Sub: Supply, Installation & ELB Approval of 11/0.415KV, 100 KVA, Substation
Sub: Supply, Installation & ELB Approval of 11/0.415KV, 100 KVA, Substation
Sub: Supply, Installation & ELB Approval of 11/0.415KV, 100 KVA, Substation
To
Managing Director
A I International Ltd
Dhaka-1216, Bangladesh.
Sub: Supply, Installation & ELB Approval of 11/0.415KV, 100 KVA, Substation.
Dear Sir,
We Thanks You a lot for your interest in Aftia Electric Engineering. The complete offer is
enclosed along with Price and technical details as desired by you. With reference to your
request for supply of Substation Equipments, we are hereby submitting our best offer fo the
mentioned equipment with the following terms & condition:
Thanking
Item No. Item Name Unit Qty Unite Price Total Price
Part- A (Substation Item supply & installation with Approval ELB)
01. 11/0.415KV,100 KVA transformer Nos. 1 2,55,000.00 2,55,000.00
02. 160 A LT Switchgear Panel Nos. 1 80,000.00 80,000.00
03. 60 KVAR PFI Plant Nos. 1 55,000.00 55,000.00
04. 11 KV, Drop out Fuse Set. 1 9,000.00 9,000.00
05. 11 KV, Lightening Arrestor Set. 1 6,000.00 6,000.00
06. 11 KV Lightening , Drop Channel Set. 1 4,000.00 4,000.00
07. 11 KV, Termination Kit (Heat shrink) Set. 4 2,500.00 10,000.00
08. Cable Stand Transformer Set. 1 1,000.00 1,000.00
09. Earthling (Boring Depth 60-80 feet) Nos. 4 15,000.00 60,000.00
10. Installation all substation equipment Job. 1 30,000.00 30,000.00
11. Electrical license Board (ELB) Approval Job. 1 50,000.00 50,000.00
Part-A- Sub- Total= 0.00
In Word= Five Lac Sixty Thousand BDT Only.
Part- B (HT/LT Cable)
14. 3 x 50rm,XLPE ,HT Cable , PARTEX, BIZLI, BRB Meter 3500.00
15. 1 x70rm, NYY, LT Cable, PARTEX, BIZLI, BRB Meter 1000.00
16. 1x10re BYA, Earthling Cable, PARTEX, BIZLI, Meter 115.00
BRB
Part-B- Sub Total=
In Word=
Part- C ( Meter, Solar, & Power Supply Authority Cost)
17. LT/CT Meter / HT Meter Nos. 1 55,000.00 55,000.00
18. 3 Phase Meter ( 8 kw + Nos. 1 5,200.00 5,200.00
19. 1 Phase Meter (1-7 KW) Nos. 1 1,300.00 1,300.00
20. Meter Box with bus-bar Nos. 1 15,000.00 15,000.00
21. Demand Note & Miscellaneous (DESCO ) KW 80 600.00 48,000.00
23. 3 Phase Meter Installation (DESCO ) Nos. 1 2,500.00 2,500.00
24. 1 Phase Meter Installation (DESCO ) Nos 1 1,500.00 1,500.00
25. File Processing & Office Maintain Job 1 80,000.00 80,000.00
Part-C- Sub Total=
In Word=
Note: 1. Any Type of Civil Work, Francine, Road Cutting, & Others Requirements of Power Supply Authority Cost. LT
Panel to Meter Board Cable Supply & Wiring works bear by client.
2. Client Supplied All Document necessary ELB & Power Supply Authority Papers and signing all document.
3. If Earthling result is not satisfactory (Less than 1.0 Ohm) extra earthling cost will be as per above rate.
Incoming:
160 A, 25 KA, TP MCCB with adjustable thermal and 1 nos. Schneider India /
adjustable magnetic short-circuit releases ABB Italy
Current Transformer (CT), ratio: 200/5, with suitable 3 nos.
accuracy and burden
Digital Amp meter and Volt meter 1 nos
Indicating Lamp 3 nos.
Control fuse 1 set
Outgoing:
125 A, 36 KA, TP MCCB with adjustable thermal and 1 nos. Schneider India /
adjustable magnetic short-circuit releases. FOR PFI ABB Italy
Or 1 nos. Schneider India /
Client Requirements (add This Price) ABB Italy
Assembled by Aftia Electric Engineering., Bangladesh
03. Technical Specification 60 KVAR PFI Plant
Item Code Item Description Qty Brand/ Origin
03. Sheet steel clad powder coated (16/18 SWG) , free standing , floor mounting type, 415v,
50 Hz,60 KVAR indoor type Automatic Power Factor Improvement Plant. Comprising:
20 KVAR Bank of TP dry type Power Capacitors with 1 nos. EPCOS, India
built-in discharge resister
10 KVAR Bank of TP dry type Power Capacitors with 2 nos. EPCOS, India.
built-in discharge resister
7.5 KVAR Bank of TP dry type Power Capacitors with 2 nos. EPCOS, India.
built-in discharge resister
5 KVAR Bank of TP dry type Power Capacitors with built- 1 nos. EPCOS, India.
in discharge resister
Automatic Power Factor Correction Relay (6 stage) 1 nos. Mikro, Malaysia.
TP Magnetic Contactors of adequate rating 6 nos Donga, Korea
TP MCB of adequate rating 6 nos Schneider, India
Current Transformer (CT), ratio: 200/5, with suitable 1 nos.
accuracy and burden.
Indicating Lamp 6 nos
Control fuse 1 Set
Assembled by Aftia Electric Engineering., Bangladesh
04.11 KV, Drop Out Fuse .
Item Code Item Description
0.4 Technical Specification :
Rated Voltage (Nominal) : 11 kV
Rated Maximum Voltage : 15 kV
Rated Frequency : 50 Hz
BIL : 75 kV
Rated Current RMS : 100 A
Interrupting Current RMS : 10 kA
copper earthling block with required Nos. of ¼" hole for ECC
connection. Size - 254mm x 40mm x 10mm. One for transformer
neutral and another for all substation Equipments ECC connections.
EARTH ELECTRODE
Supply and installation of 20ft length 1" dia GI Pipe buried up to the
depth of 80'-0" in the damp soil including 4SWG copper wire from
bottom of GI Pipe upto ground level.
EARTHING LEAD