SCADAPack 535E Hardware Manual
SCADAPack 535E Hardware Manual
Manual
2 SCADAPack 535E Hardware Manual
Table of Contents
3
4 SCADAPack 535E Hardware Manual
Version: 8.11.1
Date: November 2014
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not intended
as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications. It is the duty of any such user or integrator to perform the appropriate and
complete risk analysis, evaluation and testing of the products with respect to the relevant specific
application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be
responsible or liable for misuse of the information contained herein. If you have any suggestions for
improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
SCADAPack 535E Hardware Manual 5
1 Technical Support
Questions and requests related to any part of this documentation can be directed to one of the following
support centers.
2 Safety Information
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
6 SCADAPack 535E Hardware Manual
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can
result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can
result in minor or moderate injury.
NOTICE
NOTICE indicates a potentially hazardous situation which, if not avoided, can
result in equipment damage.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and the installation, and has received safety training to recognize and avoid the
hazards involved.
CAUTION
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary
holding means used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in minor or moderate injury.
Follow all start-up tests recommended in the equipment documentation. Store all equipment
documentation for future reference.
SCADAPack 535E Hardware Manual 7
Verify that the completed system is free from all short circuits and grounds, except those grounds
installed according to local regulations (according to the National Electrical Code in the U.S.A, for
instance). If high-potential voltage testing is necessary, follow recommendations in equipment
documentation to help prevent accidental equipment damage.
Regardless of the care exercised in the design and manufacture of equipment or in the selection and
ratings of components, there are hazards that can be encountered if such equipment is improperly
operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe
operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment
manufacturer’s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to the
operator. Access to other controls should be restricted to help prevent unauthorized changes in
operating characteristics.
ACCEPTABLE USE
SCADAPack E Remote Terminal Units (RTUs) and input/output (I/O) modules are intended for use in
monitoring and controlling non-critical equipment only. They are not intended for safety-critical
applications.
WARNING
UNACCEPTABLE USE
Do not use SCADAPack E RTUs or I/O modules as an integral part of a safety
system. These devices are not safety products.
Failure to follow this instruction can result in death or serious injury.
CAUTION
EQUIPMENT OPERATION HAZARD
When devices are used for applications with technical safety requirements, the
relevant instructions must be followed.
For safe and proper operating results, use only Schneider Electric software or
approved software with Schneider Electric hardware products.
Ex nA IIC T4 Gc
II 3 G
Applies to SCADAPack E products, models TBUP530, TBUP535 and TBUX (CSA Marked)
Those products are available for use in Class I, Division 2, Groups A, B, C & D and Class I Zone 2
Hazardous Locations. Such locations are defined in Article 500 and 505 of the US National Fire
Protection Association (NFPA) publication NFPA 70, otherwise known as the National Electrical Code,
in Section 18 of the Canadian Standards Association C22.1 (Canadian Electrical Code) and in IEC/EN
60079-10.
The products have been recognized for use in these hazardous locations by the Canadian Standards
Association (CSA) International.
CSA certification is in accordance with Standards CSA C22.2 No. 213, CSA C22.2 60079-0, CSA C22.2
60079-15, ANSI/ISA 60079-0, ANSI/ISA 60079-15, ANSI/ISA 12.12.01, FM 3600 and FM 3611 subject to
the following conditions of approval:
1. Install the product in a protective enclosure providing at least IP54 protection.
2. Confirm that the location is free from explosively hazardous gases before wiring, connecting or
disconnecting the product, using any USB connection or replacing any fuses.
Scope
This manual describes:
The physical design of the RTU, including detailed hardware specifications
The physical design of integrated inputs and outputs (I/O) and the basic requirements for adding I/O
expansion modules
Installation, wiring and addressing for the RTU
Diagnostics capabilities on the RTU
Maintenance recommendations for the RTU
Related Documents
Use this manual with other manuals included in your SCADAPack E documentation set. The table below
lists the main manuals for the tasks described. However, it is not a complete list of the manuals
available to you. Please see the SCADAPack E Reference Manual set for a complete listing of manuals.
The basic steps required to get your RTU up and The Quick Start Guide for your RTU
running
Manuals
SCADAPack 535E
Roles
The SCADAPack 535E can be configured to play one or more of the following roles in your Supervisory
Control and Data Acquisition (SCADA) environment:
RTU endpoint
DNP3 router between any combination of Ethernet and serial ports
DNP3 peer-to-peer communications device
Data concentrator for:
- Remote DNP3 and DNP3 IP slaves
- Local DNP3, DNP3 IP, Modbus RTU, Modbus TCP and DF1 serial slaves
- Local IEC 60870-5-103 protection relays
Protocol converter for:
12 SCADAPack 535E Hardware Manual
- Modbus RTU and Modbus TCP to DNP3 and DNP3 IP, and vice-versa
- Modbus RTU and Modbus TCP to IEC 60870-5-101/-104
- DF1 to DNP3 and DNP3 IP, IEC 60870-5-101/-104 or Modbus RTU and Modbus TCP
- IEC 60870-5-103 to DNP3/DNP3 IP, IEC 60870-5-101/-104 or Modbus RTU and Modbus TCP
The role your SCADAPack 535E plays in your SCADA environment determines how you should set up
communications to and from the RTU and how you should configure the RTU.
Communications
The SCADAPack 535E includes four serial ports and three Ethernet ports that are available for
communications with the SCADA master system, with other RTUs, with devices such as Programmable
Logic Controllers (PLCs), and with the local configuration software. It also includes a USB 2.0 device
port for local configuration and a USB 2.0 host port that supports plug-in media.
A socket modem port that supports GPRS, 3G or LTE communications with remote devices will be
available at a later date.
The SCADAPack 535E communicates using the Distributed Network Protocol (DNP) 3, IEC 60870-5 and
Modbus protocols.
I/O can be extended by adding up to 15 I/O expansion modules. The SCADAPack 535E supports the
6601 I/O expansion module which provides the following I/O:
16 digital inputs
8 digital outputs
6 analog inputs
2 analog outputs (this option is selected when the 6601 I/O expansion module is ordered)
Configuration
You can configure the SCADAPack 535E using three different methods:
Locally or remotely using SCADAPack E Configurator 109 , a software application that runs on a
desktop or laptop computer that is connected to the RTU through the USB device port or through any
of the available serial or Ethernet ports.
Remotely as part of an end-to-end SCADA system using the StruxureWare SCADA Expert
ClearSCADA software.
Locally using applications created in the SCADAPack Workbench or ISaGRAF 3 Workbench user
programming tools. Typically, applications created in these tools extend and enhance the functionality
provided by the RTU. However, you can also write applications that replace the configuration
functionality provided through the SCADAPack E Configurator software or the SCADA Expert
ClearSCADA software.
Before you begin configuring the RTU, determine whether the ClearSCADA software will be used for any
configuration tasks. This documentation assumes you are using the SCADAPack E Configurator
software to configure the RTU. For information about using the ClearSCADA software, see the
ClearSCADA documentation.
SCADAPack 535E Hardware Manual 13
Security
The RTU can communicate using the DNP3 protocol, which is level 4-compliant. The DNP3 protocol
supports the optional DNP3 Secure Authentication (SAv2) features and AGA-12 DNP3 Data Encryption
to help improve message confidentiality.
14 SCADAPack 535E Hardware Manual
5 Hardware Overview
The figure below shows the locations of the inputs, outputs and ports on the SCADAPack 535E.
Generally, power supply ports and input/output (I/O) terminals provide a level of protection against over-
voltages and other conditions. For ease of wiring and maintenance, external connections are terminated
on removable connectors. If you need to remove the RTU cover for any reason, first carefully consider the
following information.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
SCADAPack 535E Hardware Manual 15
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from the RTU before removing the RTU cover.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The electronics inside the RTU can be damaged by static electricity. If you need to
remove the RTU cover, wear an anti-static wrist strap that is connected to ground.
Failing to follow this simple step can cause intermittent or total loss of RTU
operation and will void the warranty.
Failure to follow these instructions can result in equipment damage.
This table below provides an overview of the major hardware components that comprise the RTU. For
complete hardware specifications, see the Specifications 135 section.
Controller board
Digital outputs 38 9
Analog inputs 39 6
Communications
RAM
The onboard battery-backed RAM is used to store:
Configuration information such as point definitions and port configurations
User-created sequence and control applications such as those created in SCADAPack Workbench or
ISaGRAF 3 Workbench
Time-stamped event data
Storage
The RTU provides internal flash storage and support for USB storage media. The internal flash storage is
described here. For more information about support for plug-in storage media, see USB Ports 29 .
The use of flash memory chips allows you to transfer new firmware locally through a serial port and
remotely using command line instructions without removing the RTU front cover.
The boot monitor also provides facilities for reprogramming the operating system and boot monitor flash
memory.
SCADAPack 535E Hardware Manual 19
For details about power supply requirements, see Power Supply Requirements 53 .
