Service Manual
Service Manual
Service Manual
Manual Registration
Manual Registration
Number
Address of
Company
Holder
Name/Building
Street/Road
Area/region
Town/City
County/State
Post/Zip Code
Country
Telephone Number
FAX Number
E Mail Address
Amendment Record
Service Manual
Manual Serial Please enter the Manual Serial Nº
Number: for future record
Issue Issue
Amendment Amended By Date
Nº Date
1 Initial issue ć ć
Service Manual
Amendment Record
This Service manual contains information concerning the installation operation and service of the folĆ
lowing UPS
Limitations of Use
ELECTROMAGNETIC COMPATABILITY
The equipment covered by this manual complies with the requirements of the EMC DirecĆ
tive 89/336/EEC and the published technical standards. Continued compliance requires
installation in accordance with these instructions and use of manufacturer approved accesĆ
sories only.
WARNING This UPS does not incorporate automatic backĆfeed protection. A warning label must be
fitted to all external primary power isolators stating:
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
UTILITY The UPS should not be supplied from electrical power systems of the `IT'
SUPPLY (Impédance à Terre) type.
(IEC 364 Ć ELECTRICAL INSTALLATION OF BUILDINGS)
WARNING Note: Where use on `IT' systems is required an optional input isolation transformer should
be fitted.
PLEASE These products are intended for Commercial/Industrial use only, and are not suitable for
NOTE use in any life support applications.
GENERAL The UPS must be approved engineer before it is put into serĆ
vice. Failure to observe this condition will invalidate any implied warranty.
In common with other types of high power equipment, dangerous voltages are present with
the UPS and battery enclosure. The risk of contact with these voltages is minimised as the
live component parts are housed behind a hinged lockable door.
Further internal safety screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner, followĆ
ing the recommended operating procedures.
All equipment maintenance and servicing procedures involving internal access, should be
carried out by trained personnel.
The UPS is for indoor use only. It must be protected from rain or excessive moisture and
installed in a clean environment, free from flammable liquids, gasses, or corrosive subĆ
stances. Do not put drinks, plants, or any other containers holding liquids, on top of the unit.
BATTERIES Battery manufacturers supply details of the necessary precautions to be observed when
working on, or in the vicinity of, a large bank of battery cells. These precautions should be
followed at all times.
Particular attention should be paid to the recommendations concerning local environĆ
mental conditions and the provision of protective clothing, first aid and fireĆfighting facilities.
TEST EQUIPMENT
When the battery is under charge it is earthĆreferenced about its midĆpoint e.g. if the battery
is being charged at 460V the battery extremities will be =230V and Ć230V with respect to
neutral (earth). When using mains powered test equipment such as oscilloscopes in the
UPS high voltage area, always use a differential mode of operation to avoid the need to disĆ
connect the oscilloscope frame earth.
PERSONNEL
When working inside the UPS (trained personnel only) is recommended that protection be
worn to prevent eye damage, should an electric arc be struck by mishandling or severe
electrical fault.
Some of the power components are very heavy. If their removal is necessary ensure that
sufficient manpower is available, otherwise use adequate mechanical handling equipment.
When working in the general area of the UPS where high voltages are present, a second
person should be standingĆby to assist and summon help in case of accident.
Personnel Categorisation
The following definitions are given to categorise the scope, and use of this service
manual:
Operator/User
This service manual is outside the scope for use by personnel who have received instrucĆ
tion on the correct operation of the UPS controls; limited to operation of the unit circuit
breakers and the Front Control Panel; operator/users are not permitted to remove any panĆ
els which are retained by screws.
Service Personnel
This Service manual is designed for use by engineers who have received the relevant
etraining and are password authorised.
Important Symbols
Competent Personnel
The Troubleshooting section, and Service procedures contained in this manual are norĆ
mally outside the scope of personnel categorised competent; though they may be aware
of the dangers appropriate to working with hazardous voltages. A Competent engineer is
deemed to have sufficient technical skills/training to make electrical connections, install
batteries, close and open circuit breakers/fuses etc. (i.e. a qualified electrician) he is not
categorised as service personnel.
Specification
Input Voltage Range 300 ć 480Vac (330 ć 480Vac full charging capability)
Maximum Input Current at Nominal Input Voltage 18.5A 25.3A 31.7A 45.0A
Input Power Factor 0.95 (over specified load and voltage ranges)
Output Data
Nominal Output Voltage 380, 400 or 415Vac selectable
Maximum Load Crest Factor 3:1 (at full load without deĆrating)
System Data
True OnĆline double conversion, high frequency,
Topology
transformerless design
Overload Capability on Static Bypass 150% for 30 minutes, 1000% for 100 m seconds
Mechanical Data
Unit Dimensions (w x h x d) 530 x 1220 x 950 mm
Unit Shipping Weight With Standard Battery 305kg 395Kg 395kg 485kg
Design Standards
Safety EN50091Ć1Ć1
Radio Frequency Interference (RFI)
Electromagnetic Compatibility (EMC) EN50091Ć2 Class A
European Directive
Quality CE marked compliance LVD / EMC
ISO9001
3 Phase 10kVA
UPS with 1 internal set of batteries
6 9 17 35 115
(Standard configuration)
3 Phase 15kVA
UPS with 2 internal sets of batteries
9 14 24 55 157
(Standard configuration)
3 Phase 20kVA
UPS with 2 internal sets of batteries
6 9 17 39 108
(Standard configuration)
3 Phase 30kVA
UPS with 3 internal sets of batteries
6 9 17 40 110
(Standard configuration)
Table of Contents
Manual Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
Amendment Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Limitations of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Important Instructions for safe use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Personnel Categorisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi
Lockable
Door
1220
530
Normal operation
During normal operation, i.e. when the UPS input supply is present and within specification, both the
converter and inverter sections are active and the automatic byĆpass is turned on to connect the inverter
output to the critical load terminals. The battery fuseĆholder switch is also closed and the battery is thereĆ
fore permanently float charged at the d.c. terminals voltage level.
Mains Failure
If the mains has a failure or is out of tolerance the converter will be supplied from the battery, while the
Inverter will continue to operate for a period of time which depends on the load and the capacity of the
battery. If the mains supply has not returned within this time, the Inverter will go off automatically and
an alarm condition will appear on the UPS operator control panel.
Critical load will not be interrupted in the event of a drop or return of the AC power mains.
UPS fault
In the event of an inverter failure, the automatic byĆpass will automatically transfer the load onto the
mains with no interruption. In such an event, request qualified technical assistance.
The load will be transferred with no interruption if the inverter is synchronised with the mains; if this is
not the case, there will be an interruption of some milliseconds.
The intervention of the automatic byĆpass line is shown on the front panel by the yellow led on.
WARNING CAUTION: When the load is being supplied from the bypass line through the automatic byĆ
pass, it is connected directly to the mains supply and is therefore no longer protected
against mains faults.
Maintenance Bypass
A second bypass circuit contained in the UPS cabinet, identified as the 'Maintenance Bypass' line is
included to enable the reserve supply to be made available to the load while facilitating a safe working
environment for carrying out scheduled UPS system maintenance or trouble shooting. The circuit is
manually selected by the Manual Bypass Switch (3) which can be padlocked in the OFF position.
WARNING CAUTION CAUTION: If an automatic circuit breaker device is not present in the input disĆ
tribution panel, there remains a dangerous voltage at the output terminals and also on the
input terminals of the UPS module that is switched off.
Note: The load is not protected from mains aberrations when operating on the
maintenance bypass mode.
UPS Split
Bypass
Input
Link
UPS
Output
Battery UPS
1.2.2 - UPS Power Configuration
Common Bypass
The UPS is factory set to operate in the Common Bypass" configuration. Split Bypass links shown
in Figure 1-2 connect the Input Mains supply to the Reserve Input (Bypass) line creating a common
input. A separate Reserve Input is therefore not required.
Split Bypass
To configure the with a Split Bypass input, the Split Bypass links shown in Figure 1-2 are removed
by the commissioning engineer. In the Split Bypass" configuration the static bypass line is connected
by a separate power switch to a dedicated `bypass' power source which also feeds the maintenance
bypass line. Where a separate power source is not available the Reserve and Converter input supply
connections would be linked together.
With the exception of the maintenance bypass switch (3), all the isolators shown must be closed during
normal UPS operation.
Material admittance
1. Remove any packaging debris, then visually examine the UPS and battery equipment for
transit damage, both internally and externally.
Report any such damage to the shipper immediately.
2. Ascertain that the material supplied corresponds with that on the freight bill.
Identification
The equipment supplied is provided with an adhesive identification label placed on the UPS rear panel
reporting type of UPS model and power.
The cases used to transport the equipment must be unpacked as specified by the procedure stated
below.
WARNING Ensure that any lifting equipment used for moving the UPS cabinet has sufficient lifting caĆ
pacity.
Ensure that the UPS weight is within the designated surface weight loading (Kg/cm2) of any
handling equipment. See the UPS specification for weight details.
The UPS can be lifted using a fork lift. Take care when using either method not to damage
the UPS castors located on the bottom of the unit.
Clearances
Cooling air enters the module through ventilation grills located at the bottom of the cabinet and is exĆ
hausted through the fan grills located on the front panel; you must therefore allow for a minimum gap
of 170 mm behind the unit to allow adequate air flow. Clearance around the front of the equipment
should be sufficient to enable free passage of personnel with the door fully opened.
Cable entry
Cables enter the UPS cabinet from the rear.
Width mm 530
Depth mm 950
Weight:
Ventilation Ć forced
Protection grade Ć IP 20
The UPS requires connection of the power cables once it has been mechanically installed. All auxiliary
cables, whether screened or not, should be run separate from the power cables in metal conduits, or
metal ducts electrically bonded to the cabinet metalwork to which they are connected.
WARNING BEFORE CABLINGĆUP THE UPS, ENSURE THAT YOU ARE AWARE OF THE LOCATION AND
OPERATION OF THE EXTERNAL ISOLATORS THAT CONNECT THE UPS INPUT/BYPASS
SUPPLY TO THE MAINS DISTRIBUTION PANEL.
