Lighting Energy Savings in Offices Using Different Control Systems and Their Real Consumption
Lighting Energy Savings in Offices Using Different Control Systems and Their Real Consumption
www.elsevier.com/locate/enbuild
Abstract
This paper compares the potential of lighting energy savings in office rooms by using different control systems, for three locations in Europe and
the four main orientations. The method is based on DAYSIM simulations to perform daylight calculations, on laboratory measurement to evaluate
precise system energy consumptions and on the implementation of a new algorithm to simulate a close-loop daylight dimming system. It appears
that the control of the electrical power in function of daylight leads to very high savings; they slightly depend on the room orientation and the
location. Savings vary from 45 to 61%. The performances of an occupancy sensor are also tested. Threshold values of occupancy rate for which
daylight dimming leads to higher gains than an occupancy control system vary between 27 and 44% depending on location and orientation. The
measurements of the energy consumption of the sensors and detectors also permit to conclude that systems with embedded DALI-compatible
ballast controllers should be abandoned in favour of a centralized DALI-compatible ballast controller or embedded analogue systems.
# 2007 Elsevier B.V. All rights reserved.
complementary electric light, for the whole year, according to energy consumption and that a daylight control system can save
the chosen time step. Secondly, the implementation of lighting up to 60%.
control systems.
2. Objectives and methodology
1.1. Evaluation of the daylight availability
The main objective of this study was to predict, by
It can be very time consuming to calculate the daylight simulation, the energy consumptions of lighting in offices
availability in a room, for a whole year. A solution to this according to different control systems. Therefore, we used
problem is to use the daylight coefficient method (DC) the simulation program DAYSIM to calculate the daylight
developed by Trengenza and Waters [8], like proposed by availability in an office room during the whole year [10].
Mardaljevic [9]. He used the software RADIANCE and found it Although DAYSIM is able to model several lighting control
accurate and faster than traditional methods. His conclusion systems, we did not use it for that part of the calculation. We
was confirmed by Reinhart and Herkel who implemented the wanted to test an individual daylight dimming control system
DC method, using RADIANCE, in a software called DAYSIM that could not be modelled in DAYSIM at that moment. We
and compared it to five other dynamic methods based on developed thus an algorithm for simulating individual daylight
RADIANCE daylight simulations [10,11]. The software dimming control systems according to a close-loop system. We
DAYSIM was validated by Reinhart and Walkenhorst by calculated then the necessary complementary artificial lighting
comparing results with measurements. The conclusion is that by implementing real consumption values of ballasts and
indoor illuminances can be modelled with comparable accuracy control systems we measured in laboratory.
for various blind settings under arbitrary sky conditions [12]. The second objective of this study was to measure the digital
controller energy consumption and to compare it with simple
1.2. Implementation of lighting control systems analog system. Indeed, nowadays, the digital addressable
lighting interface (DALI) is spreading. While its main
Some researcher have focused on the implementation of advantages are the flexibility, the independence between the
lighting control systems but made no link with the daylight luminaire control system and the electric wiring and the
modelling. Littlefair presents algorithms to quantify the savings possibility of pre-programming lighting scenes, some manu-
for various types of photoelectric and manual controls facturers have the tendency to provide one controller per
[13]. Ehrlich et al. focused on the accurate simulation of luminaire, in order to have the possibility of a standalone use
photosensor-based lighting controls in order to improve the and to facilitate the luminaire installation [23]. However, this is
comparison between such systems, their selection, placement not essential and it could induce (useless) extra energy
and commissioning [14]. Choi et al. developed a detailed consumption. With the measurements of the consumption of the
computer analysis model in order to investigate the perfor- auxiliaries, we can determine the minimum number of
mance of daylight responsive dimming systems [15]. luminaires that should be linked with one controller for the
same energy consumption as an analog system.
