphes 5.4.3.2 à 5.4.3.5 sont des exemples XML représentatifs des
EndDeviceControls.

5.4.3.2 Exemple d'une charge utile de réinitialisation de demandes

Ce qui suit est un exemple de réinitialisation de demandes. A noter que dans le présent
exemple, deux appareils sont adressés et chacun est dans son propre élément EndDevices.
L'un d'eux est adressé par mrID et l'autre est adressé par Names.
<?xml version="1.0" encoding="UTF-8"?>
<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:m = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:EndDeviceControlType ref = "3.8.0.214"/>
<m:EndDevices>
<m:mRID>3dc53ee5-777e-50b4-8699-a1c224f45f3d</m:mRID>
</m:EndDevices>
<m:EndDevices>
<m:Names>
<m:name>MeterABC</m:name>
<m:NameType>
<m:name>MeterID</m:name>
</m:NameType>
</m:Names>
</m:EndDevices>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.4.3.3 Exemple de débranchement de compteur par groupe

Ce qui suit est un exemple de débranchement de compteur par groupe.

<?xml version="1.0" encoding="UTF-8"?>


<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:m = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:EndDeviceControlType ref = "3.31.0.23"/>
<m:EndDeviceGroups>
<m:mRID>3dc53ee5-777e-50b4-8699-a1c224f45f3d</m:mRID>
</m:EndDeviceGroups>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.4.3.4 Exemple de débranchement programmé par groupe

Ce qui suit est un exemple de débranchement programmé par groupe.


<?xml version="1.0" encoding="UTF-8"?>
<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:m = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:EndDeviceControlType ref = "3.31.0.23"/>
<m:EndDeviceGroups>
<m:Names>
<m:name>Disconnects in Region 123, May 2011</m:name>
<m:NameType>
– 516 – 61968-9  CEI:2013

<m:name>Regional Disconnect Group</m:name>


<m:NameTypeAuthority>
<m:name>Utility ABC</m:name>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:EndDeviceGroups>
<m:primaryDeviceTiming>
<m:interval>
<m:start>2001-12-17T09:30:47Z</m:start>
</m:interval>
</m:primaryDeviceTiming>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.4.3.5 Exemple de branchement de compteur par Nom

Ce qui suit est un exemple de branchement de compteur, où le compteur est spécifié par
nom.

<?xml version="1.0" encoding="UTF-8"?>


<!--Connect Meters by Meter Name-->
<m:EndDeviceControls
xsi:schemaLocation = "http://iec.ch/TC57/2011/EndDeviceControls# EndDeviceControls.xsd"
xmlns:obj = "http://iec.ch/TC57/2011/EndDeviceControls#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:EndDeviceControl>
<m:mRID>76e7a0a3-3e33-4d21-b78f-b42227823ec7</m:mRID>
<m:issuerID>External System 1</m:issuerID>
<m:issuerTrackingID>123</m:issuerTrackingID>
<m:EndDeviceControlType ref = "3.31.0.18"/>
<m:EndDevices>
<m:mRID>45e7a0a3-3e99-4d17-b43f-b67221212ec0</m:mRID>
<m:Names>
<m:name>Meter 123</m:name>
<m:NameType>
<m:name>Meter Name</m:name>
<m:NameTypeAuthority>
<m:name>Utility ABC</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:EndDevices>
<m:EndDevices>
<m:mRID>09e7a0a3-3e50-4d10-b40f-b40980088ec3</m:mRID>
<m:Names>
<m:name>Meter 456</m:name>
<m:NameType>
<m:name>Meter Name</m:name>
<m:NameTypeAuthority>
<m:name>Utility ABC</m:name>
</m:NameTypeAuthority>
</m:NameType>
</m:Names>
</m:EndDevices>
<m:primaryDeviceTiming>
<m:interval>
<m:start>2011-06-17T09:30:47.0Z</m:start>
</m:interval>
</m:primaryDeviceTiming>
</m:EndDeviceControl>
</m:EndDeviceControls>

5.5 Demande de services de compteur

5.5.1 Généralités

Les demandes de services de compteur sont une sous-classe de Work, où un EndDevice est
impliqué.
61968-9  CEI:2013 – 517 –

5.5.2 Applications

5.5.2.1 Pose et dépose de compteur


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Il peut être nécessaire de poser, déposer ou configurer des compteurs suite


à l'enregistrement d'un nouveau client, au retrait d'un client ou du passage d'un client d'un
fournisseur à un autre. Il peut aussi y avoir la nécessité de remplacer un compteur qui
implique la dépose de l'ancien compteur, la pose du nouveau compteur et la configuration du
nouveau compteur dont a besoin le système de comptage.

Avant l'installation du compteur, des abonnements ont été établis entre le MS et la MDM pour
recevoir des mises à jour des données client (pour plus de détails, voir 5.10 sur la gestion
des données de référence). Le flux de travaux pour le remplacement d'un compteur est
montré à la Figure 37. Cela englobe les processus de pose de compteur et de dépose de
compteur.

Les étapes OperationSet sont incluses pour synchroniser les Master Data révisées (les
données de configuration des compteurs neufs et anciens et les changements d'association
avec l'UsagePoint) avec le système MDM et le système de comptage. Voir 5.10 et les
Annexes K et L pour obtenir des informations complémentaires relatives à la gestion de
données de référence.
– 518 – 61968-9  CEI:2013

Légende

Anglais Français
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

MeterTechnician Technicien en compteur


read old meter relever l'ancien compteur
replace old meter with new meter remplacer l'ancien compteur par le nouveau compteur
Send work order to technician Envoyer un ordre d'exécution au technicien
Technician reports meter exchange details Le technicien fait un rapport avec les détails d'échange
du compteur
Read new meter Relever le nouveau compteur

Figure 37 – Exemple d'échange de messages de pose et dépose de compteur

Le relevé initial du nouveau compteur et le relevé final de l'ancien compteur sont du type
MeterReading. MeterReading contient "UsagePoint" qui est nécessaire (en plus de
ServiceLocation) pour aider à identifier l'emplacement des nouveaux et anciens compteurs.

5.5.2.2 Compteur remplacé en raison d'un événement de dispositif terminal

Des EndDeviceEvents (tels que décrits en 5.2) peuvent entraîner une évaluation débouchant
sur une demande de remplacement de compteur. Les événements du compteur peuvent être
publiés à partir de MS ou MDM. La Figure 38 décrit un exemple d'échange où la MDM a
identifié un problème et l'a porté à l'attention du WMS qui décide de remplacer le compteur.

De nouveau, les étapes OperationSet sont incluses pour synchroniser les Master Data
révisées (les données de configuration des compteurs neufs et anciens et les changements
d'association avec l'UsagePoint) avec le système MDM et le système de comptage. Voir 5.10
et les Annexes K et L pour obtenir des informations complémentaires relatives à la gestion de
données de référence.
61968-9  CEI:2013 – 519 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
MeterTechnician Technicien en compteur
read old meter relever l'ancien compteur
replace old meter with new meter replacer l'ancien compteur par le nouveau compteur
Send work order to technician Envoyer un ordre d'exécution au technicien
Technician reports meter exchange details Le technicien fait un rapport avec les détails
d'échange du compteur
Read new meter Relever le nouveau compteur

Figure 38 – Exemple d'échange de messages d'événement de dispositif terminal


en raison d'un changement de compteur

5.5.2.3 Compteur remplacé suite à des alarmes du CIS ou à des plaintes de client

L'analyse de données effectuée par le CIS ou les plaintes de client relatives à la facturation
peuvent amener le département service clientèle à demander une visite sur site à
l'emplacement du client et un possible remplacement du compteur. La Figure 39 décrit un
exemple d'échange où le CIS a identifié un problème et l'a porté à l'attention du WMS qui
décide de remplacer le compteur.
– 520 – 61968-9  CEI:2013

De nouveau, les étapes OperationSet sont incluses pour synchroniser les Master Data
révisées (les données de configuration des compteurs neufs et anciens et les changements
d'association avec l'UsagePoint) avec le système MDM et le système de comptage. Voir 5.10
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

et les Annexes K et L pour obtenir des informations complémentaires relatives à la gestion de


données de référence.

Légende

Anglais Français
MeterTechnician Technicien compteur
read old meter relever l'ancien compteur
replace old meter with new meter remplacer l'ancien compteur par le nouveau compteur
Send work order to technician Envoyer un ordre d'exécution au technicien
Technician reports meter exchange details Le technicien fait un rapport avec les détails
d'échange du compteur
Read new meter Relever le nouveau compteur

Figure 39 – Exemple d'échange de messages suite à des alarmes du CIS


61968-9  CEI:2013 – 521 –

5.5.2.4 Remplacement de compteur pour réétalonnage

Le WMS ou d'autres systèmes d'entreprise tels que le système AM peut suivre le moment où
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

le réétalonnage du compteur est échu et remplacer le compteur. Certaines entreprises de


distribution peuvent considérer le remplacement réel du compteur comme étant un problème
relevant du WMS comme illustré à la Figure 40, alors que d'autres le traitent comme un
problème relevant du MS.

Légende

Anglais Français
MeterTechnician Technicien compteur
Meter calibration due Etalonnage du compteur échu
read old meter relever l'ancien compteur
replace old meter with new meter remplacer l'ancien compteur par le nouveau compteur
Send work order to technician Envoyer un ordre d'exécution au technicien
Technician reports meter exchange details Le technicien fait un rapport avec les détails
d'échange du compteur
Read new meter Relever le nouveau compteur

Figure 40 – Exemple d'échange de message lorsque


le compteur est remplacé pour réétalonnage
– 522 – 61968-9  CEI:2013

Les étapes OperationSet sont incluses pour synchroniser les Master Data révisées (les
données de configuration des compteurs neufs et anciens et les changements d'association
avec l'UsagePoint) avec le système MDM et le système de comptage. Voir 5.10 et les
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Annexes K et L pour obtenir des informations complémentaires relatives à la gestion de


données de référence.

5.5.3 Format des messages

La structure de charge utile de message ci-après décrit les MeterServiceRequests. Elle peut
être utilisée pour zéro, un ou plusieurs objets MeterServiceWork.

Figure 41 – Format de message de demandes de service de compteur

Le message peut inclure plus d'un élément MeterServiceWork. Chaque élément peut se
référer à deux compteurs au maximum pour fournir le moyen de remplacer un compteur. Des
relevés de compteur peuvent être obtenus comme partie du travail. Dans le cas du
remplacement d'un compteur, des relevés de l'ancien compteur peuvent être obtenus ainsi
que des relevés initiaux pour le nouveau compteur. Les références des emplacements
peuvent être fournies comme partie des données client ou pour le bien compteur, selon le
travail en cours. Le schéma XML annoté détaillé est défini à l'Annexe I.
61968-9  CEI:2013 – 523 –

5.6 Evénements relatifs au système de comptage

5.6.1 Généralités
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Il y existe des niveaux différents de besoin dans un système pour des différentes sortes de
messages.

Le système de comptage (en soi) peut présenter des problèmes au sein de son infrastructure
qui nécessitent un ordre d'exécution pour être réglés. Les exigences relatives aux données
pour communiquer cet événement sont similaires aux exigences d'EndDeviceEvent comme
décrit en 5.2. Avec un EndDeviceEvent, un simple code d'erreur peut être utilisé pour
rapporter un problème. Ce mécanisme fonctionne lorsque le destinataire est capable de
consulter et interpréter la signification du code. Cependant, lorsqu'une description plus
détaillée du problème est à fournir, un schéma plus élaboré doit être utilisé. Dans certains
cas, le destinataire est un être humain et exige une description lisible par l'homme du
problème et de la pièce particulière d'équipement impliquée. Lors de l'identification du bien, il
sera probablement nécessaire d'utiliser une terminologie spécifique au fournisseur pour
décrire le matériel.

5.6.2 Applications – Mise à niveau du firmware (microprogramme)

Pour un système de comptage automatisé capable de communication bidirectionnelle, il peut


être possible de mettre à niveau le firmware de l'infrastructure de MS sur le terrain ou, dans
certains systèmes, les biens de communication dans les dispositifs terminaux. Les
modifications apportées au système de comptage qui altèrent matériellement son
fonctionnement doivent être communiquées à toutes les parties prenantes concernées. Un
exemple de ladite publication obtenue à l'aide d'un message EndDeviceConfig est illustré à la
Figure 42.

Légende

Anglais Français
firmware upgrade occurs mise à niveau du firmware (microprogramme)

Figure 42 – Exemple d'échange de message de mise à niveau du firmware

La mise à niveau du firmware peut amener l'EndDevice ou le CommEquipmentAsset


à changer de plusieurs façons, y compris les caractéristiques fonctionnelles de l'appareil, la
version du firmware et le numéro de révision, ou la configuration (exprimée comme un
programId).
– 524 – 61968-9  CEI:2013

5.6.3 Format des messages

Se reporter au format des messages EndDeviceConfig décrit en 5.10.3.


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.7 Commutation clientèle

5.7.1 Généralités

Un client dans un marché ouvert de vente au détail peut commuter entre des fournisseurs
d'énergie. Cela peut exiger une reconfiguration et/ou une réinstallation du compteur. La
reconfiguration ou le remplacement du compteur peut être une conséquence du fait qu'un
client change de programmes d'énergie au moment du changement de fournisseur d'énergie.
Ce processus impliquerait vraisemblablement un relevé sur demande selon les besoins à des
fins de facturation finale. Un exemple d'échange de message est donné ci-dessous à la
Figure 43.

Les étapes OperationSet sont incluses pour synchroniser les Master Data révisées (les
données de configuration des revendeurs neufs et anciens et les changements d'association
avec Customer, CustomerAccount et CustomerAgreement) avec le système MDM et le
système de comptage. Voir 5.10 et les Annexes K et L pour obtenir des informations
complémentaires relatives à la gestion de données de référence.

Légende

Anglais Français
perform meter operation exécuter l'opération sur le compteur
customer selects new retailer le client sélectionne un nouveau revendeur

Figure 43 – Exemple d'échange de message de commutation clientèle

5.7.2 Format des messages

La structure d'une MeterServiceRequest a été décrite par la Figure 41. La structure d'un
message MeterReading a été décrite par la Figure 19.
61968-9  CEI:2013 – 525 –

5.8 Messages de service de comptage de paiement

5.8.1 Généralités
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les services de comptage de paiement impliquent typiquement des compteurs de


prépaiement installés dans les locaux du client et des systèmes de vente de jetons situés en
des emplacements commodes pour servir les besoins des clients. Pour les besoins de la
présente norme, les systèmes de vente sont considérés comme une partie intégrante du
système de comptage. Ces systèmes de vente exigent typiquement des informations
concernant le compteur, le client, l'emplacement du service, le point d'usage, le tarif, le
compte client, l'accord client et le fournisseur du service qui reçoit la recette collectée par les
systèmes de vente.

Les informations requises par les systèmes de vente ont leur origine dans le CIS et dans le
système de facturation et sont ensuite transférées vers les systèmes de vente au moyen des
messages donnés en 5.8.3.

Les informations de transaction et d'acquit d'autre part ont leur origine dans les systèmes de
vente lorsque le client effectue un paiement sur un compte ou achète un jeton prépayé à un
point de vente. Il est nécessaire de transférer périodiquement ces informations vers le CIS et
le système de facturation en vue d'un traitement ultérieur et les messages en 5.8.4 sont
fournis à cet effet.

Dans la CEI 61968-9:2009, plusieurs profils étaient développés comme élément des efforts de
prise en charge du comptage de paiement, dont certains étaient de nature plus générale.
Dans la présente édition, ces profils sont conservés dans la présent paragraphe 5.8 et sont
précédés du préfixe "PrePay". On espère que ceux-ci seront complètement harmonisés dans
les futures éditions de la CEI 61968-9.

5.8.2 Accords auxiliaires

Les informations relatives à la dette client pour collecte peuvent être configurées dans le MS
au moyen de la charge utile de message AuxilaryAgreementConfig.

Un exemple d'un échange de message est donné à la Figure 44 et le format de message est
donné à la Figure 65.

Figure 44 – Echange de messages pour transférer


des informations relatives aux accords auxiliaires
– 526 – 61968-9  CEI:2013

5.8.3 Applications

5.8.3.1 Généralités
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Lorsqu'un client achète un jeton prépayé à un point de vente ou effectue un paiement sur un
compte facturé, des informations financières sont créées dans le MS en rapport avec cette
transaction. Typiquement, ces informations sont transférées périodiquement au CIS et au
système de facturation en vue d'un traitement ultérieur.

Les messages définis en 5.8.4 constituent une disposition permettant de transférer ces
informations vers le CIS et le système de facturation.

5.8.3.2 Acquits

Lorsque le MS reçoit un paiement, un acquit est généré et les informations pertinentes


concernant le paiement sont typiquement enregistrées comme enregistrement d'acquit. Ces
informations peuvent être accessibles au moyen de la charge utile de message
ReceiptRecord.

Lorsqu'une plage spécifiée (par date ou mRID) de la charge utile de message est à spécifier
dans une implémentation contextuelle particulière, cela peut être réalisé par l'utilisation des
éléments facultatifs dans l'en-tête de message (voir Figure B.2).

Un exemple d'un échange de message est donné à la Figure 45 et le format de message est
donné à la Figure 48.

Légende

Anglais Français
execute exécuter

Figure 45 – Echange de messages pour transférer des informations d'acquit

5.8.3.3 Transactions

Les informations relatives à la vente d'un jeton prépayé ou à l'acquit d'un paiement de compte
sont typiquement également enregistrées par le MS sous la forme d'un enregistrement de
transactions financières saisissant les détails pertinents relatifs à la transaction particulière.
Ces informations peuvent être accessibles au moyen de la charge utile de message
TransactionRecord.
61968-9  CEI:2013 – 527 –

Un exemple d'un échange de message est donné à la Figure 46 et le format de message est
donné à la Figure 49.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 46 – Echange de messages pour transférer des informations de transaction

5.8.4 Format des messages

Le diagramme de la Figure 47 décrit la structure des messages utilisée pour configurer les
accords auxiliaires.
– 528 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 47 – Format de message de configuration des accords auxiliaires

La structure de message de la Figure 48 est utilisée pour enregistrer les acquits.


61968-9  CEI:2013 – 529 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 48 – Format de message ReceiptRecord

La structure de message dans la Figure 49 est utilisée pour enregistrer les transactions.
– 530 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 49 – Format de message TransactionRecord

5.9 Réseaux dans un local (Premise area networks)

5.9.1 Généralités

Le système de comptage a été étendu afin d'inclure les appareils qui ont été déployés dans
les foyers et les entreprises gérées par l'infrastructure de comptage. Dans la CEI 61968-9,
ces appareils existent au sein d'un réseau dans un local (PAN). Cela comprend le terme
fréquemment utilisé de réseau domestique (HAN). Les appareils PAN/HAN eux-mêmes sont
un type spécial d'EndDevice.

Compte tenu de la nature évolutive des appareils sous-jacents et des protocoles de


communication, la CEI 61968-9 tente d'adopter une vision qui peut être mise en
correspondance selon les besoins avec diverses normes relatives aux appareils.
61968-9  CEI:2013 – 531 –

5.9.2 Applications

5.9.2.1 Généralités
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les applications des appareils PAN incluent principalement la tarification dynamique, la


réponse à la demande et l'apport d'informations aux clients. Il existe plusieurs types
d'appareils PAN, notamment les thermostats intelligents, les affichages domestiques, les
relais, etc.

5.9.2.2 Pairage et suppression du pairage d'un appareil PAN

Le pairage d'un appareil PAN avec un compteur est à effectuer avant que le système de
comptage ne puisse envoyer des commandes à l'appareil PAN.

Le pairage de l'appareil PAN (et la suppression du pairage) est réalisé avec un message
EndDeviceControls comme le montre l’exemple dans la Figure 50. Les conventions spéciales
ci-après relatives au message EndDeviceControl s'appliquent au pairage d'un appareil PAN
avec un compteur:

• Il convient de sélectionner le code EndDeviceControlType approprié dans le cadre du


pairage d'un appareil PAN à l'Annexe F.
• Deux (et seulement deux) EndDevices sont identifiés par mRid ou la classe Names;
l'un est le compteur et l'autre est l'appareil PAN. L'isPan booléen sera défini sur vrai
pour l'appareil PAN; le code d'installation et electronicAddress.macAddress sont
normalement également requis.
• Les résultats de réussite ou d'échec de l'opération de pairage sont rapportés à l'aide
des messages EndDeviceEvents, avec les énumérations EndDeviceEventType
appropriées disponibles dans le Tableau E.24 de l'Annexe E. Il est possible qu’un
EndDeviceEvent ou plus soient rapportés suite à l'application de EndDeviceControl.
– 532 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
AMI commissions PAN network AMI mandate le réseau PAN
AMI carries out pairing operation with HAN AMI exécute l'opération d'appariement avec
device l'appareil HAN

Figure 50 – Pairage d'un appareil PAN

5.9.2.3 Evénements PAN

Les événements de l'appareil PAN sont générés par un appareil PAN et sont généralement
communiqués par le biais d'un compteur ou d'une passerelle vers la tête de réseau du
système de comptage. La tête de réseau du système de comptage publiera ensuite le
message vers d'autres applications d'entreprise qui se sont abonnées. Ces événements sont
transmis à l'aide du message EndDeviceEvents. Un exemple est donné par la Figure 51.
61968-9  CEI:2013 – 533 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
PAN device appareil PAN
PAN device detects event L'appareil PAN détecte l'événement
PAN device notifies AMI of event L'appareil PAN prévient AMI de l'événement

Figure 51 – Evénements de l'appareil PAN

5.9.2.4 Commandes PAN

Les commandes supplémentaires de l'appareil PAN à d'autres fins que le pairage peuvent
être lancées par une application d'entreprise telle qu'un système de gestion de réponse à la
demande vers une tête de réseau du système de comptage. Ces commandes ont également
recours au message EndDeviceControls. Etant donné qu'il existe diverses manières
d'adresser la commande, il peut y avoir plusieurs appareils PAN cible. Un exemple est donné
par la Figure 52.

Les messages EndDeviceControls prévus pour les appareils PAN comprendront en général
l'une des structures spéciales ci-après au sein du profil EndDeviceControl:

PanDemandResponse
PanDisplay
PanPricing

Les énumérations appropriées EndDeviceControlType et EndDeviceEventType desdites


fonctions peuvent être trouvées dans les Tableaux E.24 et F.3.
– 534 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
PAN device Appareil PAN
AMI sends command to PAN device AMI envoie la commande à l'appareil PAN
PAN device executes command L'appareil PAN exécute la commande
PAN device notifies AMI of successful command L'appareil PAN prévient AMI de la réussite de la
completion commande

Figure 52 – Commandes de l'appareil PAN

5.9.3 Formats des messages

Il n'existe aucun message unique défini spécifiquement pour les appareils PAN. Les appareils
PAN sont simplement des types d'EndDevices.

5.10 Messages de gestion de données de référence

5.10.1 Généralités

Les systèmes d'entreprise qui échangent les messages dans le domaine Relevé de compteur
et Commande requiert un moyen de gérer les données non-transactionnelles qui définissent
les biens, d'autres objets CIM et les relations (ou les associations entre elles). La Gestion de
données de référence (MDM) est le terme utilisé pour décrire la pratique de création, de
changement et de suppression de ces objets et relations.

Aux fins de la CEI 61968-9, les classes CIM qui s'inscrivent dans le domaine d'application de
la Gestion de données de référence et les profils de la CEI 61968-9 utilisés pour
créer/changer/supprimer ces objets (et leur "configuration") sont compris dans le Tableau 5:
61968-9  CEI:2013 – 535 –

Tableau 5 – Profils de configuration de la CEI 61968-9


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Objet CIM Profil de la CEI 61968-9


ComModule ComModuleConfig
Customer CustomerConfig
CustomerAccount CustomerAccountConfig
CustomerAgreement CustomerAgreementConfig
EndDevice EndDeviceConfig
EndDeviceGroup EndDeviceGroups
Meter MeterConfig
PricingStructure PricingStructureConfig
ServiceCategory ServiceCategoryConfig
ServiceLocation ServiceLocationConfig
ServiceSupplier ServiceSupplierConfig
a
TransformerTank
UsagePoint UsagePointConfig
UsagePointGroup UsagePointGroups
UsagePointLocation UsagePointLocationConfig
a Aux fins de la CEI 61968-9, l'objet TransformerTank a une
applicabilité pour les cas d'utilisation qui impliquent
Outage Management. Le TransformerTank est
techniquement hors du domaine d'application de la
CEI 61968-9, et il n'existe aucun profil dans la CEI 61968-
9 concernant la création, la modification ou la suppression
d'un TransformerTank. Néanmoins, le TransformerTank
peut être référencé dans le profil UsagePointConfig afin
d'identifier le transformateur qui alimente l'UsagePoint.

Les ConfigurationEvents surviennent dès qu'une opération de création, de changement ou de


suppression est réalisée en utilisant toute opération "config" à l'aide des profils de la
CEI 61968-9 dans le Tableau 5 ci-dessus et dès qu'une transaction MasterDataLinkageConfig
est exécutée pour gérer les relations des objets MDM ou qu'une transaction
ObjectNamesConfig transaction est exécutée pour ajouter, supprimer ou modifier les
identificateurs de la classe Names de ces objets.

La classe ConfigurationEvent dans le CIM est associée à chaque classe CIM dans la
première colonne du Tableau 5 et est intégrée dans chaque profil de la CEI 61968-9 dans la
colonne 2 de ce tableau. Elle est également incluse dans les profils MasterDataLinkageConfig
et ObjectNamesConfig. La fonction de la classe ConfigurationEvent est de fournir des détails
commerciaux importants concernant chaque opération "config", y compris:

• la date et l'heure auxquelles la configuration ou le changement de configuration a pris


effet ou va prendre effet;
• l'entité accomplissant l'opération de configuration, et
• les remarques sous forme libre fournissant des informations commerciales
supplémentaires relatives à l'événement de configuration.

Se référer aux Annexes K et L pour obtenir les descriptions détaillées des cas d'utilisation de
Gestion de données de référence et des exemples de messages XML qui illustrent l'utilisation
prévue des messages de 5.10.
– 536 – 61968-9  CEI:2013

5.10.2 Applications

5.10.2.1 Généralités
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Aux fins de la présente norme, deux méthodes sont utilisées pour gérer les relations entre les
objets CIM identifiés en 5.10.1. Il s'agit du profil MasterDataLinkage (décrit en 5.10.1) et, pour
un nombre limité d'objets CIM, les relations sont explicitement gérées à l'aide des profils
identifiés en 5.10.1. Le diagramme suivant identifie les relations d'objets qui sont importantes
à la Gestion de données de référence dans le domaine d'application de la présente norme et
la méthode spécifique recommandée à utiliser pour gérer chaque relation.

Légende

Anglais Français
(Distribution Utility) (Entreprise de distribution)
Meter Compteur
Manage via Gérer via
Transformer Tank Cuve de transformateur
(Retailer) (Revendeur)
Customer Client

Figure 53 – Liens de données de référence

Pour parfaitement comprendre la Figure 53, il faut comprendre que la CEI 61968-9 de la
norme fournit des messages normatifs grâce auxquels les systèmes d'entreprise peuvent
échanger des informations; cependant aucune exigence n'existe pour qu'un système donné
mette en œuvre un modèle de données interne basé sur ou cohérent avec le CIM. Par
conséquent, le diagramme ci-dessus présente la possibilité de refléter les relations de
différentes manières. Par exemple, deux systèmes peuvent reconnaître les concepts de
Customer, CustomerAccount et CustomerAgreement et choisir d'exprimer les relations entre
61968-9  CEI:2013 – 537 –

ces entités et un UsagePoint en reliant un Customer à un CustomerAccount (relation Q), puis


en reliant le CustomerAccount au CustomerAgreement (relation R) et enfin en reliant le
CustomerAgreement au UsagePoint (relation H). Dans le présent scénario, le besoin d'utiliser
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

des relations K, L ou U peut ne jamais exister.

D'autre part, il peut y avoir deux systèmes d'entreprise qui ne matérialisent pas le concept
d'un CustomerAgreement dans leurs modèles de données internes. Ces systèmes peuvent
utiliser des messages qui relient un Customer à un CustomerAccount (relation Q), puis qui
relient le CustomerAccount à l’UsagePoint (relation K). Le fait d'être prescriptif à propos des
relations illustrées dans la Figure 53 admissibles ou préférentielles ne relève pas du domaine
d'application de la CEI 61968-9 de la norme. Le profil MasterDataLinkageConfig peut être
utilisé avec souplesse afin de prendre en charge les besoins de toute entreprise et des
systèmes de son entreprise.

Il est recommandé que les relations E, F, I, J, M et V soient gérées par les profils "Config"
indiqués dans la légende de la figure, plutôt que par le biais du profil
MasterDataLinkageConfig; néanmoins, ce n'est pas une exigence et les entreprises peuvent
également choisir d'utiliser le profil MasterDatalinkageConfig pour gérer lesdites relations. La
recommandation concernant la gestion des relations spécifiques par les profils identifiés
plutôt que par le profil MasterDataLinkageConfig a une double raison:

• ces relations spécifiques changent rarement, et


• ces relations spécifiques sont vues par presque tous les systèmes d'entreprise de manière
cohérente.

L'inverse est également vrai. Les entreprises peuvent choisir de gérer les relations illustrées
sous forme de lignes rouges comme si elles étaient illustrées sous forme de lignes noires
sous réserve que la relation soit prise en charge par le CIM et reflétée dans le profil approprié
de la CEI 61968-9.

Il existe un profil supplémentaire dans la CEI 61968-9 appelé CustomerMeterDataSet. Ce


profil est utilisé uniquement avec un verbe d'en-tête Get et la réponse en résultat fournit une
représentation détaillée centrée sur le compteur de toutes les relations dans le diagramme ci-
dessus.

La Figure 53 est informative. Les entités et les relations illustrées à la Figure 53 peuvent
évoluer dans la durée à mesure que la CEI 61968-9 est étendue afin de prendre en charge
les nouveaux cas d'usage professionnel, ainsi que les cas d'usage professionnel révisés.

5.10.2.2 Fournisseurs de service

Les informations concernant le fournisseur (revendeur ou entreprise de distribution par


exemple) du service peuvent être configurées dans le MS au moyen de la charge utile de
message SupplierConfig.

Un exemple d'un échange de message est donné à la Figure 54 et le format de message est
donné en 5.10.3.3.
– 538 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 54 – Echange de messages pour transférer des informations de fournisseur

5.10.2.3 Clients

Les informations relatives aux clients du fournisseur du service peuvent être configurées dans
le MS au moyen de la charge utile de message CustomerConfig.

Un exemple d'un échange de message est donné à la Figure 55 et le format de message est
donné en 5.10.3.4.
61968-9  CEI:2013 – 539 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 55 – Echange de messages pour transférer des informations client

5.10.2.4 Accords client

Les informations relatives aux accords client peuvent être configurées dans le MS au moyen
de la charge utile de message CustomerAgreementConfig.

Un exemple d'un échange de message est donné à la Figure 56 et le format de message est
donné en 5.10.3.5.
– 540 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 56 – Echange de messages pour transférer des informations d'accord client

5.10.2.5 Comptes client

Les informations relatives aux comptes client peuvent être configurées dans le MS au moyen
de la charge utile de message CustomerAccountConfig.

Un exemple d'un échange de message est donné à la Figure 57 et le format de message est
donné en 5.10.3.6.
61968-9  CEI:2013 – 541 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 57 – Echange de messages pour transférer des informations de compte client

5.10.2.6 Catégories de services

Les informations concernant les catégories de services (électricité, eau, gaz par exemple)
peuvent être configurées dans le MS au moyen de la charge utile de message
ServiceCategoryConfig.

Un exemple d'un échange de message est donné à la Figure 58 et le format de message est
donné en 5.10.3.7.
– 542 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 58 – Echange de messages pour transférer


des informations de catégorie de service

5.10.2.7 Points d'usage

Les informations relatives aux points d'usage peuvent être configurées dans le MS au moyen
de la charge utile de message UsagePointConfig.

Un exemple d'un échange de message est donné à la Figure 59 et le format de message est
donné en 5.10.3.8.
61968-9  CEI:2013 – 543 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 59 – Echange de messages pour transférer des informations de point d'usage

5.10.2.8 Compteurs

Les informations relatives aux compteurs en service peuvent être configurées dans le MS au
moyen de la charge utile de message MeterConfig.

Un exemple d'un échange de message est donné à la Figure 60 et le format de message est
donné à la section 5.10.3.11.
– 544 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 60 – Echange de messages pour transférer des informations de compteur

5.10.2.9 Dispositifs terminaux

Les informations relatives aux compteurs en service peuvent être configurées dans le MS au
moyen de la charge utile de message EndDeviceConfig.

Un exemple d'un échange de message est donné à la Figure 61 et le format de message est
donné en 5.10.3.10.
61968-9  CEI:2013 – 545 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 61 – Echange de messages pour transférer


des informations de dispositif terminal

5.10.2.10 Emplacements des services

Les informations relatives aux emplacements de services peuvent être configurées dans le
MS au moyen de la charge utile de message ServiceLocationConfig.

Un exemple d'un échange de message est donné à la Figure 62 et le format de message est
donné en 5.10.2.10.
– 546 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 62 – Echange de messages pour transférer


des informations d'emplacement de service

5.10.2.11 Structure de tarification et barèmes

Les informations relatives aux structures de tarification peuvent être configurées dans le MS
au moyen de la charge utile de message PricingStructureConfig.

Un exemple d'un échange de message est donné à la Figure 63 et le format de message est
donné en 5.10.3.14.
61968-9  CEI:2013 – 547 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
execute exécuter

Figure 63 – Echange de messages pour transférer des structures tarifaires

5.10.3 Format des messages

5.10.3.1 Généralités

Ce paragraphe 5.10.3 décrit les formats des messages des messages


MasterDataLinkageConfig et autres messages "config" Master Data Management. La
spécification détaillée de chaque classe et attribut est disponible dans la CEI 61968-11 et la
CEI 61970-301. Le schéma XML annoté détaillé est défini à l'Annexe H.

5.10.3.2 MasterDataLinkageConfig

La Figure 64 ci-après fournit la structure de haut niveau du message Master Data Linkage
Config utilisé pour configurer les relations entre les objets.
– 548 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 64 – Format de message MasterDataLinkageConfig

Un exemple de MasterDataLinkageConfig est montré ci-dessous. Ce message illustre la


méthode "non-in-line" (pas aligné) d'établissement d'une association entre deux objets CIM;
dans ce cas, entre le compteur et le UsagePoint qui sont associés à l'aide d'une commande
MasterDataLinkageConfig. Il s'agit de la façon normative de représenter l'installation d'un
compteur à un UsagePoint.
<?xml version="1.0" encoding="UTF-8"?>
<m:MasterDataLinkageConfig
61968-9  CEI:2013 – 549 –

xsi:schemaLocation = "http://iec.ch/TC57/2011/MasterDataLinkageConfig#
MasterDataLinkageConfig.xsd"
xmlns:m = "http://iec.ch/TC57/2011/MasterDataLinkageConfig#"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:ConfigurationEvent>
<m:createdDateTime>2011-11-09T19:55:43.699Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
<m:reason>MeterInstallation</m:reason>
</m:ConfigurationEvent>
<m:Meter>
<m:Names>
<m:name>1234LG</m:name>
</m:Names>
</m:Meter>
<m:UsagePoint>
<m:Names>
<m:name>SDP1234E001001</m:name>
</m:Names>
</m:UsagePoint>
</m:MasterDataLinkageConfig>

5.10.3.3 SupplierConfig

La structure de message dans la Figure 65 permet de configurer les fournisseurs de service,


et se substitue au message SupplierConfig défini dans la CEI 61968-9 :2009.

Figure 65 – Format de message de configuration des fournisseurs de service

5.10.3.4 CustomerConfig

La structure de message dans la Figure 66 ci-après est utilisée pour configurer les clients.
– 550 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 66 – Message de configuration client

5.10.3.5 CustomerAgreementConfig

La structure de message dans la Figure 67 ci-après est utilisée pour configurer les accords
client.
61968-9  CEI:2013 – 551 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 67 – Message de configuration des accords client

5.10.3.6 CustomerAccountConfig

La structure de message dans la Figure 68 ci-après est utilisée pour configurer les comptes
client.
– 552 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 68 – Message de configuration des comptes client

5.10.3.7 ServiceCategoryConfig

La structure de message dans la Figure 69 ci-après est utilisée pour configurer les catégories
de service.

Figure 69 – Format de message ServiceCategoryConfig

5.10.3.8 UsagePointConfig

La structure de message dans la Figure 70 ci-après est utilisée pour configurer les points
d'usage. Cela remplace le message des points de livraison de service défini dans la
CEI 61968-9:2009.
61968-9  CEI:2013 – 553 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 70 – Format de message UsagePointConfig


– 554 – 61968-9  CEI:2013

Un exemple de charge utile d’UsagePointConfig est montré ci-dessous.


<?xml version="1.0" encoding="UTF-8"?>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:UsagePointConfig xsi:schemaLocation="http://iec.ch/TC57/2011/UsagePointConfig# UsagePointConfig.xs


xmlns:m="http://iec.ch/TC57/2011/UsagePointConfig#" xmlns:xsi="http://www.w3.org/2001/XMLSchema-insta
<m:UsagePoint>
<m:isSdp>true</m:isSdp>
<m:ConfigurationEvents>
<m:createdDateTime>2011-11-09T10:58:03.616Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
</m:ConfigurationEvents>
<m:Names>
<m:name>SDP1234E001001</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
<m:UsagePointLocation>
<m:Names>
<m:name>LOC1234</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
</m:UsagePointLocation>
</m:UsagePoint>
</m:UsagePointConfig>

5.10.3.9 UsagePointLocation

Le diagramme dans la Figure 71 décrit la structure du message utilisée pour définir les
UsagePointLocations.
61968-9  CEI:2013 – 555 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 71 – Format de message UsagePointLocationConfig

Un exemple de charge utile d’UsagePointLocationConfig est montré ci-dessous.


<?xml version="1.0" encoding="UTF-8"?>
<m:UsagePointLocationConfig
xsi:schemaLocation = "http://iec.ch/TC57/2011/UsagePointLocationConfig#
UsagePointLocationConfig.xsd"
xmlns:m = "http://iec.ch/TC57/2011/UsagePointLocationConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
<m:UsagePointLocation>
<m:ConfigurationEvents>
<m:createdDateTime>2011-11-09T10:57:02.583Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
</m:ConfigurationEvents>
<m:mainAddress>
<m:streetDetail>
<m:name>Main Street</m:name>
<m:number>1234</m:number>
</m:streetDetail>
<m:townDetail>
<m:country>US</m:country>
<m:name>Austin</m:name>
– 556 – 61968-9  CEI:2013

<m:stateOrProvince>TX</m:stateOrProvince>
</m:townDetail>
</m:mainAddress>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:Names>
<m:name>LOC1234</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
</m:UsagePointLocation>
</m:UsagePointLocationConfig>

5.10.3.10 EndDeviceConfig

Le diagramme dans la Figure 72 décrit le haut niveau du message EndDeviceConfig qui est
utilisé pour fournir une configuration basique des dispositifs terminaux.

Figure 72 – Format des messages de configuration de dispositif terminal

5.10.3.11 MeterConfig

La structure de message dans la Figure 73 est utilisée pour configurer les compteurs, où il est
possible de fournir des informations plus spécifiques aux compteurs.
61968-9  CEI:2013 – 557 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 73 – Message de configuration du compteur

Un exemple de charge utile de MeterConfig est montré ci-dessous.


<?xml version="1.0" encoding="UTF-8"?>
<m:MeterConfig
– 558 – 61968-9  CEI:2013

xsi:schemaLocation = "http://iec.ch/TC57/2011/MeterConfig# MeterConfig.xsd"


xmlns:m = "http://iec.ch/TC57/2011/MeterConfig#"
xmlns:xsi = "http://www.w3.org/2001/XMLSchema-instance">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<m:Meter>
<m:amrSystem>CCTR</m:amrSystem>
<m:serialNumber>82000001</m:serialNumber>
<m:ConfigurationEvents>
<m:createdDateTime>2011-11-09T13:55:02.776Z</m:createdDateTime>
<m:effectiveDateTime>2011-11-09T00:00:00.000Z</m:effectiveDateTime>
<m:reason>AssetCreation</m:reason>
</m:ConfigurationEvents>
<m:EndDeviceInfo>
<m:AssetModel>
<m:modelNumber>F60</m:modelNumber>
<m:Manufacturer>
<m:Names>
<m:name>LG</m:name>
</m:Names>
</m:Manufacturer>
</m:AssetModel>
</m:EndDeviceInfo>
<m:Names>
<m:name>1234LG</m:name>
<m:NameType>
<m:name>PrimaryName</m:name>
</m:NameType>
</m:Names>
</m:Meter>
</m:MeterConfig>

5.10.3.12 ComModuleConfig

Le diagramme ci-après fournit la structure de haut niveau du message utilisé pour configurer
les modules de communication.

Figure 74 – Format de message ComModuleConfig

5.10.3.13 ServiceLocationConfig

La structure de message dans la Figure 75 ci-après est utilisée pour configurer les
emplacements de service.
61968-9  CEI:2013 – 559 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 75 – Format de message ServiceLocationConfig

5.10.3.14 PricingStructureConfig

La structure de message dans la Figure 76 ci-après est utilisée pour configurer les structures
de tarification.
– 560 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Figure 76 – Format de message PricingStructureConfig

6 Conventions du document

6.1 Diagrammes UML

Des diagrammes de séquences en UML contenus dans le présent document sont à considérer
comme des exemples informatifs de la manière dont un échange de messages pourrait se
produire.

L'une des forces du CIM est sa flexibilité. A mesure que la technologie progresse et que de
nouveaux besoins apparaissent, de nouveaux messages peuvent être créés. Ces nouveaux
messages pourraient impliquer des systèmes supplémentaires (non illustrés). Les nouveaux
messages peuvent exercer un effet de levier sur des options différentes de celles décrites
dans l'exemple.
61968-9  CEI:2013 – 561 –

Les diagrammes de communication en UML et les diagrammes de flots de messages


contenus dans le présent document sont à considérer comme étant informatifs.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tous les diagrammes de classes en UML contenus dans le présent document sont
à considérer comme étant informatifs. Le lecteur est invité à se référer à la CEI 61968-1 pour
localiser le document qui contient les définitions normatives des classes utilisées dans le
CIM.

6.2 Définitions des messages

6.2.1 Généralités

Les diagrammes de formats de message contenus dans le corps du présent document sont à
considérer comme étant normatifs, les schémas XML normatifs sont fournis dans l'Annexe H
et les schémas XML informatifs sont fournis à l'Annexe I.

Les cas d'utilisation et les diagrammes de séquences sont présentés dans le présent
document à titre informatif seulement et représentent des exemples d'utilisation pour les
définitions de message normatives.

6.2.2 Obligatoire par opposition à optionnel

Les messages décrits dans la présente norme ont été dérivés de cas d'utilisation qui satisfont
au besoin métier sous-jacent d'un échange d'informations spécifiques. Chaque cas
d'utilisation fournit un contexte déterminé pour l'utilisation du CIM. Les diagrammes de format
de message décrivent les éléments qui sont passés. Les éléments illustrés dans des cadres
en traits tiretés sont à considérer comme étant facultatifs dans un contexte donné. Les
éléments illustrés dans des cadres en traits pleins sont à considérer comme étant obligatoires
dans un contexte donné. S'il convient qu'un diagramme décrive une classe entière comme
obligatoire ou facultative, il convient que le lecteur interprète cela comme signifiant que
l'utilisation de la classe est soit obligatoire, soit facultative, mais pas que chaque élément de
la classe est maintenant obligatoire ou facultatif. Le lecteur doit se référer à la définition
normative de la classe pour le déterminer.

6.2.3 Temps des verbes (Verbs)

Les verbes CIM de certains diagrammes de séquence au sein de la présente norme sont
affichés en MAJUSCULE; néanmoins, il est nécessaire que les verbes des en-têtes de tous
les messages CIM de la CEI 61968-9 soient en minuscules.

6.3 Messages synchrones par opposition à asynchrones

L'utilisation de messages synchrones ou asynchrones dans les diagrammes de séquence


dans le présent document sert à titre d'illustration uniquement et n'est pas normative.

6.4 Représentation des messages simples d'accusé de réception

Dans les mises en œuvre des services Web, il y a toujours un accusé de réception synchrone
des messages de demande même si le modèle d'échange global est asynchrone. Cet accusé
de réception synchrone est réalisé à l'aide d'un simple message stéréotype de réponse de la
CEI 61968-9 qui comprend:

Un en-tête de la CEI 61968-100


Une structure de réponse de la CEI 61968-100 avec:
Reply.Result = "OK"
Reply.Error.code = "0.3" (se référer à l'Annexe B).

Dans le cadre de l'utilisation de la messagerie JMS, cet accusé de réception simple est
également compris dans le modèle de messagerie si l'AckRequired booléen est défini sur
– 562 – 61968-9  CEI:2013

"vrai" dans l'en-tête 61968 Partie 100 du message de demande. Cependant, cet accusé de
réception simple est supprimé si l'AckRequired booléen est défini sur "faux".
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

La représentation ou l'absence de représentation de ces simples messages d'accusé de


réception dans les diagrammes de séquence au sein du présent document est volontairement
incohérente puisque les diagrammes de séquence sont informatifs et aucune hypothèse n'est
effectuée quant à savoir si les services JMS ou Web sont en cours d'utilisation ou si
l'AckRequired booléen est défini sur "vrai". Se reporter à la CEI 61968-100 pour de plus
amples informations sur ce sujet.
61968-9  CEI:2013 – 563 –

Annexe A
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Description des verbes de types de messages

Le Tableau A.1 est copié ici depuis l'Annexe B de la CEI 61968-100:2013 pour des raisons de
commodité uniquement.