CHECK THAT THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSĆ
ARY WARNING SIGNS TO PREVENT THEIR INADVERTENT OPERATION.
The cable connection terminal block shown in Figure 2Ć1 is located at the rear of the cabinet.
1. Prepare the power cable ends and locate in the lower terminals of the terminal block.
2. Connect Input Mains to terminals 14 (U1), 15 (V1), 16 (W1) & 17 (N1).
Caution When preparing the power cables for connection, provide sufficient spare cable to allow
the UPS to be moved if necessary from it's normal operating position for servicing access.
Spare cable can be coiled beneath the unit.
3. Tighten the terminal block lower securing screws and check that each cable is secure.
4. Connected the UPS Output power cables to terminals 1 (U2), 2 (V2), 3 (W2) & 4 (N2) as
shown in Figure 2Ć1.
5. Secure the cables to the cable securing bar adjacent to the terminal block using appropriate
cable clamps.
Caution When the UPS is to be operated in the Split Bypass" configuration, the Split Bypass shortĆ
ing links must first be removed by the Commissioning Engineer before Power is applied
to the unit.
Note: The maximum cable size that can be connected to the UPS power
terminal block is 25mm 2
PE U2 V2 W2 N2 + + ć ć U3 V3 W3 N3 U1 V1 W1 N1 PE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Ground Ground
UPS Output Ext. Battery Input Reserve Input (Bypass) Input Mains
1.. Ground (ground lead for load connection) 2.. Input reserve (Bypass) phase U3
3.. Output phase U2 4.. Input reserve (Bypass) phase V3
5.. Output phase V2 6.. Input reserve (Bypass) phase W3
7.. Output phase W2 8.. Input Reserve (Bypass) Neutral N3
9.. Output Neutral N2 10.. Input Mains phase U1
11.. Battery Positive (ext. Battery input) 12.. Input Mains phase V1
13.. Battery Positive (ext. Battery input) 14.. Input Mains phase W1
15.. Battery Negative (ext. Battery input) 16.. Input Mains Neutral N1
17.. Battery Negative (ext. Battery input) 18.. Ground (Incoming ground wire from UPS
input mains connected to this terminal)
All UPS models are normally shipped with an internal battery fitted, therefore a thorough check
of the battery installation is required before applying power to the unit. The battery capacity, number of
cells and installation is dependent on the unit power rating and autonomy option ordered. A full break
down of the different battery configurations can be found in the Specification on preliminary page Ćxiii.
In addition to the standard battery fitted to the UPS extra strings may be added (to a maximum of 4) to
upgrade the battery autonomy. Full fitting instructions for the battery upgrade are included with each
kit, however this information has been also included in this section of the manual for continuity.
The UPS may also have an extended battery option to be fitted either in a separate or atĆ
tached cabinet, therefore the same basic checks apply.
Before
WARNING THE BATTERY CHAIN IS A HIGH VOLTAGE ENERGY SOURCE. WHICH CAN BE VERY DANĆ
GEROUS GIVING A POTENTIAL RISK OF SHOCK OR BURNS.
GREAT CARE SHOULD BE EXERCISED AT ALL TIMES WHEN WORKING WITH BATTERIES.
S Special care should be taken when working with the batteries associated with this
equipment.
S When connected together, the battery terminal voltage will exceed 380Vdc and is
potentially lethal.
S Eye protection should be worn to prevent injury from accidental electrical arcs.
S If a battery leaks electrolyte, or is otherwise physically damaged, it should be
placed in a container resistant to sulphuric acid and disposed of in accordance with
local regulations.
S If electrolyte comes into contact with the skin the affected area should be washed
immediately.
Note: Battery fuses are removed for transit and should only be fitted by the
commissioning engineer. The fuses can be found with the User manual, in
the document pocket on the battery safety cover.
Battery String Voltage check
1. Ensure the battery fuses are removed from the switched fuse holders.
Warning Do not fit the battery fuses into the fuse holders or close the fuse holders.
2. With a DVM set to a DC range of above 450V, check for each individual battery string
voltage. This voltage for a serviceable battery should be between +385V and +416V DC.
3. Measure the battery string voltage from the lower connecting screw of the appropriate fuse
holder and the battery ćve connection bar. As shown in Figure 2-3
4. If a voltage of less than +385V is recorded reĆcheck the battery connections and reĆtest the
string voltage.
F1 F2 F3 F4
Battery Fuses
CN1
Battery Cable
Foam Strip
Retaining
Bracket
Battery Tray
Note: When positioning the battery trays in the UPS, slight downward pressure
may be required on the front of the tray to clear the chassis metalwork at
the rear.
2. Fit the lower battery tray of 11 batteries to the lower position and secure using the battery
tray retaining bolt.
3. Fit the second battery tray of 11 batteries to the middle position and secure using the battery
tray retaining bolt.
4. Fit the upper battery tray of 10 batteries to the top position and secure using the battery tray
retaining bolt.
5. Refer to the schematic diagram (Figure ) locate the battery string interconnecting links from
the battery cable set.
6. Thread the Red +ve wire of the lower Anderson type cable connector through the
appropriate access hole and connect it to the battery fuse lower cable terminal.
Note: Fuse F1 is used for the first battery string, F2 for the second etc.
7. Thread the Black ćve wire of the top Anderson type cable connector through the appropriate
access hole and connect it to the ćve battery connection bar cable stud.
8. Connect the wiring harness connectors to the battery tray Anderson connectors.
a) CN1 to the top battery tray.
b) CN2 to the middle battery tray.
c) CN3 to the lower battery tray.
9. Secure the Anderson type battery connectors to the battery retaining bracket using the cable
ties supplied with the kit.
Warning Do not fit the battery fuses into the fuse holders or close the fuse holders.
2. With a DVM set to a DC range of above 450V, check for each individual battery string
voltage. This voltage for a serviceable battery should be between +385V and +416V DC.
3. Measure the battery string voltage from the lower connecting screw of the appropriate fuse
holder and the battery ćve connection bar. As shown in Figure 2-3
4. If a voltage of less than +385V is recorded reĆcheck the battery connections and reĆtest the
string voltage.
The preĆsettings required are only those which concern the interfaces wiring to any external devices,
i.e., personal computer, safety switch, remote panel.
A standard Relay Card is situated on the left side of the rear panel. This card is typically supĆ
plied and is factory preĆset to operate with the PC.
When the operation is through the remote indication panel, the factory will deliver the card already preset
to operate with the remote panel.
Note: If an optional second relay interface PCB is to be fitted Refer to the `Relay
Interface PCB CS0082' on Page 5Ć7 Chapter 5 `Functional Description'
for further information on Link settings.
The relay interface PCB provides two sets of volt free contacts rated at 50V 1A the PCB receives the UPS
status signals from the Display Control Logic PCB Part Nº CS0073 and is connected to CN1.
Output signals from the relay interface are made to the terminal block M1 shown in Figure 2Ć7, or from
the RS232 DB9 connector P1 (fitted to later equipment only).
WARNING Pressing the Remote EPO push button will turn the inverter off and remove power from the
load.
The mains input, bypass input and battery terminals still carry lethal voltages after pressing
the EPO switch. Do not remove cover from these parts.
Only competent personnel must remove protection panel held in place with screws.
PIN Description
1 Low Battery (N.O.)
2 T.B.D.
3 T.B.D.
4 N.C.
5 Common
6 N.C.
7 Low Battery (N.O.)
8 Mains Fail (N.O.)
9 Mains Fail (N.O.)
WARNING The UPS must be commissioned by a suitably qualified, and manufacturer approved enĆ
gineer.
Failure to ensure proper commissioning may invalidate any implied warranty.
WARNING During the commissioning procedure the UPS output terminals will become live.
If any load equipment is connected to the UPS output terminals, fully isolate it from the UPS
to ensure that no damage is caused in the extremely unlikely event of a UPS failure
WARNING During the commissioning procedure it may be necessary to power up the unit with the side
or top covers removed, in this situation exposure to potentially lethal voltages is possible
even with the input utility supply switched off.
Take great care at all times to minimise the risk of contact with live voltages, especially when
working around the battery or the dc busbar.
3.2.1 - Positioning
1. Check that the UPS has been correctly positioned with at least 150mm clear space at the
rear.
2. Check that there is sufficient space at the sides of the unit to gain access.
If no access is available the UPS input and output cabling must be of sufficient length to
allow the unit to be moved forward.
Note: If a split bypass is fitted, apply bypass mains voltage to the bypass
terminals 10 (U3), 11 (V3), 12 (W3) & 13 (N3) and duplicate the check for
the Input Mains.
General Operation:
LINK POSITION FUNCTION
OPEN Eco mode operation (bypass line preferred)
J1
CLOSED Normal operation (inverter line preferred)
OPEN Bypass frequency window 4%
J2
CLOSED Bypass frequency window 1%
OPEN Inverter output frequency 60Hz
J3
CLOSED Inverter output frequency 50Hz
The following link position set the UPS overload level relative to the UPS kVA rating. (As shown
on the factory rating plate)
Link 10kVA 20kVA 30kVA
J6 Open Closed Open
J7 Closed Open Closed
J8 Closed Closed Open
The following link position set the inverter and converter peak current limits which is dependent
on the UPS kVA rating. (as shown in the factory rating plate). Ensure that these links are set
according to the following table:
Link 10kVA 20kVA 30kVA
J9 Open Open Open
J10 Open Open Open
J11 Closed Closed Closed
J12 Closed Closed Closed
Set the correct battery current limit according to the following link chart.
Link/Ampere 1Amp 3Amps 5Amps
JP1 Open Open Closed
JP2 Open Closed Open
Links JP5 to JP10 set the capacity of the standard battery, check the battery Ah to set the corĆ
rect value as shown in the table below
Link JP10 JP9 JP8 JP7 JP6 JP5
Ah 7.2Ah 2x7.2Ah 3x7.2Ah 4x7.2Ah 38Ah 65Ah
Set the automatic battery test interval referring to the table below (it is recommanded to use
48h)
Link J4 J5 J6
Time 12Hours 24Hours 48Hours
3 4 c
Note: The following instructions refer to the controls on the UPS OPERATOR PANEL
(shown above). The user interface consits of 4 status indicator LEDs (labled 1-4),
a LCD panel and 4 control push buttons (labled a-d).