1.3. Link between daylight availability and lighting control This paper compares three different lighting control systems
systems installed in a single office, taking into account the real energy
consumption of auxiliary systems (electronic ballast and
Some authors worked on the link between daylight management system), the daylight availability over the year,
simulations and algorithms modelling lighting control systems. the orientation of the room and its location, in Europe. The
Li and Tsang did simulations based on a DC method using lighting controls are an individual daylight dimming system
RADIANCE and implemented a unique closed loop sensor. and an occupancy control system which can either switch off or
They compared results with measurements in a corridor and dim the light. The impact of each of these systems was
concluded that results of their method are in good agreement calculated by comparison with a simple scheduled automatic
with measurements, but they did not give any quantitative switch off system. The combination of these systems was also
energy lighting savings [16]. Clarke and Janak developed a evaluated.
method based on the conflation of the ESP-r and RADIANCE The energy consumption of the lighting systems (including
systems [17]. They concluded that optimized daylighting ballast, tube and control device) was accurately measured in
control system could save between 40 and 70% of the energy laboratory. The equipment, the methodology and the results are
consumption of artificial lighting [18]. Beside the simulations described in the first part of this paper.
of gains using daylight control systems, Mahdavi et al. focused The second part of this paper describes how accurate
on the implementation of control strategies to achieve some dynamic daylight simulations, obtained from real climatic
objective functions taking into account visual comfort and data’s and taking into account the position of the blinds, were
energetic considerations [19,20,21]. Reinhart proposed the used to predict the daylight penetration and the complementary
modelling of several lighting control systems (program electric lighting necessary to reach the set point illuminance
lightswitch) and implemented those algorithms in the DAYSIM level.
software [22]. By simulations, he concluded that a switch-off Additionally, the influence of the relative room occupancy
occupancy control system can save up to 20% of lighting (in function of the working hours) on the savings was analysed.
516 B. Roisin et al. / Energy and Buildings 40 (2008) 514–523
4.2.1. Daylight
Precise dynamic daylight simulations were made using
the software DAYSIM in order to calculate the daylight
illuminance for each daylight sensor location in the room, every
5 min, over the whole year. DAYSIM, which uses the
RADIANCE algorithm, uses hourly climatic data files in order
to calculate the illuminance according to a precise sky
modelling taking into account the sun position and the real
sky distribution [12]. Moreover, this software includes the
possibility to consider the use of shadings. Two modes to
simulate shading devices such as blinds are proposed by the
software: the simple dynamic device model or the advanced
dynamic device model. We used the simple model who models
a generic blind system that transmits 25% of diffuse daylight
and no direct sunlight compared to the case when the blinds are
retracted. This is a basic blind model that is sufficient for initial
design consideration when the type of shading control device is
still unspecified. According to this model, the blinds are
lowered when the workplane irradiance is over 50 W/m2 [22].
This value was chosen following the results of a monitoring
conducted by Reinhart and Voss [25].
Fig. 2. Electrical power as a function of relative luminous flux: (a) analog
ballast; (b) DALI-compatible ballast. 4.2.2. Artificial light
The number of luminaires and their position was calculated
that we can get the overall electrical power of the system by with DIALux. The best solution was to place four luminaires in
adding the detector power to these values (0.5 W for an analog two rows as shown in Fig. 4.
ballast, 2–2.5 W for a digital (DALI-compatible) ballast). With this configuration, the average artificial illuminance is
equal to 615 lx and the uniformity on the working plane is equal
4.2. Simulation method to 0.73. The lighting system is not too oversized, which is
important in order to compare the savings with realistic values.
The objective of this work was to evaluate the lighting
energy consumption of a typical office in different situations. 4.2.3. IDDS modelling
We create thus a theoretical office (width 3.05 m, length 6.55 m The IDDS system regulates the lamp flux in function of the
and height 3.05 m (see Fig. 3)). A window of 3.05 m 1.01 m daylight availability. At each time step t, as it works in close-
is located in one of the surfaces of the room and its sill is placed loop, the simulation of its comportment requires an iterative
at 1.01 m above the ground. This window is fitted with a double process. The goal of this modelling is to dim all the lamps
glazing of 77% visible transmittance. The room was arbitrarily adequately to obtain the set-point illuminance (500 lx) under
oriented according to the four main orientations (north, south, each sensor.
