NVF5 Series Inverter Quick Start-Up Wizard: 1.safety Precautions
NVF5 Series Inverter Quick Start-Up Wizard: 1.safety Precautions
NVF5 Series Inverter Quick Start-Up Wizard: 1.safety Precautions
1.Safety Precautions
The purpose of this quick start-up wizard is to guide you
to complete the basic installation 、 wiring and basic
parameters setting、commissioning and troubleshooting for
NVF5 series inverter products. For more information, please
refer to the user manual or scan the QR code to get the user
materials. This NVF5 series products have been strictly
tested and packaged before leaving the factory. If abnormal
information such as inverter damage and wrong delivery is
found, please contact Chint channel or the relevant office
or call Chint oversea hotline:400-1177-797
Attention:
It is not permitted to conduct unauthorized modification in case of the danger of
fire/electric shock and other hurt!
Installation must be conducted by qualified personnel in case of the danger of
electric shock!
Please install the inverter on the metal equipmen(supplementary enclosure) or
other non-combustible objects in case of the danger of fire!
It is not permitted to place combustibles nearby in case of the danger of fire!
The products should be installed with either fuses or an input circuit breaker
Danger between the inverter and power supply in case of danger of fire!
It is not permitted to install the inverter in an environemnt containing explosive
gases in case of the danger of explosion!
It is not permitted to insall the inverter at a place directly exposed in sunlight in
case of the danger of equipment damage!
It is not permitted to install the inverter on occasions where water splashing in
case of the danger of equipment damage!
Installation Dimensions:
Number of
Product Applicable T: Universal Inverter Input Input Voltage Brake Unit
Model Motor Power Model Phases Rating
B: Standard
(kW)
D: Single 2:230V Embedded
Phase
4:380V~ 440V Blank: No
S: Three Embedded
Phases
W D W1 W D W1 d
H1
H1
H
H
NVF5-0.4/TD2~NVF5-2.2/TD2、NVF5-0.4/TD2-B~ NVF5-3.7/TS4-B~NVF5-7.5/TS4-B
NVF5-2.2/TD2-B and NVF5-0.4/TS4-B~NVF5-2.2/TS4-B product appearance and installation
product appearance and installation dimension diagram dimension diagram
Figure 2-1 Figure 2-2
Unit (mm)
Adaptive Output
Brake Mounting Weight
Catalog No. Motor Current
Unit W H D W1 H1 Hole kg
kW A
d
Single Phase AC 230V
NVF5-0.4/TD2
0.4 2.5
NVF5-0.4/TD2-B
NVF5-0.75/TD2
0.75 5 75 148 125.2 64 137.5 Φ5.3 1.2
NVF5-0.75/TD2-B Optional
NVF5-1.5/TD2 (embedded)
1.5 7.5
NVF5-1.5/TD2-B
NVF5-2.2/TD2
2.2 10 75 148 146.7 64 137.5 Φ5.3 1.25
NVF5-2.2/TD2-B
Three Phase AC 380V~440V
NVF5-0.4/TS4-B 0.4 1.5
NVF5-0.75/TS4-B 0.75 2.7
75 148 125.2 64 137.5 Φ5.3 1.03
NVF5-1.5/TS4-B 1.5 4.2
Standard
NVF5-2.2/TS4-B 2.2 5.8
(embedded)
NVF5-3.7/TS4-B 3.7 10.5
89.5 206 149.2 78.5 196.8 Φ5.5 1.79
NVF5-5.5/TS4-B 5.5 13
NVF5-7.5/TS4-B 7.5 17 118 216 163.4 105 205 Φ6 2.78
3.Installation and Wiring
3.1 Power Terminal Description
(1) Single Phase 230V(NVF5-0.4/TD2~2.2/TD2 (2) Three Phase380V(NVF5-0.4/TS4-B~
and NVF5-0.4/TD2-B~2.2/TD2-B) 7.5/TS4-B)
J3 Multifunction interface
RS485 communication
Figure 3-3
AO Dip Switch:Left, (0~20)mA or (4~20)mA Analog Current Ouput;Right,(0~10)
V Analog Voltage Output.
(0~20)mA or (4~20)mA Analog Current input;Right,
AI1 Dip Swith:Left, (0~10)VAnalog
Voltage input.
AI2:Current Output need to be customized.