F2
F3
PE U2 V2 W2 N2 + + ć ć U3 V3 W3 N3 U1 V1 W1 N1 PE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Ground Ground
UPS Output Ext. Battery Input Reserve Input (Bypass) Input Mains
7. Check that the Inverter Output Voltage has risen to within 1% of the appropriate level (e.g. 400Vac).
If required the level of the Inverter AC can be adjusted using the Potentiometer P1 on the 3 Phase Control Logic
PCB (CS0072).
Note: Turn P1 Counter-Clock Wise (CCW) to increase the Inverter Output Voltage.
Note:Note: Use the Reserve Mains Neutral (termial 13) should be used a common
reference, therefore the scope channels should be set to differential mode.
Once the initial start up and commissioning have been completed the UPS should be functionally checked and
before connecting to the critical load.
The following procedure describes the recommended functional checks:
3.5.1 - Bypass failure test.
3.5.2 - Mains failure checks.
3.5.3 - Load Transfer Test
3.5.4 - Maintenance bypass check.
3.5.5 - Internal EPO check.
3.5.6 - External EPO (if required).
3. Using a DVM check that the output Voltage and frequency at output Terminals is correct (e.g. 400Vac and
50Hz).
Using a DVM check that the Battery Voltage at the battery Terminals is correct (405V +/- 10V).
4. Close the `MAINS INPUT' MCB (I1).
The UPS should now return to normal Operation.
Ensure that:
D The `ć UPS in Operation ć` returns to the LCD.
D The green `NORMAL' LED ( 1 ) has illuminated,
D The red `ALARM' LED ( 2 ) has extinguished,
D The yellow `BYPASS ON' LED ( 4 ) has extinguished
D The green `LOAD-on-INV' LED ( 3 ) has illuminated.
d) Select the `INVERTER ON- OFF' screen by pressing either the `BACK' (c) or `NEXT' (b) push button.
e) Confirm `INVERTER ON' function by pressing `BACK' and `NEXT' at the same time.
D A ***CONFIRMED*** message will be displayed
f) Press `CLEAR' (d) twice to return at the main screen.
7. Within approximately 20 sec. and the follow sequence should occur:
D The green `NORMAL' LED ( 1 ) has illuminated.
D The red `ALARM' LED ( 2 ) has extinguished.
D The yellow `BYPASS ON' LED ( 4 ) has extinguished.
D The green `LOAD-on-INV' LED ( 3 ) has illuminated.
Place the mechanical lock, onto the `MANUAL BYPASS' MCB.
The UPS is now in the normal operating condition with the Inverter supplying the load.
1. Press the front panel EPO push button and hold it for at least 3 seconds to confirm it.
2. All UPS functions will stop and UPS will disconnect the critical load.
Check that the following indications are seen:
D The Alarm buzzer sounds.
D The red `ALARM' LED has illuminated.
D The green `NORMAL' LED has extinguished
D The green `LOAD-on-INV' has extinguished.
D The LCD shows the alarm `EMERGENCY POWER OFF'.
To restart the UPS after an EPO, carry out the following procedure:
1. Open the `UPS OUTPUT' MCB. ( I4)
2. Open the `INTERNAL BATTERY' fused switch. ( I5 )
3. Open the `RESERVE INPUT' MCB. ( I2 )
4. Open the `MAINS INPUT' MCB. ( I1 )
D Wait until the display has de-energized.
5. Restart the UPS by following the start up procedure in chapter 3.4.
1. Press the External EPO push button and hold it for at least 3 seconds to confirm it.
2. All UPS functions will stop and UPS will disconnect the critical load.
Check that the following indications are seen:
D The Alarm buzzer sounds.
D The red `ALARM' LED has illuminated.
D The green `NORMAL' LED has extinguished
D The green `LOAD-on-INV' has extinguished.
D The LCD shows the alarm `EMERGENCY POWER OFF'.
To restart the UPS after an EPO, carry out the following procedure:
3. Open the `UPS OUTPUT' MCB. ( I4)
4. Open the `INTERNAL BATTERY' fused switch. ( I5 )
5. Open the `RESERVE INPUT' MCB. ( I2 )
6. Open the `MAINS INPUT' MCB. ( I1 )
D Wait until the display has de-energized.
7. Restart the UPS by following the start up procedure in chapter 3.4.
After calibration the following procedure can be used to activate the UPS:
I1 I2 I3 I4 I5
MAINS INPUT MCB RESERVE INPUT MCB MANUAL BYPASS MCB UPS OUTPUT MCB INTERNAL BATTERY
FUSED SWITCH
3.6.1 - LCD Messages and LED status after starting the UPS.
During the Normal Operation of the UPS LCD panel will show the following messages:
D MAINS WITHIN LIMITS.
D BYPASS LINE WITHIN LIMITS.
D BATTERY VOLTAGE WITHIN LIMITS.
D INVERTER OPERATING.
D INVERTER-BYPASS LINE SYNCHRONIZED.
D LOAD ON INVERTER.
D The `NORMAL' green LED ( 1 )and the `LOAD on INV' green LED ( 3 ) are illuminate. The buzzer alarm is off.
Note:Note: for a full explanation of the control panel LCD and LED function refere to
chapter 4.
After calibration the following procedure can be used to shutdown the UPS to a Manual bypass condition, and then
to normal operation:
1. Press the `MENU' push button (a) on the FRONT PANEL.
a) Select the `COMMAND' screen by pressing either the `BACK' (c) or `NEXT' (b) push button.
b) Confirm the `COMMAND' menu selection by pressing `BACK' and `NEXT' at the same time (i.e. ENTER).
c) Select the `SWITCH LOAD'function by pressing either `BACK' or `NEXT'.
d) Confirm `SWITCH LOAD' function by pressing `BACK' and `NEXT' at the same time.
D A *CONFIRMED* message will be displayed
2. Press `CLEAR' (d) twice to return to the main menu.
The following change-over sequence should occur, indicating that the load has been transfer to the bypass line:
D The yellow `BYPASS ON' LED ( 4 ) is illuminated
D The green`LOAD on INV' LED is extinguished.
3. To turn off the Inverter follow the procedure below:
a) Press the `MENU' push button (a) on the FRONT PANEL.
b) Select the `COMMAND' screen by pressing either the `BACK' (c) or `NEXT' (b) push button.
c) Confirm the `COMMAND' menu selection by pressing `BACK' and `NEXT' at the same time (i.e. ENTER).
d) Select the `INVERTER ON-OFF' screen by pressing either the `BACK' (c) or `NEXT' (b) push button.
e) Confirm `INVERTER OFF' function by pressing `BACK' and `NEXT' at the same time.
D A **CONFIRMED** message will be displayed
f) Press `CLEAR' twice to return at the main screen.
4. The follow sequence should occur:
a) The Alarm buzzeris activated.
b) the Red general `ALARM' red LED ( 2 ) will illuminate.
c) the Yellow `BYPASS ON' LED ( 4 ) will illuminate.
d) the Green `NORMAL' LED will extingaquish.
e) The LCD will display the following messages:
`LOAD ON BYPASS' and `INVERTER OFF'.
5. Remove the Mechanical Lock from the MANUAL BYPASS MCB ( I3 )
6. Close the. MANUAL BYPASS MCB ( I3 )
7. Open the `UPS OUTPUT' MCB ( I4 ).
8. Open the `MAINS INPUT' MCB ( I1 ).
9. Open the `RESERVE INPUT' MCB ( I2 ).
10. Open the `INTERNAL BATTERY' fused switch ( I5 ).
11. Check that the load continues to be powered from the Maintenance Bypass Mains supply while the UPS is
off.
Link
Relay UPS Function Signal Function
JP4 JP5
Mains NOT OK Closed Open
RL1 MAINS STATUS
Mains OK Open Closed
RL2 BYĆPASS ON
RL3 UPS Ć RUN No associated link
RL4 PREĆALARM
Links fitted to the PCB allow the input mains status to be set and the serial port P1 to be enabled as shown
in Table 3-2. These signals are generated on the display control logic PCB and connected to the relay
PCB at connector CN4.
Pin Link
F
Function
ti R l
Relay
Nº JP1 JP2 JP3 JP4 JP5
5 COMMON N/A Closed ć ć
3 UPS RX N/A ć Closed ć ć
2 UPS TX N/A ć ć Closed
8 MAINS MainsĆ
RL1 ć MainsĆOK
9 STATUS NOK
1
PRE ALARM RL4 ć
7
Introduction
On the front of the UPS there is a control panel, from which it is possible to easily verify the status of the UPS, battery
and alarms. The operator control panel consists in a LCD display that indicates the operational and alarm status of
the UPS and the EPO push-button that is located at the left side.
The LCD Display Panel displays textual messages and operating parameters on a LCD screen capable of showing
4 rows of 20 characters.
The displayed screen is organized in a multi-level menu system and selected by using push button located to the
right of the screen
MENU CLEAR
CLEAR
ENTER
COMMAND MODE BATTERY TEST
NEXT BACK
NEXT BACK CLEAR
SWITCH LOAD
CLEAR
NEXT BACK
ENTER
DISPLAY EVENTS EVENT HISTORY CLEAR
INVERTER ON–OFF
NEXT BACK
NEXT
CLEAR
DELETE EVENTS NEXT BACK
NEXT
CLEAR
ENTER
OPERATING LANGUAGE ITALIAN
NEXT BACK
NEXT BACK CLEAR
ENGLISH
NEXT BACK
CLEAR
CLEAR FRENCH
NEXT
From the main menu (STATUS ALARMS MENU) the User may have also access to the Input/Output measured paraĆ
meters and the internal parameters as well as the UPS temperature and the battery back-up time.