Under each sensor i, we can say that the sum of the artificial
light and the daylight must be equal to the set-point:
X
n
Edl;i ðtÞ þ t j ðtÞE j;i ¼ SP (2)
j¼1
this luminaire), Ej,i the illuminance due to the luminaire j at full the difference (1 (ti/ti1)) was less than 106. Usually, this
flux under the sensor associated to the luminaire i (this value required 10–15 iterations.
was calculated with DIALux), and SP is the set-point illumi-
nance. 4.2.4. Occupancy modelling (MDS/MDD)
The artificial light can be separated in two: the contribution To model occupancy, a 5 min time step occupancy profile
of the luminaire associated to the sensor and the contributions was generated automatically.
of the others luminaires. We can thus rewrite Eq. (2), assuming The dimming rate of each luminaire, taking into account the
di,j a term to make this separation: occupancy, is calculated by Eq. (6):
X
n
Edl;i ðtÞ þ di; j t j ðtÞE j;i þ ti ðtÞEi;i ¼ SP with di; j t i ðtÞ ¼ PðtÞton;i ðtÞ þ ð1 PðtÞÞtoff;i ðtÞ (6)
j¼1
With P(t) equal to 1 in case of presence and to 0 in case of
¼ 1 if i 6¼ j; di; j ¼ 0 if i ¼ j (3) absence, ton,i(t) the dimming rate of the luminaire i when there
We can now isolate the dimming rate of the luminaire i: is somebody in the room (1 for MDD/MDS, the value calcu-
P lated by Eq. (5) for IDDS + MDD or IDDS + MDS) and toff,i(t),
SP Edl;i ðtÞ nj¼1 di; j t j ðtÞE j;i the dimming rate of the luminaire i when there is nobody in the
t i ðtÞ ¼ (4)
Ei;i room (0 for MDS, 0.03 for MDD).
The delay between the departure of the room occupant and
We see in Eq. (4) that the dimming rate of the luminaire i the light switch off or dimming was set to 10 min.
depends on the dimming rate of the others luminaires. Thus to Beside the three tested control systems, we considered that
calculate it, we need the following iterative process. If we note k the lights are managed by a scheduled automatic shut off
the number of iterations, for each time step t, we have ti,k the system that switches off all lamps and sensors from 6 p.m. to 8
rate ti of the kth iteration: a.m. The positive impact of this scheduled shut off system is
P
SP Edl;i ðtÞ nj¼1 di; j t j;k1 ðtÞE j;i easily understandable for IDDS and MDD. It has also a positive
t i;k ðtÞ ¼ (5) impact on energy saving with the MDS control system as
Ei;i
it switches off the light sensors preventing their parasitic
At each time step t, the iteration requires an initial value of consumption during the night.
tj,0(t) chosen arbitrary between 0 and 1. In order to speed up the The results presented at Section 5.1 are based on presence in
process, the calculation takes the dimming rate of the precedent the room from 8 a.m. to 12 a.m. and from 1 p.m. to 6 p.m. In
time step as initial value. This leads to a higher convergence Section 5.2 we analyse the influence of the occupancy profile on
speed than if the initial value was chosen randomly. energy savings with MDD and MDS systems.
The algorithm will converge to the set-point for each sensor,
only if the full fluxes of the luminaires allow it. The dimming 4.2.5. Computing the energy consumption
rate values higher than 1 are indeed forbidden. It is also The year overall energy consumption can be estimated with
impossible to have values lower than the full dimming rate the results of previous parts. The relative flux (Frelat.%) in Eq. (1).