Tableau A.1 – Verbes généralement utilisés

Verbes Signification Structure du message


create Le verbe "create" (créer) sert à éditer une demande auprès du Le message de demande
système de référence pour créer un nouvel objet. Le système de inclura les structures
référence peut à son tour éditer le nouvel objet comme un HeaderType et Payload.
événement en utilisant le verbe "created" (créé). Le système de
référence peut aussi utiliser le verbe "reply" (répondre) pour
répondre à une demande "create", indiquant si la demande a été
traitée avec succès ou non.
change Le verbe "change" (changer) sert à éditer une demande auprès du Le message de demande
système de référence pour apporter un changement à un objet en inclura les structures
fonction de l'information contenue dans le message. Le système de HeaderType et RequestType
référence peut à son tour éditer l'objet changé comme un événement ainsi que, facultativement, la
en utilisant le verbe "changed" (changé) pour signaler que l'objet a structure Payload. La
été modifié depuis sa dernière édition. Le système de référence peut structure requestType
aussi utiliser le verbe "reply" (répondre) pour répondre à une identifiera potentiellement les
demande "change", indiquant si la demande a été traitée avec ID d'objets spécifiques.
succès ou non.
cancel Le verbe "cancel" (annuler) sert à éditer une demande auprès du Le message de demande
système de référence pour annuler un objet, le plus souvent dans les inclura les structures
cas où l'objet représente un document commercial. Le système de HeaderType et RequestType
référence peut à son tour éditer le message annulé comme un ainsi que, facultativement, la
événement en utilisant le verbe "canceled" (annulé) pour signaler structure Payload. La
que le document a été annulé depuis sa dernière édition. Le système structure requestType
de référence peut aussi utiliser le verbe "reply" (répondre) pour identifiera potentiellement les
répondre à une demande "cancel", indiquant si la demande a été ID d'objets spécifiques.
traitée avec succès ou non. Le verbe "cancel" est utilisé lorsque le
contenu commercial du document n'est plus valide en raison d'une
ou plusieurs erreurs.
close Le verbe "close" (fermer) sert à éditer une demande auprès du Le message de demande
système de référence pour fermer un objet, le plus souvent dans les inclura les structures
cas où l'objet représente un document commercial. Le système de HeaderType et RequestType
référence peut à son tour éditer le message fermé comme un ainsi que, facultativement, la
événement en utilisant le verbe "closed" (fermé) pour signaler que le structure Payload. La
document a été fermé depuis sa dernière édition. Le système de structure requestType
référence peut aussi utiliser le verbe "reply" (répondre) pour identifiera potentiellement les
répondre à une demande "close", indiquant si la demande a été ID d'objets spécifiques.
traitée avec succès ou non. Le verbe "close" (fermer) est utilisé
lorsque le document commercial atteint la fin de son cycle de vie en
raison de l'achèvement réussi d'un processus commercial.
delete Le verbe "delete" (supprimer) est utilisé pour éditer une demande Le message de demande
auprès du système de référence pour supprimer un ou plusieurs inclura les structures
objets. Le système de référence peut à son tour éditer le message HeaderType et RequestType
fermé comme un événement en utilisant le verbe "deleted" (supprimé ainsi que, facultativement, la
pour signaler que l'objet a été supprimé depuis sa dernière édition. structure Payload. La
Le système de référence peut aussi utiliser le verbe "reply" structure requestType
(répondre) pour répondre à une demande "delete", indiquant si la identifiera potentiellement les
demande a été traitée avec succès ou non. Le verbe "delete" est ID d'objets spécifiques.
utilisé lorsqu'il convient de ne plus conserver l'objet commercial dans
les systèmes intégrés soit en raison d'une ou plusieurs erreurs, soit
pour des raisons d'archivage. Cependant, le système de référence
conservera très vraisemblablement un enregistrement historique de
l'objet après sa suppression.
execute Cela est utilisé lorsque le message transmet une transaction qui Voir OperationSet dans
implique plusieurs opérations de création, suppression et/ou Message.xsd.
changement. Voir les Annexes K et L.
get Le verbe "get" (récupérer) est utilisé pour émettre une demande Le message de demande
– 564 – 61968-9  CEI:2013

Verbes Signification Structure du message


d'interrogation à un système de référence pour retourner un inclura les structures
ensemble d'un nombre zéro ou supérieur d'objets qui satisfont à un HeaderType et RequestType.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

critère spécifié. Le système de référence peut à son tour retourner La structure requestType
un nombre zéro ou supérieur d'objets en utilisant le verbe "reply" identifiera potentiellement les
(répondre) dans un message de réponse. paramètres spécifiques pour
qualifier la demande, tels que
les ID d'objets.
created Le verbe "created" (créé) est utilisé pour éditer un événement qui est Le message d'événement
une notification de la création d'un objet suite à une demande inclura les structures
externe ou à une action interne au système de référence de l'objet HeaderType et Payload.
en question. Ce type de message fait habituellement l'objet d'un
abonnement de la part des systèmes intéressés et pourrait être
utilisé pour des mises à jour en masse. Il n'est pas indispensable de
répondre à ce type de message.
changed Le verbe "changed" (changé) est utilisé pour éditer un événement qui Le message d'événement
est une notification du changement d'un objet suite à une demande inclura les structures
externe ou à une action interne au système de référence de l'objet HeaderType et Payload.
en question. Il pourrait s'agir d'un changement générique du contenu
de l'objet ou d'un changement de statut spécifique tel que "approved"
(approuvé), "issued" (émis) etc. Ce type de message fait
habituellement l'objet d'un abonnement de la part des systèmes
intéressés et pourrait être utilisé pour des mises à jour en masse. Il
n'est pas indispensable de répondre à ce type de message.
closed Le verbe "closed" (fermé) est utilisé pour éditer un événement qui Le message d'événement
est une notification de la fermeture normale d'un objet suite à une inclura les structures
demande externe ou à une action interne au système de référence HeaderType et Payload.
de l'objet en question. Ce type de message fait habituellement l'objet
d'un abonnement de la part des systèmes intéressés et pourrait être
utilisé pour des mises à jour en masse. Il n'est pas indispensable de
répondre à ce type de message.
canceled Le verbe "canceled" (annulé) est utilisé pour éditer un événement qui Le message d'événement
est une notification de l'annulation d'un objet suite à une demande inclura les structures
externe ou à une action interne au système de référence de l'objet HeaderType et Payload.
en question. Ce type de message fait habituellement l'objet d'un
abonnement de la part des systèmes intéressés et pourrait être
utilisé pour des mises à jour en masse. Il n'est pas indispensable de
répondre à ce type de message.
deleted Le verbe "deleted" (supprimé) est utilisé pour éditer un événement Le message d'événement
qui est une notification de la suppression d'un objet suite à une inclura les structures
demande externe ou à une action interne au système de référence HeaderType et Payload.
de l'objet en question. Ce type de message fait habituellement l'objet
d'un abonnement de la part des systèmes intéressés et pourrait être
utilisé pour des mises à jour en masse. Il n'est pas indispensable de
répondre à ce type de message.
executed Cela fournit un événement qui indique l'exécution d'une transaction. Voir OperationSet dans
Message.xsd.
reply Il existe deux principales utilisations du verbe "reply" (répondre). Utilisé uniquement pour les
Toutefois, dans les deux cas, il est seulement utilisé en réponse messages de réponse. Pour
à des messages de demande, et ce, que le modèle utilisé soit les réponses à des
synchrone ou asynchrone. La première utilisation est d'indiquer le demandes transactionnelles,
succès, le succès partiel ou l'échec d'une demande transactionnelle le message contiendra les
au système de référence de créer, changer, supprimer, annuler ou structures HeaderType et
fermer un document. La seconde utilisation est en réponse à une ReplyType. Pour les
demande "get", lorsque les objets d'intérêt peuvent être retournés réponses à des demandes
dans la réponse. "get", le message contiendra
les structures HeaderType et
ReplyType et,
potentiellement, la structure
Payload.

NOTE 1 Les verbes tels qu'énumérés dans cette norme le sont pour des raisons de commodité et reflètent
aussi les changements qui peuvent se refléter dans les futures versions de la CEI 61968-1.

NOTE 2 Dans la présente norme (par exemple, sur les diagrammes de séquence), les verbes sont
insensibles à la casse. Cependant, dans le message standard, ils DOIVENT être en minuscule. Le verbe
SUBSCRIBE (souscrire) a été déconseillé. Toute utilisation de SUBSCRIBE indique que les messages au
niveau transport (par exemple, JMS) peuvent être transmis entre les parties, mais il ne s'agit pas de
messages de la CEI 61968-9.
61968-9  CEI:2013 – 565 –

Annexe B
(informative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Codes d'erreur de réponse

B.1 Présentation

La structure des messages pour transporter les Codes d'erreur de réponse est définie dans la
CEI 61968-1. Des détails supplémentaires peuvent être donnés dans les documents d'aide
tels que la CEI 61968-100. Les parties individuelles fournissent les codes propres aux
applications. Les codes de réponse propres à l'application de la CEI 61968-9 sont définis ici.

Les codes de réponse normatifs sont définis par la CEI 61968-100.

B.2 Catégories de code de réponse

Les ReplyCodes peuvent être répartis en des familles telles que décrites au Tableau B.1:

Tableau B.1 – Catégories ReplyCode

Catégorie ReplyCode Erreur Statut normatif


0 Exempte d'erreur N
1 Elément erroné ou absent N
2 Paramètre non valide N
3 Valeurs trop nombreuses N
4 Demande abandonnée N
5 Erreur d'application N
6 Violation des règles métier N
7 Problème de sécurité N
N Normative
I Informative
D Déconseillée

B.3 Construction de code

Ces catégories peuvent servir comme base d'un plan de numérotation pour former des codes
tels que ceux décrits par la formule ci-après.

ReplyCode::= <ReplyCode Category> "." <ReplyCode Index>


– 566 – 61968-9  CEI:2013

B.4 Index de code


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les index de chaque catégorie sont décrits dans les Tableaux B.2 à B.9 ci-dessous.

Tableau B.2 – Enumérations exemptes d'erreur

Catégorie Index Erreur Statut


ReplyCode ReplyCode normatif
0 0 Réussite / Pas d'erreur N
Résultat partiel (résultats supplémentaires transmis dans
0 1 des messages séparés) N
0 2 Résultat partiel (aucun autre résultat à suivre) N
0 3 Accusé de réception simple N

Tableau B.3 – Enumérations des éléments absents

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
1 1 Elément(s) Noun introuvable(s) dans le message N
1 2 Elément Revision introuvable dans le message N
1 3 Elément(s) Verb introuvable(s) dans le message N
1 5 Eléments Header obligatoires absents N
1 6 Eléments Request obligatoires absents N
1 7 Eléments Payload obligatoires absents N
Le format de la demande n'est pas validé par rapport au
1 8 schéma N
1 9 Révision non prise en charge dans le message d'en-tête N

Tableau B.4 – Enumérations des mauvaises valeurs

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
a
2 1 Discordance compteur/commutateur RCD N
2 2 Départ(s) non valide(s) I
a
2 3 Discordance départ/poste I
2 4 Meter(s) non valide(s) N
2 5 Noun non valide N
2 6 ReadingType(s) non valide(s) N
2 7 Poste(s) non valide(s) I
a
2 8 Discordance commutateur/poste I
2 9 Verb non valide N
2 10 Reading Type(s) non pris en charge N
2 11 Discordance de charge utile I
2 12 UsagePoint(s) non valide(s) N
a
2 13 Discordance Meter/UsagePoint N
2 14 Source non valide N
2 15 Request ID(s) non valide(s) N
61968-9  CEI:2013 – 567 –

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

2 16 ServiceLocation(s) non valide(s) N


2 17 Discordance Meter/ServiceLocation* N
a
2 18 Discordance ComModule/Meter* N
2 19 CustomerAccount(s) non valide(s) N
2 20 ServiceSupplier(s) non valide(s) N
a
2 21 Discordance CustomerAccount/ServiceSupplier N
2 22 Customer(s) non valide(s) N
a
2 23 Discordance Customer/CustomerAccount N
2 24 CustomerAgreement(s) non valide(s) N
a
2 25 Discordance CustomerAccount/CustomerAgreement N
a
2 26 Discordance CustomerAgreement/UsagePoint N
a
2 27 Discordance CustomerAccount/UsagePoint N
a
2 28 Discordance ServiceSupplier/UsagePoint N
2 29 Discordance de la relation d'objets N
2 30 ComModule(s) non valide(s) N
2 31 Catégorie(s) de service non valide(s) N
2 32 UsagePointLocation(s) non valide(s) N
2 33 PricingStructure(s) non valide(s) N
a Conservé pour la rétrocompatibilité. Destiné à la dépréciation dans la future édition de la CEI 61968- 9; 2,29
sera utilisé à la place.

Tableau B.5 – Enumérations des valeurs trop nombreuses

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
3 1 Eléments trop nombreux dans la demande N
3 2 Demandes en attente trop nombreuses N
3 3 ReadingTypes trop nombreux dans la demande I

Tableau B.6 – Enumérations des délais de demande expirés

Catégorie Index ReplyCode Erreur Statut normatif


ReplyCode
4 1 Délai de demande expiré N
4 2 Service indisponible I
4 3 Erreur locale lors du traitement I

Tableau B.7 – Enumérations des erreurs d'application

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
Incapable de traiter la demande – niveau élevé d'activité du
5 1 système N
5 2 Incapable de traiter la demande – transaction non tentée N
– 568 – 61968-9  CEI:2013

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Incapable de traiter la demande – transaction tentée et


5 3 échouée N
Incapable de traiter la demande – plusieurs types d'erreur
5 4 rencontrés N
Tout ou Partie des types de relevé demandés ne sont pas
5 5 disponibles dans le MDMS N
Tout ou Partie des types de relevé demandés ne sont pas
5 6 disponibles dans l'AMI N
Tout ou Partie des données demandées ne sont pas
5 7 disponibles N
Incapable de traiter la demande – champ(s) obligatoire(s)
5 8 absent(s) N
Transaction abandonnée pour maintenir l'intégrité
5 9 transactionnelle N
Incapable de traiter la demande – fonctionnalité non prise en
5 10 charge N
5 11 Echec dû à la sécurité N

Tableau B.8 – Enumérations des violations de règles métier

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
6 1 Demande annulée par règle métier N
6 2 Demande mise en attente par règle métier N
6 3 Demande libérée de l'emprise de la règle métier N
6 4 Demande reprogrammée par règle métier N
6 5 Demande annulée par l'utilisateur N

Tableau B.9 – Enumérations des problèmes de sécurité

Catégorie Index Erreur Statut normatif


ReplyCode ReplyCode
7 1 Echec d'authentification temporaire I
7 2 Authentification requise I
7 3 Mécanisme d'authentification insuffisant I
7 4 Echec de l'authentification I
7 5 Action non autorisée pour l'utilisateur I
7 6 Le mécanisme d'authentification nécessite un cryptage I
7 7 violation du régime de sécurité (Policy) I

B.5 Exemples de Reply.Error.code

Les codes de réponse sont construits selon une formule qui crée une notation avec point
exprimée sous forme de chaîne. Les exemples de Reply.Error.codes sont donnés dans le
Tableau B.10.
61968-9  CEI:2013 – 569 –

Tableau B.10 – Enumérations communes


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Code de réponse Description

0.0 Réussite / Pas d'erreur

0.1 Résultat partiel (résultats supplémentaires transmis dans des messages séparés)

0.2 Résultat partiel (aucun autre résultat à suivre)

0.3 Accusé de réception simple

1.5 Eléments Header obligatoires absents

1.6 Eléments Request obligatoires absents

1.7 Eléments Payload obligatoires absents

1.8 Le format de la demande n'est pas validé par rapport au schéma

1.9 Révision de message non prise en charge dans l'en-tête

2.4 Meter(s) non valide(s)

2.5 Noun non valide

2.6 ReadingType(s) non valide(s)

2.9 Verb non valide

2.10 ReadingType(s) non pris en charge

2.12 UsagePoint(s) non valide(s)

2.13 Discordance Meter/UsagePoint

2.14 Source non valide

2.15 Request ID(s) non valide(s)

2.16 ServiceLocation(s) non valide(s)

2.17 Discordance Meter/ServiceLocation*

2.18 Discordance ComModule/Meter*

2.19 CustomerAccount(s) non valide(s)

2.20 ServiceSupplier(s) non valide(s)

2.21 Discordance CustomerAccount/ServiceSupplier

2.22 Customer(s) non valide(s)

2.23 Discordance Customer/CustomerAccount

2.24 CustomerAgreement(s) non valide(s)

2.25 Discordance CustomerAccount/CustomerAgreement

2.26 Discordance CustomerAgreement/UsagePoint

2.27 Discordance CustomerAccount/UsagePoint

2.28 Discordance ServiceSupplier/UsagePoint

2.29 Discordance de la relation d'objets

2.30 ComModule(s) non valide(s)

2.31 ServiceCategory(ies) non valide(s)

2.32 UsagePointLocation(s) non valide(s)

2.33 PricingStructure(s) non valide(s)

3.1 Eléments trop nombreux dans la demande

3.2 Demandes en attente trop nombreuses

4.1 Délai de demande expiré

5.1 Incapable de traiter la demande – niveau élevé d'activité du système

5.2 Incapable de traiter la demande – transaction non tentée


– 570 – 61968-9  CEI:2013

Code de réponse Description

5.3 Incapable de traiter la demande – transaction tentée et échouée


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5.4 Incapable de traiter la demande – plusieurs types d'erreur rencontrés

5.5 Tout ou Partie des ReadingTypes demandés ne sont pas disponibles dans le MDMS

5.6 Tout ou Partie des ReadingTypes demandés ne sont pas disponibles dans l'AMI

5.7 Tout ou Partie des données demandées ne sont pas disponibles

5.8 Incapable de traiter la demande – champ(s) obligatoire(s) absent(s)

5.9 Transaction abandonnée pour maintenir l'intégrité transactionnelle

6.1 Demande annulée par règle métier

6.2 Demande mise en attente par règle métier

6.3 Demande libérée de l'emprise de la règle métier

6.4 Demande reprogrammée par règle métier

6.5 Demande annulée par l'utilisateur

7.1 Echec d'authentification temporaire

7.2 Authentification requise

7.3 Mécanisme d'authentification insuffisant

7.4 Echec de l'authentification

7.5 Action non autorisée pour l'utilisateur

7.6 Le mécanisme d'authentification nécessite un cryptage

7.7 violation du régime de sécurité (Policy)

L'enveloppe du message standard a également une seule valeur Reply.Result. Il convient


qu'elle soit remplie de la manière suivante:

"OK" s'il n'y a aucune erreur et si tous les résultats ont été renvoyés. Il n'y a aucune
exigence indiquant qu'un enregistrement Reply.Error avec le code "0.0" est à être présent.
"PARTIAL" si seul un ensemble partiel des résultats a été renvoyé, avec ou sans erreurs.
Un enregistrement Reply.Error avec le code "0.1" peut être présent, ainsi que des
enregistrements qui indiquent des erreurs.
"ERROR" si tout enregistrement Error avec un code autre que "0,*" est renvoyé, indiquant
des erreurs réelles.

Cela est représenté par le diagramme de transition d'état dans la Figure B.1.
61968-9  CEI:2013 – 571 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Start Démarrer
PARTIAL PARTIEL
FAILED ECHEC
Done Terminé

Figure B.1 – Etats des messages de réponse


– 572 – 61968-9  CEI:2013

Annexe C
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Procédure pour la création d'un nom de ReadingType

C.1 Généralités

L'énumération ReadingType est un identificateur important dans les messages MeterReading.


La présente norme spécifie un profil qui sera considéré comme étant normatif. La CEI 61968-
9 a été développée en ayant plusieurs principes de conception à l'esprit:

Il convient que les messages soient simples et à objectif général.

Il convient qu'un message "Readings" puisse transporter tout type de valeur potentiellement
présent dans un compteur, par exemple, la puissance, l'énergie, les comptes de manœuvre
relais, les informations de statut et la devise. Il convient que Readings.ReadingType puisse
réaliser la description, quelle que soit la valeur Readings.value.

Il est plus simple pour un client de données d’écarter les informations disponibles mais non
nécessaires, que de recréer les informations nécessaires mais non disponibles.

Ce troisième principe implique qu'il convient d'avoir des producteurs de données aussi
explicites que possible lors de la publication des données. Par conséquent, il convient que les
données soient totalement auto-descriptives afin que d'autres clients accédant aux données
(peut-être lorsqu'elles résident dans un entrepôt de données) puissent déterminer par eux-
mêmes la compatibilité de l'utilisation des données. Ainsi, le client de données n'aura pas
besoin d'essayer de reconstruire tout accord tacite en place au moment de la publication.

Il est admis qu'il y aura des cas où un client de données (faisant une demande d'informations)
pourrait ne pas connaître tous les détails spécifiques concernant la demande. Par exemple,
un demandeur peut souhaiter obtenir la "tension" à un emplacement donné. Il peut ne pas
savoir si le service est monophasé ou polyphasé. Il convient de pouvoir effectuer sa demande
selon les connaissances dont il dispose et le producteur de données essaye d'y répondre et
de fournir des détails supplémentaires dans la réponse appropriée. Cela peut donner un (des)
ReadingType(s) utilisé(s) dans la réponse légèrement différents du ReadingType utilisé dans
la demande.

C.2 Comprendre les attributs importants d'un nom d'élément de données

C.2.1 Généralités

Les éléments de données peuvent être décrits en termes de 18 attributs clés (dont plusieurs
sont des attributs composés (compound)). Chaque attribut comprend la caractéristique qu'une
valeur égale à zéro ("0") signifie qu'il n'est pas applicable à la description. Les attributs
composés constituent la seule exception à cette règle. Dans ce cas, deux zéros signifient que
l'attribut n'est pas applicable.

C.2.2 Attribut n° 1, macroPeriod

La macroPeriod décrit un aspect des données qui reflète la manière dont elles sont vues ou
saisies au cours d'une longue période. Celles-ci sont énumérées dans le Tableau C.1.
61968-9  CEI:2013 – 573 –

Tableau C.1 – Enumérations des périodes intéressantes

Code Enumération Commentaires Statut


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

normatif
0 none Non applicable N
8 billingPeriod Capturé pendant la période de facturation débutant à minuit au N
premier jour de la période de facturation (tel que défini par le jour
du cycle de facturation). Si cela survient pendant la période de
facturation actuelle, il indique une période depuis le début de la
période de facturation actuelle jusqu'à "maintenant".
11 daily Période quotidienne commençant à minuit. Si cela survient N
pendant la journée en cours, il indique la période à partir de
minuit jusqu'à "maintenant".
13 monthly Période mensuelle commençant à minuit le premier jour du mois. N
Si cela survient pendant le mois en cours, il indique la période
à partir du début du mois jusqu'à "maintenant".
22 seasonal Une saison qui s'étend sur plusieurs mois. Par exemple: un cycle N
basé sur l'"été", le "printemps", l'"automne" et l'"hiver". Si cela
survient pendant la saison en cours, il indique la période à partir
du début de la saison actuelle jusqu'à "maintenant".
24 weekly Période hebdomadaire commençant à minuit le premier jour de la N
semaine et se terminant l'instant avant minuit le dernier jour de la
semaine. Si cela survient pendant la semaine en cours, il indique
la période à partir du début de la semaine jusqu'à "maintenant".
32 specifiedPeriod Pour la période définie par le début et la fin de l'élément N
TimePeriod dans le message.

C.2.3 Attribut n° 2, agrégat

C.2.3.1 Généralités

La méthode d'observation d'un relevé dans l'agrégat (par comparaison avec d'autres) sert de
second attribut. Les énumérations possibles comprennent celles décrites dans le
Tableau C.2. Cet attribut peut être utilisé pour définir une opération mathématique réalisée
sur la période intéressante définie par l'attribut n° 1.

Tableau C.2 – Enumérations des qualificateurs de données

Statut
Code Enumération Commentaires
normatif
0 none Non applicable N
2 average N
La valeur représente une quantité au-dessus de laquelle un seuil
I
4 excess a été dépassé.
5 highThreshold La valeur représente un seuil programmé. I
7 lowThreshold La valeur représente un seuil programmé. I
8 maximum Valeur la plus élevée observée N
9 minimum Valeur la plus petite observée N
11 nominal I
12 normal I
16 secondMaximum Deuxième valeur la plus élevée observée N
17 secondMinimum Deuxième valeur la plus petite observée N
23 thirdMaximum Troisième valeur la plus élevée observée N
24 fourthMaximum Quatrième valeur la plus élevée observée N
25 fifthMaximum Cinquième valeur la plus élevée observée N
– 574 – 61968-9  CEI:2013

Statut
Code Enumération Commentaires
normatif
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

26 sum La somme accumulée N


Généralement utilisé pour identifier le port du flux volumique
I
27 high élevé d'un compteur d'eau composé.
Généralement utilisé pour identifier le port du flux volumique
I
28 low faible d'un compteur d'eau composé.

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.2.3.2 Modifications apportées par cette édition

Dans la CEI 61968-9:2009, il était suggéré que "TestData" puisse être utilisé en tant
qu'énumération pour indiquer qu'une valeur n'était pas une valeur réelle de facturation. Dans
cette édition de la CEI 61968-9, on encourageait plutôt l'utilisation des codes
ReadingQuality afin d'identifier les données d'essai. De la même manière, il convient
d'identifier les données "absentes" ou "instables" par le biais d'un code
ReadingQuality adapté. Les informations portant sur les codes ReadingQuality peuvent être
consultées à l'Annexe D.

Dans cette édition de la CEI 61968-9, l'attribut n° 2 est strictement utilisé pour les
qualificateurs de plage. Les termes comme "absolu" qui peuvent être utilisés pour qualifier un
relevé de pression ou des données d'intervalle sont traités ailleurs. Des unités de mesure
séparées ont été créées afin de distinguer la pression manométrique de la pression absolue.
En outre, la distinction entre "intervalData absolu" et "intervalData différentiel" est désormais
traitée par le schéma de message. Les relevés individuels (de nature "bulkQuantity" ou
"indicating") sont simplement présentés en tant que relevés ayant l'attribut "absolu" qui est
implicite. L'attribut "Incremental intervalData" est désormais décrit par le terme "DeltaData" et
par une présentation des données dans la Partie "intervalReadings" du message.

C.2.4 Attribut n° 3, measuringPeriod

C.2.4.1 Généralités

La measuringPeriod fournit un "adjectif" pour décrire les aspects d'une "période" en


relation avec la mesure. Cet attribut décrit un "attribut temps" intrinsèque ou fondamental à la
valeur de relevé. L'attribut fait référence à la manière dont la valeur a initialement été
mesurée et non à la fréquence à laquelle elle est consignée ou présentée. (Par exemple, un
intervalle horaire de données de consommation aurait un attribut de valeur "hourly".
Cependant, dans le cas d'une valeur de tension échantillonnée sur une base horaire, le
schéma meterReadings porterait les informations de taille d'intervalle "hourly".) Les valeurs
énumérées comprennent les valeurs décrites au Tableau C.3. Par comparaison avec l'attribut
#1, la measuringPeriod est un intervalle de temps de courte durée caractéristique de la
méthode de saisie du relevé, tandis que la macroPeriod est un intervalle de temps de longue
durée relatif à la méthode de rapport de ce même relevé. Ces attributs sont appelés
uniquement si la description des données le nécessite. Pour de nombreux relevés par cadran,
il est nécessaire que seul l'horodatage d'accompagnement soit significatif.
61968-9  CEI:2013 – 575 –

Tableau C.3 – Enumérations de measuringPeriod


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Statut
Code Enumération Commentaires
normatif
0 none Non applicable N
1 tenMinute 10 min N
2 fifteenMinute 15 min N
3 oneMinute 1 min N
4 twentyfourHour 24 h N
5 thirtyMinute 30 min N
6 fiveMinute 5 min N
7 sixtyMinute 60 min N
10 twoMinute 2 min N
14 threeMinute 3 min N
15 present Dans la période présente I
16 previous Dans le cycle et le jeu de données mensuels précédents I
31 twentyMinute Intervalle de 20 min N
50 fixedBlock60Min Bloc fixe de 60 min N
51 fixedBlock30Min Bloc fixe de 30 min N
52 fixedBlock20Min Bloc fixe de 20 min N
53 fixedBlock15Min Bloc fixe de 15 min N
54 fixedBlock10Min Bloc fixe de 10 min N
55 fixedBlock5Min Bloc fixe de 5 min N
56 fixedBlock1Min Bloc fixe de 1 min N
57 rollingBlock60MinIntvl30MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
30 min
58 rollingBlock60MinIntvl20MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
20 min
59 rollingBlock60MinIntvl15MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
15 min
60 rollingBlock60MinIntvl12MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
12 min
61 rollingBlock60MinIntvl10MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
10 min
62 rollingBlock60MinIntvl6MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
6 min
63 rollingBlock60MinIntvl5MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
5 min
64 rollingBlock60MinIntvl4MinSubIntvl bloc roulant de 60 min avec des sous-intervalles de N
4 min
65 rollingBlock30MinIntvl15MinSubIntvl bloc roulant de 30 min avec des sous-intervalles de N
15 min
66 rollingBlock30MinIntvl10MinSubIntvl bloc roulant de 30 min avec des sous-intervalles de N
10 min
67 rollingBlock30MinIntvl6MinSubIntvl bloc roulant de 30 min avec des sous-intervalles de N
6 min
68 rollingBlock30MinIntvl5MinSubIntvl bloc roulant de 30 min avec des sous-intervalles de N
5 min
69 rollingBlock30MinIntvl3MinSubIntvl bloc roulant de 30 min avec des sous-intervalles de N
3 min
70 rollingBlock30MinIntvl2MinSubIntvl bloc roulant de 30 min avec des sous-intervalles de N
– 576 – 61968-9  CEI:2013

Statut
Code Enumération Commentaires
normatif
2 min
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

71 rollingBlock15MinIntvl5MinSubIntvl bloc roulant de 15 min avec des sous-intervalles de N


5 min
72 rollingBlock15MinIntvl3MinSubIntvl bloc roulant de 15 min avec des sous-intervalles de N
3 min
73 rollingBlock15MinIntvl1MinSubIntvl bloc roulant de 15 min avec des sous-intervalles de N
1 min
74 rollingBlock10MinIntvl5MinSubIntvl bloc roulant de 10 min avec des sous-intervalles de N
5 min
75 rollingBlock10MinIntvl2MinSubIntvl bloc roulant de 10 min avec des sous-intervalles de N
2 min
76 rollingBlock10MinIntvl1MinSubIntvl bloc roulant de 10 min avec des sous-intervalles de N
1 min
77 rollingBlock5MinIntvl1MinSubIntvl bloc roulant de 5 min avec des sous-intervalles de 1 min N
78 twelveMinute 12 min N
79 twoHour 2h N
80 fourHour 4h N
81 sixHour 6h N
82 twelveHour 12 h N
83 threeHour 3h
100 specifiedInterval La durée de l'intervalle est décrite dans l'attribut N
n° 10 en secondes. Il convient que l'attribut n° 11 soit "1"
pour les secondes entières.
101 specifiedFixedBlock La durée du bloc fixe est décrite dans l'attribut n° 10 en N
secondes. Il convient que l'attribut n° 11 soit "1" pour les
secondes entières.
102 specifiedRollingBlock La taille du bloc roulant est décrite par l'attribut n° 10 en N
secondes et la taille du sous-intervalle par l'attribut
n° 11 en secondes.

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

En général, les compteurs consignent la demande sous une forme qui est mesurée au cours
d'une fraction d'une heure. Pour leur part cependant, les applications d'entreprise supposent
généralement que la demande (qui a une unité de mesure en "kW" ou "kVAr") est normée à
1 h. Le système de comptage doit réaliser cette transformation avant la publication et
l'utilisation par les autres systèmes. Le scalaire utilisé est choisi sur la base de la taille du
bloc (et non d'une quelconque taille de sous-intervalle). Lesdits scalaires sont répertoriés
dans le Tableau C.4

Tableau C.4 – Scalaires de normalisation de la demande

Dimension du bloc de demande Scalaire de normalisation


1h 1
30 min 2
20 min 3
15 min 4
10 min 6
1 min 60
61968-9  CEI:2013 – 577 –

Par exemple, avant la normalisation, il peut être indiqué que les données
"15minuteFixedBlock" disposent d'unités de "kilo quart-watt-heure" (kWh). Après la
normalisation, l'unité de mesure deviendrait "kilo-watt-heure". Puisque "kilo quart-watt-heure"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

n'est pas une unité de mesure utilisable, il convient que les systèmes souhaitant
communiquer les données brutes sous cette forme utilisent une unité de mesure telle que
"compte" et l'élément PendingCalculation qui transporte le scalaire (ou multiplicateur) requis
et l'unité de mesure résultante lorsqu'elle est appliquée.

C.2.4.2 Utilisations courantes (informative)

Les données d'intervalles sont généralement trouvées dans les tailles "60 min", "30 min" et
"15 min". Des tailles plus grandes telles que "24 h" et plus petites allant jusqu'à "1 min" sont
également possibles mais moins courantes. Il convient que les utilisateurs de la norme
exploitent les énumérations d'intervalles existants quand elles existent, mais si la taille
d'intervalle requise n'existe pas, un "specifiedInterval" peut être utilisé. Cela permet
à l'énumération elle-même d'intégrer la taille de l'intervalle dans l'énumération. De la même
manière, les tailles de blocs fixes et roulants non courantes peuvent être indiquées.

La CEI 61968-9:2009 proposait d'utiliser les termes "Décalé", "Présent" et "Précédent" en


tant qu'adjectifs afin de décrire l'état du compteur. Bien que cela fonctionne correctement
pour publier les données à partir d'un système de comptage, ils peuvent être difficiles
à utiliser entre d'autres applications d'entreprise. Il semble que si "present" et "previous" sont
des attributs importants de données quand ils sont au niveau du compteur; plus l'un s'éloigne
du compteur, moins ces attributs deviennent importants. Avec la cette édition de la
CEI 61968-9, on propose de se reposer sur la durée pendant laquelle les données sont
enregistrées pour déterminer si une valeur appartient à la période de facturation "present" ou
"previous" plutôt qu'aux énumérations "present" ou "previous". En outre, les règles utilisées
pour calculer la demande sont assez importantes. Une seule demande "Daily" n'est
généralement pas adaptée pour calculer la facture d'un client. Un ensemble complet de
demandes "Daily" ou une seule demande de "Billing » sont généralement requis. Il convient
de faire une distinction entre les périodes d'observation Daily/Billing/Seasonal dans le
ReadingType. Dans tous les cas, l’horodatage associé à la demande maximale pourrait être
utilisé pour savoir à quel(le) jour, mois ou saison correspond une demande "daily", "billing" ou
"seasonnal".

Dans une entreprise de distribution où plusieurs techniques de saisie de la demande existent,


il devient important de communiquer entre les systèmes la définition selon laquelle les
données de demande sont saisies. Les énumérations sont fournies dans la présente seconde
édition, ce qui permet au producteur de données d'être aussi précis que possible lors de la
description du type de données de demande transmises.

C.2.5 Attribut n° 4, accumulation

C.2.5.1 Généralités

L'attribut "accumulation" indique comment la valeur est représentée aux fins d'accumulation
au fil du temps. Les valeurs énumérées comprennent celles décrites dans le Tableau C.5.

Un avantage que présente le fait de déclarer explicitement le comportement d'accumulation


comme partie du readingType dans un échange entre un MS et une MDM est d'aider la MDM
à assurer que les règles de validation appropriées sont appliquées aux données fournies par
le MS.
– 578 – 61968-9  CEI:2013

Tableau C.5 – Enumérations des comportements d'accumulation


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Statut
Code Enumération Commentaires
normatif
0 none Non Applicable ou donné implicitement par l'unité de mesure. N
Une valeur issue d'un registre qui représente la quantité en
gros d'une marchandise. Cette quantité est calculée comme
étant l'intégrale du taux d'utilisation de la marchandise. En
général, cette valeur est utilisée comme base du relevé au
cadran sur le compteur et, de ce fait, se réinitialisera après
avoir atteint une valeur de cadran maximale.
NOTE 1 Avec le système de comptage, le comportement
d'addition implique un comportement de soustraction afin que la
1 bulkQuantity N
valeur présentée soit toujours une valeur positive (par exemple,
un entier non signé ou un décimal positif). Dans le cadre de la
communication de données entre les applications d'entreprise,
une valeur négative peut néanmoins survenir dans un cas tel
que le comptage de réseau.
NOTE 2 Un BulkQuantity fait principalement référence au
relevé au cadran et non à la consommation au cours d'une
période spécifique.
La somme des valeurs dans la période de facturation
précédente et de la valeur dans la présente période. Note:
"ContinuousCumulative" est généralement utilisé conjointement
à "demand". Le "ContinuousCumulative Demand" serait la
2 continuousCumulative somme cumulée des valeurs de demande maximale de la N
période de facturation précédente (qui survient à chaque
réinitialisation de la demande) ajouté à la valeur de demande
maximale de la période présente (qui n'a pas encore été
réinitialisée).
La somme des valeurs dans les périodes de facturation
antérieures. Note: "Cumulative" est généralement utilisé
conjointement à "demande". Chaque réinitialisation de la
demande fait que la valeur de demande maximale pour la
période de facturation présente (depuis la dernière
3 cumulative N
réinitialisation de la demande) s'ajoute en tant que total cumulé
de toutes les demandes maximales. Donc au lieu de "remettre
à zéro" le registre de demande, une réinitialisation de la
demande provoque l'ajout de la demande maximale présente
à ce total cumulé.
La différence entre la valeur à la fin de l'intervalle spécifié et au
début de l'intervalle. Cela est utilisé pour les données
d'intervalles différentielles.

4 deltaData NOTE 3 Une application commune viserait les données de N


profil de charge, une autre utilisation pourrait être de rapporter
le nombre d'événements au sein d'un intervalle (tel que le
nombre d'excitations de l'équipement pendant la période
spécifiée).
Comme si une aiguille pointait sur le compteur sur une valeur
pour indiquer la valeur courante. Note: une valeur "indicating",
généralement mesurée sur des centaines de millisecondes ou
6 indicating N
plus, peut impliquer un mécanisme "poussant" pour saisir une
valeur. Comparer cela à "instantaneous" qui est mesuré sur
une plus courte durée).
Une forme d'accumulation qui est sélective par rapport au
temps.
NOTE 4 La "Somme" pourrait être considérée comme une
9 summation spécialisation de "BulkQuantity" conformément aux règles I
d'héritage où la "Somme" cumule de manière sélective les
impulsions au cours d'un modèle temporel et où "BulkQuantity"
cumule les impulsions tout le temps.
Une forme de calcul qui introduit une caractéristique de retard
10 timeDelay I
temporel dans la valeur de la donnée
Généralement mesuré sur la période la plus rapide autorisée
12 instantaneous par la définition de la mesure (habituellement des millisecondes N
ou des dizaines de millisecondes). Note: "Instantaneous" a été
déplacé vers l'attribut n° 3 de la 61968-9 Ed2 depuis l'attribut
61968-9  CEI:2013 – 579 –

Statut
Code Enumération Commentaires
normatif
n° 1 dans la 61968-9:2009).
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Lorsque cette description est appliquée à une valeur mesurée,


cela signifie que la valeur est une quantité cumulée
indépendante du temps plus un BulkQuantity, hormis qu'il
s'insère dans la valeur maximale lorsqu'il atteint cette valeur.
Toute accumulation supplémentaire (positive ou négative) est
ignorée jusqu'à la survenue d'une réinitialisation.
NOTE 5 Un LatchingQuantity peut également survenir dans la
direction descendante, lorsqu'il atteint une valeur minimale. Les
termes "maximal" ou "minimal" seront généralement compris en
tant qu'attribut quand ce type de comportement d'accumulation
13 latchingQuantity est présent. N
Lorsque cette description est appliquée à une valeur encodée
(unité de mesure = "Code"), cela signifie que la valeur à un ou
plusieurs bits verrouillés. La condition qui a défini le bit peut
être évaporée depuis longtemps.
Dans tous les cas, le marqueur temporel qui accompagne la
valeur peut ne pas coïncider avec le moment de configuration
initiale de la valeur.
Dans les deux cas, un système devra réaliser une opération
pour effacer la valeur verrouillée.
Une quantité cumulée indépendante du temps plus un
BulkQuantity ou un LatchingQuantity, sauf que l'accumulation
s'arrête aux valeurs maximale ou minimale. Lorsque le
maximum est atteint, toute accumulation positive
supplémentaire est ignorée, mais toute accumulation négative
14 boundedQuantity N
peut être acceptée (diminuant ainsi le compteur). De la même
manière, lorsque la limite négative est atteinte, toute
accumulation négative supplémentaire est ignorée, mais toute
accumulation positive est acceptée (augmentant ainsi le
compteur).

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.2.5.2 Types d'IntervalReadings

Dans la CEI 61968-9:2009, il était dit que les IntervalReadings pouvaient être exprimés dans
plusieurs styles qualifiés par l'attribut #2 (soit "Incremental", "Relative" ou "Absolute".) La
première édition décrivait également "RecordedData" et "DeltaData".

Dans cette édition de la CEI 61968-9, un effort a été fait pour simplifier la présentation des
données. Une valeur échantillonnée appelée relevé d'"absolute interval" dans la première
édition peut être présentée sans le mot "absolute". Effectivement, lesdits relevés peuvent être
publiés dans la Partie MeterReading.Readings du message en tant que relevés ordinaires
plutôt que dans la Partie MeterReading.IntervalBlock.IntervalReadings du message. Le
concept de "Relative IntervalData" ne se trouve plus dans les énumérations car le concept est
pris en charge dans le schéma de message en tant que forme de scalaires de données
"pending » (en attente).

C.2.5.3 Utilisations courantes

Les attributs décrits dans le Tableau C.5 sont couramment utilisés de manières particulières
pour décrire les valeurs d'énergie et de la demande. Ces habitudes sont décrites dans le
Tableau C.6.
– 580 – 61968-9  CEI:2013

Tableau C.6 – Enumérations des comportements habituels d'accumulation

Type de données de métrologie Utilisations communes


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Energie (mesurée par le simple comptage et affichée BulkQuantity


pour l'utilisateur sur l'avant du compteur).
Demande (généralement mesurée en intégrant une Indicating, Cumulative, ContinuousCumulative
valeur de puissance sur une période spécifique).
Puissance (généralement mesurée en temps réel dans Instantaneous, TimeDelay
les compteurs à semi-conducteurs).
Données d'énergie selon le temps d'utilisation (TOU) Summation
(mesurées en accumulant les valeurs dans les registres
assortis selon l'heure du jour et le jour de la semaine).
Données de demande selon le temps d'utilisation (TOU) Indicating, Cumulative ou ContinuousCumulative
(dérivées en intégrant les valeurs d'énergie sur un
intervalle de demande spécifié, avec des dépendances
supplémentaires sur le calendrier TOU).
Compteurs BulkQuantity, LatchingQuantity

Typical sampled
value
«enumeration»
EngineeringData
«enumeration»
Consumption Indicating = 6
Instantaneous = 12
DeltaData = 4
TimeDelay = 10
LatchingQuantity = 13
BoundedQuantity = 14

Commonly used for


interval data.
«enumeration»
AccumulatingMeterDialRegister
«enumeration»
BulkQuantity = 1 Demand
Summation = 9
Indicating = 6
Cumulative = 3
ContinuousCumulative = 2

Commonly used for


billing quantities.

Légende

Anglais Français
Commonly used for interval data. Fréquemment utilisé pour les données d'intervalle.
Typical sampled value Valeur échantillonnée typique
Commonly used for billing quantities. Fréquemment utilisé pour les quantités de
facturation.

Figure C.1 – Enumérations typiques des comportements d'accumulationAttribut n° 5,


flowDirection
61968-9  CEI:2013 – 581 –

C.2.6.1 Généralités

Tout ce qui implique le courant est susceptible d'avoir un sens d'écoulement. Le sens
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

d'écoulement est très important, mais lorsqu'il est inconnu, il convient de le laisser non
précisé. Les énumérations possibles comprennent celles décrites dans le Tableau C.7.

Le “sens d’écoulement” englobe le concept électrique de comptage à quatre quadrants ainsi


que la nécessité pour les différents tarifs régionaux de décrire le mode de facturation.

Il convient d’admettre que les pratiques tarifaires dans différentes parties du monde reposent
sur différents cadres de référence. La plupart des régions définissent la fourniture d’énergie
selon un cadre de référence établi par les producteurs. L’énergie générée par l’entreprise
électrique est transmise par le réseau de l’entreprise électrique, le compteur et dans le
câblage du client. Le compteur capture l’énergie vendue au client. Cependant, certaines
régions considèrent le point de vue du client. Un cadre de référence du client signifie que
l’énergie peut être achetée par un client à partir du réseau. Tout flux direct passant par le
compteur régit l’énergie achetée par le client.

La présente norme tente d’appréhender l’ensemble de la question du cadre de référence en


admettant que ces deux points de vue sont équivalents. L’énergie achetée est l’énergie
vendue. Le flux “direct” depuis le côté “source” du compteur au côté “charge” du compteur (ou
en termes équivalents “V+” et “V–”) crée une mesure qui peut être utilisée pour toute
définition du tarif. La présente norme envisage le code numérique pour un concept
sémantique donné comme “normatif” tandis que le texte utilisé pour désigner le concept est
considéré comme “informatif”.

Les différences linguistiques parmi les différents pays participants de la CEI justifient en
second lieu le fait de conserver le caractère informatif des descriptions textuelles.
– 582 – 61968-9  CEI:2013

Tableau C.7 – Enumération des sens d'écoulement


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Nom Statut
Code d’énumération Commentaires normatif
(informatif) de code
0 none Non applicable (N/A) N
Connu aussi cimme "Remis" ou "importé" tel que défini dans la 61968-2.
L'énergie active directe est une valeur positive en kWh que l'on peut s'attendre
à trouver naturellement lorsque l'énergie est fournie par l'entreprise de
distribution et consommée au niveau du service.
L’énergie active directe est cumulée dans un service monophasé en observant
le débit de puissance (+P) dans les quadrants I et IV.

Légende
Axe réactif - Axe réel
1 forward L'énergie réactive directe est une valeur positive en VArh que l'on peut N
s'attendre à trouver naturellement en présence de charges inductives.
L’énergie réactive directe est cumulée dans un service monophasé en
observant le débit de puissance (+Q) dans les quadrants I et II.

Légende
Axe réactif - Axe réel

L’énergie apparente directe est une valeur positive en VAh tout comme
l’énergie active directe. Elle est cumulée dans un service monophasé en
observant le débit de puissance (S = P + jQ) dans les quadrants I et IV.
61968-9  CEI:2013 – 583 –

Nom Statut
Code d’énumération Commentaires normatif
(informatif) de code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende
Axe réactif - Axe réel
Dans le comptage polyphasé, le registre d'énergie directe est incrémenté
lorsque la somme des énergies phasées est supérieure à zéro:
Energy A + Energy B + Energy C > 0
Typiquement utilisé pour décrire qu'un facteur de puissance est en retard par
rapport à la valeur de référence (ou dire que le courant est en retard par rapport à la
tension)..
NOTE 1 Lorsqu'il est utilisé pour décrire le facteur de puissance, le terme
"lagging" implique que le FP est négatif. Dans ce cas, le terme "lagging" prend
la place du signe négatif. Si une valeur FP signée est à transmettre par le
producteur de données, il convient alors d'utiliser zéro énumération des sens
2 lagging N
d'écoulement (none aucune) afin d'éviter la création potentielle d'une
expression employant un double négatif. Il convient que le client de données
puisse dire à partir du signe des données si le FP est en avance ou en retard.
Ce principe est analogue au concept disant que l'énergie "inverse" est une
valeur négative implicite et publier une valeur inverse négative serait ambigu.
NOTE 2 Des facteurs de puissance en retard indiquent généralement des
charges inductives.
Typiquement utilisé pour décrire qu'un facteur de puissance est en avance par
rapport à la valeur de référence ou que le courant est en avance par rapport à la
3 leading tension). N
NOTE 3 Des facteurs de puissance en avance indiquent généralement des
charges capacitives.
|Forward| – |Reverse| (c'est-à-dire: direct – inverse), voir la 61968-2.
4 net NOTE 4 Dans certains systèmes, la valeur passée comme valeur "nette" N
pourrait devenir négative. Dans d'autres systèmes, la valeur passée comme
valeur "net", toujours un nombre positif, ajoute et soustrait selon les besoins.
5 q1plusQ2 Quadrants positifs réactifs. I
7 q1plusQ3 Quadrants 1 et 3 I
8 q1plusQ4 Les quadrants 1 et 4 représentent habituellement l'énergie active directe I
9 q1minusQ4 Q1 moins Q4 I
10 q2plusQ3 Les quadrants 2 et 3 représentent habituellement l'énergie active inverse I
11 q2plusQ4 Quadrants 2 et 4 I
12 q2minusQ3 Q2 moins Q3 I
13 q3plusQ4 Quadrants négatifs réactifs. I
14 q3minusQ2 Q3 moins Q2 I
– 584 – 61968-9  CEI:2013

Nom Statut
Code d’énumération Commentaires normatif
(informatif) de code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Q1 uniquement

15 quadrant1 I

Légende
Axe réactif - Axe réel

Q2 uniquement

16 quadrant2 I

Légende
Axe réactif - Axe réel
17 quadrant3 Q3 uniquement I
61968-9  CEI:2013 – 585 –

Nom Statut
Code d’énumération Commentaires normatif
(informatif) de code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende
Axe réactif - Axe réel
Q4 uniquement

18 quadrant4 I

Légende
Axe réactif - Axe réel

L'énergie active inverse est équivalente à "reçu" ou "exporté" tel que défini
dans la 61968-2.
L'énergie active inverse est une valeur positive en kWh que l'on peut s'attendre
19 reverse à trouver lorsque l'énergie est réalimentée par le service sur le réseau de N
l'entreprise de distribution.
L’énergie active inverse est cumulée dans un service monophasé en observant
le débit de puissance (-P) dans les quadrants II et III.
– 586 – 61968-9  CEI:2013

Nom Statut
Code d’énumération Commentaires normatif
(informatif) de code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende
Axe réactif - Axe réel

L'énergie réactive inverse est une valeur positive en VArh que l'on peut
s'attendre à trouver en présence de charges capacitives et d'un facteur de
puissance en avance.
L’énergie réactive inverse est cumulée dans un service monophasé en
observant le débit de puissance (-Q) dans les quadrants III et IV.

Légende
Axe réactif - Axe réel

L’énergie apparente inverse est une valeur positive en VAh tout comme
l’énergie active inverse. Elle est cumulée dans un service monophasé en
observant le débit de puissance (S = P + jQ) dans les quadrants II et III.
61968-9  CEI:2013 – 587 –

Nom Statut
Code d’énumération Commentaires normatif
(informatif) de code
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende
Axe réactif - Axe réel

Dans le comptage polyphasé, le registre d'énergie inverse est incrémenté


lorsque la somme des énergies phasées est inférieure à zéro:
Energy A + Energy B + Energy C < 0

NOTE 5 La valeur passée en tant que valeur inverse est toujours une valeur
positive. Il est compris avec l'étiquette "inverse" qui représente l'écoulement
négatif.
|Forward| + |Reverse| (c'est-à-dire: direct – inverse), voir la 61968-2.
La somme des produits dans tous les quadrants Q1+Q2+Q3+Q4.
Dans le comptage polyphasé, le registre d'énergie totale est incrémenté lorsque
20 total N
la valeur absolue de la somme des énergies phasées est supérieure à zéro:
Energy A + Energy B + Energy C < 0

Dans le comptage polyphasé, le total par registre d'énergie phasée est


incrémenté lorsque la somme des valeurs absolues des énergies phasées est
supérieure à zéro:
Energy A + Energy B + Energy C < 0
21 totalByPhase N

Dans le cadre du comptage monophasé, les formules pour "Total" et "Total par
phase" sont réduites à la même expression. Néanmoins, aux fins de la
communication, il convient d'utiliser l'énumération "Total" avec des données du
compteur monophasé.

