Fire Alarm Control Panels: Device Compatability Guide
Fire Alarm Control Panels: Device Compatability Guide
Table of Contents
MRI-M502M Monitor Module for 2- wire smoke detectors Classes A/B 200
initiating
1
Secutron Fire Alarm Panels Device Compatibility Guide
Typical Current
Model Description
Draw µA
M502M Monitor Module for 2- wire smoke detectors Classes A/B 200
initiating
Mircom FHS-210-110 75 18
Secutron MRA-24 WW 15 24
Amseco SH24W-75110 75 18
Gentex GEC3-24WW 15 24
2
Secutron Fire Alarm Panels Device Compatibility Guide
Mircom
System Sensor i3
2W-B c/w base A-A 0.10 30
System Sensor
3
Secutron Fire Alarm Panels Device Compatibility Guide
Apollo
Series 60A Bases 45681-200,-220,-232,-251
Series 65A Bases 45681-255,-256,-257,-258
Hochiki
4
Secutron Fire Alarm Panels Device Compatibility Guide
Note: Please refer to applicable installation Manual (LT-905SEC, LT-906SEC, LT-950SEC or LT-951SEC)
for specific wiring details.
Wheelock Mircom
NS-24MCW-FW 40 13 FHS-240-110 20 9
Gentex Faraday
MRA-HS3-24 32 8 6234 Series* 16 9
System Sensor
P1224 MC 32 12
5
Secutron Fire Alarm Panels Device Compatibility Guide
T8210A107 24VDC
R8210A107 24VDC
8210A107 24VDC
AMEREX
17014 Actuator
BSCO
510006 Actuator
486500-01 Actuator
Parker
SIEMENS
CPYEC-24
TSP
17842 Actuator
6
Secutron Fire Alarm Panels Device Compatibility Guide
Apollo
Mircom Series 60A Bases 45681-200,-220,-232,-251 Hochiki
Series 65A Bases 45681-255,-256,-257,-258
1451/B401B** SLR-24/NS6-220*
2451/B401B**
Note: Please refer to applicable Installation Manual (LT-905SEC, LT-906SEC, LT-950 or LT-951SEC) for
specific wiring details.
7
Secutron Fire Alarm Panels Device Compatibility Guide
Notes:
1. Whether mixing different models of compatible smoke detectors or using the same model on the
same circuit, total standby current of all detectors must not exceed 3 mA.
2. The below listed smoke detectors are compatible with initiating circuits having Compatibility
Identifier "A".
Compatibility Compatibility
Smoke Detector Rated Standby Smoke Detector Rated Standby
Identifier Identifier
Make Model / Base Current Make Model / Base Current
Head / Base Head / Base
8
Secutron Fire Alarm Panels Device Compatibility Guide
Compatibility Compatibility
Smoke Detector Rated Standby Smoke Detector Rated Standby
Identifier Identifier
Make Model / Base Current Make Model / Base Current
Head / Base Head / Base
711U/701E, 701U,
S10A - S00 0.10 mA MIR-525TU FDT-1 0.10 mA
702E, 702U
713-5U / 701E,
S10A - S00 0.10 mA FW-2 HD-6 55µA @ 24VDC
701U, 702E, 702U
5500-225/45681
721UT / 702E, 702U S10A - S00 0.10 mA 55000-225 -251, -255, -256, 0.11mA
-258
5500-225/45681
722U / 702E, 702U S10A - S00 0.10 mA 55000-325 -251, -255, -256, 0.11mA
-258
Max. # Base
Manufacturer Model Description
Detectors CID
25 System Sensor B401BH N/A 24VDC sounder base for use with B401
25 System Sensor RMK400 N/A Recessed mount kit for Series 400
9
Secutron Fire Alarm Panels Device Compatibility Guide
Manufacturer Models
741U
Sentrol-ESL 449AT, 449C, 449CT, 449CRT, 449CST, 741U WITH
WITH
449CSTE, 449CSRT, 449CSRH, 449CSST, 702U or -
702U or
449CSSTE, 449CTE, 449CLTCSLT 702E Base
702E Base
10
Secutron Fire Alarm Panels Device Compatibility Guide
Wheelock
Gentex
11
Secutron Fire Alarm Panels Device Compatibility Guide
Note: Whether mixing different models of compatible smoke detectors or using the same model on the
same circuit, the total standby current of all detectors must not exceed 3 mA.