Wiring Demonstration:
4.Integral Keypad
4.1 Integral Keypad and Indicators
Figure 4-1
4.2 Combination key Function Description
Key Description
Parameter Menu Mode Selection(F7.11)
1、 Simple Parameter Menu Mode(U-1)
+
2、 Custom Parameter Menu Mode(U-2)
3、 Engineering Parameter Menu Mode(U-3)
The system is under the main Lock Combinational Key
interface
+
In custom menu mode,in menu level Add custom parameters
one
The system is under the main Unlock Combinational Key
interface
+
In custom menu mode,in next level Delete custom parameters
menu
4.3 Parameter Menu Mode Demonstration
Simple parameter menu mode demonstration:
Below example is how to set parameter F0.05 from 5.00Hz to 10.00Hz in Simple Parameter
Menu Mode.
Change parameter
Ready status: Parameter menu No.
mode information Parameters
5.00Hz flash Press using
Press
2S
5.00 U-1 later F0.00
F0 F0.05
Press
5.00
Press Press
Press
` Press Shift
key
Figure 5-1
6. Fault description and Trouble shooting
If a fault appears,Please see for an explanation of the fault code and check by yourself firstly
before asking for help from Chint or Chint channels.When you need support,please contact
Chint or Chint channels.
Code Fault Type Fault reason Action
Inverter
Accel.
E.OC1
running Low grid voltage Check the input power supply
overcurrent Directly and quickly start rotating motor Increase accel. time
Inverter Incorrect Motor Nameplate Motor auto tuning
Decel. Too small inverter power Enlarge inverter power rate
E.OC2
running Unsuitable V / F curve Adjust V/F cruve or adjust manual
overcurrent Potential Energy Load or Big Inertial Load torque boost
Inverter Accel./Decel. Time too short Add Regen. Brake Components
constant Load Fast Change Check load
E.OC3
speed running
overcurrent
Inverter
Accel.
E.OV1
running Motor short circuit to ground
overvoltage Check motor cable
Abnormal input voltage
Check the input power supply
Inverter Motor quick start again at high speed
Start inverter when motor stop
Decel. Potential Energy Load or Big Inertial Load
E.OV2 Add Regen. Brake Components
running Increase decel. time
Increase decel. time
overvoltage Incorrect setting of Parameter ASR
Refer to Parameter Group F3
Inverter in vector control
about how to set ASR
constant Big Inertial Load
E.OV3
speed running
overvoltage
Input Lose Checking Main Power Terminal
E.SPI R.S.T lose phase
Phase Wiring
Check Input Voltage
Output Lose
E.SPO U.V.W lose phase Check Motor Cable
Phase
Check Motor and Cable
The output three-phase with
interphase short circuit or ground
short circuit Re-wire, confirm the motor
Inverter instantaneous overcurrent insulation
Fan duct blockage or fan damage See overcurrent handling
High ambient temperature Clear the fan duct or replace
Power Module
E.FO Loose I/O wiring or plug the fan
Protection
Current waveform anomaly due to output Lower ambient temperature
lose-phase and other reasons Check wiring and re-wire
Aux. power supply damage, Checking wiring
drive voltage undervoltage Asking for Chint technical support
IGBT Module Damage
Control Board Abnormal
Heat Sink High ambient temperature
E.OH1 Lower ambient temperature
Overheat Fan duct blockage
Clear the fan duct
Fan damage
Rectifier Bridge Replace the fan
E.OH2 IGBT abnormal
Overheat Asking for Chint technical support
Temperature checking circuit error
Input correct motor overload ratio
E.OL1 Motor Overload
Incorrect Motor Overload Ratio Check motor load
Motor Stall or load change frequently Select Frequency conversion
Long time low speed ruuning with excessive motor
load Check grid voltage
Low grid voltage Adjust V/F cruve or adjust manual
Inverter Unsuitable V / F curve torque boost
E.OL2 Incorrect Motor Nameplate Motor auto tuning
Overload
Excessive load Enlarge inverter power rate
Excessive DC Brake Reduce DC brake
Accel. Time too short current, increase brake time
Increase accel. time
Set Wrong Motor Data Set correct motor data
Reverse Auto Tuning is Disable Reverse
prohibited in reverse running Check motor cable
E.tE Auto Tuning Check Parameter F0.08
Poor contact of motor
connecting cable (Frequency Max.) whether is
Auto Tuning Overtime samller than rated frequency
Motor short
E.StG Motor short circuit to ground Check motor cable
circuit to ground
Check whether load loss or
Inverter Current is Smaller than the value of
E.LL Load Loss Fault parameter FE.17、FE.18、FE.19
Parameter FE.18
parameter setting