MM Ty Eccentrici: Design of Square Column

This document provides the design calculations for a square reinforced concrete column with a height of 2.84 meters and width and depth of 304.8 mm. It specifies the material properties, checks the minimum and maximum steel requirements, calculates the design moments and axial load, and designs the column reinforcement to resist earthquake loading in both directions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
111 views3 pages

MM Ty Eccentrici: Design of Square Column

This document provides the design calculations for a square reinforced concrete column with a height of 2.84 meters and width and depth of 304.8 mm. It specifies the material properties, checks the minimum and maximum steel requirements, calculates the design moments and axial load, and designs the column reinforcement to resist earthquake loading in both directions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Design of Square Column

Concrete Grade = M25 Steel Grade= Fe500


Column B3
Ref. Step Calculations Output

1 Known Data
Overall Depth of Column, D= 304.80 mm D= 304.8mm
Width of Column, B= 304.80 mm B = 304.8mm
Height, L= 2.84 m L = 2.8448m
Characteristic strength of concrete fck = 25.00 N/mm 2
2
Strength of steel fy = 500.00 N/mm

Clause 26.5.3.1 of IS 456: 2000 a Min. Reinforcement,


2
0.8% of BD Ast min = 743.22 mm Astmin= 720.00mm2
2
Clause 26.5.3.1 of IS 456: 2000 b Max. Reinforcment, Max. Ast = 4% of BD Ast max = 3716.12 mm Astmax =3600.00mm2
2
But in extreme case, Max. Ast = 6% of BD Ast max = 5574.18 mm Astmax = 5400.00mm2

2 Design for section


Axial Load, Pu = 301.74 KN
Moment about x-axis Mx = -49.62 KNm
Moment about y-axis My = 69.64 KNm
eccentricity =
clear height of column lateral dim ension e= 15.14 mm

Clause 25.4 of IS 456:2000 500 30
clear height of column L= 2.49 m
eccentrici ty  20mm
Take e= 20.00 mm

Min.Moment Pue = 6.03 KNm


Moment about y-axis Mx = 6.03 KNm
Moment about x-axis My = 69.64 KNm
a Approx Design
i Design for Earthquake in X-direction
Axial Load, Pu = 301.74 KN
Ultimate Moment about y-axis Mux = 6.03 KNm
Pu
 0.13
f ck DB

M ux
2
 0.009
f ck BD
Clear cover, C= 50.00 mm
f= 16.00 mm
d' = 58.00 mm
d'/D = 0.190
P
SP16, chart 50  0.07
f ck
pt = 0.80 %
Asc = 743.22 mm 2

Column Design-1
Design of Square Column
Concrete Grade = M25 Steel Grade= Fe500
Column B3
Ref. Step Calculations Output
ii Design for Earthquake in Y-direction
Axial Load, Pu = 301.74 KN
Ultimate Moment about x-axis Muy = 69.64 KNm
Pu
 0.13
f ck BD
M uy
 0.03
f ck DB 2
Clear cover, C= 50.00 mm
f= 16.00 mm
d' = 58.00 mm
d'/B = 0.190

P
 0.030
f ck
pt = 0.80 %
Asc = 743.22 mm 2

The required steel will be higher of above two 743.22 mm 2

Providing ( 8#-16Φ)mm dia


Asc provided = 2513.27 mm 2
Percentage of steel, pt = 2.71 %
P
 0.108
f ck
SP16, chart 50 for p/f ck = 0.108 and Pu/f ckBD = 0.13
M ux
2
 0.140
f ck BD
Muxl = 99.11 kNm
SP16, chart 50 for p/f ck = 0.108 and Pu/f ckBD = 0.13
M uy
 0.140
f ck DB 2
Muyl = 99.11 kNm

Clause 39.6 of IS 456:2000 Puz = 0.45fckAg + (0.75fy-0.45f ck)Asc Puz= 1959.36 KN


Pu
 0.15
Puz
an = 1.13
n n
 M ux   M uy 
    0.71 <1 Hence OK
M 
 M uxl   uyl 

Hence OK

Column Design-2
Design of Square Column
Concrete Grade = M25 Steel Grade= Fe500
Column B3
Ref. Step Calculations Output

3 Design of Lateral Ties

i. diameter 16/4 = 4 mm 8.00 mm


Providing 8mm lateral ties
Lateral Ties,f = 8 mm
Clause 26.5.3.2© IS 456:2000 ii. Pitch of Lateral Ties minimum of of below
b of the column = 304.8 mm
300mm
16f = 16x8 = 128mm 128.00
Clause 26.5.1.5 IS 456:2000 0.75d = 0.75x304.8 = 228.6 mm 228.60 mm

But From Ductility Consideration


Clause 7.4.1 IS 13920:1993 Confinement Length l 0
D or B 304.80 mm
L/6 414.87 mm
450 450.00 mm Take lo=600mm
Spacing of Special Confining reinforcements
Clause 7.4.6 IS 13920:1993 75mm Pitch=80 mm
Clause 7.4.6 IS 13920:1993 1/4 x 304.8 76.20 mm
= 100 mm
Provide 8mmf lateral ties @ 80mm upto 600mm from either
ends of column
iii. Pitch at mid portion of column For Mid Portion
= 125mm Pitch=125 mm
Provide 8 mmf lateral ties @ 125mm on remaining part.

Column Design-3