To scroll through these parameters use Next and Back Push Buttons. (see Table 4-2)
UPS in Operation
MESSAGE INTERPRETATION
The Main Input Line is present and the voltage is in
MAIN WITHIN LIMITS
the specified range
The Input Bypass Supply Line is present and the volĆ
BYPASS LINE WITHIN LIMITS
tage is within the specified tolerance
BATTERY VOLTAGE WITHIN LIMITS The Battery voltage is within specifications limits
The inverter is turned-on and behave with regularity
INVERTER OPERATING
operation
Indication of regular synchronism state between inverĆ
INVERTER ć BYPASS SYNCRONISED
ter and bypass line
LOAD ON INVERTER The load is supplied from the inverter
The load is supplied from the bypass line. This can be a
LOAD ON BYPASS temporary condition lasting for 20 sec when a fast overĆ
load occurs.
UPS in Alarm
In case of a failure in the UPS, the default screen will be replaced by the Alarm Screen. In this display the User will
have an overview on the type of malfunction occurred .A buzzer will be activated and can be cleared by pressing
CLEAR button. In this screen by pressing ENTER it will be shown a list of instruction to guide the Operator to underĆ
stand the meaning of the Alarm. The CLEAR push button allow to scroll through different messages As the alarm
condition is removed the current default screen will be displayed.
The List of possible Alarm and the associate help messages is displayed below.
ALARM MESSAGE CAUSE ACTION
Initial Start Up
Start the Inverter
INVERTER OFF Permanent Overload has been deĆ
Check Output
tected
Check Output Load and Restart
Continuos Overload on UPS OutĆ
INVERTER OVERLOAD Inverter
put
Check for Output Short-Circuit
High Transient Loads on UPS OutĆ
Check Output Load and Restart
BYPASS SWITCH LOCKED put. Inrush Load Current
Inverter
After 3 times
Check Battery
BATTERY FAILURE Battery Test not OK
Check Battery fuses
INVERTER SHUT-DOWN Battery almost flat, next to Make shut-down to the connecĆ
IMMINENT Shut-Down of inverter ted Loads
Check SCR of Bypass
One or more Phases in the Output
BYPASS SWITCH FAILURE Check Bypass external connecĆ
are missing
tions
MANUAL BYPASS ON UPS on Maintenance
Breaker is Open Check Main line Voltage and
MAIN OUT OF LIMITS
Main Input is missing Breaker position
The input phase rotation is not corĆ
BYPASS LINE OUT OF Check Bypass line Voltage
rect
LIMITS Check Phase Rotation
Input Voltage Missing
Restart the UPS
Fully switch-off the Breakers and
The Command EPO has been seĆ
EMERGENCY POWER OFF the Battery Fuse, wait till the LCD
lected
is complete switch-off then restart
the UPS
Battery Switch Open
BATTERY NOT CONNECTED
Battery Test Failed
Call Service Office, to replace the
BATTERY CHARGER FAULT
Battery Charger
Call Service Office, to replace the
HIGH BATTERY VOLTAGE LEVEL Battery Charger in Fault
Battery Charger
END OF BATTERY DISCHARGE Main is missing for long time
BACK NEXT
NEXT ALARM & STATE NEXT ALARM & STATE NEXT ALARM & STATE
DATE & TIME
MENU PREV. EVENT N–1 PREV. EVENT N–1 PREV.EVENT N–1
PREVIOUS EVENT
LAST–1 BACK MESSAGE 1 BACK MESSAGE 2 BACK MESSAGE M
BACK
NEXT
NEXT ALARM & STATE NEXT ALARM & STATE NEXT ALARM & STATE
DATE & TIME PREV. EVENT N–2 PREV. EVENT N–2 PREV.EVENT N–2
MENU PREVIOUS EVENT
LAST–2 BACK MESSAGE 1 BACK MESSAGE 2 BACK MESSAGE M
BACK
NEXT
NEXT ALARM & STATE NEXT ALARM & STATE NEXT ALARM & STATE
MENU DATE & TIME FIRST EVENT FIRST EVENT FIRST EVENT
FIRST EVENT
BACK MESSAGE 1 BACK MESSAGE 2 BACK MESSAGE M
BACK NEXT
To delete all unwanted EVENT first move in the DELETE EVENTS display, then press ENTER.
ENTER ENTER
DATE & TIME ENTER
EVENT HISTORY DELETE EVENTS EVENT
CLEAR CLEAR LAST EVENT CANCELLED
BACK CLEAR
BACK CLEAR
ENTER
DATE & TIME EVENT
MENU PREVIOUS EVENT CANCELLED
N–2
CLOCK MENU
This menu allows User to change the Date and Time setting on Hinet. To select Date or Time press first ENTER from
CLOCK menu then NEXT. When the Date or TIME are displayed the cursor will be over the last right character. To
scroll consecutive numbers use BACK and NEXT buttons, to move on the left use MENU button. Then type the whole
Date and press ENTER to confirm. If something is wrong in the Date or Time the message ERROR will be displayed
and the setting restart.
Note: These parameters are factory set and it is not recommanded to adjust them during
commissioning.
This chapter describes the principal PCB `s fitted to the UPS, there function, and configuration of the
potentiometers, test points and jumpers.
Abbreviations
The following abbreviations are used throughout.
P = potentiometer
TP = test point
JP = Jumper
The Control logic PCB integrates all the UPS'S functions, converter, inverter, static bypass. The control
is accomplished with programmable logic IC's fitted to the PCB. Their use significantly reduces the disĆ
crete components required, thus keeping any faults or problems to a minimum.
The principal circuit functions of the control logic are:
a) Feedback circuits (inverter voltage, converter voltage, static bypass voltage, inverter
output current).
b) Peak limit current detector circuits (inverter current and converter current).
c) Control logic power supply detector.
d) Overload detector.
e) UPS status and alarms generated by the UPS's PCB's.
b) J4ĆJ5 define the parameters of the inverter output voltage and DC Bus voltage.
Output V/Link J4 J5
Service close close
380 open close
400 close open
415 open open
d) J9ĆJ10ĆJ12 defines the inverter peak current limit for the appropriate UPS output rating.
e) J11 define the converter peak current limit. (normally closed for all UPS output ratings).
The auxiliary power supply is based on a flyĆback converter circuit, the source supply being the 750 volt
DC Bus. Secondary windings of the power supply transformer provide the control logic and the power
component gate drive circuits.
The auxiliary power supply generates a regulated 7. 5Vdc and l5Vdc voltage.
Adjustments to the battery threshold voltage are made from the auxiliary power supply by setting the
potientiometers P1, P2 and P3.
Link/Amper
IA 3A 5A
e
JPI open open close
JP2 open close open
d) Jumpers JP5 to JPI0 set the capacity for the installed battery, this is used for the battery
test function.
Link J4 J5 J6
Time 12 Hours 24 Hours 48 Hours
The function of UPS monitor board is to interface the UPS control and status alarm signals with the OperĆ
ator LCD Control panel Part Nº CS0075 , the Relay Interface PCB Part Nº CS0082 and the SNMP
adapter.
OPTIONAL RELAY
INTERFACE
P/N CS0082
SNMP CARD
This board has a microprocessor that manage and control the serial port, the SNMP adapter, the LCD
messages and UPS menu.
The LCD Display Panel displays textual messages and operating parameters on a LCD screen capable
of showing 4 rows of 20 characters.
The displayed screen is organized in a multi-level menu system and selected by using push button
located to the right of the screen.
LD1 illuminated indicates that the monitor board is failed and must be replaced.
BT2 is an hardware and software reset.
Links setting:
JP1 1-2 close and JP3 2-3 close are factory setting.
JP2 close disable the second remote EPO, JP2 open enable the second remote EPO.
Link
Relay UPS Function Signal Function
JP4 JP5
Mains NOT OK Closed Open
RL1 MAINS STATUS
Mains OK Open Closed
RL2 BYĆPASS ON
RL3 UPS Ć RUN No associated link
RL4 PREĆALARM
Links fitted to the PCB allow the input mains status to be set and the serial port P1 to be enabled as shown
in Table 5-2. These signals are generated on the display control logic PCB and connected to the relay
PCB at connector CN4.
Pin Link
F nction
Function Rela
Relay
Nº JP1 JP2 JP3 JP4 JP5
5 COMMON N/A Closed ć ć
3 UPS RX N/A ć Closed ć ć
2 UPS TX N/A ć ć Closed
8 MAINS MainsĆ
RL1 ć MainsĆOK
9 STATUS NOK
1
PRE ALARM RL4 ć
7
Caution When connecting an EPO switch to the relay PCB the Link JP6 must be opened.
Caution With two relay PCB's connected. Link JP1 on the display logic PCB must be opened in
addition to JP6 on the optional relay PCB, to allow the use of a Second EPO switch.
Safety The equipment contains live voltages at ALL Swiss unless externally isolated from the mains
Precautions supply, bypass supply and batteries.
When working on the UPS it is essential that the safety and precautionary notes in this manĆ
ual are read and FULLY UNDERSTOOD before touching any UPS internal component part.
The UPS utilises solidĆstate components not subjected to wear, with the only moving part the cooling
fan. Scheduled maintenance requirements, beyond ensuring that the environmental conditions remain
suitably cool and clean, are therefore minimal. However, a well documented periodic program of inspecĆ
tion and preventive maintenance, as suggested below; will ensure optimum equipment performance
and serve to detect minor malfunctions prior to them developing into a major fault.
Caution We strongly recommend that the annual maintenance is carried out by a manufacturerĆ
trained engineer who is fully aware of the hazards concerned and will carry out this proĆ
cedure, where necessary with the load connected to the maintenance bypass supply
WARNING LETHAL VOLTAGES ARE PRESENT IN THE UPS UNIT EVEN IF THE UNIT HAS BEEN
SWITCHED OFF AND ISOLATED
The following procedure is intended as a guide to carrying out an annual preventative maintenance
schedule. It is assumed that the engineer carrying out this procedure has been trained in the operation
of the UPS and is able to operate the unit in the `Maintenance Mode'.
Preliminary checks
1. Visually inspect the outside of the UPS and determine that the operating environment is
correct.
