Diffuser Details
Diffuser Details
&
RECTANGULAR LOUVERED
FACE DIFFUSERS
SQUARE AND RECTANGULAR LOUVERED FACE DIFFUSER
INTRODUCTION
Ceiling diffusers are the excellent choice for HVAC system where a high standard of comfort indoor air
quality and controlled performance are to be achieved. COSMOS ceiling diffusers are specially designed
for ceiling‐mounting applications. They are suitable for supply air as well as exhaust air, providing a
stable pattern of air diffusion, flowing through a number of concentrically arranged sections.
Controlled air distribution, flow equalization, sound attenuation, architectural appearance and solid
construction are all reasonable and worthwhile reasons to choose COSMOS CEILING DIFFUSERS.
Model: SQL‐4 Model: RTL‐4
COSMOS ceiling diffusers are designed to handle a wide range of horizontal airflows that will meet all
HVAC requirements, and yet with a pleasing appearance to suit architectural requirements.
An engineered blade design on all angular discharge louvers creates a stable horizontal air pattern that
is tight to the ceiling. Corners of outer cores are mechanically fastened to provide precisely mitered
corners and add strength to the diffuser.
COSMOS ceiling diffusers are available in square (SQL) or rectangular (RTL) patterns for supply air as well
as for return air and which in turn is supplied with or without opposed blade damper. When supply with
opposed blade damper ( for supply air diffuser ), damper is fixed to the outer frame of the diffuser and
is screw operated from the face of the diffuser. The damper frame is separated from its blades by using
nylon bushings to eliminate corrosion and vibration.
COSMOS ceiling diffusers SQL and RTL are multi‐vane type with a fully removable core from its face for
easy installation, with square neck and can be supplied in 1, 2, 3 and 4 way airflow patterns for all air
distribution requirement.
Different frame types are available to suit almost any mounting condition including surface mount and
T‐bar panel types. Ceiling diffuser is also available with an extended frame to suit the size of ceiling tile
thus models offer a great degree of design flexibility.
Diffusers are available with wide variety of core styles and neck sizes. A combination can be selected to
suit a specified air pattern and deliver the desired volume of air to suit any particular requirements.
Feature
• Engineered air distribution patterns for 1, 2, 3 and 4 way blow in a wide selection of square and
rectangular neck sizes.
• Spring loaded core. Removable without the use of tool.
• Secure core attachment.
• Wide variety of frame styles to suit most ceiling applications.
• Optional extruded panel to suit modular ceiling systems.
• Optional opposed blade damper with screwdriver slot operator.
• Standard finish RAL 9016.
Material
Heavy gauge aluminum extrusion.
Finish
Standard RAL 9016 powder coated. Other finishes available on request.
Volume control damper: Powder coated in matt black shade.
SELECTION OF DIFFUSERS 3. Pattern Requirement : The pattern requirement is
SQUARE & RECTANGULAR DIFFUSERS
1
this, diffusers should be located so that the cooling system operation. The room velocity VR will
diffuser mounting height. For example, in a space is based upon minimum throw. When diffuser
with a 12 ft. ceiling height diffusers should be so selection is based upon maximum throw, the room
located and in such numbers that the required throw velocity VR will not exceed 20 ft. per min. The
of any one diffuser would not exceed 18 ft. See Table tabulated values of throw apply for diffusers
1. mounted in a ceiling.
The final consideration is the pressure loss of the Selection data are given for neck velocities of from
diffuser. The allowance in the design of the system 300 to 700 ft. per min. Also listed are values of total
for outlet pressure loss should not be exceeded by pressure drop through the diffuser at each of these
TABLE 2 - RECOMMENDED MAXIMUM THROW The total pressure requirement is the sum of the
Ceiling Height ft. 8 9 10 12 neck of the diffuser. If the static pressure is required it
Maximum, throw requirement, ft. * 12 13.5 15 18 can be determined by subtracting the velocity
The values of throw shown in Table 2. are based upon bedetermined from Fig. 2.
2
Example : An air volume of 200 cfm is to be long-side of the diffuser should be approx. 9 ft. One
SQUARE & RECTANGULAR DIFFUSERS
introduced into an office which is 18 feet long and 12 half the length of the room. The short-side throw
feet wide with a ceiling height of 9 feet. A directional should be 4 ft. or 5 ft. - about half the width of the
diffuser is to be located in the center of the ceiling. room.
The NC level of the diffuser should be less than 30.
Table 2 shows that a 12 in. x 6 in. Pattern 42 diffuser
THROTTLED DAMPER / OPEN DAMPER
4
would deliver 200 cfm at a neck velocity of 400 ft. per
PRESSURE RATIO
DIFFUSER WITH OPPOSED BLADE DAMPER Determining the sound level which results from the
NC 35 3 2
sound power level referenced to 10-12 Watt. (The
NC 40 6 2
absorption is 18 db referenced to 10-13 Watt). For
3
2. From Table 5 determine the number of decibels to TABLE 5 - NC ADDITION FOR COMBINING
highest NC level. This sum is the combined NC level Difference Between Two 0 1 2 4 6 9 10
Number To Be Added To
3 2.5 2 1.5 1 0.5 0
3. If three units serve the space, determine the Higher Level To Obtain
Combined Level
difference between the combined NC level of the first
36.
4
SQUARE & RECTANGULAR DIFFUSERS
5
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
SQUARE & RECTANGULAR DIFFUSERS
7
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
Note : Min. throw based on Vt = 300 fpm with VR not greater than 50 fpm. Max. throw based on Vt = 125 fpm with VR not greater than 20 fpm.
8
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
SQUARE & RECTANGULAR DIFFUSERS
9
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
Note : Min. throw based on Vt = 300 fpm with VR not greater than 50 fpm. Max. throw based on Vt = 125 fpm with VR not greater than 20 fpm.
10
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
SQUARE & RECTANGULAR DIFFUSERS
Note : Min. throw based on Vt = 300 fpm with VR not greater than 50 fpm. Max. throw based on Vt = 125 fpm with VR not greater than 20 fpm.
11
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
Note : Min. throw based on Vt = 300 fpm with VR not greater than 50 fpm. Max. throw based on Vt = 125 fpm with VR not greater than 20 fpm.
12
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
SQUARE & RECTANGULAR DIFFUSERS
13
Table 2 - SELECTION DATA FOR DIFFUSERS (SQUARE & RECTANGULAR)
Note : Min. throw based on Vt = 300 fpm with VR not greater than 50 fpm. Max. throw based on Vt = 125 fpm with VR not greater than 20 fpm.
14