Excel For Etabs Tutorial For RC

This document provides information for structural design of a building located in Malindong, Binmaley Pangasinan, Philippines including: - Building geometry and material properties - Dead, live, and other loads - Wind and seismic parameters - Equations for calculating design base shear and overturning moment - Load combinations for structural design

Uploaded by

chbarcenal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views

Excel For Etabs Tutorial For RC

This document provides information for structural design of a building located in Malindong, Binmaley Pangasinan, Philippines including: - Building geometry and material properties - Dead, live, and other loads - Wind and seismic parameters - Equations for calculating design base shear and overturning moment - Load combinations for structural design

Uploaded by

chbarcenal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 63

Purlin spacing m

Truss spacing m

Roof mean Height for wind load calculation


m
Roof Slope = 22.62deg

STORIES (LEVELS)
Levels Storey Height (m)
Footing to GF -
GF to 2F 4
2F - 3F 3
3F-RD 3
RD-Rbeam 2.7
Rbeam-Apex 0.57
13.27
Location Malindong, Binmaley Pangasinan
Seismic Source Type A
Distance to nearest fault line* 9.1 km
*(check phivolcs website)
Zone, Z 4
Na 1
Nv 1.2
Basic Wind Speed 250 kph
STORIES (LEVELS)
Levels Storey Height (m)
Footing to GF -
GF to 2F 4
2F - 3F 3
3F-RD 3
RD-Rbeam 2.7
Rbeam-Apex
12.7

PROPERTIES
Beams Columns Slabs fc' fy fys
B250x400 S100 20.7 275 275
B200x400 C300X300 C300x400 OS100 (3000psi) (Gr40) (Gr40)
Ec 21384

LOADS
Dead Load
Concrete unit weight 23.5 kN/m3 Check
Partitions 1.2 kPa Table 204-1
Finish & Toppings 1.58 kPa Table 204-2
Ceiling 0.24 kPa Table 205-1
kPa Table 205-2
3.02 0 Table 205-3
Section 205, 206
Live Load
Residential 1.9 kPa
Balcony as exit
facility 4.8 kPa
Roof Deck 1.9 kPa
Water Tank 7.18 kPa
Seismic Parameters
15.78 0 UBC 97 / NSCP 2015
Zone
Roof LL 1 kPa Seismic Source Type
Importance Factor ( I
Linear Load R
Wchb 2.73 kPa Structure is located
Ht of wall 3.00 m Ct
8.19 kN/m Soil Type
Na
Cantilever Load Nv
Same with typical floor loads Ca
Cv
Stairs
Thread 1.9 kPa Wind Parameters
Misc 0.96 kPa Wind (ASCE 7-10 / NSCP 2015)
Self Wt 3.6 kPa Vwind
6.46 kPa I
9.88 kN/m Exposure

L of Stairs 3060
Both end discont. 20
thknss 153
t = Perimeter/180

= 4 0.4
= A
= 1.0 (Standard Occupancy)
= 8.5 - Special Moment Frame
@ 9.1km from seismic source
= 0.0731
= SD
= 1
= 1.2
= 0.44
= 0.768
CE 7-10 / NSCP 2015)
= 250 kph
= 1
= B (typical residential structure in urban area)
For Low-Rise Buildings: Component and Cladding
Simplified Procedure
ASCE 7-10
PURLINS (EFFECTIVE AREA =

Zone
1
1.09
-1.85
PURLIN SPACING = 0.8M

0.872
-1.48
Pnet = λ Kzt Pnet9

1 1 TRUSS (EFFECTIVE AREA = 24

Zone
1
0.85
-1.72
TRUSS SPACING = 2.5M

2.13
-4.3
PURLINS (EFFECTIVE AREA = 2.08 m2)
250kph
Zone
2 3
1.09 1.09 kn/m2
-3.04 -4.57 kn/m2
PURLIN SPACING = 0.8M

0.872 0.872 kn/m


-2.432 -3.656 kn/m

TRUSS (EFFECTIVE AREA = 24m2)


250kph
Zone
2 3
0.85 0.85 kn/m2
-2.44 -3.83 kn/m2
TRUSS SPACING = 2.5M

2.13 2.13 kn/m 10% least horizontal dimension 0.8


-6.1 -9.575 kn/m 0.4h 2.8
4% least horizontal dimension 0.32
0.9 0.9 governs
1.635 KN 2.5 9.6 24 0.068125 KN/M2

0.681 KN 0.8 2.5 2 0.3405 KN/M2

0.408625 KN/M2
UBC 1997

0.75
PARAMETERS T = Ct (hn) sec
Z 0.4 = 0.492 sec
I 1 < 0.70 sec therefore Ft = 0;
Rwx 8.5
Rwz 8.5
Na 1.036
Nv 1.272 V= CvIW KN
S 4 RT
Ct 0.0731 = 133.69 KN
hn 12.7
W 686.452
Cv 0.81408
Ca 0.45584

Total design base shear need not exceed:


V = 2.5Ca IW KN UBC Eq. (30-5)
R
= 92.03 KN DESIGN BASE SHEAR IS TOO LARGE!
USE THIS VALUE!

