Typical Wiring Diagram: 7310 Installation Instructions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

TYPICAL WIRING DIAGRAM DEEP SEA ELECTRONICS 053-028

7 3 1 0 I NST AL L AT I O N I N ST RU CT I O N S ISSUE 8

ACCESSING THE FRONT PANEL CONFIGURATION EDITOR

• Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset button.

• Press the Stop/Reset and Info buttons simultaneously.


• If a module security PIN has been set, the PIN number request is then
shown :

• Press , the first ‘#’ changes to ‘0’. Press (up) or (down) to adjust it to the
correct value.

• Press (right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.

• Repeat this process for the other digits of the PIN number. You can press (left) if you need to
move back to adjust one of the previous digits.

• When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.

• If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :

EDITING A PARAMETER

• Enter the editor as described above.


• Press the left or right buttons to cycle to the section you wish to view/change.
• Press the up or down buttons to select the parameter you wish to view/change within the currently
selected section.

• To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
• Press the up or down buttons to change the parameter to the required value.

• Press to save the value. The parameter ceases flashing to indicate that it has been saved.

• To exit the editor at any time, press and hold the button.

NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
Deep Sea Electronics Plc. Deep Sea Electronics inc.
Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706
security.
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708 NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to
Telephone 0845 260 8933 TOLL FREE (USA only) : Tel: 1 866 636 9703 ensure security.
Email: [email protected] Email: [email protected]
Web: www.deepseaplc.com Web: www.deepseausa.com
NOTE: More comprehensive module configuration is possible using the 7xxx series PC configuration
software. Please contact us for further details
ADJUSTABLE PARAMETERS (Configuration editor)
Front Panel Configuration Editor (continued)
Section Parameter as shown on display Factory Settings
DISPLAY Contrast 0%
Section Parameter as shown on display Factory Settings
Language English TIMERS LCD Page Timer 0h 0m 0s
LCD Page Timer 0h 0m 0s Auto Scroll Delay 0h 0m 0s
Auto Scroll Delay 0h 0m 0s Pre Heat Timer 0m 0s
Current Date and time hh:mm Crank Duration Timer 0m 0s
EDITOR Alt Config Default Config Crank Rest Timer 0m 0s
ENGINE Oil Pressure Low Shutdown 0.00bar Safety On Delay 0m 0s
Oil Pressure Low Pre Alarm 0.00bar Smoke Limiting 0m 0s
Coolant Temperature Low Warning 0ºC Smoke Limiting Off 0m 0s
Coolant Temperature High Pre Alarm 0ºC Warm Up Timer 0h 0m 0s
Coolant Temperature High Shutdown 0ºC Cool Down Timer 0h 0m 0s
Start Delay Off Load 0h 0m 0s Speed Overshoot Delay 0m 0s
Start Delay On Load 0h 0m 0s Fail To Stop Delay 0m 0s
Start Delay Mains Fail 0h 0m 0s Battery voltage Low Warning Delay 0h 0m 0s
Start Delay Telemetry 0h 0m 0s Battery Voltage High Warning Delay 0h 0m 0s
Start Delay Timer 0h 0m 0s Return Delay 0h 0m 0s
Crank Duration Timer 0m 0s Generator Transient Delay 0s
Crank Rest Timer 0m 0s Scheduler Schedule 0m 0s
Safety On Delay 0m 0s Schedule On Load 0h 0m 0s
Smoke Limiting 0m 0s Weekly, Monthly (only available when scheduler is
Schedule Period
Smoke Limiting Off 0m 0s active)
Warm Up Timer 0m 0s Schedule Time And Date Selection (1-16) Press to begin editing then up or down when
Cool Down Timer 0h 0m 0s selecting the different parameters in the scheduler.
Engine Under Speed Shutdown Active / Inactive
Engine Under Speed Shutdown 0 rpm
Engine Under Speed Warning Active / Inactive
Engine Under Speed Warning 0 rpm ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
Engine Over Speed Warning Active / Inactive
Engine Over Speed Warning 0 rpm
Engine Over Speed Shutdown 0 rpm • The ‘running’ editor can be entered while the engine is running. All protections remain active if
Engine Speed Overshoot Delay 0m 0s • the engine is running while the running editor is entered.
Engine Speed Overshoot 0%
Fail To Stop Delay 0m 0s • Press and hold the button to enter the running editor.
Battery Under Voltage Warning Active / Inactive
Battery Under voltage Warning Delay 0h 0m 0s
Battery Under Voltage 0V EDITING A PARAMETER
Battery Over Voltage Warning Active / Inactive • Enter the editor as described above.
Battery Over Voltage Warning Delay
Battery Over Voltage Warning
0h 0m 0s
0V
• Press the left or right buttons to cycle to the section you wish to view/change.
Charge Alternator Failure Warning Active / Inactive • Press the up or down buttons to select the parameter you wish to view/change within the currently
Charge Alternator Failure Warning 0V selected section.
Charge Alternator Warning Delay 0h 0m 0s
Charge Alternator Failure Shutdown
Charge Alternator Failure Shutdown
Active / Inactive
• To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that
0.0 V
Charge Alternator Shutdown Delay 0h 0m 0s you are editing the value.
Droop control Active / Inactive • Press the up or down buttons to change the parameter to the required value.
Droop control 0% (Compatible engine ECUs only)
DPTC Auto Regeneration Inhibit Active / Inactive • Press to save the value. The parameter ceases flashing to indicate that it has been saved.
Fuel Usage Alarm (Running Rate) 0%-100% (If Fuel Sender configured)
Fuel Usage Alarm (Stopped Rate) 0%-100% (If Fuel Sender configured) • To exit the editor at any time, press and hold the button.
GENERATOR Generator Under Voltage Shutdown 0V
Generator Under Voltage Pre Alarm 0V
Generator Voltage Nominal 0V
Generator Over Voltage Pre Alarm
Generator Over Voltage Shutdown
0V ADJUSTABLE PARAMETERS (Running editor)
0V
Generator Under Frequency Shutdown 0 Hz Section Parameter as shown on display Factory Settings
Generator Under Frequency Pre Alarm 0 Hz DISPLAY Contrast 53%
Generator Frequency Nominal 0 Hz Language English
Generator Over Frequency Pre Alarm 0 Hz ENGINE Manual Frequency Trim (Electronic engines only) 0.0Hz
Generator Over Frequency Shutdown 0 Hz
Full Load Rating 0A
KW Overload Trip 0%
Delayed Over Current Active / Inactive
Delayed Over Current 0%
DIMENSIONS AND MOUNTING
AC System 3 Phase, 4 Wire For flat surface mounting in a Type 1 enclosure to meet UL requirements
CT Primary 0A
CT Secondary 0A
Earth CT Primary 0A DIMENSIONS PANEL CUTOUT:
Earth Fault Trip Active / Inactive 240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”) 220mm x 160mm (8.7” x 6.3”)
Earth Fault Trip 0%
Generator Transient Delay 0s