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.2.6.2 Utilisations courantes

La terminologie utilisée pour indiquer le sens d'écoulement de l'énergie réactive et de la


puissance réactive varie considérablement selon le fournisseur. Le Tableau C.8 décrit
différents sens d'écoulement équivalents par type de puissance (ou d'énergie) et donne des
recommandations concernant une énumération préférentielle des sens d'écoulement aux fins
de la communication.
– 588 – 61968-9  CEI:2013

Tableau C.8 – Equivalences des énumérations de sens d'écoulement


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Type Unité de Sens d'écoulement équivalents couramment utilisés Sens d'écoulement


d'énergie ou mesure dans le secteur préférentiel pour la
de puissance messagerie
Actif ou réel W ou Wh Forward (Direct), Delivered (remis), Positive (positif), Q1+Q4 Forward
Reverse((Inverse), Received (reçu), Negative (négatif), Reverse
Q2+Q3
Net, Q1+Q4-(Q2+Q3) Net
Total, Q1+Q2+Q3+Q4 Total
Réactif VAr ou Forward (Direct), Delivered (remis), Positive (positif), , Forward
VArh Lagging (retard), Q1+Q2
Reverse((Inverse), Received (reçu), Negative (négatif), Reverse
Leading (avance), Q3+Q4
Net, Q1+Q2-(Q3+Q4) Net
Total, Q1+Q2+Q3+Q4 Total
Apparent VA ou Forward (Direct), Delivered (remis) Forward
VAh
Reverse((Inverse), Received (reçu), Reverse
Net Net
Total Total

class 4-DirectionOfFlow

Typical sampled
value

«enumeratio...
Not Applicable

none = 0

Measurement
Measurement
involving current
involving Power
Four-quadrant Factor
- Current
metering is a
- Energy
competing method of
- Power
describing flow
- Demand
directions.

«enumeration»
DirectionOfFlow Singlephase «enumeration»
DirectionOfFlow Polyphase «enumeration»
Forward = 1 P.F.
Net = 4 Forward = 1
Reverse = 19 Net = 4 Leading = 3
Total = 20 Reverse = 19 Lagging = 2
Total = 20
TotalByPhase = 21

Légende

Anglais Français
Typical sampled value Valeur échantillonnée typique
Four-quadrant metering is a competing method of La mesure à quatre cadrans permet de décrire
61968-9  CEI:2013 – 589 –

Anglais Français
describing flow directions. efficacement les directions de flux.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Measurement involving current Mesure qui implique un courant


Measurement involving Power Factor Mesure qui implique le facteur de puissance

Figure C.2 – Enumérations typiques des sens d'écoulement

C.2.7 Attribut n° 6, produit

Dans la cette norme, le produit qui est mesuré a été isolé pour devenir un attribut par lui-
même. Il est énuméré dans le Tableau C.9.

Tableau C.9 – Produit

Statut
Code Enumération Commentaires
normatif
0 none Non applicable N
Tous les types de quantités mesurées. Ce type de relevé
electricity
1 vient du compteur et représente une valeur mesurée N
SecondaryMetered
"secondaire".
Un compteur peut être équipé d'un VT et/ou d'un CT externe.
Le compteur peut ne pas être informé de la présence de ces
appareils et l'affichage ne compense pas cela. En dernier
2 electricity PrimaryMetered ressort, lorsque ces scalaires sont appliqués, la valeur qui N
représente la valeur de service est appelée valeur "primary
metered » (primaire mesurée). L'"index" dans la sous-
catégorie 3 reflète ceux de la sous-catégorie 0.
3 communication Une mesure de l'infrastructure de communication elle-même. N
4 air N
5 insulativeGas (SF 6 est trouvé séparément ci-après). N
6 insulativeOil N
7 naturalGas N
8 propane N
9 potableWater Eau potable N
Eau sous forme de vapeur, utilisée habituellement pour le
10 steam N
chauffage.
11 wasteWater (Assainissement) N
Ce fluide est susceptible d'être sous forme liquide. Ce n'est
pas obligatoirement de l'eau ou à base d'eau. Le liquide
12 heatingFluid N
chaud revient plus froid que lorsqu'il a été envoyé. La chaleur
transmise peut être mesurée.
Le liquide froid revient plus chaud que lorsqu'il a été envoyé.
13 coolingFluid N
La chaleur transmise peut être mesurée.
Eau récupérée: potentiellement utilisée pour l'irrigation mais
pas suffisamment traitée pour être jugée salubre pour la
14 nonpotableWater boisson. N

Humidité dans l'huile


15 nox Protoxydes d'azote, NO X N
16 so2 Dioxyde de soufre, SO 2 N
17 ch4 Méthane, CH 4 N
18 co2 Dioxyde de carbone, CO 2 N
19 carbone C I
20 hch Hexachlorocyclohexane, HCH N
21 pfc Hydrocarbures perfluorés, PFC N
22 sf6 Hexafluorure de soufre, SF 6 N
– 590 – 61968-9  CEI:2013

Statut
Code Enumération Commentaires
normatif
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

23 tvLicence Télévision N
24 internet Service Internet N
25 refuse Supprimer N
26 h2 Hydrogène, H 2 N
27 c2h2 Acétylène, C 2 H 2 N
28 c2h4 Ethylène, C 2 H 4 N
29 c2h6 Ethane, C 2 H 6 N
30 co Monoxyde de carbone, CO N
31 o2 Oxygène, O 2 N
Gaz combustible dissous (une combinaison de gaz
32 dissolvedCombustibleGas combustibles tels que H 2 , CH 4 , C 2 H 2 , C 2 H 4 , C 2 H 6 , et/ou CO N
dans certains mélanges).
33 co2e Equivalent du dioxyde de carbone, CO 2 N
34 lead Plomb, Pb N
35 mercure Mercure, Hg N
36 ozone Ozone, O 3 N

37 pm10 Matière particulaire dont la taille maximale est 10 µm. N

38 pm25 Matière particulaire dont la taille maximale est 2,5 µm. N


39 sox Oxydes de soufre, SO X N
40 Weather Conditions climatiques ou météorologiques
Etat du compteur ou du dispositif terminal proprement dit.
Par exemple, cette énumération pourrait être utilisée en
41 Device N
association avec une énumération relative à la température
pour représenter la température interne d’un compteur.

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.2.8 Attribut n° 7, measurementKind

La "measurementKind" permet d'identifier "ce qui" est mesuré. Cela détaille davantage le
produit afin de fournir une catégorie de relevé. Cet attribut travaille conjointement avec
l'attribut "unités" de manière créative afin d'apporter des détails à l'unité de mesure. Par
exemple, "Energy" avec une unité de mesure de "kWh" indique à l'utilisateur que l'énergie
active est en cours de mesure, tandis qu'avec "kVAh" ou "kVArh", cela indique l'énergie
apparente et l'énergie réactive respectivement. "Power" peut être combiné de manière
similaire à différentes unités de mesure de puissance. La puissance de distorsion
("DistortionVoltAmperes") avec "kVA" est différente de "Power" avec "kVA". Plus
d'informations peuvent être consultées en étudiant les exemples à la fin de la présente
annexe. Les natures de mesure sont énumérées dans le Tableau C.10.

Tableau C.10 – Index measurementKind

Statut
Code Enumération Commentaires
normatif
0 none Non applicable N
2 apparentPowerFactor N
3 currency fonds N
4 current N
61968-9  CEI:2013 – 591 –

Statut
Code Enumération Commentaires
normatif
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

5 currentAngle N
6 currentImbalance N
7 date N
8 demand N
9 distance N
10 distortionVoltAmperes N
11 excitation N
12 énergie N
13 energizationLoadSide N
14 fan N
15 frequency N
16 Funds Doublon avec "currency" D
17 ieee1366ASAI N
18 ieee1366ASIDI N
19 ieee1366ASIFI N
20 ieee1366CAIDI N
21 ieee1366CAIFI N
22 ieee1366CEMIn N
23 ieee1366CEMSMIn N
24 ieee1366CTAIDI N
25 ieee1366MAIFI N
26 ieee1366MAIFIe N
27 ieee1366SAIDI N
28 ieee1366SAIFI N
31 lineLosses N
32 losses N
33 negativeSequence N
34 phasorPowerFactor N
35 phasorReactivePower N
36 positiveSequence N
37 power N
38 powerFactor N
40 quantityPower N
41 sag ou creux de tension N
42 gonflement N
43 switchPosition N
44 tapPosition I
45 tariffRate N
46 temperature N
47 totalHarmonicDistortion N
48 transformerLosses N
49 unipedeVoltageDip10to15 N
50 unipedeVoltageDip15to30 N
– 592 – 61968-9  CEI:2013

Statut
Code Enumération Commentaires
normatif
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

51 unipedeVoltageDip30to60 N
52 unipedeVoltageDip60to90 N
53 unipedeVoltageDip90to100 N
54 Voltage (rms) N
55 voltageAngle N
56 voltageExcursion N
57 voltageImbalance N
Clarifié par rapport à la CEI 61968-9:2009
58 volume
pour indiquer le volume de liquide N
59 zeroFlowDuration N
60 zeroSequence N
64 distortionPowerFactor N
81 frequencyExcursion Habituellement exprimé en tant que "count" N
90 applicationContext I
91 apTitle I
92 assetNumber I
93 bandwidth I
94 batteryVoltage N
95 broadcastAddress I
96 deviceAddressType1 I
97 deviceAddressType2 I
98 deviceAddressType3 I
99 deviceAddressType4 I
100 deviceClass I
101 electronicSerialNumber I
102 endDeviceID I
103 groupAddressType1 I
104 groupAddressType2 I
105 groupAddressType3 I
106 groupAddressType4 I
107 ipAddress I
108 macAddress I
109 mfgAssignedConfigurationID I
110 mfgAssignedPhysicalSerialNumber I
111 mfgAssignedProductNumber I
mfgAssignedUniqueCommunicationAddre
112
ss I
113 multiCastAddress I
114 oneWayAddress I
115 signalStrength I
116 twoWayAddress I
Déplacé ici depuis l'unité de mesure de
117 signaltoNoiseRatio
l'attribut n° 9 I
118 alarm I
119 batteryCarryover I
61968-9  CEI:2013 – 593 –

Statut
Code Enumération Commentaires
normatif
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

120 dataOverflowAlarm I
121 demandLimit N
Habituellement exprimé en tant que compte
122 demandReset
faisant partie d'un cycle de facturation N
123 diagnostic I
124 emergencyLimit I
125 encoderTamper I
126 ieee1366MomentaryInterruption N
127 ieee1366MomentaryInterruptionEvent N
128 ieee1366SustainedInterruption N
129 interruptionBehaviour I
130 inversionTamper I
131 loadInterrupt I
132 loadShed I
133 maintenance I
134 physicalTamper I
135 powerLossTamper I
136 powerOutage I
137 powerQuality I
138 powerRestoration I
139 programmed I
140 pushbutton N
141 relayActivation N
Habituellement exprimé sous forme de
142 relayCycle
compte N
143 removalTamper I
144 reprogrammingTamper I
145 reverseRotationTamper I
146 switchArmed I
147 switchDisabled I
148 falsification I
149 watchdogTimeout I
Facture du client pour la période de
150 billLastPeriod
facturation précédente (Devise) N
Facture du client, telle que connue jusqu'ici
151 billToDate dans la période de facturation présente
(Devise) N
Facture du client, partie d’une obligation
152 billCarryover précédente reportée d’une période de
facturation précédente. (Devise) N
153 connectionFee Frais mensuels de connexion au produit. I
154 audibleVolume Son I
155 volumetricFlow I
Utilisation la plus courante consistant à N
156 relativeHumidity exprimer des conditions climatiques ou
météorologiques

157 skyCover Degré de nébulosité. Utilisé pour exprimer N


des conditions climatiques ou
– 594 – 61968-9  CEI:2013

Statut
Code Enumération Commentaires
normatif
météorologiques
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

158 Voltage Non spécifié I


159 dcVoltage I
160 acVoltagePeak Vp=√2 × V eff I
161 acVoltagePeakToPeak Vpp=2 × Vp I

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

NOTE Cette deuxième édition de la CEI 61968-9 fait une distinction supplémentaire concernant le cadre de
référence relatif à la tension. L’énumération initiale pour “voltage” (tension) est désormais utilisée de manière
explicite pour identifier Volts RMS (Volts eff ). Ceci est justifié par le fait que le type le plus courant de mesure réalisé
entre les systèmes est une valeur en Volts RMS (Volts eff ). Cependant, il ne s’agit pas du seul moyen de mesure de
la tension. De nouvelles énumérations ont été créées afin de pouvoir également identifier les Volts-peak (Volts-
crête), les Volts-peak-to-peak (Volts-crête-à-crête), les Volts DC (Volts CC) et les formes d’onde de tension non
spécifiées. La Figure C.3 définit un certain nombre de mesures de la tension. En combinaison avec l’attribut
d’accumulation, il est possible de représenter une valeur de “indicating Volts RMS ” (Volts eff d’indication) qui est
mesurée sur de nombreux cycles, une valeur de “instantaneous Volts RMS ” (Volts eff instantanée) qui est mesurée
sur un seul cycle, ou une valeur de “instantaneous voltage” (tension instantanée) qui représente un échantillon
ponctuel unique sur la forme d’onde prélevé à un instant donné.

Légende

Anglais Français
Note: An “indicating Vrms” could identify an Note: Une valeur « Veff d’indication » peut identifier
average over time une moyenne sur le temps
Voltage Tension
Vpeak Vcrête
Vpeak-to-peak Vcrête-à-crête
Vrms Veff
Time Temps
Note: An “instantaneous voltage” could Note: Une "tension instantanée" pourrait identifier
identify a sample on a voltage waveform un échantillon sur une forme d’onde de tension

Figure C.3 – Mesures de tension


61968-9  CEI:2013 – 595 –

C.2.9 Attribut n° 8 interharmonicNumerator

Voir C.2.10.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C.2.10 Attribut n° 9, interharmonicDenominator

Les interharmoniques sont représentés sous forme de nombre rationnel avec un numérateur
et un dénominateur. Les harmoniques sont représentés en utilisant le même mécanisme et
identifiés en ayant un dénominateur de "1".

Ils sont représentés au moyen d'une formule qui est:

Interharmo nicNumerat or
Interharmo nic =
Interharmo nicDenomin ator

et

Harmonic = Interharmo nicNumerat or

où le Interharmo nicDenomin ator est égal à "1".

L'énumération des harmoniques ou interharmoniques est définie par un élément composé:

<interharmonic>::= <interharmonicNumerator> <interharmonicDenominator>

Le numérateur et les dénominateurs interharmoniques normatifs sont définis dans le


Tableau C.11. Les valeurs supplémentaires peuvent être créées librement à l'aide de cette
approche et seraient considérées en tant que valeurs "informatives" plutôt que "normatives".

Tableau C.11 – Enumérations des harmoniques et interharmoniques

Numérateur Dénominateur Statut


Enumération Commentaires
interharmonique interharmonique normatif
0 0 none Non applicable N
1 2 interharmonic1/2 Interharmonique de ½ N
1 1 fondamental fondamental N
2 1 harmonic2 deuxième harmonique N
3 1 harmonic3 troisième harmonique N
4 1 harmonic4 quatrième harmonique N
5 1 harmonic5 cinquième harmonique N
6 1 harmonic6 sixième harmonique N
7 1 harmonic7 septième harmonique N

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.2.11 Attribut n° 10 argumentNumerator

Voir C.2.12.

C.2.12 Attribut n° 11, argumentDenominator

Les éléments d'argument sont utilisés pour introduire des nombres dans la description de
l'unité de mesure où ils sont nécessaires. La définition prend en charge un nombre rationnel
– 596 – 61968-9  CEI:2013

avec un numérateur et un dénominateur. Cependant, la plupart des arguments utilisés dans la


pratique seront des entiers. Les entiers auront tous "1" comme dénominateur.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

numerator
argument =
denominato r

L'énumération des arguments est définie par un élément composé:

<argument>::= <numerator> <denominator>

Le numérateur et les dénominateurs normatifs sont définis dans le Tableau C.12. Les valeurs
supplémentaires peuvent être créées librement à l'aide de cette approche. Aux fins d'essai,
les valeurs non présentées dans le tableau seraient considérées comme étant des valeurs
"informatives" plutôt que "normatives".

Tableau C.12 – Enumérations des arguments

Statut
Numérateur Dénominateur Enumération Commentaires
normatif
0 0 none Non applicable N
1 2 n½ Moitié I
"Zéro" (pour les systèmes qui utilisent des N
0 1 n0 plans de numérotation basés sur zéro)
"Un" lorsque la mesure requiert un argument N
1 1 n1 tel que CEMI(n=1)
"Deux" lorsque la mesure requiert un N
2 1 n2 argument tel que CEMI(n=2)
"Trois" lorsque la mesure requiert un N
3 1 n3 argument tel que CEMI(n=3)
"Quatre" lorsque la mesure requiert un N
4 1 n4 argument tel que CEMI(n=4)
"Cinq" lorsque la mesure requiert un N
5 1 n5 argument
6 1 n6 Six N
7 1 n7 Sept N
8 1 n8 Huit N
9 1 n9 Neuf N
10 1 n10 Dix N
15 1 n15 Quinze N
30 1 n30 Trente N
45 1 n45 Quarante cinq N
60 1 n60 Soixante N
120 1 n120 2 × 60 = 120 N
155 1 n155 Cent cinquante-cinq N
240 1 n240 4 × 60 = 240 N
305 1 n305 Trois cent cinq. N
360 1 n360 6 × 60 = 360 N
480 1 n480 8 × 60 = 480 N
720 1 n720 12 × 60 = 720 N
720 60 n720/60 12 × 60 / 1 × 60 N
720 120 n720/120 12 × 60 / 2 × 60 N
720 180 n720/180 12 × 60 / 3 × 60 N
61968-9  CEI:2013 – 597 –

Statut
Numérateur Dénominateur Enumération Commentaires
normatif
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

720 240 n720/240 12 × 60 / 4 × 60 N


720 360 n720/360 12 × 60 / 6 × 60 N

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.2.13 Attribut n° 12, tou

L'élément Temps d'utilisation (TOU) est utilisé pour décrire toute attribution de la valeur à une
case TOU spécifique. Les énumérations TOU sont définies dans le Tableau C.13.

Tableau C.13 – Enumérations de temps d'utilisation

Code Enumération Commentaires Statut normatif


0 aucun Non applicable N
1 touA Utilisation dans la première case TOU définie N
2 touB Utilisation dans la deuxième case TOU définie N
3 touC Utilisation dans la troisième case TOU définie N
4 touD Utilisation dans la quatrième case TOU définie N
5 touE Utilisation dans la cinquième case TOU définie N
6 touF Utilisation dans la sixième case TOU définie N
7 touG Etc. I

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.2.14 Attribut n° 13, cpp

L'élément Tarification pour période critique (CPP) est utilisé pour décrire toute attribution de
la valeur à une case CPP spécifique. Bien que l'élément CPP soit généralement considéré
comme étant une forme spécialisée de l'élément TOU, il est séparé des énumérations TOU
afin de faciliter la modélisation. Les énumérations CPP sont définies dans le Tableau C.14.

Tableau C.14 – Enumérations des tarifications pour période critique

Statut
Code Enumération Commentaires
normatif
0 none Non applicable N
1 cppA Consommation associée à la tarification pour période critique A N
2 cppB Consommation associée à la tarification pour période critique B N
3 cppC Consommation associée à la tarification pour période critique C N
4 cppD Consommation associée à la tarification pour période critique D N
5 cppE Consommation associée à la tarification pour période critique E N
6 cppF Consommation associée à la tarification pour période critique F N
7 cppG Etc. I

N = Normative
– 598 – 61968-9  CEI:2013

Statut
Code Enumération Commentaires
normatif
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

I = Informative

D = Déconseillé depuis la dernière édition

C.2.15 Attribut n° 14, consumptionTier

La tarification de niveau de consommation fait référence à la méthode de facturation par


laquelle un certain "block" d'énergie est acheté (ou vendu) à un prix donné, puis le bloc
d'énergie suivant est acheté à un autre prix, etc., sur toute une période définie. Au début de
la période définie, la consommation est à l'origine égale à zéro et toute utilisation est
mesurée en fonction du ConsumptionTier1 (premier niveau de consommation). Si ce bloc
d'énergie est consommé avant la fin de la période, la consommation d'énergie est alors
recombinée en fonction du ConsumptionTier2 (deuxième niveau de consommation). Si ce bloc
d'énergie est consommé avant la fin de la période, la consommation d'énergie est alors
recombinée en fonction du ConsumptionTier3 (troisième niveau de consommation), et ainsi de
suite. A la fin de la période définie, l'accumulateur de consommation est réinitialisé et
l'utilisation au sein du ConsumptionTier1 redémarre.

Ceci s'oppose au "forfait" usuel pour la puissance, pour laquelle tous les achats sont
effectués à un prix fixé. Lorsque la tarification forfaitaire est utilisée, il convient de préciser un
consumptionTier "non applicable".

Les énumérations des niveaux de consommation sont définies dans le Tableau C.15.

Tableau C.15 – Enumérations des niveaux de consommation

Statut
Code Enumération Commentaires normatif
0 aucun Non applicable N
1 consumptionTier1 Utilisation dans la première case de consommation définie N
2 consumptionTier2 Utilisation dans la deuxième case de consommation définie N
3 consumptionTier3 Utilisation dans la troisième case de consommation définie N
4 consumptionTier4 Utilisation dans la quatrième case de consommation définie N
5 consumptionTier5 Utilisation dans la cinquième case de consommation définie N
6 consumptionTier6 Utilisation dans la sixième case de consommation définie N
Des niveaux de consommation supplémentaires peuvent être créés I
7 consumptionTier7
le cas échéant.

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

La tarification TOU ou CPP peut être utilisée conjointement à la tarification des niveaux de
consommation. Les exemples fournis dans le Tableau C.16 peuvent être utiles:

Tableau C.16 – Exemples de combinaison des énumérations


de TOU et de niveaux de consommation

Code de niveau de
Code TOU Commentaires
consommation

1 0 Période A de TOU avec tarification forfaitaire


1 1 Période A de TOU avec niveau de consommation 1
1 2 Période A de TOU avec niveau de consommation 2
61968-9  CEI:2013 – 599 –

Code de niveau de
Code TOU Commentaires
consommation
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

1 3 Période A de TOU avec niveau de consommation 3


2 1 Période B de TOU avec niveau de consommation 1
2 2 Période B de TOU avec niveau de consommation 2
2 3 Période B de TOU avec niveau de consommation 3
3 1 Période C de TOU avec niveau de consommation 1
3 2 Période C de TOU avec niveau de consommation 2
3 3 Période C de TOU avec niveau de consommation 3
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C.2.16 Attribut n° 15, phases

Les énumérations de phases de comptage sont décrites dans le Tableau C.17.

Tableau C.17 – Enumérations de phases

Position 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Statut
Code Enumération Commentaires S1 S2 A1 B1 C1 N1 A2 B2 C2 N2

Wye

Delta

haute
normatif

Ouvert
Branche

En réseau
Non Applicable à une phase
0 none 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 N
quelconque
16 phaseN Neutre 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 N
17 phaseNtoGnd Neutre vers le sol 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 N
32 phaseC Phase C 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 N
33 phaseCtoN Phase C à neutre 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 N
Courant ou tension de phase C
– 600 –

40 phaseCtoAv par rapport à la tension de 0 0 0 0 0 0 0 0 0 1 0 1 0 0 0 N


phase A
41 phaseCAtoN CA à neutre 0 0 0 0 0 0 0 0 0 1 0 1 0 0 1 N
64 phaseB Phase B 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 N
65 phaseBtoN Phase B à neutre 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 N
66 phaseBtoC Phase B à C 0 0 0 0 0 0 0 0 1 0 0 0 0 1 0 N
Courant ou tension de phase B
72 phaseBtoAv par rapport à la tension de 0 0 0 0 0 0 0 0 1 0 0 1 0 0 0 N
phase A
97 phaseBCtoN BC à neutre 0 0 0 0 0 0 0 0 1 1 0 0 0 0 1 N
128 phaseA Phase A 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 N
129 phaseAtoN Phase A à neutre 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 N
132 phaseAtoB Phase A à B 0 0 0 0 0 0 0 1 0 0 0 0 1 0 0 N
61968-9  CEI:2013

Courant de phase A par rapport


136 phaseAtoAv 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 N
à la tension de phase A

193 phaseABtoN AB à neutre 0 0 0 0 0 0 0 1 1 0 0 0 0 0 1 N


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Position 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Statut
Code Enumération Commentaires S1 S2 A1 B1 C1 N1 A2 B2 C2 N2

Wye

Delta

haute
normatif

Ouvert
Branche

En réseau
224 phasesABC Impliquant toutes les phases 0 0 0 0 0 0 0 1 1 1 0 0 0 0 0 N
61968-9  CEI:2013

225 phaseABCtoN ABC à neutre 0 0 0 0 0 0 0 1 1 1 0 0 0 0 1 N

256 s2 Phase S2 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 N

257 s2N Phase S2 à neutre 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 N

512 s1 Phase S1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 N

513 s1N Phase S1 à neutre 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 N

768 s12 Phase S1 à S2 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 N


– 601 –

769 s12N Phase S1, S2 à neutre 0 0 0 0 0 1 1 0 0 0 0 0 0 0 1 N

1248 threeWireWye Montage en étoile à 3 fils 0 0 0 0 1 0 0 1 1 1 0 0 0 0 0 N

1249 fourWireWye Montage en étoile à 4 fils 0 0 0 0 1 0 0 1 1 1 0 0 0 0 1 N

2272 threeWireDelta Montage en triangle à 3 fils 0 0 0 1 0 0 0 1 1 1 0 0 0 0 0 N

2273 fourWireDelta Montage en triangle à 4 fils 0 0 0 1 0 0 0 1 1 1 0 0 0 0 1 N

6369 fourWireHLDelta Triangle à branche haute à 4 fils 0 0 1 1 0 0 0 1 1 1 0 0 0 0 1 N

10465 fourWireOpenDelta Triangle ouvert à 4 fils 0 1 0 1 0 0 0 1 1 1 0 0 0 0 1 N

17153 networked Compteur en réseau 1 0 0 0 0 1 1 0 0 0 0 0 0 0 1 N

NOTE 1 Les valeurs des codes ont été calculées par:

Code = Networked × 214 + Open × 2 13 + HighLeg × 212 + Delta × 2 11 + Wye × 210 + S 1 × 29 + S 2 × 28 + A 1 × 27 + B 1 × 2 6 + C 1 × 25 + N 1 × 24 + A 2 × 2 3 + B 2 × 22 + C1 × 21 + N 2


NOTE 2 Les vecteurs directionnels (tels que V AB vs. V BA ) sont créés dans le code de phase en invoquant la phase impliquée (de gauche à droite dans la matrice) dans
l'ordre dans lequel ils sont décrits dans l'énumération (de gauche à droite à la lecture).
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Lorsque le courant est mesuré, il est souvent simplement indiqué un conducteur monophasé tel que:

• A
• B
• C
• N

La "phase" dite du neutre vers le sol peut être utilisée pour décrire le courant circulant à partir du fil neutre vers le sol. Dans ce cas, sélectionner N 1 et
N 2 . Quand seul le neutre est sélectionné, choisir N 1 . Dans tous les autres cas, lorsqu'il est fait référence au neutre, sélectionner N 2 . Le principal objectif
est la lisibilité. Il convient que lesdites règles donnent la lisibilité nécessaire.

Lorsque la tension est mesurée, elle peut contenir une simple description du conducteur de phase ou, si elle est mesurée par rapport à quelque chose,
une indication de la mesure comme étant "ligne à neutre" (c'est-à-dire entre phase et neutre) ou "ligne à ligne" (c'est-à-dire entre phases). Les mesures
de tension communes comprennent:

• A
• B
– 602 –

• C
• AN
• BN
• CN
• AB
• BC
• CA
• ABC

Lorsque des angles de phase sont mesurés, le résultat est habituellement rapporté à une référence fixe telle que la phase de tension A. Le mot "angle" a
déjà été décrit dans un champ précédent. Ce champ peut donc contenir une désignation d'angle telle que:

• A courant A volts
61968-9  CEI:2013

• B courant A volts
• C courant A volts
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Où il est admis que la première phase énumérée décrit la phase de courant ou de tension en cours de mesure et que la seconde phase (la lettre "A")
décrit par rapport à quoi elle est mesurée (phase de tension A). Sachant que le fait que la mesure soit un angle peut être déterminé à partir du contexte
(fourni par l'unité de mesure) et que le point de référence est toujours la seconde phase, il n'est pas nécessaire de fournir d'autres indications dans le
libellé littéral de la phase. Cela permet d'utiliser souvent le même code (tel que "Phase-CA") comme un descripteur de tension entre phases, un
descripteur d'angle de phase de tension ainsi qu'un descripteur d'angle de phase de courant.

Les tensions résidentielles ou autres tensions biphasées secondaires peuvent être identifiées par "S1" ou "S2". Ces étiquettes peuvent être utilisées
61968-9  CEI:2013

lorsque les noms "ABC" des phases qui alimentent le service sont inconnus ou non importants.

Les différents câblages du réseau polyphasé peuvent être identifiés en tant que:

• Wye
• Delta
• Triangle à branche haute
• Triangle ouvert
• En réseau
– 603 –

L'utilisation de 3 ou 4 fils peut être déterminée en comptant simplement le nombre de phases (y compris neutre) impliquées dans le service.
– 604 – 61968-9  CEI:2013

C.2.17 Attribut n° 16, multiplicateur


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Le codage du ReadingType propose un champ pour décrire un multiplicateur de puissance de


dix en fonction de la valeur des données. Ce n'est pas tout à fait identique au préfixe SI
habituel, bien que le résultat soit le même dans de nombreux cas. L'utilisateur devra décider
quel symbole affichable approprié est basé sur les dimensions de l'unité de mesure. Les
énumérations de multiplicateurs sont décrites dans le Tableau concernant les unités de
2
mesure à une seule dimension (par exemple, "V" et non "V "). La valeur d'index représente la
puissance de dix.

Tableau C.18 – Enumérations de puissances de dix

Symbole affichable
pour les unités de
Code Commentaires Statut normatif
mesure à une seule
dimension
–24 y yocto = ×10 –24 N
–21 z zepto = ×10 –21 N
–18 a atto = ×10 –18 N
–15 f femto = ×10 –15 N
–12 p pico = ×10 –12 N
–9 n nano = ×10 –9 N
–6 µ micro = ×10 –6 N
–3 m milli= ×10 –3 N
–2 c centi = ×10 –2 N
–1 d deci = ×10 –1 N
0 Non applicable ou "×1" N
1 da deca = ×10 1 N
2 h hecto = ×10 2 N
3 k kilo = ×10 3 N
6 M Mega = ×10 6 N
9 G Giga = ×10 9 N
12 T Tera = ×10 12 N
15 P Peta = ×10 15 N
18 E Exa = ×10 18 N
21 Z Zetta = ×10 21 N
24 Y Yotta = ×10 24 N

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

Il convient de rappeler que ce multiplicateur de puissance de dix ne fonctionne pas de la


même manière que le préfixe SI. Le préfixe SI est considéré comme faisant partie de l'unité
de mesure. Un multiplicateur de puissance de dix ne fait pas partie de l'unité de mesure.
Lorsqu' un préfixe SI est utilisé, il est compris que "10 –3 " est représenté par "milli" et qu'un
3
mm est identique à (mm) 3 , ce qui est la même chose que (0,001 m) 3 ou 10 –9 m 3 . Ce n'est
pas le même résultat que 0,001 × m 3 (ce que donne un multiplicateur de puissance de dix).

Les règles d'utilisation des préfixes SI peuvent être consultées dans la CEI 60050-112:2010,
02-03.
61968-9  CEI:2013 – 605 –

Lorsque l'unité de mesure décrite est un rapport rendu sous la forme d'une quantité sans
dimension (comme une concentration), il arrive parfois d'afficher un symbole autre que le
symbole avec préfixe de mesure standard. Cependant, la convention moderne consiste
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

à utiliser les symboles à préfixe SI devant le rapport sans dimension décrit. Par exemple, il
convient de décrire une concentration ppm par volume ("ppmv") plutôt avec l'expression
"µL/L". Quelques scalaires historiques sans dimension sont fournis dans le Tableau C.19 pour
référence.

Tableau C.19 – Enumérations de multiplicateurs de concentration historiques

Symbole Statut
Code Commentaires
affichable normatif
0 PU Par unité = ×1 = 10 0 . I

–2 % pourcentage = ×0,01 = ×10 –2 I

–3 ‰ Pour mille = ×0,001 = ×10 –3 I

–6 ppm parts par million, ×0,000 001 = ×10 –6 I

–9 ppb parts par milliard, ×0,000 000 001 = ×10 –9 I

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C.2.18 Attribut n° 17, unité

Dans la 61968-9:2009, une unité de mesure "ppm" était prise en charge. Dans cette édition, cela a été déplacé de l'attribut d'unité de mesure à l'attribut
de multiplicateur de puissance de dix et certaines unités de mesure de "concentration" ont été introduites.

Les Tableaux C.20 à C.27 décrivent les énumérations d'unités de mesure. Elles sont organisées en fonction de leurs relations avec les unités de
mesure SI. Les unités SI sont les unités de mesure préférentielles, mais en tant que norme internationale, il est compris que d'autres unités de mesure
doivent également être prises en charge dans certaines régions.

Dans ces tableaux, la colonne "code" est une valeur unique. Le "statut normatif" indique si le "code" est normatif ou informatif. La colonne "grandeur"
indique la catégorie de mesure. Le "nom d'unité" donne le nom officiel de l'unité, ainsi que des commentaires potentiels concernant son utilisation ou sa
relation vis-à-vis des autres unités. La colonne "symbole" indique dans la majorité des cas le symbole affichable officiel de l'unité. Lorsqu'il y a eu des cas
de conflit causés par la combinaison de différents systèmes de mesure, la préférence est donnée à l'unité de mesure SI. (Cela est arrivé dans le cas de
rad (rd) et rod (rd)). La colonne "énumération" crée une chaîne unique qui pourrait être utilisée par les modélisateurs CIM afin de saisir une valeur de
chaîne pour l'unité. L'énumération a été créée selon les règles suivantes:

• Une transformation inférieure dite "camel-case" de la colonne de symbole est tentée. Tous les espaces sont supprimés du symbole pour créer
l'énumération.
• Le symbole défini est limité aux caractères alphanumériques.
• Les symboles "-", "(", et ")" sont supprimés.
– 606 –

• Le symbole "/" est remplacé par la chaîne "Par".


• Le symbole "°" est remplacé par la chaîne "Deg".
• D'autres symboles spéciaux tels que “¤”, “’”, “µ” et “ħ” sont remplacés par d'autres chaînes textuelles alphas.
• Les chiffres ne sont pas autorisés en tant que premier caractère de l'énumération.
• Le texte à indice ou à exposant est utilisé comme texte normal dans l'énumération (si les conflits sont évitables).
• Si deux symboles différents donnent la même énumération (à cause des règles de capitalisation), alors l'une d'elles est modifiée (en donnant la
"
préférence aux unités SI de base). Des exceptions ont été créées pour les symboles "A", "B", "G", "H", "ħ", "M", "m e , "S" et "T".
61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.20 – Unités de mesure SI de base

Nom d'unité Statut


Code Grandeur Symbole Enumération
(et commentaires) normatif
2 Longueur mètre m m N
3 Masse gramme g g N
5 Courant ampère A a N
61968-9  CEI:2013

6 Température Kelvin K degK I


Quantité de
mole mol mol I
7 substance
8 Intensité lumineuse candela cd cd I
27 Durée seconde s s N

N = Normative

I = Informative
– 607 –

D = Déconseillé depuis la dernière édition

NOTE L'orthographe britannique "metre" et l'orthographe américaine "meter" sont équivalentes.

Tableau C.21 – Unités de mesure SI dérivées ayant des noms spéciaux

Code Grandeur Nom d'unité (et commentaires) Symbole affichable Enumération Statut normatif
10 Angle plan Radian (m/m) rad rad N
11 Angle solide Stéradian (m 2 /m 2 ) sr sr I
21 Dose absorbée Gray (J/kg) Gy gy I
22 Radioactivité Becquerel (1/s) Bq bq I
23 Température Degrés Celsius °C degC N
24 Equivalent de dose Sievert (J/kg) Sv sv I
Capacitance
25 Farad (C/V) F f N
électrique
26 Charge électrique Coulomb (A seconde) C c I
28 Inductance électrique Henry (Wb/A) H h N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Code Grandeur Nom d'unité (et commentaires) Symbole affichable Enumération Statut normatif
29 Potentiel électrique Volt (W/A) V v N
30 Résistance électrique Ohm (V/A) Ω ohm N
31 Joule d'énergie (N·m = C·V = W·s) J j N
32 Force newton (kg m/s 2 ) N n N
33 Fréquence Cycles par seconde ou (1/s) Hz hz N
34 Puissance lumineuse (lm/m 2 ) lx lx I
35 Flux lumineux lumen (cd sr) lm lm I
36 Flux magnétique Weber (V s) Wb wb I
Densité du flux
37 Tesla (Wb/m 2 ) T t I
magnétique
Watt. Par définition, un Watt est
égal à une Joule par seconde.
La puissance électrique peut
être constituée de composants
réels et réactifs. La partie réelle
38 Puissance réelle W w N
de la puissance électrique (I 2 R),
Vicosθ est exprimée en Watts.
(Voir également la puissance
apparente et la puissance
– 608 –

réactive).
Pascal (N/m 2 )
NOTE La mesure de la
39 Pression pression absolue ou relative est Pa pa N
implicite avec cette entrée. Voir
ci-après pour des formes plus
explicites.
Conductance
53 Siemens (A / V = 1 / Ω) S siemens N
électrique
155 Pression Pascal, pression absolue PaA paA N
140 Pression Pascal, pression manométrique PaG paG N
158 Activité catalytique katal = mol / s kat kat I
61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

NOTE L'orthographe britannique "litre" et l'orthographe américaine "liter" sont équivalentes.


61968-9  CEI:2013

Tableau C.22 – Unités de mesure SI dérivées sans nom spécial

Symbole Statut
Code Grandeur Nom d'unité (et commentaires) Enumération
affichable normatif
tours par seconde
4 Vitesse rotationnelle rev/s revPerS I
(Note: comparer aux cycles par seconde, Hz)
– 609 –

41 Surface mètre carré m2 m2 N


42 Volume mètre cube m3 m3 N
43 Vélocité mètre par seconde (m/s) m/s mPerS N
44 Accélération mètre par seconde carré m/s 2 mPerS2 I
45 Débit volumétrique mètre cube par seconde m 3 /s m3PerS N
46 Efficacité énergétique mètre/mètre cube m/m 3 mPerM3 I
kilogramme mètre (kg·m) (premier moment
statique)
47 Moment de masse gm gM I
NOTE 1 Les utilisateurs doivent fournir le
préfixe "k" pour obtenir "kg m".
gramme/mètre cube
48 Densité NOTE 2 Les utilisateurs doivent fournir le g/m 3 gPerM3 I
multiplicateur de préfixe "k" pour former kg/ m 3
49 Viscosité mètre carré/seconde m 2 /s m2PerS I
50 Conductivité thermique Watt/mètre Kelvin W/(m K) wPerMK I
51 Capacité calorimétrique Joule/Kelvin J/K jPerK I
54 Vélocité angulaire radians par seconde rad/s radPerS I
Voltampère (voir également puissance réelle et
61 Puissance apparente VA vA N
puissance réactive).
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Symbole Statut
Code Grandeur Nom d'unité (et commentaires) Enumération
affichable normatif
Voltampère réactive. Le composant "réactif" ou
"imaginaire" de la puissance électrique (VISinθ).
(Voir également la puissance réelle et la
puissance apparente).
NOTE 3 Différents modèles de compteur
utilisent différentes méthodes pour obtenir leurs
63 Puissance réactive résultats. Certains compteurs peuvent calculer VAr vAr N
la puissance réactive comme une valeur
arithmétique, alors que d’autres la calculent de
manière vectorielle. Il convient que le client de
données détermine la méthode d’utilisation et le
caractère approprié de la mesure pour les
besoins prévus.
66 Volt secondes Volt seconds (Ws/A) Vs vS N
67 Volts carrés Volt carré (W 2 /A 2 ) V² v2 N
68 A secondes A secondes As aS N
69 A au carré Ampère carré A2 A2 N
70 Durée A au carré Ampère carré seconde A2s a2S I
71 Energie apparente Volt Ampère Heures VAh vAH N
– 610 –

72 Energie réelle Watt Heures Wh wH N


73 Energie réactive Volt Ampère Heures réactif VArh vArH N
74 Flux magnétique Volt par Hertz V/Hz vPerHz I
Taux de changement de
75 Hertz par seconde Hz/s hzPerS I
la fréquence
kg m 2 (Deuxième moment statique,
communément appelé le moment d'inertie)
78 Moment de masse gm 2 gM2 I
NOTE 4 Les utilisateurs doivent fournir le
préfixe "k" pour obtenir "kg m 2 ".
81 Taux de rampe Watts par seconde W/s wPerS I
82 Débit volumétrique litre par seconde L/s lPerS I
100 Quantité de puissance Q Q q I
101 Quantité d'énergie Qh Qh qh I
61968-9  CEI:2013

102 résistivité Ohm mètre, ρ (rho) Ωm ohmM I


intensité du champ magnétique, Ampère par
103 A/m A/m aPerM I
mètre
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Symbole Statut
Code Grandeur Nom d'unité (et commentaires) Enumération
affichable normatif
104 volt-heure carrée Volt-heures-carrées V2h v2H I
105 ampère-heure carrée Ampère-heure carrée A2h a2H I
106 Ampère-heures Ampère-heures Ah aH I
107 Wh/m 3 energy per volume Wh/m 3 wHPerM3 I
108 Horodatage heure et date au format ISO 8601 timeStamp timeStamp N
61968-9  CEI:2013

115 Kh-Wh constante de mesure d'énergie active Wh/rev wHPerRev N


116 Kh-VArh constante de mesure d'énergie réactive VArh/rev vArHPerRev N
117 Kh-Vah constante de mesure d'énergie apparente VAh/rev vAHPerRev N
125 Débit volumétrique mètre cube par heure m 3 /h m3PerH N
3
m
126 Débit volumétrique mètre cube compensé par heure m3CompensatedPerH N
(compensé) /h

m 3 (non
127 Débit volumétrique mètre cube non compensé par heure m3UncompensatedPerH N
– 611 –

compensé) /h

137 Débit volumétrique litre par heure L/h lPerH N


L (non
139 Débit volumétrique litre (non compensé) par heure LUncompensatedPerH N
compensé) /h

138 Débit volumétrique litre (compensé) par heure L (compensé) /h LCompensatedPerH N


161 Quantité de puissance Q mesuré à 45º Q 45 q45 I
162 Quantité de puissance Q mesuré à 60º Q 60 q60 I
163 Quantité d'énergie Qh mesuré à 45º Q 45 h q45H I
164 Quantité d'énergie Qh mesuré à 60º Q 60 h q60H I
165 Energie spécifique Joule / kg J/kg jPerKg I
mètre cube, avec la valeur non compensée m 3 (non
166 Volume m3Uncompensated N
correspondant aux effets climatiques. compensé)

mètre cube, avec la valeur compensée


167 Volume m 3 (compensé) m3Compensated N
correspondant aux effets climatiques.
173 Numéro d'onde mètre réciproque, (1/m) m –1 m1 I
174 Volume spécifique mètre cube par kilogramme, v m 3 /kg m3PerKg I
175 Viscosité dynamique Pascal seconde Pa s paS I
176 Moment de force Newton mètre Nm nM I
177 Tension superficielle Newton par mètre N/m nPerM I
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Symbole Statut
Code Grandeur Nom d'unité (et commentaires) Enumération
affichable normatif
178 Accélération angulaire radian par seconde carrée rad/s 2 radPerS2 I
Densité de flux
thermique
179 Watt par mètre carré W/m 2 wPerM2 I
, éclairement
énergétique
Capacité thermique
180 spécifique, entropie Joule par kilogramme kelvin J/(kg K) jPerKgK I
spécifique
181 densité d'énergie Joule par mètre cube J/m 3 jPerM3 I
intensité du champ
182 Volt par mètre V/m vPerM I
électrique
densité de la charge
183 Coulomb par mètre cube C/m 3 cPerM3 I
électrique
densité de la charge
184 Coulomb par mètre carré C/m 2 cPerM2 I
superficielle
185 permittivité Farad par mètre F/m fPerM I
186 perméabilité Henry par mètre H/m hPerM I
187 énergie molaire Joule par mole J/mol jPerMol I
– 612 –

entropie molaire,
188 capacité Joule par mole kelvin J/(mol K) jPerMolK I
thermique molaire
189 exposition (rayons x) Coulomb par kilogramme C/kg cPerKg I
190 débit de dose absorbée Gray par seconde Gy/s gyPerS I
191 intensité radiante Watt par stéradian W/sr wPerSr I
192 luminance Watt par mètre carré stéradian W/(m 2 sr) wPerM2Sr I
concentration d'activité
193 katal par mètre cube kat/m 3 katPerM3 I
catalytique
280 Volt-heure Volt-heures Vh VH N

N = Normative

I = Informative
61968-9  CEI:2013

D = Déconseillé depuis la dernière édition


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.23 – Unités de mesure non SI acceptées à utiliser avec le système d'unités international

Statut
Code Grandeur Nom d'unité (et commentaires) Symbole Enumération
normatif
159 Durée minute = 60 s min min I
160 Durée heure = 60 min = 3 600 s h hr I
195 Durée jour = 24 h = 86 400 s d d I
61968-9  CEI:2013

9 Angle plan degré º deg N


196 Angle plan minute ‘ angleMin I
197 Angle plan seconde “ angleSec I
198 Surface hectare ha ha I
134 Volume litre = dm 3 = m 3 /1000 L l N
"tonne" ou "tonne métrique" (1 000 kg =
199 masse t tonne I
1 Mg)

N = Normative
– 613 –

I = Informative

D = Déconseillé depuis la dernière édition

NOTE L'orthographe britannique "litre" et l'orthographe américaine "liter" sont équivalentes.


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.24 – Unités de mesure sans dimension et de concentration

Statut
Code Grandeur Nom d'unité (et commentaires) Symbole Enumération
normatif
0 N/A aucun (non applicable) aucun N

sans dimension

NOTE 1 Cette définition du facteur de puissance ne


s’applique
qu’aux systèmes équilibrés. Voir l’autre définition au
Facteur de
65 code 153. cosθ cosTheta N
puissance
NOTE 2 Tenir compte des différentes conventions de
signe appliquées entre la CEI et l’EEI. Il est supposé
que le consommateur des données comprend le type de
compteur utilisé et la convention de signe appliquée par
l’entreprise de distribution.
Bel
Ecart NOTE 3 Les utilisateurs doivent combiner cette unité
79 B bel I
logarithmique au préfixe de multiplicateur "d" pour former décibels
(dB)
statut, où:
– 614 –

"1" = "vrai", "sous tension", "on", "élevé", "configuré";


109 Etat "0" = "faux", "hors tension", "off", "faible", "supprimé" status status N
NOTE 4 Une valeur booléenne est préférentielle mais
d'autres valeurs peuvent être prises en charge
Quantité de
111 Valeur de compteur nombre nombre N
substance
Ecart
logarithmique Bel-mW, normalisé en 1 mW. NOTE Pour former
113 Bm bm N
de la puissance "dBm", combiner "Bm" au multiplicateur "d".
de signal
Valeur
114 Valeur codée code code N
d'application
118 EndDeviceEvent Valeur à interpréter comme EndDeviceEventCode meCode meCode N
Le rapport du volume d'un soluté divisé par le volume de
la solution.
61968-9  CEI:2013

143 Concentration NOTE 5 Les utilisateurs peuvent avoir besoin d'utiliser L/L lPerL N
un préfixe tel que "µ" pour exprimer une grandeur telle
que "µL/L")
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Statut
Code Grandeur Nom d'unité (et commentaires) Symbole Enumération
normatif
Le rapport de la masse d'un soluté divisée par la masse
de la solution.
144 Concentration NOTE 6 Les utilisateurs peuvent avoir besoin d'utiliser g/g gPerG N
un préfixe tel que "µ" pour exprimer une grandeur telle
que "µg/g")
La quantité de concentration de la substance, (c), la
145 Concentration quantité de solvant en moles divisée par le volume de la mol/m³ molPerM3 I
61968-9  CEI:2013

solution en m³.
Fraction molaire (χ), le rapport de la quantité molaire
146 Concentration mol/mol molPerMol I
d'un soluté divisée par la quantité molaire de la solution.
Molalité, la quantité de soluté en moles et la quantité de
147 Concentration mol/kg molPerKg I
solvant en kilogrammes.
148 Longueur Taux de longueur m/m mPerM I
Rapport de temps
NOTE 7 Les utilisateurs peuvent avoir besoin de
149 Durée s/s sPerS N
fournir un préfixe tel que "µ" pour afficher des taux tels
– 615 –

que "µs/s"
Dérivée de fréquence
NOTE 8 Les utilisateurs peuvent avoir besoin de
150 Fréquence Hz/Hz hzPerHz N
fournir un préfixe tel que "m" pour afficher des taux tels
que "mHz/Hz"
Rapport de tensions
NOTE 9 Les utilisateurs peuvent avoir besoin de
151 Tension V/V vPerV N
fournir un préfixe tel que "m" pour afficher des taux tels
que "mV/V"
Rapport d'ampérages
NOTE 10 Les utilisateurs peuvent avoir besoin de
152 Courant A/A aPerA I
fournir un préfixe tel que "m" pour afficher des taux tels
que "mA/A"
PF, le rapport de la puissance active à la puissance
apparente.
NOTE 11 La convention de signe utilisée pour le
Facteur de facteur de puissance diffère entre les compteurs CEI et
153 les compteurs EEI (ANSI). Il est supposé que les W/VA wPerVA I
puissance
consommateurs des données comprennent le type de
compteur utilisé et conviennent de la convention de
signe appliquée dans une entreprise de distribution
donnée.
Quantité de
154 Tours rev rev I
rotation
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Statut
Code Grandeur Nom d'unité (et commentaires) Symbole Enumération
normatif
Rapport de puissance
Puissance du NOTE 12 Les utilisateurs peuvent avoir besoin de
168 W/W wPerW I
signal fournir un préfixe tel que "m" pour afficher des taux tels
que "mW/W"
Index de
170 n n refractiveIndexN I
réfraction
Perméabilité relativePermeabilit
171 µr µr I
relative yMur
Ecart
172 néper Np np I
logarithmique
Humidité relative exprimée comme le rapport de la
pression partielle de la vapeur d’eau dans le mélange
281 Humidité Φ RelativeHumidity N
air-eau à la pression de vapeur saturée de l’eau à la
température spécifiée.
Rapport entre la partie du ciel couverte et l'ensemble de
282 Nébulosité SkyCover SkyCover N
la voûte céleste

N = Normative

I = Informative
– 616 –

D = Déconseillé depuis la dernière édition


61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.25 – Unités non SI dont les valeurs dans les unités SI doivent être obtenues expérimentalement

Code Grandeur Nom d'unité (et commentaires) Symbole Enumération Statut normatif
200 énergie électronvolt (1 eV = 1,602 176 × 10 –19 J) eV eV I
201 masse dalton (1 Da = 1,660 538 × 10 –27 kg) Da da I
202 masse unité unifiée de masse atomique (1u = 1 Da) u u I
unité astronomique (1ua =
203 longueur ua ua I
1,495 978 × 10 11 m)
61968-9  CEI:2013

unité naturelle de vitesse (vitesse de la


204 vitesse lumière dans le vide) c0 c0 I
= 299 792 458 m/s
unité naturelle d'action (constante réduite de
205 action Planck) ħ nuH I
= 1,054 571 × 10 –34 J s
unité naturelle de masse (masse de
206 masse l'électron) me nuMe I
– 617 –

= 9,109 382 × 10 –31 kg


nuHPerNuMeC
207 durée unité naturelle de temps ħ/(m e c 0 2 ) I
02
unités atomiques de charge (charge
208 charge élémentaire) e auE I
= 1,602 176 × 10 –19 C
unités atomiques de masse (masse de
209 masse l'électron) me auMe I
= 9,109 382 × 10 –31 kg
unité atomique d'action (constante réduite
210 action de Planck) ħ auH I
= 1,054 571 × 10 –34 J s
unité atomique de longueur, bohr (rayon de
211 longueur Bohr) a0 auA0 I
= 0,529 177 × 10 –10 m
unité atomique d'énergie, hartree
212 énergie Eh auEh I
= 4,359 744
213 durée unité atomique de temps ħ/Eh auHPerAuEh I
Légende:
N = Normative
I = Informative
D = Déconseillé depuis la dernière édition
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.26 – Autres unités de mesure non SI

Nom d'unité Statut


Code Grandeur Symbole Enumération
(et commentaires) normatif
76 Nombre de caractères caractères char char N
77 Débit de données caractères par seconde char/s charPerSec I
Argent en général
Note: les unités monétaires
80 Unité monétaire ¤ argent I
spécifiques sont identifiées
par la classe de devise.
119 Volume pied cube ft 3 ft3 N
pied cube compensé
120 Volume à cause des effets ft 3 (compensé) ft3Compensated N
climatiques
pied cube non compensé à
121 Volume ft 3 (non compensé) ft3Uncompensated N
cause des effets climatiques
122 Débit volumétrique pied cube par heure ft 3 /h ft3PerH N
pied cube compensé par
123 Débit volumétrique ft 3 (compensé)/h ft3CompensatedPerH N
heure
– 618 –

pied cube non compensé ft 3 (non


124 Débit volumétrique ft3UncompensatedPerH N
par heure compensé)/h
Gallon US
128 Volume US gal uSGal N
(1 gal = 231 in 3 = 128 fl oz).
129 Débit volumétrique Gallon US par heure US gal/h uSGalPerH N
130 Volume Gallon impérial imp gal impGal N
131 Débit volumétrique Gallon impérial par heure imp gal/h impGalPerH N
132 énergie Unité thermique britannique BTU btu N
133 Puissance BTU par heure BTU/h btuPerH N
Livre par pouce carré,
141 Pression psiA psiA I
absolu
Livre par pouce carré,
142 Pression psiG psiG I
manométrique
61968-9  CEI:2013

Litre, avec la valeur non


156 Volume compensée correspondant L (non compensé) lUncompensated N
aux effets climatiques.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Nom d'unité Statut


Code Grandeur Symbole Enumération
(et commentaires) normatif
Litre, avec la valeur
157 Volume compensée correspondant L (compensé) lCompensated N
aux effets climatiques.
169 énergie Thermique therm therm N
214 Pression bar (1 bar = 100 kPa) bar bar I
millimètre de mercure
61968-9  CEI:2013

215 Pression mmHg mmHg I


(1 mmHg ≈ 133,3 Pa)
216 Longueur ångström (1Å = 10 –10 m) Å angstrom I
mille nautique
217 Longueur M nmi I
(1 M = 1 852 m)
barn
218 Surface b barn I
(1 b = 100 fm 2 = 10 –28 m 2 )
nœud
219 Vitesse kn kn I
(1 kn = 1 852/3 600) m/s
– 619 –

220 Activité curie (1 Ci = 3,7 × 10 10 Bq) Ci ci I

roentgen
221 exposition R r I
(1 R = 2,58 × 10 –4 C/kg)
222 dose absorbée rad (1 rd = 1 cGy) rd doseRad I
223 équivalent de dose rem (1 rem = 10 –2 Sv) rem rem I
224 longueur pouce in in I
225 longueur pied (1 ft = 12 in) ft ft I
226 longueur rod (1 rod = 16,5 ft) rod rod I
227 longueur furlong (1 fur = 660 ft) fur fur I
mille (1 mille terrestre =
8 fur
228 longueur mi mi I
= 80 chaînes = 320 rods
= 5 280 pieds)
229 surface pied carré (1 ft 2 = 144 in 2 ) ft 2 ft2 I
2 2 2
230 surface yard carré (1 yd = 9 ft ) yd yd2 I
rod carré (1 rod 2 =
231 surface rod 2 rod2 I
272,25 ft 2 )
acre (1 acre = 160 rd 2
232 surface acre acre I
= 43 560 ft 2 )
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Nom d'unité Statut


Code Grandeur Symbole Enumération
(et commentaires) normatif
mille carré
233 surface mi 2 mi2 I
(1 mi 2 = 640 acres)
section de terrain
234 surface (1 mi 2 = 1 section de section de terrain sectionOfLand I
terrain)
canton
235 surface canton canton I
(1 canton = 6 milles carrés)
237 Volume yard cube (1 yd 3 = 27 ft 3 ) yd 3 yd3 I
238 longueur chaînon (1 li = 0,66 ft) li li I
chaîne (1 ch =
239 longueur 100 chaînons ch ch I
= 4 rods = 66 ft)
Pinte liquide US
240 Volume (1 pt = 28,875 in 3 = 128 fl US liq pt uSLiqPt I
dr)
Quart liquide US
241 Volume US liq qt uSLiqQt I
(1 qt = 2 pt)
Drachme liquide des
242 Volume systèmes de mesure de fl dr ap flDrAp I
– 620 –

pharmacie
Once liquide des systèmes
243 Volume de mesure de pharmacie fl oz ap flOzAp I
(1 fl oz ap = 8 fl dr ap)
Pinte sèche US
244 Volume US dry pt usDryPt I
(1 pt = 67,2 in 3 )
Quart sec US
245 Volume US dry qt usDryQt I
(1 qt = 2 pintes)
246 Volume US peck (1 pk = 8 qt) US pk usPk I
247 Volume Hectolitre US (1 bu = 4 pk) US bu usBu I
grain (1 grain = 1/7 000
avdp lb)
NOTE Le "grain" est
248 Masse identique dans les unités de gr gr I
masse des systèmes
61968-9  CEI:2013

avoirdupois, troy
et de pharmacie.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Nom d'unité Statut


Code Grandeur Symbole Enumération
(et commentaires) normatif
Drachme avoirdupois
(1 Avdp dr = 27-11/32 gr)
NOTE L'abréviation "dr"
peut être utilisée s'il n'y a
249 Masse aucune possibilité que la avdp dr avdpDr I
drachme avoirdupois ne soit
confondu avec la drachme
61968-9  CEI:2013

des systèmes troy ou de


pharmacie.
Once avoirdupois
(1 Avdp oz = 16 Avdp dr)
NOTE L'abréviation "oz"
peut être utilisée s'il n'y a
250 Masse aucune possibilité que avdp oz avdpOz I
l'once avoirdupois ne soit
confondue avec l'once des
systèmes troy ou de
pharmacie.
– 621 –

Livre avoirdupois
(1 lb = 16 oz)
NOTE Bien que le terme
"livre" soit couramment
utilisé dans plusieurs pays
simplement en tant que
"livre (lb)", le terme
historique "avoirdupois" est
ajouté pour apporter du
251 Masse contexte et le distinguer avdp lb avdpLb I
dans cette définition des
systèmes de mesure troy et
de pharmacie qui utilisent
les mêmes noms.
L'abréviation "lb" peut être
utilisée à la place de "avdp
lb" si aucune confusion
n'est possible avec la livre
nommée dans lesdits autres
systèmes.
Quintal avoirdupois
252 Masse short cwt shortCwt I
(1 cwt = 100 lbs)
Tonne avoirdupois
253 Masse tonne courte shortTon I
(1 tonne courte = 2 000 lbs)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Nom d'unité Statut


Code Grandeur Symbole Enumération
(et commentaires) normatif
Quintal brut ou long
254 Masse avoirdupois cwt long longCwt I
(1 cwt long = 112 lbs)
Tonne brute ou longue
255 Masse avoirdupois tonne longue longTon I
(1 long ton = 20 long cwt)
Pennyweight troy
256 Masse dwt dwt I
(1 dwt = 24 grains)
Once troy
257 Masse oz t ozT I
(1 oz t = 20 dwt)
258 Masse Livre troy (1 lb t = 12 oz t) lb t lbT I
Scrupule des systèmes de
259 Masse mesure de pharmacie s ap sAp I
(1 s ap = 20 grains)
Drachme des systèmes de
260 Masse mesure de pharmacie dr ap drAp I
(1 dr ap = 3 s ap)
Once des systèmes de
261 Masse mesure de pharmacie oz ap ozAp I
– 622 –

(1 oz ap = 8 dr ap)
Livre des systèmes de
262 Masse mesure de pharmacie lb ap lbAp I
(1 lp ap = 12 oz ap)
Consommation de
263 mille par gallon impérial mpg (Imp) mpgImp I
carburant
Consommation de
264 mille par gallon US mpg (US) mpgUS I
carburant
Consommation de équivalent du mille par
265 MPGe (US) mPGeUS I
carburant gallon US
Consommation de
266 litre par 100 km l/(100 km) lPer100km I
carburant
kilowattheure par mille
Consommation de (note: les utilisateurs
267 Wh/mi wHPerMi I
61968-9  CEI:2013

carburant doivent fournir le préfixe "k"


pour créer "kWh/mi")
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Nom d'unité Statut


Code Grandeur Symbole Enumération
(et commentaires) normatif
kilowattheure par 100 mille
Consommation de (note: les utilisateurs
268 Wh/(100 mi) wHPer100Mi I
carburant doivent fournir le préfixe "k"
pour créer "kWh/(100 mi)")
279 Température degrés Fahrenheit ºF degF I

N = Normative
61968-9  CEI:2013

I = Informative

D = Déconseillé depuis la dernière édition


– 623 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.27 – Unités non SI associées au système d'unités CGS et CGS gaussien

Code Quantité Nom d'unité (et commentaires) Symbole Enumération Statut normatif
269 énergie erg (1 erg = 10 –7 J) erg erg I
270 Force dyne (1 dyn = 10 –5 N) dyn dyn I
271 Viscosité dynamique poise (1 P = 0,1 Pa s) P p I
272 Viscosité cinématique stokes (1 St = 1 cm 2 /s) St st I
4
273 Luminance stilb (1 sb = 10 cd/m 2 ) sb sb I
274 Illumination phot (1 ph = 10 4 lx) ph ph I
gal (1 Gal = 10 –2 m s –2 )
NOTE Le présent "Gal" est une Gal gal I
abréviation de "Galileo" et non de
275 Accélération "gallon"
276 Flux magnétique Maxwell (1 Mx = 10 –8 Wb) Mx mx I
277 Densité du flux magnétique Gauss (1 G = 10 –4 T) G gauss I
278 Champ magnétique Œrsted (1 Oe = (10 3 /4π) A/m) Oe oe I

N = Normative
– 624 –

I = Informative

D = Déconseillé depuis la dernière édition


61968-9  CEI:2013
61968-9  CEI:2013 – 625 –

C.2.19 Attribut n° 18, devise


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les codes de devise sont définis dans l'ISO 4217. Certains codes ont été répétés dans le
Tableau C.28 pour référence. Les codes de devise supplémentaires peuvent être extraits
librement de l'ISO 4217.

Tableau C.28 – Unités de mesure des devises (issues de l'ISO 4217)

Code Symbole affichable Nom d'unité Statut normatif


0 Aucun N
36 AUD Dollar australien I
124 CAD Dollar canadien I
156 CNY Yuan renminbi chinois I
208 DKK Couronne danoise I
356 INR Roupie indienne I
392 JPY Yen japonais I
578 NOK Couronne norvégienne I
643 RUB Rouble russe I
710 ZAR Rand d'Afrique du Sud I
752 SEK Couronne suédoise I
756 CHF Franc suisse I
826 GBP Livre britannique I
840 USD US Dollar I
978 EUR Euro I

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition

C.3 Utilisation d'attributs d'éléments de données pour définir le nom de


ReadingType – Formule de construction avec des exemples de codes
ReadingType

Un "ReadingType" peut être généré automatiquement en remplissant judicieusement chacun


des attributs et en les présentant dans un ordre côte à côte. Il est recommandé que les
attributs soient les plus explicites possibles pour identifier un élément de donnée, mais sans
devenir si explicites qu'ils spécifient outre mesure l'élément de données.

Un nom de ReadingType peut être généré en présentant la forme numérique de chaque


attribut côte à côte séparée par des points.

<ReadingType.Name.name>::= <macroPeriod> “.” <aggregate> “.”<measuringPeriod>”,”


<accumulation> “.” <flowDirection> "." <commodity> "." <measurementKind> “.”
<interharmonicNumerator> "." <interharmonicDenominator> "." <argumentNumerator> “.”
<argumentDenominator> “.” <tou> "." <cpp> "." <consumptionTier> "." <phases> “.”
<multiplier> “.” <unit> “.” <currency>

Ces champs peuvent être convertis en un nom prononçable régionalisé (localisé) en utilisant
la forme textuelle régionale (locale) pour chacun des attributs non égal à zéro et en les
présentant dans l'ordre, côte à côte, séparés par des espaces et autres symboles tel
qu'approprié. Pour la plupart des applications, cela apporte généralement plus d'informations
– 626 – 61968-9  CEI:2013

qui seront dites (verbalement) que nécessaire concernant les données. Supprimer les
adjectifs descriptifs qui sont mutuellement compris par le contexte de communication est une
pratique acceptée dans le langage courant. Le Tableau C.29 donne des exemples de ces
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

conversions en anglais. Il sera noté que dans la formule EBNF ci-après, les symboles tels que
"(" et ")" sont intégrés pour améliorer la lisibilité. A des fins identiques, les espaces autour de
l'unité de mesure sont également omis.

<Name.description>::= [<macroPeriod> “ ”] [<aggregate> “ ”] [<measuringPeriod> “ ”]


[<accumulation> “ ”] [<flowDirection> “ ”] [<commodity> ” ”] [<measurementKind> “ ”]
[<interharmonicNumerator> “ ”] [<interharmonicDenominator> “ ”] [<argumentNumerator> “ ”]
[<argumentDenominator> “ ”] [<tou> “ “] [<cpp> “ ”] [<consumptionTier> “ ”] [<phases> “ ”] “(”
[<multiplier>] [<unit>] [<currency>] “)”

Alors qu'une bonne interface éliminera toute ambiguïté et n'éditera pas de données
"anonymes", une bonne interface n'ira pas non plus à l'autre extrême pour spécifier outre
mesure les données qu'elle édite. Le concept est similaire à la pratique consistant à éditer un
nombre approprié de chiffres de résolution pour une valeur numérique. Un système peut
connaître (par exemple) la phase sur laquelle une tension a été mesurée et la fournir comme
attribut de la mesure. Un autre système pourrait ne pas connaître la phase avec une bonne
autorité et éditer simplement la tension mesurée au niveau d'un compteur. Les
ReadingTypeID utilisés dans une réponse peuvent (par conséquent) différer légèrement des
ReadingTypeID utilisés dans une demande. Il convient que les codes ReadingType utilisés
par un éditeur de données soient appropriés pour les données fournies.

Les exemples donnés ci-après ne constituent nullement une liste exhaustive de ce qui peut
être construit avec les valeurs d'énumération répertoriées ci-dessus. Après avoir parcouru les
exemples (ci-dessous) et les listes d'énumérations (ci-dessous) sans avoir trouvé
l'énumération requise, des énumérations personnalisées peuvent être réalisées. Certains des
champs (comme le "numérateur") sont naturellement un champ entier. Si l'énumération
nécessaire n'est qu'un entier, il convient alors que l'utilisateur fournisse l'entier requis.
Néanmoins, si le champ est une énumération de type liste, il convient d'être prudent. Au lieu
d'utiliser simplement le prochain nombre disponible sur la liste, les énumérations
personnalisées par l'utilisateur devraient être créées, numérotées 9 000 ou plus.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau C.29 – Exemples de ReadingType

Code de ReadingType ID Description Statut


normatif
8.0.0.0.0.1.152.0.0.0.0.0.0.0.0.0.0.840 billingPeriod electricitySecondaryMetered billCarryover (USD) N
8.0.0.0.0.1.150.0.0.0.0.0.0.0.0.0.0.840 billingPeriod electricitySecondaryMetered billLastPeriod (USD) N
8.8.0.3.1.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum cumulative forward electricitySecondaryMetered demand (kW) N
61968-9  CEI:2013

8.8.53.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum fixedBlock15Min indicating forward electricitySecondaryMetered demand (kW) N


8.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.63.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand (kVAr) N
8.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand (kW) N
8.8.0.6.1.1.8.0.0.0.0.1.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touA (kW) N
8.8.0.6.1.1.8.0.0.0.0.2.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touB (kW) N
8.8.0.6.1.1.8.0.0.0.0.3.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touC (kW) N
8.8.0.6.1.1.8.0.0.0.0.4.0.0.0.3.38.0 billingPeriod maximum indicating forward electricitySecondaryMetered demand touD (kW) N
– 627 –

8.8.0.6.19.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum indicating reverse electricitySecondaryMetered demand (kW) N


8.8.71.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 billingPeriod maximum rollingBlock15MinIntvl5MinSubIntvl indicating forward electricitySecondaryMetered demand N
(kW)
8.8.101.6.1.1.8.0.0.720.1.0.0.0.0.3.38.0 billingPeriod maximum specifiedFixedBlock indicating forward electricitySecondaryMetered demand n720 (kW) N
8.8.102.6.1.1.8.0.0.720.240.0.0.0.0.3.38.0 billingPeriod maximum specifiedRollingBlock indicating forward electricitySecondaryMetered demand n720/240 (kW) N
8.0.0.9.1.1.12.0.0.0.0.1.0.0.0.3.72.0 billingPeriod summation forward electricitySecondaryMetered energy touA (kWh) N
8.0.0.9.1.1.12.0.0.0.0.2.0.0.0.3.72.0 billingPeriod summation forward electricitySecondaryMetered energy touB (kWh) N
8.0.0.9.1.1.12.0.0.0.0.3.0.0.0.3.72.0 billingPeriod summation forward electricitySecondaryMetered energy touC (kWh) N
0.0.0.1.0.1.122.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered demandReset (count) N
0.0.0.1.0.1.11.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered energization (count) N
0.0.0.1.0.1.131.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered loadInterrupt (count) N
0.0.0.1.0.1.141.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered relayActivation (count) N
0.0.0.1.0.1.142.0.0.0.0.0.0.0.0.0.111.0 bulkQuantity electricitySecondaryMetered relayCycle (count) N
0.0.0.1.1.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity forward electricitySecondaryMetered energy (kVArh) N
0.0.0.1.1.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity forward electricitySecondaryMetered energy (kWh) N
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.2.120.0 bulkQuantity forward naturalGas volume (hft³(compensated)) N
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.2.121.0 bulkQuantity forward naturalGas volume (hft³(uncompensated)) N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Code de ReadingType ID Description Statut


normatif
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.3.120.0 bulkQuantity forward naturalGas volume (kft³(compensated)) N
0.0.0.1.1.7.58.0.0.0.0.0.0.0.0.3.121.0 bulkQuantity forward naturalGas volume (kft³(uncompensated)) N
0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity net electricitySecondaryMetered energy (kVArh) N
0.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity net electricitySecondaryMetered energy (kWh) N
0.0.0.1.19.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity reverse electricitySecondaryMetered energy (kVArh) N
0.0.0.1.19.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity reverse electricitySecondaryMetered energy (kWh) N
0.0.0.1.20.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity total electricitySecondaryMetered energy (kVArh) N
0.0.0.1.20.1.12.0.0.0.0.0.0.0.0.3.73.0 bulkQuantity total electricitySecondaryMetered energy (kVArh) N
0.0.0.1.20.1.12.0.0.0.0.0.0.0.0.3.72.0 bulkQuantity total electricitySecondaryMetered energy (kWh) N
0.0.0.0.0.3.97.0.0.0.1.0.0.0.0.0.114.0 communication deviceAddressType2 n0 (code) N
0.0.0.0.0.3.123.0.0.0.0.0.0.0.0.0.114.0 communication diagnostic (code) N
0.0.0.0.0.3.104.0.0.0.1.0.0.0.0.0.114.0 communication groupAddressType2 n0 (code) N
0.0.0.0.0.3.133.0.0.0.0.0.0.0.0.0.114.0 communication maintenance (code) N
0.0.0.0.0.3.114.0.0.0.1.0.0.0.0.0.114.0 communication oneWayAddress n0 (code) N
0.0.0.0.0.3.114.0.0.1.1.0.0.0.0.0.114.0 communication oneWayAddress n1 (code) N
– 628 –

11.0.0.1.4.1.12.0.0.0.0.0.0.0.0.3.72.0 daily bulkQuantity net electricitySecondaryMetered energy (kWh) N


11.0.0.4.0.1.126.0.0.0.0.0.0.0.0.0.111.0 daily deltaData electricitySecondaryMetered ieee1366MomentaryInterruption (count) N
11.0.0.4.0.1.127.0.0.0.0.0.0.0.0.0.111.0 daily deltaData electricitySecondaryMetered ieee1366MomentaryInterruptionEvent (count) N
11.0.0.4.0.1.128.0.0.0.0.0.0.0.0.0.111.0 daily deltaData electricitySecondaryMetered ieee1366SustainedInterruption (count) N
11.0.0.4.0.1.128.0.0.0.0.0.0.0.0.0.27.0 daily deltaData electricitySecondaryMetered ieee1366SustainedInterruption (s) N
11.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 daily maximum indicating forward electricitySecondaryMetered demand (kW) N
11.0.0.9.4.1.12.0.0.0.0.1.0.0.0.3.72.0 daily summation net electricitySecondaryMetered energy touA (kWh) N
0.0.0.4.1.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData forward electricitySecondaryMetered energy (kVArh) N
0.0.0.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData forward electricitySecondaryMetered energy (kWh) N
0.0.0.4.4.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData net electricitySecondaryMetered energy (kVArh) N
0.0.0.4.4.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData net electricitySecondaryMetered energy (kWh) N
0.0.0.4.19.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData reverse electricitySecondaryMetered energy (kVArh) N
61968-9  CEI:2013

0.0.0.4.19.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData reverse electricitySecondaryMetered energy (kWh) N


0.0.0.4.20.1.12.0.0.0.0.0.0.0.0.3.73.0 deltaData total electricitySecondaryMetered energy (kVArh) N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Code de ReadingType ID Description Statut


normatif
0.0.0.4.20.1.12.0.0.0.0.0.0.0.0.3.72.0 deltaData total electricitySecondaryMetered energy (kWh) N
0.0.0.0.0.1.5.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered currentAngle (count) N
0.0.0.0.0.1.6.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered currentImbalance (count) N
0.0.0.0.0.1.11.0.0.0.0.0.0.0.0.0.109.0 electricitySecondaryMetered energization (status) N
0.0.0.0.0.1.13.0.0.0.0.0.0.0.0.0.109.0 electricitySecondaryMetered energizationLoadSide (status) N
61968-9  CEI:2013

0.0.0.0.0.1.43.0.0.0.0.0.0.0.0.0.109.0 electricitySecondaryMetered switchPosition (status) N


0.0.0.0.0.1.57.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered voltageImbalance (count) N
0.0.0.0.0.1.59.0.0.0.0.0.0.0.0.0.111.0 electricitySecondaryMetered zeroFlowDuration (count) N
0.4.0.0.0.1.55.0.0.0.0.0.0.0.0.0.111.0 excess electricitySecondaryMetered voltageAngle (count) N
0.0.2.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0 fifteenMinute deltaData forward electricitySecondaryMetered energy (kWh) N
0.0.0.6.0.1.4.0.0.0.0.0.0.0.0.0.5.0 indicating electricitySecondaryMetered current (A) N
0.0.0.6.0.1.4.0.0.0.0.0.0.0.128.0.5.0 indicating electricitySecondaryMetered current phaseA (A) N
– 629 –

0.0.0.6.0.1.4.0.0.0.0.0.0.0.64.0.5.0 indicating electricitySecondaryMetered current phaseB (A) N


0.0.0.6.0.1.4.0.0.0.0.0.0.0.32.0.5.0 indicating electricitySecondaryMetered current phaseC (A) N
0.0.0.6.0.1.5.0.0.0.0.0.0.0.136.0.9.0 indicating electricitySecondaryMetered currentAngle phaseAtoAv (deg) N
0.0.0.6.0.1.5.0.0.0.0.0.0.0.72.0.9.0 indicating electricitySecondaryMetered currentAngle phaseBtoAv (deg) N
0.0.0.6.0.1.5.0.0.0.0.0.0.0.40.0.9.0 indicating electricitySecondaryMetered currentAngle phaseCtoAv (deg) N
0.0.0.6.0.1.15.0.0.0.0.0.0.0.0.0.33.0 indicating electricitySecondaryMetered frequency (Hz) N
0.0.0.6.0.1.38.0.0.0.0.0.0.0.0.0.65.0 indicating electricitySecondaryMetered powerFactor (cosθ) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.0.0.29.0 indicating electricitySecondaryMetered voltage (V) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.128.0.29.0 indicating electricitySecondaryMetered voltage phaseA (V) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.64.0.29.0 indicating electricitySecondaryMetered voltage phaseB (V) N
0.0.0.6.0.1.54.0.0.0.0.0.0.0.32.0.29.0 indicating electricitySecondaryMetered voltage phaseC (V) N
0.0.0.6.0.1.55.0.0.0.0.0.0.0.72.0.9.0 indicating electricitySecondaryMetered voltageAngle phaseBtoAv (deg) N
0.0.0.6.0.1.55.0.0.0.0.0.0.0.40.0.9.0 indicating electricitySecondaryMetered voltageAngle phaseCtoAv (deg) N
0.0.0.6.19.1.8.0.0.0.0.0.0.0.0.3.38.0 indicating reverse electricitySecondaryMetered demand (kW) N
0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.63.0 instantaneous forward electricitySecondaryMetered power (kVAr) N
0.0.0.12.1.1.37.0.0.0.0.0.0.0.0.3.38.0 instantaneous forward electricitySecondaryMetered power (kW) N
0.0.0.12.20.1.37.0.0.0.0.0.0.0.0.3.38.0 instantaneous total electricitySecondaryMetered power (kW) N
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Code de ReadingType ID Description Statut


normatif
0.0.0.13.0.1.140.0.0.0.0.0.0.0.0.0.108.0 latchingQuantity electricitySecondaryMetered pushbutton (timeStamp) N
0.8.0.6.1.1.8.0.0.0.0.0.0.0.0.3.38.0 maximum indicating forward electricitySecondaryMetered demand (kW) N
0.9.0.6.0.1.38.0.0.0.0.0.0.0.0.0.65.0 minimum indicating electricitySecondaryMetered powerFactor (cosθ) N
0.0.0.0.19.1.4.0.0.0.0.0.0.0.0.0.111.0 reverse electricitySecondaryMetered current (count) N
22.0.0.1.1.1.12.0.0.0.0.0.0.0.0.3.73.0 seasonal bulkQuantity forward electricitySecondaryMetered energy (kVArh) N
22.8.0.6.1.1.8.0.0.0.0.1.0.0.0.3.38.0 seasonal maximum indicating forward electricitySecondaryMetered demand touA (kW) N
22.8.0.6.1.1.8.0.0.0.0.2.0.0.0.3.38.0 seasonal maximum indicating forward electricitySecondaryMetered demand touB (kW) N
22.8.0.6.1.1.8.0.0.0.0.3.0.0.0.3.38.0 seasonal maximum indicating forward electricitySecondaryMetered demand touC (kW) N
22.0.0.9.1.1.12.0.0.0.0.1.0.0.0.3.72.0 seasonal summation forward electricitySecondaryMetered energy touA (kWh) N
22.0.0.9.1.1.12.0.0.0.0.2.0.0.0.3.72.0 seasonal summation forward electricitySecondaryMetered energy touB (kWh) N
22.0.0.9.1.1.12.0.0.0.0.3.0.0.0.3.72.0 seasonal summation forward electricitySecondaryMetered energy touC (kWh) N
0.0.7.4.1.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData forward electricitySecondaryMetered energy (kVArh) N
0.0.7.4.1.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData forward electricitySecondaryMetered energy (kWh) N
0.0.7.4.4.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData net electricitySecondaryMetered energy (kVArh) N
0.0.7.4.4.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData net electricitySecondaryMetered energy (kWh) N
– 630 –

0.0.7.4.19.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData reverse electricitySecondaryMetered energy (kVArh) N


0.0.7.4.19.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData reverse electricitySecondaryMetered energy (kWh) N
0.0.7.4.20.1.12.0.0.0.0.0.0.0.0.3.73.0 sixtyMinute deltaData total electricitySecondaryMetered energy (kVArh) N
0.0.7.4.20.1.12.0.0.0.0.0.0.0.0.3.72.0 sixtyMinute deltaData total electricitySecondaryMetered energy (kWh) N
0.0.100.4.1.1.12.0.0.30.1.0.0.0.0.3.72.0 specifiedInterval deltaData forward electricitySecondaryMetered energy n30 (kWh) N
32.0.0.4.0.1.12.0.0.0.0.0.0.0.0.3.72.0 specifiedPeriod deltaData electricitySecondaryMetered energy (kWh) N
32.0.0.0.0.1.151.0.0.0.0.0.0.0.0.0.0.840 specifiedPeriod electricitySecondaryMetered billToDate (USD) N
0.0.0.9.20.1.12.0.0.0.0.1.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touA (kWh) N
0.0.0.9.20.1.12.0.0.0.0.2.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touB (kWh) N
0.0.0.9.20.1.12.0.0.0.0.3.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touC (kWh) N
0.0.0.9.20.1.12.0.0.0.0.4.0.0.0.3.72.0 summation total electricitySecondaryMetered energy touD (kWh) N
61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

N = Normative

I = Informative

D = Déconseillé depuis la dernière édition


61968-9  CEI:2013
– 631 –
– 632 – 61968-9  CEI:2013

Annexe D
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Enumérations de codes de qualité

D.1 Généralités

Les codes de qualité peuvent être retournés avec une Reading.value pour indiquer que les
données ont quelque chose de remarquable. La présente Annexe décrit un profil nord-
américain d'énumérations proposé pour les codes de qualité à utiliser dans ce contexte.

La présence d'un code de qualité est facultative. Un élément manquant implique que le
producteur de données n'affirme pas que les données soient adéquates. L'approche de
certains systèmes (de type MS, par exemple) peut être basée sur le principe "pas de
nouvelles, bonnes nouvelles", ce qui signifie que des codes de qualité ne sont ajoutés que si
des problèmes sont détectés. Cela permet de conserver un volume minimal de données.
D'autres systèmes (tels qu'un MDM) ajouteront de la valeur aux données en les validant. A ce
stade, des codes de qualité peuvent être ajoutés aux données pour déclarer explicitement
que les données sont "valides" ou qu'elles ont réussi les essais formels de "validation".

Les valeurs de code de qualité définies par la présente Annexe D sont acheminées dans un
message en utilisant un élément ReadingQuality.quality.

D.2 Identification du système proposant un commentaire sur les données

Il est concevable que toute pièce d'équipement qui touche aux données soit susceptible
d'introduire une erreur ou de présenter des remarques relatives à la véracité des données.
Par exemple, un compteur pourrait enregistrer des données d'intervalles et proposer ces
données au système de collecte de données, mais, ce faisant, indiquer qu'il s'est produit
quelque chose de remarquable (comme une panne d'alimentation en énergie ou un
réajustement d'horloge par exemple) au cours de certains des intervalles. Un système de
collecte de données de compteur pourrait obtenir des relevés sur le terrain, mais réaliser un
contrôle de bon sens sur les valeurs pour découvrir que certaines de celles-ci ne sont pas
raisonnables. Un système de gestion de données de compteur, armé de la connaissance de
l'historique du compte et des profils d'utilisation, pourrait examiner minutieusement les
données pour découvrir que certaines valeurs sont suspectes ou suggérer éventuellement
qu'une altération a pu avoir lieu. Tous ces systèmes ont besoin d'une occasion de commenter
les données sans (nécessairement) les modifier. Lorsqu'un système change effectivement les
données, cela aussi peut être noté dans les codes de qualité.

D.3 Construction

Le profil nord-américain définit le code ReadingQuality.quality à générer à partir d'un champ


en trois parties:

ReadingQuality.quality::= <System Identifier> "." <Categorization> "." <Index>

Cela crée un nom à 3 champs. Les mappages de CIM ReadingQualityType sont définis par la
norme CEI 61968-11 comme suit:

System Identifier = ReadingQualityType.systemId


Categorization = ReadingQualityType.category
Index = ReadingQualityType.subCategory
61968-9  CEI:2013 – 633 –

D.4 Identificateur système de code de qualité


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Le premier des trois champs fournit une identification du système qui a déclaré le problème
des données. Cela est décrit au Tableau D.1. D'autres systèmes, en dehors d'un sous-
système CEI 61968-9, peuvent également identifier des problèmes de données.

Tableau D.1 – Identificateur système (System Identifier)

Code d'identificateur système Description Statut normatif


0 Non applicable N
1 Dispositif terminal N
Réseau (de collecte de données) de système de
2 N
comptage
3 Système de gestion de données de compteur N
4 Autre système (non répertorié). N
Spécifié de façon externe (voir données
5 I
d'accompagnement)

I = Informative

N = Normative

D = Déconseillée

D.5 Catégorisation des codes de qualité

Le second des trois champs du code de qualité identifie une catégorie pour le problème.
Ceux-ci sont décrits individuellement dans le Tableau D.2.

Tableau D.2 – Exemples de catégories de codes de qualité

Catégorie Description Commentaire Statut normatif


0 Valide Validité des données N
L'équipement qui produit ou gère les données
1 Relatifs au diagnostic a identifié un problème de diagnostic qui peut N
avoir un effet sur cette valeur.
Problèmes relatifs à la L'équipement qui produit les données a
qualité de l'énergie au identifié des problèmes relatifs à la qualité de
2 N
niveau du point de l'énergie qui peuvent avoir un effet sur la
collecte des données véracité des données.
Relatif à la protection des Système qui identifie que les données sont
3 Recettes / contre la douteuses pour des raisons relatives à la N
falsification falsification ou à la protection des recettes.
Une condition ou un événement significatif
(qui n'est pas associé à une falsification, à la
Relatifs à la collecte de
4 qualité de l'alimentation électrique ou aux N
données
diagnostics) s'est produit et peut affecter la
véracité des données.
Ayant échoué aux essais A première vue, les données semblent
5 N
de bon sens incorrectes.
Ayant échoué aux essais Les données font échouer une ou plusieurs
6 N
de validation règles de validation.
7 Edité Remplacé ou approuvé par un individu. N
Remplacé par une valeur calculée par une
machine à partir d'une analyse de données
8 Estimé N
d'historique utilisant le même type de
mesure.
– 634 – 61968-9  CEI:2013

Catégorie Description Commentaire Statut normatif


Cette catégorie semble être couverte par
9 Battant D
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

d'autres catégories de cette norme.


La véracité de ces données est douteuse
10 Douteux pour une raison autre que celles décrites par N
les catégories 1 à 6.
La valeur a été calculée (à l'aide d'opérations
logiques ou mathématiques) à partir d'un ou
de plusieurs relevés du compteur ou de
11 Dérivé l'appareil auquel la valeur est attribuée et/ou N
à partir des relevés de compteurs ou
d'appareils autres que le compteur ou
l'appareil auquel la valeur est attribuée.
12 Prévu Valeur prévue. N

I = Informative

N = Normative

D = Déconseillée

D.6 Index de codes de qualité

Chaque catégorie fournit le contexte permettant de comprendre un index particulier.

Le Tableau D.3 s'appuie sur la "catégorie 0" définie dans le Tableau D.2.

Tableau D.3 – Codes relatifs à la validité

Catégorie Index Description Définition Statut normatif


Aucun problème de qualité des données
n'a été détecté; toutefois, les données
0 0 Data Valid N
n'ont pas été traitées par un processus
VEE (Validation, Edition et Estimation).
La lecture a passé avec succès la
partie validation d'un processus VEE
0 1 Validated (Validation, Edition et Estimation) et elle N
n'a pas été éditée ou estimée
ultérieurement.

I = Informative

N = Normative

D = Déconseillée

Le Tableau D.4 s'appuie sur la "catégorie 1" définie dans le Tableau D.2.
61968-9  CEI:2013 – 635 –

Tableau D.4 – Codes relatifs aux diagnostics


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Catégorie Index Description Commentaires Statut normatif


Un ou plusieurs diagnostics ont été générés
1 0 DiagnosticsFlag N
à partir du matériel d'origine.
1 1 BatteryLow N
1 3 SensorFailure N
Une expiration du délai du temporisateur
chien de garde ou autre défaillance de la
1 4 WatchdogFlag N
fonction chien de garde s’est produite dans
le matériel d’origine.
Une erreur de parité a été générée depuis
1 5 ParityError N
le matériel d’origine
Une erreur de contrôle de redondance
1 6 CRCError cyclique a été générée depuis le matériel N
d’origine
Une erreur de somme de contrôle a été
1 7 RAMChecksumError N
détectée dans la mémoire RAM du matériel.
Une erreur de somme de contrôle a été
1 8 ROMChecksumError N
détectée dans la mémoire ROM du matériel.
Une défaillance ou anomalie a été détectée
1 9 ClockError N
avec l’horloge dans le matériel.

I = Informative

N = Normative

D = Déconseillée

NOTE Les codes relatifs aux diagnostics peuvent produire des EndDeviceEvents correspondants à générer.

Le Tableau D.5 s'appuie sur la "catégorie 2" définie dans le Tableau D.2.

Tableau D.5 – Codes relatifs à la qualité de l'énergie

Catégorie Index Description Commentaires Statut normatif


Rechercher le(s) MeterEvent
2 0 PowerQualityFlag N
connexe(s)
Valeur dépassée pour le seuil du
2 1 ExcessiveOutageCount compte total de pannes N
d'alimentation en énergie
Valeur dépassée pour le seuil du
2 2 PqCounter N
compte total de qualité d'énergie
Opération de déconnexion du
2 3 ServiceDisconnectSwitching service pendant l'intervalle de N
collecte des données
Une panne d'alimentation s'est
produite pendant ou au début de cet
intervalle.
ANSI C12.19.
2 32 PowerFail N
Si l'alimentation est arrêtée pendant
tout l'intervalle, il convient de définir
la valeur de données présentée sur
zéro.

I = Informative

N = Normative

D = Déconseillée
– 636 – 61968-9  CEI:2013

Le Tableau D.6 s'appuie sur la "catégorie 3" définie dans le Tableau D.2.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tableau D.6 – Codes relatifs à la protection des Recettes / contre la falsification

Catégorie Index Description Commentaires Statut normatif


3 0 RevenueProtection Générique N
Le compteur indique qu'un
3 1 CoverOpened N
couvercle étanche a été ouvert.
La valeur provient d'un compteur
dont il convient qu'il
3 2 LogicalDisconnect N
(théoriquement) n'ait aucun débit
ou un débit très minime.
3 3 RevenueProtectionSuspect N
Un flux inverse du produit mesuré
a été détecté. Cela peut indiquer
une falsification sur les sites qui
3 4 ReverseRotation N
n'ont pas été identifiés comme
étant capables de génération côté
client.
Le compteur affiche une
3 5 StaticDataFlag utilisation historique très faible (le N
cas échéant).

I = Informative

N = Normative

D = Déconseillée

Le Tableau D.7 s'appuie sur la "catégorie 4" définie dans le Tableau D.2.

Tableau D.7 – Codes relatifs à la collecte de données

Catégorie Index Description Commentaires Statut normatif


4 0 AlarmFlag Alarme générique N
Un état de débordement
numérique pour une valeur de
4 1 OverflowConditionDetected N
relevé ou compteur d’impulsion a
été détecté.
Intervalle partiel (court) en
raison d'un changement
4 2 PartialInterval d'horloge, d'une panne N
d'alimentation en énergie ou d'un
événement similaire.
Long intervalle enregistré en
raison d'un changement
4 3 LongInterval N
d'horloge ou d'un événement
similaire.
Intervalle sauté par le compteur
4 4 SkippedInterval en raison d'un changement N
d'horloge ou événement similaire
Valeur de donnée obtenue alors
4 5 TestData que l’appareil était en mode N
d’essai
Configuration modifiée qui peut
4 6 ConfigurationChanged affecter la valeur de relevé ou N
son interprétation
Arrêt de l'enregistrement de
4 7 NotRecording N
profil de charge
61968-9  CEI:2013 – 637 –

Catégorie Index Description Commentaires Statut normatif


Réinitialisation qui peut affecter
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

4 8 ResetOccurred la valeur de relevé ou son N


interprétation
Une modification de l’heure de
4 9 ClockChanged N
l’horloge est intervenue
Valeur de donnée obtenue au
4 10 LoadControlOccurred moment de la présence d’une N
régulation de charge
Heure d'été/hiver d'économie
4 16 DstInEffect d'énergie en vigueur au cours ou N
au début de cet intervalle
Horloge réglée dans le sens de
l'avance au cours ou au début de
4 64 ClockSetForward N
cet intervalle. L'intervalle peut
être court.
Horloge réglée dans le sens du
retard au cours ou au début de
4 128 ClockSetBackward N
cet intervalle. L'intervalle peut
être long.
Une défaillance ayant empêché
4 129 FailedProbeAttempt la lecture par relevé manuel est N
arrivée.
La valeur de relevé a été fournie
4 130 CustomerRead N
par un client
La valeur de relevé provient d’un
agent de l’entreprise de
4 131 ManualRead N
distribution ayant réalisé un
relevé manuel.
Des données ont été
défavorablement affectées par
un changement d'heure
d'été/hiver d'économie d'énergie.
Des horodatages et/ou des
valeurs de données peuvent être
incorrect(e)s.
4 259 DstChangeOccurred NOTE En comparaison N
à l'approche ANSI C12.19 dans
laquelle l'indicateur DST est mis
pour tout l'été, cet indicateur
n'est mis pour les données
altérées que si le changement
d'heure d'été/hiver se produit au
printemps et en automne.

I = Informative

N = Normative

D = Déconseillée

Le Tableau D.8 s'appuie sur la "catégorie 5" définie dans le Tableau D.2.
– 638 – 61968-9  CEI:2013

Tableau D.8 – Codes relatifs à Ayant échoué aux essais de bon sens
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Catégorie Index Description Commentaires Statut normatif


Les données présentées ont
été identifiées comme non
5 256 DataOutsideExpectedRange N
valides par le système
émetteur.
Les données ont été
identifiées comme non
valides par le système
5 257 ErrorCode émetteur et ont été N
remplacées par une valeur
codée spéciale pour indiquer
une erreur.
Il convient que les données
soient examinées
5 258 Suspect N
méticuleusement et
considérées suspectes.
NOTE 1 Il convient que
l'élément "value" soit vide
lorsque le code de qualité
indique qu'il est (bien
5 259 KnownMissingRead entendu) manquant. N
NOTE 2 Si une raison est
connue, elle peut être fournie
par l’élément
MeterReadings.Reason

I = Informative

N = Normative

D = Déconseillée

Le Tableau D.9 s'appuie sur la "catégorie 6" définie dans le Tableau D.2.

Tableau D.9 – Codes relatifs à Ayant échoué aux essais de validation

Catégorie Index Enumération Commentaires Statut normatif


Échec de lecture à un ou plusieurs
contrôles de validation non
spécifiés. Il s’agit d’un code
6 0 Failed validation -- Generic N
générique qui peut être utilisé si
un code plus spécifique n’est pas
disponible dans ce tableau.
Échec de validation de la lecture
Failed validation --
6 1 dû à l’usage de zéro sur un N
ZeroUsageOn ActiveMeter
compteur actif.
Échec de validation de la lecture
Failed validation -- UsageOn
6 2 dû au non usage de zéro sur un N
InactiveMeter
compteur inactif.
Échec de validation de la lecture
Failed validation -- car il s’agit d’une valeur d’usage
6 3 N
UsageAbove Maximum supérieure au maximum absolu
admis.
Échec de validation de la lecture
Failed validation -- car il s’agit d’une valeur d’usage
6 4 N
UsageBelow Minimum inférieure au minimum absolu
requis.
Échec de validation de la lecture
Failed validation -- car il s’agit d’une valeur d’usage
6 5 N
UsageAbove MaximumPct supérieure au pourcentage
maximum admis.
61968-9  CEI:2013 – 639 –

Catégorie Index Enumération Commentaires Statut normatif


Échec de validation de la lecture
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Failed validation – car il s’agit d’une valeur d’usage


6 6 N
UsageBelow MinimumPct inférieure au pourcentage
minimum requis.
Échec de validation de la lecture
car la somme des valeurs
Failed Validation – TOU
6 9 d’intervalle n’est pas comparable N
SumCheck Failure
à la différence correspondante
dans les relevés de registre.
Echec de lecture à un ou plusieurs
contrôles de validation définis.
“y” est à remplacer par un entier
positif indiquant la règle de
validation ayant échoué.
Il est recommandé que les valeurs
pour y commencent à 1001 pour
permettre de constituer dans la
durée la liste des énumérations
6 y Failed Validation Rule Y normatives dans la norme CEI I
jusqu’à 1000.
Il n’existe aucune limite quant à
l’importance de la valeur du
nombre qui peut être utilisé pour
“y”; cependant, les parties
participant à l’échange de ce code
doivent avoir une compréhension
commune de la signification de
chaque règle de validation #.