A Tadiran TL-5186 3.6 V lithium battery installed on the RTU controller board provides back-up power to
the RTU's real-time clock and RAM memory. It also maintains the RTU configuration during a power-
supply interruption.
20 SCADAPack 535E Hardware Manual
Serial1 and Serial2 are general-purpose serial data communications ports that can be used for RS232
communications with the SCADA master system, with other RTUs, with devices such as Programmable
Logic Controllers (PLCs), and with the SCADAPack E Configurator computer.
Serial1 and Serial2 can also be used for ES Remote I/O communications when the RTU is functioning
as a Main RTU in an ES Remote I/O configuration.
The figure below shows a close-up view of the RS232 serial ports and their LEDs.
Serial Ports
For information about Serial3 and Serial4, see Serial3 and Serial4 Ports 23 .
Configuration
Serial1 and Serial2 support RS232 with modem control.
Using the SCADAPack E Configurator software, you can configure Serial1 and Serial2 to define the port
function, mode, baud and data mode, as summarized in the table below.
ISaGRAF (default for RS232 (RTS On) 300 bps 8-bit No Parity 1 Stop Bit
Serial1) (default) 600 bps (default)
DNP3 (default for RS232 (RTS Keyed) 1200 bps 8-bit Even Parity 1 Stop Bit
Serial2) Hayes Modem 2400 bps 8-bit Odd Parity 1 Stop Bit
Cmd Line GPRS 4800 bps 7-bit Even Parity 1 Stop Bit
PLC Device 1xRTT 9600 bps (default) 7-bit Odd Parity 1 Stop Bit
ISaGRAF-User RS232 (RTS Off) 19200 bps 8-bit No Parity 2 Stop Bits
ES Remote I/O 38400 bps
PPP/TCPIP 57600 bps
TCP Service 115,200 bps
Modbus Slave
22 SCADAPack 535E Hardware Manual
DNP-VT Service
IEC-103 Master
IEC-101 Slave
For more information about configuring serial ports, see the SCADAPack E Configurator User Manual
and the Communication Interfaces Technical Reference Manual.
Cabling
Serial1 and Serial2 support RS232 serial cables with an eight-pin RJ45 Data Terminal Equipment (DTE)
connector. For more information, see:
RS232 Pin Assignments and Cable Descriptions 77
LEDs
The following table describes the Serial1 and Serial2 LEDs on the RTU front panel and on the physical
ports.
CTS Green Lit when the CTS input is active on this serial port.
DCD Green Lit when the DCD input is active on this serial port.
Left side of the Green Blinks when the port is transmitting data over the RS232 serial
physical port connection.
Right side of the Green Blinks when the port is receiving data over the RS232 serial
physical port connection.
Binary system point 50750 indicates the status of power to pin 1. The system point is set when the
power to pin 1 is on, and is cleared when the power to pin 1 is off.
For more information, see the SCADAPack E Configurator User Manual and the Configuration Technical
Reference Manual
Specifications
SCADAPack 535E Hardware Manual 23
Serial3 and Serial4 are general-purpose serial data communications ports that can be used for RS232 or
RS485 communications with the SCADA master system, with other RTUs, with devices such as
Programmable Logic Controllers (PLCs), and with the SCADAPack E Configurator computer.
Serial3 and Serial4 can also be used for ES Remote I/O communications when the RTU is functioning
as a Main RTU in an ES Remote I/O configuration.
The figure below shows a close-up view of the serial ports and their LEDs along with the RS485 screw-
termination connectors for Serial3 and Serial4.
Serial Ports
For information about Serial1 and Serial2, see Serial1 and Serial2 Ports 21 .
Configuration
Serial3 and Serial4 are software configurable for three-wire RS232 communications or two-wire RS485
communications.
Using the SCADAPack E Configurator software, you can configure each of the serial ports to define its
function, mode, baud and data mode, as summarized in the table below.
For more information about configuring serial ports, see the SCADAPack E Configurator User Manual
and the Communication Interfaces Technical Reference Manual.
Cabling
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Serial3 and Serial4 support RS232 or RS485 operation, but not both at the same
time. If Serial3 or Serial4 is configured for RS485 operation, the port must remain
empty.
Do not insert an RS232 cable into Serial3 if there is a two-wire RS485 connection
to the screw-termination connectors labeled Serial3+ and Serial3-.
Do not insert an RS232 cable into Serial4 if there is a two-wire RS485 connection
to the screw-termination connectors labeled Serial4+ and Serial4-.
Failure to follow these instructions can result in equipment damage.
When configured as RS232, the Serial3 and Serial4 serial ports support RS232 serial cables with an
eight-pin RJ45 Data Terminal Equipment (DTE) connector. For more information, see:
When configured as RS485, the Serial3 and Serial4 screw-termination connectors support wired
connections:
If Serial3 is configured as RS485, you can create a two-wire RS485 connection to the screw-
termination connectors labeled Serial3+ and Serial3-.
If Serial4 is configured as RS485, you can create a two-wire RS485 connection to the screw-
termination connectors labeled Serial4+ and Serial4-.
A maximum of 32 RTUs and other devices can be connected to any one RS485 network.
RS485 Wiring 83
LEDs
The following table describes the Serial3 and Serial4 LEDs.
Left side of the Green Blinks when data is being transmitted over the RS232 or RS485
physical port serial connection.
If the port is configured for RS485, the LEDs on the empty port
indicate that data is being transmitted over the wired RS485
connection.
Right side of the Green Blinks when data is being received over the RS232 or RS485 serial
physical port connection.
If the port is configured for RS485, the LEDs on the empty port
indicate that data is being received over the wired RS485
connection.
Binary system point 50750 indicates the status of power to pin 1. The system point is set when the
power to pin 1 is on, and is cleared when the power to pin 1 is off.
For more information, see the SCADAPack E Configurator User Manual and the Configuration Technical
Reference Manual.
Specifications
For serial port specifications, see Communications Specifications 140 .
26 SCADAPack 535E Hardware Manual
Eth1, 2, 3 Ports 27
SCADAPack 535E Hardware Manual 27
The three Ethernet ports are UTP 10/100BASE-T LAN ports that can be used for IP communications and
for ES Remote I/O communications when the RTU is functioning as a Main RTU in an ES Remote I/O
configuration. The Ethernet ports are typically used for point-to-point Ethernet connections and are
usually connected to an Ethernet hub or switch, although it is also possible to connect devices together
directly.
Each Ethernet port can run at 10 Mbps or 100 Mbps, at half or full duplex. The RTU automatically
detects an active Ethernet port and the supported speed of the connected device, giving preference to
100 Mbps full duplex connections.
The following figure shows a close-up view of the three Ethernet ports and their LEDs.
Ethernet Ports
Configuration
Using the SCADAPack E Configurator software, you can configure each of the Ethernet ports to define
its:
Function: TCP/IP + RemIO (default) or ES Remote I/O
IP Address
Subnet Mask
For more information about configuring Ethernet ports, see the SCADAPack E Configurator User Manual
and the TCP/IP Technical Reference Manual.
Cabling
The Ethernet ports support crossover or straight-through Ethernet cables with an eight-pin RJ45
connector. The RTU will automatically detect the interface used and serve the cable appropriately.
For more information, see Ethernet Pin Assignments and Cable Descriptions 84 .
LEDs
The following table describes the Ethernet LED status indications.
Specifications
For Ethernet port specifications, see Communications Specifications 140 .
SCADAPack 535E Hardware Manual 29
The figure below shows the location of the two USB ports on the SCADAPack 535E.
The USB host port is a USB series A receptacle that allows the RTU controller board to act as a host for
a plug-in USB drive. For bus-powered USB devices, the host port can provide up to 100 mA at 5 V.
The USB host port is not user configurable. It can be mounted and accessed through the RTU file
system at /usb0. For information about support for plug-in USB drives, see Data Capacity 139 .
WARNING
EXPLOSION RISK
Use USB ports only for non-hazardous applications in locations that are known to
be in a non-hazardous state.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Verify that the data transfer between the RTU and the plug-in USB drive is complete
before removing the USB drive from the USB host port.
Removing a plug-in USB drive from the host port while the data transfer is in
progress can impact system performance and result in a system restart.
The following illustration shows the connections for the USB host port.
4 1. VBUS
3 2. D-
3. D+
2 4. GND
1
LEDs
The following table describes the USB host port LEDs on the RTU front panel.
Status Green This LED is under the control of Binary System Point 50753. It can be
controlled by a SCADAPack Workbench or ISaGRAF 3 Workbench
application or through protocol control commands.
Store Green Flashes on and off alternately at a steady rate for five seconds when
data from the USB mass storage device is successfully loaded into
the RTU.
32 SCADAPack 535E Hardware Manual
The USB device port is a USB series B receptacle that provides DNP3 communications for local
connection to a local USB device, such as the computer running the SCADAPack E Configurator
software.