(typically 3%). The possibility of convergence and the speed can be replaced by the dimming rate of luminaires calculate with
depend thus on the size of the installation and on the number of the IDDS and/or presence modelling. Multiplying this equation
sensors. For our research, we decided to stop the iteration when by the time step of the simulation and making the sum over the
B. Roisin et al. / Energy and Buildings 40 (2008) 514–523 519
Fig. 5. Annual lighting consumption and gains for Athens. Fig. 8. Monthly consumption with and without IDDS in Athens.
520 B. Roisin et al. / Energy and Buildings 40 (2008) 514–523
than for Stockholm); the savings are higher for a low latitude We observe that, even in a north orientated office in winter,
location (Athens) but remain very high (around 50%) for a high the impact of an IDDS system is quite important (about 30% of
latitude location, regardless of the window orientation. gains). The difference in consumption between a north and
Comparing the different control systems, the IDDS system is a south-orientated room is quite small compared to the
the most interesting and leads to the highest gains in case of a consumption without IDDS. This results from the fact that in a
single office with 90% occupancy. We can possibly consider south-orientated office, the blinds are closed more often than in
installing presence detector in combination with the IDDS a north orientated office (about 20% of the working hours for
system (IDDS + MDD or IDDS + MDS) but the additional the south and 0% for the north). During some months (autumn
gains are not really significant in this case. The influence of the and winter), east and west orientations could be better than
occupancy rate is discussed later in the paper. south but north is always the worst. Over the whole year, the
If we analyse the monthly energy consumption for the three south orientation leads to highest energy gains. Note that the
locations (Figs. 8–10), we can observe the difference between difference between the monthly energy consumptions without
summer and winter. IDDS system is due to the variation in the number of working
Fig. 11. Values of presence and probability to have presence for typical workdays with a presence rate of 100, 80, 60 and 20%.
B. Roisin et al. / Energy and Buildings 40 (2008) 514–523 521
Table 1
Occupancy rate threshold from which a daylight dimming sensor leads to more
savings than a MDS or a MDD sensor
MDS MDD
Athens
North 31.5 19.5
South 27 14.5
West 28.5 16
East 28.5 16
Brussels
North 38.5 27
South 35 23
West 36 25
Fig. 12. Annual gains using a MDD/MDS system in function of the presence East 36 25
rate.
Stockholm
North 43.5 32.5
South 38 26.5
days in each month (in our study the offices are empty on West 40 29
Saturday and Sunday). For instance there are 23 working East 40.5 29.5
days in January (resulting in a consumption of 50.67 kWh)
and 20 days in February (resulting in a consumption of
44.63 kWh).
The energy gains by using an occupancy sensor are not as 3% (of full flux) and then presents a power of 11 W (10.4 W
high as those reported in literature [1,26,27]. First, this is due to from remaining flux (see Fig. 2(a) or Eq. (1)) and 0.5 W from
the fact that we consider a timer that shuts off the lights during the detector) when there is nobody in the room. With the MDS
nights and weekends, in our reference case. Secondly, in this system, when nobody is present, the only consumption is the
study we consider a room occupied the whole day except during consumption of the detector, which has a power of 0.5 W.
the lunch time. Many offices have a more variable presence However, the MDD system is interesting for landscape
resulting in higher gains using presence detection. offices as it prevents people to be placed in a bright spot,
compared to the average room illuminance, when working
5.2. Impact of the presence on the MDD and MDS system alone in the office room. It keeps a low general room
illuminance, to prevent too high contrasts between the
In this section, we analyse the annual energy consumption occupant’s working plane and the rest of the room. In single
using a MDD or MDS system with a variable presence offices the MDS control system is preferred.