2. Carry out the checks detailed in `Weekly Checks'.
3. Determine if any abnormal faults have been previously recorded.
4. Confirm with the load user that it is safe to transfer the unit to maintenance bypass before
proceeding.
WARNING THE DC BUS VOLTAGE OF 750VDC MAY TAKE SEVERAL MINUTES TO DISCHARGE TO A
SAFE LEVEL.
13. Remove the top cover of the UPS to gain internal access to the unit.
Mechanical inspection
1. Carry out the weekly checks detailed above
2. Ensure that the UPS is totally powered down.
a) Check for input AC voltage at the rectifier input connections SKD 82/12 terminals 14, 15
& 16
b) Check for Battery voltage at the battery connection terminals 6 & 7 ćve, 8 & 9 +ve.
c) Check for AC voltage at the output terminal connections 2, 3 & 4.
d) Check for an AC voltage at the Reserve Bypass input terminal connections 10, 11 & 12.
Note: Refer to Figure 2Ć1 on page 2Ć4 for terminal connection detail.
3. Gain access to the UPS interior by removing the top cover panel.
4. Carry out a thorough examination of the UPS power components and subĆassemblies,
paying particular attention to the following:
a) Electrolytic capacitors Ċ check for signs of leakage, distortion etc.
b) Magnetic components Ċ check for signs of overheating, security of fixture and
deĆlamination.
c) Cables and connections Ċ check cables for signs of overheating.
d) Check that all printed circuit board connectors are secure.
e) Printed circuit boards Ċ check the cleanliness and integrity of the PCB's and replace if
any signs of deterioration are found.
5. Thoroughly clean inside the equipment enclosure using a vacuum cleaner and low pressure
air to remove any foreign debris.
6. Reconnect the UPS input mains power.
Power checks
1. Start the UPS following the appropriate operating procedure.
2. Carry out a calibration of the DC Bus Voltage and Inverter output voltage.
3. Connect a DVM set to DC volts to the DC bus and a second DVM set to AC volts to the UPS
output.
4. Select I1 (Input mains) to ON
a) The DC voltage will increase slowly up to 650 Vdc.
b) After 10 sec. the converter and the inverter will start regulating respectively
The DC Bus voltage to 750 Vdc ± 1%
The output inverter voltage to 400 Vac ± 1% (Assuming the UPS is set for an output of
400 Vac)
5. If the measured values are incorrect, reĆadjustment of the voltage settings can be carried out
using the potentiometers on the UPS control logic PCB Part Nº CS0072.
The batteries fitted within the UPS are valve regulated and require very little maintenance.
It is wrong to describe them as completely `maintenance free', because the batteries still require a mainĆ
tenance check, but at a significantly greater interval than the unsealed type.
The removal of the need to continually top up batteries, is a major advantage, but by removing access,
a visual examination of the cell plates, and electrolyte is impossible.
Battery condition and capacity can therefore only be determined as a complete 12V battery block.
The battery is an important component in the UPS system, as the UPS function relies on the battery
power, on failure of the input AC supply To ensure that the battery will support the UPS operation it should
be checked annually for performance.
Service life
Temperature is the major factor in determining the effective life of a battery if the battery is operating
above 200 C it will reduce the battery life. It is also important that the charge voltage is within limits. TypiĆ
cally a 5 year life battery will start to decline after 3 years in service, therefore the need for regular checks
is important.
Charge voltage
The nominal charge voltage is normally 2.25 volts per cell, multiplied by the number of cells in series.
Operation at voltages below 2.2 volts per cell, will lead to a undercharge and sulphation. Operation at
2.3 volts per cell and above, will cause overcharge and rapid positive plate corrosion. Positive plate corĆ
rosion is known to be the major life limiting component in all batteries, therefore for optimum life, battery
cell voltages must be within the range of 2.25 to 2.3 volts per cell.
The UPS has 32 x 12V batteries and is designed to operate with a float charge voltage of 432 V
DC.
Battery capacity
Battery capacity is used to define endĆofĆlife of the battery for example if the battery cannot supply 80%
it is deemed to be at the end of its effective life. For some applications 80% may be decreased to 50%
to mark the end of the batteries effective life.
Battery capacity from manufacture, usually increases slightly after 2 or 3 discharges and will be enĆ
hanced by high temperature and reduced by low temperature.
As the battery ages beyond 12 months the battery capacity will fall at a rate determined by the operating
temperature and the charge voltage. These adverse factors, will cause accelerate erosion to the positive
plate grid, reducing the effective battery capacity The life of the battery will then depend on the requireĆ
ments of the system, if the capacity of the UPS has been oversized then the load may only need 50%
of the normal duty.
In most applications, the battery is essentially on continuous float charge, and rarely will experience a
input supply failure longer than the end of the battery autonomy.
Therefore a battery in poor condition may well continue to support the load for short autonomies, but
will fail if the loss of the input AC supply exceeds 30 seconds.
It is therefore highly recommended that a battery autonomy test, is carried out as part of a regular mainĆ
tenance program.
The polarization voltage will disappear once loaded, but can lead to misleading terminal voltage
measurements.
To use the open circuit voltage of a battery as a guide to its capacity it must have been disconnected
for at least 72 hours. This measurement is taken off load and can only be used as a guide, it will not indiĆ
cate a battery with high internal resistance.
Float voltage
The float voltage of each battery connected in a series string, is determined by its impedance, relative
to other batteries. The voltage measured at each battery while on charge can give an indication to its
serviceability A battery on charge taking above the minimum float current, will have a different voltage
distribution to one that is fully charged. This measurement can therefore give an indication of the charge
of the battery however a valid voltage reading can only be obtained if the battery has been on float
charge for at least 48 hours.
For maintenance purposes, the ideal is to check the float voltage of each battery before shutting the UPS
down, if the test is carried out after shut down, the reading will not be valid until the float current normalĆ
izes back to its original level, prior to shut down.
It is recommended that a float voltage check is carried out on the unit if a battery problem is suspected,
a defective battery will normally give an abnormal terminal voltage.
WARNING RISK OF DEATH, SHOCK OR BURN. WHEN THIS BATTERY IS ASSEMBLED, IT IS A SOURCE
OF 390 VOLTS.
Caution Use extreme care to ensure that batteries are not accidentally short circuited by tools, rings,
watch straps etc.
Before tightening or making connections on battery strings, ensure the battery is isolated
from the UPS circuit and is earth free.
Should electrolyte contact the skin, wash the affected area immediately
Site testing
It is not normally possible to check the float voltage of the battery string prior to turning the UPS off, but
the float voltage may need to be checked subsequently.
Visual examination
1. After shutdown examine the batteries for the following:
a) White deposits around the terminal seals which indicate seal failure.
Replace any batteries found.
2. Check the security of the terminal connections. Examine for signs of corrosion or
overheating.
3. Inspect battery cases for distortion, splits or bulges.
a) Batteries near the end of their effective life, will exhibit bulges in the case, due to
increasing pressure of the positive plates as they grow in size.
b) Severe distortion may also be apparent, caused by the higher resistance of the corroded
plates, which tends to generate heat during charge and discharge. In turn the plastic of
the case will creep and failure of a single cell will cause the side of that cell to bulge.
c) Total end of life condition will normally cause all cells to bulge or distort.
Impedance measurement
Measurement of the battery AC impedance requires special test equipment, but gives a measure of how
the battery impedance has changed since new. Any battery that has been on continuous float charge
prior to the test, should not exhibit more than twice the new battery value.
Values in excess of this, indicate the battery is nearing the end of its effective life, while batteries exhibitĆ
ing 4 or more Swiss the new value, need immediate replacement.
This test will only look at the battery level and not the individual cell level, therefore, a cell with above
normal impedance to the others, will not be indicated.
Discharge test
The more common method of determining the capacity and serviceability of the batteries, is to carry out
a discharge test.
A suitable resistor designed to draw a current equal to the Ah size of the battery is placed across the
battery terminals. The battery terminal voltage is then monitored.
A fairly large wattage, 5 W resistor capable of taking 11A is connected across the battery terminals. After
10 minutes discharge, the battery terminal voltage should not fall below 11.2 V indicating the 50% capacĆ
ity level.
If a battery has high internal resistance and reduced capacity the terminal voltage will fall quickly.
Batteries with a capacity above 50% may continue to be used, but will reduce the autonomy of the sysĆ
tem. It is recommended that they be replaced, however batteries below 50%, should always be reĆ
placed.
When deciding to replace a battery the following must be considered, and a decision taken, to mix old
or new batteries in the series string. Adding new batteries to a series string that has been in use for more
than 18 months, may induce problems due to the difference in capacity A new undercharged battery
placed into a fully charged old string, may fail to achieve full charge. The other batteries in the string may
limit the charge current, as the older batteries may only require a charge current of some milliamps, this
may then cause the new battery to sulphate. If a new battery is fully charged before inclusion, the probĆ
lem should not arise, however the effective life of the new battery is limited to that of the originals. The
new battery may also have a higher terminal float voltage.
Replacing more than one battery may cause redistribution of the float voltages, causing over and underĆ
charging. Attempts to equalize the string by using a top charge of 2.4 volt per cell, may cause temporary
overheating and the test should only be carried out with continual monitoring.
Applying a top charge, (equalization) to a battery of unknown quality can lead to rapid overheating and
the possible release of acid fumes. Equalization on a long series string has not shown to be of any beneĆ
fit, due to the ability of the batteries to absorb the excess charge over a large number of cells. However~
equalization of a single battery introduced into a string, is effective.
Since a site visits to replace a single battery is a costly process, a point will be reached where it is more
cost effective to replace an entire battery string than to properly asses the battery condition, and carry
out single or multiple replacements. This decision has the additional advantage of enhancing the reliaĆ
bility of the system, and has the benefit of a 12 month warranty on the new battery.
If the UPS is to be transported, or stored in a powered down condition for any length of time, the internal
battery may discharge below the minimum battery voltage.
To prevent this condition occurring, remove the battery fuses and retain with the unit.
For periods of storage in excess of 12 weeks, the batteries will exceed their shelf life.
