UN 5000 User's Manual: Man-Machine Communication
UN 5000 User's Manual: Man-Machine Communication
Chapter 3
Man-Machine Communication
3.1 General
This document contains the information on man-machine communication required for the
UNITROL 5000 excitation system. Please read this manual carefully before starting work
on the system.
The man-machine communication tools deals with the following operations
• Display of signals and operating values.
• Display and adjustment of parameters.
• Changing of software-applications.
The changing of applications requires very thorough knowledge of the system and may only
be carried out by trained personnel.
3.2.1 Introduction
This document describes the handling of the UNS 0874 service panel and its use in
connection with the UNITROL 5000 excitation system for local control and for setting
parameter values.
All alterations to the system are made by means of so-called parameter settings and are
described in section 4, “Settings“.
Do not press the ENTER key after an operating error. This activates
alterations.
In order to cancel an alteration and quit "Parameter Setting" mode, press the
ACT key.
0 L 100.5 % II
MODE IND 1 AUTO
U MACH V 10500 V
I EXC A 16.5 A
166
COM
ACT PAR FUNC
SEL
ENTER
REM
I 0
R
UNITROL F
79.6
The service panel is connected with the UNITROL devices via a serial interface
(RS 485). The data processing rate is 9600 bit/s. The power supply to the panel is also
provided via the serial connection cable; there are no batteries in the device itself.
CHI CH II
COM
COM/SEL Switches over to "Select Device"
SEL
COM
SEL
Display for channel selection
The meaning of the individual fields on the display in the different operating modes can be
seen from the following examples:
Status row
1 L 104.5 % II
Operating mode
MODE IND 1 AUTO
Actual signal: name,
unit and value U MACH V 10500 V
Actual signal: name,
unit and value I EXC A 1367.5 A
The date and time display in the above example is to be interpreted as follows:
00.06.24-14:25:42.15 ➨ 24 June 2000, 14 hrs. 25 min. 42 sec. 150 ms
Parameter display
In Parameter Setting mode, most of the setting values of the excitation
systems can be changed, e.g. setpoint limits of the voltage regulator,
limiter settings etc.
The commissioning and maintenance personnel should only make these settings. Parameter
setting is described in section 3.2.3.9 " changing parameters”, the parameter numbers are
shown in the "parameter and signal list".
Fun(ction) display
Status row
1 L 104.5 % 00
Selectable UPLOAD <= <=
functions
DOWNLOAD => =>
Display contrast
adjusting CONTRAST 4
DOWNLOAD and UPLOAD are used to copy a complete parameter set from one channel
into the other or into the UNITROL device of another machine (with the same settings). In
addition, the contrast of the LCD display can be adjusted in Function mode. The operation of
this function is described in section 3.2.3.8 "Adjusting the display contrast".
In addition, the Function mode allows the system engineer to intervene in the control system
and introduce new function blocks.
The description of these functions goes beyond the scope of this manual and is contained in
the document "Programming Manual", which can be obtained from us on request.
Communication Selection
The Communication Selection mode is used to select the device with
COM
SEL
which the service panel is to communicate. This function is only relevant
in dual channel systems.
After the COM SEL key is pressed, the ID number of the channel with which the panel is
currently connected appears on the display. The arrow keys can be used to change the ID
number and set up communication with the other channel.
2 L 104.5% II
MODE IND 1 AUTO
U MACH V 10500 V
I EXC A 1367.5 A
2 L 104.5% II
MODE IND 1 AUTO
U MACH V 10500 V
I EXC A 1367.5 A
Start mode
When the service panel is connected or the system is
UNS874 PANEL V4.257
supplied with power, an identification display appears
showing the software version. At the same time, the
parameters are loaded from the excitation system into
the panel. On first connection, this process can take up • •
to one minute. The panel then switches to Actual Value
Display mode.
The serial connection cable to the service panel can be plugged in or unplugged at any time;
the supply voltage of the UNITROL® 5000 device need not be interrupted for this purpose.
Following a break in communication, the panel sets up connection with the same channel
which was selected before the interruption.
If the channel with which the panel is currently communicating fails, then a connection is
automatically made with the other channel. A display similar to the special status display
shown above appears, which is quitted by pressing the ACT key.
