Parallel Operation of Synchronous Generator
Parallel Operation of Synchronous Generator
EEE 205
Avijit Saha
Lecturer, Dept. of EEE, UIU
G1 Load
G2
Advantages of Operating
Generators in Parallel
G1 Load 1
6 MW 5 MW
Advantages of Operating
Generators in Parallel
After addition of 2 MW load, total load is 7 MW
which is higher than the generator 1 capacity
G1 Load 1
6 MW 5 MW
G1
7 MW
8 MW
Advantages of Operating
Generators in Parallel
Several generators can supply a bigger load than one
machine by itself
Having many generators increases reliability of the
power system, since the failure of any one of them does
not cause a total power loss to the load
G1 Load 1
6 MW 5 MW
Load 2
G2 2 MW
3 MW
Advantages of Operating
Generators in Parallel
Having many generators operating in parallel allows one or more
of them to be removed for shutdown and preventive maintenance
If only one generator is used and it is not operating at near full
load, then it will be relatively inefficient. With several smaller
machines in parallel, it is possible to operate them at near full
load and thus more efficiently
G1 Load 1
6 MW 5 MW
Load 2
G2 2 MW
3 MW
The Conditions for Paralleling
G1 Load
S
G2
a
b
G1 c
Load
a‟
b‟
G2 c‟
Explanation of the Conditions
a
G1 b Load
c
a‟
G2 c‟
b‟
Explanation of the Conditions
G1 Load
But it is found that one bulb glows other two darken and then another bulb
glows and then other. This is an indication of opposite phase sequence.
Procedure for Paralleling
nnl fnl
nfl
Frequency, Hz
ffl
Q
-Q 0 Qfl
kVAR kVAR
consumed supplied
For lagging load terminal voltage drops, and for leading load terminal
voltage rises.
The variation, naturally, is not linear, but the voltage regulator is used to
make it linear.
This relationship also plays important role in parallel operation of
generators.
Generator Working Alone
Infinite Load
Bus
Generator
House Diagram
f
fnl
PL
When two characteristics are plotted back-to-back then
it is called house diagram.
After parallel connection the frequency and terminal
voltage of all the machine must be same.
Situation Just after Synchronization
f f
fnl fnl
PG 3
I‟‟A PG 2
3
I‟A EA
IA 2
PG1
1
Pinf, kW PB1 PB2 PB3 0 PG1 PG2 PG3 PG, kW
G1 Load
G2
Immediately after synchronization
Pload=PG1+PG2
Qload=Q‟G1+Q‟G2
How to Change Power Sharing without
Changing the Frequency?
If we want to change power sharing without changing
the frequency, we should increase one‟s set point whose
power we want more and decrease the other‟s set point.
f
Pload=P‟G1+P‟G2
How to Change Frequency without
Changing Power Sharing?
If we want to change frequency without changing the
power sharing, we should increase both set point.
f1
f2
Pload=P‟G1+P‟G2
Maintaining Same Terminal Voltage
OR Same Reactive Power Sharing
Reactive power and terminal voltage adjustment
work in analogous manner.
To shift the reactive power sharing without change
in VT, simultaneously increase one‟s field current
and decrease other‟s field.
Similarly, to adjust the terminal voltage, VT without
changing the reactive power sharing,
simultaneously increase or decrease both field
currents.
Numerical Problem 02
Generator 1 has a no-load frequency of 61.5 Hz and a
slope (sp1) of 1 MW/Hz. Generator 2 has a no-load
frequency of 61.0 Hz and a slope (sp2) of 1 MW/Hz. The
two generators are supplying a real load totaling 2.5 MW at
0.8 pf lagging. Draw the house diagram for the system.
(a) At what frequency is the system operating, and how
much power is supplied by the two generators?
(b) Suppose an additional 1-MW load are attached to this
power system. What would be the new system frequency
be, and how much power would G1 and G2 supply now?
(c) With the increased load, if the governor set point on G2
is increased by 0.5 Hz, what will be the system frequency
and generators‟ power?
Solution
The Power equations will be
PG1=Sp1(fnl1-fsys)
PG2=Sp2(fnl2-fsys)
fnl1=61.5 and fnl2=61 Hz,
Sp1=Sp2=1 MW/Hz
Again, PL=PG1+PG2
So, we can write, PL=2.5=1(61.5-fsys)+1(61-fsys)
This gives, fsys=120/2=60.0 Hz
At that system frequency, PG1=1*(61.5-60.0)= 1.5MW
and PG2=1*(61-60)= 1.0 MW
(Total = 2.5 MW)
Solution
When load is increased to 3.5 MW, the power equation
will be,
PL=PG1+PG2
So, we can write, PL=3.5=1(61.5-fsys)+1(61-fsys)
This gives, fsys=119/2=59.5 Hz
At that system frequency, PG1=1*(61.5-59.5)= 2.0MW
and PG2=1*(61-59.5)= 1.5 MW
(Total = 3.5 MW)
Solution
If generator2‟s set point is increased t0 61.5 Hz, then the
power equation becomes,
Since, PL=PG1+PG2
Now, we can write, PL=3.5=1(61.5-fsys)+1(61.5-fsys)
This gives, fsys=119.5/2=59.75 Hz
At that system frequency, PG1=1*(61.5-59.75)=1.75MW
and PG2=1*(61.5-59.75)= 1.75 MW
(Total = 3.5 MW)
Numerical Problem 02
Two generators are connected in parallel. They have frequency
droops of 1 Hz/10MW and 0.75 Hz/10MW respectively. And their
voltage droops are 0.1kV/10MVAR and 0.2KV/10 MVAR
respectively. The no load settings of their governors are 51.5 Hz
and 51 Hz respectively. The no load settings of their Automatic
Voltage Regulators (AVR) are 6.6kV and 6.8kV respectively. If a
load of 22 MVA at 0.8 lagging pf is supplied by the two generators
determine the real and reactive power sharing between the
generators and also determine the system frequency and system
terminal voltage.
f VT
51.5 Hz 6.8 kV 6.6 kV
51.0 Hz
50.7429 6.5788 kV
Hz