Make Model / Base Make Model / Base Make Model / Base Make Model / Base
73595/73486
12
Secutron Fire Alarm Panels Device Compatibility Guide
The following conventional smoke detectors are ULC listed for compatibility with the MR-2900 Control Panel using
Conventional Circuit Input Modules
# of Devices # of Devices
Make & Model Make & Model
/Circuit /Circuit
Hochiki 73594/73400 60
DCD-135/NS4-220 30 73594/73401 60
DCD-190/NS6-220 30 Mircom
DCD-190/NS4-220 30 MIR-525 30
DCD-190/HSC-220R 30 MIR-525T 30
SIJ-24/NS6-220 30 MIR-1400A 30
SIJ-24/NS4-220 30 MIR-2400A 25
SIJ-24/HSC-220R 30 Simplex
SLR-24/NS6-220 30 2098-9110
SLR-24H/NS6-220 30 2400-A 25
SLR-24H/NS4-220 30 1451-A/B401B 25
SLR-24H/HSC-220R 30 1451-A/B406B 25
SLR-835/NS6-220 30 2451-A/B401B 25
SLR-835/NS4-220 30 2451-A/B406B 25
SLR-835/HSC-220R 30 1451DH/DH400A 30
SLR-835B-2 30 2451-A/DH400A 25
Mirtone 1151A 30
73471 30 2151A 30
73575 60 2400TH 30
73595/73486 60 C2WTR-B 1
73595/73497 60 C2WTA-BA 1
13
Secutron Fire Alarm Panels Device Compatibility Guide
# of Devices # of Devices
Make & Model Make & Model
/Circuit /Circuit
Edwards Fenwal
6249C 100 PSD-7131/70-201000-001 42
6266C 60 PSD-7131/70-201000-005 42
6269C 60 PSD-7130/70-201000-001 42
6270C 60 PSD-7130/70-201000-002 42
6269C-003 60 PSD-7130/70-201000-003 42
6270C-003 60 PSD-7130/70-201000-005 42
Apollo PSD-7128/70-201000-001 42
55000-325 30 PSD-7126/70-201000-002 42
DI-2 30 PSD-7129/70-201000-000 42
DI-3/DB-3S 30 PSD-7125/70-201000-001 42
DI-3C 30 PSD-7126/70-201000-002 42
DI-4 30 PSD-7125/70-201000-003 42
DI-4B 30 PSD-7125/70-201000-005 42
PEC-3 30 CPD-7021/70-201000-001 42
NAPCO CPD-7021/70-201000-002 42
FW-2 30 CPD-7021/70-201000-003 42
CPD-7021/70-201000-005 42
14
Secutron Fire Alarm Panels Device Compatibility Guide
Typical Current
Model Description
Draw µA
15
Secutron Fire Alarm Panels Device Compatibility Guide
16
Secutron Fire Alarm Panels Device Compatibility Guide
The following Listed 2-wire smoke detectors and bases are compatible with the MR-2900 Control Panel using the
MR-2918 and MR-2928 Conventional Input Circuit Modules (with compatibility identifiers MR-2918 and MR-2928,
respectively). Up to 5 μA of smoke detector normal standby load may be connected to each MR-2918 and
MR-2928 conventional initiating device circuit.
Smoke
Base Standby
Manufacturer Detector Model Current
Identifier Identifier
Model
System Sensor 1400 A N/A N/A 100 μA
1451 A B401 A 120 μA
1451 A B401B A 120 μA
2300T A N/A N/A 120 μA
2300TB A N/A N/A 120 μA
2400 A N/A N/A 120 μA
2400TH A N/A N/A 120 μA
2451 A B401 A 120 μA
2451 A B401B A 120 μA
2451 A DH400 A 120 μA
2451TH A B401 A 120 μA
2451TH A B401B A 120 μA
Apollo 55000-250 55000-250 45681-200 45681-200 59 μA
55000-250 55000-250 45681-230 45681-230 80 μA
55000-250 55000-250 45681-231 45681-231 80 μA
55000-350 55000-350 45681-200 45681-200 110 μA
55000-350 55000-350 45681-230 45681-230 130 μA
55000-350 55000-350 45681-231 45681-231 130 μA
Cerebrus DI-3C
Pyrotronics DI-4
DI-4B
PEC-3
Detection Systems DS200 A MB200-2W A 80 μA
DS200HD A MB200-2W A 80 μA
Edwards 6250B 001 6251B 001 30 μA
6270B 001 6251B 001 50 μΑ
17
Secutron Fire Alarm Panels Device Compatibility Guide
Smoke
Base Standby
Manufacturer Detector Model Current
Identifier Identifier
Model
Fenwal CPD-7023 I3FE1 CPD-001 FE01A 80 μA
CPD-7023 I3FE1 CPD-002 FE02A 80 μA
CPD-7023 I3FE1 CPD-003 FE03A 80 μA
CPD-7023 I3FE1 CPD-005 FE05A 80 μA
18
Secutron Fire Alarm Panels Device Compatibility Guide
Smoke
Base Standby
Manufacturer Detector Model Current
Identifier Identifier
Model
Hochiki SIF-24F HD-2 HS-221D HB-4 102 μA
SIF-24F HD-2 YBA-M221 HB-4 102 μA
19
Secutron Fire Alarm Panels Device Compatibility Guide
The following Listed 2-wire smoke detectors and bases are compatible with the MR-2900 Control Panel using the
MR-2938 Conventional Input Circuit Module with compatibility identifier as MR-2938. Up to 2.50 mA of smoke
detector normal standby load may be connected to each MR-2938 conventional initiating device circuit.