ON FIELD BREAKER ON
1)
OFF FIELD BREAKER OFF
(switches off excitation at the same time)
1)
only possible if the machine is isolated from the network
In dual channel systems, some fault messages can only be reset in the channel which
generated the message. If an alarm cannot be reset, you must proceed as follows:
• Set up connection with the other channel in "Communication Selection" mode.
• Wait until the fault message is displayed.
• Reset fault as described above.
In dual channel systems, this parameter is also used to switch between channels.
The adjustment range of the panel setpoint is always -100% to +150%. However, this value
is limited in the UNITROL device to the set setpoint range, e.g. 90 % to 110 % for the
voltage regulator (AUTO).
6b. or
cancel the new setting by ACT PAR 1 L 0.0 % 00
switching to a different display 5 CONVERTER
mode FUNC COM 02 I EXC A NOMINAL
SEL 1000.0 A
A number of parameters are write-protected. If one tries to adjust one of these values, the
following message appears on the display:
**WARNING**
WRITE ACCESS DENIED
PARAMETER SETTING
NOT POSSIBLE
Between DOWNLOADING and UPLOADING, the service panel can be unplugged from the
serial cable and carried to another system. The saving of the parameter set is also
guaranteed if the supply voltage is interrupted.
After UPLOADING, the parameters are stored in the volatile memory (RAM) of the target
system, i.e. the connected UNITROL device, and are effective until the next time the supply
voltage is switched off. In order to save the values permanently, they must be copied into the
non-volatile (FPROM) memory. The so-called PARAM. SAVE is used for this purpose.
FPROM Download
RAM
Upload
The Download/Upload function is carried out using the following key commands:
FUNC COM
SEL
Basically, 3 task lists are available. It is recommended that, whenever possible, task 2 or 3
be used for additional application-specific programs in order to avoid placing an
unnecessary load on the processor. The number of function blocks is limited as follows:
Task no. Interval Max. number
Task1 5ms 25
Task2 20ms 100
Task3 200ms 250
Blockname
Blocknumber
222
2909 12742
2910 ADD2
T3:223
Inputparameter
Taskorder-
Tasknumber number
222
2909 12742
2910 ADD2
T3:223
SP41
6910
pid_set2_sel1
Note If the parameter set is loaded from the panel into the
controller board, parameter 2504 is set to 0 for safety
reasons and must be reset to 1 by hand.
3.3.1 Introduction
The CMT tool can be used as man-machine interface.
It can be used to carry out the following functions:
• Monitoring of the current values of the Unitrol in graphic and numeric form.
• Alteration of parameter settings.
• Checking and display of the internal data logger.
• Saving of current settings and recorded graphics in a file.
• Local control of the Unitrol.
• Display and deletion of the internal fault logger.
• Loading of parameters and saving to disk.
• Downloading of parameters and applications from a file.
3.3.2 Installation
The plug-in card SNAT608 CMT is required for desktop PCs. This is connected directly with
the Control Board (COB) of the Unitrol 5000 via an optical cable.
UNITROL 5000
COB
optical link
UNITROL 5000
HDLC-Communication
COB SNAT622
PCMCIA HDLC
SNAT621
optical link
The initialisation should be deactivated by the insertion of "REM", as shown in the above
example (cardid.exe).
However, the initialisation file has a different name depending on the PC model.
Note The directory of the CMT tool also contains the programs
"CHECK622" and "TESTxxx". These require a PCMCIA
socket driver for DOS. These are normally not installed with
the WIN95/98 installation. This means that these two
programs will not function under WIN95/98; however, they
are not required either.
After connection has been established, the loading of the parameters from the UNITROL
starts. The parameter list is provided in the ParSig menu.
C:\cmttool\ Ddctool.exe/ M3
As a rule, these parameters can be dispensed with. If an error message appears such as
"PC Overload“, then use the parameter M :
• "Connect" menu
Establishing connection, downloading application.
• "ParSig" menu
Working with parameters.
• "Diagrams" menu
Display of function plan diagrams
• "Trending " menu
Recording and graphic representation of measured values.
• "Faults" menu
Setting and reading of the fault logger.
• "Exit" menu
Closes the program.
• "Help" menu
Information on the version and parameters
The application is downloaded using the menu option "Connect - Download Application"
After pressing the function key “F2” or selecting the menu option "Connect – show / hide
panel", the following status panel appears.
Ready to start
Datalogger activ
Excirtation on
Auto Mode
channel aktiv
Superimposed Mode activ
Alarm
Fault
Communicationbreak
(to Unitrol 5000)
The changing speed of the reverence change can be adjusted by pressing the Ref button.