WARNING
EXPLOSION RISK
Use USB ports only for non-hazardous applications in locations that are known to
be in a non-hazardous state.
Configuration
Using the SCADAPack E Configurator software, you can configure the USB device port for DNP3
communications. This is the default configuration for the port. The USB device port is referred to as Port
0 in the SCADAPack E Configurator software and in SCADAPack E diagnostics.
The following illustration shows the connections for the USB device port.
The following table describes the SCADAPack 535E input and output characteristics.
I/O board Digital inputs DI 1-8 Yes Digital inputs, the first eight (DI 1-8) of which
36 1-16 DI 9-16 have associated counters.
Counter inputs Organized into two groups of eight inputs:
37 1-8 DI 1-8 and DI 9-16.
Each group shares a common return.
The two groups are optically isolated from
one another and from the logic power.
The inputs and outputs use 5 mm (.197 in.) pitch connectors. For information about wiring these
connectors, see Wiring Screw-Termination Connectors 73 .
Data that is received and sent through the inputs and outputs can be:
Transferred to an attached Programmable Logic Controller (PLC) for processing by that PLC
Time-stamped and stored locally for manual or automatic retrieval
These capabilities are provided by the RTU firmware. For more information, see the SCADAPack E
Technical Overview.
I/O can be extended by adding the 6601 I/O expansion module with the optional analog output module.
For details, see Adding Inputs and Outputs 57 .
36 SCADAPack 535E Hardware Manual
Digital inputs are used to monitor the state of remote devices such as panel lamps, relays, motor
starters, solenoid valves and other devices.
Digital inputs are available for nominal 12...24 V operation. A current-limiting resistor on each input
determines the voltage range.
Wetting voltage for the volt-free contacts is usually provided by the DC power used with the RTU.
The digital inputs provide 1 ms Sequence of Event (SOE) time stamping to support Sequence Of Event
(SOE) applications.
The digital inputs also support state debouncing. If debouncing is enabled on a digital input channel,
then SOE time stamping on the digital point has the same resolution as the debounce resolution.
The LED for each digital input is lit when the input is active.
Configuration
Using the SCADAPack E Configurator software, you can configure each digital input to define its
characteristics, including:
DNP3 attributes
Alarm and trend attributes
Invert state
Remote control interlock attributes
Debounce time
For more information about configuring digital inputs, see the SCADAPack E Configurator User Manual
and the Configuration Technical Reference Manual.
Wiring
Digital inputs support solid or stranded wires from 3.3 mm2 to .08 mm2 (12 AWG to 28 AWG). For more
information, see Wiring Screw-Termination Connectors 73 .
Specifications
For digital input specifications, see Specifications 135 .
SCADAPack 535E Hardware Manual 37
For digital inputs that have an associated counter, the counter inputs are represented as 32-bit
counters.
The corresponding digital input invert settings are applied prior to counting transitions of the input.
If configured as non-inverting (default configuration), counter input points count OFF to ON
transitions.
If configured as inverted, ON to OFF transitions are counted on the corresponding counter channel.
The LED for each counter input is lit when the input is active.
Configuration
Using the SCADAPack E Configurator software, you can configure each counter input to define its
characteristics, including:
DNP3 attributes
Counter values
Alarm and trend attributes
Event attributes
Remote control interlock attributes
For more information about configuring counter inputs, see the SCADAPack E Configurator User Manual
and the Configuration Technical Reference Manual.
Wiring
Counter inputs support solid or stranded wires from 3.3 mm2 to .08 mm2 (12 AWG to 28 AWG). For
more information, see Wiring Screw-Termination Connectors 73 .
Specifications
For counter input specifications, see Specifications 135 .
38 SCADAPack 535E Hardware Manual
Digital outputs are used to control panel lamps, relays, motor starters, solenoid valves and other
devices. The relay outputs are well suited to applications that cannot tolerate any off-state leakage
current, that require high load currents, or that involve non-standard voltages or current ranges.
For Form A digital outputs that have a single Normally Open (NO) contact, loads can be connected to
either the high or the low side of the power source.
For Form C digital outputs that have an NO contact, a Normally Closed (NC) contact and a Common
(COM) contact, loads can be connected to either the NO or the NC terminal, and to either the high or the
low side of the power source. A signal from the second pole on each relay provides feedback to the
software to verify the correct relay activation for each operation.
The LED for each digital output is lit when the NO contact is closed, or activated, and the circuit is
continuous. For Form C digital outputs, this means the NC contact is open.
Configuration
Using the SCADAPack E Configurator software, you can configure each digital output to define its
characteristics, including:
DNP3 attributes
Alarm and trend attributes
Invert state
Remote control interlock attributes
Output pulse time
For more information about configuring digital outputs, see the SCADAPack E Configurator User Manual
and the Configuration Technical Reference Manual.
Wiring
Digital outputs support solid or stranded wires from 3.3 mm2 to .08 mm2 (12 AWG to 28 AWG).For more
information, see Wiring Screw-Termination Connectors 73 .
Specifications
For digital output specifications, see Specifications 135 .
SCADAPack 535E Hardware Manual 39
Analog inputs are used to monitor devices such as pressure, level, flow and temperature transmitters,
instrumentation such as pH and conductivity sensors, and other high-level analog signal sources.
Each analog input is individually configured for the input type — current or voltage — and range. The
SCADAPack 535E and the 6601 I/O expansion module use a 24-bit delta-sigma analog to digital (A/D)
converter.
The RTU is factory-calibrated for 0...20 mA and 4...20 mA current inputs and for 0...5 V and 1...5 V
operation. The mode of operation — current mode or voltage mode — is selected when the RTU or I/O
expansion module is purchased.
In current mode, a 250 ohm current sense resistor is used across each analog input channel. The
measurement range in current mode is 0...20 mA or 4...20 mA, selectable through the SCADAPack E
Configurator software. The 250 ohm resistor produces a voltage drop (input reading) of 5 V for 20 mA of
current flow. Loop current will only flow in analog inputs that have been configured for 20 mA.
In voltage mode, the analog inputs are high-impedance and single-ended with a measurement range of
0...5 V or 1...5 V, selectable through the SCADAPack E Configurator software.
The RTU also supports using a mix of current mode and voltage mode analog inputs if required. For
details, see Supporting Current and Voltage Inputs 98 .
Configuration
Using the SCADAPack E Configurator software, you can configure each analog input to define its
characteristics, including:
DNP3 attributes
Current values
Alarm and trend attributes
Scaling
Value deviation
For more information about configuring analog inputs, see the SCADAPack E Configurator User Manual
and the Configuration Technical Reference Manual.
Wiring
Analog inputs support solid or stranded wires from 3.3 mm2 to .08 mm2 (12 AWG to 28 AWG). For more
information, see Wiring Screw-Termination Connectors 73 .
Specifications
For analog input specifications, see Specifications 135 .
40 SCADAPack 535E Hardware Manual
The analog inputs have a 24-bit, unipolar, analog to digital (A/D) converter that measures input voltages
from 0...5 V.
To assign RTU database points to the analog input channels, use the SCADAPack E Configurator to
select the signal range for each analog input channel. Each analog input channel can be configured for
one of the following signal ranges:
0...20 mA
4...20 mA
0...5 V
1...5 V
The signal range selected is scaled to the Raw Min. to Raw Max. values defined for each analog input
point when point integer values are used. The Eng. Min. to Eng. Max. values for the point are used to
scale the analog input Engineering Floating Point database value.
For example, if an analog input point's attributes are Raw Min. = 0, Raw Max. = 10,000 and the input
channel is selected for 4...20 mA:
A 20 mA input is 100% of the selected input signal range and corresponds to 10,000 counts.
A 4 mA input is 0% of the selected input signal range and corresponds to 0 counts.
SCADAPack 535E Hardware Manual 41
The following tables show the over- and under-range status for current and voltage signals. Over- and
under-range status detection occurs when the measured input is outside of the specified range by more
than 0.2%.
Over- and Under-Range Status for Current Signals
RAW_MIN RAW_MIN
0.00 ENG_MIN 0 OFF ENG_MIN 0 ON
17.5% of RAW_MIN
3.50 range 1750 OFF ENG_MIN 0 ON
RAW_MIN
4.00 20% of range 2000 OFF ENG_MIN 0 OFF
8.00 40% of range 4000 OFF 25% of range 2500 OFF
12.00 60% of range 6000 OFF 50% of range 5000 OFF
16.00 80% of range 8000 OFF 75% of range 7500 OFF
RAW_MAX RAW_MAX
20.00 ENG_MAX 10000 OFF ENG_MAX 10000 OFF
RAW_MAX RAW_MAX
20.01 ENG_MAX 10000 ON ENG_MAX 10000 ON
RAW_MIN RAW_MIN
0.00 ENG_MIN 0 OFF ENG_MIN 0 ON
17.5% of RAW_MIN
0.99 range 1980 OFF ENG_MIN 0 ON
RAW_MIN
1.00 20% of range 2000 OFF ENG_MIN 0 OFF
2.00 40% of range 4000 OFF 25% of range 2500 OFF
42 SCADAPack 535E Hardware Manual
RAW_MAX RAW_MAX
5.00 ENG_MAX 10000 OFF ENG_MAX 10000 OFF
RAW_MAX RAW_MAX
5.01 ENG_MAX 10000 ON ENG_MAX 10000 ON
1
Over- and under-range point status may also be asserted by SCADAPack E analog
input point configuration parameters. For more information see the SCADAPack E I/O
Expansion Reference Manual and the Data Processing Technical Reference Manual.