This can be prevented by operating the UPS and allowing them to reĆcharge for 24 hours.
Battery recharging is done by:
1. Connect the UPS to an input AC supply
2. Fit the battery fuses.
3. Power up the UPS and allow it to operate for 24 hours.
7.1 - Introduction
The UPS contain complex electronic control circuits which require a firm understanding,
in order to carry out comprehensive fault diagnosis and repair of the equipment. The aim of the informaĆ
tion contained in this chapter is to provide sufficient guidance to the trained service engineer, to enable
successful fault location to printed circuit board level. Once a faulty circuit board or component has been
identified, it should be replaced or returned to the nearest service centre for repair.
The troubleshooting information has been divided into the following main areas:
a) Component location and identification.
b) Diagnostic information.
c) Troubleshooting procedures.
d) Test procedures.
There is no practical way of detecting an impending UPS malfunction, as most problems do not emerge
as a gradual performance degradation. Generally the UPS will either work correctly or shut down with
or without a warning indication.
In the event of a UPS malfunction troubleshooting should be carried out methodically along the following
guide lines.
WARNING During troubleshooting it will be necessary to power up the unit with the side or top covers
removed, in this situation exposure to potentially lethal voltages is possible even with the
input utility supply switched off.
Take great care at all Swiss to minimise the risk of contact with live voltages, especially when
working around the battery or the DC bus.
3. Power down the unit, and ensure that the DC Bus Safety discharge check is carried out.
4. Gain access to the internal components follow the procedure for removing the UPS covers.
5. Check the serviceability of the UPS Fuses refer to the check list on page 7Ć12.
6. Apply power and analyse PCB LED indications.
7. Refer to the common fault identification chart on page 7Ć9 to identify possible fault
conditions.
8. Check DC converter power components. Refer to the procedures on page 7Ć19.
9. Check Inverter power components. Refer to the procedure on page 7Ć19.
Note: When checking signal levels refer to the table of typical normal values on
page 7Ć11 for comparison.
No special tools are required to service the UPS, a normal electricians tool kit will be adequate.
However, to carry out the check procedures contained in this chapter the following test equipment will
be required.
Oscilloscope.
A dual beam oscilloscope, which has the ability to sum the two channels, allowing differential voltage
measurements to be made.
For the measures points that it is needed to check it is very important to have the oscilloscope insulated
from the supply with a transformer.
A storage facility is useful but not essential.
WARNING ENSURE THAT ANY OSCILLOSCOPE USED IS RATED FOR USE ON 1000 V AND IS FITTED
WITH APROPRIATE 1000 V LEADS AND TEST PROBES.
WARNING ENSURE THAT ANY DVM USED IS RATED FOR USE ON 1000 V AND IS FITTED WITH
APROPRIATE 1000 V LEADS AND TEST PROBES.
To gain access to the UPS components the following covers must first be removed.
Note: The battery safety cover has slots on the lower edge for easy removal and
repositioning.
3. Main Switch Cover
a) Remove the four M6 retaining bolts.
b) Carefully ease the cover away from the control switches.
4. Heatsink Cover
a) Remove the four M6 retaining bolts.
a) Carefully ease the cover away from the front of the UPS.
5. Top Cover.
WARNING DANGER OF SEVERE SHOCK OR BURNS. 800V DC IS EXPOSED WHEN TOP COVER IS
REMOVED DO NOT REMOVE THE COVER UNLESS THE UPS HAS BEEN COMPLETELY
POWERED DOWN AND THE DC BUS ALLOWED TO DISCHARGE FOR 10 MINITUES
a) Ensure that the UPS has been correctly switched off and the battery fuse switches are
opened.
b) Wait for at least 10 minutes to allow the DC bus to fully discharge.
a) Carefully lift the cover from the retaining ball studs.
6. Side Panels
a) Remove the three M6 retaining screws securing each side panel at the rear of the UPS.
b) Disconnect the earth cable fitted to the top rear of each side panel, from the UPS chassis
by removing the M6 earthing bolt.
c) Push the panel forward to disengage the front locating studs and lift the panel from the
UPS.
Rear Cover Removal
7. Power Distribution Terminal Block Cover.
a) Remove the six M6 retaining screws from the terminal block cover and lift from the UPS.
Refer to Figure 7Ć2.
Side Cover
Retaining Bolts
Before starting to repair or service the UPS models, correct identification of the main compoĆ
nents and their location is required. All the main power component are mounted on the power heatsink
under the driver interface board.
The following information is primarily to furnish the repair engineer with a quick reference to the basic
component identification and location. A detailed breakdown of the equipment components and spare
parts kits available can be found in Chapter 9 Spare Parts.
Fan PCB
Part Nº 0SDE0078
Inverter SCR's (x 3)
91A (S1 S3 S5)
Part Nº 0CASR212391
Snubber Diodes
30A (CD4 CD5)
Part Nº 0CADR210230
Input SCR
Input SCR 132A (S8)
132A (S7) Part Nº 0CSSX212413
Part Nº 0CSSX212413
Thermostat
55oC (ST2)
Thermostat Part Nº 0CEX50CLSD
85oC (ST1)
Part Nº 0CEX-SONDA
Capacitor
5ìF (C5) Capacitor
Part Nº 0CPCPP505700 15ìF (C7)
Part Nº 0CPCPP615400
Saturable Inductor
Saturable Inductor
(L4)
(L3)
Part Nº 0CEXE3206203F3 (E)
Part Nº 0CEXE3206203F3 (E)
Part Nº 0CEXEPLT322033F3 (I)
Part Nº 0CEXEPLT322033F3 (I)
Relay PCB
Part Nº 0SDE0082
Fan PCB
Part Nº 0SDE0078
The following table lists all alarm conditions shown on the Operator panel LCD, the cause of the alarm,
what checks should be carried out and possible solutions.
The activation of any alarm condition will illuminate the Red ALARM LED on the OPERATOR PANEL.
The following table of values have been taken from a serviceable UPS and are intended to give a typical
reference when carrying out fault diagnosis.
TP4 (+ve) to TP5 (Ćve) 4.31V dc Converter feedback signal to U9 Level adjusted by P2.
TP6 (+ve) to TP7 (Ćve) 4.28V dc Static Switch feedback signal to U8 Level adjusted by P3.
LED LD1 (green) UPS Normal (OFF indicates an over temperature ST1, a DC offset
ON condition or PCB power failure)
R36 5.59V dc VMAX level adjustment (P1) sets battery high level 500V.
R37 7.89V dc VMIN level adjustment (P2) sets battery low level 320V.
Molex Connector PM2 Pin 1 16.83V dc +15V supply to Inv. driver feedback PCB.
Molex Connector PM2 Pin 2 7.68V dc +7.5V supply to Inv. driver feedback PCB.
Molex Connector PM2 Pin 4 15.33V dc Battery high output to Inv. driver feedback PCB.
Molex Connector PM2 Pin 5 0.616V dc Battery low output to Inv. driver feedback PCB.
Molex Connector PM2 Pin 6 15.47V dc Battery Prealarm output to Inv. driver feedback PCB.
Prior to any fault diagnosis, a serviceability check of the fuses is recommended. Failure of a fuse
can give an indication of a defective power device or component.
1. Using the list shown in Table 7Ć3 check each fuse for serviceability.
2. Determine the serviceability of any related component or PCB and repair or replace as
required.
3. Replace the fuse with a serviceable item.
4. Continue with any required fault diagnosis.
F1 1A DC+ Input
A ilia DC
Auxiliary DCĆDC
DC Co
Converter
e te PCB
F2 1A DCć Input
F5 10A Battery ć
WARNING Wait at least 10 minutes after Shutting Down the UPS before proceeding with a StartĆ
Up procedure. to allow the DC bus to fully discharge
Note: To completely isolate the UPS from the input AC supplies, the main
external input power isolator must be opened.
On the primary input utility supply distribution panel post a label advising
personnel that the UPS circuit is under maintenance.
3x3 UPS 7 - 13
Issue 2 - November 2001
Service Manual
Test Procedures
Note: The half DC bus level can also be monitored if required by connecting the
DVM across the +ve or Ćve fuse and the DC common (neutral) bus bar as
shown in Figure 7Ć7.
F2
F3
Check Secondary DC
bus between Fuse F3
& F2
765V DC
To Check Half Secondary DC bus Voltage check for 382V DC between Fuse
F3 and Neutral Bus. (a similar check can be carried out from F2)
7 - 14 3x3 UPS
Issue 2 - November 2001
Service Manual
Test Procedures
7.8.2 - DC offset
Fault indication
The output of the UPS is monitored by the Inverter Driver Feedback PCB for any DC component on the
output waveform. If the level of DC exceeds the limit of 400mV, a signal is generated and switched to
the control logic PCB. This signal is switched through the thermostat ST1 as shown below in Figure 7Ć8.
The UPS will transfer to the bypass and the red LED LD 2 on the inverter driver/feedback PCB Part Nº
OSDE0071, will illuminate. The red LED D11 on the 3ph TL control logic PCB Part Nº OSDE0072 will
extinguish. The UPS will remain on bypass until the alarm condition is reset using the Reset push switch
S1 on the PCB, or the UPS is completely powered down and restarted.
DC Offset
0 0
DC Offset
DC Offset Condition
The most likely cause of a `DC OFFSET' condition could be:
1. The UPS is supplying an unbalanced non linear load, this could be on any phase.
2. The load is drawing DC current.
A common reason for this is an input bridge rectifier on a computer power supply is
defective and only half wave rectifying its input power.
3. An inverter gate drive circuit is defective.
This could cause the inverter EIGHT's switching to be out of balance.
3x3 UPS 7 - 15
Issue 2 - November 2001
Service Manual
Test Procedures
Action
1. To determine if the DC offset problem is load related.
Replace the normal load temporarily with a resistive load and monitor the alarm condition, if
it disappears then the problem lies with the load.
2. To measure the level of DC offset present, connect the test circuit shown in Figure 7Ć9 to the
output of the UPS.