I = Informative

N = Normative

D = Déconseillée

Les déploiements individuels s'abonneront à des ensembles particuliers de règles de


validation formelle. Bien qu'il n'existe pas de norme internationale sur les règles de validation,
la présente norme fournit un espace réservé où la première règle peut être définie en tant que
"règle n° 1" pour un déploiement donné, la deuxième règle en tant que "règle n° 2", et ainsi
de suite, selon les besoins, jusqu'à ce que toutes les règles soient numérotées. Chaque
système, s'exécutant alors en tant qu'utilitaire donné sous un ensemble donné de règles, sera
soumis au même ensemble de règles qui ont été officiellement répertoriées et numérotées.

Le Tableau D.10 décrit la "catégorie 7" définie dans le Tableau D.2.


– 640 – 61968-9  CEI:2013

Tableau D.10 – Codes relatifs à l'édition


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Catégorie Index Description Commentaires Statut normatif


La valeur de relevé a été éditée par une
personne utilisant une méthode d’estimation
Manually Edited –
7 0 manuelle non spécifiée. Il s’agit d’un code N
Generic
générique qui peut être utilisé si un code plus
spécifique n’est pas disponible dans ce tableau.
Une valeur de relevé a été ajoutée par une
7 1 Manually Added N
personne.
Une valeur a été proposée par le système ou n’a
pas satisfait à un niveau donné de contrôle de la
7 3 Manually Rejected N
qualité. La valeur a été examinée et rejetée par
un être humain
La valeur de relevé a été éditée par une
personne utilisant une méthode d’estimation
manuelle définie.
“y” est à remplacer par un entier positif indiquant
la méthode d’estimation manuelle qui a été
utilisée.
Il est recommandé que les valeurs pour y
Manually Edited – commencent à 1001 pour permettre de constituer
7 Y I
Method Y dans la durée la liste des énumérations
normatives dans la norme CEI jusqu’à 1000.
Il n’existe aucune limite quant à l’importance de
la valeur du nombre qui peut être utilisé pour “y”;
cependant, les parties participant à l’échange de
ce code doivent avoir une compréhension
commune de la signification de chaque méthode
d’édition manuelle #y.

I = Informative

N = Normative

D = Déconseillée

Le concept d'"edited" signifie qu'un être humain a participé à la création de la valeur. Il peut
faire l'objet d'une saisie clavier dans le système. Il peut être suggéré par le système à l'aide
de l'une des nombreuses approches, mais finalement approuvé par un être humain. Valeurs
qui sont générées par l'ordinateur et ne sont jamais approuvées par un être humain dans la
catégorie "estimé. Valeurs émanant d'un compteur, identifiées comme suspectes, mais
néanmoins acceptées par un être humain pour une utilisation en tant que valeurs de la
catégorie "douteux".

Les systèmes peuvent trouver différentes façons d'aider l'utilisateur à créer une nouvelle
valeur. Le schéma de numérotation permet de répertorier les différentes façons et les
identifier formellement pour un déploiement donné.

Le Tableau D.11 décrit la "catégorie 8" définie dans le Tableau D.2.


61968-9  CEI:2013 – 641 –

Tableau D.11 – Codes relatifs à l'estimation


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Catégorie Index Enumération Commentaires Statut normatif


La valeur de relevé a été estimée par une
machine avec un algorithme de calcul
utilisant une méthode d’estimation non
8 0 Estimated -- Generic N
spécifiée. Il s’agit d’un code générique qui
peut être utilisé si un code plus spécifique
n’est pas disponible dans ce tableau.
La valeur de relevé a été estimée par une
machine avec un algorithme de calcul
utilisant une méthode d’estimation définie.
“y” est à remplacer par un entier positif
indiquant la méthode d’estimation qui a été
utilisée.
Il est recommandé que les valeurs pour y
Machine Estimated – commencent à 1001 pour permettre de
8 Y constituer dans la durée la liste des I
Method Y
énumérations normatives dans la norme CEI
jusqu’à 1 000.
Il n’existe aucune limite quant à l’importance
de la valeur du nombre qui peut être utilisé
pour “y”; cependant, les parties participant à
l’échange de ce code doivent avoir une
compréhension commune de la signification
de chaque méthode d’estimation #y.

I = Informative

N = Normative

D = Déconseillée

Les estimations peuvent être générées de nombreuses manières. Par exemple, une
estimation peut être fondée sur une combinaison d'utilisation historique, d'analyse de
tendance et de conditions météorologiques. Une autre approche serait de créer une valeur
pour un compteur en s'appuyant sur une mesure d'informations équivalentes d'un autre
compteur. (Par exemple, il peut exister plusieurs sources de mesure de la tension
d'alimentation disponibles. En cas d'échec de la source préférentielle, une autre source
pourrait être utilisée avec un résultat équivalent.) Certaines techniques utilisées peuvent avoir
un caractère propriétaire. D'autres techniques d'estimation peuvent être couramment utilisées
et peuvent être requises d'un point de vue légal par certains régulateurs dans certains lieux.
Le schéma de numérotation "approche n°1", "approche n°2", et ainsi de suite, est un
emplacement réservé dans lequel les approches utilisées peuvent être officiellement
répertoriées pour un déploiement donné et identifiées en tant que technique spécifique.

Le Tableau D.12 décrit la "catégorie 10" définie dans le Tableau D.2.

Tableau D.12 – Codes relatifs à Douteux

Catégorie Index Description Commentaires Statut normatif


La qualité est inconnue ou ne peut
pas être déterminée.
NOTE 1 Similaire au cas où
aucun code qualité n'est fourni
mais dans lequel d'autres codes
10 0 Indeterminate peuvent être présents, ce qui jette N
le doute sur la véracité des
données, ou une situation, qui
peut être apparue, empêche toute
sorte d'analyse sur les données ou
sur le matériel qui a fourni les
données.
– 642 – 61968-9  CEI:2013

Catégorie Index Description Commentaires Statut normatif


NOTE 2 Lorsqu'elle est utilisée
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

en réponse à une demande Power


(Energization) Status ou Switch
Position, une qualité
"Indeterminate" (indéterminé)
signifie que l'état d'alimentation en
énergie ou la position de
l'interrupteur est inconnu(e) ou ne
peut pas être déterminé(e).
Lorsqu'il est utilisé en réponse
à une demande pour d'autres
types de lecture, "indeterminate"
signifie que la qualité de la valeur
fournie est explicitement
inconnue.
Indique que la valeur n'a pas un
certain niveau de contrôle de la
10 1 Manually accepted N
qualité, mais que la panne a été
modifiée par un utilisateur humain.

I = Informative

N = Normative

D = Déconseillée

Le Tableau D.13 décrit la "catégorie 11" définie dans le Tableau D.2.

Tableau D.13 – Codes relatifs à Dérivé

Catégorie Index Enumération Commentaires Statut normatif


"Derived "( Dérivé) indique que la
valeur a été calculée (à l'aide
d'opérations logiques ou
mathématiques) en fonction d'une ou
de plusieurs relevés du compteur ou
de l'appareil auquel la valeur est
attribuée et/ou des relevés des
compteurs ou des appareils autre
que le compteur ou que l'appareil
auquel la valeur est attribuée.
11 0 Derived – Deterministic "Deterministic"(Déterministe) (à la N
différence de "Derived" – voir article
suivant) est utilisé lorsqu'un degré
significatif d'incertitude n'existe pas
dans la valeur résultante.
Par exemple, la qualité de "x.11.0"
ou "Derived – Deterministic" peut
être utilisée quand une valeur d'un
compteur virtuel est calculée en tant
que somme des valeurs de deux
compteurs ou plus.
"Derived" indique que la valeur a été
calculée (à l'aide d'opérations
logiques ou mathématiques) en
fonction d'une ou de plusieurs
relevés du compteur ou de l'appareil
auquel la valeur est attribuée et/ou
des relevés des compteurs ou des
11 1 Derived – Infered appareils autre que le compteur ou N
que l'appareil auquel la valeur est
attribuée.
"Infered "( Déduit) (à la différence
de "Deterministic" – voir article
précédent) est utilisé lorsqu'un degré
significatif d'incertitude peut exister
dans la valeur résultante.
61968-9  CEI:2013 – 643 –

Catégorie Index Enumération Commentaires Statut normatif


Lorsqu'il est utilisé en réponse
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

à Power (Energization) Status


Checks, "x.11.1" ou "Dérivé – Déduit"
est synonyme de "Déduit".
Par exemple, un UsagePoint peut
être déterminé pour une valeur "De-
energized" et une Qualité de lecture
"Derived- Infered" s'il est déduit
comme étant hors tension, car un ou
plusieurs autres UsagePoint sont
confirmés comme étant "hors
tension" sur le même transformateur
de distribution. Dans ce cas, il y a
très peu de risques que la déduction
soit incorrecte.

I = Informative

N = Normative

D = Déconseillée

Le Tableau D.14 décrit la "catégorie 12" définie dans le Tableau D.2.

Tableau D.14 – Codes relatifs à la projection

Catégorie Index Enumération Commentaires Statut normatif


Projected -- Generic La valeur de relevé a été projetée (prévision)
avec un algorithme de calcul utilisant une
méthode de projection (prévision) non
12 0 N
spécifiée. Il s’agit d’un code générique qui
peut être utilisé si un code plus spécifique
n’est pas disponible dans ce tableau.
Projected – Method Y La valeur de relevé a été projetée (prévision)
avec un algorithme de calcul utilisant une
méthode de projection (prévision) définie.
“y” est à remplacer par un entier positif
indiquant la méthode de projection (prévision)
qui a été utilisée.
Il est recommandé que les valeurs pour y
commencent à 1001 pour permettre de
12 Y constituer dans la durée la liste des I
énumérations normatives dans la norme CEI
jusqu’à 1000.
Il n’existe aucune limite quant à l’importance
de la valeur du nombre qui peut être utilisé
pour “y”; cependant, les parties participant à
l’échange de ce code doivent avoir une
compréhension commune de la signification
de chaque méthode de projection #y.

I = Informative

N = Normative

D = Déconseillée

De la même façon que "estimated" crée une valeur générée par l'ordinateur à partir d'une vue
historique des données d'un événement qui s'est produit dans le passé, "projected" crée une
valeur générée par l'ordinateur, prévue dans l'avenir. Le schéma de numérotation "approche
n°1", "approche n°2", et ainsi de suite, est un emplacement réservé dans lequel les
approches utilisées peuvent être officiellement répertoriées pour un déploiement donné et
identifiées en tant que technique spécifique.
– 644 – 61968-9  CEI:2013

D.7 Exemples de codes de qualité


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Certains des codes décrits dans le Tableau D.15 sont utilisés dans des systèmes depuis la
publication de la CEI 61968-9:2009.

Tableau D.15 – Exemples de codes de qualité

Code de Origine Catégorie Statut


qualité (du tableau D.1) (du tableau D.2) Index (des tableaux D.3 à D.15) normatif
Non
Non fourni Non fourni AssumedValid aucun N
fourni
Dispositif
1.0.0 1 0 Validité DataValid 0 N
terminal
Dispositif
1.1.4 1 1 Diagnostic WatchdogFlag 4 N
terminal
Dispositif Collecte de
1.4.1 1 4 OverflowConditionDetected 1 N
terminal données
Dispositif Collecte de
1.4.16 1 4 DstInEffect 16 N
terminal données
Dispositif Collecte de
1.4.2 1 4 PartialInterval 2 N
terminal données
Dispositif Collecte de
1.4.3 1 4 LongInterval 3 N
terminal données
Dispositif Collecte de
1.4.4 1 4 SkippedInterval 4 N
terminal données
Dispositif Collecte de
1.4.5 1 4 TestData 5 N
terminal données
Dispositif
1.5.257 1 5 Raisonnabilité ErrorCode 257 N
terminal
2.0.0 Réseau Ms 2 0 Validité DataValid 0 N
2.3.4 Réseau Ms 2 3 Falsification ReverseRotation 4 N
2.3.5 Réseau Ms 2 3 Falsification StaticDataFlag 5 N
Collecte de
2.4.259 Réseau Ms 2 4 DstChangeOccurred 259 N
données
2.5.256 Réseau Ms 2 5 Raisonnabilité DataOutsideExpectedRange 256 N
2.5.257 Réseau Ms 2 5 Raisonnabilité ErrorCode 257 N
3.0.0 MDM 3 0 Validité DataValid 0 N
3.10.0 MDM 3 10 Douteux Indéterminé 0 N
3.10.1 MDM 3 7 Edité Accepté manuellement 1 N
3.11.0 MDM 3 11 Dérivé Dérivé – générique 0 N
3.11.1 MDM 3 11 Dérivé Dérivé – Déduit 1 N
3.3.3 MDM 3 3 Falsification RevenueProtectionSuspect 3 N
3.3.5 MDM 3 3 Falsification StaticDataFlag 5 N
3.5.259 MDM 3 5 Raisonnabilité Lecture manquante connue 259 N
Echec de la validation -
3.6.0 MDM 3 6 Validation 0 N
Générique
Edité manuellement -
3.7.0 MDM 3 7 Edité 0 N
Générique
3.8.0 MDM 3 8 Estimé Estimé - Générique 0 N
61968-9  CEI:2013 – 645 –

Annexe E
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Enumérations EndDeviceEventType

E.1 Généralités

Les systèmes de comptage non seulement collectent des relevés des compteurs mais
rapportent aussi des exceptions. La présente Annexe décrit les codes recommandés à utiliser
pour l'identification des événements CEI 61968.

Les codes d'EndDeviceEventTypes sont classés d'une manière qui divise le code énuméré en
4 parties:

EndDeviceEventType:=
<EndDeviceType>.<EndDeviceDomain>.<EndDeviceSubdomain>.<EndDeviceEventOrAction>

<EndDeviceType> = valeur numérique de l'énumération EndDeviceType (voir la section


EndDeviceType)

<EndDeviceDomain> = valeur numérique de l'énumération EndDeviceDomain (voir la section


EndDeviceDomain)

<EndDeviceSubdomain> = valeur numérique de l'énumération EndDeviSubdDomain (voir la


section EndDeviceSubdomain)

<EndDeviceEventOrAction> = valeur numérique de l'énumération EndDeviceEventOrAction (voir la


section EndDeviceEventOrAction)

E.2 Conditions d'alarme

E.2.1 Généralités

Alors que l'EndDeviceEventType définit l'événement qui s'est produit, il est également
nécessaire d'indiquer la gravité d'un événement (Alarm, Advisory, Normal, etc.). Il convient de
définir ces valeurs dans le champ EndDeviceEvent.severity. Cela permet à chaque système
mettant en œuvre des événements CIM de classifier la gravité de ses événements en fonction
de ses intentions, sans devoir effectuer un classement selon une définition rigide figurant
dans la CEI 61968-9.

E.2.2 Suppression de conditions d'alarme et communication des changements


d'état/de condition

Dans certains cas, le changement d'état d'un paramètre particulier doit être communiqué à un
système externe. Dans le petit nombre de cas qui a été découvert, on a simplement ajouté un
EndDeviceEventOrAction concis pour le décrire. Les événements suivants prennent en
charge cette méthode de communication.

Description de l'événement ou de la commande EndDeviceEvent


Catégorie (utilisant des mnémoniques d'énumération)
Diagnostic 8 Condition Fort courant neutre effacée *.Power.NeutralCurrent.
MaxLimitReachedCleared
Energie réactive avance effacée *.Power.PowerFactor.OutofRangeCleared
Attention 040000 Condition Energie réactive avance
– 646 – 61968-9  CEI:2013

Description de l'événement ou de la commande EndDeviceEvent


Catégorie (utilisant des mnémoniques d'énumération)
effacée
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Forte distorsion éliminée *.Power.PowerQuality.HighDistortionCleared


Diagnostic 5 Forte distorsion éliminée
Déséquilibre de tension éliminé *.Power.Voltage.ImbalanceCleared
Diagnostic 2 Déséquilibre de tension éliminé
Alerte phase effacée, condition d'alerte d'angle de *.Power.PhaseAngle.OutofRangeCleared
phase éliminée
Phase croisée éliminée *.Power.Phase.CrossPhaseCleared
Diagnostic 1 Polarité de condition, Phase croisée, Flux
de l'énergie Rv effacé
Phase inactive effacée *.Power.Phase.InactiveCleared
Diagnostic 3 Condition de phase inactive effacée
Bosse de tension commencée (Phase A) *.Power.PhaseAVoltage.SwellStarted
Bosse de tension commencée (Phase B) *.Power.PhaseBVoltage.SwellStarted
Bosse de tension commencée (Phase C) *.Power.PhaseCVoltage.SwellStarted
Bosse de tension éliminée *.Power. Voltage.SwellStopped
Attention 004000 Condition de surcharge de la
demande effacée
Bosse de tension arrêtée (Phase A) *.Power.PhaseAVoltage.SwellStopped
Diagnostic 7 Condition de surtension,
Phase A éliminée
Bosse de tension arrêtée (Phase B) *.Power.PhaseBVoltage.SwellStopped
Bosse de tension arrêtée (Phase C) *.Power.PhaseCVoltage.SwellStopped
Baisse soudaine de tension commencée (Phase A) *.Power.PhaseAVoltage.SagStarted
Baisse soudaine de tension commencée (Phase B) *.Power.PhaseBVoltage.SagStarted
Baisse soudaine de tension commencée (Phase C) *.Power.PhaseCVoltage.SagStarted
Baisse soudaine de tension éliminée *.Power.Voltage.SagStopped
Attention 000400 Condition de sous-tension éliminée
Baisse soudaine de tension arrêtée (Phase A); *.Power.PhaseAVoltage.SagStopped
Diagnostic 6 Condition de sous-tension,
Phase A éliminée
Baisse soudaine de tension arrêtée (Phase B) *.Power.PhaseBVoltage.SagStopped
Baisse soudaine de tension arrêtée (Phase C) *.Power.PhaseCVoltage.SagStopped

E.3 Données d'événement

Certains événements nécessitent ou contiennent plus de détails qu'une description et une


catégorie. Par exemple, la spécification d'un numéro de canal, numéro d'alarme, numéro de
relais, numéro de port, numéro de formule, numéro de version, etc. Il convient de les régler
sur l'élément identifié par la paire nom/valeur EndDeviceEvent.EventDetails.

Il convient toutefois de ne pas trop utiliser cette construction ou de l'utiliser à mauvais


escient. Cette construction a pour but unique de capturer des données auxiliaires relatives
à l'événement. Il convient de ne pas l'utiliser à la place de l'envoi d'un ensemble complet
d'informations EndDevice, par exemple (voir la Figure E.1).
61968-9  CEI:2013 – 647 –
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
Name-value pair, specific to end device Paire Name-value spécifique aux événements de
events dispositif terminal
Value, including unit information Valeur, comprenant des informations d’unité

Figure E.1 – Données d'événement

Voici quelques exemples de son utilisation:

Un événement d'appariement PAN terminé [PAN Pairing Completed] peut également fournir
les données suivantes.

<m:EndDeviceEvent>
:
<m:EndDeviceEventDetails>
<m:name>InstallDate</m:dateTime>
<m:value>2001-12-17</m:value>
</m:EndDeviceEventDetails>
<m:EndDeviceEventDetails>
<m:name>ShortId</m:dateTime>
<m:value>1002</m:value>
</m:EndDeviceEventDetails>
:
</m:EndDeviceEvent>

Un événement de téléchargement de microprogramme [Firmware Downloaded] peut


également fournir les données suivantes.

<m:EndDeviceEvent>
:
<m:EndDeviceEventDetails>
<m:name>FirmwareVersion</m:dateTime>
<m:value>1.2345</m:value>
</m: EndDeviceEventDetails>
:
</m:EndDeviceEvent>

Un événement d'exception de tension [Voltage Exception] peut également fournir les données
suivantes.

<m:EndDeviceEvent>
:
<m:EndDeviceEventDetails>
<m:name>VoltageThreshold</m:dateTime>
<m:value>3</m:value>
</m:EndDeviceEventDetails>
:
</m:EndDeviceEvent>
– 648 – 61968-9  CEI:2013

E.4 Identificateur en 4 parties: EndDeviceEventType


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Les Articles E.5 à E.8 décrivent chaque partie de l'énumération EndDeviceEventType:

• <EndDeviceType>
• <EndDeviceDomain>
• <EndDeviceSubdomain>
• <EndDeviceEventOrAction>

E.5 EndDeviceType

Au niveau le plus élevé, il est utile d'identifier le type d'appareil à partir duquel l'événement a
été créé. Il convient que chacun de ces éléments représente un appareil physique, bien que
la valeur zéro (0) puisse être utilisée dans des cas particuliers. Les codes EndDeviceType
sont énumérés et décrits dans le Tableau E.1.

Tableau E.1 – Codes EndDeviceType

Enumération EndDeviceType
Mnémonique Valeur Description
n/a 0 Non applicable. Utiliser ce type d'appareil lorsqu'un type d'appareil
n'est pas connu.
Collector 10 Appareil qui agit comme un point central de communication entre HES
et les appareils sur site.
ComDevice 26 Appareil de communication
DAPDevice 1 Appareil de point d'agrégation de données
DERDevice 2 Appareil de réponse à la demande
DSPDevice 6 Appareil de traitement de signaux numériques
ElectricMeter 3 Appareil situé sur les lieux de mesure de l'utilisation d'électricité.
ElectricVehicle 58 (ou véhicule électrique rechargeable) véhicule qui peut être branché
sur le réseau électrique.
EnergyRouter 23 Un routeur d'énergie, analogue au routeur de données et de
communications bien connu, détecte automatiquement la demande
d'électricité et délivre l'électricité sous la forme requise (CA ou CC)
à la tension et à la fréquence correctes sur un système d'alimentation
électrique.
Feeder 13 Les lignes ("feeders") transportent du courant triphasé et tendent
à suivre les chemins principaux près du poste.
GasMeter 4 Appareil situé sur les lieux pour mesurer l'utilisation du gaz.
Passerelle 5 Appareil de passerelle.
Generator 14 Il s'agit généralement d'un générateur électrique rotatif. Quelque
chose doit faire tourner le générateur: par exemple, une roue à aubes
dans un barrage hydroélectrique, un gros moteur diesel ou une turbine
à gaz.
InPremisesDisplay(IPD/IHD) 15 L'affichage IPD/IHD (In-Premises/In-Home Display) permet aux clients
de suivre leur consommation d'énergie sous une forme de tableau ou
de graphique en fonction des kWh utilisés.
LoadControlDevice 16 Appareil utilisé pour mettre en place des services "différables",
communément appelés "heures creuses".
NetworkRouter 11 Un routeur distribue des données informatiques numériques contenues
dans un paquet de données sur un réseau.
PANDevice 12 Appareil réseau PAN ("premises area network") qui ne fait l'objet de
détails supplémentaires.
PANGateway 7 Une passerelle PAN relie un réseau de communication externe à des
appareils de gestion de l'énergie dans les locaux.
61968-9  CEI:2013 – 649 –

Enumération EndDeviceType
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

PANMeter 17 Appareil réseau PAN ("premises area network") dont la fonction est
d'effectuer des mesures (de consommation électrique, par exemple).
PrepaymentTerminal 18 Appareil qui permet au client d'effectuer un paiement anticipé avant de
pouvoir utiliser l'énergie.
ProgCtlThermostat(PCT) 19 Appareil thermostat dont les paramètres peuvent être contrôlés par
l'intermédiaire d'une API (c'est-à-dire sans intervention humaine).
RangeExtender 20 Appareil d'extension de portée hertzienne ou répéteur hertzien qui
peut étendre la portée d'un réseau sans fil existant.
Regulator 21 Un régulateur de tension est un régulateur électrique conçu pour
maintenir automatiquement un niveau de tension constant.
Substation 22 Un poste ("substation") électrique est une station secondaire d'un
système de génération, de transport et de distribution de l'électricité
dans lequel la tension est diminuée ou augmentée à l'aide de
transformateurs.
Transformer 8 Appareil qui convertit la tension (de l'ordre de milliers de volts) d'un
générateur en un courant à très haute tension pour le transport longue
distance sur le réseau de transport.
WasteWaterMeter 25 Appareil de mesure de l'utilisation des eaux usées.
WaterMeter 24 Appareil de mesure de l'utilisation de l'eau.

E.6 EndDeviceDomain

Une fois le type d'appareil connu, il convient de classifier l'événement par un code
EndDeviceDomain. Ce code fournit une indication sur le caractère de haut niveau de
l'événement. Une attention particulière doit être accordée à EndDeviceDomain dans lequel un
événement est classé; grâce à une classification appropriée des événements par un petit
ensemble de codes EndDeviceDomain, un système peut exécuter plus facilement les rapports
sur la base des types d'événements qui se sont produits ou qui ont été reçus. Les codes
EndDeviceDomain sont énumérés et décrits dans le Tableau E.2.

Tableau E.2 – Codes EndDeviceDomain

Enumération EndDeviceDomain
Mnémonique Valeur Description
n/a 0 Non applicable. Utilisé lorsqu'un domaine n'est pas requis. Il convient de
ne l'utiliser que rarement.
AssociatedDevice 39 Appareil (un relais, par exemple) qui peut être associé à un dispositif
terminal.
Battery 2 Tous les événements ou les commandes relatif(ve)s à une batterie
d'appareil.
Billing 20 Evénements ou commandes relatif(ve)s au coût de l'énergie (y compris
les prix, tarifs, TOU, etc.).
Cartridge 3 Evénements ou commandes relatif(ve)s aux fusibles de cartouche.
Clock 36 Evénements ou commandes relatif(ve)s à une horloge interne d'appareil.
Communication 1 Evénements ou commandes purement relatif(ve)s aux problèmes de
communication. Envisager d'autres domaines avant d'utiliser celui-ci.
Configuration 7 Evénements ou commandes relatif(ve)s à la configuration de l'appareil.
Demand 8 Evénements ou commandes relatif(ve)s à la demande (c'est-à-dire kW) et
paramètres de la demande (par opposition à la consommation, c'est-à-
dire kWh).
Firmware 11 Evénements ou commandes relatif(ve)s au microprogramme (firmware) de
l'appareil.
GasSupply 4 Evénements ou commandes relatif(ve)s à la fourniture de gaz naturel ou
– 650 – 61968-9  CEI:2013

Enumération EndDeviceDomain
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

de propane.
Installation 6 Evénements ou commandes relatif(ve)s à l'installation de l'appareil.
KYZPulseCounter 38 Fonction de comptage d'impulsions à l'intérieur d'un compteur ou d'un
autre dispositif terminal.
LoadControl 15 Evénements ou commandes liés à la restriction ou au contrôle
automatique de la consommation d'énergie d'un client.
LoadProfile 16 Evénements ou commandes relatif(ve)s à la consommation d'énergie
(c'est-à-dire la "charge") au fil du temps sur un appareil.
Logs 17 Evénements ou commandes relatif(ve)s aux journaux internes d'un
appareil.
Memory 18 Evénements ou commandes relatif(ve)s à la mémoire de l'appareil.
Metrology 21 Evénements ou commandes relatif(ve)s à tout type de mesure réalisé par
un appareil.
MobileSecurity 14 Evénements ou commandes relatif(ve)s à la sécurité des appareils
lorsque l'appareil est accessible par le biais d'un outil ou appareil mobile.
Modem 19 Evénements ou commandes relatif(ve)s relatifs au modem d'un appareil.
ModuleFirmware 9 Evénements ou commandes relatif(ve)s au microprogramme d'un module
contenu dans un appareil.
Network 23 Evénements ou commandes relatif(ve)s au statut d'un appareil sur le
réseau. Egalement utilisé pour les événements réseau généraux, tels que
la mise en service d'un réseau PAN.
Pairing 10 Evénements ou commandes relatif(ve)s à la liaison d'appareils entre eux
(par exemple, PANDevice avec Meter, ComDevice avec Meter, etc.).
Power 26 Evénements ou commandes relatif(ve)s au statut d'alimentation d'un
appareil.
Pressure 29 Evénements ou commandes relatif(ve)s aux seuils de pression d'un
appareil.
RCDSwitch 31 Evénements ou commandes relatif(ve)s aux activités de connexion /
déconnexion à distance de l'appareil.
Recoder 41 Appareil de codage
Security 12 Evénements ou commandes relatif(ve)s à la sécurité des appareils (par
exemple, SecurityKey, HMAC, Parity, Rotation, TamperDetection, etc.).
Temperature 35 Evénements ou commandes relatif(ve)s à un appareil
VideoDisplay 13 Evénements ou commandes relatif(ve)s à l'affichage/l'écran CRT d'un
appareil.
Volume 40 Quantité d'un espace tridimensionnel délimité; espace occupé par un
liquide ou un gaz.
Watchdog 37 Fonction matérielle ou logicielle déclenchée à l'expiration d'un délai de
temporisateur.
WaterSupply 5 Evénements ou commandes relatif(ve)s à la fourniture en eau.

E.7 EndDeviceSubDomain

EndDeviceDomain peut être subdivisé en codes EndDeviceSubdomain. Les codes


EndDeviceSubdomain sont énumérés et décrits dans le Tableau E.3.

Tableau E.3 – Codes EndDeviceSubdomain

Enumération EndDeviceSubdomain
Mnémonique Valeur Description
n/a 0 Non applicable. Utilisé lorsqu'un sous-domaine n'est pas requis. Il
convient de ne l'utiliser que rarement
61968-9  CEI:2013 – 651 –

Enumération EndDeviceSubdomain
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Access 1 Relatif à la sécurité physique (c’est-à-dire, l'accessibilité) ou relatif


à l'autorisation électronique de lecture/écriture sur un support numérique
Activation 283 Ouverture d'une fonction
AlarmTable 285 Tableau interne d'un appareil pour le suivi des alarmes
ADConverter 142 Relatif à la conversion analogique-numérique
AllEvents 148 Relatif à un ensemble d'événements (généralement utilisé dans un
scénario d'annulation de tous les événements d'un contrôle de charge)
ApparentPower 290 Magnitude de la puissance complexe mesurée en volts-ampères
Allocation 2 Relatif à la désignation ou à l'affectation; généralement relatif à la
mémoire (RAM/ROM)
Association 74 Relatif à la liaison/l'appariement d'un appareil/objet à un autre
appareil/objet
AUTDProcess 3 Relatif aux processus Always Up To Date (AUTD), watchdog ou keep-alive
AutoRegistration 5 Relatif au processus d'enregistrement automatique
AutoTime 7 Relatif au réglage automatique de l'heure
BTU 13 Relatif aux British Thermal Units (BTU)
Buffer 14 Relatif au stockage temporaire de données
Cable 15 Relatif à un câble physique
Calculation 16 Relatif au calcul mathématique
Calibrage 18 Relatif à un ensemble de graduations affichant des positions ou des
valeurs
Certificate 21 Relatif à un document attestant l'authenticité de quelque chose;
généralement, un certificat de sécurité
Charge 22 relatif aux frais de facturation (billing charge, en anglais)
Checksum 284 Donnée de taille fixe calculée à partir d'un bloc arbitraire de données
numériques dans le cadre de la détection d'erreurs accidentelles
Concentration 39 Relatif à la densité ou à la composition d'une chose
Constants 23 Relatif à des valeurs définies de manière statique
ControlPoint 26 Relatif aux paramètres de contrôle de charge
Cover 29 Relatif à quelque chose qui constitue un couvercle ou qui fournit une
couverture
CRC 30 Relatif au contrôle de redondance cyclique
Credit 8 Relatif à la partie droite d'un compte; facturation
Current 6 Relatif à la puissance électrique mesurée en ampères
Data 31 Relatif aux informations factuelles
DataLog 33 Relatif à un enregistrement (c’est-à-dire un journal) d'informations
factuelles
Date 34 Relatif au temps calendaire
Day 35 Relatif à la partie jour du temps calendaire
DaylightSavingsTime 56 Relatif à la pratique consistant à avancer l'horloge d'une heure au
printemps.
DayLimit 299 Limite établie pour une période quotidienne
Decryption 36 Relatif à la conversion de données cryptées en données lisibles
Display 143 Relatif à un écran CRT, à un écran LED ou à toute autre forme d'appareil
vidéo
Door 128 Relatif à une barrière mobile utilisée pour couvrir une ouverture; par
exemple, une porte d'accès à un compteur ou à un collecteur
EmergencySupplyCapacityLimit 138 Relatif aux limites de capacité de fourniture d'urgence
– 652 – 61968-9  CEI:2013

Enumération EndDeviceSubdomain
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Encoder 40 Relatif à l'objet qui convertit les informations d'un format à un autre
EncoderRegister 41 Relatif au registre de l'encodeur (c’est-à-dire sur un compteur)
EPROM 42 Relatif à la mémoire en lecture seule programmable et effaçable
Event 43 Relatif à quelque chose qui s'est passé; il convient d'utiliser des sous-
domaines plus spécifiques avec celui-ci
EventLog 44 Relatif à un enregistrement (c’est-à-dire un journal) de données
d'événement
EWM 45 Relatif à un module sans fil externe
Feature 46 Relatif à une caractéristique non spécifique
FirmwareReset 47 Relatif à la restauration du microprogramme à son état d'origine
Flow 48 Relatif au mouvement d'une substance (électricité, gaz, eau, etc.)
FPV 49 Relatif à une forme de compressibilité élevée
Frames 50 Relatif à des blocs de taille fixe; comme en mémoire
Frequency 4 Relatif au nombre de cycles par unité de temps
GCAnalyzer 51 Relatif à l'analyseur chromatographique de gaz qui est utilisé pour
mesurer le mélange composant du gaz naturel fourni à un site
HeadEndSystem 52 Relatif au système de comptabilisation/AMI
HistoryLog 53 Relatif à un enregistrement (c’est-à-dire un journal) de données
historiques
HMAC 54 Relatif au code d'authentification du message haché; méthode spécifique
de calcul d'un MAC
Holiday 97 Relatif aux jours réservés ayant une signification spéciale
Identity 10 Relatif à un identificateur unique
Initialisation 298 Fonction de démarrage
Input 55 Relatif aux données entrées dans le système
InstallDate 57 Relatif à la date de préparation de l'utilisation
IntelligentRegister 58 Relatif à un registre spécifique sur un appareil
Interval 59 Relatif aux données d'énergie d'intervalle; durée entre deux événements
IO 60 Relatif aux entrées/sorties générales
IPAddress 127 Relatif à une adresse IP (Internet Protocol Address)
LANAddress 61 Relatif à une identification unique d'un appareil sur un réseau d'appareils
LastRead 62 Relatif à la lecture finale d'un compteur
List 63 Relatif à une liste interne [contenue en mémoire ou dans le
microprogramme]
ListPointers 64 Relatif à un ensemble spécifique de valeurs conservé par un compteur
Login 65 Relatif au processus par lequel on peut accéder à un appareil, un
ordinateur ou un système
LowSpeedBus 145 Relatif à un circuit qui relie le processeur à d'autres appareils;
transmission bas débit
MagneticSwitch 66 Relatif à n'importe quel type d'interrupteur magnétique
MaintMode 11 Relatif à un mode de fonctionnement spécifique dans lequel un appareil
peut être défini ou réglé
Measurement 67 Relatif à l'ampleur de la grandeur
MeasurementType 286 Code définissant le type de données de mesure
Mesh 68 Généralement relatif au type de compteur réseau
MeterBus 147 Relatif à un circuit qui connecte un appareil ou un module à un compteur
MeteringMode 12 Relatif à un mode de fonctionnement spécifique dans lequel un appareil
61968-9  CEI:2013 – 653 –

Enumération EndDeviceSubdomain
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

peut être défini ou réglé


Mobile 69 Relatif aux appareils qui ne sont pas confinés à un seul endroit
MOL% 70 Relatif au pourcentage de moles
NetworkId 71 Relatif à une identification unique d'un appareil sur un réseau d'appareils
NeutralCurrent 137 Relatif à la partie essentielle de l'unification électrofaible
NVRAM 72 Relatif à la mémoire vive non volatile
OptionBoard 146 Relatif à un type de module dans un compteur
Parameter 75 Relatif à une variable transmise à une fonction
ParentDevice 76 Relatif à un propriétaire d'appareil
Parity 77 Généralement relatif à un état pair/impair ou marche/arrêt; propriété de
symétrie
Password 24 Relatif à un mot de passe utilisé pour l'authentification
Phase 25 Généralement relatif à un moyen de distribuer le courant alternatif; lorsque
la phase spécifique n'est pas pertinente, il convient de l'utiliser en tant que
EndDeviceSubdomain
PhaseAngle 130 Relatif à la composante angulaire des coordonnées polaires
PhaseA 126 Relatif à la phase A d'un circuit multi-phase
PhaseAApparentPower 291 Puissance apparente de la phase A d'un circuit multi-phase
PhaseACurrent 287 Relatif au courant de la première phase d'une alimentation triphasée
PhaseAReactivePower 295 Puissance réactive de la phase A d'un circuit multi-phase
PhaseAVoltage 131 Relatif à la tension de la première phase d'une alimentation triphasée
PhaseAVoltagePotential 126 Relatif au potentiel de tension de la première phase d'une alimentation
triphasée
PhaseB 134 Relatif à la phase B d'un circuit multi-phase
PhaseBApparentPower 292 Puissance apparente de la phase B d'un circuit multi-phase
PhaseBCurrent 288 Relatif au courant de la seconde phase d'une alimentation triphasée
PhaseBReactivePower 296 Puissance réactive de la phase B d'un circuit multi-phase
PhaseBVoltage 132 Relatif à la tension de la seconde phase d'une alimentation triphasée
PhaseBVoltagePotential 134 Relatif au potentiel de tension de la seconde phase d'une alimentation
triphasée
PhaseC 135 Relatif à la phase C d'un circuit multi-phase
PhaseCApparentPower 293 Puissance apparente de la phase C d'un circuit multi-phase
PhaseCCurrent 289 Relatif au courant de la troisième phase d'une alimentation triphasée
PhaseCReactivePower 297 Puissance réactive de la phase C d'un circuit multi-phase
PhaseCVoltage 133 Relatif à la tension de la troisième phase d'une alimentation triphasée
PhaseCVoltagePotential 135 Relatif au potentiel de tension de la troisième phase d'une alimentation
triphasée
PhaseSequence 78 Relatif à l'ordre des phases d'une alimentation triphasée
PhaseVoltage 79 Dans une phase simple ou dans les situations où la phase spécifique n'est
pas pertinente, est relatif à la tension dans la phase
PowerFactor 27 Relatif au rapport de la puissance réelle découlant de la charge à la
puissance apparente dans le circuit
PowerQuality 28 Relatif à l'ensemble des limites de propriétés électriques qui permet aux
systèmes électriques de façon attendue sans perte significative de
performances
PowerQualityRecording 80 Relatif à la capture et au stockage de données de qualité électrique
PrepaymentCredit 81 Relatif à la partie droite d'un compte; facturation de comptes de
prépaiement
– 654 – 61968-9  CEI:2013

Enumération EndDeviceSubdomain
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Pricing 9 Relatif à la facturation


Processor 82 Relatif à une unité centrale de traitement, généralement
Program 83 Relatif à un ensemble prédéfini d'instructions
Pulse 84 Relatif à un moyen par lequel l'énergie est mesurée
Queue 197 Relatif à une zone de stockage relativement temporaire utilisée pour
conserver les demandes ou les tâches jusqu'à ce qu'elles puissent être
traitées
Radio 136 Relatif à un appareil physique qui traite les signaux radio
RAM 85 Relatif à la mémoire vive
Rate 86 Relatif à la vitesse
ReadAccess 202 Relatif au niveau d'autorisation détenu: lecture, écriture, mise à jour, par
exemple
Readings 87 Relatif à la collecte de données de consommation, de diagnostic et de
statut auprès d'un compteur
ReactivePower 294 Puissance qui n'effectue pas le travail mesuré en VA réactifs (VAr)
Recoder 300 Appareil de codage
Recovery 88 Relatif à un processus de restauration à partir d'un état de rupture
Register 89 Relatif à un emplacement réservé à des informations
Registration 90 Relatif à un processus par lequel un appareil est reconnu ou ajouté
Relay 91 Relatif à un interrupteur à fonctionnement électrique
RemoteAccess 211 Relatif à la sécurité physique (c’est-à-dire l'accessibilité) ou
à l'autorisation électronique de lecture/écriture sur support numérique
à partir d'un appareil mobile ou à partir d'un endroit autre que celui où se
trouve l'objet accédé
ROM 92 Relatif à la mémoire en lecture seule
Rotation 93 Relatif au déplacement d'un objet dans un mouvement circulaire
RTP 94 Relatif à la tarification en temps réel (Real-Time Pricing)
Schedule 95 Relatif à un calendrier ou un planning d'événements futurs
Season 228 Relatif à la division d'une année qui a été marquée par des changements
atmosphériques; généralement l'hiver, le printemps, l'été et l'automne
SecondaryCredit 96 Relatif à un montant de crédit autre que principal
SecuredRegister 98 Relatif à un registre spécifique sur un appareil
SecuredTable 99 Relatif à un tableau qui requiert une autorisation pour être accessible
SecurityKey 32 Relatif à un élément d'information qui détermine la sortie opérationnelle
d'un chiffrement cryptographique
SecurityKeyLength 119 Relatif à la longueur d'une clé de sécurité
SecurityKeyVersion 120 Relatif à la version d'une clé de sécurité
SelfRead 231 Relatif à un processus dans lequel un appareil se lira lui-même
SelfTest 100 Relatif à un processus où un appareil exécutera un essai interne sur lui-
même
Sensor 144 Relatif à un appareil mécanique qui transmet un signal à un appareil de
mesure
Session 129 Relatif à une session de communication, généralement
SetPoint 101 Relatif au seuil au-delà duquel une fonctionnalité est engagée;
généralement relatif au mode de commande de charge
SigmaticMessage 102 Relatif aux messages stigmatiques
Signature 103 Relatif à la sécurité électronique et à la signature de messages
SignatureLength 104 Relatif à la longueur d'une signature de sécurité
61968-9  CEI:2013 – 655 –

Enumération EndDeviceSubdomain
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

SignatureTimestamp 105 Relatif à la durée de validité d'une signature de sécurité


SignatureUsage 106 Relatif à la façon dont une signature est utilisée
SpecificGravity 240 Relatif au rapport de la densité de la substance à la densité de l'eau
StandardTime 107 Relatif à l'heure standard, par opposition à l'heure d'été
StandbyMode 108 Relatif à un mode de fonctionnement spécifique dans lequel un appareil
peut être défini ou réglé
Status 17 Relatif à l'état actuel de quelque chose
Storage 109 Relatif au support sur lequel l'information est maintenue; également relatif
à l'acte de stockage des informations
SupplyCapacityLimit 139 Relatif aux limites de capacité de fourniture
Table 110 Relatif à une structure contenant des lignes et des colonnes
Tariff 140 Terme de facturation relatif au coût ou au montant facturé
Test 111 Relatif à une classification désignant une action hors production
TestMode 19 Relatif à un mode de fonctionnement spécifique dans lequel un appareil
peut être défini ou réglé
TextMessage 112 Relatif à un message ou à un ensemble de caractères qui sont envoyés
à un appareil
Threshhold 261 Relatif à un niveau ou un point auquel il se produira quelque chose
Tier 113 Relatif à un niveau
Time 114 Relatif à l'heure du jour sous la forme
heures:minutes:secondes:millisecondes
Timeout 125 Relatif à un seuil spécifique précisant quand rendre la main
automatiquement en l'absence de réponse
TimeReset 115 Relatif à la réinitialisation de l'heure de la journée
TimeSync 116 Relatif au processus de réglage de la valeur de l'heure du jour sur un
appareil afin de le faire correspondre à celle d'une source de confiance
pour l'heure du jour
TimeVariance 117 Relatif à la différence acceptable de l'heure du jour d'un appareil par
rapport à une source de confiance pour l'heure du jour
TimeZone 118 Relatif aux régions horaires autour de la terre définies par les méridiens
TOU 121 Relatif au temps d'utilisation
Tranceiver 122 Relatif à un appareil qui possède à la fois un transmetteur et un récepteur
Usage 123 Relatif à la façon dont quelque chose est utilisé
Version 124 Relatif à une itération ou une traduction spécifique
Voltage 38 Relatif à la force électrique qui pourrait conduire un courant électrique
entre deux points
Window 73 Relatif à une période pendant laquelle un appareil peut être
associé à/couplé à un compteur ou à un autre appareil
WriteAccess 282 Relatif au niveau d'autorisation détenu: lecture, écriture, mise à jour, par
exemple

E.8 EndDeviceEventOrAction

La partie la plus spécifique de l'EndDeviceEventType est sa valeur EndDeviceEventOrAction.


Cette partie de l'énumération EndDeviceEventType se présente généralement sous la forme
d'un verbe qui définit l'action pour l'événement venant de se produire.

Les codes EndDeviceEventOrAction sont énumérés et décrits dans le Tableau E.4.