SCADAPack 535E Hardware Manual 43
Analog outputs are used to control remote devices that require varying input information, rather than
simply on or off operations.
If the optional analog output module was selected when the SCADAPack 535E or the 6601 I/O
expansion module was ordered, two 20 mA analog outputs are available for use.
The analog output channels are powered with an external 12...30 Vdc (nominally 12 Vdc or 24 Vdc)
power supply. They can be configured for 4...20 mA current or 0...20 mA current. The outputs provide a
level of transient and over-voltage protection. Analog output resolution is 12 bits. The outputs share a
common return with each other and with the analog inputs.
Configuration
Using the SCADAPack E Configurator software, you can configure each analog output to define its
characteristics, including:
DNP3 attributes
Current values
Trend inhibit state
Scaling
Value deviation
For more information about configuring analog outputs, see the SCADAPack E Configurator User Manual
and the Configuration Technical Reference Manual.
Wiring
Analog outputs support solid or stranded wires from 3.3 mm2 to .08 mm2 (12 AWG to 28 AWG).For
more information, see Wiring Screw-Termination Connectors 73 .
Specifications
For analog output specifications, see Specifications 135 .
44 SCADAPack 535E Hardware Manual
The optional analog output module, which is selected when the SCADAPack 535E or the 6601 I/O
expansion module is ordered, has a 12-bit, unipolar, digital to analog (D/A) converter.
You can select one of the following Output Type ranges on the SCADAPack I/O property page in the
SCADAPack E Configurator software. Both analog output channels use the same range:
0...20 mA
4...20 mA
The 0...20 mA output range resolution is 4.88 µA per D/A count.
Configuration for points attached to the analog output module channels uses the SCADAPack E Raw
Min. to Raw Max. and Eng. Min. to Eng. Max. parameters for integer and engineering scaling,
respectively.
These scaling ranges automatically apply to the analog input signal range selected in SCADAPack E
Configurator for the 6601 I/O expansion module analog Output Type (0...20 mA or 4...20 mA).
SCADAPack 535E Hardware Manual 45
The load resistance for any given power supply voltage is limited:
On the high resistance end by the requirement for proper operation of the analog output circuit
On the low resistance end by the power dissipation in the analog output
The table below lists the analog output load resistance range. The operating range is within the area
defined as resistance limits.
The GND connectors can be used in individual connections, or they can be connected to a terminal strip
that provides additional ground connection points.
SCADAPack 535E Hardware Manual 47
1
The optional analog outputs are selected when the SCADAPack 535E is ordered.
48 SCADAPack 535E Hardware Manual
6 Installation
The SCADAPack 535E is factory-configured and under normal conditions does not require removal or
insertion of any peripherals or components. The configurations are stored in a combination of battery-
backed RAM and flash memory.
The lithium-powered RAM back-up battery has a shelf life of approximately two years when the RTU is
not connected to a power source. Battery life can be increased to more than eight years when the RTU
is permanently connected to a power source.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
RTU configuration information can be lost if the onboard RAM back-up battery goes
flat, is disconnected, if the RTU is damaged, or if there has been a firmware
upgrade.
Verify the voltage of the onboard RAM back-up battery before installing the RTU in
the field.
Failure to follow these instructions can result in equipment damage.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Installing the RTU in an environment where the electromagnetic compatibility (EMC)
rating exceeds the certified EMC rating for the RTU can lead to unpredictable
operation and unexpected results.
Failure to follow these instructions can result in equipment damage.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the SCADAPack 535E before removing power.
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from the RTU before mounting it on a DIN rail.
Do not remove the RTU cover when mounting the RTU. The RTU is designed so
that it can be mounted on a DIN rail with the cover in place.
Failure to follow these instructions can result in death or serious injury.
50 SCADAPack 535E Hardware Manual
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The RTU can be mounted on a horizontally oriented DIN rail or on a vertically
oriented DIN rail.
The operating temperature for the RTU and the current rating for the digital outputs
are lower when the RTU is mounted on a vertically oriented DIN rail.
Read and understand the temperature specifications before mounting the RTU. See
the Specifications 135 for details.
Failure to follow these instructions can result in equipment damage.
1. With the lower part of the RTU tilted away from the DIN rail, position the mounting guide line on the
side of the RTU so that it is just above the edge of the DIN rail.
The springs on the back of the RTU should rest on the DIN rail and the edge of the DIN rail should be
under the support claws that are adjacent to the springs, as shown below.
2. Push firmly on the RTU while tilting it toward the DIN rail until the DIN rail is positioned under both
SCADAPack 535E Hardware Manual 51
3 Release the pressure on the springs so that the DIN rail is held firmly in place between the upper and
lower claws.
The mounting guide line should be aligned with the edge of the DIN rail.
The figure below shows a SCADAPack 535E with the DIN rail correctly positioned in the upper and
lower claws on the back of the RTU.
The figure below shows the front view of a SCADAPack 535E RTU that is mounted on a horizontally
oriented DIN rail.
52 SCADAPack 535E Hardware Manual
Volts (V) Power (W) Power (W) Power (W) Power (W)
WARNING
UNEXPECTED EQUIPMENT OPERATION
The input power supply must be a filtered DC supply.
Failure to follow these instructions can result in death or serious injury.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Safety Extra Low Voltage (SELV) or Protective Extra Low Voltage (PELV) power
supplies are required on the power input and I/O points. Power supplies with
100...240 Vac inputs that comply with safety standard IEC/EN 60950 generally
have SELV outputs. Check with the manufacturer or the agency certification listing
to confirm that they have SELV outputs.
Failure to follow these instructions can result in death or serious injury.
54 SCADAPack 535E Hardware Manual
Schneider Electric Phaseo regulated power supply, part number ABL 7RM24025, providing 100...240
Vac in and 24 Vdc, 2.5 A out.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Install an external 1.6 A fast-acting fuse on the input voltage side of the power
supply connection.
Failure to follow these instructions can result in equipment damage.
The following figure illustrates power supply wiring. For details on wiring the power supply connectors,
see Wiring Screw-Termination Connectors 73 .
There are two configuration options for the external 24 Vdc power supply that is required when the
optional analog output module is installed:
The analog output module and the RTU can each have their own 24 Vdc power supply. In this
configuration, the analog outputs are isolated from the system logic.
The analog output module can share an external 24 Vdc power supply with the RTU. In this
configuration, the analog outputs are not isolated from the system logic.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Install an external 1.6 A fast-acting fuse on the input voltage side of the RTU power
supply connection.
Install an external 0.063 A fast-acting fuse on the input voltage side of the analog
output power supply connection.
Failure to follow these instructions can result in equipment damage.
The following figure illustrates the power supply configurations for isolated and non-isolated analog
outputs. For details on wiring the power supply connectors, see Wiring Screw-Termination Connectors
73 .
56 SCADAPack 535E Hardware Manual
Power Requirements
The 6601 I/O expansion module requires 5 V power, which is provided by the RTU. However, if the
analog output option was selected when the 6601 I/O expansion module was purchased, an additional
24 Vdc power supply is required to power the field-side circuitry. Each analog output module requires 50
mA current regardless of the system voltage.
For more information, see:
Power Supply Specifications 137
6601 Hardware Manual
Configuration
Use the SCADAPack E Configurator software to configure the inputs and outputs on the I/O expansion
module.
For more information, see:
SCADAPack E Configurator User Manual
Configuration Technical Reference Manual
SCADAPack E I/O Expansion Reference Manual
SCADAPack E RTUs and 6601 I/O expansion modules are supplied with a short intermodule cable that
connects the unit to an RTU or to an I/O expansion module.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU or the I/O expansion module before removing power.
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from the I/O expansion module before removing the I/O expansion
module cover.
Remove power from the RTU before removing the RTU cover.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The electronics inside the I/O expansion module and the RTU can be damaged by
static electricity. If you need to remove the I/O expansion module or the RTU cover,
wear an anti-static wrist strap that is connected to ground.
Failing to follow this simple step can cause intermittent or total loss of I/O
expansion module and RTU operation and will void the warranty.
Failure to follow these instructions can result in equipment damage.
If you need to supply your own intermodule cable, follow these recommendations:
SCADAPack 535E Hardware Manual 59
Connect the shielding wire on the intermodule cable to a convenient chassis ground point. There is a
small hole in the I/O expansion module for grounding the shielding wire.