C1 C3
U3 R1 N3 R1 W3
C2
3. Measure the DC mV across each phase capacitor the nominal level should be 50mV the
maximum 400mV.
a) Measure the DC offset level with the load connected if it is out of limits then the problem
is load related.
b) Check again with no load if the DC offset level is out of limits then the problem may lie
with the UPS.
4. If the DC Offset appears to be generated by the UPS, check the voltage across D94 and D89
on the inverter driver/feedback PCB Part Nº OSDE0071.
The voltage should be equal.
5. If an unequal voltage is measured then the fault is likely to be in either the inverter gate drive
or IGBT's.
Check that the IGBT drive circuit is correct and the IGBT devices are serviceable.
6. If the circuit and IGBT checks are OK the problem points to a defective monitoring circuit in
the inverter driver/feedback PCB.
Replace the inverter driver/feedback PCB.
7. Reconnect all cables and fit any covers removed.
8. Restore the UPS to its normal running condition.
7 - 16 3x3 UPS
Issue 2 - November 2001
Service Manual
Test Procedures
1 4
3 2
8. Finally tighten the screws to the appropriate torque shown in Table 7Ć4.
Torque Nm
Pan head
Ci
Circuit
it R
Ref.
f P t Nº
Part Sems Heatsink Terminal
M4 Ć 2
IGBT Q1, Q2, Q3 (Inverter) 0CATR210415 M5 X 13FL 3 M5 Ć 3
3x3 UPS 7 - 17
Issue 2 - November 2001
Service Manual
Test Procedures
7. Disconnect the cables attached to current transformer TA1 TA2 and TA3 IGBT connection
extension pillars and lift off the CT's.
Note: An inĆsitu test for a short circuit IGBT can be carried out at this point
before the devices are removed.
8. Disconnect the gate drive fastĆon connectors from the IGBT's and note their position for
reĆassembly.
9. Remove the four retaining IGBT securing Allen screws from each IGBT and remove each
IGBT.
10. Test each IGBT for serviceability follow the IGBT test procedure on page 7Ć20.
11. Replace any components found defective.
IGBT fitting is the reverse of the removal procedure refer to Table 7-6 for correct IGBT gate drive conĆ
nector location.
Note: An inĆsitu test for a short circuit IGBT can be carried out at this point
before the devices are removed.
9. Disconnect the gate drive fastĆon connectors from the IGBT and note their position for
reĆassembly.
10. Remove the four retaining IGBT securing Allen screws and remove from IGBT from the
heatsink.
11. Carry out a test of the IGBT for serviceability follow the IGBT test procedure on page 7Ć20.
12. Replace IGBT if found defective.
IGBT fitting is the reverse of the removal procedure refer to Table 7-7 for correct IGBT gate drive conĆ
nector location.
7 - 18 3x3 UPS
Issue 2 - November 2001
Service Manual
Test Procedures
Note: A 9V PP3 battery can successfully be used as the external voltage source.
3x3 UPS 7 - 19
Issue 2 - November 2001
Service Manual
Test Procedures
6 2Ć7
Touch the +ve Battery lead to gate (base). 0.345 This will switch on the device.
[3] [2 Ć 5]
Note: Terminal connections for single pack IGBT are shown in [square brackets]
Touch the +ve Battery lead to gate (base). 4 1 0.345 This will switch on the device.
Turn off the device by shorting B1 and E1. 3 1 OL High resistance indicates the IGBT is off
Note: The DVM readings shown in the above table are typical they will vary
slightly from device to device and with the type of meter used.
7 - 20 3x3 UPS
Issue 2 - November 2001
Service Manual
Test Procedures
3x3 UPS 7 - 21
Issue 2 - November 2001
Service Manual
Test Procedures
SCR S1 S2 S3 S4 S5
S6 SEMIKRON SKKT 92/12E 91A Twin Pack 0CASR212420
Failure of a static switch or battery SCR will initiate the appropriate indication on the LED display and
will normally fail open circuit O/C or short circuit S/C. If a faulty device is suspected it can be checked
using a DVM. A short circuit across the anode cathode junction will be quickly apparent, however an
open circuit cannot so easily be diagnosed as the high resistance indicated is the normal state of the
device when turned off.
The Gate Cathode resistance can also be measured and should be in the range of 10 to 20 ohms for
a serviceable SCR, a high resistance would indicate an open circuit.
It is therefore recommended that a functional test of the SCR is carried out using the simple test circuits
shown in Figure 7Ć12 and Figure 7Ć14.
Twin Pack SCR Replacement (S1 S2 S3 S4 S5 S6)
1. Power down the UPS and carry out the DC bus discharge routine.
2. Gain access to the UPS power section by removing the top and side covers.
3. Disconnect and remove the Inverter driver/feedback PCB Part NºOSDE0071. Follow the
procedure on page 7Ć32.
4. Remove the two SCR gate drive leads from terminals 4 and 6 from each SCR and note their
position.
Note: Note SCR S6 has the gate drive leads reversed blue to 4 red to 6.
5. Remove the terminal standoffs and screws to release the bus bars from SCR terminals 1. 2
and 3.
6. Disconnect the second gate drive leads from SCR terminals 1 and 2.
7. Remove the two SCR Allen retaining screws from each SCR and lift from the Heatsink
8. Carry out the following functional test on each SCR and replace if required.
SCR fitting is the reverse of the removal procedure refer to 12. for correct SCR gate drive connector locaĆ
tion.
7 - 22 3x3 UPS
Issue 2 - November 2001
Service Manual
Test Procedures
9 volt power
source Test lamp
ćve +ve
+ve ćve
+ve ćve
+ve
ćve
To functionally test a twin pack SCR as shown in Figure 7Ć12 a DC power source and test lamp is reĆ
quired, typically a 9V PP3 battery and 12V bulb.
1. Connect the bulb and battery to SCR1 as shown, connect the +ve to the anode (1) and ćve
to the cathode (2) terminal.
2. Using a second power source or link from the battery connect the +ve lead to SCR1 gate
terminal 4 and the ćve lead gate terminal 5.
3. Switch on the SCR by briefly making the gate circuit, use a switch if available.
The SCR will fire and the bulb will light and remain on. The bulb provides a current source
for the SCR and it will continue to fire.
4. Remove the +ve connection from terminal 1.
The bulb will extinguish an the SCR will switch off.
5. Repeat the test for SCR2.
3x3 UPS 7 - 23
Issue 2 - November 2001
Service Manual
Test Procedures
Note: There is a deĆcoupling capacitor linking the heatsink from SCR mounting
screw to the neutral bus bar.
SCR S8
10. Disconnect the battery +ve cable from SCR terminal 3.
11. Disconnect red leads from R1 to SCR terminal 1 and 2.
12. Remove fuse F1 bus bar from SCR terminal 2.
13. Remove the input bridge bus bar from SCR terminal 1.
14. Remove red leads from SCR terminal 1 and 2 which connect to the fast on connectors F13
(SCR 1) and F14 (SCR 2) on the Inverter driver/feedback PCB.
15. Carry out the following functional test on each SCR and replace if required.
SCR fitting is the reverse of the removal procedure.
9 volt power
Test lamp source
+ve ćve
+ve ćve
7 - 24 3x3 UPS
Issue 2 - November 2001
Service Manual
Test Procedures
To functionally test a single SCR and diode pack as shown in Figure 7Ć12 a DC power source and test
lamp is required, typically a 9V PP3 battery and 12V bulb.
1. Connect the bulb and battery to the SCR as shown, connect the +ve to the anode (1) and
ćve to the cathode (2) terminal.
2. Using a second power source or link from the battery connect the +ve lead to the SCR gate
terminal 4 and the ćve lead gate terminal 5.
3. Switch on the SCR by briefly making the gate circuit, use a switch if available.
The SCR will fire and the bulb will light and remain on. The bulb provides a current source
for the SCR and it will continue to fire.
4. Remove the +ve connection from terminal 1.
The bulb will extinguish an the SCR will switch off.
5. Using a DVM set to the diode range check the individual diode between SCR terminal 1 and
3 for the forward and revers conditions.
3x3 UPS 7 - 25
Issue 2 - November 2001
Service Manual
Test Procedures
Amphenol Connector
connect to PM1 Rear Pin
7 - 26 3x3 UPS
Issue 2 - November 2001
Service Manual
Test Procedures
3x3 UPS 7 - 27
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
R37
(See 13.)
PM1
P3 (500Vdc)
F1
(DC +ve Input 1A)
PM2
PM2 pin 1 to 6
(See 13.)
1. Power down the UPS and carry out the DC bus discharge routine.
2. Gain access to the UPS power section by removing the top and side covers.
3. Mark all connectors before removal.
4. Disconnect Connector PM1 and PM2.
5. Release the PCB StandĆOff mounts and remover the PCB from the Unit.
Replacing the PCB
1. Replace the DC Ć DC converter PCB using the opposite sequence to the removal.
Important All replacement PCB's leave the manufacturer pre calibrated therefore no adjustment
note should be necessary.
2. Refit all covers removed and return the UPS to its normal operating condition.
7 - 28 3x3 UPS
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
7.9.2 - LCD UPS Monitor Board 0SDE0077 (PCB Label: CS0077 Exx)
J3 J2 CN1
J5
Link
JP2
J7
J6
J4
Link
JP3
Link
JP1
J1
1. Power down the UPS and carry out the DC bus discharge routine.
2. Gain access to the UPS power section by removing the top and side covers
3. Mark all connectors before removal.
4. Disconnect connectors J1; J2; J5; J6; J7 & CN1.
5. Release the PCB Stand-Off mounts and remove the PCB from the unit.
Replacing the PCB
1. Replace the UPS Monitor Board using the opposite sequence to the removal.
Important All replacement PCB's leave the manufacturer pre calibrated therefore no adjustment
note should be necessary.
2. When fitting a replacement PCB the on board links must be checked to ensure they are in
the correct position.
