Test Switch PDF
Test Switch PDF
LSP0262.eps
Fig. 1
7XV72 test switch
Application Construction
The test switch serves in the The test switch 7XV72 is hous-
testing of protection devices ed in a standard metal case
using the secondary injection 7XP20 size 1/6.
test sets 7VP15 (Omicron The 7XV7200-0 A00 can be or-
CMC 56) or 7VP48/49. dered for flush-mounting or
The following versions are surface-mounting case. The
available: other version is only available
in a flush-mounting case.
• For feeder protection with-
out an open starpoint, in a
surface mounting case or in Mode of operation
a flush mounting case The 7XV72 test switch serves
• For feeder protection with- for testing protection devices
out an open starpoint, and including C.T. circuits and com-
with additional contacts in a mand contacts. With the help
flush mounting case of the switches located on the
front side, the current and volt-
• For a 3-winding transformer
age inputs as well as the cir-
differential protection, in a
cuits of the protection device
flush mounting case
to be tested are interrupted
• For feeder protection with and applied to the plug-in con-
an open starpoint and inde- nector located on the front
pendent switchable trip and side.
c.t. circuits in a flush mount-
Via this plug-in connector cur-
ing case.
rents and voltages can be fed
The test device can be used by an injection test set and
with auxiliary supplies ranging the different commands and
from 24 V to 250 V DC. This indications can be tested.
makes selection between vary- The test position is indicated
ing power supply models un- by a red LED on the front side
necessary. as soon as the switch is in this
position.
Technical data
Auxiliary voltage Rated auxiliary voltage Vaux 24 V DC (-20 %) to 250 V (+15 %)
Power consumption of a lit LED
at 24 V DC appr. 150 mW
48 V DC 900 mW
60 V DC 1200 mW
110 to 250 V DC 900 mW
Cam switch Rated operating voltage VN 380 V AC
Rated operating current IN 6A
DC switching capacity
at 24 V DC 20 A
48 V DC 12 A
60 V DC 4.5 A
110 V DC 1A
220 V DC 0.4 A
Short time load capacity
for 1s 155 A
10 s 60 A
Pushbutton (only 7XV7208) Rated operating voltage VN 250 V AC
Rated operating current IN 6A
DC switching capacity
at 60 V DC 5A
110 V DC 2A
220 V DC 0.5 A
Construction
in 7XP20 1/6 surface mounting case B
(only possible in combination with a “0“ in the 7th position)
in 7XP20 1/6 flush mounting case C
Operation
Testing
VN
Trip
Reclose command
Operation
7XV72 Test switch
Testing
Test Systems
VL1
VL2
VL2
VL3
VL3
VN
VN
Trip L1
Trip L2
Trip L3
Reclose command
Reserve
Fig. 4
Operation Feeder protection
Testing
Operation
Testing
VL1
VL1
VL2
VL2
VL3
VL3
VN
VN
Trip L1
Trip L2
Trip L3
Reclose command
Reserve
VL1
VL1
VL2
VL2
Operation
Testing
e.g. “Testing”
Annunciation
L–"Testing" (red LED)
VL1
VL1
VL2
VL2
VL3
VL3
VN
VN
Operation
Testing
e.g. “Testing” Annunciation
Trip L1
Trip L2
Trip L3
Reclose command
Currier send
e.g. Annunciation voltage to protection
Fig. 8
7XV72 with housing 7XP2020-2 (for panel flush mounting)
Fig. 9
7XV72 with housing 7XP2020-1 (for panel surface mounting)
Subject to the
General Conditions of Supply The technical data, dimensions We reserve the right to adjust
and Delivery and weights are subject to the prices and shall charge the
for Products and Services of change unless otherwise stated price applying on the date of
the Electrical and Electronic on the individual pages of this delivery.
Industry and to any other catalog.
conditions agreed upon with The illustrations are for
the recipients of catalogs. reference only. A En 1.91a
In accordance with the present An export licence may however All product designations used
provisions of the German be required due to country- are trademarks or product
Export List and the US specific application and final names of Siemens AG or of
Commercial Control List, destination of the products. other suppliers.
export licences are not Relevant are the export criteria
required for the products stated in the delivery note and
listed in this catalog. in the invoice subject to a possi-
ble export and reexport licence.
Siemens online!
Responsible for
Technical contents: Bernhard Böckenfeld
Siemens AG, EV S V13, Nürnberg
General editing: Claudia Kühn-Sutiono
Siemens AG, EV BK T, Erlangen
Bereich
Energieübertragung und -verteilung
Geschäftsgebiet Sekundärsysteme
P. O. Box 48 06
D-90026 Nürnberg
Siemens Aktiengesellschaft Order-No.: E50001-K5762-A121-A1-7600
Printed in Germany
KG K 1297 3.0 10 En 100192 6101/U658