Confirm that the power supply is rated for the total number of modules in the system.
For additional details, refer to the SCADAPack E I/O Expansion Reference manual.
The intermodule cable is connected from the SCADAPack E RTU to the 6601 I/O expansion module
connector as shown in the illustrations below.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
To help adequate air flow through the I/O expansion module, mount it upright on a
DIN rail in the position shown below. Mounting the I/O expansion module in other
positions can affect its operation at high temperatures, leading to unexpected
results.
Failure to follow these instructions can result in equipment damage.
In every other configuration, the RTU address should remain at its default setting of 0. That means:
The physical hex switch on the RTU should remain at 0.
The read-only analog system point 50002 displays 0 in the SCADAPack E Configurator Point
Browser property page.
Startup Modes
By default, the RTU starts in Run mode when power is applied. Run mode is used for normal day-to-day
operations.
Holding down the Select button on the RTU front cover allows you to start the RTU in other modes of
operation. The startup mode is determined by the length of time the Select button is depressed when
power is applied to the RTU or a controller board reset occurs. The longer the Select button is
depressed, the more actions are applied to the RTU.
Because the startup mode is not determined until the Select button is released, you can cancel the
startup mode selection by removing power to the RTU while the Select button is depressed. This can be
a useful tactic to avoid starting up in modes where more actions are applied if you have held the Select
button down longer than your preferred startup mode requires.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment monitored and controlled by the
RTU prior to initializing it.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Starting the RTU in Cold Boot mode or Factory Boot mode returns RTU
configuration parameters to their default settings and erases applications created in
SCADAPack Workbench and ISaGRAF 3 Workbench. This information must be
reloaded into the RTU for correct RTU operation.
Before starting the RTU in Cold Boot mode or Factory Boot mode, save a copy of
the RTU configuration information, user-created applications, logs and other data to
an external drive so it can be reloaded when the procedure is complete.
Failure to follow these instructions can result in equipment damage.
SCADAPack 535E Hardware Manual 63
The following tables describe the four RTU startup modes and the actions that are applied in each case.
Startup Modes
X X Database initialized
X Files erased
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU before restarting it.
Failure to follow these instructions can result in death or serious injury.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU before removing power.
Failure to follow these instructions can result in death or serious injury.
If you release the Select button before the Status LED turns on, the RTU will start in Run mode.
68 SCADAPack 535E Hardware Manual
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU before removing power.
Failure to follow these instructions can result in death or serious injury.
SCADAPack 535E Hardware Manual 69
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Starting the RTU in Cold Boot mode returns RTU configuration parameters to their
default settings and erases applications created in SCADAPack Workbench and
ISaGRAF 3 Workbench. This information must be reloaded into the RTU for correct
RTU operation.
Before starting the RTU in Cold Boot mode, save a copy of the RTU configuration
information, user-created applications, logs and other data to an external drive so it
can be reloaded when the procedure is complete.
Failure to follow these instructions can result in equipment damage.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU before removing power.
Failure to follow these instructions can result in death or serious injury.
SCADAPack 535E Hardware Manual 71
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Starting the RTU in Factory Boot mode returns RTU configuration parameters to
their default settings and erases applications created in SCADAPack Workbench
and ISaGRAF 3 Workbench. This information must be reloaded into the RTU for
correct RTU operation.
Before starting the RTU in Factory Boot mode, save a copy of the RTU
configuration information, user-created applications, logs and other data to an
external drive so it can be reloaded when the procedure is complete.
Failure to follow these instructions can result in equipment damage.
8 Field Wiring
The serial and Ethernet ports on the SCADAPack 535E can be connected to:
A SCADA master system such as StruxureWare SCADA Expert ClearSCADA
Other SCADAPack E RTUs
Devices such as Programmable Logic Controllers (PLCs)
The SCADAPack E Configurator computer
For information about cabling for serial and Ethernet ports, see:
Serial Port Wiring 76
The inputs and outputs on the SCADAPack 535E are connected to the device that you want to monitor
or control. In general, inputs are used to monitor devices, while outputs are used to control devices.
These 5 mm (0.197 in.) pitch connectors support solid or stranded wires from 3.3 mm2 to .08 mm2 (12
AWG to 28 AWG).
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU or the I/O expansion module before removing power.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Remove power from the RTU before servicing.
Failure to follow these instructions can result in equipment damage.
74 SCADAPack 535E Hardware Manual
To Wire a Connector
1. Use a slotted screwdriver to loosen the termination screw.
2. Insert the stripped wire into the connector so that the bared wire is located under the screw.
As illustrated below, the bared wire should be placed fully within the connector.
SCADAPack 535E Hardware Manual 75
3. Apply 0.5 Nm (4.5 lb-in.) torque to tighten the screw so the wire is held firmly in place.
76 SCADAPack 535E Hardware Manual
RS485 Wiring 83
SCADAPack 535E Hardware Manual 77
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Serial3 and Serial4 support RS232 or RS485 operation, but not both at the same
time. If Serial3 or Serial4 is configured for RS485 operation, the port must remain
empty.
Do not insert an RS232 cable into Serial3 if there is a two-wire RS485 connection
to the screw-termination connectors labeled Serial3+ and Serial3-.
Do not insert an RS232 cable into Serial4 if there is a two-wire RS485 connection
to the screw-termination connectors labeled Serial4+ and Serial4-.
Failure to follow these instructions can result in equipment damage.
1 +5V
2 DCD
3 DTR
4 GND
5 RxD
6 TxD
78 SCADAPack 535E Hardware Manual
7 CTS
8 RTS
1 +5V
4 GND
5 RxD
6 TxD
8
SCADAPack 535E Hardware Manual 79
6 TxD RxD 2
5 RxD TxD 3
4 GND GND 5
3 DTR DTR 4
6 TxD TxD 3
5 RxD RxD 2
2 DCD DCD 1
4 GND GND 5
7 CTS CTS 8
8 RTS RTS 7
80 SCADAPack 535E Hardware Manual
1 +5V +5V 9
SCADAPack 535E Hardware Manual 81
The illustrations in this topic show different wiring options for the RS232 serial ports. The wiring options
you can use depend on the serial port signaling capabilities:
Serial1 and Serial2: TxD, RxD, CTS, RTS, DCD, DTR
Serial3 and Serial4: TxD, RxD
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from all devices before connecting or disconnecting inputs or
outputs to any terminal or installing or removing any hardware.
Failure to follow these instructions can result in death or serious injury.
There are several methods for wiring an RS232 serial port to Data Terminal Equipment (DTE) and Data
Communications Equipment (DCE) devices. The simplest connection requires only three wires: RxD,
TxD and signal ground. The following diagram shows the wiring between two DTE devices when
handshaking is not required.
RS-232 COM port (DTE)
8 Pin connector DTE
DCD 2 DCD
RxD 5 RxD
TxD 6 TxD
DTR 3 DTR
GND 4 GND
RTS 8
CTS 7 RTS
+ 5V 1 CTS
See device
specifications
for pin numbers
Some DTE devices may require hardware handshaking lines. The CTS and RTS lines are commonly
used for handshaking. The DTR and DCD lines are less commonly used. The RTU does not require
these lines. Refer to the specifications for the external device for exact requirements. The following
diagram shows the wiring between two DTE devices when handshaking is required.
82 SCADAPack 535E Hardware Manual
DCD 2 DCD
RxD 5 RxD
TxD 6 TxD
DTR 3 DTR
GND 4 GND
RTS 8
CTS 7 RTS
+ 5V 1 CTS
See device
specifications
for pin numbers
DCE devices require different wiring. The handshaking lines need to be connected. Many DCE devices
are half-duplex. Select half-duplex operation with these devices. The diagram below shows the wiring
between a DTE device and a DCE device with handshaking.
RS-232 COM port (DTE)
8 Pin connector DCE
DCD 2 DCD
RxD 5 RxD
TxD 6 TxD
DTR 3 DTR
GND 4 GND
RTS 8 RTS
CTS 7 CTS
+ 5V 1
See device
specifications
for pin numbers
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from all devices before connecting or disconnecting inputs or
outputs to any terminal or installing or removing any hardware.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Serial3 and Serial4 support RS232 or RS485 operation, but not both at the same
time. If Serial3 or Serial4 is configured for RS485 operation, the port must remain
empty.
Do not insert an RS232 cable into Serial3 if there is a two-wire RS485 connection
to the screw-termination connectors labeled Serial3+ and Serial3-.
Do not insert an RS232 cable into Serial4 if there is a two-wire RS485 connection
to the screw-termination connectors labeled Serial4+ and Serial4-.
Failure to follow these instructions can result in equipment damage.
The Serial3 and Serial4 RS485 screw-termination connectors support solid or stranded wires from 3.3
mm2 to .08 mm2 (12 AWG to 28 AWG). The table below describes the polarity assignment for these
connectors.