schedule. The presence schedule, during working hours, was The curves allow us to evaluate the occupancy rates
automatically and randomly generated by steps of 10% from 0 threshold for which an occupancy sensor is more interesting
to 100%. For each time step, the value 0 or 1 of the presence than a daylight dimming sensor, for each location and
(P(t)—see Eq. (6)) is generated following a probabilistic orientation. These results are presented in Table 1. For example
reasoning. If there is presence at a time step t, the probability to in a south oriented building in Brussels, we observe that the
have presence at a time step t + 1 is high and decrease with MDS system is more interesting than the IDDS system when
the time; if there is absence a time t, the probability to have occupation drops below 35%. With these values, we can say
presence at time t + 1 is low and increase with the time. The that when occupancy rate in a single office is less than 27%,
values of high and low probabilities as well as the speed of the MDS is always preferable to IDDS and when occupancy rate is
increasing/decreasing depend on the presence rate. Fig. 11 greater than 44% the best solution is to use IDDS. For
shows some examples of presence schedules with their occupancy rates between these two extremes, the best system
respective probability for 20, 60, 80 and 100% of presence rate. depends on the location and the orientation.
Fig. 12 presents the energy gains, for MDD and MDS
systems as a function of the presence rate, regardless of the 5.3. Using DALI-compatible control systems
location. Firstly, we observe that the curves are not linear. This
is due to the fact that the time delay of the control system before Results presented in Sections 5.1 and 5.2 are valid for the
extinction has a greater influence for shorter presence time. analogue ballasts. Using luminaires with a digital (DALI-
Secondly, we see that the gains are not equal to 100% when compatible) ballast and an embedded controller would decrease
the presence is null. The consumption of the detectors (for the the performance of the systems. For a 2310 working hours year,
MDS) and the remaining flux (for the MDD) are responsible for the energy consumption of the controllers of the four luminaires
this fact. The advantage of using MDS compared to MDD is (18.5 kWh) should be added to the lighting consumption. It
clear; with the MDD system, for each luminaire, the tube is lit at represents only 3% of the consumption obtained with the
522 B. Roisin et al. / Energy and Buildings 40 (2008) 514–523
References [16] D.H.W. Li, E.K.W. Tsang, An analysis of measured and simulated day-
light illuminance and lighting savings in a daylight corridor, Building and
[1] J.D. Jennings, F.M. Rubinstein, D. DiBartolomeo, S.L. Blanc, Compar- Environment 40 (2005) 973–982.
ison of control options in private offices in an advanced lighting [17] J.A. Clarke, M. Janak, Simulating the thermal effects of daylight-con-
controls testbed, Journal of the Illuminating Engineering Society trolled lighting, Building Performance (BEPAC) (1) (1998).
[18] J.A. Clarke, J.W. Hand, M. Janak, Daylight performance: daylight quality
(2000).
[2] I.P. Knight, Measured energy savings due to photocell control of indivi- and control of energy consumption—Chapter in Daylight Performance of
dual luminaire, Lighting Research Technology 31 (1) (1999) 19–22. Buildings, James and James, 1999, ISBN: 1 873936 87 7.
[3] A.D. Galasiu, M.R. Atif, R.A. MacDonald, Impact of window blinds on [19] A. Mahdavi, S. Chang, V. Pal, Exploring model-based reasoning in
lighting systems control, Journal of the Illuminating Energy Society 29
daylight-linked dimming and automatic on/off lighting controls, Solar
Energy 76 (2003) 523–544. (1) (2000) 34–40.
[4] B. Brekke, E.H. Hansen, Energy saving in lighting installations by the [20] A. Mahdavi, S. Chang, A hybrid system for daylight-responsive lighting
control, in: Proceedings of the Seventh International IBPSA Conference,
utilization of daylight, in: Proceedings of the Right Light, vol. 3, 1995, pp.
Rio de Janeiro, Brazil, August 13–15, (2001), pp. 849–856.
875–886.
[5] D.H.W. Li, T.N.T. Lam, S.L. Wong, Lighting and energy performance for [21] A. Mahdavi, B. Spasojevic, K.A. Brunner, Element of a simulation-
an office using high frequency dimming control, Energy Conversion & assisted daylight-responsive illumination system control in buildings,
in: Proceedings of the Ninth International IBPSA Conference, Montréal,
Management 47 (2006) 1133–1145.