– 656 – 61968-9  CEI:2013

Tableau E.4 – Codes EndDeviceEventorAction

Enumération EndDeviceEventorAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Mnémonique Valeur Description


n/a 0 Non applicable. Utilisé lorsqu'un EndDeviceOrAction n'est pas requis. Il
convient de ne l'utiliser que rarement.
Aborted 1 Evénement qui se produit quand une intervention provoque l'arrêt de
l'élément (identifié par EndDeviceDomain/EndDeviceSubdomain).
Accessed 2 En général, il s'agit d'un événement de sécurité qui survient lorsque
l'accès physique ou l'accès aux données a été établi (qu'il soit autorisé
ou non).
Acknowledged 3 Evénement qui indique la réception de l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain).
Activated 4 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est à présent actif alors qu'il
était inactif.
AlmostFull 283 Evénement qui indique qu'une ressource a quasiment atteint sa
capacité maximale
ArmedForClosure 11 Evénement qui indique qu'une demande ArmForClosure a été effectuée
avec succès.
ArmedForOpen 12 Evénement qui indique qu'une demande ArmForOpen a été effectuée
avec succès.
ArmForClosure 5 Commande utilisée pour indiquer une demande d'armement d'un
interrupteur pour la fermeture.
ArmForClosureFailed 226 Evénement qui indique qu'une demande ArmForClosure a échoué.
ArmForOpen 6 Commande utilisée pour indiquer une demande d'armement d'un
interrupteur pour l'ouverture.
ArmForOpenFailed 222 Evénement qui indique qu'une demande ArmForOpen a échoué.
Attempted 7 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain), basé sur la combinaison
d'EndDeviceDomain et d'EndDeviceSubdomain, a été tenté.
Calculated 21 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain), basé sur la combinaison
d'EndDeviceDomain et d'EndDeviceSubdomain, a été calculé.
Cancel 8 Commande utilisée pour indiquer une demande de fin d'une commande
précédemment émise.
CancelFailed 86 Evénement qui indique qu'une annulation (Cancel) a échoué.
Cancelled 10 Evénement qui indique qu'une commande ou un ensemble de
commandes ayant été émis précédemment s'est terminé avec succès.
Change 13 Commande pour indiquer une demande de modifications.
Changed 24 Evénement qui indique qu'une demande Change connexe a été
effectuée avec succès.
ChangedOut 284 Evénement qui indique qu'un actif a été remplacé
ChangeOutRequired 27 Commande utilisée pour demander le remplacement d'un appareil par
un appareil du même type.
ChangePending 14 Evénement qui indique qu'une mise à jour n'a pas encore été réalisée.
Charged 15 Evénement qui peut indiquer un état relatif à la facturation ou
actuellement soumis à une charge électrique.
Cleared 28 Evénement qui peut indiquer que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) sur l'appareil a été résolu ou
vidé.
Close 299 Une commande pour l’élément décrit par
EndDeviceDomain/EndDeviceSubdomain,
NOTE Cette commande pourrait être utilisé pour fermer une fenêtre
en liaison. Elle ne doit pas être utilisée pour fermer un interrupteur.
A la place, la commande ‘Connect’ doit être utilisée .
61968-9  CEI:2013 – 657 –

Enumération EndDeviceEventorAction
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Closed 16 Evénement qui indique que l'élément (identifié par


EndDeviceDomain/EndDeviceSubdomain) sur l'appareil ayant été
ouvert n'est plus ouvert.
ColdStarted 31 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été démarré alors qu'il se
trouvait à l'état arrêté (différent d'un WarmStart qui implique le
démarrage de l'élément alors que celui-ci se trouvé déjà à l'état
démarré).
Confirmed 17 Evénement qui indique la réception et l'acceptation de l'élément
(identifié par EndDeviceDomain/EndDeviceSubdomain).
Connect 18 Commande de demande de mise en service d'un appareil.
NOTE Cela doit effectivement ‘fermer’ un interrupteur électrique ou
« ouvrir » une vanne d’eau.
Connected 42 Evénement qui indique qu'un appareil a été mis en service.
ConnectFailed 67 Evénement qui indique qu'une demande Connect a échoué.
Corrupted 43 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est passé de l'état correct
à l'état incorrect.
CorruptionCleared 281 Evénement qui indique qu'une condition d'endommagement a été
éliminée.
Create 82 Commande de demande de création de quelque chose.
Created 83 Evénement qui indique qu'une demande Create a réussi.
CreateFailed 297 Evénement qui indique qu'une demande Create a échoué.
CrossPhaseCleared 70 Evénement qui indique que l'instabilité due à la modulation croisée de
phases a été corrigée.
CrossPhaseDetected 45 Evénement qui indique une instabilité due à la modulation croisée.
Deactivated 19 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) sur l'appareil qui se trouvait
précédemment à l'état actif n'est plus actif.
Decreased 57 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) possède une valeur ou une
magnitude inférieure.
Delayed 20 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est plus lent que prévu ou se
terminera plus tard que prévu.
Disable 22 Commande de demande de rendre l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain)inopérant (interdit)
Disabled 66 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été rendu inopérant
(interdit).
DisableFailed 220 Evénement qui indique qu'une demande Disable a échoué.
Disallowed 161 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) n'était pas autorisé.
Disconnect 23 Commande qui demande qu'un appareil soit mis hors service; peut
également signifier une demande de connexion serveur à l'élément
(identifié par EndDeviceDomain/EndDeviceSubdomain).
Note: Cela doit effectivement « ouvrir » un interrupteur électrique ou
« fermer » une vanne d’eau.
Disconnected 68 Evénement qui indique qu'un appareil a été mis hors service avec
succès; peut également signifier que la connexion à l'élément (identifié
par EndDeviceDomain/EndDeviceSubdomain) a été coupée ou a pris
fin.
DisconnectFailed 84 Evénement qui indique qu'une demande Disconnect a échoué.
Display 77 Commande de demande d'affichage de quelque chose (comme dans un
TextMessage).
– 658 – 61968-9  CEI:2013

Enumération EndDeviceEventorAction
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Displayed 78 Evénement qui indique qu'une demande Display connexe a été


effectuée avec succès.
DisplayFailed 87 Evénement qui indique qu'une demande Display a échoué.
Distorted 91 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve dans un état
différent de l'état attendu.
Downloaded 25 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été transmis du réseau
à l'appareil.
Enable 26 Commande de demande de rendre opérant (permettre) l'élément
(identifié par EndDeviceDomain/EndDeviceSubdomain).
Enabled 76 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été rendu opérant.(permis)
EnableFailed 221 Evénement qui indique qu'une demande Enable a échoué.
Error 79 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) ne s'est pas achevé avec
succès.
ErrorCleared 279 Evénement qui indique qu'une condition d'erreur a été éliminée.
Established 29 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été reconnu.
EventStarted 287 Evénement qui indique qu'un événement (identifié par
EndDeviceDomain/EndDeviceSubdomain) a commencé.
EventStopped 288 Evénement qui indique qu'un événement (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été stoppé.
Exceeded 139 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a dépassé la valeur attendue.
Execute 30 Commande de demande d'exécution de l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain).
Expired 64 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a atteint une fin,
généralement déterminée par une date ou une heure.
Failed 85 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) n'a pas réussi.
Frozen 88 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve à l'état statique.
Full 32 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est complet.
HighDistortion 69 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a présenté un changement
non souhaité de la forme d'onde d'un signal.
HighDistortionCleared 71 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est revenu à la normale
après avoir été à l'état HighDistortion.
ImbalanceCleared 75 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est revenu à l'état d'équilibre
après avoir été à l'état de déséquilibre.
Imbalanced 98 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) n'est pas équilibré.
Inactive 100 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve à l'état inactif.
InactiveCleared 72 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est revenu à l'état actif après
avoir été à l'état inactif.
Increased 102 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a crû.
61968-9  CEI:2013 – 659 –

Enumération EndDeviceEventorAction
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Initialized 33 Evénement qui indique que l'élément (identifié par


EndDeviceDomain/EndDeviceSubdomain) a été réglé sur des valeurs
de départ.
InProgress 34 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se dirige actuellement vers
un objectif ou une fin.
Installed 105 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été préparé pour utilisation.
Invalid 35 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve dans un état
défaillant.
LimitChanged 296 Evénement qui indique que le point de définition d'une limite a changé
LimitReached 286 Evénement qui indique qu'une limite supérieure ou inférieure a été
franchie.
Loaded 36 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est à présent engagé.
LossDetected 47 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve dans un état de
déficience. Généralement utilisé en relation avec la puissance, la
tension ou le courant électrique.
MaxLimitChanged 295 Evénement qui indique que le point de définition d'une limite maximum
a changé
MaxLimitCleared 293 Evénement qui indique qu'un événement MaxLimitReached a été
éliminé
MaxLimitReached 93 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a atteint une valeur maximale
acceptable.
MaxLimitReachedCleared 73 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est revenu à un état
acceptable après s'être trouvé à l'état MaxLimitReached.
MinLimitChanged 294 Evénement qui indique que le point de définition d'une limite minimum a
changé
MinLimitCleared 292 Evénement qui indique qu'un événement MinLimitReached précédent a
été éliminé
MinLimitReached 150 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a atteint une valeur minimale
acceptable.
Mismatched 159 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) n'est pas compatible avec
lui-même ou avec quelque chose dans son environnement.
Missing 285 Evénement qui indique qu'une entité (par exemple,
EndDeviceDomain/EndDeviceSubdomain) est manquante
Normal 37 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve dans un état (ou
une norme) typique.
NotArmed 290 Evénement qui indique qu'un appareil n'est plus dans un état armé.
NotAuthorized 38 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a fait l'objet d'un accès sans
autorisation.
NotFound 160 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est perdu ou manquant.
Open 298 Une commande pour l’élément décrit par
EndDeviceDomain/EndDeviceSubdomain
NOTE Cette commande pourrait être utilisée pour ouvrir une fençtre
en liaison . Elle ne devrait pas être utilisée pour ouvrir un
interrupteur.La commade «’Disconnect’ devrait être utilisée à la place
Opened 39 Evénement qui indique que l'élément (identifié par
– 660 – 61968-9  CEI:2013

Enumération EndDeviceEventorAction
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceDomain/EndDeviceSubdomain) est accessible.


Opted-In 80 Evénement qui indique qu'un client a accepté de se joindre à un
programme.
Opted-out 81 Evénement qui indique qu'un client ne souhaite pas se joindre à un
programme.
OutofRange 40 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) s'est trouvé en dehors des
valeurs acceptables.
OutofRangeCleared 74 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) est revenu à des valeurs
acceptables.
Overflow 177 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a dépassé sa taille ou son
volume.
Preempted 41 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été remplacé par un autre
qui a priorité sur lui.
Processed 44 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a passé avec succès toutes
les étapes d'une procédure prescrite.
Read 46 Il peut s'agir d'un événement (si le terme est considéré comme participe
passé du verbe "Read", "lu" en français) ou d'une commande (si le
terme est considéré comme le verbe "Read" à l'infinitif, "lire" en
français).
Ready 48 Evénement qui indique qu'une condition "prêt" a été atteinte sur un
appareil.
ReadyForActivation 280 Evénement qui indique qu'un appareil a été préparé
Re-established 49 Evénement qui indique qu'une condition, généralement une connexion,
a été établie après avoir été perdue.
Registered 50 Evénement qui indique qu'un appareil ou qu'une condition d'un appareil
a été enregistré.
Released 51 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été libéré.
Removed 212 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été mis hors service.
Replaced 52 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été remplacé par un nouvel
élément, généralement parce qu'il était obsolète ou usé.
Reprogrammed 213 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a changé de directions ou de
programme.
Reset 214 Commande pour demander qu'il convient de réinitialiser l'élément à un
état zéro ou un état original (élément identifié par
EndDeviceDomain.EndDeviceSubdomain).
ResetFailed 65 Evénement qui indique qu'une demande Reset a échoué.
ResetOccurred 215 Evénement qui indique qu'une demande Reset connexe a été effectuée
avec succès.
Restarted 53 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a redémarré généralement
à partir d'un état déjà démarré.
Restored 216 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été replacé à son état
antérieur.
Reversed 219 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été placé à l'opposé de son
état normal. Généralement utilisé pour une rotation.
SagStarted 223 Evénement qui indique que l'élément (identifié par
61968-9  CEI:2013 – 661 –

Enumération EndDeviceEventorAction
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceDomain/EndDeviceSubdomain) a été glissé dans un état


différent de l'état attendu.
SagStopped 224 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a cessé de fléchir.
Généralement utilisé avec l'événement SagStarted.
Schedule 300 Une commande pour demander qu’un élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) soit positionné pour une
exécution à une date ultérieure.
Scheduled 225 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été réglé pour s'exécuter
à une date future.
ScheduledFailed Un évènement pour indiquer que la commande à un élément élément
(identifié par EndDeviceDomain/EndDeviceSubdomain) pour une
éxécution à une date ultérieure a échoué.
Sealed 227 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve dans un boîtier
étanche ou auquel on ne peut pas accéder directement.
Start 54 Commande de demande de déclenchement ou de démarrage de
l'élément (identifié par EndDeviceDomain/EndDeviceSubdomain).
Started 242 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a démarré.
StartFailed 217 Evénement qui indique qu'une demande Start a échoué.
Stop 55 Commande de demande d'arrêt normal de l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain).
StopFailed 218 Evénement qui indique qu'une demande Stop a échoué.
Stopped 243 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) s'est arrêté. Lorsque cela est
le résultat d'une commande Stop, il est supposé que les choses se sont
arrêtées normalement (c.-à-d. Sans erreurs).
Substituted 56 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été remplacé par un autre.
Succeeded 58 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) s'est accompli.
SwellStarted 248 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) s'est développé à partir de
son état attendu.
SwellStopped 249 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a cessé de gonfler.
Généralement utilisé avec l'événement SwellStarted.
SwitchPositionChanged 289 Evénement qui indique qu'une position de commutateur a changé.
TamperCleared 291 Evénement qui indique qu'une alarme de fraude a été éliminée.
TamperDetected 257 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été modifié ou altéré
secrètement. Ces événements sont généralement associés à la sécurité
ou à la facturation.
Terminate 303 Une commande pour demander qu’un élément (identifié par le
EndDeviceDomain/EndDeviceSubdomain) arrête immédiatement et
brusquement.
Terminated 59 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) s'est terminé de façon subite.
TerminateFailed Un évènement pour indiquer que la tentative d’arrêt d’ un élément
(identifié par le EndDeviceDomain/EndDeviceSubdomain) a échoué.
Tilted 263 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été penché ou incliné.
Uninitialized 61 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) possède toutes ses valeurs
à leur état de départ.
– 662 – 61968-9  CEI:2013

Enumération EndDeviceEventorAction
Mnémonique Valeur Description
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Unlocked 62 Evénement qui indique que le verrou, physique ou logiciel, de l'élément


(identifié par EndDeviceDomain/EndDeviceSubdomain) a été libéré.
Unsealed 269 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) n'est pas scellé.
Unsecure 63 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve dans un état non
protégé.
Unstable 270 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) se trouve dans un état
irrégulier.
Uploaded 60 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été transmis de l'appareil
au réseau.
WarmStarted 278 Evénement qui indique que l'élément (identifié par
EndDeviceDomain/EndDeviceSubdomain) a été démarré alors qu'il se
trouvait dans l'état déjà démarré (différent d'un ColdStart qui implique
qu'il a été démarré à partir de l'état démarré).
WriteFailed 282 Evénement qui indique qu'une opération d'écriture a échoué.

E.9 EndDeviceEventTypes normatifs

Les champs EndDeviceType, EndDeviceDomain, EndDeviceSubdomain et


EndDeviceEventOrAction sont combinés et présentés sous la forme d'une chaîne unique. Les
événements normatifs sont répertoriés dans les tableaux suivants E.5 à E.31, regroupés par
EndDeviceDomain.

Tableau E.5 – Evénements de Battery (batterie)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de la
Type Type Domain SubDomain EventOrAction
commande
Condition de batterie
faible détectée
Batterie faible
détectée pour le
module *.2.22.150 * Battery Charge MinLimitReached
Batterie faible
Batterie faible
détectée pour le
module
Batterie OK
*.2.22.37 * Battery Charge Normal
Batterie Rf OK
Batterie défaillante *.2.0.85 * Battery n/a Failed
Batterie installée *.2.0.105 * Battery n/a Installed

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.6 – Evénements de Billing (facturation)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de la
Type Type Domain SubDomain EventOrAction
commande
Ajusté le crédit restant *.20.8.24 * Billing Credit Changed
Soustrait du crédit
*.20.8.57 * Billing Credit Decreased
restant
61968-9  CEI:2013 – 663 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de la
Type Type Domain SubDomain EventOrAction
commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Ajouté au crédit
*.20.8.102 * Billing Credit Increased
restant
Crédit d'urgence de
*.20.81.102 * Billing PrepaymentCredit Increased
prépaiement
Programme de
*.20.83.24 * Billing Program Changed
tarification modifié
Activation de RTP *.20.94.4 * Billing RTP Activated
Désactivation de RTP *.20.94.19 * Billing RTP Deactivated
Activation de
*.20.95.4 * Billing Schedule Activated
programme spécial
Crédit d'urgence
*.20.96.102 * Billing SecondaryCredit Increased
secondaire
Tarif quotidien changé
Tarif hebdomadaire
*.20.140.24 * Billing Tariff Changed
changé
Changement de tarif
Réinitialisation de la
facturation
déprogrammée *.20.140.214 * Billing Tariff Reset
Réinitialisation de la
facturation
Etage changé *.20.113.24 * Billing Tier Changed
Discordance de
débuts de TOU
Discordance de TOU *.20.121.159 * Billing TOU Mismatched
Discordance d'années
de TOU

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre
de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement
cet événement.

Tableau E.7 – Evénements de Cartridge (cartouche)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de la
Type Type Domain SubDomain EventOrAction
commande
Erreur de cartouche *.3.17.79 * Cartridge Status Error
Cartouche gelée *.3.17.88 * Cartridge Status Frozen
Cartouche installée *.3.17.105 * Cartridge Status Installed
Aucune cartouche
*.3.17.160 * Cartridge Status NotFound
insérée
Cartouche retirée *.3.17.212 * Cartridge Status Removed
Cartouche changée
Cartouche bouton-
poussoir changée
Cartouche de terminal
*.3.17.52 * Cartridge Status Replaced
mobile
Mode de changement
de cartouche, lecture
impossible

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.
– 664 – 61968-9  CEI:2013

Tableau E.8 – Evénements de Clock (horloge)

Description de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
Réglage
automatique de *.36.7.58 * Clock AutoTime Succeeded
l'heure effectué
Réglage de date
*.36.34.24 * Clock Date Changed
changé
Date et heure
d'exécution non
valides
*.36.34.35 * Clock Date Invalid
Plage de dates et
heures complète non
valide
Erreur de
*.36.35.79 * Clock Day Error
changement de jour
Jour de longueur
*.36.35.35 * Clock Day Invalid
incorrecte
Passe de l'heure
DST à la nouvelle *.36.56.24 * Clock DaylightSavingsTime Changed
heure
Erreur de variation
de l'heure standard
ou de l'heure *.36.56.40 * Clock DaylightSavingsTime OutofRange
d'économie
d'énergie
Passage de l'heure
DST à l'heure *.36.56.214 * Clock DaylightSavingsTime Reset
précédente
Passer à l'heure
d'économie
*.36.56.242 * Clock DaylightSavingsTime Started
d'énergie au
printemps
Congé changé
*.36.97.24 * Clock Holiday Changed
Congés changés
Date d'installation
*.36.57.35 * Clock InstallDate Invalid
non valide
Problème temporaire
*.36.0.79 * Clock n/a Error
de clock
Dysfonctionnement
d'horloge
*.36.0.85 * Clock n/a Failed
Echec d'horloge
électronique
Saison changée *.36.228.24 * Clock Season Changed
Passer à l'heure
*.36.107.242 * Clock StandardTime Started
d'automne standard
Valeur de réglage de
l'heure mise à la
nouvelle heure
Temps de travail du
registre réglé sur
une nouvelle heure
Valeur de réglage de
l'heure changée *.36.114.24 * Clock Time Changed
(ancienne heure)
Valeur de réglage de
l'heure changée
Collector Radio Set
TimeKeeper
Réglage de l'heure
du compteur
61968-9  CEI:2013 – 665 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Variation du temps >


*.36.114.40 * Clock Time OutofRange
10 secondes
Valeur de réglage de
l'heure remise
à l'heure précédente
Heure de registre de *.36.114.214 * Clock Time Reset
travail mise à l'heure
précédente
Heure réinitialisée
Incapable de
*.36.115.85 * Clock TimeReset Failed
réinitialiser l'heure
Erreur de clock du
*.36.116.79 * Clock TimeSync Error
temps
Echec de
synchro:Echec de
*.36.116.85 * Clock TimeSync Failed
synchro ou E/S de
compteur (38)
Erreur de clock de
*.36.116.58 * Clock TimeSync Succeeded
l'enregistreur
La variation du
temps a dépassé les
limites, même après
que le module a
essayé de la
corriger. *.36.117.139 * Clock TimeVariance Exceeded
La variation du
temps a dépassé les
limites sans tentative
de correction
automatique.
ID de fuseau horaire
*.36.118.35 * Clock TimeZone Invalid
non valide

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre
de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement
cet événement.
– 666 – 61968-9  CEI:2013

Tableau E.9 – Evénements de Communication


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Description de
l'événement ou EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
de la Type Type Domain SubDomain EventOrAction
commande
Défaillance de
chien de garde
*.1.3.85 * Communication AUTDProcess Failed
ou d'entretien
détectée
Câble coupé *.1.15.85 * Communication Cable Failed
Défaillance de
communication
*.1.41.85 * Communication EncoderRegister Failed
de registre de
codeur
Comm HES RF
*.1.52.29 * Communication HeadEndSystem Established
établie
Comm Rf sans
*.1.52.85 * Communication HeadEndSystem Failed
HES
Défaillance de
communication IntelligentRegist
*.1.58.85 * Communication Failed
de registre er
intelligent
Communications
perdues entre
les modules au *.1.60.85 * Communication IO Failed
sein d'un
compteur
Discordance de
définition du *.1.60.159 * Communication IO Mismatched
tableau E/S
Comm Rf sans
*.1.68.85 * Communication Mesh Failed
maillage
Echec d'appel
téléphonique
entrant *.1.0.85 * Communication n/a Failed
Echec des
communications
Communications
*.1.0.49 * Communication n/a Re-established
rétablies
Communication
terminée *.1.0.59 * Communication n/a Terminated
normalement
Alarme file
*.1.197.85 * Communication Queue Failed
d'attente
Retard de
communication *.1.17.20 * Communication Status Delayed
du collecteur
Réinitialisation
de l'émetteur- *.1.122.214 * Communication Tranceiver Reset
récepteur Rf

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.
61968-9  CEI:2013 – 667 –

Tableau E.10 – Evénements de Configuration

Description de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Constantes
changées
Constante
primaire changée
Constante *.7.23.24 * Configuration Constants Changed
secondaire
changée
Constante de
sortie changée
ID du matériel du
*.7.10.24 * Configuration Identity Changed
compteur modifié
ID de passerelle
non valide
ID de *.7.10.35 * Configuration Identity Invalid
transformateur
non valide
Nœud manquant *.7.10.160 * Configuration Identity NotFound
Liste IP groupe
*.7.127.24 * Configuration IPAddress Changed
radio collecteur
Mode
maintenance
*.7.11.242 * Configuration MaintMode Started
Mode atelier de
compteur lancé
Mode atelier de
*.7.11.243 * Configuration MaintMode Stopped
compteur arrêté
Commencer les
lectures du
compteur
*.7.12.242 * Configuration MeteringMode Started
d'enregistrement
Commencer le
mode veille
Mode de
*.7.12.243 * Configuration MeteringMode Stopped
comptage arrêté
Demander la
configuration *.7.0.13 * Configuration n/a Change
client
Paramètres
réseau groupe *.7.0.24 * Configuration n/a Changed
radio collecteur
Erreur de
configuration *.7.0.79 * Configuration n/a Error
détectée
Configuration
*.7.0.33 * Configuration n/a Initialized
Initialized
Passerelle
*.7.0.213 * Configuration n/a Reprogrammed
reprogrammée
– 668 – 61968-9  CEI:2013

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Définition de
somme changée
Type de somme
changé
Synchro de
valeurs de
compteur
Synchro de
*.7.75.24 * Configuration Parameter Changed
valeurs de
somme
Lien de sortie
changé
Format d'énergie
changé
Format électrique
changé
Changement de
programme de
*.7.83.24 * Configuration Program Changed
compteur
effectué
Vitesse changée *.7.86.24 * Configuration Rate Changed
Point de
consigne
*.7.101.139 * Configuration SetPoint Exceeded
dépassé, canal

Mode "standby"
*.7.108.242 * Configuration StandbyMode Started
lancé
Support de
*.7.109.24 * Configuration Status Changed
stockage changé
Bouton d'essai
*.7.19.76 * Configuration TestMode Enabled
enfoncé
Mode d'essai
*.7.19.242 * Configuration TestMode Started
lancé
Mode essai
*.7.19.243 * Configuration TestMode Stopped
arrêté
Date et heure
d'expiration de *.7.125.35 * Configuration Timeout Invalid
délai non valides

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.11 – Evénements de Demand (demande)

Description de
l'événement ou EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
de la Type Type Domain SubDomain EventOrAction
commande
Incapable de
réinitialiser la *.8.0.65 * Demand n/a ResetFailed
demande
Réinitialisation
de demande *.8.0.215 * Demand n/a ResetOccurred
détectée
Discordance des
définitions de *.8.0.159 * Demand n/a Mismatched
demande
Seuil de
surcharge de la *.8.261.139 * Demand Threshhold Exceeded
demande
61968-9  CEI:2013 – 669 –

Description de
l'événement ou EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
de la Type Type Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

commande
Mise en garde
MaxLimitReache
relative au seuil *.8.261.93 * Demand Threshhold
d
de demande

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.12 – Evénements de Firmware (microprogramme)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
Erreur de
convertisseur
*.11.142.79 * Firmware ADConverter Error
analogique /
numérique
Constantes non
*.11.23.35 * Firmware Constants Invalid
valides
Inconnu dans
l'analyse
*.11.31.79 * Firmware Data Error
Marqueur de
diagnostic
Code d'événement
d'enregistrement
non reconnu *.11.31.35 * Firmware Data Invalid
Message
inintelligible reçu
Ecran d'erreur figé *.11.143.88 * Firmware Display Frozen
Alarme acquittée,
*.11.43.3 * Firmware Event Acknowledged
alarme n°
Alarme activée,
alarme n° *.11.46.4 * Firmware Feature Activated
Alarme de zone
Alarme désarmée,
alarme n°
Installation
à distance *.11.46.66 * Firmware Feature Disabled
désarmée
Synch à distance
désarmée
Alarme permise,
alarme n°
Installation
à distance permise
*.11.46.76 * Firmware Feature Enabled
Synch à distance
armée
Valeur d'alarme
fixée, alarme n°
Défaillance de
*.11.46.85 * Firmware Feature Failed
commande différée
Commande illégale *.11.46.35 * Firmware Feature Invalid
Incapable de
*.11.47.85 * Firmware FirmwareReset Failed
réinitialiser
Discordance d'ID
*.11.10.159 * Firmware Identity Mismatched
d'appareil interne
Entrée instable,
*.11.55.270 * Firmware Input Unstable
entrée n°
Lire l'erreur de
*.11.63.79 * Firmware List Error
liste d'articles
– 670 – 61968-9  CEI:2013

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Aucune liste de
protocole, type
introuvable
*.11.63.160 * Firmware List NotFound
Aucun élément de
lecture dans la
liste
Erreur de bus
*.11.145.79 * Firmware LowSpeedBus Error
basse vitesse
Alarme bus de
*.11.147.79 * Firmware MeterBus Error
compteur
Démarrage à froid *.11.0.31 * Firmware n/a ColdStarted
Image de firmware
*.11.0.43 * Firmware n/a Corrupted
corrompue
Configuration
*.11.0.79 * Firmware n/a Error
perdue
DCW charge radio
*.11.0.85 * Firmware n/a Failed
du collecteur
Reprogrammation
de compteur
Dispositif terminal
programmé
Configuration
écrite/changée *.11.0.213 * Firmware n/a Reprogrammed
Reprogrammé
Compteur
reconfiguré
L'appareil a été
synchronisé
Dernière
réinitialisation par
chien de garde
*.11.0.214 * Firmware n/a Reset
Réinitialisation de
l'équipement de
comptage
Redémarrage
*.11.0.53 * Firmware n/a Restarted
imprévu
Compteur non
*.11.0.61 * Firmware n/a Uninitialized
programmé
Démarrage
*.11.0.278 * Firmware n/a WarmStarted
à chaud
Erreur de tableau
*.11.146.79 * Firmware OptionBoard Error
d'options
Erreur de
paramètre
*.11.75.79 * Firmware Parameter Error
Erreur de
configuration
Données de
reprogrammation
non valides
*.11.75.35 * Firmware Parameter Invalid
Type d'appareil
non valide, par
exemple pas TOU
Discordance de
configuration *.11.75.159 * Firmware Parameter Mismatched
diverse
Numéro de
téléphone alternatif *.11.75.56 * Firmware Parameter Substituted
utilisé
Echec du
processeur de *.11.82.85 * Firmware Processor Failed
registre
Etat illégal de
processeur de *.11.82.35 * Firmware Processor Invalid
commandes
61968-9  CEI:2013 – 671 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Réinitialisation de
*.11.82.214 * Firmware Processor Reset
processeur
Mise en garde non
*.11.83.79 * Firmware Program Error
programmée
Dysfonctionnement
*.11.83.85 * Firmware Program Failed
de programme
Erreur
d'autocontrôle
*.11.100.79 * Firmware SelfTest Error
Défaillance de
diagnostic
Echec de l'auto-
*.11.100.85 * Firmware SelfTest Failed
essai
Dysfonctionnement
*.11.144.85 * Firmware Sensor Failed
de capteur
Commande "Alter
option" exécutée *.11.17.24 * Firmware Status Changed
(changer option)
Mise à niveau du
*.11.17.14 * Firmware Status ChangePending
firmware en attente
Microprogramme
*.11.17.25 * Firmware Status Downloaded
téléchargé
Statut de
téléchargement
aval de firmware *.11.17.37 * Firmware Status Normal
Santé du compteur
vérifiée
Microprogramme
remplacé
Changement de *.11.17.52 * Firmware Status Replaced
microprogramme
Zigbee terminé
Réinitialisation
*.11.17.214 * Firmware Status Reset
d'appareil achevée
Fin du tableau
d'événements de *.11.110.79 * Firmware Table Error
données atteinte
Affichage des
différences de *.11.110.159 * Firmware Table Mismatched
tableau
Appel
téléphonique *.11.111.58 * Firmware Test Succeeded
entrant d'essai
Différences
d'affichage du *.11.19.159 * Firmware TestMode Mismatched
mode essai
Limite basse non
*.11.261.35 * Firmware Threshhold Invalid
valide
Facteur de
correction de *.11.261.40 * Firmware Threshhold OutofRange
calcul > max.
Version non valide
du logiciel de *.11.124.35 * Firmware Version Invalid
compteur
Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.
– 672 – 61968-9  CEI:2013

Tableau E.13 – Evénements GasSupply

Description de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
Perte totale de
l'approvisionnement *.4.0.85 * GasSupply n/a Failed
en gaz
Approvisionnement
*.4.0.216 * GasSupply n/a Restored
en gaz rétabli

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.14 – Evénements d'Installation

Description de
l'événement ou EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
de la Type Type Domain SubDomain EventOrAction
commande
Statut
d'enregistrement *.6.5.34 * Installation AutoRegistration InProgress
automatique
Confirmation
d'enregistrement *.6.5.58 * Installation AutoRegistration Succeeded
automatique
Remplacement
*.6.0.27 * Installation n/a ChangeOut
de compteur

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.15 – Evénements LoadControl

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Point de contrôle
changé par la
condition
Point de
régulation
changé par la
commande
Point de *.15.26.24 * Loadcontrol ControlPoint Changed
régulation
changé en raison
du prépaiement
Point de
régulation
changé par
programme
Commande
*.15.0.1 * Loadcontrol n/a Aborted
"Abort" exécutée
Sélection
utilisateur de la
*.15.83.4 * LoadControl Program Activated
régulation de la
charge
61968-9  CEI:2013 – 673 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Fermeture
momentanée du
relais de contrôle
de la charge,
relais n° *.15.91.24 * Loadcontrol Relay Changed
Relais de
commande de
sortie basculé,
relais n°
Programme de
commutation *.15.95.1 * Loadcontrol Schedule Aborted
abandonné
Programme
*.15.95.36 * Loadcontrol Schedule Loaded
chargé
Restaurer la
régulation de la *.15.17.216 * Loadcontrol Status Restored
charge
Régulation de la
charge lancée
Relais de
régulation de la
charge fermé
Fermeture
permanente du *.15.17.242 * Loadcontrol Status Started
relais de
régulation de la
charge, relais n°
Modèle de
régulation de la
charge démarré
Relais de
régulation de la
charge ouvert
Relais de *.15.17.243 * Loadcontrol Status Stopped
régulation de la
charge ouvert,
relais n°
Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.16 – Evénements LoadProfile

Description de
l'événement ou EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
de la Type Type Domain SubDomain EventOrAction
commande
Pointeurs de
*.16.64.214 * Loadprofile ListPointers Reset
liste réinitialisés
Echec des
lectures de
*.16.87.85 * Loadprofile Readings Failed
surveillance de
la charge
Données de
profil de charge *.16.109.43 * Loadprofile Status Corrupted
corrompues
Zone des
données de
profils de *.16.109.32 * Loadprofile Status Full
charges presque
pleine
Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.
– 674 – 61968-9  CEI:2013

Tableau E.17 – Evénements de Logs (journaux)

Description de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

l'événement ou EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


de la Type Type Domain SubDomain EventOrAction
commande
Journal de
données *.17.33.60 * Logs DataLog Transmitted
téléchargé
Dernier article lu
du journal
*.17.44.24 * Logs EventLog Changed
d'événements
mis à jour
Journal
d'événements *.17.44.28 * Logs EventLog Cleared
vidé
Erreur de journal
*.17.44.79 * Logs EventLog Error
d'événements
Journal
d'événements *.17.44.32 * Logs EventLog Full
plein
Journal
d'événements
téléchargé *.17.44.60 * Logs EventLog Transmitted
Appel
d'événement
Dernier article lu
du journal
*.17.53.24 * Logs HistoryLog Changed
d'historique mis
à jour
Journal
d'historique *.17.53.28 * Logs HistoryLog Cleared
effacé

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.18 – Evénements de Memory (mémoire)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Erreur
d'allocation de la *.18.2.79 * Memory Allocation Error
mémoire
Erreur
d'engorgement/d
e dépassement *.18.14.177 * Memory Buffer Overflow
de capacité de
tampon
Mémoire EPROM
*.18.42.2 * Memory EPROM Accessed
lue
Mémoire EPROM
*.18.42.24 * Memory EPROM Changed
écrite
Défaillance
*.18.42.85 * Memory EPROM Failed
d'EPROM
Erreur de
*.18.50.79 * Memory Frames Error
tramage
Dépassement
d'intervalle –
*.18.59.177 * Memory Interval Overflow
pulsations >
65 535
61968-9  CEI:2013 – 675 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Détection de
corruption de *.18.0.43 * Memory n/a Corrupted
données
Discordance de
mémoire de *.18.0.159 * Memory n/a Mismatched
masse
Défaillance de
*.18.72.85 * Memory NVRAM Failed
NVRAM
Discordance des
définitions de *.18.75.159 * Memory Parameter Mismatched
famille
Erreur de
surveillance de
*.18.84.79 * Memory Pulse Error
pulsations
redondante
Erreur de RAM *.18.85.79 * Memory RAM Error
Défaillance de
*.18.85.85 * Memory RAM Failed
RAM
Mémoire RAM
*.18.85.32 * Memory RAM Full
pleine
Erreur de
récupération de *.18.88.85 * Memory Recovery Failed
données
Erreur de ROM *.18.92.79 * Memory ROM Error
Défaillance de
*.18.92.85 * Memory ROM Failed
ROM
Disque presque
*.18.109.32 * Memory Status Full
plein
Tableau de
*.18.110.32 * Memory Table Full
données plein
Dépassement de
connecteur de *.18.110.177 * Memory Table Overflow
tableau

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.19 – Evénements de Metrology (métrologie)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
BTU alarme
BTU hors *.21.13.40 * Metrology BTU OutofRange
intervalle
Erreur de calcul
de volume *.21.16.79 * Metrology Calculation Error
corrigé
Modification de
l'étalonnage
Valeur *.21.18.24 * Metrology Calibrage Changed
d'étalonnage
établie, n°
Déviation
excessive de *.21.18.40 * Metrology Calibrage OutofRange
l'étalonnage, n°
– 676 – 61968-9  CEI:2013

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Calibrage arrivé
*.21.18.64 * Metrology Calibrage Expired
à expiration
Alarme
*.21.39.40 * Metrology Concentration OutofRange
concentration
Journal
d'événements *.21.44.28 * Metrology EventLog Cleared
vidé
Défaillance
potentielle de *.21.45.85 * Metrology EWM Failed
l'EWM
FPV calculé de
manière *.21.49.40 * Metrology FPV OutofRange
déraisonnable
Défaillance
d'analyseur de *.21.51.85 * Metrology GCAnalyzer Failed
GC
Journal
d'historique *.21.53.28 * Metrology HistoryLog Cleared
effacé
Erreur de forme
*.21.55.79 * Metrology Input Error
C, entrée n°
Valeur non
*.21.55.35 * Metrology Input Invalid
valide, canal n°
Lecture
d'intervalle *.21.59.58 * Metrology Interval Succeeded
réussie
Dernier article lu
*.21.62.24 * Metrology LastRead Changed
mis à jour
Mettre à jour les
*.21.63.24 * Metrology List Changed
pointeurs de liste
Liste effacée *.21.63.28 * Metrology List Cleared
Réinitialiser les
*.21.63.214 * Metrology List Reset
pointeurs de liste
Erreur de mesure
*.21.67.79 * Metrology Measurement Error
détectée
Mesure échouée *.21.67.85 * Metrology Measurement Failed
MOL % total hors
*.21.70.40 * Metrology MOL% OutofRange
plage
Erreur de mesure
*.21.0.79 * Metrology n/a Error
détectée
Retour du
compteur dans
*.21.0.37 * Metrology n/a Normal
les limites, voie

Compteur
reprogrammé
Dispositif *.21.0.213 * Metrology n/a Reprogrammed
terminal
programmé
Défaillance de
mémoire non *.21.72.85 * Metrology NVRAM Failed
volatile détectée
Erreur
d'impulsion de *.21.84.79 * Metrology Pulse Error
turbine
Générateur
*.21.84.85 * Metrology Pulse Failed
d'impulsion
61968-9  CEI:2013 – 677 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Surremplissage
d'impulsions, *.21.84.177 * Metrology Pulse Overflow
voie n°
Echec de relevés
*.21.87.85 * Metrology Readings Failed
de compteur
kWh reçus –
*.21.87.37 * Metrology Readings Normal
alarme effacée
Lecture attendue
*.21.87.160 * Metrology Readings NotFound
manquante
Appel
téléphonique
*.21.87.225 * Metrology Readings Scheduled
entrant
programmé
Erreur de registre *.21.89.79 * Metrology Register Error
kW précédent >
capacité du *.21.89.139 * Metrology Register Exceeded
registre
Registre plein *.21.89.32 * Metrology Register Full
Discordance des
définitions de *.21.89.159 * Metrology Register Mismatched
registre
Lecture du
*.21.89.58 * Metrology Register Succeeded
registre réussie
autorelevé du
*.21.231.58 * Metrology SelfRead Succeeded
compteur
Message
SigmaticMessag
sigmatique non *.21.102.35 * Metrology Invalid
e
valide
Alarme relative
à la masse *.21.240.40 * Metrology SpecificGravity OutofRange
volumique
Erreur
d'autocontrôle *.21.17.79 * Metrology Status Error
détectée
Activation de
tableau en *.21.110.4 * Metrology Table Activated
attente
Tableau écrit *.21.110.24 * Metrology Table Changed
Tableau en
attente *.21.110.28 * Metrology Table Cleared
d'effacement
Seuil
supérieur/supérie
ur du compteur,
canal n°
Seuil supérieur
*.21.261.139 * Metrology Threshhold Exceeded
du compteur,
canal n°
Seuil supérieur
de la vitesse
delta, canal n°
Alarme
communiquée MaxLimitReache
*.21.261.93 * Metrology Threshhold
relative à la d
limite
– 678 – 61968-9  CEI:2013

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Seuil inférieur du
compteur, canal

Seuil de
MinLimitReache
dépassement *.21.261.150 * Metrology Threshhold
d
inférieur/inférieur
, canal n°
Alarme de limite
inférieure
Seuil supérieur /
inférieur du
*.21.261.40 * Metrology Threshhold OutofRange
compteur
dépassé
Limite haute
quotidienne
*.21.123.139 * Metrology Usage Exceeded
dépassée pour le
gaz

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.20 – Evénements MobileSecurity

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Erreur de
données
aléatoires de *.14.31.79 * MobileSecurity Data Error
jeton MAT ou
erreur LAN cible
Bloc d'adresses
LAN non valide
*.14.61.35 * MobileSecurity LANAddress Invalid
pour le jeton
MAT
ID réseau non
valide du jeton *.14.71.35 * MobileSecurity NetworkId Invalid
MAT
Erreur de
génération de
*.14.32.79 * MobileSecurity SecurityKey Error
message du jeton
MAT
Jeton MAT expiré
Jeton MAT
expiré, délai *.14.32.64 * MobileSecurity SecurityKey Expired
keep-alive
dépassé
Options non
valides du jeton *.14.32.35 * MobileSecurity SecurityKey Invalid
MAT
Jeton MAT
*.14.32.41 * MobileSecurity SecurityKey Preempted
préempté
Jeton MAT traité *.14.32.44 * MobileSecurity SecurityKey Processed
Jeton MAT libéré *.14.32.51 * MobileSecurity SecurityKey Released
Longueur non
SecurityKeyLeng
valide du jeton *.14.119.35 * MobileSecurity Invalid
th
MAT
Version non
SecurityKeyVers
valide du jeton *.14.120.35 * MobileSecurity Invalid
ion
MAT
61968-9  CEI:2013 – 679 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Session
précédente *.14.129.161 * MobileSecurity Session Disallowed
déjà établie

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.21 – Evénements de modem

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Interruption
d'alimentation
MinLimitReache
électrique, *.19.22.150 * Modem Charge
d
batterie modem
faible
Défaillance de
*.19.17.85 * Modem Status Failed
modem détectée
Modem initialisé *.19.17.33 * Modem Status Initialized
Remplacement
*.19.17.105 * Modem Status Installed
de modem
Aucun modem *.19.17.160 * Modem Status NotFound

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.22 – Evénements ModuleFirmware

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Microprogramme
du module *.9.17.52 * ModuleFirmware Status Replaced
remplacé

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.23 – Evénements Network (réseau)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Défaillance
d'association de *.23.74.85 * Network Association Failed
réseau
Première
connexion du *.23.52.42 * Network HeadEndSystem Connecté
collecteur
Appareil parent
*.23.76.66 * Network ParentDevice Disabled
non opérant
Défauts de la
*.23.136.85 * Network Radio Failed
radio
– 680 – 61968-9  CEI:2013

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Données
d'enregistrement
*.23.136.50 * Network Radio Enregistré
radio du
collecteur
Fermeture
d'entrée
*.23.17.42 * Network Status Connecté
facultative,
générateur
Appareil non
opérant
*.23.17.66 * Network Status Disabled
Passerelle non
opérante
Ouverture
d'entrée
facultative,
*.23.17.68 * Network Status Disconnected
générateur
Appareil
déconnecté
Erreur de DAP
*.23.17.79 * Network Status Error
Erreur de DSP
Défaillance de
nœud
*.23.17.85 * Network Status Failed
Défaillance de
liaison de nœud
Compteur installé
Passerelle *.23.17.105 * Network Status Installed
installée
Dispositif
*.23.17.227 * Network Status Sealed
terminal scellé
Dispositif
terminal non *.23.17.269 * Network Status Unsealed
scellé

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.24 – Evénements PAN / HAN

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Fenêtre
d'appariement *.10.73.16 * Pairing Window Closed
PAN fermée
Fenêtre
d'appariement
*.10.73.39 * Pairing Window Opened
PAN ouverte
(Ready To Pair)
Appariement
*.10.0.58 * Pairing n/a Succeeded
PAN réussi
Echec de
l'appariement *.10.0.85 * Pairing n/a Failed
PAN
Message texte
*.13.112.10 * VideoDisplay TextMessage Canceled
PAN annulé
Message texte
*.13.112.78 * VideoDisplay TextMessage Affiché
PAN affiché
61968-9  CEI:2013 – 681 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Tarification PAN
*.20.9.58 * Billing Pricing Succeeded
réussie
Echec de la
*.20.9.85 * Billing Pricing Failed
tarification PAN
Echec de
l'annulation de
tous les
*.15.148.86 * LoadControl AllEvents CancelFailed
événements de
contrôle de
régulation PAN
Annulation de
tous les
événements de *.15.148.10 * LoadControl AllEvents Canceled
contrôle de
régulation PAN
Echec de
l'annulation de
l'événement de *.15.43.86 * LoadControl Event CancelFailed
contrôle de
régulation PAN
Annulation de
l'événement de
*.15.43.10 * LoadControl Event Canceled
contrôle de
régulation PAN
Evénement de
contrôle de
*.15.43.225 * LoadControl Event Scheduled
régulation PAN
programmé
Inclusion de
l'événement de
*.15.43.80 * LoadControl Event Opt-In
contrôle de
régulation PAN
Exclusion de
l'événement de
*.15.43.81 * LoadControl Event Refuser
contrôle de
régulation PAN
Appareil PAN
supprimé
Appareil de
contrôle de
*.0.0.212 * n/a n/a Removed
régulation PAN
supprimé
Passerelle PAN
supprimée
Réseau PAN
*.23.0.76 * Network n/a Enabled
rendu opérant
Network PAN
rendu non *.23.0.66 * Network n/a Disabled
opérant

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.
– 682 – 61968-9  CEI:2013

Tableau E.25 – Evénements de Power (puissance)

Description de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Limite basse du
courant *.26.6.150 * Power Current MinLimitReached
dépassée
Fréquence de
*.26.4.270 * Power Frequency Unstable
ligne instable
Fort courant
*.26.137.93 * Power NeutralCurrent MaxLimitReached
neutre
Fort courant MaxLimitReached
*.26.137.y3 * Power NeutralCurrent
neutre éliminé Cleared
Condition de CrossPhaseDetec
*.26.25.45 * Power Phase
phase croisée ted
Condition de
CrossPhaseClear
phase croisée *.26.25.70 * Power Phase
ed
effacée
Perte de phase,
Désexcitation de *.26.25.85 * Power Phase Failed
phase
Condition de
phase inactive
(tension *.26.25.100 * Power Phase Inactive
présente, courant
absent)
Condition de
phase inactive *.26.25.72 * Power Phase InactiveCleared
effacée
Alerte phase
*.26.25.37 * Power Phase Normal
effacée
Seuil de phase *.26.25.40 * Power Phase OutofRange
Rétablissement
*.26.25.216 * Power Phase Restored
de phase
Seuil au-
dessus/au-
dessous de la *.26.130.40 * Power PhaseAngle OutofRange
limite de l'angle
de phase
Seuil au-
dessus/au-
OutofRangeClear
dessous de la *.26.130.74 * Power PhaseAngle
ed
limite de l'angle
de phase effacé
Limite dépassée
pour l'angle de *.26.130.139 * Power PhaseAngle Exceeded
phase
Baisse soudaine
de tension
*.26.131.223 * Power PhaseAVoltage SagStarted
commencée
(Phase A)
Baisse soudaine
de tension
*.26.131.224 * Power PhaseAVoltage SagStopped
arrêtée
(Phase A)
Bosse soudaine
de tension
*.26.131.248 * Power PhaseAVoltage SwellStarted
commencée
(Phase A)
61968-9  CEI:2013 – 683 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Bosse de tension
arrêtée *.26.131.249 * Power PhaseAVoltage SwellStopped
(Phase A)
Phase A inactive *.26.126.100 * Power PhaseA Inactive
Baisse soudaine
de tension
*.26.132.223 * Power PhaseBVoltage SagStarted
commencée
(Phase B)
Baisse soudaine
de tension
*.26.132.224 * Power PhaseBVoltage SagStopped
arrêtée
(Phase B)
Bosse soudaine
de tension
*.26.132.248 * Power PhaseBVoltage SwellStarted
commencée
(Phase B)
Bosse de tension
arrêtée *.26.132.249 * Power PhaseBVoltage SwellStopped
(Phase B)
Phase B inactive *.26.134.100 * Power PhaseB Inactive
Baisse soudaine
de tension
*.26.133.223 * Power PhaseCVoltage SagStarted
commencée
(Phase C)
Baisse soudaine
de tension
*.26.133.224 * Power PhaseCVoltage SagStopped
arrêtée
(Phase C)
Bosse soudaine
de tension
*.26.133.248 * Power PhaseCVoltage SwellStarted
commencée
(Phase C)
Bosse de tension
arrêtée (Phase *.26.133.249 * Power PhaseCVoltage SwellStopped
C)
Phase C inactive *.26.135.100 * Power PhaseC Inactive
Erreur de
séquence de *.26.78.79 * Power PhaseSequence Error
phase
Perte de
transducteur de
tension sur une
*.26.79.47 * Power PhaseVoltage LossDetected
phase
Perte de tension
par phase
Le facteur de
puissance
*.26.27.139 * Power PowerFactor Exceeded
dépasse les
limites.
Energie réactive
avance effacée
Condition OutofRangeClear
*.26.27.24 * Power PowerFactor
d'énergie ed
réactive en
avance effacée
– 684 – 61968-9  CEI:2013

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Mise en garde
relative
à l'énergie
réactive en
avance *.26.27.40 * Power PowerFactor OutofRange
Condition
d'énergie
réactive en
avance
Forte distorsion
*.26.28.69 * Power PowerQuality HighDistortion
détectée
Forte distorsion HighDistortionCle
*.26.28.71 * Power PowerQuality
éliminée ared
Evénement de
qualité d'énergie *.26.28.40 * Power PowerQuality OutofRange
générique
Enregistrement
PowerQualityRe
rendu non *.26.80.66 * Power Disabled
cording
opérant
Enregistrement PowerQualityRe
*.26.80.76 * Power Enabled
rendu opérant cording
Vérifier
l'alimentation
électrique de la
section
Vérifier
l'alimentation
électrique du
compteur
*.26.17.68 * Power Status Disconnected
Vérifier
l'alimentation
électrique du
départ
Vérifier
l'alimentation
électrique du
transformateur
Panne
d'alimentation en
énergie du
collecteur Rf
Panne
d'alimentation en
énergie
Mise hors tension
Panne
*.26.0.85 * Power n/a Failed
d'alimentation en
énergie non
détectée
Dernière alarme
de panne de
souffle
Interruption de
service du
Transformateur
Perte de
puissance ou de
*.26.126.85 * Power PhaseA Failed
tension de la
phase A
Perte de
puissance ou de
*.26.134.85 * Power PhaseB Failed
tension de la
phase B
61968-9  CEI:2013 – 685 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Perte de
puissance ou de
*.26.135.85 * Power PhaseC Failed
tension de la
phase C
Rétablissement
du compteur
Mise sous
tension /
Alimentation *.26.0.216 * Power n/a Restored
restaurée
Rétablissement
du
transformateur
Restauration de
la puissance ou
*.26.126.216 * Power PhaseA Restored
de la tension de
la phase A
Restauration de
la puissance ou
*.26.134.216 * Power PhaseB Restored
de la tension de
la phase B
Restauration de
la puissance ou
*.26.135.216 * Power PhaseC Restored
de la tension de
la phase C
Exception de
*.26.38.139 * Power Voltage Exceeded
tension
Condition de
déséquilibre de *.26.38.98 * Power Voltage Imbalanced
tension
Condition de
déséquilibre de *.26.38.75 * Power Voltage ImbalanceCleared
tension effacée
Perte de
transducteur de
tension VT *.26.38.47 * Power Voltage LossDetected
Faible potentiel
de perte détecté
Haute tension *.26.38.93 * Power Voltage MaxLimitReached
Basse tension *.26.38.150 * Power Voltage MinLimitReached
Déséquilibre de
*.26.38.37 * Power Voltage Normal
tension éliminé
Bosse de tension
*.26.38.37 * Power Voltage Normal
éliminée
Baisse soudaine
*.26.38.223 * Power Voltage SagStarted
de tension
Baisse soudaine
de tension *.26.38.224 * Power Voltage SagStopped
éliminée
Condition de sur
*.26.38.248 * Power Voltage SwellStarted
tension
Bosse de tension
*.26.38.249 * Power Voltage SwellStopped
éliminée

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre
de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement
cet événement.
– 686 – 61968-9  CEI:2013

Tableau E.26 – Evénements de Pressure (pression)

Description de
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

EndDeviceEvent EndDevice EndDevice EndDevice EndDevice


l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
La pression
MaxLimitReache
captée est égale *.29.261.93 * Pressure Threshhold
d
à P max.
La pression
MinLimitReache
captée est égale *.29.261.150 * Pressure Threshhold
d
à P min.
La pression est
*.29.261.40 * Pressure Threshhold OutofRange
hors plage.

