General Data:: Inspection Testing and Secondary Injection of Differential Protection Relay Type P-632
General Data:: Inspection Testing and Secondary Injection of Differential Protection Relay Type P-632
General Data:: Inspection Testing and Secondary Injection of Differential Protection Relay Type P-632
1) - General data:
Relay secondary current IN: 5A 5A Built-in rated auxiliary voltage :(110-250)V AC/DC
Software Used: Easergy Studio Software Version: 651.00
CT ratio: HV: 400/5 A LV:1200 /5 A
4) – Transformer Data:
Transformer Data Primary Winding Secondary Winding
Voltage Rating 33 kV 11 kV
Capacity – P 16/20MVA 16/20 MVA
Load Current – In 280/350 A 840/1050 A
CT Ratio (In) 400/5A 1200/5A
Percentage Impedance (Z%) 10.66 % 10.66 %
6) Slope Test: