0% found this document useful (0 votes)
73 views3 pages

CB Test Report

This document contains test results for an SF6 circuit breaker installed for Bangladesh Power Development Board WAPDA. It lists the rated voltage, current capacity and withstanding voltages for the circuit breaker. It also provides insulation resistance test results showing resistances between 25-92 gigohms for each phase of the breaker. Contact resistance tests showed values between 30-33 microhms for each phase. The breaker and tests were witnessed and approved by listed personnel.

Uploaded by

aronno anupom
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views3 pages

CB Test Report

This document contains test results for an SF6 circuit breaker installed for Bangladesh Power Development Board WAPDA. It lists the rated voltage, current capacity and withstanding voltages for the circuit breaker. It also provides insulation resistance test results showing resistances between 25-92 gigohms for each phase of the breaker. Contact resistance tests showed values between 30-33 microhms for each phase. The breaker and tests were witnessed and approved by listed personnel.

Uploaded by

aronno anupom
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Project Details:

Client: Bangladesh Power Development Board WAPDA


PO No. 27.11.0000.304.19.466.19.09
Dated: 24.9.2019

SF6 Circuit Breaker Details:


Breaker Serial Number: 327100059410010000

Rated Voltage : 145 kV

Nominal Current : 3150 A

Frequency : 50 Hz

Power frequency Withstand Voltage : 275 kV (rms)

Lighting Impulse Withstand Voltage: 650 kV (peak)

Short Time Withstand Current: 40kA

Duration of short circuit: 3s

Short Circuit breaking Current(Sym): 40kA

Short Circuit breaking Current(Asym): 46.8 kA

SF6 Gas Pressure at 20◦ C, 1013 hpa: 0.64

SF6 Breakar total mass: 1384

Reference Standard: IEC-62271-100

Classification: C2-M2

Manufacturer: GE T&D INDIA LIMITED, PADAPPAI, Chennai.

Year of Manufature: 2020


Insulation Resistance Test

Project: Wapda, Saidpur


Equipement: SF6 Circuit breaker (132kV Side)
Brand: GE(India)

Phase Test Voltage Connection Point Insulation Resistance


Breaker Top to
1000 V 25.1 GΩ
Breaker Bottom

A 1000 V Breaker Top to 19.5GΩ


Ground

2500 V Breaker Bottom to 92.2 GΩ


Ground
Breaker Top to
1000 V 23.7GΩ
Breaker Bottom

B 1000 V Breaker Top to 18.7 GΩ


Ground

2500 V Breaker Bottom to 92.6 GΩ


Ground
Breaker Top to
1000V 20.1 GΩ
Breaker Bottom

C 1000V Breaker Top to 18.2 GΩ


Ground

2500 V Breaker Bottom to 88.4 GΩ


Ground

C(Breaker Close) 5000 V Breaker to Gournd 538 GΩ

Tested by: Witnessed By: Approved By:


Aronno Anupom Abu Bakkr Siddique
Contact resistance Test

Project: Wapda, Saidpur


Equipement: SF6 Circuit breaker (132kV Side)
Brand: GE(India)

Phase Injected Current Contact resistance


A 100A 33 µΩ

B 100A 33 µΩ

C 100A 30 µΩ

Tested by: Witnessed By: Approved By:


Aronno Anupom Abu Bakkr Siddique