Precision Storage Vessels PVT LTD: Pressure Test Report

The document summarizes the results of a hydrostatic pressure test of a 10-inch tangential air separator without a strainer. The test was conducted on July 16, 2020 at Precision Storage Vessels Pvt Ltd. The separator passed a 1-hour hydrotest at 15 bar (15 kg/cm2) using water as the test fluid and with the metal temperature observed at 29°C.

Uploaded by

Senthil Kumaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
627 views2 pages

Precision Storage Vessels PVT LTD: Pressure Test Report

The document summarizes the results of a hydrostatic pressure test of a 10-inch tangential air separator without a strainer. The test was conducted on July 16, 2020 at Precision Storage Vessels Pvt Ltd. The separator passed a 1-hour hydrotest at 15 bar (15 kg/cm2) using water as the test fluid and with the metal temperature observed at 29°C.

Uploaded by

Senthil Kumaran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

PRECISION STORAGE VESSELS PVT LTD

CLIENT : M/s HOTLINE TRADING LLC REPORT No. : PSV-HYDRO-J642-01


JOB/TAG NO: : J 642 DATE : '16-07-2020
DRG. No. : PSV-FG-515 Rev-0 MFR.SL.NO: : E031
MODEL : -- ITP INSP. POINT :W
ITP Clause No. : 12.2 INSP. BY. : CLIENT
PRESSURE TEST REPORT
DESCRIPTION TANGENTIAL AIR SEPERATOR - 10'' WITHOUT STRAINER
DATE OF TEST 16-07-2020

HYDROTEST PRESSURE. Kg/Cm2 / Bar (g) 15Bar

TEST FLUID WATER

HOLDING TIME,MINUTES 1 HOUR (60Minutes)

PRESSURE GAUGE RATING Kg/Cm2 / Bar (g) 0-40 Bar

CALIBRATION LABEL No. PSV-PG-005

CALIBRATION VALID UPTO. / CALIBRATION CERTIFICATE No. 15-09-2020 / MNP 3837-01/19-20

OBSERVED METAL TEMPERATURE IN OC 29˚C

TEST POSITION / PROCEDURE REF. Vertical / PSVPL/HYDRO/001 REV NO :4


REMARKS :

FOR QCI FOR QCE FOR PSVPL

NAME : NAME : NAME :

SIGNATURE : SIGNATURE : SIGNATURE :


WITNESSED BY EXAMINED BY WITNESSED & INSPECTED BY
Format: PSVPL/HYDRO/001/F01 Rev.0