Link and Jumper functions
3x3 UPS 7 - 29
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
7.9.3 - Inverter Driver/Feedback Interface Part Nº 0SDE0071 (PCB Label: CS0071 Exx)
J17 N8
2 red wires
N12
black wire
LD2
DC Offset
N16
brown wire
J23 LD1
LINK J1A J2A J3A P1 P1 f Rotation
(bypass V +10%) (bypass V ć10%)
R69 R66 R149
(See 13.) (See 13.) (See 13.)
1. Power down the UPS and carry out the DC bus discharge routine.
2. Gain access to the UPS power section by removing the top and side covers.
3. Mark all connectors before removal.
4. Disconnect connectors J19, J15 and J7.
5. Disconnect SCR driver connectors J1 to J6.
6. Disconnect the inverter IGBT gate drive connectors J9, J11 and J12.
7. Disconnect the converter IGBT gate drive lead J14.
8. Disconnect the input SCR gate drive connector J16.
9. Disconnect connectors J8, J10, J13 and J18.
10. Disconnect J21.
Note: J21 connector leaves the two rear pins free on the plug when reconnecting.
7 - 30 3x3 UPS
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
14. Remove the terminal screws and wires from the static switch SCRs.
a) N7, N8 & N9 Note: N8 has two Red wires attached.
b) N11, N12 & N13 Note: N12 has a Black wire attached.
c) N15, N16 & N17 Note: N16 has a Brown wire attached.
15. Remove the PCB Earth terminal screw N20.
16. Remove the remaining PCB retaining screw from the mounting pillar and carefully lift the
PCB from the unit feeding the gate drive lead connectors through the PCB cutĆouts.
Replacing the PCB
1. Replace the Inverter Driver/Feedback PCB using the opposite sequence to the removal.
Important All replacement PCB's leave the manufacturer pre calibrated therefore no adjustment
note should be necessary.
2. When fitting a replacement PCB the on board links must be checked to ensure they are in
the correct position.
Link and Jumper functions
a) J4AĆJ5A sets the DC Bus voltage.
3. Carry out the Inverter and Converter functional test outlined on page 7-15.
Bypass Voltage Threshold Adjustment
a) P1 = adjusts the maximum bypass voltage threshold (+10%)
b) P2 = adjusts the minimum bypass voltage threshold (Ć10%)
4. Refit all covers removed and return the UPS to its normal operating condition.
3x3 UPS 7 - 31
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
7.9.4 - 3ph TL Control Logic Part Nº 0SDE0072 * (PCB Label: CS0072 Exx)
Link TP11 TP14 Link TP30 to C30 TP12 TP9 TP10
J8 J7 J6 (See 13.) (Ref. test on page 7-27) (See 13.)
CN1 CN1
Link
J1 to J5
CN1
LD1
AC Power ON
Link
J9 J10
U7
(EPROM)
Link
J11 J12
CN1
P2
(Conv. output V adj.)
Note: * This PCB must be replaced with one of the same power rating as the UPS.
1. Power down the UPS and carry out the DC bus discharge routine.
2. Gain access to the UPS power section by removing the top and side covers.
3. Mark all connectors before removal.
4. Note the position of the shorting links fitted to the PCB
5. Disconnect connectors CN2, CN4 and CN5.
6. Release the PCB StandĆOff mounts and remove the PCB from the Unit.
Replacing the PCB
1. Replace the Control Logic PCB using the opposite sequence to the removal.
Important All replacement PCB's leave the manufacturer pre calibrated therefore no adjustment
note should be necessary.
2. When fitting a replacement PCB the on board links must be checked to ensure they are in
the correct position.
7 - 32 3x3 UPS
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
J1 OnĆLine OffĆline
J3 50Hz 60Hz
b) J4ĆJ5 define the parameters of the inverter output voltage and DC Bus voltage.
Output V/Link J4 J5
d) J9ĆJ10ĆJ12 defines the inverter peak current limit for the appropriate UPS output rating.
e) J11 define the converter peak current limit. (normally closed for all UPS output ratings).
3. Carry out the Inverter and Converter functional test outlined on page 7-15.
Potentiometer adjustment
4. It is unlikely that any potentiometer adjustment will be required on a replacement PCB
however the function is listed below.
a) P1 = adjust the inverter output voltage.
b) P2 = adjust the converter DC voltage.
c) P3 = adjust the UPS output threshold at ± 15%.
5. Refit all covers removed and return the UPS to its normal operating condition.
3x3 UPS 7 - 33
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
CN2 CN1
F5
Battery ćve
1. Power down the UPS and carry out the DC bus discharge routine.
2. Gain access to the UPS power section by removing the top and side covers.
3. Gain access to the Battery charger PCB by removing the front Top Heatsink Cover. See
Figure 7-1 UPS Cover Removal on page 7-3.
WARNING Capacitors C1, C9, C11 & C12 will remain charged for a considerable period after power
is removed from UPS. Ensure that the following PCB discharge routine is carried out before
handling the PCB.
4. With a DVM check for a voltage across F4 and F5, C1 and C9.
5. If a voltage is detected, discharge the capacitors using a 1kÙ 4Watt Resistor or equivalent.
Connect the discharge resistor to the voltage test point. (Across F4, F5, C1 and C9).
6. Mark all connectors before removal.
7. Disconnect connectors CN1, CN2 and CN3.
8. Remove the ftwo Heatsink securing bolts.
9. Carefully lift the complete PCB and Heatsink assembly from the side of the unit.
10. Remove the two fixing screws and insulated washers from the front heatsink insulated
stand-off.
11. Remove the two rear fixing screws and insulated washers from the heatsink insulated
stand-off's.
12. Remove the two Allen terminal screws from diods PD1 and PD2.
13. Remove the four terminal screws from the battery charger IGBT Q1.
14. Remove the four terminal screws from the diode pack D1.
15. Note the position of the shorting links fitted to the PCB.
16. Carefully lift the PCB from the Heatsink.
Replacing the PCB
1. Replace the Battery Charger PCB using the opposite sequence to the removal.
7 - 34 3x3 UPS
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
Important All replacement PCB's leave the manufacturer pre calibrated therefore no adjustment
note should be necessary.
2. When fitting a replacement PCB the on board links must be checked to ensure they are in
the correct position.
Link and Jumper functions
a) JPI ĆJP2 sets the recharging current.
Link/Ampere IA 3A 5A
JPI open open close
JP2 open close open
d) Jumpers JP5 to JPI0 set the capacity for the installed battery, this is used for the battery
test function.
Link J4 J5 J6
Time 12 Hours 24 Hours 48 Hours
3x3 UPS 7 - 35
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
1. Power down the UPS and carry out the DC bus discharge routine.
2. Gain access to the UPS power section by removing the top and side covers.
3. Mark filter wiring before disconnection.
4. Remove the five retaining terminal screws and disconnect the filter wires.
a) Red wire from PW3 PHĆR.
b) Black wire from PW4 PHĆS.
c) Brown wire from PW5 PHĆT.
d) Blue wire from PW2 Neutral.
5. Carefully lift the PCB from the unit.
Replacing the PCB
1. Replace the Input Filter PCB using the opposite sequence to the removal.
2. Refit all covers removed and return the UPS to its normal operating condition.
7 - 36 3x3 UPS
Issue 2 - November 2001
Service Manual
PCB Replacement Procedures
7.9.7 - Operator Control Panel (LDC) Part Nº 0SDE0075 (PCB Label: CS0075 Exx)
J1
CS0075 rear
P1
LCD Contrast
Removing the Assembly:
1. Power down the UPS and carry out the DC bus Discharge routine.
2. Gain access to the rear of the UPS's Front door.
3. Mark all connectors before removal.
4. Disconnect connectors CN1 and J1.
5. Remove the Left and Right hand fixing bolts in order to remove the assembly.
3x3 UPS 7 - 37
Issue 2 - November 2001
Chapter 8 - Optional Equipment
The following optional equipment is available for the UPS
Remote Panel
The remote indication panel provides duplication of the main functions and operating status of the
UPS control panel LED's, at a distance from the main equipment.
This Upgrade Kit allows the extension of the output power from the original rating value up to 30kVA by
changing some internal components.
Additional components may be required (Batteries, Circuit Breakers etc.) depending on the actual inĆ
stallation & unit configuration.
The isolation transformer is a starĆstar configuration and can be connected either in the input or output
side.
This item must be fitted internally in the unit for power up to 20kVA and in an external cabinet for 30kVA.
Different sizes are provided for different power ratings.
Is the same as the Internal Extended Battery Kit without the Battery.
Note: In some case the re-order number for the PCBs and the PCB Label may
differ.
For example:
The label on the `silk-screen' of the UPS Monitor Board is CS0077, however the correct re-order
number OSDE0077.
Re–order Part Number Description
0CEFNC332 Fuse 32 A 400 V
0CEVTM2200800 Fan 2GDR35 133/190R
0CPCPA06600450 Capacitor 60mF 450 V
0CSDRFBYT261P12 Diode 60 A 1.200 V
0SDE0082 Relay Board
0SDE0070 Auxiliary Converter Board
0SDE0071 Driver & Feedback Interface
0SDE0072–10 Control Logic Board 10KVA
0SDE0072–15 Control Logic Board 15KVA
0SDE0072–20 Control Logic Board 20KVA
0SDE0072–30 Control Logic Board 30KVA
0SDE0077 UPS Monitor Board
0SDE1074 Battery Charger Assembly
0SDE0075 LCD display
0SDE0078 Fan Board
0SDE0079 Input filter
0SDE0080 EMC/RF Filter Board
0SDE1051 Subassembly Module
0CEFXV412 Fuse 120 A 660 V
0CPCPA08440400 Capacitor 4400 mF 400V
0CATRCM150BU24F IGBT 150 A 1.000 V (Double)
0CATD212420 IGBT 200 A 1.200 V (Single)
0CASR212391 SCR 91 A 1.200 V
0CSSX212413 SCR 132 A 1.200 V
0CADR210230 Diode 30 A 1.000 V BYT230
0CADRFBYT231 Diode 30 A 1.000 V BYT231
0CADTSSKD82/12 Bridge SKD 82/12
0CESO4063 Circuit Breaker 63A 4
0CBE1200 Sealed Battery 7,2 Ah 12 V