Serial3 Positive
+
Serial3 Negative
-
Serial4 Positive
+
Serial4 Negative
-
Either of the terminal connections labeled GND (ground) can be used with RS485 screw-termination
connections.
For instructions on inserting wires into the RS485 connectors, see Wiring Screw-Termination
Connectors 73 .
84 SCADAPack 535E Hardware Manual
1 +Tx
2 -Tx
3 +Rx
6 -Rx
8
86 SCADAPack 535E Hardware Manual
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The IEEE 802.3 10 BASE-T specification requires that 10 BASE-T and 100 BASE-T
devices support UTP 100-120 unshielded twisted pair cables of not less than 100 m
(328 ft) in length.
This requirement does not factor in losses due to connectors, patch panels, punch-
down blocks, or other cable management hardware, which introduce additional
loss.
For each connector or other intrusive cable management device in the total link,
subtract 12 m (39 ft) from the total allowable link length.
As long as specifications are met for the entire length of the cable, UTP cable segments can be run up
to a maximum allowable length of 200 m (656 ft).
The Ethernet ports on the RTU automatically configure themselves for Medium Dependent Interface
(MDI) or MDI-X. This means that either a crossover or a straight-through Ethernet cable can be used. The
RTU will automatically detect the interface used and serve the cable appropriately.
SCADAPack 535E Hardware Manual 87
NOTICE
88 SCADAPack 535E Hardware Manual
The figure below shows a connection from Din 2 and a ground connector to a power supply or battery.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
When wiring digital and counter inputs:
Confirm that the connection to the digital or counter input does not exceed the
ratings for the input. See the specifications 135 section for details.
Confirm that the polarity of the connection is correct with the two positive
terminals wired together and the two negative terminals wired together.
Failure to follow these instructions can result in equipment damage.
SCADAPack 535E Hardware Manual 89
NOTICE
UNEXPECTED EQUIPMENT OPERATION
When the unit is operating in an electrically noisy environment use shielded wires
on connections to digital and counter inputs 1-4.
Failure to follow these instructions can result in equipment damage.
The figure below shows a shielded connection to DI 1 and an unshielded connection to DI 5. Both
connections are wired to the common for digital inputs 1-8 and to a power supply or battery.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Incandescent lamps and other loads may have inrush currents that will exceed the
rated maximum current of the relay contacts. This inrush current may damage the
relay contacts. Interposing relays need to be used in these situations.
Failure to follow these instructions can result in equipment damage.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
External lightning protection is required if the device being controlled is outside the
physical area (cubicle or building) in which the RTU is located.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
When controlling inductive loads, the relay contacts on digital outputs must be
protected. The energy stored in the coil can generate significant electrical noise
when the relay contacts are opened.
To suppress the noise in DC circuits, place a diode across the coil.
To suppress the noise in AC circuits, place a metal-oxide varistor (MOV) across
the coil.
The figure below shows a wiring example for the controller board digital output which provides an open
drain metal-oxide semiconductor field-effect transistor (MOSFET) for controlling loads such as relays or
lamps. See the specifications 135 for details about the power rating for this digital output.
For information about controlling devices with this digital output, see Controlling Devices with the
Controller Board Digital Output 92 .
92 SCADAPack 535E Hardware Manual
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Incandescent lamps and other loads may have inrush currents that will exceed the
rated maximum current of the relay contacts. This inrush current may damage the
relay contacts. Interposing relays need to be used in these situations.
Failure to follow these instructions can result in equipment damage.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
External lightning protection is required if the device being controlled is outside the
physical area (cubicle or building) in which the RTU is located.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
When controlling inductive loads, the relay contacts on digital outputs must be
SCADAPack 535E Hardware Manual 93
protected. The energy stored in the coil can generate significant electrical noise
when the relay contacts are opened.
To suppress the noise in DC circuits, place a diode across the coil.
To suppress the noise in AC circuits, place a metal-oxide varistor (MOV) across
the coil.
The single digital output on the controller board does not include an internal relay. As a result, this digital
output needs an external interposing relay to control devices.
Add the external interposing relay between the digital output and the device that you want to control. The
example below shows the wiring needed to control a grounded device, such as a radio.
See the specifications 135 for details about the power rating for this digital output.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Incandescent lamps and other loads may have inrush currents that will exceed the
rated maximum current of the relay contacts. This inrush current may damage the
relay contacts. Interposing relays need to be used in these situations.
Failure to follow these instructions can result in equipment damage.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
External lightning protection is required if the device being controlled is outside the
physical area (cubicle or building) in which the RTU is located.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
When controlling inductive loads, the relay contacts on digital outputs must be
protected. The energy stored in the coil can generate significant electrical noise
when the relay contacts are opened.
To suppress the noise in DC circuits, place a diode across the coil.
To suppress the noise in AC circuits, place a metal-oxide varistor (MOV) across
the coil.
NOTICE
SCADAPack 535E Hardware Manual 97
Loop-powered transmitters are two-terminal devices that are connected between a power supply and
the analog input. The loop current from the power supply passes through the transmitter and returns to
the power supply through a 250 ohm resistor in the 20 mA input circuit.
Self-powered transmitters have three terminals:
Power In connects to a power supply
Signal Out connects to the analog input channel
Common connects to COM
Self-powered transmitters can have a current or voltage output.
In the wiring example below, Transmitter 1 is grounded and connected to AI 1-. Transmitter 6 is
connected to the positive power supply and to AI 6+. These two connections are possible because the
analog inputs are isolated.
Overview
The unit is shipped with the six analog inputs operating either in DC current mode or in DC voltage
mode. However, you can change the input mode for individual analog inputs to support a mix of current
and voltage analog inputs if needed.
The unit is factory-calibrated for 0...20 mA and 4...20 mA current inputs and for 0...5 V and 1...5 V
operation so there is no need to adjust the calibration when you change the input mode for an analog
input.
Changing voltage inputs to current inputs
If the analog inputs are operating in DC voltage mode, there are two ways to support DC current input:
Add an external resistor to convert the current input to voltage input. This is the recommended
approach because:
You do not need to remove the unit from the DIN rail or disconnect the wiring.
The current loop can be configured so it is not interrupted if you need to service the unit.
For details, see Converting Current Input to Voltage Input 98 .
Move the appropriate analog input dip switches from the voltage position to the current position. This
approach is not recommended because:
In most situations you need to remove the unit from the DIN rail and disconnect the wiring.
The current loop is interrupted if you need to service the unit.
If you choose this approach, carefully consider the precautions below before proceeding. For details,
see Moving the Analog Input DIP Switch to Change the Input Mode 100 .
Changing current inputs to voltage inputs
If the analog inputs are operating in DC current mode, you can move the appropriate analog input dip
switches to the voltage position to support DC voltage inputs. Carefully consider the precautions below
before proceeding. For details, see Moving the Analog Input DIP Switch to Change the Input Mode 100 .
Moving the Analog Input DIP Switch to Change the Input Mode
The procedure below describes how to move the dip switches on the back of the unit to change the
analog input mode from DC voltage mode to DC current mode, or from DC current mode to DC voltage
mode.
If you have open access to the back of the unit, where the dip switches are located, you do not need to
remove the unit from the DIN rail or the wiring from the unit to access the dip switches. In this case, skip
to step 4 in the procedure below.
If you do not have open access to the back of the unit, you will need to remove the unit from the DIN rail
and you will likely need to remove the wiring from the unit to access the dip switches. In this case, follow
the procedure below from step 1. Carefully consider the precautions below before proceeding.
To change the operating mode for an analog input
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the SCADAPack E RTU and the I/O expansion module before removing power.
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from all devices before connecting or disconnecting inputs or outputs
to any terminal or installing or removing any hardware.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Do not connect I/O devices that exceed the maximum current or voltage for an
analog input.
The maximum DC current for an analog input is 20 mA.
102 SCADAPack 535E Hardware Manual
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from all devices before connecting or disconnecting inputs or
outputs to any terminal or installing or removing any hardware.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Do not exceed the maximum voltage specified for each analog input.
Failure to follow these instructions can result in equipment damage.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The RTU or I/O expansion module must be the only loop current measurement
device in the loop when using the analog inputs in the 20 mA measurement
mode. If power to the module is removed, the module reverts to voltage mode
and results in an open current loop. Applications that cannot tolerate this
possibility need to utilize external current sense resistors with the module input
range set to voltage.
Failure to follow these instructions can result in equipment damage.
Add 250 ohm external resistors to the current loop at the terminal strip to help prevent interruption of the
current loop if the RTU or I/O expansion module is being serviced. The physical wiring of the external 250
ohm external resistors at the terminal strip is illustrated below.
104 SCADAPack 535E Hardware Manual
As illustrated below, the RTU or I/O expansion module providing the analog inputs does not need to be
the last device in the current loop.
The figure below shows loads connected to the two analog outputs.