The following window appears after pressing the Ref button:
Reset After pressing the Reset button the fault indications are reset if the faults are not
present anymore. for more details about fault descriptions refer to chapter 8.
Fig. 3-13 Uploading parameters and signal values from UNITROL into PC
Note Please ensure that the file "dhlen.txt" in the CMT directory
is compatible with the loaded software.
If the versions are not compatible, the upload cannot be
carried out successfully.
If no compatible version is present, it is possible to work
without "dhlen.txt". However, in this case no help text is
available in the CMT.
Parameter-
nummer
Default
Parameterwert
Aktueller
Parameterwert
Parameterbezei
chnung
Eingabefeld für
neuen Wert
Note After downloading, the file is only stored in the RAM of the
UNITROL 5000. If the power supply is interrupted, the
data are lost. In order to prevent this, the data must be
loaded into the flash memory of the UNITROL 5000. This
is done by setting the parameter "Backupstoremode" to
"Save paramset 1".
upload parameterfile
(e.g. parsig_new.qop of new Version)
Choose parametefilei
(e.g. parsig_old.qop of old Version)
Display
Text file
414
3288
PAR ADD_Input_AVR
P1 0 O
Value
Signallist
Offset
Task1 5ms 25
Task2 20ms 100
Task3 200ms 250
The function blocks available in the function block library have permanently assigned inputs
and outputs, as the following example shows:
Blockname
Blocknumber
222
2909 12742
2910 ADD2
T3:223
Inputparameter
Taskorder-
Tasknumber number
For example, the application function block is connected with the standard program (SP-41,
AVR_INPUT) in this way. For this purpose, the parameter 6910 is assigned the value 12742.
Once the function blocks have been included in a task list and connected together to form a
function, the function blocks still have to be activated. This is done using the parameter
2504. This must be set to "1". This is done in turn using the PAR function (see preceding
section).
How one includes function blocks in a task list and how the inputs of the function blocks are
connected is explained in the following:
The application can be altered or added to using the CMT tool. Function blocks contained in
the library can be inserted, deleted or changed.
Move to DrvFuncs menu.
The screen display, which appears, represents the service panel. The display appears in the
field "Information Display". The control keys appear in the field "Selection Buttons ".
Select "FB Programming". The following Information Display appears
INFORMATION DISPLAY
FB Programming
FUNC MENU
Selection Buttons
FORWARD
++ +
ENT ENTER
BACK-- -
L/R START
1 0 STOP
You can move back and forth between the menu options using "+" or "-" To select the
required option, click on "ENT".
INFORMATION DISPLAY
FB Programming
FUNC MENU
Select the required task number with "+" or "-". The following are available
TASK 1 : 5ms
TASK 2 : 10ms
TASK 3 : 200ms
FB Programming
TASK3
1: [INV (10)]
INFORMATION DISPLAY
FB Programming
FUNC MENU
2727
12666
2909 2727 AND2
12742
2910 ADD2
INFORMATION DISPLAY
FB Programming
FUNC MENU
INFORMATION DISPLAY
FB Programming
FUNC MENU
• To break the connection: enter the value "0" for the input parameter.
• Select " DELETE FUNC BLOCK".
• Select the task number with "+" or "-".
• Confirm with "ENT".
• Select the FB element with "+" or "-". You can jump directly to the next FB group using
"++" or "--".
• Confirm with "ENT".
Fig. 3-37 Fault logger data uploaded from the UNITROL 5000
Time stamp format :
Example: 24 June 2000 , 14 hrs 25 min. 42 sec. 150 ms
Y Y . M M . D D - H H : M M : S S . 1/10s 1/100s
0 0 . 0 6 . 2 4 - 1 4 : 2 5 : 4 2 . 1 5
Communications error
Information for operator
Setup of communication between CMT and
UNITROL has failed.
Troubleshooting
• Check connections; optical cable between
Cannot start communication with drive UNITROL and PC.
Communications error
Information for operator
The CMT tool is not in ONLINE mode
although this is required in order to carry out
the selected command
Troubleshooting
• Switch tool to ONLINE and re-start CMT.
Communications error
Information for operator
Communication between CMT and
UNITROL has been broken.
Troubleshooting
Connection to drive is broken • Check connections; optical cable between
UNITROL and PC.