[6] D.H.W. Li, J.C. Lam, Evaluation of lighting performance in office Canada, August 15–18, (2005), pp. 693–700.
buildings with daylighting controls, Energy and Buildings 33 (2001) [22] C.F. Reinhart, Lightswitch-2002: a model for manual and automated
793–803. control of electric lighting and blinds, Solar Energy 77 (2004) 15–28.
[23] DALI AG of Zvei, Division Luminaires, DALI Manual. AG DALI,
[7] S. Onaygil, Ö. Güler, Determination of the energy saving by daylight
responsive lighting control systems with an example from Istanbul, Frankfurt am Main Richard Pflaum Verlag, 2001.
Building and Environment 38 (2003) 973–977. [24] www.etaplighting.com.
[8] P.R. Trengenza, I.M. Waters, Daylight coefficients, Lighting Research & [25] C.F. Reinhart, K. Voss, Monitoring manual control of electric lighting and
blinds, Lighting Research & Technology 35 (3) (2003) 243–260.
Technology 15 (2) (1983) 65–71.
[9] J. Mardaljevic, Simulation of annual daylighting profiles for internal [26] W. Morrow, B. Rutledge, D. Maniccia, M. Rea, High performance lighting
illuminance, Lighting Research & Technology 32 (3) (2000) 111–118. controls in private offices: a field study of user behavior and preference, in:
World Workplace ’98 Proceedings, International Facilities Management
[10] C.F. Reinhart, S. Herkel, The simulation of annual daylight illuminance
distributions—a state-of-the-art comparison of six RADIANCE-based Association, Chicago, IL, 1998.
methods, Energy and Buildings 32 (2000) 167–187. [27] B. VonNieda, D. Maniccia, A. Tweed, An analysis of the energy and cost
[11] C.F. Reinhart, Daylight availability and manual lighting control in office savings potential of occupancy sensors for commercial lighting systems,
in: Illuminating Engineering Society of North America 2000 Annual
buildings—simulation studies and analysis of measurement, PhD Thesis,
Fraunhofer Institut Solar Energiesysteme, 2001. Conference: Proceedings, IESNA, New York, 2000, pp. 433–459.
[12] C.F. Reinhart, O. Walkenhorst, Validation of dynamic RADIANCE-based [28] A.D. Galasiu, J.A. Veitch, Occupant preference and satisfaction with the
daylight simulations for a test office with external blinds, Energy and luminous environment and control system in daylit offices: a literature
review, Energy and Buildings 38 (2006) 728–735.
Buildings 33 (2001) 683–697.
[13] P.J. Littlefair, Predicting lighting energy use under daylight linked [29] C.F. Reinhart, M. Morrison, F. Dubrous, The lightswitch wizard—reliable
lighting controls, Building Research & Information 26 (4) (1998) daylight simulations for initial design investigation, in: Proceedings of the
Buildings Simulation, vol. III, Eindhoven, The Netherlands, August 11–
208–222.
[14] C. Ehrlich, K. Papamichael, J. Lai, K. Revzan, A method for simulating 14, (2003), pp. 1093–1100.
the performance of photosensor-based lighting controls, Energy and [30] O. Walkenhorst, J. Luther, C.F. Reinhart, J. Timmer, Dynamic annual
Buildings 34 (2002) 883–889. daylight simulation based on one-hour and one-minute means of irradi-
ance data, Solar Energy 72 (2) (2002) 385–395.
[15] A.-S. Choi, K.-D. Song, Y.-S. Kim, The characteristics of photosensors
and electronic dimming ballasts in daylight responsive dimming systems, [31] A. Skartveit, J.A. Olseth, The probability density and autocorrelation of
Building and Environment 40 (2005) 39–50. short-term global and beam irradiance, Solar Energy 49 (6) (1999) 477–487.