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.27 – Evénements RCDSwitch

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Mise en marche
du service
Clôture d'entrée
de statut, n°
*.31.0.42 * RCDswitch n/a Connecté
Compteur
branché
Branchement
exécuté
Echec de
*.31.0.67 * RCDSwitch n/a ConnectFailed
connexion
Arrêt du service
Ouverture
d'entrée de
statut, n°
Compteur
*.31.0.68 * RCDswitch n/a Disconnected
débranché
Fonctionnement
du disjoncteur
Débranchement
exécuté
Echec de
connexion
*.31.0.84 * RCDswitch n/a DisconnectFailed
Echec de la
connexion

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre
de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement
cet événement.

Tableau E.28 – Evénements de Security (sécurité)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
tentative d'accès
*.12.1.38 * Security Access NotAuthorized
non autorisé
Unité accédée
Unité accessible au
lecteur *.12.1.58 * Security Access Succeeded
Unité accédée par
l'enregistreur
61968-9  CEI:2013 – 687 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Alerte expiration de
certificat
*.12.21.64 * Security Certificate Expired
Expiration de
certificat
Retrait de couvercle
*.12.29.212 * Security Cover Removed
détecté
Erreur CRC *.12.30.79 * Security CRC Error
Erreur de
déchiffrement de *.12.31.63 * Security Data Unsecure
texte en clair
Erreur générale de
*.12.36.79 * Security Decryption Error
déchiffrement
Echec de décryptage *.12.36.85 * Security Decryption Failed
Evénement de capot
*.12.128.2 * Security Door Accessed
du collecteur
Porte fermée *.12.141.16 * Security Enveloppe Closed
Porte ouverte *.12.141.39 * Security Enveloppe Opened
Falsification de
*.12.40.257 * Security Encoder TamperDetected
codeur
Echec d'initialisation
*.12.46.85 * Security Feature Failed
du cryptage
Ecoulement inverse
*.12.48.219 * Security Flow Reversed
détecté
Erreur de
décryptage, échec *.12.54.85 * Security HMAC Failed
HMAC
Echec d'ouverture
de session
utilisateur
*.12.65.85 * Security Login Failed
Echec d'ouverture
de session
passerelle
Alarme commutateur
*.12.66.257 * Security MagneticSwitch TamperDetected
magnétique
Falsification
physique
Indication de fraude *.12.0.257 * Security n/a TamperDetected
Tentative de fraude
détectée
Inclinaison détectée *.12.0.263 * Security n/a Tilted
ID réseau non valide
du jeton de *.12.71.35 * Security NetworkId Invalid
configuration
Erreur de parité *.12.77.79 * Security Parity Error
Mot de passe
*.12.24.24 * Security Password Changed
changé
Mot de passe non
*.12.24.35 * Security Password Invalid
valide
Unité accédée
*.12.211.58 * Security RemoteAccess Succeeded
à distance
Compteur inversé ou
rotation inverse
détectée *.12.93.219 * Security Rotation Reversed
Rotation inverse
détectée
– 688 – 61968-9  CEI:2013

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Registre sécurisé lu
*.12.98.2 * Security SecuredRegister Accessed
Tableau sécurisé lu
Clé locale
*.12.32.66 * Security SecurityKey Deactivated
désactivée
Clé locale activée *.12.32.76 * Security SecurityKey Activated
Erreur de génération
de message du jeton *.12.32.79 * Security SecurityKey Error
de configuration
Clé de sécurité non
*.12.32.35 * Security SecurityKey Invalid
valide
Options non valides
du jeton de *.12.32.35 * Security SecurityKey Invalid
configuration
Clé précédente
*.12.32.41 * Security SecurityKey Preempted
utilisée
Jeton de
*.12.32.44 * Security SecurityKey Processed
configuration traité
Clé locale débloquée *.12.32.62 * Security SecurityKey Unlocked
Longueur non valide
SecurityKeyLeng
pour le jeton de *.12.119.35 * Security Invalid
th
configuration
Version non valide
SecurityKeyVers
du jeton de *.12.120.35 * Security Invalid
ion
configuration
Erreur générale de
*.12.103.79 * Security Signature Error
signature
Erreur d'algorithme
de signature
Echec de vérification
de signature
Erreur de vérification
de signature
*.12.103.85 * Security Signature Failed
Echec de vérification
de signature
Erreur d'algorithme
de signature
Echec de vérification
de signature
Clé de signature non
valide spécifiée
Erreur de vérification
de signature
Clé de signature non
valide spécifiée
*.12.103.35 * Security Signature Invalid
Erreur de vérification
de signature
Clé de signature non
valide spécifiée
Erreur de vérification
de signature
Signature
*.12.103.160 * Security Signature NotFound
manquante
Longueur non valide *.12.104.35 * Security SignatureLength Invalid
Marqueur temporel
SignatureTimest
de signature non *.12.105.35 * Security Invalid
amp
valide
Erreur d'utilisation
*.12.106.79 * Security SignatureUsage Error
de signature
61968-9  CEI:2013 – 689 –

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de
Type Type Domain SubDomain EventOrAction
la commande
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Dispositif terminal
accessible en *.12.282.58 * Security WriteAccess Succeeded
écriture

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.29 – Evénements de Temperature (température)

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou de la
Type Type Domain SubDomain EventOrAction
commande
La température
retourne dans la *.35.0.37 * Temperature n/a Normal
plage.
La température est
*.35.0.40 * Temperature n/a OutofRange
hors plage.
La température captée
*.35.261.93 * Temperature Threshhold MaxLimitReached
est égale à T max.
La température captée
*.35.261.150 * Temperature Threshhold MinLimitReached
est égale à T min.

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.30 – Evénements VideoDisplay

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Défaillance
*.13.17.85 * VideoDisplay Status Failed
d'affichage

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.

Tableau E.31 – Evénements WaterSupply

Description de
EndDeviceEvent EndDevice EndDevice EndDevice EndDevice
l'événement ou
Type Type Domain SubDomain EventOrAction
de la commande
Perte totale de
l'approvisionnem *.5.0.47 * WaterSupply n/a Failed
ent en eau
Approvisionneme
*.5.0.270 * WaterSupply n/a Restored
nt en eau rétabli

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le
cadre de n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie
réellement cet événement.
– 690 – 61968-9  CEI:2013

Annexe F
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Enumérations EndDeviceControlType

F.1 Généralités

De nombreux systèmes de comptage ont la capacité d'émettre une commande à l'équipement


de terrain qui entreprend une action. L'action pourrait être une réinitialisation de demande,
une ouverture ou une fermeture d'un interrupteur ou un certain nombre d'autres activités. La
présente Annexe F décrit des exemples de codes qui peuvent être utilisés pour de telles
applications.

Les énumérations EndDeviceControlType sont classées de la même manière que les


énumérations EndDeviceEventType décrites à l'Annexe E. Le code est divisé en 4 parties:

EndDeviceControl.type:=
<EndDeviceType>.<EndDeviceDomain>.<EndDeviceSubdomain>.<EndDeviceEventOrAction>


<EndDeviceType> valeur numérique de l'énumération EndDeviceType (voir
EndDeviceType à l'Annexe E)
<EndDeviceDomain> valeur numérique de l'énumération EndDeviceDomain (voir
EndDeviceDomain à l'Annexe E)
<EndDeviceSubdomain> valeur numérique de l'énumération EndDeviSubdDomain (voir
EndDeviceSubdomain à l'Annexe E)
<EndDeviceEventOrAction> valeur numérique de l'énumération EndDeviceEventOrAction (voir
EndDeviceEventorAction à l'Annexe E)

Ces types de commandes comprennent les types de commandes utilisés pour les commandes
d'appareil PAN. Les commandes peuvent entraîner la génération d'un événement par le
dispositif terminal, opération qui serait ensuite rapportée par un message EndDeviceEvents.

F.2 Enumérations normatives EndDeviceControlType

Les champs EndDeviceType, EndDeviceDomain, EndDeviceSubdomain et EndDeviceEventO


rAction sont combinés et présentés sous la forme d'une chaîne unique. Les événements
normatifs sont répertoriés dans les tableaux suivants F.1 à F.4, regroupés par
EndDeviceDomain.

Tableau F.1 – Commandes de demande

Description de EndDeviceControl Evénements attendus EndDevice EndDevice EndDevice


l'événement ou de la Type
commande Domain SubDomain EventOrAction

Réinitialiser la demande *.8.0.214 *.8.0.215 Demand n/a Reset


*.8.0.65

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre de
n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement cet
événement.
61968-9  CEI:2013 – 691 –

Tableau F.2 – Commandes LoadControl

Description de EndDeviceControl Evénements attendus EndDevice EndDevice EndDevice


COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

l'événement ou de Type
la commande Domain SubDomain EventOrAction

Lancer régulation de *.15.0.54 *.15.17.242 LoadControl n/a Start


la charge, port 0
*.15.17.217
Arrêter/terminer la *.15.0.55 *.15.17.216 LoadControl n/a Stop
régulation de la
charge, port 1 *.15.17.218

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre de
n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement cet
événement.

Tableau F.3 – Commandes PAN/HAN

Description de l'événement EndDeviceControl Evénements EndDevice EndDevice EndDevice


ou de la commande Type attendus
Domain SubDomain EventOrAction
Fenêtre d'appariement PAN *.10.73.298 *.10.73.39 Pairing Window Open
ouverte
Fenêtre d'appariement PAN *.10.73.299 *.10.73.16 Pairing Window Close
ouverte
Message texte PAN affiché *.13.112.77 *.13.112.78 VideoDisplay TextMessage Display
Annulation du message texte *.13.112.8 *.13.112.10 VideoDisplay TextMessage Cancel
PAN
Créer un signal de prix PAN *.20.9.82 *.20.9.58 Billing Pricing Créer
Annulation de tous les *.15.148.8 *.15.148.10 LoadControl AllEvents Cancel
événements de contrôle de
régulation PAN
Annulation de l'événement *.15.43.8 *.15.43.10 LoadControl Event Cancel
de contrôle de régulation
PAN
Programmation de *.15.43.300 *.15.43.225 LoadControl Event Programme
l'événement de contrôle de
régulation PAN
Activation du réseau PAN *.23.0.26 *.23.0.76 Network n/a Activer
Désactivation du réseau *.23.0.22 *.23.0.66 Network n/a Désactiver
PAN

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre de
n'importe quelle utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement cet
événement.

Tableau F.4 – Commandes RCDSwitch

Description de l'événement EndDeviceControl Evénements EndDevice EndDevice EndDevice


ou de la commande Type attendus
Domain SubDomain EventOrAction
Désactiver la limite de *.31.138.22 *.31.138.66 RCDSwitch EmergencySupplyCapacityLimit Disable
capacité de fourniture
d'urgence RCD *.31.138.220

Activer la limite de capacité *.31.138.26 *.31.138.76 RCDSwitch EmergencySupplyCapacityLimit Enable


de fourniture d'urgence RCD
*.31.138.221
Armer le commutateur de *.31.0.5 *.31.0.11 RCDSwitch n/a ArmForClosure
branchement/débranchement
à distance en vue de la *.31.0.226
fermeture
– 692 – 61968-9  CEI:2013

Description de l'événement EndDeviceControl Evénements EndDevice EndDevice EndDevice


ou de la commande Type attendus
Domain SubDomain EventOrAction
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Armer le commutateur de *.31.0.6 *.31.0.12 RCDSwitch n/a ArmForOpen


branchement/débranchement
à distance en vue de *.31.0.222
l'ouverture
Fermer le commutateur de *.31.0.18 *.31.0.42 RCDSwitch n/a Connect
branchement/débranchement
à distance *.31.0.67

Désactiver la formule n°1 de *.31.0.22 *.31.0.66 RCDSwitch n/a Disable


limitation de demande pour
le commutateur RCD *.31.0.220
Désactiver le commutateur
RCD
Ouvrir le commutateur de *.31.0.23 *.31.0.68 RCDSwitch n/a Disconnect
branchement/débranchement
à distance *.31.0.84

Activer la formule n°2 de *.31.0.26 *.31.0.76 RCDSwitch n/a Enable


limitation de demande pour
le commutateur RCD *.31.0.221
Activer le commutateur RCD
Désactiver la limite de *.31.139.22 *.31.139.66 RCDSwitch SupplyCapacityLimit Disable
capacité de fourniture RCD
*.31.139.220
Activer la limite de capacité *.31.139.26 *.31.139.76 RCDSwitch SupplyCapacityLimit Enable
de fourniture RCD
*.31.139.221

Un astérisque (*) désigne n'importe quelle valeur EndDeviceType. Il est supposé que la valeur utilisée dans le cadre de n'importe quelle
utilisation de production de ces événements sera pertinente pour l'appareil qui envoie réellement cet événement.
61968-9  CEI:2013 – 693 –

Annexe G
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Conventions de désignation et d'identification des objets

G.1 Généralités

Cette Annexe décrit un exemple d'utilisation d'identificateurs d'objet requis par les messages
CEI 61968 pour maintenir la synchronisation et la corrélation des informations entre les
systèmes.

G.2 Identificateurs d'objet

Figure G.1 – Désignation CIM

CIM reconnaît qu'un objet peut être connu sous de nombreux noms. Il convient que les objets
reçoivent un "nom" donné par le système d'enregistrement en utilisant l'un des éléments de
désignation. Il convient que la valeur de mRID soit un identificateur global unique avec
un GUID mais il est vrai que les valeurs de nom sont généralement plus conviviales et
évocatrices. La contrainte d'unicité peut également être assouplie, comme défini pour les
règles d'un type de nom donné. Les règles d'unicité peuvent se répartir comme suit:

• unique de façon globale


• unique de façon globale pour un type de nom et l'autorité de type de nom associée
• unique à l'intérieur d'un appareil (par exemple, un compteur)
• emplacement physique (par exemple, un poste)
• sans contrainte d'unicité.

Dans tous les cas, les applications consommatrices nécessitent d’être conscientes des limites
d'unicité pour un type de nom donné s'il en existe un.

G.3 Identificateurs d'objet dans les messages

La Figure G.1 représente les modèles CIM utilisés pour les noms. Dans la Figure G.2, le
modèle est visible du point de vue d'une structure XML exemple qui serait réalisée dans un
profil de message.
– 694 – 61968-9  CEI:2013
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Légende

Anglais Français
A Model Authority issues mRIDs. Given that Un Modeling Authority (c'est-à-dire une autorité de
each Model Authority has a unique id and this modélisation) émet des mRID. Sachant que chaque
is part of the mRID, then the mRID is globally Modeling Authority a un identificateur unique et que
unique. cet identificateur fait partie du mRID, le mRID est
unique au niveau global.
Any free text that name the object. Tout texte libre qui désigne l'objet.
All names of this identified object. Tous les noms de cet objet identifié.
Type of this name. Type de ce nom.
Description of the name type. Description du type de nom.
Name of the name type. Nom du type de nom.
Authority responsible for managing names of Autorité en charge de la gestion des noms de ce
this type. type.

Figure G.2 – Structure XML exemple pour les noms

En utilisant l'exemple ci-dessus comme référence, les règles importantes suivantes doivent
être suivies:

Un objet peut être identifié à l'aide d'un mRID unique de façon globale

Un objet peut être identifié par une ou plusieurs valeurs Name.name

Les valeurs de mRID et Name.name peuvent être fournies

Si plusieurs valeurs Name.name sont fournies, il convient que chaque Name (nom) identifie
une valeur NameType.name correspondante

Alors que la valeur d'IdentifiedObject.name est définie au sein de la CIM, elle ne l'est pas
dans les profils CEI 61968-9 afin d'éviter les ambiguïtés, car un producteur pourrait choisir
d'utiliser IdentifiedObject.name et un consommateur s'attendre à rencontrer
IdentifiedObject.Name.name. C'est pourquoi l'utilisation d'IdentifiedObject.name est
déconseillée du point de vue de la norme CEI 61968-9.

Les producteurs et les consommateurs doivent convenir de l'utilisation des valeurs de mRID
ou de Name.name dans le cadre de la corrélation d'objets. Cela peut varier pour une mise en
œuvre donnée, mais l'utilisation des valeurs de Name.name est vivement recommandée.
61968-9  CEI:2013 – 695 –

Dans les cas de mises en œuvre où plusieurs consommateurs peuvent exister, un producteur
peut avoir à fournir plusieurs valeurs de Name.name, chacune avec un NameType.name
différent afin de répondre aux besoins spécifiques de chaque consommateur.
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

G.4 Références d'objet dans les messages

Dans les profils de messages, il est possible de se référer à un objet "par référence" ainsi que
"par valeur" (méthode courante imbriquée). Ces références peuvent être établies à l'aide de
valeurs de mRID ou de Name.name. Un exemple courant d'utilisation des références,
applicable dans le cadre de la norme CEI 61968-9, est disponible pour les ReadingTypes
(voir la Figure G.3).

Légende

Anglais Français
Type information for this reading value. Informations relatives au type pour cette valeur de
relevé.

Figure G.3 – Utilisation de noms comme références

Dans un message XML, l'attribut "ref " identifierait alors un ReadingType spécifique utilisant
une valeur de Name.name pour le type de lecture. Cette approche présente de nombreux
avantages, tels que la réduction de la taille du message XML et l'utilisation d'alias d'objet,
dans laquelle un objet peut être identifié par plusieurs noms.

Les références sont aussi utilisées pour identifier les types spécifiques d'EndDeviceControls
ou d'EndDeviceEvents; dans ce cas, des références à un EndDeviceControlType ou à un
EndDeviceEventType sont utilisées, le cas échéant.
– 696 – 61968-9  CEI:2013

Annexe H
(normative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Schémas XML pour les charges utiles de message

H.1 Généralités

La présente Annexe H a pour objet de fournir des schémas XML pour les charges utiles de
message afin d'augmenter les descriptions données plus haut dans le présent document. Ces
schémas XML ont été définis à l'aide des définitions de profils au sein de CIMTool. Ces
schémas peuvent être étendus selon les besoins à des fins de mises en œuvre spécifiques.
Cette Annexe H est complétée par les schémas XML informatifs fournis à l'Annexe I.

H.2 CustomerAccountConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerAccountConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/CustomerAccountConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">

<xs:element name="CustomerAccountConfig" type="m:CustomerAccountConfig"/>


<xs:complexType name="CustomerAccountConfig">
<xs:sequence>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="billingCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.billingCycle"/>
<xs:element name="budgetBill" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.budgetBill"/>
61968-9  CEI:2013 – 697 –

<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.ConfigurationEvents"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.3 CustomerAgreementConfig
<?xml version="1.0" encoding="UTF-8"?>
– 698 – 61968-9  CEI:2013

<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerAgreementConfig#"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/CustomerAgreementConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="CustomerAgreementConfig" type="m:CustomerAgreementConfig"/>
<xs:complexType name="CustomerAgreementConfig">
<xs:sequence>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Document.lastModifiedDateTime"/>
<xs:element name="loadMgmt" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.loadMgmt"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="signDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.signDate"/>
61968-9  CEI:2013 – 699 –

<xs:element name="subject" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.ConfigurationEvents"/>
<xs:element name="DemandResponsePrograms" type="m:DemandResponseProgram" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement.DemandResponsePrograms"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement.ServiceCategory"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="validityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.validityInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DemandResponseProgram"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DemandResponseProgram">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
– 700 – 61968-9  CEI:2013

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.4 CustomerConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/CustomerConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="CustomerConfig" type="m:CustomerConfig"/>
<xs:complexType name="CustomerConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
61968-9  CEI:2013 – 701 –

<xs:element name="type" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="pucNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.pucNumber"/>
<xs:element name="specialNeed" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.specialNeed"/>
<xs:element name="vip" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.vip"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#OrganisationRole.ConfigurationEvents"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#OrganisationRole.Organisation"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
– 702 – 61968-9  CEI:2013

<xs:element name="NameType" type="m:NameType" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Organisation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Organisation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Organisation.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone2"/>
<xs:element name="postalAddress" type="m:PostalAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.postalAddress"/>
<xs:element name="streetAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.streetAddress"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PostalAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PostalAddress">
<xs:sequence>
<xs:element name="poBox" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.poBox"/>
<xs:element name="postalCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.postalCode"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
61968-9  CEI:2013 – 703 –

<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.5 EndDeviceConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/EndDeviceConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/EndDeviceConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="EndDeviceConfig" type="m:EndDeviceConfig"/>
– 704 – 61968-9  CEI:2013

<xs:complexType name="EndDeviceConfig">
<xs:sequence>
<xs:element name="ComFunction" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="ConnectDisconnectFunction" type="m:ConnectDisconnectFunction"


minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="SimpleEndDeviceFunction" type="m:SimpleEndDeviceFunction" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ActivityRecord" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ActivityRecord">
<xs:sequence>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Channel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Channel">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.isVirtual"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
61968-9  CEI:2013 – 705 –

<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConnectDisconnectFunction"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="eventCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.eventCount"/>
<xs:element name="isConnected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isConnected"/>
<xs:element name="isDelayedDiscon" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isDelayedDiscon"/>
– 706 – 61968-9  CEI:2013

<xs:element name="isLocalAutoDisconOp" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoDisconOp"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="isLocalAutoReconOp" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoReconOp"/>
<xs:element name="isRemoteAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoDisconOp"/>
<xs:element name="isRemoteAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoReconOp"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="rcdInfo" type="m:RemoteConnectDisconnectInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.rcdInfo"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="installCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.installCode"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
61968-9  CEI:2013 – 707 –

<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:element name="ActivityRecords" type="m:ActivityRecord" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Asset.ActivityRecords"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ConfigurationEvents"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="ConnectDisconnectFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="SimpleEndDeviceFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SimpleEndDeviceFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:choice>
<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceCapability"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability">
<xs:sequence>
<xs:element name="autonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.autonomousDst"/>
<xs:element name="communication" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.communication"/>
<xs:element name="connectDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.connectDisconnect"/>
<xs:element name="demandResponse" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.demandResponse"/>
<xs:element name="electricMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.electricMetering"/>
<xs:element name="gasMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.gasMetering"/>
– 708 – 61968-9  CEI:2013

<xs:element name="metrology" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.metrology"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="onRequestRead" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.onRequestRead"/>
<xs:element name="outageHistory" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.outageHistory"/>
<xs:element name="pressureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pressureCompensation"/>
<xs:element name="pricingInfo" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pricingInfo"/>
<xs:element name="pulseOutput" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pulseOutput"/>
<xs:element name="relaysProgramming" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.relaysProgramming"/>
<xs:element name="reverseFlow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.reverseFlow"/>
<xs:element name="superCompressibilityCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.superCompressibilityCompensation"/>
<xs:element name="temperatureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.temperatureCompensation"/>
<xs:element name="textMessage" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.textMessage"/>
<xs:element name="waterMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.waterMetering"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="EndDeviceFunctionKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunctionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="autonomousDst"/>
<xs:enumeration value="demandResponse"/>
<xs:enumeration value="electricMetering"/>
<xs:enumeration value="gasMetering"/>
<xs:enumeration value="metrology"/>
<xs:enumeration value="onRequestRead"/>
<xs:enumeration value="outageHistory"/>
<xs:enumeration value="relaysProgramming"/>
<xs:enumeration value="reverseFlow"/>
<xs:enumeration value="waterMetering"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="isSolidState" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.isSolidState"/>
<xs:element name="phaseCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.phaseCount"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedCurrent"/>
<xs:element name="ratedVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedVoltage"/>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
<xs:element name="capability" type="m:EndDeviceCapability" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.capability"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate.installationDate"/>
61968-9  CEI:2013 – 709 –

<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate.manufacturedDate"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="purchaseDate" type="xs:date" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ProductAssetModel">
<xs:sequence>
<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
<xs:element name="modelNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.modelNumber"/>
<xs:element name="modelVersion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.modelVersion"/>
<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
– 710 – 61968-9  CEI:2013

<xs:element name="numerator" type="xs:integer"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="ReadingInterharmonic"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Register" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Register">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.isVirtual"/>
<xs:element name="leftDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.leftDigitCount"/>
<xs:element name="rightDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.rightDigitCount"/>
<xs:element name="touTierName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTierName"/>
<xs:element name="Channels" type="m:Channel" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.Channels"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="touTier" type="m:TimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTier"/>
</xs:sequence>
61968-9  CEI:2013 – 711 –

</xs:complexType>
<xs:complexType name="RemoteConnectDisconnectInfo"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RemoteConnectDisconnectInfo">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="armedTimeout" type="m:Seconds" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.armedTimeout"/>
<xs:element name="customerVoltageLimit" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.customerVoltageLimit"/>
<xs:element name="energyLimit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyLimit"/>
<xs:element name="energyUsageStartDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageStartDateTime"/>
<xs:element name="energyUsageWarning" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageWarning"/>
<xs:element name="isArmConnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmConnect"/>
<xs:element name="isArmDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmDisconnect"/>
<xs:element name="isEnergyLimiting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isEnergyLimiting"/>
<xs:element name="needsPowerLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsPowerLimitCheck"/>
<xs:element name="needsVoltageLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsVoltageLimitCheck"/>
<xs:element name="powerLimit" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.powerLimit"/>
<xs:element name="usePushbutton" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.usePushbutton"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Seal" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seal">
<xs:sequence>
<xs:element name="appliedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.appliedDateTime"/>
<xs:element name="condition" type="m:SealConditionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.condition"/>
<xs:element name="kind" type="m:SealKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.kind"/>
<xs:element name="sealNumber" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.sealNumber"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SealConditionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SealConditionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="broken"/>
<xs:enumeration value="locked"/>
<xs:enumeration value="missing"/>
<xs:enumeration value="open"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="SealKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealKind">
<xs:restriction base="xs:string">
<xs:enumeration value="lead"/>
<xs:enumeration value="lock"/>
<xs:enumeration value="other"/>
<xs:enumeration value="steel"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="SimpleEndDeviceFunction"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction">
– 712 – 61968-9  CEI:2013

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="configID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="kind" type="m:EndDeviceFunctionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction.kind"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Registers" type="m:Register" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.Registers"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.end"/>
<xs:element name="start" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Voltage">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivePower">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Seconds" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seconds">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Money">
<xs:restriction base="xs:decimal"/>
61968-9  CEI:2013 – 713 –

</xs:simpleType>
</xs:schema>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

H.6 EndDeviceControls
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/EndDeviceControls#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/EndDeviceControls#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="EndDeviceControls" type="m:EndDeviceControls"/>
<xs:complexType name="EndDeviceControls">
<xs:sequence>
<xs:element name="EndDeviceControl" type="m:EndDeviceControl"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceControlType" type="m:EndDeviceControlType"
minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ControlledAppliance"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ControlledAppliance">
<xs:sequence>
<xs:element name="isElectricVehicle" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isElectricVehicle"/>
<xs:element name="isExteriorLighting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isExteriorLighting"/>
<xs:element name="isGenerationSystem" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isGenerationSystem"/>
<xs:element name="isHvacCompressorOrFurnace" type="xs:boolean"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isHvacCompressorOrFurnace"/>
<xs:element name="isInteriorLighting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isInteriorLighting"/>
<xs:element name="isIrrigationPump" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isIrrigationPump"/>
<xs:element name="isManagedCommercialIndustrialLoad" type="xs:boolean"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isManagedCommercialIndustrialLoad"/>
<xs:element name="isPoolPumpSpaJacuzzi" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isPoolPumpSpaJacuzzi"/>
<xs:element name="isSimpleMiscLoad" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isSimpleMiscLoad"/>
<xs:element name="isSmartAppliance" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isSmartAppliance"/>
<xs:element name="isStripAndBaseboardHeater" type="xs:boolean"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isStripAndBaseboardHeater"/>
<xs:element name="isWaterHeater" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ControlledAppliance.isWaterHeater"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence/>
</xs:complexType>
<xs:complexType name="DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
– 714 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="ElectronicAddress"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="installCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.installCode"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Asset.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceAction"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction">
<xs:sequence>
<xs:element name="command" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.startDateTime"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControl"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="drProgramLevel" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.drProgramLevel"/>
<xs:element name="drProgramMandatory" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.drProgramMandatory"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.issuerTrackingID"/>
<xs:element name="priceSignal" type="m:FloatQuantity" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.priceSignal"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.reason"/>
61968-9  CEI:2013 – 715 –

<xs:choice minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.EndDeviceAction">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="PanDemandResponse" type="m:PanDemandResponse"


sawsdl:modelReference=""/>
<xs:element name="PanDisplay" type="m:PanDisplay"
sawsdl:modelReference=""/>
<xs:element name="PanPricing" type="m:PanPricing"
sawsdl:modelReference=""/>
</xs:choice>
<xs:element name="EndDeviceControlType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.EndDeviceControlType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="EndDeviceGroups" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.EndDeviceGroups"/>
<xs:element name="EndDevices" type="m:EndDevice" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.EndDevices"/>
<xs:element name="primaryDeviceTiming" type="m:EndDeviceTiming"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.primaryDeviceTiming"/>
<xs:element name="secondaryDeviceTiming" type="m:EndDeviceTiming"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.secondaryDeviceTiming"/>
<xs:element name="UsagePointGroups" type="m:UsagePointGroup"
minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.UsagePointGroups"/>
<xs:element name="UsagePoints" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.UsagePoints"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControlType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="domain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType.domain"/>
<xs:element name="eventOrAction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControlType.eventOrAction"/>
<xs:element name="subDomain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControlType.subDomain"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType.type"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceInfo"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo">
<xs:sequence/>
</xs:complexType>
<xs:complexType name="EndDeviceTiming"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceTiming">
<xs:sequence>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceTiming.duration"/>
– 716 – 61968-9  CEI:2013

<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceTiming.durationIndefinite"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="randomisation" type="m:RandomisationKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceTiming.randomisation"/>
<xs:element name="interval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceTiming.interval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanDemandResponse"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse">
<xs:sequence>
<xs:element name="avgLoadAdjustment" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.avgLoadAdjustment"/>
<xs:element name="cancelControlMode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.cancelControlMode"/>
<xs:element name="cancelDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.cancelDateTime"/>
<xs:element name="cancelNow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.cancelNow"/>
<xs:element name="command" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="coolingOffset" type="m:Temperature" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.coolingOffset"/>
<xs:element name="coolingSetpoint" type="m:Temperature" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.coolingSetpoint"/>
<xs:element name="criticalityLevel" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.criticalityLevel"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="dutyCycle" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.dutyCycle"/>
<xs:element name="enrollmentGroup" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.enrollmentGroup"/>
61968-9  CEI:2013 – 717 –

<xs:element name="heatingOffset" type="m:Temperature" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.heatingOffset"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="heatingSetpoint" type="m:Temperature" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDemandResponse.heatingSetpoint"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.startDateTime"/>
<xs:element name="appliance" type="m:ControlledAppliance" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDemandResponse.appliance"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanDisplay" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PanDisplay">
<xs:sequence>
<xs:element name="command" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="confirmationRequired" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDisplay.confirmationRequired"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="priority" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDisplay.priority"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.startDateTime"/>
<xs:element name="textMessage" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanDisplay.textMessage"/>
<xs:element name="transmissionMode" type="m:TransmissionModeKind"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanDisplay.transmissionMode"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanPricing" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PanPricing">
<xs:sequence>
<xs:element name="command" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.command"/>
<xs:element name="duration" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceAction.duration"/>
<xs:element name="durationIndefinite" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.durationIndefinite"/>
<xs:element name="providerID" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricing.providerID"/>
<xs:element name="startDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceAction.startDateTime"/>
<xs:element name="PanPricingDetails" type="m:PanPricingDetail"
minOccurs="0" maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricing.PanPricingDetails"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PanPricingDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail">
<xs:sequence>
<xs:element name="alternateCostDelivered" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.alternateCostDelivered"/>
<xs:element name="alternateCostUnit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.alternateCostUnit"/>
<xs:element name="currentTimeDate" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.currentTimeDate"/>
<xs:element name="generationPrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.generationPrice"/>
<xs:element name="generationPriceRatio" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.generationPriceRatio"/>
– 718 – 61968-9  CEI:2013

<xs:element name="price" type="m:Money" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.price"/>
<xs:element name="priceRatio" type="xs:float" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.priceRatio"/>
<xs:element name="priceTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.priceTier"/>
<xs:element name="priceTierCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.priceTierCount"/>
<xs:element name="priceTierLabel" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.priceTierLabel"/>
<xs:element name="rateLabel" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PanPricingDetail.rateLabel"/>
<xs:element name="registerTier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.registerTier"/>
<xs:element name="unitOfMeasure" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PanPricingDetail.unitOfMeasure"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RandomisationKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RandomisationKind">
<xs:restriction base="xs:string">
<xs:enumeration value="default"/>
<xs:enumeration value="end"/>
<xs:enumeration value="none"/>
<xs:enumeration value="start"/>
<xs:enumeration value="startAndEnd"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence/>
</xs:complexType>
<xs:simpleType name="TransmissionModeKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TransmissionModeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="anonymous"/>
<xs:enumeration value="both"/>
<xs:enumeration value="normal"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="FloatQuantity" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#FloatQuantity">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
61968-9  CEI:2013 – 719 –

<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#Money">
<xs:restriction base="xs:decimal"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:simpleType>
<xs:simpleType name="Temperature" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Temperature">
<xs:restriction base="xs:float"/>
</xs:simpleType>
</xs:schema>

H.7 EndDeviceEvents
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/EndDeviceEvents#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/EndDeviceEvents#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="EndDeviceEvents" type="m:EndDeviceEvents"/>
<xs:complexType name="EndDeviceEvents">
<xs:sequence>
<xs:element name="EndDeviceEvent" type="m:EndDeviceEvent" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Asset" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Asset">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.issuerTrackingID"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.userID"/>
<xs:element name="Assets" type="m:Asset" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.Assets"/>
<xs:element name="EndDeviceEventDetails" type="m:EndDeviceEventDetail" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.EndDeviceEventDetails"/>
<xs:element name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEvent.EndDeviceEventType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
– 720 – 61968-9  CEI:2013

<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.UsagePoint"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="EndDeviceEventDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail.name"/>
<xs:element name="value" type="m:StringQuantity" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="domain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.domain"/>
<xs:element name="eventOrAction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEventType.eventOrAction"/>
<xs:element name="subDomain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.subDomain"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.type"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
61968-9  CEI:2013 – 721 –

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="StringQuantity" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StringQuantity">
<xs:restriction base="xs:string"/>
</xs:simpleType>
</xs:schema>

H.8 GetCustomerAccountConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetCustomerAccountConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetCustomerAccountConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetCustomerAccountConfig" type="m:GetCustomerAccountConfig"/>
<xs:complexType name="GetCustomerAccountConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
– 722 – 61968-9  CEI:2013

<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#Name">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.9 GetCustomerAgreementConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetCustomerAgreementConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetCustomerAgreementConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetCustomerAgreementConfig" type="m:GetCustomerAgreementConfig"/>
<xs:complexType name="GetCustomerAgreementConfig">
61968-9  CEI:2013 – 723 –

<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"


maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
– 724 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier">
<xs:sequence>
61968-9  CEI:2013 – 725 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.10 GetCustomerConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetCustomerConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetCustomerConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetCustomerConfig" type="m:GetCustomerConfig"/>
<xs:complexType name="GetCustomerConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer.kind">
<xs:simpleType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
</xs:element>
– 726 – 61968-9  CEI:2013

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.11 GetEndDeviceConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetEndDeviceConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetEndDeviceConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetEndDeviceConfig" type="m:GetEndDeviceConfig"/>
<xs:complexType name="GetEndDeviceConfig">
61968-9  CEI:2013 – 727 –

<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"


maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 728 – 61968-9  CEI:2013

<xs:element name="amrSystem" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
61968-9  CEI:2013 – 729 –

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="Names" type="m:Name" minOccurs="0"


maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.12 GetEndDeviceControls
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetEndDeviceControls#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetEndDeviceControls#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetEndDeviceControls" type="m:GetEndDeviceControls"/>
<xs:complexType name="GetEndDeviceControls">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceControl" type="m:EndDeviceControl"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceControlType" type="m:EndDeviceControlType"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 730 – 61968-9  CEI:2013

<xs:element name="Names" type="m:Name" minOccurs="0"


maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControl"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceControl.issuerTrackingID"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControl.reason"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceControlType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceControlType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
61968-9  CEI:2013 – 731 –

</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
– 732 – 61968-9  CEI:2013

<xs:element name="Names" type="m:Name" minOccurs="0"


maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.13 GetEndDeviceEvents
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetEndDeviceEvents#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetEndDeviceEvents#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetEndDeviceEvents" type="m:GetEndDeviceEvents"/>
<xs:complexType name="GetEndDeviceEvents">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceEvent" type="m:EndDeviceEvent" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
61968-9  CEI:2013 – 733 –

</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEvent"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.issuerTrackingID"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
– 734 – 61968-9  CEI:2013

</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
61968-9  CEI:2013 – 735 –

<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#ServiceKind">
<xs:restriction base="xs:string">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.14 GetMeterConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetMeterConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetMeterConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetMeterConfig" type="m:GetMeterConfig"/>
<xs:complexType name="GetMeterConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
– 736 – 61968-9  CEI:2013

<xs:element name="CustomerAgreement" type="m:CustomerAgreement"


minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDeviceGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
61968-9  CEI:2013 – 737 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>
– 738 – 61968-9  CEI:2013

H.15 GetMeterReadings
<?xml version="1.0" encoding="UTF-8"?>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetMeterReadings#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetMeterReadings#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetMeterReadings" type="m:GetMeterReadings"/>
<xs:complexType name="GetMeterReadings">
<xs:sequence>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="EndDeviceGroup" type="m:EndDeviceGroup" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="MeterReadings" type="m:MeterReadings" minOccurs="0"/>
<xs:element name="Reading" type="m:Reading" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingQuality" type="m:ReadingQuality" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="TimeSchedule" type="m:TimeSchedule" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TransformerTank" type="m:TransformerTank" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CoincidentReading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Reading">
<xs:sequence>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.reason"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="ReadingType" type="m:ReadingType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.ReadingType"/>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.EndDeviceEventType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
61968-9  CEI:2013 – 739 –

</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#EndDeviceGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterReadings" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MeterReading">
<xs:sequence>
<xs:element name="isCoincidentTrigger" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading.isCoincidentTrigger"/>
<xs:element name="EndDeviceEvents" type="m:EndDeviceEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.EndDeviceEvents"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Meter"/>
<xs:element name="Readings" type="m:CoincidentReading" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Readings"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Reading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Reading">
<xs:sequence>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.reason"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
– 740 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="ReadingQuality" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingQuality">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="ReadingQualityType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingQuality.ReadingQualityType">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQualityType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeSchedule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TimeSchedule">
<xs:sequence>
<xs:element name="scheduleInterval" type="m:DateTimeInterval"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TimeSchedule.scheduleInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TransformerTank" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TransformerTank">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  CEI:2013 – 741 –

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
</xs:schema>

H.16 GetServiceCategoryConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetServiceCategoryConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetServiceCategoryConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetServiceCategoryConfig" type="m:GetServiceCategoryConfig"/>
<xs:complexType name="GetServiceCategoryConfig">
<xs:sequence>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
– 742 – 61968-9  CEI:2013

<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
</xs:schema>

H.17 GetServiceLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetServiceLocationConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetServiceLocationConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetServiceLocationConfig" type="m:GetServiceLocationConfig"/>
<xs:complexType name="GetServiceLocationConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
61968-9  CEI:2013 – 743 –

<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>
– 744 – 61968-9  CEI:2013

H.18 GetServiceSupplierConfig
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<?xml version="1.0" encoding="UTF-8"?>


<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetServiceSupplierConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetServiceSupplierConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetServiceSupplierConfig" type="m:GetServiceSupplierConfig"/>
<xs:complexType name="GetServiceSupplierConfig">
<xs:sequence>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
</xs:schema>
61968-9  CEI:2013 – 745 –

H.19 GetUsagePointConfig
<?xml version="1.0" encoding="UTF-8"?>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetUsagePointConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetUsagePointConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="GetUsagePointConfig" type="m:GetUsagePointConfig"/>
<xs:complexType name="GetUsagePointConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
– 746 – 61968-9  CEI:2013

<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
61968-9  CEI:2013 – 747 –

</xs:simpleType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.20 GetUsagePointLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/GetUsagePointLocationConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/GetUsagePointLocationConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="GetUsagePointLocationConfig" type="m:GetUsagePointLocationConfig"/>
<xs:complexType name="GetUsagePointLocationConfig">
<xs:sequence>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement"
minOccurs="0" maxOccurs="unbounded"/>
– 748 – 61968-9  CEI:2013

<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"


maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePointGroup" type="m:UsagePointGroup" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
61968-9  CEI:2013 – 749 –

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
– 750 – 61968-9  CEI:2013

<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-


schema-cim15#UsagePoint">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointGroup"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointGroup">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.21 MasterDataLinkageConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/MasterDataLinkageConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/MasterDataLinkageConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="MasterDataLinkageConfig" type="m:MasterDataLinkageConfig"/>
<xs:complexType name="MasterDataLinkageConfig">
<xs:sequence>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ComModule" type="m:ComModule" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ConfigurationEvent" type="m:ConfigurationEvent" minOccurs="0"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="EndDevice" type="m:EndDevice" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="PricingStructure" type="m:PricingStructure" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="TransformerTank" type="m:TransformerTank" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComModule">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  CEI:2013 – 751 –

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
– 752 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TransformerTank" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TransformerTank">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  CEI:2013 – 753 –

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.22 MeterConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#" xmlns:m="http://iec.ch/TC57/2011/MeterConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/MeterConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="MeterConfig" type="m:MeterConfig"/>
<xs:complexType name="MeterConfig">
<xs:sequence>
<xs:element name="ComFunction" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ConnectDisconnectFunction" type="m:ConnectDisconnectFunction"
minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="SimpleEndDeviceFunction" type="m:SimpleEndDeviceFunction" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ActivityRecord" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ActivityRecord">
<xs:sequence>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Channel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Channel">
– 754 – 61968-9  CEI:2013

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.isVirtual"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
61968-9  CEI:2013 – 755 –

<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="modifiedBy" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConnectDisconnectFunction"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="eventCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.eventCount"/>
<xs:element name="isConnected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isConnected"/>
<xs:element name="isDelayedDiscon" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isDelayedDiscon"/>
<xs:element name="isLocalAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoDisconOp"/>
<xs:element name="isLocalAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoReconOp"/>
<xs:element name="isRemoteAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoDisconOp"/>
<xs:element name="isRemoteAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoReconOp"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="Names" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
– 756 – 61968-9  CEI:2013

</xs:complexType>
</xs:element>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
<xs:element name="rcdInfo" type="m:RemoteConnectDisconnectInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.rcdInfo"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceCapability"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability">
<xs:sequence>
<xs:element name="autonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.autonomousDst"/>
<xs:element name="communication" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.communication"/>
<xs:element name="connectDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.connectDisconnect"/>
<xs:element name="demandResponse" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.demandResponse"/>
<xs:element name="electricMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.electricMetering"/>
<xs:element name="gasMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.gasMetering"/>
<xs:element name="metrology" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.metrology"/>
61968-9  CEI:2013 – 757 –

<xs:element name="onRequestRead" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.onRequestRead"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="outageHistory" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.outageHistory"/>
<xs:element name="pressureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pressureCompensation"/>
<xs:element name="pricingInfo" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pricingInfo"/>
<xs:element name="pulseOutput" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pulseOutput"/>
<xs:element name="relaysProgramming" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.relaysProgramming"/>
<xs:element name="reverseFlow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.reverseFlow"/>
<xs:element name="superCompressibilityCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.superCompressibilityCompensation"/>
<xs:element name="temperatureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.temperatureCompensation"/>
<xs:element name="textMessage" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.textMessage"/>
<xs:element name="waterMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.waterMetering"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="EndDeviceFunctionKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunctionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="autonomousDst"/>
<xs:enumeration value="demandResponse"/>
<xs:enumeration value="electricMetering"/>
<xs:enumeration value="gasMetering"/>
<xs:enumeration value="metrology"/>
<xs:enumeration value="onRequestRead"/>
<xs:enumeration value="outageHistory"/>
<xs:enumeration value="relaysProgramming"/>
<xs:enumeration value="reverseFlow"/>
<xs:enumeration value="waterMetering"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="isSolidState" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.isSolidState"/>
<xs:element name="phaseCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.phaseCount"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedCurrent"/>
<xs:element name="ratedVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedVoltage"/>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
<xs:element name="capability" type="m:EndDeviceCapability" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.capability"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate.installationDate"/>
<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate.manufacturedDate"/>
– 758 – 61968-9  CEI:2013

<xs:element name="purchaseDate" type="xs:date" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="formNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.formNumber"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:element name="ActivityRecords" type="m:ActivityRecord" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Asset.ActivityRecords"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ConfigurationEvents"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="ConnectDisconnectFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="SimpleEndDeviceFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SimpleEndDeviceFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:choice>
<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
61968-9  CEI:2013 – 759 –

<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="MeterMultipliers" type="m:MeterMultiplier" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter.MeterMultipliers"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MeterMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:MeterMultiplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.kind"/>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="MeterMultiplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MeterMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="kE"/>
<xs:enumeration value="kH"/>
<xs:enumeration value="kR"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ProductAssetModel">
<xs:sequence>
<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
<xs:element name="modelNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.modelNumber"/>
– 760 – 61968-9  CEI:2013

<xs:element name="modelVersion" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.modelVersion"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingInterharmonic"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Register" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Register">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  CEI:2013 – 761 –

<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.isVirtual"/>
<xs:element name="leftDigitCount" type="xs:integer" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.leftDigitCount"/>
<xs:element name="rightDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.rightDigitCount"/>
<xs:element name="touTierName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTierName"/>
<xs:element name="Channels" type="m:Channel" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.Channels"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="touTier" type="m:TimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTier"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RemoteConnectDisconnectInfo"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RemoteConnectDisconnectInfo">
<xs:sequence>
<xs:element name="armedTimeout" type="m:Seconds" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.armedTimeout"/>
<xs:element name="customerVoltageLimit" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.customerVoltageLimit"/>
<xs:element name="energyLimit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyLimit"/>
<xs:element name="energyUsageStartDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageStartDateTime"/>
<xs:element name="energyUsageWarning" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageWarning"/>
<xs:element name="isArmConnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmConnect"/>
<xs:element name="isArmDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmDisconnect"/>
<xs:element name="isEnergyLimiting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isEnergyLimiting"/>
<xs:element name="needsPowerLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsPowerLimitCheck"/>
<xs:element name="needsVoltageLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsVoltageLimitCheck"/>
<xs:element name="powerLimit" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.powerLimit"/>
<xs:element name="usePushbutton" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.usePushbutton"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Seal" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seal">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="appliedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.appliedDateTime"/>
<xs:element name="condition" type="m:SealConditionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.condition"/>
<xs:element name="kind" type="m:SealKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.kind"/>
<xs:element name="sealNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.sealNumber"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SealConditionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SealConditionKind">
– 762 – 61968-9  CEI:2013

<xs:restriction base="xs:string">
<xs:enumeration value="broken"/>
<xs:enumeration value="locked"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="missing"/>
<xs:enumeration value="open"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="SealKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealKind">
<xs:restriction base="xs:string">
<xs:enumeration value="lead"/>
<xs:enumeration value="lock"/>
<xs:enumeration value="other"/>
<xs:enumeration value="steel"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="SimpleEndDeviceFunction"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="kind" type="m:EndDeviceFunctionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction.kind"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Registers" type="m:Register" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.Registers"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.end"/>
<xs:element name="start" type="xs:time" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Voltage">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
61968-9  CEI:2013 – 763 –

<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#ActivePower">
<xs:restriction base="xs:float"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:simpleType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Seconds" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Seconds">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

