SE TEA Quick Guide How To Set Up Export Limiting Using The Fronius Smart Meter en AU
SE TEA Quick Guide How To Set Up Export Limiting Using The Fronius Smart Meter en AU
SE TEA Quick Guide How To Set Up Export Limiting Using The Fronius Smart Meter en AU
Version 1.0/2015
Fronius reserves all rights, in particular rights of reproduction, distribution and translation.
No part of this work may be reproduced in any way without the written consent of Fronius. It must not be saved, edited,
reproduced or distributed using any electrical or electronic system.
You are hereby reminded that the information published in this document, despite exercising the greatest of care in its
preparation, is subject to change and that neither the author nor Fronius can accept any legal liability
Gender-specific wording refers equally to female and male form.
The Fronius Datamanager 2.0 is able to limit the inverter output power dynamically and therefore to control and
limit the amount of energy which is export into the grid in accordance to the consumption of the loads.
The Datamanager Card 2.0 offers the following options to control the power output of the inverter:
- Modbus RTU
- Modbus TCP
- 8-bit binary input
- Dynamic Power Reduction using the Fronius Smart Meter
Therefore there are two possible ways to achieve export limiting with Fronius Inverters:
- Using the Fronius Smart Meter. Datamanager controls the inverter as a Master
- 3rd party controller issuing commands to the Datamanager.
The simplest and most cost effective way to achieve export control with Fronius inverters is to use the Fronius
Smart Meter. The meter measures the amount of energy imported or exported to the grid and the Datamanager
uses these values to calculate the appropriate output power of the inverter to limit the export to the grid.
This document describes how to set up export control using the single phase or 3-phase Fronius Smart Meter.
Feed-in path – bi-directional energy measurement. Load = Meter reading + Inverter power
Consumption path – single direction energy measurement. Load is measured directly.
Due to NET metering and the common way installations are done in Australia, in almost all cases, the Fronius
Smart Meter will be installed in the feed-in path. This is also the default setting on the Datamanager METER
tab.
/ Feed-in point
In this position the solar & the loads are in parallel. The solar is connected to the “load” side of the Fronius
Smart Meter.
Loads
PV System
Loads
1.2 Requirements
Important! The Fronius Datamanager 2.0 needs a software version of 3.5.1-2 or greater. It can be downloaded
from the Fronius Website under Solar Energy/Info & Support/Software Downloads/Software Updates or click
here: http://www.fronius.com/cps/rde/xchg/SID-1CE5A97E-8EC72008/fronius_australia/hs.xsl/25_7671.htm
For more detailed information on how to upgrade the firmware of Fronius Datamanger 2.0 please see the
Operating Instructions on the Fronius website under Solar Energy / Products / System monitoring / Datalogging
/Fronius Datamanager 2.0 or click: http://www.fronius.com/cps/rde/xbcr/SID-DBD64F5C-
18F6818F/fronius_australia/42_0426_0191_EA_388899_snapshot.pdf
2.1 Intro
Fronius Smart Meters (single phase or 3-phase) are energy meters with
ModBus RTU / RS 485 communication. It is needed for measuring the
load and energy fed into the grid.
L1
N
Please note:
/ Wiring between meter and inverter should use CAT5 or CAT6 cable (LAN cable)
/ Connection is a data line for Modbus RTU / RS485 using screw terminals on the meter
/ Maximum distance: 300 m (980 feet)
Wiring detail for 3-Phase Fronius Smart Meter 63A/3PH and Datamanager 2.0
Wiring detail for 3-Phase Fronius Smart Meter 50kA/3PH and Datamanager 2.0
Please Note:
The termination resistance must be activated for the first and last device in an RS-485 bus.
For information of how to set up the Fronius Datamanager please see the manual of the Fronius inverter or the
Fronius Datamanager (for Fronius Galvo/Symo/Primo/Eco):
http://www.fronius.com/cps/rde/xbcr/SID-DBD64F5C-
18F6818F/fronius_australia/42_0426_0191_EA_388899_snapshot.pdf
Before it is possible to enter the METER settings a service password is required. If no service password has
been set, it needs to be created first!
Go to ‘METER’ to do the
relevant settings.
Choose location.
For further explanations on feed-in path and consumption path see chapter 1.1 Location of the energy meter
Dynamic power reduction has the capability to control the inverter’s output power according to the site’s load
and the export limitation. The export limit can be set on the web interface of the Fronius Datamanager as shown
in the following picture.
Go to ‘DNO Editor’.
Once you saved your settings by selecting the in the Dynamic power reduction field, the set-up of the export
limit is completed.
If the system comprises multiple inverters, all inverters which are connected in the SolarNet ring to the
Datamanager will be equally power limited to achieve the set output limit.
For more information on the Fronius Datamanager 2.0 please see the Operating Instructions on the Fronius
website under Solar Energy / Products / System monitoring / Datalogging /Fronius Datamanager 2.0
or click: http://www.fronius.com/cps/rde/xbcr/SID-DBD64F5C-
18F6818F/fronius_australia/42_0426_0191_EA_388899_snapshot.pdf