UniGear Catalogue
UniGear Catalogue
UniGear Catalogue
ABB is a global leader in Power and Automation ABB manufacturing facilities conform to the highest
technologies that enable utility and industry quality standards and environment norms. The
customers to improve performance while lowering facilities are ISO 9001 and ISO 14001 compliant and
environmental impact. The ABB Group of certified by leading international authorities.
companies operates in around 100 countries.
Advantage ABB
2 ABB
UniGear: an innovative solution for all installation requirements
Salient Features
• Metal-clad, four-sided internal arc-proof
construction (IAC AFLR)
Vacuum Circuit-breaker -
• Designed in conformance with the highest in Floor-rolling version
• Circuit-breaker for all fields of application
class for minimum Loss of Service Continuity -
• Vacuum Interrupters, using radial magnetic
'LSC-2B with metallic partitions' field contact system, rotate arc column
over the complete contact periphery to
• Constructed with pre-galvanized sheets without give the best current-interruption
welding points, making it the most reliable performance at all current values
switchgear in its range • Epoxy resin poles for greater protection
of the interrupters
• REF542 and other high-end communicable relays
offer intelligent solutions for all installation
requirements
• It is virtually maintenance-free and all circuit-
breaker operations can be carried out with the
door closed
Vacuum Circuit-breaker
• Earthing-switch is provided as an option. It is with magnetic drive
rated for full making capacity and is provided • The magnetic actuator is a bi-stable
with safe and reliable position indicators system with electromagnetic coils for
driving the armature and permanent
• All compartments can be accessed from the magnet for latching on to the end positions
front, hence the switchgear can be placed • All functions like charging, switching,
controlling and self-diagnostics are carried
against the wall out from an integrated electronic controller
• The switchgear is provided with conventional or • Equipped with multivoltage feeder in direct
and alternating current
integrated protection and measurement systems
• It is fitted with conventional instrument
transformers or new generation sensors
Vacuum Contactors
• Optimal solution for motor and
transformer switching and switching of
capacitor bank for power-factor control
• Fitted with medium voltage fuses according
to DIN and BS Standards
• Availability of operating mechanisms with
electric or mechanical latching functions
• Equipped with multivoltage feeder in direct
and alternating current
ABB 3
UniGear with single busbar system
Typical unit cross-section - Cassette version Typical unit cross-section - Floor-rolling version
Height with exhaust duct
Height
4 ABB
UniGear with single busbar system
Electrical characteristics
Rated voltage kV 7.2 12 17.5 24
ABB 5
UniGear with double busbar system
The double busbar system switchgear is based on – balance of the outgoing units under normal
two different schemes: service conditions
– two busbar systems, two line-side isolators and a – flexibility during the inspection and maintenance
circuit-breaker (actual system) procedures without interruption of the load
– two busbar systems, two circuit-breaker units – possibility of extension without turning the
with one or two circuit-breakers (duplex system). switchgear off.
The schemes offer redundancy of the busbar system The switchgear offers:
with physical isolation between the systems. The use
Line with double isolation up to 2500 A
of this switchgear may be necessary in the case of:
3150 A and 4000 A duplex line
– switch incoming units with unsynchronised circuit-
breakers Segregated busbar and isolation compartments
– disconnection of loads with different levels of Earthing switch with making capacity
importance under emergency conditions
Operations can be carried out from the front
– isolation of particular outgoing units from the
normal network Reliable and uninterrupted service conditions
Height
Rated frequency Hz 50-60 50-60 50-60
Rated short time kA 3s ...31.5 ...31.5 ...25
withstand current
Peak current kA ...80 ...80 ...63
Internal arc withstand current kA 1s ...31.5 ...31.5 ...25
Main busbar rated current A 1250...4000 1250...4000 1250...2500 Depth
Width
Branch connection rated current A 630...3150 630...3150 630...2000 A Apparatus C Feeder
Branch connection rated current A 3600...4000 3600...4000 – B1 Busbar 1 D Instruments
with forced ventilation B2 Busbar 2 E Gas exhaust duct
Width: 650/800/1000 Depth: 2021mm Height: 2075 mm
Single-line diagram of the main typical units
6 ABB
UniGear type ZVC switchgear for motor switching and control
Height
Internal arc withstand current kA 1s …40 …40 A A
kA 0.5s …50 …50
Main busbar rated current A …4000 …4000
Branch connection rated current A 400 400
Depth
1 2
Width
A Apparatus D Instruments
B Main busbar E Gas exhaust duct
C Feeder
3 Off Width - 325 mm Height - 2200 mm Depth - 1125 mm
Standard components
Accessories
Alternative solutions
ABB 7
ABB Limited operates a process of continuous
product development. We therefore reserve the
right to change designs, dimensions and data
without prior notice.