100 617 - DE - Booster - 3pump - Standby - Submittal PDF
100 617 - DE - Booster - 3pump - Standby - Submittal PDF
100 617 - DE - Booster - 3pump - Standby - Submittal PDF
617
STANDBY | N 3 3 0 2 0 2s — N 3 9 0 3 0 2s | S U B M I T T A L
Date: june 27, 2017
Job: Representative:
Notes:
1 nsf 61 and nsf 372 certified complete package assembly.
2 Standard right hand connection orientation illustrated, please
indicate alternate connection orientation, if required.
3 All pumps are equal.
4 Standard grooved header connections.
Optional flanged ansi 150# or 300# connections available.
5 Optional tank shipped loose, installed by others.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s
max working
booster a b c max d e f g h j j1 weight
pressure
model
inches (mm) psi (bar) lbs (kg)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 3 0 2 0 2S 232 (16) 1034 (469)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 3 0 4 0 2S 232 (16) 1123 (509)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 3 0 6 0 2S 232 (16) 1136 (515)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 3 0 9 0 2S 232 (16) 1374 (623)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 8.25
N3 312 0 2S 363 (25) 1746 (792)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (210)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 8.25
N3 316 0 2S 363 (25) 1914 (868)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (210)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
N3 5 010 2S 232 (16) 1722 (781)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
N3 5 0 222S 232 (16) 1883 (854)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
N3 5 0 3 22S 232 (16) 2407 (1092)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
N3 5 0 4 3 2S 232 (16) 2487 (1128)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 41.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 10.00
N3 5 0 5 0 2S 363 (25) 2942 (1334)
(2451) (1057) (1592) (205) (2200) (577) (200) (800) (229) (254)
96.48 41.63 63.40 8.06 86.61 22.72 7.87 31.50 9.00 10.00
N3 5 0 6 0 2S 363 (25) 3795 (1722)
(2451) (1057) (1610) (205) (2200) (577) (200) (800) (229) (254)
96.78 43.85 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
N3 6 010 2S 232 (16) 2104 (954)
(2458) (1114) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 43.85 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
N3 6 0 212S 232 (16) 2682 (1216)
(2458) (1114) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 43.85 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
N3 6 0 3 22S 232 (16) 3123 (1416)
(2458) (1114) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 45.85 69.73 9.44 86.61 22.72 7.87 31.50 13.50 15.00
N3 6 0 5 0 2S 363 (25) 5094 (2311)
(2458) (1165) (1771) (240) (2200) (577) (200) (800) (343) (381)
96.78 48.87 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
N37010 2S 232 (16) 3193 (1448)
(2458) (1241) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 48.87 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
N370 212S 232 (16) 3680 (1669)
(2458) (1241) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 48.87 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
N370 3 22S 232 (16) 4576 (2076)
(2458) (1241) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 51.44 66.03 9.44 86.61 22.72 7.87 31.50 13.50 15.00
N370 422S 363 (25) 5554 (2519)
(2458) (1307) (1677) (240) (2200) (577) (200) (800) (343) (381)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 8 010 2S 232 (16) 1014 (460)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 8 0 3 0 2S 232 (16) 1165 (529)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 8 0 4 0 2S 232 (16) 1319 (598)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 8 0 5 0 2S 232 (16) 1669 (757)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 8 070 2S 232 (16) 1836 (833)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 8.25
N3 810 0 2S 363 (25) 2249 (1020)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (210)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 9 0 2 0 2S 232 (16) 1085 (492)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
N3 9 0 3 0 2S 232 (16) 1307 (593)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
Note:
All dimensions are inches (mm), tolerances are (+/-) ½" (12 mm) unless otherwise specified.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby
q [l/min]
0 50 100 150 200 250 300 400
280
900
p h h
[psi] [ft] vms 1016/15 hp vms 10b - 60 hz - 3450 rpm [m]
348 800 vms 1015/15 hp 240
vms 1014/15 hp
700
290
200
vms 1012/10 hp
600
vms 1011/10 hp
vms 1008/7.5 hp
174 400 120
vms 1007/7.5 hp
vms 1006/5 hp
300
116 vms 1005/5 hp 80
vms 1004/5 hp
200
vms 1003/3 hp
58 40
100 vms 1002/2 hp
vms 1001/1 hp
0 0 0
0 10 20 3 40 50 60 70 80 U.S.g.p.m.
0 2 4 6 8 10 12 14 16 18 20 q [m3/h]
80
1.5
% 60 [%]
p2 1
[hp] Single Impeller hp
0.5 40
0 20
0 10 20 3 40 50 60 70 80 U.S.g.p.m.