H.23 MeterReadings
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#" xmlns:m="http://iec.ch/TC57/2011/MeterReadings#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/MeterReadings#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="MeterReadings" type="m:MeterReadings"/>
<xs:complexType name="MeterReadings">
<xs:sequence>
<xs:element name="EndDeviceEventType" type="m:EndDeviceEventType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="MeterReading" type="m:MeterReading" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ReadingQualityType" type="m:ReadingQualityType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Asset" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Asset">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="issuerID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.issuerID"/>
<xs:element name="issuerTrackingID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.issuerTrackingID"/>
– 764 – 61968-9  CEI:2013

<xs:element name="reason" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.userID"/>
<xs:element name="Assets" type="m:Asset" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.Assets"/>
<xs:element name="EndDeviceEventDetails" type="m:EndDeviceEventDetail" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEvent.EndDeviceEventDetails"/>
<xs:element name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEvent.EndDeviceEventType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEvent.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail.name"/>
<xs:element name="value" type="m:StringQuantity" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventDetail.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceEventType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceEventType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="domain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.domain"/>
<xs:element name="eventOrAction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceEventType.eventOrAction"/>
<xs:element name="subDomain" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.subDomain"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceEventType.type"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="IntervalBlock" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#IntervalBlock">
<xs:sequence>
<xs:element name="IntervalReadings" type="m:IntervalReading" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IntervalBlock.IntervalReadings"/>
<xs:element name="PendingCalculation" type="m:PendingCalculation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IntervalBlock.PendingCalculation"/>
<xs:element name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IntervalBlock.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="IntervalReading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#IntervalReading">
<xs:sequence>
<xs:element name="reportedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.reportedDateTime"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
61968-9  CEI:2013 – 765 –

<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeasurementValue.timeStamp"/>
<xs:element name="value" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.value"/>
<xs:element name="ReadingQualities" type="m:ReadingQuality" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#BaseReading.ReadingQualities"/>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterReading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MeterReading">
<xs:sequence>
<xs:element name="isCoincidentTrigger" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading.isCoincidentTrigger"/>
<xs:element name="EndDeviceEvents" type="m:EndDeviceEvent" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading.EndDeviceEvents"/>
<xs:element name="IntervalBlocks" type="m:IntervalBlock" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterReading.IntervalBlocks"/>
<xs:element name="Meter" type="m:Meter" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Meter"/>
<xs:element name="Readings" type="m:Reading" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.Readings"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.UsagePoint"/>
<xs:element name="valuesInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterReading.valuesInterval"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PendingCalculation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PendingCalculation">
– 766 – 61968-9  CEI:2013

<xs:sequence>
<xs:element name="multiplyBeforeAdd" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#PendingCalculation.multiplyBeforeAdd"/>
<xs:element name="offset" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PendingCalculation.offset"/>
<xs:element name="scalarDenominator" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PendingCalculation.scalarDenominator"/>
<xs:element name="scalarFloat" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PendingCalculation.scalarFloat"/>
<xs:element name="scalarNumerator" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PendingCalculation.scalarNumerator"/>
<xs:element name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PendingCalculation.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Reading" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Reading">
<xs:sequence>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Reading.reason"/>
<xs:element name="reportedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.reportedDateTime"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.source"/>
<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeasurementValue.timeStamp"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.value"/>
<xs:element name="ReadingQualities" type="m:ReadingQuality" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#BaseReading.ReadingQualities"/>
<xs:element name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Reading.ReadingType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="timePeriod" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#BaseReading.timePeriod"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingInterharmonic"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingQuality" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingQuality">
<xs:sequence>
<xs:element name="comment" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.comment"/>
<xs:element name="source" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.source"/>
61968-9  CEI:2013 – 767 –

<xs:element name="timeStamp" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQuality.timeStamp"/>
<xs:element name="ReadingQualityType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#ReadingQuality.ReadingQualityType">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingQualityType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingQualityType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="category" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType.category"/>
<xs:element name="subCategory" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingQualityType.subCategory"/>
<xs:element name="systemId" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingQualityType.systemId"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
– 768 – 61968-9  CEI:2013

<xs:element name="argument" type="m:RationalNumber" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="StringQuantity" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StringQuantity">
<xs:restriction base="xs:string"/>
</xs:simpleType>
</xs:schema>

H.24 ServiceCategoryConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ServiceCategoryConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/ServiceCategoryConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="ServiceCategoryConfig" type="m:ServiceCategoryConfig"/>
<xs:complexType name="ServiceCategoryConfig">
<xs:sequence>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
61968-9  CEI:2013 – 769 –

<xs:element name="type" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceCategory.ConfigurationEvents"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
– 770 – 61968-9  CEI:2013

<xs:element name="remark" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.25 ServiceLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ServiceLocationConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/ServiceLocationConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="ServiceLocationConfig" type="m:ServiceLocationConfig"/>
<xs:complexType name="ServiceLocationConfig">
<xs:sequence>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CoordinateSystem" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CoordinateSystem">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="crsUrn" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CoordinateSystem.crsUrn"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
61968-9  CEI:2013 – 771 –

<xs:element name="password" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PositionPoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PositionPoint">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.sequenceNumber"/>
<xs:element name="xPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.xPosition"/>
<xs:element name="yPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.yPosition"/>
<xs:element name="zPosition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.zPosition"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.accessMethod"/>
<xs:element name="direction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.direction"/>
<xs:element name="geoInfoReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.geoInfoReference"/>
<xs:element name="needsInspection" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation.needsInspection"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation.siteAccessProblem"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.ConfigurationEvents"/>
<xs:element name="CoordinateSystem" type="m:CoordinateSystem" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.CoordinateSystem"/>
– 772 – 61968-9  CEI:2013

<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.electronicAddress"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone2"/>
<xs:element name="PositionPoints" type="m:PositionPoint" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Location.PositionPoints"/>
<xs:element name="secondaryAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.secondaryAddress"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
61968-9  CEI:2013 – 773 –

<xs:element name="countryCode" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.26 ServiceSupplierConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ServiceSupplierConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/ServiceSupplierConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="ServiceSupplierConfig" type="m:ServiceSupplierConfig"/>
<xs:complexType name="ServiceSupplierConfig">
<xs:sequence>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
– 774 – 61968-9  CEI:2013

<xs:element name="email2" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Organisation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Organisation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Organisation.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone2"/>
<xs:element name="postalAddress" type="m:PostalAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.postalAddress"/>
<xs:element name="streetAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.streetAddress"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PostalAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PostalAddress">
<xs:sequence>
<xs:element name="poBox" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.poBox"/>
<xs:element name="postalCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.postalCode"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.streetDetail"/>
61968-9  CEI:2013 – 775 –

<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.townDetail"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerIdentificationNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier.issuerIdentificationNumber"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#OrganisationRole.ConfigurationEvents"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#OrganisationRole.Organisation"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SupplierKind">
– 776 – 61968-9  CEI:2013

<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
</xs:schema>

H.27 UsagePointConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/UsagePointConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/UsagePointConfig#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="UsagePointConfig" type="m:UsagePointConfig"/>
<xs:complexType name="UsagePointConfig">
<xs:sequence>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0"
maxOccurs="unbounded"/>
<xs:element name="UsagePoint" type="m:UsagePoint" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AmiBillingReadyKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AmiBillingReadyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="amiCapable"/>
<xs:enumeration value="amiDisabled"/>
<xs:enumeration value="billingApproved"/>
<xs:enumeration value="enabled"/>
<xs:enumeration value="nonAmi"/>
<xs:enumeration value="nonMetered"/>
<xs:enumeration value="operable"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  CEI:2013 – 777 –

<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MetrologyRequirement"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.reason"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingTypes" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MetrologyRequirement.ReadingTypes">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="PhaseCode" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PhaseCode">
– 778 – 61968-9  CEI:2013

<xs:restriction base="xs:string">
<xs:enumeration value="A"/>
<xs:enumeration value="AB"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="ABC"/>
<xs:enumeration value="ABCN"/>
<xs:enumeration value="ABN"/>
<xs:enumeration value="AC"/>
<xs:enumeration value="ACN"/>
<xs:enumeration value="AN"/>
<xs:enumeration value="B"/>
<xs:enumeration value="BC"/>
<xs:enumeration value="BCN"/>
<xs:enumeration value="BN"/>
<xs:enumeration value="C"/>
<xs:enumeration value="CN"/>
<xs:enumeration value="N"/>
<xs:enumeration value="s1"/>
<xs:enumeration value="s12"/>
<xs:enumeration value="s12N"/>
<xs:enumeration value="s1N"/>
<xs:enumeration value="s2"/>
<xs:enumeration value="s2N"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="PricingStructure"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ReadingInterharmonic"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingType">
<xs:sequence>
61968-9  CEI:2013 – 779 –

<xs:element name="mRID" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceCategory"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
– 780 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="ServiceMultiplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceMultiplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.kind"/>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceMultiplierKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceSupplier"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SupplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="other"/>
<xs:enumeration value="retailer"/>
<xs:enumeration value="utility"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="TransformerTank"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TransformerTank">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePoint">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amiBillingReady" type="m:AmiBillingReadyKind"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.amiBillingReady"/>
<xs:element name="checkBilling" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.checkBilling"/>
61968-9  CEI:2013 – 781 –

<xs:element name="connectionState" type="m:UsagePointConnectedKind"


minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.connectionState"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="estimatedLoad" type="m:CurrentFlow" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.estimatedLoad"/>
<xs:element name="grounded" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.grounded"/>
<xs:element name="isSdp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isSdp"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.isVirtual"/>
<xs:element name="minimalUsageExpected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.minimalUsageExpected"/>
<xs:element name="nominalServiceVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.nominalServiceVoltage"/>
<xs:element name="outageRegion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.outageRegion"/>
<xs:element name="phaseCode" type="m:PhaseCode" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.phaseCode"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedCurrent"/>
<xs:element name="ratedPower" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ratedPower"/>
<xs:element name="readCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.readCycle"/>
<xs:element name="readRoute" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.readRoute"/>
<xs:element name="serviceDeliveryRemark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.serviceDeliveryRemark"/>
<xs:element name="servicePriority" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.servicePriority"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.ConfigurationEvents"/>
<xs:element name="Equipments" type="m:TransformerTank" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.Equipments"/>
<xs:element name="MetrologyRequirements" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.MetrologyRequirements">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement">
<xs:sequence>
<xs:element name="mRID" type="xs:string"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.mRID"/>
<xs:element name="reason" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.reason">
<xs:simpleType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration
value="billing"/>
<xs:enumeration
value="demandReset"/>
<xs:enumeration
value="inquiry"/>
<xs:enumeration
value="installation"/>
<xs:enumeration
value="loadManagement"/>
<xs:enumeration
value="loadResearch"/>
<xs:enumeration
value="moveIn"/>
<xs:enumeration
value="moveOut"/>
<xs:enumeration
value="other"/>
<xs:enumeration
value="removal"/>
<xs:enumeration
value="serviceConnect"/>
– 782 – 61968-9  CEI:2013

<xs:enumeration
value="serviceDisconnect"/>
</xs:restriction>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:simpleType>
</xs:element>
<xs:element name="Names" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name"
type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType">
<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>

<xs:element name="NameTypeAuthority" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority">

<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">

<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>

</xs:sequence>

</xs:complexType>

</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
<xs:element name="ReadingTypes"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MetrologyRequirement.ReadingTypes">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref"
type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
<xs:element name="PricingStructures" type="m:PricingStructure"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.PricingStructures"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceCategory"/>
<xs:element name="ServiceLocation" type="m:ServiceLocation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceLocation"/>
<xs:element name="ServiceMultipliers" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceMultipliers">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier">
61968-9  CEI:2013 – 783 –

<xs:sequence>
<xs:element name="mRID" type="xs:string"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.kind">
<xs:simpleType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration
value="ctRatio"/>
<xs:enumeration
value="ptRatio"/>
<xs:enumeration
value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
</xs:element>
<xs:element name="value" type="xs:float"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceMultiplier.value"/>
<xs:element name="Names" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name"
type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType">
<xs:complexType
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType">
<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>

<xs:element name="NameTypeAuthority" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority">

<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">

<xs:sequence>

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>

<xs:element name="name" type="xs:string"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>

</xs:sequence>

</xs:complexType>

</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
</xs:element>
<xs:element name="ServiceSupplier" type="m:ServiceSupplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePoint.ServiceSupplier"/>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation"
minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePoint.UsagePointLocation"/>
</xs:sequence>
– 784 – 61968-9  CEI:2013

</xs:complexType>
<xs:simpleType name="UsagePointConnectedKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointConnectedKind">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:restriction base="xs:string">
<xs:enumeration value="connected"/>
<xs:enumeration value="logicallyDisconnected"/>
<xs:enumeration value="physicallyDisconnected"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="UsagePointLocation"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Voltage" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Voltage">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="CurrentFlow" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CurrentFlow">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="ActivePower" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ActivePower">
<xs:restriction base="xs:float"/>
</xs:simpleType>
</xs:schema>

H.28 UsagePointLocationConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#"
xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/UsagePointLocationConfig#"
xmlns:sawsdl="http://www.w3.org/ns/sawsdl" xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/UsagePointLocationConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="UsagePointLocationConfig" type="m:UsagePointLocationConfig"/>
<xs:complexType name="UsagePointLocationConfig">
<xs:sequence>
<xs:element name="UsagePointLocation" type="m:UsagePointLocation" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
61968-9  CEI:2013 – 785 –

<xs:element name="status" type="m:Status" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="CoordinateSystem" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CoordinateSystem">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="crsUrn" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CoordinateSystem.crsUrn"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PositionPoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#PositionPoint">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.sequenceNumber"/>
<xs:element name="xPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.xPosition"/>
<xs:element name="yPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.yPosition"/>
– 786 – 61968-9  CEI:2013

<xs:element name="zPosition" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.zPosition"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TelephoneNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#TelephoneNumber">
<xs:sequence>
<xs:element name="areaCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.areaCode"/>
<xs:element name="cityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.cityCode"/>
<xs:element name="countryCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.countryCode"/>
<xs:element name="extension" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.extension"/>
<xs:element name="localNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TelephoneNumber.localNumber"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="TownDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#TownDetail">
<xs:sequence>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.code"/>
<xs:element name="country" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.country"/>
61968-9  CEI:2013 – 787 –

<xs:element name="name" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.name"/>
<xs:element name="section" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.section"/>
<xs:element name="stateOrProvince" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#TownDetail.stateOrProvince"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="UsagePointLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#UsagePointLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointLocation.accessMethod"/>
<xs:element name="direction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.direction"/>
<xs:element name="geoInfoReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.geoInfoReference"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#UsagePointLocation.remark"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#UsagePointLocation.siteAccessProblem"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.type"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.ConfigurationEvents"/>
<xs:element name="CoordinateSystem" type="m:CoordinateSystem" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.CoordinateSystem"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.electronicAddress"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone2"/>
<xs:element name="PositionPoints" type="m:PositionPoint" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Location.PositionPoints"/>
<xs:element name="secondaryAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.secondaryAddress"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.status"/>
</xs:sequence>
</xs:complexType>
</xs:schema>
– 788 – 61968-9  CEI:2013

Annexe I
(informative)
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

Schémas XML pour les charges utiles de message

I.1 Généralités

La présente Annexe a pour objet de fournir des schémas XML informatifs pour les charges
utiles de message afin d'augmenter les descriptions données plus haut dans le présent
document. Ces schémas XML ont été définis à l'aide des définitions de profils au sein de
CIMTool. Ces schémas peuvent être étendus selon les besoins à des fins de mises en oeuvre
spécifiques. Ces schémas peuvent être révisés ou promus à l'état normatif dans une
prochaine édition.

I.2 AuxiliaryAgreementConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch C57/2011/AuxiliaryAgreementConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch
C57/2011/AuxiliaryAgreementConfig#" elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="AuxiliaryAgreementConfig" type="m:AuxiliaryAgreementConfig"/>
<xs:complexType name="AuxiliaryAgreementConfig">
<xs:sequence>
<xs:element name="AuxiliaryAgreement" type="m:AuxiliaryAgreement" minOccurs="0"
maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AccountMovement" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AccountMovement">
<xs:sequence>
<xs:element name="amount" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AccountMovement.amount"/>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountMovement.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AccountMovement.reason"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AccountingUnit" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AccountingUnit">
<xs:sequence>
<xs:element name="energyUnit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountingUnit.energyUnit"/>
<xs:element name="monetaryUnit" type="m:Currency" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountingUnit.monetaryUnit"/>
<xs:element name="multiplier" type="m:UnitMultiplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AccountingUnit.multiplier"/>
<xs:element name="value" type="xs:float" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AccountingUnit.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAccount" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="balance" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAccount.balance"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="principleAmount" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.principleAmount"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.revisionNumber"/>
61968-9  CEI:2013 – 789 –

<xs:element name="subject" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch


C57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="Charges" type="m:Charge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.Charges"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="due" type="m:Due" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAccount.due"/>
<xs:element name="lastCredit" type="m:AccountMovement" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.lastCredit"/>
<xs:element name="lastDebit" type="m:AccountMovement" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAccount.lastDebit"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AuxiliaryAgreement" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="arrearsInterest" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAgreement.arrearsInterest"/>
<xs:element name="auxCycle" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.auxCycle"/>
<xs:element name="auxPriorityCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAgreement.auxPriorityCode"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="fixedAmount" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.fixedAmount"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="minAmount" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.minAmount"/>
<xs:element name="payCycle" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.payCycle"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="signDate" type="xs:date" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Agreement.signDate"/>
<xs:element name="subject" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="subType" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#AuxiliaryAgreement.subType"/>
<xs:element name="title" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="vendPortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#AuxiliaryAgreement.vendPortion"/>
<xs:element name="vendPortionArrear" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement.vendPortionArrear"/>
<xs:element name="AuxiliaryAccounts" type="m:AuxiliaryAccount" minOccurs="0"
maxOccurs="unbounded" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement.AuxiliaryAccounts"/>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Document.ConfigurationEvents"/>
<xs:element name="CustomerAgreement" type="m:CustomerAgreement" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#AuxiliaryAgreement.CustomerAgreement"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="validityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Agreement.validityInterval"/>
– 790 – 61968-9  CEI:2013

</xs:sequence>
</xs:complexType>
<xs:complexType name="Charge" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="ChildCharges" type="m:ChildCharge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.ChildCharges"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ChargeKind" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#ChargeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="auxiliaryCharge"/>
<xs:enumeration value="consumptionCharge"/>
<xs:enumeration value="demandCharge"/>
<xs:enumeration value="other"/>
<xs:enumeration value="taxCharge"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ChildCharge" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Currency" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#Currency">
<xs:restriction base="xs:string">
<xs:enumeration value="AUD"/>
<xs:enumeration value="CAD"/>
<xs:enumeration value="CHF"/>
61968-9  CEI:2013 – 791 –

<xs:enumeration value="CNY"/>
<xs:enumeration value="DKK"/>
<xs:enumeration value="EUR"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="GBP"/>
<xs:enumeration value="INR"/>
<xs:enumeration value="JPY"/>
<xs:enumeration value="NOK"/>
<xs:enumeration value="RUR"/>
<xs:enumeration value="SEK"/>
<xs:enumeration value="USD"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Due" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Due">
<xs:sequence>
<xs:element name="arrears" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.arrears"/>
<xs:element name="charges" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.charges"/>
<xs:element name="current" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.current"/>
<xs:element name="interest" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.interest"/>
<xs:element name="principle" type="m:Money" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Due.principle"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch C57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch C57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch C57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
– 792 – 61968-9  CEI:2013

<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

C57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0" sawsdl:modelReference="http://iec.ch
C57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="UnitMultiplier" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#UnitMultiplier">
<xs:restriction base="xs:string">
<xs:enumeration value="G"/>
<xs:enumeration value="M"/>
<xs:enumeration value="T"/>
<xs:enumeration value="c"/>
<xs:enumeration value="d"/>
<xs:enumeration value="k"/>
<xs:enumeration value="m"/>
<xs:enumeration value="micro"/>
<xs:enumeration value="n"/>
<xs:enumeration value="none"/>
<xs:enumeration value="p"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="RealEnergy" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#RealEnergy">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch C57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

I.3 ComModuleConfig
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/ComModuleConfig#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema" targetNamespace="http://iec.ch/TC57/2011/ComModuleConfig#"
elementFormDefault="qualified" attributeFormDefault="unqualified">
<xs:element name="ComModuleConfig" type="m:ComModuleConfig"/>
<xs:complexType name="ComModuleConfig">
<xs:sequence>
<xs:element name="ComFunction" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ComModule" type="m:ComModule" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ActivityRecord" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ActivityRecord">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
61968-9  CEI:2013 – 793 –

<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComModule">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="supportsAutonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.supportsAutonomousDst"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
– 794 – 61968-9  CEI:2013

<xs:element name="ActivityRecords" type="m:ActivityRecord" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ActivityRecords"/>
<xs:element name="AssetInfo" type="m:EndDeviceInfo" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.AssetInfo"/>
<xs:element name="ComFunctions" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.ComFunctions">
<xs:complexType sawsdl:modelReference="">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="ConfigurationEvents" type="m:ConfigurationEvent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.ConfigurationEvents"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConfigurationEvent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.createdDateTime"/>
<xs:element name="effectiveDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConfigurationEvent.effectiveDateTime"/>
<xs:element name="modifiedBy" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.modifiedBy"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConfigurationEvent.remark"/>
<xs:element name="severity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.severity"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.type"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ActivityRecord.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
61968-9  CEI:2013 – 795 –

<xs:element name="email2" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.installationDate"/>
<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.manufacturedDate"/>
<xs:element name="purchaseDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
– 796 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
<xs:element name="modelNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelNumber"/>
<xs:element name="modelVersion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelVersion"/>
<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Status">
<xs:sequence>
<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="Minutes" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Minutes">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="PerCent" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PerCent">
<xs:restriction base="xs:float"/>
</xs:simpleType>
<xs:simpleType name="Money" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Money">
<xs:restriction base="xs:decimal"/>
</xs:simpleType>
</xs:schema>

I.4 CustomerMeterDataSet
<?xml version="1.0" encoding="UTF-8"?>
<xs:schema xmlns="http://langdale.com.au/2005/Message#" xmlns:a="http://langdale.com.au/2005/Message#"
xmlns:m="http://iec.ch/TC57/2011/CustomerMeterDataSet#" xmlns:sawsdl="http://www.w3.org/ns/sawsdl"
xmlns:xs="http://www.w3.org/2001/XMLSchema"
targetNamespace="http://iec.ch/TC57/2011/CustomerMeterDataSet#" elementFormDefault="qualified"
attributeFormDefault="unqualified">
<xs:element name="CustomerMeterDataSet" type="m:CustomerMeterDataSet"/>
<xs:complexType name="CustomerMeterDataSet">
<xs:sequence>
<xs:element name="Meter" type="m:Meter" minOccurs="0" maxOccurs="unbounded"/>
<xs:element name="ReadingType" type="m:ReadingType" minOccurs="0" maxOccurs="unbounded"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="AccountingUnit" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AccountingUnit">
<xs:sequence>
<xs:element name="energyUnit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.energyUnit"/>
<xs:element name="monetaryUnit" type="m:Currency" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.monetaryUnit"/>
<xs:element name="multiplier" type="m:UnitMultiplier" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AccountingUnit.multiplier"/>
<xs:element name="value" type="xs:float" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#AccountingUnit.value"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AmiBillingReadyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AmiBillingReadyKind">
61968-9  CEI:2013 – 797 –

<xs:restriction base="xs:string">
<xs:enumeration value="amiCapable"/>
<xs:enumeration value="amiDisabled"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:enumeration value="billingApproved"/>
<xs:enumeration value="enabled"/>
<xs:enumeration value="nonAmi"/>
<xs:enumeration value="nonMetered"/>
<xs:enumeration value="operable"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="AssetInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AssetInfo">
<xs:sequence>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="AssetModelUsageKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#AssetModelUsageKind">
<xs:restriction base="xs:string">
<xs:enumeration value="customerSubstation"/>
<xs:enumeration value="distributionOverhead"/>
<xs:enumeration value="distributionUnderground"/>
<xs:enumeration value="other"/>
<xs:enumeration value="streetlight"/>
<xs:enumeration value="substation"/>
<xs:enumeration value="transmission"/>
<xs:enumeration value="unknown"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Channel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Channel">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Channel.isVirtual"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingType" minOccurs="0" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Channel.ReadingType">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Charge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ChargeKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="ChildCharges" type="m:ChildCharge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.ChildCharges"/>
<xs:element name="fixedPortion" type="m:AccountingUnit" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ChargeKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ChargeKind">
<xs:restriction base="xs:string">
<xs:enumeration value="auxiliaryCharge"/>
<xs:enumeration value="consumptionCharge"/>
<xs:enumeration value="demandCharge"/>
<xs:enumeration value="other"/>
<xs:enumeration value="taxCharge"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ChildCharge" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Charge">
– 798 – 61968-9  CEI:2013

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="kind" type="m:ChargeKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.kind"/>
<xs:element name="variablePortion" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.variablePortion"/>
<xs:element name="fixedPortion" type="m:AccountingUnit"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Charge.fixedPortion"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComDirectionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComDirectionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="biDirectional"/>
<xs:enumeration value="fromDevice"/>
<xs:enumeration value="toDevice"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ComFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrAddress" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrAddress"/>
<xs:element name="amrRouter" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.amrRouter"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="direction" type="m:ComDirectionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.direction"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="technology" type="m:ComTechnologyKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComFunction.technology"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ComModule" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComModule">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="supportsAutonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.supportsAutonomousDst"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
61968-9  CEI:2013 – 799 –

<xs:element name="AssetInfo" type="m:AssetInfo" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.AssetInfo"/>
<xs:element name="ComFunctions" type="m:ComFunction" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ComModule.ComFunctions"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ComTechnologyKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComTechnologyKind">
<xs:restriction base="xs:string">
<xs:enumeration value="cellular"/>
<xs:enumeration value="ethernet"/>
<xs:enumeration value="homePlug"/>
<xs:enumeration value="pager"/>
<xs:enumeration value="phone"/>
<xs:enumeration value="plc"/>
<xs:enumeration value="rf"/>
<xs:enumeration value="rfMesh"/>
<xs:enumeration value="zigbee"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ConnectDisconnectFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConnectDisconnectFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="eventCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.eventCount"/>
<xs:element name="isConnected" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isConnected"/>
<xs:element name="isDelayedDiscon" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isDelayedDiscon"/>
<xs:element name="isLocalAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoDisconOp"/>
<xs:element name="isLocalAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isLocalAutoReconOp"/>
<xs:element name="isRemoteAutoDisconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoDisconOp"/>
<xs:element name="isRemoteAutoReconOp" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction.isRemoteAutoReconOp"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="rcdInfo" type="m:RemoteConnectDisconnectInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConnectDisconnectFunction.rcdInfo"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ConsumptionTariffInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ConsumptionTariffInterval">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConsumptionTariffInterval.sequenceNumber"/>
<xs:element name="startValue" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConsumptionTariffInterval.startValue"/>
<xs:element name="Charges" type="m:Charge" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ConsumptionTariffInterval.Charges"/>
</xs:sequence>
– 800 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="CoordinateSystem" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CoordinateSystem">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="crsUrn" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CoordinateSystem.crsUrn"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CorporateStandardKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#CorporateStandardKind">
<xs:restriction base="xs:string">
<xs:enumeration value="experimental"/>
<xs:enumeration value="other"/>
<xs:enumeration value="standard"/>
<xs:enumeration value="underEvaluation"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="Currency" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Currency">
<xs:restriction base="xs:string">
<xs:enumeration value="AUD"/>
<xs:enumeration value="CAD"/>
<xs:enumeration value="CHF"/>
<xs:enumeration value="CNY"/>
<xs:enumeration value="DKK"/>
<xs:enumeration value="EUR"/>
<xs:enumeration value="GBP"/>
<xs:enumeration value="INR"/>
<xs:enumeration value="JPY"/>
<xs:enumeration value="NOK"/>
<xs:enumeration value="RUR"/>
<xs:enumeration value="SEK"/>
<xs:enumeration value="USD"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Customer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Customer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:CustomerKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.kind"/>
<xs:element name="pucNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.pucNumber"/>
<xs:element name="specialNeed" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.specialNeed"/>
<xs:element name="vip" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.vip"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.Organisation"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Customer.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAccount" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAccount">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="billingCycle" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.billingCycle"/>
<xs:element name="budgetBill" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAccount.budgetBill"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
61968-9  CEI:2013 – 801 –

<xs:element name="subject" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="CustomerAgreement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerAgreement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="loadMgmt" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.loadMgmt"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="signDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.signDate"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="Customer" type="m:Customer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.Customer"/>
<xs:element name="CustomerAccount" type="m:CustomerAccount" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.CustomerAccount"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#CustomerAgreement.ServiceCategory"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="validityInterval" type="m:DateTimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Agreement.validityInterval"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="CustomerKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#CustomerKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercialIndustrial"/>
<xs:enumeration value="energyServiceScheduler"/>
<xs:enumeration value="energyServiceSupplier"/>
<xs:enumeration value="internalUse"/>
<xs:enumeration value="other"/>
<xs:enumeration value="pumpingLoad"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="residentialAndCommercial"/>
<xs:enumeration value="residentialAndStreetlight"/>
<xs:enumeration value="residentialFarmService"/>
<xs:enumeration value="residentialStreetlightOthers"/>
<xs:enumeration value="windMachine"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="DateTimeInterval" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#DateTimeInterval">
<xs:sequence>
<xs:element name="end" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.end"/>
<xs:element name="start" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#DateTimeInterval.start"/>
</xs:sequence>
– 802 – 61968-9  CEI:2013

</xs:complexType>
<xs:complexType name="ElectronicAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ElectronicAddress">
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:sequence>
<xs:element name="email1" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email1"/>
<xs:element name="email2" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.email2"/>
<xs:element name="lan" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.lan"/>
<xs:element name="mac" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.mac"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.password"/>
<xs:element name="radio" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.radio"/>
<xs:element name="userID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.userID"/>
<xs:element name="web" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ElectronicAddress.web"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDevice" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDevice">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="installCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.installCode"/>
<xs:element name="isPan" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isPan"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ComFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="ConnectDisconnectFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ConnectDisconnectFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
<xs:element name="SimpleEndDeviceFunction" sawsdl:modelReference="">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SimpleEndDeviceFunction">
<xs:attribute name="ref" type="xs:string"/>
</xs:complexType>
</xs:element>
</xs:choice>
<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
61968-9  CEI:2013 – 803 –

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="EndDeviceCapability" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceCapability">
<xs:sequence>
<xs:element name="autonomousDst" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.autonomousDst"/>
<xs:element name="communication" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.communication"/>
<xs:element name="connectDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.connectDisconnect"/>
<xs:element name="demandResponse" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.demandResponse"/>
<xs:element name="electricMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.electricMetering"/>
<xs:element name="gasMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.gasMetering"/>
<xs:element name="metrology" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.metrology"/>
<xs:element name="onRequestRead" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.onRequestRead"/>
<xs:element name="outageHistory" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.outageHistory"/>
<xs:element name="pressureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.pressureCompensation"/>
<xs:element name="pricingInfo" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pricingInfo"/>
<xs:element name="pulseOutput" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.pulseOutput"/>
<xs:element name="relaysProgramming" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.relaysProgramming"/>
<xs:element name="reverseFlow" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.reverseFlow"/>
<xs:element name="superCompressibilityCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.superCompressibilityCompensation"/>
<xs:element name="temperatureCompensation" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceCapability.temperatureCompensation"/>
<xs:element name="textMessage" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.textMessage"/>
<xs:element name="waterMetering" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceCapability.waterMetering"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="EndDeviceFunctionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#EndDeviceFunctionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="autonomousDst"/>
<xs:enumeration value="demandResponse"/>
<xs:enumeration value="electricMetering"/>
<xs:enumeration value="gasMetering"/>
<xs:enumeration value="metrology"/>
<xs:enumeration value="onRequestRead"/>
<xs:enumeration value="outageHistory"/>
<xs:enumeration value="relaysProgramming"/>
<xs:enumeration value="reverseFlow"/>
<xs:enumeration value="waterMetering"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="EndDeviceInfo" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#EndDeviceInfo">
<xs:sequence>
<xs:element name="isSolidState" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.isSolidState"/>
– 804 – 61968-9  CEI:2013

<xs:element name="phaseCount" type="xs:integer" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.phaseCount"/>
<xs:element name="ratedCurrent" type="m:CurrentFlow" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedCurrent"/>
<xs:element name="ratedVoltage" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.ratedVoltage"/>
<xs:element name="AssetModel" type="m:ProductAssetModel" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetInfo.AssetModel"/>
<xs:element name="capability" type="m:EndDeviceCapability" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceInfo.capability"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="LifecycleDate" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#LifecycleDate">
<xs:sequence>
<xs:element name="installationDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.installationDate"/>
<xs:element name="manufacturedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.manufacturedDate"/>
<xs:element name="purchaseDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.purchaseDate"/>
<xs:element name="receivedDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.receivedDate"/>
<xs:element name="removalDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.removalDate"/>
<xs:element name="retiredDate" type="xs:date" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#LifecycleDate.retiredDate"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Manufacturer" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Manufacturer">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Meter" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="amrSystem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.amrSystem"/>
<xs:element name="formNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.formNumber"/>
<xs:element name="initialCondition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialCondition"/>
<xs:element name="initialLossOfLife" type="m:PerCent" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.initialLossOfLife"/>
<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.isVirtual"/>
<xs:element name="lotNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lotNumber"/>
<xs:element name="purchasePrice" type="m:Money" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.purchasePrice"/>
<xs:element name="serialNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.serialNumber"/>
<xs:element name="timeZoneOffset" type="m:Minutes" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.timeZoneOffset"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.type"/>
<xs:element name="utcNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.utcNumber"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Assets">
<xs:element name="ComModule" type="m:ComModule" sawsdl:modelReference=""/>
<xs:element name="EndDevice" type="m:EndDevice" sawsdl:modelReference=""/>
</xs:choice>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.electronicAddress"/>
<xs:choice minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceFunctions">
<xs:element name="ComFunction" type="m:ComFunction" sawsdl:modelReference=""/>
<xs:element name="ConnectDisconnectFunction" type="m:ConnectDisconnectFunction"
sawsdl:modelReference=""/>
61968-9  CEI:2013 – 805 –

<xs:element name="SimpleEndDeviceFunction" type="m:SimpleEndDeviceFunction"


sawsdl:modelReference=""/>
</xs:choice>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="EndDeviceInfo" type="m:EndDeviceInfo" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.EndDeviceInfo"/>
<xs:element name="lifecycle" type="m:LifecycleDate" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.lifecycle"/>
<xs:element name="MeterMultipliers" type="m:MeterMultiplier" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Meter.MeterMultipliers"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Seals" type="m:Seal" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetContainer.Seals"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Asset.status"/>
<xs:element name="UsagePoint" type="m:UsagePoint"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDevice.UsagePoint"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="MeterMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:MeterMultiplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.kind"/>
<xs:element name="value" type="xs:float" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MeterMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="MeterMultiplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#MeterMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="kE"/>
<xs:enumeration value="kH"/>
<xs:enumeration value="kR"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="MetrologyRequirement" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#MetrologyRequirement">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="reason" type="m:ReadingReasonKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.reason"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ReadingTypes" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#MetrologyRequirement.ReadingTypes">
<xs:complexType sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
</xs:element>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Name" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name">
<xs:sequence>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#Name.name"/>
<xs:element name="NameType" type="m:NameType" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Name.NameType"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameType">
<xs:sequence>
– 806 – 61968-9  CEI:2013

<xs:element name="description" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

schema-cim15#NameType.name"/>
<xs:element name="NameTypeAuthority" type="m:NameTypeAuthority" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameType.NameTypeAuthority"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="NameTypeAuthority" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#NameTypeAuthority">
<xs:sequence>
<xs:element name="description" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#NameTypeAuthority.description"/>
<xs:element name="name" type="xs:string" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#NameTypeAuthority.name"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Organisation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Organisation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.electronicAddress"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.phone2"/>
<xs:element name="postalAddress" type="m:PostalAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.postalAddress"/>
<xs:element name="streetAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Organisation.streetAddress"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="PhaseCode" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PhaseCode">
<xs:restriction base="xs:string">
<xs:enumeration value="A"/>
<xs:enumeration value="AB"/>
<xs:enumeration value="ABC"/>
<xs:enumeration value="ABCN"/>
<xs:enumeration value="ABN"/>
<xs:enumeration value="AC"/>
<xs:enumeration value="ACN"/>
<xs:enumeration value="AN"/>
<xs:enumeration value="B"/>
<xs:enumeration value="BC"/>
<xs:enumeration value="BCN"/>
<xs:enumeration value="BN"/>
<xs:enumeration value="C"/>
<xs:enumeration value="CN"/>
<xs:enumeration value="N"/>
<xs:enumeration value="s1"/>
<xs:enumeration value="s12"/>
<xs:enumeration value="s12N"/>
<xs:enumeration value="s1N"/>
<xs:enumeration value="s2"/>
<xs:enumeration value="s2N"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="PositionPoint" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PositionPoint">
<xs:sequence>
<xs:element name="sequenceNumber" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.sequenceNumber"/>
<xs:element name="xPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.xPosition"/>
<xs:element name="yPosition" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.yPosition"/>
<xs:element name="zPosition" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PositionPoint.zPosition"/>
</xs:sequence>
</xs:complexType>
61968-9  CEI:2013 – 807 –

<xs:complexType name="PostalAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#PostalAddress">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="poBox" type="xs:string" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.poBox"/>
<xs:element name="postalCode" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.postalCode"/>
<xs:element name="streetDetail" type="m:StreetDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PostalAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="PricingStructure" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.code"/>
<xs:element name="createdDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.createdDateTime"/>
<xs:element name="dailyCeilingUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.dailyCeilingUsage"/>
<xs:element name="dailyEstimatedUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#PricingStructure.dailyEstimatedUsage"/>
<xs:element name="dailyFloorUsage" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.dailyFloorUsage"/>
<xs:element name="lastModifiedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.lastModifiedDateTime"/>
<xs:element name="revenueKind" type="m:RevenueKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.revenueKind"/>
<xs:element name="revisionNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.revisionNumber"/>
<xs:element name="subject" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.subject"/>
<xs:element name="taxExemption" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.taxExemption"/>
<xs:element name="title" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.title"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.type"/>
<xs:element name="docStatus" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.docStatus"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="ServiceCategory" type="m:ServiceCategory" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.ServiceCategory"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Document.status"/>
<xs:element name="Tariffs" type="m:Tariff" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#PricingStructure.Tariffs"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ProductAssetModel" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel">
<xs:sequence>
<xs:element name="corporateStandardKind" type="m:CorporateStandardKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ProductAssetModel.corporateStandardKind"/>
<xs:element name="modelNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelNumber"/>
<xs:element name="modelVersion" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.modelVersion"/>
<xs:element name="usageKind" type="m:AssetModelUsageKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.usageKind"/>
<xs:element name="Manufacturer" type="m:Manufacturer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ProductAssetModel.Manufacturer"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RationalNumber" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RationalNumber">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.denominator"/>
– 808 – 61968-9  CEI:2013

<xs:element name="numerator" type="xs:integer"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RationalNumber.numerator"/>
</xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

</xs:complexType>
<xs:complexType name="ReadingInterharmonic" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ReadingInterharmonic">
<xs:sequence>
<xs:element name="denominator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.denominator"/>
<xs:element name="numerator" type="xs:integer"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingInterharmonic.numerator"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ReadingReasonKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingReasonKind">
<xs:restriction base="xs:string">
<xs:enumeration value="billing"/>
<xs:enumeration value="demandReset"/>
<xs:enumeration value="inquiry"/>
<xs:enumeration value="installation"/>
<xs:enumeration value="loadManagement"/>
<xs:enumeration value="loadResearch"/>
<xs:enumeration value="moveIn"/>
<xs:enumeration value="moveOut"/>
<xs:enumeration value="other"/>
<xs:enumeration value="removal"/>
<xs:enumeration value="serviceConnect"/>
<xs:enumeration value="serviceDisconnect"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ReadingType" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ReadingType">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accumulation" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.accumulation"/>
<xs:element name="aggregate" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.aggregate"/>
<xs:element name="commodity" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.commodity"/>
<xs:element name="consumptionTier" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.consumptionTier"/>
<xs:element name="cpp" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.cpp"/>
<xs:element name="currency" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.currency"/>
<xs:element name="flowDirection" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.flowDirection"/>
<xs:element name="macroPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.macroPeriod"/>
<xs:element name="measurementKind" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measurementKind"/>
<xs:element name="measuringPeriod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.measuringPeriod"/>
<xs:element name="multiplier" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.multiplier"/>
<xs:element name="phases" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.phases"/>
<xs:element name="tou" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.tou"/>
<xs:element name="unit" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.unit"/>
<xs:element name="argument" type="m:RationalNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.argument"/>
<xs:element name="interharmonic" type="m:ReadingInterharmonic" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ReadingType.interharmonic"/>
<xs:element name="Names" type="m:Name" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="Register" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#Register">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
61968-9  CEI:2013 – 809 –

<xs:element name="isVirtual" type="xs:boolean" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.isVirtual"/>
<xs:element name="leftDigitCount" type="xs:integer" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.leftDigitCount"/>
<xs:element name="rightDigitCount" type="xs:integer" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.rightDigitCount"/>
<xs:element name="touTierName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTierName"/>
<xs:element name="Channels" type="m:Channel" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.Channels"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="touTier" type="m:TimeInterval" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Register.touTier"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="RemoteConnectDisconnectInfo"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#RemoteConnectDisconnectInfo">
<xs:sequence>
<xs:element name="armedTimeout" type="m:Seconds" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.armedTimeout"/>
<xs:element name="customerVoltageLimit" type="m:Voltage" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.customerVoltageLimit"/>
<xs:element name="energyLimit" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyLimit"/>
<xs:element name="energyUsageStartDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageStartDateTime"/>
<xs:element name="energyUsageWarning" type="m:RealEnergy" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.energyUsageWarning"/>
<xs:element name="isArmConnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmConnect"/>
<xs:element name="isArmDisconnect" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isArmDisconnect"/>
<xs:element name="isEnergyLimiting" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.isEnergyLimiting"/>
<xs:element name="needsPowerLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsPowerLimitCheck"/>
<xs:element name="needsVoltageLimitCheck" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.needsVoltageLimitCheck"/>
<xs:element name="powerLimit" type="m:ActivePower" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.powerLimit"/>
<xs:element name="usePushbutton" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RemoteConnectDisconnectInfo.usePushbutton"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="RevenueKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#RevenueKind">
<xs:restriction base="xs:string">
<xs:enumeration value="commercial"/>
<xs:enumeration value="industrial"/>
<xs:enumeration value="irrigation"/>
<xs:enumeration value="nonResidential"/>
<xs:enumeration value="other"/>
<xs:enumeration value="residential"/>
<xs:enumeration value="streetLight"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="Seal" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal">
<xs:sequence>
<xs:element name="appliedDateTime" type="xs:dateTime" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.appliedDateTime"/>
<xs:element name="condition" type="m:SealConditionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.condition"/>
– 810 – 61968-9  CEI:2013

<xs:element name="kind" type="m:SealKind" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.kind"/>
<xs:element name="sealNumber" type="xs:string" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Seal.sealNumber"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SealConditionKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealConditionKind">
<xs:restriction base="xs:string">
<xs:enumeration value="broken"/>
<xs:enumeration value="locked"/>
<xs:enumeration value="missing"/>
<xs:enumeration value="open"/>
<xs:enumeration value="other"/>
</xs:restriction>
</xs:simpleType>
<xs:simpleType name="SealKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#SealKind">
<xs:restriction base="xs:string">
<xs:enumeration value="lead"/>
<xs:enumeration value="lock"/>
<xs:enumeration value="other"/>
<xs:enumeration value="steel"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceCategory" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceCategory">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceCategory.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceKind">
<xs:restriction base="xs:string">
<xs:enumeration value="electricity"/>
<xs:enumeration value="gas"/>
<xs:enumeration value="heat"/>
<xs:enumeration value="internet"/>
<xs:enumeration value="other"/>
<xs:enumeration value="rates"/>
<xs:enumeration value="refuse"/>
<xs:enumeration value="sewerage"/>
<xs:enumeration value="time"/>
<xs:enumeration value="tvLicence"/>
<xs:enumeration value="water"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceLocation" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceLocation">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="accessMethod" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.accessMethod"/>
<xs:element name="direction" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.direction"/>
<xs:element name="geoInfoReference" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.geoInfoReference"/>
<xs:element name="needsInspection" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.needsInspection"/>
<xs:element name="siteAccessProblem" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceLocation.siteAccessProblem"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.type"/>
<xs:element name="CoordinateSystem" type="m:CoordinateSystem" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.CoordinateSystem"/>
<xs:element name="electronicAddress" type="m:ElectronicAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.electronicAddress"/>
<xs:element name="mainAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.mainAddress"/>
61968-9  CEI:2013 – 811 –

<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="phone1" type="m:TelephoneNumber" minOccurs="0"
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone1"/>
<xs:element name="phone2" type="m:TelephoneNumber" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.phone2"/>
<xs:element name="PositionPoints" type="m:PositionPoint" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.PositionPoints"/>
<xs:element name="secondaryAddress" type="m:StreetAddress" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.secondaryAddress"/>
<xs:element name="status" type="m:Status" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Location.status"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="ServiceMultiplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceMultiplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="kind" type="m:ServiceMultiplierKind"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceMultiplier.kind"/>
<xs:element name="value" type="xs:float" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceMultiplier.value"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="ServiceMultiplierKind" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#ServiceMultiplierKind">
<xs:restriction base="xs:string">
<xs:enumeration value="ctRatio"/>
<xs:enumeration value="ptRatio"/>
<xs:enumeration value="transformerRatio"/>
</xs:restriction>
</xs:simpleType>
<xs:complexType name="ServiceSupplier" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="issuerIdentificationNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#ServiceSupplier.issuerIdentificationNumber"/>
<xs:element name="kind" type="m:SupplierKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#ServiceSupplier.kind"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Organisation" type="m:Organisation" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#OrganisationRole.Organisation"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="SimpleEndDeviceFunction" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#SimpleEndDeviceFunction">
<xs:sequence>
<xs:element name="mRID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.mRID"/>
<xs:element name="configID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.configID"/>
<xs:element name="enabled" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.enabled"/>
<xs:element name="firmwareID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.firmwareID"/>
<xs:element name="hardwareID" type="xs:string"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.hardwareID"/>
<xs:element name="kind" type="m:EndDeviceFunctionKind" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#SimpleEndDeviceFunction.kind"/>
<xs:element name="password" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.password"/>
<xs:element name="programID" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#AssetFunction.programID"/>
<xs:element name="Names" type="m:Name" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#IdentifiedObject.Names"/>
<xs:element name="Registers" type="m:Register" minOccurs="0" maxOccurs="unbounded"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#EndDeviceFunction.Registers"/>
</xs:sequence>
</xs:complexType>
– 812 – 61968-9  CEI:2013

<xs:complexType name="Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-


cim15#Status">
<xs:sequence>
COPYRIGHT © IEC. NOT FOR COMMERCIAL USE OR REPRODUCTION

<xs:element name="dateTime" type="xs:dateTime" minOccurs="0"


sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.dateTime"/>
<xs:element name="reason" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.reason"/>
<xs:element name="remark" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.remark"/>
<xs:element name="value" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#Status.value"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetAddress" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetAddress">
<xs:sequence>
<xs:element name="status" type="m:Status" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-
schema-cim15#StreetAddress.status"/>
<xs:element name="streetDetail" type="m:StreetDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.streetDetail"/>
<xs:element name="townDetail" type="m:TownDetail"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetAddress.townDetail"/>
</xs:sequence>
</xs:complexType>
<xs:complexType name="StreetDetail" sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-
cim15#StreetDetail">
<xs:sequence>
<xs:element name="addressGeneral" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.addressGeneral"/>
<xs:element name="buildingName" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.buildingName"/>
<xs:element name="code" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.code"/>
<xs:element name="name" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.name"/>
<xs:element name="number" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.number"/>
<xs:element name="prefix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.prefix"/>
<xs:element name="suffix" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suffix"/>
<xs:element name="suiteNumber" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.suiteNumber"/>
<xs:element name="type" type="xs:string" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.type"/>
<xs:element name="withinTownLimits" type="xs:boolean" minOccurs="0"
sawsdl:modelReference="http://iec.ch/TC57/2010/CIM-schema-cim15#StreetDetail.withinTownLimits"/>
</xs:sequence>
</xs:complexType>
<xs:simpleType name="SupplierKind" sawsdl:mo

You might also like