Design base shear shall not be less than:


V = 0.11CaIW KN UBC Eq. (30-6)
= 34.42 KN OK!

V = 0.8ZNvIW KN UBC Eq. (30-7)


R
= 32.87 KN OK!

If Ft≠ 0:
Ft = 0.07TV UBC Eq. (30-14)
= 4.60 KN
< 0.25V = 33.42
UBC Eq. (30-8)

< 0.70 sec therefore Ft = 0;

UBC Eq. (30-4)


3735.59 3735.59 0
DECK 21081.2 21081.2 0 3735.59
0
22138.45 22138.45
21081.2
23019.48 23019.48 0 22138.45
Base 7228.4 7228.4 23019.48
69974.72 9.81 686.452
Section 203
Load Combination
203.2 Symbols and Notation
D Dead Load
E Earthquake Load Section 208.6.1
Em Estimated maximum earthquake force that
can be developed in the structure as set forth in Section 208.6.1
F Load due to fluids with well-defined pressures and max heights
H Load due to lateral pressure of soil and water in soil
L Live load, except for roof live load, including any permitted live load reduction
Lr Roof live load, including any permitted live load reduction
P Ponding load
R Rain load on the undeflected roof
T Self-straining force and effects arising from contraction or expansion
resulting from temperature change, shrinkage, moisture change,
creep in component materials…
W Load due to wind pressure

203.3 Load combination due to strength design or lrfd


203.3.1 Basic Load Combinations
… shall resist the most critical effects from the ff:
1.4 (D + F) 203-1
1.2(D + F + T) + 1.6(L+H) + 0.5(Lr or R) 203-2
1.2D +1.6(Lr or R) + (f1L or 0.5W) 203-3
1.2D +1.0W +f1L +0.5(Lr or R) 203-4
1.2D +1.0E + f1L 203-5
0.9D +1.0W +1.6H 203-6
0.9D +1.0E +1.6H 203-7
where
f1 = 1.0 for floors in places for public assembly,
for live loads in excess of 4.8kPa, and for garage live load
= 0.5 for other live loads

203.3.2 Other Loads


Where P is to be considered in design, the applicable load
shall be added in Section 203.3.1 factored as 1.2P

203.5 Special Seismic Load Combination


…shall be used specifically required by Section 208, or by Chapter 3 through 7
1.2D +f1L +1.0Em 203-19
0.9D +/- 1.0Em 203-20
where
f1 = 1.0 for floors in places for public assembly,
for live loads in excess of 4.8kPa, and for garage live load
= 0.5 for other live loads
Em = the maximum effect of the horizontal and vertical
forces as set forth in Section 208.6.1
Ultimate Load Combo

ULC1 1.4 (DL) + 1.4(SDL) E = pEh + Ev


ULC2 1.2(DL) + 1.2(SDL) + 1.6(L) + 0.5(Lr) p = 1 if drift is to be checked
1.2(DL) + 1.2(SDL) +f1(LL) +1.0Em Eh = EQX or EQY
ULC3 1.2(DL) + 1.2(SDL) +f1(LL) + 1.0 (EQX) + O.5 Ca I DL Ev = 0.5 Ca I DL
ULC4 1.2(DL) + 1.2(SDL) +f1(LL) - 1.0 (EQX) + O.5 Ca I DL E = 1.0 (EQX or EQY) + O.5 Ca I DL
ULC5 1.2(DL) + 1.2(SDL) +f1(LL) + 1.0 (EQY) + O.5 Ca I DL
ULC6 1.2(DL) + 1.2(SDL) +f1(LL) - 1.0 (EQY) + O.5 Ca I DL
0.9D + 1.0Em
ULC7 0.9(DL) + 0.9(SDL) + 1.0 (EQX) + O.5 Ca I DL
ULC8 0.9(DL) + 0.9(SDL) - 1.0 (EQX) + O.5 Ca I DL
ULC9 0.9(DL) + 0.9(SDL) + 1.0 (EQY) + O.5 Ca I DL
ULC10 0.9(DL) + 0.9(SDL) - 1.0 (EQY) + O.5 Ca I DL
0.9D - 1.0Em
ULC11 0.9(DL) + 0.9(SDL) - 1.0 (EQX) - O.5 Ca I DL
ULC12 0.9(DL) + 0.9(SDL) + 1.0 (EQX) - O.5 Ca I DL
ULC13 0.9(DL) + 0.9(SDL) - 1.0 (EQY) - O.5 Ca I DL
ULC14 0.9(DL) + 0.9(SDL) + 1.0 (EQY) + O.5 Ca I DL

f1 1
Ca 0.44
I 1
O.5 Ca I DL 0.22 DL

1.2DL + 0.5 Ca I DL 1.42 DL 1.42 SDL

0.9DL + 0.5 Ca I DL 1.12 DL 1.12 SDL

0.9DL - 0.5 Ca I DL 0.68 DL 0.68 SDL