NOTICE
106 SCADAPack 535E Hardware Manual
The analog output circuitry is configured internally to receive power from an external power supply on
pins 1 and 2 of the removable terminal block. Pin 5 (Com 1-2) and pin 2 (power input –) are connected
internally. As illustrated in the following figure, the two analog outputs are not isolated from each other,
but are isolated from the RTU logic.
SCADAPack 535E Hardware Manual 107
The analog outputs can be configured for 4...20 mA current or 0...20 mA current.
If a voltage output is required (1...5 V, for example), run the 4...20 mA or 0...20 mA signal to the device
that requires voltage input and place a 250 ohm resistor across the input terminals on the device. With
this resistor in place, the analog output is electrically isolated from the rest of the RTU, but is not
isolated from the power supply.
The table below lists resistance values and output range settings for common voltage ranges. The
resistance value listed is the parallel resistance of the device and the load resistor.
9 Configuration
The RTU can be configured:
Locally or remotely using SCADAPack E Configurator 109 , a software application that runs on a
desktop or laptop computer.
Remotely as part of an end-to-end SCADA system using the StruxureWare SCADA Expert
ClearSCADA software.
Locally using applications created in SCADAPack Workbench or ISaGRAF 3 Workbench. 111
Before you begin configuring the RTU, determine whether the SCADA Expert ClearSCADA software will
be used for any configuration tasks. This documentation assumes you are using the SCADAPack E
Configurator software to configure the RTU. For information about using the ClearSCADA software, see
the ClearSCADA documentation.
1 The SCADAPack 530E does not provide counter inputs, analog inputs or analog outputs. Add the 6601
I/O expansion module if you need these input or output types.
110 SCADAPack 535E Hardware Manual
The figure below illustrates the Ports 0-4 property page for the SCADAPack 530E and SCADAPack
535E and shows the location of the other property pages listed in the table. For details about using
SCADAPack E Configurator, refer to the SCADAPack E Configurator User Manual.
To write digital data, including digital output points, use SCADAPack Workbench RTU_BIN_WRITE I/O
devices.
To read or write data to the digital inputs or outputs in ISaGRAF 3 Workbench applications, use rtuxxdi,
rtuxxdo or rtuxxdos I/O boards.
For ISaGRAF 3 Workbench applications, use rtuxxao I/O boards to write to the analog inputs and
rtuxxaos I/O boards to read analog outputs.
More Information
Refer to the SCADAPack E Target 5 Technical Reference Manuals, ISaGRAF 3 Technical Manuals, or
the SCADAPack E Configurator User Manual for information about how to assign RTU points.
112 SCADAPack 535E Hardware Manual
10 Diagnostics
The RTU provides a number of capabilities that can help you monitor RTU operations and perform
troubleshooting tasks. They include:
LEDs that indicate the status of RTU ports and communications
Diagnostics for several aspects of RTU communications and exceptional RTU operating conditions
System points that measure internal RTU temperature and provide power supply and battery status
System points that provide communications status information
Status codes that provide information about system, communication and device status
The following topics provide an overview of the diagnostics capabilities on the RTU:
LEDs 113
Accessing Diagnostics 116
Startup Diagnostics 118
Internal Temperature Reading 119
Power Supply and Battery Status 120
Communication Statistics 121
Status Codes 122
SCADAPack 535E Hardware Manual 113
10.1 LEDs
The front panel for the SCADAPack 530E and SCADAPack 535E provides 16 LEDs to indicate hardware
status. The figure below shows the RTU front panel LEDs.
In addition to the front panel LEDs, the serial and Ethernet ports and the digital inputs and outputs on
the RTU include LEDs to indicate status. The following table describes the LEDs on the SCADAPack
530E and SCADAPack 535E.
General Power Green Lit when correct voltage is applied to the power
terminals. Does not indicate whether the CPU is
running.
Force Red Lit when an I/O point is being forced into a state that
does not represent its actual state. This typically
114 SCADAPack 535E Hardware Manual
Input and Digital input Green Lit when the digital input is active.
Output Blinks when pulses are applied if the digital input is
configured to be a counter (SCADAPack 535E only).
USB Host Status Green This LED is under the control of Binary System Point
50753. It can be controlled by a SCADAPack
Workbench or ISaGRAF 3 Workbench application or
through protocol control commands.
Modem1 TxD Green Lit when the (optional) cellular modem is transmitting
data.
Link Green Lit when the (optional) cellular modem has an active
network connection.
Serial1 and CTS Green Lit when the CTS input is active on the port.
Serial2
DCD Green Lit when the DCD input is active on this serial port.
Left side of the Green Blinks when the port is transmitting data over the
physical port RS232 serial connection.
Right side of Green Blinks when the port is receiving data over the RS232
the physical serial connection.
port
Serial3 and Left side of the Green Blinks when data is being transmitted over the
Serial4 physical port RS232 or RS485 serial connection.
Right side of Green Blinks when data is being received over the RS232 or
the physical RS485 serial connection.
port
If the port is configured for RS485, the LEDs on the
empty port indicate that data is being received over
the wired RS485 connection.
To Access Diagnostics
Use a command line in a diagnostic display session to query the RTU's operational status. The
commands available are detailed in the SCADAPack E Operational Reference Manual.
There are three main ways to access command line diagnostics:
Using an ASCII terminal connected to any RTU serial port configured for the Cmd Line function. This
is the method used to display startup diagnostics. For details, see Startup Diagnostics 118 . To access
a diagnostic display session, use the DIAG command as described in the SCADAPack E Operational
Reference manual.
Using an ASCII terminal connected to any RTU serial port configured for the ISaGRAF function.
Enable the SCADAPack Workbench or ISaGRAF 3 Workbench functionality to enter command line
mode through an ISaGRAF port. To access the command line, press the Enter key three times. To
return to SCADAPack Workbench or ISaGRAF 3 Workbench debugging mode, type the BYE
command.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The BYE command should be issued prior to disconnecting the ASCII terminal for
correct SCADAPack Workbench or ISaGRAF 3 Workbench operation.
Failure to follow these instructions can result in equipment damage.
Using Telnet over TCP/IP links. Multiple Telnet sessions may be established with the RTU on the
same TCP/IP interface, or multiple sessions may be simultaneously established on multiple TCP/IP
interfaces.
SCADAPack 535E Hardware Manual 117
Where a direct serial connection or Telnet is not available, diagnostics can be directed to an RTU file.
This is achieved using the FILEDIAG command described in the SCADAPack E Operational Reference
Manual. This diagnostics log file can then be retrieved for analysis using DNP3 file transfer.
You can also use the Transfer > Remote Command Line menu option in SCADAPack E Configurator
to access the command line interface for remote SCADAPack ES units through a virtual terminal window
over DNP3 links. The RTU does not need to be configured with a Cmd Line or ISaGRAF port to access
this functionality.
118 SCADAPack 535E Hardware Manual
Internal Temperature oC
Analog System Point 50062
This analog system point measures the ambient temperature at the controller board in degrees Celsius.
It is useful for measuring the operating environment of the controller board and returns an integer value in
the range –40°C to 75°C. Temperatures outside this range cannot be measured.
Use the system point directly by defining an analog system point with the point number 50062 in the
RTU points database.
Read the system point into a user-created SCADAPack Workbench or ISaGRAF 3 Workbench
application as an Integer or Real variable from an input board connection.
Internal Temperature oF
Analog System Point 50063
This analog system point measures the ambient temperature at the controller board in degrees
Fahrenheit. It is useful for measuring the operating environment of the controller board and returns an
integer value in the range –40°F to 167°F. Temperatures outside this range cannot be measured.
Use the system point directly by assigning an analog system point with the point number 50063 in
the RTU points database
Read the system point into a user-created SCADAPack Workbench or ISaGRAF 3 Workbench
application as an Integer or Real variable from an input board.
120 SCADAPack 535E Hardware Manual
Use the system point directly by assigning a binary point to this point number (50206) in the RTU
database.
For SCADAPack Workbench and ISaGRAF 3 Workbench applications, read the status point through
an input board connection.
Use the system point directly by assigning a binary point to this point number (50207) in the RTU
database.
For SCADAPack Workbench and ISaGRAF 3 Workbench applications, read the status point through
an input board connection.
SCADAPack 535E Hardware Manual 121
SCADAPack E RTUs provide system status codes through analog system points. The latest status is
retained as the value of the system status. DNP3 event reporting may be configured for the system
status point to provide a time-stamped history of status codes.
User-defined status codes may be generated through SCADAPack Workbench or ISaGRAF 3
Workbench using the RTUPARAM function block with the SYS_ERR_CODE parameter.
The status of SCADAPack Workbench and ISaGRAF 3 Workbench applications are reported:
To the SCADAPack Workbench or ISaGRAF 3 Workbench Debugger if connected locally or
remotely
Through the SCADAPack E System Error Point
Through a SCADAPack E diagnostic display session
1-100 ISaGRAF Target Status See the SCADAPack E ISaGRAF Technical Reference
Manual and the SCADAPack E Target 5 Technical
Reference Manual.