8
20
npsh npsh
[ft] 10 4 [m]
0 0
0 10 20 3 40 50 60 70 80 U.S.g.p.m.
note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s
q [l/min]
0 100 200 300 400 500
280
900
p h h
vms 1512b/25hp [m]
[psi] [ft] vms 15b - 60 hz - 3500 rpm
348 800
vms 1511b/25hp 240
vms 1510b/20hp
700
290
200
vms 1509b/20hp
600
vms 1508b/20hp
232 160
500 vms 1507b/15hp
vms 1506b/15hp
174 400 120
vms 1505b/10hp
300
vms 1504b/10hp
116 80
vms 1503b/7.5hp
200
vms 1502b/5hp
58 40
100
vms 1501b/2hp
0 0 0
0 20 40 60 80 100 120 U.S.g.p.m.
0 5 10 15 20 25 q [m3/h]
80
2.5
%
60 [%]
p2 2
[hp]
1.5 40
Single impeller hp
1 20
0 20 40 60 80 100 120 U.S.g.p.m.
8
20
npsh 4
npsh
[ft] 10 [m]
0 0
0 20 40 60 80 100 120 U.S.g.p.m.
note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby
q [l/min]
0 100 200 300 400 500 600
280
900
p h h
[psi] [ft] vms 20b - 60 hz - 3450 rpm [m]
348 800 vms 2010/25 hp
240
vms 2009/25 hp
700
290
vms 2008/20 hp
200
600
vms 2007/20 hp
232 160
500
vms 2006/15 hp
vms 2004/10 hp
300
116 80
vms 2003/7.5 hp
200
vms 2002/5 hp
58 40
100 vms 2001/3 hp
0 0 0
0 20 40 60 80 100 120 140 U.S.g.p.m.
40q [m /h]
3
0 5 10 15 20 25 30
3 80
%
60 [%]
p2 2.5
[hp]
2 40
Single Impeller hp
1.5 20
0 20 40 60 80 100 120 140 U.S.g.p.m.
12
30
npsh 8 npsh
20
[ft] 4
[m]
10
0 0
0 20 40 60 80 100 120 140 U.S.g.p.m.
note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s
335 1100
H H
(m) (ft) vms 32 - 60 hz - 3500 rpm
304 1000 vms 3210-1
min. flow
244 800
vms 3208-3
vms 3207
213 700
vms 3206
183 600
vms 3205
152 500
122 400 20 6
vms 3204-3
vms 3203
91 300 15 4.5
nsph(m)
nsph(ft)
vms 3203-2
vms 3201
30 100 5 1.5
npsh
0 0 0 0
0 20 40 60 80 100 120 140 160 180 200
us gpm
0 5 9 14 18 23 27 32 36 41 45
q m3/h
80
70
60
50
eff.% 40
30
20
10
0
0 20 40 60 80 100 120 140 160 180 200
us gpm
note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby
274 900
H H
(m) (ft)
vms 4507-2 vms 45 - 60 hz - 3500 rpm
244 800 min. flow
vms 4506
213 700
vms 4505
183 600
152 500
vms 4504-1
122 400 20 6
vms 4503
vms 4503-2
91 300 15 4.5
nsph(m)
nsph(ft)
vms 4502-1
61 200 10 3
0 0 0 0
0 50 100 150 200 250 300
us gpm
0 11 13 34 45 57 68
q m3/h
90
80
70
60
eff.% 50
40
30
20
10
0
0 50 100 150 200 250 300
us gpm
note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s
183 600
H H vms 64 - 60 hz - 3500 rpm
(m) (ft) vms 6404 min. flow
vms 6403
122 400
vms 6403-2
91 300
vms 6402
vms 6402-1
61 200 20 6
vms 6401
15 4.5
nsph(m)
nsph(ft)
vms 6401-1
30 100 10 3
5 1.5
npsh
0 0 0 0
0 50 100 150 200 250 300 350 400 450
us gpm
0 11 13 34 45 57 68 80 91 102
q m /h 3
90
80
70
60
eff.% 50
40
30
20
10
note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby
10
4
3 11 6
2
discharge
j1 connection
grooved
standard
c max 7
b
8
9 f
5
d
j
g suction
h 10 a connection
1 grooved
e standard
11
Models N330202S - N390302S
item description
1 Stainless steel suction header
12 2 Stainless steel discharge header
3 Pump with integrated ivs controls
4 Control panel with plc
5 Suction isolation valve
6 Grooved connection
7 Pressure gauge
8 Pressure transducer
9 Pressure gauge isolation valve
toronto
10 Stainless steel base and panel support
+1 416 755 2291
11 Plug pipe
buffalo
12 Flo-Trex valve
+1 716 693 8813
birmingham
+44 (0) 8444 145 145
manchester
+44 (0) 8444 145 145
bangalore
+91 (0) 80 4906 3555
shanghai
+86 21 3756 6696
a r m s t r o n g f lu i d t e c h n o lo g y
são paulo established 1934 a r m s t r o n g f lu i d t e c h n o lo g y. c o m
+55 11 4785 1330