EL3024 - 4-Channel Analog Input Terminal 4 20 Ma, Differential Input, 12 Bit

The EL3024 is a 4-channel analog input terminal that handles signals in the range of 4 to 20 mA with 12-bit resolution. Each channel has a differential input and common ground potential. It detects overloads and broken wires and indicates their status via LEDs. The terminal receives power from the E-bus and transmits data in an electrically isolated form to a higher-level automation device.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
174 views1 page

EL3024 - 4-Channel Analog Input Terminal 4 20 Ma, Differential Input, 12 Bit

The EL3024 is a 4-channel analog input terminal that handles signals in the range of 4 to 20 mA with 12-bit resolution. Each channel has a differential input and common ground potential. It detects overloads and broken wires and indicates their status via LEDs. The terminal receives power from the E-bus and transmits data in an electrically isolated form to a higher-level automation device.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Analog input EL3024

Run LED Run LED


Error LED1 Error LED2
Run LED Run LED
Error LED3 Error LED 4

+Input 1 +Input 2

-Input 1 -Input 2
Power contact
+24 V

+Input 3 +Input 4
Power contact 0 V

-Input 3 -Input 4

Top view Contact assembly

EL3024 | 4-channel analog input terminal 4…20 mA,


differential input, 12 bit
The EL3024 analog input terminal handles signals in the range from 4 to 20 mA. The current is digitised to a resolution of 12 bits and is transmitted, in
an electrically isolated form, to the higher-level automation device. The input channels of the EtherCAT Terminal have differential inputs and possess a
common, internal ground potential. The EL3024 combines four channels in one housing. An open lead or overload condition are detected and the
terminal status is relayed to the controller via the E-bus. The EtherCAT Terminal indicates its signal state by means of light emitting diodes. The error
LEDs indicate an overload condition and a broken wire.

Technical data EL3024 | ES3024


Number of inputs 4 (differential)
Power supply via the E-bus
Technology differential input
Signal current 4…20 mA
Distributed clocks –
Internal resistance 85 Ω typ. + diode voltage
Input filter limit frequency 1 kHz
Common-mode voltage UCM 10 V max.
Conversion time 0.625 ms default setting, configurable
Resolution 12 bit (16 bit presentation, incl. sign)
Measuring error < ±0.3 % (relative to full scale value)
Surge voltage resistance 35 V DC
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power –
contacts
Current consumption E-bus typ. 130 mA
Bit width in the process image inputs: 16 byte
Configuration no address or configuration setting
Special features standard and compact process image, activatable FIR/IIR filters, limit value monitoring
Weight approx. 60 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Approvals CE, UL, Ex

BECKHOFF New Automation Technology We reserve the right to make technical changes.