Smoke
Base Standby
Manufacturer Detector Model Current
Identifier Identifier
Model
System 1400 A N/A N/A 100 μA
Sensor 1451 A B401 A 120 μA
1451 A B401B A 120 μA
20
Secutron Fire Alarm Panels Device Compatibility Guide
The following notification appliances, where a current rating is shown, may be used with the MR-2900 Control Units.
Wheelock
WST-24-FR Strobe - 25
21
Secutron Fire Alarm Panels Device Compatibility Guide
WS1T-24-FR Strobe - 25
WS3T-24-FR Strobe - 25
WHT-24-FR Strobe - 75
WH1T-24-FR Strobe - 75
WH3T-24-FR Strobe - 75
WMT-24-FR Strobe - 88
WM1T-24-FR Strobe - 88
WM3T-24-FR Strobe - 88
VLPM-24-W-VF-R Strobe - 88
34T-24-R Horn 63 -
MIZ-24-R Mini-Horn 15 -
MIZ-24-W Mini-Horn 15 -
CH-BF1-R Chime 20 -
CH-CF1-W Chime 20 -
CH-DF1-R Chime 20 -
22
Secutron Fire Alarm Panels Device Compatibility Guide
23
Secutron Fire Alarm Panels Device Compatibility Guide
NH-12/24 Horn 28 -
24
Secutron Fire Alarm Panels Device Compatibility Guide
25
Secutron Fire Alarm Panels Device Compatibility Guide
CH70-24 Chime 20 -
CH90-24 Chime 20 -
RSS-24l5W Strobe - 53
RSS-241575W Strobe - 68
RSS-243OW Strobe - 85
26
Secutron Fire Alarm Panels Device Compatibility Guide
RSS-2415C Strobe - 70
27
Secutron Fire Alarm Panels Device Compatibility Guide
28
Secutron Fire Alarm Panels Device Compatibility Guide
Gentex
29
Secutron Fire Alarm Panels Device Compatibility Guide
GXS-4-15 Strobe 15 Cd - 78
GXS-4-30 Strobe 30 Cd - 93
SPKE4-15 Speaker/Strobe 4@ 15 cd - 78
30
Secutron Fire Alarm Panels Device Compatibility Guide
SPKE8-15 Speaker/Strobe 8@ 15 cd - 78
SPKE4-30 Speaker/Strobe 4@ 30 cd - 93
SPKE8-30 Speaker/Strobe 8@ 30 cd - 93
Potter
31
Secutron Fire Alarm Panels Device Compatibility Guide
Space Age
SSU7620 Strobe - 80
SSU7522 Speaker/Strobe - 80
System Sensor
P241575K Horn/Strobe 39 64
P241575F Horn/Strobe 39 64
S241575K Strobe - 64
S241575F Strobe - 64
H12/24 Horn 39 -
32
Secutron Fire Alarm Panels Device Compatibility Guide
HC12/24 Horn 39 -
HC12/24K Horn 39 -
SSM24-6 Bell 30 -
SSM24-8 Bell 30 -
SSM24-10 Bell 30 -
SS24LO Strobe - 45
SS24LOC Strobe - 45
SS24LOLA Strobe - 80
33
Secutron Fire Alarm Panels Device Compatibility Guide
RP2415ADA Strobe - 90
The following Listed devices are compatible with the output of the 24 VDC auxiliary power circuits of the MR-2900.
Each circuit may be loaded to a maximum of 150 mA in standby or alarm conditions.
Input Current at
Manufacturer Model Type
24 VDC
34
Secutron Fire Alarm Panels Device Compatibility Guide
35
Secutron Fire Alarm Panels Device Compatibility Guide
The following listed door holders are compatible with the MR-2900 and MR-2400 door holder/releaser circuits:
Input Current
Manufacturer Model Type
at 24 VDC
36