100-999 User Defined Status For SCADAPack Workbench, see the RTUPARAM
function block in the SCADAPack E Target 5 Function
Block Reference Manual.
For ISaGRAF 3 Workbench, see the RTUPARAM function
block in the ISaGRAF Function Blocks Reference Manual.
1001-1009 ISaGRAF Application Load Did not load SCADAPack Workbench or ISaGRAF 3
Status Workbench application files or memory application for
targets.
1030-1039 Event & Trend Status Event storage threshold status codes.
3000-3099 Extended Status Additional configuration file and firmware update status
codes.
124 SCADAPack 535E Hardware Manual
For details about SCADAPack E system status codes, see the SCADAPack E Operational Reference
Manual.
SCADAPack 535E Hardware Manual 125
TCP/IP Status
TCP/IP communication and configuration status is reported by the RTU through a diagnostic display
session as TCP/IP diagnostic information. These status codes are also reported through the
SCADAPack Workbench or ISaGRAF Workbench TCP/IP function blocks in the output STATUS
variable.
TCP/IP status is reported through the RTU System Error Point for incorrect TCP/IP configuration.
See the SCADAPack E TCP/IP Technical Reference Manual for a complete list of TCP/IP
communication status codes.
11 Maintenance
The following sections describe the recommended maintenance activities for the RTU:
Calibration 127
Preventive Maintenance 128
Routine Maintenance 130
Replacing the Battery 133
SCADAPack 535E Hardware Manual 127
11.1 Calibration
The RTU is electronically calibrated at the factory during the manufacturing process and after any repair
procedures.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU or the I/O expansion module before removing power.
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from the RTU before removing the RTU cover.
Remove power from the RTU before servicing.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Treat batteries with care.
Follow the manufacturers’ instructions concerning battery storage, use and
disposal.
Keep batteries clean and free from contaminants or other materials that could
short the terminals.
Connect new batteries using the correct polarity.
Replace batteries with new units of the same chemistry, capacity and make.
Observe the manufacturers’ instructions regarding disposal of batteries.
Considerable energy remains in the battery.
Failure to follow these instructions can result in equipment damage.
SCADAPack 535E Hardware Manual 129
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The electronics inside the RTU can be damaged by static electricity. If you need to
remove the RTU cover, wear an anti-static wrist strap that is connected to ground.
Failing to follow this simple step can cause intermittent or total loss of RTU
operation and will void the warranty.
Failure to follow these instructions can result in equipment damage.
130 SCADAPack 535E Hardware Manual
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU or the I/O expansion module before removing power.
Failure to follow these instructions can result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK
Remove power from the RTU before removing the RTU cover.
Remove power from the RTU before servicing.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The electronics inside the RTU can be damaged by static electricity. If you need to
remove the RTU cover, wear an anti-static wrist strap that is connected to ground.
Failing to follow this simple step can cause intermittent or total loss of RTU
operation and will void the warranty.
Failure to follow these instructions can result in equipment damage.
NOTICE
LOSS OF DATA
RTU memory contents are lost when:
The onboard RAM back-up battery goes flat.
The onboard RAM back-up battery is replaced while power to the RTU is
disconnected.
When memory contents are lost, RTU configuration information and user-created
applications must be reloaded for correct RTU operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Before replacing the onboard RAM back-up battery, save a copy of the RTU
configuration information, user-created applications, logs and other data to an
external drive so it can be reloaded when the procedure is complete.
Failure to follow these instructions can result in equipment damage.
The onboard RAM back-up battery will retain the RTU configuration for at least two years if the unit is not
powered. Replace the battery after every five years of continuous use, or earlier if necessary.
RAM back-up batteries are not rechargeable.
Cleaning
There are no special cleaning instructions for this product.
132 SCADAPack 535E Hardware Manual
Modems CR
The RAM battery status is provided on the Controller Status property page in the SCADAPack E
Configurator software. Take care not to confuse this status with an external power supply low condition.
The following procedure requires the RTU to be powered off briefly. It also requires restarting the RTU in
Cold Boot mode. As a result, the following precautions should be carefully considered before proceeding.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
RTU memory contents are lost when:
The onboard RAM back-up battery goes flat.
The onboard RAM back-up battery is replaced while power to the RTU
disconnected, as required in the procedure below.
The RTU is started in Factory Boot mode or in Cold Boot mode. Starting in Cold
Boot mode is required in the procedure below.
When memory contents are lost, RTU configuration information and user-created
applications must be reloaded for correct RTU operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
UNEXPECTED EQUIPMENT OPERATION.
Before replacing the onboard RAM back-up battery or starting the RTU in Factory
Boot mode or Cold Boot mode, save a copy of the RTU configuration information,
user-created applications, logs and other data to an external drive so it can be
reloaded when the procedure is complete.
Failure to follow these instructions can result in equipment damage.
134 SCADAPack 535E Hardware Manual
NOTICE
UNEXPECTED EQUIPMENT OPERATION
The electronics inside the RTU can be damaged by static electricity. If you need to
remove the RTU cover, wear an anti-static wrist strap that is connected to ground.
Failing to follow this simple step can cause intermittent or total loss of RTU
operation and will void the warranty.
Failure to follow these instructions can result in equipment damage.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Evaluate the operational state of the equipment being monitored or controlled by
the RTU before removing power.
Failure to follow these instructions can result in death or serious injury.
NOTICE
UNEXPECTED EQUIPMENT OPERATION
Before you install any firmware updates, check the Release Notes for the firmware
update to determine the most suitable firmware versions for the functionality you are
using and to confirm version compatibility.
Failure to follow these instructions can result in equipment damage.
For the procedures to update firmware, see the SCADAPack E Firmware Update User Manual.
12 Specifications
The following topics provide detailed hardware specifications for the RTU, its ports and its inputs and
outputs.
General 136
Power Supply 137
Controller Board 137
12.1 General
Environment -40°C … 70°C (-40°F…158°F) operating temperature when
mounted on a horizontally oriented DIN rail
-40°C … 65°C (-40°F…149°F) operating temperature when
mounted on a vertically oriented DIN rail
-40°C … 85°C (-40°F…185°F) storage temperature
5% to 95% relative humidity, non-condensing
Pollution Degree 2, Installation Category I, Indoor use
Elevation 3,000 m (9,842 ft)
Terminations 3.3 mm2 to .08 mm2 (12 AWG to 28 AWG), solid or stranded
Internal Analog Inputs Power input: 37 V full scale. Accuracy is 0.5% of full scale.
Onboard lithium battery: 4 V full scale. Accuracy is 0.5% of full scale.
5 V power supply: 6 V full scale. Accuracy is 0.5% of full scale.
3.3 V power supply: 4 V full scale. Accuracy is 0.5% of full scale
Internal Temperature Monitor Controller temperature: -40°C…75°C (-40°F...167°F)
138 SCADAPack 535E Hardware Manual
12.5 Communications
Serial1, 2 RS232 signals: TxD, RxD, CTS, RTS, DCD, DTR
I/O Bus I/O expansion module bus. The RTU supports the 6601
I/O expansion module which provides:
16 digital inputs, 8 of which have an associated counter
8 digital (relay) outputs
6 analog inputs
2 analog outputs (this option is selected when the 6601
I/O expansion module is ordered)
Maximum Modbus/TCP Server Fixed: 20
Connections
SCADAPack 535E Hardware Manual 141
I/O Board
Digital Inputs
Normal Operation Range 12…24 Vdc
Counter Inputs
Electrical Characteristics Shared with digital input channels
Frequency Up to 8 channels:
DI 1 to 4: 0...1.5 kHz
DI 5 to 8: 0...150 Hz
142 SCADAPack 535E Hardware Manual
I/O Board
Type 2 Form C SPDT relays available to the application
Separate Normally Open/Normally Closed/Common
Reporting Deviation
8 alarm limits
Under- and over-range events
Quality flags
Integer/floating point
Time-stamped events
Polled, unsolicited reporting on deviation and per alarm limit
144 SCADAPack 535E Hardware Manual
Isolation Transformer
500 Vdc maximum to RTU logic and chassis
Range 0...20 mA
4...20 mA
Voltage output may be accomplished with external
precision resistor
Status & Reporting Power missing
Temperature too high
Open loop detected
Values out of range
ADC reference check
Controls Direct Operate
Select Before Operate
Load Range 12 Vdc: 0…475 ohms
24 Vdc: 0…1075 ohms
30 Vdc: 250…1375 ohms
146 SCADAPack 535E Hardware Manual
Industrial Standards
Requirements specific to the PAC functional characteristics, immunity, robustness, and safety:
IEC/EN 61131-2
CSA 22.2 No.142 completed by CSA-E 61131-2
UL 508
Specific Countries
For Australia and New Zealand: ACMA requirements for RCM marking
For United States: FCC Part 15 Subpart B Class A
More details on certifications are available on the Schneider Electric website: www.schneider-electric.
com.